Você está na página 1de 343

SETOR

RESIDNCIA (SEDE)

GALPO

ARMAZM

ORDENHA

IRRIGAO
TOTAL

SETOR
1
2
3
4
5

RESIDNCIA (SEDE)
GALPO
ARMAZM
ORDENHA
IRRIGAO

TABE
SETOR
1
2
3
4

RESIDNCIA (SEDE)
GALPO
ARMAZM
ORDENHA

5 IRRIGAO
TOTAL

FATORES DE PROJETO
PINST. (kW)
DM (kW)
Dm (kW)

95.58
46.08

FDemanda

0.48

FCarga

0.23

FUtilizao
FReserva

0.11

10.77

2.07

REGIO
FUNCIONAMENTO
FPerdas

A
FOLGADO
0.11

Fdiversidade
FSimultaneidade

4.28
0.23

LOCALIZAO DO TRAN
1
2
3
4
5

RESIDNCIA (SEDE)
GALPO
IRRIGAO
ARMAZEM
SALA DE ORDENHA
TOTAL

CENTRO DE CARGA - DISTRIBUIO MISTA


XCC (m)
1044
YCC (m)
716
DEMANDA MXIMA (KVA)

DESCRIO
CLASSE DE TENSO (kV)
TENSO NOMINAL (V)
ENROL. PRIMRIO (V)
ENROL. SECUNDRIO (V)
POTNCIA (kVA)
TIPO DE LIGAO

54.48

SUBESTAO ABAIXADORA
Transformador Trifsico
15
13800
13800/13200/12600/12000
380/220
75
Estrela com neutro aterrado

CARGAS
2
1
1
1
1
1
1
1
1
1
TOTAL

ILUMINAO
TOMADAS
CHUVEIRO ELTRICO
RESERVA
ILUMINAO
TOMADAS
ESMERIL
SERRA ELTRICA
SOLDA
RESERVA
ILUMINAO
TOMADAS
VENTILAO
ELEVADOR
DESINTEGRADOR
RESERVA
ILUMINAO
TOMADAS
TANQUE DE RESFRIAMENTO
ORDENHA
RESERVA
ILUMINAO
BOMBA DE IRRIGAO
RESERVA

540
3600
7500
2200
6400
8000
1
2
4500
2200
4000
2000
10
15
7.5
2200
650
700
1.5
2
2200
700
7.5
2200

POTNCIA TOTAL INSTALADA


PE (T) (kW)

fp
0.95
0.83
0.89
0.82
0.86

13.84
25.72
38.87
7.17
9.98

Q (kVAr)
4.76
17.58
19.41
5.03
5.80

TABELA DE DEMANDAS
PINST. (kW)

DM (kW)

13.84
25.72
38.87
7.17

10.50
9.29
26.45
4.77

D' (kW) (17-18)


0.60
19.03
26.45
0

9.98
95.58

LOCALIZAO DO TRANSFORMADOR
D (kVA)
14.63
31.15
43.45
8.76
11.54
109.53

COTA CORRIGIDA
900
765

7.78
58.79

0
46.08

X (m)
800
1635
740
1312
695
-

Y (m)
1000
1067
280
1161
708
-

540
3600
7500
2200
6400
8000
736
1472
4500
2200
4000
2000
7360
11040
5520
2200
650
700
1104
1472
2200
700
5520
2200
-

h
1.00
1.00
1.00
1.00
1.00
1.00
0.68
0.65
0.78
1.00
1.00
1.00
0.72
0.82
0.79
1.00
1.00
1.00
0.70
0.72
1.00
1.00
0.78
1.00
-

gi'

gi

gi PINST.

0.76
0.36
0.68
0.67

0.11
0
0
0

1.52
0.00
0.00
0.00

PS(W)
W
W
W
W
W
W
CV
CV
W
W
W
W
CV
CV
CV
W
W
W
CV
CV
W
W
CV
W

S (kVA)
14.63
31.15
43.45
8.76
11.54

POTNCIA TOTAL INSTALADA


PE (T) (kW)
fp
0.54
3.60
7.50
2.20
6.40
8.00
1.08
2.26
5.77
2.20
4.00
2.00
10.22
13.46
6.99
2.20
0.65
0.70
1.58
2.04
2.20
0.70
7.08
2.20
95.58

0.80
0.80
1.00
0.80
0.80
0.80
0.85
0.75
0.92
0.80
0.80
0.80
0.93
0.94
0.85
0.80
0.80
0.80
0.82
0.85
0.80
0.80
0.89
0.80
0.88

Q (kVAr)
0.41
2.70
0.00
1.65
4.80
6.00
0.67
2.00
2.46
1.65
3.00
1.50
4.04
4.89
4.33
1.65
0.49
0.53
1.10
1.27
1.65
0.53
3.63
1.65
50.92

0.78
-

1.00
0.40

X D (kVAm)

Y D (kVAm)
14634
33235
12165
10170
8171
716

11707
50928
32152
11493
8021
1044

9.98
38.23

S (kVA)
0.68
4.50
7.50
2.75
8.00
10.00
1.27
3.02
6.27
2.75
5.00
2.50
10.99
14.32
8.22
2.75
0.81
0.88
1.92
2.41
2.75
0.88
7.95
2.75
108.29

SETOR

0-1

1-2

2-3

3-4

4-5

5-6
0.30

DEMANDA ATIVA (kW)

6-7
1.00

1.58

1.58

1.58

5
TOTAL

D t (h)
e (Wh)
Dm (kW)

0.65
0.50
1.58

0.65
0.50
1.58

0.70

0.70

7.08

7.08

0.65
0.50
1.58
2.04

1.58

1.58

1.58

1.58

10.51

10.51

5.07

2.58

1
1580.00
1.58

1
1580.00
1.58

1
1580.00
1.58

1
10506.92
10.51

1
10506.92
10.51

1
5074.44
5.07

1
2577.14
2.58

0.30

1.00

4.77

1.58

DEMANDA ATIVA (kW)

SETOR
1
2
3
4
5
TOTAL

fp

1.58

1.58

0.82

1.58

1.58

0.82

1.58

1.58

0.82

2.73

2.73

7.78
10.51

7.78
10.51

0.86

0.86

5.07

0.83

2.58

0.81

HORAS DO DIA - D (kW)


7-8
1.50
7.50

8-9
1.20
4.00
3.50
1.08

9-10
0.70
4.00
3.50
1.08

10-11
0.80

11-12
0.80

12-13
2.00

13-14
2.00

14-15
0.70

4.00
3.50
1.08

15-16
0.60
4.00
2.00

4.00
2.00
10.22

4.00
2.00
10.22

5.77
4.00
2.00

6.99

6.99

1.58

1.58

1.58

1.58

1.58

1.58

1.58

1.58

1.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

25.49

26.94

1
10580.00
10.58

1
11362.35
11.36

1
10862.35
10.86

1
10962.35
10.96

1
2380.00
2.38

1
19802.22
19.80

1
3580.00
3.58

1
25489.56
25.49

1
26936.57
26.94

2.00

0.70

0.60

HORAS DO DIA - D (kW)


