CONDUCTORS RATING

PVC ABC Bare Al


Rating Rating Rating Size Rating (A)
Size Size
AI(A) Cu(A) (A) Al
7/083 (25mm) 90 110 1x16+25 80 3/132 120
19/064 (35mm) 120 140 3x16+25 80 7/122 (50mm) 170
19/083 (70mm) 180 230 3x95+70 190 7/173 (100mm) 260
7/173 (100mm) 250 3x185+120 300
CABLES RATING
XLPE PILC
11kV LV 11kV LV
Size (mm) Size (mm)
Rating (A) Rating (A) Rating (A) Rating (A)
25 110 25 80 90
70 190 70 140 160
120 250 120 200 230
185 320 185 250 290
300 400 300 330 380
95 210
150 280
240 350
500 550
CONDUCTORS FUSE RATING
PVC ABC Bare Al
Max Fuse Max Fuse Max Fuse Size Max
Size Size
AI(A) Cu(A) (A) Al Fuse (A)
7/083 (25mm) 60 80 1x16+25 50 3/132 80
19/064 (35mm) 80 100 3x16+25 50 7/122 (50mm) 100
19/083 (70mm) 125 160 3x95+70 125 7/173 (100mm) 160
7/173 (100mm) 160 3x185+120 200
TRANSFORMERS/CABLES (FUSE RATING)
TRANSFORMER LV CABLE
11kV 22kV 33kV PILC XLPE
KVA HT Fuse (A) HT Fuse (A) HT Fuse (A) Cable Size Max Fuse (A) Max Fuse (A)
50 5 5 2 25 60 75
100 10 5 5 70 100 100
300 30 15 10 120 125 160
500 50 25 20 185 200 200
750 75 40 30 300 250 250
1000 90 50 40