Specifications
Temperature & Pressure Relief Valves Each hot water storage heater shall be equipped with an automatic temperature and pressure relief valve to protect the heater from excessive pressure and excessive temperature. The device shall be certified as meeting the requirements of ASME low pressure heating boiler code and ANSI Z21.22. The BTU discharge capacity of the device shall be in excess of the BTU input rating of the heater. The device shall be constructed using Lead Free* materials. Lead Free* automatic re-seating T&P relief valves shall comply with state codes and standards, where applicable, requiring reduced lead content. The T&P valve shall be a Watts Series LF40, LF140, LFN240 or LF340.
Features
Lead Free cast body Non-mechanical seat-to-disc alignment Tamper-resistant bonnet screws Series 34" LF40 and LF140 feature a unique thermostat with a special thermo-bonded coating Series 1" LF140 are furnished with stainless steel thermostat tube Series LFN240 and LF340 are hot furnished with stainless steel thermostat tube
Following installation, the valve lever MUST be operated AT LEAST ONCE A YEAR by the water heater owner to ensure that the waterways are clear. Certain naturally occurring mineral deposits may adhere to the valve, blocking waterways, rendering it inoperative. When the lever is operated, Hot water will discharge if the waterways are clear. Precautions must be taken to avoid personal injury from contact with hot water and to avoid property damage.
IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES FOR LOCAL INSTALLATION REQUIREMENTS
* The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Standards
ASME Rated, ANSI Z21.22, Design certified and listed by CSA, National Board of B&PVI to Section IV of the ASME B&PV code and meet current FHA requirements and ANSI Z21.22 in addition to Military Spec. MIL-V136-12D, Type I.
Pressure Temperature
Temperature relief 210F (99C) Pressure range 75 150psi (5.2 10.3 bar) Standard setting 75, 100, 125 and 150psi (5.2, 6.9, 8.6 and 10.3 bar)
General Recommendations
For Heaters with Direct Top Tapping
Use standard or extra length extension thermostat. For gas, electric or oil-fired storage water heaters between 180,000 to 205,000 BTU/Hr. rating: Use 34" (20mm) Series LF40, LF140 tested under ANSI Z21.22 with ratings as certified and listed by CSA. For gas or oil-fired storage water heaters between 205,000 and 730,000 BTU/Hr. rating and for compliance with applicable water heater labeling requirements: Use 1" (25mm) LF40, LF140, LFN240 Series tested under ANSI Z21.22 with ratings as certified and listed by CSA. For installations of gas or oil-fired hot water supply boilers over 730,000 BTU/Hr. output heating domestic water and for steam coil storage water heaters: Use Series LF340, LF342 tested under ANSI Z21.22 with rating as certified and listed by CSA.
Thermostat Inlet X Length (in.) Outlet (Below Inlet Model (in.) thread)
**ASME Pressure Steam Rating BTU/HR @75psi set pres. @100psi set pres. @125psi set pres. @150psi set pres.
34 M x 34 F LF40L-3 3 558 258 134 180,000 777,600 997,600 1,217,600 1,437,600 3 3 LF40XL-5 4 M x 4 F 5 558 258 134 205,000 777,600 997,600 1,217,600 1,437,600 34 M x 34 F LF40XL-8 8 558 258 134 205,000 777,600 997,600 1,217,600 1,437,600 34 F x 34 F LF140S-3 3 558 258 134 180,000 777,600 997,600 1,217,600 1,437,600 3 3 LF140X-5 4 F x 4 F 5 558 258 134 205,000 777,600 997,600 1,217,600 1,437,600 3 3 LF140X-8 4 F x 4 F 8 558 258 134 205,000 777,600 997,600 1,217,600 1,437,600 LF40L-2 1M x 1F 2 614 234 214 450,000 1,155,000 1,481,000 1,808,000 2,134,000 LF40XL-4 1M x 1F 4 614 234 214 500,000 1,155,000 1,481,000 1,808,000 2,134,000 LF40XL-7 1M x 1F 7 614 234 214 500,000 1,155,000 1,481,000 1,808,000 2,134,000 *LF140S-3 1F x 1F 3 512 3 214 570,000 1,670,000 2,140,000 2,610,000 3,085,000 *LF140X-6 1F x 1F 6 512 3 214 670,000 1,670,000 2,140,000 2,610,000 3,085,000 *LF140X-9 1F x 1F 9 512 3 214 670,000 1,670,000 2,140,000 2,610,000 3,085,000 *LFN240X-6 1F x 1F 6 658 338 234 730,000 2,195,000 2,817,000 3,438,000 4,059,000 *LFN240X-9 1F x 1F 9 658 338 234 730,000 2,195,000 2,817,000 3,438,000 4,059,000 *LFN241X-5 114 M x 1F 5 658 338 234 730,000 2,195,000 2,817,000 3,438,000 4,059,000 *LFN241X-8 114 M x 1F 8 658 338 234 730,000 2,195,000 2,817,000 3,438,000 4,059,000 1 1 *LF340-3 1 2 F x 1 2 F 3 934 412 7 1,150,000 3,450,000 4,426,000 5,403,000 6,379,000 1 1 *LF340X-8 1 2 F x 1 2 F 8 934 412 8 1,150,000 3,450,000 4,426,000 5,403,000 6,379,000 *LF342-3 2 M x 112 F 3 934 412 7 1,150,000 3,450,000 4,426,000 5,403,000 6,379,000 *LF342X-8 2 M x 112 F 8 934 412 8 1,150,000 3,450,000 4,426,000 5,403,000 6,379,000 *Furnished with stainless steel thermostat tube. M = Male F = Female **ASME capacities are steam pressure ratings and do not reflect the CSA temperature relieving capacity of the valves for selection purposes. LFLL40XL and LFLLL40XL valves with extended inlet shanks should be used for water heaters that have extra thick insulation, Ask for ES-LFLL/LLL40XL.
Temperature and Pressure Relief Valves should be inspected AT LEAST ONCE EVERY TWO TO FOUR YEARS, and replaced, if necessary, by a licensed plumbing contractor or qualified service technician, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions can only be detected if the valve and its components are physically removed and inspected. Do not attempt to conduct an inspection on your own. Contact your plumbing contractor for a reinspection to ensure continuing safety.
USA: Tel: (978) 688-1811 Fax: (978) 794-1848 www.watts.com Canada: Tel: (905) 332-4090 Fax: (905) 332-7068 www.watts.ca