SECTION – 1
1
ESTIMATING DATA – 2007
(EXTERNAL ELECTRIFICATION)
SER DESCRIPTION UNIT RATE REMARKS
NO (Minimum amount)
9 -- do -- but above 62.5 KVA & upto 82.5 KVA KVA 10026.0 701188.0
10 -- do -- but above 82.5 KVA & upto 100 KVA KVA 10002.0 827145.0
11. -- do -- but above 100 KVA & upto 160 KVA KVA 9343.0 1000200.0
12. -- do -- but above 160 KVA & upto 250 KVA KVA 9200.0 1494880.0
13. -- do -- but above 250 KVA & upto 320 KVA KVA 9105.0 2300000.0
14. -- do -- - but above 320 KVA & upto 400 KVA KVA 8671.0 2913600.0
15. -- do -- but above 400 KVA & upto 500 KVA KVA 9168.0
2
SER DESCRIPTION UNIT RATE REMARKS
NO
18. -- do -- but above 5 KVA & upto 10 KVA. KVA 29505.0 214005.0
19. -- do -- but above 10 KVA & upto 15 KVA. KVA 22371.0 295050.0
20. -- do -- but above 15 KVA & upto 20 KVA. KVA 24476.0 335565.0
21. -- do -- but above 20 KVA & upto 30 KVA. KVA 20227.0 489520.0
22. -- do -- but above 30 KVA & upto 40 KVA. KVA 17075.0 606810.0
23. -- do -- but above 40 KVA & upto 50 KVA. KVA 14554.0 683000.0
24. -- do -- but above 50 KVA& upto 62.5 KVA. KVA 12067.0 727700.0
25. -- do -- but above 62.5 KVA & upto 82.5 KVA. KVA 10960.0 754188.0
26. -- do -- but above 82.5 KVA & upto 100 KVA. KVA 11367.0 904200.0
27. -- do -- but above 100 KVA & upto 160 KVA. KVA 9959.0 1136700.0
28.. -- do -- but above 160 KVA & upto 250 KVA. KVA 9663.0 1593440.0
29. -- do -- but above 250 KVA & upto 320 KVA. KVA 9625.0 2415750.0
30. -- do -- but above 320 KVA & upto 400 KVA. KVA 9614.0 3080000.0
31. -- do -- but above 400 KVA & upto 500 KVA. KVA 9923.0
Note:— (i) Rates are based on reputed manufacturer/ assembler like Kirloskar electric/ Jakson Ltd
(ii) Building for generator is not required but operator rest room, toilet & store for fuel is to be planned.
3
Sr. DESCRIPTION UNIT RATE REMARKS
NO
TRANSFORMER
11 KV/433V VOLTAGE RATIO
33. Supply & install transformer step up/ step down, KVA 3167.0
indoor/outdoor type complete with standard fittings,
HT 11 KV 3 Phase, LT 433 volts, 3 Phase 4 wire
with off load tappings on HT side to vary secondary
voltage within limit, all as per IS:2026 of capacity upto 63 KVA.
Note:— (i) Foundation for out door transformer and cattle fencing around transformer is included
in the above rates.
(ii) Rates are based on reputed makes like Kirloskar / Crompton / Alsthom
4
Sr. DESCRIPTION UNIT RATE REMARKS
NO
Note:—(i) Cost of PCC platform for out door transformer is included in the above rates
(ii) Rates are based on reputed makes like Kirloskar / Crompton / Alsthom
H.T SWITCHGEAR
VACUUM CIRCUIT BREAKER
INDOOR
5
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
56. -- do -- as per item 52, but of 2500 Amp Each 10, 27,383.0
capacity.
OUT DOOR
INDOOR
6
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
OUTDOOR
63. Ring main unit one incoming two out going Each 8,69,325.0
SF6 filled load break switch 11 KV
7
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
to IS-3156.
8
Sr. DESCRIPTION UNIT RATE REMARKS
NO
85. Supply and install HT 33KV out door gang Each 56356.0
operated air break switch 9 insulator rocking type
horizontal mounting of 200/400 Amp rating
Note:— Cost of GOD include cost of GI pipe required for operation and these rates are based on reputed manufacturer
like Jaipuria/ Pactil/ Elpro etc.
9
Sr. DESCRIPTION UNIT RATE REMARKS
NO
Note:— Rates are based on reputed manufacturer like L&T / Schneider/ Crompton.
99. 4 pole plug in box 100 Amp with MCCB 35 KA Each 40835.0
100. 4 pole plug in box 250 Amp with MCCB 35 KA Each 74787.0
101. 4 pole plug in box 315 Amp with MCCB 35 KA Each 80866.0
102. 4 pole plug in box 400 Amp with MCCB 35 KA Each 91893.0
103. 4 pole plug in box 630 Amp with MCCB 35 KA Each 130741.0
104. 4 pole plug in box 800 Amp with MCCB 35 KA Each 213016.0
Note:— To decide type of capacitor to be used, first find out percentage of non linear load in the system as worked out
below and then select the type of capacitor as given in table:—.
MPP-S 10%
10
Sr. DESCRIPTION UNIT RATE REMARKS
NO
MPP-H 15%
MD-XL 20%
CAPACITOR MPP-H
11
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
CAPACITOR MPP-S
12
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
CAPACITOR MD—XL
158. -- do-- but of 100 (10 x 10) KVAR capacity Each 685796.0
13
Sr. DESCRIPTION UNIT RATE REMARKS
NO. (Minimum Amount)
165. -- do-- but of 250 (25 x 10) KVAR capacity Each 1204123.0
166. -- do-- but of 275 (25 x 11) KVAR capacity Each 1260940.0
HT 11 KV CAPACITOR
Note: — Rates of LT capacitors are based on L&T/ Asian and for HT are based on M/S ABB/ Universal.
LT SWITCHES
(SUITABLE FOR EXTERNAL MOUNTING)
14
__________________________________________________________________________
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
180. Switch fuse unit TPN 500 Volts 3 phase Each 1461.0
with HRC fuses suitable for interior
mounting in panel of capacity 32 Amp .
192. Supply and fix RCCB WITH MCB of 2 pole , Each 2665.0
6 Amp rating with sensitivity of 30 MA suitable
for 240 Volts
15
_________________________________________________________________________________
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
4 Pole MCCB
16
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
17
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
Note: — Rates are based on reputed manufacturer like M/S L&T/ Crompton/ Siemens.
18
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
19
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
Note:— Rates are based on reputed manufacturer like Merlin Gerin/ scheinder
Sr No. 276 to 280 left blank
20
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
VOLTAGE STABILISER
281. Voltage stabilizer for automatic operation, Each 3789.0
single phase naturally air cooled indoor type
& designed for input variation between 170 V
to 250 V with output voltage stabilized at 230 V
with accuracy of ± 2.5% and of capacity 0 .5 KVA .
21
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
22
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
Note:— Rates are based on DGS&D rate running contract with the assumption that items are to be issued free for fixing
under sch ‘B’
326. Supply and lay cable XLPE Insulated screened Meter 209.0
PVC bedded, galvanized steel strip or wire
armored, electric power cables (heavy duty)
1100 Volts grade with stranded aluminium
conductor of size 6.0 sq mm 2 core.
23
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
NOTE : Rate of under ground cables include excavation in trenches, sand cushioning/GI tubing light grade in lieu of
sand cushioning, PCC tile as covering material and high voltage testing etc.
24
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
NOTE : Rate of under ground cables include excavation in trenches, sand cushioning/GI tubing light grade in lieu of
sand cushioning, PCC tile as covering material and high voltage testing etc.
