Você está na página 1de 9

Gs Refrigerante: R-134 a

1.1 Esquema Multicompresso/Multievaporao

1.2 Diagrama de Mollier

1.3 Trocadores de calor

Coeficiente de pelcula: 500 kcal/h


Coeficiente do fludo: 1000 kcal/h
TC 1
Q = M.C. T
Q= 40.000 X 0,92 X 6
Q= 220.800 kcal/h
TC 2
Q = M.C.T
Q= 60.000 X 0,96 X 8

3
Q= 460.800 kcal/h

TC 1

rea de tubulao
A= X XLXN
A = 3,1415 X 0,025 X 10 X 50
A = 39,26 m2

Tml= 16,87C

23-TEV = 1,42 (17-TEV)

4
0,42 TEV = 1,14
TEV = 2,71C
TC 2

rea de tubulao
A= X XLXN
A = 3,1415 X 0,03 X 8 X 70
A = 52,77 m2

Tml= 26,2C

24-TEV = 1,36 (16-TEV)

5
0,36 TEV = - 2,24
TEV = - 6.3C
ENTALPIAS
H1=93,99 kcal/kg
H2=94,65 kcal/kg
H3= 94,52 kcal/kg
H4= 96,08 kcal/kg
H5= 95.78 kcal/kg
H6= 97,21 kcal/kg
H7= 96,77 kcal/kg
H8= 97.94 kcal/kg
H9= 97,82 kcal/kg
H10= 100,90 kcal/kg
H11=61,38 kcal/kg
H12= 61,38 kcal/kg
H13= 53,75 kcal/kg
H14= 53,75 kcal/kg
H15= 51,10 kcal/kg
H16= 51,10 kcal/kg
H17= 48,71 kcal/kg
H18= 48,71 kcal/kg
H19= 45,84 kcal/kg
H20= 45,84 kcal/kg

ENTROPIAS
S1= S2 = 0,4148 Kcal/kg.K

TEMPERATURA DE -10C

S3= S4 = 0,4142 Kcal/kg.K

TEMPERATURA DE -6,3C

S5= S6 = 0,4129 Kcal/kg.K

TEMPERATURA DE 2,71C

S7= S8 = 0,4121 Kcal/kg.K

TEMPERATURA DE 10C

S9= S10 = 0,4113 Kcal/kg.K

TEMPERATURA DE 18C

CAPACIDADE DOS EVAPORADORES


QRF1 = 1.512.000 kcal/h ( 500 TR)
QRF2 = 362.880 kcal/h (120 TR)
QRF3 = 220.800 kcal/h (73 TR)
QRF4 = 460.800 kcal/h( 152 TR)
QRF5 = 302.400 kcal/h (100 TR)
QRF1 = M12A x ( H9 H 12)

M12A = 41.492 kg/h


QRF2 = M14A x ( H7 H 14)

M14A = 8.435 kg/h


QRF3 = M16A x ( H5 H 16)

M16A = 4.942 kg/h

7
QRF4 = M18A x ( H3 H 18)

M18A = 10.074 kg/h


QRF5 = M1 x ( H1 H 20)

M1 = 6280 kg/h

BALANO DOS SISTEMAS

Primeiro balano - Congelados


M1 = M2 = M19
M3 = M18A + M18B
M18A .H8 + M18B.H18 + M2H2 + QRF4 = M19.H19 + M3.H3
(10.074X48,71)+ 48,71M18B + (6280 X 94,65) + 460.800 = 6280 X 45,84 +
(M18A +M18B).94,52
94,52.M18B 48,71.M18B = 1.545.906 1.240.069
M18B = 6021Kg/h
Segundo balano TC2
M3 = M4= M17
M5 = M16A + M16B
M16A .H16 + M16B.H16 + M4H4 + QRF3= M17.H17 + M5.H5
(4.942X51,1)+51,1M16B + (16095X 96,08)+ 220.800= 16095X 48,71 + (M16A
+M16B).95,78

8
95,78M16B 51,1M16B = 2.019.990- 1.257331
M16B = 17069 Kg/h
Terceiro Balano TC 1
M5 = M6 = M15
M7 = M14A + M14B
M14A.H14 + M14B.H14+ M6H6+ QRF2= M15.H15 + M7.H7
(8.435X53,75)+53,75.M14B+(22011X97,21)+362.880=22011X51,1+
(M14A+M14B).96,77
96,77M14B 53,75M14B= 2.955.950- 1.941.077
M14B= 23.592 Kg/h
Quarto Balano Climatizao
M8 = M7 = M13
M9 = M12A + M12B
M12A.H12 + M12B.H12+ M8H8+ QRF1= M13.H13 + M9.H9
(41.492X61,38)+61,38.M12B+(32.072X97,94)+1.512.000=32072X53,75+
(M12A+M12B).97,82
97,82M12B 61,38M12B= 7.199.910- 5.782.617
M12B= 38.894 Kg/h
TRABALHOS DE COMPRESSO - WCP
WCP1 = M9 .( H10-H9)
WCP1 = 80.386.( 100,9-97,82)
WCP1 = 247.588 Kcal/h ou 386 HP
WCP2 = M7 .( H8-H7)
WCP2 = 32.072.( 97,94-96,77)

9
WCP2 = 37.524 Kcal/h ou 58 HP
WCP3 = M5 .( H6-H5)
WCP3 = 22.011.( 97,21-95,78)
WCP3 = 31.475 Kcal/h ou 49 HP
WCP4 = M3 .( H4-H3)
WCP4 = 22.011.( 96,08-94,52)
WCP4 = 25.108 Kcal/h ou 39 HP
WCP5 = M1 .( H2-H1)
WCP5 = 22.011.( 94,65-93,99)
WCP5 = 4.144 Kcal/h ou 6,5 HP
CONDENSAO
Fluxo de calor cedido pelo sistema:

COEFICIENTE DE EFICINCIA

Você também pode gostar