Jail and Prison
Housing Units
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
SEPTEMBER/OCTOBER 2005
PSDMAGAZINE.ORG
Continuing Education
INTRODUCTION
The objective of this chapter is to help the designer under-
standanddealwiththeproblemsofdesigningwaterheating
systemsforjailandprisonhousingunits.Itisimportantthat
thedesignerrecognizethateachbuildingisuniqueandwork
closelywiththeowner,architect,andgovernmentauthorities
todeterminehowabuildingwilloperate.Abuildingsopera-
tion will affect when and for how long the peak hot water
demandwilloccur.
The first part of this chapter discusses generally some of
the design criteria and areas of special concern involved in
designingforjailandprisonhousingunits.Thesecondpart
givestwopracticalexamplesofsizingmethodology,onefor
jailsandoneforprisons.
GENERAL
The design criteria used to design hot water systems
forjailhousingunitsdifferfromthoseusedforprisonhous-
ingunits.Thisdifferenceisduetothefactthatthefacilities
areusedfordifferentpurposes.Jailsareusedprimarily
to house people awaiting trial or serving short sentences.
Prisonsareusedtohouseconvictedcriminalsservinglong
prisonterms.Thisdifferenceaffectstheprisonersdailyrou-
tines,which,inturn,determinewhenthefacilitiespeakhot
waterdemandsoccur.
Itisrequiredthathotwatertemperaturefortheshowersand
lavatoriesinjailsandprisonsbelimitedtobetween100and
110F(38and43C).Thistemperaturerangehasbeenestab-
lishedtopreventinmatesfromusinghotwaterasaweapon.
1
0.61=0.08L/secwillbe60Chotwater)
8inmates3.5min=28minofwaterflowingpershower
duringthepeakhour
6pods3showersperpod=18showerstotal
18showers28min=504min
504min1.53gpm=771.12gal140Fhotwaterper
peakhourdemand
(504min
0.10L/sec
60sec/min=3024L60Chot
waterperpeakhourdemand)
Atthistimeajudgmentwillhavetobemadebythedesigner
astowhetherornottheauxiliaryequipmentwillbeoperating
duringthepeakhour.Forthisexample,wewillassumeitwill
not.
Auxiliary Equipment Demand
Doortypedishwasherwithinternalheater=69gph
(261.17L/h)
Singlecompartmentsink=30gph(113.55L/h)
Clotheswashingmachines,1perpod6pods=6
62loads@20gal/load=240gph
(6
2loads@75.7L/load=908.40L/h)
Auxiliaryequipmentdemandfor140Fwater=339gph
(Auxiliaryequipmentdemandfor60Cwater=1283.12
L/h)
Assuming that operation of the auxiliary equipment does
not coincide with the peak hour demand, sizing the heater
and storage tank to handle the additional load will not be
necessary. The heater size required for inmate showering is
morethantwicethesizeneededfortheauxiliaryequipment
demand.
Recommendation
Heater sizing
Twoheatersshouldbeselected,eachsizedtoservebetween
60 and 100% of the total demand. In prison housing units
some redundancy in the water heating system is necessary.
Thelevelofredundancyshouldbediscussedwiththefacilitys
owners.
Storage tank sizing
Ifthewaterheaterissizedtomeettherecoveryrequiredto
handle the peak shower demand, the storage tank may be
sized to handle approximately 50% of the shower demand
during the period of peak use. The storage tank should be
large enough to prevent the heater from cycling on and off
more than four times per hour during off-peak hours. This
requirementnecessitatesfindingabalancebetweenexcessive
tanksizeandshortcycling.
Calculation
771.12gph0.50=385.6gal
(2.93m
3
/h
0.50=1.47m
3
/h)
385.6
=481.6galstoragetanksize
0.80
[
1470L
=1837.5Lstoragetanksize
]
0.80
Theauxiliaryequipmentdemandof339gph(1283.12L/h)
willhavethegreatestinfluenceontheamountofcyclingdone
bytheheaterduringoff-peakhours.
339gph
=5.56gpmaverageflowof140Fwater
60
[
1283.12L/h
=0.36L/secaverageflowof60Cwater
]
60
60
5.56gpm15min=83.4gal
(0.36L/sec
60sec/min
15min=324L)
83.4
=104.25galstorage
0.80
[
324L
=405Lstorage
]
0.80
The selected size of a 481.6-gal (1837.5-L) storage tank is
morethanadequatetomeetthisdemand.
PRISON EXAMPLE
This is an example of a housing facility for 384 inmates. It
hasfourwings(96inmatesperwing)andeachwinghasfour
stories(24inmatesperwingperstory).Acentralkitchenand
laundryarelocatedinaseparatebuilding.Showerareasare
providedoneveryfloorofeverywing,andeachoftheseareas
hasthreeshowerheads.
Design Criteria and Assumptions
1. Inmatelavatoriesandshowerswillbesuppliedwith105F
(41C)circulatedhotwater.Showersaretohave2.5gpm
(0.16L/sec)flowrestrictorsandlavatories2.0gpm(0.13
L/sec)flowrestrictors.
2. Therewillbeseparatesystemsforthekitchenandlaun-
dryareas.
3. Thewatertemperatureforthelaundryareawillbe180F
(82C)andforthekitchenarea140F(60C),plusthere
willbeaseparateloopof105F(41C)waterforthehand
washinglavatoriesandtoiletslocatedinthekitchenarea.
4. Waterat140F(60C)willbesuppliedtothedishwasher.
Thedishwasherwillhaveaseparateboosterheaterto
raisewatertemperaturetothe180F(82C)requiredfor
thefinalrinsecycle.
5. Thestoragetankcapacityvariesconsiderablyfrom
0%forinstantaneousheaterstomorethan100%.Check
Reprinted from Domestic Water Heating Design Manual, 2nd ed. 2003. Chicago: American Society of Plumbing Engineers. Chapter 9, Jail
and Prison Housing Units (pp. 179-188). 2003, American Society of Plumbing Engineers.
Continuing Education: Jail and Prison Housing Units
5 PlumbingSystems&Design Sept/Oct 2005
todetermineiftheownerhasapreference.Remember,
mostownersalreadyoperateexistingjailsorprisons;they
mayhaveestablisheddesignparameters.Theinitialcost
ofequipment,theunitperformance,andoperatingcosts
arealsofactorstobeconsideredwhensizingthestorage
tank.
6. Lookforadditionalsupportfacilities,suchasthebarber
shop,pantries,oranemergencymedicalclinic.
7. Althoughoperatinghoursforthelaundryareaaregener-
allyfrom8:00A.M.to5:00P.M.,reviewoperationaltimes
andscheduleswiththeowner.
8. Sourcesofheat:Theselectionofsteam,naturalgas,or
electricitywillhaveanenormousimpactonthetypeof
heaterandonenergyconsumption.
Note:Acentralsteamgenerationplantmayfavoran
instan-taneoustypesteam-to-hot-waterconverterwith
minimumhotwaterstorageforsurges.Remember,redun-
dancyinheatersisalwaysrequiredforjailsandprisonsto
allowforproblemscreatedbyinmates.Thecostofgen-
eratinganddistributingsteamisalsoafactortobeconsid-
ered.
9. Themethodtouseforsizingthewaterheaterandstorage
tankmaybedeterminedbytheowner/operatorofthe
facility.
10.Oneinmatepercellequals384inmates.Aquestionthat
shouldbeaskediswhethertheownerplanstoexpandin
thefuturebyputtingmorethanoneinmateineachcell.
Questions
1. Willtheinmatesberequiredtoshowerataspecifictime?
No
2. Willtheshowerdurationperinmatebelimitedordo
inmateshavecontroloverwhentheyshower?
Showersarelimitedto7minperinmate,with3.5min
ofwaterusagepershower.
3. Willallofthecellpodsreleasetheirinmatesfor
showeringwithinthesamehour?
Yes.(Thismeansthatthedesignmustaccommodatea
1-hrecoveryperiod.)
4. Doesthefacilityanticipatedoublebunkingtheinmates
noworinthefuture?
No
5. Doesthefacilityhaveawork-releaseprogram?
Yes
6. Whatisthetimeallocatedforthework-releaseinmates
toshowerpriortoleavingfortheirdutiesinthework
releaseprogram?
Onehour,atthesameapproximatetimeastheother
inmates.
Calculations for Inmate Housing Units
Refertothecalculationsdoneforthejailexampleforthemeth-
odology for determining the 1.53 gpm (0.1 L/sec) flow per
showerheadandtheoperationtimeof28minpershower.
48showers28min=1344min
1344min1.53gpm=2056galof140Fhotwaterfor
peakhourdemand
(1344min
0.096L/sec
60sec/min=7741.44L/hof60C
hotwaterforpeakhourdemand)
Storage Tank Sizing
Inthisexample,inmatelavatorieswillhavetheonlyimpacton
tanksizingbecausethekitchenandlaundrywillhaveseparate
systems.
If the water heater is sized to meet the recovery required
tohandlethepeakshowerdemand,thestoragetankmaybe
sized to handle approximately 50% of the shower demand
during the period of peak use. The storage tank should be
large enough to prevent the heater from cycling on and off
more than four times per hour during off-peak hours. This
requirementnecessitatesfindingabalancebetweenexcessive
tanksizeandshortcycling.
Calculation
2056gph0.50=1028gal140Fhotwater
(7.74m
3
/h
0.50=3.87m
3
60Chotwater)
1028gal
=1285galstoragetanksize
0.80eff.
[
3870L
=4837.5Lstoragetanksize
]
0.80eff.
Kitchen Considerations
1. Theitemthathasthegreatesteffectonhotwaterdemand
isthedishwasher.Somecentralkitchensdonothave
diningareas,inwhichcaseallmealsareshippedtothe
housingunitsinbulkfordistributionandthedishwashers
areinthehousingunits.
2. Thetemperatureofthehotwatergoingtokitchenlavato-
riesshouldnotexceed110F(43C)forsafetyreasons.
3. Checktoseeifthedishwasherhasaboosterheater
anddeterminethetypeofenergyused(steamorelectric-
ity).Thisinformationwillhelpyoudecidewhetherornot
togenerate180F(82C)water.
Note:Somedishwashersonthemarketusechemicals
fordisinfecting,thusthehigherwatertemperatureisnot
required.
4. Afterdishwashers,compartmentsinksarethenextlargest
userof140F(60C)hotwater.Thehighertemperatureis
requiredtocutthroughgreaseonpotsandpans.Some
three-compartmentsinkshaveboosterheatersintherinse
tanktomaintainthehighertemperature.
5. Otherkitchenitemsthatusehotwateraretheprerinsefor
thedishwasher,thevegetablesinks,andthecartwash-
downhosebibs.
6. Alwayscheckthekitchenconsultantsplansforhotwater
requirements.
7. RefertotheHospitalschapterforadditionalinformation
onkitchens.
Laundry Considerations
1. Reviewthelaundryconsultantsplansanddeterminethe
typeofwashingmachine/extractorused.Prisonlaun-
driesaresimilartohospitallaundriesinthattheyprocess
sheets,pillowcases,anduniforms.Thesizeandnumber
Sept/Oct 2005 PlumbingSystems&Design 5
of machines are normally decided by the owner or the
consultant.
2. Inmates each generate about 30 lb (13.61 kg) of laundry a
week. This consists of 1 pillowcase, 2 sheets, 1 towel, and
uniforms.
3. Additionally, prison laundries usually handle the uniforms
of the correctional officers.
4. Sometimes prison laundries do laundry for outside hospi-
tals as a prison industry.
5. Consider the feasibility of a heat recovery system that uses
the wash-water discharge. The laundry consultant can
probably advise you about this.
6. Laundry equipment suppliers are the only reliable source
of information on the hot water demands and required
temperaures of their washers. They can tell you how
many gallons (liters) of water the machines require and
the maximum number of cycles per hour they will oper-
ate.
7. Washers demand their hot water fast. It is not unusual for
a 2-in. (DN50) hot water line to be connected to the larger
washers. Therefore, larger than normal storage capacity is
needed to handle the surges in hot water demand. One
rule of thumb is to provide 75% of the maximum hourly
demand in storage; dont provide less than 50% of that
amount.
8. In 1992 a new federal law (Bloodborne Pathogen) was
passed to protect workers against the human immunodefi-
ciency virus (HIV) and hepatitis B virus (HBV). All deten-
tion facilities are now under this new federal regulation.
A major/critical new standard was created by the law:
When an officers uniform becomes contaminated with
blood products, the officer cannot leave his workplace
with the uniform on. The facility must clean that uniform
and reissue it to the officer. The law states further that
inmate labor cannot be used when handling blood con-
taminated items.
A washer and dryer for the aforementioned are required
to achieve compliance with the law. They should be
located in a space that is under the direct supervision of
an officer so the security of the officers uniforms will not
be jeopardized. n
Continuing Education: Jail and Prison Housing Units
60 PlumbingSystems&Design Sept/Oct 2005
1. The sizing of a domestic water storage tank shall be large
enough to prevent the water heaters from cycling no more
than ____________ times per hour during off-peak hours.
a. two
b. four
c. six
d. eight
2. What are some of the most important factors to consider
when sizing a domestic hot water storage tank?
a. operating costs
b. initial costs
c. unit performance
d. all of the above
. The American Corrections Association ____________.
a. has established the hot water requirements for jails and
prisons
b. requires the temperature of the hot water at inmate
showers be between 100
o
F and 110
o
F
c. has established the generally used standard of 105
o
F for
inmate showers
d. requires the use of push button type showers
4. A typical hot water delivered temperature for inmate
lavatories is ____________
o
F.
a. 95
b. 100
c. 105
d. 110
. If the water heater is sized to meet the recovery required
to handle the peak shower demand of a jail housing unit,
____________.
a. the storage tank may be sized to handle approximately
50% of the shower demand
b. the storage tank should be large enough to prevent the
heater from cycling on and off more than four times per
hour during off-peak hours
c. the storage tank should be 481.6 gallons
d. both a and b
6. The main factor to consider in sizing a water heating
system for a jail is ____________.
a. showers
b. the many lavatories in housing units
c. the temperature of the hot water to be provided and the
duration of the peak flow
d. the efficiency of the storage system
. Each inmate generates approximately ____________
pounds of laundry per week.
a. 10
b. 20
c. 30
d. 40
8. In what year was the Bloodborne Pathogen law passed
that was intended to protect workers against human
immunodeficiency virus (HIV) and the hepatitis B virus
(HBV)?
a. 1986
b. 1992
c. 1998
d. 2004
. Auxiliary equipment demand ____________.
a. must be included in the water heating sizing
b. must be assumed to not be in operation during the
shower period
c. should be determined whether or not it will be operating
during the peak hour
d. is equal to 69 gallons per hour
10. The item of kitchen equipment that has the greatest effect
on the hot water demand is the ____________.
a. vegetable prep sink
b. triple pot sink
c. dishwasher
d. exhaust hood washdown system
11. A jail housing pod of 20 cells, each with one inmate, would
require how many showers?
a. one per cell
b. three
c. four
d. the number is determined by the architect
12. The objective of this chapter is ____________.
a. to help government authorities determine how the
building will operate
b. to help the designer understand and deal with the
problems of designing water heating systems for jail and
prison housing units
c. to help the designer understand and deal with the
problems of designing water heating equipment for jail
and prison housing units
d. all of the above
Do you find it difficult to obtain continuing education units
(CEUs)? Is it hard for you to attend technical seminars? Through
Plumbing Systems & Design (PSD), ASPE can help you accumulate
the CEUs required for maintaining your Certified in Plumbing Design
(CPD) status.
ASPE features a technical article in every issue of PSD, excerpted
from its own publications. Each article is followed by a multiple-
choice test and a simple reporting form.
Reading the article and completing the form will allow you
to apply to ASPE for CEU credit. For most people, this process
will require approximately 1 hour. A nominal processing fee is
charged$25 for ASPE members and $35 for nonmembers (until
further notice, the member fee is waived). If you earn a grade of
90% or higher on the test, you will be notified that you have logged
0.1 CEU, which can be applied toward the CPD renewal requirement
or numerous regulatory-agency CE programs. (Please note that it is
your responsibility to determine the acceptance policy of a particular
agency.) CEU information will be kept on file at the ASPE office for 3
years.
No certificates will be issued in addition to the notification letter.
You can apply for CEU credit on any technical article that has
appeared in PSD within the past 12 months. However, CEU credit only
can be obtained on a total of eight PSD articles in a 12-month period.
Note: In determining your answers to the CE questions, use only
the material presented in the continuing education article. Using
other information may result in a wrong answer.
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson, Chicago Chapter President
CE QuestionsJail and Prison Housing Units (PSD 129)
Sept/Oct 2005 PlumbingSystems&Design 1
P
S
D
1
3
0
Valves
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
NOVEMBER/DECEMBER 2005
PSDMAGAZINE.ORG
Continuing Education
Reprinted from American Society of Plumbing Engineers Data Book Volume 4: Plumbing Components and Equipment, Chapter 3: Valves.
2003, American Society of Plumbing Engineers.
Valvesservethepurposeofcontrollingthefluidsinbuildingser-
vice piping. They come in many shapes, sizes, design types, and
materialstoaccommodatedifferentfluids,piping,pressureranges,
andtypesofservice.Properselectionisimportanttoensurethemost
efficient,cost-effective,andlong-lastingsystems.Nosinglevalveis
best for all services. This chapter is limited to manually operated
valvesthatstart,stop,andregulateflow,andpreventitsreversal.
Functions
Valvesaredesignedtoperformfourprincipalfunctions:
1. Startingandstoppingflow
2. Regulating(throttling)flow
3. Preventingthereversalofflow
4. Regulatingorrelievingtheflowpressure.
Service Considerations
1. Pressure
2. Temperature
3. Typeoffluid
A. Liquid
B. Gas,i.e.,steamorair
C. Dirtyorabrasive(erosive)
D. Corrosive
4. Flow
A. On-off
B. Throttling
C. Needtopreventflowreversal
D. Concernforpressuredrop
E. Velocity
5. Operatingconditions
A. Frequencyofoperation
B. Accessibility
C. Overallspace/sizeavailable
D. Manualorautomatedcontrol
E. Needforbubble-tightshut-off
F. Concernsaboutbodyjointleaks
G. Firesafedesign
H. Speedofclosure.
Approvals
1. ManufacturersStandardizationSociety(MSS)
2. Fireprotection:ULandFactoryMutual(FM)
3. Stateandlocalcodes
4. AmericanPetroleumIndustries(API).
Types of Valve
Gate Valve
With starting and stopping flow its prime function, the gate valve
isintendedtooperateeitherfullyopenorfullyclosed.Whenfully
open,ithastheleastresistancetoflowofallthevalvetypes.
From an examination of Figure 1, it becomes readily apparent
howthegatevalvegotitsname.Agate-likedisc,actuatedbyastem
screwandhandwheel,movesupanddownatrightanglestothe
pathofflowandseatsagainsttwofacestoshutoffflow.Asthedisc
ofthegatevalvepresentsaflatsurfacetotheoncomingflow,this
valve is not suited for regulating or throttling flow. Flow through
apartiallyopengatevalvecre-
ates vibration and chattering
and subjects the disc and seat
toinordinatewear.
There is a wide variety of
seatsanddiscstosuitthecon-
ditions under which the valve
istooperate.Forrelativelylow
pressures and temperatures
and for ordinary fluids, seating
materials are not a particularly
difficult problem. Bronze and
ironvalvesusuallyhavebronze
or bronze-faced seating sur-
faces; iron valves may be all
iron.Nonmetalliccomposition
discsareavailablefortightseat-
ingorhard-to-holdfluids,such
asairandgasoline.
Gate discs can be classified
as solid-wedge discs, double
discs or split-wedge discs. In
thesolid-wedgedesign,asingle
tapereddisc,thinatthebottom
andthickeratthetop,isforced
intoasimilarlyshapedseat.
Inthedoubleandsplit-wedge
discdesigns,twodiscsareemployedbacktoback,withaspreading
devicebetweenthem.Asthevalvewheelisturned,thegatedrops
into its seat (as with any other gate valve), but on the final turns
of the wheel, the spreader
forces the discs outward
against the seats, effecting
tighterclosure.
Bypass valves should be
providedwherethedifferen-
tialpressureexceeds200psi
(1378kPa)onvalvessized4
to6in.(101.6to152.4mm),
and 100 psi (689 kPa) on
valves 8 in. (203.2 mm) or
larger. Bypass valves should
be1in.(12.7mm)for4-in.
(101.6-mm)valves,andin.
(19.1mm)for5-in.(127-mm)
valvesorlarger.
Globe Valve
The globe valve (which is
named for the shape of its
body)ismuchmoreresistant
to flow than the gate valve,
ascanbeseenbyexamining
the path of flow through it
(Figure 2). Its main advan-
tagesoverthegatevalveare
Valves
|lqare |e|e \a|e
|lqare 1 ate \a|e
PlumbingSystems&Design Nov/Dec 2005
itsuseasathrottlingvalvetoregulateflow
anditseaseofrepair.
Because all contact between seat and
disc ends when flow begins, the effects of
wire drawing (seat erosion) are minimized.
The valve can operate just barely open or
fully open with little change in wear. Also,
becausethediscoftheglobevalvetravelsa
relativelyshortdistancebetweenfullyopen
and fully closed, with fewer turns of the
wheel required, an operator can gauge the
rate of flow by the number of turns of the
wheel.
Aswiththegatevalve,thereareanumber
of disc and seat arrangements. These are
classified as conventional disc, plug type,
andcompositiondisc.
The conventional disc is relatively flat,
with beveled edges. On closure it
ispusheddownintoabeveled,cir-
cularseat.
Plug type discs differ only
in that they are far more tapered,
thereby increasing the contact sur-
face between disc and seat. This
characteristic has the effect of
increasing their resistance to the
cutting effects of dirt, scale, and
otherforeignmatter.
The composition disc differs
from the others in that it does not
fit into the seat opening but over
it,muchasabottlecapfitsoverthebottle
opening.Thisseatadaptsthevalvetomany
services, including use with hard-to-hold
substances such as compressed air, and
makesiteasytorepair.
Angle Valve
Verymuchakintotheglobevalve,theangle
valve (Figure 3) can cut down on piping
installation time, labor, and materials by
serving as both valve and 90 elbow. It is
lessresistanttoflowthantheglobevalve,as
flowmustchangedirectiontwiceinsteadof
threetimes.Itisalsoavailablewithconven-
tional,plugtype,orcompositiondiscs.
Ball Valve
The ball valve derives its name from the
drilled ball that swivels on its vertical axis
and is operated by a handle, as shown in
Figure 4. Its advantages are its straight-
through flow, minimum turbulence, low
torque,tightclosure,andcompactness.Also,
aquarterturnofthehandlemakesitaquick-
closingor-openingvalve.Reliability,easeof
maintenance,anddurabilityhavemadethe
ball valve popular in industrial, chemical,
andgastransmissionapplications.
Butterfy Valve
Figure5illustratesabutterflyvalve,thevalve
mostcommonlyusedinplaceofagatevalve
incaseswhereabsolute,bubble-freeshut-offis
required.Itismanufacturedinnominaldiam-
etersfrom1to72in.(25.4to1828.8mm).
Inadditiontoitstightclosing,oneofthe
valves advantages is that it can be placed
intoaverysmallspacebetweenpipeflanges.
Itisavailablewithseveraltypesofoperator,
motorizedandmanual,andavarietyofcom-
ponentmaterialcombinations.
Screwed-lug type valves should be pro-
vided so that equipment may be removed
withoutdrainingdownthesystem.
Check Valve
Swing checks and lift checks are the most
common forms of check valve. Both are
designed to prevent reversal of flow in a
pipe. The swing check, Figure 6, permits
straight-through flow when open and is,
therefore,lessresistanttoflowthan
theliftcheck.
Note: Awordofcautionregard-
ing the swing check: There have
beeninstanceswhenaswingcheck
stayedopenafewsecondsafterthe
reversalofflowbegan,allowingthe
velocityofbackflowtorisetosuch
a point that, when closure finally
didoccur,itwasinstantaneousand
the resulting shock to the valve
andsystemcausedseriousdamage.
Goodinsuranceagainstsuchapos-
sibility is a lever and weight or a
spring to ensure immediate closure upon
reversalofflow.
The lift check, Figure 7, is primarily for
usewithgasesorcompressedairorinfluid
systemswherepressuredropisnotcritical.
Valve Materials
A single valve may be constructed of sev-
eralmaterials.Itmayhaveabronzebody,a
monelseat,andanaluminumwheel.Mate-
rial specifications depend on the operating
conditions.
|lqare 8atter0, \a|e
|lqare 1 8a|| \a|e
|lqare 1 kaq|e \a|e
|lqare !wlaq C|ec|
Nov/Dec 2005 PlumbingSystems&Design 1
Brass and Bronze
Brass usually consists of 85% copper, 5%
lead, 5% tin, and 5% zinc. Bronze has a
higher copper content, ranging from 86 to
90%,withtheremainingpercentagedivided
amonglead,tin,andzinc.
Of particular importance is the zinc
content.Industrymaximumissetat15%,but
certainmilitaryandgovernmentspecifcations
allownomorethan6%.
Under certain circumstances, a phe-
nomenon known as dezincifcation will
occurinvalvesorpipescontainingzinc.The
action is a result of electrolysis; in effect,
thezincisactuallydrawnoutandremoved
fromthebrassorbronze,leavingaporous,
brittle, and weakened material. The higher
thezinccontent,thegreaterthesusceptibil-
itytodezincifcation.Tosloworpreventthe
process,tin,phosphorusantimony,andother
inhibitorsareadded.Brassvalvesshouldnot
be used for operating temperatures above
450F (232.2C). The maximum for bronze
in550F(287.8C).
Iron
IronusedinvalvesusuallyconformstoASTM
Standard A26. Although iron-bodied valves
are manufactured in sizes as small as -in.
(6.4-mm) nominal diameter, they are most
commonlystockedinsizesof2in.(50.8mm)
andabove.Intheselargersizes,theyarecon-
siderablylessexpensivethanbronze.
Thehigherweightofironvalves,ascom-
paredtobronzevalves,shouldbeconsidered
when fguring hanger spacing and loads.
A typical 2-in. (50.8-mm) screwed, bronze,
globe valve rated at 125 psi (861.3 kPa)
weighsabout13lb(5.9kg).Thesamevalve
inironweighs15lb(6.8kg)and,ifspecifed
withayokebonnet,about22lb(10kg).
Malleable Iron
Malleable iron valves are stronger, stiffer,
and tougher than iron-bodied valves and
hold tighter pressures. Toughness is most
valuableforpipingsubjectedtostressesand
shocks.
Stainless Steel
For highly corrosive fluids, stainless steel
valves provide the maximum corrosion
resistance,highstrength,andgoodwearing
properties.Seatingsurfaces,stems,anddiscs
ofstainlesssteelaresuitablewhereforeign
materials in the fluids handled could have
adverseeffects.
Valve Ratings
Most valve manufacturers rate their prod-
ucts in terms of saturated steam pressure;
or pressure of nonshock cold water, oil,
or gas (WOG); or both. These ratings usu-
ally appear on the body of the valve. For
instance, a valve with the markings 125
with200 WOG will operate safely at 125
psi(861.3kPa)ofsaturatedsteamor200psi
(1378kPa)coldwater,oil,orgas.
Theengineershouldbefamiliarwiththe
markingsonthevalvesspecifiedandshould
keep them in mind during construction
inspection. A ruptured valve can do much
damage.
Valve Components
Stems
Stemdesignsfallintofourbasiccategories:
rising stem with outside screw, rising stem
withinsidescrew,nonrisingstemwithinside
screw,andslidingstem.
Rising stem with outside screw This
design is ideal where the valve is infre-
quently used and the possibility of stick-
ingwouldconstituteahazard,suchasina
fire-protection system. In this arrangement,
the screws are not subject to corrosion or
elements in the line fluid that might cause
damagebecausetheyareoutsidethevalve
body.Also,beingoutside,theycaneasilybe
lubricated.
As with any other rising stem valve, suf-
ficientclearancemustbeallowedtoenable
afullopening.
Rising stem with inside screw This
design is the simplest and most common
stemdesignforgate,globe,andanglevalves.
Thepositionofthehandwheelindicatesthe
positionofthedisc,openedorclosed.
Nonrising stem These are ideal where
headroom is limited. They are generally
limitedtousewithgatevalves.Inthistype,
thescrewdoesnotraisethestembutrather
raisesandlowersthedisc.Asthestemonly
rotatesanddoesnotrise,wearonpackings
isslightlylessened.
Sliding stem These are applied where
quick opening and closing are required. A
lever replaces the hand wheel, and stem
threadsareeliminated.
Bonnets
In choosing valves, the service characteris-
ticsofthebonnetjointshouldnotbeover-
looked. Bonnets and bonnet joints must
provide a leakproof closure for the body.
Therearemanymodifications,butthethree
mostcommontypesarescrewed-inbonnet,
screwed union-ring bonnet, and bolted
bonnet.
Screwed-in bonnet This is the simplest
andleastexpensiveconstruction,frequently
used on bronze gate, globe, and angle
valves and recommended where frequent
dismantling is not needed. When properly
designedwithrunningthreadsandcarefully
assembled, the screwed-in bonnet makes a
durable,pressure-tightsealthatissuitedfor
manyservices.
Screwed union-ring bonnet This con-
struction is convenient where valves need
frequent inspection or cleaningalso for
quickrenewalorchangeoverofthediscin
composition disc valves. A separate union
ringappliesadirectloadonthebonnetto
hold the pressure-tight joint with the body.
Theturningmotionusedtotightenthering
is split between the shoulders of the ring
and bonnet. Hence, the point of seal con-
tactbetweenthebonnetandthebodyisless
subjecttowearfromfrequentopeningofthe
joint.
Contactfacesarelesslikelytobedamaged
inhandling.Theunionringgivesthebody
added strength and rigidity against internal
pressureanddistortion.
Whileidealonsmallervalves,thescrewed,
union-ring bonnet is impractical on large
sizes.
Bolted bonnet joint A practical and
commonlyusedjointforlargersizevalvesor
for higher-pressure applications, the bolted
bonnet joint has multiple boltings with
smaller diameter bolts that permit equal-
ized sealing pressure without the excessive
torqueneededtomakelargethreadedjoints.
Onlysmallwrenchesareneeded.
End Connections
Valves are available with screwed, welded,
brazed, soldered, flared, flanged, and hub
ends.
Screwed End
Thisisbyfarthemostwidelyusedtypeof
end connection. It is found in brass, iron,
steel,andalloypipingmaterials.Itissuited
for all pressures but is usually confined
to smaller pipe sizes. The larger the pipe
size,themoredifficultitistomakeupthe
screwedjoint.
Welded End
This type of end is available only in steel
valvesandfittingsandismainlyforhigher-
pressureand-temperatureservices.Itisrec-
Continuing Education: Valves
|lqare I |lft C|ec|
PlumbingSystems&Design Nov/Dec 2005
ommended for lines not requiring frequent
dismantling.Therearetwotypesofwelded
endmaterials:buttendsocketwelding.Butt-
weldingvalvesandfittingscomeinallsizes;
socket-welding ends are usually limited to
smallersizes.
Brazed End
Thisisavailableonbrassmaterials.Theends
ofsuchmaterialsarespeciallydesignedfor
theuseofbrazingalloystomakethejoint.
When the equipment and brazing material
areheatedwithaweldingtorchtothetem-
perature required by the alloy, a tight seal
is formed between the pipe and valve or
fitting. While made in a manner similar to
a solder joint, a brazed joint can withstand
higher temperatures due to the brazing
materialsused.
Soldered Joint
Thisisusedwithcoppertubingforplumb-
ingandheatinglinesandformanylow-pres-
sureindustrialservices.Thejointissoldered
byapplyingheat.Becauseofcloseclearance
betweenthetubingandthesocketofthefit-
tingorvalve,thesolderflowsintothejoint
bycapillaryaction.Theuseofsolderedjoints
underhightemperaturesislimitedbecause
ofthelowmeltingpointofthesolder.Silver
solderorsilfosareusedforhigherpressures
andtemperatures.
Flared End
This is commonly used on valves and fit-
tingsformetalandplastictubingupto2in.
(50.8mm)diameter.Theendofthetubing
isskirtedorflaredandaringnutisusedto
makeauniontypejoint.
Flanged End
This is generally used when screwed ends
become impractical because of cost, size,
strengthofjoint,etc.Flangedendsaregen-
erally used for larger-diameter lines due to
ease of assembly and dismantling. Flanged
facings are available in various designs
depending on service requirements. One
important rule is to match facings. When
bolting iron valves to forged steel flanges,
thefacingshouldbeoftheflatfacedesign
onbothsurfaces.
Hub End
Thisisgenerallylimitedtovalvesforwater-
supply and sewage piping. The joint is
assembledonthesocketprinciple,withthe
pipeinsertedinthehubendofthevalveor
fittingthencaulkedwithoakumandsealed
withmoltenlead.
Abbreviations
AGA AmericanGasAssociation
AISI AmericanIronandSteelInstitute
ANSI AmericanNationalStandardsInstitute
API AmericanPetroleumInstitute
ASME AmericanSocietyofMechanical
Engineers
ASTM AmericanStandardforTestingand
Material
AWWA AmericanWaterWorksAssociation
BUNA-N Butadieneandacryloni-
trile (nitrilerubber)
CSA CanadianStandardsAssociation(also
CSAInternational)(approvalagencyfor
AGA)
CWP Coldworkingpressure
EPDM Ethylene-propylenedienemonomer
IBBM Ironbody,bronzemounted(trim)
IS Insidescrew
MSS ManufacturersStandardizationSociety
oftheValveandFittingsIndustry
NBR Acrylonitrile-butadienerubber
NFPA NationalFireProtectionAssociation
NRS Nonrisingstem
OS&Y Outsidescrewandyoke
PSI Poundspersquareinch
PTFE Polytetrafluoroethyleneplastic
RS Risingstem
SWP Steamworkingpressure
TFE Tetrafluoroethyleneplastic
WCB Wroughtcarbon,gradeB
WOG Water,oil,gas(coldworkingpres-
sure)
WWP Waterworkingpressure
Glossary
Ball Avalveconsistingofasingledrilled
ball that is operated by a handle attached
to the vertical axis of the ball, which per-
mits fluid flow in a straight-through direc-
tion.Theballwithinthevalvebodymaybe
rotatedfullyopenedorfullyclosedbyone
quarterturnofthehandle.
Body Thatpartofthevalvethatattaches
tothepipelineorequipmentwithscrewed
ends,flangedends,orsoldered/weldedjoint
endsandenclosestheworkingpartsofthe
valve.
Bonnet The part of the valve housing
throughwhichthestemextends.Itprovides
support and protection to the stem and
housesthestempacking.Itmaybescrewed
orboltedtothebody.
Butterfly A type of valve consisting of
a single disc that is operated by a handle
attachedtothedisc,whichpermitsfluidflow
inastraight-throughdirection.Thevalveis
bidirectional.Thediscwithinthevalvebody
mayberotatedfullyopenorfullyclosedby
onequarterturnofthehandle.
Cap The top part of the housing of a
check valve (equivalent to the bonnet of a
gate or globe valve), which may be either
screwedorboltedontothemainbody.
Check valve An automatic, self-closing
valve that permits flow in only one direc-
tion.Itautomaticallyclosesbygravitywhen
liquidceasestoflowinthatdirection.
Clapper A common term that is used
todescribethediscofaswingtype,check
valve.
Disc The disc-shaped device that is
attachedtothebottomofthestemandthat
isbroughtintocontactwithorliftedoffthe
seating surfaces to close or open a globe
valveorbutterflyvalve.
Flanged bonnet A type of bonnet so
constructed that it attaches to the body
by means of a flanged, bolted connection.
The whole bonnet assembly, including the
handwheel,stem,anddisc,maybequickly
removed by unscrewing the nuts from the
bonnetstudbolts.
Gatevalve Avalvethatisusedtoopen
orcloseofftheflowoffluidthroughapipe.
Itissonamedbecauseofthewedge(gate)
thatiseitherraisedoutoforloweredintoa
double-seated sluice to permit full flow or
completely shut off flow. The passageway
through a gate valve is straight through,
uninterrupted, and is the full size of the
pipelineintowhichthevalveisinstalled.
Glandbushing Ametalbushinginstalled
betweenthepackingnutandthepackingto
transmittheforceexertedbythepackingnut
againstthepacking.
Globevalve Avalvethatisusedforthrot-
tlingorregulatingtheflowthroughapipe.
Itissonamedbecauseoftheglobularshape
ofthebody.Thediscisraisedoffahorizon-
talseatingsurfacetopermitfloworlowered
againstthehorizontalseatingsurfacetoshut
offflow.Thediscmaybeliftedcompletely
to permit full flow or lifted only slightly to
throttleorregulateflow.Theflowthrougha
globevalvehastomaketwo90turns.
Hand wheel The wheel-shaped turning
devicebywhichthestemisrotated,thuslift-
ingorloweringthediscorwedge.
Hingepin Thevalvepartthatthediscor
clapperofacheckvalveswings.
Outside screw and yoke A type of
bonnet so constructed that the operating
threads of the stem are outside the valve
housing, where they may be easily lubri-
catedanddonotcomeintocontactwiththe
fluidflowingthroughthevalve.
Packing A general term describing any
yieldingmaterialusedtoaffectatightjoint.
Valvepackingisgenerallyjampacking;itis
pushedintoastuffingboxandadjustedfrom
timetotimebytighteningdownapacking
glandorpackingnut.
Packinggland Adevicethatholdsand
compresses the packing and provides for
additional compression by manual adjust-
ment of the gland as wear of the packing
occurs.Apackingglandmaybescrewedor
boltedinplace.
Packing nut A nut that is screwed into
placeandpressesdownuponaglandbush-
ing, which transmits the force exerted by
Nov/Dec 2005 PlumbingSystems&Design 1
thepackingnuttothepacking.Itservesthe
samepurposeasthepackinggland.
Risingstem Athreadedcomponentthat
isunscrewedorscrewedthroughthebonnet
toopenorclosethevalve.Thehandwheel
mayrisewiththestem,orthestemmayrise
throughthehandwheel.
Screwed bonnet A type of bonnet so
constructed that it attaches to the body by
meansofascrewedjoint.Abonnetmaybe
attached to the body by screwing over the
bodyorinsidethebody,orbymeansofa
uniontype,screwedconnection.
Solidwedge Awedgeconsistingofone
solid piece into which the valve stem is
attached, so it seals against the valve seat-
ingsurfacestoensureatightsealwhenthe
valveisclosed.
Split wedge A wedge consisting of two
piecesintowhichthevalvestemisscrewed,
so it expands the two pieces against the
valveseatingsurfacestoensureatightseal
whenthevalveisclosed.
Standard port The area through the
valveislessthantheareaofstandardpipe.
Stem Theusuallythreadedshafttowhich
is attached the hand wheel at the top and
thediscorwedgeatthelowerend.Thestem
mayalsobecalledthespindle.
Stopplug Anadjustingscrewthatextends
throughthebodyofacheckvalve.Itadjusts
andcontrolstheextentofmovementofthe
discorclapper.
Swing check valve A check valve that
uses a hinged disc or clapper to limit the
direction of flow. The pressure exerted by
the fluid flowing through the valve forces
the disc away from the seating surface.
When the flow ceases, the clapper falls to
its original position, preventing flow in the
oppositedirection.
Union A coupling fitting consisting of
threeparts(ashoulderpiece,athreadpiece,
andaring)thatisusedforcouplingtheends
of pipe sections. Adjoining faces of shoul-
der and thread pieces are lapped together
to form a tight joint. Unions permit easy
disconnectionforrepairandreplacementof
pipingandfittings.
Union bonnet A type of bonnet that is
soconstructedthatthewholebonnetassem-
bly, including the hand wheel, stem, and
disc assembly, may be quickly removed by
unscrewingthebonnetunionringfromthe
valvebody.
Unionring Alargenut-likecomponent
thatsecurestheunionthreadandtheunion
shoulder together. It slips over and against
the shoulder piece and screws onto the
unionthreadpiece.
Union shoulder piece A part of the
union fastened to the pipe that retains the
unionring.
Union threaded piece That part of the
union that is fastened to the pipe and has
external threads over which the union ring
isscrewedtoeffectacoupling.
Wedge (Seealsodisc.)Thewedge-shaped
devicethatfitsintotheseatingsurfacesofa
gatevalveandthatisdrawnoutofcontact
withtheseatingsurfacestopermitfloworis
pushed down into contact with the seating
surfacestocloseoffflowwiththevalve.
100%area(fullport) Theareathrough
thevalveisequaltoorgreaterthanthearea
ofstandardpipe.
MSS Standard Practices
Number
SP-25 Standard Marking System for Valves,
Fittings, Flanges and Unions
SP-42 150 lb. Corrosion Resistant Cast
Flanged Valves
SP-67 Butterfy Valves
SP-70 Cast Iron Gate Valves, Flanged and
Threaded Ends
SP-71 Cast Iron Swing Check Valves, Flanged
and Threaded Ends
SP-72 Ball Valves with Flanged or Butt-Weld-
ing Ends for General Service
SP-78 Cast Iron Plug Valves
SP-80 Bronze Gate, Globe, Angle and Check
Valves
SP-81 Stainless Steel, Bonnetless, Flanged,
Wafer, Knife Gate Valves
SP-82 Valve Pressure Testing Methods
SP-85 Cast Iron Valves
SP-110 Ball Valves
Notes: 1. Use of the last approved revi-
sion of all standards shall be used. 2. A
largenumberofformerMSSStandardPrac-
tices have been approved by the American
NationalStandardsInstitute(ANSI)asANSI
Standards. To maintain a single source of
authoritativeinformation,MSSwithdrawsits
StandardPracticeswhentheyareapproved
asANSIStandards.
Valve Design Choices
1. Multiturntype
A. Gate
B. Globe/angle-globe
C. Endconnection
2. Checktype(backflowprevention)
A. Swing
B. Lift
C. Silentornonslam
D. Endconnection
3. Quarter-turntype
A. Ball
B. Butterfly-resilientseated
C. Plug
D. Endconnection.
Design Detail: Gate Valves
Advantages and Recommendations
1. Goodchoiceforon-offservice
2. Fullflow,lowpressuredrop
3. Bidirectional
4. Bypassvalvesshouldbeprovided
wherethedifferentialpressureexceeds
200psionvalves41to6in.and100
psionvalves8in.andlarger.Bypass
valvesshouldbe1in.for4-in.valves
andin.for5-in.valvesorlarger.
Disadvantages
1. Notforthrottling:Usefullyopenorfully
closed.Flowthroughapartiallyopen
gatevalvecausesvibrationandchat-
teringandsubjectsthediscandseatto
inordinatewear.
2. Metal-to-metalseatingmeansnotbest
choiceforfrequentoperation.Bubble-
tightseatingshouldnotbeexpected
withmetal-to-metaldesign.
3. Difficulttoautomate.
Disc and Seat Designs
1. Bronzeorbronze-facedseatingsurfaces
areusedwithbronzeandironvalves.
Ironvalvesmayuseall-ironseating
surfaces.Thesearepreferredforlow
pressuresandtemperaturesandfor
ordinaryfluids.Stainlesssteelisusedfor
high-pressuresteamanderosivemedia.
2. Nonmetallic,compositiondiscsare
availablefortightseatingorhard-to-
holdfluids,suchasairandgasoline.
3. Solid-wedgediscdesignisthinneratthe
bottom,thickeratthetop,andforced
intotheseatofasimilarshape.
4. Double-discorsplit-wedgediscdesign
aretwodiscsemployedbacktoback
withaspreadingdevicebetweenthem.
Asthevalvewheelisturned,thegate
dropsintoitsseat(aswithanyother
gatevalve),butonthefinalturnsofthe
wheel,thespreaderforcesthediscsout-
wardagainsttheseats,effectingtighter
closure.
5. Resilientwedgeisarubberencapsu-
latedmetalwedgethatsealsagainstan
epoxy-coatedbody.Resilientwedgeis
limitedtocold-waterapplications.
Design Detail: Globe/Angle-Globe
Valve
Advantages and Recommendations
1. Recommendedforthrottlingapplica-
tions.
2. Positivebubble-tightshut-offwhen
equippedwithresilientseating.
3. Goodforfrequentoperation.
4. Easytorepair.
Continuing Education: Valves
1 PlumbingSystems&Design Nov/Dec 2005
Disadvantages
1. Flowpathcausesasignificantpressure
drop.
2. Globevalvesaremorecostlythanalter-
nativevalves.
Disc and Seat Designs
1. Resilient(soft)seatdiscsarepreferred
overmetal-to-metalexceptwheretem-
peratures,veryclosethrottlingorabra-
siveflowmakeall-metalseatingabetter
choice.Stainlesssteeltrimisavailable
formedium-tohigh-pressuresteamand
abrasiveapplications.Tetrafluoroethyl-
ene(TFE)isthebestresilientdiscmate-
rialformostservices,althoughrubbers
softnessgivesgoodperformanceincold
water.TFEisgoodupto400F.Butadi-
eneandacrylonitrile(Buna-N)isgood
upto200F.
2. Automatic,steam,stop-check,angle-
globevalvesarebestonmedium-pres-
suresteamservice.
3. Wheretheslidingactionofthesemiplug
discassemblypermitsthevalvetoserve
asashut-offvalve,throttlingvalve,and
oracheckvalve.
Design Detail: Check Valves (Backfow
Prevention)
1. Swingtypecheckvalvesoffertheleast
pressuredropandoffersimpleauto-
maticclosure;whenfluidflowstops,
gravityandflowreversalclosethevalve.
ManybronzevalvesofferaY-pattern
bodywithanangleseatforimproved
performance.ResilientTeflonseatingis
preferredfortightershut-off.
2. Liftcheckscomeinanin-lineorglobe-
stylebodypattern.Bothcausegreater
pressuredropthantheswingtype,with
thehorizontalpatternsimilarinrestric-
tiontoglobevalves.
3. Somestylesarespringactuatedand
centerguidedforimmediateclosure
whenflowstops.Thein-line,spring-
actuatedliftcheckisalsoreferredtoas
thesilentcheckbecausethespring
closesthevalvebeforegravityandfluid
reversalcanslamthevalveclosed.Resil-
ientseatingisrecommended.
4. Double-disccheckvalveshavetwin
discsonaspring-loadedcentershaft.
Thesevalveshavebetterflowcharac-
teristicsthanliftchecksandmostoften
useawaferbodyforlowcostandeasy
installation.Resilientseatingisrecom-
mended.
Design Detail: Quarter-Turn Ball
Valves
Advantages and Recommendations
1. Bubble-tightshut-offfromresilient(TFE)
seats
2. Quick,90open/close,nottorque
dependentforseating
3. Straight-through,unobstructedflow,
bidirectional
4. Easiertoautomatethanmultiturnvalves
5. Morecompactthanmultiturnvalves
6. Offerlongcyclelife.
Disadvantages
1. Temperatureandpressurerangelimited
byseatmaterial.
2. Cavityaroundballtrapsmediaanddoes
notdrainentrappedmedia.Susceptible
tofreezing,expansion,andincreased
pressureduetoincreasedtemperature.
Body Styles
1. One-piecevalveshavenopotential
bodyleakpathbuthaveadouble
reducedport,thus,significantpressure
dropoccurs.Notrepairable,theyare
usedprimarilybychemicalandrefining
plants.
2. Two-pieceendentriesareusedmost
commonlyinbuildingservices.Theyare
thebestvaluevalvesandareavailable
infull-orstandard-portballs.Theyare
recommendedforon-offorthrottling
serviceandnotrecommendedtobe
repaired.
3. Three-piecetypevalvesaremorecostly
butareeasiertodisassembleandoffer
thepossibilityofin-linerepair.Theyare
availableinfull-orstandard-portballs.
Port Size
1. Full-portballvalvesprovideapressure
dropequaltotheequivalentlengthof
thepipe,slightlybetterthangatevalves.
2. Standard-(conventional-)portballsare
uptoonepipesizesmallerthanthe
nominalpipesizebutstillhavesignifi-
cantlybetterflowcharacteristicsthan
globevalves.
3. Reduced-portballvalveshavegreater
thanonepipesizeflowrestriction
andarenotrecommendedinbuilding
servicespipingbutratherareusedfor
processpipingforhazardousmaterial
transfer.
End Connections
1. ThreadedballvalveswithANSIfemale
taperthreadsaremostcommonlyused
withpipeupto2in.
2. Soldered-endvalvespermitthedirect
connectionofbronzeballvalvesto2-
in.coppertubing.Caremustbetaken
nottooverheatanddamagethevalves
duringthesolderingprocess.
Handle Extensions
1. Insulatedhandleextensionsorextended
handlesshouldbeusedtokeepinsu-
latedpipingsystemsintact.
Design Detail: Quarter-Turn Butterfy
Valves
Advantages and Recommendations
1. Bubble-tightshut-offfromresilientseats
2. Quick,90open/close;easiertoauto-
matethanmultiturnvalves
3. Verycost-effectivecomparedtoalterna-
tivevalvechoices
4. Broadselectionoftrimmaterialsto
matchdifferentfluidconditions
5. Morecompactthanmultiturnvalves
6. Offerlongcyclelife
7. Dead-endservice.
Disadvantages
1. Nottobeusedwithsteam.
2. Gearoperatorsareneededfor8in.and
largervalvestoaidinoperationand
protectagainstoperatingtooquickly
andcausingdestructivelineshock.
Body Styles
1. Waferstylevalvesareheldinplace
betweentwopipeflanges. Theyare
easytoinstallbutcannotbeusedas
isolationvalves.
2. Lug-stylevalveshavewaferbodiesbut
tappedlugsmatchinguptoboltcircles
ofclass125/150-lbflanges.Theyare
easilyinstalledwithcapscrewsfrom
eitherside.Lugstyledesignsfromsome
manufacturerspermitdroppingthepipe
fromonesidewhilethevalveholdsfull
pressureifneeded.
3. Groovebutterflyvalvesdirectlyconnect
topipeusingiron-pipe-size,grooved
couplings.Whilemorecostlythanwafer
valves,groovedvalvesaretheeasiestto
install.
Design Detail: Quarter-Turn Valves,
Lubricated Plug Cocks
Advantages and Recommendations
1. Bubble-tightshut-offfromstemsealof
reinforcedTeflon.Leakproof,spring-
loadedballandlubricated,sealedcheck
valveandcombinationlubricantscrew
andbuttonheadfittingpreventforeign
matterfrombeingforcedintothelubri-
cationsystem.
2. Quick,90open/close,notdependent
ontorqueforseating.
Nov/Dec 2005 PlumbingSystems&Design
3. Straight-through,unobstructedflow,
bidirectionalflow,three-wayflow,or
four-wayflow.
4. Offerslongcyclelife.
5. Adjustablestopforbalancingorthrot-
tlingservice.
6. Canbesuppliedwithround,diamond,
orrectangular(standard)plug.
7. Mechanismforpoweroperationor
remotecontrolofanysizeandtypeto
operatewithair,oil,orwater.
Disadvantages
1. Temperatureandpressurerangelimited
bytypeoflubricantsealantandANSI
Standardrating,i.e.150psisteamwork-
ingpressure(SWP)and200psinon-
shock,coldworkingpressure(CWP),
andwater,oil,gas(WOG).
General Valve Specifcation by Service
Hot and Cold Domestic Water Service
Gate valve
2in.andsmaller Valves2in.andsmaller
shall be class 125, rated 125 psi SWP, 200
psinonshockCWP,risingstem.Body,union
bonnet, and solid wedge shall be of ASTM
B-62castbronzewiththreadedends.Stems
shall be of dezincification-resistant silicon
bronze,ASTMB-371,orlow-zincalloy,ASTM
B-99. Packing glands shall be of bronze,
ASTM B-62, with aramid fiber, nonasbes-
tos packing, complete with malleable hand
wheel.ValvesshallcomplywithMSSSP-80.
2 in. and larger Valves 21 in. and
largershallbeclass125,rated100psiSWP,
150 psi nonshock CWP; and have an iron
body, bronze-mounted outside screw and
yoke(OS&Y),withbodyandboltedbonnet
conformingtoASTMA-126classBcast-iron,
flangedends,witharamidfiber,nonasbestos
packingandtwo-piecepackingglandassem-
bly.ValvesshallcomplywithMSSSP-70.
Alldomesticwatervalves4in.andlarger
that are buried in the ground shall be iron
body, bronze-fitted, with O-ring stem seal;
andhaveepoxycoatinginsideandoutside
and a resilient-seated gate valve with non-
risingstemandmechanicaljointorflanged
ends as required. All valves furnished shall
open left. All internal parts shall be acces-
siblewithoutremovingthevalvebodyfrom
the line. Valves shall conform to AWWA
C509-89, Standard for Resilient-Seated
Gate Valves. Epoxy coating shall conform
to AWWA C550-90, Standard for Protective
Epoxy Interior Coating for Valves.
Ball valves
2in.andsmaller Valves2in.andsmaller
shallberated150psiSWP,600psinonshock
CWP;andhavetwo-piece,castbrassbodies,
replaceablereinforcedTeflonseats,full-port
1 in., conventional-port 12 in., blow-
out-proof stems, chrome-plated brass ball,
andthreadedorsolderedends.Valvesshall
complywithMSSSP-110
Globe valves
2in.andsmaller Valves2in.andsmaller
shallbeofclass125,rated125psiSWP,200
psi nonshock CWP; body and bonnet shall
be of ASTM B-62 cast-bronze composition
withthreadedorsolderedends.Stemsshall
beofdezincification-resistantsiliconbronze,
ASTMB-371,orlow-zincalloy,ASTMB-99.
Packingglandsshallbeofbronze,ASTMB-
62,witharamidfiber,nonasbestospacking,
completewithmalleablehandwheel.Valves
shallcomplywithMSSSP-80.
2 in. and larger Valves 21 in. and
largershallbeclass125,rated125psiSWP,
200 psi nonshock CWP; and have an iron
body, bronze-mounted OS&Y, with body
and bolted bonnet conforming to ASTM
A-126 class B cast-iron, flanged ends, with
aramidfiber,nonasbestospacking,andtwo-
piece packing gland assembly. Valves shall
complywithMSSSP-85.
Butterfy valves
2 in. and larger Valves 2 1 in. and
largershallberated200psinonshockCWP;
and have a lug or IPS grooved type body
with2-in.extendedneckforinsulating.They
shallbeductileiron,ASTMA536;withstain-
lesssteeldisc;416stainlesssteelstem;eth-
ylene-propylenedienemonomer(EPDM)O-
ringstemseals;andresilient,EPDMrubber
molded to seat. Sizes 21 to 6 in. shall be
lever operated with a ten-position throt-
tlingplate;sizes8to12in.shallhavegear
operators;sizes14in.andlargershallhave
wormgearoperatorsonly.Theyaresuitable
foruseasbidirectionalisolationvalvesand,
as recommended by the manufacturer, on
dead-endserviceatfullpressurewithoutthe
needfordownstreamflanges.
ValvesshallcomplywithMSSSP-67.
Note: Butterfly valves in dead-end ser-
vicerequirebothupstreamanddownstream
flanges for proper shut-off and retention
or must be certified by the manufacturer
for dead-end service without downstream
flanges.
Check valves
2in.andsmaller Valves2in.andsmaller
shallbeclass125,rated125psiSWP,200psi
nonshock CWP; and have threaded or sol-
deredends,withbodyandcapconforming
to ASTM B-62 cast bronze composition, y-
patternswingtypedisc.Valvesshallcomply
withMSSSP-80
Note: Class150valvesmeetingtheabove
specifications may be used where system
pressure requires. For class 125 seat disc,
specifyBuna-NforWOGserviceandTFEfor
steamservice.Forclass150seatdisc,specify
TFEforsteamservice.
2 in. and larger Valves 21 in. and
largershallbeclass125,rated125psiSWP,
200 psi nonshock CWP; iron body, bronze
mounted,withbodyandboltedbonnetcon-
forming to ASTM A-126 class B cast-iron,
flanged ends, swing type disc, and nonas-
bestosgasket.ValvesshallcomplywithMSS
SP-71.
Alternative check valves (21 in. and
larger) shall be class 125/250 iron body,
bronze mounted, wafer check valve, with
endsdesignedforflangedtypeconnection,
aluminum bronze disc, EPDM seats, 316
stainlesssteeltorsionspring,andhingepin.
A spring-actuated check valve is to be
usedonpumpdischarge.Swingcheckwith
outsideleverandspring(notcenterguided)
is to be used on sewage ejectors or storm-
watersumppumps.
Fire-Protection System
Gate valves
2 in. and smaller Valves 2 in. and
smallershallbeofclass175psiwaterwork-
ing pressure (WWP) or greater, with body
andbonnetconformingtoASTM-B-62,cast-
bronze composition, threaded ends, OS&Y,
solid disc and listed by UL, FM approved,
andincompliancewithMSSSP-80.
2 in. and larger Valves 21 in. and
largershallberated175psiWWPorgreater,
andhaveanironbody,bronzemountedor
with resilient rubber encapsulated wedge,
withbodyandbonnetconformingtoASTM
A-126, class B cast-iron, OS&Y, class 125
flanged or grooved ends. If of resilient
wedgedesign,interiorofvalveistobeepoxy
coated.ValvesshallmeetorexceedAWWA
C509-89,Standard for Protective Epoxy Inte-
rior Coating for Valves.ValvesaretobeUL
listed,FMapproved,andincompliancewith
MSSSP-70.
Valves 4 in. and larger for under-
groundburyshallberated200psiWWP
or greater, with body and bonnet con-
forming to ASTM A-126, class B cast iron,
bronzemounted,resilient-seatedgatevalve
withnonrisingstem,withO-ringstemseal,
epoxycoatinginsideandoutside,flangedor
mechanicaljointendsasrequired.Allvalves
furnished shall open left. All internal parts
shall be accessible without removing the
valve body from the line. Valves shall con-
formtoAWWAC509-89,Standard for Resil-
ient-Seated Gate Valves. Epoxycoatingshall
conform to AWWA C550-90, Standard for
Protective Epoxy Interior Coating for Valves.
Valves shall come complete with mounting
plateforindicatorpostandbeULlisted,FM
approved,andincompliancewithMSSSP-
70.
Continuing Education: Valves
PlumbingSystems&Design Nov/Dec 2005
When required, a vertical indicator post
may be used on underground valves. Posts
must provide a means of knowing if the
valve is open or shut. Indicator posts must
be UL listed and FM approved.
High-Rise Service
Gate valves
2- to 12-in. Gate valves 2 to 10 in.
shall be rated 300 psi WWP or greater, 12
in. shall be rated 250 psi WWP, and have an
iron body, bronze mounted, with body and
bonnet conforming to ASTM A-126, class B,
cast iron, OS & Y, with flanged ends for use
with class 250/300 flanges. They shall be UL
listed, FM approved, and in compliance with
MSS SP-70.
Check valves
2- to 12-in. Check valves 2 to 10 in.
shall be rated 300 psi WWP or greater, 12 in.
shall be rated 250 psi WWP, and have an iron
body, bronze mounted, with a horizontal
swing check design, with body and bonnet
conforming to ASTM A 126 Class B, cast
iron, with flanged ends for use with class
250/300 flanges. They shall be UL listed, FM
approved, and in compliance with MSS SP-
71.
Note: In New York City, valves are to be
approved by the New York City Materials
and Equipment Acceptance Division (MEA),
in addition to the above specifications.
Ball valves
2 in. and smaller Valves 2 in. and smaller
shall be constructed of commercial bronze,
ASTM B 584, rated 175 psi WWP or higher,
with reinforced TFE seats. Valves shall have
a gear operator with a raised position indi-
cator and two internal supervisory switches.
Valves shall have threaded or IPS grooved
ends and shall have blowout-proof stems
and chrome-plated balls. They shall be UL
listed, FM approved, and in compliance with
MSS SP-110 for fire-protection service.
Butterfy valves
4 to 12 in. Butterfly valves may be sub-
stituted for gate valves, where appropri-
ate. Valves shall be rated for 250 psi WWP,
175 psig working pressure, UL listed, FM
approved and in compliance with MSS SP-
67.
Valves furnished shall have ductile-iron
ASTM A-536 body, and may have ductile-iron
ASTM A-395 (nickel-plated) discs or alumi-
num bronze discs, depending upon the local
water conditions. In addition, wafer style for
installation between class 125/150 flanges or
lug style or grooved body may be specified,
depending upon the system needs.
Valves shall be equipped with weather-
proof gear operator rated for indoor/out-
door use, with hand wheel and raised posi-
tion indicator with two internal supervisory
switches.
Check valves Valves 2 in. and larger
shall be 500 psi WWP, bolted bonnet, with
body and bonnet conforming to ASTM A-
126, class B cast iron, flanged end with com-
position y-pattern, horizontal, swing type
disc. They shall be UL listed, FM approved,
and in compliance with MSS SP-71 type 1 for
fire-protection service. n
Nov/Dec 2005 PlumbingSystems&Design 57
Continuing Education: Valves
1. Dezincification occurs in valves as a result of _________.
a. electrolysis
b. high velocity
c. high pressure
d. water hammer
2. All domestic water gate valves 4 inches and larger that
are buried in the ground shall be iron body, bronze
fitted with __________.
a. o-ring stem seal
b. epoxy coating inside and out
c. resilient seats
d. all of the above
. MSS withdraws its standard practices when __________.
a. they have been revised
b. they are approved as ANSI standards
c. they are in conflict with local codes
d. none of the above
4. The valve type that is best suited for all services is a
__________ valve.
a. ball
b. gate
c. globe
d. none of the above
. When a gate valve is fully open, it __________.
a. has the highest resistance to flow of all valve types
b. has the least resistance to flow of all valve types
c. causes water hammer in the piping system
d. creates velocity surges
6. Butterfly valves in dead-end service require __________.
a. flanges upstream and down stream for shut-off and
proper retention
b. lock nuts on the flange bolts
c. certification by the manufacture for dead-end service
without downstream flanges
d. a or c but not b
. Bypass valves should be provided where the differential
pressure exceeds __________ psi on valves sized 4-6
inches.
a. 100
b. 150
c. 200
d. 250
8. Two-inch and smaller ball valves rated 10 psi SWP,
600 psi non-shock CPW with two-piece, cast brass
bodies, replaceable reinforced Teflon seats, blowout-
proof stems, chrome plated brass ball and threaded or
soldered ends must comply with MSS __________.
a. SP-110
b. standard practices
c. SP-72
d. all of the above
. The cap of a check valve is the equivalent to the ______.
a. bonnet of a gate or globe valve
b. operating pressure
c. packing gland of a ball valve
d. none of the above
10. By-pass valves __________.
a. are required when differential pressure exceeds 200
psi on gate valves 4-6 inches and 100 psi gate valves 8
inches and larger
b. must be 2 inches in diameter
c. should be provided where the differential pressure
exceeds 200 psi on gate valves 4-6 inches and 100 psi
on gate valves 8 inches and larger
d. must be inch or inch only
11. One advantage of the butterfly valve is that it can be
placed in very small spaces between __________.
a. other valves
b. equipment
c. piping
d. pipe flanges
12. When flow begins in a globe valve, __________.
a. wire drawing is minimized
b. contact between the seat and disk ends
c. a and b above
d. none of the above
Do you find it difficult to obtain continuing education units
(CEUs)? Is it hard for you to attend technical seminars? Through
Plumbing Systems & Design (PS&D), ASPE can help you accumulate
the CEUs required for maintaining your Certified in Plumbing Design
(CPD) status.
ASPE features a technical article in every issue of PS&D, excerpted
from its own publications. Each article is followed by a multiple-
choice test and a simple reporting form.
Reading the article and completing the form will allow you
to apply to ASPE for CEU credit. For most people, this process
will require approximately 1 hour. A nominal processing fee is
charged$25 for ASPE members and $35 for nonmembers (until
further notice, the member fee is waived). If you earn a grade of
90% or higher on the test, you will be notified that you have logged
0.1 CEU, which can be applied toward the CPD renewal requirement
or numerous regulatory-agency CE programs. (Please note that it is
your responsibility to determine the acceptance policy of a particular
agency.) CEU information will be kept on file at the ASPE office for 3
years.
No certificates will be issued in addition to the notification letter.
You can apply for CEU credit on any technical article that has
appeared in PS&D within the past 12 months. However, CEU credit
only can be obtained on a total of eight PS&D articles in a 12-month
period.
Note: In determining your answers to the CE questions, use only
the material presented in the continuing education article. Using
other information may result in a wrong answer.
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson, Chicago Chapter President
CE QuestionsValves (PSD 130)
PlumbingSystems&Design Nov/Dec 2005
P
S
D
1
3
1
Medical Gas
and Vacuum
Systems
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
JANUARY/FEBRUARY 2006
PSDMAGAZINE.ORG
GENErAl
Health care is in a constant state of change, which forces the
plumbing engineer to keep up with new technology to provide
innovative approaches to the design of medical-gas systems. In
designingmedical-gasandvacuumsystems,thegoalistoprovide
asafeandsufcientfowatrequiredpressurestothemedical-gas
outletorinletterminalsserved.Systemdesignandlayoutshould
allowconvenientaccessbythemedicalstaftooutlet/inlettermi-
nals,valves,andequipmentduringpatientcareoremergencies.
Tis section focuses on design parameters and current stan-
dards required for the design of nonfammable medical-gas and
vacuum systems used in therapeutic and anesthetic care. Te
plumbing engineer must determine the needs of the health-care
staf.Trytoworkcloselywiththemedicalstaftoseekanswersto
thefollowingfundamentaldesignquestionsatthestartofaproj-
ect:
1. Howmanyoutlet/inletsarerequestedbystaf?
2. Howmanyoutlet/inletsarerequired?
3. Basedoncurrentconditions,howoftenistheoutlet/inlet
used?
4. Basedoncurrentconditions,whatistheaveragedurationof
useforeachoutlet/inlet?
5. Whatistheproperusage(diversity)factortobeused?
MEDICAl-GASSySTEMDESIGNChECklIST
As any hospital facility must be specially designed to meet the
applicablelocalcoderequirementsandthehealth-careneedsof
thecommunityitserves,themedical-gasandvacuumpipingsys-
temsmustalsobedesignedtomeetthespecifcrequirementsof
eachhospital.
Following are the essential steps to a well-designed and func-
tionalmedical-gaspipedsystem,whicharerecommendedtothe
plumbingengineer:
1. Analyzeeachspecifcareaofthehealth-carefacilitytodeter-
minethefollowingitems:
A. Whichpipedmedical-gassystemsarerequired?
B. Howmanyofeachdiferenttypeofmedical-gasoutlet/inlet
terminalarerequired?
C. Whereshouldtheoutlet/inletterminalsbelocatedfor
maximumefciencyandconvenience?
D. Whichtypeandstyleofoutlet/inletterminalbestmeetthe
needsofthemedicalstaf?
2. Anticipateanybuildingexpansionandplaninwhichdirec-
tiontheexpansionwilltakeplace(verticallyorhorizontally).
Determinehowthemedical-gassystemshouldbesizedand
valvedinordertoaccommodatethefutureexpansion.
3. Determinelocationsforthevariousmedical-gassupply
sources.
A. Bulkoxygen(O
2
).
B. High-pressurecylindermanifolds(O
2
,N
2
OorN
2
).
C. Vacuumpumps(VAC).
D. Medical-aircompressors(MA).
4. Preparetheschematicpipinglayoutlocatingthefollowing:
A. Zonevalves.
B. Isolationvalves.
C. Masteralarms.
D. Areaalarms.
5. Calculatetheanticipatedpeakdemandsforeachmedical-gas
system.Appropriatelysizeeachparticularsectionso asto
avoidexceedingthemaximumpressuredropsallowed.
6. Sizeandselectthevariousmedical-gasandvacuumsupply
equipmentthatwillhandlethepeakdemandsforeach
system,includingfutureexpansions.Ifthisprojectisanaddi-
tiontoanexistingfacility,determinethefollowing:
A. Whatmedicalgasesarecurrentlyprovidedandwhatare
thelocationsandnumberofthestations?
B. Canthecurrentgassupplier(orthehospitalspurchasing
department)furnishtheconsumptionrecords?
C. Arethecapacitiesoftheexistingmedical-gassupplysys-
temsadequatetohandletheadditionaldemand?
D. Areanyexistingsystemsvalvedthatcouldbeusedforan
extension?Aretheexistingpipesizesadequatetohandle
theanticipatedadditionalloads?
E. Whattypeofequipmentisinuseandwhoisthemanufac-
turer?Isthisequipmentstate-of-the-art?
F. Isitfeasibletomanifoldthenewandexistingequipment?
G. Whatisthephysicalconditionoftheexistingequipment?
H. Isthereadequatespaceavailableforthenewmedical-gas
supplysystemsandrelatedequipmentattheexistingloca-
tion?
I. Isexistingequipmentscheduledtobereplaced?(Amain-
tenancehistoryoftheexistingequipmentmayhelpinthis
determination.)
NuMBEroFSTATIoNS
Tefrststepistolocateandcounttheoutlet/inlets,oftencalled
stations,foreachrespectivemedical-gassystem.Tisisusually
donebyconsultingaprogrampreparedbythefacilityplanneror
architect. Tis program is a list of all the rooms and areas in the
facilityandtheservicesthatarerequiredineach.Ifaprogramhas
not been prepared, the foor plans for the proposed facility shall
beused.
Tere is no code that specifcally mandates the exact number
ofstationsthatmustbeprovidedinvariousareasorroomsforall
health-carefacilities.Infact,thereisnoclearconsensusofopinion
amongmedicalauthoritiesordesignprofessionalsastohowmany
stations are actually required in the facility areas. Guidelines are
C0N7INUINC DUCA7I0N
Medical Gas and
Vacuum Systems
Reprinted from American Society of Plumbing Engineers Data Book Volume 3: Special Plumbing Systems, Chapter 2: Medical Gas and Vacuum
Systems. 2000, American Society of Plumbing Engineers.
44 PlumbingSystems&Design JANUARY/FEBRUARY 2006 PSDMAGAZINE.ORG
published by the American Institute of Architects
(AIA),NationalFireProtectionAssociation(NFPA),
and ASPE that recommend the minimum number
ofstationsforvariousservicesinspecifcareas.
Te most often-used recommendations in deter-
miningthenumberofstationsforhospitalsarethose
necessarytobeaccreditedbytheJointCommission
for the Accreditation of Hospitals Organization
(JCAHO).AccreditationisrequiredforMedicareand
Medicaid compensation. Te JCAHO publishes a
manualthatreferstotheAIAguidelinesforthemini-
mum number of stations for oxygen, medical air,
andvacuumthatmustbeinstalledinordertoobtain
accreditation. If this is a factor for the facility, these
requirements are mandatory. Other jurisdictions,
such as state or local authorities, may require plans
to be approved by local health or building ofcials.
Tese approvals may require adhering to the state
orlocalrequirementsand/orNFPA99,Health-Care
Facilities.
If accreditation or the approval of authorities is
not a factor, the number and area locations of sta-
tions are not mandated. Te actual count then will
depend upon requirements determined by each
individualfacilityoranothermemberofthedesign
team using both past experience and anticipated
future use, often using the guideline recommenda-
tionsasastartingpoint.
MEDICAl-GASFlowrATES
Eachstationmustprovideaminimumfowrateforthe
proper functioning of connected equipment under
designandemergencyconditions.Tefowratesand
diversity factors vary for individual stations in each
systemdependingonthetotalnumberofoutletsand
thetypeofcareprovided.
Tefowratefromthetotalnumberofoutlets,with-
out regard for any diversity, is called the total con-
nectedload.Ifthetotalconnectedloadwereusedfor
sizingpurposes,theresultwouldbeavastlyoversized
system, since not all of the stations in the facility will
be used at the same time. A diversity, or simultane-
ous-usefactor,isusedtoallowforthefactthatnotall
ofthestationswillbeusedatonce.Itisusedtoreduce
thesystemfowrateinconjunctionwiththetotalcon-
nectedloadforsizingmainsandbranchpipingtoall
parts of the distribution system. Tis factor varies for
diferentareasthroughoutanyfacility.
Teestimatedfowrateanddiversityfactorsforvarioussystems,
areastations,andpiecesofequipmentarefoundinTable1.
Total demand for medical-gas systems varies as a function of
time of day, month, patient-care requirements, and facility type.
Te number of stations needed for patient care is subjective and
cannot be qualifed based on physical measurements. Knowing
thetypesofpatientcareand/orauthorityrequirementswillallow
placementofstationsinusagegroups.Tesegroupscanestablish
demand and simultaneous-use factors (diversities), which are
usedinthecalculationforsizingaparticularsystem.Allmedical-
gas piping systems must be clearly identifed using an approved
color-codingsystemsimilartothatshowninTable2.
MEDICAl-GASSySTEMDISPENSINGEquIPMENT
Medical-gas outlet/inlet terminals Most manufacturers of
medical-gas system equipment ofer various types of medical-
gasoutlets.Tesemedical-gasoutletsareavailableinvariousgas
orders(e.g.,O
2
-N
2
O-Air),center-linespacing,andforexposedand
concealedmountings.Outlettypesandconfgurationsmustmeet
the requirements of the local jurisdictional authority and NFPA
99. All outlets must be properly identifed and confrmed. Care
shouldalsobetakentoaccuratelycoordinatethevariouspiecesof
medical-gasdispensingequipmentwiththearchitectandmedical
stafinvolvedinthegivenproject.Iftheprojectisarenovation,the
outlettypesshouldmatchexistingequipment.Withprefabricated
patient headwall units, the medical-gas outlets are generally fur-
nished by the equipment manufacturer, and it is very important
thatcoordinationbemaintainedbytheengineersothatunneces-
table 1 Outlet Rating Chart for Medical-Vacuum Piping Systems
Free-Air Allowance, cfm
(L/min) at 1 atmosphere
Zone Allowances Corridors,
Risers, Main Supply Line,
Valves
Location of Medical-Surgical Vacuum
Outlets Per Room Per Outlet
Simultaneous
Usage Factor
(%)
Air to Be
Transported,
cfm (L/min)
a
Operating rooms:
Major A(Radical, open heart; organ
transplant; radical thoracic) 3.5 (100) 100 3.5 (100)
Major B(All other major ORs) 2.0 (60) 100 2.0 (60)
Minor 1.0 (30) 100 1.0 (30)
Delivery rooms 1.0 (30) 100 1.0 (30)
Recovery room (post anesthesia) and
intensive-care units (a minimum of 2
outlets per bed in each such department):
1st outlet at each bed 3 (85) 50 1.5 (40)
2nd outlet at each bed 1.0 (30) 50 0.5 (15)
3rd outlet at each bed 1.0 (30) 10 0.1 (3)
All others at each bed 1.0 (30) 10 0.1 (3)
Emergency rooms 1.0 (30) 100 1.0 (30)
Patient rooms:
Surgical 1.0 (30) 50 0.5 (15)
Medical 1.0 (30) 10 0.1 (3)
Nurseries 1.0 (30) 10 0.1 (3)
Treatment & examining rooms 0.5 (15) 10 0.05 (1)
Autopsy 2.0 (60) 20 0.04 (1)
Inhalation therapy, central supply &
instructional areas 1.0 (30) 10 0.1 (3)
a
Free air at 1 atmosphere.
table 2 Color Coding for Piped Medical Gases
Gas Intended for Medical Use United States Color Canada Color
Oxygen Green Green on white
a
Carbon dioxide Gray Black on gray
Nitrous oxide Blue Silver on blue
Cyclopropane Orange Silver on orange
Helium Brown Silver on brown
Nitrogen Black Silver on black
Air Yellow* White and black on black and white
Vacuum White Silver on yellow
a
Gas mixtures (other than
mixtures of oxygen and nitrogen)
Color marking of mixtures shall be a combination of color
corresponding to each component gas.
Gas mixtures of oxygen and
nitrogen
19.5 to 23.5% oxygen
All other oxygen concentrations
Yellow
a
Black and green
Black and white
Pink
Source: Compressed Gas Association, Inc.
a
Historically, white has been used in the United States and yellow has been used in Canada to identify vacuum systems.
Therefore, it is recommended that white not be used in the United States and yellow not be used in Canada as a marking
to identify containers for use with any medical gas. Other countries may have difering specifc requirements.
JANUARY/FEBRUARY 2006 PlumbingSystems&Design 45
C0N7INUINC DUCA7I0N: MedicaI Cas and Vacuum Systems
saryduplicationofworkisavoided.Also,withregardtotheover-
the-bed medical-gas service consoles, these consoles are often
specifed in the electrical or equipment section of the specifca-
tionandmedical-gasserviceoutletsarespecifed,furnished,and
installedunderthemechanicalcontract.
Gas-outlet sequence, center-line spacing, and multiple-gang-
service outlets are some of the considerations to be taken into
accountwhenrequestinginformationfromthevariousequipment
manufacturers.Itismorepractical,intermsofboththecostofthe
equipmentandtheinstallation,tospecifyandselectthemanufac-
turersstandardoutlet(s).Detailsandspecifcationsregardingthe
individualstandardoutletsareusuallyavailablefromallmanufac-
turersuponrequest.
Teexistingoutletsarecompatiblewiththeadaptersfoundon
the hospitals anesthesia machines, fow meters, vacuum regula-
tors,etc.Careshouldbetakentomakesureallfutureexpansions
inthesamefacilityhavecompatibleequipment.
Patient head-wall systems A recent and growing trend in
hospital construction is the requirement for patient head-wall
systems, which incorporate many services for the patients care.
Teseunitsmayincludethefollowing:
1. Medical-gasoutlets.
2. Electrical-serviceoutlets(includingemergencypower).
3. Directandindirectlighting.
4. Nurse-callsystem.
5. Isolationtransformers.
6. Groundingoutlets.
7. Patient-monitoringreceptacles.
8. VacuumslideandIVbrackets.
9. Nightlights.
10.Electricalswitches.
Bed locator units are also available, which serve to provide
powerforthemoreadvancedpatientbeds,telephone,nightlights,
and standard power. Tese units
also function to protect the walls
from damage as beds are moved
andadjusted.
Head walls currently vary in
shape, size, type, and cost from a
simple over-the-patient-bed stan-
dard confguration to elaborate
total-wall units. Most manufactur-
ersofmedical-gasequipmentofer
medical-gas outlets for all types
of patient consoles available in
todays market. When specifying
head-walls outlets, the plumbing
engineer should consider the fol-
lowing:
1. Istheserviceoutletselected
compatiblewiththeexisting
outletcomponent?
2. Doesthepatienthead-wall
manufacturerincludethetype
ofmedical-gasoutletsrequired
aspartoftheproduct?
Special types of ceiling-
mounted, medical-gas out-
lets In critical-care areas, which are generally considered by
mostindividualstobethoselocationsofthehospitalprovidinga
specialtreatmentorserviceforthepatient(suchassurgery,recov-
ery,coronary,orintensive-careunits),thedesignersselectionand
placement of the medical-gas service equipment must be done
verycarefullyinordertoprovideefcientworkcentersaroundthe
patientforthemedicalstaf.
Manufacturers of medical-gas service equipment usually pro-
vide a wide range of equipment that is available for use in these
areas. Depending upon the customers preference and the avail-
able budget, the equipment is selected to provide the necessary
individualgasservicesandaccessories.
Table3providesaquickreferenceguidefortheengineertouse
asabasisforselectingthecommonlyusedtypesofoutletdispens-
ingequipment.
Example 1
Te following illustrative example presents some of the most
importantcritical-careareaequipmentandoptionsfortheselec-
tionoftheequipment.
Surgerymedical-gasservicestobepipedinclude:
1. Oxygen.
2. Nitrousoxide.
3. Nitrogen.
4. Medicalcompressedair.
5. Vacuum.
6. Wasteanesthetic-gasdisposal.
Providingmedical-gasserviceoutletsinthesurgeryroommay
beaccomplishedinseveralways,suchasthefollowing:
1. Ceiling outlets Individualmedical-gasoutletsmountedinthe
ceilingwithhoseassembliesprovidingthemedicalstafwith
connectionsfromtheoutletstotheadministeringapparatus.
Tismethodisconsideredbymosttobethemosteconomi-
calmeansofprovidinganadequategasservicetothesurgery
table 3 Types of Dispensing Equipment for Specifc Areas
Hospital Areas
Medical Gas Outlet Dispensing Equipment
Wall-
Mounted
Outlets
Patient
Care Head
Wall
Ceiling-
Mounted
Outlets with
Hose Stops
Rigid
Ceiling
Columns
Retractable
Ceiling
Columns
Ceiling
with Gas
Stacks
Nitrogen
Control
Cabinets
Autopsy rooms
Delivery rooms
Emergency examination and treatment
rooms
Emergency operating rooms
Induction rooms
Labor rooms
Major surgery rooms
Minor surgery, cystoscopy
Neonatal intensive care units
Normal nursery rooms
Nursery workrooms
O.B. recovery rooms
Patient rooms
Pediatric and youth intensive care unit
Post-operative recovery rooms
Premature and pediatric nursery rooms
Pre-op holding rooms
Radiology rooms
Respiratory care unit
Specialized surgeries (cardiac and neuro)
46 PlumbingSystems&Design JANUARY/FEBRUARY 2006 PSDMAGAZINE.ORG
areas.Teceilinggas-serviceoutletsaregenerallylocatedat
boththeheadandthefootoftheoperatingtableinorderto
providealternatepositioningoftheoperatingtable.
2. Surgical ceiling columns Surgicalceilingcolumnsareusu-
allyavailableintwodesigns:rigid(apredeterminedlength
fromtheceilingheightabovethefoor)andretractable.Both
surgicalceilingcolumnsprovidemedical-gasserviceswithin
anenclosurethatprojectsdownfromtheceiling.Teceiling
columnsareusuallylocatedatoppositeendsoftheoperating
tableinordertoprovideconvenientaccesstothemedical-gas
outletsbytheanesthesiologist.Inadditiontothemedical-gas
outlets,theseceilingcolumnscanbeequippedwithelectri-
caloutlets,groundingreceptacles,physiologicalmonitor
receptacles,andhooksforhangingintravenous-solution
bottles.
Mostmanufacturersoferingsurgicalceilingcolumnsallowfor
manyvariationsinroomarrangementsofmedical-gasservices
andrelatedaccessories,dependinguponthespecifccustomers
needsandtheengineersspecifcations.Whenspecifyingthis
typeofequipment,itisnecessarytospecifycarefullyallmedical-
gasservicerequirementsandtheirdesiredarrangement(s).Also,
theengineermustcoordinateallotherrequiredserviceswiththe
electricalengineerandmedicalstaf.
3. Surgical gas tracks Surgicalgastracksareformsofceiling
outletandhose-droparrangementsthatallowthemovement
ofthehosedropsfromoneendoftheoperatingtabletothe
otheronslidingtracksmountedontheceiling.Teseprod-
uctsarecurrentlyavailablefromvariousmanufacturersand
allprovidethesamebasicservices.Teproperselectionand
specifcationofspecifctypesarebasedonindividualcus-
tomerpreference.Manyvariationsinproductsandparticular
productapplicationsareavailableincritical(intensive)care
areas.Consultationwithappropriatemanufacturersforrec-
ommendationsisalwaysadvisable.
4. Articulating ceiling-service center Articulatedceiling-ser-
vicecentersaremovedbypneumaticdrivesystemsandare
designedfortheconvenientdispensingofmedical-gasand
electricalservicesinoperatingrooms.Temedical-gasand
electricalsystemsarecompleteforsingle-pointconnectionto
eachoutletatthemountingsupportplatform.
High-pressure nitrogen (N
2
) dispensing equipment Special
consideration must be given by the plumbing engineer to the
placementofthenitrogenoutlets.Teprimaryuseofnitrogengas
inhospitalsisfordrivingturbo-surgicalinstruments.Variationsof
these turbo-surgical instruments, in both their manufacture and
theirintendeduse,willrequirethatseveraldiferentnitrogen-gas
pressure levels be available. For this reason, it is necessary that
the engineer provide an adjustable pressure-regulating device
near the nitrogen gas outlet. A nitrogen control panel is usually
located on the wall (in the surgery room) opposite the operating
areasterilefeld.Teinstallationshouldallowfortheaccessand
adjustmentofpressuresettingsbyasurgicalnurse.
Pipingfromthenitrogencontrolpaneltoasurgicalceilingoutlet
willprovideaconvenientsourceofnitrogenforsurgicaltools.Tis
willpreventhosesfrombeinglocatedonthefoororbetweenthe
walloutletandtheoperatingtable.Excesshosecanbeobstructive
tothesurgicalteam.
MEDICAl-GASSTorAGE
Afterdecidingthemedical-gasservicestobeprovidedatthefacil-
ity, the engineer should determine the storage capacity and the
pipe sizing required and possible locations for the source. Local
codesandreferencesaswellastheadministrativeauthorityhaving
jurisdictionshouldbeconsultedforeachmedical-gassystem.
Because of the unique characteristics of each medical-gas
source, the gases are described separately in this section. Also,
an explanation of the techniques currently employed to exhaust
anestheticgasesisprovided.
Oxygen (O
2
) Severalfactorsmustbeknownwhenestimating
the monthly consumption of oxygen in new or existing health-
carefacilities:
1. Typeofmedicalcareprovided.
2. Numberofoxygenoutletsor
3. Numberofpatientbeds.
4. Futureexpansionoffacility.
5. Inexistingfacilities,approximateconsumption.
Two methods can be used by the plumbing engineer to esti-
matetheconsumptionofoxygen.Temoreaccuratemethodisto
obtainadetailedconsumptionrecordfromthehealth-carefacility
orobtainmonthlyoxygenshipmentinvoicesfromthesupplier.If
inventoryrecordsarenotavailablefromthehealth-carefacilityor
the supplier, use consumption records from a comparably sized
facility,withgoodjudgment.
Te second method is to apply the following rule of thumb to
estimate the monthly supply of oxygen. Tis estimating method
shouldbeusedwithgoodjudgment.Alwayscoordinateestimated
demandwiththeoxygensupplierduringthedesignprocess.
1. Innon-acute-careareas,allow500ft
3
(14m
3
)perbedper
monthforsupplyandreserveoxygenstorage.
2. Inacute-careareas,allow1000ft
3
(28m
3
)perbedpermonth
forsupplyandreserveoxygenstorage.
Oxygensupplysourcesaredividedintotwocategories:(1)bulk-
oxygen systems and (2)cylinder-manifold-supply systems. Bulk-
oxygen systems should be considered for health-care facilities
with an estimated monthly demand above 35,000 ft
3
(991 m
3
) or
equal to 70 oxygen outlets. Manifold systems are used in small
generalhospitalsorclinics.
Bulk-oxygen systems Whenselectingandplacingbulk-oxygen
systems,thereareseveralfactorstobeconsidered:Oxygentrans-
port truck size, truck access to bulk-storage tanks, and NFPA 50,
Standard for Bulk Oxygen Systems at Consumer Sites.Bulk-oxygen
equipment,construction,installation,andlocationmustcomply
with NFPA 50 recommendations. If liquid oxygen is spilled or
leaked,anextremefreorexplosivehazardcouldoccur.NFPAhas
designstandardstominimizefreexposuretoandfromsurround-
ingstructures.
Bulk-storagesystemsconsistofcryogenictanksthatstoreliquid
oxygen at low pressures (225 psi [1551.3 kPa] or less). Cryogenic
tanksareASMEunfred,double-walled,vacuum-insulated,pres-
sure vessels. Liquid oxygen has a boiling point (nbp) of 297.3F
(182.9C) and a liquid density of 71.27 lb/ft
3
(1141.8 kg/cm
3
).
Whenvaporizedintogas,itproduces900timesitsliquidvolume.
Furthermore,sincethetankischangedlessoften,processstabil-
ity is maximized and the introduction of atmospheric impurities
isreduced.Tanksystemsarefurnishedwithanintegralpressure-
relief valve vented to the atmosphere should the liquid oxygen
converttoagas.
JANUARY/FEBRUARY 2006 PlumbingSystems&Design 47
C0N7INUINC DUCA7I0N: MedicaI Cas and Vacuum Systems
Most bulk-oxygen storage systems are furnished with vapor-
izers. Vaporizers are banks of fnned-tube heat exchangers that
converttheliquidtoitsgaseousstate.Tevaporizerscomeinsev-
eral stylesincluding atmospheric, powered (forced-air, steam,
and electric), waste-heat, and hybridand sizes. Te selec-
tion of vaporizers should be based on demand, intermittent or
continuous usage, energy costs, and temperature zones. Poorly
ventilated sites or undersized heat exchangers can cause ice to
form on vaporizers during the conversion process. Excessive ice
formations can clog and damage the vaporizer. Also, ice could
allowextremelycoldgasorthecryogenicliquidtoenterthepiped
system; damage the valves, alarms, and medical components;
andeveninjurepatients.Figure1illustratesatypicalbulk-oxygen
systemschematic.
Automaticcontrolsfurnishedwiththetanksregulatethefowof
liquidthroughthevaporizers.Whenthereisademandforoxygen,
thesupplysystemdrawsliquidfromthebottomofthecryogenic
storagetankthroughthevaporizers.Tegasmovesthroughafnal
line regulator. Tus, a constant supply of oxygen at a regulated
pressureisprovided.
In case of mechanical difculty or the depletion of the liquid-
oxygensupply,thereservesupplywillbegintofeedintothedistri-
butionsystemautomatically.
An alarm signal should alert appropriate hospital personnel
when the liquid in the oxygen storage tank reaches a predeter-
mined level. Te alarm signals should indicate low liquid levels,
reserveinuse,andreservelow.
Cylinder-manifold supply systems Compressed-oxygen
systems are comprised of cylinder manifolds that allow a pri-
marysupplysourceofoxygencylinderstobeinuseandanequal
numberofoxygencylinderstobeconnectedasareservesupply.
Te controls of the cylinder manifold will automatically shift the
fow of the oxygen gas from the service side to the reserve side
whentheservicesideisdepleted.
Manifold systems can be located indoors or outdoors. When
manifolds are located indoors, the engineer should observe the
following:
Location Preferably,themanifoldshouldbeinadedicated
roomonanoutsidewallnearaloadingdockandhaveade-
quateventilationandserviceconvenience.
Adjacent areas Tereshouldbenodoors,vents,orother
directcommunicationsbetweentheanesthetizinglocationor
thestoragelocationandanycombustibleagents.Iflocating
nearoradjacenttoanelevatedtemperatureareaisunavoid-
able,theengineershouldspecifysufcientinsulationtopre-
ventcylinderoverheating;
Fire rating Tefre-resistanceratingoftheroomshouldbeat
least1h.
Ventilation Outsideventilationisrequired.
Security Teroom(orarea)mustbeprovidedwithadoorora
gatethatcanbelockedandlabeled.
Oxygen manifolds are sized taking into consideration the fol-
lowing:
1. Tesizeofthecylinders,244ft
3
(6909L)H-cylinder(seeTable
4forasizingchart).
2. Tehospitalsusageofoxygen,inft
3
(L)permonth.
Figure 1 Typical Bulk Supply System (Schematic)
48 PlumbingSystems&Design JANUARY/FEBRUARY 2006 PSDMAGAZINE.ORG
table 4 Selection Chart for Oxygen Manifolds
Hospital Usage Duplex Manifold Size
Cu. Ft. (10
3
L) per month Total Cylinders Cylinders per Side
5,856 (165.8) 6 3
9,760 (276.4) 10 5
13,664 (386.9) 14 7
17,568 (497.5) 18 9
21,472 (608.0) 22 11
25,376 (718.6) 26 13
29,280 (829.1) 30 15
33,154 (938.8) 34 17
Note: Based on use of 244 ft
3
(6909.35 L) H-cylinders.
Nitrous oxide(N
2
O) Tecommonsourceofnitrousoxideisa
cylinder-manifold system. High-pressure manifold systems con-
sist of two banks of cylinders, primary and reserve. (See discus-
sionunderOxygen,above.)
Systemdemandsfornitrousoxidecanbemoredifculttodeter-
minethantheyareforothermedicalgases.Tenumberofsurger-
ies scheduled, the types and lengths of surgery, and the admin-
istering techniques used by the anesthesiologists cause extreme
variations in the amount of nitrous oxide used. Because of this
variation, considerations must be given to the size and selection
ofthenitrous-oxidemanifoldsystem.
Avoid locating the nitrous-oxide manifold system outdoors in
areaswithextremelycoldclimates.Nitrousoxideissuppliedlique-
fed at its vapor pressure of 745 psi (5136.6 kPa) at 70F (21.1C).
At extremely cold temperatures, the cylinder pressure will drop
dramatically, reducing the cylinder pressure to a point where it is
impossibletomaintainanadequatelinepressure.Tisisduetoa
lackofheatforvaporization.
Fornitrous-oxidemanifoldslocatedindoors,thesameprecau-
tionspreviouslylistedforoxygensystemsmustbeobserved.
Te following should be considered when selecting and sizing
nitrous-oxidemanifoldsanddeterminingthenumberofcylinders
required:
1. Tesizeofthecylinders:489ft
3
(13847L)K-cylinders(see
Table5).
2. Tenumberofanesthetizinglocationsoroperatingrooms.
3. Provideof1cylinderperoperatingroomforin-serviceand
reservesupplies.
table 5 Sizing Chart for Nitrous Oxide Cylinder Manifolds
Number of
Operating
Rooms
Duplex Manifold Size
Indoor Outdoor
Total Cylinders
Cylinders per
Side Total Cylinders
Cylinders per
Side
4 4 2 4 2
8 8 4 10 5
10 10 5 12 5
12 12 6 14 7
16 16 8 20 10
Note: Based on use of 489 ft
3
(13.85 103 L) K-cylinders.
Medical compressed air Medical compressed air may be
supplied by two types of system: (1) a high-pressure cylinder-
manifoldsystem;and(2)amedicalair-compressorsystem.
Temanifoldsystemsforcompressedairaresimilarinconfgu-
rationtothoseforoxygenandnitrousoxide(seediscussionunder
Oxygen, above). Air supplied from cylinders or that has been
reconstitutedfromoxygenU.S.P.andnitrogenN.F.mustcomply,
asaminimum,withGradeDinANSIZE86.I,Commodity Specif-
cation for Air.
Medical compressed air can be produced on site from atmo-
spheric air using air compressors designed for medical applica-
tions.Terearethreemajortypesofaircompressorinthemarket-
place today: the centrifugal, reciprocating, and rotary screw. Te
reciprocating and rotary screw are positive-displacement type
units, while the centrifugal compressor is a dynamic type com-
pressor. Te medical air compressor shall be designed to prevent
theintroductionofcontaminantsorliquidintothepipelinebyone
oftwomethods:Type1aircompressorseliminateoilanywherein
thecompressor.Type2aircompressorsseparatetheoil-containing
sectionfromthecompressionchamber.Examplesofatype1com-
pressor are the liquid ring, rotary screw, and permanently sealed
bearingcompressor.Type2compressorshaveextendedheads.
Apositive-displacementcompressorisnormallyratedinactual
cubicfeetperminute(acfm).Tisistheamountofairtakenfrom
atmosphericconditionsthattheunitwilldeliveratitsdischarge.
Withinabroadrange,changesininletairtemperature,pressure,
andhumiditydonotchangetheacfmratingofeithertherecipro-
cating or the rotary screw compressor. Te centrifugal compres-
sors capacity, however, is afected slightly by the inlet air condi-
tionsduetothenatureofthecompressionprocess.Forexample,
as the air temperature decreases, the capacity of the dynamic
compressor will increase. Te capacity of a centrifugal compres-
sorisnormallydefnedininletcubicfeetperminute(icfm).Inan
eforttoobtainanapplestoapplescomparisonofvariouscom-
pressors,manymanufacturersspecifytheircapacityrequirements
instandardcubicfeetperminute(scfm).Tissometimescauses
much confusion because many people do not fully understand
how to convert from acfm or icfm to scfm. Te design engineer
specifying scfm must defne a typical inlet air condition at the
buildingsiteandtheirsetofstandardconditions(normally14.7
psia [101.4 kPa], 60F [15.6C], and 0% relative humidity). Typi-
cally, the warmest normal condition is specifed because as the
temperaturegoesupscfmwillgodown.
Toconvertfromacfmtoscfm,thefollowingequationisused.
Equation 1
scfm =acfm
P
i
(P
pi
%RH)
T
std
P
std
(P
p
std
%RH
std
) T
i
where
P
i
=Initialpressure
P
pi
=Partialinitialpressureofwatervaporin100%humidairat
thetemperatureinquestion
RH=Relativehumidity
P
std
=Pressureunderstandardconditions
P
pstd
=Partialstandardpressureofwatervaporin100%humid
airatthetemperatureinquestion
RH
std
=Relativehumidityatstandardconditions
T
std
=Temperatureatstandardconditions,F(C)
T
i
=Inlettemperature,F(C)
JANUARY/FEBRUARY 2006 PlumbingSystems&Design 49
C0N7INUINC DUCA7I0N: MedicaI Cas and Vacuum Systems
Equation 1a
TisequationisderivedfromthePerfectGaslaw,whichis:
P
1
V
1
=
P
2
V
2
T
1
T
2
or:
V
2
=V
1
P
1
T
2
P
2
T
1
where
P
1
=Initialpressure
V
1
=Initialvolume
T
1
=Initialtemperature
P
2
=Finalpressure
V
2
=Finalvolume
T
2
=Finaltemperature
Forareciprocatingorrotary-screwcompressor,theconversion
fromacfmtoscfmissimple.Teinletairconditionsandstandard
conditions are inserted into the above formula and multiplied
by the acfm capacity of the unit. It makes no diference what the
design conditions are for that compressor, as these do not fgure
intotheformula.Inthecaseofadynamiccompressor,theicfmair
fow at the given inlet conditions is inserted in place of the acfm
intheformula.Anotherdesignissuethattheengineershouldbe
aware of is how altitude afects the output of the compressor. At
altitudes above sea level, all medical-air systems have reduced
fow. In these cases, the required sizing will need to be adjusted
tocompensate.Todothis,multiplythescfmrequirementsbythe
correctionfactorinTable6.
table 6 Altitude Correction Factors for Medical-Air Systems
Altitude, ft (m)
Normal Barometric
Pressure, in. Hg (mm Hg)
Correction
Factor for SCFM
(L/min)
Sea level 29.92 (759.97) 1.0 (28.31)
1,000 (304.8) 28.86 (733.04) 1.01 (28.6)
2,000 (609.6) 27.82 (706.63) 1.03 (29.16)
3,000 (914.4) 26.82 (681.23) 1.05 (29.73)
4,000 (1219.2) 25.84 (656.33) 1.06 (30.01)
5,000 (1524) 24.90 (632.46) 1.08 (30.58)
6,000 (1828.8) 23.98 (609.09) 1.10 (31.14)
7,000 (2133.6) 23.09 (586.48) 1.12 (31.71)
8,000 (2438.4) 22.23 (564.64) 1.15 (32.56)
9,000 (2743.2) 21.39 (543.3) 1.17 (33.13)
10,000 (3048) 20.58 (522.7) 1.19 (33.69)
In other words, to correctly size the medical-air system, you
wouldapplythecorrectionfactorlistedinthechartabovetothe
peak-calculatedload(scfm)atsealevel.
Example 2
Afacilityislocatedat5000ft(1524m)abovesealevelandthesystem
demand is 29.4 SCFM. Take the 29.4 scfm and multiply it by 1.08
(correction factor from Table 5) to get the adjusted scfm require-
mentof31.8scfmat5000ftabovesealevel.Terefore,amedical-air
systemofgreatercapacityisneededathigheraltitudes.
Another handy formula for compressed-air systems is the fol-
lowing:toconvertscfmtoL/minmultiplyby28.31685.
Each compressor must be capable of maintaining 100% of the
medical-air peak demand regardless of the standby compressors
operating status. Te basic compressor package consists of flter
intakes, duplex compressors, after-coolers, receiving tanks, air
dryers, in-line flters, regulators, dew-point monitors, and valves.
Te compressor components are connected by piping that allows
equipment isolation, provides pressure relief, and removes con-
densate from receivers. Medical-air compressors must draw out-
sideairfromabovetherooflevel,remotefromanydoors,windows,
andexhaustorventopenings.Wheretheoutsideatmosphericairis
polluted,specialflterscanbeattachedtothecompressorsintake
to remove carbon monoxide and other contaminants. Refer to
NFPA99forproperlocationofmedical-airintakes.Medicalcom-
pressedairmustcomplywithNFPA99and/orCanadianStandards
Associations(CSAs)defnitionofair-qualitystandards.
Wheremorethantwounitsareprovidedforthefacility,anytwo
units must be capable of supplying the peak calculated demands.
Provide automatic alternators (duty-cycling controls) to ensure
evenwearinnormalusage.Alternatorcontrolsincorporateaposi-
tivemeansofautomaticallyactivatingtheadditionalunit(orunits)
shouldthein-servicepumpfailtomaintaintheminimumrequired
pressure.
Medical compressed air produced by compressors may be
defnedasoutsideatmospheretowhichnocontaminants(inthe
formofparticulatematter,odors,oilvapors,orothergases)have
been added by the compressor system. Not every compressor is
suitableforuseasasourceformedicalcompressedairinhealth-
care facilities. Only those compressor units specifcally designed
andmanufacturedformedicalpurposesshouldbeconsideredas
a reliable source of oil-free, moisture-free, and low-temperature
compressedair.Acceptablecompressortypesincludeoil-free,oil-
less, and liquid-ring compressors. Separation of the oil-contain-
ingsectionfromthecompressionchamberbyatleasttwosealsis
requiredbythecompressormanufacturers.
Aircompressedformedical-breathingpurposesaretobeused
for this purpose only and should not be used for other applica-
tionsorcross-connectedwithothercompressedairsystems.
table 7 Minimum Pipe Sizes for Medical Air-Compressor Intake Risers
Pipe size, in.
(mm)
Flow rate, cfm
(L/min)
2.5 (63.5) 50 (1416)
3 (76.2) 70 (1985)
4 (101.6) 210 (5950)
5 (127.0) 400 (11330)
Table7providestheminimumpipesizesformedicalair-com-
pressor intake risers. Consult with the compressor manufacturer
on intake recommendations and allowable friction loss for the
intakeriserbeforefnalizingthepipesizeequipmentselection.