364. Supply and lay PVC insulated PVC sheathed Meter 106.0
cable galvanized steel strip or wire armoured,
electric control cables (Heavy duty) with stranded
Copper conductor of size 1.5 sq mm 2 core 1100 Volts grade.
25
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
377. Supply and fix cable jointing kit for 1.1 Each 888.0
KV grade cable for straight through joint
complete with Jointing material (Epoxy Based)
and accessories suitable for 3½/ 4 core XLPE
armoured Al conductor cable of size 25 to 50 sq mm.
382. Supply and fix cable jointing kit for 11 Each 6640.0
KV grade cable for in door termination heat
shrink type joint complete with jointing material
and accessories suitable for3 core XLPE armoured
Al conductor cable of size 16 sq mm to 50 sq mm
386. -- do-- but for cable of size 400 sq mm. Each 9492.0
387. Supply and fix cable jointing kit for 11 Each 11484.0
KV grade cable for outdoor termination heat
26
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
392. Supply and fix cable jointing kit for 33 Each 13824.0
KV grade cable for in door termination heat
shrink type joint complete with jointing material
and accessories suitable for3 core XLPE armoured
Al conductor cable of size 25 sq mm to 50 sq mm
396. Supply and fix cable jointing kit for 33 Each 19495.0
KV grade cable for outdoor termination heat
shrink type joint complete with jointing material
and accessories suitable for 3 core XLPE armoured
Al conductor cable of size 25 sq mm to 50 sq mm
400. Supply and fix cable jointing kit for 11 Each 11020.0
KV grade cable for indoor termination cold
27
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
403. Supply and fix cable jointing kit for 11 Each 18158.0
KV grade cable for out door termination cold
shrink type joint complete with jointing material
and accessories suitable for3 core XLPE armoured
Al conductor cable of size 50 sq mm to 95 sq mm
406. Supply and fix cable jointing kit for 11 Each 21149.0
KV grade cable for straight through cold
shrink type joint complete with jointing material
and accessories suitable for3 core XLPE armoured
Al conductor cable of size 50 sq mm to 95 sq mm
409. Supply and fix cable jointing kit for 33 Each 26954.0
KV grade cable for indoor termination cold
shrink type joint complete with jointing material
and accessories suitable for 3 core XLPE armoured
Al conductor cable of size 50 sq mm to 70 sq mm
28
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
400 sq mm.
413. Supply and fix cable jointing kit for 33 Each 34122.0
KV grade cable for outdoor termination cold
shrink type joint complete with jointing material
and accessories suitable for 3 core XLPE armoured
Al conductor cable of size 50 sq mm to 120 sq mm
416. Supply and fix cable jointing kit for 33 Each 44414.0
KV grade cable for straight through heat
shrink type joint complete with jointing material
and accessories suitable for 3 core XLPE armoured
Al conductor cable of size 50 sq mm to 120 sq mm
CABLE GLAND
419. Supply and fix double compression copper Each 165.0
stain less steel gland for fixing armoured cable
in panel of 2 core 6 Sq mm to 16 sq mm size
29
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
425. -- do-- but for cable of size 3½ core 150 sq mm Each 700.0
to 185 sq mm above.
426. -- do-- but for cable of size 3½ core 240 sq mm Each 1116.0
to 300 sq mm Above.
427. -- do-- but for cable of size 3½ core 400 sq mm Each 1538.0
30
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
Note: - While working out the rates, length of OH line is taken as 990 RM and spacing between pole is 30 mtr.
31
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
32
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
Note:- While working out the rates, length of OH line is taken as 1000 RM and spacing between pole is 50 mtr.
33
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
488. Supply & erect 4 pole structure on 11 mtr PCC Each 90770.0
Pole consisting of PCC pole with anti-climbing
device, PCC foundation & cross arms etc for
one incoming and two out going.
489. Supply & erect 4 pole structure on 11 mtr PCC Each 105774.0
Pole consisting of PCC pole with anti-climbing
device, PCC foundation & cross arms etc for
one incoming and three out going.
490. Supply and erect 2 pole structure on 11 mtr PCC Each 37364.0
pole consisting of PCC pole with anti-climbing
device, PCC foundation & cross arms etc.
492. Supply & erect 4 pole structure on 11 mtr steel Each 132445.0
tubular pole consisting of pole with anti-climbing
device, PCC foundation & cross arms etc for
one incoming and two out going.
493. Supply & erect 4 pole structure on 11 mtr steel Each 147449.0
tubular pole consisting of pole with anti-climbing
device, PCC foundation & cross arms etc for
one incoming and three out going.
494. Supply and erect 2 pole structure on 11 mtr steel Each 58201.0
Tubular pole consisting of PCC pole with
anti-climbing device, PCC foundation & cross arms etc.
34
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
Note:—Cost of 4 & 2 Pole structure only include cost of pole, foundation and steel bracings but does not include cost of
Gang Operated Device.
LIGHTNING ARRESTORS
496. Supply and fixing lightning arrestor LT 433 V Set of 3 4589.0
EARTHING
SERVICE CONNECTIONS
METERS
35
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
FANS
510. Providing fans ceiling complete with Each 963.0
resistance type Regulator and
accessories 230V SP 1200 mm sweep.
36
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
532. Supply & fixing street light fitting HPSV Each 4743.00
lamp, ballast, igniter and other
accessories for 70 Watt lamp.
37
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
536. Flood light fitting, complete with switch gear, Each 11742.0
control gear unit lamp and fixing for 400 Watt
metal halide (MH)
TIME SWITCHES
538. Supply and fix time switches 250 V single Each 7385.0
Phase of 20 Amp rating with contactor
Fitted inside steel enclosure
539. Supply and fix time switches 415 V three Each 7755.0
Phase of 20 Amp rating with contactor
Fitted inside steel enclosure
540. Supply and fix time switches astro type Each 10204.0
(Having longitude and latitude of Indian
cities in memory) 250 V single phase of 20 Amp
rating with contactor fitted inside steel enclosure.
38
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
39
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
40
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
NOTE : Rates of PCC Poles are for supply and fix including foundation and coping.
41
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
584. -- do-- but type 410 SP-31 (9.0 metres long) Each 11999.0
585 -- do-- but type 410 SP-37 (9.5metres long) Each 12358.0
586. -- do-- but type 410 SP-44 (10.0 metres long) Each 13856.0
587. -- do-- but type 410 SP-55 (11.0 metres long) Each 17774.0
588. -- do-- but type 410 SP-64 (12.0 metres long) Each 21781.0
589. Supply & install steel tubular swaged poles Each 12024.0
Type 410 SP-31 (9.0 metres long) complete
with CI base plate and finial and single swan neck.
including foundation
590. -- do-- but type 410 SP- 44 (10.0 metres long) Each 13852.0
591. -- do-- but type 410 SP-55 (11.0 metres long) Each 17685.0
592. Supply & install steel tubular swaged poles Each 12434.0
type 410 SP-31 (9.0 metres long) complete
with CI base plate and finial and double swan neck.
including foundation
593. -- do-- but type 410 SP-44 (10.0 metres long) Each 14263.0
594. -- do-- but type 410 SP-55 (11.0 metres long) Each 18096.0
NOTE : Rates of steel tubular poles are for supply and fix including foundation and coping.
CRANES
42
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
LIFTS
43
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
(b) Add 150,000.0 for automatic rescue device if there is no emergency supply with AMF
panel.
