Data taken from Manohar Prasad, Refrigeration & Air Conditioning Dimensions of compressor Bore : 80 mm Stroke : 75 mm Refrigerant used

: R-134a Compression Index = n =1.12 RPM of compressor = N = 1500 Temperature Range: -150 C to 400 C Ratio of Vc to Vs = C = 0.03 TEMPERATURE (0 C) 400 C -150 C ENTHALPY (KJ/Kg) 419.8 KJ/Kg 389.29 KJ/Kg PRESSURE (KPa) 1017 KPa 165 KPa

Specific Volume (at -150 C ) = V1 = 0.8653 m3/kg Volumetric Efficiency = v = 1- [ C { P2/P1}(1/1.12) 1] = 0.878 ( on calculation by using given values) Stroke Volume = /4*(d2 L N)/60 = 0.00942 m3 / s ( on calculation by using given values ) Mass flow rate = m* = Vs (v / V1 ) = 0.00955 kg/s Power = m* ( h2 h1) = 0.2913 KW = 291.3 Watts