9.00

1.20

0.70

0.80

8.58

8.58

8.58

0.80

2.00

11.77
16.22

1.58

10.58

0.94

1.58

11.36

0.81

1.58

10.86

0.81

1.58

10.96

0.81

1.58

2.38

0.81

1.58

19.80

0.86

1.58

3.58

0.81

23.21

12.99

1.58

1.58

25.49

0.86

26.94

0.82

16-17
0.60

17-18
0.30
0.80

4.00
7.00

4.00
2.00

2.26
5.77
4.00
2.00

2.26

18-19
0.40
0.80

19-20
0.40
2.00
7.50

20-21
0.40
2.00
7.50

21-22
0.40

22-23

23-24

1.58

1.58

1.58

1.58

1.58

13.46
6.99

1.58

0.65
0.50
1.58
2.04

0.65
0.50
1.58
0.70

0.70

7.08

7.08

47.66

14.14

11.70

11.48

11.48

1
47664.60
47.66

1
14139.06
14.14

1
11704.07
11.70

0.60

1.10

1.20

9.90

9.90

0.40

19.03

8.26

2.73

1.58

1.58

1.58

1
1
11480.00 11480.00
11.48
11.48

1.98

9.36

1.58

1
1980.00
1.98

1
9356.92
9.36

1
1580.00
1.58

1.58

1.58

26.45
1.58

47.66

0.87

4.77

14.14

0.77

7.78
11.70

0.86

11.48

0.92

11.48

0.92

1.98

0.82

7.78
9.36

0.87

1.58

0.82

Carga capacitiva a ser adicionada Q(VAr)


Carga Reativa Corrigida Q(KVAr)
S(KVA) Corrigido
fp Corrigido

SETOR

0-1

1-2

2-3

3-4

4-5

5-6
0.23

DEMANDA REATIVA (kW)

0.75

1.10

1.10

1.10

5
TOTAL

DEMANDA REATIVA (kW)

6-7

1.10

1.10

1.10

0.49
0.38
1.10

0.49
0.38
1.10

0.53

0.53

3.63

3.63

6.11

6.11

0.49
0.38
1.10
1.27

1.10

3.46

1.85

0.23

0.75

3.23

1.10

SETOR
1
2
3
4
5
TOTAL

1.10

1.10

1.10

1.10

1.10

1.10

1.96

1.96

4.15
6.11

4.15
6.11

3.46

1.85

citiva a ser adicionada Q(VAr)


eativa Corrigida Q(KVAr)
S(KVA) Corrigido
fp Corrigido

Correo da Carga
0.43
0.67
1.93
0.82

0.43
0.67
1.93
0.82

0.43
0.67
1.93
0.82

1.64
4.48
12.16
0.86

1.64
4.48
12.16
0.86

1.29
2.16
6.14
0.83

0.75
1.10
3.17
0.81

HORAS DO DIA - DQ (kVAr)


7-8

8-9

9-10

10-11

11-12

12-13

13-14

14-15

15-16

16-17

1.13
0.00

0.90

0.53

0.60

0.60

1.50

1.50

0.53

0.45

0.45

3.00
2.63
0.67

3.00
2.63
0.67

3.00
2.63
0.67

3.00
2.63

3.00
2.63

2.46
3.00
1.50

2.00
2.46
3.00
1.50

4.33

4.33

4.89
4.33

3.00
1.50
4.04

3.00
1.50
4.04

1.10

1.10

1.10

1.10

1.10

1.10

1.10

1.10

1.10

1.10

2.23

8.30

7.92

8.00

1.70

11.14

2.60

14.50

18.46

25.35

1.50

0.53

0.45

0.45

8.08

10.08

12.87

8.83

13.72

1.10

1.10

1.10

HORAS DO DIA - DQ (kVAr)


1.13

0.90

0.53

0.60

6.30

6.30

6.30

0.60

1.50

8.54
1.10

2.23

1.10

8.30

1.10

7.92

1.10

8.00

1.10

1.70

1.10

11.14

1.10

2.60

14.50

18.46

25.35

Correo da Carga Reativa Q(VAr)


2.28
3.46
3.29
3.33
-0.06
4.84
4.63
4.67
10.81
14.07
13.44
13.57
0.98
0.81
0.81
0.81

0.69
1.01
2.93
0.81

2.71
8.44
22.72
0.87

1.08
1.53
4.43
0.81

3.64
10.86
29.32
0.87

6.99
11.47
32.66
0.82

5.04
20.31
53.99
0.88

17-18
0.23
0.60

18-19
0.30
0.60

19-20
0.30
1.50
0.00

20-21
0.30
1.50
0.00

21-22
0.30

22-23

23-24

1.10

1.10

1.10

1.10

1.10

2.00

0.49
0.38
1.10
1.27

0.49
0.38
1.10
0.53

0.53

3.63

3.63

11.68

7.01

2.90

2.90

1.40

0.83

0.90

1.80

1.80

0.30

1.96

1.10

1.10

1.10

5.25

1.10

1.10

1.10

7.62

3.23

11.68

4.15
7.01

2.90

2.90

1.40

4.15
5.25

1.10

DEMANDA APARENTE (kW)

DEMANDA APARENTE (kW)

3.00
2.63

5.65
6.02
18.34
0.77

2.03
4.99
13.64
0.86

1.99
0.91
11.84
0.97

1.99
0.91
11.84
0.97

0.56
0.84
2.43
0.82

1.27
3.99
10.73
0.87

0.43
0.67
1.93
0.82

SETOR

0-1

1-2

2-3

3-4

4-5

5-6
0.38

6-7

7-8

1.25

1.88
8

1.92

1.92

6.14

3.17

11.30

0.38

1.25

9.38

5.77

1.92

1.92

1.92

1.92

1.92

5
TOTAL

1.92

1.92

1.92

0.81
0.63
1.92

0.81
0.63
1.92

0.88

0.88

7.95

7.95

12.19

12.19

0.81
0.63
1.92
2.41

SETOR
1
2
3
4
5
TOTAL

1.92

1.92

1.92

1.92

1.92

1.92

3.36

3.36

8.83
12.19

8.83
12.19

6.14

3.17

11.30

HORAS DO DIA - DS (kVA)


8-9

9-10

10-11

11-12

12-13

13-14

14-15

15-16

16-17

1.50

0.88

1.00

1.00

2.50

2.50

0.88

0.75

0.75

17-18
0.38
1.00

5
4
1.27

5
4
1.27

5
4
1.27

5
3

5
7

5
3

3.02
6.27
5.00
2.50

3.02

6.27
5.00
2.50

8.22

14.32
8.22

5.00
2.50
10.99

5.00
2.50
10.99
8.22

0.81
0.63
1.92
2.41

1.92

1.92

1.92

1.92

1.92

1.92

1.92

1.92

1.92

14.07

13.45

13.57

2.92

22.91

4.42

29.51

32.96

54.48

18.46

2.50

0.88

0.75

0.75

1.38

14.57

21.77

11.32

26.71

15.72

30.04

1.92

1.92

1.92

HORAS DO DIA - DS (kVA)


1.50

0.88

1.00

10.65

10.65

10.65

1.00

2.50

18.49
1.92

14.07

1.92

13.45

1.92

13.57

1.92

2.92

1.92

22.91

1.92

4.42

29.51

32.96

54.48

5.77

18.46

18-19
0.50
1.00

0.81
0.63
1.92

19-20
0.50
2.50
8

20-21
0.50
2.50
8

21-22
0.50

22-23

23-24

1.92

1.92

1.92

1.92

1.92

DEMANDAS M
0.88

0.88

7.95

7.95

13.69

12.42

12.42

2.42

10.75

Ds mx (kVA)
1.92

54.48

DEMANDAS M

Ds mx (kVA)
1.50

10.50

10.50

0.50

10.50
21.77
30.04

3.36
8.83
13.69

1.92

12.42

1.92

12.42

1.92

2.42

1.92
18.70
20.62

1.92

1.92

5.77
18.70
54.48

DEMANDAS MXIMAS

D mx (kW)

DQ mx (kVAr)

fp

47.66

25.35

0.87

D mx (kW)