Note:- (a) Extra Rs 80,000.0 for additional floor for each hospital lift
(b) Lift with collapsible gate has not been considered because as per NBC – 2005, no collapsible gate is
permitted in lift.
LIGHTNING PROTECTION
622. Supply & fix single pointed air termination Each 119.0
Aluminium rod, 12 mm dia, 300 mm long.
44
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
45
SECTION – 2
46
ESTIMATING DATA — 2007
EXTERNAL WATER SUPPLY
Section-2
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
TUBE WELLS
For bore well having casing pipe for pump as 350 mm dia and other as 250 mm
dia
651. Fixing cost for MS reducer, bail plug, Job 50,000.0
well cap, MS strip for centering, MS iron
clamps, electric logging and sample strata box.
47
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
657. Yield test for the bore well by continuously Each 10,000.0
pumping for 16 hours to determine safe pumping
yield
For bore well having casing pipe for pump as 200 mm dia
658. Fix cost for MS reducer, bail plug, Job 45,500.0
well cap, MS etc strip for centring, MS iron
clamps, electric logging and simple strata box
48
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
664. Yield test for the bore well by continuously Each 10,000.0
pumping for 16 hours to determine safe pumping
yield
49
Sr. DESCRIPTION UNIT RATE REMARKS
NO
DOL Starter
681. For 2 HP Each 841.0
686. Supply and fix monobloc pump set suitable Each 25852.0
for 415 V TPN system having capacity 5 HP
687. Supply and fix monobloc pump set suitable Each 43294.0
for 415 V 3 phase of capacity 10 HP.
50
Sr. DESCRIPTION UNIT RATE REMARKS
NO (Minimum Amount)
Note :—(i) In above prices (Item NO. 686 to 700 ) include cost of automatic starter for pump above 10 WHP. For pump
upto 10 WHP, cost of DOL starter has been included.
(ii) Rates are based on reputed manufacturer like Kirloskar brothers/ Mather & Platt/ KSB
51
Sr. DESCRIPTION UNIT RATE REMARKS
NO
and installed complete upto 5 WHP
inclusive of 40 metre long submersible
cable and starter.
Note :-- Above rates of submersible pump also include cost of submersible cable from pump to starter and cost of starter.
TREATMENT PLANTS
52
Sr. DESCRIPTION UNIT RATE REMARKS
NO
PIPES
CAST IRON PIPE CLASS ‘B’
53
Sr. DESCRIPTION UNIT RATE REMARKS
NO
732. Both ends flanged and drilled Pipes cast Iron, Metre 800.0
including Specials Class “B” supplied and laid
complete 80 mm (3”)dia.
Note :- Rates of flanged pipe has been worked out based on pipe length as 5.5 mtr. Rate has been taken from rate
contract and it is assumed that pipe shall be issued under sch ‘B’. Rate does not include cost of PCC/ Brick pillar but
include cost of jointing.
54
Sr. DESCRIPTION UNIT RATE REMARKS
NO
Note for class ‘A’ and ‘LA’ pipe:— Rates are based on price list of reputed manufacturers. Rates has been worked out
based on assumption that these are supplied and fixed by the contractor. Rate include cost of laying, excavation, jointing
etc.
55
Sr. DESCRIPTION UNIT RATE REMARKS
NO
CLASS ‘ K – 9’
CLASS ‘ K – 7’
56
Sr. DESCRIPTION UNIT RATE REMARKS
NO
Note :— Rates are based on price list of reputed manufacturers. Rates has been worked out based on assumption that
these are supplied and fixed by the contractor. Rate include cost of laying, excavation, jointing etc.
57
Sr. DESCRIPTION UNIT RATE REMARKS
NO
Note:— Rates for item 804 is based on price list of reputed manufacturers. For items at sr No. 799 to 803 Rates has been
worked out based on rate running contract with DGS&D that these are issued free for fixing. Rate include cost of laying,
excavation, jointing etc.
M S PIPE (ERW)
58
Sr. DESCRIPTION UNIT RATE REMARKS
NO
Note :—Cost of ERW pipe does not include cost of laying ,excavation and jointing charges.
WATER METERS
VALVES
59
Sr. DESCRIPTION UNIT RATE REMARKS
NO
REFLEX VALVES
60
Sr. DESCRIPTION UNIT RATE REMARKS
NO
BUTTERFLY VALVES
61
Sr. DESCRIPTION UNIT RATE REMARKS
NO
FOOT VALVES
STRAINER
62
Sr. DESCRIPTION UNIT RATE REMARKS
NO
893. Cast Iron Air Valves with single air Each 1843.0
Outlets, conforming to IS 14845 of size
50 mm dia bore and fixing up in Cast Iron
Water supply mains of size 50 mm dia.
894. Cast Iron Air Valves with two air Each 3532.0
Outlets, 50 mm dia bore and fixing
Up in cast iron water supply mains.
GLOBE VALVE
63
Sr. DESCRIPTION UNIT RATE REMARKS
NO
924. Solar water heating system with heat exchanger Each 26100.0
type for cold region of 100 litre capacity,
with electrical heating back up of 2 KW and
make up water tank
925. Solar water heating system with heat exchanger Each 45098.0
type for cold region of 200 litre capacity, with
64
Sr. DESCRIPTION UNIT RATE REMARKS
NO
926. Solar water heating system with heat exchanger Each 62741.0
type for cold region of 300 litre capacity,
with electrical heating back up of 4 KW and
make up water tank
Note :—Rate for geyser and solar water heating system except item No. 914 and 915 are based on RC rate and
considered as issued on sch ‘B’. Rates for item No. 914 and 915 are based on supplied and fixed
927. Supply & fix fire hydrant landing valve Each 8144.0
type A (single head outlet) of 63 mm dia of
size conforming to IS 5290
929. Supply and fix hose box for keeping 2 Nos Each 2403.0
hose pipe of length 15 mtr each, branch pipe.
nozzle, coupling etc of MS sheet of
Thickness 2.0 mm
930. Supply and fix 63 mm dia gun metal branch Each 1869.0
pipe and nozzle conforming to IS 903
931. Supply and fix hose box for hose reel Each 3605.0
of 20 mm size of 30 mtr length complete
with coupling branch pipe and nozzle
932. Supply and fix hose reel of 20 mm dia and Each 4806.0
30 mtr length conforming to IS 5132
933. Supply and fix branch pipe and nozzle for Each 601.0
20 mm dia hose reel conforming to IS 8090
934. Supply and fix 63 mm dia 15 mtr long hose Each 4206.0
conforming to IS 636 complete with male
and female coupling conforming to IS 903
935. Supply and fix fire hydrant stand post with Each 1682.0
provn of single outlet conforming to IS 908
65
Sr. DESCRIPTION UNIT RATE REMARKS
NO
938. Filtration cum recycle plant for swimming pool Each 21,27,038.0
of size 25 x 12.5 x 2.5 (Avg. depth) mtr
having total water capacity 8,00,000 litre
suitable for 8 hr turn over period complete with
following:—
(f) Water circulating pump 2Nos(1 W + 1S)having discharge
100 M3/hr head 16 mtr
66
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
Note Rates are based on reputed manufacturer like Chloromax/ Ion exchange
PRESSURE FILTER
945. -- do – but flow rate 100 M3/hr, dia 2500 mm Each 6,28,505.0
and height 1800mm
946. -- do – but flow rate 125 M3/hr, dia 2800 mm Each 7,34,171.0
and height 1800mm
947. -- do – but flow rate 150 M3/hr, dia 3000 mm Each 8,05,530.00
and height 1800mm
Note Rates are based on reputed manufacturer like Chloromax/ Ion exchange
67
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
949. -- do – but for capacity 2.0 to 4.0 lakh litre Each 120761.0
950. -- do – but for capacity 4.0 to 8.0 lakh litre Each 189375.0
951. -- do – but for capacity 8.0 to 12.0 lakh litre Each 227799.0
952. -- do – but for capacity 12.0 to 16.0 lakh litre Each 263478.0
953 -- do – but for capacity 16.0 to 20.0 lakh litre Each 307391.0
954. -- do – but for capacity 20.0 to 24.0 lakh litre Each 381495.0
955. -- do – but for capacity 24.0 to 32.0 lakh litre Each 430211.0
68
SECTI0N- 3
SEWAGE DISPOSAL
(Sr No. 1001 to 1200)
69
ESTIMATING DATA 2007
SEWAGE DISPOSAL
Section-3
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
SEWERS
70
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
71
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
72
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
73
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
74
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
75
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
76
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
Note : (i) For pipes laid under sub-soil water conditions and/or in soils of treacherous
nature, the rates of items at serial 951 to 1034 above be increased by 6% to cater for
timbering, dewatering of trenches etc.
