Reference
Calculation
Output
Pv = = Pv =
Cl. 3.12.8.4
Ultimate anchorage Bond Stress Fbu = = Fbu = 0.2 1.3 x sqrt(40) N/mm2 > 0.67 Safe
0.28
75
50 75 100 75
Project
ASCON
Rev 1 Tel: Fax:
Reference
Calculation
Output
TABLE OF CONTENTS
S.NO DESCRIPTION P. NO
DESIGN ABSTRACT
LOAD CALCULATION
32
DESIGN CHECK
51
DEFLECTION CHECK
54
CONNECTIONS DESIGN
55
CONCLUSION
70
Project
ASCON
Rev 1 Tel: Fax:
Reference
Calculation
Output
1. DESIGN ABSTRACT
END MEMBERS
C- Section 80x60x6
INTERMEDIATE MEMBERS
EA 40x40x4
CONNECTIONS
The structural steel members, connecting cleat angles and bolts used in this project are all of SS316 stainless steel.
Project
ASCON
Rev 1 Tel: Fax:
Reference
Calculation
Output
a) BS 5950 - Part 1: 2000 - Structural use of steelwork in building b) BS 6399 - Part- 1 & 2: 1997 - Loading for Buildings c) UBC 1997 - Uniform Building Code
2. Material a) Structural Steel - SS 316 of BS EN 10088 b) Welding Electrodes E7018 to BS 639 (Minimum Yield strength 355 N/sq.mm)
3. Loads
a) Dead Load BS648 - 1964i) Weight of the Plywood P-31 ii) Weight of 18mm Thick Plywood = = 0.70 Kg/ m2/ mm
18.00 Kg/ m2
b) Live Load UBC 1997 Cl.1611.5 Table - 16B In the absence of any imposed (horizontal) live load Minimum Horizontal Live load, as per UBC's requirement = = 5 x 0.0479 0.24 kN/ sq.mm
c) Wind Load
Wind Load intensity calculation will be in accordance with BS 6399 -2: 1997
AMG-BCH-001
= =
Project
ASCON
Rev 1 Tel: Fax:
Reference
Calculation Basic Assumptions 1. Assume basic Wind load = 2. D / H > 1 3. Rectangular plan building 25 m/sec
Output
Where -
Vb = Sa Sd Ss Sp -
Therefore,
Vs = Vs =
25 X 1 X 1 X 1 X 1 25 m/s
cl.2.2.3.1
Ve =
Vs X Sb
where - Sb is the terrain and building factor Assume that site is in town and extends 2 km upwind from the site and interpolating the values given in table -4, Sb for He = 11.15m we get Sb = Table - 4 Therefore = Ve = Ve = 1.73 + [(1.85 - 1.73) / (15 - 10)] X (11.15 - 10) 1.76 25 X 1.76 44 m/s
Dynamic Pressure
qs = = qs =
Pressure Coefficients External Pressure Coefficients ( Cpe) External Wall pressure coefficients due to wind acting perpendicular to the wall cl.2.4 Table -5 assuming D / H > 1 External Wall pressure coefficient Cpe Wind ward Lee ward = = + 0.85 0.50
Project
ASCON
Rev 1 Tel: Fax:
Reference
Calculation
Output
cl.2.1.3.1
Pe =
qs Cpe Ca
Where - qs is dynamic pressure - Cpe is external pressure coefficient Ca - is size factor for external pressure derived in cl 2.1.3.4
cl. 2. 1. 3. 4 Figure - 4
For all individual structural components, cladding units and their fixings, take a =5. For a = 5, Ca = 1 Therefore, External surface pressure in wind ward direction e = P Pe = 1.187 X 0.85 X 1 1.00 kN/sq.mm
In Leeward direction
Pe = Pe =
Cl. 2.6.1.2
For enclosed building, internal pressure coefficient should be taken as either - 0.3 or + 0.2 which ever gives large net pressure coefficient across the wall Take Cpi = - 0.3 Ca = 1 (same as above)
= =
= =
1.36 0.23
kN/sq.mm kN/sq.mm
(- 0.59) - (-0.36)
highest of the above is 1.36 kN/sq.mm Take Wind load = 1.36 kN/sq.mm
e) Earth Quake Load UBC 1997 Cl. 1632.2 The total Lateral Seismic Force Fp = [(ap. Ca . Ip / Rp) (1+ 3 (hx/hr)]Wp
As per DM's recommendation, earth quake load has been calculated for seismic Zone 2A of UBC 1997 = = = = 1.00 3.00 11.50 m 11.50 m
