ROUTINE TEST REPORT

HIGH VOLTAGE CIRCUIT BREAKER


TYPE: DT1-72.5 F1 FK
SERIAL NUMBER: 16186-DT09 Rev. 0
TEST NUMBER: D13848, TEST DATE: 4/29/2011
CUSTOMER: Techna S.A./ Carbones Del Cerrejon
CONTENTS: PAGE
1. GENERAL INFORMATION .......................................................................................... 2
2. RATED VALUES OF CIRCUIT BREAKER ................................................................2
2.1 CONTROL VOLTAGES ............................................................................................... 2
2.2 FUNCTIONAL LIMITS OF CLOSING AND AUXILIARY FUNCTIONS......................... 2
3. CURRENT TRANSFORMER TESTS ................................................................ 3
4. NAMEPLATE CHECK ................................................................................................ 3
5. LEAKAGE TEST ................................................................................................ 3
6. HEATER AND COIL VALUES ..................................................................................... 3
7. ELECTRICAL CONTROLS AND SECONDARY WIRING CHECK TEST ................... 3
8. CLEARANCE AND MECHANICAL ADJUSTMENT CHECK TESTS .......................... 3
9. CONDUCTIVITY OF CURRENT PATH TEST ............................................................. 4
10. TIMING TESTS ...........................................................................................................
4
11. MOTOR CHARACTERISTICS (STORED ENERGY SYSTEM TEST) ........................ 5
12. MECHANICAL OPERATION TESTS ........................................................................... 5
13. LOW-FREQUENCY WITHSTAND VOLTAGE TESTS ON MAJOR
INSULATION COMPONENTS ..................................................................................... 5
14. LOW-FREQUENCY WITHSTAND VOLTAGE TESTS ON CONTROL AND
SECONDARY WIRING ................................................................................................ 5
15. GAS DENSITY MONITORING SYSTEM ................................................................ 6
16. ADDITIONAL MEASUREMENTS AND VALUES......................................................... 6
17. ADDENDUM ...............................................................................................................
6
Tested by (inspector): BS Date: 4/29/2011

Review and release: Sig. Date: 4/29/2011

One Power Lane – Charleroi, PA 15022 – Tel. : 724-483-7308 – Fax : 724-483-7771


QUALITY ASSURANCE Page: 2

AREVA T&D Inc. Charleroi ROUTINE TEST REPORT D13848 Test date: 4/29/2011

1. GENERAL INFORMATION

Manufacturer: AREVA T&D Inc.


Circuit breaker type: DT1-72.5 F1 FK
AREVA test plan: Q-10-120 Rev. 8
According to standard: IEC 62271-100
Operating mechanism type: FK3-1/131
Circuit breaker serial no: 16186-DT09 Rev. 0
Contract no: CX06005
Test no: D13848
Outline drawing number: DT09C12666 Rev. 0
Wiring diagram number: DT09C02666 Rev. 0
Instruction manual number: IB-DT09-F1-ESP
Customer: Techna S.A./ Carbones Del Cerrejon
Plant/Substation: N/A
Purchase order no.: SE-2010-005
Equipment / Item no.: N/A

2. RATED VALUES OF CIRCUIT BREAKER

Rated voltage: 72.5 kV


Maximum service voltage: 72.5 kV
Rated frequency: 60 Hz
Rated continuous current: 1250 A
Rated short circuit breaking current: 25 kA
Rated pressure: 66.7 psig

2.1 CONTROL VOLTAGES AND FUNCTIONAL LIMITS

Closing coil(s): 125 DC V


Tripping coil(s): 125 DC V
Control apparatus: 125 DC V
Spring winding motor: 125 DC V
Cabinet heater: 120 AC V
Tank heaters: N/A V

2.2 FUNCTIONAL LIMITS OF CLOSING AND AUXILIARY FUNCTIONS

Min. Max.
Closing and auxiliary functions: 106 DC V 137 DC V
Tripping functions: 87 DC V 137 DC V
Motor voltage: 106 DC V 137 DC V