(ii) Both internal and external plaster to the manholes brick work has been
considered while working out the rates.
77
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
78
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
FILTER BEDS
79
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
EFFLUENT DRAINS
80
------------------------------------------------------------------------------------------------------------------
SER DESCRIPTION UNIT RATE REMARKS
NO
1145. -- do -- but 4 m dia and 7.5 m depth & pump house Each 804722.00
4 x 4m.
1149 -- do -- but 3.00 m dia and 9.00 m depth and Each 530273.00
3 x 3m pump house.
1150 -- do – but 5.00 m dia and 6.00 m depth and Each 1124360.00
4 x 5m pump house.
SEWAGE PUMPS
1156. Non clog sewage centrifugal, electric driven pump Each 118150.0
for sewage containing solids upto 2.5” size
including maintenance spares for
2 years supplied and installed complete
from 5 HP to 12.5 HP.
81
SER DESCRIPTION UNIT RATE REMARKS
NO
82
SER DESCRIPTION UNIT RATE REMARKS
NO
1177 --do—but where the waste water coming out Each 9749325.0
of plant is to be recycled for horticulture, MT wash
etc then additional civil works to include one
RCC filter feed tank, two filter feed pumps, one
dual media filter, one activated carbon filter and one
RCC treated water tank rate for 600 m3/day capacity
83
SER DESCRIPTION UNIT RATE REMARKS
NO
Notes : (i) Rates are based on quotation received from reputed manufacturer like Thermax / Dorr Oliver/ Degre Mont.
(ii) Rates for items No. 1168 to 1185 include the cost of civil work directly connected with the above said
equipment like foundation and supporting structure but does not include the cost of civil works which are
required but not directly connected with the equipment like fencing, building etc.
NOTE:--(i) Rate are based on reputed manufacturer prices like m/s ion exchange.
(ii)Prices for sr No. 1186 & 1187 does not include the cost of civil work.
84
adequate slope could be maintained. If the final disposal is through
soil absorption system, septic tanks of capacity greater than 300 users
is not recommended.
85
SECTION – 4
REFRIGERATION
AND
AIR-CONDITIONING
(Sr No. 1201 TO 1400)
86
ESTIMATING DATA -2007
REFRIGERATORS
1201. Supply and installed refrigerators, Each 6890
electric driven (single phase),
capacity 100 litres.
WATER COOLERS
STORAGE TYPE
87
Sr. DESCRIPTION UNIT RATE REMARKS
NO
Note :— Rates have been worked out based on RC and item shall be issued under sch ‘B’ as free for fixing.
DEEP FREEZER
Note :— Rates are based on reputed makes like M/S Voltas/ Blue Star.
EVAPORATIVE COOLERS
1217. Supply and installed desert cooler Each 2943.0
electric driven (single phase),
having nominal air flow capacity of
1800 Cu,M per hour.
(or nearest size).
88
SER DESCRIPTION UNIT RATE REMARKS
NO
Note :— Rates have been worked out based on RC and item shall be issued under sch ‘B’ as free for fixing.
AIR CONDITIONER
(0) ROOM AC (WINDOW TYPE)
1223. -do- but capacity 4500 K. Cal (1.5 ton). Each 23099.0
Note :— Rates have been worked out based on RC and item shall be issued under sch ‘B’ as free for fixing.
89
SER DESCRIPTION UNIT RATE REMARKS
NO
Note :— Rates have been worked out based on reputed manufacturer like Volta/ Blue star.
1232. Supply and installed air cooled split unit Each 31251.0
Air conditioners electric driven single
Phase of capacity of 1.5 TR.
Note :— Rates have been worked out based on RC and item shall be issued under sch ‘B’ as free for
fixing.
1235. Supply and installed central air conditioning Per Ton 67500.0
installations including water pump
sets cooling towers, ducting and electrical
connection suitable for 3 phase, AC supply
direct expansion system capacity up to
10 Ton.
1239. Supply and installed central air conditioning Per Ton 76950.0
installations including water pump sets cooling
towers, ducting and electrical connection suitable
for 3 phase, AC supply chilled water system,
90
SER DESCRIPTION UNIT RATE REMARKS
NO
capacity of 40 Tons.
1243. Add for provisions of air filters capable Per Ton 4050.0
Of filtering 5 Microns and above
Particles size.
91
SECTION – 5
92
ESTIMATING DATA -2007
Aluminium Ladders
1401. Self supporting Cum extendable Aluminium Each 7125.0
Ladder of 12 feet mtr extendable upto 21 feet.
Crimping Tools
93
SER DESCRIPTION UNIT RATE REMARKS
NO
Digital Meter
1415. Ac Power clamp on meter to measure Each 14107.0
KWH, KVA, KVAR Voltage
OTHER METER
1421. Digital Tachometer Each 2579.0
94
————————————————————————————————————————
SER DESCRIPTION UNIT RATE REMARKS
NO
Note : Prices are based on reputed manufactures like Stanley/Electron devices /Meco.
95
SER DESCRIPTION UNIT RATE REMARKS
NO
1466. Hammer with handle (Ball pein and cross pein) of Each 92.0
200 gms weight conforming to IS 841
96
SER DESCRIPTION UNIT RATE REMARKS
NO
1467. Hammer with handle (Ball pein and cross pein) Each 104.0
of 340 gms weight conforming to IS 842
1468. Hammer with handle (Ball pein and cross pein) Each 141.0
of 500 gms weight conforming to IS 843
1469. Claw hammer with handle of 340 gms weight Each 145.0
1470. Claw hammer with handle of 450 gms weight Each 152.0
97
SER DESCRIPTION UNIT RATE REMARKS
NO
IS 2028 of size 18 x 21 mm
98
SER DESCRIPTION UNIT RATE REMARKS
NO
DISCHARGE ROD
1515. Wooden discharge rod PVC Coated suitable Each 2714.0
99
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
for 11 KV
Note: Rates are based on reputed manufacturer like Jaipuria brothers/ Elpro
Note: Rates are based on reputed manufacturer like Stanley/ Jupiter/ Electron Devices
WATER SUPPLY
1522. Chlorine gas mask Each 4071.0
100
Sr. DESCRIPTION UNIT RATE REMARKS
NO.
and alarm
1528. New empty 100 Kgs capacity chlorine cylinder Each 29857.0
fitted with valves and valve guard
SWIMMING POOL
1532. Suction Sweeper complete with motor, Each 94999.0
pump & starter, mounted on trolley including
nylon rope, hose pipe float etc complete.