50 PlumbingSystems&Design JANUARY/FEBRUARY 2006 PSDMAGAZINE.ORG
C0N7INUINC DUCA7I0N
1. When Iiquid oxygen is vaporized into a gas, it
produces ________ times its Iiquid voIume.
a. 0
b. 450
c. 900
d. 1,350
2. Nitrous oxide (N
2
0) is typicaIIy used by whom in the
surgery room!
a. the attending physician
b. the attending physicians assistant
c. the surgical nurse
d. the anesthesiologist
3. 7he medicaI-gas and vacuum piping systems must be
designed to ________.
a. meet the specifc requirements of each hospital
b. anticipate any building expansion
c. not cross connect to any existing system
d. all of the above
4. 7he primary use of nitrogen gas in hospitaIs is ______
__.
a. driving turbo-surgical instruments
b. pressurizing piping systems
c. in the laboratory Bunsen burners
d. none of the above
5. MedicaI-gas ow rates ________.
a. must include diversifcation
b. must provide for the total connected load
c. must provide the minimum required fow for the
proper functioning of connected equipment
d. must be estimated
6. Providing medicaI-gas service outIets in the surgery
room may be accompIished by Iocating them in
______.
a. the ceiling
b. the surgical ceiling columns
c. the surgical gas tracks
d. any of the above noted areas and others not listed
7. In acute-care areas, aIIow ________ cubic feet per bed
per month for suppIy and reserve oxygen storage.
a. 250
b. 500
c. 750
d. 1,000
8. 7he exact number of medicaI-gas outIets required in
the various areas or rooms is mandated by ________.
a. the various codes that apply to work at the project
site
b. the American Institute of Architects (AIA)
c. the National Fire Protection Association (NFPA)
d. none of the above
9. MedicaI-gas outIet types and congurations must
meet the requirements of the IocaI jurisdictionaI
authority and ________.
a. ANSI 1416
b. NFPA 99
c. NFPA 50
d. ANSI 1763
10. SeveraI factors must be known when estimating the
monthIy consumption of oxygen, such as ________.
a. the number of patient beds
b. the type of medical care provided
c. the future expansion plans of the facility
d. all of the above
11. What is the SCFM correction factor for a medicaI-air
system Iocated in a faciIity at an aItitude of 7,000 feet
above sea IeveI!
a. 1.05
b. 1.08
c. 1.12
d. 1.17
12. 7he goaI in designing medicaI-gas and vacuum
systems is ________.
a. to provide a safe system
b. to provide a sufcient fow of gas or vacuum
c. to provide the required pressure
d. all of the above
Doyoufnditdifculttoobtaincontinuingeducationunits(CEUs)?
Is it hard for you to attend technical seminars? Trough Plumbing
Systems & Design (PS&D), ASPE can help you accumulate the CEUs
required for maintaining your Certifed in Plumbing Design (CPD)
status.
ASPEfeaturesatechnicalarticleineveryissueofPS&D,excerpted
fromitsownpublications.Eacharticleisfollowedbyamultiple-choice
testandasimplereportingform.
Readingthearticleandcompletingtheformwillallowyoutoapply
to ASPE for CEU credit. For most people, this process will require
approximately 1 hour. A nominal processing fee is charged$25 for
ASPE members and $35 for nonmembers (until further notice, the
memberfeeiswaived).Ifyouearnagradeof90%orhigheronthetest,
youwillbenotifedthatyouhavelogged0.1CEU,whichcanbeapplied
towardtheCPDrenewalrequirementornumerousregulatory-agency
CE programs. (Please note that it is your responsibility to determine
theacceptancepolicyofaparticularagency.)CEUinformationwillbe
keptonfleattheASPEofcefor3years.
No certifcates will be issued in addition to the notifcation letter.
YoucanapplyforCEUcreditonanytechnicalarticlethathasappeared
inPS&Dwithinthepast12months.However,CEUcreditonlycanbe
obtainedonatotalofeightPS&Darticlesina12-monthperiod.
Note:IndeterminingyouranswerstotheCEquestions,useonlythe
material presented in the continuing education article. Using other
informationmayresultinawronganswer.
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD
CE QuestionsMedical Gas and Vacuum Systems (PSD 131)
52 PlumbingSystems&Design JANUARY/FEBRUARY 2006 PSDMAGAZINE.ORG
P
S
D
1
3
2
Plumbing
Design for
Health Care
Facilities
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
MARCH/APRIL 2006
PSDMAGAZINE.ORG
InTroDuCTIon
Health-care facilities, nursing homes, medical schools,
and medical laboratories require plumbing systems that
aremorecomplexthanthoseformostothertypesofbuild-
ing. Te plumbing designer should work closely with the
architect and facility staf and be involved in meetings and
discussionsinordertofullyunderstandtheplumbingrequire-
ments for any new or special medical equipment. Te plumb-
ing design must be coordinated with the civil, architectural,
structural, mechanical, and electrical designs to ensure that
adequate provisions have been made for utility capacities, for
thenecessaryclearancesandspacerequirementsofthepiping
systemsandrelatedplumbingequipment,andforcompliance
withapplicablecodes.Health-carefacilitiesmayhavediferent
requirements or be exempt from some codes and standards,
such as water and energy conservation codes and regulations
regarding the physically challenged. Te plumbing engineer
should consult with the administrative authority in order to
ensureconformancewithlocalordinances.
Tis chapter discusses the provisions that may be encoun-
teredbytheplumbingprofessionalinthedesignofahealth-care
facility, including the following: plumbing fxtures and related
equipment,thesanitarydrainagesystem,thewater-supplysys-
tem, laboratory waste and vent systems, pure-water systems,
andmedical-gassystems.
PLuMBInGFIxTurESAnDrELATEDEquIPMEnT
SELECTIonProCESS
Meetingsoftheplumbingengineerwiththearchitectandthe
facilitystaftodiscussthegeneralandspecifcrequirements
regardingtheplumbingfxturesandrelatedequipmentare
usuallyheldafterthearchitecthaspreparedthepreliminary
drawings.Atthesemeetings,theplumbingdesignershould
assistintheselectionofplumbingfxtures.Followingthese
sessions,theplumbingdesignercanpreparethepreliminary
drawingsandcoordinatewiththearchitectandfacilitystaf
therequiredpipingsystemsandtheplumbingfxturespacere-
quirements.Indetailingthepipingsystemspacesandplumb-
ingfxturelocations,theplumbingengineershouldreferto
theframingdrawings.Itiscommonforthearchitecttolocate
thepipingshaftsandthespacesindirectconfictwiththe
framing;itistheplumbingdesignersresponsibilitytogivethe
architectdirectionsregardingthespacerequirements,fxture
arrangement,andpipe-shaftsizeandlocations.
Following the meetings held with the architect and hospital
staf,andwiththepreliminarydrawingsavailable,theplumbing
designershouldprepareanoutlinespecifcationfortheplumb-
ing fxtures and related equipment. A guide to the required
plumbing fxtures and equipment for health-care facilities is
providedinTable1andisdiscussedlaterinthissection.
Areviewofapplicablecoderequirementsregardingthequality
andtypesofplumbingfxturesisalwaysrequired.Inadditionto
thelocalcodes,itisnecessaryfortheplumbingengineertorefer
tothespecialhospitalcoderequirementspublishedbythelocal
hospital authorities, the state hospital or health-department
authorities,theJointCommissionfortheAccreditationofHos-
pitalsOrganization(JCAHO),andtheUSDepartmentofHealth
and Human Services. Te architect may investigate these spe-
cial requirements; however, the plumbing designer must be
familiar with them since they contain many other applicable
requirements(inadditiontothetableindicatingtheplumbing
fxturesnecessaryforaparticularinstallation).
GEnErALrEquIrEMEnTS
Plumbing fxtures in health-care facilities should be of dense,
imperviousmaterialshavingsmoothsurfaces.Plumbingfxtures
of vitreous china, enameled cast iron, and stainless steel are
commonlyused.Fixturebrassincludingfaucets,traps,strain-
ers, escutcheons, stops, and suppliesshould be chromium
plated in a manner approved by the administrative author-
ity. Die-cast metals should not be used. Faucets should have
a laminar fow device (no alternative) of brass, Monel metal,
or stainless-steel trim. Each plumbing fxture in health-care
facilities should be provided with individual stop valves. Each
water-service main, branch main, and riser shall have valves.
Accessshallbeprovidedatallvalves.Allsubmergedinlets,fau-
cetswithhoseadapters,andfushvalvesmustbeequippedwith
approved vacuum breakers. Backfow-prevention devices shall
beinstalledonhosebibbs,supplynozzlesusedfortheconnec-
tionofhosesortubing,andatotherlocationswherethepotable
watersupplymustbeprotectedfromcontamination.
Allplumbingfxtures,faucets,piping,solder,andfuxesused
inpotentialdrinking-waterareasshouldcomplywiththelatest
maximumleadcontentregulations.Facilitiesforthephysically
challengedshallbeincompliancewiththeAmericanswithDis-
abilitiesAct(ADA)accessibilityguidelines.
FIxTurESForSPECIFICHEALTH-CArEArEAS
General-use staf and public areas
Water closets Vitreouschina,siphon-jetwaterclosetwithelon-
gated bowl design with open-front seat, less cover, should be
specifed.Wall-hungwaterclosetsarepreferredforeasyclean-
ing;however,foor-setmodelsarealsoacceptablebymostlocal
jurisdictions. All water closets should be operated by water-
saverfushvalves.
Lavatories and sinks Vitreous china, enameled cast iron
or stainless-steel lavatories and sinks should be specifed. Te
most commonly specifed size is 20 18 7 in. deep (508
457.2 190.5 mm deep). Hands-free controls (foot or knee
C0N7INUINC DUCA7I0N
Plumbing Design for
Health Care Facilities
Reprinted from American Society of Plumbing Engineers Data Book Volume 3: Special Plumbing Systems, Chapter 2: Plumbing Design for
Health Care Facilities. 2000, American Society of Plumbing Engineers.
56 PlumbingSystems&Design MARCH/APRIL 2006 PSDMAGAZINE.ORG
controls) are generally employed for staf use and for scrub-up
sinks. In public areas, codes should be checked for the require-
ment of self-closing valves and/or metered valves. Stops should
be provided for all supply lines. Aerators are not permitted; use
laminar fow devices. Insulated and/or ofset p-traps should be
used for handicapped fxtures.
Faucets Valves should be operable without hands, i.e., with
wrist blades or foot controls or electronically. If wrist blades
are used, blade handles used by the medical and nursing staf,
patients, and food handlers shall not exceed 4 in. (11.43 cm) in
length. Handles on scrub sinks and clinical sinks shall be at least
6 in. (15.24 cm) long. Water spigots used in lavatories and sinks
shall have clearances adequate to avoid contaminating utensils
and the contents of carafes, etc.
Urinals Vitreous china wall-hung urinals with fush valves.
Flush valves should be equipped with stops and may be of the
exposed or concealed design.
Showers Te shower enclosures and foor specifed by the
plumbing engineer may be constructed of masonry and tile or
of prefabricated fberglass. Showers and tubs shall have nonslip
walking surfaces. Te shower valve should automatically com-
pensate for variations in the water-supply pressure and tem-
perature to deliver the discharge water at a set temperature that
will prevent scaldings.
Drinking fountains and water coolers Drinking fountains
are available in vitreous china, steel and stainless steel. Units for
exterior installations are available in suitable materials. Refrig-
erated water coolers are available in steel or stainless steel. All
of these materials are acceptable by most local administrative
Table 1 RecommendedPlumbingFixturesandRelatedEquipment
Medical-CareAreas
Public/Staf Restrooms l l l l l l l
Staf Lounge l l l l l l
Patient Rooms l l l l
Isolation Rooms l l l l
Nurse Stations l
Nursery l l
Formula Room l l l
Intensive-Care Room l l l
Outpatient-Services Area l l l l
Emergency Rooms l l l l l
Exam/Treatment Room l l l
Labor Room l l l
Janitors Closet l l l
Clean Linen Holding l
Soiled Linen Holding l l
Nourishment Station l l l
Patient Bathing Area l l l l l
Critical-Care Area l l l l l
Pharmacy l
Surgical Scrub-up l
Anesthesia Workroom l
Surgical Supply Services l
Surgical Cleanup Room l
Doctors Locker Room l l l l
Nurses Locker Room l l l
Recovery Room l l l
Fracture Room l l
Cleanup/Utility Room l l l l
Sub-Sterilizing Room l
Medical Laboratory l l l l l l l l l l l
Physical Therapy Room l l l l l l l
Cystoscopic Room l l l l l l
Autopsy Room l l l l l l l l
Dietary Services l l l l l l l l l l
Laundry Facility l l l l
Family Waiting Room l l l
E
l
o
n
g
a
t
e
d
W
a
t
e
r
C
l
o
s
e
t
,
F
l
u
s
h
V
a
l
v
e
U
r
i
n
a
l
H
a
n
d
w
a
s
h
i
n
g
L
a
v
a
t
o
r
y
S
h
o
w
e
r
D
r
i
n
k
i
n
g
F
o
u
n
t
a
i
n
/
W
a
t
e
r
C
o
o
l
e
r
M
o
p
S
e
r
v
i
c
e
B
a
s
i
n
C
o
u
n
t
e
r
S
i
n
k
,
S
i
n
g
l
e
C
o
m
p
a
r
t
m
e
n
t
C
o
u
n
t
e
r
S
i
n
k
,
D
o
u
b
l
e
C
o
m
p
a
r
t
m
e
n
t
C
l
i
n
i
c
S
i
n
k
,
F
l
u
s
h
i
n
g
R
i
m
S
c
r
u
b
-
u
p
S
i
n
k
U
t
i
l
i
t
y
S
i
n
k
S
i
n
k
,
T
r
i
p
l
e
C
o
m
p
a
r
t
m
e
n
t
P
l
a
s
t
e
r
S
i
n
k
,
P
l
a
s
t
e
r
T
r
a
p
C
u
p
S
i
n
k
F
l
o
o
r
D
r
a
i
n
F
l
o
o
r
D
r
a
i
n
,
F
l
u
s
h
i
n
g
R
i
m
E
m
e
r
g
e
n
c
y
S
h
o
w
e
r
E
m
e
r
g
e
n
c
y
E
y
e
w
a
s
h
B
a
t
h
t
u
b
/
S
h
o
w
e
r
S
i
t
z
B
a
t
h
B
e
d
p
a
n
W
a
s
h
e
r
W
a
s
t
e
G
r
i
n
d
e
r
I
c
e
M
a
k
e
r
A
r
m
/
L
e
g
B
a
t
h
I
m
m
e
r
s
i
o
n
B
a
t
h
G
l
a
s
s
W
a
s
h
e
r
I
n
f
a
n
t
B
a
t
h
t
u
b
MARCH/APRIL 2006 Plumbing Systems & Design 57
C0N7INUINC DUCA7I0N: PIumbing Design for HeaIth Care FaciIities
authorities. Tese units may be of the surface-mounted, semi-
recessedorfully-recesseddesign.
Chilled water for drinking purposes should be provided
between 45 and 50F (7.2 and 10.0C) and obtained by chill-
ingwaterwitharefrigerationcompressor.Tecompressormay
be enclosed in a cabinet with the dispenser (water cooler),
installedinawallcavitybehindagrilladjacenttothedispenser,
orremotelylocatedforsingleormultipledispensers.Aremotely
installed unit for multiple dispensers (central system) should
havearecirculationsystem.
Mop-service basins Floor-mounted mop-service basins
can be obtained in precast or (terazzo) molded-stone units of
various sizes. Te plumbing engineer should specify the most
suitablemodel.Rimguardsarenormallyprovidedtoprotectthe
rimsfromdamageandwallguardsareprovidedtoprotectwalls
fromsplashingandchemicalstains.Tewater-supplyfxtureis
usuallyatwo-handlemixingfaucetmountedonthewallwitha
wallbrace,vacuumbreaker,andhoseadapter.
Floor drains Floordrainsintoiletroomsareoptionalinmost
cases;however,therearemanyinstanceswherethefoordrains
are required by the applicable codes. Te plumbing designer
shouldgiveconsiderationtomaintainingatrapsealinthefoor
drain through the use of deep-seal p-traps and/or trap prim-
ers.Floordrainsshallnotbeinstalledinoperatinganddelivery
rooms.
Patient rooms Teserooms(privateorsemiprivate)usually
areprovidedwithatoiletroomcontainingawatercloset,alava-
tory, and a shower or bathtub. (Some hospitals use common
shower and bath facilities for a group of patient rooms.) Te
plumbing fxtures should conform with the following recom-
mendations:
Tewaterclosetshouldbevitreouschina,wall-hungorfoor-
mounteddesign,withanelongatedbowl.Allwaterclosetsshould
be operated by a fush valve. Water closets should have open-
frontseats,lesscover.Bedpanlugsandbedpanwashersareoften
required by the local codes. Bedpan-fushing devices shall be
provided in each inpatient toilet room; however, installation is
optional in psychiatric and alcohol-abuse units, where patients
areambulatory.
Te lavatory should be a minimum of 20 18 7 in. (508
457.2190.5mm)deep.Lavatoriesshouldbeinstalledatleast34
in. (863.6 mm) above the foor. Mixing faucets should be of the
gooseneck-spout design and provided with wrist-blade handles,
electronic,orhands-freecontrols.
Teshowerisusuallyconstructedofmasonryandtile,acrylics,
or fberglass. Te shower bases should be nonslip surfaces. Te
showervalveshouldautomaticallycompensateforvariationsin
the water-supply pressure and temperature to deliver the dis-
chargewateratasettemperaturethatwillpreventscalding.Grab
bars,locatedwithintheshowerenclosure,areusuallyrequiredby
thelocalcodes.Teplumbingengineershouldalwayscheckwith
thelocaladministrativeauthorityregardingapproveddesigns.
Bathtubs can be constructed of cast iron, fberglass, acryl-
ics,orsteel.Faucetsshouldbeastheyareforshowers.Shower
heads may be of the stationary design, but in many locations
hand-heldshowersarerequired.
Alavatoryintendedforusebydoctors,nurses,andotherhos-
pital staf is sometimes required by the local ordinances. Tis
particular lavatory is usually located on the wall near the door
withagooseneckspoutandhands-freecontrols.
A water closet and lavatory, with a fxed or fold-away water
closetmadeofstainlesssteel,maybeconsidered.Tisconcept,
aswellastheconstructionoftheunit,mustbeacceptedbythe
administrativeauthority.
Ward rooms Ward rooms are infrequently found in health-
care facilities, particularly in the private hospital feld. Tese
roomsrequireatleast1lavatory.Tislavatoryshouldbeamini-
mum2018in.(508457.2mm)andmadeofvitreouschina
or stainless steel. Te faucet should be of the gooseneck-spout
design and provided with wrist-blade handles or hands-free
controls.
Nurseries Te hospitals nursery is usually provided with a
minimumsize2018in.(508457.2mm)lavatorywithhands-
free controls and a high gooseneck spout. An infants bathtub,
wall-orcounter-mountedwithanintegrallargedrainboardand
rinsingbasin,isprovided.Water-supplyfttingsarefllerspouts
over the basins with separate hand-valve controls. Te spout
and the spray are usually supplied and controlled through a
thermostatic mixing valve. Te ultimate in maintaining a safe
watertemperatureisaseparatesupplytank.
Intensive-care rooms Teseroomsusuallyhaveutilitysinks
with hands-free controls with high gooseneck spouts. A water-
supplyfttingequippedwithagooseneckspoutandprovisionfor
bedpanwashing(eitheratanimmediatelyadjacentwatercloset
orataseparatebedpanwashingstationwithinanenclosurein
the room) should be provided. Newer designs have included
combinationlavatory/waterclosetsforpatientuse,especiallyin
cardiac-careunits.
Emergency (triage) rooms Te plumbing fxtures provided
in emergency rooms include a utility sink with an integral tray
and a water-supply ftting with a gooseneck spout and wrist-
blade handles. A vitreous china clinic sink (or a fushing-rim
sink), for the disposal of solids, with the water-supply ftting
consisting of a fush valve and a separate combination faucet
withvacuumbreakermountedonthewallabovetheplumbing
fxture,shouldalsobeprovided.
Examination and treatment rooms Tese rooms are usu-
ally provided with vitreous china or stainless-steel lavatories.
Tewater-supplyfttingshouldbeahands-freevalveequipped
with a high, rigid, gooseneck spout. For a particular examina-
tionroomoragroupofpatientrooms,anadjacenttoiletroomis
providedcontainingaspecimen-typewaterclosetforinserting
a specimen-collecting bedpan. Te toilet room also requires a
lavatoryandawatersupplywithwrist-bladehandlesorhands-
freecontrolsandwithagooseneckspout.
Physical-therapy treatment rooms Te plumbing fxtures
and related equipment for these rooms usually include hydro-
therapyimmersionbathsandleg,hip,andarmbaths.Teseunits
are generally furnished with electric-motor-driven whirlpool
equipment.Tewaterisintroducedintothestainless-steeltank
enclosure by means of a thermostatic control valve to prevent
scalding, usually wall mounted adjacent to the bath for opera-
tion by a hospital attendant. Te water supply should be sized
tominimizetubflltime.Teimmersionbathsareusuallypro-
videdwithoverheadhoistsandcanvasslingsforfacilitatingthe
liftinginandoutofthebathofacompletelyimmobilepatient.
A hydrotherapy shower is sometimes required. Tese showers
usually consist of multiple shower heads, sometimes as many
as12to16,verticallymountedinordertodirectthestreamsof
wateratastandingpatientbymeansofasophisticatedcontrol
consoleoperatedbyahospitalattendant.
58 PlumbingSystems&Design MARCH/APRIL 2006 PSDMAGAZINE.ORG
Cystoscopic rooms Among the various plumbing fxtures
requiredincystoscopicroomsarethefollowing:wall-mounted
clinicsinksequippedwithfushvalvesandbedpanwasherand
combinationfaucets;lavatoriesprovidedwithwater-supplyft-
tings and gooseneck spouts; and, in a separate adjacent room,
specimenwaterclosetandalavatory.Ifafoordrainisinstalled
in cystoscopy, it shall contain a nonsplash, horizontal-fow
fushingbowlbeneaththedrainplate.
Autopsy room Te autopsy room table is usually provided
with cold and hot-water supplies, with a vacuum breaker or
backfow preventer, and a waste line. It is necessary that the
plumbing designer consult with the table manufacturer and
the administrative authority regarding the requirements of the
autopsy room table. Drain systems for autopsy tables shall be
designed to positively avoid splatter or overfow onto foors or
back siphonage and for easy cleaning and trap fushing. Te
autopsy room is also usually equipped with a stainless steel or
vitreous china sink with hands-free fttings, a clinic sink and a
bloodtypefoordrain.Adjacenttotheautopsyroomawater
closet and a shower room are usually provided. Many autopsy
roomsareequippedwithwaste-disposalunitsintegralwiththe
sink.
Nourishment stations Tesestationsareusuallyprovidedon
eachpatientroomfoornearthenursestationforservingnour-
ishment between regularly scheduled meals. A sink, equipped
forhandwashingwithhands-freecontrols,anicemaker,anda
hot-water dispenser (optional) to provide for the patients ser-
viceandtreatmentshouldbeprovided.
Pharmacy and drug rooms Teplumbingfxturesforthese
roomsincludemedicineandsolutionsinks.Teseunitscanbe
counter-typeormadeofstainlesssteelorvitreouschinawitha
mixingfaucetandaswingspout.Asolidsinterceptorshouldbe
consideredforcompoundingareas.
Operating-room areas No plumbing fxtures or foor drains
are required in the hospitals operating room. However, the
scrubbingstationlocatedadjacenttotheoperatingroomshould
haveatleasttwoscrubsinks,usuallymadeofvitreouschinaor
stainless steel, furnished with hands-free water-supply fttings,
and equipped with gooseneck spouts. Tese sinks should be
largeanddeepenoughtoallowscrubbingofhandsandarmsto
theelbow.Asoiledworkroom,designedfortheexclusiveuseof
the hospitals surgical staf, should be located near the operat-
ingroomarea.Tisworkroomshouldcontainavitreouschina,
fushing-rim clinical sink, for the disposal of solids, with the
water-supplyfttingsconsistingofafush-valvebedpanwasher
andaseparatefaucetmountedonthewallabovethefxtureand
hand-washing facilities consisting of a vitreous china or stain-
less-steel lavatory with a gooseneck spout and equipped with
wrist-bladehandles.Substerileroomsshouldbeequippedwith
aninstrumentsterilizerandgeneral-purposesink.Teplumbing
designershouldconsultwiththeinstrumentsterilizermanufac-
turerforanyspecialrequirementsfortheequipment.Tegen-
eral-purpose sink can be countertop-mounted and equipped
withahands-freewater-supplyfttingwithagooseneckspout.
Recovery rooms Teroomsforthepost-anesthesiarecovery
ofsurgicalpatientsshouldincludeahand-washingfacility,such
as a vitreous china or stainless-steel lavatory equipped with a
gooseneckspoutandwrist-bladehandles;andavitreouschina,
fushing-rim, clinical sink for the disposal of solids, with the
water-supply ftting consisting of a fush valve and a separate
faucet mounted on the wall above the fxture with a vacuum
breaker. A bedpan washer should also be installed next to the
clinical sink. Te type of bedpan washer will depend upon the
hospitalsmethodofwashingandsterilizingbedpans.
Birthing rooms Eachbirthingroomshouldincludeavitreous
chinalavatoryprovidedwithagooseneckspoutandwrist-blade
handles or hands-free controls. Each labor room should have
accesstoawaterclosetandalavatory.Ashowershouldbepro-
videdforthelabor-roompatients.Teshowercontrols,includ-
ingpressure/thermostaticmixingvalve,shouldbelocatedout-
sidethewetareaforusebythehospitalsnursingstaf.Awater
closetshouldbeaccessibletotheshowerfacility.
Anesthesia workrooms Tis area is designed for the clean-
ing,testing,andstoringoftheanesthesiaequipmentandshould
containaworkcounter-mountedsink.Tesinkisusuallymade
of stainless steel. Te faucet should be of the gooseneck spout
designwithwrist-bladehandlesand/orhands-freecontrols.
Fracture rooms A large-size, vitreous china plaster, work
sink equipped with a combination water-supply ftting and
wrist-blade handles, gooseneck spout, and plaster trap on the
wasteline(locatedforconvenientaccess)shouldbeprovided.
Kitchens and Laundries
Teplumbingdesignershouldconsultwiththearchitectandthe
food-service consultant for kitchen equipment utility require-
ments. Typically, one of these people should provide location
and rough-in drawings for all kitchen equipment. Normally
required are toilet fxtures for kitchen staf, food preparation
sinks, hand-wash sinks, pot and pan-wash sinks, dishwashers,
glassware washers, foor drains, hose bibbs, mixing stations,
and grease interceptors. Kitchen grease traps shall be located
and arranged to permit easy access without the necessity of
enteringfoodpreparationorstorageareas.Greasetrapsshallbe
ofthecapacityrequiredandshallbeaccessiblefromoutsidethe
building without the necessity of interrupting any services. In
dietary areas, foor drains and/or foor sinks shall be of a type
that can be easily cleaned by the removal of a cover. Provide
foor drains or foor sinks at all wet equipment (such as ice
machines) and as required for the wet cleaning of foors. Te
location of foor drains and foor sinks shall be coordinated to
avoid conditions where the location of equipment makes the
removalofcoversforcleaningdifcult.Also,thekitchenequip-
mentmayrequireotherutilityservices,suchasfuelgas,steam,
andcondensate.
When considering laundry facilities, the plumbing designer
shouldconsultwiththearchitectandthelaundryconsultantfor
equipment utility requirements. Tese facilities require large-
capacity washers/extractors and dryers, presses, and folding
machines. Waste-water drainage may require lint intercepters.
Tese facilities are prime candidates for heat and water-recov-
ery systems. Also, the laundry equipment may require other
utilityservices,suchasfuelgas,steam,andcondensate.
Te hot-water temperatures required for these areas (100,
140, and 180F [38, 60, and 82C]) are discussed in Data Book,
Volume2,Chapter6,DomesticWater-HeatingSystems.
Laboratory Rooms
Laboratory sinks Mostofthetimearchitectsprovidethecoun-
tertopsandsinks,usuallymadeofepoxyorotheracid-resistant
materials, in their specifcations. However, occasionally the
plumbing designer is responsible for selecting the laboratory
sinks. Laboratory sinks should be acid resistant and can be of
stainless steel, stone, or plastic. Laboratory and cup sinks are
MARCH/APRIL 2006 PlumbingSystems&Design 59
C0N7INUINC DUCA7I0N: PIumbing Design for HeaIth Care FaciIities
currently available in epoxy resin, composition stone, natural
stone, ceramic or vitreous china, polyester fberglass, plastic,
stainless steel, and lead. Te lead type is not recommended
wheremercury,nitric,hydrochloricoraceticacidsareused.
Oftentheselaboratorysinksarefurnishedwiththelaboratory
equipment as rectangular sinks or cup sinks mounted in, or
as part of, counter tops and as cup sinks in fume hoods. Rules
of thumb that can be used when the sink sizes are not recom-
mendedbythelaboratorystafareasfollows:
1. Sinkswithacompartmentsizeof12167.5in.(304.8
406.4190.5mm)forgenerallaboratoryworkareas.
2. Sinkswithacompartmentsizeof182410in.(457.2
609.6254mm)forclassroomworkandtests.
3. Sinkswithacompartmentsizeof243612in.(609
914.4304.8mm)forwashinglargeequipment.
Tesinkitselfandsinkoutletshouldbechemicallyresistant,
aminimumof316stainlesssteel,andsodesignedthatastopper
or an overfow can be inserted and removed easily. Te outlet
shouldberemovableandhaveastrainertointerceptanymate-
rials that might cause a stoppage in the line. Unless an indus-
trialwatersystemisemployedthatisolatesthelaboratorywater
systemsfromthepotablewatersystem,viaacentralbackfow-
preventiondevice,allfaucetsshouldbeprovidedwithvacuum
breakers.Supplyfttingsfordistilledordeionizedwaterareusu-
allyeithervirginplasticortinlinedand,wherecentralsystems
are used, should be able to withstand higher pressures. Many
fttingtypes,especiallyPVC,canhandlepressuresuptobutnot
exceeding50psig(344.74kPa).Inthesecases,pressureregula-
tionisrequired.
Cup sinks Tesearesmall,36in.,39in.,or311in.(76.2
152.4 mm, 76.2 228.6 mm, or 76.6 279.4 mm) oval sinks
forreceivingchemicals,normallyfromacondensateorasupply
line.Teyaredesignedtoftintothecentersectionbetweenthe
tabletops;againstawall;oronraised,backledges.Tesesinks
arealsocommoninfumehoods.
Laboratory glass washers are usually included, either fur-
nishedbythelaboratoryequipmentsupplierorselectedbythe
plumbing designer. Automatic washers are available. In addi-
tiontowasteorindirectwasteservices,theseunitsrequirehot
water (usually 140F [60C] boosted to 180F [82C]) internal
to the unit, distilled or deionized water, and compressed air.
Manual-typeglassbottleandtubewashersmayalsoberequired
in these rooms. Tube washers may have manifold-type supply
fttingsusingcoldwateronly.Temanifoldscanbefttedwitha
numberofindividuallyserratedtipoutletsprovidedwithsepa-
ratecontrolsandvacuumbreakers.
Emergency showers should be included throughout and
locatedintheadjacentcorridorsoratthedoorexits.Teshow-
ersmustbeaccessible,requirenomorethan10storeach,and
bewithinatraveldistanceofnogreaterthan100ft(30.5m)from
thehazardrooms.Teshowerheadisadeluge-typeshowerwith
a1-in.(25.4mm)nominalcoldwater,stay-opendesign,supply
valveoperatedbyahangingpullrod,orachainandpullring,or
apullchainsecuredtothewall.Afoordrainmaybeprovided,
ifrequired.Iffoordrainsareprovided,trapprimersshouldbe
incorporated.
Eye and face-wash fountains are also required. Tese are
wallorcounter-mountedunitswithafoot-pedalorwrist-blade-
handle-operated, water-supply fxture; double side-mounted,
fullface-washoutlets;ordeck-mounted,hand-held(withhose)
face and body-spray units. Te latest edition of the ANSI stan-
dardforemergencyeyewashandshowerequipmentandlocal
codesshouldbeconsulted.Atemperedwatersupplyshouldbe
considered.
Laboratory service outlets forgas,air,nitrogen,vacuum,and
otherrequiredgasservicesmaybefurnishedaspartoftherelated
equipment under another contract or may be included in the
plumbing work. In either case, the plumbing designer should
beknowledgeableaboutthevarioustypesofserviceoutletcur-
rently available, the materials (or construction), and the usage
(diversity).Itisdesirabletohavebodiesofcastredbrass,brass
forgings,orbrassbarstockthatarespeciallydesignedforlabo-
ratory use and, where possible, made by one manufacturer.
Handles should be made of forged brass and provided with
screw-in-type, color-coded index discs. All outlets should be
properly labeled. Serrated tips should be machined from solid
stock or forgings. Te service fttings should be chrome plated
overnickelplatingorcopperplating.Teoutletsinfumehoods
should have an acid and solvent-resistant, plastic coating over
thechrome-platedsurfaceorbemadeofacid-resistantmateri-
als.Nonmetallicfttingsarealsoavailable.
Special Equipment
Dialysis machines Dialysismachinesrequireafunneldrainor
foorsinkandcold-waterhosebibbwithvacuumbreaker.
Heart-and-lung machines Heart-and-lung machines also
require a funnel-type drain. If the apparatus is located in the
operatingroom,anindirectwasteisrequired.
Electron microscopes Electronmicroscopesrequirefltered,
backfow-protected,coldwaterorcirculatedchilledwater.
Stills Stills for producing distilled water require cold water
withavacuumbreakerandfoorsinksorfunneldrains.
Sterilizers Sterilizers require an acid-resistant foor sink or
funnel drains, a backfow-protected water supply and some-
timessteamandcondensateconnections.
Film-processing equipment Film-processing (x-ray) areas
requireanacid-resistantfoorsinkorfunneldrainsforindirect
waste; and a hot, cold and/or tempered water supply operat-
ingbetween40and90F(4.4and32.2C).Drainpipingforany
photo-developing equipment should not be brass or copper.
Polypropylene,high-silica,cast-iron,corrosion-resistantpiping
and drains should be used. Silver recovery and neutralization
mayberequired;consultwiththelocalauthority.
Dental equipment Dentalareasshouldincludeconsoleser-
vices(water,air,medicalgas,nitrousoxideandwaste);andfor
oralsurgeryaseparatesurgicalvacuumsystemshouldbepro-
vided.
Teplumbingengineershouldalwaysconsultwiththeequip-
ment manufacturers authorized representative and the local
administrative authority, in order to determine the equipment
requirements and the acceptability under the jurisdictions
applicablecodes,duringthepreliminarydesign.
DrAInAGESySTEMSForLABorATorIES
Inadditiontotheconventionalsanitarydrainagesystems(those
foundinmostbuildings),specialsanitarydrainagesystemsmay
berequiredinhealth-carefacilities.
Insofar as possible, drainage piping shall not be installed
within the ceiling or exposed in operating or delivery rooms,
nurseries, food-preparation centers, food-serving facilities,
food-storageareas,centralservices,electronicdata-processing
areas,electricclosets,andothersensitiveareas.Whereexposed,
60 PlumbingSystems&Design MARCH/APRIL 2006 PSDMAGAZINE.ORG
overheaddrainpipingintheseareasisunavoidable,specialpro-
visionsshallbemadetoprotectthespacebelowfromleakage,
condensation,ordustparticles.
ACID-WASTEDrAInAGESySTEMS
Acid-waste drainage systems require special design criteria
becausethecorrosivesolutionsdemandspecialhandlingfrom
the actual work area to an approved point at which such acid
waste(andfumes)canbesafelyneutralizedanddischarged.Te
plumbingengineermustexerciseextremecareinthisregard.
Acid-resistant waste and vent systems are necessary where
acids with a pH lower than 6.5 or alkalis with a pH greater
than 8.5 are present. Tese special conditions are commonly
encountered in hospitals, research facilities, and laboratories.
Sinceacidfumesareoftenmorecorrosivethantheliquidacids
themselves,properdrainageandventingisimperative.
Nationally recognized standards for sanitary systems that
handle acid wastes and other reagents are set forth in model
plumbing codes; such systems are often further regulated by
local building and safety or health department requirements.
For these reasons, the plumbing engineer should check for all
specialdesignconditionsthatmayafecttheproject.
Strongacidsandcausticsmayenterthesanitary-wastesystem
in large quantities and at elevated temperatures. Tese sub-
stances can mix to form highly corrosive and even dangerous
compounds.Commonlaboratoryproceduresencourageneutral-
ization or fushing with copious amounts of water in order to
diluteandcoolthesechemicalstomoreacceptablelevels.How-
ever,theplumbingengineermustprotecttheacid-wastesystem
bydesigningforthemaximumhazardconditionsthatmightbe
broughtaboutbyanyhumanerror,poorhousekeeping,oracci-
dentalspillage.
CorroSIvE-WASTESySTEMSMATErIALS
Borosilicate glass pipe Sizesrangefrom1to6-in.(40to150-
mm) pipe. Mechanical joint, fame resistance, and clear pipe
allowforeasyvisualinspectionandhighcorrosionresistance.
High-silicon cast iron Sizes range from 1 to 4-in. (40 to
100-mm) pipe. Mechanical joint, fame resistance, high corro-
sionresistance,frestopatfoorpenetrationequaltocastiron.
More fragile and heavier than standard-weight cast iron and
easier to break in the feld. Excellent application for moderate
tohigh-budgetproject.
Polypropylene Sizesrangefrom1to6-in.(40to150-mm)
pipe. Mechanical or heat-fusion joints. Mechanical joints are
notrecommendedforstraightrunsorsizesover2in.(50mm);
they should be used to access p-traps or other maintenance
areas.Flameresistantandacceptablewithinmostjurisdictions
(meets 25/50 fame/smoke criteria), newer UL listed methods
are close to glass in cost. Consult local authority for approval.
Lightweightandeasytoinstall.Goodapplicationformoderate
acidsatlowtemperatures.Mustbeinstalledbyqualifedtechni-
cians. Inexpensive compared to borosilicate glass or high-sili-
conecastiron.
Double-containment waste piping With ever-increasing
pressuretoprotectourenvironment,double-containment(pipe
within a pipe) systems have become a consideration. Usually
made of polypropylene inside and PVC or fberglass outside.
Systemsshouldbepitchedtowardacontainmentvaultforcol-
lectionofleakingfuid.
Alarm systems canbeemployedtodetectleaksatthecollec-
tion basin or, if the budget and the nature of the liquid allow,
sensorscanbeinstalledbetweenthepipewallsthatcanpinpoint
theoriginalleaklocation.Telattercouldreducetheamountof
excavationorexplorationrequiredtofndtheleak.
DISCHArGEToSEWErS
Many local jurisdictions require that the buildings sanitary-
sewer discharge be at an acceptable pH level before it can be
admittedintoasanitary-sewagesystem.Insuchcases,itisrec-
ommended that a clarifying (or neutralizing) tank be added to
the sanitary system. Small ceramic or polypropylene clarifers
with limestone can be located under casework for low fow
rates;however,sufcientspacemustbeallowedabovetheunit
for servicing. Unless properly maintained and monitored, this
typeofsystemcanberenderedinefective.Largeclarifersand
neutralizers may be regulated by the requirements of a local
industrial-wastedepartment.
ACIDIC-WASTEnEuTrALIzATIon
Te lower the pH number, the
higher the concentration of acid.
Discharging high concentrations
of acid into a public sewer may
cause considerable corrosion to
piping systems and eventual fail-
ure. Most local authorities do not
allowacidwastestobedischarged
to a public sewer without some
formoftreatment.
Te neutralization of acidic
wastes is generally and most eco-
nomically dealt with through an
acid-neutralizationtank.Anacid-
neutralization tank may be con-
structed of polyethylene, molded
stone, stainless steel, or another
acid-resistant material. Tanks are
sizedtoprovideadwelltimeof2to
3h(refertoTable2).Limestoneor
marblechipsflltheinteriorofthe
tank,helpingtoneutralizeincom-
ingacidwastes.Chipsmaybe1to
3in.(25.4to76.2mm)indiameter
andshouldhaveacalciumcarbonatecontentinexcessof90%.
AdischargepHsensorandroutinemaintenanceschedulemust
beprovidedtoensurethatthesystemoperatesproperly.
ACID-WASTESoLIDSInTErCEPTor
Aswithmanysewersystems,itisimpossibletocontrolallmate-
rials discarded to the drain system. Unless building efuent is
controlled,manyunwanteditems,suchasglassfragmentsand
needles, will fnd their way to the neutralization tank, thereby
cloggingthelimestoneormarblechips.
When this happens, replacement of the chips is required.
One way to prolong chip life is to install an acid-waste solids
interceptor immediately upstream of the neutralization tank,
although maintenance of the interceptor may have to be done
quitefrequently.
ACID-WASTEMETErInGDETAIL
Many local authorities require some means of sampling efu-
ent from industrial, institutional, and laboratory buildings. An
example of a device used for this purpose is a sampling man-
hole.Tisunitisinstalledasthelastcomponentbeforeneutral-
table 2 Acidic-Waste Neutralization
Tank Sizing Table
Number of
Lab Sinks
gal (L)
2 5 (18.9)
4 15 (56.8)
8 30 (113.6)
16 55 (208.2)
22 75 (283.9)
27 90 (340.7)
30 108 (408.8)
40 150 (567.8)
50 175 (662.4)
60 200 (757.0)
75 275 (1,040.9)
110 360 (1,362.6)
150 500 (1,898.5)
175 550 (2,081.8)
200 650 (2,460.3)
300 1200 (4,542)
500 2000 (7,570)
600 3000 (11,355)
Note: For commercial and industrial
laboratories, the number of lab sinks should be
multiplied by a 0.5 use factor.
MARCH/APRIL 2006 PlumbingSystems&Design 61
C0N7INUINC DUCA7I0N: PIumbing Design for HeaIth Care FaciIities
ized acidic wastes or treated industrial wastes are discharged
to a public sewer. Tere are as many types of sampling point
requirementsastherearemunicipalsewerauthorities.Consult
localcodeauthoritiesforindividualrequirements.
TrAPSForLABorATorySInkS
Tetrapisrecognizedbymostplumbingengineersastheweak-
est link in the acid-waste system. Te trap must be acid resis-
tant.Ifstrongacidsandsolventscollectinanordinarytrap,fail-
ureofthesystemwilloccur.Treetypesofacid-wastetrapsare
currently in common use: p-traps, drum traps, and centrifugal
drumtraps.(Runningands-trapsarenotallowedbymanylocal
plumbingcodesbecauseofthepotentialfortrapsiphoning.)
1. P-trapsmaintainawatersealtokeeptheacidfumesfrom
reenteringtheworkarea.
2. Drum trapsprovideagreaterwatersealandarefrequently
usedtoseparateeitherpreciousmetalsorothermatter
beforetheyenterthedrainagesystemtobecomelostor
causeastoppageinthesink.Drumtrapswithremovable
bottomsshouldbeinstalledhighenoughabovethefoor
forservicing.P-traps,includingsomeofthesimpledrum
traps,caneasilybeback-siphonediftheheadpressuresare
extreme.
3. Centrifugal drum trapsaredesignedtopreventback-
siphonageconditions.
LABorAToryWASTEAnDvEnTPIPInG
Sizingforunder-tablewasteandventpiping,asdeterminedby
thelocalplumbingcodes,shouldbesuitablefortheinstallation
and allow for future expansion. Approved corrosion-resistant
pipingshouldbeusedforventpipingaswell,sinceacidfumes
are also highly corrosive. Space is often limited under tables
andinventareas.Tespace-savingfeaturesofmechanicaljoint
pipinghaveproventobeusefulinmanyinstallations.
Note: When fusion-joint, plastic piping systems are used,
mechanicaljointsshouldbeinstalledattrapsandtraparmsfor
maintenancereasons.
Specialisland(orloop)ventingisfrequentlyusedwhencabi-
nets or work tables are located in the center of the laboratory
area.
Tetransportatingofacidwaste,aboveandbelowtheground,
must be done in approved, corrosion-resistant piping (accept-
able to the local administrative authority) and continued to a
suitable point where neutralization can occur or where suf-
cientwaterorchemicalscanbeintroducedtobringthepHlevel
of the solution to an acceptable level. Acids below a pH of 6.5
normallymaynotbeadmittedintothesanitary-sewagesystem
or emitted into surrounding soil, polluting (or degenerating)
local ground water. High-silicon cast iron with hub-and-spigot
jointsmaybecaulkedwithtefon,orneoprenegasketsmaybe
usedforsealing.Tistypeofjointwillallowfexibilityand,when
properly supported, is particularly recommended on the hori-
zontal runs where the expansion and contraction of pipe from
heated chemicals can cause leaking. Plumbing codes require
proper bed preparation and careful backflling on all below-
groundpiping,particularlyplasticpiping.
Teplumbingengineershouldcheckthemanufacturersrec-
ommendationsinordertoevaluatetheseverityofthechemicals
to be used. A listing of the common chemicals and how these
substancesreactwiththevariousmaterialsmustbeconsidered
bythedesigner.
WATEr-SuPPLySySTEMS
A domestic-water supply of adequate fow volume and pres-
suremustbeprovidedforalltheplumbingfxturesandrelated
equipment. Systems typically encountered in these types of
facilityareasfollows:
1. Potable-watersystems.
A. Coldwater.
B. Hotwater(atvarioustemperatures).
C. Chilledwater.
D. Controlled-temperature(tempered)water.
E. Hotwaterrecirculation.
2. Non-potablewatersystems.
3. Pure-watersystems.
A. Distilledwater.
B. Deionized(ordemineralized)water.
C. Reverseosmosis.
Health-care facilities should have dual domestic-water ser-
vices installed to ensure provision of an uninterrupted supply
of water. Te design should consider water-conservation pro-
visions. Many local jurisdictions have strict water-conserva-
tion laws in efect. Water recycling may be a consideration for
use in landscaping, etc., depending on local code and health-
departmentregulations.(Formoreinformation,seeData Book,
Volume2,Chapter2,Gray-WaterSystems.)
Water supply through a tank (suction or gravity type) should
beconsideredbytheplumbingengineerwhenthewater-supply
source may be subjected to some unusual demands, pressure
fuctuations,and/orinterruptionsthatwillcauseasuddenexces-
sivedrawandpressurelossonthemainsystem.Tetankwillact
asabufer.Inadequatefowandpressurerequirethedesignofa
water-storagetankand/oraboosterpumpforthewater-supply
system.Excessivepressurefuctuationsarehighlyundesirablein
medical-researchlaboratories.Whensuchfacilitiesaresupplied
fromstreetpressuresystems,theengineermayprovidepressure-
reducingvalvesonthebranchlines,oragravitytanksystem.
Use of diversity factors for sizing the water systems must be
carefully analyzed by the designer. Medical-school laboratory
classrooms have higher rates of simultaneous use than most
researchlaboratories.Emergencyrooms,out-patienttreatment
rooms,andoperating-roomwash-upareasalsohavehighrates
ofsimultaneoususe.
Extreme care must be taken in order to protect the potable-
water supply from contamination (cross connection). When
anindustrial(non-potable)systemisnotpresent,theengineer
shouldspecifytheappropriatetypeofvacuumbreakers(neces-
saryforeachfxturebelowtherimconnection),hose-endoutlet,
andanaspiratororotherserrated-tiplaboratoryoutlet,whether
theyarerequiredbythelocalplumbingregulationsornot.Te
vacuum breakers provided for fume-hood outlets should be
locatedoutsidethehood.Built-in(orintegral)vacuumbreakers
arepreferredtothehose-endtypeunits.
PoTABLE-WATErSySTEMS
Coldwatershouldbeprovidedatallrequiredlocations.Tehot
water should be generated with the most economical heating
mediumavailable.
With todays technology, several reliable methods can be
applied to produce and store domestic hot water. Refer to
ASPEsDomestic Water Heating Design Manual andASPE Data
Book Volume2,Chapter6,DomesticWater-HeatingSystems,
62 PlumbingSystems&Design MARCH/APRIL 2006 PSDMAGAZINE.ORG
forin-depthexplanationsofdesignmethodsforhot-watersys-
tems and a discussion of the various hot-water systems avail-
able. When large dump loads are anticipated (kitchens and
laundries), storage of hot water is recommended. Hot-water
usageinpatient-careareasrequiresconsiderationofwatertem-
peratureandbacterialgrowth.Temostcommonwater-borne
bacteriumofconcernisLegionellapneumophila.
Recommended water temperatures for specifc applications
areasfollows:
1. Patient-careandhospitalgeneralusagerequireswatertem-
peraturesbetween105and120F(40.5and49C),except
wherethelocalplumbingcodesorotherregulationsrequire
othermaximumtemperatures.Hot-waterdistribution
systemsservingpatient-careareasshallbeunderconstant
recirculationtoprovidecontinuoushotwaterateach
hot-wateroutlet.Tetemperatureofhotwaterforbathing
fxturesandhand-washlavatoriesshallbeappropriatefor
comfortableusebutshallnotexceed120F(49C).
2. Kitchengeneralusagerequires140F(60C)tofxtures,
exceptthedishwasherssanitizingcycle.Tesanitizing
cyclerequires180to190F(82to88C)tothedishwasher,
with180F(82C)minimumrequiredatthedishrack.
(Consultlocalhealth-departmentregulations.)Also,some
healthdepartmentssetamaximumtemperatureof105to
120F(40.5to49C)forhand-washinglavatories.
3. Laundryfacilitiesshouldbesuppliedwithtwowatertem-
peratures,140F(60C)forgeneralusageand160F(71C)
minimumtowashers/extractorsforlaundrysterilizations.
Providing a point-of-use booster heater for high-temperature
applicationsinsteadofacentralwater-heatersystemisoftenmore
economical.
Aclosedsystemofchilledwatermayberequiredforthecool-
ingofelectronmicroscopesandx-raytubesandshouldbeofa
recirculatingdesign.
Film processors operate at a normal range of 40 to 30F (4.4
to 1.1C). Some models do require controlled water tempera-
tureforflmprocessing.Dependingonthequalityofthewater
supply,a5to75-fltermayberequired.
A thermometer should also be provided on the outlets of
waterheatersandthermostaticallycontrolledvalves.Apressure
regulator,gauge,andfowmetermayalsobedesiredontheinlet
sideofpressure-sensitiveequipment.
non-PoTABLEWATErSySTEMS
Non-potable water systems are usually employed in areas
havingmultiplewaterrequirementsthatcouldcontaminatethe
potable-water supply. Areas in this category include: fushing-
rim foor drains in animal rooms, all outlets in autopsy rooms,
outlets in isolation rooms, and all outlets in infectious-disease
andtissue-culturerooms.Tesesystemsnormallyusereduced-
pressure-type backfow preventers as the means to protect the
potable-water system. Hot water, when required, may be pro-
vided by a separate generator supplied from the non-potable
watersystem.
PurE-WATErSySTEMS
Pure water is the term generally used to describe water that
isfreefromparticulatematters,minerals(solubleions),bacte-
ria, pyrogens, organic matters, and dissolved gases, which fre-
quently exist in the potable water supply. Pure-water systems
areusuallyrequiredinthehospitalspharmacy,central-supply
room,laboratories,andlaboratory-glasswarewashingfacilities.
Tere are two basic types of pure water available in hospital
facilities: bio-pure water (water containing no bugs or other
life forms) and high-purity water (pure water that is free from
minerals,dissolvedgases,andmostparticulatematters).Refer
to ASPE Data Book, Volume 2, Chapter 11, Water Treatment,
Conditioning, and Purifcation, for additional information on
waterpurity.
Waterpurityismosteasilymeasuredasspecifcresistance(in
ohm-centimeter [-cm] units) or expressed as parts per mil-
lion(ppm)ofanionizedsalt(NaCl).Tetheoreticalmaximum
specifcresistanceofthepurewaterisgivenas18.3M-cmat
77F(25C).Tiswaterpurityisdifculttoproduce,store,and
distribute.Tiswaterisstarvedforimpuritiesandconstantly
attempts to absorb contaminants. It is important to note that
thespecifcresistanceofthepurewaterisindicativeonlyofits
mineral contents and in no way shows the level of bacterial,
pyrogenic, or organic contamination. An independent labora-
toryanalysisshouldbemade,wheneverpossible.
Tefvebasicmethodsofproducingpurewaterareasfollows:
distillation, demineralization, reverse osmosis, fltration, and
recirculation.Dependinguponthetypeofpurewaterrequired
in the facility, one (or more) of these methods will be needed.
Under certain conditions, a combination of several methods
maybenecessary.
1. Distillation producesbio-purewater,whichiscompletely
freefromparticulatematters,minerals,organics,bacte-
ria,pyrogens,andmostofthedissolvedgasesandhasa
minimumspecifcresistanceof300,000.Animportant
considerationinthiscaseisthatthewaterisfreefrombac-
teriaandpyrogencontamination,whichisdangerousto
thepatients,particularlywhereintravenoussolutionsare
concerned.Bio-purewaterisneededinthehospitalsphar-
macy,central-supplyroom,andotherareaswherethere
maybepatientcontact.Bio-purewatermayalsobedesired
incertainspecifclaboratoriesattheownersrequestandas
afnalrinseinthelaboratorysglasswarewasher.
Tetypicalwater-distillationapparatusconsistsofan
evaporatorsection,aninternalbafesystem,awater-
cooledcondenser,andastoragetank.Tebestmaterialfor
itsconstructionisapureblock-tincoatingforboththestill
andthetank.Teheatsources,inorderofpreferencebased
oneconomyandmaintenance,areasfollows:steam,gas,
andelectricity.Testillmaybeoperatedmanuallyorauto-
matically.Tedistilledwatermaybedistributedfromthe
storagetankbygravityorbyapump.Adrainisrequiredfor
systemdrainageandfushing.Onstillslargerthan50gph
(189.3L/h),acoolingtowershouldbeconsideredforthe
condenserwater.
2. Demineralization, sometimescalleddeionization,pro-
duceshigh-puritywaterthatiscompletelyfreefromminer-
als,mostparticulatematters,anddissolvedgases.Depend-
ingupontheequipmentused,itcanhaveaspecifcresis-
tancerangingfrom50,000tonearly18M.However,it
couldbecontaminatedwithbacteria,pyrogens,andorgan-
ics(thesecontaminantsmaybeproducedinsidethedemin-
eralizeritself ).Demineralizedwatercanbeemployedin
MARCH/APRIL 2006 PlumbingSystems&Design 63
C0N7INUINC DUCA7I0N: PIumbing Design for HeaIth Care FaciIities
mostlaboratories,thelaboratorysglass-washingfacilities
(asafnalrinse)andasthepre-treatmentforstillfeedwater.
Tetypicaldemineralizerapparatusconsistsofeither
atwo-beddeionizingunit(witharesistivityrangeof
50,000to1M)oramixed-beddeionizingunit(witha
resistivityrangeof1to18M).Tecolumnsareofaninert
materialflledwithasyntheticresin,whichremovesthe
mineralsbyanionizationprocess.Sincetheunitoperates
onpressure,astoragetankisnotrequiredorrecommended
(asbacteriawillgrowinit).Ademineralizermustbechemi-
callyregeneratedperiodically,andduringthatregeneration
timenopurewaterisproduced.Ifacontinuoussupplyof
purewaterisneeded,abackupunitshouldbeconsidered
bytheengineer,astheregenerationprocesstakesseveral
hours.Teregenerationprocesscanbedonemanuallyor
automatically.Anatmospheric,chemical-resistantdrainis
required.High-fowwaterisrequiredforbackwashduring
theregeneration.
3. Reverse osmosis (RO) producesahigh-puritywaterthatdoes
nothavethehighresistivityofdemineralizedwaterandis
notbio-pure.UndercertainconditionsanROprocesscan
ofereconomicadvantagesoverdemineralizedwater.In
areasthathavehighmineralcontents,anROprocesscanbe
usedasapre-treatmentforademineralizerorstill.
Tereareseveraltypesofreverseosmosisunitscurrently
available.Unitsconsistofasemipermeablemembrane,in
eitherarollformoratubecontainingnumeroushollow
fbers.Tewateristhenforcedthroughthesemipermeable
membraneunderhighpressure.Adrainisrequiredwith
thesesystems.
Note:Chlorinemustberemovedfromthewater,otherwise
itwilldestroytheROmembrane.
4. Filtration Varioustypesofflterarecurrentlyavailable
toremovetheparticulatemattersfromthewaterasapre-
treatment.Dependinguponthetypeofflter,adrainmay
berequired.Bacteriamaybeeliminatedthroughultraviolet
sterilization.
5. Recirculation High-puritysystemsshouldbeprovided
withacirculationloop.Dead-endlegsshouldbeavoided
wheneverpossibleorlimitedto50in.(1.52m). System
designvelocityshouldbebetween4and7fps(1.22and2.13
m/s)soastodiscouragebacteriaaccumulationandprovide
transportbacktoanultravioletsterilizerandfltrationfor
removal.
Pure-water piping system materials Water-treatment
system components are selected to remove various impurities
fromtheinfuentwater.Connectingvarioussystemcomponents
together involves the use of interconnecting piping. Te use of
this piping should not contribute to adding any such impurity
backintothetreatedwater.
Selection of piping-system materials is determined by the
application intended, the availability of the material, and the
costofthematerial.Pure-waterapplications,suchasexistinthe
health-careindustry,canbeverysensitivetothepipingmeth-
odsselected.
Generalpure-waterpipingrequirementsinclude:
1. Inertmaterialsmustnotleachcontaminationintowater.
2. Cleanjoiningmethodsavoidsolvents,lubricants,and
crevices.
3. Nomaterialerosionmustnotfakeofparticles.
4. Materialshouldnotenhancemicroorganismgrowth.
5. Materialshouldbesmooth,crackandcrevice-free,and
nonporous.
6. Avoiddeadlegssystemshouldhavecontinuousfow
throughpiping.
7. Providechemicalcleaningconnections.
8. Install(slope)withfuturecleaninganddisinfectionin
mind.
Awidevarietyofpipingmaterialsareavailableonthemarket
today.Teirpropertiesandcostcoverawiderange.
Common pure-water materials
1. Stainlesssteelvariousgrades(304L&316L).
2. Aluminum.
3. Tin-linedcopper.
4. Glassorglass-linedpipe.
5. PVC/CPVCPolyvinylchloride/chlorinatedpolyvinylchlo-
ride.
6. Polypropylene.
7. Polyethylene.
8. ABSAcrylonitrilebutadienestyrene.
9. PVDFPolyvinylidenefuoride.
Metal pipe Aluminum, tin-lined copper, and stainless-steel
pipe have all been used in pure-water treatment systems. Tin-
lined pipe was once the material of choice in ultra-pure water
systems. However, it does leach tin and eventually copper into
the process fuid. Methods of joining tin-lined pipe can also
leavenon-smoothjointswithcrevices.
Aluminum pipe has also been used in pure-water systems.
Pure water creates an oxide layer inside the pipe that continu-
allyerodes,producingparticlesandaluminuminthewater.
Stainlesssteelhasbeenusedextensivelyinhigh-puritywater
systems.Itcanbejoinedwiththreads,buttwelded,fanged,or
manufactured with sanitary-type connection ends. Because
it can use sanitary joints and can handle steam sterilizing, the
sanitary-typeconnectionmethodhasbeenusedinmanyphar-
maceutical applications. However, experience has shown that
even the best grades of stainless steel, with the best joints, still
leachmaterialfromthemetalthatcancauseproblemsincriti-
calwatersystems.
Glass or glass-lined pipe Glasspipinghasbeenusedinsome
special laboratory applications but, because it is fragile and
doesleachmaterialintothewater,itisnotgenerallyconsidered
applicableforhigh-puritywatersystems.
PVC PVC pipe has been used on equipment and in piping
systems successfully for many years. Advances in technology,
especially in electronics, have now raised questions about the
truepurityorinertnessofPVC.
PVC pipe contains color pigments, plasticizers, stabilizers,
and antioxidants that can all leach out of the plastic and into
ultra-purewater.Rememberthat18,000,000-qualitywateris
highlyaggressive.WhenPVCpipeismade(extruded),bubbles
of air exist, some of which are covered over with a thin flm of
PVContheinteriorwallsofthepipe.Asthepipeages,thesethin
coveringswearaway,exposingsmallholeswhichthenserveas
64 PlumbingSystems&Design MARCH/APRIL 2006 PSDMAGAZINE.ORG
debris-collecting or microorganism-breeding sites, not to men-
tion the contribution of PVC particles and the potential release
of organic dispersants, stabilizers, etc., originally trapped in
these bubbles (holes).
Joints, either solvent welded or threaded, can leave crevices
for the accumulation of particles and bacteria. Solvents from the
weld can also leach into the water.
Premium grades of PVC, which reportedly have fewer leach-
ables than standard PVC, are now being marketed.
CPVC is a special high-temperature PVC that has similar ero-
sion and leachable characteristics.
Polypropylene Polypropylene is a very inert, strong piping
material. However, in the manufacture of the pipe antioxidants
and other additives are used to control embrittlement. Tese
additives are potential sources of contaminants that can leach
into the water. However, a virgin material with no leachable
products is now available.
Polypropylene pipe shows good ability to withstand both cor-
rosive chemicals and high temperatures, up to 220F (104C).
Te natural toughness of the material minimizes damage to
pipe during installation and service.
Polypropylene is generally joined by the butt-fusion method,
resulting in smooth joints.
ABS Acrylonitrile butadiene styrene (ABS) plastic pipe has
been used in the primary stages of water-treatment systems
because of relatively low cost and ease of installation.
ABS has some of the same contamination leach problems as
PVC. In its manufacture, pigment dispersants, surfactants, sty-
rene, and other additives are used that can leach into water over
time. Hydrogen peroxide (used for system cleaning) will also
attack ABS plastic.
PVDF Tere are numerous types of high-molecular-weight
fuorocarbon pipes on the market, SYGEF, KYNAR, and HALAR,
to name a few. Polyvinylidene fuoride (PVDF) plastic can be
extruded without the use of additives that can leach out later.
Te diferent polymerization techniques used by each manu-
facturer can produce slightly diferent properties.
PVDF pipe is currently considered to be the state of the art
in pure-water piping systems. It has exceptional chemical resis-
tance; temperature range, 40 to 320F (40 to 160C); impact
strength; resistance to UV degradation; abrasion resistance; and
smooth, clean, inside surfaces that discourage the collection of
bacteria and particles. Most laboratory test reports show virtu-
ally zero leachables from PVDF piping systems.
PVDF pipe is joined by the butt-fusion method, resulting in
clean, smooth joints.
When system pressures exceed 70 psig (482.6 kPa) or tem-
peratures exceed 75F (24C), plastic piping system manufac-
turers should be consulted for compatibility. Polypropylene
or PVDF-lined metal piping systems may be incorporated to
meet pressures up to 150 psig (1034.2 kPa).
MARCH/APRIL 2006 Plumbing Systems & Design 65
C0N7INUINC DUCA7I0N
1. High-siIicon cast iron pipe is _________ than standard
weight cast iron pipe.
a. lighter
b. heavier
c. more costly
d. less costly
2. Fixture-unit vaIues for unique xtures found in
heaIth-care faciIities can be _________.
a. estimated
b. assigned by the authority having jurisdiction
c. higher then anticipated
d. found in Table 2-2
3. 7he theoreticaI maximum specic resistance of pure
water is _________ ohm-centimeter units at 77
o
F.
a. 12.6
b. 16.8
c. 18.3
d. 20.2
4. Hand washing Iavatories are not required in _______.
a. family waiting rooms
b. janitors closets
c. outpatient services areas
d. nurses stations
5. A review of appIicabIe code requirements is ________.
a. always required
b. is under the jurisdiction of the Joint Commission of
the Accreditation of Hospital Organization (JCAHO)
c. restricted to local codes only
d. is not necessary for the experienced plumbing
engineer
6. When referring to acid waste, the Iower the pH
number, the _________ the concentration of acid.
a. lower
b. higher
c. more neutral
d. none of the above
7. It is common for architects to Iocate the piping shafts
and the spaces in direct conict with the structuraI
framing because _________.
a. they do not know any better
b. it serves their purpose
c. the plumbing designer has not given the architect
direction regarding space requirements
d. none of the above
8. What type of vent system is used on Iaboratory sinks
that are Iocated in the center of Iaboratory areas!
a. end vent
b. stack vents
c. loop vents
d. crown vents
9. What is the size, in Iiters, of an acid waste
neutraIization tank that serves 75 Iaboratory sinks!
a. 1,020.9
b. 1,040.9
c. 1,050.9
d. 1,060.9
10. 7his chapter discusses _________.
a. the requirements of health care facilities
b. the provisions that may be encountered by the
plumbing professional in the design of a health care
facility
c. nursing homes, medical schools, and medical
laboratories
d. energy codes as they apply to medical facilities
11. X-ray areas require _________.
a. tempered water
b. corrosion-resistant piping and drains
c. silver recovery
d. a and b
12. Which of the foIIowing piping materiaIs is not
commonIy used for the distribution of pure water!
a. aluminum
b. CPVC
c. copper
d. PVDF
Doyoufnditdifculttoobtaincontinuingeducationunits(CEUs)?
Is it hard for you to attend technical seminars? Trough Plumbing
Systems&Design(PS&D),ASPEcanhelpyouaccumulatetheCEUs
required for maintaining your Certifed in Plumbing Design (CPD)
status.
ASPEfeaturesatechnicalarticleineveryissueofPS&D,excerpted
from its own publications. Each article is followed by a multiple-
choicetestandasimplereportingform.
Readingthearticleandcompletingtheformwillallowyoutoapply
to ASPE for CEU credit. For most people, this process will require
approximately1hour.Anominalprocessingfeeischarged$25for
ASPE members and $35 for nonmembers (until further notice, the
member fee is waived). If you earn a grade of 90% or higher on the
test,youwillbenotifedthatyouhavelogged0.1CEU,whichcanbe
applied toward the CPD renewal requirement or numerous regula-
tory-agencyCEprograms.(Pleasenotethatitisyourresponsibilityto
determinetheacceptancepolicyofaparticularagency.)CEUinfor-
mationwillbekeptonfleattheASPEofcefor3years.
No certifcates will be issued in addition to the notifcation letter.
You can apply for CEU credit on any technical article that has
appeared in PS&D within the past 12 months. However, CEU credit
onlycanbeobtainedonatotalofeightPS&Darticlesina12-month
period.
Note: In determining your answers to the CE questions, use only
the material presented in the continuing education article. Using
otherinformationmayresultinawronganswer.
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
CE QuestionsPlumbing Design for Health Care Facilities (PSD 132)
66 PlumbingSystems&Design MARCH/APRIL 2006 PSDMAGAZINE.ORG
P
S
D
1
3
3
Reflecting
Pools and
Fountains
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
MAY/JUNE 2006
PSDMAGAZINE.ORG
InTRODuCTIOn
Refectingpoolsandfountainsprovidevisualandauditoryplea-
sure, add charm to garden areas, and provide a retreat area in
which to rest and relax. Fountains generate sound and provide
a cooling efect on hot summer days. Fountains may be self-
contained units or pre-engineered kits or they may be custom
designedandbuilt.Self-containedfountains,consistingofpools,
pumps, valves, lights, and other hardware, are shipped assem-
bled,andtheadditionofwaterisallthatisnecessarytoputthe
fountain into normal operation. No permanent connections to
theplumbingsystemarerequired.Pre-engineeredfountainkits,
complete with equipment, need only assembly and hook-up to
thewater-supply,drainage,andpowersources.
Plumbingengineers,architects,andlandscapearchitectsare
all involved in the creation of display fountains and refecting
pools. Te architects are concerned with the overall aesthet-
ics, whereas the engineers must be familiar with the available
fountain equipment and the technical details of each compo-
nent if they are to design systems that will achieve the desired
displayefects.Teplumbingengineershouldworkcloselywith
thearchitectandthelandscapearchitecttoachievethedesired
display.Inaddition,thesystemsshouldbedesignedwithprovi-
sionsforcleaning,watertreatment,andmaintenance.Custom
fountains providing small or large water displays with almost
anydesireddecorativeefectsarediscussedinthischapter.Also
included are the technical details of pool design; mechanical
equipment,includingspraysystems;andoperationandmain-
tenance.
Teengineermustalsobeawarethatthefountainisusuallyrep-
resentedonasetofarchitecturaldrawingsasanundefnedspace
or a rendering. It is also usually the last item to be coordinated.
Whatthismeansisthattheengineerusuallydesignsthefountain
in its entirety, including the water efect and its infuence on the
surroundingarea.Ten,he/sheneedstoquickly(andaccurately)
selectthenozzles,determinefowrates,selecttheequipment,try
to get space for the equipment, coordinate with the other disci-
plinesinvolved,thencoachcontractors,wholookuponafountain
asaglorifedswimmingpool.Whenallthisisdone,however,the
engineercanlookuponabeautifulpieceofengineeredartthatwill
mostlikelyneverbeduplicatedandcanbeproudtoclaimitashis/
herwork.
POOLDESIGn
GEnERALCOnSIDERATIOnS
A number of general items of information should be kept in
mindwhendesigningafountain.
For an engineer or designer, the most important issue sur-
rounding any body of water is safety. Tere is always a risk
attached to a water feature. It is not the intent of this chapter
toacquainttheengineerwithdrowningandentrapmentissues,
but the engineer is encouraged to study the available codes
and standards regarding swimming pools and spas and apply
themasnecessary.Manyjurisdictionsregard18in.(457.2mm)
ofwaterasthemaximumdepthallowedwithoutsevereaccess
restrictions,suchasrailings,fences,andgates.
From a mechanical, operating perspective, the most impor-
tantthingistolocateallpumpstoensurefoodedsuctionlines.
If at all possible, locate the pumps so that the operating water
levelofthefountainisabovethesuctioninletofthepump.Tis
helpstopreventcavitationandtoensurethatthepumpprimes
quickly.
Paintingthepoolinterioradarkcolorhelpstoconcealpiping,
lighting,cable,junctionboxes,andotherequipmentlocatedin
thepool,and,inaddition,providesrefectivequalities.Butthe
dark color tends to cause an increase in water temperature by
absorbingthesunsheat.Tis,inturn,createsarequirementfor
morechlorine.Tinorfne-mistsprayefectsaredifculttosee
against light colors, mixed colors, or lace-type backgrounds. A
massivedisplayshouldbeusedundertheseconditions.
Te construction of pools at or below grade level creates a
potential problem with leaves and other debris blowing into
thepool,therefore,thisshouldbeavoided.Refectingpoolsand
fountains may be installed above or below grade. Above-grade
fountainsofertheadvantageofaddingmoreheighttothewater
display.Multilevelpoolsprovidethepossibilityofhavingnumer-
ouswaterfalldisplayswithonlyonewatersource.
Aeratingnozzlesthatuseaventuriactiontoentrainairintothe
waterstreamcancauseawaveactionincircularpools.Insuch
cases,surgecollarsorunderwaterbafesshouldbeinstalledto
minimizethisaction.
Water will splash horizontally approximately one half the
height of the water display except where wind is a problem.
Since wind can push water long distances, it is important to
locatenozzlessothatthesplashandwindefectwillnotcreate
undueproblems.Itmaybeadvisabletoprovideawindcontrol
tolowertheheightofthedisplayortoshutofthesystemwhen
thereistoomuchwind.
Waterhittingwatercreatesalotofnoise.Terearetimesand
locations when this is desirable. When the noise is too loud,
however,itcanbereducedbylocatingvarioustypesofplanting
aroundapool.
MuLTILEVELPOOLS
Multilevel and multiple pools involve special considerations,
which, if taken into account, do not present any difculty. If
theseconsiderationsarenottakenintoaccount,however,disas-
tercanresult.
Te amount of fow over a waterfall is determined by the
height of the water fowing over the weir. Tis height over the
weiristhesameastheheightofthepoolbehindtheweir.When
thepumpsstop,thiswaterwillallcomeovertheweirandspill
intothepoolbelow.Tewaterintheair(i.e.,thewaterfall)will
alsocometorestinthelowerpool.Telowerpoolmustbesized
COnTInuInG EDuCaTIOn
Reflecting Pools and Fountains
Reprinted from American Society of Plumbing Engineers Data Book Volume 3: Special Plumbing Systems, Chapter 5: Refecting Pools and
Fountains. 2000, American Society of Plumbing Engineers.
PlumbingSystems&Design MAY/JUNE 2006 PSDMAGAZINE.ORG
to accommodate this extra water. For the water in the air, the
depthovertheweirtimestheheightofthewaterissufciently
accuratetocalculatethevolume.
Multilevel pools should have some method of draining the
upper pools. A small drain line with a screw plug at the upper
poolcanbeused.Tedrainlineshouldbeamaximumof1in.
(31.75mm)torestrictthedischargerateintothelowestpool.
Formultiplepoolswithdiferentelevations,acommonrefer-
encemustbeestablishedtodrainthebasins.Anexamplewould
be waterfalls at several diferent elevations with basins at sev-
eraldiferentelevationsservedbyasinglepumpsystem.Ifthe
pumpswereturnedof,thewaterinthebasinswouldalldrain
tothelowestbasinthroughthecommonsuctionheader.Topre-
ventthis,eithercheckvalvesmustbeinstalledinallsuctionand
dischargelinesorallbasinsmustdraintoasurgepit.Tesurge
pit provides a common reference for the pumps and allows
each basin to drain independently of the others. Te surge pit
method is also much easier to balance than the method with
checkvalves.(SeeFigure1.)
For multiple pools at the same elevation, an equalizer line
should be run between the pools. No matter how accurate the
calculationsandinstallation,twoidenticalpoolswillhavevary-
ing fow rates. Te equalizer line should not tie into any other
lineexceptavalveddrain.Teequalizershouldbesizedsothat
itisaslargeasthelargestlinecomingintothepools.Ifeachpool
receivesthedischargethrougha4-in.(100-mm)line,theequal-
izershouldbea4-in.(100-mm)line.
PRELIMInARyDISPLAySELECTIOnAnDDETERMInATIOnOF
FLOWRATES
Spray jets and nozzlesTefowratesforsprayjetsandnozzles
shouldbedeterminedbythemanufacturersdata.Mostmanu-
facturers publish catalogs showing the various types of jet in
operation.Teclientshouldbegiventheopportunitytoselect
thejetsfromasubjectivestandpoint;theselectionshouldthen
bereviewedbytheengineerforpracticality.
Weirs Weirs are normally sized by the length of the weir and
thedepthofthewaterfowingovertheweiredge.Teengineer
may have to assist the client in determining the efect desired.
Itisusefultohavetheclientseeanexistingwaterfeaturethen
actually measure the depth over a weir. If the client desires an
unbroken sheet of water over the weir into the pool, a rule of
thumbisaboutin.(6.35mm)ofwaterovertheweirper4ftof
verticaldrop.
Te four most common types of weir are the rounded edge;
theupward-taperedweir;thedownward-taperedweir;andthe
downward-tapered, metal-edge weir. Te rounded-edge weir
is used when it is desired to have the water run down the wall
surface.Teupward-taperedweirrequiresmorewaterthanthe
othertypesandshouldnotbeusedforwaterfallsexceeding5ftin
height.Tedownward-taperedweirisveryefectiveincreating
smoothsheetsforwaterfallsupto15ftinheight.Tedownward-
tapered,metal-edgeweirachievesthesameefectasthedown-
ward-taperedweirwiththeaddedadvantageofbeingeasierto
level.
Te waterfall or weir is normally supplied from a trough
behind the weir edge. Te trough can be supplied with water
by many methods as long as the surface disturbance is kept to
aminimum.Aheadercanbeinstalledwithholesdrilledalong
the length of the header to supply
water equally along the length of
thetrough.Hydrophilicwellpiping,
precut with slots along the length
of the pipe, makes a very smooth
supply method. Oversized inlets
(to lower the water velocity) in the
bottom of the trough with diverter
platescanalsobeused.
Weirlipsmustbelevel.Tisisdif-
fcult to achieve with poured con-
crete,therefore,ametalorplasticlip
shouldbeprovided.Ifthespilllipis
in the shape of an overhang, a drip
lipintheshapeofain.(6.35mm)
deeprectangularslotshouldbepro-
vided under the slot. Tis will pre-
vent the water from running down
thewall.
Filtration turnover Te fltration
turnover rate is determined by the
volumeofthepoolandthedesirednumberofhourspercom-
plete water change. Te fltration turnover can vary from 4 to
12 h per complete water change. Tis needs to be determined
by the engineer. For areas with blowing dust and debris, a
fasterwaterchangeisneeded.Forcleanerareas,suchasthose
indoors,aslowerwaterchangecanbeused.Tefltrationfow
rateisdeterminedbydividingthepoolwatervolume,ingallons
(liters),bytheturnovertime,inminutes.
Example 1
An8000-galpooldividedby(12hx60min)equals11.1gpm
fowrate.
(A30283-Lpooldividedby[12hx60min]equals45.42L/min
fowrate.)
Terefore,afltrationsystemsizedforafowrateof12gpm
(45.42L/min)wouldbeadequate.
InLET/OuTLETAnDDEVICELOCATIOn
By convention, an inlet is defned as a device allowing water
tofowintothepool.Anoutletisdefnedasadeviceallowing
watertoleavethepool.
Figure 1 Multilevel Pools with a Surge Pit
MAY/JUNE 2006 PlumbingSystems&Design
COnTInuInG EDuCaTIOn: reflecting Pools and fountains
Main drains Maindrainsareprovidedforpumpsuctionand
draining the pool. Main drains should be located at the lowest
point of the pool. Tere should be at least one main drain for
thelowestbasin.Maindrainsshouldbelocatedsothatthereis
notmorethan20ftbetweendrainsormorethan15ftfromthe
sidewallofthepool.Temaindrainsshouldbesizedtoaccom-
modatethefullfowofthesystem.Main-draingratingsshould
be sized at no greater than 1.5 fps through the grating. See the
manufacturerslistingsfortheapprovedfowratethroughanti-
vortexgratings.
Maindrainsusedforpumpsuctionmusthavesomemethod
of preventing entrapment: either they must be the anti-vortex
type or they must be
installed in pairs at
least 4 ft apart to pre-
vent suction entrap-
ment.Althoughrefect-
ingpoolsandfountains
are not intended to be
occupied by humans,
people do acciden-
tally (and on purpose)
fall into them. Pair-
ing drains and using
anti-vortex drains
minimizes the risk of
suction entrapment and disembowelment. If paired drains are
used,theymustbeconnectedtoacommonsuctionlinewithout
anyinterveningvalves.(SeeFigure2.)
Main drains are used to empty the pool for cleaning and to
drainstormwaterwhenthepoolisempty.Adrainlineisrunto
theneareststormdrainlineandavalveisinstalledinthisline.
Skimmers Skimmers are necessary in all pools to collect
windblown debris and dust. Even indoor pools can collect an
amazing amount of foating debris that must be cleaned out
periodically.Skimmersnormallyconsistofaskimmerbodythat
is cast into the pool wall, a foating weir, and a strainer basket.
Te foating weir draws a thin layer of water into the skimmer.
Withathinlayer,thewatersvelocityishigheranditsinfuence
extendsfartheroutintothepool.Skimmerstrainerbasketsneed
tobecleanedoutperiodically,andaccesstothestrainerdefnes
thetypeofskimmerused.Top-accessskimmers,whileeasiestto
maintain, are very visible. Since architects prefer to hide every
component possible, front-loading skimmers are preferred. In
addition,front-loadingskimmersarelesspronetovandalism.
Skimmers should be located so that there is 1 skimmer pro-
videdforeach500ft
2
(46.45m
2
)oflowerbasin,withaminimum
of 1 skimmer. Te skimmer system should be sized to accom-
modate the full fltration fow. A 2-in. (50.8-mm) skimmer can
accept about 30 gpm (113.56 L/min), but skimmers can be
ganged together to increase their capacity. A majority of the
skimmersshouldbelocatedsuchthattheprevailingwindsand
currentblowthedebristowardthem.
Filtration return inlets Filtrationreturninletscomefromthe
fltersandreturncleanwatertothepool.Returninletsshouldbe
placedatleast12in.(304.8mm)belowwaterleveltominimize
surfacedisturbance.Ifthepoolistooshallow,increasetheinlet
pipesizetoreducethevelocityintothepool.Eachpoolshould
have a minimum of 2 inlets, with a sizing criteria of 1 inlet per
600 ft
2
(0.093 m
2
) of basin. Inlets should be sited to direct fow
towardtheskimmers.
Mechanical space or vault Te pumping equipment can be
locatedinthebuilding,inanundergroundequipmentvault,or
outdoorsabovegroundinaprotectedarea.Tedetermination
astowhetherornottoprovideavaultdependsonthefollowing
factors:(1)thedistancefromthepooltothemechanicalspace
inthebuildingvs.thedistancefromthepooltoanunderground
vault;(2)thediferenceincostforpiping,electricalwiring,and
conduitbetweenthetwolocations;(3)thecostofthemechani-
calspacevs.thecostofavault;and(4)whetherornotmechani-
calspaceisavailable.
Iftheequipmentisinstalledinanarearemotefromthefoun-
tain,itisadvisabletohavearemote-controlpanellocatedwithin
viewofthefountain.
Provideadequatespaceforallfountainequipment,including
electricalpanels.Observeallcode-mandatedclearancerequire-
ments.Allowsomemethodofremovingmotorsandpumpsthat
willnotrequiretheremovalofpartsofthebuilding.Tiscould
beanoverheadcranerailormerelyaneyeboltattachedtothe
structureovereachmotorforlifting.
A foor drain is required near the equipment. Specify a foor
drain with a backwater valve if there is any possibility of water
backing up through the drain, especially in a vault. If a foor
draincannotfowbygravitytothesewer,asumppitandpump
is required. If the equipment is installed in a vault, a battery-
operated,backupsumppumpmaybedesirable.
Inavault,provideanelectricreceptacle;alight;ahosebibb;
aventilatingblower;intakeandexhaustvents;anaccessladder;
and a lockable, spring-loaded access hatch big enough for all
equipment to pass through. A heavy manhole cover is not
recommended because the maintenance personnel become
annoyed with lifting the cover and tend to forget their mainte-
nance duties. In some cases, a 3-ft deep vault with an access
hatchcoveringtheentirevaultisadequate.
FOunTAInSySTEMSAnDCOMPOnEnTS
Tefountainsystemconsistsofthefollowingmajorsystems:
1. Displaysystem.
2. Pipingsystem.
3. Water-treatmentsystem.
A. Mechanical-fltrationsystem.
B. Chemical-treatmentsystem.
4. Makeup-watersystem.
5. Overfowanddrainagesystem.
6. Lightingsystem.
7. Othermiscellaneoussystems.
Te refecting pool may or may not have a display system,
dependingonthedesiredefect.
Each of these systems often overlaps or relies on another
systemtofunctioncorrectly.Forinstance,ifthefltrationsystem
isnotworkingproperly,thesprayheadswillloadupwithdebris
andnotfunctioncorrectly.Ifthewaterisnotkeptattheproper
levelwithanautofll,thelightingsystemmayoverheat.
DISPLAySySTEM
Tere are two distinct display types: static and dynamic. Static
displayshaveaconstantornearlyconstantvolumetricfowrate
at all times. Examples include a waterfall weir and constant-
heightjets.Dynamicdisplaysvarythefowthroughthesystem.
Examplesaredancingfountains,wherethefountainappearsto
react to music or lights, and waterfalls and rivers that are part
Figure 2 Main Drains
PlumbingSystems&Design MAY/JUNE 2006 PSDMAGAZINE.ORG
of a simulated storm scenario. For either type of display, the
typical system consists of the following components: suction
outlets and suction piping, pump(s), return piping, and dis-
chargedevice(s).Tedisplaysystemforeachtypeofefect,e.g.,
nozzles, weirs, whirlpools, and waves, should have a diferent
pumpsystemdedicatedtoit.
PIPInGSySTEM
Two separate types of piping systems are defned for any foun-
tain. Tese are the display systems and the flter system. Te
piping for these systems can normally share suction outlets but
shouldremainseparatefromthereuntilreturningtothepool.An
exampleofapoordesignisafountainsystemwherethedisplay
waterandtheflterwaterarecombinedsuchthatasinglepump
draws from the pool and pumps through the flter then back to
thenozzle.Whentheflterisclean,thissystemwillworkfne.As
soonasthefltergetsdirty,however,thefowfromthenozzlewill
graduallydropuntiltheflterisbackwashed.Tenthecyclewill
beginagain.
WATER-TREATMEnTSySTEM
Tewater-treatmentsystemconsistsoftwoseparateprocesses.
First,mechanicalfltrationremovesthesolidsandsomeofthe
suspendedorganicsfromthewater.Second,thechemicalfltra-
tion disinfects and balances the water to provide clean, spar-
kling clear, odor-free water that is pleasing to the eye and not
detrimentaltothepoolandequipment.
MAKEuP-WATERSySTEM
Itisessentialtomaintaintheproperwaterlevelinthepool.
Tereasonsarethreefold.First,certainspraynozzlesrequire
thatthewaterlevelvarynomorethanin.(12.7mm)in
ordertoachievethedesireddisplay.Avariationinthewater
levelcausesthenozzledisplaytobecomeerraticandtodifer
fromtheoriginaldesign.Second,underwaterlightsmustbe
submergedtoaspecifcdepthtobothprotectthelightsandto
removeheat.Tird,asubstantialwater-leveldropcouldcause
thesuctionlinetoentrainair,resultinginpumpcavitationand
possibledamage.
OVERFLOWAnDDRAInAGESySTEM
Te fountain must be equipped with an overfow system
to handle storm water and the possible malfunction of the
makeup-water system. In addition, mundane reasons, such as
drainingthepoolforwinterandcleaning,mandatethatadrain
systembeinstalled.
WATER-HEATInGSySTEM
Ifafountainistobekeptinoperationduringthewintermonths
anditispossibleforthewatertofreeze,anaquastat-controlled
pool heater should be provided. Te heater should be sized to
maintainpoolwateratabout35to40F(1.67to4.44C).
LIGHTInGSySTEM
Underwaterlightsareusedtoprovideilluminationforthevari-
ous displays. Te number of lights depends on the overall size
ofthepool,thedepthofthewater,theheightandwidthofthe
waterdisplay,andpossibleinterferencefromambientlighting.
Lightscanbewhiteoranothercolorasdesired.
SySTEMAnDCOMPOnEnTSELECTIOnAnDDESIGn
CRITERIA
FILTERSySTEMS
Types of flter Tere are many types of flter on the market
today. Some of these are specialty flters for water treatment,
ROsystemsandthelike.Forfountains,swimmingpoolandspa
flters best ft the application. Mechanical fltration is required
to remove suspended particulates down to about 50 . In this
range, cartridge flters and high-rate, pressure sand flters are
thebestchoiceforfountains.
Tere is a division in flter sizes that occurs around the 120
gpm(454.25L/min)fowrate.Abovethatratearethecommer-
cialfltersusedonlargerpoolsandfountainsandbelowarethe
residential flters used on smaller pools and fountains. Many
manufacturers do not make a distinction regarding quality at
the diferent levels, but some do. Check with the distributors
andpoolcontractorsastowhichflterscausetheleasttrouble.
Whensizingflters,itisgoodpracticetousemorethanoneflter
whenthefowrateisabove120gpm(454.25L/min).Forexam-
ple,asystemthatrequires280gpm(1059.92L/min)offltration
woulddobetterwithtwoflterssizedat140gpm(529.96L/min)
eachthanonefltersizedat280gpm(1059.92L/min).Tereason
is cleaning time. Whether the flter selected is a cartridge, sand,
or diatomaceous earth (DE), it will have to be cleaned at some
time.Withmultipleflters,thefltrationprocesscontinueswhile
oneflterisbeingcleaned.Inthecaseofsandflters,thefltertype
ofchoiceformostlargesystems,thebackwashfowrateislower,
necessitatingasmallerbackwashpitandsewerline.
Withmultipleflters,usemultiplepumps.Althoughthepumps
are not to be piped individually to each flter, a pump can be
shut down while a flter is serviced. Tis will prevent overrun-
ningtheotherflterswhileoneflterisdown.
Cartridge flters Cartridgefltersarelowerinfrstcostthan
theothertypesoffltersandarerelativelyeasytomaintain.Te
flter consists of a body constructed of plastic or stainless steel
thatcontainsapolyesterelement.Tecartridgeflterelementis
cleanedbyremovingthefltertopandpullingouttheelement.
Itcanthenbehosedcleanandreinstalledinthebody.Tesefl-
tersareavailableinsizesrangingfrom150gpmdownto5gpm.
Tesmall-sizefltersareoftheinlinetypemadeforflteringspas
andareexcellentforsmallfountains.
Cartridgefltersmustberemovedfromthebodytobecleaned
and require some space to be hosed down. Tis is a consider-
ation when the fountain is indoors and requires that the car-
tridgesbetakenawaytobecleaned.Asecondsetofcartridges
willbenecessaryforaswap.
Cartridges should be sized at 0.375 gpm/ft
2
maximum fow
rate.
High-rate, pressure sand flters A pressure sand flter con-
sistsofabodyconstructedofplastic,fberglass,orstainlesssteel
thatcontainssandtoflterthewater.Tetermhighratecomes
from the fow rate per square foot of sand bed. If the fow rate
is above about 10 gpm (37.85 L/min), the flter is classifed as
high rate. Tere are sand flters that are considered low or
slow rate, but they are seldom specifed today. Water enters
the flter at the top and is pumped down through the sand to
an underdrain manifold with slots narrow enough so that the
water will pass but the sand will not. Te water is piped to the
sandflterthroughaseriesofvalves(seeFigure3)oramultiport
valve.Amultiportvalveisasingle-handlecontrolwithfourports
MAY/JUNE 2006 PlumbingSystems&Design
COnTInuInG EDuCaTIOn: reflecting Pools and fountains
thatcanbeconfguredtoeitherflter,backwash,rinse,shutof,
bypass, or drain. Tey are limited to flters with 3-in. (80-mm)
orsmallerconnections.Eitherthevalveseriesorthemultiport
valvemaybeautomated.
As the flter accumulates debris, the diferential pressure
acrosstheflterwillincrease.Whenthediferentialpressurehas
increasedtoaspecifcpoint,normallyabout15psi,theflterhas
reachedthelimitofitsefectiveflterrunandrequirescleaning.
Cleaningisaccomplishedbybackwashing.
Backwashingasandflterisexactlywhatitsoundslike.Back-
washing reverses the fow so that the pump now forces water
through the underdrain manifold with enough fow to lift the
sandbedandstiritaround.Tedebrisisfoatedoutofthesand
and fows out the inlet pipe to a drain. A backwash sight glass
shouldbeinstalledtoallowtheoperatortoseewhentheefu-
entisclear.
Provisionsmustbemadewiththeprojectplumbingengineerif
asandflteristobeused.Manyjurisdictionsrequirethatasand
flterbebackwashedintoasandtraptopreventsandfromenter-
ingthesewersystem.Somejurisdictionsrequirethatasandflter
backwashasanindirectwasteintoapit.Teultimatedestination
ofthebackwashefuentmustalsobedetermined.Somejurisdic-
tions allow efuent to fow to the
storm sewer, others require it to
gotothesanitarysewer.Provision
mustbemadetohandlethelarge
fowratesthatarecustomarywith
a sand-flter backwash. Although
the backwash only lasts 5 min at
maximum, an enormous amount
ofwatercanbeusedinthattime.
Backwash rates are generally 20
gpm/ft
2
offlterarea.
Ahigh-rate,pressuresandflter
isgenerallysizedat12to15gpm/
ft
2
offlterarea,althoughtheflter
mayberatedupto20gpm/ft
2
.
Sizing flters To size a flter,
frst determine the fltration rate
through the pool. Once this is
established, divide the fltration
rate by 0.375 for cartridge flters
or 12 to 15 for sand flters. Tis
willdeterminetherequiredflter
area. For fltration rates over 120
gpm (454.25 L/min), dual flters
should be considered, with the
fow divided equally between
them. Filters should never be
sized at their maximum allowed
fow rate. Tis will cause higher
pressure drops through the flter
over the flter run and will sub-
stantially increase the energy
usedbythepump.
PuMPS
Display pumps Displaypumps
canbethedrytype,theself-prim-
ing dry type, or the submers-
ible type. When it is necessary
to locate the pump above water
level,aself-primingpumpshouldbeused.Ifthesizeandcostof
aself-primingpumpprecludeitsuse,afootvalveorcheckvalve
maybeinstalledinthesuctionline.
Submersiblepumpsaremoreexpensivethandry-typepumps
and may require additional water depth in the pool. Tis can
be accomplished by providing a pump pit in the water and
installing a fberglass grating over the pit. Te grate ofers pro-
tectionfromvandalsandalsohidesthepumpsfromview.Te
advantageofusingasubmersiblepumpisthatitcaneliminate
the need for long runs of pump suction and discharge piping,
thereby saving on horsepower. Since there is less piping and
corresponding friction loss, the required pump head is lower.
Insomecases,thiscanmeanasubstantialdiferenceinhorse-
power. Te National Electric Code does not allow submersible
pumpsover230Vtobeinstalledinfountains.
Dry-type pumps are installed in a vault adjacent to the pool
oramechanicalequipmentroomwithinthebuilding.Tepre-
ferredinstallationisonewherethepump-suctioninletislocated
below the pools operating water level. If this is not allowed, a
self-primingpumpmaybeused.Inmostprojects,anend-suc-
tion, close-coupled, centrifugal pump is used, but there are
Figure 3 Fountain Components
PlumbingSystems&Design MAY/JUNE 2006 PSDMAGAZINE.ORG
some projects where a horizontal, split-case, centrifugal pump
isnecessary.Tiscanoccurwherethefowrateishighandthe
required pump head is low. In all cases, the pump selection
should be made using the manufacturers pump curves. Mul-
tiplepumpsinparallelarepreferredtoonelargepump.Redun-
dancy, wind control, and opportunities for diferent displays
areexcellentreasonsformultiplepumps.Somefountainshave
displaysthatrequirehigh-pressure,low-fownozzles;low-pres-
sure, high-fow nozzles; and waterfall discharges. Where there
aremultipletypesofdisplay,aseparatepumpingsystemshould
beusedforeachtype.
Display pumps are sized according to the hydraulic calcu-
lations for friction loss and fow rate. Pumps can be cast iron,
bronzeorplastic.Pumpmaterialsshouldbesuitableforcontact
with fresh water. Since vaults and mechanical spaces are fre-
quentlytight,itshouldbepossibletoremovethepumpsmotors
andimpellerswithoutdisconnectingthepiping.Pumpsshould
beequippedwithsuctionbasketstrainerswithremovablebas-
kets,suctionanddischargegaugetaps,isolationandbalancing
valves,eccentricandconcentricreducersasrequired,andfex-
ible connectors. Proper pump piping practices, as described
elsewhereintheData Book, shouldbefollowed.
To size the display pump the following steps should be fol-
lowed:
1. Determinethestaticheadrequiredbetweenthelowest
waterlevelandthehighestwaterlevel.Tisisimportantfor
multilevelfountains.
2. Determinetheheadrequiredatthedischargepoint.Manu-
facturersprovidechartsthatgivethegpmandpressure
requiredatthenozzle.Ifthedischargeisforawaterfall
efectwiththedischargepointsubmerged,use10ftofhead.
3. Calculatethefrictionlossinthepiping,fttings,andvalves.
4. Addtheresultstoobtaintherequiredpumphead.
5. Determinethetotalgpmasrequiredforthenozzles,using
themanufacturerscharts(orthegpmforaweir,ascalcu-
latedusingtheweirlengthanddepth).
6. Selectthepumpusingthemanufacturerspumpcurves.
Iftheexactfowrateandheadcannotbeobtained,select
thenextlargersizepump.Inalmostallcases,thepump
selectedshouldhaveafatpumpcurve.Selectthemotor
thatwillprovideanonoverloadingconditionfortheentire
lengthofthepumpcurve.Wide-openconditionsare
commoninwaterefects.
Filter pumps Filterpumpsmaybeofthesametypeasthedis-
playpumps.(Seediscussionabove.)Terearefewreasonswhy
allthepumpscannotbeofthesametype.
Filterpumpsaresizedtomatchthegpm(L/min)requiredfora
properfltrationrateandtheheadrequiredtogivethatratewith
adirtyflter.Componentsinthefltersystemthatcontributeto
head loss include: skimmers and main drains (piped in paral-
lel so that the longest run must be determined), valves, basket
strainers, face piping (the piping connecting the pump to the
flter),returnpiping,andreturninlets.Elevationchangesneed
to be accounted for and added or subtracted. Generally, since
returninletsarebelowthewaterlevel,thereisnonetelevation
change.
Itisimportantthatthepumpbesizedtogivetheproperfow
ratewithadirtyflter,butitisalsoimportantthattheengineer
calculate the operating point on the pump curve with a clean
flter. Tere can be a substantial diference between these two
conditions in pump fow, and a variable fow-control device
mightbeconsideredforeveningoutthefowrates.
Pump strainers and suction screens Asageneralrule,suction
strainersprotectthepumpsanddischargestrainersprotectthe
nozzles.Displaypumpsarenotaslikelytopickupwaterborne
debris as are flter pumps, which are connected to skimmers
andmaindrains.Provisionscanbemadefordisplaypumpsto
havegratingsovertheirsuctionoutletsinthefountain.
Basket strainers on the pump suction protect the pump
from waterborne debris, which could get caught in the impel-
ler. Although display pumps can be protected somewhat from
debris large enough to damage the pump, flter pumps should
alwayshavebasketstrainers.
Y-typestrainersaremostlyusedtoprotectnozzleswithsmall
openings. Tey are installed on the discharge side of display
pumps to intercept waterborne debris before it jams inside an
actuatorororifce.Testrainershouldbeequippedwithavalve
andhoseconnectiontoallowforeasyblowdown.
Suctiondifusersareinstalledonthesuctioninlettothepump
and allow for rapid changes in the direction of piping close to
the pump. Te difuser slows the water down and straightens
it so that it enters the pump with less turbulence. Suction dif-
fusersarealsoequippedwithscreensbuttheyareverydifcult
toremoveforcleaningandshouldprobablynotbeusedwhen
othermethodsareavailable.
PIPInGAnDVALVES
Most piping for fountains is made of Schedule 40 PVC plastic.
Easyhandling,light weight, andlow frictionlosses make it the
piping of choice in most fountains. Although PVC seems to be
theperfectchoice,therearesomecaveatspertainingtoitsuse.
Pipinginstalledthroughpoolwallsandfoorsandintothepool
shouldbecopperorbrass.PVCpipingexposedtosunlightwill
become brittle, unless it is specifcally made to withstand the
efects of ultraviolet rays. Pump suction and discharge piping
installed underground or within a building can be PVC where
allowed by the local authorities. Be aware that smooth holes
have been found in plastic piping installed underground. Te
University of Illinois and the University of Florida both deter-
mined that the holes were caused by termites. Tey do not eat
the PVC; they chew through it when it gets in the way of their
continuedforagingforfood.Also,beawarethatmostcodesdo
notallowplasticpipingtobeinstalledinaplenum.Ductileiron,
galvanizedsteelpipe,orstainless-steelpipecanbeusediflarge
pipe sizes are required and PVC cannot be used. Carbon-steel
pipingshouldneverbeusedinafountainduetothehighlyoxy-
genatedwaterrunningthroughthepiping.
Allburiedpipingshouldbetreatedasawater-serviceapplica-
tion. Specifcally, piping needs to be bedded in sand or clean,
rock-free backfll. All changes of direction in piping 3 in. (76.2
mm)andlargerneedtoberestrainedwithpouredconcretethrust
blocks. Starts and stops in fountain systems can cause severe
waterhammerandresultantfailureinunrestrainedsystems.
All piping penetrations into the pool wall should be water
stoppedinsomefashion.Acommonmethodistouseapuddle
fange attached to the pipe itself. For penetrating walls into
mechanical rooms, a mechanical pipe seal can be used. (See
Figure4.)
Unions or fanges should be used at the fnal connection to
all equipment so that the equipment can be easily removed for
MAY/JUNE 2006 PlumbingSystems&Design
COnTInuInG EDuCaTIOn: reflecting Pools and fountains
repairs.Drainagelinesfromtheoverfowanddrainlinesshould
be either PVC or cast iron, as required by local code. Water
makeup and fll lines should be copper tubing. Diferent metal
pipes carrying water or installed underground must not come
intocontactwitheachother(dielectricisolation).
All piping systems should be pressure tested immediately
afterinstallation,andthetestshouldbeleftonuntilthepiping
is ready to be connected to the inlet and outlet devices and
equipment.Tisway,aglanceatapressuregaugecanindicate
immediatelyifapipehasbeenbrokenduringanotherphaseof
the construction. Te test pressure should be limited to 50 psi
(344.74 kPa), since the fountain piping systems are operated
at relatively low pressures. If the system requires higher pres-
sure, the pressure test should be made at a pressure that is 25
psi(172.37kPa)higherthantheoperatingpressure.Makesure
thatplasticpipingistestedwithinthepressuresrecommended
bythemanufacturer.
Prior to connecting the devices and equipment, piping sys-
tems should be fushed and cleaned. Caps should be left on
untilreadytomakethefnalconnectiontopreventdebrisfrom
enteringthepiping.Morethanonepumphasbeendamagedor
hadreducedfowduetodebristhatwasinthepipebeforethe
pumpwasconnected.
Suction-line piping Size the suction line at a velocity not to
exceed6fpsforcopperpipingand10fps(3.05m/s)forplastic
piping. Provide a suction inlet designed so that the drain will
not trap a person in the pool. Tis is accomplished by having
dual drains spaced at least 4 ft apart or dual drains located in
diferent planes (such as a bottom drain and a sidewall drain)
or by using anti-vortex drains. Some means of preventing vor-
texing should be used to prevent cavitation of the pumps. If a
minimumof18in.(457.2mm)ofwatercannotbeprovidedover
a suction drain, size the drain for of the manufacturers rec-
ommendedmaximumfowandaddmoredrainsasnecessary.
Suction-line piping should be installed without vertical loops,
whichcanbecomeairbound.Inaddition,itiscriticalthatsuc-
tion piping pass a 25 psi (172.37 kPa) pressure test because a
voidassmallasapinholecanpreventaself-primingpumpfrom
pumping.
Return piping Return piping should be sized at 6 fps maxi-
mumforcopperpipingand10fpsmaximumforplasticpiping.
Return piping, especially piping close to the discharge of the
pump,shouldbeproperlybracedwithinthemechanicalroom.
Fire-protectionbracingmethodsmaybeused.Returnpipingto
multiple inlets (nozzles, etc.) must be hydraulically balanced.
Filterreturnpipingterminatesineitheradjustableornonadjust-
ablereturnfttings.Returnfttingscanbewallorfoormounted
and should be adjusted to direct fow to the main drain and
skimmers.Deadspotsshouldnotbeallowedinapool.