DQ mx (kVAr)

fp

19 -21

9.90

1.80

0.94

16 - 17

19.03

10.08

0.87

16 - 17

26.45

13.72

0.88

5-6 / 17 - 18

4.77

3.23

0.83

3-5 / 18-19/ 22-23


16 - 17

7.78
47.66

4.15
25.35

0.42
0.87

HORA(S) DO DIA
16 - 17

DEMANDAS MXIMAS

HORA(S) DO DIA

Curva de Carga
60.00

50.00

47.66

D (kW)

40.00

30.00
25.49

26.94

19.80

20.00

14.14
11.70 11.48 11.48

10.58 11.36 10.86 10.96

10.51 10.51

9.36

10.00
5.07
1.58

1.58

2.58

1.58

3.58

2.38

1.98

0.00
0-1

2-3

4-5

6-7

8-9

10-11

12-13

Horas do dia

14-15

16-17

18-19

20-21

22-23

Demanda Reativa
30.00

25.35
25.00

D (kW0

20.00

18.46

14.50

15.00

11.68

11.14
10.00

8.30

7.92

8.00
7.01

6.11

6.11

5.25
5.00

3.46
1.10

1.10

1.10

1.85

2.23

2.90

2.60

2.90

1.70

1.40

1.10

0.00
4

10

11

12

13

Horas do dia

14

15

16

17

18

19

20

21

22

23

24

Demanda Aparente
60.00
54.48

50.00

40.00

D (kW)

32.96
29.51

30.00
22.91

18.46

20.00
14.07 13.45 13.57

12.19 12.19

13.69

11.30

12.42 12.42
10.75

10.00
6.14
1.92

1.92

1.92

3.17

4.42

2.92

2.42

1.92

0.00
4

10

11

12

13

Horas do dia

14

15

16

17

18

19

20

21

22

23

24

1.00
0.94
0.90

0.86

0.83

0.82

0.81
0.81

0.87
0.86

0.81
0.81

0.81

0.92

0.87

0.86

0.86

0.86

0.82 0.82
0.80

0.92

0.82

0.82

0.81

0.77
0.70

0.60

0.50

0.40

0.30

0.20

0.10

0.00
1

11

13

15

17

19

21

23

Carga capacitiva necessria


8.00

6.99

7.00

6.00

5.65
5.04

Carga

5.00

4.00

3.46

3.64
3.29 3.33

3.00

2.71
2.28
2.03 1.99 1.99

2.00

1.64 1.64
1.29

1.27

1.08
1.00

0.75

0.69

0.43 0.43 0.43

0.56

0.43

0.00
0-1

1-2

2-3

3-4

4-5

5-6

6-7

7-8

8-9

9-10 10-11 11-12 12-13 13-14 14-15 15-16 16-17 17-18 18-19 19-20 20-21 21-22 22-23 23-24
Horas do dia

Potncia Total Instalada - SEDE


Iluminao (W)

540.00 W

T.U.G.s (W)

3600.00 W

T.U.E.s (W)

7500.00 W

Cargas Especiais (W)

0.00 W

Reserva (W)

2200.00 W

fp Total

0.95
Potncia Total Instalada

13840.00 W

14634.06 VA

13.84 KW

14.63 KVA

Demanda Provvel
D = A + (B1 + B2 + B3 + B4 + B5 + B6 + B7 + B8) + C + D + E

A (Demanda de Iluminao, Tomadas de Uso Geral e Reserva)

PT (W)

DP (W)

0 < P <= 1

0.86

1000

860

1 < P <= 2

0.75

1000

750

2 < P <= 3

0.66

1000

660

3 < P <= 4

0.59

1000

590

4 < P <= 5

0.52

1000

520

5 < P <= 6

0.45

1000

450

6 < P <= 7

0.40

340

136

Total

6340.00

3966.00

B1 ( Demanda de Chuveiros Eltricos)


Nmero de Aparelhos

0.68

Potncia de Entrada (W)

3750

Demanda Provvel (W)

5100

Demanda Provvel

9066.00 W

9586.15 VA

Demanda Provvel

9.07 KW

fp Total

0.66

Ramal de Entrada
B1

Categoria
Potncia Instalada

13.84

kW

Demanda Provvel

9.59

kVA

50

Ramal de Ligao Areo / Alumnio / Multiplex / XLPE

10

mm

Ramal de Entrada / Cobre / PVC (70C)

10

mm

Aterramento
Cobre Nu

10

Disjuntor Termomagntico
Condutores

mm

Tipos de Ligao:
Fases

Fios

Dimetro Nominal Interno dos Eletrodutos:


Ramal de Entrada

32

mm

Aterramento

16

mm

9.59 kVA

Potncia Total Instalada - GALPO


Iluminao (W)

6400.00 W

T.U.G.s (W)

8000.00 W

T.U.E.s (W)

5769.23 W

Cargas Especiais (W)

3346.97 W

Reserva (W)

2200.00 W

fp Total

0.83
Potncia Total Instalada

25716.20 W

31148.47

25.72 KW

31.15

Demanda Provvel
D = A + (B1 + B2 + B3 + B4 + B5 + B6 + B7 + B8) + C + D + E

A (Demanda de Iluminao, Tomadas de Uso Geral e Reserva)

PT (W)

DP (W)

0 < P <= 1

0.86

1000

860

1 < P <= 2

0.75

1000

750

2 < P <= 3

0.66

1000

660

3 < P <= 4

0.59

1000

590

4 < P <= 5

0.52

1000

520

5 < P <= 6

0.45

1000

450

6 < P <= 7

0.40

1000

400

7 < P <= 8

0.35

1000

350

8 < P <= 9

0.31

1000

310

9 < P <= 10

0.27

1000

270

10<p

0.24

6600

1584

Total

16600.00

6744.00

B1 (Demanda da Solda)
Nmero de Aparelhos

Potncia de Entrada (W)

5769.2

Demanda Provvel (W)

5769.23

D1 (Demanda de Fora - Esmeril)


Total de Motores

Demanda Provvel (kVA)

6.27

Demanda Provvel (W)

5330.27

D2 (Demanda de Fora - Serra Eltrica)


Total de Motores

Demanda Provvel (kVA)

3.02

Demanda Provvel (W)

2264.62

Demanda Provvel

20108.11 W

24355.73

Demanda Provvel

Fator de Demanda

20.11 KW

0.78

Ramal de Entrada
Categoria

T1

Potncia Instalada

25.72 kW

Demanda Provvel

24.36 KVA

Disjuntor Termomagntico

40 A

Condutores:
Ramal de Ligao Areo / Alumnio / Multiplex / XLPE

10 mm

Ramal de Entrada / Cobre / PVC (70C)

10 mm

Aterramento:
Cobre Nu

10 mm

Tipos de Ligao:
Fases

Fios

Dimetro Nominal Interno dos Eletrodutos:


Ramal de Entrada

32 mm

Aterramento

16 mm

24.36

Potncia Total Instalada - ARMAZM


Iluminao (W)

4000.00 W

T.U.G.s (W)

2000.00 W

T.U.E.s (W)

0.00 W

Cargas Especiais (W)

30673 W

Reserva (W)

2200 W

fp Total

0.89

VA

Potncia Total Instalada

38872.98 W

KVA

38.87 KW

Demanda Provvel
D = A + (B1 + B2 + B3 + B4 + B5 + B6 + B7 + B8) + C + D + E

A (Demanda de Iluminao, Tomadas de Uso Geral e Reserva)

PT (W)

0 < P <= 1

0.86

1000

1 < P <= 2

0.75

1000

2 < P <= 3

0.66

1000

3 < P <= 4

0.59

1000

4 < P <= 5

0.52

1000

5 < P <= 6

0.45

1000

6 < P <= 7

0.40

1000

7 < P <= 8

0.35

1000

8 < P <= 9

0.31

200

Total

8200.00

D1 (Demanda de Fora - Ventilao)