101
SECTION – 6
TECHNICAL DATA
102
Table 1 Maximum Permissible Number of Single Core Cables up to and Including 1100 V that can be Drawn
into Rigid Steel Conduit and Rigid Non–Metallic Conduits
Table 2 Maximum permissible number of single core cables that can be drawn into cable
tunneling and ducting system (Casing and Caping)
Source for table 1 & 2 Page No. 33 of part 8 section 2 of NBC — 2005
103
Table 3 AREA REQUIRED FOR TRANSFORMER ROOM AND SUBSTATION FOR DIFFERENT
CAPACITIES
104
Table 4 Voltage Drop in Over head Lines LT and HT
Sr No. Type of Conductor Voltage drop for LT line in Voltage drop for HT
Volt per Amp per KM line in Volt per Amp
per KM
Note :— While calculating the voltage drop resistance at 40 0C and inductance at 30 cm (For LT)
and 50 cm (For HT) spacing between the conductor has been considered.
105
Table 5 MINIUM CLEARANCES FOR INDOOR TRANSFORMER
Minimum clearance between the highest point of conservation tank to the ceiling of the transformer
room should be sufficient to remove the mounting on the transformer like the conservator.
However, this clearance should not be less than 0.5 mtr. Minimum spacing between the walls of
room and the transformer is given below:—
106
Table 6 Maximum allowable losses for oil filled distribution transformers with highest
voltage for equipment 36 KV, at 50% and 100 % of the load.
107
Table 7 Estimated Voltage Drops in XLPE Aluminium Cables For A C System
108
Table 8 Short Circuit Rating For XLPE Cables (For duration of one second)
109
TABLE 9 TYPICAL ALLOWANCES FOR DIVERSITY
Purpose of final circuit Fed Individual Household Type of Premises small, Type of premises
from conductors or Installations, including shops, stores offices and small Hotels,
Switchgear to which Individual Dwelling of Business Premises Boarding Houses
Diversity Applies a Block etc.
(3) (4)
(1) (2)
Lighting 66 % of total current 99% of total current 75% of total
demand demand current demand
Heating and power 80% of total current 80% full load of largest 80 % full load of
demand upto 10A + 40% appliance largest appliance
of any current demand in + 60 % of remaining + 60% of second
excess of 10 A appliances largest appliances
+40% of
remaining
appliances
Cooking appliances 10 A 80 % full load of largest 80% of largest
+30% full load of appliances appliance
connected cooking +60% full load of 60% of full load of
appliance in excess of second largest appliance second largest
10A+5A if socket-outlet +50% full load of appliance + 50%
incorporated in unit . appliances full load of
remaining
appliances
Motors (other than lift 80% full load of largest 80% full load of
motors which are subject to motor largest motor
special consideration) + 60% full load of + 50% full load of
second largest motor remaining motors
+ 50% full load of
remaining motors
Water Heater 80% full load of largest 80% full load of largest 80% full load of
appliance appliance largest appliance
+ 50% of second largest + 60% of second largest + 60% of second
appliance appliance appliance
+ 25% full load of + 25% full load of + 25% full load of
remaining appliances remaining appliances remaining
appliances
Floor warming installations 50%
110
stationery equipment other current demand of every + 60% of current point of + 60% of
than those listed above other point of demand of every other current demand of
point of every point in
main
rooms(dinning
rooms, etc)+ 40%
of current demand
of every other
point of.
NOTES :
1. For the purpose of the table an instantaneous water heater is deemed to be water heater of any loading
which heats water only while the tap is turned on and therefore uses electricity intermittently .
2. It is important to ensure that the distribution boards are of sufficient rating to take total load connected
to them without the application of any diversity .
3. After calculating the electrical load on the above basis, a load factor of 70 to 90 percent is to be
applied to arrive at the minimum capacity of substation.
111
GEN SET DERATING
Gen Set are to be derated based on altitude, temperature and humidity. Procedure for derating
of Gen Set is explained here with an example.
For 15 KVA load a Gen Set is to be installed at 3000 mtr altitude. Power factor is 0.8
Hence 15 KVA = 15 x 0.8 = 12 KW
Derating factor for 3000 mtr altitude (Refer table given below)
= 31.00 HP
112
3. Cooling water temperature 3.0%
at inlet of intercooler
Humidity % 10 20 30 40 50 60 70 80 90
Typical raw water pump size (Diesel engine) 20 mtr total head.
113
Table 10 Recommended Values for Air Changes for air exhaust application
114
S/No. Application Air Change per Hour
(1) (2) (3)
115
TABLE 11 INSIDE DESIGN CONDITIONS FOR AIR CONDITIONING
116
TABLE 12 OUTDOOR DESIGN CONDITIONS FOR VARIOUS CITIES OF INDIA
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (15) (16) (17)
Ahmedabad 42.3 24.1 41.2 23.5 40.0 24.3 28.7 34.3 28.2 33.6 27.8 33.1 11.5 9.0 12.9 9.8
Akola 43.4 24.0 42.2 23.3 41.0 23.6 27.6 37.8 26.7 34.4 26.1 33.5 12.7 10.3 13.9 10.6
AllAhabad 43.7 23.4 42.2 23.5 40.8 22.7 28.8 33.0 28.4 32.8 28.0 32.6 07.9 7.0 9.1 8.3
Amritsar 41.6 23.2 40.3 24.6 38.9 24.4 29.3 34.8 28.8 34.8 28.4 3.4 2.7 2.3 4.0 3.5
Aurangabad 40.3 22.1 39.3 22.9 38.3 21.3 26.3 36.2 25.3 23.1 24.7 31.4 10.6 8.2 12.0 9.1
Bangalore 34.7 19.6 34.0 19.6 33.1 19.2 23.5 28.9 22.9 28.2 22.5 27.7 14.9 13.0 15.7 13.8
