Escolar Documentos
Profissional Documentos
Cultura Documentos
2 or 4 Lamp T8 or T12
CONSTRUCTION/FINISH
Pattern 12 bottom prisms with interior linear side wall prisms for maximum cleanliness and light control. Tapered shape provides a modern appearance. Full steel end plates feature embosses for improved aesthetics. 100% virgin acrylic lens hinges from either side for easy maintenance. Housing is multi-stage phosphate treated for maximum corrosion resistance and finish coat is high reflectance baked white enamel. Multiple knockouts accomodate a variety of mounting methods. Heavy duty channel of code gauge die formed steel. For surface or stem mounting.
ELECTRICAL
UL listed for direct mounting on low density ceilings and damp locations. Class P, HPF ballasts comply with E Federal Ballast Law (Public Law 100-357,1988). Lampholders may be individually replaced or rewired. Self-contained fluorescent emergency power packs can be incorporated, UL listed for dry locations.
CATALOG NUMBER
OW
PRODUCT FAMILY OW Wraparound
W
NO. OF LAMPS PER CROSS SECTION
(not included)
VOLTAGE
2 4
WIDTH W - Wide
OPTIONS 1/2 One 2-lamp ballast (electronic or non-standard) 1/4 One 4-lamp ballast (electronic or non-standard) 2/2 Two 2-lamp ballasts (electronic or non-standard) EB Electronic ballast, <20% THD EB10I Electronic ballast, instant start, <10% THD EB10R Electronic ballast, program rapid start, <10% THD E1 DEB-1 emerg. ballast, 350-450 lumens, UL dry loc. E7 DEB-7 emerg. ballast, 600-700 lumens, UL dry loc. E5 DEB-5 emerg. ballast, 1100-1400 lumens, UL dry loc. E5ST DEB-5ST emerg. ballast w/self test, 1100-1400 lumens, UL dry loc. GLR# Fusing, fast blow (# = number of ballasts) LPT735 Installed lamps, 70+ CRI, 3500K See Section 1600-OA for Option Information. See Page 950-SS for Mounting Hardware.
JOB INFORMATION
1027.1-WP
OW WIDE WRAPAROUND
DIMENSIONS
13-7/8" (352mm)
2-11/16" (68mm)
13-7/8" (352mm)
2-11/16" (68mm)
(1219 mm)
CATALOG # OWW 432-1/4-EB LAMPS = F32 T8 INPUT WATTS = 107 TEST # ITL41980 S/MH=1.4 BALLAST = ELECTRONIC BALLAST FACTOR = .91 COMPARATIVE YEARLY LIGHTING ENERGY COST PER 1000 LUMENS = $3.29 BASED ON 3000 HRS. AND $.08 PER KWH.
PHOTOMETRIC DATA
CANDLEPOWER
Angle
0 5 15 25 35 45 55 65 75 85 95 105 115 125 135 145 155 165 175
LER = 73
FIXTURE EFFICIENCY= 74.1% COEFFICIENT OF UTILIZATION
pfc pcc pw RCR 0 1 2 3 4 5 6 7 8 9 10 20 80 70 50 30 86 80 72 66 86 76 67 58 86 72 61 53 70 70 50 30 83 77 69 64 83 73 65 56 83 70 59 52 50 50 30 79 69 60 54 79 67 57 50
End
2848 2852 2761 2567 2281 1875 1144 555 276 98 1 2 6 9 11 12 12 11 9
Cross
2848 2840 2818 2741 2567 2248 1267 739 528 379 311 270 202 142 88 64 47 28 15
80-50-20 Reflectances (Ceiling-Wall-Floor) LLF = 0.75 2900 Lumens/Lamp very clean Room width divided by room height = 5 or more, 2 or 1
Fixture Size & # of Lamps 4' 4- Lamp Approx. Area (sq. ft.) per Fixture Room Width Room Height = 10 ft-c 30 ft-c 50 ft-c 70 ft-c 100 ft-c 5 2 1 112 133 92 67 95 65 48 66 46 34
60 52 46 56 46 40 52 41 35 47 45 41 39 38 34 32 29 32 28 26 23
58 51 45 54 46 40 50 40 34 46 42 40 38 38 34 30 28 32 28 26 23
48 44 44 38 40 34 35 33 29 28 30 28 25 23
TYPICAL V.C.P.s
Room Size
30x30 40x40 60x30 60x60 100x100
LIGHT DISTRIBUTION
DEGREES LUMENS % LAMP % FIXTURE 0-30 0-40 0-60 0-90 90-180 0-180 2289 3817 6596 7968 631 8599 19.7 32.9 56.9 68.7 5.4 74.1 26.6 44.4 76.7 92.7 7.3 100.0
LLF = .75 LLF = LIGHT LOSS FACTOR LLF = LDD X LLD X BF LDD = VERY CLEAN 0.94 CLEAN 0.90 LLD = 0.88 @ 40% RATED LAMP LIFE BF = 0.91 ELECTRONIC BALLAST & T8 LAMP (RELAMP AT 70% LAMP LIFE)
1027.1-WP
DAY-BRITE LIGHTING www.daybritelighting.com 776 South Green Street Tupelo, Mississippi 38804 PH: (662) 842-7212 FAX: (662) 841-5501 CANADIAN DIVISION 189 Bullock Drive Markham, Ontario L3P 1W4 PH: (905) 294-9570 FAX: (905) 294-9811
JUNE 2010 DAY-BRITE LIGHTING DAY-BRITE RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.