Nmero de Aparelhos

Demanda Provvel (kVA)

10.99

Demanda Provvel (W)

10222.22

D2 (Demanda de Fora - Elevador)


Total de Motores

Demanda Provvel (kVA)

14.32

Demanda Provvel (W)

13463.41

D3 (Demanda de Fora - Desintegrador)


Total de Motores

Demanda Provvel (kVA)

8.22

Demanda Provvel (W)

VA

6987.34

Demanda Provvel

35314.98 W

Demanda Provvel

kVA

Fator de Demanda

35.31 KW

0.91

Ramal de Entrada
Categoria

T2

Potncia Instalada

38.87 kW

Demanda Provvel

39.47 KVA

Disjuntor Termomagntico

60 A

Condutores:
Ramal de Ligao Areo / Alumnio / Multiplex / XLPE

16 mm

Ramal de Entrada / Cobre / PVC (70C)

16 mm

Aterramento:
Cobre Nu

16 mm

Tipos de Ligao:
Fases

Fios

Dimetro Nominal Interno dos Eletrodutos:


Ramal de Entrada

40 mm

Aterramento

16 mm

Potncia Total Instalada - ORDENHA


Iluminao (W)
T.U.G.s (W)
T.U.E.s (W)
Cargas Especiais (W)
Reserva (W)

fp Total
43448.14 VA

Potncia Total Instalada

43.45 KVA

Demanda Provvel
D = A + (B1 + B2 + B3 + B4 + B5 + B6 + B7 + B8) + C + D + E

DP (W)

A (Demanda de Iluminao, Tomadas de Uso Geral e Reserva)

860

0 < P <= 1

750

1 < P <= 2

660

2 < P <= 3

590

3 < P <= 4

520

Total

450
400
350
62
4642.00

D1 (Demanda de Fora - Tanque de resfriamento)


Nmero de Aparelhos
Demanda Provvel (kVA)
Demanda Provvel (W)

D1 (Demanda de Fora - Ordenha)


Nmero de Aparelhos
Demanda Provvel (kVA)
Demanda Provvel (W)

39471.38 VA

Demanda Provvel

Demanda Provvel

39.47 kVA

Fator de Demanda

Ramal de Entrada
Categoria
Potncia Instalada
Demanda Provvel
Disjuntor Termomagntico
Condutores:
Ramal de Ligao Areo / Alumnio / Multiplex / XLPE
Ramal de Entrada / Cobre / PVC (70C)
Aterramento:
Cobre Nu
Tipos de Ligao:
Fases
Fios
Dimetro Nominal Interno dos Eletrodutos:
Ramal de Entrada
Aterramento

650.00 W
700.00 W
0.00 W
3622 W
2200 W
0.82
7171.59 W

8759.93 VA

7.17 KW

8.76 KVA

vel

6 + B7 + B8) + C + D + E

PT (W)

DP (W)

0.86

1000

860

0.75

1000

750

0.66

1000

660

0.59

550.00

324.5

Total

3550.00

2594.50

1
1.92
1577.14

1
2.41
2044.44

6216.09 W

7592.81 VA

6.22 KW

0.87

M2
7.17 kW
7.59 KVA
40 A

10 mm
10 mm
10 mm

1
2

25 mm
16 mm

7.59 kVA

Potncia Total Instalada - IRRIGAO


Iluminao (W)

700.00 W

T.U.G.s (W)

0.00 W

T.U.E.s (W)

0.00 W

Cargas Especiais (W)

7076.92 W

Reserva (W)

2200.00 W

fp Total

0.86
Potncia Total Instalada

9976.92 W

11540.63 VA

9.98 KW

11.54 KVA

Demanda Provvel
D = A + (B1 + B2 + B3 + B4 + B5 + B6 + B7 + B8) + C + D + E

A (Demanda de Iluminao, Tomadas de Uso Geral e Reserva)

PT (W)

DP (W)

0 < P <= 1

0.86

1000

860

1 < P <= 2

0.75

1000

750

2 < P <= 3

0.66

900

594

Total

2900.00

2204.00

D1 (Demanda de Fora - Bomda de irrigao)


Nmero de Aparelhos

Demanda Provvel (kVA)

7.95

Demanda Provvel (W)

7076.92

Demanda Provvel

2211.95 W

2558.64 VA

Demanda Provvel

Fator de Demanda

2.21 KW

0.22

Ramal de Entrada
Categoria

M3

Potncia Instalada

9.98 kW

Demanda Provvel

2.56 KVA

Disjuntor Termomagntico

60 A

Condutores:
Ramal de Ligao Areo / Alumnio / Multiplex / XLPE

10 mm

Ramal de Entrada / Cobre / PVC (70C)

16 mm

Aterramento:
Cobre Nu

16 mm

Tipos de Ligao:
Fases

Fios

Dimetro Nominal Interno dos Eletrodutos:


Ramal de Entrada

32 mm

Aterramento

16 mm

2.56 kVA

1
2
3
4
5

1
2
3
4
5

SETOR
SEDE
GALPO
ARMAZM
ORDENHA
IRRIGAO

TRECHO
A-B
A-C
A-D
A-E
A-F

POTNCIA INSTALADA(KW)
13.84
25.72
38.87
7.17
9.98

TIPO DE CIRCUITO
3(F +F+ F+N)
3(F +F+ F+N)
3(F +F+ F+N)
3(F +F+ F+N)
3(F +F+ F+N)

DSMX(KVA)
9.59
24.36
39.47
7.59
2.56

SETOR

TRECHO
A-B
A-C
A-D
A-E
A-F

POTNCIA INSTALADA(KW)
13.84
25.72
38.87
7.172
9.977

TIPO DE CIRCUITO
3(F +F+ F+N)
3(F +F+ F+N)
3(F +F+ F+N)
3(F +F+ F+N)
3(F +F+ F+N)

DSMX(KVA)
9.59
24.36
39.47
7.59
2.56

TRECHO
A-B
A-C
A-D
A-E
A-F

POTNCIA INSTALADA(KW)
13.84
25.72
38.87
7.17
9.98

TIPO DE CIRCUITO
3(F +F+ F+N)
3(F +F+ F+N)
3(F +F+ F+N)
3(F +F+ F+N)
3(F +F+ F+N)

DSMX(KVA)
9.59
24.36
39.47
7.59
2.56

SEDE
GALPO
ARMAZM
ORDENHA
IRRIGAO

SETOR

1
2
3
4
5

SEDE
GALPO
ARMAZM
ORDENHA
IRRIGAO

ALIMENTADORES-T1
k
3
3
3
3
3

VNOMINALV)
380
380
380
380
380

IPROJETO(A)
8.4
21.4
34.6
6.7
2.2

S(AWG)
6
6
4
6
6

S(mm)
13
13
21
13
13

k
3
3
3
3
3

VNOMINALV)
380
380
380
380
380

RAMAIS DE LIGAO-T1
S(mm)
IPROJETO(A)
8.4
3X1X10+10
21.4
3X1X10+10
34.6
3X1X10+16
6.7
3X1X10+10
2.2
3X1X10+10

k
3
3
3
3
3

VNOMINALV)
380
380
380
380
380

IPROJETO(A)
8.4
21.4
34.6
6.7
2.2

RAMAIS DE ENTRADA-T1
S(mm)
1.5
2.5
6
1.5
1.5

LTRECHO(m)
207
530
324
150
485

VADMISSVEL(%)

LTRECHO(m)
20
25
15
12
10

VADMISSVEL(%)