Barmer 43.1 24.2 42.0 23.6 41.0 23.3 28.5 37.9 27.8 35.3 27.2 33.3 9.5 5.1 10.7 5.5
Belgaum 36.5 19.4 35.7 19.6 34.7 19.2 24.3 29.2 23.8 29.5 23.4 28.2 13.2 11.3 14.3 12.2
Bhagalpur 42.2 26.8 40.7 27.4 38.9 25.6 30.0 37.1 29.6 36.4 29.2 35.2 11.4 10.3 12.6 12.4
Bhopal 41.7 22.0 40.5 21.7 39.3 21.3 26.0 31.0 25.6 30.3 25.2 29.9 9.8 6.8 11.0 8.0
Bhubaneshwa 38.9 25.5 37.6 26.6 36.3 26.3 29.4 35.2 28.9 33.3 28.5 32.7 14.4 13.1 15.4 14.0
Bikaner 44.8 22.4 43.4 22.4 42.0 23.1 28.5 34.6 27.9 33.1 27.3 34.7 3.8 2.2 5.3 3.1
Chennai 38.4 26.2 37.3 26.7 36.3 26.4 29.1 33.8 28.6 33.2 28.1 31.9 19.5 20.2 18.7 19.3
Chitradurg 36.6 18.8 35.8 19.0 35.0 19.6 23.9 28.9 23.5 28.2 23.2 28.5 15.4 12.5 16.4 13.3
Dehradun 37.8 23.5 36.3 23.9 34.8 22.8 27.0 31.3 26.5 30.1 26.0 29.8 5.9 5.0 6.8 5.8
Dibrugarh 34.0 27.4 33.2 26.8 32.3 26.7 28.3 32.6 27.8 31.8 27.4 31.3 7.5 7.2 8.7 8.4
Gorakhpur 41.4 26.2 40.3 26.0 39.1 26.4 29.9 35.2 29.7 35.5 29.4 34.7 7.9 7.5 9.0 8.4
Guwahati 34.4 26.9 33.4 27.3 32.7 26.8 28.8 32.4 28.3 31.8 27.9 31.5 10.2 9.8 11.3 10.8
Gwalier 43.9 23.0 42.5 22.9 41.3 23.5 27.9 32.9 27.6 32.4 27.3 32.7 4.9 3.8 6.4 5.3
Hissar 44.7 56.5 43.3 25.8 41.7 27.9 30.1 40.2 29.9 39.0 29.4 36.8 5.0 4.2 6.1 5.2
H’bad 40.4 22.5 39.2 22.5 38.2 22.4 25.6 33.7 25.2 32.4 24.8 32.0 14.4 4.4 15.5 12.9
Imphal 31.1 23.3 30.2 23.5 29.6 22.9 25.0 29.5 24.6 28.6 24.3 28.3 3.9 3.6 5.0 4.6
117
____________________________________________________________________________________________________
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (15) (16) (17)
Indore 51.1 20.7 40.4 20.6 38.9 21.0 25.7 31.0 25.2 30.0 24.8 29.8 8.2 5.0 9.7 6.5
Jabalpur 42.6 22.7 41.2 23.2 39.8 22.5 26.8 31.8 26.4 32.0 26.0 31.2 7.8 6.7 9.3 7.6
Jagdelpur 39.4 22.3 38.6 22.5 37.4 22.4 26.4 32.4 25.9 31.8 25.4 30.7 8.9 7.9 10.1 8.7
Jaipur 42.8 22.5 41.4 22.6 39.4 22.6 27.4 33.1 27.0 32.1 26.6 31.7 6.4 4.5 8.0 5.8
Jaisalmer 43.7 23.7 42.5 23.1 41.4 23.5 27.7 34.8 27.3 34.5 26.9 34.4 5.0 2.5 6.5 3.7
Jamnagar 37.1 24.4 36.1 25.6 35.3 25.1 29.2 33.0 28.4 32.5 27.9 32.0 10.0 8.6 11.7 10.5
Jodhpur 42.0 23.2 40.8 23.0 39.6 22.7 28.0 35.4 27.4 33.7 26.9 33.8 7.5 4.3 8.7 5.4
Jorhat 34.4 28.2 33.6 27.7 32.9 27.3 28.7 32.7 28.3 32.1 28.0 31.8 9.6 9.0 10.6 10.1
Kolkatta 37.2 25.4 36.2 26.1 35.2 26.5 29.5 34.3 29.0 33.4 28.6 32.7 12.0 10.9 13.1 12.9
Kota 43.5 23.0 42.4 22.6 41.2 22.6 27.3 35.2 26.8 33.0 26.5 31.8 9.9 6.7 10.8 7.6
Kurnool 41.6 23.2 40.3 24.6 38.9 24.4 29.3 34.8 28.8 34.8 28.4 33.4 2.7 2.3 4.0 3.5
Lucknow 42.0 24.2 40.8 24.8 39.3 24.5 28.8 33.3 28.4 32.4 28.0 32.2 7.5 6.8 8.4 7.7
Manglore 33.9 24.4 33.9 24.0 33.4 24.2 27.1 31.0 26.7 31.0 26.4 30.7 19.7 17.0 20.5 18.1
Mumbai 35.3 22.8 34.3 23.3 33.5 24.0 27.9 31.8 27.5 31.3 27.2 31.1 16.5 13.9 17.8 14.8
Nagpur 43.8 23.6 42.6 23.9 41.4 23.6 27.3 31.2 26.6 33.2 26.2 31.9 11.5 9.4 12.8 10.2
Nellore 40.4 27.8 39.0 28.1 37.8 27.2 30.0 37.1 29.4 35.4 28.8 34.0 19.4 18.3 20.2 19.3
New Delhi 41.8 23.6 40.6 23.8 39.4 23.5 28.4 33.3 28.0 33.3 27.6 32.7 6.0 5.2 7.1 6.3
Panjim 34.0 24.8 33.5 25.2 33.0 25.2 27.7 32.3 27.4 31.5 27.0 30.9 19.6 17.8 20.3 18.7
Patana 40.7 23.4 39.5 23.7 38.0 24.7 29.0 33.9 28.6 33.1 28.3 32.6 8.0 7.6 9.2 8.6
Pune 38.4 20.5 37.4 20.4 36.3 20.6 24.8 30.9 24.4 30.6 24.0 29.6 9.2 8.0 10.3 9.2
Raipur 43.6 23.3 42.2 23.3 40.8 23.0 27.1 31.8 26.8 32.0 26.5 31.2 11.3 9.9 12.6 10.4
Rajkot 40.8 23.1 39.9 23.8 38.9 23.4 28.1 33.9 27.6 33.3 27.1 32.3 10.9 6.5 12.2 7.7
Rama- 43.4 25.6 42.2 25.1 40.7 25.8 28.3 37.3 27.9 35.6 27.4 34.4 12.5 11.2 13.7 12.5
-gundam
Ranchi 38.9 22.1 37.7 21.8 36.4 21.5 26.2 31.7 25.6 30.4 25.2 29.2 9.1 7.2 10.4 8.3
Ratnagiri 34.1 22.4 33.4 23.2 32.8 23.6 27.6 31.1 27.3 30.8 27.0 30.2 18.3 14.9 19.2 16.5
Raxaul 38.6 23.1 36.9 24.5 35.5 24.6 28.9 33.0 28.4 32.0 28.1 31.8 7.5 7.3 8.5 8.2
118
—————————————————————————————————————————————————————
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (15) (16) (17)
______________________________________________________________________________________________________
Saharan 41.3 23.8 39.6 24.6 38.1 24.0 28.5 33.6 28.1 32.9 27.8 32.5 1.7 1.5 3.0 2.7
Pur
Shillong 24.2 19.7 23.5 19.4 22.8 18.9 20.7 23.3 20.3 22.7 19.9 22.2 -1.0 -1.1 0.1 -0.5
Sholapur 41.1 21.6 40.1 21.6 39.1 21.2 26.6 32.6 25.8 32.1 25.1 31.5 16.3 12.4 17.2 12.5
Sundar- 36.1 19.1 34.6 19.9 33.1 19.4 25.2 30.1 24.8 29.2 24.4 28 1.8 1.3 2.8 2.2
-nagar
Surat 38.4 22.7 36.9 23.9 35.7 23.4 28.3 32.4 27.9 31.7 27.6 31.4 14.8 12.6 16.2 12.5
Tezpur 34.2 27.4 33.3 26.5 32.5 27.1 28.9 32.8 28.4 31.8 28.0 31.4 10.5 10.0 12.4 10.9
Tiruchi - 39.6 24.6 38.7 25.1 37.8 24.9 27.7 34.5 27.2 33.7 26.9 33.3 19.3 18.2 20.1 18.7
-rapalli
Thiruva - 33.9 26.0 33.4 26.1 32.9 25.9 27.7 32.4 27.4 31.9 27.0 31.0 21.6 20.1 22.2 20.8
-nantha-
-puram
Veraval 35.2 23.9 33.8 23.5 32.8 26.6 29.1 32.3 28.7 31.6 28.4 31.1 14.3 10.1 15.6 12.3
Vishakha- 36.4 26.5 35.6 27.3 35.0 27.1 29.2 33.8 28.8 33.0 28.4 32.5 15.4 14.9 16.8 16.2
-patanam
119
120
121
DERATING FACTORS FOR THE CABLE
(1) Cables laid directly in ground
Ground 15 20 25 30 35 40 45 50
Temperature
(0C)
Ratings 1.17 1.12 1.06 1.0 0.94 0.87 0.79 0.76
Factors
122
(2) Cables laid directly in duct
75 1.00
90 0.99
105 0.98
120 0.97
150 0.96
180 0.95
270 0.92
360 0.91
450 0.90
540 or more 0.89
GROUND 15 20 25 30 35 40 45
TEMPERATURE 0C
123
(d) Group rating factors for multi-core cables in horizontal formation.
