COLLING FAN SELECTION FOR PANEL

DESCRIPTION TEPMERATURE DIFFERENT Maximum ambient temperature Desired interior temperature Temperature differential TOTAL INSTALL POWER Bus bar Semi-conductor Realy Transformers Installed stray power AIR CONSTANT Air constant VALUE UNITS 50 k 323 k 273 k

150 20 150 75 395 w

3 3.16 m K/Wh

VOLUME FLOW Required volume flow in m^3/h Required volume flow in CFM

4.572161172 m^3/h 2.691073478 CFM

Air Change Method


DESCRIPTION PANEL SIZE Length Width Height Volume of panel REQUIRED AIR CHANGE Airchanges per hour VOLUME FLOW Fan Requirement Fan Requirement VALUE 3 0.3 3 2.7 UNITS m m m m^3

60 /h

162 m^3/h 95.349636 CFM

TOTAL CFM

98.04070948

INLET AND OUTLET SIZE

V = 4005 x Sqrt(P)

V = 4005 x Sqrt(0.75)

REMARKS

The components installed in enclosures (e.g. transformers, relays, semi-conductors, bus bars, etc.) generate heat when in operation. Standard Air Conditions Air density,for many applications, is taken at standard conditions (70F at 29.92" of mercury).

CFM = (watts x 3.16) / Temp. diff 1m^3/hour = 0.588578 CFM

REMARKS

It means 1 min one changes

1m^3/hour = 0.588578 CFM

V = 4005 x Sqrt(P)

V = 4005 x Sqrt(0.75)

Ft/Min.