Hydraulic balancing Suction and return headers should be
hydraulically balanced as closely as possible to ensure even
fow throughout the fountain. (See Figure 5.) For applications
where the fountain can be encircled by a header, this provides
an excellent balancing tool. Nozzle patterns and return inlet
headerscanbesizedusingthefollowingequation:
Equation 1
q
n
=2.45C(D
2
)(2gh
n
)
where
q
n
=Dischargefromorifcen,gpm(L/min)
2.45 =Conversionfactorusedtoexpressthedischargeingal/
min(L/min)whenthediameterisexpressedininches
(mm)andthevelocityisexpressedinfps(m/s).
Figure 4 Wall Penetrations
Figure 5 Hydraulic Balancing
PlumbingSystems&Design MAY/JUNE 2006 PSDMAGAZINE.ORG
C =Orifcedischargecoefcient(usually=0.61forholes
drilledinthefeld)
D =Diameteroforifce,in.(mm)
g =Accelerationduetogravity,32.2ft/s
2
(9.81m/s
2
)
h
n
=Headonorifcen,ft.(m)
Teheadonorifcenisequalto:
Equation 2
h
n
=
[
1
]
q
n
2
(2.45CD
2
)
2
2g
=kq
n
2
=k(mq
1
)
2
=m
2
h
1
where
k =Constant
h
1
=Headonorifce1,ft(m)
m=Massfowrate
Teheadlossbetweenorifce1andn,whichcorrespondstothe
headlossinthedistributionpipebetweenorifce1andn,is:
Equation 3
h
(1n)
=h
1
h
n
Nowitcanbeshownthattheheadlossbetweenthefrstorifce
and the last orifce in a distribution pipe with multiple, evenly
spacedorifcesisapproximatelyequaltoone-thirdofthehead
lossthatwouldoccurifthetotalfowweretopassthroughthe
samelengthofdistributionpipingwithoutorifces.Tus,
Equation 4
h
fdp
=
1
3h
fp
=h
(1n)
where
h
fdp
=Actualheadlossthroughdistributionpipe,ft(m)
h
fp
=Headlossthroughpipewithoutorifces,ft(m)
Te head loss through the pipe can be computed using the
Hazen-Williamsequation:
Equation 5
h
fp
=10.5(L
1n
)
Q
1.85D4.87
C
where
h
fp
=Headlossthroughthepipefromorifce1toorifcen,ft
(m)
L
1n
=Lengthofpipebetweenorifce1andn,ft(m)
Q=Pipedischarge,gpm(L/min)
C=Hazen-Williamscoefcient(150forplasticpipe)
D=Insidediameterofpipe,in.(mm)
Tediferenceindischargebetweenorifce1andnforagiven
distributionpipeandorifcesizecannowbedeterminedusing
Equations5-1through5-5.Ifthecom-
puted value of m is too low (<0.98),
the size of the distribution pipe can
be increased. Te percent diference
in fow between 1 and n will be [(1
n)100].Agoodvaluewouldbeless
than2%.
Valves
Shutof valves Most valves for
fountains are of a type that allows
throttling.Sinceadjustingthefountainisverysubjective,almost
everyvalveinthesystemcouldbeinvolvedinthefnaladjust-
ments.Tislimitstheselectiontoball-and-globevalvesforthe
smaller pipe and butterfy valves for the larger pipe. Lug-type,
butterfyvalvesarenormallyusedinapplicationswhereequip-
mentneedstobedisconnectedwhilestillunderwaterpressure.
Apumproomthatismuchlowerthanthefountainwillbebest
served by lug valves at the equipment connections so that the
equipmentcanbeservicedwithoutdrainingthefountain.
Check valves Tere are several types of check valve, but
mostareoftwotypes:gravityandspringloaded.Tegravity,or
swing-check, valve must be installed in a prescribed manner.
Tegravitycheckshouldbeinstalledwherewaterpressurewill
help provide a positive closure. Where a check valve must be
installedonahorizontalline,aspringcheckshouldbeinstalled.
A foot valve is a special type of check valve that is installed in
thepump-suctionline.Tepurposeofafootvalveistoprevent
the suction line from draining back into the pool and causing
thepumptoloseprime.Avalvedlinefromthemakeupsystem
shouldbeinstalledbetweenthepumpandthefootvalvetoaid
inpriming.Itwouldbeprudentalsotoinstalladraininthatsec-
tionofpipe.
Pressure-regulating valves Dynamicfountainsaredesigned
usingpressure-regulatingvalves.Teregulatingvalvemaintains
a selected downstream pressure regardless of the changes in
theupstreampressure.Terefore,whenthesprayheightofone
setofnozzlesisraisedorlowered,theregulatingvalvekeepsa
secondsetofnozzlesatthesamesprayheight.
Actuator-control valves In addition, actuator-controlled,
motorized, or pneumatic valves can be controlled using a 4 to
20-milliamp (mA) electrical signal. Te valve can be set to be
fully closed at 4 mA and fully open at 20 mA. At any point in
between,thevalvewillbeopenanamountcorrespondingtothe
positionofthepointwithinthisrange.Forexample,at6mA,the
valve will be slightly open and at 15 mA it will be almost fully
open. A computer can be programmed to provide signals to
openandclosethevalvesinanypatterndesired.
Materials Asamplescheduleofpipingmaterialsisshownin
Table1.
DISCHARGEDEVICES
Manyreturnmethodsareusedtoreturnthewaterintothepool.
Tedesignermustchoosewhichmethodeithercreatestheleast
disturbance to the desired water efect or creates the desired
waterefect.
Weir pools Commonmethodsofreturnintoupperweirpools
are:diverterplates(oftenanti-vortexdrainsusedonthereturn
side),wellscreens,anddoubletees.(SeeFigure6.)
Spray jets Numerous types of nozzle are manufactured. Te
designer should select the type of that will provide the desired
table 1 Sample Schedule of Materials
System
Indoor/
Outdoor
Abv/Blw
Grade
Size, in.
(mm) Pipe Material Fittings Joints
Static display piping Either Either 24
(12.5600)
Sch. 40 PVC Socket Solvent weld
Dynamic display piping Either Either 16
(12.5400)
Sch. 80 PVC Socket Solvent weld
Filtration piping Either Either 24
(12.5600)
Sch. 40 PVC Socket Solvent weld
Makeup water Either Either 4
(12.5100)
Type L copper Wrot copper Solder
Makeup water Either Either 6+ (150+) Type 302
stainless steel
Type 302
stainless steel
Mechanical
groove
MAY/JUNE 2006 PlumbingSystems&Design
COnTInuInG EDuCaTIOn: reflecting Pools and fountains
sprayefect.Tiscanonlybedonebyreferringtothedatalisted
in the manufacturers catalogs. Nozzles are available to pro-
vide solid or aerated columns of water, pyramid-like columns
of water, aerated mounds of water, mushroom shapes, foating
dandelionefects,fan-shapedsprays,fnger-likefansprays,bell-
likeshapes,twirlingjets,andnumerousotherefects.
Allaeratingjetsofvarioustypesfallintotwocategories:water-
level dependent and water-level independent. Te water-level
dependenttypeofjetreliesonthewaterlevelinthepoolbeing
constant.Tisconstantlevelallowsthejettoaspirateairintothe
watertogiveapleasing,frothingefect.Tereisarangeofdepths
formostmanufacturersjetswithazoneof1-2in.whereinthe
jet will function. Tese jets are slightly less expensive than the
independenttypebutrequirethatthelevelbemaintainedvery
accurately.Usingjetsinapoolthatemptiesoveraweirisavery
goodapplicationofthisjet.Usingjetstosurroundageyserthat
eruptseveryfewsecondsisnotagoodapplication,asthewater
willsurgeagreatdeal.Inthelattercase,awater-levelindepen-
dentjetwouldbetheanswer.
COnTROLS
Remote control Display pumps and flter pumps should be
controlled from a point within view of the fountain. Tis can
be achieved with a remote, hard-wired control panel and key
switchesoraradiosignal.Radioremote-controlunitsthatcon-
trol several separate electrical loads by means of a hand-held
transmitter and a manual switching panel are available. Tese
enableadoormanorconciergetoquicklyshutdownthefoun-
tain in the event of a problem, such as someone jumping into
thefountain.
Pump starters Allpumpsshouldhavestarterswithoverload
protectiontoprotecttheirmotors.Adisconnectswitchmustbe
installed within view of the pump. Te engineer should verify
that these items are provided for under the scope of electrical
work.
Wind controls Windcontrolsreducetheheightofafountain
display or shut of the display pump. A time-delay relay keeps
the pump of for at least 3 min to avoid the problem of pump
cycling. Tree methods are used to reduce the height of the
fountaindisplay:
1. Tewindcontrolopensorclosesasolenoidormotorized
valve,therebybypassingwaterfromthenozzlesbackinto
thepoolandreducingthesprayheightofthenozzles.
Tevalveandbypasslinemustnotbeundersized,orthe
requiredfowwillnotbebypassed.
2. Apressure-regulatingvalvecanbeinstalledinthedischarge
lineofthedisplaypump,andareduced-pressuresettingis
usedtolowerthesprayheight.Tismethodissomewhat
moreexpensivethanthebypass-controlvalve.
3. Ifthedisplaypumpsconsistoftwoormorepumpsinparal-
lel,shuttingdownapumpwillreducetheheightbyslightly
lessthantheproportionalamountproducedbytheshut
downpump.Reducedfrictioninthedischargelinewill
slightlyincreasethedischargeoftheremainingpump.
Withallthesemethods,hydrauliccalculationsarerequiredto
determine that the capacities and friction losses are adequate
to achieve the desired efect. A two-stage wind control is often
used, in which the frst stage reduces the height of the display
andthesecondstageturnsthesystemofcompletely.
Time switches Various types of time switches are available,
from electric motor operator to electronic. Time switches can
beusedtooperatethepumpsatthedesiredtimes.Inaddition,
cycle timers can be used to turn solenoid valves on and of at
presetintervalsof5sormore.
Pressure and fow switches Pressure and fow switches are
used to shut pumps of in the event that the pressure or fow
dropstoolowinthepumpdischarge.Teyarealsousedtosignal
water-treatmentsystemsoffow/nofowconditions.Start/stop
switchesareequippedwithtime-delayrelaystoallowthepump
tobestartedandalsotokeepthepumpofforaprogrammable
delaytopreventpumpcycling.
Figure 6 Discharge Devices
0 PlumbingSystems&Design MAY/JUNE 2006 PSDMAGAZINE.ORG
LIGHTInG
Lightsareavailableinlow-voltageaswellasnormallinevoltage.
Some jurisdictions, such as the City of New York, require only
low-voltagelightingandapprovalofalllightsandtransformers
used in the jurisdiction. Most lights can be obtained with col-
ored lenses if desired. Rock guards are required. Maintain the
waterleveloverthelightsasrequiredbythemanufacturer.Te
National Electrical Code(NEC)mustbefollowedwheninstall-
ing underwater lights, transformers, and submersible pumps.
Allelectricalsystemsthatsupplypowertoequipmentorlights
inthepoolmusthaveground-faultinterruptercircuitbreakers.
Fountain lights should be installed directly under the water
displaytoilluminatethegeneralpoolareaaswellasthewater
display. Te number of lights and the wattage depend on the
overall size of the pool, the height and width of the water dis-
play,andpossibleinterferencefromambientlighting.
Free-standinglightsarewiredthroughabronze,underwater
junctionbox.Teboxmustbelistedbyanationallyrecognized
testingagencyandapprovedforunderwateruse.Tecablefrom
the light is fed through a compression seal that is connected
to the junction box. When the architect wants to conceal the
cable,thecableisfedthroughacompressionsealtoanadjacent
brassconduittoaremotejunctionbox.Tecablemustbelong
enoughtoreachtheremotejunctionboxwithoutsplices.
Niche lights that are installed in pool walls have conduit
directly connected to the niche and extended to a remotely
locatedswitchbox.Tecablemustbelongenoughtoreachthe
remotejunctionboxwithoutsplices.
Lights are usually controlled by either astronomical time
switchesorregulartimeswitchesandaphotocell.Itisadvisable
todesignthecontrolsystemsothatmaintenancepersonnelare
not required to adjust the light timers for daylight savings time
andchangingsunsettimes.
In general, selecting colors for
the lights should be done with care
because of the subjective nature
with which each person views the
fountain. If blue, red, amber, and
otherdarkcolorsareused,thelights
shouldhaveahigherwattage.
WATERHEATInGEquIPMEnT
If a fountain is to be kept in opera-
tion during the winter months and
it is possible for the water to freeze,
a pool water heater should be pro-
vided. Te pool heater can be a
steam heat exchanger, a hot-water
heat exchanger, an electric water
heater, or a gas-fred water heater.
Teheatershouldbesizedtomain-
tainthepoolwaterataminimumof
35F(1.67C).
Overall heat loss due to surface
evaporation, radiation, conduction,
and convection for concrete pools
where the water temperature is 35F
(1.67C) and the air temperature is
10F(12.2C)canbeobtainedasfol-
lows:
25 mph wind velocity
TotalBtu/hheatloss=[203surfaceareaofthepoolinft
2
(m
2
)]+[34sidewallareainft
2
(m
2
)]
20 mph wind velocity
TotalBtu/hheatloss=[176surfaceareaofthepoolinft
2
(m
2
)]+[33sidewallareainft
2
(m
2
)]
15 mph wind velocity
TotalBtu/hheatloss=[145surfaceareaofthepoolinft
2
(m
2
)]+[32sidewallareainft
2
(m
2
)]
It is also necessary to include the heat loss from the piping.
Select a heater with an output equal to the Btu/h heat loss. In
manylargebuildings,theheatingmediumcanbetheheatinghot
water or steam. Te heater is controlled by a temperature con-
trolwiththesensingbulblocatedintheinletpipetotheheater.
Tecontrolwillturnontheheateriftheincomingwaterfromthe
pool is below 35F (1.67C) and shut it of if the temperature is
above 37F (2.78C). A fow switch in the inlet to the heater will
preventoperationoftheheaterifthereisinsufcientornofow.
Teheatershouldbelocatedonabypassline,asshowninFigure
7.Tepipingwithin3ftoftheheatershouldbeTypeLcopper
tubing.
WATER-TREATMEnTSySTEM
A properly engineered water-treatment system will allow the
operatortomaintainasparklingclear,odor-andalgae-freepool.
Certain water-treatment methods should be engineered into
thesystemandcertainwater-treatmentmethodscanbeadmin-
isteredbytheoperator.Water-treatmentparametersinclude:
1. Disinfectant residualmeasuredinpartspermillion(ppm).
2. Oxidation reduction potential (ORP)ameasureofthe
cleanlinessofthewater.Measuredinmillivolts(mV).
3. pHameasureoftheacidityorcausticityofthewater.
Figure 7 Piping Schematics
MAY/JUNE 2006 PlumbingSystems&Design 1
COnTInuInG EDuCaTIOn: reflecting Pools and fountains
4. Alkalinityameasureoftheresistanceofthewaterto
changeinpH,adimensionlessnumber.
5. Total dissolved solidsameasureofthetotaldissolved
solidsinthewater,measuredinppm.
6. Calcium Saturation Index (CSI) or Langeliers Indexa
dimensionlessnumber.
7. Cyanuric acid levelCyanuricacidisusedtopreventthe
dissipationofchlorinebysunlight.Itisalsotoxicathigher
levels.Measuredinppm.
Engineeredsystemsinclude:
1. Mechanical fltrationsandorcartridgeflters,which
removeparticulatesfromthewater.
2. Disinfection systemsincludingchlorineandbrominefeed-
ersandozone.Providecontroloforganicsandalgae.
3. pH control systemsgaseousCO
2
contacttanksandacid/
basefeeders.
4. Oxidation reduction potential (ORP) monitorsprovidean
overallmeasureofthecleanlinessofthewater.
Operator-administeredtreatmentsinclude:
1. Water chemistryAlthoughsomechemistriescanbedone
electronically,mostmustbedonebytheoperatorandthe
datarecorded.
2. Shock or hyperchlorinationusedtodestroychloramines
formedwhenchlorinedestroysorganiccompoundsinthe
water.Chloraminesgivepoolsthatdistinctivechlorine
smell.Amassivedoseofchlorine(10ppm)willdestroythe
chloramines.
3. DechlorinationAftershocktreatments,thewaterisoften
dechlorinatedwithsodiumthiosulfate.
4. pH adjustmentDiferentchlorinecompoundswilleither
raiseorlowerthepH.Gaseouschlorine(rarelyused)will
lowerthepHandsodaashwillneedtobeadded.Powdered
orliquidchlorinewillraisethepHandmuriaticacidwill
havetobeadded.
Althoughproperwaterchemistryisimportantfromadisinfec-
tionstandpoint,resultinginanalgae-freepool,waterbalanceis
equally important. Te Calcium Saturation Index or Langliers
Indexisameasureofthecorrosivenessofthewater.IftheCSIis
below0,thewateriscorrosiveandwillstarttocorrodethepool
walls, fttings, and equipment. If the CSI is above 0, the water
issaturatedandwillbegintoplateoutcalciumdepositsonthe
poolwall,fttingsandequipment.
Disinfection in refecting pools is necessary to control algae
andtodestroyorganicsinthewater.Commonmethodsofdis-
infection are chlorine, bromine, and ozone. Chlorine can be
used indoors or out with equal success. If used outdoors, the
chlorineshouldbecombinedwithcyanuricacidasastabilizer.
Tecyanuricacidwillenablethechlorinetolastmuchlongerin
directsunlight.Bromineisnotrecommendedforoutdoorpools
becausethereiscurrentlynowaytostabilizeitanditdissipates
rapidly.
Chlorine comes in three forms: gaseous, liquid, and solid.
Gaseous chlorine is the most efcient method of delivery but
canbeverydangerouswhenmishandled.Liquidchlorineisthe
preferred method when dealing with multiple bodies of water
or a single body of water in excess of 75,000 gal (283 905 L). A
chemical proportioning pump and 50-gal (189.27-L) chlorine
solution tank is used to administer the disinfectant. Te injec-
tionpointshouldbedownstreamoftheflter.Solidordrychlo-
rinecomesinmanyforms:solidpellets,granular,orpowder.It
isadministeredusinganerosionfeederthatisinstalledinparal-
lel with the flter and works on the diferential pressure across
theflter.
Caution: Two types of dry chlorine, sodium hypochlorite
andcalciumhypochlorite,arebothcurrentlyused.Ifthesetwo
compounds are mixed together, a violent explosion can result.
Chlorineusevariesfrom1to5oz/day/1000gal(0.03to0.15L/
day/3785.4L),dependingonthetemperatureofthewaterand
theamountofsunlight.Bothwarmwaterandsunlightdissipate
chlorinerapidly.
Ozone is an excellent method of disinfection for water but
doeshavelimitations.Teozonegasshouldbeappliedinacon-
tacttankandtheofgasfromthetankshouldbedirectedtoan
unoccupied area. In addition, ozone does not leave a residual
in the water. A small chlorine feeder should be added to pools
receivingahighorganicload,suchasoutdoorpools.Asafnal
note,certainmanufacturerswillnotwarrantytheirproductsfor
useinanozone-treatedpool.
MAKEuP-WATERSySTEM
Te fountain should be provided with both a manual and
an automatic fll system piped in parallel (see Figure 8). Te
manualflllineshouldbeatleast1to2in.(40to50mm)and
theautomaticflllinebein.(20mm)forsmallandmedium
fountains and as large as 4 in. (100 mm) for large fountains. A
good rule is to determine the makeup-water rate for cooling
towers in the area. Te information should be in gpm (L/min)
ofmakeupwaterpergpm(L/min)ofcondenserwater.Tiswill
translatedirectlytogpm(L/min)ofmakeupwaterpergpm(L/
min)ofefectwater.Forrefectingpools,thelocalwaterauthor-
ity should have information regarding evaporation rates from
swimmingpools.Whendesigningthemakeup-watersystem,it
maybeadvantageoustoconnectthemakeup-waterlinetothe
flter-pumpsuctionline.Ifthisisdone,makesurethatthereare
novalvesbetweenthemakeup-waterinletandthepool.Tisis
toensurethatthefltersystemdoesnotbecomepressurizedto
domestic-waterlinepressure.Mostpoolequipmentisnotbuilt
towithstandthehigherpressure.
Inallcases,backfowpreventersarerequiredonmakeup-water
piping to foat valves. Tey are also required on solenoid-oper-
ated,makeuplinesunlesstheinletpipeisatleast2pipediam-
etersormoreabovethepoolwall.Verifyallmethodsofbackfow
preventionwiththelocalauthorityhavingjurisdiction.
Multilevel pools require that a water-level sensor (not a foat
valve) be located in the lowest pool and the makeup inlet
be located in the highest pool. Low-water cutof sensors are
requiredinthelowestpooland,iftheunderwaterlightsdonot
have individual low-water cutofs, then every pool level must
havealow-watercutof.
Figure 8 Makeup-Water Devices
PlumbingSystems&Design MAY/JUNE 2006 PSDMAGAZINE.ORG
Makeup-Water Devices
Stilling wells or chambers Stillingwellsorchambersarean
importantpartofanymakeup-watersystem.Withastillingwell,
thelevelinthewellisanaccuraterepresentationofthelevelin
the pool. Te advantage to the stilling well is that it remains
relatively calm inside the well and does not refect the surface
disturbancesthatmayoccurinthepoolitself.Astillingwellcan
alsoincorporateanoverfowdrain.
Mechanical methods Mechanical water makeup is the
cheapestmethodandisleastpronetomaintenanceproblems.
In this method, a foat valve installed in the wall of the pool
providesautomaticmakeup.Tetopofthepoolwatermustbe
at least 5 in. above the water level for the foat box to ft in the
poolwall.Amethodofremotelymaintainingthewaterlevelis
toinstallafoatvalveinanopentankorconnectedtothepool
by a pipe and rooted to a remote location. Tere should be no
connectiontothispipeexceptforavalveddrain.Withthepipe
openateitherend,thewaterlevelinthetankwillbethesameas
thewaterlevelinthepool.Teproblemencounteredwiththis
applicationisfndingalocationforthetank.
Another method, commonly used on large pools, uses a pilot-
operated makeup valve. With this method, a small foat valve is
installedinastillingwellandthepilotwaterforthelargervalveis
routedthroughit.Whentheleveldrops,thepilotfoatvalveopens
andwaterisallowedtoopenthelargervalve.Teadvantagetothis
method is that a small stilling chamber can be located near the
pool while the larger valve can be located near the pumps in the
mechanicalroom.
Electrical method Where the above methods cannot be
used,watermakeupcanbeprovidedbyusingelectricalsensors
thatopenorcloseasolenoidvalveonthemakeup-waterline.A
manual fll valve is ordinarily installed in a bypass around the
solenoidvalve.Tesensorsuselowvoltageorinducedvoltage
thatprecludesanyelectricaldanger.Sensorsthatutilizeareed
switch,activatedbyapermanentmagnet,arealsoavailable.Te
sensorscanbemountedinthewallofthepool,accessiblefrom
the front. (See Figure 9.) Tey can also be located in the top of
thewallwiththesensorshangingdownintoa1-in.(32-mm)
brass pipe that has an air vent and a horizontal leg extending
intothepoolwater.Whereitisnotfeasibletomountthesensors
inthepoolwall,theycanbelocatedanywhereinthepoolwater
bymountingthesensorboxontopofabrassconduitwherever
it enters the pool. Te sensor will generate a small amount of
currentfromthesensortip,throughthewaterandintothebrass
pipe.Ifwaterisnotpresent,thecurrentfowstopsandthecon-
trolpanelopensthesolenoidvalve.Brasspipingmustbeused
as it provides the electrical ground path. Electrical wiring has
tobeextendedtothesensorsinthepoolareaaswellastothe
controlpanelandthesolenoidvalve.
Dualsensorsareavailablethatwillprovideforwatermakeup
andlow-watercutof(sothatpumpswillbeshutofintheevent
oflowwaterlevel).Teycanalsoshutoftheunderwaterlights,
which can be damaged by operation without adequate water
cover.
OVERFLOWAnDDRAInAGESySTEM
Overfow drains Overfow drains are required for two rea-
sons:toprovideameanstoremovewaterifthemakeup-water
valve malfunctions and to provide a means to remove storm
waterandmaintainafxedwaterlevelsothatnozzleswillwork
properly.Tesizeofanoverfowdrainforanindoorpoolshould
be 2 in. If the makeup-water line is larger than 1 in., increase
thesizeoftheoverfowdraintopreventfooding.Sizingforan
outdoorpoolshouldbebasedontheareaofthepool,inft
2
(m
2
),
asrequiredbythelocalplumbingcodeforstormdrainage.
Te preferred location for an overfow drain is in the pool
wall, because it is less obtrusive there. Tere are times though
whenthepoolwallisinsufcientfortheinstallationofanover-
fow drain. In such cases, a removable overfow standpipe can
be provided. A dome or screen should be placed on top of the
standpipe.Teoverfowdrainalsoactsasthemaindrainwhen
the standpipe is removed. Overfow standpipes are subject to
vandalism and should be located so that they are not easily
accessible to the public. Another method is to install an over-
fowpipeonabypassaroundamaindrainvalve.Teoverfow
pipeinvertmustbeslightlyhigherthanthehighwaterleveland
haveanairopeningtopreventsiphonage.
Emergency drains Emergency drains are needed to drain
thepooliftheoutsidetemperaturedropsbelowfreezing.Tisis
achievedbyprovidinganaquastatthatcontrolsasolenoidvalve
locatedinthedrainline.Teaquastatshouldbesettoopenthe
solenoid valve if the temperature drops too low. Te solenoid
valvemusthaveamanualoverrideintheeventofapowerfailure
andmustnotrequirediferentialpressuretoopenthevalve.An
Ongontzvalveisanotheremergencydrainvalvethatmechani-
callystartstoopenwhenthetemperaturedropsto38F(3.33C)
and fully opens at 34F (1.11C). In the above cases, electrical
sensors, as described above under Makeup-Water Devices,
shouldbeprovidedtoshutoftheelectricalpowertothepumps
andlights.Temakeup-watervalveshouldbewiredtocloseif
the emergency drain valve is open. It may also be advisable to
have an alarm ring to indicate that the emergency drain valve
hasopened.
REFEREnCES
1. AmericanNationalStandardsInstitute/NationalSpaand
PoolInstitute.1991.Standard for public swimming pools,
ANSI/NSPI-11991.Alexandria,VA:NationalSpaandPool
Institute.
2. Kowalsky,L.1990. Pool/spa operators handbook.SanAnto-
nio,TX:NationalSwimmingPoolFoundation.
3. Tchobanoglous,George,andFranklinL.Burton.1991.
Wastewater engineering: Treatment, disposal, and reuse.3d
ed.NewYork:McGraw-Hill.
Figure 9 Electronic Makeup-Water Device
MAY/JUNE 2006 PlumbingSystems&Design
COnTInuInG EDuCaTIOn
1. The fltration turnover rate in a refecting pool or
fountain is determined by _______.
a. the local code
b. the architect
c. the engineer
d. the color of the water desired
. Surge collars are used to minimize _______ in circular
pools.
a. discoloration
b. plant growth
c. evaporation
d. waves
. The water treatment system should maintain _______.
a. sparkling clean water
b. odor-free water
c. an algae-free pool
d. all of the above
. When a fountain is to be operated in freezing
conditions, the water should be heated to maintain
_______ degrees fahrenheit minimum.
a. 10
b. 35
c. 40
d. all of the above
. The university of Illinois and the university of florida
have determined that the smooth holes found in
underground PVC pipe are caused by _______.
a. exposure to ultraviolet rays
b. exposure to sunlight
c. termites
d. high velocity
. The headers indicated in fig. may have their orifces
balanced using _______.
a. equations 1 through 5
b. the average percentage indicated
c. good engineering practice
d. looped piping around the fountain
. all pumps serving the pool and/or fountain should be
located to ensure _______.
a. they are higher than the pool or fountain for
maintenance purposes
b. they are lower than the pool or fountain to maintain
a fooded suction line
c. that they can be viewed by the public
d. none of the above
. The most common types of weirs are _______.
a. metal edge
b. upward tapered
c. rounded edge
d. all of the above
. Oxidation reduction potential (OrP) is _______.
a. controlled by the pH
b. a measure of the total dissolved solids in water
c. controlled by the operator
d. a measure of the cleanliness of the water
10. refecting pools and fountains provide _______.
a. a place to grow water plants
b. a retreat area in which to rest and relax
c. a place to fsh
d. a place for frogs to play
11. hydraulic balancing of the suction and return
headers is required _______.
a. to ensure even fow throughout the fountain
b. by local codes
c. to keep sound levels low
d. all of the above
1. When using a sand flter, what fow rate and above, in
gallons per minute, will classify it as a high-rate flter?
a. gpm
b. 4 gpm
c. 8 gpm
d. 10 gpm
Doyoufnditdifculttoobtaincontinuingeducationunits(CEUs)?
Is it hard for you to attend technical seminars? Trough Plumbing
Systems&Design(PS&D),ASPEcanhelpyouaccumulatetheCEUs
required for maintaining your Certifed in Plumbing Design (CPD)
status.
ASPEfeaturesatechnicalarticleineveryissueofPS&D,excerpted
from its own publications. Each article is followed by a multiple-
choicetestandasimplereportingform.
Readingthearticleandcompletingtheformwillallowyoutoapply
to ASPE for CEU credit. For most people, this process will require
approximately1hour.Anominalprocessingfeeischarged$25for
ASPE members and $35 for nonmembers (until further notice, the
member fee is waived). If you earn a grade of 90% or higher on the
test,youwillbenotifedthatyouhavelogged0.1CEU,whichcanbe
applied toward the CPD renewal requirement or numerous regula-
tory-agencyCEprograms.(Pleasenotethatitisyourresponsibilityto
determinetheacceptancepolicyofaparticularagency.)CEUinfor-
mationwillbekeptonfleattheASPEofcefor3years.
No certifcates will be issued in addition to the notifcation letter.
You can apply for CEU credit on any technical article that has
appeared in PS&D within the past 12 months. However, CEU credit
onlycanbeobtainedonatotalofeightPS&Darticlesina12-month
period.
Note: In determining your answers to the CE questions, use only
the material presented in the continuing education article. Using
otherinformationmayresultinawronganswer.
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
CE QuestionsReflecting Pools and Fountains (PSD 133)
PlumbingSystems&Design MAY/JUNE 2006 PSDMAGAZINE.ORG
P
S
D
1
3
4
Life-Safety
Systems
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
JULY/AUGUST 2006
PSDMAGAZINE.ORG
IntroductIon
A threat to personnel safety often present in pharmaceutical
facilities is accidental exposure and possible contact with toxic
gases, liquids, and solids. Tis chapter describes water-based
emergency drench equipment and systems commonly used as
a frst-aid measure to mitigate the efects of such an accident,
Also described are the breathing-air systems that supply air to
personnel for escape and protection when they are exposed to
either a toxic environment resulting from an accident or normal
working conditions that make breathing the ambient air haz-
ardous.
EmErgEncy drEnch-EquIpmEnt SyStEmS
gEnEral
When toxic or corrosive chemicals come in contact with the
eyes, face, and body, fushing with water for 15 min with the
clothing removed is the most recommended frst-aid action that
can be taken by nonmedical personnel prior to medical treat-
ment. Emergency drench equipment is intended to provide a
sufcient volume of water to efectively reach any area of the
body exposed to or has come into direct contact with any inju-
rious material. Within facilities, specially designed emergency
drench equipment, such as showers, drench hoses, and eye and
face washes, are located adjacent to all such hazards. Although
the need to protect personnel is the same for any facility, specifc
requirements difer widely because of architectural, aesthetic,
location, and space constraints necessary for various industrial
and laboratory installations.
SyStEm claSSIfIcatIonS
Drench equipment is classifed into two general types of system
based on the source of water. Tese are plumbed systems, which
are connected to a permanent water supply, and self-contained
or portable equipment, which contains its own water supply.
Self-contained systems can be either gravity feed or pressur-
ized.
One type of self-contained eyewash unit is available that does
not meet code requirements for storage or delivery fow rate.
Tis is called the personnel eyewash station and is selected only
to supplement, not replace, a standard eyewash unit. It consists
of a solution-flled bottle(s) in a small cabinet. Tis cabinet is
small enough to be installed immediately adjacent to a high
hazard. If an accident occurs, the bottle containing the solu-
tion is removed and used without delay to fush the eyes while
waiting for the arrival of trained personnel and during travel to
a code-approved eyewash or frst-aid station.
codES and StandardS
1. ANSI Z-358.1, Emergency Shower and Eyewash Equipment.
2. OSHA has various regulations for specifc industries per-
taining to the location and other criteria for emergency
eyewashes and showers.
3. Te Safety Equipment Institute (SEI) certifes that equip-
ment meets ANSI standards.
4. Applicable plumbing codes.
For the purposes of the discussion in this section on drench
equipment, the word code shall refer to ANSI Z-358.1.
typES of drEnch EquIpmEnt
Emergency drench equipment consists of showers, eyewash
units, face-wash units, and drench hoses, along with intercon-
necting piping and alarms if required. All of these units are
available either singly or in combination with each other. Ancil-
lary components include thermostatic mixing systems, freeze
protection systems and enclosures. Each piece of equipment
is designed to perform a specifc function. One piece is not
intended to be a substitute for another, but rather, to comple-
ment the others by providing additional availability of water to
specifc areas of the body as required.
Emergency Showers
Plumbed Showers Plumbed emergency showers are perma-
nently connected to the potable water piping and designed to
continuously supply enough water to drench the entire body.
A unit consists of a large-diameter shower head intended to
distribute water over a large area. Te most commonly used
type has a control valve with a handle extending down from the
valve on a chain or rod that is used to turn the water on and of
manually. Code requires the shower be capable of delivering a
minimum of 30 gpm (113.6 L/min) of evenly dispersed water at
a velocity low enough so as not to be injurious to the user. Where
this fow rate is not available, 20 gpm (75.7 L/min) is acceptable
if the shower-head manufacturer can show the same spray pat-
tern required for 30 gpm can be achieved at the lower fow rate.
Te minimum spray pattern shall have a diameter of 20 in. (58.8
cm), measured at 60 in. (152.4 cm) above the surface on which
the user stands. Tis requires a minimum pressure of approxi-
mately 30 psi (4.47 kPa). Emergency showers can be ceiling
mounted, wall mounted or foor mounted on a pipe stand, with
the center of the spray at least 16 in. (40.6 cm) from any obstruc-
tion. Showers should be chosen for the following reasons:
1. When large volumes of potentially dangerous materials are
present.
2. Where a small volume of material could result in large
afected areas, such as in laboratories and schools.
A typical emergency shower head mounted in a hung ceiling
is illustrated in Figure 1.
Self-Contained Showers Self-contained emergency show-
ers have a storage tank for water. Often this water is heated. Te
shower shall be capable of delivering a minimum of 20 gpm
(75.5 L/min) for 15 min. Te requirements for mounting height
and spray pattern are the same as they are for plumbed show-
ers.
Life-Safety Systems
Reprinted from Pharmaceutical Facilities Plumbing Systems, Chapter 8: Life-Safety Systems, by Michael Frankel.
American Society of Plumbing Engineers.
Plumbing Systems & Design JULY/AUGUST 2006 PSDMAGAZINE.ORG
CONTINUING EDUCATION
Emergency Eyewash
Plumbed Eyewash Emergency eyewashes are specifcally
designed to irrigate and fush both eyes simultaneously with
dual streams of water. Te unit consists of dual heads in the
shape of a U, each specifcally designed to deliver a narrow
stream of water, and a valve usually controlled by a large push
plate. Code requires the eyewash to be capable of delivering a
minimum of 0.4 gpm (1.5 L/min). Many eyewashes of recent
manufacture deliver approximately 3 gpm (11.4 L/min). Once
started, the fow must be continuous and designed to operate
without the use of the hands, which shall be free to hold open
the eyelids. Te fow of water must be soft to avoid additional
injury to sensitive tissue. To protect against airborne
contaminants, each dual stream head must be pro-
tected with a cover that is automatically discarded
when the unit is activated. Te head covers shall be
attached to the heads by a chain to keep them from
being lost. Te eyewash can be mounted on a coun-
ter or wall, or as a free stranding unit attached to the
foor. Te eyewash could be provided with a bowl. Te
bowl does not increase the efciency or usefulness of
the unit but aids in identifcation by personnel. It is
common practice to mount a swivel type eyewash on
a laboratory sink faucet, installed so it can be swung
out of the way during normal use of the sink but can
be swung over the sink bowl in order to be operated
in an emergency.
Te code recommends (but does not require) the
use of a bufered saline solution to wash the eyes. Tis
could be accomplished with a separate dispenser
flled with concentrate that will introduce the proper
solution into the water supply prior to reaching the
device head. A commonly used device is a wall-
mounted, 5 to 6-gal (20 to 24-L) capacity solution
tank connected to the water inlet dispenses a mea-
sured amount of solution when fow to the eyewash
is activated. A backfow device shall be installed on
the water supply.
Self-Contained Eyewash A typical self-con-
tained eyewash has a storage tank with a minimum
15-min water supply. Te mounting height and spray
pattern requirements are the same as those for a
plumbed eyewash.
Emergency Face Wash
Te face wash is an enhanced version of the eyewash.
It has the same design requirements and confgura-
tion, except the spray heads are specifcally designed
to deliver a larger water pattern and volume will fush
the whole face and not just the eyes. Te face wash
should deliver approximately 8 gpm (55 L/min). Te
stream confguration is illustrated in Figure 2. Very
often, the face wash is chosen for combination units.
In general, the face wash is more desirable than the
eyewash because it is very likely an accident will
afect more than just the eyes. All dimensions and
requirements of the free-standing face wash are
similar to those for the eyewash.
Drench Hoses
A drench hose is a single-head unit connected to a
water supply with a fexible hose. Te head is gener-
ally the same size as a single head found on an eye/
face wash. Code requires the drench hose be capable of deliver-
ing a minimum of 0.4 gpm (1.5 L/min). It is controlled either by a
squeeze handle near the head or a push-plate ball valve located
at the connection to the water source. It is used as a supplement
to showers and eye/face washes to irrigate specifc areas of the
body. Drench hoses are selected for the following reasons:
1. To spot drench a specifc area of the body when the large
volume of water delivered by a shower is not called for.
2. To allow irrigation of an unconscious person or a victim
who is unable to stand.
3. To irrigate under clothing prior to the clothings removal.
Figure 2 Combination Emergency Shower, Eye/Face Wash, and Drench Hose Unit
Figure 1 Typical Emergency Shower
JULY/AUGUST 2006 Plumbing Systems & Design
Combination Equipment
Combination equipment consists of multiple-use units with a
common water supply and supporting frame. Combinations are
available that consist of a shower, eye/face wash, and drench
hose in any confguration. Te reason for the use of combina-
tion equipment is usually economy, but the selection should
be made considering the type of irrigation appropriate for the
potential injuries at a specifc location. For combination units,
the water supply must be larger, capable of delivering the fow
rate of water required to satisfy two devices concurrently rather
than only a single device.
Te most often-used combination is the drench shower and
face wash. Figure 2 illustrates a combination shower, eye/face
wash and drench hose complete with mounting heights.
drEnch EquIpmEnt componEntS
Controls
Often referred to as activation devices, controls cause water to
fow at an individual device. Stay-open valves are required by
code in order to leave the hands free for the removal of clothing
or for holding eyelids open. Te valves most often used are ball
valves with handles modifed to provide for the attachment of
chains, rods, and push plates. In very limited situations, such
as in schools, valves that automatically close (quick-closing) are
permitted if they are acceptable to the facility and authorities
having jurisdiction.
Valves are operated by diferent means to suit the specifc
hazard, location, durability, and visibility requirements. Te
operators on valves are handles attached to pull rods, push
plates, foot-operated treadle plates and triangles. A solid pull
rod is often installed on concealed showers in order to push
the valve closed after operation. Another method is to have two
handles attached to chains that extend below the hung ceiling,
one to turn on the valve and another handle to turn it of. Chains
are used if the handle might be accidentally struck, they enable
the handle to move freely and not injure the individual who
might accidentally strike the hanging operator.
Operating handles for the physically challenged are mounted
lower than those for a standard unit. In many cases, this requires
that operating handles be placed near walls to keep them out
of trafc patterns where they would be an obstruction to able-
bodied people passing under them. A free-standing combination
shower and eyewash that is handicapped accessible using handles
hung from the ceiling is illustrated in Figure 3. Te handle must
be located close enough to the center of the shower to be easily
reached, which is about 2 ft 0 in. from the center of the shower.
Alarms
Alarms are often installed to alert security or other rescue per-
sonnel that emergency drench equipment has been operated
and to guide them rapidly to the scene of the accident. Com-
monly used alarms are audible and visual devicessuch as
fashing or rotating lights on top of, or adjacent to, a shower
or eyewashand electronic alarms wired to a remote security
panel. Remote areas of a plant are particularly at risk if person-
nel often work alone. Alarms are most often operated by a fow
switch activated by the fow of water when a piece of equipment
is used.
When tempered water systems are used to supply drench
equipment, a low water temperature of 60F shall cause an
alarm annunciation.
Flow-Control Device
Where water pressure exceeds 80 psig (550 kPa) or if the difer-
ence in water pressure between the frst and last shower head
is more than 20 psig (140 kPa), it is recommended that a self-
adjusting fow-control device be installed in the water-supply
pipe. Its purpose is to limit the fow to just above the minimum
required by the specifc manufacturer for proper functioning
of equipment. Such devices are considered important because
a shower installed at the beginning of a long run has a much
greater fow than the device at the end. During operation, the
higher pressure could cause the fow rate to be as much as 50
gpm (L/min). If no foor drain is provided, the higher fow for
15 min at the higher pressure could produce a much greater
amount of water that must be cleaned up and disposed of after-
wards. Drench hoses and eye and face washes are not afected
because of their lower fow rates and their fow head designs.
Where pressure-reducing devices are required for an entire
system, they should be set to provide approximately 50 psig (345
kPa).
SyStEm dESIgn
General
It is a requirement that a plumbed system be connected to a
potable water supply as the sole source of water. Tis system is
therefore subject to fling with a plumbing or other code of-
cial for approval and inspection of the completed facility, as are
standard plumbing systems.
An adequately sized pipe with sufcient pressure must be
provided from the water supply to meet system and device
operating-pressure requirements for satisfactory functioning.
One maintenance requirement is that the water in the piping
system be fushed to avoid bacterial growth.
It is common practice to add antibacterial and saline products
to a self-contained eyewash unit and an antibacterial additive to
an emergency shower. Water is also commonly used if it can be
changed every week. It is well established that no preservative
will inhibit bacterial growth for an extended period of time. Self-
contained equipment must be checked regularly to determine if
the quality of the stored water has deteriorated to a point where
it is not efective or safe to use.
If valves are placed in the piping network for maintenance
purposes, they should be made for unauthorized shut-of.
Figure 3 Clearance Dimensions Around Shower and Eye/Face Wash
Plumbing Systems & Design JULY/AUGUST 2006 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Life-Safety Systems
Water-Supply Pressure and Flow Rates
Emergency showers require between 20 and 30 gpm (76 to 111
L/min), with 30 gpm recommended. Te minimum pressure
required is 30 psig (4.5 kPa) at the farthest unit, with a generally
accepted maximum pressure of 70 psi (485 kPa). Code mentions
a high pressure of 90 psig (612 kPa), which is generally consid-
ered to be excessive. Most plumbing codes do not permit water
pressures as high as 90 psig. Generally accepted practice limits
the high water pressure to between 70 and 80 psig (480 and 620
kPa).
Most eyewash units require a minimum operating pressure
of 15 psig (105 kPa) with a fow rate minimum of 3 gpm (12 L/
min) at the farthest unit. Maximum pressure is similar to that
for showers. Face washes and drench hoses require a minimum
operating pressure of 15 psig (105 kPa) with a minimum fow
rate of 8 gpm (30 L/min) at the farthest unit.
System Selection
Plumbed System
Te advantages of a plumbed system include:
1. Permanent connection to a fresh supply of water, requiring
no maintenance and only minimum testing of the devices
to ensure proper operation.
2. It provides an unlimited supply of water often at larger vol-
umes than self-contained units.
Disadvantages include:
1. Higher frst cost than a self-contained system.
2. Maintenance is intensive. Such systems require weekly
fushing, often into a bucket, to remove stagnant water in
the piping system and replace it with fresh water.
Self-Contained System
Advantages of the self-contained system include:
1. Lower frst cost compared to a plumbed system.
2. Can be flled with a bufered, saline solution, which is rec-
ommended for washing eyes.
3. Available with a container to catch waste water.
4. Portable units can be moved to areas of greatest hazard
with little difculty.
5. A gravity eyewash is more reliable. Te water supply can be
installed where there is room above the unit. If not, a pres-
surized unit mounted remotely should be selected.
Disadvantages include:
1. Only a limited supply of water at a lesser fow rate is avail-
able.
2. Te stored liquid must be changed on a regular basis to
maintain purity.
Te plumbed system is the type of system selected most often
because of the unlimited water supply.
Pipe Sizing and Material
In order to supply the required fow rate to a shower, a mini-
mum pipe size of 1 in. (25 mm) is required by code, with 1 in.
(30 mm) recommended. If the device is a combination unit, a
1-in. size should be considered as minimum. An emergency
eye/face wash requires a minimum in. (13 mm) pipe size.
Except in rare cases where multiple units are intended to be
used at once, the piping system size should be based on only
one unit operating. Te entire piping system is usually a single
size pipe based on the requirements of the most remote fxture.
Appropriate pressure loss calculations should be made to ensure
the hydraulically most remote unit is supplied with adequate
pressure with the size selected. Adjust sizes accordingly to meet
friction loss requirements.
Te pipe material should be copper to minimize clogging the
heads of the units in time with the inevitable corrosion products
released by steel pipe. Plastic pipe (PVC) should be considered
where excessive heat and the use of closely located supports will
not permit the pipe to creep in time.
Emergency drench equipment shall be sized based on the
single highest fow rate, usually 30 gpm (115 L/min) for an
emergency shower. Piping is usually a 1-in. header of copper
pipe for the entire length of a plumbed system.
Flushing Water Disposal
Water from emergency drench equipment is mainly discharged
onto the foor. Individual eye/face washes mounted on sinks
discharge most of the water into the adjacent sink. Combination
units have an attached eye/face wash also discharge water on
the foor. Tere are diferent methods of disposing of the water
resulting from an emergency device depending on the facility.
Te basic consideration is whether to provide a foor drain adja-
cent to a device to route that water from the foor to a drainage
system.
It is accepted practice not to provide a foor drain at an emer-
gency shower. Experience has shown in most cases, particularly
in schools and laboratories, it is easier to mop up water from the
foor in the rare instances emergency devices are used rather
than add the extra cost of a foor drain, piping and a trap primer.
Considerations include:
1. If the drain is not in an area where frequent cleaning is
done, the trap may dry out, allowing odors to be emitted.
2. Is there an available drainage line in the area of the device?
3. Can the chemical, even in a diluted state, be released into
the sanitary sewer system or must it be routed to a chemical
waste system for treatment?
4. Must purifcation equipment be specially purchased for
this purpose?
InStallatIon rEquIrEmEntS for drEnch EquIpmEnt
Te need to provide emergency drench equipment is deter-
mined by an analysis of the hazard by design professionals or
health or safety personnel and by the use of common sense in
conformance with OSHA, CFR, and other regulations for spe-
cifc occupations. Judgment is necessary in the selection and
location of equipment. Very often, facility owners have specifc
regulations for its need and location.
Dimensional Requirements
Te mounting height of all equipment, as illustrated in ANSI Z-
358.1, is shown in Figure 2. If the shower head is free-standing,
the generally accepted dimension for the mounting height is 7
ft 0 in. (2.17 m) above the foor. Generally accepted clearance
around showers and eye/face washes is illustrated in Figure 3. A
wheelchair-accessible, free-standing, combination unit is illus-
trated in Figure 4.
Equipment Location
Te location of the emergency drench equipment is crucial to
the immediate and successful frst-aid treatment of an accident
victim. It should be located as close to the potential hazard as is
practical without being afected by the hazard itself or potential
accidental conditions, such as a large release or spray of chemi-
JULY/AUGUST 2006 Plumbing Systems & Design
cals resulting from an explosion or a pipe and tank rupture.
Another location problem is placement adjacent to electrical
equipment. Location on normal access and egress paths in the
work area will reinforce the location to personnel, who will see
it each time they pass.
Tere are no requirements in any code pertaining to the loca-
tion of any drench equipment in terms of specifc, defnitive
dimensions. ANSI code Z-358.1 requires emergency showers be
located a maximum distance of either 10 seconds travel time by
an individual or no more than 75 ft (22.5 m) from the potential
protected hazard, whichever is shorter. If strong acid or caus-
tic is used, the equipment should be located within 10 ft (3 m)
of the potential source of the hazard. Te path to the unit from
the hazard shall be clear and unobstructed, so impaired sight or
panic will not prevent clear identifcation and access. Tere is
no regulation as to what distance could be covered by an indi-
vidual in 10 seconds. Tere are also no specifc provisions for
the physically challenged.
Since there are no specifc code requirements for locat-
ing drench equipment, good judgment is required. Accepted
practice is to have the equipment accessible from three sides.
Anything less generally creates a tunnel efect that makes it
more difcult for the victim to reach the equipment. It should be
located on the same level as the potential hazard when possible.
Traveling through rooms that may have locked doors to
reach equipment shall be avoided, except placing emer-
gency showers in a common corridor, such as outside
individual laboratory rooms, is accepted practice. Care
should be taken to avoid locating the shower in the path
of the swinging door to the protected room to prevent
personnel coming to the aid of the victims from knock-
ing them over.
Emergency eye/face washes should be located close
to the potential source of hazard. In laboratories,
accepted practice is to have 1 sink in a room ftted with
an eyewash on the counter adjacent to the sink. Te sink
cold-water supply provides water to the unit. Te eye-
wash could be designed to swing out of the way of the
sink if desired.
Visibility of Devices
High visibility must be considered in the selection of
any device. Te recognition methods usually selected
are high-visibility signs mounted at or on the device;
having the surrounding foors and walls painted a con-
trasting, bright color; and having the device in a bright,
well lit area on the plant foor to help a victim identify
the area and help in frst-aid activities.
Number of Stations
Te number of drench-equipment devices provided
in a facility is a function of the number of people in
rooms and areas with potential exposure to any par-
ticular hazard at any one time, based on a worst-case
scenario. It is rare for more than one combination unit
to be installed. It is important to consider if a group of
individuals has potential exposure to a specifc hazard,
more than one drench unit may be required. Consulting
with the end user and the safety ofcer will provide a
good basis for the selection of the type and number of
equipment.
Generally, one shower can be provided between an
adjacent pair of laboratories, with emergency eye/face washes
located inside each individual laboratory. In open areas, it is
common practice to locate emergency equipment adjacent to
columns for support.
Water Temperature
Code now requires tempered water of approximately 85F be
supplied to equipment. A comfortable range of 60 to 95F (15
to 35C) is mentioned in the code. For most indoor applica-
tions, this temperature range is achieved because the interior
of a facility is heated in the winter and cooled in the summer to
approximately 70F (20 C). Since the water in the emergency
drench system is stagnant, it assumes the temperature of the
ambient air. A generally accepted temperature of between 80
and 85F (27 and 30C) has been established as a comfort zone
and is now the recommended water temperature.
Te body will attempt to generate body heat lost if the
drenching fuid is at a temperature below the comfort zone. Te
common efect is shivering and increased heart rate. In fact,
most individuals are uncomfortable taking a shower with water
at about 60F (15C). With the trauma induced by an accident,
the efect is escalated.
Another consideration is the potential chemical reaction
and/or acceleration of reaction with fushing water or water at
Figure 4 Wheelchair-Accessible Shower and Eyewash Equipment
Plumbing Systems & Design JULY/AUGUST 2006 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Life-Safety Systems
a particular temperature. Where the hazard is a solid, such as
radioactive particles, that can enter the body through the pores,
a cold-water shower shall be used in spite of its being uncom-
fortable. It is necessary to obtain the opinions of medical and
hygiene personnel where any doubt exists about the correct use
of water or water temperature in specifc facilities.
Where showers are installed outdoors, or indoors where heat-
ing is not provided, the water supplying the showers must be
tempered if the air temperature is low. Manufacturers ofer a
variety of tempering methods, including water-temperature
maintenance cable similar to that used for domestic hot-water
systems for this purpose and mixing valves with hot and cold-
water connections. In remote locations, complete self-contained
units are available with storage tanks holding and maintaining
heated water.
Protection Against Temperature Extremes
In areas where freezing is possible and water drench equipment
is connected to an above-ground, plumbed water supply, freeze
protection is required. Tis is most often accomplished by using
electric heating cable and providing insulation around the
entire water-supply pipe and the unit itself. It is recommended
the water temperature be maintained at 85F (20C).
For exterior showers located where freezing is possible, the
water supply shall be installed below the frost line and a freeze-
proof shower shall be installed. Tis type of shower has a method
of draining the water above the frost line when the water to the
drench equipment is turned of.
When a number of drench-equipment
devices are located where low temperature is
common, a circulating tempered-water supply
should be considered. Tis uses a water heater
and a circulating pump to supply the drench
equipment. Te heater shall be capable of gen-
erating water from 40 to 80F at a rate of 30 gpm
(or more if more than one shower could oper-
ate simultaneously).
In areas where the temperature may get too
high, it is accepted practice to insulate the
water-supply piping.
BrEathIng-aIr SyStEmS
gEnEral
Breathing-air systems supply air of a specifc
minimum purity to personnel for purposes
of escape and protection after exposure to
a toxic environment resulting from an acci-
dent or during normal work where conditions
make breathing the ambient air dangerous.
As defned by 30 CFR 10, a toxic environment
has air that may produce physical discomfort
immediately, chronic poisoning after repeated
exposure, or acute adverse physiological symp-
toms after prolonged exposure.
Tis section discusses the production, puri-
fcation, and distribution of a low-pressure
breathing air and individual breathing devices
used to provide personnel protection only
when used with supplied air systems. Low pres-
sure for breathing air refers to compressed air
pressures up to 250 psig (1725 kPa) delivered to
the respirator. Te most common operating range for systems is
between 90 and 110 psig (620 and 760 kPa).
Much of the equipment used in the generation, treatment,
and distribution of compressed air for breathing-air systems is
common to that for medical/surgical air discussed in the Com-
pressed-Gas Systems chapter.
codES and StandardS
1. OSHA: 29 CFR 1910.
2. CGA: commodity specifcations G-7 and G-7.1.
3. Canadian Standards Association (CSA).
4. National Institute of Occupational Safety and Health
(NIOSH).
5. Mine Safety and Health Act (MSHA).
6. NFPA: NFPA-99, Medical Compressed Air.
7. DOD (Department of Defense): Where applicable.
8. ANSI: Z-88.2, Standard for Respiratory Protection.
9. Code of Federal Regulations (CFR).
BrEathIng-aIr purIty
Air for breathing purposes supplied from a compressor or a
pressurized tank must comply, as a minimum, with quality
verifcation level grade D in CGA G-7.1 (ANSI Z-86.1). Table 1,
from ANSI/CGA G-7.1, lists the maximum contaminant levels
for various grades of air.
For grade D quality air, individual limits exist for condensed
hydrocarbons, carbon monoxide, and carbon dioxide. Particu-
Table 1 Maximum Contaminant Levels for Various Grades of Air
(in ppm [mole / mole] unless shown otherwise)
Limiting Characteristics A K L D E G J M N
Percent O
2
balance
predominantly N
2
a
atm /
19.5 -
23.5
atm /
19.5 -
23.5
atm /
19.5 -
23.5
atm /
19.5 -
23.5
atm /
20 -
22
atm /
19.5 -
23.5
atm /
19.5 -
23.5
atm /
19.5 -
23.5
atm /
19.5 -
23.5
Water, ppm (v / v)
b
200 50 1 3
Dew point, F
b
-33 -54 -104 -92
Oil (condensed) (mg / m
3
at NTP) 5
c
5
c
None
d
Carbon monoxid 10
e,f
10 5 1 1 10
Odor None
Carbon dioxide 1000
f
500 500 0.5 1 500
Total hydrocarbon
content (as methane) 25 25 15 0.5 1
Nitrogen dioxide Nitric
oxide
2.5 0.1
}
0.5 2.5
Sulfur dioxide 2.5 0.1 5
Halogenated Solvents 10 0.1
Acetylene 0.05
Nitrous oxide 0.1
USP Yes
Source: ANSI / CGA G-7.1.ANSI 2-86.1, Table 1.
Note: The 1973 edition of CGA G-7.1 listed nine quality verifcation levels of gaseous air, lettered A to J, and two quality verifcation levels
of liquid air, lettered A and B. Some of those letter designations were dropped from the 1989 edition, since they no longer represent major
volume usage by industry. Four new letter designations, K, L, M, and N, have been added to refect current specifcations. To get a listing of
quality verifcation levels dropped, see CGA-7-1-1973 or contact the Compressed Gas Association.
a The term atmospheric (atm) denotes the oxygen content normally present in atmospheric air; the numerical values denote the oxygen
limits for synthesized air.
b The water content of compressed air required for any particular quality verifcation level may vary with the intended use from saturated
to very dry. For breathing air used in conjunction with a self-contained breathing apparatus in extreme cold where moisture can
condense and freeze, causing the breathing apparatus to malfunction, a dew point not to exceen -50F (63 ppm v / v), or 10 lower
than the coldest temperature expected in the area, is required. If a specifc water limit is required, it should be specifed as a limiting
concentration in ppm (v / v) or dew point. Dew point is expressed in F at 1 atmosphere pressure absolute, 101 kPa abs. (760 mm Hg).
c Not required for synthesized air whose oxygen and nitrogen components are produced by air liquefaction.
d Includes water.
e Not required for synthesized air when the nitrogen component was previously analyzed and meets National Formulary (NF) specifcation.
f Not required for synthesized air when the oxygen component was produced by air liquefaction and meets United States Pharmacopeia
(USP) specifcation.
JULY/AUGUST 2006 Plumbing Systems & Design
lates and water vapor, whose allowable quantities have not been
established, must also be controlled because of the efects they
may have on diferent devices of the purifcation system, on the
piping system, and on the end user of the equipment.
Contaminants
Condensed Hydrocarbons Oil is a major contaminant in
breathing air. It causes breathing discomfort, nausea, and, in
extreme cases, pneumonia. It can also create an unpleasant
taste and odor and interfere with an individuals desire to work.
In addition, the oxidation of oil in overheated compressors can
produce carbon monoxide. A limit of 5 ppm has been estab-
lished.
Some types of reciprocating and rotary-screw compressors
put oil into the airstream as a result of their operating character-
istics. Accepted practice is to use only oil-free air compressors
in order to eliminate the possibility of introducing oil into the
airstream.
Carbon Monoxide Carbon monoxide is the most toxic of
the common contaminants. It enters the breathing-air system
through the compressor intake or is produced by the oxidation
of heated oil in the compressor. Carbon monoxide easily com-
bines with the hemoglobin in red blood cells, replacing oxygen.
Te lack of oxygen causes dizziness, loss of motor control, and
loss of consciousness. A limit of 10 ppm in the airstream has
been established based on NIOSH standards.
Carbon Dioxide Carbon dioxide is not considered one of
the more dangerous contaminants. Although the lungs have
a concentration of approximately 50,000 ppm, a limit of 1,000
ppm has been established for the breathing airstream.
Water and Water Vapor Water vapor enters the piping
system through the air compressor intake. Since no upper or
lower limits have been established by code, the allowable con-
centration is governed by specifc operating requirements of
the most demanding device in the system, which is usually the
CO converter, or the requirement of being 10F lower than the
lowest possible temperature the piping may experience.
After compression, water vapor is detrimental to the media
used to remove CO. Te dew point of the airstream must be
greatly lowered at this point in order to provide the highest ef-
ciency possible for this device. Water vapor is removed to such a
low level that breathing air with this level of humidity will prove
uncomfortable to users.
After purifcation, too much humidity will fog the faceplate of
a full face mask. It will also cause freeze-up in the pipeline if the
moisture content of the airstream in the pipe has a dew point
that is higher than the ambient temperature of the area where
the compressed-air line is installed.
Solid Particles Solid particles known as particulates can
enter the system through the intake. Tey are released from
non-lubricated compressors as a result of friction from carbon
and Tefon material used in place of lube oils. No limits on par-
ticulates have been established by code.
Odor Tere is no standard for odor measurement. A gener-
ally accepted requirement is that there be no detectable odor in
the breathing air delivered to the user. Tis requirement is sub-
jective and will vary with individual users.
typES of SyStEm
Tere are three basic types of breathing-air system: constant
fow, demand fow, and pressure demand.
Constant-Flow System
Also known as a continuous-fow system, the constant-fow
system provides a continuous fow of purifed air through per-
sonnel respirators to minimize the leakage of contaminants into
the respirator and to ventilate the respirator with cool or warm
air depending on conditions.
Tis system could be used in a wide variety of areas, ranging
from least harmful to most toxic, depending on the type of res-
pirator selected.
Demand-Flow System
Te demand-fow system delivers purifed air to personnel res-
pirators only as the individual inhales. Upon exhalation, the
fow of air is shut of until the next breath. Demand-fow systems
automatically adjust to an individuals breathing rate.
Tis system requires tight-ftting respirators. Its application
is generally limited to less harmful areas because the negative
pressure in the respirator during inhalation may permit leakage
of external contaminants. Tis system is designed for economy
of air use during relatively short-duration tasks and is usually
supplied from cylinders.
Pressure-Demand System
A pressure-demand system delivers purifed air continuously
through personnel respirators with increased air fow during
inhalation. By continuously providing a fow of air above atmo-
spheric pressure, leakage of external contaminants is mini-
mized.
Tis system also uses tight-ftting respirators, but the positive
pressure aspect allows them to be used in more toxic applica-
tions.
SyStEm componEntS
Te breathing-air system consists of a compressed-air source,
purifcation devices and flters to remove unwanted contami-
nants from the source airstream, humidifers to introduce water
vapor into the breathing air, the piping distribution network,
respirator outlet manifolds, respirator hose, and the individual
respirators used by personnel. Alarms are needed to monitor the
quantity of contaminants and other parameters of the system as
a whole and to notify personnel if necessary.
Compressed-Air Source
Te source of air for the breathing-air system is an air compres-
sor and/or high-pressure air stored in cylinders. Cylinders use
ambient air, which is purifed to reduce or eliminate impurities
to the required level, and compress it to the desired pressure. A
typical schematic detail is shown in Figure 5.
Air Compressor Te standard for air compressors used to
supply breathing air shall comply with the requirement for oil-
free medical gas discussed in the Compressed-Gas Systems
chapter. Medical-gas type compressors are used because these
systems as a whole generate far fewer contaminants than other
types of system. When a liquid-ring compressor is used, it has
the advantage of keeping the temperature of the air leaving the
unit low. It is also possible to use any type of compressor for this
service, provided the purifcation system is capable of produc-
ing air meeting all the requirements of code.
Te air-compressor assembly consists of the intake assem-
bly (including the inlet flter), the compressor and receiver, the
aftercooler, and the interconnecting water-seal supply and the
other ancillary piping. All of these components are discussed in
the Specialty Gases for Laboratories section.
Plumbing Systems & Design JULY/AUGUST 2006 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Life-Safety Systems
Air compressors have a high frst cost and are selected if the
use of air for breathing is constant and continuous, making the
use of cylinders either too costly or too maintenance intensive
because of the frequent changing of cylinders.
Storage Cylinder When high-pressure cylinders are used
either as a source or as an emergency supply of breathing air,
they shall be flled with air conforming to breathing-air stan-
dards. Te regulator should be set to about 50 psi (340 kPa)
depending on the pressure required to meet system demands
and losses.
Te cylinders have a low initial cost and are not practical to
use if there is continuous demand. Cylinders are best suited to
intermittent use for short periods of time or as an emergency
escape backup for a compressor.
Aftercooler
Some components of the purifcation system require a specifc
temperature in order to function properly. Depending on the
type of compressor selected and the type of purifcation nec-
essary, the temperature of the air leaving the compressor may
have to be reduced. Tis is done with an aftercooler.
Aftercoolers can be supplied with cooling water or use air
as the cooling medium. Water, if recirculated, is the preferred
method. Te manufacturer of both the compressor and purif-
cation system should be consulted as to the criteria used and
the recommended size of the unit.
Purifcation Devices
Te contaminants that are problematic for breathing-air systems
must be removed. Tis can be done with separate devices used
to remove individual contaminants or with a prepiped assem-
bly of all the necessary purifcation devices, commonly referred
to as a purifcation system, which requires only an inlet and
outlet air connection. For breathing-air systems it is commonly
done with a purifcation system.
Te individual purifcation methods used to remove specifc
contaminants are the same as those discussed in the Com-
pressed-Gas Systems chapter. For breathing air, oil and par-
ticulates are removed by coalescing and other flters, water is
removed by desiccant or refrigerated dryers, and carbon mon-
oxide is removed by chemical conversion to carbon dioxide
using a catalytic converter.
Carbon Monoxide Converter Te purpose of the converter
is to oxidize carbon monoxide and convert it into carbon diox-
ide, which is tolerable in much greater quantities. Tis is typi-
cally accomplished by the use of a catalyst usually consisting
of manganese dioxide, copper oxide, cobalt, and silver oxide in
various combinations and placed inside a single cartridge. Te
material is not consumed but does become contaminated. Te
conversion rate greatly decreases if any oil or moisture is present
in the airstream. Terefore, moisture must be removed before
air enters the converter. Catalyst replacement is recommended
generally once a year since it is not possible to completely con-
trol all contaminants that contribute to decreased conversion.
Moisture Separator Water and water vapor are removed
by two methods, desiccant and refrigerated dryers. Te most
common desiccant drying medium is activated alumina. For a
discussion of air-drying methods, refer to the Compressed-Gas
Systems systems.
Odor Remover Activated, granular charcoal in cartridges is
used for the removal of odors.
Particulates Remover Particulates are removed by means
of in-line flters. Generally accepted practice eliminates particu-
lates 1 and larger from the piping system .
Figure 5 System with Standby High-Pressure Breathing Air Reserve
S
o
u
r
c
e
:
C
o
u
r
t
e
s
y
o
f
N
o
m
o
n
o
x
.
JULY/AUGUST 2006 Plumbing Systems & Design
Humidifer
When water is removed from the compressed airstream prior
to catalytic conversion, the dryer produces very dry air. If the
breathing-air system is intended to be used for long periods
of time, very low humidity will dry the mucous membranes of
the eyes and mouth. Terefore, moisture must be added to the
airstream to maintain recommended levels. Humidifers, often
called moisturizers, are devices that inject the proper level of
water vapor into an airstream. Some require a water connec-
tion.
A recommended level of moisture is 50% relative humidity
in the compressed airstream. Care must be taken not to route
the air-distribution piping through areas capable of having tem-
peratures low enough to cause condensation. If the routing is
impossible to change, a worker will have shorter periods of time
on the respirator.
Combination Respirator Manifold and Pressure Reducer
Tis is a single component with multiple quick-disconnect out-
lets providing a convenient place both to reduce the pressure of
the distribution network and to serve as a connection point for
several hoses. A pressure gauge should be installed on the man-
ifold to ensure the outlet pressure is within the limits required
by the respirator.
Respirator Hose
Te respirator hose is fexible and is used to connect the res-
pirator worn by an individual to the central-distribution piping
system. Code allows a maximum hose length of 300 ft (93 m)
Personnel Respirators
Tere are two general categories of respirator used for individual
protection: air purifying and supplied air.
Te air-purifying type of respirator is portable and has self-
contained flters that purify the ambient air on a demand basis.
Te advantages to its use are that it is less restrictive to move-
ments and is light in weight. Disadvantages are that it must not
be used where gas or vapor contamination cannot be detected
by odor or taste and in an oxygen-defcient atmosphere. Tis
type of respirator is outside the scope of this book, it is men-
tioned only because of its availability.
Te type of respirator selected depends on the expected
breathing hazards. In the choice of a respirator, the highest
expected degree of hazard, applicable codes and standards,
manufacturer recommendations, suitability for the intended
task and the comfort of the user are all important consider-
ations.
Te EPA Ofce of Emergency and Remedial Response has
identifed four levels of hazard at cleanup sites involving haz-
ardous materials and lists guidelines for the selection of protec-
tive equipment for each:
1. Level A calls for maximum available protection, requiring a
positive-pressure, self-contained suit, generally with a self-
contained breathing apparatus worn inside the protective
suit.
2. Level B protection is required when the highest level of
respiratory protection is needed but a lower level of skin
protection is acceptable.
3. Level C protection uses a full face piece and air-purifying
respiratory protection with chemical resistant, disposal
garments. Tis is required when the contaminant is known
and the level is relatively constant. Typical of its uses is for
asbestos removal.
4. Level D protection is used where special respiratory or skin
protection is not required but a rapid increase of contami-
nant level or degradation of ambient oxygen content is pos-
sible.
If the hazard cannot be identifed, it must be considered an
immediate danger to life and health (IDLH). Tis is a condition
that exists when the oxygen content falls below 12.5% (95 ppm
O
2
) or where the air pressure is less than 8.6 psi (450 mm/Hg),
which is the equivalent of 14,000 ft (4270 m).
Tere are fve general types of respirator available, as follows:
Mouthpiece Respirators Used only with demand type
systems, mouthpiece respirators are designed only to deliver
breathable air. Tey ofer no protection to the skin, eyes, or face.
Teir use is limited to areas where there is insufcient oxygen
and no other contaminants could afect the eyes and skin.
Half-Face-Piece Respirators Half-face-piece respira-
tors cover the nose and mouth and are designed primarily for
demand and pressure type systems. Tey are usually tightftting
and provide protection for extended periods of time in atmo-
spheres that are not harmful to the eyes and skin. Often worn
with goggles, these respirators are limited to areas of relatively
low toxicity.
Full-Face-Piece Respirators Full-face-piece respirators
cover the entire face and are designed for use with constant-fow
and pressure-demand systems. Tey are tightftting and suitable
for atmospheres of moderate and high toxicity. Tey are usually
used in conjunction with full protective clothing for such tasks
as chemical-tank cleaning where corrosive and toxic gas, mist,
and liquids may be present. Since the face masks provide pro-
tection to the face and eyes, they are also suitable for other tasks,
such as welding and the inspection of tanks and vessels where
there is an oxygen-defcient atmosphere.
Hood-and-Helmet Respirators Hood-and-helmet respira-
tors cover the entire head and are normally used with a con-
stant-fow system. Tey are loose ftting and suitable only for
protection against contaminants such as dust, sand, powders,
and grit. Constant fow is necessary to ventilate the headpiece
and to provide sufcient air pressure to prevent contaminants
from entering the headpiece.
Full-Pressure Suits Full-pressure suits range in design from
loose-ftting, body-protective clothing to completely sealed,
astronaut-like suits that provide total environmental life sup-
port. Tey are designed to be used only with constant-fow sys-
tems and are suitable for the most toxic and dangerous environ-
ments and atmospheres.
componEnt SElEctIon and SIzIng
Breathing-Air Source
Air Compressor Te air-compressor size is based on the high-
est fow rate, in cfm (L/min), required by the number and type
of respirators intended to be used simultaneously and the mini-
mum pressure required by the purifcation system.
Te following general fow rates are provided as a prelimi-
nary estimate for various types of respirator. Since there is a
wide variation in the pressure and fow rates required for vari-
ous types of respirator, the actual fgures used to size the system
must be based on the manufacturers recommendations for the
specifc respirators selected.
1. 4 scfm (113 L/min) for pressure-demand respirators.
2. 6 scfm (170 L/min) for constant-fow respirators.
10 Plumbing Systems & Design JULY/AUGUST 2006 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Life-Safety Systems
3. Up to 16 scfm (453 L/min) for fooded-hood respirators.
4. Up to 35 scfm (990 L/min) for fooded suits.
5. Add 15 scfm (425 L/min) of air for suit cooling if used.
High-Pressure Storage Cylinder High pressure cylinders
are used either to supply air for normal operation to a limited
number of personnel for short periods of time or as an emer-
gency supply to provide a means of escape from a hazardous
area if the air compressor fails. Te main advantage to using
cylinders is the air in the cylinders is prepurifed, and no further
purifcation of the air is necessary.
Te number of cylinders is based on the simultaneous use of
respirators, the cfm (L/min) of each and the duration, in min,
the respirators are expected to be used, plus a 10% safety factor.
Te total amount of compressed air in the cylinders should not
be allowed to decrease too low. A low-pressure alarm should
sound when pressure falls to 500 psig (3450 kPa) in a cylinder
normally pressurized to 2400 psig (16 500 kPa) when flled to
capacity.
Example 9-1
Establish the number of cylinders required for an emergency
supply of air for 8 people using constant-fow respirators require
15 min to escape the area.
1. 8 6 15 = 720 scfm + 72 (10%) = 792 scfm total required
2. Next, fnd the actual capacity of a single cylinder at the
selected high pressure, generally 2400 psi (16 500 kPa),
and divide the capacity of each cylinder into the total scfm
required to fnd the number of cylinders required.
3. If 1 cylinder has 225 scf, 792 225 = 3.5. Use 4 cylinders.
Purifcation Components
Te air used to fll breathing-air cylinders is purifed before
being compressed. Breathing air produced by air compressors
requires purifcation to meet minimum code standards for
breathing air.
Prior to the selection of the purifcation equipment, several
samples of the air where the compressor intake is to be located
should be taken so specifc contaminants and their amounts
can be identifed. Te ideal situation is to have the tests taken at
diferent times of the year and diferent times of the day. Tese
tests quantify the type and amount of contaminants present at
the intake. With this information known, the purifcation sys-
tems needed to meet code criteria can be chosen. Te other
requirement is the highest fow rate that can be expected. With
these criteria, the appropriate size and types of purifer can be
selected.
Te most commonly used method of purifcation is an assem-
bly of devices called a purifcation system specifcally chosen
and based on the previously selected criteria. Manufacturers
recommendations are commonly followed in the selection and
sizing of the assembly.
Carbon-Monoxide Converter Te requirement for installa-
tion of a carbon-monoxide converter is rare. Te need for a con-
verter is based on tests of the air at the proposed location of the
compressor intake. Another source of information is the EPA,
which has conducted tests in many urban areas throughout the
country. Another indication that installation may be necessary
is the use of a non-oil-free compressor. Good practice requires
the installation of a converter if there is an outside chance the
level of carbon monoxide may rise above the 10 ppm limit set
by code.
Te converter is sized based on the fow rate of the system.
Coalescing Filter/Separator Te coalescing flter/separa-
tor is a single unit that removes large oil and water drops and
particulates from the airstream before the air enters the rest of
the system. It is selected on the basis of maximum system pres-
sure, fow rate, and the expected level of contaminants leaving
the air compressor, using manufacturers recommendations. If
an oil-free compressor is used, a simple particulate flter could
be substituted for the coalescing flter.
Dryers (Moisture Separators)
Desiccant Dryers Te two types of desiccant media dryer most
commonly used are the single-bed dryer, which is a disposable
cartridge, and the continuous-duty, two-bed dryer.
When two-bed dryers are used, a portion of the air from the
compressor is used for drying one bed while the other is in ser-
vice. Te compressor must be capable of producing enough air
for both the system and dryer use.
Te single-bed dryer has a lower frst cost but a higher operat-
ing cost. Te disposable cartridge often is combined with other
purifcation devices into a single, prepiped unit. An indicator is
often added to the media so the need for replacement is indi-
cated by a color change.
Disposable units are best suited for short durations or occa-
sional use, such as for replacement of a main unit during peri-
ods of routine service. Because of their generally small size, only
a limited number of respirators can be supplied from a single
unit. Other considerations are that these disposable units have
a limited capacity, in total cfh, they can process. Manufacturers
recommendations must be used in the selection of the size and
number of replacement cartridges required for any application.
Te two-bed unit, commonly called a heatless dryer, is simi-
lar in principle to that discussed in the Compressed-Gas Sys-
tems chapter. Such units are used for continuous duty.
Te two factors contributing to the breakdown of media are
fast-drying cycles and high air velocity. If a desiccant dryer is
selected, the velocity of air through the unit shall conform to
manufacturers recommendations. Velocity should be as low
as is practical to avoid fuidizing the bed. High velocity requires
more cycles for drying, which means wasting more air. If the
size of the dryer is a concern, more drying cycles means smaller
dryer beds. Longer drying cycles reduce component wear.
Refrigerated Dryers Refrigerated dryers are used if there is
no requirement for a nitrous oxide converter and if the 3539F
dew point produced is 10F below the lowest ambient air tem-
perature where any pipe will be installed. Te refrigerated dryer
is less efcient than the desiccant dryer. Its advantages are that
all the air produced by the compressor is available to the system
and it has a lower pressure loss.
When refrigerated dryers are preferred, several purifcation
devices are often combined into a single unit, including the
refrigeration unit, flter/separator for oil and water, and a char-
coal flter for odor removal. Tis unit produces air that is lower
in temperature than the inlet air.
If the breathing-air distribution piping is to be routed through
an area of lower temperature, the pressure dew point of the air
must be reduced to 10F lower than the lowest temperature
expected.
Odor Remover Odors are not usually a problem, but their
removal is provided for as a safeguard. Te activated charcoal
cartridges remove odors are selected using manufacturers rec-
JULY/AUGUST 2006 Plumbing Systems & Design 11
ommendations based on the maximum calculated fow rate of
the breathing-air system. Te cartridges must be replaced peri-
odically.
Humidifers
Often called a moisturizer, a humidifer is required to increase
the relative humidity of the breathing air to approximately 50%
if required. Te unit is selected using the increase in moisture
required for the airstream and the fow rate of air. Caution must
be used so as not to increase the dew point of the compressed
air above a temperature 10F lower than the lowest temperature
in any part of the facility the pipe is routed through.
Respirator Hose
Te respirator hose most often used to connect the respirator
worn by an individual to the central-distribution piping system
is
3
8 in. (10 mm) in size. Code allows a maximum hose length of
300 ft (93 m). Te most common lengths are between 25 and 50
ft (7.75 and 15.5 m).
System Sizing Criteria
System Pressure Te outlet pressure of the compressor shall
be within the range required by the purifcation system. Typi-
cally, the pressure is approximately 100 psi (70.3 kg/cm2). Te
precise range of pressure and fow rate shall be obtained from
the purifcation system manufacturer selected for the project.
Te pressure in the distribution system should be as high as
possible to reduce the size of the distribution-piping network.
Code requires the pressure be kept below 125 psi (88 kg/cm2).
Te distribution-piping pressure range is usually 90 to 110 psig
(620 to 760 kPa) available in the system after the purifer.
Te pressure required at the respirator ranges from approxi-
mately 15 psig for pressure-demand respirators to 80 psig for
full-fooded suits that require cooling. Te actual requirements
can be obtained only from the manufacturer of the proposed
equipment because of the wide variations possible. Pressure-
regulating valves shall be installed to reduce the pressure to the
range acceptable to the respirator used. Often, this reduction
is done at the respirator manifold, if one is used, or, if a single
respirator type with a single pressure is used throughout the
facility, a single regulator can be installed to reduce the pressure
centrally.
Pipe Sizing and Materials Te most commonly used pipe
is type L copper tubing, with wrought copper fttings and brazed
joints.
For pipe sizing, follow the sizing procedure discussed in the
Compressed-Gas Systems chapter. Te number of simultane-
ous users must be obtained from the facility. No diversity factor
should be used.
Alarms and Monitors
Te following alarms and monitors are often provided:
CO Monitor Usually included as a built-in component, this
monitor measures the CO content of the airstream and sounds
an alarm when the level reaches a predetermined high set
point.
Oxygen-Defciency Monitor Used as a precautionary mea-
sure in an area where respirators are not normally required,
the oxygen monitor measures the oxygen content of the air in a
room or other enclosed area and sounds an alarm to alert per-
sonnel when the level falls below a predetermined level. Usu-
ally, several alarm points are annunciated prior to reaching a
level low enough to require the use of respirators.
Low-Air-Pressure Monitor Te low-air-pressure monitor
must sound an alarm when the pressure in the system reaches
a predetermined low point. Tis set point allows the users of
the breathing-air system to leave the area immediately while
still being able to breathe from the system. For cylinder storage,
this set point is about 500 psig in the cylinders. For a compres-
sor system, the alarm should sound when the pressure falls to
a point 10 psig below the pressure set to start the compressor.
Tis should also switch over to the emergency backup supply
if one is used. If no backup is used, the pressure set point shall
be 5 psig higher than the minimum required by the respirators
being used.
Dew-Point Monitor A dew-point monitor is used to mea-
sure the dew point and sound an alarm if it falls to a low point,
set by a health ofcer, that might prove harmful to the users. It is
required to alarm if the dew point reaches a point high enough
to freeze in some parts of the system.
High-Temperature Air Monitor Some purifers or purifer
components will not function properly if the inlet air tempera-
ture is too high. Te set point is commonly 120 F but will vary
among diferent manufacturers and components.
Failure-to-Shift Monitor Tis monitor is placed on des-
iccant dryers to initiate an alarm if the unit fails to shift from
the saturated dryer bed to the dry bed when regeneration is
required.
1 Plumbing Systems & Design JULY/AUGUST 2006 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Life-Safety Systems
CONTINUING EDUCATION
P
S
D
1
3
4
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
CE QuestionsLife-Safety Systems (PSD 134)
About This Issues Article
The July/August 2006 continuing education article is
Life-Safety Systems, Chapter 8 of Pharmaceutical Facilities
Plumbing Systems by Michael Frankel. This chapter describes
water-based emergency drench equipment and systems
commonly used as a first-aid measure to mitigate the effects
of such an accident. Also described are the breathing-air
systems that supply air to personnel for escape and protec-
tion when they are exposed to either a toxic environment
resulting from an accident or normal working conditions
that make breathing the ambient air hazardous.
You may locate this article at www.psdmagazine.org.
Read it, take the following exam, and submit it to the ASPE
office to potentially receive 0.1 CEU (comparable to 1.0 PDH).
1. The recommended supply pipe size to an emergency
shower is ________.
a. inch, b. 1 inch, c. 1 inches, d. 1 inches
. Since oil is a major contaminant in breathing air
systems, the maximum allowed is ___________.
a. 5 ppm, b. 5 ppb, c. 10 ppm, d. 10 ppb
. An emergency shower drench hose is used to _________.
a. wash the foor after a chemical spill
b. irrigate the body under the clothing prior to removal of
the clothing
c. provide a means to fll mop bucket
d. none of the above
. A failure-to-shift monitor is ___________.
a. used to control multi-stage compressors
b. used to initiate an alarm if a desiccant dryer fails to
shift from the saturated bed to the dry bed when
regeneration is required
c. used to coordinate the output signal of the low air
pressure monitor and the refrigerated dryer
d. not required on modern systems
. In areas where strong acid or caustic is used, the
emergency shower and eyewash equipment should be
located within ___________ feet of the potential source
of the hazard per ANSI code Z-.1.
a. 5, b. 10, c. 15, d. 20
. What is the established comfort zone water temperature
for emergency drench equipment?
a. 7075F, b. 7580F, c. 8085F, d. 8590F
. As defned by 0 CFR 10, a toxic environment has air
that ___________.
a. may produce physical discomfort immediately
b. may cause chronic poisoning after repeated exposure
c. may cause acute adverse physiological symptoms after
prolonged exposure
d. all of the above
. The code-required fow rate from an emergency shower
is ___________ gpm.
a. 25, b. 30, c. 35, d. 40
. How many cylinders of air are required for an
emergency supply of air for eight people using pressure
demand respirators needing 1 minutes to escape the
area?
a. 2.3 use 3 cylinders
b. 3.5 use 4 cylinders
c. 4.7 use 5 cylinders
d. cannot be determined
10. Refrigerated dryers are used ___________.
a. when money is of no concern
b. when order removal is not required
c. when system pressure is high enough to accommodate
them
d. none of the above
11. The minimum diameter of the spray pattern from an
emergency shower, measured at 0 inches above
the surface on which the user stands, is ___________
inches.
a. 18, b. 20, c. 22, d. 24
1. An oxygen content below 1. percent and/or a pressure
of . psi should be considered ___________.
a. as a Level A hazard as established by the EPA
b. as a Level C hazard as established by the EPA
c. as a Level E hazard as established by the EPA
d. as an immediate danger to life and health
Do you fnd it difcult to obtain continuing education units (CEUs)?
Trough this special section in every issue of PS&D, ASPE can help
you accumulate the CEUs required for maintaining your Certifed in
Plumbing Design (CPD) status.
Now Online!
Starting with this issue, the technical article you must read to com-
plete the exam will be located at www.psdmagazine.org. Te following
exam and application form also may be downloaded from the Web site.
Reading the article and completing the form will allow you to apply to
ASPE for CEU credit. For most people, this process will require approxi-
mately one hour. If you earn a grade of 90 percent or higher on the test,
you will be notifed that you have logged 0.1 CEU, which can be applied
toward the CPD renewal requirement or numerous regulatory-agency
CE programs. (Please note that it is your responsibility to determine the
acceptance policy of a particular agency.) CEU information will be kept
on fle at the ASPE ofce for three years.
Note: In determining your answers to the CE questions, use only the material
presented in the corresponding continuing education article. Using information
from other materials may result in a wrong answer.
1 Plumbing Systems & Design JULY/AUGUST 2006 PSDMAGAZINE.ORG
P
S
D
1
3
6
Animal-care
Facility
Piping
Systems
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
NOVEMBER/DECEMBER 2006
PSDMAGAZINE.ORG
INTRODUCTION
Tis chapter discusses various piping systems uniquely associ-
ated with the physical care, health, and well-being of labora-
tory animals. Included are various utility systems for animal
watering, water treatment, room and foor cleaning, equipment
washing, cage fushing and drainage, and other specialized
piping required for laboratory and experimental work within
the facility. Other systems involved with general laboratory and
facility work, such as those for compressed gases and plumbing,
are discussed in their respective chapters.
GeNeRal
It is expected that a facility involved with long-term studies
will have diferent operating and animal drinking-water qual-
ity requirements than one used for medical research. For criti-
cal studies, the various utility systems shall incorporate design
features necessary to ensure reliability and provide a consistent
environment. As many variables as are practical (or desirable)
shall be eliminated to ensure the accuracy of the ongoing exper-
iments being conducted. Regardless of the facility type, diferent
users and owners have individual priorities based on experi-
ences, operating philosophies, and corporate cultures that must
be established prior to the start of the fnal design phase of a
project.
CODes aND sTaNDaRDs
1. Te local codes applicable to plumbing systems must
be observed in the design and installation of ordinary
plumbing fxtures and potable water and drainage lines for
the facility.
2. 10-CFR-58 is the code (by the agencies of the federal
government) for good laboratory practice for nonclinical
laboratory studies.
3. 21-CFR-211, cGMP, requires compliance with FDA
protocols for pharmaceutical applications.
4. NIH publication 86-23, Guide for the Care and Use of
Laboratory Animals.
5. American Association for Accrediation of Laboratory
Animal Care (AAALAC). Inspection and accreditation by
the AAALAC is accepted by the NIH as assurance that the
facility is in compliance with Public Health Services (PHS)
standards.
aNImal DRINkING-WaTeR sysTems
Te purpose of the animal drinking-water system is to produce,
distribute, and maintain an uninterruptible supply of drinking
water with a specifc and consistent range of purity to all ani-
mals in a facility. Tere are two general types of systems: an
automated central-distribution system and individual water
bottles.
sysTem Types
Te great majority of animals used by laboratories for medical
and product research are mice, rats, guinea pigs, rabbits, cats,
dogs, and primates. Smaller animals and primates are kept in
stacked cages, often on racks. Medium-sized animals, such as
dogs, goats, and pigs, are kept in kennels or pens. Larger foor
areas are required for barnyard animals such as cows. Water-
ing can be done either by an automatic, reduced-pressure, cen-
tral system, which pipes water from the source directly to each
cage, kennel or pen; or by separate drinking bottles or watering
devices manually placed in individual cages or pens.
Automated, Central Supply-and-Distribution System
Te purpose of an automated, central, drinking-water supply
system is to automatically treat and distribute drinking water.
Ancillary devices are used to fush the system and maintain a
uniform and acceptable level of purity.
Te system consists of a raw or treated water source, a purif-
cation system, medicinal and disinfection injection equipment
if necessary, pressure-reducing stations, and a distribution
piping network consisting of a low-pressure room-distribution
piping system and a rack-manifold pipe terminating in a drink-
ing valve for each cage or pen for the animals. Also necessary is
an automated fushing system for the room-distribution piping
activated by a fush-sequence panel, and a monitoring system
to automatically provide monitoring of such items as drinking-
water pressure, fow, and possible leakage.
Animals in cages are kept in animal rooms. Cages are usually
placed in multi-tiered, portable or permanent cage racks, which
contain a number of cages. Te cage rack has an integral piping
system installed, called a rack manifold, that distributes the
water to all cages. Te rack manifold could be installed by the
manufacturer or in the facility by operating personnel. Te rack
manifold receives its water from the room-distribution piping.
Te connection between the room-distribution piping and the
rack manifold is made by means of a detachable recoil hose
generally manufactured from Polypropylene (PP), nylon, or Eth-
ylene-Propylene Diene Monomer (EPDM). Tis hose is fexible,
generally
3
8 in. (12 mm) in size and coiled to conserve space. It
will stretch to a length of about 6 ft 0 in. (2 m). Each end is pro-
vided with a quick-disconnect ftting used to attach the hose to
both the room-distribution piping and the rack manifold.
To maintain drinking-water quality, a method of fushing the
room-distribution piping and the rack manifold shall be pro-
vided. Ancillary equipment includes fushing and sanitizing
systems to wash the recoil hose and the cage rack-piping inte-
rior.
Water Bottles
Drinking water bottles are individual units with an integral
drinking tube that are placed by hand on a bracket in each cage.
Animal-care Facility
Piping Systems
Reprinted from Pharmaceutical Facilities Plumbing Systems, Chapter 7: Animal-care Facility Piping Systems, by Michael Frankel.
American Society of Plumbing Engineers.
2 Plumbing Systems & Design NOVEMBER/DECEMBER 2006 PSDMAGAZINE.ORG
C0N7INUINC DUCA7I0N
Tese bottles could be flled either by hand or automatically via
a bottle fller.
Automatic bottle fllers should be considered to reduce the
time necessary to fll bottles and minimize water spillage. Bottle
fllers are available with manifolds to ft any size bottles. Tey
can be supplied with purifed water from a central water supply
andwith separate, programmable proportionerscould
acidify, chlorinate, and medicate the water as required. Te
bottle fller automates the flling procedure so that the bottles
are correctly positioned during flling and stops the fow when
the water reaches a predetermined level.
Flushing System
In order to maintain drinking-water quality, the drinking-water
distribution system should be fushed periodically. Tis is
accomplished by having the same drinking water that is nor-
mally distributed to the animals fow through the piping system
at an elevated fow rate, pressure, and velocity. Te water is sent
to drain and not recovered. Tis is initiated automatically at
the drinking-water pressure-reducing station by the addition
of separate regulating valves and pressure-regulating arrange-
ments.
Diferent fushing arrangements are possible, depending
on the cost, facility protocol, and purity desired. One method
fushes only the main runs by the addition of a solenoid valve
at the end of the main run and the provision of a return line to
drain from this point. Another method is to fush the mains and
the room-distribution piping by adding the solenoid valve at
the end of each room-distribution branch with the return line to
drain from each room. A third method fushes the entire system,
including the rack manifold, by adding a solenoid valve on each
cage connection to the room-distribution pipe, which fushes
the recoil hose and the rack manifold.
It is accepted practice to replace all the drinking water in the
room-distribution piping system at regular intervals, a minimum
of twice daily. To approximate the amount of water in the pipe,
allow 1 gal (4 L) for each 33 ft 0 in. (10 m) of pipe. General prac-
tice is to fush the system with water at about 15 psi (90 kPa) at a
rate of 15 gpm (60 L/min). If the drinking water is not purifed,
it is recommended that the piping be fushed at least twice daily
for about 2 min. For purifed water, fush once daily for about
1 min. Flushing can be done manually by means of a valve in
the pressure-reducing station enclosure or automatically by the
addition of a bypass and solenoid valve around the low-pres-
sure assembly to the pressure-reducing station. Te
sequence and duration of the automatic fush cycle
is controlled from a fush-sequencer panel.
DRINkING-WaTeR TReaTmeNT sysTems
Te purpose of the drinking-water treatment system
is to remove impurities from the raw-water supply
to achieve the water quality required by the animals
in the facility. In addition, disinfectant and medica-
tion can be added to the water during treatment if
required.
sysTems DesCRIpTION
Tere are no generally recognized and accepted
standards for animal drinking-water quality. Purity
and consistency requirements depend on the
incoming water quality, the established protocol of
the end user, the importance of either the initial or
the operating cost of the proposed system, the species of ani-
mals housed in the facility, and the animal-housing methods.
Te overall objective is to eliminate as many variables as pos-
sible for the entire period of time the studies or experiments are
conducted.
Te most often-used treatment for drinking water is reverse
osmosis. Other possible treatment methods are distillation
and deionization. A discussion of these purifcation methods
appears in the chapter Water Systems.
Reverse Osmosis
When a higher-quality water is required and other types of puri-
fed water are not available in a facility, reverse osmosis (RO) is
normally selected. Since the amount of water is usually small, a
package type unit mounted on a skid is provided and connected
directly to the water supply. Te RO system is fexible and, when
used in combination with DI water supply, will provide water
that is virtually contamination free.
Disinfection and Medication of Drinking Water
Disinfection chemical mixtures are added to the animal drink-
ing-water supply to eliminate and control bacterial contamina-
tion in the central and room-distribution piping system. Medi-
cation is added to conform with experimental protocols if nec-
essary. Tese mixtures are usually introduced into the piping
system by a self-contained, central, proportioning (injector)
unit using facility water pressure. Medication is added to the
drinking water using the same proportioning equipment that
adds disinfectant. All equipment is available in a wide range of
sizes and materials. A schematic detail of a typical central pro-
portioner is illustrated in Figure 7-1.
Chlorination Chlorination is a recognized biocidal treat-
ment that leaves a residual of chlorine in the entire central-dis-
tribution system. Hyperchlorinated water is not as corrosive as
acidifed water and could be used with brass/copper distribution
system components. Accepted practice is to provide a pH higher
than 4, with a residual range of free chlorine between 5 and 12
ppm. Free chlorine in water dissipates in time with light, heat,
and reaction with organic contaminants, making it inefective
when water bottles are used. Chlorine creates toxic compounds
in reaction with some water contaminants and medications.
Acidifcation Acidifcation has an advantage over chlori-
nation in that it is more stable and lasts longer in the system. Te
disadvantage is that corrosion-resistant materials must be used.
Te pH range should be between 2.5 and 3 in order to be efec-
Figure 7-1 Typical Central Proportioning Unit
NOVEMBER/DECEMBER 2006 Plumbing Systems & Design 3
tive. A pH lower than 2.5 will cause the water to become sour
and the animals will not drink it. At a pH above 3, the mixture is
not considered an efective germicide.
DRINkING-WaTeR sysTem COmpONeNTs aND seleCTION
pRessURe-ReDUCING sTaTION
Te pressure-reducing station reduces the normal pressure of
the raw-water supply to a level required for the animal-room
drinking-water distribution system. As an option, a secondary
system can be added to provide a higher pressure in the room-
distribution system for fushing.
Te pressure and fow rate depend on the type and number
of animals to be supplied. Also usually included are a 5-
water flter, a pressure gauge, and a backfow preventer. Timing
devices that automatically control fushing duration are con-
trolled by a remote fush-sequencer panel, which controls all
fushing sequencing operations. Te recommended pressures
for animal-room piping distribution to various animals are as
follows:
Small animals, such as
Rats and mice 3-5 psig (20.4-34 kPa)
Primates 3-5 psig
Dogs and cats 3-5 psig
Swine and piglets 6-12 psig (41-81.6 kPa)
Te secondary pressure-reducing assembly used to provide
automatically room-distribution pipe-fushing water operates
at a pressure of 15 psig (102 kPa). Tis assembly is installed as a
bypass around the low-pressure assembly. Manual operation at
a lower cost could also be provided. Tis additional pressure for
a short period of time will not cause the animals any difculty if
they decide to drink during the fushing cycle.
One pressure-reducing station can be connected to as many
as 35 interconnect stations to small animal-rack manifolds,
often referred to as drops. Tis allows 1 station to control more
than 1 animal room.
Te pressure-reducing station is a preassembled unit com-
plete with all the various valves, fttings, and reducing valves
required for a specifc project. All the components are installed
in a cabinet, which requires only mounting and utility connec-
tions.
DRINkING ValVes
Drinking valves are used by the animals
to obtain water from the distribution-
system piping. An internal mechanism
keeps the valve normally closed; the
animal drinking from the valve must
open it by some action, such as moving
the entire valve or operating a small
lever inside the body of the valve with
the tongue. Many diferent kinds of
valve are available to supply any type of
animal that may be kept in the facility.
Te valves can be mounted on cages,
on the rack manifold, or on the walls
of pens and kennels at varying heights
with the use of special brackets.
aNImal-RaCk maNIfOlD CONfIGURaTIONs
Te confguration of the piping on the animal rack plays an
important part in the efectiveness and efciency of the flling
and fushing of the drinking-water system. Te two most often-
used confgurations are the reverse S and the H.
Te reverse S, illustrated in Figure 7-2, is the most often-used
confguration. It has two basic styles based on the valve location
in the fush drain line. One style has a supply control valve at the
top and the other has a drain valve at the bottom. Either location
is acceptable, with the deciding factor being the ease of operating
the valve where the rack is installed. Tis confguration has the
advantage of eliminating dead legs and ofers more convenience
to facility personnel when they fll the piping after washing. Te
vent is a manually operated air bleed used when the cage rack
is reconnected to the room-distribution pipe. It is opened until
water is discharged, thereby eliminating any air pockets in the
manifold. Tis manifold style provides a positive exchange of
water during fushing with a minimum usage of time and water.
Figure 7-2 Reverse S Confguration Watering Manifold
Figure 7-3 Typical Room Distribution, On-Line, Rack Manifold Flushing System
S
o
u
r
c
e
:
C
o
u
r
t
e
s
y
o
f
E
d
s
t
r
o
m
I
n
d
u
s
t
r
i
e
s
.
4 Plumbing Systems & Design NOVEMBER/DECEMBER 2006 PSDMAGAZINE.ORG
C0N7INUINC DUCA7I0N: AnimaI-care FaciIity Piping Systems
Tis confguration is used far more than any
other manifold style. It is easily converted
to automatic fushing by the installation of
solenoid devices on the valve. It is recom-
mended when micro-isolator cage systems
are installed. Te complete, on-line, rack-
manifold fushing system is illustrated in
Figure 7-3. Tis cage system has the advan-
tage of the complete isolation of individual
cages, with the accompanying capability
for additional fushing and disinfection of
the piping system.
One variation of the reverse S is the
standard S, illustrated in Figure 7-4. Tis
confguration has the advantage of com-
plete on-line fushing and lower initial cost
of the manifold. Disadvantages are the
need for extra supports on the cage rack
and the need for venting to be done man-
ually or by the animals after being placed
in service. Tis confguration is no longer recommended.
Te H style, illustrated in Figure 7-5, although rigidly
installed and with positive venting, is not suitable for on-line
fushing. Because of this, it is rarely used except for larger ani-
mals, which will consume all the water in the rack piping mani-
fold.
Te most common piping materials are CPVC and 304L stain-
less steel. CPVC conforms to ASTM D 2846, is 0.875 outside
diameter (OD) with 0.188 in. minimum wall thickness. Joining
process is done with solvent cement socket joints. Te drinking
valves are installed with a proprietary, drilled and tapped ft-
ting. Te 304L stainless steel tubing is 0.50 OD with a 0.036 in.
minimum wall thickness. Fittings are made with O-ring joints
and socket fttings or compression type fttings. Te mounting of
both pipe materials is accomplished by the use of 304 SS stain-
less-steel clamps and fasteners.
sysTem sIzING meThODs
Te water consumption of small animals in cages is very low.
It is also probable that the animal room will not be used to full
capacity. Because of this low consumption fow rate, the fush-
ing-water fow rate of the system is the critical factor in sizing
the piping. Typically, the animal-room piping distribution net-
work is a header uniformly sized at in. (50 mm) throughout
the animal room.
Te pipe sizes in other areas of the
animal facility are determined based on
the requirements of maximum fow rate at
the necessary pressure to supply the fush-
ing velocity. Maximum fow rate depends
on the fush sequencing, and the pressure
drop depends on overcoming pressure
loss through the equipment connected to
the branch being sizedsuch as pressure-
reducing stations, solenoid valves, and
recoil hosesand friction loss through the
piping network. Allowance must be made
to provide a sufciently high fow rate and
water velocity to efciently provide the
fushing action desired.
CleaNING aND DRaINaGe sysTems
aND pRaCTICes
GeNeRal
Keeping the animal rooms and cages
clean is an extremely important facet of facility practice. Te
cleaning of the animal room is accomplished either by sponging
the walls, foors, and ceiling or by hosing down the room. Cage
racks can be cleaned by washing them with a hose or by placing
them in a large washing machine. Cages are cleaned in a cage
washer. Pens and kennels are hosed down. Floors in pens are
cleaned with hoses and the bedding with feces is pushed into
trenches with foor drains.
In specialized areas, such as holding or isolation rooms where
only small animals are kept, it is common practice to have per-
manent cage racks or have the portable racks remain in the
animal room. Te litter is put into bags and brought to other
areas for disposal. Te cage racks are manually wiped down
and no rack washer is required. A sink is usually provided in
the animal room for the convenience of the cleaning personnel.
Individual water bottles, if provided, could be washed in the
sink. Te cages are removed and washed separately in a cage
washer. Tis type of animal room usually does not require a
foor drain if the entire room will be sponged down. If hosing is
practiced, a foor drain is required.
Rabbits and guinea pigs have a tendency to spray urine and
feces. Tis requires that the racks be hosed down in the room. A
wash station with a hose reel and detergent injection capability
to hose down the cage racks and the room itself is usually placed
in individual rooms. Citric acid is often used as a cleaning agent
for rabbits.
hOse sTaTIONs
Hose stations usually consist of a mixing valve with cold water
and steam to make hot water or hot water alone, a length of fex-
ible hose, and an adjustable spray nozzle. Hot and cold water
are also used. It can be exposed or provided with an enclosure
when an easily cleaned surface is required.