LTRECHO(m)
5
5
5
5
5

VADMISSVEL(%)

2
2
2
2
2

2
2
2
2
2

4
4
4
4
4

R(/Km)
2.6476
2.6476
1.6667
2.6476
2.6476

XL(/km)
0.3904
0.3904
0.374
0.3904
0.3904

t
1
1
1
1
1

fp
0.655
0.782
0.908
0.867
0.222

V(V)

V(%)

S(AWG)
6
6
6
6
6

S(mm)
13
13
13
13
13

3.53
26.20
18.74
2.49
1.05

0.93
6.89
4.93
0.65
0.28

R(/Km)
3.701
3.701
2.295
3.701
3.701

XL(/km)
0.123
0.123
0.101
0.123
0.123

t
1
1
1
1
1

fp
0.655
0.782
0.908
0.867
0.222

V(V)

V(%)

S(mm)

0.42
1.59
1.10
0.26
0.02

0.11
0.42
0.29
0.07
0.01

3X1X10+10
3X1X10+10
3X1X10+16
3X1X10+10
3X1X10+10

XL(/km)
0.16
0.15
0.14
0.16
0.16

t
1
1
1
1
1

fp
0.655
0.782
0.908
0.867
0.222

V(V)

V(%)

S(mm)

0.40
0.75
0.59
0.42
0.04

0.11
0.20
0.16
0.11
0.01

1.5
2.5
6
1.5
1.5

VERIFICACO
OK
NO OK
NO OK
OK
OK

VERIFICACO
OK
OK
OK
OK
OK

21
R(/Km)
14.48
8.87
3.69
14.48
14.48

VERIFICACO
OK
OK
OK
OK
OK

SETOR

1
2
3
4
5

CIRCUITO
1
2
3
4
5

SEDE
GALPO
ARMAZM
ORDENHA
IRRIGAO

TIPO/MODELO
DTM/TQC3415
DTM/TQC1230
DTM/TQC1235
DTM/TQC3410
DTM/TQC3410

TRECHO
A-B
A-C
A-D
A-E
A-F

POTNCIA INSTALADA(KW)
13.84
25.72
38.87
7.17
9.98

PROTEO(DTM=DISJUNTOR TERMOMAGNTICOS)-T1
IPROJETO(A)
N DE PLOS
3
10.5
1
26.7
3
34.6
3
6.7
3
2.8

RAMAL DE ENTRADA BT E CENTRO DE DISTRIBUIO-T1


TIPO DE CIRCUITO
3(F +F+ F+ N)
3(F +F+ F+ N)
3(F +F+ F+ N)
3(F +F+ F+ N)
3(F +F+ F+ N)

DSMX(KVA)
9.59
24.36
39.47
7.59
2.56

k
3
3
3
3
3

VNOMINAL (V)
380
380
380
380
380

GNTICOS)-T1
IN(A)(T=40C)
15
30
35
10
10

IMONTANTE(A)

IPROJETO(A)
10.5
26.7
34.6
6.7
2.8

RIBUIO-T1
S(mm)
1.5
4
6
1.5
1.5

LTRECHO(m)
207
530
324
150
485

12.5

VADMISSVEL(%)

1
1
1
1
1

R(/Km)
2.19
0.23
0.32
3.69
8.87

XL(/km)
0.13
0.11
0.1
0.14
0.15

t
1
1
1
1
1

fp
0.655
0.782
0.908
0.867
0.222

V(V)

V(%)

3.34
3.52
3.73
3.27
2.87

0.88
0.93
0.98
0.86
0.76

S(mm)
10
95
70
6
6

VERIFICACO
OK
OK
OK
OK
OK

DIMENSIONAMENTO DOS ELETRODUTOS DE RAMAL DE ENTR


SETOR

P(KW)

DSMAX(KVA)

TIPO DE CIRCUITO

S(mm)

SEDE
GALPO
ARMAZM
ORDENHA
IRRIGAO

13.84
25.72
38.87
7.17
9.98

9.59
24.36
39.47
7.59
2.56

3(F +F+ F+ N)
3(F +F+ F+ N)
3(F +F+ F+ N)
3(F +F+ F+ N)
3(F +F+ F+ N)

10
95
70
6
6

DIMENSIONAMENTO DOS ELETRODUTOS SUBID


TRECHO

P(KW)

DSMAX(KVA)

TIPO DE CIRCUITO

S(mm)

QT-CM
DC-AG

13.84
25.72

9.59
24.36

3
3

2.5
4

GD-CD
FD-BG
SS-AG

38.87
7.17
9.98

39.47
7.59
2.56

3
3
3

6
2.5
2.5

NTO DOS ELETRODUTOS DE RAMAL DE ENTRADA


REA TOTAL(mm)

REA TIL(mm)

REFERNCIA DE ROSCA

DIMETRO
NOMINAL(mm)

24.6
177
133
15.2
15.2

67.1
107.9
107.9
67.1
67.1

3/8"
1/2"
1/2"
3/8"
3/8"

16
20
20
16
16

AMENTO DOS ELETRODUTOS SUBIDAS E DESCIDA DO QUADRO DE MEDIO


REA TOTAL(mm)

REA TIL(mm)

REFERNCIA DE ROSCA

DIMETRO
NOMINAL(mm)

42.8
55.2

50.7
81.4

3/8"
1/2"

40
20

15.2
42.8
42.8

67.1
50.7
50.7

3/4"
3/8"
3/8"

16
40
40

REFERNCIA DE ROSCA

DIMETRO
NOMINAL(mm)

3/4"
1"

25
32

1.1/4"
3/4"
3/4"

40
25
25

220

6400

2 TUG_GALPO

220

3 TUE_SOLDA

220

4 MOTOR_ESMERIL

220

5 MOTOR_SERRA ELTRICA

220

6 RESERVA
Total

Carga TUG (W)

Carga ILUM. (W)

1 ILUMINAO_GALPO

Circuito N

Tenso Nominal (V)

Circuito Tipo / Local

Diviso da Instalao
em Circuitos

8000

220

6400

8000

CIRCUITO N 1
TRECHO

I (A)

T21_20

1.38

T20_19

2.76

T19_18

4.15

T18_17

5.53

T17_16

6.91

T16_15

8.29

T15_14

9.67

T14_13

11.05

T13_12

12.44

T12_11

13.82

T11_10

15.20

T10_9

16.58

T9_8

17.96

T8_7

19.35

T7_6

20.73

T6_5

22.11

T5_4

23.49

T4_3

24.87

T3_2

26.25

T2_1

27.64

T6_QT

29.02

Total

29.02

5769
1082
2265

5769

3347

8000

S (VA)

8000

Q (Var)

6400

Fase F3 (W)

Fase F1 (W)

6400

Fase F2 (W)

Carga Total (W)

Carga Reserva (W)

Cargas Especiais (W)

Carga TUE (W)

Tenso, Corrente e Potncia

4800.00

8000

6000.00

10000

5769

5769

2457.68

6270.90

1082

1082

670.78

1273.36

2265
2200

2200

2200

25716

2265

8665

8000

1997.20

3019.49

2200

2750

9052

15927

30249.0054

CIRCUITO N 1

CIRCUITO N2
I L (A KM)

TRECHO

0.00358

0.00494967

TUG19_18

2.27

0.00280

0.00636364

0.00358

0.00989935

TUG18_17

4.55

0.00540

0.02454545

0.00358

0.01484902

TUG17_16

6.82

0.00365

0.02488636

0.00358

0.01979869

TUG16_15

9.09

0.00436

0.03963636

0.00358

0.02474836

TUG15_14

11.36

0.00400

0.04545455

0.00358

0.02969804

TUG14_13

13.64

0.00359

0.04895455

0.00480

0.04642909

TUG13_12

15.91

0.00442

0.07031818

0.00358

0.03959738

TUG12_11

18.18

0.00400

0.07272727

L (KM)