One Power Lane – Charleroi, PA 15022 – Tel. : 724-483-7308 – Fax : 724-483-7771


QUALITY ASSURANCE Page: 3

AREVA T&D Inc. Charleroi ROUTINE TEST REPORT D13848 Test date: 4/29/2011

3. CURRENT TRANSFORMER TESTS

Polarity after assembly: Pass


Wiring check: Pass
CT ratios: Pass

4. NAMEPLATE CHECK

Check for completeness of identification and rating: Pass

5. LEAKAGE TEST

Test pressure 66.7 psig: Pass (no leaks detected)

6. HEATER AND COIL VALUES

1. Closing coil: 36.1 Ω


2. Closing coil: N/A Ω

1. Trip coil: 36.1 Ω


2. Trip coil: 35.7 Ω

1. Cabinet heater: 139.2 Ω


2. Cabinet heater: 139.4 Ω
3. Cabinet heater: N/A Ω
4. Cabinet heater: N/A Ω

1. Auxiliary cabinet heater N/A Ω


2. Auxiliary cabinet heater N/A Ω

Tank heaters A (Phases 1/2/3): N/A Ω


Tank heaters B (Phases 1/2/3): N/A Ω

7. ELECTRICAL CONTROLS AND SECONDARY WIRING CHECK TEST

Continuity test: Pass


Functional test: Pass

8. CLEARANCE AND MECHANICAL ADJUSTMENT CHECK TESTS

Mechanical adjustments: Pass


Kirk key locking device N/A

One Power Lane – Charleroi, PA 15022 – Tel. : 724-483-7308 – Fax : 724-483-7771


QUALITY ASSURANCE Page: 4

AREVA T&D Inc. Charleroi ROUTINE TEST REPORT D13848 Test date: 4/29/2011

9. CONDUCTIVITY OF CURRENT PATH TEST

Phase A B C
Resistance at 100 A min. 135 µΩ 137 µΩ 137 µΩ

10. TIMING TESTS

CLOSING
Parameter / Phase A B C
Closing time 70.5 ms 70.0 ms 70.0 ms
Difference between phases 0.5 ms

OPENING
Parameter / Phase A B C
Opening time 26.7 ms 27.7 ms 27.2 ms
Difference between phases 1.0 ms

CLOSE-OPEN
Parameter / Phase A B C
Trip-free time 47.4 ms 48.9 ms 48.5 ms

OPEN-CLOSE
Parameter / Phase A B C
Reclose time 76.4 ms 75.0 ms 75.5 ms

One Power Lane – Charleroi, PA 15022 – Tel. : 724-483-7308 – Fax : 724-483-7771


QUALITY ASSURANCE Page: 5

AREVA T&D Inc. Charleroi ROUTINE TEST REPORT D13848 Test date: 4/29/2011

11. MOTOR CHARACTERISTICS (STORED ENERGY SYSTEM TEST)

Peak motor current at rated voltage: 8.3 A


Motor running time at rated voltage: 3.1 sec

12. MECHANICAL OPERATION TESTS

Operation Control voltage Number of Results


operations
Close - Minimum Voltage 106 DC V 5 Pass
Close - Rated Voltage 125 DC V 5 Pass
Close - Maximum Voltage 137 DC V 5 Pass
Open - Minimum Voltage 87 DC V 5 Pass
Open - Rated Voltage 125 DC V 5 Pass
Open - Maximum Voltage 137 DC V 5 Pass
Close-Open - Rated Voltage 125 DC V 5 Pass
Open-Close - Rated Voltage 125 DC V 5 Pass

13. LOW-FREQUENCY WITHSTAND VOLTAGE TESTS ON MAJOR INSULATION


COMPONENTS

Test frequency: 60 Hz
Test pressure: 47.9 psig
Duration: 60 sec

Test conditions Results


Condition Applied voltage (kV) Phase 1 Phase 2 Phase 3
Across open contacts 160 Pass Pass Pass
Line to ground 160 Pass Pass Pass