CleaNING-aGeNT sysTems
Cleaning agents are used to clean and/or disinfect the walls,
ceiling, and foor of a room and to add agent to the cage wash
water. When used to clean rooms, the equipment used for this
purpose is commonly called a facility detergent system. When
used to add agent to the cage washing water it is often called
a cage-washing detergent system. Tese are separate systems
and are not capable of providing agent to each other.
Figure 7-4 Standard S Confguration Manifold
Figure 7-5 Standard H Confguration Manifold
NOVEMBER/DECEMBER 2006 Plumbing Systems & Design 5
A single-station detergent-dispensing system is used when
rooms are cleaned with mops or squeegees. It consists of a wall-
mounted unit having a holder for detergent concentrate and an
injector unit. A container flled with detergent concentrate is
placed in the holder and is used to supply agent to the injector
that dispenses a metered amount of agent when a hose bibb is
opened to fll the pail or container. Tese rooms usually have
sinks and mop racks inside to be used only for these rooms. A
typical schematic detail of a single-station detergent system is
illustrated in Figure 7-6.
When used to supply a single or multiple-spray hose for
cleaning foors and walls, a central system could be installed to
supply several rooms within a facility by means of a detergent
pump that dispenses agent. A 55-gal drum of agent
should be used to reduce the number of times the
supply has to be changed. A typical central-supply deter-
gent-dispensing system is illustrated in Figure 7-7.
Te cage-washing detergent system is usually located in
the wet area of the cage-washing facility and, with the use
of a detergent pump, could be used as a central system to
supply cage and bottle washers. A typical schematic detail
of a cage-washing system is illustrated in Figure 7-8.
It is common practice to have a central system or a wall-
mounted cleaning-agent dispenser unit along with the hose
station. Separate, portable units could be used when cross
contamination between animal rooms is a consideration.
A typical, wall-mounted, cleaning-agent system consists
of separate water and cleaning-agent tanks; a water pump;
and a special, coaxial hose that sprays a proportioned mix-
ture of the water and cleaning agent. Compressed air is
often used to provide pressure.
CaGe-flUshING WaTeR sysTem
Te removal of animal waste from cages can be done by sev-
eral methods. One method removes the waste along with
the bedding at the time cages are removed from the animal
room to be washed. Another method uses an independent
rack-fush system to automatically remove animal waste
from cages on racks while the animals and cages remain in
the animal room.
Te independent rack fush is a separate system that
uses chlorinated water automatically distributed to each
animal room. Te cages and racks are constructed so that
the animal droppings fall through the cage foor onto a sloping
pan below each tier of cages. Each tier is cascaded at the end
onto the sloping pan below. Eventually, the lowest pan spills
into a drain trough in the animal room. Te fushing schedule is
decided by facility personnel.
Te water supply could be a reservoir placed on the rack that
is flled with water and automatically discharged onto the pans
at preset intervals. Tese preset intervals are determined based
on experience and generally range from once to three times
daily. Another method uses a solenoid valve to automatically
discharge water onto the pans; the valve is sequenced by a timer
set to alternate fll and dump cycles. Te timer could be either
Figure 7-6 Single-Station Detergent System
Figure 7-8 Typical Cage-Washing Detergent System
Figure 7-7 Central-Supply Detergent System
6 Plumbing Systems & Design NOVEMBER/DECEMBER 2006 PSDMAGAZINE.ORG
C0N7INUINC DUCA7I0N: AnimaI-care FaciIity Piping Systems
centrally located or installed separately in each animal room.
Larger cages, such as those for primates, are usually stacked
no more than two cages high. Current practice is to have these
cages manually cleaned by personnel who hose down the pans
directly into foor or wall troughs.
Water is supplied to each cage rack by means of a recoil hose,
which has a diferent quick-disconnect end than that of the
drinking water recoil hose to avoid cross
connection. Refer to Figure 7-9 for a detail
of a typical cage-rack utility connection
arrangement.
sOlID-WasTe DIspOsal
Solid waste consists of bedding, feces,
animal carcasses, and other miscella-
neous waste, including straw and sawdust
used for larger farm animals. Bedding
comprises the largest quantity of this
solid waste. It is necessary to determine
the quantity of bedding before a decision
can be made as to the most cost-efective
method to dispose of it.
Bedding can be disposed of by incin-
eration, as regular garbage, or into the
sewer system. Incinerators are costly,
require compliance with many regulatory
agencies and multiple permits, and often
result in objections from adjoining prop-
erty owners. Incineration is the preferred
method of disposing of carcasses and
large quantities of contaminated waste.
Carcasses could also be autoclaved and
disposed of as regular garbage. Regular gar-
bage disposal is the most common method of
disposal. It involves collecting, moving, and
storage of the waste into large containers until
regular garbage collection is made. Tis is very
labor intensive.
Discharge into the drainage system must
frst be accepted by the local authorities and
responsible code ofcials. Tis requires the
bedding to be water soluble, that it shall not
foat, and provision be made to thoroughly mix
the bedding with water. Tis mixture is called a
slurry. Experience has shown, if done prop-
erly, discharge into an adequately sized drain
lineminimum size 6 in. (150 mm)has
caused no problems, since the efuent has the
same general characteristics of water.
A self-contained waste-disposal system is
available that is capable of disposing of animal
bedding and waste. Te system consists of a
pulping unit to grind the waste into a slurry
and sanitize it, a water extractor to remove
most of the water from the slurry, and the
interconnecting piping system that transports
the slurry from the pulper to the extractor
and recirculates the water removed from the
extractor back to the pulping unit for reuse. Te
solid waste is removed as garbage. Manufac-
turers are available for assistance in the design
and equipment selection for this specialized
system. Te system has the advantages of reducing water use,
reducing operating costs by eliminating the handling of the
waste by operating personnel, compacting the waste to about
20% of the space required for standard garbage not compacted,
and reducing the possibility of contamination by isolation of the
disposal equipment. Te disadvantage is its high initial cost.
Figure 7-9 Typical Cage-Rack Utility Connections
Figure 7-10 Typical Waste-Disposal System
NOVEMBER/DECEMBER 2006 Plumbing Systems & Design 7
Tis system could consist of single or multiple units of dif-
ferent capacities. It requires water intermittently for pulping at
the rate of about 10 to 30 gpm (63 to 190 L/min). Hose bibbs
should be installed for washdown. Te pipe should be sized for
a maximum velocity of 8 fps (1.75 m/s), with typical slurry lines
ranging between 2 and 4 in. (50 and 200 mm) and return lines
generally 2 in. (50 mm) in size. Te extractor discharges into a
drain that should be 4 or 6 in. (100 or 150 mm) depending on
the fow. A typical schematic diagram of a multiple installation
is illustrated in Figure 7-10.
ROOm-WasTe DIspOsal
Te rooms in which animals are kept must be designed to allow
proper drainage practices and in accordance with the antici-
pated cleaning procedures of the facility. Floor drains, drainage
trenches (or troughs) at room sides, adequate and consistent
foor pitch to drains or troughs, and foor surfaces are all impor-
tant considerations.
Tere are several considerations to be taken into account in
locating foor drains. Experience has shown that placing drains
in the center of a room is not acceptable because it is difcult
to hose solids down a drain in this location. Another reason is
that the foor must be pitched to the drain and if a cage rack is
defective, it should roll to the side of the room. Te best loca-
tion is in a corner or at the side. Floor drains without troughs
can be considered if the foors will only be squeegeed rather
than hosed down. Tey should also be considered in contagious
areas where contamination between rooms must be avoided.
Gratings must have openings smaller than the wheels of racks
or cages.
In rooms where washdown and cage-rack fushing are
expected, the provision of a foor trough should be consid-
ered. Troughs are often provided at opposite ends of the room
to minimize the amount of foor drop due to pitch. Accepted
practice uses a minimum foor pitch of
1
8 in./ft of foor run. Te
foor is pitched to the troughs to facilitate cleaning and also to
provide an easy method to dispose of waste generated from the
rack-fush system. It is common practice to provide an auto-
matic or manual trough-fushing system with nozzles or jets to
wash down the trough sides and eliminate as much of the con-
tamination remaining in the trough as possible. Wall troughs,
similarly to roof gutters, are located at a higher elevation. Tis
type of trough arrangement is sometimes provided in addition
to or in lieu of foor troughs if the arrangement of elevated cages
and racks make it an efective drainage method. Experience has
shown that prefabricated drain troughs in foors are preferred
over those built on the wall as part of the architectural construc-
tion.
Te foor troughs are drained by means of a foor drain placed
in a low point at one end. Te troughs are usually pitched at
in./ft of run to the drain. Te drain should be constructed of acid-
resistant materials and have a grate that can be easily removed.
For small animal rooms where bedding is not disposed of in the
room, a 4-in. (100-mm) drain is considered adequate. In most
other locations, it is recommended that a 6-in. (150-mm) drain
be provided. A fushing-rim type drain should be considered to
fush all types of waste into the drainage system.
Floor drains should have the capability of being sealed by the
replacement of the grates with solid covers during periods when
the room may not be in service.
eqUIpmeNT WashING
Most facilities contain washing and sanitizing machines to wash
cages, cage racks, and bottles, if used. Tere are two commonly
used types of cage washer: the batch type and conveyer (tunnel)
type. Batch washers require manual loading and unloading and
are used where a small number of cages and racks are washed.
Te conveyer type is similar to a commercial dishwasher, where
the cages and racks are loaded on a conveyer and automatically
moved through the machine for the washing and sanitizing
cycles.
eqUIpmeNT saNITIzING
Maintaining drinking-water quality requires that the recoil
hoses and rack manifolds be not merely washed but internally
sanitized. Tis is most often done at the same time the cages are
washed. Separate rack-manifold and recoil-hose fush stations
are available for this purpose and are usually installed in the
cage-wash area. Washing can be done manually or automati-
cally. Te hoses are fushed for 1 to 2 min with 4 gpm (16 L/min)
of water. Chlorine is injected into the water by a chlorine-injec-
tion station (proportioner) set to deliver 10 to 20 ppm into the
fush water. Ten scfm of oil-free compressed air at 60 psig is
blown through the hoses to dry them. If chlorine is used as a
disinfectant, a contact time of 30 min is recommended before
evacuation and drying.
Periodic sanitizing of the room-distribution piping system is
required for maintaining good water quality. Sanitizing is done
prior to system fushing. To accomplish this, a portable sanitizer
is used to manually inject a sanitizing solution directly into the
piping system. In order to do this, an injection port is required
at the inlet to the pressure-reducing station. Te portable sani-
tizer usually consists of a 20-gal (90-L) polyethylene tank with
a submersible pump inside and a fexible hose used to connect
the tank to the injection port. Te disinfecting solution is a mix-
ture of chlorine and water with 20 ppm of chlorine. Te mixture
should maintain a contact time in the piping of 30 to 45 min.
DRaINaGe-sysTem sIzING
As mentioned previously, for individual animal rooms where
bedding is not disposed of in the drainage system, a 4-in. drain is
acceptable. In general, a 6-in. drain is considered good practice.
Te size of the drainage system piping should be a minimum
of 6 in., with a -in. pitch when possible and the piping sized
to fow to
2
3 full in order to accommodate unexpected infow.
mONITORING sysTems
Te monitoring of various animal-utility systems is critical to
keep within a range of values consistent with the protocol of
the experiments being conducted at the facility. Tis is accom-
plished by a central monitoring system that includes many mea-
surements from HVAC and electrical systems. For the animal
drinking-water system, parameters such as water pressure, fow
rates, leakage, pH, and temperature in various areas of the facil-
ity are helpful for maintenance, monitoring, and alarms.
sysTems DesIGN CONsIDeRaTIONs
Te amount of exposed piping inside any animal room should be
minimized. Te exception is the animal drinking-water system,
which is usually exposed on the walls of the room. Tis piping
should be installed using standofs to permit proper cleaning of
the wall and around the pipe.
Te piping material used for all systems should be selected
with consideration given to the facility cleaning methods and
8 Plumbing Systems & Design NOVEMBER/DECEMBER 2006 PSDMAGAZINE.ORG
C0N7INUINC DUCA7I0N: AnimaI-care FaciIity Piping Systems
type of disinfectant. Where sterilization is required and cleaning
very frequent, stainless-steel pipe should be considered.
If insulation is used on piping, it should be protected with a
stainless steel jacket to permit adequate cleaning.
Pipe penetrations should be sealed with a high-grade, imper-
vious, and fre-resistant sealant. Escutcheons should not be
used because they allow the accumulation of dirt and bacteria
behind them.
NOVEMBER/DECEMBER 2006 Plumbing Systems & Design 9
C0N7INUINC DUCA7I0N
P
S
D
1
3
6
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
CE QuestionsAnimal-care Facility Piping Systems (PSD 136)
About This Issues Article
The November/December 2006 Continuing Education
article is Animal-care Facility Piping Systems, Chapter 7
of Pharmaceutical Facilities Plumbing Systems by Michael
Frankel. This chapter discusses the various piping systems
uniquely associated with the physical care, health, and well-
being of laboratory animals. Included are utility systems for
animal watering, water treatment, room and floor cleaning,
equipment washing, cage flushing and drainage, and other
specialized piping required for laboratory and experimental
work within the facility.
You may locate this article at www.psdmagazine.org.
Read the article, complete the following exam, and submit
your answer sheet to the ASPE office to potentially receive
0.1 CEU.
1. What comprises the Iargest soIid waste item from animaI
cages!
a. bedding, b. feces, c. carcasses, d. miscellaneous waste
2. 7his chapter discusses various piping systems uniqueIy
associated with the physicaI care, heaIth, and weII-being
of ___________.
a. laboratory workers, b. laboratory animals,
c. animal watering, d. cage cleaning
3. A singIe-station detergent-dispensing system is used
when rooms are ___________.
a. hosed down
b. cleaned with mops or squeegees
c. cleaned with steam
d. none of the above
4. 7o maintain drinking water quaIity, ___________.
a. a water purifcation system must be designed
b. the water system must be allowed to run continuously
c. there must be chlorine injection
d. the drinking water distribution system must be fushed
periodically
5. FIoor drains shouId not be pIaced ___________ where
animaIs are kept.
a. under cages in rooms
b. in the center of the room
c. at the back edge of cages in rooms
d. none of the above
6. A puIping unit is used to ___________.
a. separate water from solid waste
b. determine the pH of the waste
c. determine the temperature of the waste
d. grind the waste into a slurry
7. 10-CFR-58 ___________.
a. is the federal code that must be followed when keeping
animals for research
b. requires compliance with FDA protocols for
pharmaceutical applications
c. is the guide for the care and use of laboratory animals
d. is the code for good laboratory practice for non-clinical
laboratory studies
8. SeIect the true statement beIow.
a. There are no generally recognized and accepted
standards for animal drinking water.
b. Drinking valves are not used by animals to obtain water
from the distribution system.
c. Water pressure, minimum and maximum, for the
various animals to be served is mandated in the
plumbing code.
d. Reverse osmosis (RO) systems are inappropriate for
animal drinking water systems.
9. 7he recommended water pressure for dogs and cats is
___________.
a. 612 psig, b. 20.434 kPa,
c. more than for rats and mice, d. none of the above
10. What ow rate and pressure of oiI-free air is used to dry
the interior of hoses!
a. 5 scfm at 30 psig
b. 10 scfm at 30 psig
c. 5 scfm at 60 psig
d. 10 scfm at 60 psig
11. What type of piping materiaI shouId be used on systems
that require frequent steriIization!
a. cast iron
b. copper
c. galvanized
d. stainless steel
12. 7he water consumption of smaII animaIs in cages is
___________.
a. based on a fushing system to maintain fresh water in
the piping at all times
b. established by experience
c. very low
d. none of the above
Do you fnd it difcult to obtain continuing education units (CEUs)?
Trough this special section in every issue of PS&D, ASPE can help
you accumulate the CEUs required for maintaining your Certifed in
Plumbing Design (CPD) status.
Now Online!
Te technical article you must read to complete the exam is located
at www.psdmagazine.org. Te following exam and application form
also may be downloaded from the Web site. Reading the article and
completing the form will allow you to apply to ASPE for CEU credit.
For most people, this process will require approximately one hour. If
you earn a grade of 90 percent or higher on the test, you will be notifed
that you have logged 0.1 CEU, which can be applied toward the CPD
renewal requirement or numerous regulatory-agency CE programs.
(Please note that it is your responsibility to determine the acceptance
policy of a particular agency.) CEU information will be kept on fle at
the ASPE ofce for three years.
Note: In determining your answers to the CE questions, use only the material
presented in the corresponding continuing education article. Using information
from other materials may result in a wrong answer.
10 Plumbing Systems & Design NOVEMBER/DECEMBER 2006 PSDMAGAZINE.ORG
P
S
D
1
3
7
Vent
Systems
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
JANUARY/FEBRUARY 2007
PSDMAGAZINE.ORG
Flow of air is the primary consideration in the design of a
venting system for the ventilation of the piping and protection
of the fxture trap seals of a sanitary drainage system. Since air
is of such primary importance, it is essential that the plumbing
engineer be familiar with certain physical characteristics that
are pertinent to its behavior in a plumbing system.
Density of any substance is its mass per unit volume. Te den-
sity of air is its weight in pounds per cubic foot of volume. Te
density of air is afected by temperature, moisture content, and
pressure. Te density of standard air is taken at atmospheric
pressure and 68.4F. It is equal to 0.075 lbm/ft
3
. With a rise in
temperature, the density of air decreases and with a lowering of
temperature its density increases. Te moisture content of air in
the plumbing system has a negligible efect on its density and
can be disregarded in all calculations. Pressure has an appre-
ciable efect; the higher the pressure the greater the density, and
the lower the pressure the less the density.
Specifc Weight of a fuid is not an absolute property, but
depends upon the local gravitational feld (gravitational accel-
eration on earth is g=32.2 ft/sec
2
) and the properties of the fuid
itself. Commonly called density when concerning gravita-
tional force, the numerical value of specifc weight (lbf/ft
3
) is
equal to density (lbm/ft
3
).
Elasticity is the ability of a substance to assume its original
characteristics after the removal of a force that has been applied.
Air is a perfectly elastic substance. From the scientifc defnition
of elasticity it becomes clear that a rubber band is really a very
inelastic material. If a weight is suspended from a rubber band
and left for a few hours, then the weight is removed, the rubber
band will spring back, but defnitely not to its original length. If a
force is applied to air, the force can be applied for days or years,
and when it is removed, the air will return exactly to its original
condition.
Air is compressible. Tere is an increase in pressure when air
is compressed. In the plumbing system, only an extremely small
change in pressure can be tolerated. For a pressure of 1 in. of
water column (0.036 psi), the volume of air will be compressed
by
1
400 of its original volume. Assuming an original volume of
400 ft
3
of air at atmospheric pressure and the application of a
pressure of 1 in. of water column, the air will be compressed by
400
1
400 = 1 ft
3
. It is obvious that a comparatively small change
in volume can very easily cause the accepted design limitation
of 1 in. of pressure to be exceeded with the consequent danger
of destroying the trap seals. Te vent piping must be designed to
permit the air to fow freely without compression or expansion
except for the small amount necessary to overcome friction.
Static Head
Static head is the pressure exerted at any point by the weight of
the substance above that point. Te pressure can be stated in
feet of the substance, i.e., when the substance is water the static
head is 100 ft of water, or if the substance is air, 100 ft of air. To
convert from feet of head to pounds-force per square inch:
(1)
p =
h
and h =
144p
144
where
p = Pressure, lbf./in
2
= Specifc weight of substance, lbf/ft
3
h = Static head, ft
Pneumatic effectS in Sanitary SyStemS
As water fows in contact with air in vertical or horizontal piping,
there is friction between the air and water. Te frictional efect
causes the air to be dragged along with the water and at practi-
cally the same velocity as the water. When the cross-sectional
area of the water occupying the pipe is suddenly increased,
such as at the hydraulic jump or where a branch discharges into
the stack, the air passage is constricted. Tis constriction acts
exactly the same as a stoppage or a blockage to the fow of air.
Tis causes a buildup of pressure, the highest pressure occur-
ring at the constriction and diminishing upstream. It is for this
reason that excessive pressure usually develops at the lower
foors of a building and at ofsets of the stack. It is important to
always be aware that protection from the entry of sewer gases is
aforded by the 2-in. trap seal, and the design of plumbing sys-
tems must be such as to maintain pressure variations within 1
in. column of water.
rate of flow from outletS
Te velocity at which air fows out of an outlet to the atmosphere
(at the roof terminal of a stack) is due to the total pressure avail-
able in the vent pipe at the outlet. Tis pressure is the fow pres-
sure, which is equal to the static pressure less the pressure lost in
friction. Te maximum rate of discharge in practice is expressed
as:
(2)
q
D
= c
D
q
1
where
q
D
= Actual quantity of discharge, gpm
q
1
= Ideal quantity of discharge, gpm
c
D
= Coefcient of discharge
Utilizing the formula q = AV and substituting,
(3)
q
D
= c
D
(2.448 d
O
2
V
1
)
where
d
O
= Outlet diameter, in.
V
1
= Ideal velocity, fps
Velocity is equal to 2gh, where g = acceleration due to gravity
and h = height (or head) of air column.
(4)
q
D
= c
D
(2.448 d
O
2
2gh)
(5)
= c
D
(19.65 d
O
2
h)
Using 0.67 as an acceptable coefcient of discharge, per Equation
6-1,
Vent Systems
Reprinted from Engineered Plumbing Design II, Chapter 8: Vent Systems, by A. Calvin Laws, PE, CPD.
American Society of Plumbing Engineers.
2 Plumbing Systems & Design JANUARY/FEBRUARY 2007 PSDMAGAZINE.ORG
C0N7INUINC DUCA7I0N
q
D
= 13.17 d
O
2
h
= 13.17 d
O
2
(69.23)
= (13.17) (8.32) d
O
2
= 109.57 d
O
2
The gallons per minute (cubic
feet per minute) discharge rate
for various diameters of vent pipe
at a fow pressure of 1 in. of water
column is given in Table 1.
friction Head loSS
When air fows in a pipe there is
a pressure loss which occurs due
to the friction between the air and
pipe wall. Tis loss of pressure can
be expressed by the Darcy formula:
(7)
h =
f L V
2
D2 g
where
h = friction head loss, ft. of air column
f = coefcient of friction
L = length of pipe, ft.
D = diameter of pipe, ft.
V = velocity of air, ft/sec
g = gravitational acceleration 32.2 ft./sec
2
air flow in StackS
Te complete venting of a sanitary drainage system is very
complicated as evidenced by the variety of vents employed.
Tere are so many variables that produce positive and negative
pneumatic pressure fuctuations that it is not feasible to prepare
tables of vent sizing for each particular design. Recognizing this,
authorities base the formulation of venting tables for vent stacks
and horizontal branches on the worst conditions that may rea-
sonably be expected. To determine the maximum lengths and
minimum diameters for vent stacks it would be valuable to
review the conditions of fow in the drainage stack.
At maximum design fow, the water fows down the stack as a
sheet of water occupying
7
24 of the cross-sectional area of the
stack. Te remaining
17
24 is occupied by a core of air. As the
water falls down the stack, it exerts a frictional drag on the core
of air and as this air is dragged down it must be replaced by an
equivalent quantity of air so as not to develop negative pressures
in excess of -1 in. of water. Tis is accomplished by extending
the soil stack through the roof so that air may enter the stack to
replenish the air being pulled down the stack. Tis is why stacks
must be extended full size through the roof and also why soil
stacks may not be reduced in size even though the load is less on
the upper portions of the stack than it is at the lower portions.
Any restriction in the size before terminating at the atmosphere
would cause violent pressure fuctuations.
As the water fows down the stack and enters the horizontal
drain there is a severe restriction to the fow of air as the hydrau-
lic jump occurs. Te air is compressed and pressure buildup
may become very high. A vent stack is provided in this area of
high pressure to relieve the pressure by providing an avenue for
the fow of air. Obviously, the vent stack must be large enough
to permit the maximum quantity of air dragged down the drain-
age stack to discharge through it and to the atmosphere without
exceeding 1 in. of water fuctuation Te rate of air discharge
that must be accommodated for various sizes of drainage stacks
fowing at design capacity is tabulated in Table 2.
air flow in Horizontal drainS
It is assumed that the drainage branch fows half full at design
conditions and the air in the upper half of the pipe is fowing at
the same velocity and capacity. Table 3 tabulates these values
for various slopes of drain.
Table 2 Air Required by Attendant Vent Stacks
(Drainage Stack Flowing
7
24 Full)
Diameter of Drainage
Stack, inches Water Flow, gpm Air Flow, gpm (cfm)
2 23.5 57.1 (7.6)
3 70.0 170.1 (22.7)
4 145.0 352.4 (47.1)
5 270.0 656.1 (87.7)
6 435.0 1057.1 (141.3)
8 920.0 2235.6 (298.9)
10 1650.0 4009.5 (536)
12 2650.0 6439.5 (860.8)
Table 1 Discharge Rates of Air
(1 Inch Water Pressure)
Outlet Diam,
d
O
inches
Air Discharge,
q
D
gpm (cfm)
2 438.3 (58.6)
2 684.8 (91.5)
3 986.1 (131.8)
4 1753.0 (234.3)
5 2739.0 (366.1)
Table 3 Rate of Air In Horizontal Drains
Diameter of Drain,
inches
Slope,
inches per foot
Rate of Flow,
gpm (cfm)
1 6.0 (.80)
2 8.8 (1.2)
2 15.5 (2.1)
3 25.5 (3.4)
4
1
8 38.0 (5.1)
5
1
8 69.0 (9.2)
6
1
8 112.0 (15)
8
1
8 240.0 (32.1)
JANUARY/FEBRUARY 2007 Plumbing Systems & Design 3
PermiSSible lengtH of Vent PiPe
Te maximum length of vent piping, for any particu-
lar size with a pressure drop of 1 in. of water, is estab-
lished by computing the pressure loss for various rates
of fow in vents of various diameters. Combining Dar-
cys pipe friction formula (Equation 7) and the fow
formula, and converting the terms of the equations to
units generally used in plumbing:
h =
f L V
2
D 2g
(8)
q = 2.448 d
2
V
(9)
V =
q
2.448d
2
Substituting V in the Darcy equation,
h =
f Lq
2
(
d
12)(64.4)(2.448)
2
(d)
4
Solving for L,
(10)
L =
h d
5
=
2226 d
5
0.013109 f q
2
f q
2
where
L = Length of pipe, ft
d = Diameter of pipe, in.
f = Coefcient of friction
q = Quantity rate of fow, gpm
graVity circulation
Te principle of gravity circulation of air is utilized
to keep the entire sanitary system free of foul odors
and the growth of slime and fungi. Te circulation is
induced by the diference in head (pressure) between
outdoor air and the air in the vent piping. Tis difer-
ence of head is due to the diference in temperature,
and thus the diference in density, of each and the
height of the air column in the vent piping. Te cool
air, being more dense, tends to displace the less dense
air of the system and circulation of the air is induced.
Te formula is
(11)
H = 0.1925 (
O
-
1
) H
S
where
H = Natural draft pressure, in. of water
O
= Specifc weight of outside air, lbf/ft
3
1
= Specifc weight of air in pipe, lbf/ft
3
H
S
= Height of air column or stack, ft
Under conditions of natural draft, the rate of fow will be just
great enough to overcome losses due to friction.
Vent StackS
Every drainage stack should be extended full size through the
roof. Te pipe from the topmost drainage branch connection
through the roof to atmosphere is called the vent extension.
Te vent extension provides the air that is dragged down the
stack and also provides means for the gravity circulation of air
throughout the system. Vent extensions may be connected with
the vent stack before extending through the roof or may be con-
nected together with other vent extensions or vent stacks in
a vent header and the header extended through the roof as a
single pipe.
Every drainage stack should have an attendant vent stack. Te
purpose of installing a vent stack is to prevent the development
of excessive pressures in the lower regions of the drainage stack
by relieving the air as rapidly as it is carried down by the dis-
charge of the drainage stack. Te most efective location for the
vent stack is below all drainage branch connections and pref-
erably at the top of the horizontal drain immediately adjacent
to the stack base ftting. It is at this location that pressure is at
its maximum and the danger of closure due to fouling is at its
minimum. Figure 1 illustrates acceptable methods of vent stack
connections.
Te vent stack should extend undiminished in size through
the roof or connect with the vent extension of the drainage stack
at least 6 in. above the overfow of the highest fxture or connect
to a vent header.
Vent terminalS
Vent terminals should not be located within 10 ft of any door,
window, or ventilation intake unless they are extended at least 2
ft above such openings. Terminals should be at least 6 in. above
roof level and at least 5 ft above when the roof is used for other
Figure 1 Various Vent Stack Connections
4 Plumbing Systems & Design JANUARY/FEBRUARY 2007 PSDMAGAZINE.ORG
C0N7INUINC DUCA7I0N: Vent Systems
purposes. When it is impractical to extend the vent through the
roof, it is permissible to terminate through a wall, but the ter-
minal must turn down and be covered with a wire screen. Te
terminal should never be located beneath a building overhang.
fixture traP VentS
Te water seal of all fxture traps should be protected against
siphonage or blowout by the proper installation of a venting
system. When drainage stacks are provided with an adequate
supply of air at the terminal and an adequate vent stack is pro-
vided to relieve excess pressures at the base of the drainage
stack, the only additional vent protection required to prevent
water seal loss in fxture traps is that necessary to prevent self-si-
phonage when the fxture discharges and to relieve excessive
pneumatic efects in the branch drains when other fxtures dis-
charge into the branch. Some municipalities require that every
fxture trap be individually vented, but most localities permit
alternate methods such as
1. Wet venting
2. Stack venting
3. Circuit and loop venting
4. Combination waste and vent venting
diStance of Vent from traP
Te most comprehensive investigations of conditions under
which fxture traps will be safe from self-siphonage have been
conducted by the National Bureau of Standards in the United
States and by the Building Research Station in England. Te rec-
ommended maximum distances of a vent from the weir of the
trap to the vent connection are tabulated in Table 4.
As illustrated in Figure 2, the vent pipe opening, except for
water closets and similar fxtures, must never be below the
weir of the fxture trap. A
fxture drain that slopes
more than one pipe diam-
eter between vent opening
and trap weir has a greater
tendency to self-siphon
the trap seal than a fxture
drain installed at a slope
of not more than one pipe
diameter.
Self-Siphonage of Fix-
ture Traps, National Bureau of Standards Building Materials and
Structures Report BMS 126 (1951), prepared by John L. French
and Herbert N. Eaton, is a very thorough study of self-siphonage
Some of the conclusions drawn by French and Eaton as a result
of their investigations are very illuminating and are quoted
herewith:
1. Increasing the diameter of the outlet orifce of a lavatory
from 1
1
8 in. to 1 in. increases the trap seal loss greatly, fre-
quently more than 100%, owing to the increased discharge
rate.
2. Flat-bottomed fxtures cause smaller trap seal losses than
do round fxtures, owing to the greater trail discharge from
the former.
3. With a 1-in. fxture trap and drain, an 1in. by 20-in. lava-
tory gave greater trap-seal losses than did a 20-in. by 24-in.
lavatory, presumably owing to the greater trail discharge of
the latter. When a 1 in. trap and drain were used, no par-
ticular diference was noted in the trap seal losses caused by
the two lavatories.
4. Te elimination of the overfow in lavatories will increase
the trap seal losses substantially.
5. Te efect on trap seal losses of varying the vertical distance
from the fxture to the trap from 6 in. to 12 in. appears to be
negligible.
6. For a given rate of discharge from a lavatory, decreasing the
diameter of the drain will increase trap seal losses.
7. An increase in slope or a decrease in diameter of the fxture
drain will tend to cause increased losses due to self-siphon-
age, and these two dimensions are fully as important as the
length of fxture drain in causing self-siphonage.
8. Trap seal losses are usually much greater when a long-turn
stack ftting is used than when a short-turn or straight-tee
ftting is used. No signifcant diference between the behav-
ior of short-turn and straight-tee fttings was observed.
Tus, since it is known that a long-turn ftting is more efec-
tive in introducing water from a horizontal branch into the
stack than is either the short-turn or straight-tee ftting, the
characteristics of these fttings are contradictory in these
respects. Te ftting that is most advantageous from the
standpoint of introducing the water into the stack is the
least advantageous from the standpoint of self-siphonage.
9. Trap seal losses are increased if the internal diameter of
a P-trap is less than that of the fxture drain. Tus, if we
are to prevent excessive trap seal losses for a P-trap due to
self-siphonage, we should use a trap having a fairly large
internal diameter. Furthermore, siphonage of the trap due
to pressure reductions caused by the discharge of other fx-
tures on the system can be rendered less harmful by using
a trap with a large depth of seal. While increasing the depth
of seal may lead to greater trap seal losses, it also results in a
greater remaining trap seal than if a trap with a shallow seal
were used.
10. Te test results on the self-siphonage of water closets have
indicated that the unvented length of drain for these fxtures
need not be limited because of self-siphonage.
11. Standardization of the dimensions of fxture traps and
especially of lavatory traps, with regard to internal diameter
and depth of trap seal is highly desirable. Minor restrictions
on these dimensions can lead to substantially increased
lengths of fxture drains.
Figure 2 Vent Pipe Opening
Table 4 Distance of Vent from Fixture Traps
Size of Fixture Drain
inches
Maximum Distance
of Vent to Trap
inches
1 30
1 42
2 60
3 72
4 120
JANUARY/FEBRUARY 2007 Plumbing Systems & Design 5
12. Standardization of the hydraulic characteristics of fxtures is
desirable, at least for lavatories, sinks, and combination fx-
tures. Substantially increased permissible unvented lengths
of fxture drains can be obtained for a moderate decrease in
the discharge rates of the fxtures.
13. Increase in depth of trap seal above the 2-in. minimum
commonly permitted by codes will make it possible to
increase appreciably the maximum permissible unvented
lengths of fxture drains.
Tese conclusions clearly illustrate various approaches in the
efort to make plumbing systems less costly without afecting
efciency. Te proper design of fxtures and fxture drain lines
and limiting the maximum discharge rates of faucet-controlled
fxtures could result in longer unvented lengths of drains.
VariouS metHodS of fixture traP Venting
Figure 3 illustrates various fxture trap vents and their proper
nomenclature. When venting one trap the vent is called an indi-
vidual or back vent. If fxtures are back to back or side by side
and one vent is used for the two traps, the vent is a common
vent. Any connection from the vent stack is a branch vent.
All vent piping should be graded to drain back to the drainage
piping by gravity. Te vent should be taken of above the cen-
terline of the drainpipe and rise vertically or at an angle of not
more than 45 from the vertical. Te horizontal run of the vent
should be at least 6 in. above the overfow level of the fxture.
(See Figure 4.)
relief VentS
Pressures in the drainage and vent stacks of a multistory build-
ing are constantly fuctuating. Te vent stack connection at the
base of the drainage stack and the branch vent connections to
the branch drains cannot always eliminate these fuctuations.
It then becomes extremely important to balance pressures
throughout the drainage stack by means of relief vents located
at various intervals. Te fuctuations in pressure may be caused
by the simultaneous discharge of branches on various sepa-
rated foors. Drainage stacks in buildings having more than ten
branch intervals should be provided with a relief vent at each
tenth interval, counting from the topmost branch downward.
Te lower end of the relief vent should connect to the drainage
stack below the drainage branch connection and the upper end
should connect to the vent stack at least 3 ft above the foor level.
(See Figure 5.)
Relief vents are required where a drainage stack ofsets at an
angle of more than 45 to the vertical. Such ofsets are subject
to high pneumatic pressure increases and extreme surging fow
Figure 3 Various Fixture Trap Vents
Figure 4 Horizontal Run of Vent
Figure 5 Venting for Stacks Having More Than 10 Branch Intervals
6 Plumbing Systems & Design JANUARY/FEBRUARY 2007 PSDMAGAZINE.ORG
C0N7INUINC DUCA7I0N: Vent Systems
conditions. Te methods of installing relief vents are illustrated
in Figure 6.
continuouS Venting
A system of individual or common vents for every trap is called
continuous venting. Every fxture trap is provided with a vent.
It is the most expensive system but provides positive protection
of all trap seals.
wet Venting
A wet vent is a vent that vents a particular fxture and at the
same time serves as a waste to receive the discharge from other
fxtures. Te objective of using wet vents is to minimize the vent
piping required by employing one pipe to serve two functions.
Tere are three fundamental rules to follow when utilizing a wet
vent:
At top foor:
1. No more than 1 FU is discharged into a 1-in. wet vent nor
more than 4 FU into a 2-in. wet vent.
2. Length of drain does not exceed maximum permissible
distance between trap and vent.
3. Branch connects to the stack at the water closet
connection level or below. (See Figure 7.)
At lower foors:
Te rules are the same except that the water closets must
be vented and the wet vent must be 2 in. minimum. Water
closets below the top story need not be individually vented
if a 2-in. wet vented waste pipe connects directly to the
upper half of the horizontal water closet drain at an angle
no greater than 45 from the angle of fow. (See Figure 8.)
Stack venting fnds its general application in one-family
homes and the top foor of multistory buildings. (See Figures 7
and 9.)
combination waSte and Vent Venting
Combination waste and vent venting is used primarily for
venting foor drains and laboratory and work tables. Te drain-
age piping is oversized at least two sizes larger than required
for draining purposes only and the drainage branch and stack
should be provided with vent piping. Tis type of venting is
employed when it is impractical to employ the other methods.
circuit and looP Venting
Tere has developed a tendency to call all circuit venting by
the name applicable to a special installation of circuit venting. A
circuit vent is a branch vent that serves two or more foor outlet
fxtures, except blowout water closets, and extends from in front
of the last fxture connection on the horizontal drain to the vent
stack. A loop vent is the same, except that it is employed on
the topmost foor serving fxtures and is connected to the vent
Figure 8 Wet Venting Below Top Floor
Figure 7 Wet Venting at Top Floor Figure 6 Venting at Stack Ofsets
JANUARY/FEBRUARY 2007 Plumbing Systems & Design 7
extension of the drainage stack instead of to the vent stack.
(See Figure 10.) When wall outlet fxtures are connected to the
branch drain serving the foor outlet fxtures, the former must
be provided with individual vents that can connect to the circuit
vent or loop vent.
common VentS
Where two fxtures are connected to a vertical branch at the
same level, a common vent may be employed. When one of the
fxtures connects at a diferent level than the other, observe the
following procedure. If fxture drains are the same size, increase
the vertical drain one size. If fxture drains are of diferent sizes,
connect the smaller above the larger connection and maintain
the vertical size up to the top connection.
SudS PreSSure
Te prevalent use of high-sudsing detergents in washing
machines, dishwashers, laundry trays, and kitchen sinks has cre-
ated serious problems in all residential buildings and especially
in high-rise buildings. Until manufacturers are forced to market
only detergents without sudsing characteristics, the plumbing
engineer must understand and cope with the dangers created
in the sanitary system by the presence of suds. (An interesting
sidelight is that suds, in and of themselves, do not enhance the
cleaning ability of soaps or detergents in any way.)
When the fow of wastes from upper foors contains deter-
gents, the sudsingredients are vigorously mixed with the water
and air in the stack as the waste fows down the stack and further
mixing action occurs as other branch waste discharges meet this
fow. Tese suds fow down the stack and settle in the lower sec-
tions drainage system and at any ofsets greater than 45 degrees
in the stack. Investigation has shown that when sudsing wastes
are present, the sanitary and vent stacks are laden with suds and
this condition was found to exist for extended periods of time.
Liquid wastes are heavier than suds and easily fow through
the suds-loaded drainage piping without carrying the suds along
with the fow. Everyone is aware of the difculty of fushing the
suds out of a sink. Te water simply fows through the suds and
out the drain, leaving the major portion of the suds behind. Te
same action occurs in the lower sections of the drainage system
except for one important diferenceair, as well as water, is now
fowing in the piping. Tis air, which is carried down with the
waste discharge, compresses the suds and forces them to move
through any available path of relief. Te relief path may be the
building drain, any branches connected to the building drain,
the vent stack, branch vents, individual vents or combinations
of the foregoing. A path of relief may not always be available or
could be cut of or restricted by the hydraulic jump, or a path
may just be inadequate because of location or size. If one or
more of these conditions exist, excessively high suds pressure
can develop and blow the seals of traps with the accompanying
appearance of suds in fxtures.
High suds pressure zones occur at every change in direction,
vertically or horizontally, that is greater than 45. Where vent
stack base connections, relief vents, branch vents, or individual
vents serve as the relief path for the high suds pressure, they
are usually found to be inadequate in size with resultant
suds conditions appearing at the fxtures. Te vent pipe
sizing tables in practically every code are calculated on the
basis of air fow capacity and do not in any way provide
for the more demanding fow of suds. Sizes that are based
on these code tables are inadequate to accommodate suds
fow and thus are incapable of providing adequate suds
pressure relief.
Suds are much heavier than air and consequently do
not fow with the same ease. Tey produce a much greater
friction head loss for the same rate of fow. Te density of
old or regenerated suds varies from 2 lb/ft
3
to a high of
19 lb/ft
3
, depending upon the detergent used. For equal
rates of fow and pressure loss, the vent pipe diameter for
suds relief fow must be from 20 to 80% greater than for air
fow.
Whenever a soil or waste stack receives washing
machines, dishwashers, laundry trays, kitchen sinks, or
other fxtures where sudsing detergents are used, the
drainage and vent piping for the lower-foor fxtures or for
the fxtures above ofsets must be arranged to avoid con-
nection to any zone where suds pressure exists.
Suds pressure zones exist in the following areas:
1. At a soil or waste stack
ofset greater than 45: 40 stack diameters upward and 10
stack diameters horizontally from the base ftting for the
Figure 10 Circuit and Loop Venting
Figure 9 Stack Vented Unit
8 Plumbing Systems & Design JANUARY/FEBRUARY 2007 PSDMAGAZINE.ORG
C0N7INUINC DUCA7I0N: Vent Systems
upper stack section. A pressure zone also exists 40 stack
diameters upstream from the top ftting of the lower stack
section.
2. At the base of a soil or waste stack: Te suds pressure zone
extends 40 stack diameters upward from the base ftting.
3. In the horizontal drain from the base of a stack: Te
suds pressure zone extends 10 stack diameters from the
base ftting, and where an ofset greater than 45 in the
horizontal occurs, the pressure zones extend 40 stack
diameters upstream and 10 diameters downstream from
the ofset ftting.
4. In a vent stack connected to a suds pressure zone: Te suds
pressure zone exists from the vent stack base connection
upward to the level of the suds pressure zone in the soil or
waste stack.
Figure 11 illustrates all the above zones.
VaPor VentS (local VentS)
Years ago water closets and urinals were equipped with con-
nections for venting the fxture to the outdoors to eliminate foul
odors. Fixture design has been improved so that these vents are
no longer required. Te use of vapor vents is now applied to
sterilizing equipment and bedpan washers. Tis application is
also rapidly disappearing as new methods of condensing the
foul vapors are being built into the equipment. When a vapor
vent is used, it must be isolated from the sanitary venting system.
Te base of a vapor vent stack should terminate in a trap, to pre-
vent the escape of vapors, and spill to a trapped, vented, and
water-supplied receptacle. Te stack should extend through
the roof.
An individual vapor vent drip can be connected through
an air gap to the inlet of the trap serving the fxture. Vapor
vents for bedpan washers and bedpan sterilizers must not
connect with the vapor vents of other fxtures.
Sizing of the vapor vent stack may be by empirical methods
or the rational approach may be used. Te minimum size of
the stack should be 1 in.
ejector and SumP VentS
Ejectors, other than the pneumatic type, operate at atmo-
spheric pressure and receive drainage discharge under grav-
ity fow conditions. An ejector is installed when the level of
fxture discharge is below the level of the public sewer. It is
convenient to view an ejector system as being exactly simi-
lar to the gravity sanitary system and all of the requirements
for the proper design of the sanitary system are applicable.
Tus, the air required to be conveyed by the vent piping is
the same as the maximum rate at which sewage enters or is
pumped out of the receiver.
Te ejector vent can be determined by reference to Equa-
tion 10:
L = 2226
(
d
2
) fq
2
and using Table 1, which gives air discharge in gpm for vari-
ous pipe diameters. It has been found in practice that 3 in. is
adequate except for extremely large installations.
froSt cloSure
Where the danger of frost closure of vent terminals is pres-
ent, the minimum size of the vent stack or vent extension
through the roof should be 3 in. When a vent stack must be
increased in size going through the roof, the increase should be
made inside the building at least 1 ft below the roof.
Te National Bureau of Standards has investigated the prob-
lem of frost closure both theoretically and experimentally. It was
demonstrated that a 3-in. vent terminal froze up solidly at -30F
only over an extended period of time. Closure occurs at the rate
of 1 in. for every 24 hr. that the temperature remains at -30F.
It can be seen that frost closure presents a real problem only
in the far northern regions. Te problem is serious in Canada,
and they have devised various methods of overcoming it:
1. Vent terminal to extend only 1 in. or 2 in. above the roof.
Te more pipe exposed to the atmosphere, the greater
the problem. Snow covering the vent terminal has proven
to cause no trouble. Te snow is porous enough for the
passage of air and melts rather rapidly at the outlet.
2. Enlargement of the stack below the roof. Te increased
diameter decreases the chance of complete closure and
the stream of air tends to fow through the enlarged
portion without touching the walls of the enlarged pipe.
3. Install cap fashing at the terminal and counterfashing to
leave an air space from the heated building.
Frost closure depends upon the: (1) outside temperature, (2)
temperature and humidity of inside air, (3) wind velocity, (4)
length of exposed pipe, (5) diameter of exposed pipe, and (6)
velocity of air fow. Tere is very little danger of frost closure
unless the outside temperature falls below -10F and remains
Figure 11 Suds Pressure Zones
JANUARY/FEBRUARY 2007 Plumbing Systems & Design 9
there for several days. It has been found that if frost closure does
occur, siphonage of traps is reduced or prevented by connecting
the drainage and vent stacks together before extending through
the roof. An analysis of air fow under these conditions will con-
vince the plumbing engineer of its validity, as it can be seen that
air forced into the vent stack at its base will be introduced into
the soil stack at the top connection.
teStS of Plumbing SyStemS
Te complete storm and sanitary system should be subjected to
a water test and proven watertight upon completion of the rough
piping installation and prior to covering or concealment. Te
test pressure should be a minimum of a 10-ft column of water
except for the topmost 10 ft of pipe. Te test pressure should
never exceed a maximum of a 100-ft column of water. Any greater
pressure will cause the test plugs used to seal temporarily open
piping in the system to blow. If the system is higher than 100 ft,
test tees may be installed at appropriate heights so as to test the
building in sections. Very rarely in practice are more than seven
stories tested at one time.
If it is not possible to perform a water test, an air test is accept-
able. Te air test shall be made by attaching an air compressor
testing apparatus to any suitable opening, and, after closing all
other inlets and outlets to the system, forcing air into the system
until there is a uniform gage pressure of 5 psi (34.5 kPa) or a
pressure sufcient to balance a column of mercury 10 in. (254
mm) in height. Te pressure shall be held without introduction
of additional air for a period of at least 15 min.
Upon completion of the sanitary system and after all fxtures
are installed with traps flled with water, the system should be
subjected to an additional test and proved gastight.
An alternate test is the smoke test. Te smoke test is performed
by introducing pungent, thick smoke produced by smoke bombs
or smoke machines. When smoke appears at the roof terminals,
each terminal is sealed and a smoke pressure of 1-in. column of
water is maintained to prove the system gastight. Tis test is not
practical and is seldom used.
Another alternate test is the peppermint vapor test. At least 2
oz. of oil of peppermint are introduced into each roof terminal
and vaporized by immediately pouring 10 qt of boiling water
down the stack. Te terminals are promptly sealed. Oil of pepper-
mint and any person coming in contact or handling the oil must
be excluded from the interior of the building for the duration of
the test. Leakages will be detected by the peppermint odor at the
source. However, it is very difcult to pinpoint the leak by this
method. Tis test is not practical and is seldom used.
10 Plumbing Systems & Design JANUARY/FEBRUARY 2007 PSDMAGAZINE.ORG
C0N7INUINC DUCA7I0N: Vent Systems
C0N7INUINC DUCA7I0N
P
S
D
1
3
7
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
CE QuestionsVent Systems (PSD 137)
About This Issues Article
The January/February 2007 continuing education article is
Vent Systems, Chapter 8 of Engineered Plumbing Design II by A.
Calvin Laws, PE, CPD.
Flow of air is the primary consideration in the design of a
venting system for the ventilation of the piping and protection
of the fixture trap seals of a sanitary drainage system. Since air
is of such primary importance, it is essential that the plumbing
engineer be familiar with certain physical characteristics that
are pertinent to its behavior in a plumbing system. This chapter
explains these fundamentals that are vital to the design of a
vent system. It also covers vent stacks, the various types of
vents and venting, the effects of suds pressure, frost closure,
and vent system pressure tests.
You may locate this article at www.psdmagazine.org. Read
the article, complete the following exam, and submit your
answer sheet to the ASPE office to potentially receive 0.1 CEU.
Do you fnd it difcult to obtain continuing education units (CEUs)?
Trough this special section in every issue of PS&D, ASPE can help
you accumulate the CEUs required for maintaining your Certifed in
Plumbing Design (CPD) status.
Now Online!
Te technical article you must read to complete the exam is located
at www.psdmagazine.org. Te following exam and application form
also may be downloaded from the Web site. Reading the article and
completing the form will allow you to apply to ASPE for CEU credit.
For most people, this process will require approximately one hour. If
you earn a grade of 90 percent or higher on the test, you will be notifed
that you have logged 0.1 CEU, which can be applied toward the CPD
renewal requirement or numerous regulatory-agency CE programs.
(Please note that it is your responsibility to determine the acceptance
policy of a particular agency.) CEU information will be kept on fle at
the ASPE ofce for three years.
Note: In determining your answers to the CE questions, use only the material
presented in the corresponding continuing education article. Using information
from other materials may result in a wrong answer.
1. A wet vent is ___________.
a. not allowed by most codes
b. a vent that vents a particular fxture and at the same
time serves as a waste vent to receive the discharge
from other fxtures
c. not allowed to serve water closets
d. a system of individual or common vents for every trap
2. 7he vent piping must be designed to permit the air to
___________.
a. fow freely
b. enter the piping network
c. exit the piping network
d. be compressed
3. Suds, in and of themseIves, ___________.
a. do not enhance the cleaning ability of soaps or
detergents in any way
b. are only a problem if they are allowed to accumulate in
large numbers
c. require wet venting to rinse the suds out of the drain
pipe
d. none of the above
4. 7he most expensive venting system is a ___________
system.
a. wet vent, b. continuous vent, c. circuit vent, d. loop vent
5. Vapor vents ___________.
a. must be isolated from the sanitary venting system
b. may be connected through an air gap to the trap
serving the fxture
c. must not be connected to the vapor vents of other
types of equipment
d. all of the above
6. 7o compensate for suds density, the vent pipe for suds
reIief ow must ___________.
a. not be depended on for suds protection
b. connect to each fxture trap
c. connect 10 pipe diameters from any high pressure suds
zone
d. be 20 percent to 80 percent larger in diameter
7. What is the primary consideration in the design of a
venting system!
a. removing odors from the sewer system
b. correctly sizing the vent piping to match the size of the
waste piping
c. the fow of air in the vent system
d. none of the above
8. For a given rate of discharge from a Iavatory, decreasing
the diameter of the drain wiII ___________.
a. increase the water discharge velocity from the fxture
b. decrease the water discharge velocity from the fxture
c. increase trap seal losses
d. prevent trap seal losses
9. Smoke tests and peppermint air tests ___________.
a. can detect the location of a leak in a vent system
b. are no longer allowed by OSHA and the EPA
c. are not practical and seldom used
d. may not be used where frost closure is expected
10. A coIumn of air 69.23 feet high exerts the same pressure
as a coIumn of water ___________ high.
a. 1 inch, b. 10 inches, c. 100 inches, d. 1,000 inches
11. A branch vent intervaI is ___________.
a. determined by the foor-to-foor height of the building
b. dependent on the arrangement of the fttings
connecting at each foor
c. at least 8 feet between branches
d. of no importance in modern plumbing systems
12. 7he maximum distance of a vent to a 2-inch-diameter
trap is ___________.
a. 30 inches, b. 42 inches, c. 60 inches, d. 72 inches
12 Plumbing Systems & Design JANUARY/FEBRUARY 2007 PSDMAGAZINE.ORG
P
S
D
1
3
8
Water
System
Design
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
MARCH/APRIL 2007
PSDMAGAZINE.ORG
Te objective in designing the water supply systems for any
project is to ensure an adequate water supply at adequate pres-
sure to all fxtures and equipment at all times and to achieve the
most economical sizing of the piping.
Tere are at least six important reasons that proper design of
water distribution systems is absolutely essential:
1. Health. Tis is of irrefutable and paramount importance.
Inadequate or improper sizing can cause decreases in
pressure in portions of the piping system, which in turn
can cause contamination of the potable water supply by
backfow or siphonage. Tere are too many well-docu-
mented deaths attributable to this cause.
2. Pressure. It is essential to maintain the required fow pres-
sures at fxtures and equipment or improper operation will
result.
3. Flow. Proper and adequate quantities of fow must be
maintained at fxtures and equipment for obvious reasons.
4. WaterSupply. Improper sizing can cause failure of the
water supply due to corrosion or scale buildup.
5. PipeFailure. Pipe failure can occur due to the relation of
the rate of corrosion with excessive velocities.
6. Noise. Velocities in excess of 10 ft/sec will cause noise and
increase the danger of hydraulic shock.
Of all the complaints resulting from improperly designed
water systems, the two that occur most frequently are (1) lack of
adequate pressure and (2) noise.
Noise may not be detrimental to the operation of a water dis-
tribution system but it is very defnitely a major nuisance. Te
lack of adequate pressure, however, can have very serious reper-
cussions in the operation of any water system.
Flow Pressure
It is essential that the term fow pressure be thoroughly under-
stood and not confused with static pressure. Flow pressure is that
pressure that exists at any point in the system when water is fow-
ing at that point. It is always less than the static pressure. To have
fow, some of the potential energy is converted to kinetic energy
and additional energy is used in overcoming friction, which
results in a fow pressure that is less than the static pres-
sure.
When a manufacturer lists the minimum pressure
required for the proper operation of a fush valve as
25 psi, it is the fow pressure requirement that is being
indicated. Te fush valve will not function at peak
efciency (if at all) if the engineer has erroneously
designed the system so that a static pressure of 25 psi
exists at the inlet to the fush valve.
Flow at an outlet
Tere are many times when the engineer must deter-
mine how many gallons per minute are being delivered
at an outlet. Tis can easily be determined by installing
a pressure gauge in the line adjacent to the outlet and
reading the gauge while fow is occurring. With the fow pres-
sure known, the following formula can be used:
(1)
q = 20d
2
p
where
q = rate of fow at the outlet, gpm
d = actual inside diameter (ID) of outlet, in.
p = fow pressure, psi
Assume a faucet with a
3
8-in. supply and the fow pressure is
16 psi. Ten:
q = 20 (
3
8)
2
(16)
= 20
9
64 4
= 11.25 gpm
Te fow for a -in. and
1
8-in. supply at the same pressure
would be 5 gpm and 1.25 gpm, respectively.
Constant Flow
Pressures in the various parts of the piping system are con-
stantly fuctuating depending upon the quantity of fow at any
moment. Under these conditions the rate of fow from any one
outlet will vary with the change of pressure. In industrial and
laboratory projects there is some equipment that must be sup-
plied with a fxed and steady quantity of fow regardless of line
pressure fuctuations. Tis feature is also desirable in any type
of installation.
Tis criterion can easily be achieved by the utilization of an
automatic fow-control orifce. A fow control is a simple, self-
cleaning device designed to deliver a constant volume of water
over a wide range of inlet pressures. (See Figures 1 and 2.) Te
automatic controlling mechanism consists of a fexible orifce
that varies its cross-sectional area inversely with the pressure
so that a constant fow rate is maintained under all conditions.
Until the inlet pressure reaches the threshold pressure (1215
psi), the fexible insert acts as a fxed orifce. When the thresh-
old pressure is exceeded, the cross-sectional area of the orifce
is decreased by the fexure of the insert. Tis causes a pressure
drop that is equal to whatever pressure is necessary to absorb
the energy not required to overcome system friction and to
Water System Design
Reprinted from Engineered Plumbing Design II, Chapter 13: Water System Design, by A. Calvin Laws, PE, CPD.
American Society of Plumbing Engineers.
Figure 1 Flow Control
Plumbing Systems & Design MARCH/APRIL 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION
sustain the rated fow. Te curve shown in Figure 2 is typical of
most fow controls regardless of the rated fow, which is why no
fgures are shown for the gallons per minute axis. It is possible to
approximate the fow of a specifc fow control by using the line
marked Nominal Flow Rate as the desired rate.
Assume a piece of equipment requires the fxed
fow of 40 gpm and there is considerable line pres-
sure fuctuation. A fow control would be specifed
to deliver 40 gpm. By use of the curve in Figure 2 the
deviation from 40 gpm at various pressures can be
read by assigning a value of 40 to the nominal fow
rate line on the vertical scale and zero to the baseline.
Standard fow controls are available in sizes from
in. to 2 in. and fow rates from to 90 gpm. Tey are
ideal for use in limiting the maximum rate of fow to
any fxture.
It is not unusual in a water distribution system to
experience fuctuating discharges at fxtures and
equipment due to other fxtures and equipment start-
ing up or shutting down. Flow controls will minimize
these problems because they automatically com-
pensate for changes in the line pressure to hold the
rate of water delivery from all outlets to a preselected
number of gallons per minute. One very important
word of cautiona fow control is not designed to
perform the function of pressure regulation and
should never be used where a pressure-regulating
valve is required.
Material seleCtion
Before the type of material for the piping of a water
distribution system can be selected, certain factors
must be evaluated:
1. Te characteristics of the water supply must be
known. What is the degree of alkalinity or acidity?
A pH above 7 is alkaline and below 7 is acidic.
A pH of 7 represents neutral water. What is the
air, carbon dioxide, and mineral content? Te
municipal water supply department can usually
furnish all this information. If it is not available,
a water analysis should be made by a qualifed
laboratory.
2. What are the relative costs of the various suitable
materials?
3. Ease of replacementcan the material be
obtained in a reasonable time or must it be
shipped from localities that might delay arrival
for months?
4. Actual inside dimensions of the same nominal size of vari-
ous materials difer. Tis variation in ID can have a signif-
cant efect on sizing because of the variation in quantity
rates of fow for the same design velocity. Table 1 shows the
actual ID for various materials.
5. Te roughness or smoothness (coefcient of friction) of the
pipe will have a marked efect on pipe sizes.
Parallel CirCuits
Tere are many parallel pipe circuits in the water distribution
system of any job. An arrangement of parallel pipe circuits is
one in which fow from a single branch divides and fows in
two or more branches which again join in a single pipe. Figure
3 illustrates a simple two-circuit system. Te total fow enter-
ing point A is the same leaving point A with a portion fowing
through branch 1 and the rest through branch 2. Flows q
1
and q
2
must equal q and the total pressure drop from A to B is the same
Figure 2 Flow Control Device Curve (Dole Valve)
Figure 3 Typical Parallel Pipe Circuit
Nominal
Pipe Size,
In.
Iron or Steel
Pipe, Sch.
40
Brass or
Copper Pipe
Copper Water
Tube, Type K
Copper Water
Tube, Type L
0.622 0.625 0.527 0.545
0.824 0.822 0.745 0.785
1 1.049 1.062 0.995 1.025
1 1.380 1.368 1.245 1.265
1 1.610 1.600 1.481 1.505
2 2.067 2.062 1.959 1.985
2 2.469 2.500 2.435 2.465
3 3.068 3.062 2.907 2.945
4 4.026 4.000 3.857 3.905
5 5.047 5.062 4.805 4.875
6 6.065 6.125 5.741 5.845
8 7.981 8.001 7.583 7.725
10 10.020 10.020 9.449 9.625
Table 1 Actual Inside Diameter of Piping,in Inches
MARCH/APRIL 2007 Plumbing Systems & Design
whichever branch is traversed. Te rate of fow through each
branch becomes such as to produce this equal pressure drop.
Te division of fow in each branch can then be expressed as:
(2)
q
1
=
L2
(
d1
)
5
q
2 L
1
d
2
Assume there is a fow in a 3in. pipe of 160 gpm entering
point A and leaving point B as shown in Figure 4. Te length of
branch 1 is 20 ft and branch 2 is 100 ft. Te size of branch 1 is
2 in. and branch 2 is 3 in. To determine the quantity of fow in
each branch, the basic formula is applied, and:
q
1
=
100
(
2
)
5
q
2 20 3
= 5 (.66)
5
= 5 0.125
= 0.79
q
1
= 0.79q
2
since q
1
+ q
2
= 160
then 0.79q
2
+ q
2
= 160
1.79q
2
= 160
q
2
= 89.4 gpm
and q
1
= 160 - 89.4 = 70.6 gpm
or q
1
= 0.79 89.4 = 70.6 gpm
inadequate Pressure
As previously noted, lack of adequate pressure is one of the most
frequent complaints and could be the cause of serious troubles.
Te pressure available for water distribution within a building
can come from various sources. Municipalities usually maintain
water pressure in their distribution mains within the range of
3545 psi. Tere are localities where the pressure maintained is
much less or greater. Te local utility will furnish the information
as to their minimum and maximum operating pressures. When
utilizing only the public water main pressure for the water dis-
tribution system within a building, it is very important to deter-
mine the pressure available in the mains during the summer
months. Huge quantities of water are used during this period
for sprinkling of lawns and for air-conditioning cooling tower
makeup water, which usually cause excessive pres-
sure loss in the mains. Future growth of the area
must also be analyzed. If large housing, commer-
cial, or industrial development is anticipated, the
pressure available will certainly decrease as these
loads are added to the public mains. It is good
practice to assume a pressure available for design
purposes as 10 psi less than the utility quotes.
If the pressure from the public mains is inade-
quate for building operation, other means must be
provided for increasing the pressure to an adequate
level. Tere are three basic methods available:
1. Gravity tank system
2. Hydropneumatic tank system
3. Booster pump system
Each system has its own distinct and special
advantages and disadvantages. All three should be
evaluated in terms of capital expenditure, operat-
ing costs, maintenance costs, and space require-
ments. Depending upon which criteria are the most important,
this will dictate which system is selected.
Flow deFinitions
Maximum fow or maximum possible fow is the fow that will
occur if the outlets on all fxtures are opened simultaneously.
Average fow is that fow likely to occur in the piping under
normal conditions. Maximum probable fow is the maximum
fow that will occur in the piping under peak conditions. It is
also called peak demand or peak fow.
deMand tyPes
Some outlets impose what is called a continuous demand on
the system. Tey are diferentiated from outlets that impose an
intermittent demand. Outlets such as hose bibbs, lawn irriga-
tion, air-conditioning makeup, water cooling, and similar fow
requirements are considered to be continuous demands. Tey
occur over an extended period of time. Plumbing fxtures draw
water for a relatively short period of time and are considered as
imposing an intermittent demand.
Each fxture has its own singular loading efect on the system,
which is determined by the rate of water supply required,
the duration of each use, and the frequency of use. Te water
demand is related to the number of fxtures, type of fxtures, and
probable simultaneous use.
estiMating deMand
Te basic requirements for estimating demand call for a
method that
1. Produces estimates that are greater than the average
demand for all fxtures or inadequate supply will result
during periods of peak demand.
2. Produces an accurate estimate of the peak demand to
avoid oversizing.
3. Produces estimates for demand of groups of the same type
of fxtures as well as for mixed fxture types.
design loads
Arriving at a reasonably accurate estimate of the maximum
probable demand is complicated due to the intermittent opera-
tion and irregular frequency of use of fxtures. Diferent kinds
of fxtures are not in uniform use. Bathroom fxtures are most
frequently used on arising or retiring and, not surprisingly,
during television commercials. Kitchen sinks fnd heavy usage
Figure 4 Example of Division of Flow in a Parallel Pipe Circuit
Plumbing Systems & Design MARCH/APRIL 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Water System Design
before and after meals. Laundry trays and washing machines
are most likely to be used in the late morning. During the period
from midnight to 6 P.M. there is very little fxture use. Luckily,
fxtures are used intermittently and the total time in operation is
relatively small so it is not necessary to design for the maximum
potential load. Maximum fow is therefore of no real interest to
the designer. Average fow is also of no concern, for if a system
were designed to meet this criterion it would not satisfy the con-
ditions under peak fow. It is therefore necessary to consider
only the maximum probable demand (peak demand) imposed
by the fxtures on a system.
Two methods have evolved in the United States that, when
used where applicable, have proven to give satisfactory results.
Tey are the empirical method and method of probability. Te
empirical method is based upon arbitrary decisions arrived at
from experience and judgment. It is useful only for small groups
of fxtures. Te method of probability is based upon the theory
of probabilities and is most accurate for large groups of fxtures.
In the past, certain demand rates became generally accepted
as standard. Tese rates are tabulated in Table 2 for the common
types of fxtures and the average pressure necessary to deliver
this rate of fow. Te actual pressure for a specifc fxture will
vary with each manufacturers design, some requiring a greater
or lesser pressure than others.
Although the fow rates shown in Table 2 have been used by
engineers, they are hopelessly outdated. Water conservation
measures being mandated by federal regulations and model
codes make the fow rates shown in Table 2 unreasonable for
use in the design of systems. Te federal Energy Policy Act
(EPACT92) established the following criteria for water use by
fxture:
Water closets: 1.6 gal/fush
Urinals: 1.5 gal/fush
Showers: 2.5 gpm
Lavatories: 2.5 gpm
Sinks: 2.5 gpm
Manufacturers ofer fxtures meeting these and more stringent
requirements. Lavatories with 0.5 gpm fow rates and urinals
with 1.0 gal/fush have been installed in thousands of buildings
with satisfactory results. However, there is a need for research
to determine the actual minimum fow required, for each type
of fxture, to satisfy psychological requirements of the user and
provide the necessary sanitary requirements.
water suPPly Fixture units
A standard method for estimating the water demand for a build-
ing has evolved through the years and has been accepted almost
unanimously by plumbing designers. It is a system based on
weighting fxtures in accordance with their water supply load-
producing efects on the water distribution system. Te National
Bureau of Standards has published report BMS 65, Methods of
Estimating Loads in Plumbing Systems, by the late Dr. Roy B.
Hunter, which gives tables of load-producing characteristics
(fxture unit weights) of commonly used fxtures, along with
probability curves that make it possible to apply the method
easily to actual design problems.
Te method of probability should not be used for a small
number of fxtures. Although the design load, as computed by
this method, has a certain probability of not being exceeded,
it may nevertheless be exceeded on rare occasions. When a
system contains only a few fxtures, the additional load imposed
by one fxture more than has been calculated by the theory of
probability can easily overload the system. When a system con-
tains a large number of fxtures, one or several additional fxture
loadings will have an insignifcant efect on the system.
In developing the application of the theory of probability to
determine design loads on a domestic water distribution system,
Hunter assumed that the operation of the fxtures in a plumb-
ing system could be viewed as purely random events. He then
determined the maximum frequencies of use of the fxtures. He
obtained the values of the frequencies from records collected
in hotels and apartment houses during the periods of heaviest
usage. He also determined characteristic values of the average
rates of fow for diferent fxtures and the time span of a single
operation of each.
If only one type of fxture were used in a building, the appli-
cation of the theory of probability would be very simple and
straightforward. When dealing with systems composed of
various types of fxtures that must be combined, the process
becomes extremely involved and too complicated to be of any
practical use. Faced with this dilemma, Hunter devised an inge-
nious method to circumvent the problem by a simple process
which yields results within % accuracy of the more involved
and laborious calculations required. He conceived the idea of
assigning fxture loading factors or fxture unit weights to
the diferent kinds of fxtures to represent the degree to which
they loaded a system when used at their maximum assumed
frequency. A fxture unit weight of 10 was arbitrarily assigned
by Hunter to a fush valve, and all other fxtures were assigned
values based on their load-producing efect in relation to the
fush valve. All fxtures have been converted, in essence, to one
fxture type and the application of the theory of probability is
greatly simplifed.
Hunter assigned water supply fxture unit (FU) values for dif-
ferent kinds of fxtures, which are given in Table 3. Conversion
of fxture unit values to equivalent gallons per minute, based on
the theory of probability of usage developed by Hunter, is given
in Table 4. A graphic representation of this table is shown by
Figures 5 and 6 (Hunters Curve). Figure 7 gives a graphic rep-
resentation of the conversion from fxture units to gallons per
minute for a mixed system. An examination of the curves and
tables reveals that demand for a system utilizing fush valves is
much greater than that for fush tanks for small quantities. Te
diference in demand for each system decreases as the fxture
unit load increases until 1,000 FUs are reached. At this loading
and beyond, the demand for both types of systems is the same.
Fixture Flow Pressure,
psi
Flow Rate,
gpm
Ordinary lavatory faucet 8 3.0
Self-closing lavatory faucet 12 2.5
Sink faucet,
3
8 in. 10 4.5
Sink faucet, in. 5 4.5
Bathtub faucet 5 6.0
Laundry tub faucet, in. 5 5.0
Shower head 12 5.0
Water closet fush tank 15 3.0
Water closet fush valve, 1 in. 1025 1545
Urinal fush valve, in. 15 15.0
Hose bibb or sill cock, in. 30 5.0
Table 2 Demand at Individual Fixtures and Required
Pressure
MARCH/APRIL 2007 Plumbing Systems & Design
Fixture or Group Occupancy
Type of Supply
Control
Fixture Units
Hot Cold Total
Water closet Public Flush valve 10 10
Water closet Public Flush tank 5 5
Pedestal urinal Public Flush valve 10 10
Stall or wall urinal Public Flush valve 5 5
Stall or wall urinal Public Flush tank 3 3
Lavatory Public Faucet 1.5 1.5 2
Bathtub Public Faucet 3 3 4
Shower head Public Mixing valve 3 3 4
Service sink Ofce, etc. Faucet 3 3 4
Kitchen sink Hotel or restaurant Faucet 3 3 4
Water closet Private Flush valve 6 6
Water closet Private Flush tank 3 3
Lavatory Private Faucet .75 .75 1
Bathtub Private Faucet 1.5 1.5 2
Shower head Private Mixing valve 1.5 1.5 2
Bathroom group Private Flush valve W.C. 2.25 6 8
Bathroom group Private Flush tank W.C. 2.25 4.5 6
Separate shower Private Mixing valve 1.5 1.5 2
Kitchen sink Private Faucet 1.5 1.5 2
Laundry tray Private Faucet 2 2 3
Combination fxture Private Faucet 2 2 3
Table 3 Demand Weight of Fixtures, in Fixture Units
Figure 6 Conversion of Fixture Units to gpm (enlarged scale)
Figure 5 Conversion of Fixture Units to gpm
Demand
(Load)
Fixture Units
Demand
(Load), gpm
System with
Flush Tanks
Demand
(Load), gpm
System with
Flush Valves
1 0
2 1
3 3
4 4
5 6
6 5
8 6.5
10 8 27
12 9 29
14 11 30
16 12 32
18 13 33
20 14 35
25 17 38
30 20 41
35 23 44
40 25 47
45 27 49
50 29 52
60 32 55
70 35 59
80 38 62
90 41 65
100 44 68
120 48 73
140 53 78
160 57 83
180 61 87
200 65 92
225 70 97
250 75 101
275 80 106
300 85 110
400 105 126
500 125 142
750 170 178
1,000 208 208
1,250 240 240
1,500 267 267
1,750 294 294
2,000 321 321
2,250 348 348
2,500 375 375
2,750 402 402
3,000 432 432
4,000 525 525
5,000 593 593
6,000 643 643
7,000 685 685
8,000 718 718
9,000 745 745
10,000 769 769
Table 4 Conversion of Fixture Units to
Equivalent gpm
Plumbing Systems & Design MARCH/APRIL 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Water System Design
For hot water piping and where there are no fush valves on
the cold water piping, the demand corresponding to a given
number of fxture units is determined from the values given for
the fush tank system.
Te accuracy of Hunters curve, however, has come into seri-
ous question. Results utilizing the curve have proven to be as
much as 100% infated in some instances. Te consistent overde-
sign, however, should in no way be interpreted as indicating that
Hunters basic research and approach are incorrect.
His method is demonstrably accurate, but it must be remem-
bered that his basic assumptions and criteria were promulgated
more than 60 years ago. Many things have changed, and changed
drastically, in the interim. Improvements have been made in
fush valve design as well as in faucets and fxtures. Social cus-
toms and living patterns have changed. Te public emphasis on
water and energy conservation has altered many basic criteria.
It is now necessary to change some of Hunters basic assump-
tions (but not his concept).
It has been demonstrated by thousands of projects operating
satisfactorily that it is safe to reduce the values obtained by use
of Hunters curve by 40%. It is stressed again that this reduction
can be applied only for systems with a large number of fxtures.
Te opposite is true for water use in toilet facilities where large
numbers of people gather, such as sport facilities and auditori-
ums. In these types of facilities, demand fow rates will exceed
those determined by Hunters curve because many people will
use the toilet rooms during breaks in the game or performance.
Te student is again warned to use the table of fxture unit
values in the code applicable to the locality of the project. Te
values vary slightly from code to code. Te student is also alerted
to the fact that water supply fxture units are not the same as
drainage fxture unit values. Te discharge rates of cer-
tain fxtures are entirely diferent from the rate at which
water is supplied, e.g., bathtubs. Te loading efect is
therefore diferent on the drainage system than it is on
the water supply system for specifc fxtures.
For supply outlets that are likely to impose continuous
demands, estimate the continuous demand separately
from the intermittent demand and add this amount in
gallons per minute to the demand of the fxtures in gal-
lons per minute.
It should be kept in mind when calculating maxi-
mum probable demands that, except for continuous
demands, fxture unit values are always added, never
gpm values. For example, if the maximum probable
demand for two branches is required and one branch
has a load of 1250 FU and the other 1750 FU, it would be
wrong to add 240 gpm + 294 gpm to obtain 534 gpm for
the total demand. Te correct procedure is to add 1250
FU + 1750 FU to obtain a total FU value of 3000 and then
from Table 4 determine the correct peak demand as 432
gpm. Te 432 gpm value refects the proper application
of the theory of probability.
Te following example illustrates the procedure for
sizing a system.
Example 1
Determine the peak demands for hot and cold and
total water for an ofce building that has 60 fush valve
water closets, 12 wall hung urinals, 40 lavatories, and
2 hose bibbs and requires 30 gpm for air-conditioning
water makeup.
From Table 3 determine the FU values:
Hot Water Cold Water Total (Hot & Cold)
60 WC 10 600 600
12 UR 5 60 60
40 Lavs 2 80
40 Lavs 1.5 60 60
60 FU 720 FU 740 FU
From Table 4 or Figure 5:
60 FU = 32 gpm hot water demand
720 FU = 174 gpm cold water demand
740 FU = 177 gpm total water demand
To the cold water and total water demand must be added the
continuous demand:
2 hose bibbs 5 (from Table 2) = 10 gpm
Air-conditioning makeup = 30 gpm
40 gpm
Ten:
Hot water demand: = 32 gpm
Cold water demand: 174 + 40 = 214 gpm
Total water demand: 177 + 40 = 217 gpm
Te conversion of fxture unit loads to equivalent gallons
per minute demand was obtained from Table 4 using straight
line interpolations to obtain intermediate values. Total water
demand is required for sizing the water service line for the
building and also for the cold water piping inside the build-
ing up to the point where the connection is taken of to the hot
water heater supply.
Figure 7 Conversion of Fixture Units to gpm (Mixed System)
MARCH/APRIL 2007 Plumbing Systems & Design
CONTINUING EDUCATION
About This Issues Article
The March/April 2007 continuing education article is Water
System Design, Chapter 13 of Engineered Plumbing Design II by
A. Cal Laws, PE, CPD.
The objective in designing the water supply systems for
any project is to ensure an adequate water supply at adequate
pressure to all fixtures and equipment at all times and to
achieve the most economical sizing of the piping. There are at
least six important reasons why proper design of water distri-
bution systems is absolutely essential: health, pressure, flow,
water, pipe failure, and noise. This chapter describes how to
design an effective water system keeping these factors in mind,
focusing on pressure, flow, and demand.
You may locate this article at www.psdmagazine.org. Read
the article, complete the following exam, and submit your
answer sheet to the ASPE office to potentially receive 0.1 CEU.
P
S
D
1
3
8
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
CE QuestionsWater System Design (PSD 138)
1. The fow of water through two parallel circuits of
diferent pipe sizes results in a pressure loss _________.
a. of equal proportions in each circuit
b. higher in the circuit with the smaller pipe size
c. lower in the circuit with the larger pipe size
d. that is double compared to a single piping run
. The accuracy of Hunters Curve has been proven to be
_________ percent infated.
a. 25
b. 50
c. 75
d. 100
. The coefcient of friction is the measurement of _______
in piping.
a. pressure drop
b. velocity
c. roughness or smoothness
d. none of the above
. Flow rates shown in Figure are _________.
a. generally accepted by system designers
b. hopelessly outdated
c. unreasonable for use in designing systems
d. b and c
. Pipe failure can be caused by corrosion from _________.
a. contaminated water
b. excessive velocities
c. softened water
d. hot water
. The actual inside diameter of -inch Type K copper
tube is _________.
a. 2.435 inches
b. 2.465 inches
c. 2.469 inches
d. 2.500 inches
. The empirical method is _________.
a. based on arbitrary decisions
b. cannot be duplicated
c. allowed only by the most out-of-date codes
d. used only by the most senior and the most junior of
designers
8. Research is required to _________.
a. determine the actual minimum fow required for each
fxture type
b. satisfy the psychological requirements of the users
c. provide the necessary sanitary requirements
d. all of the above
9. The pressure that exists in a piping network at any point
when water is fowing is considered _________.
a. static Pressure
b. residual Pressure
c. fow pressure
d. none of the above
10. The probability method _________.
a. works for all plumbing systems
b. unanimously accepted by plumbing engineers
c. should not be used for small numbers of fxtures
d. a and b
11. The two methods of sizing domestic water, empirical
method and method of probability, _________.
a. are contradictory
b. give satisfactory results
c. cannot be relied upon
d. have been replaced by computer-based methods
1. An automatic fow control orifce is designed to _______.
a. regulate pressure
b. deliver constant fow
c. restrict pressure
d. increase pressure
Do you fnd it difcult to obtain continuing education units (CEUs)?
Trough this special section in every issue of PS&D, ASPE can help
you accumulate the CEUs required for maintaining your Certifed in
Plumbing Design (CPD) status.
Now Online!
Te technical article you must read to complete the exam is located
at www.psdmagazine.org. Te following exam and application form
also may be downloaded from the website. Reading the article and
completing the form will allow you to apply to ASPE for CEU credit.
For most people, this process will require approximately one hour. If
you earn a grade of 90 percent or higher on the test, you will be notifed
that you have logged 0.1 CEU, which can be applied toward the CPD
renewal requirement or numerous regulatory-agency CE programs.
(Please note that it is your responsibility to determine the acceptance
policy of a particular agency.) CEU information will be kept on fle at
the ASPE ofce for three years.
Note: In determining your answers to the CE questions, use only the material
presented in the corresponding continuing education article. Using information
from other materials may result in a wrong answer.
8 Plumbing Systems & Design MARCH/APRIL 2007 PSDMAGAZINE.ORG
P
S
D
1
3
9
Private Sewage
Disposal
Systems
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
MAY/JUNE 2007
PSDMAGAZINE.ORG
With the ever-increasing cost of land located in proximity to
urban centers, more and more construction is being imple-
mented in outlying areas. Sanitary sewers are not usually avail-
able in these remote locations and it becomes necessary for the
plumbing engineer to design private sewage systems to handle
the wastes from buildings. Before the rapid escalation of land
values, most private sanitary disposal systems were used almost
exclusively for private residences. It is estimated that 15 mil-
lion such systems are presently in use in the United States. Of
greater signifcance, roughly 25% of all new home construction
now employs the septic tanksoil absorption sewage disposal
system.
Where the concentration of population is not sufcient to
economically justify the installation of public sewer systems,
installation of a septic tank in conjunction with a subsurface soil
absorption feld has proven to be an exceptionally satisfactory
method of sewage disposal. When properly designed, installed,
operated, and maintained, it compares very favorably with the
most sophisticated municipal sewage treatment plants.
In 1946, the U.S. Public Health Service, in cooperation with
other federal agencies involved in housing, embarked upon a
fve-year study to establish criteria for the design, installation,
and maintenance of the septic tank. Most of the information in
this chapter is freely drawn from that study and a later report
issued in 1967.
Sewage SyStem Criteria
Te proper disposal of sewage is a major factor afecting the
health of the public. When improper or inadequate disposal
of sewage occurs, many diseases, such as dysentery, infectious
hepatitis, typhoid, paratyphoid, and various types of diarrhea
are transmitted through contamination of food and water. To
avoid such hazards, any system of sewage disposal must meet
the following criteria:
It must not contaminate any drinking water supply.
It must not be accessible to insects, rodents, or other
possible carriers that might come in contact with food or
drinking water.
It must not be accessible to children.
It must not violate laws or rules and regulations governing
water pollution or sewage disposal.
It must not pollute or contaminate the waters of any bath-
ing beach, shellfsh breeding ground, or any stream used
for public or private water supply or for recreational pur-
poses.
It must not become malodorous or unsightly in appear-
ance.
All these criteria are admirably fulflled by a public sewage dis-
posal system. Every efort should be made to utilize such facili-
ties if at all possible. When public sewers are not available, some
other satisfactory method must be employed.
Any method of sewage disposal is merely an attempt to com-
plete the hydrologic cycle, or as it is now popularly called, the
ecological cycle. Contaminated water (wastes) of undesirable
quality is received and, after processing, returned at an accept-
able level of quality. Te systems to be discussed are those that
return the waste water to the soil and ultimately to the ground
water (water table).
Tere are presently two systems that return waste water to the
soil. Tey are the cesspool and the septic tanksoil absorption
systems.
CeSSpoolS
A cesspool is nothing more than a covered pit with an open-
jointed or perforated lining into which raw sewage is discharged.
Te liquid portion of the sewage is disposed by seepage or leach-
ing into the porous soil surrounding the cesspool. Te solids
(sludge) are retained in the pit.
A cesspool fnds its greatest application in receiving the efu-
ent from one-family homes and it is not recommended even
for this use. Te raw sewage tends to seal the openings in the
pit lining as well as the surrounding soil, thus necessitating fre-
quent visits from the honey dippers (cesspool cleaning ser-
vices). Cloggage may become so severe that complete abandon-
ment of the existing cesspool and the construction of a new pit
is often necessary. A cesspool should never be recommended as
a substitute for a septic tank with a soil absorption feld.
A seepage pit (discussed in another portion of this chapter)
should never be confused with a cesspool. Although the con-
struction is the same for both, a seepage pit receives the efu-
ent from a septic tank (where the solids have been liquifed),
whereas a cesspool receives raw sewage.
SeptiC tankS
A septic tank is a liquid-tight structure, with inlet and outlet
connections, which receives raw sewage. It is basically a sewage
settling tank in which raw sewage is retained for a specifed
period of time, usually 24 hr. Te primary purpose of the septic
tank is to act as a settling tank and to break up solids so that the
resulting efuent will not clog the pores of the soil in the leach-
ing feld. Very little purifcation is accomplished in the tank; the
actual treatment and digestion of harmful waste materials takes
place in the ground after discharge from the tank.
Tree functions are performed by a septic tank to produce an
efuent suitable for acceptance by a subsoil absorption system
of sewage disposal: (1) removal of solids, (2) biological treat-
ment, and (3) sludge and scum storage.
removal of SolidS
Clogging of the soil varies directly with the amount of suspended
solids in the liquid. Te rate of fow entering the septic tank is
reduced within the tank so that solids sink to the bottom or rise
to the surface of the liquid in the tank. Tese solids are retained
and the clarifed efuent is discharged.
Private Sewage
Disposal Systems
Reprinted from Engineered Plumbing Design II, Chapter 21: Private Sewage Disposal Systems, by A. Calvin Laws, PE, CPD.
American Society of Plumbing Engineers.
Plumbing Systems & Design MAY/JUNE 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION
Solids and liquid in the tank are exposed to bacterial and
natural processes, which decompose them. Te bacteria pres-
ent in the wastes are of the anaerobic type, which thrives in the
absence of oxygen. Decomposition of the sewage under anaer-
obic conditions is termed septic and it is from this the tank
derives its name.
After such biological action, the efuent causes less clogging
of the soil than untreated sewage containing the same quantity
of suspended solids.
Sludge and SCum Storage
Sludge is an accumulation of solids at the bottom of the tank.
Scum is a partially submerged foating mat of solids that forms
at the surface of the liquid in the tank. Te sludge is digested and
compacted into a smaller volume. Te same action occurs with
the scum but to a lesser degree. Regardless of the efciency of
the operation of the septic tank, a residual of inert solid mate-
rial will always remain. Adequate space must be provided in the
tank to store this residue during the intervals between cleanings.
Sludge and scum will fow out of the tank with the efuent and
clog the disposal feld in a very short period of time if pumping
out of the residue is not performed when required.
Septic tanks are eminently efective in performing their pur-
pose when adequately designed, constructed, operated, and
maintained. Tey do not accomplish a high degree of bacte-
ria removal. Although the sewage undergoes some treatment
in passing through the tank, infectious agents present in the
sewage are not removed. Te efuent of a septic tank cannot be
considered safe. In many respects, the discharged liquid is more
objectionable than the infuent because it is septic and mal-
odorous. Tis should not be construed in any way as detracting
from the value of the tank because its primary purpose is simply
to condition the raw sewage so that it will not clog the disposal
feld.
Continued treatment and the removal of pathogens are
accomplished by percolation through the soil. Disease-produc-
ing bacteria will die out after a time in the unfavorable environ-
ment of the soil. Bacteria are also removed by physical forces
during fltration through the soil. Tis combination of factors
achieves the eventual purifcation of the septic tank efuent.
SeptiC tank loCation
Te location of the septic tank should be chosen so as not to
cause contamination of any well, spring, or other source of
water supply. Underground contamination can travel in any
direction for considerable distances unless efectively fltered.
Tanks should never be closer than 50 ft to any source of water
supply and, where possible, greater distances are preferable.
Tey should be located where the largest possible area will be
available for the disposal feld and should never be located in
swampy areas subject to fooding. Ease of maintenance and
accessibility for cleaning are important factors to be considered.
When it is anticipated that public sewers will be available in the
future, provisions should be made for the eventual connection
of the house sewer to such a public source.
tank CapaCity
Studies have proven that liberal tank capacity is not only desir-
able from a functional viewpoint but is good economical design
practice. Te liquid capacities recommended in Table 1 make
allowances for all household appliances including garbage
grinders.
tank material
Septic tanks must be watertight and constructed of materials
not subject to excessive corrosion or decay. Acceptable materi-
als are concrete, coated metal, vitrifed clay, heavyweight con-
crete blocks, or hard-burned bricks. Properly cured precast and
cast-in-place, reinforced concrete are believed to be acceptable
everywhere. Local codes should be checked as to the acceptabil-
ity of the other materials. Steel tanks conforming to U.S. Depart-
ment of Commerce Standard 177-62 are generally acceptable.
Precast tanks should have a minimum wall thickness of 3 in. and
should be adequately reinforced to facilitate handling. When
precast slabs are used as covers, they should be watertight, at
least 3 in. thick and adequately reinforced. All concrete surfaces
should be coated with a bitumastic paint or similar compound
to minimize corrosion.
tank aCCeSS
Access should be provided to each compartment of the tank for
cleaning and inspection by means of a removable cover or a 20-
in. minimum size manhole. When the top of the tank is more
than 18 in. below grade, manholes and inspection holes should
be extended to approximately 8 in. below grade. Tey can be
extended to grade if a seal is provided to prevent the escape of
odors.
tank inlet
Te invert elevation of the inlet should be at least 3 in. above
the liquid level in the tank. Tis will allow for momentary surges
during discharge from the house sewer into the tank and also
prevent the backup and stranding of solids in the piping enter-
ing the tank.
A vented inlet tee or bafe should be provided to direct the
infuent downward. Te outlet of the tee should terminate at
least 6 in. below the liquid level but in no case should it be lower
than the bottom of the outlet ftting or device.
tank outlet
Te outlet ftting or device should penetrate the liquid level
just far enough to provide a balance between the sludge and
scum storage volumes. Tis will assure usage of the maximum
available tank capacity. A properly operating tank divides itself
into three distinct layers: scum at the top, a middle layer free of
solids (clear space), and sludge at the bottom layer. While the
outlet tee or device retains the scum in the tank, it also limits the
amount of sludge that can be retained without passing some of
the sludge out with efuent.
Data collected from feld observation of sludge accumulations
indicate that the outlet device should extend to a distance below
the liquid level equal to 40% of the liquid depth. For horizontal
cylindrical tanks the percentage should be 35. Te outlet device
or tee should extend up to within 1 in. of the top of the tank for
venting purposes. Te space between the top of the tank and
Table 1 Liquid Capacity of Tank (gal)
(provides for use of garbage grinders, automatic clothes
washers, and other household appliances)
Number of
Bedrooms
Recommended
Minimum Tank
Capacity
Equivalent
Capacity per
Bedroom
2 or less 750 375
3 900 300
4
a
1000 250
a For each additional bedroom, add 250 gal.
MAY/JUNE 2007 Plumbing Systems & Design
the bafe permits gas to pass through the tank into the building
sanitary system and eventually to atmosphere where it will not
cause a nuisance.
tank Shape
Available data indicate that for tanks of a given capacity and
depth, the shape of a septic tank is unimportant and that shal-
low tanks function equally as well as deep ones. It is recom-
mended, however, that the minimum plan dimension be 2 ft
and the liquid depth range from 30 to 60 in.
SCum Storage SpaCe
Space is required above the level of the liquid in the tank for the
accumulated scum, which foats on top of the liquid. Although
there is some variation, approximately 30% of the total amount
of scum will accumulate above the liquid level and 70% will be
submerged. In addition to the scum storage space, 1 in. should
be provided at the top of the tank for free passage of gas through
the tank back to the inlet and building drainage system.
For tanks with vertical walls, the distance between the top of
the tank and the liquid level should be approximately 20% of the
liquid depth. For horizontal cylindrical tanks, the liquid depth
should be 79% of the diameter of the tank. Tis will provide an
open area at the top of the tank equal to 15% of the total cross-
sectional area of the tank.
CompartmentS
Although a number of arrangements are possible, compart-
ments refer to the number of units in series. Tey can be sepa-
rate units connected together or sections enclosed in one con-
tinuous shell with watertight partitions separating the individual
compartments.
A single-compartment tank gives acceptable performance,
but available research data indicate that a two-compartment
tank with the frst compartment equal to to
2
3 of the total
volume provides better suspended solids removal. Tanks with
three or more equal compartments perform about on an equal
basis with a single-compartment tank of the same
total capacity. Te use of a more than two-compart-
ment tank is therefore not recommended. All the
requirements of construction stated previously for
a single-compartment tank apply to the two-com-
partment tank. Each compartment should be pro-
vided with an access manhole and venting between
compartments for the free passage of gas.
Figure 1 illustrates all the salient features of a
typical two-compartment septic tank.
Cleaning of tankS
Before too much sludge or scum is allowed to accu-
mulate, septic tanks should be cleaned to prevent
the passage of sludge or scum into the disposal
feld. Tanks should be inspected at least once a year
and cleaned when necessary.
Cleaning is usually accomplished by pumping
the contents of the tank into a tank truck. A small
residual of sludge should be left in the tank for
seeding purposes. Tanks should never be washed
or disinfected after cleaning.
ChemiCal additiveS
Te operation of a septic tank is not improved in
any way whatsoever by the addition of chemicals;
and such additions are not recommended. Some products
that claim to clean septic tanks contain sodium hydroxide or
potassium hydroxide as the active agent. Such compounds may
result in sludge bulking and a sharp increase in alkalinity, which
may interfere with digestion. Te efuent may severely damage
the soil structure of the disposal feld and cause accelerated
clogging even though some immediate temporary relief may be
experienced shortly after application of the product.
On the other hand, ordinary household chemicals in general
use around the home will not have a harmful efect on the oper-
ation of a septic tank. Small amounts of chorine bleach or small
quantities of lye or caustic are not objectionable. If tanks are
sized as recommended herein, the dilution of the lye or caus-
tics in the tank will be enough to minimize any harmful efects.
Soaps, detergents, bleaches, drain cleaners, etc., will have no
appreciable adverse efect on the system. However, since both
the soil and the organisms might be susceptible to large doses
of chemicals, moderation is recommended.
Toilet paper substitutes, paper towels, newspaper, wrapping
paper, rags, and sticks should not be introduced into the septic
tank. Tey may not decompose and are likely to lead to clogging
of the disposal feld.
Backwash from a household water-softening unit has no
adverse efect on the operation of a septic tank, but may cause a
slight shortening of life of the disposal feld installed in a struc-
tured clay type soil.
SeptiC tankS for nonreSidential BuildingS
Table 1 gives the liquid capacity of tanks on the basis of the
number of bedrooms. When designing a septic tank for other
types of buildings, Table 2 may be used to estimate the quantity
of sewage fow. Te quantities listed are merely the best aver-
ages presently available and should be modifed in localities or
establishments where available information indicates a need to
do so.
Figure 1 Precast Septic Tank
Plumbing Systems & Design MAY/JUNE 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Private Sewage Disposal Systems
Te retention period of the sewage in a septic tank should be
24 hr. Table 2 gives the gallons per person per day (24 hr). Te
required liquid capacity of the tank can then be determined by
multiplying the values given in the table by the estimated popu-
lation.
Tables 3 and 4 give daily gallonages in terms of fxtures for
country clubs and public parks, respectively.
SuBSurfaCe Soil aBSorption SyStem
Criteria for deSign
Te frst step in the design of a subsurface soil absorption
sewage disposal system is to determine whether the soil is suit-
able for the absorption of the septic tank efuent. If it is, the next
step is to determine the area required for the disposal feld. Te
soil must have an acceptable percolation rate and should have
adequate clearance from ground water. In general, two criteria
must be met:
1. Te percolation rate should be within the range shown in
Table 5 or Table 6.
2. Te maximum elevation of the groundwater table should
be at least 4 ft below the bottom of the trench or seepage
pit. Rock formation or other impervious strata should be at
a depth of more than 4 ft below the bottom of the trench or
seepage pit.
Table 2 Quantities of Sewage Flows
Type of Establishment
Gallons Per Person Per Day
(unless otherwise noted)
Airports (per passenger) 5
Apartmentsmultiple family (per resident) 60
Bathhouses and swimming pools 10
Camps:
Campground with central comfort stations 35
With fush toilets, no showers 25
Construction camps (semi-permanent) 50
Day camps (no meals served) 15
Resort camps (night and day) with limited plumbing 50
Luxury camps 100
Cottages and small dwellings with seasonal occupancy 50
Country clubs (per resident member) 100
Country clubs (per non-resident member present) 25
Dwellings:
Boarding houses 50
additional for non-resident boarders 10
Luxury residences and estates 150
Multiple-family dwellings (apartments) 60
Rooming houses 40
Single-family dwellings 75
Factories (gallons/person/shift, exclusive of industrial wastes) 35
Hospitals (per bed space) 250
Hotels with private baths (2 persons per room) 60
Hotels without private baths 50
Institutions other than hospitals (per bed space) 125
Laundries, self service (gal/wash, i.e., per customer) 50
Mobile home parks (per space) 250
Motels with bath, toilet, and kitchen wastes (per bed space) 50
Motels (per bed space) 40
Picnic parks (toilet wastes only) (per picknicker) 5
Picnic parks with bathrooms, showers, and fush toilets 10
Restaurants (toilet and kitchen wastes per patron) 10
Restaurants (kitchen wastes per meal served) 3
Restaurants, additional for bars and cocktail lounges 2
Schools:
Boarding 100
Day, without gyms, cafeterias, or showers 15
Day, with gyms, cafeterias, and showers 25
Day, with cafeterias, but without gyms or showers 20
Service stations (per vehicle served) 10
Swimming pools and bathhouses 10
Theaters:
Movie (per auditorium seat) 5
Drive-in (per car space) 5
Travel trailer parks
Without individual water and sewer hookups (per space) 50
With individual water and sewer hookups (per space) 100
Workers:
Construction (at semi-permanent camps) 50
Day, at schools and ofces (per shift) 15
Table 3 Sewage Flow from
Country Clubs
Type of Fixture
Gallons per Day
per Fixture
Showers 500
Baths 300
Lavatories 100
Toilets 150
Urinals 100
Sinks 50
Table 4 Sewage Flow at Public
Parks (during hours when park is open)
Type of Fixture
Gallons per Day
per Fixture
Flush toilets 36
Urinals 10
Showers 100
Faucets 15
Table 6 Allowable Rate of Sewage Application to a Soil
Absorption System
Percolation Rate
(time for water to fall
1 in.), in minutes
Maximum Rate of Sewage Application
(gal/ft
2
/day)
a
for Absorption Trenches
b
,
Seepage Beds, and Seepage Pits
c
1 or less 5.0
2 3.5
3 2.9
4 2.5
5 2.2
10 1.6
15 1.3
30
d
0.9
45
d
0.8
60
d, e
0.6
a Not including efuents from septic tanks that receive wastes from garbage grinders
and automatic washing machines.
b Absorption area is fgured as trench bottom area, and includes a statistical allowance
for vertical sidewall area.
c Absorption area for seepage pits is efective sidewall area.
d Over 30 unsuitable for seepage pits.
e Over 60 unsuitable for absorption systems.
Table 5 Absorption Area Requirements for Individual Residences
a
(provides for garbage grinder and automatic clothes washing machines)
Percolation Rate
(time required for water
to fall 1 in.), in minutes
Required Absorption Area, in
ft
2
/bedroom
b
, standard trench
c
,
seepage beds
c
, and seepage pits
d
1 or less 70
2 85
3 100
4 115
5 125
10 165
15 190
30
c, e
250
45
c, e
300
60
c, e, f
330
a It is desirable to provide sufcient land area for an entire new absorption system if
needed in the future.
b In every case, sufcient land area should be provided for the number of bedrooms
(minimum of two) that can be reasonably anticipated, including the unfnished space
available for conversion as additional bedrooms.
c Absorption area is fgured as trench bottom area and includes a statistical allowance for
vertical side wall area.
d Absorption area for seepage pits is fgured as efective side wall area beneath the inlet.
e Unsuitable for seepage pits if over 30.
f Unsuitable for absorption systems if over 60
MAY/JUNE 2007 Plumbing Systems & Design
If these two primary conditions cannot be met, the site is
unsuitable for a soil absorption system and some other seepage
disposal system must be employed.
perColation teStS
Percolation tests help to determine the acceptability of the
site and establish the size of the disposal system. Te length of
time required for percolation tests varies for diferent types of
soil. Te safest method is to make tests in holes that have been
kept flled with water for at least 4 hrs and preferably overnight.
Percolation rates should be determined on the basis of test
data obtained after the soil has had the opportunity to become
wetted or saturated.
Enough tests should be made in separate holes to assure
the validity of results. Te percolation test as developed at the
Robert A. Taft Sanitary Engineering Center has proven to be one
of the best in the country and is given here in its entirety:
Procedure for Percolation Tests
1. Number and Location of Tests. Six or more tests shall be
made in separate test holes spaced uniformly over the pro-
posed absorption feld site.
2. Type of Test Hole. Dig or bore a hole, with horizontal
dimensions of from 4 to 12 in. and vertical sides to the
depth of the proposed absorption trench. In order to save
time, labor, and volume of water required per test, the
holes can be bored with a 4-in. auger.
3. Preparation of a Test Hole. Carefully scratch the bottom
and sides of the hole with a knife blade or sharp-pointed
instrument, in order to remove any smeared soil surfaces
and to provide a natural soil interface into which water
may percolate. Remove all loose material from the hole.
Add 2 in. of coarse sand or fne gravel to protect the bottom
from scouring and sediment.
4. Saturation and Swelling of the Soil. It is important to
distinguish between saturation and swelling. Saturation
means that the void spaces between soil particles are full of
water. Tis can be accomplished in a short period of time.
Swelling is caused by intrusion of water into the individual
soil particle. Tis is a slow process, especially in clay-type
soil, and is the reason for requiring a prolonged soaking
period.
In the conduct of the test, carefully fll the hole with clear
water to a minimum depth of 12 in. over the gravel. In
most soils, it is necessary to refll the hole by supplying a
surplus reservoir of water, possibly by means of an auto-
matic syphon, to keep water in the hole for at least 4 hrs
and preferably overnight. Determine the percolation rate
24 hrs after water is frst added to the hole. Tis procedure
is to ensure that the soil is given ample opportunity to
swell and to approach the condition it will be in during
the wettest season of the year. Tus, the test will give com-
parable results in the same soil, whether made in a dry
or wet season. In sandy soils, containing little or no clay,
the swelling is not essential, and the test may be made as
described under item 5C, after the water from one flling of
the hole has completely seeped away.
5. Percolation Rate Measurement. With the exception of
sandy soils, percolation rate measurements shall be made
on the day following the procedure described under item
4, above.
A. If water remains in the test hole after the overnight
swelling period, adjust the depth to approximately 6
in. over the gravel. From a fxed reference point, mea-
sure the drop in water level over a 30-min. period. Tis
drop is used to calculate the percolation rate.
B. If no water remains in the hole after the overnight
swelling period, add clear water to bring the depth of
water in the hole to approximately 6 in. over the gravel.
From a fxed reference point, measure the drop in
water level at approximately 30-min intervals for 4 hrs,
reflling 6 in. over the gravel as necessary. Te drop
that occurs during the fnal 30-min period is used to
calculate the percolation rate. Te drops during prior
periods provide information for possible modifcation
of the procedure to suit local circumstances.
C. In sandy soils (or other soils in which the frst 6 in. of
water seeps away in less than 30 min, after the over-
night swelling period), the time interval between mea-
surements shall be taken as 10 min and the test run
for 1 hr. Te drop that occurs during the fnal 10 min is
used to calculate the percolation rate.
aBSorption area
For locations where the percolation rates and soil characteris-
tics prove to be satisfactory, the next step is to determine the
required absorption area from Table 5 for residences or from
Table 6 for other types of buildings. As noted in the tables, soil
in which the percolation rate is slower than 1 in. in 30 min is not
suitable for seepage pits and a rate slower than 1 in. in 60 min is
not satisfactory for any type of soil absorption system.