I (A)

L (KM)

I L (A KM)

0.00358

0.04454705

TUG11_10

20.45

0.01014

0.20736818

0.00358

0.04949673

TUG10_9

22.73

0.00600

0.13636364

0.00358

0.0544464

TUG9_8

25.00

0.01014

0.253475

0.00358

0.05939607

TUG8_7

27.27

0.00800

0.21818182

0.00358

0.06434575

TUG7_6

29.55

0.00400

0.11818182

0.00480

0.09285818

TUG6_5

31.82

0.00400

0.12727273

0.00358

0.07424509

TUG4_3

34.09

0.00400

0.13636364

0.00358

0.07919476

TUG3_2

36.36

0.00400

0.14545455

0.00358

0.08414444

0.00358

0.08909411

0.00358

0.09404378

0.00358

0.09899345

0.00313

0.09089075

0.103943

Total

36.36

0.055795

Seo
Mnima
Fator de Potncia

f1 x f2 x f3 x f4

Corrente de Projeto (A)

S (mm)

FCT

N/( )

FCA

Mtodo de
Referncia

Corrente Corrigida (A)

S (mm)

Critrio: Capacidade de Corrente

0.80

36.36

1.5

0.87

0.60

B1

69.66

16.0

0.80

45.45

2.5

0.87

0.60

B1

87.08

25.0

0.92

28.50

2.5

0.87

0.60

B1

54.61

10.0

0.85

5.79

2.5

0.87

0.60

B1

11.09

1.5

0.75

13.72

2.5

0.87

0.60

B1

26.29

4.0

0.80

0.85

0.79

45.83

f1

0.66

TAmbiente (C)

40

FCTAmbiente

0.87

f2

1.00

TSolo (C)

30

FCTSolo

0.89

f3

1.20

R.T.S.(Km/W)

2.5

FCRTS

1.00

f4

1.00

Dimensionamento de Condutores e
Estimativas Prelim

e (%)

e (%) x V (V)

L (Km)

I x L (A Km)

DV unit. (V/AKm)

S (mm)

Condutores Fase (mm)


Estimativa Preliminar 1

Condutores Fase (mm)


Estimativa Preliminar 2

Tipo

N de Plos

Critrio: Limite da Queda de Tenso

4.4

0.103943127

42.3308411

2.5

16.0

16.0

DTM

4.4

0.055795455

78.8594705

1.5

25.0

25.0

DTM

4.4

0.0105320

0.461196845

9.54039483

6.0

10.0

10.0

DTM

4.4

0.0067400

0.440604818

9.986273

4.0

4.0

10.0

DTM

4.4

0.0022700

0.049024858

89.7503875

1.5

4.0

10.0

DTM

DTM

Dimensionamento
de Condutores

Ic (A)

Iz (A)

Verificaao\

Condutores Fase (mm)


Estimativa Preliminar 3

Condutores Fase (mm)

Condutor Neutro (mm)

Condutor Terra (mm)

Tipo

N de Plos

Dimensionamento d

In (A) ( C)

to de Condutores e Dispositivos de Proteo:


Estimativas Preliminares

37.5

76

39.672

OK

16.0

16.0

16.0

16.0

DTM

48.6

101

52.722

OK

25.0

25.0

25.0

25.0

DTM

23.6

57

29.754

NO OK

10.0

10.0

10.0

10.0

DTM

23.6

57

29.754

OK

10.0

10.0

10.0

10.0

DTM

23.6

57

29.754

OK

10.0

10.0

10.0

10.0

DTM

60

DTM

IN (A) (50 C)

Ic (A)

Iz (A)

Verificaao

In^ (A)

Dimensionamento de Dispositivos de Proteo

37.5

76

39.672

OK

40

48.6

101

52.722

OK

50

37.5

76

39.672

OK

40

23.6

57

29.754

OK

25

23.6

57

29.754

OK

25

OK

60

60.0

LISTA DE MATERIAIS
CDIGO
1
1.1
2

ESPECIFICAO DO MATERIAL

QUANT.

UNIDADE

SUBESTAO ABAIXADORA
TRANSFORMADOR TRIFSICO
POTNCIA: 75kVA

PEA

CONDUTORES

2.1

CABOS UNIPOLARES DE ALUMNIO N COM


ALMA DE AO
SEO: 6 AWG

700

METROS

2.2

CABOS UNIPOLARES DE ALUMNIO N COM


ALMA DE AO
SEO: 4 AWG

500

METROS

2.3

CABOS UNIPOLARES DE ALUMNIO


MULTIPLEXADO ISOLAO XLPE (90)
SEO: 1x1x10+10 mm

450

METROS

2.4

CABOS UNIPOLARES DE ALUMNIO


MULTIPLEXADO ISOLAO XLPE (90)
SEO: 2x1x10+10 mm

20

METROS

2.5

CABOS UNIPOLARES DE ALUMNIO


MULTIPLEXADO ISOLAO XLPE (90)
SEO: 2x1x16+16 mm

50

METROS

2.6

CABOS UNIPOLARES DE ALUMNIO


MULTIPLEXADO ISOLAO XLPE (90)
SEO: 3x1x10+10 mm

25

METROS

2.7

CABOS UNIPOLARES DE ALUMNIO


MULTIPLEXADO ISOLAO XLPE (90)
SEO: 3x1x16+16 mm

35

METROS

2.8

CABOS UNIPOLARES DE ALUMNIO


MULTIPLEXADO ISOLAO XLPE (90)
SEO: 3x1x35+70 mm

12 / 4

METROS

2.9

CABOS UNIPOLARES DE COBRE


ISOLAO DE PVC
SEO: 2,5mm

105

METROS

2.10

CABOS UNIPOLARES DE COBRE


ISOLAO DE PVC
SEO: 4,0mm

55

METROS

2.11

CABOS UNIPOLARES DE COBRE


ISOLAO DE PVC
SEO: 10mm

35

METROS

2.12

CABOS UNIPOLARES DE COBRE


ISOLAO DE PVC
SEO: 16mm

85

METROS

2.13

CABOS UNIPOLARES DE COBRE


ISOLAO DE PVC
SEO: 25mm

600

METROS

200

METROS

60

METROS

2.14

2.15
3

CABOS UNIPOLARES DE COBRE


ISOLAO DE PVC
SEO: 35mm
CABOS UNIPOLARES DE COBRE
ISOLAO DE PVC
SEO: 50 mm
ELETRODUTOS

3.1

PVC RIGIDO ROSCVEL-CLASSE A


DIAMETRO: 16mm (3/8")

30

METROS

3.2

PVC RIGIDO ROSCVEL-CLASSE A


DIAMETRO: 20mm (1/2")

25

METROS

3.3

PVC RIGIDO ROSCVEL-CLASSE A


DIAMETRO: 32mm (1")

METROS

3.4

RGIDOS DE AO CARBONO ROSCVEL


DIMETRO: 20mm (1/2")

METROS

3.5

RGIDOS DE AO CARBONO ROSCVEL


DIMETRO: 25mm (3/4")

15

METROS

3.6

RGIDOS DE AO CARBONO ROSCVEL


DIMETRO: 32mm (1")

10

METROS

RGIDOS DE AO CARBONO ROSCVEL


DIMETRO: 60mm (2'')