(f) Group rating factors for circuits of three single-core cables in trefoil touching formation.
Ambient air 20 25 30 35 40 45 50
temperature (0C)
Rating factor 1.07 1.04 1.00 0.95 0.91 0.86 0.82
(b) Group rating factors for multi-core cables laid on racks in air (with cables touching)
124
(c) Group rating factors for multi-core cables laid on racks in air (with spacing between cables
equal to diameter of cable).
(d) Group rating factors for Single core cables in 3 phase system when laid on racks in air in Trefoil
formation (with spacing between circuits equal to twice the diameter of cable)
125
AN EXAMPLE OF FAULT LEVEL CALCULATIONS
TRANSFORME STANDBY
R G
GENERATOR
PCC 1600 1250 KVA
11 ° ) 12 ° )
° °
°) 13 F2
21 ° ) 22 ° ) F1 23 ° ) 24 ° )
° ° ° °
MCC BUSBAR
31 °) U/G CABLE
°
°) CB
° ° F3 ° ° °
°
SDF
M M M M STARTER
50HP 100HP 30HP 150HP
2. SYSTEM DATA
126
Un = NOMINAL SYSTEM VOLTAGE (LINE TO LINE)
Z = TOTAL IMPEDANCE FROM SOURCE TO THE
POINT OF FAULT, IN OHMS
4. CALCULATION OF ‘Z’
Z=
WHERE,
RS, XS = RESISTANCE & REACTANCE OF THE SOURCE
= RT, XT (FOR TRANSFORMER-UTILITY SUPPLY)
= RGK, XGK (FOR GENERATOR)
= RM, XM (FOR Induction Motor)
RL, XL = TOTAL LINE OR CABLE RESISTANCE &
REACTANCE FROM SOURCE TO THE POINT
OF FAULT
5. CALCULATION OF ‘RT’ & ‘XT’
KG = Un C
UrG ( 1 + (xd″) ( Sin φrG) )
Xd″ = 10 (%xd″)(KV)2
KVA rating of generator
127
1250
RG = 0.15 Xd″ = (0.15)(0.02756) = 0.00413 OHMS
CALCULATION OF RL & XL
= 0.00649 Ω
128
DIMENSIONAL DETAIL OF LIFT
Recommended Dimension of Passenger lift
(All dimension in millimeters)
129
NOTES :
1. The total overhead dimensions has been calculated on the basis of car height of 2.3 m.
2. In case of manually operated doors, clear entrance will be reduced by the amount of
projection of handle on the landing door .
3. All dimensions given above for lifts having centre opening power operated doors with
counterweight at rear, are recommended dimensions primarily for architects and building
planners . Any variations mutually agreed between the manufacture and the purchaser are
permitted . However, variation in :
(a) Car inside dimensions shall be within the maximum area limits specified in accordance with
accepted standards [8-5(4)] .
(b) Entrance width on higher side is permitted .
(c) Entrance width on lower side is permitted up to 100 mm subject to minimum of 700mm.
4. Dimensions of pit depth and overhead may differ in practice as per individual manufacture’s
design depending upon load, speed and drive. Recommended dimensions for pit depth, overhead
and machine-room for different lift speeds are given in Table 1A .However, the pit depth and
overhead shall be such as to confirm to the requirement of bottom clearance and top clearance in
accordance with the accepted standards[8-5(5)]
SPEED :— It is dependent upon the quantity of service required and the quality of service desired.
Therefore, no set formulae for indicating the speed can be given. However, the following
general recommendations are made:
No of Floors Speed
Source :— For all lift data given above and afterward please refer IS 14665 (Part I).
130
Recommended Dimension of Goods lift
(All dimension in millimeters)
131
Recommended Dimension of Hospital lift
(All dimension in millimeters)
132
Recommended Dimension of Service lift
(All dimension in millimeters)
133
TABLE 4 CAPACITOR SIZES FOR POWER FACTOR IMPROVEMENT
Factor 0.80 0.85 0.90 0.91 0.92 0.93 0.94 0.95 0.96 0.97 0.98 0.99 1.00
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14)
MULTIPLYING FACTOR
0.40 1.537 1.668 1.805 1.832 1.861 1.895 1.924 1.959 1.998 2.037 2.085 2.146 2.288
0.41 1.474 1.605 1.742 1.769 1.798 1.831 1.860 1.896 1.935 1.973 2.021 2.082 2.225
0.42 1.413 1.544 13681 1.709 1.738 1.771 1.800 1.836 1.874 1.91 1.961 2.022 2.165
0.43 1.356 1.487 1.624 1.651 1.680 1.713 1.742 1.778 1.816 1.855 1.903 1.964 2.107
0.44 1.290 1.421 1.558 1.585 1.614 1.647 1.677 1.712 1.751 1.790 1.837 1.899 2.041
0.45 1.230 1.360 1.501 1.532 1.561 1.592 1.626 1.659 1.695 1.737 1.784 1.846 1.988
0.46 1.179 1.309 1.446 1.473 1.502 1.533 1.567 1.600 1.636 1.677 1.725 1.786 1.929
0.47 1.130 1.260 1.397 1.425 1.454 1.485 1.519 1.552 1.588 1.629 1.677 1.758 1.881
0.48 1.076 1.206 1.343 1.370 1.400 1.430 1.464 1.497 1.534 1.575 1.623 1.684 1.826
0.49 1.030 1.160 1.297 1.326 1.355 1.386 1.420 1.453 1.489 1.530 1.578 1.639 1.782
0.50 0.982 1.112 1.248 1.276 1.303 1.337 1.369 1.403 1.441 1.481 1.529 1.590 1.732
0.51 0.936 1.066 1.202 1.230 1.257 1.291 1.323 1.357 1.395 1.435 1.483 1.544 1.686
0.52 0.894 1.024 1.160 1.188 1.215 1.249 1.281 1.315 1.353 1.393 1.441 1.502 1.644
0.53 0.850 0.980 1.116 1.144 1.171 1.205 1.237 1.271 1.309 1.349 1.397 1.458 1.600
0.54 0.809 0.939 1.075 1.103 1.130 1.164 1.196 1.230 1.268 1.308 1.356 1.417 1.559
0.55 0.769 0.899 1.035 1.063 1.090 1.124 1.136 1.190 1.228 1.268 1.316 1.377 1.519
0.56 0.730 0.860 0.996 1.024 1.051 1.085 1.117 1.151 1.189 1.229 1.277 1.338 1.480