Tere are three types of soil absorption systems:
1. Absorption trenches
2. Seepage beds
3. Seepage pits.
Te selection of the system will be afected by the location
of the system in the area under consideration. A safe distance
must be maintained between the site and the source of any
water supply. No specifc distance can be absolutely safe in all
localities because of the many variables involved in the under-
ground travel of pollution. Table 7 can be used as a guide for
establishing minimum distances between various components
of a sewage disposal system.
Seepage pits should never be installed in areas of shallow
wells or where there are limestone formations and sinkholes
Table 7 Minimum Distance Between Components of Sewage Disposal System
Horizontal Distance (ft)
Component of
System
Well or
Suction Line
Water Supply
Line (pressure)
Stream Dwelling Property
Line
Building sewer 50 10
a
50
Septic tank 50 10 50 5 10
Disposal feld
and seepage bed
100 25 50 20 5
Seepage pit 100 50 50 20 10
Cesspool
b
100 50 50 20 15
a Where the water supply line must cross the sewer line, the bottom of the water service within 10 ft of the
point of crossing shall be at least 12 in. above the top of the sewer line. The sewer line shall be of cast iron
with leaded or mechanical joints at least 10 ft on either side of the crossing.
b Not recommended as a substitute for a septic tank. To be used only when found necessary and approved by
the health authority.
Plumbing Systems & Design MAY/JUNE 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Private Sewage Disposal Systems
with connection to underground channels through
which pollution could travel to water sources.
aBSorption trenCheS
Te drain pipe for a soil absorption feld may be 12-in.
lengths of 4-in. agricultural drain tile, 23 ft lengths of
open-joint vitrifed clay sewer pipe, or perforated non-
metallic pipe. Individual laterals should not exceed 100
ft in length and the trench bottom and piping should be
level. Use of more and shorter laterals is recommended
because if a breakdown should occur in any one lateral,
most of the feld would still be operative. Te space
between laterals should be at least twice the depth of
gravel to prevent overtaxing the percolative capacity of
the adjacent soil.
Te depth of the absorption trenches should be at least
24 in. to provide the minimum required gravel depth
and earth cover. Additional depth may be required for
ground contour adjustment, for extra aggregate speci-
fed under the pipe, or for other design purposes. Te
minimum distance of 4 ft between the bottom of the
trench and the water table is essential to minimize
groundwater contamination. Freezing is an extremely
rare occurrence in a well-constructed system that is
kept in continuous operation. It is of course extremely
important that the pipe be completely surrounded by the gravel
to provide for free movement of the waste water.
Te required absorption area is based upon the results of the
percolation tests and may be selected from Table 5 or 6.
Example 1
For a three-bedroom house and a percolation rate of 1 in. in
15 min, the necessary absorption area will be 3 bedrooms 190
ft
2
per bedroom (Table 5) = 570 ft
2
. For 2-ft-wide trenches with 6
in. of gravel below the drain pipe the total length of trench will
be: 570 2 = 285 ft. If this length is divided into three portions
(3 laterals), the length of each lateral will be 285 3 = 95 ft. If
this length is too long for the site, the number of laterals must
be increased. Using 5 laterals, the length of each lateral will be
57 ft. If the trenches are separated by 6 ft, the width of the feld
will be 2-ft-wide trenches 5 trenches = 10 ft plus 6 ft between
trenches 4 spaces = 24 ft. Te total feld will then be 57 ft in
length by 34 ft. in width for a total area of 1938 ft
2
plus the addi-
tional land required to keep the feld an acceptable distance
from property lines, wells, etc.
Construction
Careful construction is extremely important in achieving a sat-
isfactory soil absorption system. Care must be exercised so as
not to seal the surfaces on the bottom and sides of the trenches.
Trenches should not be excavated when the soil is wet enough
to smear or compact easily. Open trenches should always be
protected from surface runof to prevent entrance of silt and
debris. All smeared or compacted surfaces should be raked to a
depth of 1 in. and loose material removed before placing gravel
in the trench.
Te pipe should be completely surrounded by clean, graded
gravel ranging in size from to 2 in. Cinders, broken shells,
or similar materials are unsuitable as they are too fne and will
lead to premature clogging of the soil. Te gravel should extend
at least 2 in. above the top of the pipe, at least 6 in. below the
bottom of the pipe and fll the entire width of the trench. Te top
of the gravel should be covered with untreated building paper
or a 2-in. layer of hay, straw, or similar pervious material to pre-
vent the earth backfll from clogging the gravel. If an impervious
covering is used, it will interfere with evapotranspiration at the
surface. Tis is an important factor in the operation of a disposal
feld and, although evapotranspiration is not generally taken
advantage of in the calculations, it provides an added factor of
safety.
If tile pipe is used, the upper half of the joint openings should
be covered. Drain tile connectors, collars, clips or other spacers
with covers for the upper half of the joints may be used to assure
uniform spacing, proper alignment, and protection of the joints.
Tey are available in galvanized iron, copper, and plastic.
Te problem of root penetration can be avoided by the use of
a liberal quantity of gravel around the pipe. Tere should be at
least 12 in. of gravel beneath the pipe when a trench is within 10
ft of large trees or dense shrubbery.
Backflling of the trench should be hand tamped and the trench
should be overflled at least 4 to 6 in. Tis will prevent settlement
to a point lower than the surface of the adjacent ground where
storm water could collect and cause premature saturation of the
absorption feld and possible complete washout of the trench.
Machine tamping or hydraulic backflling should never be per-
mitted. Figure 2 illustrates a typical absorption trench.
Seepage BedS
Te use of seepage beds in lieu of standard trenches has been
around for over twenty-fve years. Common design practice for
soil absorption felds is for trenches with widths varying from 12
to 36 in. When trenches are wider than 3 ft they are called seep-
age beds. Typically rectangular in shape, seepage beds are com-
pact and used when less land is available for system design. Dry
climates prove to be a better environment for use than climates
having wet, humid conditions. Keep in mind, seepage beds do
not have the sidewall area to provide oxygen to the center of a
bed and long-term performance depends on the condition of
the sidewall area. Slopes greater than 5% are not suitable for this
absorption system application. Care must be taken during con-
Figure 2 Section through Typical Absorption Trench
MAY/JUNE 2007 Plumbing Systems & Design
struction so as not to destroy soil structure by compacting the
soil in the bottom of the bed. Additionally, the Federal Build-
ing Administration has sponsored studies indicating that seep-
age beds are a satisfactory method for disposing of the efuent
from septic tanks in soils that are satisfactory for soil absorp-
tion systems. Te studies have demonstrated that the empirical
relationship between percolation tests and the bottom area of
trenches is applicable for the design of seepage beds.
Te three main elements of a seepage bed are the same as those
of trenches:
1. Te absorption surface
2. Te gravel layer
3. Te distribution system.
Te advantages of seepage beds are (1) a wide bed makes more
efcient use of land than a series of long narrow trenches with
wasted land between the trenches and (2) efcient use can be
made of a variety of modern earth-moving equipment already
at the site, which will result in lower costs for the system.
Design Criteria for Seepage Beds
Te following criteria should be adhered to in the design of
seepage beds:
1. Te amount of bottom absorption area
shall be the same as for trenches, shown
in Table 5 or 6.
2. Percolation tests should be performed as
previously outlined.
3. Te bed should have a minimum depth
of 24 in. to provide a minimum earth
backfll cover of 12 in.
4. Te bed should have a minimum of 12
in. depth of gravel extending at least 2 in.
above and 6 in. below the pipe.
5. Te bottom of the bed and the distribu-
tion tile or perforated pipe should be
level.
6. Te drain lines for distributing the efu-
ent from the septic tank should be spaced no greater than 6
ft apart and no greater than 3 ft from the bed sidewalls.
Distribution Boxes
Although many codes specifcally require the use of a distribu-
tion box in a soil absorption system, research and feld tests
have conclusively demonstrated that they ofer practically no
advantages and can be a source of serious problems in many
installations. As a result of its study of distribution boxes, the
Public Health Service set forth the following conclusions in the
report to the Federal Housing Administration:
1. Distribution boxes can be eliminated from septic tank-
soil absorption systems in favor of some other method of
distribution without inducing increased failure of disposal
felds. In fact, evidence indicates that distribution boxes as
presently used may be harmful to the system.
2. Data indicate that on level ground, equal distribution is
not necessary if the system is designed so that an overload
trench can drain back to the other trenches before failure
occurs.
3. On sloping ground a method of distribution is needed to
prevent excessive buildup of head and failure of any one
trench before the capacity of the entire system is utilized.
It is doubtful that distribution boxes as presently used give
equal distribution. Rather, they probably act as diversion
devices sending most of the liquid to part of the system.
Because of the above fndings, it is recommended that distri-
bution boxes be eliminated in all disposal feld systems where
they are not specifcally required by local codes.
Seepage pitS
Where absorption felds are impractical, seepage pits may be
applicable. Te capacity of a seepage pit should be computed
on the basis of percolation tests made in each vertical stratum
penetrated. Te weighted average of the results should be used
to obtain the design fgure. Soil strata in which percolation rates
are in excess of 30 min/in. should not be included in computing
the absorption area.
Efective Area of Seepage Pit
Te efective area of a seepage pit is the vertical wall area of the
pervious ground below the inlet. Te area of the bottom of the
pit is not considered in calculating the efective area nor is any
impervious vertical areas. Table 8 is a compilation of vertical
surface area for various pit diameters and depths. Te bottom of
the pit must always be at least 4 ft above groundwater table.
When more than one pit is required to obtain the necessary
absorption area, the distance between the walls of adjacent pits
should be equal to three times the diameter of the largest pit.
For pits 20 ft or greater in depth the minimum spacing between
walls should be 20 ft.
Construction of Seepage Pit
All loose material should be removed from the excavated
pit. Te pit should be backflled with clean gravel to a depth
of 1 ft above the pit bottom to provide a sound foundation for
the pit lining. Material for the lining may be clay or concrete
brick, block, or rings. Rings should have weepholes or notches
to provide for seepage. Brick and block should be laid dry with
staggered joints. Brick should be laid fat to form a 4-in. wall.
Te outside diameter of the lining should be 12 in. less than the
diameter of the pit to provide a 6-in. annular space between
the lining and pit wall. Tis annular space should be flled with
clean, coarse gravel to the top of the lining.
Flat concrete covers are recommended. Tey should be sup-
ported by undisturbed earth and extend at least 12 in. beyond
the excavation. Te cover should not bear on the lining for sup-
port. A 9-in. capped opening in the pit cover is convenient for pit
inspection. All concrete surfaces should be coated with a bitu-
mastic paint or similar product to minimize corrosion.
Table 8 Vertical Wall Areas of Seepage Efective Strata Depth Below Flow Line (below inlet)
Diameter of seep-
age pit (feet) 1 foot 2 feet 3 feet 4 feet 5 feet 6 feet 7 feet 8 feet 9 feet 10 feet
3 9.4 19 28 38 47 57 66 75 85 94
4 12.6 26 38 50 63 75 88 101 113 126
5 15.7 31 47 63 79 94 110 126 141 157
6 18.8 38 57 75 94 113 132 151 170 188
7 22.0 44 66 88 110 132 154 176 198 220
8 25.1 50 75 101 126 151 176 201 226 251
9 28.3 57 85 113 141 170 198 226 251 283
10 31.4 63 94 126 157 188 220 251 283 314
11 34.6 69 101 138 173 207 212 276 311 346
12 37.7 75 113 151 188 226 264 302 339 377
Example: A pit of 5-foot diameter and 6-foot depth below the inlet has an efective area of 94 square feet. A pit of 5-foot diameter and
16-foot depth has an area of 94 + 157, or 251 square feet.
Plumbing Systems & Design MAY/JUNE 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Private Sewage Disposal Systems
All connecting piping should be laid on a frm bed of undis-
turbed soil throughout their length and at a minimum grade of
2% ( in./ft). Te pit inlet pipe should extend at least 1 ft into
the pit with a tee or ell to direct the fow downward to prevent
washing and eroding of the sidewalls. When more than one pit
is utilized they should be connected in series.
MAY/JUNE 2007 Plumbing Systems & Design
CONTINUING EDUCATION
About This Issues Article
The May/June 2007 continuing education article is Private
Sewage Disposal Systems, Chapter 13 of Engineered Plumbing
Design II by A. Cal Laws, PE, CPD.
With the ever-increasing cost of land located in proximity to
urban centers, more and more construction is being imple-
mented in outlying areas. Sanitary sewers are not usually avail-
able in these remote locations and it becomes necessary for the
plumbing engineer to design private sewage systems to handle
the wastes from buildings. Where the concentration of popula-
tion is not sufcient to economically justify the installation of
public sewer systems, installation of a septic tank in conjunction
with a subsurface soil absorption feld has proven to be an excep-
tionally satisfactory method of sewage disposal. This chapter
explains the diferent types of private sewage disposal systems
for residential and commercial applications as well as criteria for
their design and construction.
You may locate this article at www.psdmagazine.org. Read the
article, complete the following exam, and submit your answer
sheet to the ASPE office to potentially receive 0.1 CEU.
P
S
D
1
3
9
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
CE QuestionsPrivate Sewage Disposal Systems (PSD 139)
1. The retention period of sewage in a septic tank should
be _________.
a. 12 hours, b. 24 hours, c. 36 hours, d. 48 hours
. The frst step in the design of a subsurface soil
absorption sewage disposal system is _________.
a. ascertain the code requirements
b. determine the area required for the disposal feld
c. determine whether the soil is suitable for the
absorption of the septic efuent
d. calculate the fxture unit load to be served
. The recommended septic tank capacity for a fve-
bedroom home is _________.
a. 750, b. 900, c. 1,000, d. 1,250
. The minimum distance between a cesspool and a water
supply line, as noted in Table , is _________.
a. 100 feet
b. 20 feet
c. 15 feet
d. not recommended as a substitute for a septic tank
. What approximate percentage of new home
construction employs a septic tank/soil absorption
sewage disposal system?
a. 15 percent
b. 20 percent
c. 25 percent
d. 30 percent
. Distribution boxes _________.
a. are required by many codes
b. should be used only when specifcally required by code
c. ofer practically no advantages
d. all of the above
. The absorption area to be provided for an individual
residence containing three bedrooms with a percolation
rate of three minutes is recommended to be _________.
a. 100 square feet
b. 200 square feet
c. 300 square feet
d. 600 square feet
. A covered pit with an open-jointed or perforated lining
into which raw sewage is discharged is called a ________.
a. septic tank
b. cesspool
c. seepage pit
d. none of the above
. The drain lines for distributing the efuent from the
septic tank should be spaced no grater than _________
apart.
a. 3 feet, b. 6 feet, c. 9 feet, d. a and b
10. The quantity of sewage fow from a single-family
dwelling per person is _________ gallons per day.
a. 50
b. 75
c. 100
d. 125
11. The primary purpose of a septic tank is to _________.
a. distribute raw sewage to the leaching feld
b. chemically treat raw sewage
c. vent odors to atmosphere
d. act as a settling tank
1. Sewage pit connecting piping _________.
a. should be laid at a minimum grade of 2 percent
b. must be 6 inches in diameter minimum
c. must be a least 5 feet deep
d. none of the above
Do you fnd it difcult to obtain continuing education units (CEUs)?
Trough this special section in every issue of PS&D, ASPE can help
you accumulate the CEUs required for maintaining your Certifed in
Plumbing Design (CPD) status.
Now Online!
Te technical article you must read to complete the exam is located
at www.psdmagazine.org. Te following exam and application form
also may be downloaded from the website. Reading the article and
completing the form will allow you to apply to ASPE for CEU credit.
For most people, this process will require approximately one hour. If
you earn a grade of 90 percent or higher on the test, you will be notifed
that you have logged 0.1 CEU, which can be applied toward the CPD
renewal requirement or numerous regulatory-agency CE programs.
(Please note that it is your responsibility to determine the acceptance
policy of a particular agency.) CEU information will be kept on fle at
the ASPE ofce for three years.
Note: In determining your answers to the CE questions, use only the material
presented in the corresponding continuing education article. Using information
from other materials may result in a wrong answer.
10 Plumbing Systems & Design MAY/JUNE 2007 PSDMAGAZINE.ORG
P
S
D
1
4
0
Flow in Water
Piping
ContinuingEducationfromPlumbing Systems & Design
KennethG.Wentink,PE,CPD,andRobertD.Jackson
JULY/AUGUST 2007
PSDMAGAZINE.ORG
Hydraulics can be defned as the study of the principles and
laws that govern the behavior of liquids at rest or in motion.
Hydrostatics is the study of liquids at rest and hydrokinetics is
the study of liquids in motion.
Although this text deals exclusively with water, all the data
developed can be applied to any liquid.
Physical ProPerties of Water
Te weight of water, or its density, varies with its temperature
and purity. Water has its greatest specifc weight (weight per
cubic foot) at a temperature of 39.2F. If this phenomenon did
not occur, lakes would start freezing from the bottom up instead
of from the top down. Table 1 tabulates densities of pure water
at various tempera-
tures. For the normal
range of tempera-
tures met in plumb-
ing systems, the den-
sity of water is very
close to 62.4 lbm/ft
3
and this value can be
used for all calcula-
tions without any
signifcant error.
Viscosity can be
defned as the inter-
nal friction, or inter-
nal resistance, to the relative motion of fuid particles. It can also
be defned as the property by which fuids ofer a resistance to a
change of shape under the action of an external force. Viscosity
varies greatly from one liquid to another. It approaches the condi-
tions of a solid for highly viscous liquids and approaches a gas for
the slightly viscous liquids. Viscosity decreases with rising tem-
peratures. For example, #6 oil is a solid at low temperatures and
begins to fow as it is heated.
Water is perfectly elastic, compressing when pressure is
imposed and returning to its original condition when the pres-
sure is removed. Te compressibility of water may be expressed
as 1/K, where K is the coefcient of compressibility and is equal
to 43,200,000 lb/ft2. It can be seen that if a pressure of 100 lb/ft2
were applied, the volumetric change would be 10043,200,000.
Te change is of such negligible signifcance that water is always
treated as incompressible for all calculations in plumbing
design.
Te temperature at which water boils varies with the pressure
to which it is subjected. At sea level14.7 psiwater boils at
212F. At an elevation above sea level, where the atmospheric
pressure is less than 14.7 psi, water will boil at a lower tem-
perature. In a closed system, such as that found in the domestic
hot water system where the pressure is generally around 50 psi
above atmospheric pressure, the water will not boil until a tem-
perature of 300F is reached.
tyPes of floW
When water is moving in a pipe, two types of fow can exist. One
type is known by the various names of streamline, laminar, or
viscous. Te second is called turbulent fow. At various viscosi-
ties (various temperatures), there is a certain critical velocity for
every pipe size above which turbulent fow occurs and below
which laminar fow occurs. Tis critical velocity occurs within
a range of Reynolds numbers from approximately 2100 to 4000.
Reynolds formula is:
Equation 1
R
e
=
DV
g
c
where
R
e
= Reynolds number, dimensionless
D = Pipe diameter, ft
V = Velocity of fow, ft/sec
= Density, lbm/ft
3
= Absolute viscosity, lbf sec/ft
2
gc = Gravitational constant, 32.2 lbmft/lbfsec2
Within the limits of accuracy required for plumbing design,
it can be assumed that the critical velocity occurs at a Reynolds
number of 2100. In laminar fow, the roughness of the pipe wall
has a negligible efect on the fow but the viscosity has a very
signifcant efect. In turbulent fow, the viscosity has an insignif-
icant efect but the roughness of the pipe wall has a very marked
efect on the fow.
Very rarely is a velocity of less than 4 ft/sec employed in
plumbing design. Te Reynolds number for a 3 in. pipe and a
velocity of fow of 4 ft/sec would be
R
e
=
(0.250ft)(4ft/sec)(62.4lbm/ft
3
)
= 82,500
(2.35 10
5
lbfsec/ft
2
)(32.2 lbmft/lbfsec
2
(which is well above the critical number of 2,100)
It can be seen that all plumbing design is with turbulent fow
and only when very viscous liquids or extremely low velocities
are encountered does the plumbing engineer deal with laminar
fow. Critical velocities of , 1, and 2-in. pipe at 60F are 0.61,
0.31, and 0.15 ft/sec, respectively, and at 140F they are 0.25,
0.13, and 0.06 ft/sec, respectively.
Velocity of floW
When the velocity of fow is measured across the section of pipe
from the center to the wall, it is found that there is a variation in
the velocity, with the greatest velocity at the center and a mini-
mum velocity at the walls. Te average velocity for the entire
cross-section is approximately 84% of the velocity as measured
at the center. Te plumbing engineer is concerned only with
the average velocity, and all formulas are expressed in average
velocity. Whenever and wherever the term velocity is used, it is
the average velocity of fow that is meant.
Since water is incompressible within the range of pressures
met in plumbing design, a defnite relationship can be expressed
between the quantity fowing past a given point in a given time
Flow in Water Piping
Reprinted from Engineered Plumbing Design II, Chapter 11: Flow in Water Piping, by A. Calvin Laws, PE, CPD.
American Society of Plumbing Engineers.
Table 1 Density of Pure Water at Various
Temperatures
Temperature
F
Density
lbm/ft
3
Temperature
F
Density
lbm/ft
3
32 62.416 100 61.988
35 62.421 120 61.719
39.2 62.424 140 61.386
40 62.423 160 61.006
50 62.408 180 60.586
60 62.366 200 60.135
70 62.300 212 59.843
80 62.217
Plumbing Systems & Design JULY/AUGUST 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION
and the velocity of fow. Tis can be expressed as (Equation 3-
2):
Q = AV
where
Q = quantity of fow (volumetric fow rate), ft
3
/sec
A = cross-sectional area of fow, ft
2
V = velocity of fow, ft/sec
Te units employed in this fow formula are inconvenient for
use in plumbing design. Te plumbing engineer deals in gallons
per minute and inches for pipe sizes. Converting to these terms,
the fow rate becomes (Equation 8-8):
q = 2.448 d
2
V
where
q = quantity of fow (fow rate), gpm
d = diameter of pipe, in.
V = velocity of fow, ft/sec
Potential energy
One of the most fundamental laws of thermodynamics is that
energy can be neither created nor destroyed; it can only be con-
verted from one form to another. Te energy of a body due to
its elevation above a given level is called its potential energy in
relation to that datum. Work had to be performed to raise the
body to that elevation and this work is equal to the product of
the weight of the body and the height it was raised. Tis can be
expressed as:
Equation 2
E
P
= w h =
mgh
g
c
where
E
P
= potential energy, ft lbf
w = weight of the body, lbf
h = height raised, ft
g = gravitational acceleration, 32.2 ft/s
2
g
c
= gravitational constant, 32.2 lbmft/
lbfs
2
When the weight is equal to 1 lb the for-
mula becomes
Equation 3
E
P
=
hg
g
c
where
EP = potential energy per pound weight
Kinetic energy
Te energy of a body due to its motion is
called kinetic energy and is equal to one-half
its mass and the square of its velocity. Mass
is equal to the weight of the body divided by
its acceleration imposed by gravity.
Equation 4
m =
wg
c
g
c
Equation 5
E
K
=
wg
c
V
2
=
w
V
2
g
c
g
c 2g
where
E
K
= kinetic energy, ft lbf
w = weight of body, lbf
m = mass of the body, lbm
g = gravitational acceleration, 32.2 ft/sec
2
g
c
= gravitational constant, 32.2 lbmft/lbfsec
2
V = velocity, ft/sec
When the body weighs 1 lb the formula becomes
Equation 6
E
K
=
V
2
2g
c
where
E
K
= kinetic energy per pound weight
static head
At any point below the surface of water that is exposed to atmo-
spheric pressure, the pressure (head) is produced by the weight
of the water above that point. Te pressure is equal and efective
in all directions at this point and is proportional to the depth
below the surface. Tis pressure is variously called static head,
static pressure, hydrostatic head, or hydrostatic pressure. It is the
measure of the potential energy. Because pressure is a function
of the weight of the water, it is possible to convert the static head
expressed as feet of head into pounds per square inch. (See
Table 2.)
Te pressure developed by the weight of a column of water 1
in.
2
in cross-sectional area and h ft high may be expressed as
Equation 7
p =
h
144
where
p = pressure, lbf/in
2
=specifcweightofwater,lbf/ft
3
h = static head, ft
At 50F, the pressure expressed in pounds per square inch for
a 1-ft column of water is then:
Table 2 Heads of Water in Feet Corresponding to Pressure in Pounds per Square Inch
PSI 0 1 2 3 4 5 6 7 8 9
0 2.3 4.6 6.9 9.2 11.6 13.9 16.2 18.5 20.8
10 23.1 25.4 27.7 30.0 32.3 34.7 37.0 39.3 41 .6 43.9
20 46.2 48.5 50.8 53.1 55.4 57.8 60.1 62.4 64.7 67.0
30 69.3 71.6 73.9 76.2 78.5 80.9 83.2 85.5 87.8 90.1
40 92.4 94.7 97.0 99.3 101.6 104.0 106.3 108.6 110.9 113.2
50 115.5 117.8 120.1 122.4 124.7 127.1 129.4 131.7 134.0 136.3
60 138.6 140.9 143.2 145.5 147.8 150.2 152.5 154.8 157.1 159.4
70 161.7 164.0 166.3 168.6 170.9 173.3 175.6 177.9 180.2 182.5
80 184.8 187.1 189.4 191.7 194.0 196.4 198.7 201.0 203.3 205.6
90 207.9 210.2 212.5 214.8 217.1 219.5 221.8 224.1 226.4 228.7
100 231.0 233.3 235.6 237.9 240.2 242.6 244.9 247.2 249.5 251.8
110 254.1 256.4 258.7 261.0 263.3 265.7 268.0 270.3 272.6 274.9
120 277.2 279.5 281.8 284.1 286.4 288.8 291.1 293.4 295.7 298.0
130 300.3 302.6 304.9 307.2 309.5 311.9 314.2 316.5 318.8 321.1
140 323.4 325.7 328.0 330.3 332.6 335.0 337.3 339.6 341.9 344.2
150 346.5 348.8 351.1 353.4 355.7 358.1 360.4 362.7 365.0 367.3
160 369.6 371.9 374.2 376.5 378.8 381.2 383.5 385.8 388.1 390.4
170 392.7 395.0 397.3 399.6 401.9 404.3 406.6 408.9 411.2 413.5
180 415.8 418.1 420.4 422.7 425.0 427.4 429.7 432.0 434.3 436.6
190 438.9 441.2 443.5 445.8 448.1 450.5 452.8 455.1 457.4 459.7
200 462.0 464.3 466.6 468.9 471.2 473.6 475.9 478.2 480.5 482.8
210 485.1 487.4 489.7 492.0 494.3 496.7 499.0 501.3 503.6 505.9
220 508.2 510.5 512.8 515.1 517.4 519.8 522.1 524.4 526.7 529.0
230 531.3 533.6 535.9 538.2 540.5 542.9 545.2 547.5 549.8 552.1
240 554.4 556.7 559.0 561.3 563.6 566.0 568.3 570.6 572.9 575.2
250 577.5 579.8 582.1 584.4 586.7 589.1 591.4 593.7 596.0 598.3
Notes: 1. To use the chart, fnd the point corresponding to the specifc pressure (psi) by adding incremental values in the top line to the base values in the extreme
left column. For example, to fnd head in ft. corresponding to 25 psi, follow the line of fgures to the right of 20 psi and read 57.8 ft under 5 psi. 2. Head values in
the body of the chart were calculated by multiplying psi by 2.31. To convert ft of head to psi, multiply by 0.433, or use the chart in reverse.
JULY/AUGUST 2007 Plumbing Systems & Design
p =
62.408
1 = 0.433 lbf/in
2
144
Conversely, the height of a column of water that will impose a
pressure of 1 lb/in.
2
is
h = p
144
h = 1
144
= 2.31 ft
62.408
To convert from feet of head to pounds per square inch, mul-
tiply the height by 0.433. To convert pounds per square inch to
feet of head, multiply the pounds per square inch by 2.31.
Velocity head
In a piping system with the water at rest, the water has poten-
tial energy. When the water is fowing it has kinetic energy as
well as potential energy. To cause the water to fow some of the
available potential energy must be converted to kinetic energy.
Te decrease in the potential energy, or static head, is called the
velocity head.
In a freely falling body, the body is accelerated by the action
of gravity at a rate of 32.2 ft/sec
2
. Te height of the fall and the
velocity at any moment may be expressed as:
Equation 8
h =
gt
2
2
Equation 9
V = gt
or t =
V
g
where
h = velocity head, ft
t = time, sec
g = gravitational acceleration, 32.2 ft/sec
2
V = velocity, ft/sec
Substituting t = V/g in the frst equation,
h =
g
V
2
2
g
2
Equation 10
h =
V
2
2g
Te foregoing illustrates the conversion of the
potential energy of a body (static head) due to its
height into kinetic energy (velocity head). Te
velocity head, V
2
/2g, is a measure of the decrease in
static head expressed in feet of column of water.
Bernoullis theorem
As previously stated, energy can be neither created
nor destroyed. Bernoulli developed an equation to
express this conservation of energy as it is applied
to a fowing liquid. Te liquid is assumed to be fric-
tionless and incompressible.
Equation 11
Zg
+
Pg
c
+
V
2
= E
T
g
c
g 2g
c
where
E
T
= total energy ftlbf/lbm
Z = height of point above datum, ft
P = pressure, lbf/ ft
2
= density, lbm/ft3
V = velocity, ft/sec
g = gravitational acceleration, 32.2 ft./sec
2
g
c
= gravitational constant, 32.2 lbmft/lbfsec
2
Te term Pg
c
/g is equal to the static head or height of the
liquid column. Substituting in the equation it becomes
Equation 12
Zg
+ h +
V
2
= E
T
g
c 2g
c
For any two points in a system, we may then write:
Equation 13
Z
1
g
+ h
1
+
V
1
2
=
Z
2
g
+ h
2
+
V
2
2
g
c 2g
c
g
c 2g
c
Figure 1 illustrates the application of this equation.
friction
When water fows in a pipe, friction is produced by the rubbing
of water particles against each other and against the walls of
the pipe. Tis friction generates heat, which is dissipated in the
form of a rise in the temperature of the water and the piping.
Tis temperature rise in plumbing systems is insignifcant and
can safely be ignored in plumbing design. It requires a potential
energy of 778 ft-lbf to raise 1 lb of water 1F. Te friction pro-
duced by fowing water also causes a pressure loss along the
line of fow, which is called friction head. By utilizing Bernoullis
equation this friction head loss can be expressed as:
Figure 11-1 Bernoulli's Theorem (Disregarding Friction)
Z
1
g
+ h
1
+
V
1
2
=
Z
2
g
+ h
2
+
V
2
2
g
c 2g
c
g
c 2g
c
Plumbing Systems & Design JULY/AUGUST 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Flow in Water Piping
h
F
=
[
Z
1
g
+ h
1
+
V
1
2
]
-
[
Z
2
g
+ h
2
+
V
2
2
] g
c 2g
c
g
c 2g
c
floW from outlets
Experiments to determine the velocity of fow from an
outlet in the side of an open tank were performed by
Toricelli in the 17th century. Te result of these experi-
ments was expounded in the theorem: Except for minor
frictional efects, the velocity is the same as if the fuid
had fallen freely from the surface through a vertical dis-
tance to the outlet. Tis can be expressed as:
Equation 15
V = 2gh
It is graphically shown in Figure 2.
If friction, size, and shape of the opening and entrance
losses are disregarded, the ideal velocity is the same as the
maximum velocity and is equal to the velocity attained
by free fall. Te actual velocity, however, is always less
than the ideal. All the factors, previously ignored, when
taken into consideration can be expressed as the coef-
fcient of discharge, C
D
. Te actual velocity can then be
written:
Equation 16
V = C
D
2gh
For most outlets encountered in a plumbing system
an average coefcient of discharge of 0.67 can be safely
applied.
floW in PiPing
Te velocity of fow at any point in a system is due to the
total energy at that point. Tis is the sum of the potential
and kinetic energy, less the friction head loss. Te static
head is the potential energy, but some of it was con-
verted to kinetic energy to cause fow and some of it was
used to overcome friction. It is for these reasons that the
pressure during fow is always less than the static pressure. Te
pressure measured at any point while water is fowing is called
the fow pressure. Tis is the pressure that is read on a pressure
gauge installed in the piping.
Te kinetic energy of water fowing in a plumbing system is
extremely small. Very rarely is the design velocity for water fow
in plumbing systems greater than 8 ft/sec. Te kinetic energy
(velocity head) at this velocity is V
2
/2g or
8
2
64.4. Tis is equal to
1 ft or 0.433 psi, which is less than 0.5 psi. It can be seen that
such an insignifcant pressure can be safely ignored in all calcu-
lations. Te maximum rate of discharge from an outlet can now
be determined from the fow pressure and the diameter of the
outlet (using Equations 8-2 to 8-5):
q
D
= C
D
q
1
q
D
= C
D
2.448 d
2
V
1
q
D
= C
D
2.448d
2
2gh
q
D
= C
D
19.65d
2
h or
Equation 17
q
D
= C
D
29.87d
2
p
where
q
D
= actual quantity of discharge, gpm
q
1
= ideal quantity of discharge, gpm
C
D
= coefcient of discharge, dimensionless
d = diameter of outlet, in.
V
1
= ideal velocity, ft/sec
h = fow pressure, ft
p = fow pressure, psi
If 0.67 is used for the coefcient of discharge, then, per Equa-
tion 6-1,
q
D
= 13.17d
2
h
and
Equation 18
q
D
= 20d
2
p
friction in PiPing
As stated previously, whenever fow occurs, there is a continu-
ous loss of pressure along the piping in the direction of fow. Te
amount of this head loss because of friction is afected by
1. Density and temperature of the fuid
2. Roughness of the pipe
3. Length of run
4. Velocity of the fuid
Experiments have demonstrated that the friction head loss is
inversely proportional to the diameter of the pipe, proportional
to the roughness and length of the pipe, and varies approxi-
Figure 11-2 Toricelli's Theorem
JULY/AUGUST 2007 Plumbing Systems & Design
mately with the square of the velocity. Darcy expressed this rela-
tionship as:
h =
fLV
2
or
D 2g
Equation 19
p =
fLV
2
144D 2g
c
where
h = friction head loss, ft
p = friction head loss, lbf/in
2
= density of fuid, lbm/ft3
f = coefcient of friction, dimensionless
L = length of pipe, ft
D = diameter of pipe, ft
V = velocity of fow, ft/sec
g
c
= gravitational constant, 32.2 lbm ft/lbf sec
2
Values for the coefcient of friction are given in Table 3.
It can be seen from Table 3 that steel pipe is much rougher
than brass, lead or copper. It follows that there will be a greater
head loss in steel pipe than in the other material.
For ease of application for the plumbing engineer, the for-
mula for friction head loss can be reduced to a simpler form.
Assuming an average value for the coefcient of friction of 0.02
for brass and copper and 0.04 for steel, the formula becomes:
For brass and copper
Equation 20
h = 0.000623q
2
L
d
5
Equation 21
p = 0.00027q
2
L
d
5
and for steel
Equation 22
h = 0.00124q
2
L
d
5
Equation 23
p = 0.00539q
2
L
d
5
Tese formulas can be rearranged in another
useful form:
For brass and copper
Equation 24
q = 40.1 d
2
(
h
)
L
Equation 25
q = 60.8 d
2
(
p
)
L
and for steel
Equation 26
q = 28.3 d
2
(
h
)
L
Equation 27
q = 43.0 d
2
(
p
)
L
where
q = quantity of fow, gpm
d = diameter of pipe, in.
h = pressure, ft
p = pressure, psi
L = length of pipe, ft
Te terms h/L and p/L represent the loss of head due to fric-
tion for 1 ft of pipe length and is called the uniform friction loss.
Values of d
2
for various diameters of pipe and various materials
are given in Table 4.
In all water fow formulas, the term L (length of run in feet)
is always the equivalent length of run (ELR).Every ftting and
valve imposes more frictional resistance than the pipe itself.To
take this additional friction head loss into account, the ftting or
valve is converted to an equivalent length of pipe of the same
size that will impose an equal friction loss, e.g., a 4-in. elbow
is equivalent to 10 ft of 4-in. pipe.Tus, if the measured length
of run of 4-in. piping with one elbow is 15 ft, then the equiva-
lent length of run is 15 + 10 = 25 ft.Te length of pipe measured
Table 4 Values of d
2
Nominal
Size, In.
Brass or
Copper Pipe
Copper
Type K
Copper
Type L
Galvanized
Iron or Steel
0.31 0.20 0.22 0.31
0.61 0.48 0.55 0.62
1 1.16 0.99 1.06 1.13
1 2.19 1.73 1.80 2.24
1 3.24 2.67 2.78 3.29
2 6.17 5.37 5.55 6.14
2 9.88 9.25 9.54 9.58
3 16.41 14.41 14.87 16.48
4 32.00 29.23 30.13 32.53
Table 5 Equivalent Pipe Length for Valves and Fittings
Nominal
Pipe Size
inches
Gate
Valve
Full
Open
Angle
Valve Full
Open
Globe
Valve Full
Open
Swing
Check Full
Open
45
Elbow
Long
Sweep
Elbow or
Run of Tee
Std.
Elbow
Std. Tee
Thru
Side
Outlet
0.35 9.3 18.6 4.3 0.78 1.11 1.7 3.3
0.44 11.5 23.1 5.3 0.97 1.4 2.1 4.2
1 0.56 14.7 29.4 6.8 1.23 1.8 2.6 5.3
1 0.74 19.3 38.6 8.9 1.6 2.3 3.5 7.0
1 0.86 22.6 45.2 10.4 1.9 2.7 4.1 8.1
2 1.10 29.0 58.0 13.4 2.4 3.5 5.2 10.4
2 1.32 35.0 69.0 15.9 2.9 4.2 6.2 12.4
3 1.60 43.0 86.0 19.8 3.6 5.2 7.7 15.5
4 2.10 57.0 113.0 26.0 4.7 6.8 10.2 20.3
5 2.70 71.0 142.0 33.0 5.9 8.5 12.7 25.4
6 3.20 85.0 170.0 39.0 7.1 10.2 15.3 31.0
8 4.30 112.0 224.0 52.0 9.4 13.4 20.2 40.0
Table 3 Average Values for Coefcient of Friction, f
Nominal
Pipe Size, in.
Brass, Copper,
or Lead
Galvanized
Iron or Steel
0.022 0.044
0.021 0.040
1 0.020 0.038
1 0.020 0.036
1 0.019 0.035
2 0.018 0.033
2 0.017 0.031
3 0.017 0.031
4 0.016 0.030
Plumbing Systems & Design JULY/AUGUST 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Flow in Water Piping
along the centerline of pipe and fttings is the developed length.
Table 5 shows equivalent lengths of pipe for valves and fttings
of various sizes. Note that the larger the pipe size, the more
signifcant the equivalent length of run becomes. In the design
phase of piping systems, the size of the piping is not known and
the equivalent lengths cannot be accurately determined. A rule
of thumb that has worked exceptionally well is to assume 50%
of the developed length as an allowance for fttings and valves.
Once the sizes are determined, the accuracy of the assumption
can be checked.
All equipment imposes a friction head loss and must be care-
fully considered in the design and operation of a system. Te
pressure drop through any piece of equipment can be obtained
from the manufacturer. Te knowledgeable engineer is care-
ful to specify the maximum pressure drop he/she will permit
through a piece of equipment.
JULY/AUGUST 2007 Plumbing Systems & Design
CONTINUING EDUCATION
AboutThisIssuesArticle
TheJuly/August2007continuingeducationarticleisFlow
inWaterPiping,Chapter11ofEngineered Plumbing Design II
byA.CalLaws,PE,CPD.
Thischapterdiscusseshydraulics,whichcanbedefnedas
thestudyoftheprinciplesandlawsthatgovernthebehav-
iorofliquidsatrestorinmotion,hydrostatics,thestudy
ofliquidsatrest,andhydrokinetics,orthestudyofliquids
inmotion.Althoughthistextdealsexclusivelywithwater,
allthedatadevelopedcanbeappliedtoanyliquid.The
chapterdelvesintothephysicalpropertiesofwater,types
offow,BernoullisandToricellisTheorems,andfrictionin
pipingastheyrelatetosizingpipingsystems.Itprovides
calculationsforfndingtheReynoldsnumber,velocityof
fow,potentialandkineticenergy,pressure,velocityhead,
andBernoullisTheorem,amongothers.
Youmaylocatethisarticleatwww.psdmagazine.org.Read
thearticle,completethefollowingexam,andsubmityour
answersheettotheASPEofficetopotentiallyreceive0.1CEU.
P
S
D
1
4
0
ContinuingEducationfromPlumbing Systems & Design
KennethG.Wentink,PE,CPD,andRobertD.Jackson
CEQuestionsFlowinWaterPiping(PSD140)
1. The average coefcient of friction (f) in a -inch steel
pipe is _________.
a. 0.037
b. 0.035
c. 0.033
d. 0.031
. Friction is created by the fow of water in piping. This
friction generates _________.
a. pressuredrop
b. pressureincrease
c. heat
d. noneoftheabove
. Number six () oil _________.
a. isnotpartofthischapter
b. isasolidatlowtemperatures
c. beginstofowwhenheated
d. bandconly
. Water is _________.
a. notcompressible
b. perfectlyelastic
c. greatlycompressible
d. noneoftheabove
. Experiments to determine the velocity of fow from an
outlet were performed by _________ in the 1th century.
a. Bernoulli
b. Reynolds
c. Toricelli
d. Hunter
. Velocity head (V
/g) _________.
a. isameasureofthedecreaseinstatichead
b. isofnoconsequencetotheplumbingengineer
c. mustbeunderstoodtocontrolwaterhammer
d. isresponsibleformostpipefttingfailures
. How much potential energy is required to raise 1 pound
of water 1F?
a. 728ft-lbf,b. 778ft-lbf,c. 828ft-lbf,d. 878ft-lbf
8. The pressure at any point below the surface of water
exposed to atmospheric pressure is referred to as ______.
a. statichead
b. hydrostaticpressure
c. specifcpressure
d. aorb
9. What is the equivalent pipe length for a -inch fully
open globe valve?
a. 113.0
b. 142.0
c. 170.0
d. 224.0
10. The critical velocity of water _________.
a. in-inch,1-inch,and2-inchpipeislessthan0.5fpsat
temperaturesof60Fto140F
b. isrepresentedbyaReynoldsnumberof82,500
c. isR
e
=DVp/ug
c
d. isgreaterthan20ft/secforallpipe10inchesand
smallerattemperaturesof60Fto140F
11. The static pressure is always _________ the pressure
during fow.
a. lessthan
b. greaterthan
c. thesameas
d. noneoftheabove
1. Water in motion _________.
a. hasuseditspotentialenergy
b. hasonlykineticenergy
c. hasbothkineticandpotentialenergy
d. noneoftheabove
Do you fnd it difcult to obtain continuing education units (CEUs)?
Trough this special section in every issue of PS&D, ASPE can help
you accumulate the CEUs required for maintaining your Certifed in
Plumbing Design (CPD) status.
NowOnline!
Te technical article you must read to complete the exam is located
at www.psdmagazine.org. Te following exam and application form
also may be downloaded from the website. Reading the article and
completing the form will allow you to apply to ASPE for CEU credit.
For most people, this process will require approximately one hour. If
you earn a grade of 90 percent or higher on the test, you will be notifed
that you have logged 0.1 CEU, which can be applied toward the CPD
renewal requirement or numerous regulatory-agency CE programs.
(Please note that it is your responsibility to determine the acceptance
policy of a particular agency.) CEU information will be kept on fle at
the ASPE ofce for three years.
Note: In determining your answers to the CE questions, use only the material
presented in the corresponding continuing education article. Using information
from other materials may result in a wrong answer.
8 Plumbing Systems & Design JULY/AUGUST 2007 PSDMAGAZINE.ORG
P
S
D
1
4
1
Irrigation
Systems
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
SEPTEMBER 2007
PSDMAGAZINE.ORG
IntroductIon
Te function of an automatic irrigation
system is to provide and distribute a pre-
determined amount of water to economi-
cally produce and maintain ornamental
shrubs, cultivated lawns, and other large
turf areas. Other benefts of an automatic
irrigation system include convenience,
full landscape coverage, easy control for
overnight and early morning watering,
and minimized plant loss during drought.
Tis chapter discusses the basic design
criteria and components of irrigation
systems for ornamental lawns and turf.
Among the factors considered are water
quality and requirements, soil consid-
erations, system concepts, and system
components. A design information sheet
is also provided, as Appendix A, to assist
the plumbing engineer in the orderly col-
lection of the required feld information
and other pertinent data.
Water QualIty and
reQuIrements
In urban areas, where the source of the
water supply is often the municipal water
system, the plumbing engineer does not
need to be concerned with the qual-
ity of the water. In cases where private
sources are used and the water quality is
unknown, the water should be analyzed
by the appropriate local health authority
having jurisdiction prior to use. Te three
main areas of concern are as follows:
1. Any silt content that, if high, may
result in the baking and sealing of
soils
2. Any industrial waste that may be
harmful to good growth
3. Any soluble salts that may build up
in the root area
Te most common solution currently
available for handling excessive amounts
of silt is the construction of a settling
basin, usually in the form of a decorative
lake or pond. In those areas where the salt
content is excessive, 1,000 parts per mil-
lion (ppm) and above, the inability of the
soil to cope with the problem may require
the use of special highly salt-tolerant
grasses.
Te quantity of water required for an
efective irrigation system is a function
of the type of grass, the soil, and local
weather conditions. Te quantity of water
is usually expressed as the depth of the
water applied during a given period over
the area to be covered. Te amount of
water applied to a given area can be con-
trolled easily by adjusting the irrigation
systems length and frequency of opera-
Irrigation Systems
Reprinted from ASPE Data Book Volume 3: Special Plumbing Systems, Chapter 4: Irrigation Systems.
American Society of Plumbing Engineers.
Table 1 Net Amount of Water to Apply per Irrigation
Cycle
Soil Profle Amount, in. (mm)
Coarse, sandy soils 0.45 (11.43)
Fine, sandy loams 0.85 (21.59)
Silt loams 1.10 (27.94)
Heavy clay or clay loams 0.90 (22.86)
Note: Net amount of moisture required based on 12 in. (304.8 mm) root depth.
Figure 1 Examples of a Block System
2 Plumbing Systems & Design SEPTEMBER 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION
tion. An efcient irrigation system takes
into consideration the rate of the appli-
cation of the water, usually expressed in
inches per hour, and the attempt to match
the application rate with the absorption
rate of the soil. Often, this condition is
achieved through frequent short water-
ing cycles.
soIl consIderatIons
Sandy, porous soils have relatively high
absorption rates and can handle the high
output of the sprinklers. Steep slopes
and very tight, nonporous soils require
low precipitation rates to avoid erosion
damage and wasteful runof.
A sufcient amount of water must be
applied during each irrigation period to
ensure penetration to the root zone. Table
1 suggests guidelines for several soil pro-
fles (net amount of water to apply per
irrigation cycle). In the absence of any
specifc information on the soil and local
weather conditions, the irrigation system
may be designed for 1 inches (38.1 mil-
limeters) of water per week. Te plumb-
ing engineer should consult with the local
administrative authority to determine
compliance with the applicable codes in
the jurisdiction. Te engineer can obtain
specifc information on the soil and local
weather conditions by contacting a local
weather bureau, university, or state engi-
neer.
system concepts
Te three basic system concepts that can
be used by the engineer in the design
of an irrigation network are the block
method, the quick-coupling method, and
the valve-per-sprinkler method.
Te block system is an approach in
which a single valve controls the fow of
water to several sprinklers. It is ideal for
residential and other small turf areas.
Either manual or automatic valves may
be used in the block system. As the irriga-
tion area increases or where high-volume
sprinklers are employed, the block system
becomes less attractive to the engineer
because of the large valves and pipelines
required. Examples of the block system
are shown in Figure 1.
Te quick-coupling irrigation system
is an answer to the high cost incurred on
large block system projects. Development
of the quick-coupling valve provided a
more fexible irrigation system. Te valve
is located underground but can be acti-
vated from the surface. Where manpower
is not critical and security is reasonable,
the quick-coupling irrigation system may
be considered by the engineer. An exam-
ple of a quick-coupling valve is illustrated
in Figure 2.
Te last concept in
sprinkler system design
is the valve-per-sprinkler
method. Small actuator
valves, operated at low volt-
age, provide great fexibil-
ity and control. Sprinklers
in diverse areas having the
same (or similar) water
requirements may be
operated concurrently. In
other applications, such as
quarter applications cov-
ering quarter circles or half
circles, the irrigation sprin-
klers may be piped, wired,
and operated together
through system program-
mers. Te valve-per-sprin-
kler system provides the
opportunity to standardize
the pipe sizes by selecting
the appropriate sprinklers
to be operated at any given time. Figure 3
illustrates this design.
system components
sprInklers
One of the most important considerations
for the plumbing engineer when design-
ing an irrigation system is the selection of
the sprinklers. Sprinklers are mechanical
devices with nozzles used to distribute
water by converting water pressure to a
high-velocity discharge stream. Many
diferent types of sprinklers are manufac-
tured for a variety of system applications.
Te plumbing engineer should become
knowledgeable of the various types before
selecting the sprinklers, as the fow rates
and operating pressures must be nearly
the same in each of the irrigation systems
circuits.
Spray Sprinklers Surface-type spray
and pop-up spray sprinklers (see Figure
4) produce a single sheet of water and
cover a relatively small area, about 10 to 20
feet (3.05 to 6.10 meters) in radius. Tese
sprinklers can operate on a low-pressure
range of 15 to 35 pounds per square inch
(psi) (103.4 to 241.3 kPa). Tey apply the
water at a high rate of application1 to
2 inches/hour (25.4 to 50.8 mm/hour)
and are most economical in small turf
or shrub areas and in irregularly shaped
areas.
Due to the fne spray design, the pattern
can be easily distorted by the wind; there-
Figure 2 Quick-Coupling Valve
Figure 3 Valve-in-Head System
SEPTEMBER 2007 Plumbing Systems & Design 3
fore, these sprinklers should be installed
in protected areas.
Impact Sprinklers Impact sprinklers
(see Figure 5) can be permanent or mov-
able and either the riser-mounted type
(see Figure 2) or the pop-up rotary type
(see Figure 6).
Impact sprinklers have an adjustable,
revolving water stream and are available
in both single-nozzle and
double-nozzle designs.
Tese devices can oper-
ate at a higher pressure
(25 to 100 psi [172.3 to
689.5 kPa]) and cover
larger areas (40 to 100
feet [12.2 to 30.5 meters]
in radius). Te water is
applied at a lower rate
(0.20 to 0.5 inches/hour
[5.08 to 12.7 mm/hour]).
Because of its larger,
more compact stream
of water, this sprinkler
is not easily distorted
by the wind and is most
economical in large,
open turf areas.
Freestanding sprin-
klers are not desirable
where they are exposed.
In such cases, the pop-up,
rotary-type sprinklers
shown in Figure 6 may be
used. Tese nozzles rise
above the ground level
only when the water is
being delivered to the
unit.
Half-circle, rotary
sprinklers can discharge
the same volume of
water as full-circle units.
A half-circle, rotary
sprinkler can provide the
same amount of water
as a full-circle unit over
half the area, doubling
the application rate.
Quarter-circle sprinklers
will quadruple the appli-
cation rate. Some equip-
ment manufacturers use
diferent nozzles to com-
pensate for the reduced
area and to provide a
uniform application rate.
If compensating nozzles
are not used in half-
circle sprinklers, these
units must be valved and
operated separately for a balanced appli-
cation of the water.
Shrub Sprinklers Several types of
shrub sprinklers are available, including
bubblers (see Figure 7), fat-spray sprin-
klers, and stream-spray sprinklers. Shrub
sprinklers can be mounted on risers to
spray over plants. If the plants are tall
and not dense near the ground, shrub
sprinklers can be used on short risers,
and the spray can be directed under the
plants. Te spray can also be kept below
the plant. Flat-spray shrub heads are best
employed for these applications.
Trickle Irrigation Trickle irrigation
is commonly used in vineyards and
orchards and routed through tubing with
special emitters installed at each planting.
Most emitters have fexible orifces and
may have provisions for adding fertilizer.
Tese irrigation systems have a low-vol-
ume usage and usually are not installed
in conjunction with conventional lawn
sprinkler systems.
ValVes
Remote-control valves are generally clas-
sifed into three basic categories: electric,
hydraulic, and thermal-hydraulic. Te
electrically operated valve receives an
electric signal from the controller and
actuates a solenoid in the valve. Tis sole-
noid opens and closes the control valve.
Te hydraulic control valve is operated
with the water pressure and has control
tubing from the controller to the valve.
Te thermal-hydraulic control valve uses
an electric signal from the controller to
heat up the components of the valve to
open the unit. Te most common use of
this valve is to control the water usage to
the diferent zones.
Tese devices should be installed with
access for maintenance. Most control
valves have some provisions for manual
operation. In some systems, manual con-
trol valves are installed in pits or vaults
Figure 4 Pop-Up Spray Heads
P
h
o
t
o
c
o
u
r
t
e
s
y
o
f
R
a
i
n
B
i
r
d
C
o
r
p
o
r
a
t
i
o
n
Figure 5 Impact Sprinkler
P
h
o
t
o
c
o
u
r
t
e
s
y
o
f
R
a
i
n
B
i
r
d
C
o
r
p
o
r
a
t
i
o
n
Figure 6 Rotor SprinklerArcs and Full Circles
P
h
o
t
o
c
o
u
r
t
e
s
y
o
f
R
a
i
n
B
i
r
d
C
o
r
p
o
r
a
t
i
o
n
4 Plumbing Systems & Design SEPTEMBER 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Irrigation Systems
with a long T-handle wrench used for the
activation of each circuit.
An irrigation system may be installed
with an automatic check valve on the
sprinkler heads. When a zone is installed
on sloping terrain, these valves will close
when they sense a low pressure at turn-
of, preventing the drainage of the supply
pipe through a sprinkler head installed in
a lower area.
Atmospheric vacuum breakers (see
Figure 8) must be installed on every
sprinkler circuit downstream of the con-
trol valve to eliminate the possibility of
back-siphonage into the potable water
system. Many (if not all) local jurisdic-
tions have codes that require this type
of valve. Te plumbing designer should
consult with the local administrative
authority and check all applicable codes
for their requirements.
Pressure-reducing valves are installed
where higher street pressures are involved
and also are commonly used to maintain
a constant pressure where the inlet pres-
sures may vary. Some manufacturers
ofer remote-control valves with pressure
regulation.
Low-fow control valves may be
installed to avoid damage to the piping
or tubing from pressure surges during the
flling of a (dry) system. Tis control valve
allows a slow flling of the piping or tubing
until the pressure is established.
In climates where freezing conditions
may occur, automatic-type drain valves
should be installed at the low points of
the system to allow for drainage of the
system. Tis control valve will open auto-
matically when the water pressure drops
below a set point. In heavy or dense soils,
a pit of gravel should be provided for
quick drainage.
BackfloW deVIces
An irrigation system may be installed with
an automatic check valve on the sprin-
klers. When a zone is installed on sloping
terrain, these valves will close when they
sense a low pressure at turnof, prevent-
ing drainage of the supply pipe through a
sprinkler head installed in a low area.
Te use of pressure vacuum break-
ers to eliminate the possibility of back-
siphonage into the potable water system
is the minimum level of backfow pre-
vention accepted by most jurisdictions.
Te plumbing engineer should consult
with the local administrative authority
and check all applicable codes for their
requirements.
controllers
Presently, many types of controllers for
irrigation systems are available. Selec-
tion of this device is based on the spe-
cifc application involved. Controllers
are programmed to activate each irriga-
tion zone at a specifc time and also will
control the length of time that each zone
is activated. Some controllers have a cal-
endar that allows the irrigation system to
be used only on certain days. Other types
of controllers have manual (or automatic)
overrides to shut down all systems during
rain or to turn on specifc zones for extra
water. Some controllers have soil mois-
ture monitors, which turn on zones only
when needed. Controller panels can be
surface mounted, recessed mounted, or
pedestal mounted. Figure 9 shows a typi-
cal illustration of a surface-mounted and
a pedestal-mounted irrigation system
programmer.
desIgn InformatIon
When designing an underground sprin-
kler system, the plumbing engineer
should consider the following factors: the
site plan, type of plants, type of soil, type
and source of water, and system location.
sIte plan
An accurate site plan, preferably laid
out to scale and showing all buildings,
shrubs, trees, hedges, walks, drives, and
parking, should be drawn as accurately as
possible. Areas where overspray is unde-
sirable, such as walkways and buildings,
should be clearly noted. Property lines
also should be shown on the site plan.
Te heights and diameters of shrubs and
hedges should be indicated.
types of plantIngs
Te engineer should show the areas that
will be irrigated on the site plan as well as
the areas that will be omitted. Tose areas
that require a diferent style of sprinkler
and separate zoning also should be indi-
cated. Some plantings require more fre-
quent watering than others; therefore,
they will require a separate zone and
control valve. Te engineer should deter-
mine whether the plantings allow spray
on their leaves (or any other special type
of spray) and should select the sprinklers
accordingly.
Figure 8 Installation of Atmospheric-Type Vacuum Breakers
Figure 7 NozzlesAdjustable Arcs and Patterns
P
h
o
t
o
c
o
u
r
t
e
s
y
o
f
R
a
i
n
B
i
r
d
C
o
r
p
o
r
a
t
i
o
n
SEPTEMBER 2007 Plumbing Systems & Design 5
type of soIl
Te type of soil determines the proper
rate of application of water to the soil. Te
length and frequency of the applications
can be determined by considering the
soil and the types of plants.
A sufcient amount of water must be
applied during each irrigation period to
ensure penetration to the root zone. Table
1 recommends acceptable guidelines for
several types of soil profles. Where avail-
able, the engineer should secure local soil
and weather conditions by contacting
the local state extension engineer, a uni-
versity, or the weather bureau. Te local
weather bureau usually publishes an
evapotranspiration guide, which shows
the defcit water required to maintain turf
grass. Tis value is compiled by measuring
the rainfall minus the evaporation taking
place during a particular period. Te bal-
ance is the amount of water required. In
the absence of any specifc information
on local soil and weather conditions, the
irrigation system should be designed for
a minimum of 1 inches (38.1 mm) of
water per week.
Sandy, porous soils (as previously indi-
cated) have relatively high absorption
rates and can handle the high output of
sprinklers. Steep slopes and very tight,
nonporous soils require low precipita-
tion rates to avoid erosion damage and
runofs.
type and source of Water
Te source of the water should be located
on the site plan. If the water source is a
well, the pump capacity, well depth,
pump discharge pressure, and other
pertinent data should also be recorded.
If the water source is a city water main,
the locations, size, service-line material,
and length of piping from the service line
to the meter should be researched by
the plumbing engineer. Te water meter
size and the static water pressure of the
city main are also needed. Te engineer
should determine whether special meter
pits or piping arrangements are required
by the utility company.
system locatIon
Due to the infuence of physical and
local climatic conditions, the general
area may require specifc design consid-
erations, such as drain valves on systems
subjected to freezing temperatures. Windy
areas require closer spacing of sprinklers,
and the wind velocity and direction must
be considered. For areas on sloping ter-
rain, there will be a diference in the
outlet pressure, and consideration must
be made for system drainage.
Te engineer must review local codes
to determine acceptable piping materi-
als, installation, requirements, and the
approved connection to municipal water
works.
references
Te ABCs of Lawn Sprinkler Systems. Irri-
gation Association, Fairfax, Virginia.
Pair, Claude H., ed. Sprinkler Irrigation,
4th edition. Sprinkler Irrigation
Association, Silver Spring, Maryland.
Architect-engineers Turf Sprinkler
Manual. Te Rainbird Company,
Glendora, California.
Design Information for Large Turf Irriga-
tion Systems. Te Toro Company,
Riverside, California.
Young, Virgil E. Sprinkler Irrigation
Systems. Mister Rain, Inc., Auburn,
Washington.
resources
Te Irrigation Association, www.irriga-
tion.org
Figure 9 Irrigation Sprinkler Programmers
P
h
o
t
o
c
o
u
r
t
e
s
y
o
f
R
a
i
n
B
i
r
d
C
o
r
p
o
r
a
t
i
o
n
6 Plumbing Systems & Design SEPTEMBER 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Irrigation Systems
appendIx a
suggested InformatIon sheet for sprInkler system desIgn
All available information should be contained on this sheet, plot plan, or both.
1. Project name_______________________________ Address_______________________________________
2. Water supply:
a. Location and size of existing tap, meter, pump, or other __________________________________
b. Existing meter, pump, or tap capacity: Residual pressure _______________GPM _____________
c. Power supply: Location _________________________________________ Voltage _________________
d. Length, type, location, and size of existing supply line (identify on plan)
3. Area to be watered. Identify all planted areas whether shrubbery or trees; indicate clearance under trees. (Identify on plan.)
4. Soil type: Light _______________________ Medium _____________________ Heavy __________________
5. Hours per day and night allowed for irrigation __________________________________________________
6. Amount of precipitation required per week __________________________________________________
7. Area to be bordered or not watered (identify on plan)
8. Elevations and prevailing wind conditions (identify on plan)
9. Type of system: (a) Automatic electric _________________ (b) Automatic hydraulic _______________
(c) Manual pop-up ______________ (d) Manual quick-coupling _____________ (e) Other____________
10. Indicate equipment preference _____________________________________________________________
11. Indicate preferred location for valves and controllers _________________________________________________________________
______________________________________________________________
12. Indicate vacuum breaker and/or drain valve requirement ____________________________________________________________
_________________________________________________________________
13. Indicate pipe material preference: 2 and larger ______________ 2 and smaller _______________
14. Indicate any preference for sprinkler riser types ____________________________________________
SPECIAL NOTES (use additional sheet if necessary) _____________________________________________________________________
____________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________
SEPTEMBER 2007 Plumbing Systems & Design 7
About This Issues Article
The September 2007 continuing education article is
Irrigation Systems, Chapter 4 of ASPE Data Book 3: Special
Plumbing Systems.
This chapter discusses the basic design criteria and com-
ponents of irrigation systems for ornamental lawns and
turf. Among the factors considered are water quality and
requirements, soil considerations, systems concepts, and
components. A design information sheet is also provided, as
Appendix A, to assist the plumbing engineer in the orderly
collection of the required feld information and other perti-
nent data.
You may locate this article at www.psdmagazine.org. Read
the article, complete the following exam, and submit your
answer sheet to the ASPE office to potentially receive 0.1 CEU.
P
S
D
1
4
1
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
CE QuestionsIrrigation Systems (PSD 141)
1. The function of an irrigation system is _________.
a. to conserve water
b. as a labor-saving device for yard maintenance
c. to provide and distribute a predetermined amount of
water to economically produce and/or maintain shrubs,
lawns, and turf
d. none of the above
2. When designing an underground sprinkler system,
the plumbing engineer should consider which of the
following factors?
a. site plan, b. types of plants, c. type of soil,
d. all of the above
3. The amount of water to apply per irrigation cycle in
coarse, sandy soil, assuming a 14-inch root depth, is ____.
a. 0.45 inch, b. 0.85 inch, c. 1.10 inches,
d. none of the above
4. The three basic concepts that can be used by the engineer
in the design of the irrigation network are _________.
a. block method, quick-coupling method, and valve-per-
sprinkler method
b. uniform water coverage, controlled depth of water per
square foot, and zone control method
c. both a and b
d. none of the above
5. Water for irrigation systems _________.
a. may be from an urban source
b. may be from a private source
c. may be from a storage reservoir, tank, or surface pond
d. any of the above
6. Soil conditions _________.
a. need not be considered when urban sources of water are
used
b. afect the amount of water needed
c. are not important because the landscaper will supply the
proper soil for the plants used
d. should have high absorption rates
7. The last concept in sprinkler system design is _________.
a. plant type, b. soil type, c. the valve-in-head method,
d. slope of grade at the site
8. One of the most important considerations for the
plumbing engineer when designing an underground
sprinkler system is _________.
a. the selection of the sprinkler heads
b. the system controller
c. using a sufcient quantity of water
d. using the least amount of water
9. Windy areas require _________.
a. more water due to evaporation
b. closer spacing of sprinklers
c. increased outlet pressure
d. both a and c
10. Atmospheric vacuum breakers must be installed
_________.
a. only if required by code
b. on every sprinkler circuit downstream of the control
valve
c. when the designer does not want to use a backfow
preventer
d. below grade
11. Trickle irrigation is commonly used in _________.
a. vineyards and orchards
b. where water is scarce
c. foreign countries
d. less afuent areas
12. In climates where freezing conditions may occur,
_________.
a. manual drain valves should be installed
b. reduced-pressure backfow preventers should not be
installed
c. automatic-type drain valves should be installed
d. the piping system must be heat traced
Do you fnd it difcult to obtain continuing education units (CEUs)?
Trough this special section in every issue of PS&D, ASPE can help
you accumulate the CEUs required for maintaining your Certifed in
Plumbing Design (CPD) status.
Now Online!
Te technical article you must read to complete the exam is located
at www.psdmagazine.org. Te following exam and application form
also may be downloaded from the website. Reading the article and
completing the form will allow you to apply to ASPE for CEU credit.
For most people, this process will require approximately one hour. If
you earn a grade of 90 percent or higher on the test, you will be notifed
that you have logged 0.1 CEU, which can be applied toward the CPD
renewal requirement or numerous regulatory-agency CE programs.
(Please note that it is your responsibility to determine the acceptance
policy of a particular agency.) CEU information will be kept on fle at
the ASPE ofce for three years.
Note: In determining your answers to the CE questions, use only the material
presented in the corresponding continuing education article. Using information
from other materials may result in a wrong answer.
8 Plumbing Systems & Design SEPTEMBER 2007 PSDMAGAZINE.ORG
P
S
D
1
4
2
Sanitary
Drainage
Systems
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
NOVEMBER 2007
PSDMAGAZINE.ORG
INTRODUCTION
Te purpose of the sanitary drainage system is to remove efu-
ent discharged from plumbing fxtures and other equipment to
an approved point of disposal. A sanitary drainage system gen-
erally consists of horizontal branches, vertical stacks, a building
drain inside the building, and a building sewer from the build-
ing wall to the point of disposal.
To economically design a sanitary drainage system, use the
smallest pipes according to the code that can rapidly carry away
the soiled water from individual fxtures without clogging the
pipes, leaving solids in the piping, generating excessive pneu-
matic pressures at points where the fxture drains connect to the
stack (which might cause the reduction of trap water seals and
force sewer gases back through inhabitable areas), and creating
undue noise.
Since vents and venting systems are described in Chapter 3 of
this volume, the following discussion centers only on the design
of drain and waste systems.
CODES AND STANDARDS
Plumbing codes establish a minimum acceptable standard for
the design and installation of systems, including sanitary drain-
age. Tere are various model codes, but some states and large
cities have adopted plumbing codes other than the ones usually
associated with the region. Because of this non-standardization,
the actual plumbing code used for each specifc project must be
obtained from a responsible code ofcial. Tere are a variety of
diferent codes used to lay out and size interior sanitary drain-
age system. Some codes have been adopted by major cities such
as New York, Chicago, Los Angles, and others.
Te information pertaining to sanitary design for any specifc
project appears in the approved local plumbing code and must
be the primary method used for the accepted methods and
sizing. Te tables and charts appearing in this chapter are used
only to illustrate and augment discussions of sizing methods,
sizing procedures, and design methods and should not be used
for actual design purposes.
FLOW IN STACKS, BUILDING DRAINS, AND FIXTURE
DRAINS
FLOW IN STACKS
A stack is considered a main vertical pipe that carries away dis-
charge from within a facility of water closets and urinals (soil
stack) or other clear water waste from equipment and non-
sanitary fxtures (waste stack). Flow in the drain empties into
the vertical stack ftting, which may be a long-turn tee-wye or
a short-turn or sanitary tee. Each of these fttings permits fow
from the drain to enter the stack with a component directed
vertically downward. Depending on the rate of fow out of the
drain into the stack, the diameter of the stack, the type of stack
ftting, and the fow down the stack from higher levels, if any,
the discharge from the fxture drain may or may not fll the cross
section of the stack at the level of entry. In any event, as soon as
the water enters the stack, the force of gravity rapidly accelerates
it downward, and before it falls very far, it assumes the form of a
sheet around the wall of the stack, leaving the center of the pipe
open for the fow of air.
Tis sheet of water continues to accelerate until the frictional
force exerted by the wall of the stack on the falling sheet of water
equals the force of gravity. From that point onif the distance
the water falls is great enough and provided that no fow enters
the stack at lower levels to interfere with the sheetthe sheet
remains unchanged in thickness and velocity until it reaches
the bottom of the stack. Te ultimate vertical velocity the sheet
attains is called the terminal velocity. Te distance the sheet
must fall to attain this terminal velocity is called the terminal
length. Following are the formulae developed for calculating
the terminal velocity and terminal length:
Equation 1
V
T
= 3.0
(
Q
)
2/5
d
L
T
= 0.052V
T
2
where
V
T
= Terminal velocity in stack, fps (m/s)
L
T
= Terminal length below point of fow entry, ft (m)
Q = Quantity rate of fow, gpm (L/s)
d = Diameter of stack, in. (mm)
Terminal velocity is approximately 10 to 15 fps (3.05 to 4.57
m/s), and this velocity is attained within 10 to 15 ft (3.05 to 4.57
m) of fall from the point of entry.
At the center of the stack is a core of air that is dragged along
with the water by friction and for which a supply source must
be provided if excessive pressures in the stack are to be avoided.
Te usual means of supplying this air are through the stack vent
or vent stack. Te entrained air in the stack causes a pressure
reduction inside the stack, which is caused by the frictional
efect of the falling sheet of water dragging the core of air along
with it.
If the sheet of water falling down the stack passes a stack ft-
ting through which the discharge from a fxture is entering the
stack, the water from the branch mixes with or defects the
rapidly moving sheet of water. An excess pressure in the drain
from which the water is entering the stack is required to defect
the sheet of water fowing downward or mix the branch water
with it. Te result is a backpressure created in the branch, which
increases with the fow rate and fow velocity down the stack
and with the rate of fow out of the drain.
Te importance of this research is that it conclusively abol-
ishes the myth that water falling from a great height will destroy
the fttings at the base of a stack. Te velocity at the base of a
100-story stack is only slightly and insignifcantly greater than
the velocity at the base of a three-story stack. Te concern is the
weight of the stack, which must be supported by clamps at each
foor level.
Sanitary Drainage Systems
Reprinted from Plumbing Engineering Design Handbook, Volume 2: Plumbing Systems, Chapter 1: Sanitary Drainage Systems.
American Society of Plumbing Engineers.
2 Plumbing Systems & Design NOVEMBER 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION
FLOW IN BUILDING DRAINS
When the sheet of water reaches the bend at the base of the
stack, it turns at approximately right angles into the building
drain. Flow enters the horizontal drain at a relatively high veloc-
ity compared to the velocity of fow in a horizontal drain under
uniform fow conditions. Te slope of the building drain is not
adequate to maintain the velocity that existed in the vertical
sheet when it reached the base of the stack and must fow hori-
zontally. Te velocity of the water fowing along the building
drain and sewer decreases slowly then increases suddenly as
the depth of fow increases and completely flls the cross section
of the drain. Tis phenomenon is called a hydraulic jump.
Te critical distance at which the hydraulic jump may occur
varies from immediately at the stack ftting to 10 times the diam-
eter of the stack downstream. Less hydraulic jump occurs if the
horizontal drain is larger than the stack. After the hydraulic
jump occurs and water flls the drain, the pipe tends to fow full
until the friction resistance of the pipe retards the fow to that of
uniform fow conditions.
FLOW IN FIXTURE DRAINS
Determination of the required drain size is a relatively simple
matter, since the fxture drain must be adequate only to carry
the discharge from the fxture to which it is attached. Because of
the problem of self-siphonage, however, it is advisable to select
the diameter of the drain so that the drain fows little more than
half full under the maximum discharge conditions likely to be
imposed by the fxture.
For example, a lavatory drain capable of carrying the fow dis-
charged from a lavatory may still fow full over part or all of its
length. Tere are several reasons for this. Te vertical compo-
nent of the fow out of the trap into the drain tends to make the
water attach itself to the upper elements of the drain, and a slug
of water is formed, flling the drain at that point. If there is not
sufcient air aspirated through the overfow, the pipe will fow
full for part of its length, with the average velocity of fow being
less than the normal velocity for the rate of fow in the drain at
a given slope.
If the fxture considered is a water closet, the surge of water
from the closet will continue almost without change even
along a very long drain until it reaches the stack. Tus, it can be
assumed, for all practical purposes, that the surge caused by the
discharge of a water closet through a fxture drain reaches the
stack or horizontal branch with practically the same velocity it
had when it left the fxture.
PNEUMATIC PRESSURES IN A SANITARY
DRAINAGE SYSTEM
Because of the pressure conditions in a stack and a
building drain, the wastewater does not fll the cross
section anywhere, so the air can fow freely along with
the water. Te water fowing down the wall of the stack
drags air with it by friction and carries it through the
building drain to the street sewer. Te air is then vented
through the main street sewer system so dangerous
pressures do not build up. Te generally accepted
pressure is plus or minus 1 inch of water column.
If air is to enter the top of the stack to replace the
air being carried along with the water, there must be
a pressure reduction inside the stack. Because of the
head loss necessary to accelerate the air and to provide
for the energy loss at the entrance, however, this pres-
sure reduction is negligible; it amounts to only a small fraction
of an inch (a millimeter) of water. What causes appreciable pres-
sure reductions is the partial or complete blocking of the stack
by water fowing into the stack from a horizontal branch.
A small increase in pneumatic pressure will occur in the
building drain even if there is no complete blocking of the air-
fow by a hydraulic jump or by submergence of the outlet and
the building sewer. Tis is due to the decrease in cross-sectional
area available for airfow when the water fowing in the drain
has adapted itself to the slope and diameter of the drain.
FIXTURE DISCHARGE CHARACTERISTICS
Te discharge characteristic curvesfow rates as a function of
timefor most water closet bowls have the same general shape,
but some show a much lower peak and a longer period of dis-
charge. Te discharge characteristics for various types of water
closet bowls, particularly low-fow water closets, have a sig-
nifcant impact on estimating the capacity of a sanitary drain-
age system. Other plumbing fxtures, such as sinks, lavatories,
and bathtubs, may produce similar surging fows in drainage
systems, but they do not have as marked of an efect as water
closets.
Drainage Loads Single-family dwellings contain certain
plumbing fxturesone or more bathroom groups, each consist-
ing of a water closet, a lavatory, and a bathtub or shower stall; a
kitchen sink, dishwasher, and washing machine; and, possibly,
a set of laundry trays. Large buildings also have other fxtures,
such as slop sinks and drinking water coolers. Te important
characteristic of these fxtures is that they are not used continu-
ously. Rather, they are used with irregular frequencies that vary
greatly during the day. In addition, the various fxtures have
quite diferent discharge characteristics regarding both the aver-
age rate of fow per use and the duration of a single discharge.
Consequently, the probability of all the fxtures in the building
operating simultaneously is small. Assigning drainage fxture
unit (dfu) values to fxtures to represent their load-producing
efect on the plumbing system was originally proposed in 1923
by Dr. Roy B. Hunter. Te fxture unit values were designed for
application in conjunction with the probability of simultaneous
use of fxtures to establish the maximum permissible drainage
loads expressed in fxture units rather than in gallons per minute
(gpm, L/s) of drainage fow. Table 1 gives the recommended fx-
ture unit values. Te plumbing engineer must conform to local
code requirements.
Table 1 Residential Drainage Fixture Unit (dfu) Loads
Fixture Drainage Fixture Units (dfu) IPC UPC
Bathtub 2 3
Clothes washer 3 3
Dishwasher 2 2
Floor drain 3 * * Trap loadings
Laundry tray 2 2 1" 1 dfu
Lavatory, single 1 1 1" 3 dfu
Lavatory, in sets of 2 or 3 2 2 2 4 dfu
Shower (each head) 2 2 3" 6 dfu
Sink (including dishwasher and garbage disposer) 3 3 4" 8 dfu
Water closet (1.6-gpf gravity tank) 4 4
Water closet (1.6-gpf fushometer tank) 5 5
Water closet (1.6-gpf fushometer valve) 4 4
NOVEMBER 2007 Plumbing Systems & Design 3
A dfu is a quantity of load-producing discharge in relation to
that of a lavatory.
Dr. Hunter conceived the idea of assigning a fxture unit value
to represent the degree to which a fxture loads a system when
used at the maximum assumed fow and frequency. Te pur-
pose of the fxture unit concept is to make it possible to calcu-
late the design load of the system directly when the system is a
combination of diferent kinds of fxtures, each having a unique
loading characteristic. Current or recently conducted studies of
drainage loads on drainage systems may change these values.
Tese include studies of (1) reduced fow from water-saving fx-
tures; (2) models of stack, branch, and house drain fows; and
(3) actual fxture use.
STACK CAPACITIES
Te criterion of fow capacities in drainage stacks is based on
the limitation of the water-occupied cross section to a speci-
fed fraction (r
s
) of the cross section of the stack where terminal
velocity exists, as suggested by earlier investigations.
Flow capacity can be expressed in terms of the stack diameter
and the water cross section:
Equation 2
Q = 27.8 r
s
5/3
D
8/3
where
Q = Capacity, gpm (L/s)
r
s
= Ratio of cross-sectional area of the sheet of water to
cross-sectional area of the stack
D = Diameter of the stack, in. (mm)
Values of fow rates based on r = ,
7
24, and
1
3 are tabulated in
Table 2.
Whether or not Equation 2 can be used safely to predict stack
capacities remains to be confrmed and accepted. However, it
provides a defnite law of variation of stack capacity with diam-
eter. If this law can be shown to hold for the lower part of the
range of stack diameters, it should be valid for the larger diam-
eters. It should be remembered that both F.M. Dawson and Dr.
Hunter, in entirely independent investigations, came to the
conclusion that slugs of water, with their accompanying violent
pressure fuctuations, did not occur until the stack fowed to
1
3 full. Most model codes have based their stack loading tables
on a value of r = or
7
24.
Te recommended maximum permissible fow in a stack is
7
24
of the total cross-sectional area of the stack. By substituting r =
7
24
into Equation 2, the corresponding maximum permissible fow
for the various sizes of pipe in gpm (L/s) can be determined.
Table 1-3 lists the maximum permissible fxture units (fu) to be
conveyed by stacks of various sizes. Te table was created by
taking into account the probability of simultaneous use of fx-
tures. For example, the 500 fu is the maximum loading for a 4-in.
(100-mm) stack, thus 147 gpm (9.3 L/s) is equivalent to 500 fu.
Tis is the total load from all branches.
It should be noted that there is a restriction of the amount
of fow permitted to enter a stack from any branch when the
stack is more than three branch intervals. If an attempt is made
to introduce too large a fow into the stack at any one level, the
infow will fll the stack at that level and will even back up the
water above the elevation of infow, which will cause violent
pressure fuctuations in the stackresulting in the siphoning of
trap sealsand may also cause sluggish fow in the horizontal
branch. Tis problem was solved in a study of stack capacities
made by Wyly and Eaton at the National Bureau of Standards for
the Housing and Home Finance Agency in 1950.
Te water fowing out of the branch can enter the stack only by
mixing with the stream fowing down the stack or by defecting
it. Such a defection of the high-velocity stream coming down
the stack can be accomplished only if there is a large enough
hydrostatic pressure in the branch, since a force of some kind is
required to defect the downward fowing stream and therefore
change its momentum. Tis hydrostatic pressure is built up by
the backing up of the water in the branch until the head thus
created sufces to change the momentum of the stream already
in the stack to allow the fow from the branch to enter the stack.
Te magnitude of the maximum hydrostatic pressure that
should be permitted in the branch as a result of the backing up
of the spent water is based on the consideration that this backup
should not be sufciently great to cause the water to back up
into a shower stall or to cause sluggish fow. It is half the diam-
eter of the horizontal branch at its connection to the stack. Tat
is, it is the head measured at the axis of the pipe that will cause
the branch to fow full near the exit.
When a long-turn tee-wye is used to connect the branch to
the stack, the water has a greater vertical velocity when it enters
the stack than it does when a sanitary tee is used, and the back
pressures should be smaller in this case for the same fows down
the stack and in the branch.
Table 3 shows the maximum permissible fu loads for sanitary
stacks. Te procedure for sizing a multistory stack (greater than
three foors) is to frst size the horizontal branches connected to
the stack. Tis is done by totaling the fxture units connected to
Table 3 Horizontal Fixture Branches and Stacks
Diameter
of pipe, in.
(mm)
Maximum Number of Drainage Fixture Units (dfu) that May
Be Connected
Any
Horizontal
Fixture
Branch
a
1 Stack of
3 or Fewer
Branch
Intervals
Stacks with More than 3
Branch Intervals
Total for
Stack
Total at
1 Branch
Interval
1 (40) 3 4 8 2
2 (50) 6 10 24 6
2 (65) 12 20 42 9
3 (80) 20
b
48
b
72
b
20
b
4 (100) 160 240 500 90
5 (125) 360 540 1,100 200
6 (150) 620 960 1,900 350
8 (200) 1,400 2,200 3,600 600
10 (250) 2,500 3,800 5,600 1,000
12 (300) 3,900 6,000 8,400 1,500
15 (380) 7,000
a
Does not include branches of the building drain.
b
No more than two water closets or bathroom groups within each branch interval or more than
six water closets or bathroom groups on the stack.
Table 2 Capacities of Stacks
Pipe Size,
in. (mm)
Flow, gpm (L/s)
r =
1
4 r =
7
24 r =
1
3
2 (50) 17.5 (1.1) 23.0 (1.45) 28 (1.77)
3 (80) 52 (3.28) 70 (4.41) 85 (5.36)
4 (100) 112 (7.07) 145 (9.14) 180 (11.35)
5 (125) 205 (12.93) 261 (16.5) 324 (20.44)
6 (150) 330 (20.82) 424 (26.8) 530 (33.43)
8 (200) 710 (44.8) 913 (57.6) 1,140 (72)
10 (250) 1,300 (82.0) 1,655 (104.4) 2,068 (130.5)
12 (300) 2,082 (131.4) 2,692 (170) 3,365 (212.3)
4 Plumbing Systems & Design NOVEMBER 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Sanitary Drainage Systems
each branch and size in accordance with
column 2 in Table 3. Next, total all the
fxture units connected to the stack and
determine the size from the same table,
under column 4. Immediately check the
next column, Total at One Branch Inter-
val, and determine if this maximum is
exceeded by any of the branches. If it is
exceeded, the size of the stack as originally
determined must be increased at least
one size, or the loading of the branches
must be redesigned so maximum condi-
tions are satisfed. Take, for example, a
4-in. (100-mm) stack more than three
stories in height. Te maximum loading
for a 4-in. (100-mm) branch is 160 fu, as
shown in column 2 of Table 3. Tis load
is limited by column 5 of the same table,
which permits only 90 fu to be introduced
into a 4-in. (100-mm) stack in any one-
branch interval. Te stack would have to
be increased in size to accommodate any
branch load exceeding 90 fu.
To illustrate clearly the requirements
of a stack with an ofset of more than
45 from the vertical, Figure 1 shows the
sizing of a stack in a 12-story building
where there is one ofset between the ffth
and sixth foors and another ofset below
the street foor.
Sizing is computed as follows:
Step 1. Compute the fxture units connect-
ed to the stack. In this case, assume
1,200 fxture units are connected to
the stack from the street foor through
the top foor.
Step 2. Size the portion of the stack above
the fifth-floor offset. There are 400
fxture units from the top foor down
through the sixth foor. According to
Table 3, column 4, 400 fxture units
require a 4-in. (100-mm) stack.
Step 3. Size the ofset on the ffth foor. An
ofset is sized and sloped like a building drain.
Step 4. Size the lower portion of the stack from the ffth foor down
through the street foor. Te lower portion of the stack must be
large enough to serve all fxture units connected to it, from the
top foor down (in this case 1,200 fxture units). According to
Table 3, 1,200 fxture units require a 6-in. (150-mm) stack.
Step 5. Size and slope the ofset below the street foor the same
as a building drain.
Te fxture on the sixth foor should be connected to the stack
at least 2 ft (0.6 m) above the ofset. If this is not possible, then
connect them separately to the stack at least 2 ft (0.6 m) below
the ofset. If this is not possible either, run the fxture drain down
to the ffth or fourth foor and connect to the stack at that point.
CAPACITIES OF SLOPING DRAINS
Te characteristics of sewage are the same as plain water.
Capacities of horizontal or sloping drains are complicated by
surging fow.
Te determination of drain size is based on highly fuctuating
or surging fow conditions in the horizontal branches carrying
the discharge of fxtures to the soil or waste stack. After falling
down the vertical stack, the water is assumed to enter the build-
ing drain with peaks of the surges leveled of somewhat but still
in a surging condition.
In a large building covering considerable ground area there
are probably several primary branches and certainly at least one
secondary branch. After the water enters the building drain, the
surge continues to level of, becoming more and more nearly
uniform, particularly after the hydraulic jump has occurred. If
the secondary branch is long enough, and if the drain serves
a large number of fxtures, the fow may become substantially
uniform before it reaches the street sewer.
Figure 1 Procedure for Sizing an Ofset Stack
NOVEMBER 2007 Plumbing Systems & Design 5
STEADY, UNIFORM FLOW CONDITIONS IN SLOPING DRAINS
Although the equations of steady, uniform fow in sloping drains
should not be used to determine the capacities of sloping drains
in which surging fow exists, fow computations based on these
formulas aford a rough check on values obtained by the more
complicated methods that are applicable to surging fow. Hence,
three of the commonly used formulas for fow in pipes will be
considered: (1) Hazen and Williams, (2) Darcy-Weisbach, and
(3) Manning.
Hazen and Williams formula Tis formula is
usually written as follows:
Equation 3
V = 1.318 C R
0.63
S
0.54
where
V = Mean velocity of fow, fps (m/s)
C = Hazen and Williams coefcient
R = Hydraulic radius of pipe, ft (m)
S = Slope of pressure gradient
Te exponents of R and S in Equation 3 have been
selected to make the coefcient C as nearly constant
as possible for diferent pipe diameters and for dif-
ferent velocities of fow. Tus, C is approximately
constant for a given pipe roughness.
Darcy-Weisbach formula In this formula the dimensionless
friction coefcient f varies with the diameter of the pipe, the
velocity of fow, the kinematic viscosity of the fuid fowing, and
the roughness of the walls. It is usually written as follows:
Equation 4
h
f
=
f L V
2
D 2g
where
h
f
= Pressure drop or friction loss, ft (m)
f = Friction coefcient
L = Length of pipe, ft (m)
D = Diameter of pipe, ft (m)
V = Mean velocity of fow, fps (m/s)
g = Acceleration of gravity, 32.2 fps
2
(9.8 m/s
2
)
Manning formula Te Manning formula, which is similar
to the Hazen and Williams formula, is meant for open-channel
fow and is usually written as follows:
Equation 5
V =
1.486
R
2/3
S
1/2
=
1.486
R
0.67
S
0.50
n n
In this formula, n is the Manning coefcient and varies with
the roughness of the pipe and the pipe diameter.
Te quantity of fow is equal to the cross-sectional area of fow
times the velocity of fow obtained from the above three equa-
tions. Tis can be expressed as:
Equation 5a
Q = AV
where
Q = Quantity rate of fow, cfs (m
3
/s)
A = Cross-sectional area of fow, ft
2
(m
2
)
V = Velocity of fow, fps (m/s)
By substituting the value of V from Mannings formula, the
quantity of fow in variously sized drains of the same material
can be calculated as
Equation 5b
Q = A
(
1.486
)
R
2/3
S
1/2
n
Tis is the formula used by many plumbing engineers to deal
with sloping drain problems. Te signifcant hydraulic param-
eters used in the above equation are listed in Table 4.
It should be noted that the units in the above equations should
be converted to the proper units whenever utilizing Equations
5a or 5b.
SLOPE OF HORIzONTAL DRAINAGE PIPING
Horizontal drains are designated to fow at half-full capacity
under uniform fow conditions to minimize the generation of
pneumatic pressure fuctuations. A minimum slope of in./
ft (6.4 mm/m) should be provided for pipe 3 in. (80 mm) and
smaller,
1
8 in./ft (3.2 mm/m) for 4-6-in. (100-150-mm) pipe,
and
1
16 in./ft (1.6 mm/m) for pipe 8 in. (200 mm) and larger.
Tese slopes are not a hard and fast rule and might be less
under unusual conditions. Te signer must confrm required
slopes with the local code authority. Tese minimum slopes
are required to maintain a velocity of fow greater than 2 fps
for scouring action. Table 5 gives the approximate velocities for
given fow, slopes, and diameters of horizontal drains based on
the Manning formula for half-full pipe and n = 0.015.
A fow velocity of 2 fps will prevent the solids within a pipe
from settling out and forming a system stoppage. Table 6 has
been prepared to give the size of a pipe in conjunction with fow
rate to maintain a self-cleansing velocity of 2 fps.
LOAD OR DRAINAGE PIPING
Te recommended loads for building drains and sewers are tab-
ulated in Table 7. Tis table shows the maximum number of fx-
ture units that may be connected to any portion of the building
drain or building sewer for given slopes and diameters of pipes.
For example, an ofset below the lowest branch with 1,300 fu at
in./ft (6.4 mm/m) slope requires an 8-in. (200-mm) pipe.
For devices that provide continuous or semi-continuous fow
into the drainage system, such as sump pumps, ejectors, and air-
conditioning equipment, a value of 2 fu can be assigned for each
gpm (L/s) of fow. For example, a sump pump with a discharge
rate of 200 gpm (12.6 L/s) is equivalent to 200 2 = 400 fu.
COMPONENTS OF SANITARY DRAINAGE SYSTEMS
SUMPS AND EjECTORS
Te distinction between sump and ejector pumps is more termi-
nology than actual fact. A sump pump is designed to transport
clear, non-sanitary wastewater with some turbidity and sus-
Table 4 Values of R, R2/3, AF, and AH
Pipe Size,
in. (mm) R =
D
4, ft (mm) R
2/3
, ft (mm)
A
F
(Cross-Sectional
Area for Full Flow),
ft
2
(m
2
)
AH (Cross-Sectional
Area for Half-full
Flow), ft
2
(m
2
)
1 (40) 0.0335 (1.02) 0.1040 (3.17) 0.01412 (0.0013) 0.00706 (0.00065)
2 (50) 0.0417 (1.27) 0.1200 (3.66) 0.02180 (0.0020) 0.01090 (0.0009)
2 (65) 0.0521 (1.59) 0.1396 (4.24) 0.03408 (0.0031) 0.01704 (0.0015)
3 (80) 0.0625 (1.90) 0.1570 (4.78) 0.04910 (0.0046) 0.02455 (0.0023)
4 (100) 0.0833 (2.54) 0.1910 (5.82) 0.08730 (0.0081) 0.04365 (0.0040)
5 (125) 0.1040 (3.17) 0.2210 (6.74) 0.13640 (0.0127) 0.06820 (0.0063)
6 (150) 0.1250 (3.81) 0.2500 (7.62) 0.19640 (0.0182) 0.09820 (0.0091)
8 (200) 0.1670 (5.09) 0.3030 (9.23) 0.34920 (0.0324) 0.17460 (0.0162)
10 (250) 0.2080 (6.33) 0.3510 (10.70) 0.54540 (0.0506) 0.27270 (0.0253)
12 (300) 0.2500 (7.62) 0.3970 (12.10) 0.78540 (0.0730) 0.39270 (0.0364)
15 (380) 0.3125 (9.53) 0.4610 (14.05) 1.22700 (0.0379) 0.61350 (0.0570)
6 Plumbing Systems & Design NOVEMBER 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Sanitary Drainage Systems
pended solids no larger than sand grains. An ejector pump is
designed to transport sanitary waste and larger solids suspended
in the efuent. All efuent is a liquid with solids suspended in it
but has the same hydraulic characteristics as water.
Building drains that cannot fow directly into a sewer by grav-
ity must be discharged into a covered basin from which fuid is
lifted into the buildings gravity drainage system by automatic
pump equipment or by any equally efcient method approved
by the administrative authority.
An ejector basin must be of airtight construction and must
be vented. It is airtight to prevent the escape of foul odors gen-
erated by sanitary waste from the subdrainage system. Since
it is airtight, a vent is required to relieve the air in the basin as
wastes discharge into it and also to supply air to the basin while
the contents are being discharged to the sanitary gravity drain-
age system. A duplex pump system shall be used. If one pump
breaks down, the control system will alert the second pump
to start. Te system will remain in operation and no damage
will be caused by the cessation of system operation. When a
Table 5 Approximate Discharge Rates and Velocities in Sloping Drains, n = 0.015
a
Actual Inside
Diameter of
Pipe,
in. (mm)
Actual Inside Half-full Flow Discharge Rate and Velocity
1
16 in./ft (1.6 mm/m) Slope
1
8 in./ft (3.2 mm/m) Slope
1
4 in./ft (6.4 mm/m) Slope
1
2 in./ft (12.7 mm/m) Slope
Disch.,
gpm (L/s)
Velocity, fps
(mm/s)
Disch.,
gpm (L/s)
Velocity, fps
(mm/s)
Disch.,
gpm (L/s)
Velocity, fps
(mm/s)
Disch.,
gpm (L/s)
Velocity, fps
(mm/s)
1 (31.8) 3.40 (0.21) 1.78 (45.5)
1
3
8 (34.9) 3.13 (0.20) 1.34 (0.41) 4.44 (0.28) 1.90 (48.3)
1 (38.9) 3.91 (0.247) 1.42 (0.43) 5.53 (0.35) 2.01 (51.1)
1
5
8 (41.28) 4.81 (0.30) 1.50 (0.46) 6.80 (0.38) 2.12 (53.9)
2 (50.8) 8.42 (0.53) 1.72 (0.52) 11.9 (0.75) 2.43 (61.8)
2 (63.5) 10.8 (0.68) 1.41 (0.43) 15.3 (0.97) 1.99 (0.61) 21.6 (1.36) 2.82 (71.7)
3 (76.3) 17.6 (1.11) 1.59 (0.49) 24.8 (1.56) 2.25 (0.69) 35.1 (2.21) 3.19 (81.1)
4 (101.6) 26.70 (1.68) 1.36 (34.6) 37.8 (2.38) 1.93 (0.59) 53.4 (3.37) 2.73 (0.83) 75.5 (4.76) 3.86 (98.2)
5 (127) 48.3 (3.05) 1.58 (40.2) 68.3 (4.30) 2.23 (0.68) 96.6 (6.10) 3.16 (0.96) 137 (8.64) 4.47 (113.7)
6 (152.4) 78.5 (4.83) 1.78 (45.3) 111 (7.00) 2.52 (0.77) 157 (10) 3.57 (1.09) 222 (14.0) 5.04 (128.2)
8 (203.2) 170 (10.73) 2.17 (55.2) 240 (15.14) 3.07 (0.94) 340 (21.5) 4.34 (1.32) 480 (30.3) 6.13 (155.9)
10 (256) 308 (19.43) 2.52 (64.1) 436 (27.50) 3.56 (1.09) 616 (38.9) 5.04 (1.54) 872 (55.0) 7.12 (181.0)
12 (304.8) 500 (31.55) 2.83 (72.0) 707 (44.60) 4.01 (1.22) 999 (63.0) 5.67 (1.73) 1413 (89.15) 8.02 (204.0)
a
n = Manning coefcient, which varies with the roughness of the pipe.
For full fow: Multiply discharge by 2.00.
For full fow: Multiply velocity by 1.00.
For smoother pipe: Multiply discharge and velocity by 0.015 and divide by n of another pipe.
Table 7 Building Drains and Sewers
a
Diameter
of Pipe, in.
(mm)
Maximum Permissible Fixture Units for
Sanitary Building Drains and Runouts
From Stacks
Slope, in./ft (mm/m)
1
16 (1.6)
1
8 (3.2)
1
4 (6.4)
1
2 (12.7)
2 (50) 21 26
2 (65) 24 31
3 (80) 20 42
b
50
b
4 (100) 180 216 250
5 (125) 390 480 575
6 (150) 700 840 1,000
8 (200) 1400 1600 1,920 2,300
10 (250) 2500 2900 3,500 4,200
12 (300) 2900 4600 5,600 6,700
15 (380) 7000 8300 10,000 12,000
a
On-site sewers that serve more than one building may be sized according to the
current standards and specifcations of the administrative authority for public
sewers.
b
No more than two water closets or two bathroom groups, except in single-family
dwellings, where no more than three water closets or three bathroom groups may be
installed. Check the local codes in the area served for exact requirements or restrictions.
Table 6 Slopes Of Cast Iron Soil Pipe Sanitary Sewers Required To Obtain Self-cleansing Velocities Of 2.0 And 2.5 Ft./sec.
(Rased On Mannings Formula With N = .012)
Pipe
Size (in.)
Velocity
(ft./sec.)
1/4 Full 1/2 Full 3/4 Full Full
Slope
(ft./ft.)
Flow
(Gal./min.)
Slope
(ft./ft.)
Flow
(Gal./min.)
Slope
(ft./ft.)
Flow
(Gal./min.)
Slope
(ft./ft.)
Flow
(Gal./min.)
2.0 2.0 0.0313 4.67 0.0186 9.34 0.0148 14.09 0.0186 18.76
2.5 0.0489 5.04 0.0291 11.67 0.0231 17.62 0.0291 23.45
3.0 2.0 0.0178 10.71 0.0107 21.46 0.0085 32.23 0,0107 42.91
2.5 0.0278 13.47 0.0167 26.62 0.0133 40.29 0.0167 53.64
4.0 2.0 0.0122 19.03 0.0073 38.06 0.0058 57.01 0.0073 76.04
2.5 0.0191 23.79 0.0114 47.58 0.0091 71.26 0.0114 95.05
5.0 2.0 0.0090 29.89 0.0054 59.79 0.0043 89.59 0.0054 119.49
2.5 0.0141 37.37 0.0085 74.74 0.0067 111.99 0.0085 149.36
6.0 2.0 0.0071 43.18 0.0042 86.36 0.0034 129.54 0.0042 172.72
2.5 0.0111 53.98 0.0066 101.95 0.0053 161.93 0.0066 215.90
8.0 2.0 0.0048 77.20 0.0029 154.32 0.0023 231.52 0.0029 308.64
2.5 0.0075 96.50 0.0045 192.90 0.0036 289.40 0.0045 385.79
10.0 2.0 0.0036 120.92 0.0021 241.85 0.0017 362.77 0.0021 483.69
2.5 0.0056 151.15 0.0033 302.31 0.0026 453.46 0.0033 604.61
12.0 2.0 0.0028 174.52 0.0017 349.03 0.0013 523.55 0.0017 678.07
2.5 0.0044 218.15 0.0026 436.29 0.0021 654.44 0.0026 612.58
15.0 2.0 0.0021 275.42 0.0012 550.84 0.0010 826.26 0.0012 1101.68
2.5 0.0032 344.28 0.0019 688.55 0.0015 1032.83 0.0019 1377.10
NOVEMBER 2007 Plumbing Systems & Design 7
duplex unit is used, each pump should be sized for 100 percent
fow, and it is good practice to have the operation of the pumps
alternate automatically.
A sump basin need not be airtight or vented because of the
lack of objectionable odors. Incoming water is collected in the
sump before it is pumped to the gravity drain pipe. Heavy-
fow drains require large sumps to retain greater-than-usual
amounts of water, thereby creating more head pressure on the
pipe inlet. Most manufacturers make their basins with bottom,
side, or angle inlets and with inside caulk, no-hub, push-on,
spigot, or screwed connections. Outlet connections are made to
accept pressure-type pipe joints. No-hub pipe and fttings are
not acceptable on pumped discharge piping due to the pressure
limitations of the pipe joints.
Sump and ejector systems normally use a wet pit and will have
the pumps either above slab or submerged. Tey are controlled
with a foat switch or electronic, with control switches mounted
inside the basin. Typical ejector installations are illustrated in
Figure 2. Typical ejector installations are illustrated in Figure 3.
CLEANOUTS
Te cleanout provides access to horizontal and verti-
cal lines to facilitate inspection and provide a means
of removing obstructions such as solid objects, greasy
wastes, and hair. Cleanouts, in general, must be gas- and
water-tight, provide quick and easy plug removal, allow
ample space for the operation of cleaning tools, have a
means of adjustment to fnished surfaces, be attractive
in appearance, and be designed to support whatever
trafc is directed over them.
Some cleanouts are designed with a neoprene seal
plug, which prevents freezing or binding to the fer-
rule. All plugs are machined with a straight or running
thread and a fared shoulder for the neoprene gasket,
permitting quick and certain removal when necessary. A
maximum opening is provided for tool access. Recessed
covers are available to accommodate carpet, tile, ter-
razzo, and other surfaces fnishes and are adjustable to
the exact foor level established by the adjustable hous-
ing or by the set screws.
Waste lines are normally laid beneath the foor slabs
at a distance sufcient to provide adequate backfll over
the joints. Cleanouts are then brought up to foor-level
grade by pipe extension pieces. Where the sewer line is
at some distance below grade and not easily accessible
through extensions, small pits or manholes with access
covers must be installed. When cleanouts are installed
in trafc areas, the trafc load must be considered when
the materials of construction are selected.
Te size of the cleanout within a building should be
the same size as the piping, up to 4 in. (100 mm). For
larger size interior piping, 4-in. (100-mm) cleanouts
are adequate for their intended purpose; however, 6-in.
(150-mm) cleanouts are recommended to allow for a
larger variety of access needs such as for sewer video
equipment.
Cleanouts should be provided at the following loca-
tions:
1. Five ft 0 in. (1.5 m) outside or inside the building at
the point of exit.
2. At every change of direction greater than 45.
3. A maximum distance between cleanouts of 50 ft (15.1 m)
should be maintained for piping 4 in. (100 mm) and smaller,
and of 75 ft (22.9 m) for larger piping. Underground sanitary
sewer piping larger than 10 in. (250 mm) in diameter should
be provided with cleanouts at every change of direction and
every 150 ft (45.7 m).