15

METROS

DISPOSITIVOS DE PROTEO

DISPOSITIVOS DE PROTEO

4.1

DISJUNTOR TERMOMAGNTICO
DTM/TQC3415

PEA

4.2

DISJUNTOR TERMOMAGNTICO
DTM/TQC1230

PEA

4.3

DISJUNTOR TERMOMAGNTICO
DTM/TQC1235

PEA

4.4

DISJUNTOR TERMOMAGNTICO
DTM/TQC3410

PEAS

MESES

DIAS

JANEIRO

0-1

1-2

2-3

3-4

31

1.58

1.58

1.58

10.51

FEVEREIRO

28

1.58

1.58

1.58

10.51

MARCO

31

1.58

1.58

1.58

10.51

ABRIL

30

1.58

1.58

1.58

10.51

MAIO

31

1.58

1.58

1.58

10.51

JUNHO

30

1.58

1.58

1.58

10.51

JULHO

31

1.58

1.58

1.58

10.51

AGOSTO

31

1.58

1.58

1.58

10.51

SETEMBRO

30

1.58

1.58

1.58

10.51

OUTUBRO

31

1.58

1.58

1.58

10.51

NOVEMBRO

30

1.58

1.58

1.58

10.51

DEZEMBRO

31

1.58

1.58

1.58

10.51

MESES

DIAS

0-1

1-2

2-3

3-4

JANEIRO

31

1.58

1.58

1.58

10.51

FEVEREIRO

28

1.58

1.58

1.58

10.51

MARCO

31

1.58

1.58

1.58

10.51

ABRIL

30

1.58

1.58

1.58

10.51

MAIO

31

1.58

1.58

1.58

10.51

JUNHO

30

1.58

1.58

1.58

10.51

JULHO

31

1.58

1.58

1.58

10.51

AGOSTO

31

1.58

1.58

1.58

10.51

SETEMBRO

30

1.58

1.58

1.58

10.51

OUTUBRO

31

1.58

1.58

1.58

10.51

NOVEMBRO

30

1.58

1.58

1.58

10.51

DEZEMBRO

31

1.58

1.58

1.58

10.51

MESES

DIAS

0-1

1-2

2-3

3-4

JANEIRO
FEVEREIRO

31
28

1.58
1.58

1.58
1.58

1.58
1.58

10.51
10.51

MARCO
ABRIL
MAIO
JUNHO
JULHO
AGOSTO
SETEMBRO
OUTUBRO
NOVEMBRO
DEZEMBRO

31
30
31
30
31
31
30
31
30
31

1.58
1.58
1.58
1.58
1.58
1.58
1.58
1.58
1.58
1.58

Concluso

Consumo anual
2693.23

Consumo mensal

6550.91

545.91

11748.53

979.04

Tarifa Horo-sazonal azul


Tarifa Horo-sazonal verde
Tarifa convencional

1.58
1.58
1.58
1.58
1.58
1.58
1.58
1.58
1.58
1.58

1.58
1.58
1.58
1.58
1.58
1.58
1.58
1.58
1.58
1.58

10.51
10.51
10.51
10.51
10.51
10.51
10.51
10.51
10.51
10.51

224.44

Tarifa escolhida: Horo-sazona

TARIFA HORO-SAZONAL AZUL-A3a (30 A 44KV )


HORAS DO DIA(KW)
4-5

5-6

6-7

7-8

8-9

9-10

10-11

11-12

12-13

13-14

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

TARIFA HORO-SAZONAL VERDE-A3a (30 A 44KV )


HORAS DO DIA(KW)
4-5

5-6

6-7

7-8

8-9

9-10

10-11

11-12

12-13

13-14

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

10.51

5.07

2.58

10.58

11.36

10.86

10.96

2.38

19.80

3.58

TARIFA CONVENCIONAL-A3a (30 A 44KV )