Table 16 - O ap - amplification factor Table 16 - O Rp - Component response modification factor Table 16 - O hr - The structure roof elevation with respect to grade hx - Average mid height Assume soil profile type as Type - Se
Table 16 - Q For seismic zone 2A and soil type Se, we get, Table 16 - K Ip - Seismic importance factor
Ca =
0.18
Project
ASCON
Rev 1 Tel: Fax:
Reference
Output
Therefore Fp
= =
Where Wp = Mass of the structure = self weight of the structural frame + stone cladding
0.16 + 1.02
1.18
kN/ sq.m
( Assume Self weight of the frame as 0.16 kN/sq.m) Fp = Fp = 0.214 x 1.18 0.252 kN /sq.m
The above load will be shared by two vertical members which are spaced apart by 0.5m
1.02 x1.0 / 2
0.51
kN/m
Total Load
0.51
kN/m
iii) Self weight of the structural steel frame This will be generated using the self weight load generator function within STAAD Pro model
b) Live Load Horizontal Live Load intensity Load in X direction ( only one member faces X direction) LLX = = = 0.24 0.12 0.12 kN/m kN / sq.mm
c)
= = =
kN/sq.mm
kN/m
(ii) Wind Load in Z direction Gap between brick wall and stone cladding WLZ = = 0 m 0.272 kN/m
Project
ASCON
Rev 1 Tel: Fax:
Reference
Calculation
Output
c)
0.252 kN / sq.m
The above load will be applied as UDL on each vertical member in both X and Z direction Earth quake load intensity on each member in each direction ELX / ELZ Take ELX / ELZ = = 0.252 X 1.0/2 = 0.17 kN/m 0.126 kN/m
LOAD COMBINATIONS a) load combinations for serviceability checks UBC 1997 Cl. 1612.3 Combination 21 = Combination 22 = Combination 23 = Combination 24 = DL + LL DL + 0.8 LLX + 0.8 WLX DL + 0.8 LLX + 0.8 WLZ DL + 0.8 LLX - 0.8 WLZ
b) Load combinations for ULS check BS 5950 -2 Load combination 30 UBC 1997 Load combination 31 = = = = = = = = = 1.4 DL + 1.6 LLX 1.2 DL + 1.2 LL + 1.2 WLX 1.2 DL + 1.2 LL + 1.2 WLZ 1.2 DL + 1.2 LL - 1.2 WLZ 1.2 DL + 1.2 LL + 1.0 ELX 1.2 DL + 1.2 LL + 1.0 ELZ 1.2 DL + 1.2 LL - 1.0 ELZ 0.9 DL + ELX 0.9 DL + ELZ 0.9 DL - ELZ
Cl. 1612.2.1 Load combination 32 Eqn 12 -5 & 6Load combination 33 Load combination 34 Load combination 35 Load combination 36 Load combination 37 Load combination 38 Load combination 39
Project
ASCON
Rev 1 Tel: Fax:
Reference
Calculation
Output
Project
ASCON
Rev 1 Tel: Fax:
Reference
Calculation
Output
The section capacity calculations are in accordance with BS 5950 Part-2: 2000
Project
ASCON
Rev 1 Tel: Fax:
Reference
Calculation
Output
6. DESIGN CHECKS
Since all the structural member used here are of grade SS316, STAAD Pro doesn't have the provision to carry out design checks for Structural members of this grade. Therefore design checks were carried out by manual calculations.
All the design checks were in accordance with BS 5950 -1: 2000's requirements.
Project
ASCON
Rev 1 Tel: Fax:
Reference
Calculation
Output
7. DEFLECTION CHECK
BS5950-1:2000 Maximum allowable deflection Table - 8 Vertical Member = span / 300
Unrestrained length of the member for deflection along X - axis Allowable deflection along X - axis
LX = DX = =
mm mm < 2.4
Sheet -
Project
ASCON
Rev 1 Tel: Fax:
Reference
Calculation
Unrestrained length of the member for deflection along Z - axis Allowable deflection along X - axis
LZ = DZ = =
mm
Sheet -
mm <
4.8
Hence O.K.
9. CONCLUSION
Design checks for all the structural members had been carried out and they all found to meet BS 5950 requirements
Deflection check carried out for all structural steel members under service load conditions meets