4. At the base of all stacks.
5. To comply with applicable codes.
Optional locations include:
1. At the roof stack terminal.
2. At the end of horizontal fxture branches or waste lines.
3. At fxture traps. (Fixture traps can be pre-manufactured with
cleanout plugs, although some codes prohibit the installa-
tion of this kind of trap.)
Figure 2 Typical Ejector Pump Installation
8 Plumbing Systems & Design NOVEMBER 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Sanitary Drainage Systems
FLOOR DRAINS AND FLOOR SINKS
A large-diameter drain with a deep sump connected to a large-
diameter pipe passes more water faster than a smaller drain.
However, economics do not allow the designer arbitrarily to
select the largest available drain when a smaller, less-expen-
sive unit will do a satisfactory job. High-capacity drains are
intended for use primarily in locations where the fow reaches
high rates, such as malls, wash-down areas, and certain indus-
trial applications. Table 8, which shows minimum ratios of open
grate area based on pipe diameter, is ofered as a guide for the
selection of drains where the drain pipe diameter is known.
Te only drawback to using the open-area-pipe-diameter-
ratio method is that all drain manufacturers do not list the total
open areas of grates in their catalogs. Tis information usually
can be obtained upon request, however.
For the sizing of foor drains for most indoor applications, the
capacity of a drain is not extremely critical because the drains
primary function is to handle minor spillage or fxture overfow.
Te exceptions are, of course, cases where equipment discharges
to the drain, where automatic fre sprinklers may deluge an area
with large amounts of water, and where fushing of the foor is
required for sanitation.
Generally located foor drains or drains installed to anticipate
a failure may not receive sufcient water fow to keep the pro-
tective water seal or plumbing trap from evaporating. If it does
evaporate, sewer gases will enter the space. Auto-
matic or manual trap primers should be installed
to maintain a proper trap seal. (A small amount of
vegetable oil will dramatically reduce the evapora-
tion rate of infrequently used foor drains and foor
sinks.)
Figure 4 shows the basic components of a foor
drain.
GRATES / STRAINERS
Te selection of grates is based on use and the
amount of fow. Light-trafc areas may have a nickel-
bronze-fnished grate, while mechanical areas may
have a large, heavy-duty, ductile iron grate.
Te wearing of spike-heeled shoes prompted the
replacement of grates with a heel-proof, -in.-square
(6.4-mm) grate design in public toilet rooms, corri-
dors, passageways, promenade decks, patios, stores,
theaters, and markets. Tough this type of grating
has less drainage capacity than the previous one, its
safety feature makes it well worth the change.
Grates or strainers should be secured with stain-
less-steel screws in nickel-bronze tops. Vandal-proof
fasteners are available from most manufacturers.
Vandal-proofng foor drain grates is advisable. If
there is public access to the roof, consideration must
be given to protecting the vent openings from van-
dals.
In school gymnasium shower rooms, where the
blocking of fat-top shower drains with paper towels
can cause fooding, dome grates in the corners of
the room or angle grates against the walls can be
specifed in addition to the regular shower drains.
Shower-room gutters and curbs have become unde-
sirable because of code requirements and the obvi-
ous dangers involved. Terefore, the passageways
from shower areas into locker areas need extended-
length drains to prevent runof water from entering
the locker areas.
Where grates are not secured and are subject to
vehicular trafc, it is recommended that non-tilting
and /or tractor-type grates be installed. When a grate
Figure 3 Typical Submerged Sump Pump Installation
Table 8 Recommended Grate Open Areas for Various
Floor Drains With Outlet Pipe Sizes
Nominal Pipe
Size, in. (mm)
Recommended Minimum Grate
Open Area for Floor Drains
Transverse Area
of Pipe, in.
2a
( 10 mm
2
)
Minimum Inside
Area, in.
2
( 10 mm
2
)
1 (40) 2.04 (1.3) 2.04 (1.3)
2 (50) 3.14 (2.0) 3.14 (2.0)
3 (80) 7.06 (4.6) 7.06 (4.6)
4 (100) 12.60 (8.1) 12.06 (8.1)
5 (125) 19.60 (12.7) 19.60 (12.7)
6 (150) 28.30 (18.3) 28.30 (18.3)
8 (200) 50.25 (32.4) 50.24 (32.4)
a
Based on extra-heavy soil pipe, nominal internal diameter.
NOVEMBER 2007 Plumbing Systems & Design 9
starts to follow a wheel or is hit on one edge and starts to tilt,
the skirt catches the side of the drain body and the grate slides
back into its original position. Ramp-drain gratings should be
slightly convex because rapidly fowing ramp water has a ten-
dency to fow across the grate. A better solution to this problem
is to place fat-top grates on a level surface at the bottom of the
ramp, rather than on the ramp slope.
A technique in casting grates is the reversal of pattern draft,
which removes the razor-sharp edges created when grates are
bufed. See Figure 5. Te prevalent bufng technique is called
scuf-buf because it gives the grate a slightly used appearance.
Te use of slots in grates is becoming obsolete because of the
slicing edges they create, which cause excess wear and tear on
the wheels of hand-trucks and other vehicles. Square openings
are more desirable because they shorten this edge and provide
greater drainage capacity than round holes.
FLASHING RING
Tis component makes an efective seal, which prevents water
from passing around the drain to the area below.
SEDIMENT BUCKET
A sediment bucket is an additional internal strainer designed
to collect debris that gets by the regular strainer. It is required
wherever the drain can receive solids, trash, or grit that could
plug piping, such as the following locations:
1. Toilet rooms in commercial buildings should be equipped with
foor drains with sediment buckets to facilitate cleaning.
2. Floor drains with sediment buckets must be provided in
mechanical equipment rooms, where pumps, boilers, water
chillers, heat exchangers, and HVAC equipment regularly
discharge and /or must be periodically drained for mainte-
nance and repairs. HVAC equipment requires the drainage
of condensate from cooling coils using indirect drains.
3. Boilers require drains with sediment buckets. Strategically
located foor drains are also required in buildings with wet
fre-protection sprinkler systems to drain water in case
sprinkler heads are activated. Te maximum temperature
of liquids discharged should be 140F (60C).
Floor drains shall connect to a trap so constructed that it can
be readily cleaned and sized to serve efciently the purpose
for which it is intended. A deep-seal-type trap or an approved
automatic priming device should be provided. Te trap shall be
accessible either from the foor-drain inlet or by a separate clea-
nout within the drain. Figure 6 illustrates several types of drains
that meet these conditions.
(A) Removable Grate; (B) Rust-Resistant Bolts; (C) Integral, One-Piece, Flashing Ring; (D) Cast Drain Body with Sump; (E) Sediment Bucket (optional).
Figure 4 Basic Floor-Drain Components:
(a) Sharp Edge, (b) Reverse Pattern
(a)
(b)
Figure 5 Pattern Draft for Floor Gratings
(A) Typical Drain with Integral Trap that May Be Cleaned Through Removable
Strainer at Floor Level;
(B) Floor Drain with Combination Cleanout and Backwater Valve, for Use Where
Possibility of Backfow Exists;
(C) Drain with Combined Cleanout, Backwater Valve, and Sediment Bucket.
Figure 6 Types of Floor Drain
10 Plumbing Systems & Design NOVEMBER 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Sanitary Drainage Systems
ACCESSORIES
A variety of accessories are available to make the basic drain
adaptable to various types of structures. Te designer must
know the construction of the building, particularly the foor and
deck structures, to specify the appropriate drain.
BACKWATER VALVES
A backwater valve can be installed on a building sewer/house
drain when the drain is lower than the sewer line, when unusual
sewer surcharges may occur due to combined storm water and
sanitary sewer systems, or when old municipal sewers incur high
rates of infltration. A backwater valve reacts similarly to a check
valve. Te device consists of a mechanical fapper or disc, which
requires a certain amount of maintenance; therefore, attention
must be given during the placement of these devices to a free
area and access for maintenance. Sediment can accumulate
on the fapper valve seat, preventing the fapper from closing
tightly. Also, many valves employ a spring or mechanical device
to exert a positive pressure on the fapper device, which requires
occasional lubrication. Most manufacturers of backwater valves
provide an access cover plate for maintenance, which may also
be used as a building sewer cleanout.
Figure 7 illustrates various types of backwater valves that may
be installed where there is a possibility of backfow.
OIL INTERCEPTORS
In commercial establishments such as service stations, garages,
auto repair shops, dry cleaners, laundries, industrial plants,
and process industries having machine shops, metal-treating
process rooms, chemical process or mixing rooms, etc., there
is always the problem of fammable or volatile liquids entering
the drainage system, which can contaminate the sewer line and
cause a serious fre or explosive condition.
Oil interceptors are designed to separate and collect oils and
other light-density, volatile liquids, which would otherwise
be discharged into the drainage system. An oil interceptor is
required wherever lubricating oil, cutting oil, kerosene, gaso-
line, diesel fuel, aircraft fuel, naphtha, parafn, trisodium phos-
phate, or other light-density and volatile liquids are present in
or around the drainage system.
Te interceptor is furnished with a sediment bucket, which
collects debris, small parts, chips, particles, and other sediment
that are frequently present in industrial waste from these types
of facilities and could clog the drainage system. A gasketed,
removable cover permits access for cleaning the interceptor. To
eliminate pressure buildup inside the interceptor, a connection
on each side of the body allows venting of the interceptor.
Oil interceptors are sized in accordance with the maximum
anticipated gpm (L/s) fow rate of wastewater that could be
discharged through a tailpiece and are typically protected from
back-siphonage by the vacuum breaker mounted at the tailpiece
entrance.
Fixture wastewater type. Tese devices are mounted on the
trap of frequently used fxtures. A tapping at the overfow line
will allow small amounts of wastewater to enter an adjacent,
infrequently used drain as the trap surges during use.
Automatic trap primers can be obtained as pre-engineered
devices, which have widely accepted approval. All direct con-
nections between the sewer system and the potable water
system must be protected from potential contamination. Te
above-referenced primers can be manufactured, or ftted with,
devices that are approved to prevent cross-contamination.
SUPPORTS
Te location of pipe supports is usually specifed by code. Tey
are located to maintain a slope that is as uniform as possible
and will not change with time. In this regard, the rigidity of pipe
and joints and the possibility of creep and bedding settlement
are primary considerations. When building settlement may be
signifcant, special hanging arrangements may be necessary.
Underground piping should be continuously and frmly sup-
ported, but blocking below metal pipe is usually acceptable.
Consult the manufacturer for recommendations for piping
materials not covered in the code and for special problems.
Hangers should be designed adequately. To protect from
damage by building occupants, allow at least a 250-lb (113.4-kg)
safety factor when designing hangers. See Data Book, Volume 4,
Chapter 6 for further information.
Seismic restraint must also be considered.
MATERIALS
PIPING
Materials recommended for soil and waste piping, installed
aboveground within buildings, are copper alloy, copper, cast
iron (hub-and-spigot or hubless), galvanized steel, or PVC plas-
tic pipe. Underground building drains should be cast-iron soil
pipe, hard-temper copper tube, ABS or PVC, PVDF, DWV pattern
Schedule 40 plastic pipe with compression joints or couplings,
Figure 7 Various Types of Backwater Valve
Figure 8 Combination Floor Drain and Indirect Waste Receptor
NOVEMBER 2007 Plumbing Systems & Design 11
installed with a minimum cover of 12 in. (300 mm). Corrosive
wastes require suitably acid-resistant materials such as high-
silicon cast iron, borosilicate glass, polypropylene, etc. (Note:
Some blood analyzers discharge sodium azide, which forms a
very dangerous, explosive compound with copper pipes. Either
other piping must be used or the sodium azide must be kept out
of the system.) Te materials used for pipe fttings must be com-
patible with the materials utilized for piping. Fittings should
slope in the direction of fow and have smooth interior surfaces
without ledges, shoulders, or reductions that may obstruct the
fow in piping.
Drains specifed with cast-iron or PVC bodies should be suit-
able for most installations. Where extra corrosion resistance is
required, high-silica cast iron, polypropylene, borosilicate glass,
stainless steel, galvanized iron, or other acid-resisting material
should be selected. Where a sediment bucket is used, it should
be bronze or galvanized or stainless steel. Enameled sediment
buckets are impractical because they chip when cleaned.
In the selection of materials for top surfaces, such as grates,
where foor drains are visible in fnished areas, appearance is a
prime consideration. As cast iron will rust and galvanizing and
chrome plating will eventually be worn of by trafc, the pre-
ferred material is solid, cast nickel-bronze, which maintains its
attractive appearance. In a swimming pool, however, chlorine
necessitates the use of chlorine-resistant materials. For large
grates that will be subject to hand-truck or forklift trafc, a duc-
tile iron grate with or without a nickel-bronze veneer is recom-
mended.
Polished brass or bronze for foor service has the disadvan-
tage of discoloring unless there is constant trafc over it. Cast
aluminum has also been found inadequate for certain foor-
service applications due to excessive oxidation and its inability
to withstand abrasion.
jOINING METHODS
Drain and cleanout outlets are manufactured in fve basic
types:
1. Inside caulk. In this arrangement, the pipe extends up into
the drain body and oakum is packed around the pipe tightly
against the inside of the outlet. Molten lead is then poured
into this ring and later stamped or caulked to correct for lead
shrinkage. Current installation methods use a fexible gasket
for a caulking material. See Figure 9.
2. Spigot outlet. Tis type utilizes the caulking method as out-
lined above, except that the spigot outlet is caulked into the
hub or bell of the downstream pipe or ftting. See Figure
1-10.
3. Push-seal gasketed outlet. Tis type utilizes a neoprene gasket
similar to standard ASTM C564 neoprene gaskets approved
for hub-and-spigot, cast-iron soil pipe. A ribbed neoprene
gasket is applied to the accepting pipe, thus allowing the
drain outlet to be pushed onto the pipe.
4. No-hub. Tis type utilizes a spigot (with no bead on the end)
that is stubbed into a neoprene coupling with a stainless-steel
bolting band (or other type of clamping device), which, in
turn, accepts a downstream piece of pipe or headless ftting.
See Figure 11.
5. IPS or threaded. Tis type is a tapered female thread in the
drain outlet designed to accept the tapered male thread of
a downstream piece of pipe or ftting. See Figure 12.
Figure 9 Inside-Caulk Drain Body
Figure 10 Spigot-Outlet Drain Body
Figure 12 IPS or Threaded Outlet Drain Body
Figure 11 No-Hub-Outlet Drain Body
12 Plumbing Systems & Design NOVEMBER 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Sanitary Drainage Systems
NOISE TRANSMISSION
Avoiding direct metal-to-metal connections may reduce noise
transmission along pipes. Using heavier materials generally
reduces noise transmission through pipe walls. Isolating piping
with resilient materials, such as rugs, belts, plastic, or insulation
may reduce noise transmission to the building. See Table 9 for
relative noise-insulation absorption values.
BUILDING SEWER INSTALLATION
Te installation of building sewers is very critical to the opera-
tion of the sewer. Inadequate bedding in poor soils may allow
the sewer to settle, causing dips and low points in the sewer.
Te settlement of sewers interrupts fow, diminishes minimum
cleansing velocity, reduces capacity, and creates a point where
solids can drop out of suspension and collect.
Te following are some guidelines for installing building
sewers:
1. Compacted fll. Where natural soil or compacted fll exists,
the trench must be excavated in alignment with the proposed
pitch and grade of the sewer. Depressions need to be cut out
along the trench line to accept the additional diameter at
the piping joint or bell hub. A layer of sand or pea gravel is
placed as a bed in the excavated trench because it is easily
compacted under the pipe, allowing more accurate align-
ment of the pipe pitch. Te pipe settles into the bed and is
frmly supported over its entire length.
2. Shallow fll. Where shallow amounts of fll exist, the trench
can be over-excavated to accept a bed of sand, crushed stone,
or similar material that is easily compacted. Bedding should
be installed in lifts (layers), with each lift compacted to en-
sure optimum compaction of the bedding. Te bed must be
compacted in alignment with the proposed pitch and grade
of the sewer. It is recommended that pipe joints or bell hub
depressions be hand-prepared due to the coarse crushed
stone. Te soil-bearing weight determines trench widths and
bedding thickness.
3. Deep fll. Where deep amounts of fll exist, the engineer
should consult a geotechnical engineer, who will perform
soil borings to determine the depths at which soils with
proper bearing capacities exist. Solutions include compact-
ing existing fll by physical means or removing existing fll
and replacing it with crushed stone structural fll.
4. Backflling. Backflling of the trench is just as critical as the
compaction of the trench bed and the strength of existing
soils. Improper backfll placement can dislodge pipe and
cause uneven sewer settlement, with physical depressions
in the surface. Te type of backfll material and compac-
tion requirements need to be reviewed to coordinate with
the type of permanent surface. Landscaped areas are more
forgiving of improper backfll placement than hard surface
areas such as concrete or bituminous paving.
Care must be taken when using mechanical means to com-
pact soils above piping. Mechanical compaction of the frst layer
above the pipe by vibrating or tamping devices should be done
with caution. Compacting the soil in 6-in. (150-mm) layers is
recommended for a good backfll.
Proper sewer bedding and trench backfll will result in an instal-
lation that can be counted upon for long, trouble-free service.
SANITATION
All drains should be cleaned periodically, particularly those
in markets, hospitals, food-processing areas, animal shelters,
morgues, and other locations where sanitation is important.
Where sanitation is important, an acid-resisting enameled
interior in foor drains is widely accepted. Te rough surfaces
of either brass or iron castings collect and hold germs, fungus-
laden scum, and fne debris that usually accompany drain
waste. Tere is no easy or satisfactory way to clean these rough
surfaces. Te most practical approach is to enamel them. Te
improved sanitation compensates for the added expense. How-
ever, pipe threads cannot be cut into enameled metals because
the enameling will chip of in the area of the machining. Also,
pipe threads themselves cannot be enameled; therefore, caulked
joints should be specifed on enameled drains. Most adjustable
foor drains utilize threaded adjustments. Te drains cannot be
enameled because of this adjusting thread. However, there are
other adjustable drains that use sliding lugs on a cast thread and
may be enameled.
Another point to remember is that a grate or the top ledge of
a drain can be enameled, but the enamel will not tolerate traf-
fc abrasion without showing scratches and, eventually, chip-
ping. Te solution to this problem is a stainless-steel or nickel-
bronze rim and grate over the enameled drain body, a common
practice on indirect waste receptors, sometimes referred to as
foor sinks. Specifers seem to favor the square, indirect waste
receptor, but the round receptor is easier to clean and has better
anti-splash characteristics. For cases where the choice of square
or round is infuenced by the foor pattern, round sinks with
square tops are available.
In applications such as hospital morgues, cystoscopic rooms,
autopsy laboratories, slaughterhouses, and animal dens, the
enameled drain is ftted with a fushing rim. Tis is most advis-
able where blood or other objectionable materials might cling
to the sidewalls of the drain.
Where the waste being drained can create a stoppage in the
trap, a heel inlet on the trap with a fushing connection is rec-
ommended in addition to the fushing rim, which merely keeps
the drain sides clean. (Tis option may not be allowed by cer-
tain codes.) A 2-in. (50-mm) trap fushes more efectively than
a 3-in. (80-mm) trap because it allows the fushing stream to
drill through the debris rather than completely fush it out. A
Table 9 Relative Properties of Selected Plumbing
Materials for Drainage Systems
Materials
Noise
Absorption
Corrosion
Resistance
a
ABS Fair Good
Cast iron Excellent Good
Clay
b
Excellent
Concrete
c
Fair
d
Copper Fair Good
Glass borosilicate
b
Excellent
Polypropylene Fair Excellent
PVC Fair Excellent
Silicon iron
c
Excellent
Steel, galvanized Good Fair
a
This refers to domestic sewage. Consult manufacturer for resistance to particular
chemicals.
b
Since these materials are used only aboveground for chemical waste systems,
this is not applicable.
c
This material is usually allowed only belowground.
d
Susceptible to corrosion from hydrogen sulfde gas.
NOVEMBER 2007 Plumbing Systems & Design 13
valve in the water line to the drain is the best way to operate the
fushing-rim drain. Flush valves have been used and save some
water; however, they are not as convenient or efective as a shut-
of valve. In any fushing water-supply line to a drain, a vacuum
breaker installed according to code must be provided.
KITCHEN AREAS
When selecting kitchen drains, the designer must know the
quantity of liquid and solid waste the drains will be required
to accept, as well as which equipment emits waste on a regular
basis and which produces waste only by accidental spillage.
Floor-cleaning procedures should be ascertained to deter-
mine the amount of water used. If any amount of solid waste is
to be drained, receptors must be specifed with removable sedi-
ment buckets made of galvanized or stainless steel. Also, there
must be enough vertical clearance over these drains to conve-
niently remove the sediment buckets for cleaning.
Many kitchen planners mount kitchen equipment on a 5-in.
(125-mm) curb. Placing the drain on top of the curb and under
the equipment makes connection of indirect drain lines dif-
cult and the receptor inaccessible for inspection and cleaning.
Mounting the receptor in front of the curb takes up foor space,
and the myriad of indirect drains that discharge into it create
a potential hazard for employees who may trip over them. Te
solution requires close coordination between the engineer and
the kitchen designer. Figure 1-8 shows an arrangement whereby
any spillage in front of the curb can be drained by half of the
receptor, while indirect drains are neatly tucked away.
Where equipment is on the foor level and an indirect waste
receptor must be provided under the equipment, a shallow
bucket that can easily be removed is recommended.
WATERPROOFING
Whenever a cast-iron drain is cemented into a slab, separation
due to expansion and contraction occurs and creates several
problems. One is the constant wet area in the crevice around
the drain that promotes mildew odor and the breeding of bac-
teria. Seepage to the foor below is also a possibility. A seepage
or fashing fange can correct this problem. Weep holes in the
fashing fange direct moisture into the drain. Also, this fange
accepts membrane material and, when used, the fashing ring
should lock the membrane to the fange.
One prevalent misconception about the fashing fange is that
it can have weep holes when used with cleanouts. In this case,
there can be no weep holes into the cleanout to which the mois-
ture can run. Weep holes should also be eliminated from the
fashing fanges of drains, such as refection-pool drains, where
an overfow standpipe to maintain a certain water level shuts of
the drain entrance.
Te term non-puncturing, used in reference to membrane-
fashing, ring-securing methods, is now obsolete, as securing
bolts have been moved inboard on fashing L fanges and the
membrane need not be punctured to get a seal. Of the various
arrangements, this bolting method allows the greatest squeeze
pressure on the membrane.
FLOOR LEVELING
A major problem in setting foor drains and cleanouts occurs
when the concrete is poured level with the top of the unit, ignor-
ing the fact that the addition of tile on the foor will cause the
drain or cleanout to be lower than the surrounding surface. To
solve the problem, cleanouts can be specifed with tappings in
the cover rim to jack the top part of the cleanout up to the fn-
ished foor level. Floor drains can be furnished with adjustable
tops to attain an installation that is fush with the fnished foor.
THERMAL EXPANSION
When excessive thermal expansion is anticipated, pipe move-
ment should be controlled to avoid harmful changes in slope or
damage. Anchoring, using expansion joints, or using expansion
loops or bends may do this. When anchoring, avoid excessive
stress on the structure and the pipe. Piping or mechanical engi-
neering handbooks should be consulted if stress analysis is to
be performed due to excessive stresses or to the difering expan-
sion characteristics of materials.
PROTECTION FROM DAMAGE
Following are some common types of damage to anticipate and
some methods of protection:
Hazard Protection
Abrasion Plastic or rubber sleeves. Insulation where copper
pipe leaves slab.
Condensation Insulation on piping.
Corrosion See Plumbing Engineering Design Handbook, Vol. 1,
Ch. 8: Corrosion.
Earth loads Stronger pipe or pipe sleeves.
Expansion and
contraction
Flexible joints, loops, swing joints, or ofsets.
Fire Building construction around pipe. Some
jurisdictions require metal piping within 2 ft (0.6 m)
of an entry into a frewall. Must maintain fre ratings.
Heat Keeping thermoplastic pipe away from sources of
heat or using insulation.
Nails Using ferrous pipe, steel sleeves, steel plates, or space
pipe away from possible nail penetration zone.
Seismic Bracing pipe and providing fexible joints at the
connection between piping braced to walls or
structure and piping braced to the ceiling and
between stories (where there will be diferential
movements).
Settlement Sleeves or fexible joints. When embedded in
concrete, covering with three layers of 15-lb (6.8-kg)
felt.
Sunlight Protecting thermoplastic pipe by insulation and
jacket or shading to avoid warping.
Vandals Installing pipe above reach or in areas protected by
building construction. Piping needs to be supported
well enough to withstand 250 lb (113.4 kg) hanging
on the moving pipe.
Wood Shrinkage Providing slip joints and shrinkage clearance for
pipe when wood shrinks. Approximately
5
8 in. (16
mm)/foor is adequate for usual frame construction,
based on 4% shrinkage perpendicular to wood grain.
Shrinkage along the grain does not usually exceed
0.2%.
ALTERNATE SANITARY SYSTEMS
Te design and installation of alternative engineered plumbing
systems is permitted in all codes. A licensed professional engi-
neer who is responsible for the proper operation of the system
must design them. Te most important consideration is that if an
alternative system is contemplated, submission to, and approval
by, the authorities having jurisdiction must be obtained. In order
to expedite approval, the following is suggested:
1. Indicate on the design documents that the plumbing system,
or parts thereof, is an alternative design.
14 Plumbing Systems & Design NOVEMBER 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Sanitary Drainage Systems
2. Submit enough technical data to support the proposed al-
ternative design and prove the system conforms to the intent
of the code. Tis shall include suitability for the intended
purpose, strength, equivalent level of performance compared
to traditional installations, safety, and quality of materials.
3. Te design documents shall include foor plans, riser dia-
grams, and an indication of the proposed fow.
4. Assurance that manufacturers installation instructions will
be adhered to.
5. If approval is given, the permit and all
construction applications shall indicate
an alternative engineered design is part
of the approved installation.
Te alternative systems are characterized
by, but not limited to, using a single stack
for both sanitary and vent or no vent at all.
One exception is a conventional drainage,
reduced vent system. All of the following
described systems have been successfully
used in the United States and in other parts
of the world for many years and have proven
efective in actual use.
All of the alternative systems to be dis-
cussed have combined sanitary and vent.
Because it is considered appropriate, they
have been included in the sanitary drainage
system chapter.
SOVENT SYSTEM
Te Sovent system was developed in 1959
in Switzerland. It is a patented, single-stack,
combination drainage and vent system that
uses a single stack instead of a conventional
two-pipe drainage and vent stack. Te Sovent
system uses copper pipe and is suitable
only for multistory buildings because it will
allow substantial economy in piping instal-
lation. Although installed in many countries
throughout the world, it remains an alter-
native, unconventional system with only
limited usage in the United States. It shall
conform to ANSI B-16.45 and CISMA Stan-
dard 177. It is not the intent of this chapter to
provide specifc design criteria for a Sovent
system, but rather to discuss the individual
component characteristics that will enable
a plumbing engineer to obtain a working
knowledge of how the Sovent system works.
A typical Sovent-Stack system is illustrated in
Figure 13.
Te entire Sovent system consists of three
principal parts: copper DWV piping for all
branch wastes and stacks, an aerator ftting at
each foor level where the branch waste line
connects to the stack, and a deaerator ftting
at the base of a stack where a stack enters the
house drain.
Te starting point is the horizontal soil and
waste branches. Te fxture units and branch
sizes are similar to those fgures found in
conventional systems. Te maximum fxture units that may be
connected to a branch or stack are also similar to that of conven-
tional systems. Branch sizes must be increased one size where
the following exists:
1. A second vertical drop or a vertical drop of more than 3 ft
(0.9 m) requires an increase in the downstream side of the
connection.
Figure 13 (A) Traditional Two-Pipe System, (B) Typical Sovent Single-Stack Plumbing System.
(A)
(B)
NOVEMBER 2007 Plumbing Systems & Design 15
2. When three 90-degree changes in direction occur in a hori-
zontal branch, the horizontal branch shall be increased in
size at the upstream side of the third change.
3. When a branch serves two water closets and one or more ad-
ditional fxtures, the soil line shall be increased to 4 in. (100
mm) at the point where one water closet and one additional
fxture are connected.
4. When a soil branch exceeds 12 ft (3.7 m) in horizontal
length.
5. When a waste line exceeds 15 ft (4.6 m) in horizontal
length.
Stacks must be carried full size through the roof. Two stacks
can be connected at the top above the highest fxture. Two stacks
may also be combined at the bottom prior to entering the build-
ing drain. Te size is based on the total fxture units. Fixtures
may be connected into a horizontal ofset in a stack below the
deaerator ftting.
An aerator ftting is required at each level where a soil branch,
a waste line the same size as the stack, or a waste branch one size
smaller than the stack is connected. It consists of an upper stack
inlet, a mixing chamber, and a bafe in the center of the ftting.
Tis provides a chamber where the fow from the branches may
gradually mix smoothly with the air and liquid already fow-
ing in the stack. It also limits the turbulence and velocity of the
entering water. A 2-in. (50-mm) horizontal branch may enter the
stack with no ftting. Tere are two basic styles of aerator ftting
that meets the needs of most design conditions: the double-side
entry ftting and the single-entry ftting. Face entry and top entry
are used in special cases.
A deaerator ftting is required at the bottom of a stack and is
designed to overcome the tendency of the falling waste to build
up excessive back pressure at the bottom of the stack when the
fow is decelerated by the bend into the horizontal drain. It con-
sists of an air separation chamber, a nose piece, a pressure relief
outlet at the top connected to the building drain, and a stack
outlet at the bottom. Te purpose of the deaerator is to separate
the air fow from the stack and ensure the smooth fow of liquid
into the building drain and to relieve the positive pressure gen-
erated at the stacks base. Te confguration of the ftting causes
part of the air falling with the liquid to fow through the pres-
sure relief line, and the remainder of the air goes directly into
the building drain.
Tere is great importance in explaining the special require-
ments of the Sovent system to the installing contractor. It is
probable the contractor is unfamiliar with this system and a
complete explanation will be necessary. Te engineer should
make regular inspections of the project to assure the design
conditions are met. A complete set of contract documents shall
be provided to the owner to allow proper alteration or expan-
sion of the project in the future.
For additional information and specifc sizing contact the
Copper Development Association.
SINGLE-STACK SYSTEM
Te single-stack system is a combination drainage and vent
system consisting of a single stack instead of conventional sepa-
rate drainage and vent stacks. Tis drainage system is one where
the drainage stack shall serve as both a single-stack drainage
and vent system when properly sized. Te relief of internal air
pressure depends on making the one-pipe system larger than
that required for drainage purposes alone. Te drainage stack
and branch piping shall be considered as vents for the drainage
system as a whole. Although the pipe sizing is larger in a single-
stack system than in a conventional one, installation savings are
achieved by reducing the amount of vent piping required.
Te major components of the one pipe system are oversize,
unvented S traps instead of the conventionally sized and vented
P traps and fxtures that allow water to run of after the tap is
closed to fll the traps with water to maintain the trap seal. Te
trap arm length is limited to reduce any suction buildup, and the
stack is oversized to limit the internal air pressure and vacuum
buildup.
Often referred to as the Philadelphia code, this unconven-
tional system has successfully operated for more than 100 years
with no problems. Consideration has been made by code bodies
to include this system as an engineered design, which allows this
to be used providing an engineer has designed it in accordance
with code. For further information, contact the Philadelphia
building department. A riser diagram of a typical Philadelphia
System is illustrated in Figure 13.
REDUCED-SIzE VENTING
In 1974, the National Bureau of Standards (NBS) conducted a
laboratory study of one-story and split-level experimental drain-
age systems where the vents varied from one to six pipes smaller
than those for conventional systems. Tey showed satisfactory
hydraulic and pneumatic performance under various loading
conditions. At the same time, the 10-story wet vent system at
the Stevens Building Technology Research Laboratory had been
modifed by reducing the vents one to three pipe sizes in accor-
dance with the plans and specifcations of the NBS and reducing
the size of the vents. Te results also indicated that the vents in
a two-story housing unit can safely be made smaller than pres-
ently allowed without jeopardizing the trap seals.
Tis system may allow economies of pipe size in the venting
design of low-rise residential buildings, although this particu-
lar system has not been accepted by authorities. It is limited to
special conditions and requires the vent pipes be of a material
such as copper or plastic that will resist the buildup of products
of corrosion.
VACUUM DRAINAGE SYSTEM
Vacuum drainage operates on the principal of having the major-
ity of the system under a continuous vacuum. Te system is
proprietary and is made by various manufacturers. Te difer-
ent manufacturers have diferent names for devices performing
similar operations, so generic identifcation is used. Tere are
various designs capable of sanitary and waste disposal, either
separate or in combination, and are used for various projects
such as prisons, supermarkets, and ships. Tere is no direct con-
nection from the sanitary waste to the vacuum system. Te one
big advantage is that piping is installed overhead and no pipe is
required to be placed underground.
Te system consists of three basic components: a vacuum
network of piping and other devices that collects and transports
waste from its origin, vacuum generation pumps, and a vacuum
interface device at the point of origin that isolates the vacuum
piping from atmospheric pressure. When the system is to serve
water closets, the water closets must be purpose made, designed
to rinse and refll with gallon (2.2 L) of water.
Te piping network for a vacuum waste system is held under
a constant vacuum between 12 and 18 in. of mercury (in Hg)
16 Plumbing Systems & Design NOVEMBER 2007 PSDMAGAZINE.ORG
CONTINUING EDUCATION: Sanitary Drainage Systems
(4065 kPa) and is generally fabricated from PVC, copper, or
other nonporous, smooth-bore material. Horizontal piping shall
slope at a rate of 1/8 in. per foot (1.18 mm) toward the vacuum
center. Tis piping slope is just as it is in conventional systems. If
this slope cannot be maintained, the traps created in the piping
runs when routed around obstacles would be cleared because of
the diferential pressure that exists between the vacuum center
and the point of origin. Te discharge of the piping system is
into the waste storage tanks.
Te vacuum generation system includes the vacuum pumps
that create a vacuum in the piping and storage tanks that col-
lect and discharge the waste into the sewer system. Te vacuum
pumps run only on demand and redundancy is provided. Tey
also have sewage pumps that pump the drainage from the stor-
age tank(s) into the sewer.
Te vacuum interface is diferent for sanitary drainage than
for clear waste similar to that of supermarkets. Water closet
and gray water waste are separate. Te vacuum toilets operate
instantly upon fushing. When a vacuum toilet is cycled, a dis-
charge control panel assembly is activated sending the discharge
to the tank. A valve acts as an interface between the vacuum and
the atmosphere controls gray water. It is designed to collect a
given amount of the water and then activate, sending the drain-
age into the tank. Te tank will discharge into the sewer when a
predetermined level is reached.
When clear water is discharged from a project like a super-
market, the water from cases, etc. goes into an accumulator.
When a controller senses sufcient waste is present, it opens
the normally closed extraction valve, which separates the atmo-
spheric pressure from the vacuum, and removes the waste from
the accumulator.
Because the vacuum toilets use 0.5 gallon/fush as compared
to 3.5 gallons/fush (1.9 L to 13 L) from a conventional system,
the holding tanks could be smaller. Tere is also a fush control
panel designed to provide all the control functions associated
with vacuum toilets. Te control panel consists of a fush valve,
fush controller, water valve, and vacuum breaker. All controls
are pneumatically operated. Te fush controller controls the
opening of the fush valve and the rinse valve as well as the
duration of the time the fush valve is open.
REFERENCES
1. Daugherty, Robert L., Joseph B. Franzini, and E. John
Finnemore. 1985. Fluid mechanics with engineering applica-
tions. 8th ed. New York: McGraw-Hill.
2. Dawson, F.M., and A.A. Kalinske. 1937. Report on hydraulics
and pneumatics of plumbing drainage systems. State Univer-
sity of Iowa Studies in Engineering, Bulletin no. 10.
3. Wyly and Eaton. 1950. National Bureau of Standards, Housing
and Home Finance Agency.
NOVEMBER 2007 Plumbing Systems & Design 17
About This Issues Article
The November 2007 continuing education article is Sani-
tary Drainage Systems, Chapter 1 of ASPEs Plumbing Engi-
neering Design Handbook Volume 2: Plumbing Systems.
The purpose of the sanitary drainage system is to remove ef-
fuent discharged from plumbing fxtures and other equip-
ment to an approved point of dis posal. A sanitary drainage
system generally consists of horizontal branches, vertical
stacks, a building drain inside the building, and a building
sewer from the building wall to the point of disposal. The
discussion in this chapter cen ters only on the design of
drain and waste systems.
You may locate this article at www.psdmagazine.org. Read
the article, complete the following exam, and submit your
answer sheet to the ASPE ofce to potentially receive 0.1 CEU.
P
S
D
1
4
2
Continuing Education from Plumbing Systems & Design
Kenneth G.Wentink, PE, CPD, and Robert D. Jackson
CE QuestionsSanitary Drainage Systems (PSD 142)
1. A vertical pipe that carries away clear water waste
from equipment and non-sanitary fxtures is called a
_________.
a. sanitary stack
b. soil stack
c. waste stack
d. water stack
2. The generally accepted pressure in a sanitary drainage
system is _________.
a. +/ 0.1 inch of water column
b. +/ 1 inch of water column
c. +/ 10 inches of water column
d. +/ 100 inches of water column
3. Who originally proposed using drainage fxture units
to represent a fxtures load-producing efect on the
plumbing system?
a. F.M. Dawson
b. Wyly and Eaton
c. Roy B. Hunter
d. none of the above
4. What is the recommended drainage fxture unit load for
a single lavatory?
a. 1, b. 2, c. 3, d. 4
5. Which common formula for calculating fow in pipes is
meant for open-channel fow?
a. Hazen and Williams
b. Manning
c. Darcy-Weisbach
d. none of the above
6. Which of the following is designed to transport sanitary
waste and larger solids suspended in the efuent?
a. storm sewer
b. sump pump
c. ejector pump
d. manhole
7. Cleanouts should be provided _________.
a. at the base of all stacks
b. at every change in direction greater than 45 degrees
c. at the roof stack terminal
d. all of the above
8. Which of the following is not a basic foor drain
component?
a. sediment bucket
b. removable grate
c. air-admittance valve
d. cast drain body with sump
9. In a basic foor drain assembly, the _________ pre vents
water from passing around the drain to the area below.
a. fashing ring
b. sediment bucket
c. grate
d. strainer
10. The recommended material for a sediment bucket is
_________.
a. bronze
b. galvanized steel
c. stainless steel
d. all of the above
11. Which of the following pipe materials ofers excellent
noise absorption?
a. ABS
b. cast iron
c. PVC
d. galvanized steel
12. The single-stack system is also referred to as the
_________ system.
a. Sovent
b. Philadelphia
c. vacuum drainage
d. none of the above
Do you fnd it difcult to obtain continuing education units (CEUs)?
Trough this special section in every issue of PS&D, ASPE can help
you accumulate the CEUs required for maintaining your Certifed in
Plumbing Design (CPD) status.
Now Online!
Te technical article you must read to complete the exam is located
at www.psdmagazine.org. Te following exam and application form
also may be downloaded from the website. Reading the article and
completing the form will allow you to apply to ASPE for CEU credit.
For most people, this process will require approximately one hour. If
you earn a grade of 90 percent or higher on the test, you will be notifed
that you have logged 0.1 CEU, which can be applied toward the CPD
renewal requirement or numerous regulatory-agency CE programs.
(Please note that it is your responsibility to determine the acceptance
policy of a particular agency.) CEU information will be kept on fle at
the ASPE ofce for three years.
Note: In determining your answers to the CE questions, use only the material
presented in the corresponding continuing education article. Using information
from other materials may result in a wrong answer.
18 Plumbing Systems & Design NOVEMBER 2007 PSDMAGAZINE.ORG
P
S
d
1
4
3
Recirculating
Domestic
Hot Water
Systems
Continuing education from Plumbing Systems & Design
Haig demergian, Pe, CPd
DECEMBER 2007
PSDMAGAZINE.ORG
INTRODUCTION
It has been determined through feld studies that the correct sizing
and operation of water heaters depend on the appropriateness of the
hot water maintenance system. If the hot water maintenance system
is inadequate, the water heater sizing criteria are wrong and the
temperature of the hot water distributed to the users of the plumb-
ing fxtures is below acceptable standards. Additionally, a poorly
designed hot water maintenance system wastes large amounts of
energy and potable water and creates time delays for those using
the plumbing fxtures. Tis chapter addresses the criteria for estab-
lishing an acceptable time delay in delivering hot water to fxtures
and the limitations of the length between a hot water recirculation
system and plumbing fxtures. It also discusses the temperature
drop across a hot water supply system, types of hot water recircula-
tion system, and pump selection criteria, and gives extensive infor-
mation on the insulation of hot water supply and return piping.
BaCkgROUND
In the past, the plumbing engineering community considered the
prompt delivery of hot water to fxtures either a requirement for a
project or a matter of no concern. Te plumbing engineers decision
was based primarily on the type of facility under consideration and
the developed length from the water heater to the farthest fxture.
Previous reference material and professional common practices
have indicated that, when the distance from the water heater to the
farthest fxture exceeds 100 ft (30.48 m) water should be circulated.
However, this recommendation is subjective, and, unfortunately,
some engineers and contractors use the 100-ft (30.48-m) criterion
as the maximum length for all uncirculated, uninsulated, dead-end
hot water branches to fxtures in order to cut the cost of hot
water distribution piping. Tese long, uninsulated, dead-end
branches to fxtures create considerable problems, such as a
lack of hot water at fxtures, inadequately sized water heater
assemblies, and thermal temperature escalation in showers.
Te 100-ft (30.48-m) length criterion was developed in 1973
after the Middle East oil embargo, when energy costs were the
paramount concern and water conservation was given little
consideration. Since the circulation of hot water causes a loss
of energy due to radiation and convection in the circulated
system and such energy losses have to be continually replaced
by water heaters, the engineering community compromised
between energy loss and construction costs and developed
the 100-ft (30.48-m) maximum length criterion.
LeNgTh aND TIme CRITeRIa
Recently, due to concern about not only energy conservation
but also the extreme water shortages in parts of the country, the
100-ft (30.48-m) length criteria has changed. Water wastage
caused by the long delay in obtaining hot water at fxtures has
become as critical an issue as the energy losses caused by hot
water temperature maintenance systems. To reduce the wast-
ing of cooled hot water signifcantly, the engineering com-
munity has reevaluated the permissible distances for uncir-
culated, dead-end branches to periodically used plumbing fxtures.
Te new allowable distances for uncirculated, dead-end branches
represent a trade-of between the energy utilized by the hot water
maintenance system and the cost of the insulation, on the one
hand, and the cost of energy to heat the excess cold water makeup,
the cost of wasted potable water, and extra sewer surcharges, on the
other hand. Furthermore, engineers should be aware that various
codes now limit the length between the hot water maintenance
system and plumbing fxtures. Tey also should be aware of the
potential for liability if an owner questions the adequacy of their
hot water system design.
What are reasonable delays in obtaining hot water at a fxture?
For anything beside very infrequently used fxtures (such as those in
industrial facilities or certain fxtures in ofce buildings), a delay of
0 to 10 sec is normally considered acceptable for most residential
occupancies and public fxtures in ofce buildings. A delay of 11 to
30 sec is marginal but possibly acceptable, and a time delay longer
than 31 sec is normally considered unacceptable and a signifcant
waste of water and energy. Terefore, when designing hot water
systems, it is prudent for the designer to provide some means of
getting hot water to the fxtures within these acceptable time limits.
Normally this means that there should be a maximum distance of
approximately 25 ft (7.6 m) between the hot water maintenance
system and each of the plumbing fxtures requiring hot water, the
distance depending on the water fow rate of the plumbing fxture
at the end of the line and the size of the line. (See Tables 1, 2, and 3.)
Te plumbing designer may want to stay under this length limita-
tion because the actual installation in the feld may difer slightly
from the engineers design, and additional delays may be caused
Recirculating Domestic Hot
Water Systems
Reprinted from Domestic Water Heating Design Manual, Second Edition, Chapter 14: Recirculating Domestic Hot Water Systems.
American Society of Plumbing Engineers , 2003.
2 Plumbing Systems & Design DECEMBER 2007 PSDMAGAZINE.ORG
CONTINUINg eDUCaTION
Table 1 Water Contents and Weight of Tube or Piping per Linear Foot
Nominal
Diameter
Copper Pipe
Type L
Copper Pipe
Type M
Steel Pipe
Schedule 40
CPVC Pipe
Schedule 40
(in.)
a
Water
(gal/ft)
Wgt.
(lb/ft)
Water
(gal/ft)
Wgt.
(lb/ft)
Water
(gal/ft)
Wgt.
(lb/ft)
Water
(gal/ft)
Wgt.
(lb/ft)
0.012 0.285 0.013 0.204 0.016 0.860 0.016 0.210
0.025 0.445 0.027 0.328 0.028 1.140 0.028 0.290
1 0.043 0.655 0.045 0.465 0.045 1.680 0.045 0.420
1 0.065 0.884 0.068 0.682 0.077 2.280 0.078 0.590
1 0.093 1.14 0.100 0.940 0.106 2.720 0.106 0.710
a
Pipe sizes are indicated for mild steel pipe sizing.
Table 1(M) Water Contents and Weight of Tube or Piping per Meter
Nominal
Diameter
Copper Pipe
Type L
Copper Pipe
Type M
Steel Pipe
Schedule 40
CPVC Pipe
Schedule 40
(mm)
a
Water
(L)
Wgt.
(kg)
Water
(L)
Wgt.
(kg)
Water
(L)
Wgt.
(kg)
Water
(L)
Wgt.
(kg)
DN15 0.045 0.129 0.049 0.204 0.061 0.390 0.061 0.099
DN20 0.095 0.202 0.102 0.328 0.106 0.517 0.106 0.132
DN25 0.163 0.297 0.170 0.465 0.170 0.762 0.170 0.191
DN32 0.246 0.401 0.257 0.682 0.291 1.034 0.295 0.268
DN40 0.352 0.517 0.379 0.940 0.401 1.233 0.401 0.322
a
Pipe sizes are indicated for mild steel pipe sizing.
by either the routing of the pipe or other problems. Furthermore,
with the low fxture discharge rates now mandated by national and
local laws, it takes considerably longer to obtain hot water from
non-temperature maintained hot water lines than it did in the past,
when fxtures had greater fow rates. For example, a public lavatory
with a 0.50 or 0.25 gpm (0.03 or 0.02 L/sec) maximum discharge
rate would take an excessive amount of time to obtain hot water
from 100 ft (30.48 m) of uncirculated, uninsulated hot water piping.
(See Table 3.) Tis table gives conservative approximations of the
amount of time it takes to obtain hot water at a fxture. Te times
are based on the size of the line, the fxture fow rate, and the times
required to replace the cooled of hot water, to heat the pipe, and to
ofset the convection energy lost by the insulated hot water line.
ResULTs Of DeLays IN DeLIveRINg hOT WaTeR TO
fIxTURes
As mentioned previously, when there is a long delay in obtaining
hot water at the fxture, there is signifcant wastage of potable water
as the cooled hot water supply is simply discharged down the drain
unused. Furthermore, plumbing engineers concerned about total
system costs should realize that the cost of this wasted, previously
heated water must include: the original cost for obtaining potable
water, the cost of previously heating the water, the fnal cost of the
waste treatment of this excess potable water, which results in larger
sewer surcharges (source of supply to end disposal point), and the
cost of heating the new cold water to bring it up to the required tem-
perature. Furthermore, if there is a long delay in obtaining hot water
at the fxtures, the faucets are turned on for long periods of time to
bring the hot water supply at the fxture up to the desired tempera-
ture. Tis can cause the water heating system to run out of
hot water and make the heater sizing inadequate, because
the heater is unable to heat all the extra cold water brought
into the system through the wastage of the water discharged
down the drain. In addition, this extra cold water entering
the hot water system reduces the hot water supply tempera-
ture. Tis exacerbates the problem of insufcient hot water
because to get a proper blended temperature more lower
temperature hot water will be used to achieve the fnal mixed
water temperature. (See Chapter 1, Table 1.1.) Additionally,
this accelerates the downward spiral of the temperature of
the hot water system.
Another problem resulting from long delays in getting hot
water to the fxtures is that the fxtures operate for longer than
expected periods of time. Terefore, the actual hot water
demand is greater than the demand normally designed for.
Terefore, when sizing the water heater and the hot water
piping distribution system, the designer should be aware
that the lack of a proper hot water maintenance system can
seriously impact the required heater size.
meThODs Of DeLIveRINg ReasONaBLy PROmPT
hOT WaTeR sUPPLy
Hot water maintenance systems are as varied as the imagina-
tions of the plumbing engineers who create them. Tey can
be grouped into three basic categories, though any actual
installation may be a combination of more than one of these
types of system. Te three basic categories are
1. Circulation systems.
2. Self-regulating heat trace systems.
3. Point-of-use water heaters (include booster water heat-
ers).
CirCulation SyStemS for CommerCial, induStrial,
and large reSidential ProjeCtS
A circulation system is a system of hot water supply pipes
and hot water return pipes with appropriate shutof valves,
balancing valves, circulating pumps, and a method of controlling
the circulating pump. Te diagrams for six basic circulating systems
are shown in Figures 1 through 6.
Self-regulating Heat traCe
Over approximately the last 20 years, self-regulating heat trace has
come into its own because of the problems of balancing circulated
hot water systems and energy loss in the return piping. For further
discussion of this topic, see Chapter 15.
DECEMBER 2007 Plumbing Systems & Design 3
Table 3 Approximate Time Required to Get Hot Water to a Fixture
Delivery Time (sec)
Fixture Flow
Rate (gpm) 0.5 1.5 2.5 4.0
Piping
Length (ft) 10 25 10 25 10 25 10 25
Copper in. 25 63
a
8 21 5 13 3 8
Pipe in. 48
a
119
a
16 40
a
10 24 6 15
Steel Pipe in. 63
a
157
a
21 52
a
13 31
a
8 20
Sched. 40 in. 91
a
228
a
30 76
a
18 46
a
11 28
CPVC Pipe in. 64
a
159
a
21 53
a
13 32
a
8 20
Sched. 40 in. 95
a
238
a
32 79
a
19 48
a
12 30
Note: Table based on various fxture fow rates, piping materials, and dead-end branch lengths. Calculations are based
on the amount of heat required to heat the piping, the water in the piping, and the heat loss from the piping. Based on
water temperature of 140F and an air temperture of 70F.
a
Delays longer than 30 sec are not acceptable.
Table 3(M) Approximate Time Required to Get Hot Water to a Fixture
Delivery Time (sec)
Fixture Flow
Rate (L/sec) 0.03 0.10 0.16 0.25
Piping
Length (m) 3.1 7.6 3.1 7.6 3.1 7.6 3.1 7.6
Copper DN15 25 63
a
8 21 5 13 3 8
Pipe DN22 48
a
119
a
16 40
a
10 24 6 15
Steel Pipe DN15 63
a
157
a
21 52
a
13 31
a
8 20
Sched. 40 DN20 91
a
228
a
30 76
a
18 46
a
11 28
CPVC Pipe DN15 64
a
159
a
21 53
a
13 32
a
8 20
Sched. 40 DN20 95
a
238
a
32 79
a
19 48
a
12 30
Note: Table based on various fxture fow rates, piping materials, and dead-end branch lengths. Calculations are based
on the amount of heat required to heat the piping, the water in the piping, and the heat loss from the piping. Based on
water temperature of 60C and an air temperture of 21.1C.
a
Delays longer than 30 sec are not acceptable.
Table 2 Approximate Fixture and Appliance Water Flow Rates
Fittings
Maximum Flow Rates
a
GPM L/Sec
Lavatory faucet 2.0 1.3
Public non-metering 0.5 0.03
Public metering 0.25 gal/cycle 0.946 L/cycle
Sink faucet 2.5 0.16
Shower head 2.5 0.16
Bathtub faucets
Single-handle 2.4 minimum 0.15 minimum
Two-handle 4.0 minimum 0.25 minimum
Service sink faucet 4.0 minimum 0.25 minimum
Laundry tray faucet 4.0 minimum 0.25 minimum
Residential dishwasher 1.87 aver 0.12 aver
Residential washing machine 7.5 aver 0.47 aver
a
Unless otherwise noted.
Point-of-uSe HeaterS
Tis concept is applicable when there is a single
fxture or group of fxtures that is located far
from the temperature maintenance system. In
such a situation, a small, instantaneous, point-
of-use water heateran electric water heater, a
gas water heater, or a small under-fxture stor-
age type water heater of the magnitude of 6 gal
(22.71 L)can be provided. (See Figure 7.) Te
point-of-use heater will be very cost-efective
because it will save the cost of running hot water
piping to a fxture that is a long distance away
from the temperature maintenance system. Te
plumbing engineer must remember, however,
that when a water heater is installed there are
various code and installation requirements that
must be complied with, such as those pertain-
ing to T & P relief valve discharge.
Instantaneous electric heaters used in point-
of-use applications can require a considerable
amount of power, and may require 240 or 480
V service.
POTeNTIaL PROBLems IN CIRCULaTeD
hOT WaTeR maINTeNaNCe sysTems
Te following are some of the potential prob-
lems with circulated hot water maintenance
systems that must be addressed by the plumb-
ing designer.
Water VeloCitieS in Hot Water PiPing
SyStemS
For copper piping systems, it is very important
that the circulated hot water supply piping and
especially the hot water return piping be sized
so that the water is moving at a controlled veloc-
ity. High velocities in these systems can cause
pinhole leaks in the copper piping in as short a
period as six months or less.
BalanCing SyStemS
It is extremely important that a circulated hot
water system be balanced for its specifed fows,
including all the various individual loops within
the circulated system. Balancing is required
even though an insulated circulated line usu-
ally requires very little fow to maintain satis-
factory system temperatures. If the individual
hot water circulated loops are not properly bal-
anced, the circulated water will tend to short-
circuit through the closest loops, creating high
velocities in that piping system. Furthermore,
the short-circuiting of the circulated hot water
will result in complaints about the long delays
in getting hot water at the remotest loops. If the
hot water piping is copper, high velocities can
create velocity erosion which will destroy the
piping system.
Because of the problems inherent in manu-
ally balancing hot water circulation systems,
many professionals incorporate factory preset
fow control devices in their hot water systems.
While the initial cost of such a device is higher
than the cost of a manual balancing valve, a
4 Plumbing Systems & Design DECEMBER 2007 PSDMAGAZINE.ORG
CONTINUINg eDUCaTION: Recirculating Domestic hot Water systems
* See text for requirements for strainers.
Fixture 1 Upfeed Hot Water System with Heater at Bottom of System.
Figure 2 Downfeed Hot Water System with Heater at Top of System.
* See text for requirements for strainers.
Figure 3 Upfeed Hot Water System with Heater at Bottom of System.
* See text for requirements for strainers.
preset device may be less expensive when the
feld labor cost for balancing the entire hot
water system is included. When using a preset
fow control device, however, the plumbing
designer has to be far more accurate in select-
ing the control devices capacity as there is no
possibility of feld adjustment. Terefore, if
more or less hot water return fow is needed
during the feld installation, a new fow control
device must be installed and the old one must
be removed and discarded.
iSolating PortionS of Hot Water
SyStemS
It is extremely important in circulated systems
that shutof valves be provided to isolate an
entire circulated loop. Tis is done so that if
individual fxtures need modifcation, their
piping loop can be isolated from the system so
the entire hot water system does not have to
be shut of and drained. Te location of these
shutof valves should be given considerable
thought. Te shutof valves should be acces-
sible at all times, so they should not be located
in such places as the ceilings of locked ofces or
condominiums.
maintaining tHe BalanCe of Hot
Water SyStemS
To ensure that a balanced hot water system
remains balanced after the shutof valves have
been utilized, the hot water return system must
be provided with a separate balancing valve in
addition to the shutof valve or, if the balanc-
ing valve is also used as the shutof valve, the
balancing valve must have a memory stop.
(See the discussion of balancing valves with
memory stops below.) With a memory stop
on the valve, plumbers can return a system to
its balanced position after working on it rather
than have the whole piping system remain
unbalanced, which would result in serious
problems.
ProViding CHeCk ValVeS at tHe endS of
Hot Water looPS
Te designer should provide a check valve on
each hot water return line where it joins other
hot water return lines. Tis is done to ensure
that a plumbing fxture does not draw hot return
water instead of hot supply water, which could
unbalance the hot water system and cause
delays in obtaining hot water at some fxtures.
a delay in oBtaining Hot Water at
dead-end lineS
Keep the delay in obtaining hot water at fx-
tures to within the time (and branch length)
parameters given previously to avoid unhappy
users of the hot water system and to prevent
lawsuits.
fLOW BaLaNCINg DevICes
Te following are the more common types of
balancing device.
DECEMBER 2007 Plumbing Systems & Design 5
Figure 4 Downfeed Hot Water System with Heater at Top of System.
* See text for requirements for strainers.
Note: This piping system increases the developed length of the HW system over the upfeed systems shown in Figures 1 and 3.
* See text for requirements for strainers.
Figure 5 Combination Upfeed and Downfeed Hot Water System with Heater at Bottom of System.
Note: This piping system increases the developed length of the HW system over the downfeed systems shown in Figures 2 and 4.
* See text for requirements for strainers.
Figure 6 Combination Downfeed and Upfeed Hot Water System with Heater at Top of System.
fixed orifiCeS and VenturiS
Tese can be obtained for specifc fow rates and
simply inserted into the hot water return piping system.
(See Figure 8.) However, extreme care should be taken
to locate these devices so they can be removed and
cleaned out, as they may become clogged with the
debris in the water. It is recommended, therefore, that
a strainer with a blowdown valve be placed ahead of
each of these devices. Additionally, a strainer with a
fne mesh screen can be installed on the main water
line coming into the building to help prevent debris
buildup in the individual strainers. Also, a shutof valve
should be installed before and after these devices so
that an entire loop does not have to be drained in order
to service a strainer or balancing device.
faCtory PreSet automatiC floW Control
ValVeS
Te same admonition about strainers and valves
given for fxed orifces and venturis above applies
to the installation and location of these devices. (See
Figure 9.)
floW regulating ValVeS
Tese valves can be used to determine the fow rate
by reading the pressure drop across the valve. Tey
are available from various manufacturers. (See Figure
10.)
BalanCing ValVeS WitH memory StoPS
Tese valves can be adjusted to the proper setting by installing
insertable pressure measuring devices (Petes Plugs, etc.) in the
piping system, which indicate the fow rate in the pipe line. (See
Figure 11.)
sIzINg hOT WaTeR ReTURN PIPINg sysTems aND
ReCIRCULaTINg PUmPs
Te method for selecting the proper size of the hot water return
piping system and the recirculating pump is fairly easy, but it does
require engineering judgment. First, the plumbing engineer has
to design the hot water supply and hot water return piping sys-
tems, keeping in mind the parameters for total developed length,
1
prompt delivery of hot water to fxtures, and velocities in pipe lines.
Te plumbing engineer has to make assumptions about the sizes of
the hot water return piping.
After the hot water supply and hot water return systems are
designed, the designer should make a piping diagram of the hot
water supply system and the assumed return system showing
piping sizing and approximate lengths. From this piping diagram
the hourly heat loss occurring in the circulated portion of the hot
water supply and return systems can be determined. (See Table 4
for minimum required insulation thickness and Table 5 for approx-
imate piping heat loss.)
Next determine the heat loss in the hot water storage tank if one
is provided. (See Table 6 for approximate tank heat loss.) Calculate
the total hot water system energy loss (tank heat loss plus piping
heat loss) in British thermal units per hour (watts). Tis total hot
water system energy loss is represented by q in Equation 1 below.
Note: Heat losses from storage type water heater tanks are not nor-
mally included in the hot water piping system heat loss because
the water heater capacity takes care of this loss, whereas pumped
hot water has to replace the piping convection losses in the piping
system.
(1) q = 60rwcT
[q = 3600rwcT]
where
60 = min/h
3600 = sec/h
q = piping heat loss, Btu/h (kJ/h)
r = fow rate, gpm (L/sec)
w = weight of heated water, lb/gal (kg/L)
c = specifc heat of water, Btu/lb/F (kJ/kg/K)
T = change in heated water temperature (tem-
perature of leaving water minus temperature of
incoming water, represented in this manual as T
h
T
c
, F [K])
Terefore
q = c (gpm 8.33 lb/gal)(60 min/h)(F temperature
drop)
= 1(gpm) 500 F temperature drop
[q = c (L/sec
1kg/L)(3600 sec/h)(K temperature drop)
= 1(L/sec)
15 077 kJ/L/sec/K
K temperature drop]
(2) gpm
system heat loss (Btu/h)
500 F temperature drop
[L/sec
system heat loss (kJ/h)
]
15 077
K temperature drop
In sizing hot water circulating systems, the designer should note
that the greater the temperature drop across the system, the less
water is required to be pumped through the system and, therefore,
the greater the savings on pumping costs. However, if the domestic
hot water supply starts out at 140F (60C) with, say, a 20F (6.7C)
temperature drop across the supply system, the fxtures near the
end of the circulating hot water supply loop could be provided
with a hot water supply of only 120F (49C). In addition, if the hot
water supply delivery temperature is 120F (49C) instead of 140F
(60C), the plumbing fxtures will use greater volumes of hot water
to get the desired blended water temperature (see Chapter 1, Table
1.1). Terefore, the recommended hot water system temperature
drop should be of the magnitude of 5F (3C). Tis means that if
the hot water supply starts out from the water heater at a tempera-
ture between 135 and 140F (58 and 60C), the lowest hot water
supply temperature provided by the hot water supply system could
6 Plumbing Systems & Design DECEMBER 2007 PSDMAGAZINE.ORG
CONTINUINg eDUCaTION: Recirculating Domestic hot Water systems
S
o
u
r
c
e
:
C
o
u
r
t
e
s
y
o
f
C
h
r
o
n
o
m
i
t
e
L
a
b
o
r
a
t
o
r
i
e
s
,
I
n
c
.
Figure 7 Instantaneous Point-of-Use Water Heater Piping Diagram.
be between 130 and 135F (54 and 58C). With multiple tempera-
ture distribution systems, it is recommended that the recirculation
system for each temperature distribution system be extended back
to the water heating system separately and have its own pump.
Using Equation 2, we determine that, if there is a 5F (3C) tem-
perature drop across the hot water system, the number to divide
into the hot water circulating system heat loss (q) to obtain the
minimum required hot water return circulation rate in gpm (L/sec)
is 2500 (500 5F), (45 213 [15 071
3C]).
For a 10F (6C) temperature drop that number is 5000 (from
Equation 2, 500 10F = 5000) (90 426 [from Equation 2, 15 071
6C
= 90 426]). However, this 10F (6C) temperature drop may produce
hot water supply temperatures that are lower than desired.
After Equation 2 is used to establish the required hot water return
fow rate, in gpm (L/sec), the plumbing designer can size the hot
water return piping system based on piping fow rate velocities
and the available pump heads. It is quite common that a plumb-
ing designer will make wrong initial assumptions about the sizes
of the hot water return lines to establish the initial
heat loss fgure (q). If that is the case, the plumbing
engineer will have to correct the hot water return
pipe sizes, redo the calculations using the new data
based on the correct pipe sizing, and verify that all
the rest of the calculations are now correct.
examPLe 1 CaLCULaTION TO
DeTeRmINe ReQUIReD CIRCULaTION RaTe
1. Assume that the hot
water supply piping system has 800 ft (244 m) of
average size 1 in. (DN32) pipe. From Table 5,
determine the heat loss per linear foot (meter). To
fnd the total heat loss, multiply length times heat
loss per foot (meter):
800 ft 13 Btu/h/ft = 10,400 Btu/h supply piping losses
(244 m
9.6 W/m =
293 W piping loss
)
528 W piping loss
3. Determine the hot water storage tank heat loss. Assume the
system in no. 1 above has a 200-gal (757-L) hot water storage
DECEMBER 2007 Plumbing Systems & Design 7
S
o
u
r
c
e
:
C
o
u
r
t
e
s
y
o
f
G
e
r
a
n
d
E
n
g
i
n
e
e
r
i
n
g
C
o
.
Figure 8 Fixed Orifces and Venturi Flow Meters.
S
o
u
r
c
e
:
C
o
u
r
t
e
s
y
o
f
G
r
i
s
w
o
l
d
C
o
n
t
r
o
l
s
.
Figure 9 Preset Self-Limiting Flow Control Cartridge.
tank. From Table 6 determine the heat loss of the storage tank
@ 759 Btu/h (222 W).
4. Determine the hot water systems total heat losses by totaling
the various losses:
A. Hot water supply piping losses 10,400 Btu/h
B. Hot water return piping losses 1,800 Btu/h
C. Hot water storage tank losses 759 Btu/h
Total system heat losses 12,959 Btu/h
Total system piping heat losses (A + B) = 12,200 Btu/h
[A. Hot water supply piping losses 3050 W
B. Hot water return piping losses 527 W
C. Hot water storage tank losses 222 W
Total system heat losses 3799 W
Total system piping heat losses (A + B) = 3577 W]
From Equation 2, using a system piping loss of 12,200 Btu/h
(3577 W) and a 5F (3C) temperature drop,
12,200 Btu/h
= 4.88 gpm (say 5 gpm)
required hot water return
circulation rate
5F temperature diference 500
3577 W
= 0.29 (say 0.3) L/sec
required hot water return
circulation
3C temp. diference
4188.32 kJ/m
3
reCalCulation of Hot Water SyStem loSSeS
1. Assume that the hot water supply piping system has 800 ft
(244 m) of average size 1 in. (DN32) pipe. From Table 5
determine the heat loss per linear foot (meter):
800 ft 13 Btu/h/ft = 10,400 Btu/h piping loss
(244 m
[C/W]
mm) on a
fat surface at a mean temperature of 75F (24C). Minimum insula-
10 Plumbing Systems & Design DECEMBER 2007 PSDMAGAZINE.ORG
CONTINUINg eDUCaTION: Recirculating Domestic hot Water systems
tion thickness shall be increased for materials having R values less
than 4.0 ft
2
h (F/Btu) in. (0.028 m
2
[C/W]
mm) or may be
reduced for materials having R values greater than 4.6 ft
2
h (F/
Btu) in. (0.032 m
2
[C/W]
mm).
1. For materials with thermal resistivity greater than 4.6
ft
2
h (F/Btu) in. (0.032 m
2
[C/W]
Table 4 thickness
= New minimum thickness
)
Actual R
2. For materials with thermal resistivity less than 4.0 ft
2
h (F/
Btu) in. (0.028 m
2
[C/W]
CV
14.7
where:
VC = Volume of gas in the proposed cylinder at
pressure, cubic feet (m
3
)
CP = Actual proposed cylinder pressure, psi (kPa)
CV = Actual cylinder volume, cubic feet (m
3
)
Cylinders are available in many sizes and pressure
ratings. Figure 12-4 illustrates the typical sizes. The
cylinders themselves are available in four general catego-
ries. The frst is the plain carbon steel tank. The second
is called the ultra-clean tank, which is made of a slightly
different alloy steel and has been completely cleaned, pre-
pared, and dried to reduce contaminants in the cylinder.
The third classifcation is aluminum tanks, in which the
tank interior has been specially prepared and the walls
treated to maintain stability and reduce particulates.
Aluminum is used for cleanliness and for gases that will
react with steel. In many cases, the exterior also is treated
to be easily cleaned, such as required for clean room installa-
tions. The fourth type of cylinder is made of stainless steel,
which is often used for ultra-pure gases.
Following are the general recommendations for the instal-
lation and storage of cylinders:
The room or area in which the cylinders are placed shall
have adequate ventilation and be free from combustible
material and separated from sources of ignition.
Consideration should be given for the storage of ad-
ditional full and empty cylinders in the same room for
convenience.
Enough room should be allowed for the easy changing of
cylinders. They are brought in on a hand truck or cart,
and room, usually 3 feet (0.91 m), should be allowed for
their maneuvering.
Gas cylinders in active use shall be secured against fall-
ing by means of foor stands, wall brackets, or bench
brackets. These brackets use straps to attach the cylinder
to the bracket. Also available are foor racks and stands
that can be provided for the installation and support of
cylinders that cannot be located near walls.
Empty cylinders also shall be secured against falling.
Dewers
When a larger amount of gas storage is desired, dewers typi-
cally are used. Typical dewers are illustrated in Figure 12-5.
Dewers should be placed at least 3 inches (1.5 cm) apart for
easy changing.
Gas Cabinet
When toxic or reactive gases are used, the cylinders should
be placed in a vented gas cabinet. The basic purpose of the
cabinet is to isolate the cylinders and to contain the gases
in the event of a leak. Escaped gases shall be directed away
from the immediate vicinity of the cylinder and cylinder
Figure 12-1 Moisture Content of Saturated Air
JANUARY/FEBRUARY 2012 Plumbing Systems & Design 5
storage area to a point outside the building where they can
be diluted with the outside air.
The typical cabinet construction is 11-gauge painted steel
or thicker to provide a one-half hour fre rating. The cabinet
can contain panel-mounted manifolds, purging equipment,
and other devices to allow some degree of control of oper-
ating parameters. They also can be provided with vertical
and horizontal adjustable cylinder brackets. The following
options also are available with the cylinder cabinet:
Automatic shutoff of gas in the event of a catastrophic
failure (fow limit)
Purging of gas lines after cylinder changes
Mechanical cabinet exhaust (typically 13 air changes per
minute with the access window open)
A sprinkler head for fammable gases, typically rated
at 135F (57.2C) with a minimum water pressure of 25
psig (172.4 kPa)
For toxic and reactive gases, a small access window could
be provided to operate the valves without opening the
main door and compromising the exhaust system. A fxed
access window is acceptable for inert gases.
Specialty Gas Generators
In some cases, it is more desirable for
a small facility to generate their own
high-purity specialty gases rather than
having them supplied in cylinders. A
limited number of gases is available for
which the anticipated volume allows
this choice in laboratory or research
facilities. Among them are nitrogen,
hydrogen, helium, and compressed air.
The generating units have their own
filters and purifiers that can create
gases of ultra-high purity. In particular,
the use of these units for the genera-
tion of hydrogen eliminates fammable
cylinders in the laboratory or separate
storage areas and keeps the actual
amount of gas stored below that needed
for explosion to take place. These units
may need to be supplied with utilities
such as electrical power, compressed air,
or deionized water.
DISTRIbuTION SYSTEm
COmPONENTS
The components that distribute high-
purity gas are different than those that
distribute standard laboratory gases.
Following is a discussion of only those
accessories and considerations that are
necessary to accomplish higher purity.
manifolds
A manifold is an assembly used to con-
nect multiple cylinders. This assembly
also could contain regulators, shutoff
valves, gauges, etc. A header with in-
dividual shutoff valves and connecting
pigtail is used to physically connect
several cylinders to a changeover manifold. Manifolds can
be specifed with manual or automatic changeover, and they
can be constructed of high-purity and other special materials
compatible with any specifc gas being used. The most often
used materials for the header, manifold, interconnecting pipe,
and fttings are brass and stainless steel, with stainless steel
fexible connections connecting the cylinders to the header.
When use is intermittent and the demand is low, a manual
single-cylinder (station) supply is appropriate. The cylinder
must be changed when the pressure becomes marginally low,
which will require an interruption in the supply. The same
system also could be used for greater demand where a bank of
cylinders is used. When an uninterrupted supply is required,
some method of automatic changeover must be used.
The simplest and least costly of the automatic types is the
semiautomatic or differential type of changeover manifold.
For this type of installation, the regulators for each bank of
cylinders are manually set at different pressures. Usually, the
secondary bank is set 5 psig lower than the primary bank.
When the pressure of the primary bank falls below the lower
Figure 12-2 Dewpoint Conversion Chart
Source: Hankison Corp.
WWW.PSDMAGAZINE.ORG
6 Plumbing Systems & Design JANUARY/FEBRUARY 2012
CONTINUING EDUCATION: Laboratory Gases
setting of the reserve bank, the secondary bank automatically
becomes the primary supply by default, since it has a higher
pressure than the primary bank. A low-pressure alarm or
low-pressure gauge reading will indicate that the changeover
has taken place. To change the cylinders, the empty bank
frst must be manually isolated. Then, the pressures on the
respective primary and secondary regulators must be reset
to new settings to refect the 5-psig difference between the
former reserve supply, which is now the primary supply, and
vice versa. In other types of semiautomatic manifolds, the
changeover is fully automatic, but a switch must be manu-
ally turned from the reserve position to the primary position
when changing cylinders.
The fully automatic changeover manifold uses pressure
switches or transducers to sense changes in line and supply
pressures. This in turn sends an electric signal to a relay that
turns off or on appropriate valves that accomplish the change-
over with no variation in system delivery pressure. It also
changes the secondary operating bank indicator to primary.
In addition, an alarm is sent when the cylinders need to be
changed. For critical applications, connection of the power
supply to optional standby power should be considered.
A typical manifold assembly is illustrated in Figure 12-6.
Exact manifold dimensions vary and need to be obtained
from the specifc manufacturer.
Regulators
A regulator is a device used to reduce a variable high inlet
pressure to a constant lower outlet pressure. The two broad
categories of regulators are cylinder and line. Cylinder
pressure regulators are mounted directly on high-pressure
cylinders to reduce high-pressure gases, generally in the
range of 2,000 to 6,000 psig (13,789.5 to 41,368.5 kPa), to a
lower pressure, generally around 150 psig (1,034.2 kPa). Line
regulators are inline devices used to reduce a higher pressure
to a lower working pressure of 55 psig (379.2 kPa) and also are
used on cryogenic tanks to reduce the pressure of the vapor
above the vaporized liquid, generally in the range of 150 to
250 psig (1,034.2 to 1,723.7 kPa). The regulator is the frst
device installed in the distribution system. Depending on the
purity of the gas, an integral inlet flter should be considered
to keep particulates from entering the regulator.
Regulators are available in two types: single and double
stage. The single stage is less costly and less accurate. This
type should be chosen if maintenance of exact pressure is not
a major factor in system operation. The double stage is more
costly and more accurate and able to achieve a constant outlet
pressure within a narrow operating range. When selecting a
regulator for specifc accuracy requirements, obtain the accu-
racy envelope diagrams from the manufacturer to check the
devices parameters using actual anticipated system design
pressures and fow rates. Typical single- and double-stage
regulators are illustrated in Figure 12-7.
The single-stage regulator reduces pressure in one step.
Typical differences in outlet pressure could vary as much as
7 psig (48.2 kPa) from low to high fow rates. The double-
stage regulator reduces the pressure in two steps. Typical
differences in outlet pressure could vary as much as 3 psig
(20.7 kPa) from low to high fow rates.
Another parameter that may be important in some instal-
lations is regulator creep. This is the rise in delivery pressure
due to differences in motion of the internal mechanical
components caused by aging. Creep is also caused by foreign
material interfering with the mechanical operation of the
unit. This is the most common cause of unit failure.
The following should be considered when selecting a
regulator:
The regulator should have a positive gas vent.
The regulator must be rated for the highest possible
working pressure.
The delivery pressure range must be adequate.
The operating temperature must be compatible with the
environment in which the valve is located.
Table 12-4 Flammability Limits and Specifc Gravity
for Common Gases
Gas
Specifc
Gravity
Flammability in air, %
Low High
Acetylene 0.906 25 100
Air 1.00
Ammonia 0.560 15 28
Argon 1.38
Arsine 2.69 5.1 78
Butane 0.600 1.8 8.4
Carbon dioxide 1.52
Carbon monoxide 0.967 12.5 74
Chlorine 2.49
Cyclopropane 0.720 2.4 10.4
Ethane 1.05 3.0 12.4
Ethylene 0.570 2.7 36
Ethyl chloride 2.22 3.8 15.4
Fluorine 1.31
Helium 0.138
Hydrogen 0.069 4.0 75
Hydrogen sulfde 1.18 4.0 44
Isobutane 2.01 1.8 9.6
Isopentane 2.48
Krypton 2.89
Methan 0.415 5.0 15
Methyl chloride 1.74 10.7 17.4
Natural gas 0.600
Neon 0.674
Nitrogen 0.966
Nitrous oxide 1.53
Oxygen 1.10
Phosgene 1.39
Propane 1.580 2.1 9.5
Silane 1.11 1.5 98
Sulphur dioxide 2.26
Xenon 4.53
JANUARY/FEBRUARY 2012 Plumbing Systems & Design 7
The valve body and internal materials should be selected
for the specifc purity of the desired gas, such as being
machine welded or having diffusion-resistant materials
and packing, low particulate metals, and fexible dia-
phragms. High-purity regulators shall have little dead
space internally and diaphragm seals that are consistent
with the required purity.
The pressure range of the gauges must be compatible
with the pressures expected. As an ideal, the working
pressure should be one-half of the maximum outlet
gauge reading.
One feature that should be considered when only gas is to
be used from a bulk liquid supply is an internal tank piping
arrangement called an economizer. Provided as an integral
part of the tank, this allows use of the gas available in the
vapor space above the liquid in the tank before the liquid
itself has to be vaporized. A special type of pressure regula-
tor shall be provided that will switch from the economizer
to the liquid line when the pressure in the vapor space falls
below a preset level.
Filters and Purifers
Filters and purifers are necessary to reduce or eliminate
unwanted contaminants and particulates in the gas stream.
The most common purifers are those used to remove oxygen,
water vapor, hydrocarbons, and particulates. For delivery of
sterile gases, a 0.2- flter is used to remove any organisms
suspended in the air stream. Filters also are used to eliminate
other unwanted trace elements.
Many different types of flters are available.
The most often used flter removes particulates 0.2 m
and larger.
To remove hydrogen, palladium flters are used.
Ceramic, fberglass, sintered metal, and other adsorbent
materials are used to remove oil, moisture, and other
trace contaminants to make the main gas as pure as
possible. For some flter mediums, colored materials
can be added to indicate when it is time to replace the
flter medium.
The molecular sieve flter is a synthetically produced
crystalline metal powder that has been activated for
adsorption by removing the water of hydration. This
material is manufactured with precise and uniform sizes
and dimensions. The size determines what can be fltered.
Sieves are available as powder, pellets, beads, and mesh,
although mesh is not used in laboratories.
The requirements of the end user will dictate the flter
medium and type. A flter shall be placed before any fow
meter and any other type of equipment where required.
The housing must be compatible with the gas being fl-
tered and the pressure involved. No flter should be subject
to pressures more than the 60 psig (413.7 kPa) normally used
in most laboratories unless specifed for a higher pressure.
Pressure drop through the flter medium is a critical factor
in the selection of the material used. For large installations,
pressure gauges on each side of the flters are used to monitor
their effectiveness. Usually, a 5-psig (34.5-kPa) drop means
that replacement is required.
It is not possible to improve the purity of a gas with the
use of purifers. If a gas of a certain purity is required, a gas
of that grade must be used from the outset.
Refer to Figure 12-8 for a typical system purifer arrange-
ment. Components shall be eliminated as required.
Gauges
Gauges (other than those integral to regu-
lators) for pressures up to 10 psig (68.9
kPa) are usually the diaphragm sensing-
element type. For pressures more than
10 psig (68.9 kPa), use the bourdon style.
They should be cleaned for oxygen service,
and the materials must be compatible with
the intended gas. For single gauges, pro-
vide a small gas cock of the needle valve
type between the pipeline and the gauge
to shut off the fow and allow the gauge
to be replaced without shutting down the
system.
Flash Arresters
Flash arresters (see Figure 12-9) are
required when the gas being used is
flammable, particularly hydrogen and
acetylene. They are mounted inline to
prevent any fame from going back into the
tank in the event that gas in the delivery
piping system has ignited. It is standard
procedure for a check valve to be made an
integral part of a fash arrester, although
this is not true in all cases.
Figure 12-3 Typical Arrangements and Dimensions of Cylinder
Installations (9-in. diameter)
WWW.PSDMAGAZINE.ORG
8 Plumbing Systems & Design JANUARY/FEBRUARY 2012
CONTINUING EDUCATION: Laboratory Gases
Table 12-5 Sizing for Oxygen, Nitrogen, and Air
scfm acfm
Copper Tube Type L, 55 psi, Specifc Gravity = 1
in. in. 1 in. 1 in. 1 in. 2 in. 2 in. 3 in. 4 in.
psi per 100 feet of pipe
5 1.1 0.15 0.04 0.01
10 2.2 0.51 0.13 0.04 0.01
15 3.3 1.04 0.27 0.09 0.02 0.01
20 4.3 0.45 0.14 0.04 0.02
25 5.4 0.67 0.21 0.06 0.03 0.01
30 6.5 0.93 0.29 0.08 0.04 0.01
35 7.6 1.18 0.39 0.10 0.05 0.02 0.01
40 8.7 0.49 0.13 0.06 0.02 0.01
45 9.8 0.60 0.16 0.08 0.02 0.01
50 10.9 0.73 0.20 0.09 0.03 0.01
60 13.0 1.01 0.27 0.13 0.04 0.02 0.01
70 15.2 1.28 0.36 0.17 0.05 0.02 0.01
80 17.4 0.45 0.22 0.07 0.03 0.01
90 19.5 0.56 0.27 0.08 0.03 0.01
100 21.7 0.68 0.32 0.10 0.04 0.02 0.00
110 23.9 0.81 0.38 0.12 0.05 0.02 0.01
120 26.0 0.94 0.45 0.14 0.06 0.02 0.01
130 28.2 1.09 0.52 0.16 0.07 0.02 0.01
140 30.4 1.22 0.59 0.18 0.08 0.03 0.01
150 32.6 0.67 0.20 0.09 0.03 0.01
175 38.0 0.89 0.27 0.11 0.04 0.01
200 43.4 1.13 0.34 0.14 0.05 0.01
225 48.8 1.28 0.42 0.18 0.06 0.02
250 54.3 0.51 0.22 0.08 0.02
275 59.7 0.60 0.26 0.09 0.02
300 65.1 0.71 0.30 0.11 0.03
325 70.5 0.82 0.35 0.12 0.03
350 76.0 0.94 0.40 0.14 0.04
375 81.4 1.06 0.45 0.16 0.04
400 86.8 1.18 0.51 0.18 0.05
450 97.7 0.63 0.22 0.06
500 108.5 0.76 0.27 0.07
550 119.4 0.90 0.32 0.09
600 130.2 1.06 0.37 0.10
650 141.1 1.21 0.43 0.12
700 151.9 0.49 0.13
750 162.8 0.56 0.15
800 173.6 0.63 0.17
850 184.5 0.70 0.19
900 195.3 0.78 0.21
950 206.2 0.89 0.23
1,000 217.0 0.25
1,100 238.7 0.30
1,200 260.4 0.35
1,300 282.1 0.41
1,400 303.8 0.47
1,500 325.5 0.53
Note: Values in table are for fow velocities not exceeding 4,000 fpm.
Table 12-6 Factors
for the Sizing of
Any Gas, Based on
Specifc Gravity
Specifc
Gravity
Factor
.05 4.50
.10 3.16
.15 2.58
.20 2.20
.25 2.00
.30 1.79
.35 1.68
.40 1.57
.45 1.49
.50 1.41
.55 1.33
.60 1.28
.65 1.23
.70 1.19
.75 1.15
.80 1.12
.85 1.07
.90 1.05
.95 1.02
1.00 1.00
1.10 .95
1.20 .91
1.30 .87
1.40 .85
1.50 .81
1.60 .78
1.70 .76
1.80 .74
1.90 .72
2.00 .70
2.10 .69
2.20 .67
2.30 .65
2.40 .63
2.50 .62
2.60 .61
2.70 .60
3.00 .56
4.50 .25
Note: Multiply factor by scfm in
Table 12-8. Calculate adjusted
scfm. Use adjusted scfm to
obtain friction loss.
JANUARY/FEBRUARY 2012 Plumbing Systems & Design 9
Valves
Valves are an often overlooked component
of any system, but the selection of valve
type and material is important to effciency
and operating life. The valves used should
have been designed for the type of service
for which they will be used. Be careful to
examine valve specifcations for airway
ports or openings smaller than the nomi-
nal size indicated or expected. The most
often used shutoff valves are ball valves.
Three-piece valves are the most desired
because the body can be separated from
the end connections when being installed
and serviced.
For exacting control and modulating
purposes, needle valves are used because
of the precise level of control permitted.
The materials of the valve and seals must
be compatible with the gas used.
For specialty applications, diffusion-
resistant valves reduce or eliminate
unwanted gases from entering the system
through the packing. Where purity is a
major consideration, packless and bellows-
sealed diaphragm valves are available.
The following should be considered
when selecting valves:
The most important valve feature is
minimum fow restriction (pressure
drop) when the valve is open full. Ball,
gate, and plug valves have the lowest
pressure drop, so it is extremely rare
to use these types for fow restriction.
Where this feature is important, the
needle type of valve is used.
The pressure rating should be suitable
for the maximum pressure possible.
The valve body and seat materials
must be compatible with the expected
trace gases and contaminants.
There must be positive shutoff.
There should be minimum or no leakage through the
valve stem.
Flow Limit Shutoff Valve
A fow limit shutoff valve (see Figure 12-9) automatically
shuts off the fow from a cylinder if the fow rate exceeds
a predetermined limit, which is usually about 10 times the
highest expected fow rate. This valve must be manually
reset after operation.
Check Valves
Check valves (see Figure 12-9) are used to prevent the re-
verse fow of gas in the delivery piping system. If one gas at
a higher pressure possibly may force its way into another
piping system or if system failure is a possibility, a check
valve shall be installed.
Relief Valves
Relief valves (see Figure 12-10) are used to protect a system
from overpressure. A relief valve must be provided between
the regulator and the frst shutoff valve in the system, with
the discharge independently piped outdoors. The discharges
from a single gas service manifold or regulator may be
connected, but no connection from any source to a relief
discharge may be made from any other system. The discharge
pipe should be a minimum of inch in diameter.
The relief valve shall be located at the frst point in the
system that could be subject to full cylinder pressure if the
regulator failed. No valve should be located between the relief
valve and the regulator. The relief valve release point should
be set to 50 percent over working pressure.
When two-stage regulators are used, a preset frst-stage
(or interstage) relief valve is sometimes required to protect
the second stage from overpressure. Additionally, it is good
Figure 12-4 Typical Cylinder Dimensions
Source: Liquid Carbonic
WWW.PSDMAGAZINE.ORG
10 Plumbing Systems & Design JANUARY/FEBRUARY 2012
CONTINUING EDUCATION: Laboratory Gases
practice to install an adjustable relief valve on the second
stage to protect the system and instruments from damage due
to excessive pressure. For outdoor installations involving in-
ert gases, the relief valve can exhaust directly to atmosphere.
For indoor installations or any installation involving toxic or
fammable gases, the relief valve exhaust should be captured
and vented to a safe location outside.
manifold and Regulator Purge Devices
The replacement of cylinders introduces unwanted room
air into the piping manifold assembly and the connecting
cylinder pigtails. When maintaining a high purity level of the
gas is necessary, purge valves are installed to run system gas
through the contaminated parts of the system to replace all
such air. The purge valve outlet should be vented outside the
building. If the gas is suitable and low enough in volume and
the storage room is large enough and well
ventilated, it could discharge into the room
since the purge volume used is generally
quite small. The regulator often requires
special purging techniques recommended
by the manufacturer. Purge gas shall be
taken from a dedicated source used only
for this purpose and as illustrated in Figure
12-11.
Flow measurement
Flow meters can be either of two types: elec-
tric or mechanical. The mechanical kind is
called a variable-area type and uses a small
ball as an indicator in a variable-area verti-
cal tube. The type of mechanical meter most
often used has an accuracy of 10 percent full
scale. This means that if the fow range is
from 1 to 10 scfm, the accuracy is 1 acfm.
However, more accurate variable-area fow
meters are available.
Mass fow meters are electronically oper-
ated, using the difference in temperature
that gas creates when fowing over a heated
element. The mass fow meter is quite ac-
curate and expensive.
Gas Warmers
On occasion, the gas in cylinders is with-
drawn so fast that the regulator could freeze
because of the change in temperature.
If this occurs, an electrically heated gas
warmer is available to be installed inline,
and this warmer heats the gas out of the
cylinder before it reaches the regulator.
The rule of thumb is to consider a warmer
if the use of gas exceeds 35 acfm. The actual
fgure should be based on the specifc type
of gas being used, so consult with the sup-
plier. Carbon dioxide, for example, presents
a particular problem.
On occasion, the temperature of the
delivered gas is a critical factor. If a low
temperature could harm instruments or
interfere with the procedures being con-
ducted, a low-temperature cutoff should be installed with a
solenoid valve to stop the fow of gas. If this happens often,
a gas warmer might be required.
Alarms
Alarms are necessary to alert the user to immediate or po-
tential trouble. They could be visible and/or audible. The
typical alarms are high system pressure, low system pres-
sure, and reserve in use. In some installations, a normal
light is also requested. If a single cylinder is the sole source
of supply, an alarm might be installed when the pressure in
the tank reaches 400 psig (2,757.9 kPa). Other alarms could
be provided that will indicate high pressure loss at flters,
low gas temperature, purifers at limit of capacity, and fow
limit valve operation.
Figure 12-5 Cryogenic Containers
Source: Mathison
JANUARY/FEBRUARY 2012 Plumbing Systems & Design 11
These alarms are usually installed in an alarm panel,
which can be mounted in the room where the gases are stored,
in a constantly occupied location such as a maintenance shop
or receptionist area, or in the laboratory itself, depending on
the availability and level of maintenance. Often, multiple
locations are desirable if a continued supply of gas is criti-
cal. Various devices must be placed in the system for these
alarms to function, such as pressure switches, transducers,
and auxiliary contacts in a manifold assembly to transmit
the alarm signal to the alarm panel.
Toxic and Flammable Gas monitors
If a toxic and/or fammable gas might accumulate in an en-
closed area or room, a gas monitor must be installed to signal
an alarm if the gas percentage rises above a predetermined
limit that is considered harmful or dangerous. This should
be 50 percent of either the lower fammability limit (LFL)
or the level of concentration that may cause ill effects or
breathing problems. The oxygen concentration of ambient
air should never be allowed to fall below 19.5 percent. In ad-
dition, much lower levels should also be alarmed to indicate
that a problem exists well before the evacuation of an area
is required because of a leak. Refer back to Table 12-4 for
the fammability limits of some of the more common gases.
Request the MSDS for gases not listed.
Gas mixers
For certain applications, gas mixers are available to accu-
rately mix different gases to produce various proportions.
The accuracy of the mixture, fow rates of the various gases,
and the compatibility of the piping materials and the gases
are considerations in the selection of the mixer.
Vibration Isolation
Vibration isolation is achieved by the proper selection of
resilient devices between the pump base and the building
structure. This isolation is accomplished by placing isolators
between the pump and the foor, fexible connections on all
piping from the compressor, and spring-type hangers on the
piping around the compressor.
DISTRIbuTION NETWORk
System Pressure
Unless otherwise instructed, it is generally accepted prac-
tice to use a pressure of 5055 psig (344.7379.2 kPa) in
the normal centralized piping distribution system, with a
nominal 5-psig (34.5-kPa) loss in the system. High-pressure
systems, if specifcally requested by the end user or required
by the laboratory equipment manufacturer, use a different
pressure. Accepted practice limits the allowable friction loss
in the piping system to 10 percent of initial pressure. These
fgures are not set in stone and should be adjusted for spe-
cifc conditions or special systems when necessary. The most
important consideration is the actual pressure required by
the equipment being used. The maximum pressure set by
a regulator should be 10 psi (69 kPa) above the minimum
recommended by the manufacturer or end user.
Pipe material Selection
Consider the following when selecting the pipe material and
type for a specialty gas system:
Compatibility with the specifc gas used
Capability of delivering the desired gas purity for the
anticipated usage
Pressure rating of the pipe and joining methods
Temperature rating and the ability to be cleaned or
sterilized in place
Joining method
If all elements are equal, the least expensive piping shall
be selected
Figure 12-6 Typical Manifold Assembly
Source: Scott
Figure 12-7 Typical Single- and Double-stage
Regulators
Source: Scott
WWW.PSDMAGAZINE.ORG
12 Plumbing Systems & Design JANUARY/FEBRUARY 2012
CONTINUING EDUCATION: Laboratory Gases
Refer to the manufacturer or supplier of the gas for pipe
compatibility. The pipe most often used to maintain the
highest purity is grade 304L or 316L stainless steel tubing
conforming to ASTM A270: Standard Specifcation for Seam-
less and Welded Austenitic Stainless Steel Sanitary Tubing.
The interior should be electro-polished, and the exterior could
be mill fnished in concealed spaces. In exposed locations
and where the pipe exterior will be sterilized or cleaned, the
pipe exterior should have a No. 4 fnish. Stainless steel pipe
is capable of withstanding repeated sterilization by steam
and a variety of chemicals. The pipe is joined by orbital
welding, so the tube should have a minimum wall thickness
of 0.65 inch to be welded. When welding is not required, a
tube wall thickness of 0.28 inch is commonly used, but the
wall thickness must be able to handle the working pressure
of the system. The total installed cost often is less than that
of copper tube.
When hard pipe is not desired or used from a cylinder
or system to a movable instrument, it is common practice
to use -inch (6-mm) polyethylene (PE), stainless steel, or
copper tubing of suffcient pressure rating and compatibility
with the specifc gas, with no joints between the cylinder
and instrument.
In many laboratory applications, maintaining ultra-high
purity of a gas from the storage tank to the outlet is not an
absolute requirement. For this type of service, copper tube
and fttings that have been cleaned for oxygen service and
joined by brazing and properly purged often are inexpensive
and the material of choice. The following grades of copper
pipe have been used:
ASTM B88: Standard Specifcation for Seamless Copper
Water Tube
ASTM B819: Standard Specifcation for Seamless Copper
Tube for Medical Gas Systems
ASTM B280: Standard Specifcation for Seamless Cop-
per Tube for Air Conditioning and Refrigeration Field
Service
ASTM B75: Standard Specifcation for Seamless Copper
Tube
Another type of material for non-critical applications is
aluminum tubing ASTM B210: Standard Specifcation for
Aluminum and Aluminum-Alloy Drawn Seamless Tubes,
alloy 6061, T4 or T6 temper. This pipe is commonly
joined by patented fare joints.
The pipe pressure rating is selected to resist the
highest system design pressure, which is usually
in the range of 5055 psig (344.7379.2 kPa). Cop-
per tubing type L is used for pressures up to 200
psig (1,379 kPa), and type K is used for pressures
up to 300 psig (2,068.4 kPa). The pressures are
lowered internally at the equipment if the supplied
pressure is too great. Based on experience, the al-
lowable pressure range is usually between 30 and
75 psig (206.8 and 517.1 kPa). Higher pressures in
the 300 psig (2,068.4 kPa) range for special uses
are well within the limits of piping with fared,
orbital welded, and brazed joints. The allowable
pressure ratings for the various piping materials
at ambient temperatures based on wall thickness
values are calculated from equations appearing in ASME
B31.3: Process Piping Design.
The piping system also shall be capable of being cleaned
and sterilized in place, often, if required. Cleaned in place
(CIP) uses chemicals, so the pipe must be able to resist cor-
rosion. Refer to the manufacturers literature to establish
compatibility. Steam in place (SIP) raises the distribution
system to a high temperature that kills microbes. A drain
for the system is often required. The piping system materi-
als need to be steam compatible for the temperatures that
may be experienced.
Another consideration in maintaining a high-purity gas
is outgasing. This is a phenomenon in which a gas under
pressure is absorbed into any porous material. This occurs
primarily in elastomers used as gaskets or seals and to some
lesser extent into metallic and plastic pipe and tubing ma-
terials. When the pressure is reduced or eliminated, such as
when changing cylinder banks or during maintenance, the
absorbed gases are spontaneously given off, adding impuri-
ties into the gas piping system.
Experience has shown that reaming the ends of pipe or
tubing to obtain a smooth interior has left pieces of shaved
metal in the pipe. If this is a cause for concern, reaming meth-
ods and tools are available that eliminate this problem.
Joints
The joining method may be a criteria in the selection of pipe
wall thickness or pipe material composition. The temper of
the pipe may have to be carefully selected to use proprietary
fttings.
The most often used joints for copper tubing are brazed.
No fux is permitted, so only cast or wrought copper fttings
should be used. The interior of the joint shall be purged
with an inert gas, such as nitrogen type NF or argon. The
reason for making up a joint in this manner is to eliminate
any residue that may be produced as a by-product by the
brazing process.
For stainless steel pipe, orbital welding leaves the
smoothest interior surface, but it should be used only on
tubing with a wall thickness of 0.65 inch or thicker. Another
type of joint that can be used is the patented fared joint,
which is preferable to solder or brazed joints that often
leave a residue that contributes particulates into the gas
Figure 12-8 Typical Purifer Arrangement
JANUARY/FEBRUARY 2012 Plumbing Systems & Design 13
stream. In addition, the fared joint is popular because it
can be made up using only a saw and some wrenches. When
copper tubing is used with fared joints, the pipe shall not
have embossed identifcation stamped into the pipe because
doing so causes leaks at the joint. There is no ASTM designa-
tion for patented fare joints, but they are acceptable for all
applications as long as the allowable joint pressure ratings
are not exceeded.
PIPE SIzING AND LAYOuT
Before laying out the piping system, the following informa-
tion must be known:
All air- or gas-consuming devices
Minimum and maximum pressure requirements for
each device
Actual volume of air or gas used by each device
Suggested duty cycle and diversity factor for equip-
ment
Special individual air or gas purifcation requirements
System Sizing Procedure
Following is a recommended system sizing procedure. It is
not intended for compressed air in common laboratories.
Refer to Chapter 9 for that information.
1. Locate the gas storage area and lay out the cylinders,
manifolds, and so on.
2. Establish a general layout of the system from the
storage area to the farthest outlet or use point. Measure
the actual distance along the run of pipe to the most
remote outlet. Next, add a ftting allowance. For ease
of calculations, the addition of 50 percent of the actual
measured run will give a conservative approximation
of the entire system. Adding the measured length to
the ftting allowance will result in the equivalent run of
pipe.
3. Choose all of the flters, purifers, and accessories
necessary for system purity. This will establish a
combined allowable pressure drop through each of them
and the assembly as a whole.
4. Establish the actual pressure required at the farthest
outlet.
5. Calculate the allowable total system friction loss.
It is accepted practice for general use to have a mini- a.
mum system pressure of 45 to 55 psig (310.3 to 379.2
kPa) and to allow 5 psig (34.5 kPa) as a pressure loss
in the pipe. For high-pressure systems serving spe-
cifc equipment or tools, start with the high end of
the range for the actual pressure required. Accepted
practice is to allow 10 percent of the proposed sys-
tem pressure for pipe friction loss. So, for a 125-psig
(861.8-kPa) system, a 12-psig (82.7-kPa) friction
loss will be allowed. This fgure is variable. To that
fgure add the pressure required to overcome the
drop through the flter-purifer-manifold assembly
and other accessories.
Divide the total equivalent run of pipe (in hundreds b.
of feet) by the allowable friction loss to calculate the
allowable friction loss in psig per 100 feet of pipe. This
calculation is necessary to allow the use of the sizing
Figure 12-9 Typical Single-cylinder Installation Detail
Figure 12-10 Typical Relief Venting
WWW.PSDMAGAZINE.ORG
14 Plumbing Systems & Design JANUARY/FEBRUARY 2012
CONTINUING EDUCATION: Laboratory Gases
chart provided in this chapter. If other methods are
used to indicate friction loss in the piping system,
calculate the loss in that specifc method.
6. Calculate the connected fow rate for the piping to be
sized. For general use, a fgure of 1 scfm (30 nLpm) for
each outlet unless the end user indicates otherwise.
Calculate the scfm (nLpm) of gas through each branch,
from the farthest outlet back to the source (or main).
For specifc equipment, use the fow rate recommended
by the manufacturer.
7. Calculate the expected fow rate for all points using
the appropriate diversity factor for all parts of the
system. For specifc equipment, the diversity factor
must be obtained from the end user. The diversity
(or simultaneous use) factor, which determines the
maximum number of outlets in use at any one time, has
a major infuence on the sizing of the piping system.
Specialty gas systems have no exact calculation method,
so consultation with the end user is the best method
and is strongly suggested.
8. The sizing chart, Table 12-5, has been calculated for a
gas with a specifc gravity of 1 (which is air), using type
L copper pipe, and a pressure of 55 psig (379.2 kPa).
This table also can be used for gases with a specifc
gravity ranging from 1.90 to 1.10. Slight differences
are well within accepted accuracy. To fnd the specifc
gravity of many common gases, refer back to Table
12-4.
With all the above information available, the pipe can
now be sized. Starting from the most remote point on
the branch and then proceeding to the main, calculate
the actual fow rate using the appropriate diversity
factor. Enter Table 12-5 with the actual fow rate and
the allowable friction loss. Find the fow rate, and then
read across to fnd a friction loss fgure that is equal
to or less than the allowable friction loss. Read up the
column to fnd the size. In some cases, the diversity
factor for the next highest range
of outlets may result in a smaller-
size pipe than the range calculated.
If this occurs, do not reduce the
size of the pipe; keep the larger
size previously determined. For
equipment using capillary piping
and tubing, refer to Figure 12-12 for
nominal -inch pipe.
To calculate the specifc gravity of a.
any gas not covered in Table 12-4,
divide the molecular weight of that
gas by 29, which is the composite
molecular weight of air.
When any gas with a specific b.
gravity other than 1 is used, an
adjustment factor is provided in
Table 12-6 that will convert scfm
to the equivalent of any other
gas or combination of gases for
use in Table 12-5. Multiply the
factor found in the table by the
compressed air fow rate to obtain the new fow rate
for the gas in question.
For pressures other than 55 psig (379.2 kPa), use the c.
following formula:
Equation 12-2
PD =
P
1
+ 14.7
PD
r
P
2
+ 14.7
For the fow of any compressed gas at temperatures other
than 60F (15.6C), use the following formula to calculate a
factor that, when multiplied by the fow rate, will give the
fow rate at the new temperature:
Equation 12-3
f =
460 + t
520
where:
PD = New pressure drop, psig (kPa)
P
1
= 55 (referenced table pressure), psig (kPa)
P
2
= Actual service pressure, psig (kPa)
PD
r
= Referenced pressure drop found in Table 12-5,
psi/100 feet (kPa/30m)
t = Temperature under consideration, F (C)
f = Factor
Having calculated the scfm (nLpm) and the allowable
friction loss in each section of the piping being sized,
now size the piping using the charts for system
pressure. Since all pipe sizing charts are formulated on
the loss of pressure per some length of piping (usually
100 feet [30 m]), it will be necessary to arrive at the
required value for the chart being used. A maximum
velocity of 4,000 fpm (1,200 m/min) is recommended.