HORAS DO DIA(KW)
4-5

5-6

6-7

7-8

8-9

9-10

10-11

11-12

12-13

13-14

10.51
10.51

5.07
5.07

2.58
2.58

10.58
10.58

11.36
11.36

10.86
10.86

10.96
10.96

2.38
2.38

19.80
19.80

3.58
3.58

10.51
10.51
10.51
10.51
10.51
10.51
10.51
10.51
10.51
10.51

5.07
5.07
5.07
5.07
5.07
5.07
5.07
5.07
5.07
5.07

olhida: Horo-sazonal azul

2.58
2.58
2.58
2.58
2.58
2.58
2.58
2.58
2.58
2.58

10.58
10.58
10.58
10.58
10.58
10.58
10.58
10.58
10.58
10.58

11.36
11.36
11.36
11.36
11.36
11.36
11.36
11.36
11.36
11.36

10.86
10.86
10.86
10.86
10.86
10.86
10.86
10.86
10.86
10.86

10.96
10.96
10.96
10.96
10.96
10.96
10.96
10.96
10.96
10.96

2.38
2.38
2.38
2.38
2.38
2.38
2.38
2.38
2.38
2.38

19.80
19.80
19.80
19.80
19.80
19.80
19.80
19.80
19.80
19.80

3.58
3.58
3.58
3.58
3.58
3.58
3.58
3.58
3.58
3.58

14-15

15-16

16-17

17-18

18-19

19-20

20-21

21-22

22-23

23-24

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

14-15

15-16

16-17

17-18

18-19

19-20

20-21

21-22

22-23

23-24

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

25.49

26.94

47.66

14.14

11.70

11.48

11.48

1.98

9.36

1.58

14-15

15-16

16-17

17-18

18-19

19-20

20-21

21-22

22-23

23-24

25.49
25.49

26.94
26.94

47.66
47.66

14.14
14.14

11.70
11.70

11.48
11.48

11.48
11.48

1.98
1.98

9.36
9.36

1.58
1.58

25.49
25.49
25.49
25.49
25.49
25.49
25.49
25.49
25.49
25.49

26.94
26.94
26.94
26.94
26.94
26.94
26.94
26.94
26.94
26.94

47.66
47.66
47.66
47.66
47.66
47.66
47.66
47.66
47.66
47.66

14.14
14.14
14.14
14.14
14.14
14.14
14.14
14.14
14.14
14.14

11.70
11.70
11.70
11.70
11.70
11.70
11.70
11.70
11.70
11.70

11.48
11.48
11.48
11.48
11.48
11.48
11.48
11.48
11.48
11.48

11.48
11.48
11.48
11.48
11.48
11.48
11.48
11.48
11.48
11.48

1.98
1.98
1.98
1.98
1.98
1.98
1.98
1.98
1.98
1.98

9.36
9.36
9.36
9.36
9.36
9.36
9.36
9.36
9.36
9.36

1.58
1.58
1.58
1.58
1.58
1.58
1.58
1.58
1.58
1.58

DEMANDA(MENSAL)
KW

KWh

R$/KW

R$

TOTAL(R$)
PONTA FORA DE PONTA PONTA FORA DE PONTA PONTA FORA DE PONTA

PONTA
SECO

FORA DE PONTA

MIDO

SECO

11.70

14.14

23.69

5.09

277.27

71.97

349.24

11.70

14.14

23.69

5.09

277.27

71.97

349.24

970.59

11.70

14.14

23.69

5.09

277.27

71.97

349.24

1074.59

11.70

14.14

23.69

5.09

277.27

71.97

349.24

1039.92

11.70

14.14

23.69

5.09

277.27

71.97

349.24

1074.59

597.65

11.70

14.14

23.69

5.09

277.27

71.97

349.24

1039.92

578.37

11.70

14.14

23.69

5.09

277.27

71.97

349.24

1074.59

597.65

11.70

14.14

23.69

5.09

277.27

71.97

349.24

1074.59

597.65

11.70

14.14

23.69

5.09

277.27

71.97

349.24

1039.92

578.37

11.70

14.14

23.69

5.09

277.27

71.97

349.24

1074.59

597.65

11.70

14.14

23.69

5.09

277.27

71.97

349.24

1039.92

578.37

11.70

14.14

23.69

5.09

277.27

71.97

DEMANDA ANUAL
DEMANDA MENSAL

1074.59

349.24

1074.59

4190.85
349.24

DEMANDA(MENSAL)
KW

KWh

R$/KW

R$

TOTAL(R$)
PONTA FORA DE PONTA PONTA FORA DE PONTA PONTA FORA DE PONTA

PONTA
SECO

MIDO

FORA DE PONTA
SECO

47.66

8.02

382.27

382.27

718.71

47.66

9.02

429.93

429.93

649.15

47.66

10.02

477.60

477.60

718.71

47.66

11.02

525.26

525.26

695.52

47.66

12.02

572.93

572.93

718.71

597.65

47.66

13.02

620.59

620.59

695.52

578.37

47.66

14.02

668.26

668.26

718.71

597.65

47.66

15.02

715.92

715.92

718.71

597.65

47.66

16.02

763.59

763.59

695.52

578.37

47.66

17.02

811.25

811.25

718.71

597.65

47.66

18.02

858.92

858.92

695.52

578.37

47.66

19.02

906.58

906.58

DEMANDA ANUAL
DEMANDA MENSAL

7733.11
644.43

DEMANDA(MENSAL)

718.71

CONSUMO(MENSAL)

KW

KW/R$

R$

TOTAL(R$)

KWh

R$/KWh

R$

TOTAL(R$)

47.66
47.66

24.94
24.94

1188.76
1188.76

1188.76
1188.76

8207.11
7412.87

0.12158
0.12158

997.82
901.26

997.82
901.26

47.66
47.66
47.66
47.66
47.66
47.66
47.66
47.66
47.66
47.66

24.94
24.94
24.94
24.94
24.94
24.94
24.94
24.94
24.94
24.94

1188.76
1188.76
1188.76
1188.76
1188.76
1188.76
1188.76
1188.76
1188.76
1188.76

1188.76
1188.76
1188.76
1188.76
1188.76
1188.76
1188.76
1188.76
1188.76
1188.76

DEMANDA ANUAL
DEMANDA MENSAL

14265.06
1188.76

8207.11
7942.37
8207.11
7942.37
8207.11
8207.11
7942.37
8207.11
7942.37
8207.11

0.12158
0.12158
0.12158
0.12158
0.12158
0.12158
0.12158
0.12158
0.12158
0.12158

997.82
965.63
997.82
965.63
997.82
997.82
965.63
997.82
965.63
997.82

CONSUMO ANUAL
CONSUMO MENSAL

997.82
965.63
997.82
965.63
997.82
997.82
965.63
997.82
965.63
997.82
11748.53
979.04

CONSUMO(MENSAL)
R$/KWh
FORA DE PONTA
MIDO

PONTA
SECO

R$
FORA DE PONTA

MIDO

SECO

PONTA

TOTAL(R$)
FORA DE PONTA

SECO

MIDO

SECO

MIDO

SECO

MIDO

101.71

0.00

64.83

0.00

597.65

0.17018

0.10848

0.00

539.81

0.17018

0.10848

0.00

91.87

0.00

58.56

0.00

597.65

0.17018

0.10848

0.00

101.71

0.00

64.83

0.00

578.37

0.17018

0.10848

0.00

98.43

0.00

62.74

0.00

0.18771

0.11866

201.71

0.00

70.92

0.00

272.63

0.18771

0.11866

195.20

0.00

68.63

0.00

263.83

0.18771

0.11866

201.71

0.00

70.92

0.00

272.63

0.18771

0.11866

201.71

0.00

70.92

0.00

272.63

0.18771

0.11866

195.20

0.00

68.63

0.00

263.83

0.18771

0.11866

201.71

0.00

70.92

0.00

272.63

0.18771

0.11866

195.20

0.00

68.63

0.00

263.83

0.00

101.71

0.00

64.83

597.65

0.17018

0.10848

0.00
CONSUMO ANUAL
CONSUMO MENSAL

CONSUMO(MENSAL)
R$/KWh
FORA DE PONTA
MIDO

PONTA
SECO

MIDO

R$
FORA DE PONTA

SECO

PONTA

TOTAL(R$)
FORA DE PONTA

MIDO

SECO

MIDO

SECO

MIDO

SECO

597.65

0.66869

0.10848

0.00

480.59

0.00

64.83

0.00

539.81

0.66869

0.10848

0.00

434.08

0.00

58.56

0.00

597.65

0.66869

0.10848

0.00

480.59

0.00

64.83

0.00

578.37

0.66869

0.10848

0.00

465.09

0.00

62.74

0.00

597.65

0.68622

0.11866

493.19

0.00

70.92

0.00

564.11

0.68622

0.11866

477.28

0.00

68.63

0.00

545.91

0.68622

0.11866

493.19

0.00

70.92

0.00

564.11

0.68622

0.11866

493.19

0.00

70.92

0.00

564.11

0.68622

0.11866

477.28

0.00

68.63

0.00

545.91

0.68622

0.11866

493.19

0.00

70.92

0.00

564.11

0.68622

0.11866

477.28

0.00

68.63

0.00

545.91

0.00

480.59

0.00

64.83

0.00

0.66869

0.10848

CONSUMO ANUAL
CONSUMO MENSAL

TOTAL(R$)
MIDO

R$

166.54

166.54

150.42

150.42

166.54

166.54

161.17

161.17

0.00

272.63

0.00

263.83

0.00

272.63

0.00

272.63

0.00

263.83

0.00

272.63

0.00

263.83

166.54

166.54

CONSUMO ANUAL
CONSUMO MENSAL

2693.23
224.44

TOTAL(R$)
MIDO

R$

545.42

545.42

492.64

492.64

545.42

545.42

527.83

527.83

0.00

564.11

0.00

545.91

0.00

564.11

0.00

564.11

0.00

545.91

0.00

564.11

0.00

545.91

545.42

545.42

CONSUMO ANUAL
CONSUMO MENSAL

6550.91
545.91

POSTES DE CONCRETO
Comprimento
8m
Vos da rede
60 m
Ramais de entrada 5 m
N DE POSTES
Trecho
ARMAZM
ORDENHA
IRRIGAO
GALPO
SEDE
Total

Quantidade

10
2
9
11
3
35

CLCULO DE QUEDA DE TENSO


CARGA

TRECHO
DESIGNAO

COMPRIMENTO

DISTRIBUDA NO TRECHO

ACUMULADA NO FIM DO TRECHO

TOTAL

A
Primrio
Secundrio

B
Km
100m
2.000
0.550
0.590
1.000
1.600
0.340
0.980

C
MVA
kVA
-

D
MVA
kVA
0.400
0.325
0.310
0.010
0.075
0.015
0.300

E = B(C/2+D)
MVA x Km
kVA x 100m
0.800
0.179
0.183
0.010
0.120
0.005
0.294

A-B
B-C
C-D
D-E
B - B1
C - C1
D - D1

CONDUTORES
F
N #AWG/MCM
3#4(4)
3#4(4)
3#4(4)
1#4(4)
3#4(4)
1#4(4)
3#4(4)

QUEDA DE TENSO
UNITRIA

TRECHO

TOTAL

H = ExG

0.8349
0.8349
0.8349
4.3858
0.8349
4.3858
0.8349

0.6679
0.1492
0.1527
0.0439
0.1002
0.0224
0.2455

1.5028
0.9841
0.9876
4.4297
0.9351
4.4082
1.0804