14. LOW-FREQUENCY WITHSTAND VOLTAGE TESTS ON CONTROL AND


SECONDARY WIRING

Location Test frequency Duration Applied voltage Results


Wiring / coils / control apparatus 60 Hz 1 sec 2 kV Pass
Spring winding motor 60 Hz 1 sec 2 kV Pass
Current transformers and wiring 60 Hz 60 sec 3.0 kV Pass

One Power Lane – Charleroi, PA 15022 – Tel. : 724-483-7308 – Fax : 724-483-7771


QUALITY ASSURANCE Page: 6

AREVA T&D Inc. Charleroi ROUTINE TEST REPORT D13848 Test date: 4/29/2011

15. GAS DENSITY MONITORING SYSTEM

Alarm level 52.2 psig


Lockout 47.9 psig
Lockout #2 47.9 psig
Test temperature: 20 (deg C)

16. ADDITIONAL MEASUREMENTS AND VALUES

No. of operations on counter after factory testing: 52

17. ADDENDUM

Enclosed documents:
- Travel-time curves

Serial Number Listing:

Operating mechanism: 172202


Current transformers 1/W/X/Y/Z: - / 30097505 / 30097504 / -
Current transformers 2/W/X/Y/Z: - / 30097507 / 30097601 / -
Current transformers 3/W/X/Y/Z: - / 30097508 / 30097502 / -
Current transformers 4/W/X/Y/Z: - / 30097506 / 30097602 / -
Current transformers 5/W/X/Y/Z: - / 30097501 / 30097503 / -
Current transformers 6/W/X/Y/Z: - / 30097509 / 30097603 / -
Insulators 1/2/3/4/5/6: C-2-108 / C-2-1029 / C-2-1073 / C-2-1057 / C-2-
1064 / C-2-1096
Phase vessels 1/2/3 (ht/serial no): 10Y2803-1223 / 10X0101-1222 / 10Y2811-
1220

One Power Lane – Charleroi, PA 15022 – Tel. : 724-483-7308 – Fax : 724-483-7771


5.0 ° 1.25 A /D IV

I COIL C

S MAIN C1

CMAIN A1

CMAIN B1

CMAIN C1

-50.00 ms -25.00 ms 0.00 ms 25.00 ms 50.00 ms 75.00 ms 100.00 ms 125.00 ms 150.00 ms 175.00 ms 200.00

Teststep: close
4/29/2011 1:41:02 PM 16186B-DT09

ACTAS Advanced circuit breaker test system CX06005


5.0 ° 1.25 A /D IV

I COIL C

S MAIN C1

CMAIN A1

CMAIN B1

CMAIN C1

-50.00 ms -25.00 ms 0.00 ms 25.00 ms 50.00 ms 75.00 ms 100.00 ms 125.00 ms 150.00 ms 175.00 ms 200.00

Teststep: Open
4/29/2011 1:41:14 PM 16186B-DT09

ACTAS Advanced circuit breaker test system CX06005


5.0 ° 1.25 A /D IV

I COIL C

S MAIN C1

CMAIN A1

CMAIN B1

CMAIN C1

-50.00 ms 0.00 ms 50.00 ms 100.00 ms 150.00 ms 200.00 ms 250.00 ms 300.00

Teststep: CO
4/29/2011 1:41:46 PM 16186B-DT09

ACTAS Advanced circuit breaker test system CX06005


5.0 ° 1.25 A /D IV

I COIL C

S MAIN C1

CMAIN A1

CMAIN B1

CMAIN C1

-50.00 ms 0.00 ms 50.00 ms 100.00 ms 150.00 ms 200.00 ms 250.00 ms 300.00

Teststep: OC
4/29/2011 1:42:08 PM 16186B-DT09

ACTAS Advanced circuit breaker test system CX06005