Another method, applicable only to branch lines
with small numbers of laboratory outlets used for aver-
age purposes, is to use a prepared chart based on the
number of outlets with the actual fow of gas not consid-
Table 12-7 Typical Laboratory Branch Sizing Chart
No. of
Connections
Pipe Diameter, in.
Cold water,
hot water
Air Gas Vacuum
Oxygen
D.W. Nitrogen
1
2
3
4
5
6 1
7 1 1
8 1 1
1
9 1 1
1
10 1 1
1
1120 1 1 1
1
21 and over 1 1 1 1 1 (2130)
1 (3150)
1 (51 and over)
1 1
Note: 1 in. = 25.4 mm
JANUARY/FEBRUARY 2012 Plumbing Systems & Design 15
ered. The fow rate and diversity of use are taken into
consideration in the sizing chart, which assumes that suf-
fcient system pressure is available. With a small number of
outlets on a branch, this method provides a suffcient degree
of accuracy and speed of calculation. Table 12-7 is such a chart
for various systems found in a typical laboratory.
COmPRESSOR INLET PIPING
Since air compressor performance depends on inlet condi-
tions, this system deserves special care. The air intake should
provide a supply of air to the compressor that is as clean, cool,
and dry as possible. The proposed location should be studied
for the presence of any type of airborne contamination and
positioned to avoid the probability of a contaminated intake.
Intake piping is discussed in Chapter 9. For sizing intake
piping, refer to Table 12-8.
TESTS
Bulk storage tanks and dewers are required to be ASME
rated and therefore are tested at the factory before ship-
ment. They are not tested after installation. Cylinders are
not tested for the same reason. This means that only the
distribution system, from the cylinder valve to the outlets,
must be subject to pressure tests.
Testing is done by pressurizing the system to the test
pressure with an inert, oil-free, and dry gas. Nitrogen is often
used because of its low cost and availability. The system test
pressure for low-pressure systems is 150 percent over the
working pressure. For systems with a working pressure up
to 200 psig (1,379 kPa), the entire piping system, including
the cylinder manifold, is tested to 300 psig (2,068.4 kPa) for
one hour with no leakage permitted. If a working pressure
higher than 200 psig (1,379 kPa) is required, the system is
tested at 150 percent of the system pressure.
The pressure testing should be done in increments of 100
psig (689.5 kPa), starting with 100 psig. This is done to avoid
damage due to a catastrophic failure. Leaks are repaired after
each increment. After fnal testing, it is recommended that
the piping be left pressurized at the system working pressure
with system gas if practical.
FLuSHING, TESTING, AND PuRGING
THE DISTRIbuTION SYSTEm
After the system is completely installed and before it is
placed in service, the piping system frst must be fushed to
remove all loose debris, then tested, and fnally purged with
the intended system gas to ensure purity.
An accepted fushing method is to allow a volume of two
to fve times the expected fow through each respective part
of the system. This is done by connecting the fushing gas
under pressure to the piping system and then opening and
closing all outlets and valves starting from the closest and
working to the most remote.
To test for particulates, fow the gas into a clean white
cloth at a minimum rate of 15 cfm (100 L/min) and inspect
the cloth for contamination.
Finally, the system must be capable of providing the de-
sired purity when actually placed in operation. Since fushing
and testing may leave the piping system flled with inert or
other gases, they must be removed, or purged. This is accom-
plished by allowing the system gas to fow through all parts of
the piping system, opening all of the valves, and testing the
gas purity at various points of the system until the desired
purity level is reached. For high-purity gases, a laboratory
specializing in testing for the purity level required shall be
used unless the facility is capable of performing the test.
It is often best to use the system gas for testing pur-
poses.
Table 12-8 Recommended Air Compressor
Inlet Pipe Size
Maximum scfm Free
Air Capacity
Minimum Size, in.
50 2
110 3
210 4
400 5
800 6
Note: 1 cfm = 0.03 m3/min
Source: James Church
Figure 12-11 Typical Purging Arrangement
WWW.PSDMAGAZINE.ORG
16 Plumbing Systems & Design JANUARY/FEBRUARY 2012
CONTINUING EDUCATION: Laboratory Gases
Figure 12-12
1
/8-in. OD Tubing
JANUARY/FEBRUARY 2012 Plumbing Systems & Design 17
CONTINUING EDUCATION: Laboratory Gases CONTINUING EDUCATION: Laboratory Gases
About This Issues Article
P
S
D
1
8
4
Continuing Education from Plumbing Systems & Design
CE Questions Laboratory Gases (PSD 184)
Dry air is composed of ________ percent carbon monoxide by 1.
volume.
0.0001 a.
0.00001 b.
0.0003 c.
0.003 d.
Which of the following is considered a contaminant of air? 2.
water a.
hydrocarbons b.
rust c.
all of the above d.
________ gases will spontaneously ignite upon contact with air 3.
under normal conditions.
fammable a.
oxidizer b.
pyrophoric c.
corrosive d.
________ typically are used when a large amount of gas storage 4.
is desired.
cabinets a.
dewers b.
cylinders c.
manifolds d.
A ________ is an assembly used to connect multiple gas 5.
cylinders.
header a.
bank b.
manifold c.
connector d.
A ________ is used to reduce a variable high inlet pressure to a 6.
constant lower outlet pressure.
regulator a.
pressure gauge b.
flter c.
shutoff valve d.
________ can be used to remove moisture to make the main gas 7.
as pure as possible.
fberglass a.
ceramic b.
sintered metal c.
all of the above d.
Bourdon gauges are used when pressures are more than 8.
________.
10 psig a.
100 psig b.
68.9 kPa c.
both a and c d.
What type of valve is used to protect the system from 9.
overpressure?
fow-limit shutoff a.
relief b.
check c.
needle d.
The recommended pipe diameter of a branch line with fve 10.
connections for a vacuum system is ________.
inch a.
inch b.
inch c.
1 inch d.
To maintain the highest purity, ________ pipe is the most often 11.
used.
polyethylene a.
copper b.
304L or 316L stainless steel c.
glass d.
Allow ________ of the proposed system pressure for pipe friction 12.
loss.
5 percent a.
10 percent b.
12 percent c.
none of the above d.
Do you fnd it difcult to obtain continuing education units (CEUs)?
Trough this special section in every issue of PS&D, ASPE can help you
accumulate the CEUs required for maintaining your Certifed in Plumb-
ing Design (CPD) status.
Now Online!
Te technical article you must read to complete the exam is located at
www.psdmagazine.org. Just click on Continuing Education at the top
of the page. Te following exam and application form also may be down-
loaded from the website. Reading the article and completing the form will
allow you to apply to ASPE for CEU credit. If you earn a grade of 90 percent
or higher on the test, you will be notified that you have logged 0.1
CEU, which can be applied toward CPD renewal or numerous regulatory-
agency CE programs. (Please note that it is your responsibility to determine
the acceptance policy of a particular agency.) CEU information will be kept
on fle at the ASPE ofce for three years.
Note: In determining your answers to the CE questions, use only the material pre-
sented in the corresponding continuing education article. Using information from
other materials may result in a wrong answer.
The January/February 2012 continuing education article
is Laboratory Gases.
This chapter describes the design criteria and central
piping distribution methods for various laboratory-grade
specialty gas systems, including pure compressed air used
for laboratory processes. Also included in the discussion
are various specialty compressed air and gas systems typi-
cally used for organic and inorganic chemistry, physics,
and biological laboratories and those used for research,
development, and commercial purposes. This chapter
concentrates on cylinder and dewer supply and the local
generation of such gases.
You may locate this article at psdmagazine.org. Read
the article, complete the following exam, and submit your
answer sheet to the ASPE offce to potentially receive 0.1
CEU.
WWW.PSDMAGAZINE.ORG
18 Plumbing Systems & Design JANUARY/FEBRUARY 2012
C
E
U
1
8
5
Treatment
of Industrial
Waste
Continuing Education from the
American Society of Plumbing Engineers
MARCH 2012
ASPE.ORG/ReadLearnEarn
Industrial wastewater is a generic term used to describe
nonsanitary (plumbing) effuent, such as that typically found
in chemical, pharmaceutical, and other manufacturing facili-
ties. It also may be applied to wastewater from commercial
facilities, such as self-service laundries or large restaurants.
The defnition also includes storm water runoff containing
anything considered harmful by the U.S. Environmental
Protection Agency (EPA) discharged from sites involving
any industrial activity or construction.
This chapter describes the regulatory framework gov-
erning industrial wastewater, hazardous substances, and
hazardous wastes and the impact of these regulations on
industrial-process plumbing design. It also contains design
considerations, describes a few of the more common treat-
ment technologies, and provides resources from which more
detailed information can be obtained.
Whether discharged to municipal sewers, surface waters,
deep wells, or land, industrial wastewater and some storm
water runoff are subject to government permitting require-
ments. In most cases, these wastes must be treated before
discharge to abate pollution. Permits specify the maximum
allowable concentrations of pollutants in the discharge and
the frequency and type of monitoring required to show
compliance. Pollution abatement by dilution is no longer al-
lowed. The segregation of incidental water streams, such as
non-contact cooling water or storm water runoff, from pro-
cess wastewater is almost universally required. Even clean,
incidental wastewater streams require a permit.
Most nonaqueous liquids (including solvents, oils, and
sludge) and some solids and gases are regulated as hazardous
substances or hazardous wastes during their generation, use,
collection, storage, transportation, treatment, and disposal.
Some aqueous wastes that are not regulated under a waste-
water permit are regulated as either hazardous substances
or hazardous wastes.
As a result of these regulations, plumbing designers must
either consult with an experienced environmental engineer
or become familiar with the various environmental require-
ments to ensure an acceptable installation. New facilities
must meet both environmental and plumbing code require-
ments. For novel manufacturing processes, the designer,
environmental engineer, and owner may be required to
work with regulatory authorities during the design stage to
ensure compliance with the intent of the various codes and
regulations. The designer is responsible for producing an
installation with a low probability of failure. For plumbing
design, this means minimizing the possibility of leaks and
providing a means to limit the impact of spills on the publics
safety and the environment.
Definitions
Hazardous substance Under Section 311 of the Clean
Water Act, the EPA has compiled a list of hazardous sub-
stances (40 CFR 116). If a substance on this list is spilled or
discharged, it must be reported to the EPA.
Priority pollutant The Natural Resources Defense
Council and the EPA determine priority toxic pollutants.
These pollutants have been incorporated into several regu-
latory programs, including NPDES permits, pretreatment
standards (40 CFR 403), hazardous wastes (40 CFR 261),
and CERCLA (42 USC 103).
Hazardous wastes The EPA has adopted regulations to
control hazardous wastes under RCRA. These regulations (40
CFR 261) list hazardous wastes, including specifc chemicals
and mixtures defned by their characteristics. It should be
noted that controls under RCRA apply to waste only and not
to hazardous substances that are being stored prior to use in
product manufacturing or that are to be reclaimed, recycled,
or reused. RCRA regulates the generation, transportation,
storage, treatment, and disposal of hazardous wastes.
Hazardous materials This term means substances
or materials that have been determined by the secretary of
transportation, under 49 CFR 172, to be capable of posing
an unreasonable risk to health, safety, and property when
transported in commerce. Chemicals included in this defni-
tion are hazardous substances, hazardous wastes, most of the
priority pollutants, and many other chemicals in commerce
that are too numerous to mention here. In this chapter, the
term hazardous materials is used to describe all the previ-
ously defned materials and substances.
For detailed listings of these and other regulated chemi-
cals and wastes, refer to the regulations cited in the above
defnitions.
RegulatoRy fRamewoRk
The most important pieces of environmental legislation
affecting the design of plumbing systems for hazardous
material and waste facilities serving industrial plants are
the Clean Water Act (CWA), Resource Conservation and
Recovery Act (RCRA), and Comprehensive Environmental
Response, Compensation, and Liability Act (CERCLA), oth-
erwise known as Superfund. These regulations, promulgated
by the EPA and enforced by either the EPA or counterpart
state agencies, provide a comprehensive framework of pollu-
tion control. The National Pollutant Discharge Elimination
System (NPDES) permitting program has recently been
revised to include the discharge of storm water from selected
industrial sites. Current EPA regulations can be found in
Reprinted from Chapter 3, ASPE Plumbing Engineering Design Handbook, Vol 3 (2011).
Note: In determining your answers to the CE questions, use only the material presented in the corresponding continuing education
article. Using information from other materials may result in a wrong answer.
2 Read, Learn, Earn MARCH 2012
READ, LEARN, EARN
the Code of Federal Regulations (CFR), which is an annually
updated compendium of all federal regulations. Any updates
or regulation changes after the last publication date of the
CFR can be found in the Federal Register, a daily government
newspaper in which all agencies and departments publish
their notices, proposals, and fnal regulations. Most states
with counterpart regulations have similar codifcations and
newspapers.
The great body of codes and regulations can easily be a
labyrinth, even for those persons with a good understanding
of the overall outline and purpose of the statutes. Anyone
with questions should not hesitate to seek advice from
trade groups, regulatory offcials, environmental engineers,
lawyers, and other specialists as needed. Numerous current
event reporting services digest federal and state regulatory
actions and publish readable evaluations as well as reprints
of important regulations, policies, and case notes.
Clean water act
The CWA establishes a mechanism for setting uniform
national standards for discharge to surface waters and sew-
ers. The EPA has established categorical effuent standards,
usually prorated to production volume, for 56 industrial clas-
sifcations under the Effuent Guidelines Program Plan. The
affected industries are listed in Table 3-1. The EPA has also
promulgated general standards for discharge to public sewer
systems. These standards restrict pollutants that interfere
with sewage treatment, pass through the system untreated,
damage sewer lines or treatment facilities, or overload treat-
ment processes.
State laws and regulations follow the federal format, with
a few important differences. All states are allowed to make
their regulations more stringent than the federal standards.
Additionally, some states regulate discharges to the land (and
hence to the groundwater). States also set goals for water
quality levels in streams, lakes, and coastal waters. They then
determine the allowable loading of each pollutant and allocate
portions of that loading based on low-fow conditions where
dilution is minimal. Water quality-based discharge permit
limits are almost always more stringent than industry-wide
limits of the categorical effuent standards.
Two types of water discharge permits may require treat-
ment processes. Permits for a direct discharge into a surface
water (stream, lake, ocean) are called National Pollutant
Discharge Elimination System permits. These permits may
be issued by the EPA or a state or jointly, depending on the
location. Application is required well in advance of initiating
a discharge.
The other type of industrial discharge permit is obtained
from a publicly owned treatment works (POTW). Industrial
discharges to a POTW are called indirect discharges and are
regulated by pretreatment ordinances to ensure that the
POTW meets the conditions of its NPDES permit. The ordi-
nances are usually administered by the POTW, except when
the industrial discharge is large, the POTW fails to meet its
permit requirements, or the discharge is from an industry
regulated under the Effuent Guidelines Program Plan.
Table 3-1 Industries Affected by the Effuent
Guidelines Program Plan
Number Industry Category
1 Aluminum Forming
2 Asbestos Manufacturing
3 Battery Manufacturing
4 Canned and Preserved Fruits and Vegetable
Processing
5 Canned and Preserved Seafood Processing
6 Carbon Black Manufacturing
7 Cement Manufacturing
8 Centralized Waste Treatment
9 Coal Mining
10 Coil Coating
11 Concentrated Animal Feeding Operations
12 Concentrated Aquatic Animal Production
13 Copper Forming
14 Dairy Products Processing
15 Electrical and Electronic Components
16 Electroplating
17 Explosives Manufacturing
18 Ferroalloy Manufacturing
19 Fertilizer Manufacturing
20 Glass Manufacturing
21 Grain Mills
22 Gum and Wood Chemicals
23 Hospitals
24 Ink Formulating
25 Inorganic Chemicals
26 Iron and Steel Manufacturing
27 Landflls
28 Leather Tanning and Finishing
29 Meat and Poultry Products
30 Metal Finishing
31 Metal Molding and Casting
32 Metal Products and Machinery
33 Mineral Mining and Processing
34 Nonferrous Metals Forming and Metal Powders
35 Nonferrous Metals Manufacturing
36 Oil and Gas Extraction
37 Ore Mining and Dressing
38 Organic Chemicals, Plastics, and Synthetic Fibers
39 Paint Formulating
40 Paving and Roofng Materials (Tars and Asphalt)
41 Pesticide Chemicals
42 Petroleum Refning
43 Pharmaceutical Manufacturing
44 Phosphate Manufacturing
45 Photographic
46 Plastic Molding and Forming
47 Porcelain Enameling
48 Pulp, Paper, and Paperboard
49 Rubber Manufacturing
50 Soaps and Detergents Manufacturing
51 Steam Electric Power Generating
52 Sugar Processing
53 Textile Mills
54 Timber Products Processing
55 Transportation Equipment Cleaning
56 Waste Combustors
Source: U.S. Environmental Protection Agency, 2008
MARCH 2012 Read, Learn, Earn 3
RCRA permits for a facility may take six months and may
require public hearings and disclosure of detailed process
and waste information, including chemical material safety
data sheets (MSDS).
When evaluating waste streams to determine if they are
regulated as hazardous wastes, it is important to check both
federal and state regulations. This is because states are al-
lowed to be more stringent than the EPA. States may defne
certain wastes as hazardous when the EPA doesnt consider
them so. For example, waste oil is considered hazardous by
many states, but not by the EPA.
The relationship between RCRA and CERCLA is shown
by this example: A tank containing a hazardous substance
begins to leak onto the ground. Under CERCLA, the owner
must notify the EPA and the state, stop the leak, and clean
up the spilled material. If the owner fails to take action, the
regulatory agency may act under CERCLA and then seek
reimbursement up to triple the cost of its expenses. Under
RCRA, the spilled hazardous substance and any contami-
nated soil become hazardous waste. The hazardous waste
must be removed, stored, transported, and disposed of in
accordance with RCRA requirements.
Design ConsiDeRations
For plumbing designers, the challenge is to design systems
that minimize the chance of leaks, contain any spills that
might occur, and segregate hazardous substances from both
nonhazardous process streams and incompatible hazardous
process streams. The design of a system that anticipates the
potential for leaks and spills must include suitable materi-
als, reliable joining, good fabrication, and provision for the
secondary containment of liquids in areas and systems that
pose a high spill risk.
RCRa and CeRCla
These two laws, together with the federal and state regula-
tions derived from them, have had a major impact on the
industrial management of hazardous substances and hazard-
ous wastes. Almost all nonaqueous liquids, many aqueous
mixtures, and many solids and gases are regulated when
they become wastes or are spilled.
The purpose of CERCLA is to limit the uncontrolled re-
lease or threat of release of hazardous substances into the
environment and to provide for a coordinated and effective
response to mitigate actual releases. CERCLA requires in-
dustrial risk evaluations, in the form of contingency plans,
and establishes a mechanism for governmental response to
environmental and health hazards. CERCLA does not require
any permits and does not force changes in current hazard-
ous substance handling methods. Nevertheless, a great deal
of publicity can result when the mishandling of hazardous
substances leads to an environmental incident. There also
can be an enormous cost to dispose of the hazardous wastes
generated during a spill. These are strong inducements to
chemical manufacturers and users to install process systems
that minimize risk.
RCRAs purpose is similar to CERCLAs, except that
RCRA regulates hazardous wastes from ongoing manu-
facturing activities. The goals of RCRA are accomplished
through strict licensing and operational standards for every
aspect of hazardous waste management.
RCRA requires identifcation numbers and/or permits
for every hazardous waste activity. The permit applica-
tion requirements are lengthy and technical for some of
the regulated activities. In some cases, the regulations
give performance standards that the designer must meet
to obtain a permit for the facility. In other cases, the com-
pliance method is almost completely specifed. Obtaining
Table 3-2 General Properties of Materials Used for Storage Tanks and Piping
Containment Materials Advantages Disadvantages
Carbon steel Compatible with petroleum products
and dry organics and incompatible
with many aqueous solutions.
Subject to attack by corrosive soils and
chemicals.
Stainless steel Better corrosion resistance than
carbon steel and higher structural
strengthThere are more than 70
standard types of stainless steel and
many special alloys.
Corroded by chloride and exposure to
reducing environments.
Fiberglass-reinforced
plastic (FRP)
Compatible with a wide range of
petroleum and chemical products, if
proper resin is selected.
Lacks the structural strength and impact
resistance of steel tanks.
Polyvinyl chloride Excellent chemical resistance to
acids, alkalis, and gasoline.
Lower structural strength than steels,
generally not suited for the storage or
handling of organic solvents such as
benzene, carbon tetrachloride, and acetone,
or use at temperatures above 140F (60C).
Concrete Generally good resistance to alkaline
chemicals, epoxy coatings often
applied to concrete to increase
chemical resistance.
Subject to cracking and spalling with
changes in temperature such as during
freeze/thaw cycles, uncoated concrete
absorbs solvents.
Polypropylene Resistance to all aqueous solutions
except strong oxidizers.
Low structural strength, temperature limit of
248F (120C).
Lined steel Chemical resistance of plastic and
structural strength of steel.
Relatively high cost for material and
installation.
4 Read, Learn, Earn MARCH 2012
READ, LEARN, EARN: Treatment of Industrial Waste
Many leaks occur as a result of material incompatibility
between the equipment and either the hazardous substances
handled or the atmosphere in which the equipment is uti-
lized. The incompatibility can be physical, such as polyvinyl
chloride (PVC) pipes melting at high temperatures or plastic
pipes dissolving in solvents they were not designed to contain.
Table 3-2 lists the general properties of the most common
tank and pipe materials. Specifc applications should be
checked with the appropriate chemical compatibility refer-
ences from the manufacturer.
Even the best designed liquid-handling systems are sub-
ject to occasional failure, particularly during liquid transfer
operations. Secondary containment is an important aspect of
any hazardous material system design to protect employees
and the environment. Secondary containment may include
a dike around a tank or tank farm or pipes within pipes for
systems handling extremely hazardous liquids. Common
secondary containment systems typically have the following
features:
Containment foors, pads, ponds, and dikes constructed
of materials impervious to the substance stored
Perimeter diking and storage reservoirs sized to contain
110 percent of the largest tank plus the maximum rain-
fall predicted to occur over 24 hours once in 10 years in
exterior areas (or 20 minutes of sprinkler water fow for
interior areas)
Pumps, drain valves, or siphons to empty the secondary
containment area to either a storage tank or a treatment
facility
Controls and procedures to prevent the accidental release
of contained spills and an alarm system to notify opera-
tions personnel if a spill occurs
Minimal equipment and practices for preventing trans-
fer spills should include overfll prevention including level
sensors, gauges and a high-level alarm, automatic valve and
pump shutdown, established transfer procedures including
an operator on duty, proper curbing and containment, re-
dundant valves and controls, vapor recovery, alarms, regular
inspections, and a maintenance program. The equipment
used in water treatment is operated to achieve the following:
mixing and focculation, sedimentation, clarifcation, flter-
ing, turbidity removal, metals removal, and disinfection.
Historically, underground tanks up to 10,000 gallons
(37,854 L) in capacity and occasionally larger have been
preferred for hazardous materials, primarily to minimize
fre risks. Unfortunately, many of these tanks were kept in
service too long and, because of corrosion, have leaked and
contaminated drinking water supplies. As a result, designers
now must compare the environmental and fre risks of the
aboveground tank. In either case, more attention must be
given in the design to ensure that an installation is resistant
to leaks and capable of containing spills. Soil conditions and
groundwater levels, which affect the design, must be evalu-
ated for each installation. Secondary containment of these
tanks is the primary method of ensuring against leakage.
elements of an inDustRial
wastewateR HanDling system
pH Control
Neutralization for pH control involves the chemical reaction
of an acid with an alkaline substance (a base), resulting in the
formation of a salt and water. In an aqueous solution, the acid
or base molecules dissociate and form ions. Sulfuric acid is
presented in the solution as H
+
(hydrogen) and SO
4
(sulfate)
ions and caustic soda as Na
+
(sodium) and OH
(hydroxide)
Figure 3-1 Acid/Caustic Neutralization Diagram
MARCH 2012 Read, Learn, Earn 5
Figure 3-3 Treatment System with Wastewater Stream Segregation
Note: Not to scale.
Figure 3-2 Conventional Electroplating Industry Wastewater Treatment
Note: Not to scale.
6 Read, Learn, Earn MARCH 2012
READ, LEARN, EARN: Treatment of Industrial Waste
ions. The H
+
ions of the sulfuric acid and the OH
ions of the
caustic soda have a strong attraction to each other and combine
to form H
2
O (water). For example, in the neutralization reac-
tion of H
2
SO
4
(sulfuric acid) and NaOH (sodium hydroxide),
the following process occurs:
H
+
2
SO
4
+ 2Na
+
OH
Na
+
2
SO
4
+ 2H
2
O
If excess hydrogen ions remain, the liquid will be acidic,
and with a surplus of hydroxide ions, the liquid will be al-
kaline.
The acidity or alkalinity of a solution is expressed on the
pH scale, with neutral water at a pH of 7, in the middle of
the range between extremely acid (pH = 0) and extremely
alkaline (pH = 14). The scale is logarithmic, so a pH of 3 is 10
times more acidic than a pH of 4. Buffers, such as bicarbon-
ate/carbonate, undergo a chemical change when strong acids
or bases are added to a solution and thereby act as capacitors
that must be flled before the pH will change.
A typical two-stage, continuous-fow pH neutralization
process is shown in Figure 3-1. For fows less than 10 gallons
per minute (gpm) (37.85 L/min), neutralizing in a batch basis,
with two tanks alternating between collection and treatment,
is sometimes preferred.
The most critical feature of the pH adjustment system is
the controller that activates the chemical feed pumps. The
controller must have the ability to prevent overfeeding of
either acid or base, which would cause wide pH swings and
subsequent repetitive chemical additions. Overfeeding is
most probable in wastewater with no buffering capacity near
the pH setpoint (e.g., deionized and soft water). Controllers
with multi-rate response adjustment should be specifed for
each application.
Sulfuric acid is the most costly method for pH adjustment
purposes, although in some cases the commercial 93 percent
acid must be diluted prior to use. The manufacturers rec-
ommendations for materials of construction, control of the
heat of dilution, and safety precautions should be carefully
followed. Carbon steel pipe and tanks are commonly used
for 93 percent sulfuric acid, with stainless alloy 20 (a high
nickel alloy) valves, as well as PVC and chlorinated polyvinyl
chloride (CPVC) plastics. For sulfuric acid at concentrations
below 93 percent, polypropylene (PP), fberglass-reinforced
plastic (FRP), PVC, CPVC, and lined steel are preferred.
Sodium hydroxide (caustic or caustic soda) in 50 percent
solution is the most convenient commercial alkaline material
for pH adjustment. Unfortunately, 50 percent caustic freezes
at 54F (12.2C), so indoor storage or heated tanks are neces-
sary. (Note that 20 percent caustic freezes at -18F [-27.7C].)
Caustic solutions may be handled in carbon steel, stainless
steel, and PVC tanks and pipe. Lime and hydrated lime are
considerably less expensive than caustic but must be fed with
dry feeders and/or slurry tanks, which require considerable
maintenance. Consequently, lime is favored in applications
where the cost outweighs the convenience of caustic.
Figure 3-4 Typical Continuous Treatment of Wastewater and Solids-handling System for Heavy Metals
Note: Not to scale.
MARCH 2012 Read, Learn, Earn 7
Removal of Dissolved and suspended metals
Another common industrial wastewater treatment require-
ment is the removal of dissolved and suspended metals. The
most popular method is to separate cyanide and chromium
VI wastewater sources from each other and all other metal-
bearing wastewaters. The cyanide is destroyed by oxidation
with chlorine (or a sodium hypochlorite solution) at a pH of
9 to 11, and the chromium VI is reduced to chromium III
with sulfur dioxide or sodium bisulfate at a pH of 2. Various
treatment methods are shown in Figures 3-2, 3-3, and 3-4.
For trace metals up to 1,000 parts per million (ppm), the
use of ion-exchange vessels containing resin beads tailored to
the application may be considered. Ion exchange is a revers-
ible chemical reaction wherein an ion (an atom or molecule
that has lost or gained an electron and thus acquired an
electrical charge) from a wastewater solution is exchanged
for a similarly charged ion attached to an immobile solid
particle. These solid ion particles are either naturally oc-
curring inorganic zeolites or synthetically produced organic
resins, which are the predominant type used today because
their characteristics can be tailored to specifc applications.
This process is similar to the process for purifying water for
laboratory or process applications. The exact ion combina-
tions are based on the metals to be removed. The exchange
vessels can be sized for the wastewater fow, or multiple ves-
sels can be manifolded together to handle higher wastewater
fows or to allow standby capacity. Automated controls and
accessories can be furnished to back-fush or regenerate the
vessels. The removed metals can then be reclaimed or safely
disposed. This technology should be evaluated against other
technologies for overall operating cost based on size and the
type of application.
oil/water separation
Oil/water separation may involve free-foating oils, mechani-
cal emulsions or diversions, and chemical emulsions. The size
of the oil droplets in emulsions may range from less than 20
microns () to more than 150 . In selecting the separation
equipment, the designer must consider the oil quantities,
droplet size, presence of emulsifers, temperature of the water
and oil, difference in the specifc gravity of the fuids, fuid
viscosity, pH, and other wastewater constituents.
Separators are on the market to suit every situation,
including simple settling tanks (e.g., American Petroleum
Institute separators), tanks with coalescing media to promote
the agglomeration of dispersed oils, and tanks with chemi-
cal pretreatment to promote the separation of chemically
emulsifed oils. Equipment options include sludge removal
and automatic oil skimming. In special conditions, such as
where oil is mixed with and adheres to suspended solids,
dissolved-air fotation separators may be necessary. Figure
3-5 shows a unit designed to remove free and mechanically
emulsifed oil.
Biological treatment
Wastewater discharging directly to surface or groundwater
must be treated to remove organic compounds, which would
deplete the dissolved oxygen in the receiving water. Typi-
cally, permits allow an average of 30 milligrams per liter of
fve-day biological oxygen demand (BOD5). Treatment is
accomplished by processes that convert soluble organic
compounds to biological cell mass, which can be separated
from the effuent by gravity in a clarifer. Colloidal material
and some nondegradable compounds are normally absorbed
in the settled solids.
Figure 3-5 Emulsifed Oil Removal Flow Sheet
Note: Not to scale.
8 Read, Learn, Earn MARCH 2012
READ, LEARN, EARN: Treatment of Industrial Waste
Biological wastewater treatment plants are expensive to
build and operate, and specialized experience is necessary to
produce a successful design. Consequently, a company faced
with biological treatment requirements should frst compare
the feasibility and economics of discharging to a municipal
treatment system to building its own facility. If the build
alternative is indicated, a choice must be made among the
available application methods, including activated sludge,
aerated lagoons, trickling flters and rotating flters, and the
anaerobic process. Expert advice is warranted.
RefeRenCes
Codes and standards
ANSI/ASME B31.3: Process Piping
API Spec 12D: Specifcation for Field Welded Tanks for
Storage of Production Liquids
API Spec 12F: Specifcation for Shop Welded Tanks for
Storage of Production Liquids
API Std 650: Welded Tanks for Oil Storage
International Boiler and Pressure Vessel Code
FM Global Data Sheet 7-83: Drainage Systems for Flam-
mable Liquids
NFPA 30: Flammable and Combustible Liquids Code
UL 142: Steel Aboveground Tanks for Flammable and
Combustible Liquids.
government Publications
Activated Carbon Process for the Treatment of Wastewater
Containing Hexavalent Chromium, U.S. Environmental
Protection Agency
Effuent Limitation Guidelines, U.S. Environmental
Protection Agency
Treatment of Organic Chemical Manufacturing Wastewa-
ter for Reuse, U.S. Environmental Protection Agency
Technology for the Storage of Hazardous Liquids: A
State-of-the-Art Review, New York State Department of
Environmental Conservation
CFR 40: Protection of Environment, U.S. Environmental
Protection Agency
technology and industry Handbooks
DeRenzo, D.J., Corrosion Resistant Materials Handbook,
4th edition, William Andrew Publishing/Noyes, 1985.
Kirk-Othmer Encyclopedia of Chemical Technology, John
Wiley and Sons Inc., 2004.
Perrys Chemical Engineers Handbook , 8th edition,
McGraw-Hill, 2008.
Schweitzer, Philip A., Handbook of Corrosion Resistant
Piping, 2nd edition, Krieger Publishing, 1985.
Ion Exchange for Heavy Metal Removal , Wastech Con-
trols and Engineering.
ResouRCes
American National Standards Institute: ansi.org
American Petroleum Institute: api.org
American Society of Mechanical Engineers: asme.org
National Fire Protection Association: nfpa.org
National Technical Information Service: ntis.gov
New York State Department of Environmental Conserva-
tion: www.dec.ny.gov
U.S. Government Printing Offce: gpoaccess.gov
Underwriters Laboratories: ul.com
MARCH 2012 Read, Learn, Earn 9
READ, EARN, LEARN: Laboratory Gases CONTINUING EDUCATION: Treatment of Industrial Waste
CE Questions
Treatment of Industrial Waste (CEU 185)
Which of the following regulates the 1.
generation, storage, treatment, and
disposal of hazardous wastes?
Clean Water Act a.
Resource Conservation and Recovery b.
Act
Superfund c.
CERCLA d.
Which of the following is considered a 2.
hazardous material?
hazardous substances a.
substances that are capable of posing b.
an unreasonable risk to health when
transported in commerce
hazardous wastes c.
all of the above d.
________ is also known as Superfund. 3.
EPA a.
RCRA b.
CERCLA c.
NPDES d.
Industrial discharges to a publicly owned 4.
treatment works are called what?
untreated sewage a.
direct discharges b.
indirect discharges c.
foreign substance d.
________ is designed to limit the 5.
uncontrolled release or threat of release
of hazardous substances into the
environment.
CERCLA a.
RCRA b.
Effuent Guidelines Program Plan c.
Clean Water Act d.
Plumbing designers must design systems 6.
that ________.
contain spills a.
minimize leaks b.
segregate hazardous substances c.
all of the above d.
Reading the article and completing the form will
allow you to apply to ASPE for CEU credit. If you
earn a grade of 90 percent or higher on the test,
you will be notified that you have logged 0.1
CEU, which can be applied toward CPD renewal
or numerous regulatory-agency CE programs.
(Please note that it is your responsibility to deter-
mine the acceptance policy of a particular agency.)
CEU information will be kept on fle at the ASPE
ofce for three years.
ASPE Continuing Education Application Form
This form is valid up to one year from date of publication. Expiration date: Continuing education credit will be given for this examination
through March 31, 2013. Applications received after that date will not be processed.
Submit this form with payment via mail (ASPE Read, Learn, Earn, 2980 S. River Road, Des Plaines, IL 60018), fax (847-296-2963), or email
aspeeducation@aspe.org.
Please print or type; this information will be used to process your credits.
Name ______________________________________________________________________ ASPE Membership No. ______________
Organization ___________________________________________________ Daytime telephone _____________________________
Billing Address ________________________________________________________________________________________________
City _________________________________________ State/Province ________________________ Zip ______________________
E-mail _______________________________________________________________________ Fax ____________________________
PE State _____________________________________________ PE No. _________________________________________________
Notice for North Carolina Professional Engineers: State regulations for registered PEs in North Carolina now require you to complete ASPEs online CEU validation form
to be eligible for continuing education credits. After successfully completing this quiz, just visit ASPEs CEU Validation Center at aspe.org/CEUValidationCenter.
I certify that I have read the article indicated
above.
Signature
Payment:
Member: Free
Nonmember: Each examination: $35
Personal Check (payable to ASPE)
Business or government check
DiscoverCard VISA MasterCard AMEX
If rebilling of a credit card charge is necessary, a $25
processing fee will be charged.
ASPE is hereby authorized to charge my CE
examination fee to my credit card
Account Number
Expiration date
Signature
Cardholders name (Please print)
Which of the following has excellent 7.
chemical resistance to acids, alkalis, and
gasoline?
stainless steel a.
polyethylene b.
polyvinyl chloride c.
polypropylene d.
Which of the following can be used to 8.
prevent transfer spills?
proper curbing and containment a.
overfll prevention b.
redundant valves and controls c.
all of the above d.
The ________ is the most critical feature 9.
of a pH adjustment system.
chemical feed pump a.
controller b.
pH probe c.
agitator d.
What is the most convenient commercial 10.
alkaline material for pH adjustment?
lime a.
50 percent caustic b.
sulfuric acid c.
bicarbonate d.
________ may be considered to remove 11.
trace metals up to 1,000 ppm from
wastewater.
ion exchange a.
pH adjustment b.
neutralization c.
biological treatment d.
You must consider ________ when 12.
selecting oil/water separation
equipment.
temperature of the oil and water a.
oil droplet size b.
fuid viscosity c.
all of the above d.
Circle the correct answers below.
10 Read, Learn, Earn MARCH 2012
C
E
U
1
8
6
Pharmaceutical
Laboratory
Drainage
Systems
Continuing Education from the
American Society of Plumbing Engineers
APRIL 2012
ASPE.ORG/ReadLearnEarn
Sanitary Drainage anD Vent
SyStemS
Te design of the domestic sanitary-drainage and vent systems are
standard plumbing systems, with efuent discharging directly into
the public sanitary sewer. All plumbing fxtures and equipment
and all sanitary-drainage piping shall be designed and installed
in strict conformance with the applicable plumbing code for the
project location. In terms of the design of these systems, there is
nothing unique to pharmaceutical facilities that is not applicable
to conventional plumbing systems.
It is good practice to have the sanitary house sewer and the dis-
charge from an acid-neutralizing basin run separately outside
the building then combine to dilute the neutralized acid efuent
as much as possible prior to its discharge into a public sanitary
sewer.
Special plumbing-Fixture requirementS
One unique requirement of pharmaceutical clean rooms is a
hand-washing sink in the gowning area at the entrance to the
clean room. To be efective, the sink water-supply controls shall
be capable of being operated without having hands touch them.
Current practice uses proximity devices to turn the water on when
hands are placed under the spout.
Laboratory Drainage anD Vent
SyStemS
introduction
A laboratory is generally considered to be any room or area
within a building where investigation, testing, experiments, and/
or research is conducted. Pharmaceutical facilities generally pre-
pare, manufacture, and package drugs and devices of all kinds.
Manufacturing is generally considered to be any facility where
a product is the end result of having material or components
packaged or assembled from parts obtained elsewhere or made
within the facility.
Te purpose of the drainage system installed in a typical chemis-
try or physics laboratory is to collect and transport liquid wastes
from the laboratory fxtures and equipment for discharge into a
facility chemical-waste treatment system for appropriate treat-
ment and disposal or into the acid-waste treatment system for
neutralization and eventual discharge into the public sanitary
sewer. Te acid vent system equalizes fow in the drainage system
and maintains constant atmospheric pressure in the same man-
ner as the sanitary drainage vent system does.
Laboratory waste consists primarily of dilute and concentrated
mixtures of liquid chemical substances of mineral and organic
origin and water. Acids of many types are usually present. Labo-
ratory waste is discharged from sinks, cup sinks, fume hoods,
and other similar fxtures and equipment. Discharge from foor
drains, autoclaves, and glass washers, and condensed water from
various sources are also included. Except for exotic discharges,
laboratory waste is assumed to have the viscosity of water. Te
drainage piping is sized based on that assumption.
Te above defnition of a laboratory and the classifcation of
so-called typical laboratory waste is meant to be used only for
this manual to distinguish this type of efuent from that of other
waste-drainage systems.
pH deFinition
Any dissolved impurity in water separates to form negative and
positive charged atoms called ions. Negative ions are called
cations because they migrate to the cathode and positive ions
are called anions because they migrate to the anode.
All acid compounds consist of hydrogen combined with an acid
radical. In a mix ture of acid and water, hydrogen ions result. pH is
a measure ment of the hydrogen ion concentration of a solution.
Since the balance of hydroxyl (cation) and hydrogen (anion) ions
must be constant, changes in one ion concentration produce cor-
responding changes in the other. Te pH value is calculated from
the logarithmic reciprocal of the hydrogen-ion concentration in
water. Te pH scale ranges from 0 to 14, with 0 being acid, 14 be-
ing al kaline, and 7.0 being neutral. A change of 1 unit represents
a tenfold increase (or decrease) in strength. pH is not a measure
of alkalinity.
Selection oF piping and Joint material
Te majority of the efuent from an average laboratory consists
primarily of a mixture of water and acid. Te chemicals used, if
toxic to the staf, are confned to fume hoods. Information regard-
ing the extent and concentration of all the chemicals expected
to be used in the laboratory should be obtained from the end
user. At one time or another, these chemicals will fnd their way
into the drain pipe. Te piping system and jointing method must
resist them all.
An often-used material for piping above the foor drainage and
vent piping from laboratory fxtures is fre-retardant polypropyl-
ene (PP), with either heat-fused socket or proprietary screwed-
mechanical type joints. Other acceptable materials are glass with
compression-sleeve joints and high-silicon cast-iron with caulked
or compression-gasket joints. Although Polyvinyl Chloride (PVC)
and Chlorinated Polyvinyl Chloride (CPVC) pipe have the lowest
initial cost, they also have a limited range of chemical compat-
ibility, with PVC having a low temperature rating. Polyvinylidene
Flouride (PYDF) pipe had higher chemical resistancy and tem-
perature ratings than PP, PVC or CPVC pipe but also has higher
Reprinted from Pharmaceutical Facilities Plumbing Systems by Michael Frankel, 2004, American Society of Plumbing Engineers
Note: In determining your answers to the CE questions, use only the material presented in the corresponding continuing education
article. Using information from other materials may result in a wrong answer.
2 Read, Learn, Earn APRIL 2012
read, learn, earn
costs. Polytetrafuoroethylene (PTFE) is the most resistant to the
widest variety of chemicals, has the highest temperature rating,
and has the highest cost.
Piping underground could also be polypropylene with heat-fused
socket joints or high-silicon cast iron with compression-gasket
joints. Glass piping should be encased in a continuous sleeve of
polyethylene for protection.
Vent pipe shall be the same material as the drain pipe. Te vent
shall be carried up to above the roof level. Vent piping penetrating
the roof shall not be glass. An adapter can be used and any other
acceptable acid-resistant pipe material can be provided through
the roof penetration.
SyStem deSign conSiderationS
Te same general system design considerations apply to the labo-
ratory drainage system as apply to the sanitary drainage system,
including placement of cleanouts. Each fxture shall be individu-
ally trapped and vented. Clean water, such as is discharged from
air compressors and other condensate drains, could also spill
into the laboratory drainage system when convenient. Because
of possible stoppages that could food all the pipe, the entire
laboratory waste system shall be the of the same acid-resistant
piping material.
Where the only waste discharge is from laboratory fxtures, the
use of fxture unit schedules for pipe sizing is acceptable, except
that simultaneous use should be factored into the sizing process.
When the efuent is from a discharge whose fow is known (in
gpm), base the size on that gpm and the equivalent gpm from
the fxtures. Te pipe shall be sized using the actual pitch and
a half-full pipe. Table 2-1 gives the capacity of horizontal drain-
age piping fowing half full at various slopes. Table 2-2 gives the
capacity of vertical stacks.
Te laboratory drainage and vent system shall be separate from
all other systems. Te acid drainage shall be adequately treated
and run separately outside the building, then combined on the
site with the sanitary waste line.
laboratory acid-WaSte treatment
All acid waste requires neutralization to a pH of between 7.5 and
4.0 before it is permitted to discharge into any public sewer for
disposal. Commonly accepted practice permits local authorities
to allow primary treated efuent to discharge directly into the
public sanitary sewer system after only pH treatment. Te most
often-used primary procedures are direct, continuous contact
with limestone chips in an acid-neutralizing basin or continu-
ous or batch treatment in an automated neutralization system
utilizing chemical-feed neutralizing.
An acid-neutralizing basin operates on the principle of a chemical
reaction between the acid and the limestone chips. Each basin
shall be designed by the manufacturer to allow sufcient contact
time for the chemical reaction to accomplish complete neutral-
ization based on the maximum fow rate anticipated. Actual tests
have shown that 100 lb. of limestone chips treat 97 lb. of sulfuric
acid and 75 lb. of hydrochloric acid. Efuent consisting mostly of
sulfuric acid should be treated with dolomite limestone chips.
For general laboratory waste, several devices for treatment using
limestone chips are available. For single, isolated sinks, an acid-
neutralizing trap should be considered. For a small number of
sinks in a cluster, a shelf-mounted, small-diameter basin could
be used. It should be limited to the treatment of acids from a
small number of fxtures and used only in remote locations. A
larger basin, such as that illustrated in Figure 2-1, is available
to treat the efuent from a large number of laboratory sinks. If
the discharge of oil or grease is expected in the laboratory waste
stream, the installation of an interceptor basin before the acid
sump is recommended. Some objectionable contaminants can
coat individual chips and prevent the proper chemical action
required to neutralize the acid.
For a larger number of fxtures or equipment and where treat-
ment by limestone chips alone is not practical, a system consist-
ing of single or multiple basins and/or a mixing tank should be
installed. If the system is located at a low level, a pump will be
required to discharge up to the level of the sewer. A sophisticated
Table 2-2 Drainage Capacity of Stacks
Pipe diameter, in. 1 1 2 2 3 4 5 6 8
Capacity, gpm 6.5 10.5 22.6 41 67.2 143 261 423 915
Table 2-1 Capacity of Horizontal Drainage Piping Flowing Half Full
Actual
Inside
Diameter
of Pipe,
in.
Discharge rate anD Velocity
1
16 in./ft Slope
1
8 in./ft Slope in./ft Slope in./ft Slope
Discharge,
gpm
Velocity,
fps
Discharge,
gpm
Velocity,
fps
Discharge,
gpm
Velocity,
fps
Discharge,
gpm
Velocity,
fps
1 3.40 1.78
1 3.91 1.42 5.53 2.01
2 8.42 1.72 11.9 2.43
2 10.8 1.41 15.3 1.99 21.6 2.82
3 17.6 1.59 24.8 2.25 35.1 3.19
4 26.70 1.36 37.8 1.93 53.4 2.73 75.5 3.86
5 48.3 1.58 68.3 2.23 96.6 3.16 137.0 4.47
6 78.5 1.78 111.0 2.52 157.0 3.57 222.0 5.04
8 170.0 2.17 240.0 3.07 340.0 4.34 480.0 6.13
10 308.0 2.52 436.0 3.56 616.0 5.04 872.0 7.12
12 500.0 2.83 707.0 4.01 999.0 5.67 1413.0 8.02
a
Computed from the Manning Formula for -full pipe, n = 0.015. For -full pipe, multiply discharge by 0.274; multiply velocity by 0.701. For -full pipe,
multiply discharge by 1.82; multiply velocity by 1.13. For full pipe, multiply discharge by 2.00; multiply velocity by 1.00. For smoother pipe, multiply
discharge and velocity by 0.015 and divide by n value of smoother pipe.
APRIL 2012 Read, Learn, Earn 3
tion or burns. Ingestion will destroy the tissue of the
mouth, throat, and stomach. Extreme care should be
exercised in the handling and cleanup of all acids.
Tis mandates that emergency drench equipment be
provided immediately adjacent to all hazards and lo-
cations where spills and other accidents could occur.
If several people are normally present at a hazard-
ous location, multiple drench equipment should be
provided. Where fumes may be given of, emergency
breathing apparatus shall be provided.
For the laboratory environment, emergency showers
shall be provided immediately outside every room.
Where rooms are adjacent, a single shower is ac-
cepted. Floor drains are not required but will prevent the foor
surrounding the shower from becoming wet and a hazard to help-
ing individuals. Every room shall have an emergency eyewash
inside the room, usually mounted on a sink or free standing if
sink mounting is not practical.
Where vapor is possible, fog nozzles using water to suppress the
vapor and foam systems to prevent vapor from rising should be
considered.
common acidS
Acids are widely used in the pharmaceutical-processing industry.
Te acid most often used is sulfuric acid (H
2
SO
4
). Sulfuric acid is
commercially available in many concentrations and as various
percentages of oleum. Oleum is sulfuric acid containing sulfur
trioxide dissolved in the acid; these grades are called fuming
grades.
Selection oF equipment, piping, and Joint
materialS
Generally recommended piping materials for these acids at low
temperatures (140F and lower) and up to 90% concentration are
PVC, CPVC, PP, Polyvinylidene Flouride (PVDF), Ethylenetetra-
fuoroethylene (ETFE) and High Density Polyethylene (HDPE)
plastic, glass, alloy 20, duriron and Fiber Reinforced Plastic (FRP)
piping with special resins. At 90% and higher concentration,
carbon steel schedule 80 is often used. Stainless steel is generally
unsuitable, except for olium greater than 103% concentration.
Vent lines should be of the same material as the drain line.
Valve types include ball, gate, and diaphragm, with gate valves
being the most commonly used. For low pressure and tempera-
tures suitable for specifc plastic pipe, plastic is often used. For
higher temperatures and pressures, alloy 20 is preferred. In all
cases, because of diferences in manufacturing, pipe vendors
should be consulted as to the suitability of materials for specifc
acid piping service.
Centrifugal pumps constructed of SS alloy 320 with Tefon pack-
ing are in common use. Other manufacturers use FRP and plastic
pumps. Also available are metallic pumps lined with plastic or
glass. Temperature limits should be carefully checked for mate-
rial suitability.
accident conSiderationS
Spills of concentrated acids from tanks onto foors and equipment
should be immediately washed of and fooded with water, which
is then routed to the acid drainage system for neutralization.
arrangement of probes, chemical feed pumps, level indicators,
and alarms will be required. An agitator or mixer may be installed
in the basin to mix the acid with the caustic. Te addition of a re-
corder may be desired. Te acid-neutralizing system operates on
the principle of automatically adding proper amounts of caustic
to the incoming acid waste, thereby neutralizing the acid. Te
probe is connected to an automatic caustic feed pump that intro-
duces the proper amount of neutralizing liquid into the basin or
mixing tank. Te most commonly used neutralizing chemical is
caustic soda. Continuous treatment may also require additional
downstream sensing probes and chemical additive locations to
ensure that the discharge is within acceptable limits. Figure 2-2
illustrates a typical continuous waste-treatment system. Various
manufacturers have numerous proven and successful methods
of acid treatment.
It is good engineering practice to have the discharge from the
neutralizer routed separately into the sanitary house drain out-
side a building for dilution prior to its ultimate discharge into the
public sewer. Tis may also be necessary for local authorities to
monitor the waste stream without entering a building.
For a preliminary determination of the number of sinks required
for an average laboratory, allow 1 sink for each 200 ft2 of labora-
tory area. Each sink will discharge 1 gpm. Cup sinks will discharge
0.5 gpm. For a maximum fow rate, assume that 50% of the sinks
could discharge simultaneously.
aciD-WaSte Drainage
Acid waste from pharmaceutical facilities consists of accidental
spills originating from tanks and piping and anticipated waste
from equipment discharging into drains. Very often, the drainage
piping has to carry any of the acids used as part of the process.
Where spills are directed into holding tanks, the drainage piping,
tanks, pumps, and piping necessary to convey the efuent to
treatment facilities is normally part of the plumbing engineers
responsibility.
Te most important considerations in the selection of piping,
valves, and tanks for acid are the concentration and temperature
of the acid. Acid waste water from chemical and other facilities
must be neutralized to a pH of 4.0 or higher prior to discharge
into the sanitary system.
HealtH and SaFety concernS
All grades and concentrations of acids can cause severe damage
to the eyes and tissues of the body. Contact with the skin will
cause irritation and burns. Contact with the eyes could cause
blindness. Inhalation of the mist or vapors could cause lung irrita-
Figure 2-1 Large Acid-Neutralizing Basin
4 Read, Learn, Earn APRIL 2012
READ, LEARN, EARN: Pharmaceutical Laboratory Drainage Systems
Tanks that contain this spillage should
be of a suitable plastic. Since water reacts
rapidly with the acid and splatters, caution
should be exercised. Heat and fumes are
also given of. Breathing the fumes will
cause throat and lung injury. Where this
situation is possible, suitable emergency
breathing apparatus should be provided.
An emergency shower should be provided
in the immediate vicinity of acid storage
and pipe routing.
Sulfuric acid is nonfammable but highly
reactive. Below a concentration of 75% it
reacts with carbon steel and other metals to
form hydrogen. It is particularly hazardous
when in contact with carbides, chlorates,
nitrates, fulminates, picrates, and pow-
dered metals. In higher concentrations it
will ignite combustible materials such as
oily rags and sawdust. Dry chemicals or
carbon dioxide are the fre-suppression
methods of choice.
Oleum spills, because of the danger of
fumes, should be contained by curbs and
the liquid diverted away from the area of a
spill to a containment area where the liquid
will be neutralized. Te resulting liquid should be absorbed with
diatomaceous earth, expanded clay, or another nonreactive mate-
rial. Tis material should be carted away for suitable disposal.
raDioactiVe-WaSte Drainage anD
Vent SyStemS
general
Radioactive materials are used for various types of procedures.
When pharmaceutical facilities use them, they generate low
quantities of radioactive waste and use materials with low levels of
radioactivity. Terefore, a less stringent set of regulatory require-
ments is necessary compared to those for facilities discharging or
producing large quantities of radioactive wastes. Te principles
of drainage-system design apply to all kinds of systems, though
some may have signifcantly higher levels of radiation than most.
Te design philosophy is the same, but the documentation that
must be submitted for the protection of the public and workers
in the event of any accident is considerably more complex for
facilities having higher quantities of radioactive material and
levels of radiation. Because of the small amount of radioactive
material present at pharmaceutical facilities, larger storage and
treatment systems are not provided and severe safety require-
ments are not necessary.
With the exception of providing radiation shielding where neces-
sary, the requirements for the use of radioisotopes in laboratories
are essentially no diferent than the requirements for other labora-
tories handling toxic chemicals or pathogens. Te ideal objective
is to keep the exposure of workers, staf, and the general public to
zero. Since this is not realistic, it is required not only to prevent
overexposure but to keep any exposure to radiation as low as is
reasonably achievable. Te design shall implement criteria that
will eliminate or reduce to allowable levels the radiation exposure
of workers and maintenance personnel and prevent exposure
of the general public to unacceptable amounts of radiation by
waterborne radioactive waste (radwaste).
tHe nature oF radiation
Radioactivity is the spontaneous emission of harmful par-
ticles from the unstable nucleus of an atom changing its atomic
structure and creating a new element. Tere are many interme-
diate steps in the stabilization cycle that include the formation
of other less complex radioactive byproducts called isotopes.
Tese byproducts in turn decay to form other unstable isotopes
as the cycle continues. Te end result is an element that is highly
stable. As an example, the end product of uranium is lead. One
of the intermediate byproducts of uranium is radon.
Radiation is a general term that means any or all of the fol-
lowing: alpha rays, beta rays, gamma rays, neutrons, x-rays, and
other atomic particles. Tere are three general classifcations
of radiation of concern, namely alpha, beta and gamma. Alpha
radiation is actually a helium atom with a high velocity. Beta
radiation is an electron with a high velocity. Gamma radiation
is a particle similar to a photon, which is light. Alpha and beta
radiation can generally be stopped by the skin or clothing, paper,
or another similar light material. Alpha loses energy very quickly
in air and is no practical concern for distances greater than 12 in.
High-energy beta radiation is commonly contained by only 1 in.
of solid, dense plastic. Beta is denser, carries more energy greater
distances than Alpha, and will burn bare skin and in particular,
damage the eye, but will generally not penetrate into the body to
cause any internal damage. Te greatest danger with beta radia-
tion is to the eyes, particularly when the eye is directly exposed
close to the source.
Gamma radiation is electromagnetic in nature. It carries the most
energy and therefore is the most dangerous to humans. Its wave-
Figure 2-2 Continuous Acid-Neutralizing System
Note: Variations of this setup are available, including one large tank with three compartments instead of three separate tanks.
APRIL 2012 Read, Learn, Earn 5
length is shorter than light waves. When generated, it is similar
to x-rays and behaves in a manner similar to light waves. When
released from a source, gamma rays have a mass and velocity that
has a measurable energy potential.
radiation meaSurement
Radioactivity is a general term used for the total release of radia-
tion of all types from a source. Its is measured in disintegrations
per second (dps). Tis measurement is possible for gamma radia-
tion because in most radioactive materials, dps also produces a
known amount of gamma radiation. However, the best manner
of measuring gamma radiation is from the energy it produces per
kilogram of air. Because the instruments needed to measure ra-
diation this way are very expensive, this method is not widely used
outside the laboratory. Te so-called Geiger-Mueller counter is
the most common method of measuring radiation. It measures
the penetration of ionizing radiation particles that enter a sealed
tube where the particles strike the gas creating an electrical im-
pulse between two electrodes connected to a suitable counting
device. If an amplifcation device is used, the electrical impulses
can be heard in the form of static. Te more modern instruments
have a digital readout.
Units of Radiation dose
Particulate radiation is measured by the number of disintegra-
tions per unit of time. A curie is equal to 3.710
10
disintegrations
per second. One millicurie is 0.001 curie, or 3.710
7
dps. One
rad is defned as the dose corresponding to the absorption of
100 ergs/gram of tissue. A roentgen measures ions carrying a
total of 2.5810
4
coulombs of electrical energy.
Since the term radiation is a general one, a more specific
method must be used to measure its efect on humans. Tat
measurement is called a dose. A dose is defned as the total
quantity of radiation absorbed by the body or any portion of the
body. Much of the time, the dose is modifed by reference to a
unit of time. Tis difers from radioactivity because all radiation
is not absorbed by the body.
A rad is a measure of the dose to body tissue in terms of energy
absorbed per unit mass. Gamma radiation is the most common
type of radiation measured.
Te most important measurement is the radiation equivalent to
man, or rem. A rem is the measure of ionizing radiation pass-
ing through or absorbed by the body in terms of the biological
efect relative to a dose of 1 roentgen of x-rays. Te relation of the
rem to other dose units depends upon the actual biological efect
to the particular part of the body being studied and the actual
conditions and amount of time of the irradiation. One rem is the
equivalent of 1 roentgen due to x or gamma radiation, and also
1 rad due to x, gamma, or beta radiation. One rem of high-fux
neutrons is roughly equivalent to 14 million neutrons per cm
2
incident to the body.
alloWable radiation levelS
Tere is no exact radiation level that is certain to cause any indi-
vidual permanent harm. Many scientists believe there is no level
below which radiation is harmless. Tere is a background level of
radiation that exists all over the world. Te most common source
is the sun, which produces what is called cosmic radiation. In
addition, there are many substances that emit radiation, such
as fy ash from burning organic fuels (particularly coal), granite,
and many other natural substances that contain trace isotopes
of elements. One of the most common of these trace elements is
carbon 14, used by scientists to date many materials.
Te Nuclear Regulatory Commission (NRC) is a governmental
body that has the responsibility for establishing criteria for the
feld of radioactivity. Tese criteria appear in the federal govern-
ments Code of Federal Regulations.
All personnel working at any site that has a possibility of exposure
to radiation are required to wear some type of exposure detec-
tion device that allows accurate determination of their actual
exposure. Te photographic badge is the most common device
and is used where sensitivity is required. A pen-shaped device
called a dosimeter is commonly used where there is less need
for accuracy. It is used where the instantaneous determination
of dose is necessary.
An unrestricted area is any area within a facility that is not spe-
cifcally controlled for the purpose of protecting any individual
from radiation or radioactive materials. A restricted area is
access controlled. Another term, environs, may also be used to
describe areas adjacent to a restricted or high-radiation area.
A high-radiation area is defned as any accessible area within a
facility that is capable of allowing the body to receive 100 millirem
(mrem) of radiation in a 1-hour period.
SHielding
Te purpose of shielding is to reduce or eliminate radiation
emanating from any source within the facility. Te greater the
density, the more efective the material, so lead is universally
used for this purpose. Another commonly used material is con-
crete. In terms of shielding, 0.1576 in. of lead is the equivalent of
12 in. of concrete. Te basic philosophy is that concrete used as
a structural element of the building serves a second purpose as
a very good shielding material. It is up to the Radiological Safety
Ofcer (RSO), whose responsibilities we discuss later, to deter-
mine the type and placement of shielding to lower radiation in
specifc areas. Radiation travels in a straight line, therefore, if a
tank or a length of pipe has to be shielded, the proper manner is
to form a labyrinth, so that the shine from the tank cant escape
in a straight line.
Te materials most commonly used for shielding purposes are
concrete and sheet lead. Other materials that have proven efec-
tive include: (1) lead-lined concrete blocks, (2) lead-lined lath for
plaster, and (3) lead-lined panels and gypsum boards.
Two levels of barrier are set up to reduce radiation levels: primary
barriers, which are the frst line of defense, and secondary barri-
ers, which are used to eliminate leakage radiation and scattered
radiation where it may possibly exist.
radioactive materialS
Radioactive materials are used for the following fve general
purposes:
1. Imaging sciences.
2. Diagnostic purposes.
3. Treatment purposes.
4. Industrial uses.
5. Research.
6 Read, Learn, Earn APRIL 2012
READ, LEARN, EARN: Pharmaceutical Laboratory Drainage Systems
Almost all of the materials used are isotopes. An isotope is a
form of an element with a diferent (or excess) number of neutrons
in its nucleus. Because of this diference, the atom is unstable.
Isotopes are identifed by their atomic weight, which is the num-
ber of neutrons and protons in the nucleus.
Tere are a great number of isotopes in use today. Some of the
more common are:
1. Iodine 131 (8-day half-life).
2. Phosphorus 32.
3. Technetium 99 (6-hour half-life).
4. Calcium 45.
5. Carbon 14.
6. Strontium 90.
7. Radium 226.
Since radioactive materials of any given amount remain active
for diferent periods of time, it is not possible to predict when any
material will become completely stable. Te method used is to
determine when a specifc material loses one half of its radioac-
tivity. Tis is called its half-life.
SyStem deSign
the appRoval pRocess and application
ReqUiRements
Te use of any radioactive material requires the licensing of the
site for a specifc purpose, quantity, and amount of radioactive
material. Application for this license is made to either the NRC
or a particular state. Tose states that have elected to adapt the
NRC regulations and provide their own staf for the purpose of
issuing and approving licenses are called agreement states. In
some cases, these states make additional regulations of their own.
Tose states that rely on the NRC to review and issue licenses
are non-agreement states. Te application is made to the ap-
propriate party.
Te duties of the Radiological Safety Ofcer (RSO) include admin-
istration, monitoring personnel exposure limits, and controlling
any release of radio nuclides to the sewer system. In addition, it is
the RSO who usually works with engineers in the design phase of
the facility to ensure that the piping runs and all other mechanical
work will result in a low exposure to people within the facility. For
the most part, this work is meant to ensure that facility personnel
do not exceed the maximum permissible radiation dose allowed
under the applicable codes for any particular type of radioactive
material present and that non-staf members are not subject to
unacceptable levels of radiation. Te RSO is also responsible for
the following:
1. Teaching facility staf of the potential dangers.
2. Keeping the necessary records for the facility.
3. Keeping inventory of material and records disposal.
4. Te concentration of materials at the facility.
5. Assisting engineers in the design of mechanical systems.
6. Designating areas within the facility to be restricted.
GeneRal desiGn cRiteRia and consideRations
Te prime consideration in the design of any facility is a con-
cept concerning the exposure of personnel to radiation called
ALARA, which is an acronym for as low as reasonably achiev-
able. Adherence to this concept requires that in the design of the
facility consideration must be given to every reasonable method
to limit the possible exposure of personnel inside the facility and
keep the presence of radioactivity in any unrestricted area to a
level that is as low as reasonably achievable. Te designer must
take into account the current state of technology, the economics
of further improvements in relation to benefts to the public health
and safety, and other socioeconomic considerations relating to
the utilization of radioactive material in the general public inter-
est. Te designer of the facility must also make a reasonable efort
to eliminate residual radiation. One of the overriding concepts is
the worst-case possibility, wherein the worst possible combina-
tion of circumstances is used to determine the possible level of
radiation and the amount of exposure during a period of time.
Tis concept should not be overused; a general rule is to have only
one accident at a time. As an example, a serious spill and a fre
would not be considered as likely to occur simultaneously.
Human or animal waste, even that contaminated with radioactiv-
ity, is exempt from all NRC regulations, requiring only compliance
with local codes as far as disposal, sizing, and all other criteria
applicable to standard drainage systems. Also many isotopes
are exempt from regulations regarding disposal into the public
sewer.
Another requirement is that the liquid radwaste to be discharged
shall be diluted with the ordinary waste efuent from the rest of
the facility before being discharged to the public sewer system.
Tis usually requires that the radwaste piping frst be kept sepa-
rate from the rest of the facilitys efuent but then be combined
before leaving the building for discharge into a public sewer. A
method should be provided for the RSO to take a grab sample of
the radwaste stream if desired, such as a valved outlet from both
the radwaste line and the combined discharge.
Te pitch of the piping should be kept as steep as possible in order
to empty the pipe quickly and allow a scouring action to keep the
radioactive solids in suspension.
It is common practice to have high levels of radiation confned to
glove boxes or protected fume hoods. Te small amount of liquid
waste produced from this equipment would be stored in shielded
containers below the equipment and removed periodically. If
storage of larger quantities of low-level radwaste is required, the
radwaste is piped to a holding tank. A common holding time is
ten half-lives of the efuent. Usually, radwaste is stored for dis-
posal on the site, outside of a building and where easy transfer of
the radwaste is possible. Te removal must be done by licensed
waste-disposal contractors who remove the waste from the hold-
ing tank into a special truck, which transports the liquid waste
to a designated site suitable for disposal of low-level radwaste.
Te solid wastes, such as gloves, wipes, and the like, are stored in
special containers, which are removed to the disposal area with
the liquid radwaste.
Floor drains are normally not desired in laboratories. If there
is a spill of radioactive material, it is wiped up by hand using
absorbent material, and the solid containing the spill is put in a
special radwaste holding container within the lab. If, however, a
foor drain is to be installed, all the major manufacturers make
stainless steel drains. For testing purposes and to close of a drain
when it is not expected to be used, each drain should be supplied
with a closure plug. If there are areas that may have a spill, the
foor must be pitched to a foor drain. A generally accepted value
for the pitch of the foor is 1 in. per 20 ft. Te thickness of the slab
APRIL 2012 Read, Learn, Earn 7
must be closely coordinated because the slab should be thinnest
at the drain and thicker at the ends of the area served to make up
the pitch. It is not practical to cast the slab evenly and add a top-
ping because there is a tendency for thin set topping to crack and
chip and create the possibility of a radioactive spill permeate the
top coating. It is necessary to indicate the top of drain elevation
at each drain since the slab depth is greater the longer the run to
the drain. Tis also makes it easier for the shop fabricator to make
up accurate pipe spools and foor drain extension collars.
Drains also require special treatment. Tey should also be manu-
factured of stainless steel. Tere will be diferent types of drains in
diferent areas, and they may be installed at diferent elevations.
Because of this and the probability that the piping will be made
in spools (preassembled sections of piping), it is a good idea to
number all the individual drains on the design drawings. A tag
next to each drain can be used to provide information regarding
type, number, and elevation.
Since fttings are a natural crud trap, avoid running piping in, un-
der, over, or adjacent to unrestricted areas in a facility. If this is not
possible, place the line where additional shielding can be added
either at the time of construction or after the start of actual use,
when the RSO may determine by survey that additional shielding
is necessary. Much of the time, the ability to take apart the joint
and fush out any crud is an advantage. Any of the popular joints
for no-hub or grooved pipe are acceptable, as well as glass pipe
if used in a laboratory for chemical resistance.
Be generous with cleanouts. Tey may be needed to fush out
the line to reduce spot high radiation rather than having to rod
it out.
pipe mateRial selection
Te pipe selected for the radioactive drainage system depends
upon the type of radiation and the level of radioactivity, which, in
turn, depends upon the amount and type of radioactive material
at the facility. In general, an ideal radwaste drainage pipe should
have the following properties:
1. It must be nonporous.
2. It must be easy to clean and decontaminate.
3. It should be acid resistant.
4. It should be nonoxidizing.
5. Te joints should not form crud traps.
6. Joint materials must not be afected by radiation exposure.
It is possible in very high radiation areas to have a pipe afected by
the radiation present. Te oxides of the pipe can become radioac-
tive or the pipe itself could be weakened. Another consideration
is the weakening of elastomeric seals or gaskets because of high
levels of radiation. For this reason, Tefon is never used where
anything more than a very low level of radiation is present. Other
materials should be investigated regarding suitability of use for
the levels anticipated.
All the commonly used materials (cast iron, ductile iron, copper,
steel, and glass) and the joints normally used to put the pipes
together fall far short of the ideal. However, they are all suitable
for low-level waste and the radioactive source materials found in
facilities with a low level of radiation. Plastic piping is not accept-
able for radwaste systems due to the possibility that the plastic
may be afected by the radiation. It is only when the radiation
levels of the waste materials reach the high radiation category
that they fail one or more of these conditions. As a result, stainless
steel with welded joints has emerged as the material of choice
for all industrial type waste products. Type 316L is the most
commonly used.
A welded joint is the only type of joint that meets the criteria for
not allowing a crud trap. Te orbital welding process is often used
since it produces the cleanest interior weld surface. Te proper
weld end preparation is critical to proper welding and must be
diagrammed or described in the specifcations.
Tere are two types of joint used for drainage pipe: butt welded
and socket welded. Butt welded is a term used to describe two
pipes placed end to end and joined with no overlapping. Socket
welded describes the joint that results when one pipe is placed
inside the other and only one end of the exposed pipe is actually
welded around the exterior of the pipe. Tis is like a coupling,
with only the joint on the outside of the pipe welded. In general,
only pipe 2 in. and less are socket welded. Pipe this small (2 in.
and under) is called small bore pipe.
Specifcations for, and approval of, the entire welding process
for both shop welding and feld welding are necessary. It is also
necessary to qualify welding personnel to ensure that they have
sufcient training and knowledge to produce a weld of the re-
quired quality called for in the specifcations. Qualifcations of
welding personnel are difcult to assess. High-temperature, high-
pressure pipe is covered by ASME codes that specify the selection
of successive welding type passes, fller metal composition, joint
preparation, movement and handling of the pipe, tack welding
and clamping, welding currents, metal deposit rates, and weld
inspection. None of these code requirements apply to welded,
non-pressure drainage pipe. If the engineer does not have the
knowledge to specify the minimum requirements for welders and
the welding process, it could be left to the contractor to determine
the correct specifcations for the project and recommend them
to the engineer for approval. When this is done, the contractor
establishes the minimum criteria that qualify any individual for
welding on this particular project. It is then up to the contractor
to test a welders ability to make sound welds under the actual
working conditions and using the same equipment expected to
be used on the job and to certify that person as qualifed. Tese
criteria should be reviewed by the engineer for acceptability. It
is common practice to use an outside, knowledgeable third party
for this review process.
Te defects in welded piping must be found and corrected. All of
them center around the fact that the weld does not actually create
a monolithic piece of pipe. Te faws are cracks or voids in the
joint. Te testing methods, which are of the nondestructive type
(NDT), are as follows:
1. Visual inspection of the weld.
2. Dye penetrate.
3. Magnetic testing.
4. Ultrasonic testing.
5. X-ray.
8 Read, Learn, Earn APRIL 2012
READ, LEARN, EARN: Pharmaceutical Laboratory Drainage Systems
infectiouS anD bioLogicaL-WaSte
Drainage SyStemS
introduction
Biological waste has the same basic characteristics as other
laboratory and production facility waste but with the addition
of biohazardous material. Biohazardous material consists of live
organisms that are suspended in the waste stream and, if not
contained, have the potential to cause infection, sickness, and
other very serious diseases. Tis waste is discharged by gravity
and under pressure from many sources, including:
1. Fermentation tanks and equipment.
2. Process centrifuges.
3. Sinks, both hand washing and process.
4. Containment-area foor drains.
5. Janitor closet drains.
6. Necropsy table drains.
7. Autoclave drains.
8. Contaminated condensate drains.
Containment is the method used to isolate and confne biohaz-
ardous material. Te facility equipment and design shall conform
to acceptable and appropriate containment practices based on
the hazard potential. A containment category is used to describe
an assembly of both primary and secondary preventive measures
that provide personnel, environmental, and experimental protec-
tion. Primary barriers are specifc pieces of equipment, such as
the biological safety cabinet (which is the biologists equivalent
of the chemists fume hood) and glove boxes. Secondary contain-
ment consists of features of the facility design that surround and
support the primary containment. Tese features are described
and classifed in publications of the National Institutes of Health
among other publications.
Te classifcations for biological containment in laboratories
comprise four biosafety levels, BL1 through BL4. Publications
describe the work practices, equipment, and BL selection criteria
based on the activity of a particular laboratory. If the laboratory
or production facility produces or uses greater than 10 L involving
viable organisms, the facility may be classifed as a large scale
(LS) biosafety level. Tis is noted as BL2 LS.
Manufacturing standards shall conform to good large scale pro-
duction (GLSP) standards. Te same standards apply to both
small and large-scale facilities.
Facility types of work are outlined later in this chapter in a very
abbreviated form.
codeS and StandardS
Mandated guidelines and regulations include the following:
1. OSHA bloodborne pathogen regulations.
2. NIH guidelines for the use of recombinant microorganisms.
3. FDA cGMP regulations.
4. CDC/NIH guidelines for biosafety in microbiological and
biomedical laboratories.
biological SaFety levelS
CDC/NIH guidelines for biosafety in microbiological and bio-
medical laboratories are summarized in the following laboratory
containment levels.
Biosafety Level 1 (BL1) containment. Tis classifca-
tion is the typical biological research facility classifcation
for work with low-hazard agents. Viable microorganisms
not known to cause disease in healthy adults are used at
this level. Work is done on an open bench and any hazard
present can be controlled by using standard laboratory
practice. Standard features consist of impervious and easily
sanitized bench surfaces separated from general ofces,
animal rooms, and production areas. Contaminated liquid
and solid waste shall be treated to remove biological haz-
ards before disposal. Wastes containing DNA materials or
potentially infectious microorganisms shall be decontami-
nated before disposal. Hand wash facilities are required in
each laboratory.
Biosafety Level 2 (BL2) containment. Construction of
this level facility is similar to that for a BL1 facility, except
that the microorganisms may pose some risk and safety
cabinets are often present. Equipment and work surfaces
shall be wiped down with a suitable disinfectant. Sinks shall
be scrubbed daily with a chlorine containing abrasive and
fushed with a suitable disinfectant. All liquid waste shall
be immediately decontaminated by mixing with a suitable
disinfectant.
Nearly all laboratories operate under levels 1 or 2 contain-
ment. At these levels, the facility is engaged in research,
diagnostic, or production activities thought to pose little or
minimal risk to workers.
Biosafety Level 3 (BL3) containment. Level 3 activity
involves organisms that pose a signifcant risk or represent
a potentially serious threat to health and safety. Biosafety
cabinets are required and all penetrations to outside the
facility must be sealed to prevent leakage. Tese seals must
be capable of being cleaned. Liquid waste is kept within the
laboratory or facility and steam sterilized prior to discharge
or disposal. Vacuum inlets must be protected by appropri-
ate flters and/or disinfectant traps. Laboratory animals
require special housing or, if conventional housing is used,
personnel must be appropriately protected with full suits
and respirators. A hand-washing sink that is routed to ster-
ilization shall be located adjacent to the facility exit. Vents
from plumbing fxtures must be fltered.
Biosafety Level 4 (BL4) containment. Tis rarely used
classifcation is reserved for facilities whose activities re-
quire a very high level of containment. Te organisms have
a life-threatening potential and may initiate a serious epi-
demic disease. All of the BL3 requirements apply. In addi-
tion, showers shall be provided for personnel at the airlock
where clothes are changed upon entry or exit. Breathing air
is generated outside the BL 4 unit and provided directly to
full protective suits. Nothing is allowed outside the facility.
A biowaste treatment system shall be provided within the
facility to sterilize liquid waste.
LiquiD-WaSte Decontamination
SyStem
A liquid-waste decontamination system (LWDS) collects and
sterilizes (decontaminates) liquid waste. Efuent containing
potentially hazardous biomatter is collected in a dedicated
drainage system generally discharging by gravity into a sump
below the foor level within the facility. From the sump, efuent
is pumped into a kill tank where the actual sterilization occurs.
A kill tank is a vessel into which steam or chemical disinfectant
APRIL 2012 Read, Learn, Earn 9
can be injected to kill any organism. Te kill-tank system shall be
qualifed to the same biosafety level as the facility that it receives
its discharge from. Te kill-tank system must be a batch-process
system, since time, based on the process used, is needed to com-
plete the sterilization and decontamination.
SyStem componentS
In addition to piping, the system consists of the sump or tank to
receive contaminated discharge from the drains and equipment
of the facility, a pump to remove the contaminated efuent from
the sump and into the kill tank(s), and the kill tanks that will
decontaminate and sterilize the efuent to a point permitting
disposal into the same system as the sanitary waste from the
facility, generally into a public sanitary sewer.
sUmp pit
Te sump pit into which the efuent drains shall have a gasketed,
waterproof cover. Te controls are similar to those provided on a
plumbing sump pump and shall be capable of being chemically or
steam sterilized. Te sizing of the pit is done in conjunction with
the sizing of the pump so that the pump stays on for a minimum
of 1 min to avoid frequent starting. Other considerations, such
as having the pit contain one batch of product if necessary, may
be considered.
Kill-tanK assembly
Te kill-tank component has a duplex-tank arrangement, which
allows one batch to be decontaminated while the second tank is
flling. Te size of the tanks varies based on the individual facility,
but common practice is to have each tank capable of containing
one days efuent plus the chemicals used for decontamina-
tion. Another consideration is to have sufcient size to hold a
catastrophic spill. Tere is usually an agitator to mix the efuent
with the deactivation chemicals to accelerate the treatment pro-
cess. In addition to the kill tanks, tanks containing disinfectant
chemicals to be injected are required. A fully automatic control
system must be provided to ensure the timely addition of the
required chemicals in the correct amounts and for the required
duration of deactivation of the biomatter. Alarms and status shall
be displayed on an appropriate panel located in a facility control
room or monitoring areas.
dRainaGe system and components
Te drainage system must be closed, which requires sealed foor
drains and valved connections to equipment when not in use,
since the ventilation system maintains a negative pressure within
the space. It is important that the trap on all foor drains have a
seal 2 in. deeper than the negative diference in air pressure.
Te traps of foor drains shall be flled with a disinfectant solution
when not being used to discharge waste to eliminate the possibil-
ity of spreading organisms between diferent areas served by the
same connected sections of the piping system.
Te drainage piping material is based on the expected composi-
tion of efuent chemicals and the sterilization method to be used.
If the local authorities determine that the biowaste is hazardous,
a double-contained piping system with leak detection may be
required. Stainless steel or PTFE pipe is usually chosen where
higher-temperature efuent may be discharged or steam ster-
ilization may be required. PVC, CPVC, polypropylene, or lined
Fiber Reinforced Plastic (FRP) pipe could be used where efuent
temperatures are lower and where chemicals will provide the
method of sterilization.
If waste from pressurized equipment is discharged into a gravity
system, the system must be adequately sized to convey the fow
at the proposed fow rate with the gravity system pipe fowing
half full, and adequate vents shall be provided to equalize and
ensure the internal pressure of the pipe is always at atmospheric
pressure.
Valves shall be of the diaphragm type and capable of being steril-
ized with the same method used for the pipe. After appropriate
decontamination, the kill-tank efuent shall be discharged to
drain. Tis efuent also must be treated prior to discharge into a
public sewer system for disposal.
vents
A system vent from pipe, fxtures, sealed sump pits and kill tanks
must be flter sterilized prior to leaving the system with a High
Efciency Particulate Air (HEPA) or a 0.2- flter.
In the event of an accident, OSHA has published rules to aid
personnel responding to emergencies involving any hazardous
material.
SyStem deSign conSiderationS
Te treated discharge from any containment treatment shall be
separately routed to the sanitary system outside the building to
allow for monitoring and sampling.
chemicaL WaSte SyStemS
Chemical-waste drainage systems could contain a wide variety
of waterborne wastes, including chemicals, solvents, suspended
solids, fammable liquids, and waste water, many of which are
considered hazardous. Te purpose of the chemical-waste drain-
age system is to collect and transport these wastes from inside
a facility to a point on site where treatment or disposal will be
accomplished.
codeS and StandardS
A great many regulations afect the design of any industrial drain-
age system. Among them are the federal Clean Water Act (CWA)
and Resource Conservation and Recovery Act (RCRA), which are
administered by the federal Environmental Protection Agency
(EPA) as well as state and other local agencies. Local authorities
are also empowered to enforce and legislate regulations that
are stricter than the federal regulations. Where production and
manufacturing facilities discharge waste, it is a general practice to
engage the services of professionals experienced in waste-water
treatment and environmental issues to ensure compliance with
all the latest applicable regulations and an acceptable treatment
system.
Te major regulatory consideration to be determined is whether
any particular waste stream is hazardous. If so, protective mea-
sures, such as double-contained piping systems and leak detec-
tion, may be required.
pipe material and Joint Selection
Because of the vast diversity of manufacturing processes, it is
impossible to make any general characterizations of industrial
waste water. It is common to have various areas within a plant
10 Read, Learn, Earn APRIL 2012
READ, LEARN, EARN: Pharmaceutical Laboratory Drainage Systems
or industrial complex discharge diferent types of efuent with
greatly varying characteristics.
Te largest quantity of efuent in an industrial facility originates
from drains. Drains receive discharge from production equip-
ment; foor wash down; process and production machines and
other equipment, such as compressors and boilers. Te foor
drain and discharge pipe from the drain must be capable of
resisting the chemicals discharged from the production equip-
ment. Selection of the most appropriate piping material can be
accomplished only if the nature of both present and future efu-
ent is known and taken into account.
An often-used material is vitrifed clay sewer pipe because of its
resistance to most chemicals. Manholes are lined for protection
against all possible acids or chemicals. A typical lined manhole
is illustrated in Figure 2-3.
SyStem deSign conSiderationS
Te design of the drainage system is dependent on the loca-
tion, composition, and quantity of discharged efuent from all
sources. Te layout and engineering of a piping network requires
ingenuity and attention to detail. Piping shall be sized based on
the maximum possible fow (in gpm) and the slope of the pipe.
Table 2-3 provides the information necessary to size drainage
piping fowing full.
Selection of the type and location of foor drains is a major aspect
of drainage system design. Te following are general guidelines
for doing this:
1. Wet foors are to be avoided. Drains should be lo-
cated next to equipment and be large enough to allow
multiple discharges to spill over them without spilling
on the foor and running to the drain or requiring a
run of pipe over the foor. If large fow rates are ex-
pected, select a large drain.
2. Te use of long trench drains in areas where there
are several pieces of equipment will create easy ac-
cess from the equipment to all the various drains.
Tis arrangement is usually less costly than multiple
drains.
3. In many cases, the discharge from a piece of equip-
ment may be under pressure because of the head
of water in the equipment, such as occurs when a
tank is emptied. Te drain should be large enough to
accept the largest expected fow. Te drain open-
ing must be large enough to accept the maximum
quantity fowing full by gravity without overfowing.
An air gap shall be provided to prevent pressurizing
the gravity-drainage system.
4. A funnel or open site type drain should be provid-
ed to accept a quantity of small-sized drainage lines
from equipment. Te top of the funnel should be as
close to the foor as is reasonable in order for an air
gap to be provided between the top of the foor drain
and the end of the equipment drain. Tis air gap shall
be twice the diameter of the drainage line.
5. Provide adequate cleanouts in drain lines. In lines
that are at the ceiling of a high foor, extend the clea-
nouts to the foor above to avoid the need for mainte-
nance personnel to climb ladders to clean stoppages.
6. To facilitate maintenance, the minimum size drain
line under an isolated slab or underground should
be 2 in. (50 mm). Floor drains should be a minimum
size of 4 in. (100 mm).
7. Adequate venting of the drainage line must be provided to
allow for smooth fow. Vents shall be connected to the top
of the drain line in order to allow air at the top of the pipe
to be either vented out (when there is a slug of liquid) or to
admit air required by the fow of water or due to a partial
vacuum created by the liquid fowing full. Vents shall be a
minimum size of 2 in.
8. Local regulations may require the use of double-contained
piping to prevent potential leakage from discharging into
the environment. A leak-detection system should be pro-
vided that allows leakage to be annunciated.
fire-SuppreSSion Water Drainage
introduction
For industrial facilities, the water used to suppress a fre could be-
come contaminated with the products and raw materials it comes
in contact with. It is required that any water, such as sprinkler and
fre-hose discharge, that has the possibility of being contaminated
in this manner, must be routed to holding basins for analysis and
possible treatment before being discharged into the environment.
If there are no materials capable of causing contamination, no
special consideration is necessary except to protect other areas
of the facility from possible fooding.
Figure 2-3 Lined Manhole
APRIL 2012 Read, Learn, Earn 11
SyStem deScription
Te components of the fre-suppresion drainage system are drains
located in such a manner to intercept the fow of fre water, the
drainage piping, a holding basin on site to contain and treat the
total volume of water, and the necessary treatment system that will
neutralize the water prior to discharge into the environment.
Te amount of water discharged from the fre-suppression system
is far greater than the amount of waste water discharged from
the facility under normal operating conditions. Overfow foor
drains large enough to take the design fow rate shall be installed
at points where they can intercept the water before it fows out of
doorways or drive bays and route it to holding basins. Te place-
ment of these overfow drains shall be selected to intercept all the
water discharged and prevent it from damaging other parts of the
facility, or escaping away from the property or into the ground.
Te size of the drainage piping is based on fow rate and pitch from
the facility to the detention basin. Te efuent is essentially clear
water with a few solids. Te fow rate of the water that must be
disposed of is determined by frst calculating the sprinkler-water
density over the area used for hydraulic calculations. Added to this
is the average fow rate from the maximum number of fre stand-
pipe hose streams in simultaneous use. Velocity in the drainage
pipe is not a major consideration because the system will rarely
be used. A shallow pitch will give a low velocity that may result
in the deposit of some material that could be fushed out after
the fre event. A high velocity will not afect the life of the piping
system because of the short amount of time the system will be in
operation. Pipe size is selected based on the actual pitch of the
pipe and the capacity fowing full. Refer to Table 2-3 for sizing.
Venting the system is required to allow free fow of the efuent.
Each individual drain need not be vented, but each branch should
have a loop vent at least 2 in.(50 mm) in size. Te vent could be
connected to the sanitary vent system or carried through the roof
independently.
Te pipe material selected shall be compatible with the potential
chemicals that might be carried.
fLammabLe anD VoLatiLe-LiquiD
Drainage
Federal, state and local regulations have established standards for
the discharge of volatile liquids, particularly oil, into storm-water
and sanitary sewers. Tese standards vary, and the responsible
enforcement and code authorities must be consulted to deter-
mine the level of treatment required.
Te potential hazard created by volatile liquids could be either
one of safety (since the vapors could create an explosive condi-
tion and oil will foat on water and could be set on fre) or one of
health (where the breathing of the vapors is dangerous to health
and the substance is toxic if ingested by humans). Te character-
istic common to all these substances is that they are lighter than
water. Teir removal is similar to that of oil, which is the most
common fammable liquid.
oil in Water
Oil is considered immiscible since it cannot be mixed with water:
Oil in water exists in several forms:
1. Free oil.
2. Mechanically dispersed oil, which consists of fne droplets
ranging in size from microns to fractions of a millimeter.
Tey are stable due to electrical charges and other forces
but not due to the presence of surface active agents.
3. Chemically stabilized emulsions, which are fne droplets
that are stable due to surface active agents.
4. Dissolved and dispersed oil is suspended in such a small
sizetypically 5 microns () or smallerthat ordinary
fltration is not possible.
5. Oil-wet solids, which are particulates that oil adheres to the
surface of.
metHodS oF Separation and treatment
Oil spills and leaks are best treated in their most concentrated
state, which is at their source or as close as is reasonable to the
source. Te primary methods used to separate and remove free
oil and oil-wet solids are fotation and centrifugation. Secondary
treatments, such as chemical treatment/coalescence and fltra-
tion, are then used to break up oil/water emulsions and remove
dispersed oil. Finally, tertiary treatments, such as ultrafltration,
biological treatment, and carbon adsorption, remove the oil to
required levels prior to discharge. Tis chapter discusses only the
general principles of primary and secondary separation methods
and devices.
Te American Petroleum Institute (API) has established criteria
for the large-scale removal of globules larger than 150 . In ab-
breviated form, they are:
1. Te horizontal velocity through the separator may be up to
15 times the rise velocity of the slowest-rising globule, up to
a maximum of 3 ft/s (fps).
2. Te depth of fow in the separator shall be between 3 ft 0 in.
and 8 ft 0 in above the outlet.
3. Te width of the separator shall be between 6 ft 0 in. and 20
ft 0 in.
4. Te depth to width ratio shall be between 0.3 and 0.5.
5. An oil-retention bafe should be located no less than 12 in.
downstream from a skimming device.
GRavity sepaRatoRs
Gravity separation is the primary and most often-used separation
method. It is based on the specifc gravity diference between
immiscible oil globules and water. Since all of these liquids are
lighter than an equal volume of water, gravity separators operate
on the principle of fotation. As the water and oil fow through the
unit, the oil foats to the top and is trapped inside by a series of
internal bafes. Since the oil remains liquid, it is easily drawn of
via gravity. For larger-scale service, the rate at which oil and oil-
Table 2-3 Capacity of Drainage Piping Flowing
Full (n = 0.013)
Pipe
Diameter,
in.
Horizontal Piping, gpm
Slope, in./ft
Stacks,
gpm
1
8
2 30
2 54
3 92 36 51 80
4 192 77 110 174
6 563 220 315 449
8 1208 494 696 987
10 2600 943 1302 1800
12 6000 1526 2154 2800
15 2873 3500 4950
12 Read, Learn, Earn APRIL 2012
READ, LEARN, EARN: Pharmaceutical Laboratory Drainage Systems
wet solids foat to the top of the separation chamber is enhanced
by the attachment of small bubbles of air to the surface of the
slow-rising oil globules. Tis is done by adding compressed air
to the bottom of the fotation chamber. As the air saturated fow
is brought back to atmospheric pressure, microscopic bubbles
are formed that will mix with, and attach themselves to, the oil
globules.
centRifUGal sepaRatoRs
Te centrifugal separator is used on large-scale services, also. Tis
device operates on the principle of inducing the combined oil
and water mixture to fow around a circular separation chamber.
Te lighter oil globules collect around the central vortex which
contains the oil-removal mechanism and the clear water collects
at the outer radial portion of the separation chamber. Methods
have evolved that can produce efuent water with only 50 to
70 ppm of oil, and proprietary devices exist that can lower oil
content to 10 ppm.
filtRation
Chemical methods used to break oil/water emulsions followed
by the use of depth type flters to remove the destabilized mixture
have proven efective in removing oil globules in sizes ranging
from 1 to 50 . Te velocity and fow rate of the mixture to be
treated must be carefully controlled to achieve optimum perfor-
mance of the system.
methods foR smalleR systems
Oil separators for small fows usually take the form of a single unit
consisting of a drain grating into which the efuent fows and in
which the oil remains to be drawn of manually. Another type of
unit uses an overfow arrangement that sends the trapped oil to
a remote oil-storage tank.
Because there is a possibility that the vapor given of by the vola-
tile liquid could ignite, it is important to provide a separator vent
that terminates in the open air at an approved location above the
highest part of the structure. Some codes require that a fame
arrester be installed on the vent.
Te material most commonly used for oil interceptors is cast
iron, although steel can be used for less severe service. Gratings
must have the strength to withstand the weight of the types of
vehicle expected.
Figure 2-4 illustrates a typical small oil interceptor, Figure 2-5 the
installation of a typical oil interceptor with gravity oil draw of for
multiple foor-drain inlets.
Figure 2-4 Typical Small Oil Interceptor
Figure 2-5 Installation of a Typical Small Oil
Interceptor with Gravity Oil Draw Of
APRIL 2012 Read, Learn, Earn 13
READ, EARN, LEARN: Pharmaceutical Laboratory Drainage Systems CONTINUING EDUCATION: Pharmaceutical Laboratory Drainage Systems
CE Questions
Pharmaceutical Laboratory Drainage Systems (CEU 186)
Wastewater with a pH of 1 would be 1.
considered ________.
alkaline a.
neutral b.
acidic c.
none of the above d.
Which of the following has the highest 2.
temperature rating, but also the highest
cost?
CPVC a.
PYDF b.
PTFE c.
PP d.
A 3-inch horizontal drainage pipe fowing 3.
half-full at a inch per foot slope has a
velocity of ________.
1.59 fps a.
1.99 fps b.
2.25 fps c.
3.19 fps d.
Which of the following is part of a typical 4.
continuous acid-neutralizing system?
chemical feed pump a.
pH probe b.
mixing tank c.
all of the above d.
Which of the following is recommended 5.
to suppress a fre involving sulfuric acid?
carbon dioxide a.
dry chemicals b.
water c.
both a and b d.
The materials most commonly used to 6.
shield radiation are ________.
concrete and wood a.
sheet lead and concrete b.
lead and glass c.
FRP and concrete d.
Reading the article and completing the form will
allow you to apply to ASPE for CEU credit. If you
earn a grade of 90 percent or higher on the test,
you will be notified that you have logged 0.1
CEU, which can be applied toward CPD renewal
or numerous regulatory-agency CE programs.
(Please note that it is your responsibility to deter-
mine the acceptance policy of a particular agency.)
CEU information will be kept on fle at the ASPE
ofce for three years.
ASPE Continuing Education Application Form
this form is valid up to one year from date of publication. Expiration date: Continuing education credit will be given for this examination
through april 30, 2013. Applications received after that date will not be processed.
Submit this form with payment via mail (ASPE Read, Learn, Earn, 2980 S. River Road, Des Plaines, IL 60018), fax (847-296-2963), or email
aspeeducation@aspe.org.
Please print or type; this information will be used to process your credits.
Name ______________________________________________________________________ ASPE Membership No. ______________
Organization ___________________________________________________ Daytime telephone _____________________________
Billing Address ________________________________________________________________________________________________
City _________________________________________ State/Province ________________________ Zip ______________________
E-mail _______________________________________________________________________ Fax ____________________________
PE State _____________________________________________ PE No. _________________________________________________
Notice for North Carolina Professional Engineers: State regulations for registered PEs in North Carolina now require you to complete ASPEs online CEU validation form
to be eligible for continuing education credits. After successfully completing this quiz, just visit ASPEs CEU Validation Center at aspe.org/CEUValidationCenter.
I certify that I have read the article indicated
above.
Signature
Payment:
Member: Free
Nonmember: Each examination: $35
Personal Check (payable to ASPE)
Business or government check
DiscoverCard VISA MasterCard AMEX
If rebilling of a credit card charge is necessary, a $25
processing fee will be charged.
ASPE is hereby authorized to charge my CE
examination fee to my credit card
Account Number
Expiration date
Signature
Cardholders name (Please print)
An ideal radwaste drainage pipe should 7.
be ________.
nonoxidizing a.
easy to clean b.
nonporous c.
all of the above d.
Which of the following is not acceptable 8.
for radwaste systems?
stainless steel a.
plastic b.
glass c.
copper d.
________ is an example of a primary 9.
barrier for biohazardous materials.
biological safety cabinet a.
emergency shower b.
glove box c.
both a and c d.
An LWDS contains which of the 10.
following?
kill tank a.
fume hood b.
caustic acid storage tank c.
none of the above d.
Floor drains in chemical waste drainage 11.
systems should be ________ minimum.
2 inches a.
4 inches b.
6 inches c.
8 inches d.
________ is a primary method used to 12.
separate and remove free oil and oil-wet
solids.
foatation a.
ultrafltration b.
centrifugation c.
both a and c d.
Circle the correct answers below.
14 Read, Learn, Earn APRIL 2012
C
E
U
1
8
7
Sanitary
Drainage
Systems
Continuing Education from the
American Society of Plumbing Engineers
MAY 2012
ASPE.ORG/ReadLearnEarn
The purpose of the sanitary drainage system is to remove
effuent discharged from plumbing fxtures and other equip-
ment to an approved point of disposal. A sanitary drainage
system generally consists of horizontal branches, vertical
stacks, a building drain inside the building, and a building
sewer from the building wall to the point of disposal.
To economically design a sanitary drainage system, the
designer should use the smallest pipes possible according to
the applicable code that can rapidly carry away the soiled
water from individual fxtures without clogging the pipes,
leaving solids in the piping, generating excessive pneumatic
pressures at points where the fxture drains connect to the
stack (which might cause the reduction of trap water seals
and force sewer gases back through inhabitable areas), and
creating undue noise.
Since vents and venting systems are described in Chapter
3 of this volume, the following discussion centers only on the
design of drain and waste systems.
CODES AND STANDARDS
Plumbing codes establish a minimum acceptable standard
for the design and installation of systems, including sanitary
drainage. There are various model codes, but some states and
large cities have adopted their own plumbing codes, rather
than the ones usually associated with the region. Because
of this non-standardization, the actual plumbing code used
for each specifc project must be obtained from a responsible
code offcial.
A variety of different codes are used to lay out and size
interior sanitary drainage systems, and the information
pertaining to sanitary design for a specifc project appears
in the approved local plumbing code, which must be the pri-
mary method used for the accepted methods and sizing. The
tables and charts appearing in this chapter are used only to
illustrate and augment discussions of sizing methods, sizing
procedures, and design methods and should not be used for
actual design purposes.
FLOW IN STACKS
A stack is the main vertical pipe that carries away discharge
from water closets and urinals (soil stack) or other clear wa-
ter waste from equipment and non-sanitary fxtures (waste
stack). Flow in the drain empties into the vertical stack
ftting, which may be a long-turn tee-wye or a short-turn
or sanitary tee. Each of these fttings permits fow from the
drain to enter the stack with a component directed vertically
downward. Depending on the rate of fow out of the drain
into the stack, the diameter of the stack, the type of stack
ftting, and the fow down the stack from higher levels (if any),
the discharge from the fxture drain may or may not fll the
cross-section of the stack at the level of entry. In any event,
as soon as the water enters the stack, the force of gravity
rapidly accelerates it downward, and before it falls very far,
it assumes the form of a sheet around the wall of the stack,
leaving the center of the pipe open for the fow of air.
This sheet of water continues to accelerate until the fric-
tional force exerted by the wall of the stack on the falling
sheet of water equals the force of gravity. From that point
on, if the distance the water falls is suffcient enough and
provided that no fow enters the stack at lower levels to
interfere with the sheet, the sheet remains unchanged in
thickness and velocity until it reaches the bottom of the stack.
The ultimate vertical velocity the sheet attains is called the
terminal velocity. The distance the sheet must fall to attain
this terminal velocity is called the terminal length.
Following are the formulae developed for calculating the
terminal velocity and terminal length:
Equation 1-1a (terminal velocity)
V
T
= 3.0(Q/d)
2/5
Equation 1-1b (terminal length)
L
T
= 0.052V
T
2
where
V
T
= Terminal velocity in the stack, feet per second (fps)
(meters per second)
L
T
= Terminal length below the point of fow entry, feet
(meters)
Q = Quantity rate of fow, gallons per minute (gpm) (liters
per second)
d = Diameter of stack, inches (millimeters)
Terminal velocity is approximately 10 to 15 fps (3.05 to
4.57 meters per second), and this velocity is attained within
10 to 15 feet (3.05 to 4.57 meters) of fall from the point of
entry.
At the center of the stack is a core of air that is dragged
along with the water by friction. A supply source of air must be
provided to avoid excessive pressures in the stack. The usual
means of supplying this air are through the stack vent or vent
stack. The entrained air in the stack causes a pressure reduc-
tion inside the stack, which is caused by the frictional effect of
the falling sheet of water dragging the core of air with it.
If the sheet of water falling down the stack passes a stack
ftting through which the discharge from a fxture is entering
the stack, the water from the branch mixes with or defects
the rapidly moving sheet of water. An excess pressure in the
drain from which the water is entering the stack is required
to defect the sheet of water fowing downward or to mix the
Reprinted from Plumbing Engineering Design Handbook, Volume 2. 2010, American Society of Plumbing Engineers.
Note: In determining your answers to the CE questions, use only the material presented in the corresponding continuing education
article. Using information from other materials may result in a wrong answer.
2 Read, Learn, Earn MAY 2012
READ, LEARN, EARN
branch water with it. The result is a back-pressure created
in the branch, which increases with the fow rate and fow
velocity down the stack and with the fow rate out of the
drain.
The importance of this knowledge is that it conclusively
abolishes the myth that water falling from a great height will
destroy the fttings at the base of a stack. The velocity at the
base of a 100-story stack is only slightly and insignifcantly
greater than the velocity at the base of a three-story stack.
The concern is the weight of the stack, which must be sup-
ported by clamps at each foor level.
Flow in Building Drains
When the sheet of water reaches the bend at the base
of the stack, it turns at approximately right angles into
the building drain. Flow enters the horizontal drain at a
relatively high velocity compared to the fow velocity in a
horizontal drain under uniform fow conditions. The slope of
the building drain is not adequate to maintain the velocity
that existed in the vertical sheet when it reached the base
of the stack and must fow horizontally. The velocity of the
water fowing along the building drain and sewer decreases
slowly and then increases suddenly as the depth of fow in-
creases and completely flls the cross-section of the drain.
This phenomenon is called a hydraulic jump.
The critical distance at which the hydraulic jump may oc-
cur varies from immediately at the stack ftting to 10 times
the diameter of the stack downstream. Less hydraulic jump
occurs if the horizontal drain is larger than the stack. After
the hydraulic jump occurs and water flls the drain, the pipe
tends to fow full until the friction resistance of the pipe
retards the fow to that of uniform fow conditions.
Flow in Fixture Drains
Determination of the required drain size is a relatively simple
matter, since the fxture drain must be adequate only to
carry the discharge from the fxture to which it is attached.
Because of the problem of self-siphonage, however, it is advis-
able to select a diameter large enough that the drain fows
little more than half-full under the maximum discharge
conditions likely to be imposed by the fxture.
For example, a lavatory drain capable of carrying the fow
discharged from a lavatory may still fow full over part or all
of its length. This occurs for several reasons. The vertical
component of the fow out of the trap into the drain tends to
make the water attach to the upper elements of the drain,
and a slug of water is formed, flling the drain at that point.
If insuffcient air is aspirated through the overfow, the pipe
will fow full for part of its length, with the average fow
velocity being less than the normal velocity for the fow rate
in the drain at a given slope.