0.57 0.692 0.822 0.958 0.986 1.013 1.047 1.079 1.113 1.151 1.191 1.239 1.300 1.442
0.58 0.655 0.785 0.921 0.949 0.976 1.010 1.042 1.076 1.114 1.54 1.202 1.263 1.405
0.59 0.618 0.748 0.884 0.912 0.939 0.973 1.005 1.039 1.077 1.117 1.165 1.226 1.368
0.60 0.584 0.714 0.849 0.878 0.905 0.939 0.971 1.005 1.043 1.083 1.131 1.192 1.334
0.61 0.549 0.679 0.815 0.843 0.870 0.904 0.936 0.970 1.008 1.048 1.096 1.157 1.299
0.62 0.515 0.645 0.781 0.809 0.836 0.870 0.902 0.936 0.974 1.014 1.062 1.123 1.265
0.63 0.483 0.613 0.749 0.777 0.804 0.838 0.870 0.904 0.942 0.982 1.030 1.091 1.233
0.64 0.450 0.580 0.716 0.744 0.771 0.805 0.837 0.871 0.909 0.949 0.997 1.058 1.200
0.65 0.419 0.549 0.85 0.713 0,740 0.774 0.806 0.840 0.878 0.918 0.966 1.027 1.169
0.66 0.388 0.518 0.654 0.682 0.709 0.743 0.775 0.809 0.847 0.887 0.935 0.996 1.138
0.67 0.358 0.488 0.624 0.652 0.679 0.713 0.745 0.779 0.817 0.857 0.905 0.966 1.108
0.68 0.329 0.459 0.595 0.623 0.650 0.684 0.716 0.750 0.788 0.828 0.876 0.937 1.079
0.69 0.299 0.429 0.565 0.593 0.620 0.654 0.686 0.720 0.758 0.98 0.810 0.907 1.049
0.70 0.270 0.400 0.536 0.564 0.591 0.625 0.657 0.691 0.729 0.769 0.811 0.878 1.020
0.71 0.242 0.372 0.508 0.536 0.563 0.597 0.629 0.663 0.701 0.741 0.785 0.850 0.992
0.72 0.213 0.343 0.479 0.507 0.534 0.568 0.600 0.634 0.672 0.712 0.754 0.821 0.963
0.73 0.186 0.316 0.452 0.480 0.507 0.541 0.573 0.607 0.648 0.685 0.727 0.794 0.926
0.74 0.159 0.289 0.425 0.53 0.480 0.514 0.546 0.580 0.618 0.658 0.700 0.740 0.909
0.75 0.132 0.262 0.398 0.426 0.453 0.487 0.519 0.553 0.591 0.61 0.673 0.713 0.882
0.76 0.105 0.235 0.371 0.399 0.426 0.460 0.492 0.526 0.564 0.604 0.652 0.687 0.855
0.77 0.079 0.0209 0.345 0.373 0.400 0.434 0.466 0.500 0.538 0.578 0.620 0.661 0.829
0.78 0.053 0.183 0.319 0.347 0.374 0.408 0.440 0.474 0.512 0.552 0.594 0.634 0.803
0.79 0.026 0.156 0.292 0.320 0.347 0.381 0.413 0.447 0.485 0.525 0.567 0.608 0.776
0.80 - 0.136 0.266 0.294 0.321 0.355 0.387 0.421 0.459 0.499 0.541 0.582 0.750
0.81 0.104 0.240 0.268 0.295 0.329 0.361 0.433 0.473 0.515 0.556 0.724 -
0.82 - 0.078 0.214 0.242 0.269 0.303 0.369 0.407 0.447 0.489 0.530 0.498
0.83 - 0.052 0.188 0.216 0.243 0.277 0.343 0.381 0.421 0.463 0.504 0.672
0.84 - 0.026 0.162 0.190 0.217 0.251 0.317 0.355 0.395 0.437 0.478 0.645
0.85 - - 0.136 0.164 0.191 0.225 0.291 0.329 0.369 0.417 0.450 0.620
0.86 - - 0.109 0.140 0.167 0.198 0.264 0.301 0..343 0.390 0.424 0.593
0.87 - - 0.083 0.114 0.141 0.172 0.238 0.275 0.317 0.364 0.395 0.567
134
MULTIPLYING FACTOR
Factor 0.80 0.85 0.90 0.91 0.92 0.93 0.94 0.95 0.96 0.97 0.98 0.99 1.00
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14)
0.88 - - 0.054 0.085 0.112 0.143 0.209 0.246 0.288 0.335 0.395 0.538
0.89 - 0.028 0.059 0.086 0.117 0.149 0.183 0.230 0.262 0.309 0.369 0.512 -
0.90 - - - 0.031 0.058 0.089 0.121 0.155 0.192 0.234 0.281 0.341 0.484
0.91 - - - - 0.027 0.058 0.090 0.124 0.167 0.203 0.250 0.310 0.453
0.92 - - - - - 0.027 0.063 0.097 0.134 0.176 0.223 0.283 0.426
0.93 - - - - - - 0.032 0.066 0.103 0.145 0.192 0.252 0.395
0.94 - - - - - - - 0.34 0.071 0.113 0.160 0.220 0.363
0.95 - - - - - - - - 0.037 0.079 0.126 0.186 0.329
0.96 - - - - - - - - - 0.042 0.089 0.149 0.292
0.97 - - - - - - - - - - 0.047 0.107 0.250
0.98 - - - - - - - - - - 0.60 0.203 -
0.99 - - - - - - - - - - - - 0.143
135
HEAD LOSS DUE TO FRICTION IN PIPE
Friction loss in pipe has been worked out by modified Hazen Willium formula. As per the formula friction loss in pipe is directly proportional
to length of pipe but it is exponentially related to discharge and dia of pipe. Hence friction loss has been worked out for various discharge values and
different dia but for fixed length of pipe line. Users are requested to multiply the corresponding friction loss in pipe line by required length. Friction
loss given here is applicable to GI/CI/DI pipes
Friction drop in meter for 100 (One hundred) meter length of pipe
1 25 5.0066 17.5551
2 40 0.5221 1.8306 6.4188
3 50 0.1387 0.4864 1.7055 3.5528 5.9801 8.9560 12.4576
4 63 0.0456 0.1600 0.5611 1.1689 1.9675 2.9467 4.0987 5.4178 6.8991 8.5384
5 80 0.0145 0.0507 0.1778 0.3705 0.6236 0.9339 1.2990 1.7171 2.1865 2.7061 3.2746
6 100 0.0049 0.0173 0.0608 0.1267 0.2132 0.3193 0.4441 0.5870 0.7475 0.9251 1.1195
7 150 0.0007 0.0025 0.0086 0.0180 0.0303 0.0454 0.0632 0.0835 0.1063 0.1316 0.1592
8 200 0.0002 0.0006 0.0022 0.0045 0.0076 0.0114 0.0158 0.0209 0.0266 0.0330 0.0399
136
Friction drop in meter for 1000 (One thousand) meter length of pipe
137
Friction drop in meter for 1000 (One thousand) meter length of pipe
1 400 0.4817 0.6134 0.9186 1.2777 1.6889 2.1507 2.6617 3.2209 6.7097 11.2939
2 450 0.2733 0.3481 0.5213 0.7251 0.9584 1.2205 1.5105 1.8278 3.8077 6.4092
3 500 0.1647 0.2097 0.3140 0.4368 0.5774 0.7353 0.9100 1.1011 2.2939 3.8611
4 600 0.0685 0.0872 0.1307 0.1817 0.2402 0.3059 0.3786 0.4581 0.9543 1.6064
138