In the past, with a fxture such as a toilet, the surge of water
from the toilet continued almost without change even along a
very long drain until it reached the stack. This still is generally
true, but the use of low-fow and dual-fush toilets requires the
design of the horizontal piping to be reconsidered. It cannot be
assumed, for all practical purposes, that the surge caused by
the discharge of a toilet through a fxture drain reaches the
stack or horizontal branch with practically the same velocity
it had when it left the fxture.
PNEUMATIC PRESSURES IN A
SANITARY DRAINAGE SYSTEM
Due to the pressure conditions in a stack and a building
drain, wastewater does not fll the cross-section anywhere,
so the air can fow freely with the water. The water fowing
down the wall of the stack drags air with it by friction and
carries the air through the building drain to the street sewer.
The air is then vented through the main street sewer system
so dangerous pressures do not build up. The generally ac-
cepted pressure is 1 inch of water column.
When air enters the top of the stack to replace the air
being carried with the water, the pressure inside the stack
decreases. However, because of the head loss necessary to
accelerate the air and to provide for the energy loss at the
entrance, this pressure reduction is negligible, amounting
to only a small fraction of an inch of water. Appreciable
pressure reductions are caused by the partial or complete
blocking of the stack by water fowing into the stack from a
horizontal branch.
A small increase in pneumatic pressure will occur in the
building drain even if the airfow is not completely blocked
by a hydraulic jump or by submergence of the outlet and the
building sewer. This is due to the decrease in cross-sectional
area available for airfow when the water fowing in the drain
has adapted to the slope and diameter of the drain.
FIXTURE DISCHARGE
CHARACTERISTICS
The discharge characteristic curvesfow rates as a function
of timefor most toilet bowls have the same general shape,
but some show a much lower peak and a longer period of
discharge. The discharge characteristics for various types
of bowls, particularly for low-fow toilets, have a signifcant
impact on estimating the capacity of a sanitary drainage
system. Other plumbing fxtures, such as sinks, lavatories,
and bathtubs, may produce similar surging fows in drain-
age systems, but they do not have the same effect as water
closets.
Drainage Loads
Single-family dwellings contain certain plumbing fxtures,
such as one or more bathroom groups, each consisting of a
toilet, lavatory, and bathtub or shower stall, a kitchen sink,
dishwasher, and washing machine. Large buildings also have
other fxtures, such as slop sinks and drinking water coolers.
The important characteristic of these fxtures is that they are
not used continuously. Rather, they are used with irregular
frequencies that vary greatly during the day. In addition, the
various fxtures have quite different discharge characteristics
regarding both the average fow rate per use and the duration
of a single discharge. Consequently, the probability of all the
fxtures in the building operating simultaneously is small.
Assigning drainage fxture unit (dfu) values to fxtures to
represent their load-producing effect on the plumbing system
originally was proposed in 1923 by Dr. Roy B. Hunter. The
fxture unit values were designed for application in conjunction
with the probability of simultaneous use of fxtures to establish
the maximum permissible drainage loads expressed in fxture
units rather than in gpm of drainage fow. Table 1-1 gives the
MAY 2012 Read, Learn, Earn 3
tions, came to the conclusion that slugs of water, with their
accompanying violent pressure fuctuations, did not occur
until the stack fowed one-quarter to one-third full. Most
model codes have based their stack loading tables on a value
of r = or 7/24.
The recommended maximum permissible fow in a stack
is 7/24 of the total cross-sectional area of the stack. By
substituting r = 7/24 into Equation 1-2, the correspond-
ing maximum permissible fow for the various sizes of pipe
in gpm can be determined. Table 1-3 lists the maximum
permissible fxture units (fu) to be conveyed by stacks of
various sizes. The table was created by taking into account
the probability of simultaneous use of fxtures. For example,
if 500 fxture units is the maximum loading for a 4-inch
(100-millimeter) stack, then 147 gpm (9.3 liters per second)
is equivalent to 500 fxture units. This is the total load from
all branches.
It should be noted that there is a restriction on the amount
of fow permitted to enter a stack from any branch when the
stack is more than three branch intervals. If an attempt is
made to introduce an overly large fow into the stack at any
one level, the infow will fll the stack at that level and will
back up the water above the elevation of infow, which will
cause violent pressure fuctuations in the stackresulting
in the siphoning of trap sealsand also may cause sluggish
fow in the horizontal branch. This problem was solved in
a study of stack capacities made by Wyly and Eaton at the
National Bureau of Standards for the Housing and Home
Finance Agency in 1950.
recommended fxture unit values. The plumbing engineer must
conform to local code requirements.
Dr. Hunter conceived the idea of assigning a fxture unit
value to represent the degree to which a fxture loads a sys-
tem when used at its maximum assumed fow and frequency.
The purpose of the fxture unit concept is to make it possible
to calculate the design load of the system directly when the
system is a combination of different kinds of fxtures, with
each having a unique loading characteristic. Current or
recently conducted studies of drainage loads on drainage
systems may change these values. These include studies of
reduced fow from water-saving fxtures, models of stack,
branch, and house drain fows, and actual fxture use.
Stack Capacities
The criterion of fow capacities in drainage stacks is based
on the limitation of the water-occupied cross-section to a
specifed fraction (r
s
) of the cross-section of the stack where
terminal velocity exists, as suggested by earlier investiga-
tions.
Flow capacity can be expressed in terms of the stack
diameter and the water cross-section.
Equation 1-2
Q = 27.8 x r
s
5/3
x D
8/3
where
Q = Capacity, gpm (liters per second)
r
s
= Ratio of the cross-sectional area of the sheet of water
to the cross-sectional area of the stack
D = Diameter of the stack, inches (millimeters)
Values of fow rates based on r = , 7/24, and are tabu-
lated in Table 1-2.
Whether or not Equation 1-2 can be used safely to predict
stack capacities remains to be confrmed and accepted. How-
ever, it provides a defnite law of variation of stack capacity
with diameter. If this law can be shown to hold for the lower
part of the range of stack diameters, it should be valid for the
larger diameters. It should be remembered that both F.M.
Dawson and Dr. Hunter, in entirely independent investiga-
Table 1-1 Residential Drainage Fixture Unit (dfu) Loads
Fixture IPC UPC
Bathtub 2 3
Clothes washer 3 3
Dishwasher 2 2
Floor drain
1-inch trap loading
1-inch trap loading
2-inch trap loading
3-inch trap loading
4-inch trap loading
3
1
3
4
6
8
Laundry tray 2 2
Lavatory, single 1 1
Lavatory, in sets of two or three 2 2
Shower (each head) 2 2
Kitchen sink (including dishwasher and garbage
disposal)
3 3
Toilet (1.6-gpf gravity tank) 4 4
Toilet (1.6-gpf fushometer tank) 5 5
Toilet (1.6-gpf fushometer valve) 4 4
Table 1-2 Capacities of Stacks
Pipe Size,
in. (mm)
Flow, gpm (L/s)
r =
1
4 r =
7
24 r =
1
3
2 (50) 17.5 (1.1) 23.0 (1.45) 28 (1.77)
3 (80) 52 (3.28) 70 (4.41) 85 (5.36)
4 (100) 112 (7.07) 145 (9.14) 180 (11.35)
5 (125) 205 (12.93) 261 (16.5) 324 (20.44)
6 (150) 330 (20.82) 424 (26.8) 530 (33.43)
8 (200) 710 (44.8) 913 (57.6) 1,140 (72)
10 (250) 1,300 (82.0) 1,655 (104.4) 2,068 (130.5)
12 (300) 2,082 (131.4) 2,692 (170) 3,365 (212.3)
Table 1-3 Maximum Permissible Fixture Unit Loads for
Sanitary Stacks
Diameter
of Pipe, in.
(mm)
Maximum dfu that May Be Connected
Any
horizontal
fxture
branch
a
One stack
of three
or fewer
branch
intervals
Stacks with more than
three branch intervals
Total for
stack
Total at
one branch
interval
1 (40) 3 4 8 2
2 (50) 6 10 24 6
2 (65) 12 20 42 9
3 (80) 20
b
48
b
72
b
20
b
4 (100) 160 240 500 90
5 (125) 360 540 1,100 200
6 (150) 620 960 1,900 350
8 (200) 1,400 2,200 3,600 600
10 (250) 2,500 3,800 5,600 1,000
12 (300) 3,900 6,000 8,400 1,500
15 (380) 7,000
a Does not include branches of the building drain.
b No more than two water closets or bathroom groups within eachbranch interval or more
than six water closets or bathroom groups on the stack.
4 Read, Learn, Earn MAY 2012
READ, LEARN, EARN: Sanitary Drainage Systems
The water fowing out of the branch can enter the stack
only by mixing with the stream fowing down the stack or
by defecting it. Such a defection of the high-velocity stream
coming down the stack can be accomplished only if there is a
signifcant hydrostatic pressure in the branch, since a force
of some kind is required to defect the downward fowing
stream and change its momentum. This hydrostatic pressure
is created by the water backing up in the branch until the
head changes the momentum of the stream already in the
stack to allow the fow from the branch to enter the stack.
The maximum hydrostatic pressure that should be
permitted in the branch as a result of the backing up of
the spent water is based on this consideration: The backup
should not be of a magnitude that would cause the water to
back up into a shower stall or cause sluggish fow. It is half
of the diameter of the horizontal branch at its connection to
the stack. That is, it is the head measured at the axis of the
pipe that will cause the branch to fow
full near the exit.
When a long-turn tee-wye is used
to connect the branch to the stack, the
water has a greater vertical velocity
when it enters the stack than it does
when a sanitary tee is used. The back-
pressures should be smaller in this case
for the same fows down the stack and
in the branch.
Table 1-3 shows the maximum per-
missible fxture unit loads for sanitary
stacks. The procedure for sizing a mul-
tistory stack (greater than three foors)
is to frst size the horizontal branches
connected to the stack. This is done by
totaling the fxture units connected to
each branch and using the correspond-
ing fgure in column 2 of Table 1-3.
Next, total all the fxture units con-
nected to the stack and determine the
size from the same table, under column
4. Immediately check the next column,
Total at One Branch Interval, and
determine if this maximum is exceeded
by any of the branches. If it is exceeded,
the stack as originally determined must
be increased at least one size, or the
loading of the branches must be rede-
signed so the maximum conditions are
satisfed.
For example, consider a 4-inch (100-
millimeter) stack more than three
stories high. The maximum loading for
a 4-inch (100-millimeter) branch is 160
fxture units, as shown in column 2 of
Table 1-3. This load is limited by column
5 of the same table, which permits only
90 fxture units to be introduced into
a 4-inch (100-millimeter) stack in any
one-branch interval. The stack would
have to be increased in size to accommodate any branch load
exceeding 90 fxture units.
To illustrate the requirements of a stack with an offset
of more than 45 degrees from the vertical, Figure 1-1 shows
the sizing of a stack in a 12-story building, with one offset
between the ffth and sixth foors and another offset below
the street foor.
Sizing is computed as follows:
Compute the fxture units connected to the stack. 1.
In this case, assume 1,200 fxture units are con-
nected to the stack from the street foor through
the top foor.
Size the portion of the stack above the ffth-foor 2.
offset. There are 400 fxture units from the top foor
down through the sixth foor. According to Table 1-3,
column 4, 400 fxture units require a 4-inch (100-
millimeter) stack.
Figure 1-1 Procedure for Sizing an Offset Stack
MAY 2012 Read, Learn, Earn 5
Size the offset on the ffth foor. An offset is sized and 3.
sloped like a building drain.
Size the lower portion of the stack from the ffth foor 4.
down through the street foor. The lower portion of the
stack must be large enough to serve all of the fxture
units connected to it, from the top foor down (in this
case, 1,200 fxture units). According to Table 1-3, 1,200
fxture units require a 6-inch (150-millimeter) stack.
Size and slope the offset below the street foor the 5.
same as a building drain.
The fxture on the sixth foor should be connected to the
stack at least 2 feet (0.6 meter) above the offset. If this is not
possible, then connect them separately to the stack at least 2
feet (0.6 meter) below the offset. If this is not possible either,
run the fxture drain down to the ffth or fourth foor and
connect to the stack at that point.
CAPACITIES OF SLOPING DRAINS
The characteristics of sewage are the same as plain water.
The capacities of horizontal or sloping drains are complicated
by surging fow.
Determining drain size is based on highly fuctuating or
surging fow conditions in the horizontal branches carrying
the discharge of fxtures to the soil or waste stack. After fall-
ing down the vertical stack, the water is assumed to enter
the building drain with surge peaks leveled off somewhat,
but still in a surging condition.
A large building covering considerable ground area prob-
ably has several primary branches and certainly at least one
secondary branch. After the water enters the building drain,
the surge continues to level off, becoming more and more
nearly uniform, particularly after the hydraulic jump has
occurred. If the secondary branch is long enough and if the
drain serves a large number of fxtures, the fow may become
substantially uniform before it reaches the street sewer.
Steady, Uniform Flow Conditions in Sloping
Drains
Although the equations of steady, uniform fow in sloping
drains should not be used to determine the capacities of slop-
ing drains in which surging fow exists, fow computations
based on these formulas afford a rough check on values ob-
tained by the more complicated methods that are applicable
to surging fow. Hence, three of the commonly used formulas
for fow in pipes will be considered: Hazen and Williams,
Darcy-Weisbach, and Manning.
Hazen-Williams Formula
This formula usually is written as follows:
Equation 1-3
V = 1.318 x C x R
0.63
x S
0.54
where
V = Mean velocity of fow, fps (meters per
second)
C = Hazen and Williams coeffcient
R = Hydraulic radius of pipe, feet (meters)
S = Slope of pressure gradient
The exponents of R and S in Equation 1-3 have been
selected to make the coeffcient C as nearly constant as pos-
sible for different pipe diameters and for different velocities
of fow. Thus, C is approximately constant for a given pipe
roughness.
Darcy-Weisbach Formula
In this formula, the dimensionless friction coeffcient f var-
ies with the diameter of the pipe, the velocity of fow, the
kinematic viscosity of the fuid fowing, and the roughness
of the walls. It usually is written as follows:
Equation 1-4
h
f
=
FLV
2
D2g
where
h
f
= Pressure drop or friction loss, feet (meters)
f = Friction coeffcient
L = Length of pipe, feet (meters)
D = Diameter of pipe, feet (meters)
V = Mean velocity of fow, fps (meters per second)
g = Acceleration of gravity, 32.2 fps
2
(9.8 m/s
2
)
Manning Formula
The Manning formula, which is similar to the Hazen and
Williams formula, is meant for open-channel fow and usu-
ally is written as follows:
Equation 1-5
V =
1.486 x R
x S
=
1.486
x R
0.67
x S
0.50
n n
In this formula, n is the Manning coeffcient, which varies
with the roughness of the pipe and the pipe diameter.
The fow quantity is equal to the cross-sectional area of
the fow times the fow velocity obtained from the above three
equations. This can be expressed as:
Equation 1-5a
Q = AV
where
Q = Quantity rate of fow, cubic feet per second (cfs) (cubic
meters per second)
A = Cross-sectional area of fow, square feet (square
meters)
V = Velocity of fow, fps (meters per second)
By substituting the value of V from Mannings formula,
the quantity of fow in variously sized drains of the same
material can be calculated as:
Table 1-4 Values of R, R
2/3
, A
F
, and A
H
Pipe Size,
in. (mm) R =
1
4, ft (mm) R
2/3
, ft (mm)
A
F
(Cross-
sectional Area for
Full Flow), ft
2
(m
2
)
A
H
(Cross-sectional
Area for Half-full
Flow), ft
2
(m
2
)
1 (40) 0.0335 (1.02) 0.1040 (3.17) 0.01412 (0.0013) 0.00706 (0.00065)
2 (50) 0.0417 (1.27) 0.1200 (3.66) 0.02180 (0.0020) 0.01090 (0.0009)
2 (65) 0.0521 (1.59) 0.1396 (4.24) 0.03408 (0.0031) 0.01704 (0.0015)
3 (80) 0.0625 (1.90) 0.1570 (4.78) 0.04910 (0.0046) 0.02455 (0.0023)
4 (100) 0.0833 (2.54) 0.1910 (5.82) 0.08730 (0.0081) 0.04365 (0.0040)
5 (125) 0.1040 (3.17) 0.2210 (6.74) 0.13640 (0.0127) 0.06820 (0.0063)
6 (150) 0.1250 (3.81) 0.2500 (7.62) 0.19640 (0.0182) 0.09820 (0.0091)
8 (200) 0.1670 (5.09) 0.3030 (9.23) 0.34920 (0.0324) 0.17460 (0.0162)
10 (250) 0.2080 (6.33) 0.3510 (10.70) 0.54540 (0.0506) 0.27270 (0.0253)
12 (300) 0.2500 (7.62) 0.3970 (12.10) 0.78540 (0.0730) 0.39270 (0.0364)
15 (380) 0.3125 (9.53) 0.4610 (14.05) 1.22700 (0.0379) 0.61350 (0.0570)
6 Read, Learn, Earn MAY 2012
READ, LEARN, EARN: Sanitary Drainage Systems
Equation 1-5b
Q = A x
1.486
x R
x S
n
This is the formula used by many plumbing engineers to
deal with sloping drain problems. The signifcant hydraulic
parameters used in the above equation are listed in Table
1-4.
Slope of Horizontal Drainage Piping
Horizontal drains are designated to fow at half-full capacity
under uniform fow conditions to minimize the generation
of pneumatic pressure fuctuations. The minimum slopes
are as follows:
Pipe 3 inches (80 millimeters) and smaller: inch
per foot (6.4 millimeters per meter)
4- to 6-inch (100- to 150-millimeter) pipe: inch per
foot (3.2 millimeters per meter)
Pipe 8 inches (200 millimeters) and larger: 1/16 inch
per foot (1.6 millimeters per meter)
These slopes are not a hard and fast rule and might be less
under unusual conditions. The designer must confrm
the required slopes with the local code authority. These
minimum slopes are required to maintain a velocity of
fow greater than 2 fps for scouring action. Table 1-5
gives the approximate velocities for given fow, slopes,
and diameters of horizontal drains based on the Man-
ning formula for half-full pipe and n = 0.015.
A fow velocity of 2 fps will prevent the solids within
a pipe from settling out and forming a system stoppage.
Table 1-6 has been prepared to give the size of a pipe
in conjunction with the fow rate to maintain a self-
cleansing velocity of 2 fps.
Loads for Drainage Piping
The recommended loads for building drains and sewers
are tabulated in Table 1-7. This table shows the maxi-
mum number of fxture units that may be connected to
any portion of the building drain or building sewer for
given slopes and diameters of pipes. For example, an
offset below the lowest branch with 1,300 fu at a slope
of inch per foot (6.4 millimeters per meter) requires
an 8-inch (200-millimeter) pipe.
For devices that provide continuous or semi-con-
tinuous fow into the drainage system, such as sump
pumps, ejectors, and air-conditioning equipment, a
value of 2 fxture units can be assigned for each gpm
(liter per second) of fow. For example, a sump pump
with a discharge rate of 200 gpm (12.6 liters per second)
is equivalent to 200 x 2 = 400 fxture units.
COMPONENTS OF SANITARY
DRAINAGE SYSTEMS
Sumps and Ejectors
The distinction between sump and ejector pumps is
more terminology than actual fact. A sump pump is
designed to transport clear, non-sanitary wastewater
with some turbidity and suspended solids no larger
than sand grains. An ejector pump is designed to trans-
port sanitary waste and larger solids suspended in the
effuent. All effuent is a liquid with solids suspended in it,
but it has the same hydraulic characteristics as water.
Building drains that cannot fow directly into a sewer by
gravity must be discharged into a covered basin. From there,
the fuid is lifted into the buildings gravity drainage system
by automatic pump equipment or by any equally effcient
method approved by the administrative authority.
An ejector basin must be of airtight construction and must
be vented. It is airtight to prevent the escape of foul odors
generated by sanitary waste from the sub-drainage system.
Since it is airtight, a vent is required to relieve the air in the
basin as wastes discharge into it and also to supply air to the
basin while the contents are being discharged to the sanitary
gravity drainage system. A duplex pump system shall be
used. If one pump breaks down, the control system will alert
the second pump to start. Thus, the system will remain in
operation, and no damage will be caused by the cessation of
system operation. When a duplex unit is used, each pump
Figure 1-2 Typical Ejector Pump Installation
MAY 2012 Read, Learn, Earn 7
Table 1-5 Approximate Discharge Rates and Velocities in Sloping Drains, n = 0.015
a
Actual Inside
Diameter of
Pipe,
in. (mm)
Actual Inside Half-full Flow Discharge Rate and Velocity
1
16 in./ft (1.6 mm/m) Slope
1
8 in./ft (3.2 mm/m) Slope
1
4 in./ft (6.4 mm/m) Slope
1
2 in./ft (12.7 mm/m) Slope
Discharge,
gpm (L/s)
Velocity, fps
(mm/s)
Discharge,
gpm (L/s)
Velocity, fps
(mm/s)
Discharge,
gpm (L/s)
Velocity, fps
(mm/s)
Discharge,
gpm (L/s)
Velocity, fps
(mm/s)
1 (31.8) 3.40 (0.21) 1.78 (45.5)
1
3
8 (34.9) 3.13 (0.20) 1.34 (0.41) 4.44 (0.28) 1.90 (48.3)
1 (38.9) 3.91 (0.247) 1.42 (0.43) 5.53 (0.35) 2.01 (51.1)
1
5
8 (41.28) 4.81 (0.30) 1.50 (0.46) 6.80 (0.38) 2.12 (53.9)
2 (50.8) 8.42 (0.53) 1.72 (0.52) 11.9 (0.75) 2.43 (61.8)
2 (63.5) 10.8 (0.68) 1.41 (0.43) 15.3 (0.97) 1.99 (0.61) 21.6 (1.36) 2.82 (71.7)
3 (76.3) 17.6 (1.11) 1.59 (0.49) 24.8 (1.56) 2.25 (0.69) 35.1 (2.21) 3.19 (81.1)
4 (101.6) 26.70 (1.68) 1.36 (34.6) 37.8 (2.38) 1.93 (0.59) 53.4 (3.37) 2.73 (0.83) 75.5 (4.76) 3.86 (98.2)
5 (127) 48.3 (3.05) 1.58 (40.2) 68.3 (4.30) 2.23 (0.68) 96.6 (6.10) 3.16 (0.96) 137 (8.64) 4.47 (113.7)
6 (152.4) 78.5 (4.83) 1.78 (45.3) 111 (7.00) 2.52 (0.77) 157 (10) 3.57 (1.09) 222 (14.0) 5.04 (128.2)
8 (203.2) 170 (10.73) 2.17 (55.2) 240 (15.14) 3.07 (0.94) 340 (21.5) 4.34 (1.32) 480 (30.3) 6.13 (155.9)
10 (256) 308 (19.43) 2.52 (64.1) 436 (27.50) 3.56 (1.09) 616 (38.9) 5.04 (1.54) 872 (55.0) 7.12 (181.0)
12 (304.8) 500 (31.55) 2.83 (72.0) 707 (44.60) 4.01 (1.22) 999 (63.0) 5.67 (1.73) 1,413 (89.15) 8.02 (204.0)
a
n = Manning coeffcient, which varies with the roughness of the pipe.
For full fow: Multiply discharge by 2.
For full fow: Multiply velocity by 1.
For smoother pipe: Multiply discharge and velocity by 0.015 and divide by n of another pipe.
Table 1-7 Building Drains and Sewers
a
Diameter
of Pipe, in.
(mm)
Maximum Permissible Fixture Units for
Sanitary Building Drains and Runouts
from Stacks
Slope, in./ft (mm/m)
1
16 (1.6)
1
8 (3.2)
1
4 (6.4)
1
2 (12.7)
2 (50) 21 26
2 (65) 24 31
3 (80) 20 42
b
50
b
4 (100) 180 216 250
5 (125) 390 480 575
6 (150) 700 840 1,000
8 (200) 1400 1600 1,920 2,300
10 (250) 2500 2900 3,500 4,200
12 (300) 2900 4600 5,600 6,700
15 (380) 7000 8300 10,000 12,000
a
On-site sewers that serve more than one building may be sized according to the current
standards and specifcations of the administrative authority for public sewers.
b
No more than two water closets or two bathroom groups, except in single-family
dwellings, where no more than three water closets or three bathroom groups may be
installed. Check the local codes in the area served for exact requirements or restrictions.
Table 1-6 Slopes of Cast Iron Soil Pipe Sanitary Sewer Required to Obtain Self-cleansing
Velocities of 2.0 and 2.5 ft/sec. (based on Manning formula with n = 0.012)
Pipe
Size
(in.)
Velocity
(ft/sec.)
1/4 Full 1/2 Full 3/4 Full Full
Slope
(ft/ft)
Flow
(gpm)
Slope
(ft/ft)
Flow
(gpm)
Slope
(ft/ft)
Flow
(gpm)
Slope
(ft/ft)
Flow
(gpm)
2.0 2.0 0.0313 4.67 0.0186 9.34 0.0148 14.09 0.0186 18.76
2.5 0.0489 5.04 0.0291 11.67 0.0231 17.62 0.0291 23.45
3.0 2.0 0.0178 10.71 0.0107 21.46 0.0085 32.23 0,0107 42.91
2.5 0.0278 13.47 0.0167 26.62 0.0133 40.29 0.0167 53.64
4.0 2.0 0.0122 19.03 0.0073 38.06 0.0058 57.01 0.0073 76.04
2.5 0.0191 23.79 0.0114 47.58 0.0091 71.26 0.0114 95.05
5.0 2.0 0.0090 29.89 0.0054 59.79 0.0043 89.59 0.0054 119.49
2.5 0.0141 37.37 0.0085 74.74 0.0067 111.99 0.0085 149.36
6.0 2.0 0.0071 43.18 0.0042 86.36 0.0034 129.54 0.0042 172.72
2.5 0.0111 53.98 0.0066 101.95 0.0053 161.93 0.0066 215.90
8.0 2.0 0.0048 77.20 0.0029 154.32 0.0023 231.52 0.0029 308.64
2.5 0.0075 96.50 0.0045 192.90 0.0036 289.40 0.0045 385.79
10.0 2.0 0.0036 120.92 0.0021 241.85 0.0017 362.77 0.0021 483.69
2.5 0.0056 151.15 0.0033 302.31 0.0026 453.46 0.0033 604.61
12.0 2.0 0.0028 174.52 0.0017 349.03 0.0013 523.55 0.0017 678.07
2.5 0.0044 218.15 0.0026 436.29 0.0021 654.44 0.0026 612.58
15.0 2.0 0.0021 275.42 0.0012 550.84 0.0010 826.26 0.0012 1101.68
2.5 0.0032 344.28 0.0019 688.55 0.0015 1032.83 0.0019 1377.10
8 Read, Learn, Earn MAY 2012
READ, LEARN, EARN: Sanitary Drainage Systems
should be sized for 100 percent fow, and it is good practice
to automatically alternate the operation of the pumps.
A sump basin need not be airtight or vented because of
the lack of objectionable odors. Incoming water is collected
in the sump before it is pumped to the gravity drain pipe.
Heavy-fow drains require large sumps to retain greater-
than-usual amounts of water, thereby creating more head
pressure on the pipe inlet. It is good practice to install the
sump basins rim a minimum of 1 inch above the fnished
foor in case the sanitary building drain backs up. This will
prevent sewerage infltration into the clear water system.
Most manufacturers make their basins with bottom, side, or
angle inlets and with inside caulk, no-hub, push-on, spigot, or
screwed connections. Outlet connections are made to accept
pressure-type pipe joints. No-hub pipe and fttings are not
acceptable on pumped discharge piping due to the pressure
limitations of the pipe joints.
Sump and ejector systems normally use a wet pit, with
the pumps either above the slab or submerged. They are
controlled with a foat switch or electronically with
control switches mounted inside the basin. A typical
ejector pump installation is illustrated in Figure 1-2.
A typical submerged sump pump installation is illus-
trated in Figure 1-3.
Cleanouts
A cleanout provides access to horizontal and vertical
lines to facilitate inspection and provide a means of
removing obstructions such as solid objects, greasy
wastes, and hair. Cleanouts, in general, must be gas-
and water-tight, provide quick and easy plug removal,
allow ample space for the operation of cleaning tools,
have a means of adjustment to fnished surfaces, be
attractive in appearance, and be designed to support
whatever traffc is directed over them.
Some cleanouts are designed with a neoprene seal
plug, which prevents it from freezing, or binding, to
the ferrule. All plugs are machined with a straight or
running thread and a fared shoulder for the neoprene
gasket, permitting quick and certain removal when
necessary. A maximum opening is provided for tool
access. Recessed covers are available to accommodate
carpet, tile, terrazzo, and other surface fnishes and
are adjustable to the exact foor level established by
the adjustable housing or by the set screws.
Waste lines typically are laid beneath the foor slabs
at a distance suffcient to provide adequate backfll
over the joints. Cleanouts then are brought up to foor
level by pipe extension pieces. Where the sewer line is
at some distance below grade and not easily accessible
through extensions, small pits or manholes with access
covers must be installed. When cleanouts are installed
in traffc areas, the traffc load must be considered
when the construction materials are selected.
The size of the cleanout within a building should
be the same size as the piping, up to 4 inches (100
millimeters). For larger size interior piping, 4-inch
(100-millimeter) cleanouts are adequate for their
intended purpose; however, 6-inch (150-millimeter)
cleanouts are recommended to allow for a larger variety of
access needs such as for sewer video equipment.
Cleanouts should be provided at the following locations:
Five feet (1.5 meters) outside or inside the building
at the point of exit
At every change of direction greater than 45 de-
grees
At every change of direction and every 150 feet (45.7
meters)for underground sanitary sewer piping larger
than 10 inches (250 millimeters) in diameter
At the base of all stacksit is good practice to install
cleanouts a minimum of 6 inches above the food rim
of the highest fxture served on the lowest level
To comply with applicable codes
Optional locations include:
At the roof stack terminal
At the end of horizontal fxture branches or waste
lines
Figure 1-3 Typical Submerged Sump Pump Installation
MAY 2012 Read, Learn, Earn 9
At fxture traps, which can be pre-manufactured
with cleanout plugs, although some codes prohibit
the installation of this kind of trap
A maximum distance between cleanouts of 50 feet
(15.1 meters) should be maintained for piping 4
inches (100 millimeters) and smaller and of 75 feet
(22.9 meters) for larger piping. Greasy waste piping
shall have a maximum distance of 40 feet (12.2 me-
ters) between cleanouts.
Floor Drains and Floor Sinks
A large-diameter drain with a deep sump connected to a
large-diameter pipe passes more water faster than a smaller
drain. However, economics do not allow the designer to ar-
bitrarily select the largest available drain when a smaller,
less-expensive unit will do a satisfactory job. High-capacity
drains are intended for use primarily in locations where the
fow reaches high rates, such as malls, wash-down areas, and
certain industrial applications. Table 1-8, which shows the
minimum ratio of open grate area based on pipe diameter, is
offered as a guide for the selection of drains where the drain
pipe diameter is known.
The only drawback to using the open-area, pipe-diameter
ratio method is that all drain manufacturers do not list the
total open areas of grates in their catalogs. However, this
information usually can be obtained upon request.
When sizing foor drains for most indoor applications,
the capacity of a drain is not extremely critical because the
drains primary function is to handle minor spillage or fxture
overfow. The exceptions are, of course, cases where equip-
ment discharges to the drain, where automatic fre sprinklers
may deluge an area with large amounts of water, and where
fushing of the foor is required for sanitation.
Floor drains or drains installed to anticipate a failure
may not receive suffcient water fow to prevent the protec-
tive water seal or plumbing trap from evaporating. If the
seal does evaporate, sewer gases will enter the space. Thus,
automatic or manual trap primers should be installed to
maintain a proper trap seal. (A small amount of vegetable oil
will dramatically reduce the evaporation rate of infrequently
used foor drains and foor sinks.)
Figure 1-4 shows the basic components of a foor drain.
Floor drains shall connect to a trap that can be readily
cleaned and sized to effciently serve the purpose for which it
is intended. A deep-seal trap or an approved automatic prim-
ing device should be provided. The trap shall be accessible
either from the foor-drain inlet or by a separate cleanout
within the drain. Figure 1-5 illustrates several types of
drains that meet these conditions.
Grates/Strainers
The selection of grates is based on use and the amount of
fow. Light-traffc areas may have a nickel-bronze grate,
while mechanical areas may have a large, heavy-duty, ductile
iron grate.
The wearing of spike-heeled shoes prompted the replace-
ment of grates with a heel-proof, -inch (6.4-millimeter)
square grate design in public toilet rooms, corridors, pas-
sageways, promenade decks, patios, stores, theaters, and
markets. Though this type of grating has less drainage
capacity than typical grates, its safety feature makes it well
worth the change.
Table 1-8 Recommended Grate Open Areas
for Various Floor Drains with Outlet Pipe Sizes
Nominal
Pipe Size, in.
(mm)
Recommended Minimum Grate
Open Area for Floor Drains
Transverse Area
of Pipe, in.
2a
( 10 mm
2
)
Minimum Inside
Area, in.
2
( 10 mm
2
)
1 (40) 2.04 (1.3) 2.04 (1.3)
2 (50) 3.14 (2.0) 3.14 (2.0)
3 (80) 7.06 (4.6) 7.06 (4.6)
4 (100) 12.60 (8.1) 12.06 (8.1)
5 (125) 19.60 (12.7) 19.60 (12.7)
6 (150) 28.30 (18.3) 28.30 (18.3)
8 (200) 50.25 (32.4) 50.24 (32.4)
a
Based on extra-heavy soil pipe, nominal internal diameter.
Figure 1-4 Basic Floor-Drain Components:
(A) Removable Grate; (B) Rust-resistant Bolts; (C) Integral, One-piece Flashing Ring;
(D) Cast Drain Body with Sump; (E) Sediment Bucket (optional)
10 Read, Learn, Earn MAY 2012
READ, LEARN, EARN: Sanitary Drainage Systems
Grates or strainers should be secured with stainless-steel
screws in nickel-bronze tops. If the public may access the roof,
consideration must be given to protecting vent openings from
vandals, and vandal-proof fasteners are available from most
manufacturers.
In school gymnasium shower rooms, where the blocking
of fat-top shower drains with paper towels can cause food-
ing, dome grates in the corners of the room or angle grates
against the walls can be specifed in addition to the regular
shower drains. Shower-room gutters and curbs have become
undesirable because of code requirements and the obvious
dangers involved. Therefore, the passageways from shower
areas into locker areas need extended-length drains to pre-
vent runoff water from entering the locker areas.
Where grates are not secured and are subject to vehicular
traffc, it is recommended to install non-tilting and/or tractor-
type grates. With these grates, when it moves out of position
the skirt catches the side of the drain body, and the grate
slides back into its original position. Ramp-drain gratings
should be slightly convex because rapidly fowing ramp water
has a tendency to fow across fat grates. A better solution to
this problem is to place fat-top grates on a level surface at
the bottom of the ramp, rather than on the ramp slope.
Flashing Ring
This component makes an effective seal, which prevents
water from passing around the drain to the area below.
Sediment Bucket
A sediment bucket is an additional internal strainer designed
to collect debris that gets by the regular strainer. It is re-
quired wherever the drain can receive solids, trash, or grit
that could plug piping, such as the following situations:
Toilet rooms in industrial/manufacturing buildings
should be equipped with foor drains with sediment
buckets to facilitate cleaning.
Floor drains with sediment buckets must be pro-
vided in mechanical equipment rooms, where pumps,
boilers, water chillers, heat exchangers, and HVAC
equipment regularly discharge and/or must be peri-
odically drained for maintenance and repairs. HVAC
equipment requires the drainage of condensate from
cooling coils using indirect drains.
Boilers require drains with sediment buckets. Stra-
tegically located foor drains also are required in
buildings with wet sprinkler systems to drain water
in case the sprinkler heads are activated. The maxi-
mum temperature of liquids discharged should be
140F (60C).
Where a residential garage requires a foor drain, a
sediment bucket shall be used.
Accessories
A variety of accessories are available to make the basic
drain adaptable to various types of structures. The designer
must know the construction of the building, particularly the
foor and deck structures, to specify the appropriate drain
accessories.
Backwater Valves
A backwater valve can be installed on a building sewer/house
drain when the drain is lower than the sewer line, when
unusual sewer discharges may occur due to combined storm
water and sanitary sewer systems, or when old municipal
sewers incur high rates of infltration.
A backwater valve reacts similarly to a check valve.
The device consists of a mechanical fapper or disc, which
requires a certain amount of maintenance; therefore, these
devices must be placed to provide a free area and access for
maintenance. Sediment can accumulate on the fapper valve
seat, preventing the fapper from closing tightly. Also, many
valves employ a spring or mechanical device to exert a posi-
tive pressure on the fapper device, which requires occasional
lubrication. Most manufacturers of backwater valves provide
an access cover plate for maintenance, which also may be
used as a building sewer cleanout.
Figure 1-6 illustrates two types of backwater valves that
may be installed where there is a possibility of backfow.
Oil Interceptors
In commercial establishments such as service stations, ga-
rages, auto repair shops, dry cleaners, laundries, industrial
plants, and process industries having machine shops, metal-
treating process rooms, chemical process or mixing rooms,
etc., fammable or volatile liquids may enter the drainage
system, which can contaminate the sewer line and cause a
serious fre or explosion.
Oil interceptors are designed to separate and collect
oils and other light-density, volatile liquids, which would
otherwise be discharged into the drainage system. An oil
interceptor is required wherever lubricating oil, cutting oil,
Figure 1-5 Types of Floor Drain:
(A) Typical Drain with Integral Trap
that May Be Cleaned Through Removable Strainer at
Floor Level;
(B) Floor Drain with Combination Cleanout and
Backwater Valve, for Use Where
Possibility of Backfow Exists;
(C) Drain with Combined Cleanout,
Backwater Valve, and Sediment Bucket
Figure 1-6 Types of Backwater Valve
MAY 2012 Read, Learn, Earn 11
kerosene, gasoline, diesel fuel, aircraft fuel, naphtha, paraf-
fn, tri-sodium phosphate, or other light-density and volatile
liquids are present in or around the drainage system.
The interceptor is furnished with a sediment bucket,
which collects debris, small parts, chips, particles, and
other sediment frequently present in industrial waste and
could clog the drainage system. A gasketed, removable cover
permits access for cleaning. To eliminate pressure buildup
inside the interceptor, a connection on each side of the body
allows venting of the interceptor.
Oil interceptors are sized in accordance with the
maximum anticipated gpm (liter per second) fow rate of
wastewater that could be discharged through a tailpiece and
typically are protected from back-siphonage by a vacuum
breaker mounted at the tailpiece entrance.
Fixture Wastewater Type
These devices are mounted on the trap of frequently used fx-
tures. A tapping at the overfow line will allow small amounts
of wastewater to enter an adjacent, infrequently used drain
as the trap surges during use.
Automatic trap primers can be obtained as pre-engineered
devices, which have widely accepted approval. All direct con-
nections between the sewer system and the potable water
system must be protected from potential contamination.
Primers can be manufactured or ftted with devices that are
approved to prevent cross-contamination.
Supports
The location of pipe supports usually is specifed by code.
They are located to maintain a slope that is as uniform
as possible and will not change with time. In this regard,
the rigidity of pipe and joints and the possibility of creep
and bedding settlement are primary considerations. When
building settlement may be signifcant, special hanging ar-
rangements may be necessary. Underground piping should
be continuously and frmly supported, but blocking below
metal pipe is usually acceptable. Consult the manufacturer
for recommendations for piping materials not covered in the
code and for special problems.
Hangers should be designed adequately. To protect
them from damage by building occupants, allow at least a
250-pound (113.4-kilogram) safety factor when designing
hangers. See Plumbing Engineering Design Handbook,
Volume 4, Chapter 6 for further information on hangers
and supports.
Seismic restraint also must be considered.
PIPING MATERIALS
The materials recommended for soil and waste piping,
installed aboveground within buildings, are copper alloy,
copper, cast iron (hub-and-spigot or hubless), galvanized
steel, and PVC. Underground building drains should be cast
iron soil pipe, hard-temper copper tube, ABS, PVC, PVDF,
or DWV pattern Schedule 40 with compression joints or
couplings, installed with a minimum cover of 12 inches (300
millimeters). Corrosive wastes require suitably acid-resistant
materials such as high-silicon cast iron, borosilicate glass,
or polypropylene. (Note: Some blood analyzers discharge
sodium azide, which forms a very dangerous, explosive com-
pound with copper pipes. Other piping must be used, or the
sodium azide must be kept out of the system.)
The materials used for the pipe fttings must be compat-
ible with the piping materials. Fittings should slope in the
direction of fow and have smooth interior surfaces without
ledges, shoulders, or reductions that may obstruct the fow
in the piping.
Drains specifed with cast iron or PVC bodies should
be suitable for most installations. Where extra corrosion
resistance is required, high-silica cast iron, polypropylene,
borosilicate glass, stainless steel, galvanized iron, or other
acid-resisting material should be selected. Where a sediment
bucket is used, it should be bronze, galvanized, or stainless
steel. Enameled sediment buckets are impractical because
they chip when cleaned.
In the selection of materials for top surfaces, such as
grates, where foor drains are visible in fnished areas, ap-
pearance is a prime consideration. As cast iron will rust and
galvanizing and chrome plating eventually will be worn off
by traffc, the preferred material is solid, cast nickel-bronze,
which maintains its attractive appearance. In a swimming
pool, however, chlorine necessitates the use of chlorine-
resistant materials. For large grates that will be subject to
hand-truck or forklift traffc, a ductile iron grate with or
without a nickel-bronze veneer is recommended.
Polished brass or bronze for foor service will discolor
unless there is constant traffc over it. Cast aluminum has
also been found inadequate for certain foor-service applica-
tions due to excessive oxidation and its inability to withstand
abrasion.
JOINING METHODS
Drain and cleanout outlets are manufactured in fve basic
types.
Figure 1-7 Inside Caulk Drain Body
Figure 1-8 Spigot Outlet Drain Body
12 Read, Learn, Earn MAY 2012
READ, LEARN, EARN: Sanitary Drainage Systems
Inside Caulk
In the inside caulk arrangement, the pipe extends up into
the drain body, and oakum is packed around the pipe tightly
against the inside of the outlet. Molten lead then is poured
into this ring and later stamped or caulked to correct for
lead shrinkage. Current installation methods use a fexible
gasket for the caulking material. See Figure 1-7.
Spigot Outlet
The spigot outlet utilizes the caulking method as outlined
above for the inside caulk, except that the spigot outlet is
caulked into the hub or bell of the downstream pipe or ft-
ting. See Figure 1-8.
Push-seal Gasketed Outlet
The push-seal gasketed outlet utilizes a neoprene gasket
similar to standard ASTM C564 neoprene gaskets approved
for hub-and-spigot cast iron soil pipe. A ribbed neoprene
gasket is applied to the accepting pipe, thus allowing the
drain outlet to be pushed onto the pipe.
No-hub Outlet
The no-hub type utilizes a spigot (with no bead on the end)
that is stubbed into a neoprene coupling with a stainless-
steel bolting band (or other type of clamping device), which,
in turn, accepts a downstream piece of pipe or headless ft-
ting. See Figure 1-9.
IPS or Threaded Outlet
The threaded type is a tapered female thread in the drain
outlet designed to accept the tapered male thread of a down-
stream piece of pipe or ftting. See Figure 1-10.
Noise Transmission
Avoiding direct metal-to-metal connections may reduce noise
transmission along pipes. Using heavier materials generally
reduces noise transmission through pipe walls. Isolating pip-
ing with resilient materials, such as rugs, belts, plastic, or
insulation may reduce noise transmission to the building. See
Table 1-9 for relative noise-insulation absorption values.
BUILDING SEWER INSTALLATION
The installation of building sewers is very critical to the
operation of the sewer. Inadequate bedding in poor soils may
allow the sewer to settle, causing dips and low points in the
sewer. The settlement of sewers interrupts fow, diminishes
minimum cleansing velocity, reduces capacity, and creates a
point where solids can drop out of suspension and collect.
Following are some guidelines for installing building
sewers.
Where natural soil or compacted fll exists, the trench
must be excavated in alignment with the proposed
pitch and grade of the sewer. Depressions need to be
cut out along the trench line to accept the additional
diameter at the piping joint or bell hub. A layer of
sand or pea gravel is placed as a bed in the excavated
trench because it is easily compacted under the pipe,
allowing more accurate alignment of the pipe pitch.
The pipe settles into the bed and is frmly supported
over its entire length.
Where shallow amounts of fll exist, the trench can
be over-excavated to accept a bed of sand, crushed
stone, or similar material that is easily compacted.
Bedding should be installed in lifts (layers), with each
lift compacted to ensure optimum compaction of the
bedding. The bed must be compacted in alignment
with the proposed pitch and grade of the sewer. It is
recommended that pipe joints or bell hub depressions
be hand-prepared due to the coarse crushed stone.
The soil-bearing weight determines trench widths
and bedding thickness.
Where deep amounts of fll exist, the engineer should
consult a geotechnical engineer, who will perform soil
borings to determine the depths at which soils with
proper bearing capacities exist. Solutions include
compacting existing fll by physical means or remov-
ing existing fll and replacing it with crushed stone
structural fll.
Backflling of the trench is just as critical as the com-
paction of the trench bed and the strength of existing
soils. Improper backfll placement can dislodge pipe
and cause uneven sewer settlement, with physical
depressions in the surface. The type of backfll mate-
rial and compaction requirements must be reviewed
to coordinate with the type of permanent surface.
Landscaped areas are more forgiving of improper
backfll placement than hard surface areas such as
concrete or bituminous paving.
Figure 1-10 IPS or Threaded
Outlet Drain Body
Figure 1-9 No-hub Outlet Drain Body
MAY 2012 Read, Learn, Earn 13
Care must be taken when using mechanical means to
compact soils above piping. Mechanical compaction of
the frst layer above the pipe by vibrating or tamping
devices should be done with caution. Compacting the
soil in 6-inch (150-millimeter) layers is recommended
for a good backfll.
Proper sewer bedding and trench backfll will result in
an installation that can be counted on for long, trouble-free
service.
SANITATION
All drains should be cleaned periodically, particularly
those in markets, hospitals, food-processing areas, animal
shelters, morgues, and other locations where sanitation is
important.
For sanitation purposes, an acid-resisting enameled in-
terior in foor drains is widely accepted. The rough surfaces
of brass and iron castings collect and hold germs, fungus-
laden scum, and fne debris that usually accompany drain
waste, and there is no easy or satisfactory way to clean these
rough surfaces. The most practical approach is to enamel
them, and the improved sanitation compensates for the
added expense. However, pipe threads cannot be cut into
enameled metals because the enameling will chip off in the
area of the machining. Also, pipe threads themselves cannot
be enameled; therefore, caulked joints should be specifed
on enameled drains. Most adjustable foor drains utilize
threaded adjustments, so these drains cannot be enameled.
However, adjustable drains that use sliding lugs on a cast
thread may be enameled.
A grate or the top ledge of a drain can be enameled, but
the enamel will not tolerate traffc abrasion without show-
ing scratches and, eventually, chipping. The solution to this
problem is a stainless-steel or nickel-bronze rim and grate
over the enameled drain body, a common practice on indi-
rect waste receptors, sometimes referred to as foor sinks.
Specifers seem to favor the square, indirect waste receptor,
but the round receptor is easier to clean and has better anti-
splash characteristics. For cases where the choice of square
or round is infuenced by the foor pattern, round sinks with
square tops are available.
In applications such as hospital morgues, cystoscopic
rooms, autopsy laboratories, slaughterhouses, and animal
dens, where blood or other objectionable materials might
cling to the sidewalls of the drain, it is recommended to ft
the enameled drain with a fushing rim.
Where the waste being drained can clog the trap, a heel
inlet on the trap with a fushing connection is recommended
in addition to the fushing rim, which merely keeps the drain
sides clean. (This option may not be allowed by certain codes.)
A 2-inch (50-millimeter) trap fushes more effectively than
a 3-inch (80-millimeter) trap because it allows the fushing
stream to drill through the debris rather than completely
fush it out. A valve in the water line to the drain is the best
way to operate the fushing-rim drain. Flush valves have been
used and can save water; however, they are not as convenient
or effective as a shutoff valve. In any fushing water-supply
line to a drain, a vacuum breaker installed according to code
must be provided.
KITCHEN AREAS
When selecting kitchen drains, the designer must know
the quantity of liquid and solid waste the drains will be
required to accept, as well as which equipment emits waste
on a regular basis and which produces waste only by acci-
dental spillage. Dishwashing machines, steamers, booster
heaters, and other kitchen equipment may discharge waste
of 180F or higher into the sanitary drain, so cast iron pip-
ing or coolers may be required in these cases.
Floor-cleaning procedures should be ascertained to de-
termine the amount of water used. If any amount of solid
waste is to be drained, receptors must be specifed with
removable sediment buckets made of galvanized or stainless
steel. Also, suffcient vertical clearance over these drains
must be provided to conveniently remove the sediment
buckets for cleaning.
Many kitchen planners mount kitchen equipment on a
5-inch (125-millimeter) curb. Placing the drain on top of the
curb and under the equipment makes connection of indirect
drain lines diffcult and the receptor inaccessible for inspec-
tion and cleaning. Mounting the receptor in front of the curb
takes up foor space, and the myriad of indirect drains that
discharge into it create a potential hazard for employees who
may trip over them. The solution requires close coordination
between the engineer and the kitchen designer. Figure 1-11
shows an arrangement whereby any spillage in front of the
curb can be drained by half of the receptor, while indirect
drains are neatly tucked away.
Where equipment is on the foor level and an indirect
waste receptor must be provided under the equipment, a shal-
low bucket that can be removed easily is recommended.
WATERPROOFING
Whenever a cast-iron drain is cemented into a slab, separa-
tion due to expansion and contraction occurs and creates
several problems. One is the constant wet area in the crev-
ice around the drain that promotes mildew odor and the
breeding of bacteria. Seepage to the foor below is also a pos-
sibility. A seepage or fashing fange can correct this problem.
Weep holes in the fashing fange direct moisture into the
Table 1-9 Relative Properties of Selected
Plumbing Materials for Drainage Systems
Materials
Noise
Absorption
Corrosion
Resistance
a
ABS Fair Good
Cast iron Excellent Good
Clay
b
Excellent
Concrete
c
Fair
d
Copper Fair Good
Glass borosilicate
b
Excellent
Polypropylene Fair Excellent
PVC Fair Excellent
Silicon iron
c
Excellent
Steel, galvanized Good Fair
a
This refers to domestic sewage. Consult manufacturer for
resistance to particular chemicals.
b
Since these materials are used only aboveground for chemical
waste systems, this is not applicable.
c
This material is usually allowed only belowground.
d
Susceptible to corrosion from hydrogen sulfde gas.
14 Read, Learn, Earn MAY 2012
READ, LEARN, EARN: Sanitary Drainage Systems
drain. Also, this fange accepts membrane material, and
when used, the fashing ring should lock the membrane to
the fange.
One prevalent misconception about the fashing fange
is that it can have weep holes when used with cleanouts;
however, there can be no weep holes into a cleanout to which
moisture can run. Weep holes also should be eliminated from
the fashing fanges of drains, such as refection-pool drains,
where an overfow standpipe to maintain a certain water
level shuts off the drain entrance.
The term non-puncturing, used in reference to mem-
brane-fashing, ring-securing methods, is now obsolete,
as securing bolts have been moved inboard on fashing L
fanges, and the membrane need not be punctured to get a
seal. Of the various arrangements, this bolting method allows
the greatest squeeze pressure on the membrane.
FLOOR LEVELING
A major problem in setting foor drains and cleanouts occurs
when the concrete is poured level with the top of the unit,
ignoring the fact that the addition of tile on the foor will
cause the drain or cleanout to be lower than the surrounding
surface. To solve the problem, cleanouts can be specifed with
tappings in the cover rim to jack the top part of the cleanout
up to the fnished foor level. Floor drains can be furnished
with adjustable tops to attain an installation that is fush
with the fnished foor.
THERMAL EXPANSION
When excessive thermal expansion is anticipated, pipe move-
ment should be controlled to avoid damaging changes in slope.
Anchoring, using expansion joints, or using expansion loops or
bends may accomplish this. When anchoring, avoid excessive
stress on the structure and the pipe. Piping or mechanical
engineering handbooks should be consulted if stress analysis
is to be performed due to excessive stresses or to the differing
expansion characteristics of materials.
PROTECTION FROM DAMAGE
Following are some common hazards that may damage drains
and drain piping and some methods of protection.
Abrasion: Use plastic or rubber sleeves or insulate
where copper pipe leaves the slab.
Condensation: Insulate the piping.
Corrosion: Use methods recommended in Plumbing
Engineering Design Handbook Volume 1, Chapter
8: Corrosion.
Heavy earth loads: Use stronger pipe or pipe
sleeves.
Expansion and contraction: Use fexible joints, loops,
swing joints, or offsets.
Fire: Use an appropriate building construction
around the pipe. Some jurisdictions require metal
piping within 2 feet (0.6 meter) of an entry into a
frewall. All materials must conform to the appropri-
ate fre ratings.
Heat: Keep thermoplastic pipe away from sources of
heat or use insulation.
Nails: Use ferrous pipe, steel sleeves, or steel plates
or do not locate pipe near possible nail penetration
areas.
Seismic activity: Brace pipe and provide fexible
joints at connections between piping braced to walls
or the structure and piping braced to the ceiling and
between stories (where differential movements will
occur).
Settlement: Use sleeves or fexible joints. When em-
bedded in concrete, cover piping with three layers of
15-pound (6.8-kilogram) felt.
Sunlight: Protect thermoplastic pipe by insulation
and a jacket or shade it to avoid warping.
Vandals: Install pipe above reach or in areas protected
by building construction. Piping must be supported to
withstand 250 pounds (113.4 kilograms) hanging from
the moving pipe.
Wood shrinkage: Provide slip joints and clearance
for pipe when wood shrinks. Approximately s inch
(16 millimeter) per floor is adequate for typical
frame constructions, based on 4 percent shrinkage
perpendicular to wood grain. Shrinkage along the
grain usually does not exceed 0.2 percent.
ALTERNATE SANITARY SYSTEMS
The design and installation of alternative engineered plumb-
ing systems are permitted in all codes, so long as they are
designed by a licensed professional engineer who is respon-
sible for the proper operation of the systems. If an alternative
system is contemplated, submission to and approval by the
authority having jurisdiction must be obtained. To expedite
approval, the following steps are suggested.
Indicate on the design documents that the plumbing 1.
system (or parts thereof) is an alternative design.
Submit enough technical data to support the proposed 2.
alternative design and prove that the system conforms
Figure 1-11 Combination Floor Drain
and Indirect Waste Receptor
MAY 2012 Read, Learn, Earn 15
to the intent of the code. This shall include suitability
for the intended purpose, strength, equivalent level
of performance compared to traditional installations,
safety, and quality of materials.
Include foor plans, riser diagrams, and an indication 3.
of the proposed fow.
Provide assurance that the manufacturers installa- 4.
tion instructions will be followed.
If approval is given, indicate on the permit and all con- 5.
struction applications that an alternative engineered
design is part of the approved installation.
Alternative systems are characterized by, but not 6.
limited to, using a single stack for both sanitary and
vent or no vent at all. One exception is a conventional
drainage, reduced-vent system. All of the following
systems have been used successfully in the United
States and around the world for many years and have
proven effective in actual use. All of the alternative
systems discussed have combined sanitary and vent
systems.
SOVENT AND PROVENT
The Sovent system was developed in 1959 in Switzerland. It is
a patented, combination drainage and vent system that uses a
single stack instead of a conventional two-pipe drainage and
vent stack. The Sovent system uses cast iron and/or copper
pipe and is suitable only for multistory buildings because it
allows substantial economy in piping installation.
The Provent system is similar to the Sovent system, but it
uses PVC. Although installed in many countries throughout
the world, it remains an alternative, unconventional system
with only limited usage in the United States.
It is not the intent of this chapter to provide specifc design
criteria for a Sovent or Provent system, but rather to discuss
the individual component characteristics that will enable a
plumbing engineer to obtain a working knowledge of how
these systems work. A typical Sovent single-stack system is
illustrated in Figure 1-12.
A Sovent or Provent system consists of three principal parts:
piping for all branch wastes and stacks, an aerator ftting at
each foor level where the branch waste lines connect to the
stack, and a deaerator ftting at the base of the stack where it
enters the house drain.
The starting point is the horizontal soil and waste
branches. The fxture units and branch sizes are similar to
those fgures found in conventional systems. The maximum
fxture units that may be connected to a branch or stack are
also similar to that of conventional systems.
Branch sizes must be adjusted according to the follow-
ing.
A second vertical drop or a vertical drop of more
than 3 feet (0.9 meter) requires an increase in the
downstream side of the connection.
When three 90-degree changes in direction occur in
a horizontal branch, the horizontal branch shall be
increased in size at the upstream side of the third
change.
When a branch serves two water closets and one
or more additional fxtures, the soil line shall be
increased to 4 inches (100 millimeters) at the point
where one water closet and one additional fxture
are connected.
The branch must be increased one size when a soil
branch exceeds 12 feet (3.7 meters) in horizontal
length.
The branch must be increased one size when a
waste line exceeds 15 feet (4.6 meters) in horizontal
length.
Stacks must be carried full size through the roof. Two
stacks can be connected at the top above the highest fx-
ture or at the bottom prior to entering the building drain.
The size is based on the total fxture units. Fixtures may
be connected into a horizontal offset in a stack below the
deaerator ftting.
An aerator ftting is required at each level where a soil
branch, a waste line the same size as the stack, or a waste
branch one size smaller than the stack is connected. The
aerator consists of an upper stack inlet, a mixing chamber,
and a baffe in the center of the ftting. This provides a
chamber where the fow from the branches may gradually
mix smoothly with the air and liquid already fowing in the
stack. It also limits the turbulence and velocity of the incom-
ing water. A 2-inch (50-millimeter) horizontal branch may
enter the stack with no ftting. Two basic styles of aerator
ftting meet the needs of most design conditions: the double-
side entry ftting and the single-entry ftting. Face entry and
top entry are used in special cases.
A deaerator ftting is required at the bottom of the stack
and is designed to overcome the tendency of the falling waste
to build up excessive back pressure at the bottom of the stack
when the fow is decelerated by the bend into the horizontal
drain. The deaerator consists of an air separation chamber,
a nose piece, a pressure relief outlet at the top connected to
the building drain, and a stack outlet at the bottom. The
purpose of the deaerator is to separate the airfow from the
stack to ensure the smooth fow of liquid into the building
drain and to relieve the positive pressure generated at the
stacks base. The confguration of the ftting causes part of
the air falling with the liquid to fow through the pressure
relief line, and the remainder of the air goes directly into
the building drain.
The plumbing engineer must explain the special require-
ments of the Sovent or Provent system to the installing
contractor. The engineer also should make regular inspec-
tions of the project to ensure that the design conditions are
met. A complete set of contract documents shall be provided
to the owner to allow proper alteration or expansion of the
project in the future.
SINGLE-STACK SYSTEM
The single-stack system is a combination drainage and vent
system consisting of a single stack instead of conventional
separate drainage and vent stacks. In this drainage system,
the drainage stack serves as both a single-stack drainage
and vent system when properly sized. To relieve internal
air pressures, the one-pipe system must be larger than that
required for drainage purposes alone. The drainage stack
and branch piping shall be considered vents for the drainage
16 Read, Learn, Earn MAY 2012
READ, LEARN, EARN: Sanitary Drainage Systems
system as a whole. Although the pipe sizing is larger in a
single-stack system than in a conventional one, installation
savings are achieved by reducing the amount of vent piping
required.
The major components of the one-pipe system are over-
size, unvented S traps instead of the conventionally sized
and vented P traps and fxtures that allow water to run off
after the tap is closed to fll the traps with water to maintain
the trap seal. The trap arm length is limited to reduce any
suction buildup, and the stack is oversized to limit internal
air pressure and vacuum buildup.
Often referred to as the Philadelphia stack, this uncon-
ventional system has operated successfully for more than 100
years with no problems. Consideration has been made by code
bodies to include this system as an engineered design, which
allows it to be used providing the engineer has designed it
in accordance with code.
REDUCED-SIzE VENTING
In 1974, the National Bureau of Standards (NBS) conducted
a laboratory study of one-story and split-level experimental
drainage systems where the vents varied from one to six
pipe sizes smaller than those for conventional systems. They
showed satisfactory hydraulic and pneumatic performance
under various loading conditions. At the same time, the
10-story wet vent system at the Stevens Institute Building
Technology Laboratory had been modifed by reducing the
vents one to three pipe sizes in accordance with the plans
and specifcations of the NBS. The results also indicated
that the vents in a two-story housing unit can safely be
made smaller than previously allowed without jeopardizing
the trap seals.
This system may allow economies of pipe size in the vent-
ing design of low-rise residential buildings, although this
particular system has not been accepted by authorities. It
is limited to special conditions and requires the vent pipes
to be of a material such as copper or plastic that will resist
the buildup of corrosion products.
VACUUM DRAINAGE SYSTEM
Vacuum drainage operates on the principle that the major-
ity of the system is under a continuous vacuum. The system
is proprietary and is made by various manufacturers, all of
which have different names for devices performing similar
operations, so generic identifcation is used here. Various
designs are capable of sanitary and waste disposal, either
separate or in combination, and are used for various projects
such as prisons, supermarkets, and ships. There is no direct
connection from the sanitary waste to the vacuum system.
The one big advantage is that piping is installed overhead
and no pipe is required to be placed underground.
The system consists of three basic components: a vacuum
network of piping and other devices that collects and trans-
ports waste from its origin, vacuum generation pumps, and
a vacuum interface device at the point of origin that isolates
the vacuum piping from atmospheric pressure. When the
system serves water closets, the water closets must be pur-
pose made, designed to rinse and refll with 0.5 gallon (2.2
liters) of water.
The piping network for a vacuum waste system is held
under a constant vacuum between 12 and 18 inches of mer-
cury (in Hg) (4065 kilopascals) and generally is fabricated
from PVC, copper, or other nonporous, smooth-bore mate-
rial. Horizontal piping shall slope at a rate of 8 inch per
foot (1.18 millimeter per meter) toward the vacuum center.
This piping slope is the same as in conventional systems. If
this slope cannot be maintained, the traps created in the
piping runs when routed around obstacles would be cleared
because of the differential pressure that exists between the
vacuum center and the point of origin. The discharge of the
piping system is into the waste storage tanks.
Figure 1-12 Typical Sovent Single-stack System
MAY 2012 Read, Learn, Earn 17
The vacuum generation system includes vacuum pumps,
which create a vacuum in the piping and storage tanks that
collect and discharge the waste into the sewer system. The
vacuum pumps run only on demand, and redundancy is pro-
vided. They also have sewage pumps that pump the drainage
from the storage tanks into the sewer.
The vacuum interface is different for sanitary drainage
than for clear waste. Vacuum toilets operate instantly upon
fushing, and when a vacuum toilet is cycled, a discharge
control panel assembly is activated, sending the discharge to
the tank. A valve acts as an interface between the vacuum
and the atmosphere. The tank will discharge into the sewer
when a predetermined level of discharge is reached.
When clear water is discharged, the water goes into an
accumulator. When a controller senses that suffcient waste
is present, it opens the normally closed extraction valve,
which separates the atmospheric pressure from the vacuum
and removes the waste from the accumulator.
Because vacuum toilets use 0.5 gallon per fush, the hold-
ing tanks can be smaller than those for conventional toilets.
A fush control panel is designed to provide all of the control
functions associated with the vacuum toilet. The control
panel consists of a fush valve, fush controller, water valve,
and vacuum breaker. All controls are pneumatically oper-
ated. The fush controller controls the opening of the fush
valve and the rinse valve as well as the duration of the time
the fush valve is open.
REFERENCES
Daugherty, Robert L., Joseph B. Franzini, and E. 1.
John Finnemore, Fluid Mechanics with Engineering
Applications, McGraw-Hill, 1985.
Dawson, F.M. and A.A. Kalinske. 2. Report on Hydraulics
and Pneumatics of Plumbing Drainage Systems, State
University of Iowa Studies in Engineering, Bulletin
No. 10, 1937.
18 Read, Learn, Earn MAY 2012
READ, LEARN, EARN: Sanitary Drainage Systems
CONTINUING EDUCATION: Sanitary Drainage Systems
CE Questions
Sanitary Drainage Systems (CEU 187)
A _______ is the main vertical pipe that 1.
carries clear water waste from non-
sanitary fxtures.
soil stack a.
building drain b.
waste stack c.
vent stack d.
What is the recommended drainage 2.
fxture unit value for a kitchen sink?
2 a.
3 b.
4 c.
5 d.
How many drainage fxture units 3.
maximum may be connected to one
3-inch sanitary stack with two branch
intervals?
20 a.
42 b.
48 c.
72 d.
An offset is sized and sloped like a 4.
________.
building sewer a.
building drain b.
horizontal branch c.
vertical stack d.
The equation Q = AV calculates what? 5.
fow velocity a.
fow quantity b.
friction loss c.
area of fow d.
The minimum slope of a 2-inch horizontal 6.
drain is ________.
1/8 inch per foot a.
inch per foot b.
inch per foot c.
1 inch per foot d.
Reading the article and completing the form will
allow you to apply to ASPE for CEU credit. If you
earn a grade of 90 percent or higher on the test,
you will be notified that you have logged 0.1
CEU, which can be applied toward CPD renewal
or numerous regulatory-agency CE programs.
(Please note that it is your responsibility to deter-
mine the acceptance policy of a particular agency.)
CEU information will be kept on fle at the ASPE
ofce for three years.
ASPE Continuing Education Application Form
This form is valid up to one year from date of publication. Expiration date: Continuing education credit will be given for this examination
through May 31, 2013. Applications received after that date will not be processed.
Submit this form with payment via mail (ASPE Read, Learn, Earn, 2980 S. River Road, Des Plaines, IL 60018), fax (847-296-2963), or email
aspeeducation@aspe.org.
Please print or type; this information will be used to process your credits.
Name ______________________________________________________________________ ASPE Membership No. ______________
Organization ___________________________________________________ Daytime telephone _____________________________
Billing Address ________________________________________________________________________________________________
City _________________________________________ State/Province ________________________ Zip ______________________
E-mail _______________________________________________________________________ Fax ____________________________
PE State _____________________________________________ PE No. _________________________________________________
Notice for North Carolina Professional Engineers: State regulations for registered PEs in North Carolina now require you to complete ASPEs online CEU validation form
to be eligible for continuing education credits. After successfully completing this quiz, just visit ASPEs CEU Validation Center at aspe.org/CEUValidationCenter.
I certify that I have read the article indicated
above.
Signature
Payment:
Member: Free
Nonmember: Each examination: $35
Personal Check (payable to ASPE)
Business or government check
DiscoverCard VISA MasterCard AMEX
If rebilling of a credit card charge is necessary, a $25
processing fee will be charged.
ASPE is hereby authorized to charge my CE
examination fee to my credit card
Account Number
Expiration date
Signature
Cardholders name (Please print)
A typical ejector pump installation 7.
contains which of the following?
foat a.
discharge pipe b.
gate valve c.
all of the above d.
Cleanouts should be installed no more 8.
than _________ apart for 3-inch piping.
50 feet a.
75 feet b.
100 feet c.
150 feet d.
A ________ prevents 9. water from passing
around a drain to the area below.
grate a.
gasket b.
fashing ring c.
cleanout d.
The recommended material for 10.
aboveground soil waste piping within a
building is ________.
PVC a.
cast iron b.
galvanized steel c.
all of the above d.
In a Sovent system, the 11. branch must be
increased one size when a waste line
exceeds ________ in horizontal length.
12 feet a.
15 feet b.
18 feet c.
20 feet d.
The horizontal piping in a vacuum waste 12.
system shall slope ________ inch per foot
toward the vacuum center.
1/16 a.
1/8 b.
c.
d.
Circle the correct answers below.
MAY 2012 Read, Learn, Earn 19
C
E
U
1
8
8
Energy and
Resource
Conservation
in Plumbing
Systems
Continuing Education from the
American Society of Plumbing Engineers
JUNE 2012
ASPE.ORG/ReadLearnEarn
Prior to the 19731974 OPEC oil embargo, energy was
considered inexhaustible and expendable. As energy costs
grew, society turned its attention toward energy conserva-
tion. The Energy Policy and Conservation Act (EPCA) of
1975 was the frst major piece of legislation that addressed
federal energy management. Additional laws soon followed,
including the Resource Conservation and Recovery Act of
1976, National Energy Conservation Policy Act of 1978,
Federal Energy Management Improvement Act (FEMIA)
of 1988, and the most recent Energy Policy Act (EPAct) of
2005, which expanded on the previous legislation.
Along with the federal government, other sectors of
society made strides to reduce energy consumption. The
automotive industry, which was heavily impacted by the oil
embargo, was quick to adapt by producing smaller, lighter,
more fuel-effcient cars. The construction market also made
strides by adopting model energy codes, effciency stan-
dards, and alternate fuel sources. A green movement has
spread across the nation, pushing for the implementation
of effcient and sustainable technologies.
One of the highest energy-consuming plumbing sys-
tems is domestic hot water, often consuming 2 to 4 percent
of the total energy used in an offce building and 8 percent
in residential properties. This plumbing system has a great
need for energy-conservation measures.
Just as important as energy conservation is resource
conservation. Obviously, a resource greatly affected by
plumbing system design is water. Water use in the United
States has more than doubled in the past half-century, from
approximately 180 billion gallons per day in 1950 to more
than 400 billion gallons a day in 2000. Because of increases
in population and demand, at least 36 states are projecting
water shortages by 2013.
Each American uses an average of 100 gallons of water
a day at home, and it is important to note that by reduc-
ing hot water use, both energy and water are conserved.
For example, if one in every 10 homes in the United States
were to install low-fow faucets or faucet accessories in their
bathrooms, it could save 6 billion gallons of water and more
than $50 million in the energy costs to supply, heat, and
treat that water.
This chapter is intended to provide a plumbing engineer
with design techniques that conserve both energy and water
and to assist them in selecting energy- and water-effcient
equipment and systems. Where the recommendations set
forth in this chapter do not meet the minimum provisions
of the local code, the code shall apply.
DESIGN TECHNIQUES FOR DOMESTIC
HOT WATER SYSTEM ENERGY
CONSERVATION
Hot water use can vary from handwashing, showering,
and janitorial needs to cooking, dishwashing, and laun-
dering needs. Design techniques that can be employed to
conserve energy when heating water follow.
Eliminate Leaks
One of the frst and easiest actions to take to conserve energy
and resources is by repairing leaking fxtures, appliances,
and hot water piping.
Reduce Domestic Hot Water Temperature
Many domestic water-heating systems are designed to deliver
140F water based on the anticipated needs of kitchen and
janitorial uses, though water for human contact typically is
delivered between 110 F and 105F. Often, 105F water is
produced by blending 140F hot water with cold water. While
this reduces the amount of hot water required, it does not
decrease the energy used to heat the water. Many energy
codes and standards for new buildings require the domestic
hot water system to be set at 110F. (It is important to note
that setting a water heater below 120F may allow Legionella
bacteria to grow inside the domestic hot water tank.)
The temperature, after mixing two or more volumes (or
fows) of water, is calculated using the following equation:
Equation 7-1
t
m
=
Q
1
t
1
+ Q
2
t
2
Q
1
+ Q
2
where
t
m
= Temperature of mixture
t
1
= Temperature of fow Q
1
t
2
= Temperature of fow Q
2
Q
1
= Cold water, gallons per minute (gpm) (liters per
second [L/s])
Q
2
= Hot water, gpm (lpm)
Example 7-1
What is the temperature of 45 gpm (2.84 L/s) of 155F (68.5C)
water mixed with 55 gpm (3.47 L/s) of 75F (23.9C) water?
45 155 + 55 75
= 111F
45 + 55
In SI units:
(
2.84 68.5 + 3.47 23.9
= 44C
)
2.84 + 3.47
The ratio (percentage) of hot water required to be mixed
with cold water to provide a mixed water requirement is
determined using the following equation:
Reprinted from Plumbing Engineering Design Handbook, Volume 1. 2009, American Society of Plumbing Engineers.
Note: In determining your answers to the CE questions, use only the material presented in the corresponding continuing education
article. Using information from other materials may result in a wrong answer.
2 Read, Learn, Earn JUNE 2012
READ, LEARN, EARN
Equation 7-2
Ratio HW =
t
m
t
1
t
2
t
1
Example 7-2
How much hot water is required to provide 80 gallons per
hour (gph) (0.084 L/s) of 110F (43C) mixed water with 155F
(68.5C) hot water and 75F (23.9C) cold water?
110 75
= 0.44 or 44% hot water
155 75
80 gph x 0.44 = 35 gph of 155F hot water
(0.084 L/s x 0.44 = 0.037 L/s of 68.5C hot water)
How much hot water is required to provide 80 gph (0.084 L/s)
of 110F (43C) mixed water with 125F (51.5C) hot water
and 75F (23.9C) cold water?
110 75
= 0.70 or 70% hot water
125 75
80 gph 0.70 = 56 gph of 125F hot water
(0.084 L/s 0.70 = 0.059 L/s of 51.5C hot water)
As shown, the reduction in domestic water temperature in
itself does not necessarily result in a reduction in energy
input related to the water consumed.
Reduce Fixture Flow Rates
The EPAct of 1992 set maximum water usages for specifc
fxtures (e.g., 1.6 gallons per fush [gpf] for water closets).
Reduced flow rates result in less water needing to be
pumped and heated, smaller pipe sizes, and less heat loss
from piping, consequently saving energy. Fixture fow rates
vary depending on the supply ftting design and water pres-
sure. Manufacturers test results have shown that fows
for lavatories and showers can be quite high, making them
prime candidates for fxture fow reduction. Providing auto-
matic fow-control fttings can reduce fxture fow rates. On
lavatories, the type of faucet and spout usually dictates the
location of these fttings. In showers, the type of head and
arm determines the ftting location. After being ftted with a
fow-control device, reduced fow rates of 1 gpm or less usually
are seen in lavatories and 2.5 gpm or less in showers.
Figure 7-1 provides a way to translate fxture fow rate
to annual consumption and is useful in determining the
most energy-effcient design fow rate. By varying the per-
cent of hot water at the fxture, annual energy consumption
can be predicted. Figure 7-1 can be used as a design tool
for many purposes, some of which are to predict energy
consumption, anticipated utility costs, and payback calcula-
tions for fxture replacement.
Manufacturers of fow-control devices describe in greater
detail their design and installation requirements. The instal-
lation of this water-conserving device has resulted in the
savings of millions of gallons of water per year throughout
the country. This reduction in water demand translates into
water the local utility company does not have to pump, the
purifcation plant does not have to handle and process, and
the waste treatment plant does not have to treat.
Example 7-3
A faucet using 3.25 gallons of 150F hot water per day with
a 100 percent faucet fow rate equates to an annual energy
use of 774,000 British thermal units (Btu) per year (3.25 gal
8.33 lb/gal 110FT 260 days). A 50 percent fow rate
reduces energy use to 387,000 Btu per year.
Apply Economical Thermal Insulation
Economical thermal insulation is the amount of insulation
that annually produces the lowest sum of energy lost versus
the annual cost of insulation. In addition to conserving en-
ergy by retarding heat loss, insulation provides additional
benefts such as protection against burns, reduction of noise,
and control of condensation. The North American Insulation
Manufacturers Association (NAIMA) has developed software
called 3E Plus, which calculates the thermal performance
of both insulated and uninsulated piping, ducts, and equip-
ment; translates Btu losses into actual dollars; and calculates
greenhouse gas emission and reductions.
The International Energy Conservation Code requires
automatic-circulating hot water system piping to be insulated
with 1 in. of insulation having a conductivity not exceeding
0.27 Btu per inch/h
ft
2
.
Energy savings, in Btu, can be determined by the fol-
lowing formula:
Equation 7-3
S = g L
where
S = Energy savings, Btu per hour (Btuh) (kilojoules per
hour [kJ/h])
g = Factors taken from Table 7-1 or 7-2 at a particular
T, Btuh/ft (kJ/h/m)
L = System length, ft (m)
Hot water pipes should be continuously insulated from the
heater to the end use, while cold water lines should be in-
sulated near the water heater tank to minimize convective
losses.
Limit Water Heater and
Circulation Pump Operation
Buildings with large hot water distribution systems use
circulating loops to ensure that hot water is available to
all fxtures within a timely manner. By limiting the hours
of operation of these pumps and water heaters, substantial
savings can be realized.
An automatic thermostatic control should be installed to
cycle the pump on and off in response to the temperature of
water returning to the water heater through the recircula-
tion piping. The minimum differential, or deadband, of the
control shall not be less than 20F.
Time clocks can be used to control hot water circulating
pumps. The energy saved when using time clocks can be
calculated as follows:
Equation 7-4
Motor kilowatts (kW) off hours
electric rate ($/kWh) = total savings ($)
JUNE 2012 Read, Learn, Earn 3
to achieve the desired temperature levels, saving the system
from having to operate during the day. Depending on the
difference in electrical rates, an off-peak powered hot water
system generally pays (in a few years) for the additional
equipment required, including the effects of equipment heat
losses during periods of standby.
Upgrade to More Effcient Equipment
Equipment specifcations need to be examined to ensure
that only hot water heating equipment meeting minimum
energy standards is approved for installation. The following
factors contribute to the effciency of gas-fred water heaters
and need to be taken into consideration when selecting this
equipment: combustion equipment and its adjustment, tank
insulation, heat exchanger effectiveness, fring rate, pickup
and demand, and standby stack losses.
Water Heater Location
Many hot water heaters are installed in central locations,
requiring long supply and return piping runs to reach plumb-
ing fxtures. Moving these heaters near the most frequent
points of use can minimize piping heat loss.
DOMESTIC HOT WATER
HEATING EQUIPMENT
There are many different means of generating hot water.
Each has its own advantages and disadvantages, and it is
the plumbing engineers responsibility to determine which
technology is best suited for an application. The recovery
effciency and standby losses of water heating equipment
should comply with the latest codes and regulations for the
manufacturer. State energy codes also mandate the use of
energy-effcient equipment and should be checked by the
plumbing engineer prior to the preparation of specifca-
tions.
Listed below are several hot water heating technolo-
gies.
Storage Water Heaters
Tank-type water heaters are self-contained units that heat
and store water within the same storage tank. Insulation
is added around the exterior of the tank to prevent heat
from escaping. Because the tanks maintain a stored water
temperature, there is an associated standby energy loss.
Compared to tankless heaters, storage water heaters have the
advantage of using energy (gas or electricity) at a relatively
slow rate, storing the heat for later use.
Electric The heating element for electric tank-type
water heaters is immersed directly into the water, allowing
energy to transfer from the element to the water fast and
effciently. They can be used for many applications ranging
from commercial and industrial to booster heaters for dish-
washing needs.
Gas Fired A gas-fred tank-type water heater uses
natural gas or propane to heat stored water.
Tankless Water Heaters
These water heaters heat the water as the water fows
through the device (demand based) and do not retain any
water internally, except for what is in the heat exchanger
coil. Tankless water heaters often have minimum fow
Consume Off-peak Power
One of a plumbing engineers responsibilities is to size the
domestic water heating equipment to meet the needs of the
buildings occupants in the most energy-effcient manner.
While using off-peak power to heat and circulate water does
not change the amount of Btu required, it does allow the
buildings owner and tenants to beneft from lower utility
costs. Power companies encourage their commercial cus-
tomers to purchase power during off-peak hours in hopes
of fattening or evening out the demand on their generating
equipment. Some utility companies not only offer lower
rates for electricity purchased during off-peak and semi-
peak periods, but in many instances also have no customer
demand charges. The plumbing engineer can obtain electric
rate schedules from the utility serving the site and observe
the off-peak periods to program the operation of domestic
water heating equipment. Typically, the highest demand for
hot water takes place when electrical costs are at their peak.
To account for this, the hot water system can maintain the
heated water at an elevated temperature, which is blended
A
N
N
U
A
L
E
N
E
R
G
Y
U
S
E
P
E
R
Y
E
A
R
(
1
0
6
B
T
U
)
V
O
L
U
M
E
U
S
E
D
P
E
R
D
A
Y
(
G
A
L
)
Chart allows user to estimate domestic hot water heating use in terms of water
temperature and faucet fow rate.
Source: Cassidy 1982.
Figure 7-1 Energy Savings from
Reduced Faucet Flow Rates
F
A
U
C
E
T
F
L
O
W
R
A
T
E
1
5
0
F
H
O
T
W
A
T
E
R
TEM
P
1
4
0
F
1
3
0
F
120F
110F
s
s
4 Read, Learn, Earn JUNE 2012
READ, LEARN, EARN: Energy and Resource Conservation in Plumbing Systems
Table 7-1 Energy Savings Chart for Steel Hot Water Pipes and Tanks
T
F (C) Pipe Size, in. (mm)
Hot Water Tanks,
Btu/h/ft
2
(kJ/h/m
2
)
(12.7)
(19.1)
1
(25.4)
1
(31.8)
1
(38.1)
2
(50.8)
2
(63.5)
with
Insulation
with out
Insulation
40 (4.4) 14 (48.44) 17 (58.8) 21 (72.7) 26 (90.0) 29 (100.3) 35 (121.1) 42 (145.3) 6 (68.1) 57 (647.3)
45 (7.2) 16 (55.36) 20 (69.2) 24 (83.0) 30 (103.8) 33 (114.2) 41 (141.9) 48 (166.1) 6 (68.1) 65 (738.2)
50 (10.0) 18 (62.28) 22 (76.1) 27 (93.4) 34 (117.6) 38 (131.5) 47 (162.6) 55 (190.3) 7 (79.5) 73 (829.1)
55 (12.8) 20 (69.20) 25 (86.5) 31 (107.3) 38 (131.5) 42 (145.3) 52 (179.9) 62 (214.5) 7 (79.5) 83 (942.6)
60 (13.6) 23 (79.58) 28 (96.9) 35 (121.1) 42 (145.3) 48 (166.1) 58 (200.7) 69 (238.7) 9 (102.2) 92 (1044.8)
65 (18.3) 25 (86.50) 31 (107.3) 38 (131.5) 47 (162.6) 53 (183.4) 65 (224.9) 77 (266.4) 9 (102.2) 102 (1158.4)
70 (21.1) 28 (96.88) 34 (117.6) 42 (145.3) 52 (179.9) 58 (200.7) 71 (245.7) 84 (290.6) 10 (113.6) 112 (1272.0)
75 (23.9) 30 (103.8) 36 (124.6) 46 (159.2) 56 (193.8) 64 (221.4) 78 (269.9) 91 (314.9) 11 (124.9) 122 (1385.6)
80 (26.7) 33 (114.2) 41 (141.9) 50 (173.0) 61 (211.1) 69 (238.7) 84 (290.6) 99 (342.5) 11 (124.9) 132 (1499.1)
85 (28.4) 36 (124.6) 44 (152.2) 54 (186.8) 67 (231.8) 74 (256.0) 91 (314.9) 107 (370.2) 12 (136.3) 142 (1612.7)
90 (32.2) 38 (131.5) 47 (162.6) 58 (200.7) 72 (249.1) 80 (276.8) 98 (339.1) 116 (401.4) 12 (136.3) 154 (1749.0)
95 (35.0) 42 (145.3) 51 (176.5) 62 (214.5) 77 (266.4) 86 (297.6) 105 (363.3) 124 (429.0) 14 (159.0) 164 (1862.5)
100 (37.8) 45 (155.7) 54 (186.8) 66 (228.4) 82 (283.7) 93 (321.8) 113 (391.0) 133 (460.2) 14 (159.0) 175 (1987.5)
105 (38.0) 47 (162.6) 58 (200.7) 72 (249.1) 87 (301.0) 98 (339.1) 120 (415.2) 141 (487.9) 15 (170.4) 187 (2123.8)
110 (43.0) 51 (176.5) 62 (214.5) 75 (259.5) 93 (321.8) 104 (359.8) 128 (442.9) 150 (519.0) 16 (181.7) 198 (2248.7)
115 (46.0) 54 (186.8) 65 (224.9) 80 (276.8) 98 (339.1) 110 (380.6) 135 (467.1) 159 (550.1) 16 (181.7) 210 (2385.0)
120 (49.0) 56 (193.8) 69 (238.7) 85 (294.1) 104 (359.8) 117 (404.8) 143 (494.8) 169 (584.7) 17 (193.1) 222 (2521.3)
Source: San Diego Gas & Electric Co.
Notes: 1. Savings are in Btu/h/linear ft. (kJ/h/linear m), unless otherwise indicated.
2. Figures are based on an assumption of 1 in. (25.4 mm) of insulation.
3. T = t
o
t
a
where t
o
= Hot water circulating temperature and t
a
= Air temperature surrounding piping system.
Table 7-2 Energy Savings Chart for Copper Hot Water Pipes
T
F (C)
Pipe Size, in. (mm)
(12.7)
(19.1)
1
(25.4)
1
(31.8)
1
(38.1)
2
(50.8)
2
(63.5)
3
(76.2)
40 (4.4) 8 (27.68) 12 (41.5) 14 (48.4) 17 (58.8) 20 (69.2) 25 (86.5) 30 (103.8) 35 (121.1)
45 (7.2) 10 (34.6) 13 (45.0) 16 (55.5) 20 (69.2) 23 (79.6) 29 (100.3) 35 (121.1) 40 (138.4)
50 (10.0) 12 (41.5) 15 (51.9) 19 (65.7) 23 (79.6) 26 (90.0) 33 (114.2) 40 (138.4) 46 (159.2)
55 (12.8) 13 (45.0) 17 (58.8) 21 (72.7) 26 (90.0) 30 (103.8) 38 (131.5) 45 (155.7) 52 (179.9)
60 (13.6) 15 (51.9) 20 (69.2) 24 (83.0) 29 (100.3) 34 (117.6) 42 (145.3) 51 (176.5) 58 (200.7)
65 (18.3) 16 (55.4) 21 (72.7) 27 (93.4) 32 (110.7) 37 (128.0) 47 (162.6) 56 (193.8) 65 (224.9)
70 (21.1) 18 (62.3) 24 (83.0) 30 (103.8) 35 (121.1) 41 (141.9) 52 (180.0) 62 (214.5) 71 (245.7)
75 (23.9) 20 (69.2) 26 (90.0) 33 (114.2) 39 (134.9) 44 (152.2) 56 (193.8) 67 (231.8) 76 (263.0)
80 (26.7) 21 (72.7) 28 (96.7) 35 (121.1) 42 (145.3) 49 (169.5) 61 (211.1) 73 (252.6) 85 (294.1)
85 (29.4) 22 (76.1) 31 (107.3) 38 (131.5) 45 (155.7) 53 (183.4) 66 (228.4) 79 (273.3) 92 (318.3)
90 (32.2) 24 (83.0) 33 (114.2) 41 (141.9) 49 (169.5) 57 (197.2) 71 (245.7) 85 (294.1) 99 (342.5)
95 (35.0) 26 (90.0) 36 (124.6) 44 (152.2) 53 (183.4) 61 (211.1) 76 (263.0) 91 (314.9) 106 (366.7)
100 (37.8) 28 (96.7) 38 (131.5) 48 (166.1) 57 (197.2) 65 (224.9) 82 (283.7) 98 (339.1) 113 (391.0)
105 (38.0) 30 (103.8) 41 (141.9) 51 (176.5) 60 (207.6) 70 (242.2) 87 (301.0) 104 (359.8) 121 (418.7)
110 (43.0) 32 (110.7) 43 (148.8) 54 (186.8) 65 (224.9) 74 (256.0) 93 (321.8) 111 (384.1) 128 (442.9)
115 (46.0) 34 (117.6) 46 (159.2) 57 (197.2) 68 (235.3) 78 (269.9) 98 (339.1) 118 (408.3) 136 (470.6)
120 (49.0) 36 (124.6) 49 (169.5) 61 (211.1) 72 (249.1) 83 (287.2) 104 (359.8) 125 (432.5) 144 (498.2)
Source: San Diego Gas & Electric Co.
Notes: 1. Savings are in Btu/h/linear ft (kJ/h/linear m).
2. Figures are based on an assumption of 1 in. (25.4 mm) of insulation.
3. T = t
o
t
a
where t
o
= Hot water circulating temperature and t
a
= Air temperature surrounding piping system.
Table 7-3 The Effect of Stopping Circulation
Operating
Temperature,
F (C)
Piping
Insulation
Thickness,
in. (mm)
Energy Conserved,
Btu/yr (kJ/yr)
140 (60) (12.7) 1428 10
6
(1506.5 10
6
)
125 (51.5) (12.7) 1153 10
6
(1216 10
6
)
110 (43) (12.7) 824 10
6
(869.3 10
6
)
140 (60) 1 (25.4) 934 10
6
(985.4 10
6
)
125 (51.5) 1 (25.4) 714 10
6
(753.3 10
6
)
110 (43) 1 (25.4) 522 10
6
(550.7 10
6
)
JUNE 2012 Read, Learn, Earn 5
requirements before the heater is activated, and this can
result in a gap between the cold water temperature and the
coolest warm water temperature that can be achieved with
a hot and cold water mix.
Electric Electric tankless water heaters consume large
amounts of energy when operating. This has relegated their
use to remote areas with low fxture counts and infrequent
use. They usually are installed near the point of use to mini-
mize pipe heat loss.
Gas Fired These heaters can be found in commercial,
industrial, and residential applications. They are typically
direct-vent exhaust and carry a very high rate of effciency.
Condensing Condensing gas water heaters recover the
heat created by the combustion gases. The recovered heat is
referred to as the latent heat of vaporization and is directed
back into the water, increasing the units effciency. A con-
densing water heater operates at approximately 95 percent
effciency compared to 8085 percent for a noncondensing
water heater. The condensate generated from a condensing
unit needs to be drained, but care must be taken to account
for its acidic nature. With a pH rating of approximately 5,
the condensate must be either diluted until it reaches an ac-
ceptable pH range or drained to a neutralization tank.
Steam Fired Steam-fred tankless water heaters gener-
ate hot water through the use of a heat exchanger. They are
used in hospitals, industrial plants, restaurants, apartment
houses, laundries, universities, and hotels, among other ap-
plications. They can be combined in parallel to meet high fow
requirements while requiring less space than comparable
tank-type units. The installation of a mixing valve is recom-
mended to ensure that steam does not enter the hot water
system in the event of a heat-exchanger breach.
Direct Fired These heaters are used in applications
where several hundred gallons of hot water are needed per
minute. These units use a direct exchange between the water
and combustion products produced by the burner assembly.
This process eliminates standby losses and can achieve op-
erating effciencies in excess of 98 percent.
ALTERNATIVE RESOURCES
As the consumption of fossil fuels increases, so does the
need to develop alternative fuel sources. One of these
sources is solar energy. Energy captured from sunlight can
be converted to power to heat domestic water. Other forms
of alternative energy are geothermal and solid wastes,
which have been used to heat water while reducing the load
placed on mainstream resources. The designer may choose
to use alternative energy resources for all or part of the
hot water system. This helps meet restrictions placed on
domestic water heating systems by energy codes in many
parts of the country.
Solar Energy
One of the most cost-effective ways to include renewable
technologies in a building is by incorporating solar hot water.
A typical residential solar water heating system reduces the
need for conventional water heating by about two-thirds. It
minimizes the expense of electricity or fossil fuel to heat the
water and reduces the associated environmental impacts.
Most solar water heating systems for buildings have two
main parts: a solar collector and a storage tank. The most
common collector used in solar hot water systems is the
fat-plate collector.
Solar water heaters use the sun to heat either water or
a heat-transfer fuid in the collector. Heated water then is
held in the storage tank ready for use, with a conventional
system providing additional heating as necessary. The tank
can be a modifed standard water heater, but it is usually
larger and very well insulated. Solar water heating systems
can be either active or passive, but the most common are
active systems.
Active solar water heaters rely on electric pumps and
controllers to circulate water or other heat-transfer fuids
through the collectors. Following are the three types of active
solar water heating systems:
1. Direct-circulation systems use pumps to circulate pres-
surized potable water directly through the collectors.
These systems are appropriate in areas that do not
freeze for long periods and do not have hard or acidic
water. These systems are not approved by the Solar
Rating and Certifcation Corp. (SRCC) if they use recir-
culation freeze protection (circulating warm tank water
during freeze conditions) because that requires electri-
cal power for the protection to be effective.
2. Indirect-circulation systems pump heat-transfer
fuids through collectors. Heat exchangers transfer
the heat from the fuid to the potable water. Some
indirect systems have overheat protection, which is a
means to protect the collector and the glycol fuid from
becoming super-heated when the load is low and the
intensity of incoming solar radiation is high. The two
most common indirect systems are:
Antifreeze:Teheattransferfuidisusuallyaglycol-wa-
termixturewiththeglycolconcentrationdependingon
theexpectedminimumtemperature.Teglycolisusually
food-gradepropyleneglycolbecauseitisnontoxic.
Drainback:Tissystemusespumpstocirculatewater
throughthecollectors.Tewaterinthecollectorloop
drainsintoareservoirtankwhenthepumpsstop.Tis
makesdrainbacksystemsagoodchoiceincoldercli-
mates.Drainbacksystemsmustbecarefullyinstalledto
ensurethatthepipingalwaysslopesdownward,sothat
thewaterwillcompletelydrainfromthepiping.Tiscan
bedifculttoachieveinsomecircumstances.
3. Passive solar water heaters rely on gravity and the
tendency for water to naturally circulate as it is heated.
Because they contain no electrical components, passive
systems are generally more reliable, easier to maintain,
and possibly have a longer work life than active sys-
tems. The two most popular types of passive systems
follow:
Integral-collectorstoragesystemsconsistofoneor
morestoragetanksplacedinaninsulatedboxwitha
glazedsidefacingthesun.Tesesolarcollectorsare
suitedforareaswheretemperaturesrarelygobelow
freezing.Teyarealsogoodinhouseholdswithsignif-
cantdaytimeandeveninghotwaterneeds,butthey
donotworkwellinhouseholdswithpredominantly
6 Read, Learn, Earn JUNE 2012
READ, LEARN, EARN: Energy and Resource Conservation in Plumbing Systems
morningdrawsbecausetheylosemostofthecollected
energyovernight.
Termosyphonsystemsareaneconomicalandreliable
choice,especiallyinnewhomes.Tesesystemsrelyon
thenaturalconvectionofwarmwaterrisingtocirculate
waterthroughthecollectorsandtothetank(located
abovethecollector).Aswaterinthesolarcollector
heats,itbecomeslighterandrisesnaturallyintothe
tankabove.Meanwhile,thecoolerwaterfowsdown
thepipestothebottomofthecollector,enhancingthe
circulation.Somemanufacturersplacethestoragetank
inthehousesattic,concealingitfromview.Indirect
thermosyphons(thatuseaglycolfuidinthecollector
loop)canbeinstalledinfreeze-proneclimatesifthe
pipingintheunconditionedspaceisadequatelypro-
tected.
Solid-waste Disposal Energy
Solid-waste collection and disposal systems produce vari-
ous gases during decomposition. One of these is methane,
which can be recovered and burned to produce heat. A
second source of methane is leachate evaporation sys-
tems in landfll closures. Lastly, solid-waste incineration
systems constructed to stringent pollution-control rules
and regulations are another source of methane. These
systems potentially can provide large volumes of steam
and/or domestic hot water.
The use of these alternate energy sources should be
within reasonable proximity to the resource. Typical ap-
plications include industrial plants with large volumes of
burnable materials such as trash, paper, scrap wood, and
plastics. A solid-waste incinerator system typically consists
of a waste-disposal plant with a conveyer, loading system,
boiler, ash-disposal equipment, heat exchanger, insulated
piping, circulating pump, and controls.
Geothermal Energy
Geothermal energy is heat from the earth. In states where
this form of energy is believed to be available at reasonable
depths, the U.S. Department of Energy (DOE) is supporting
various state energy commissions in their funding of geother-
mal assessment programs. The temperature of the available
liquid or gas (created when water fows through heated,
permeable rock) and the cost of retrieval dictate the viability
of geothermal energy. Some geothermal energy uses include
steam for the generation of electricity, building domestic hot
water systems with a minimum temperature of 150F, and
space and water heating needs for industrial parks.
Three prime areas of concern must be addressed when
planning and developing geothermal energy:
1. Competitive institutional processes
2. Adequate temperature and fow rate
3. Termalloadstomakethesystemeconomicallyviable
A geothermal energy system typically consists of pro-
duction and disposal wells, water-to-water heat exchangers
(usually shell-and-tube type and two are requiredone
for operation while the other is being cleaned of deposits),
insulated piping, a circulating pump, and a control system.
The plumbing engineer should consult with the state energy
offce (Department of Energy or the Geothermal Resources
Council) for resource information to apply this high-capital,
low operating cost, alternate energy source.
Heat Recovery
Heat recovery is the capture and reuse of energy that nor-
mally would be lost from a facility. It could be in the form of
a liquid or a gas. Common waste heat sources are:
Heatrejectedfromair-conditioningandcommercial
refrigeration processes
Heatreclaimedfromsteamcondensate
Heatgeneratedbycogenerationplants
Heatpumpsandheatreclamationsystems
Heatfromwastewater
When considering heat recovery, it is important to de-
termine if the hot water demand justifes the equipment and
maintenance costs and if the heat recovered is suffcient to
serve as a heat source. Facilities that typically have the proper
blend of demand and waste heat are hospitals, military bases,
and industrial facilities.
Air-conditioning and Commercial Refrigeration
Systems with air- or water-cooled or evaporative condensers
reject heat from air-conditioning and refrigeration systems
that can be reclaimed. Within the refrigerant cycle is a con-
denser that rejects heat while an evaporator creates a cooling
effect. For example, for every 1 Btuh of cooling effect pro-
duced by a 40F evaporator, a 105F condensing unit rejects
1.15 Btuh of heat. Systems with an air-cooled or evaporative
condensor can be supplemented with a heat exchanger in the
compressors hot gas discharge line to capture the rejected
heat. (Refer to Figure 7-2.)
Systems with water-cooled condensers can be supple-
mented with a heat exchanger in the hot water return line
from the condenser to the cooling tower. (Refer to Figure 7-3.)
System effciency can be improved by providing a storage
tank with a tube bundle. (Refer to Figure 7-4.)
An advantage of the system shown in Figure 7-4 is that
simultaneous use of the domestic water and refrigeration
systems does not need to occur for heat recovery. Another
advantage of the system shown in Figure 7-4 is when an insuf-
fcient amount of heat is rejected, a backup water heater can
be used to bring the water in the storage tank to the proper
design temperature. The backup heater can operate on fossil
fuel, electricity, or steam or may be ftted with a tube bundle
utilizing hot water.
Steam Condensate When steam is used as a source
for space heating, water heating, or process work, steam
condensate generally is produced. The heat content of the
condensate can be captured and reused for heating with the
use of a heat exchanger. Laundries are a prime example of
facilities where heat reclaimed from steam condensate can
be put to use in heat recovery. It is essential to select a sys-
tem with adequate storage to compensate for fuctuations
in the condensate and domestic water fow. When deciding
whether to capture and reuse steam condensate, remember
that energy will not be saved if the boiler used to raise the
JUNE 2012 Read, Learn, Earn 7
Figure 7-2 Refrigeration Waste Heat Recovery
Figure 7-3 Condenser Water Heat Recovery
8 Read, Learn, Earn JUNE 2012
READ, LEARN, EARN: Energy and Resource Conservation in Plumbing Systems
Figure 7-4 Condenser Water Heat Recovery with Storage Tank
Figure 7-5 Wastewater Heat Recovery
JUNE 2012 Read, Learn, Earn 9
temperature of the returned condensate is less effcient than
the primary water heater.
Cogeneration Plants The heat produced as a by-
product of generating electricity from reciprocating engines
or gas turbines can be reclaimed from the cooling systems
and exhaust gases by using a waste heat boiler and heat
exchanger. The heat then can be used to produce steam
or medium-temperature water. To be economically viable,
most systems must have a year-round thermal heat load.
Reheating makeup water and maintaining temperature in
a domestic hot water system are excellent ways to maintain
high overall thermal effciencies.
Heat Pumps In todays buildings where computer rooms
are continuously generating heat and industrial plants are
producing waste heat, heat pumps can be used to transfer this
heat to the domestic hot water systems, resulting in energy
conservation. Either direct-expansion or chilled-water heat
pumps can be used to transfer heat through the refrigeration
process from the surrounding air to a water storage tank. The
mechanics of this system are to extract heat from a warm
environment directly, either through a heat exchanger or
cooling coil.
Drainline Heat Reclaim Systems It has been esti-
mated that 8090 percent of all hot water energy is wasted.
The U.S. DOE estimates this amount of energy to be 235
billion kWh a year. One method of recouping some of this
energy is using a drainline heat reclaim system. This device
can be a passive or active piece of equipment installed in
the wastewater drainline of a building. Passive devices use
a copper coil wrapped around a vertical portion of a waste
line. Domestic water is fed through the copper coil to the hot
water heater. As hot water is drained, heat is transferred
from the drainline to the incoming domestic water. It has
been estimated that these exchangers have an operating ef-
fciency of up to 60 percent and can raise the incoming water
temperature by as much as 36F. Active systems utilize a
wastewater circulating pump in conjunction with the heat
exchanger. This system is shown in Figure 7-5.
DESIGN TECHNIQUES FOR
WATER MANAGEMENT
Conserving water benefts both the buildings owner and the
local municipality. The owner saves by having lower utility costs,
while the municipality saves resources by having to treat and
circulate less water and wastewater. To realize these savings,
the plumbing engineer must provide designs that reduce water
consumption without compromising a fxtures operation.
For a water management program to be successful in
renovation projects, it is important to frst establish the
buildings current water consumption. The U.S. DOE has
developed eight steps to make a successful water manage-
ment plan:
1. Gather information
2. Conductacomprehensivefacilitysurvey
3. Exploreandevaluatewatermanagementoptions
4. Conductlife-cyclecostanalysisandexplorefnancingop-
tions
5. Developawatermanagementplanandworkschedule
6. Informbuildingoccupantsaboutwatermanagement
7. Implementthewatermanagementplan
8. Monitorthewatermanagementplan
For more information, refer to the U.S. DOEs Greening
Federal Facilities Guide.
Some design techniques previously mentioned are:
Eliminatefaucetandpipeleaks
Reducefxturefowrates
Other methods of unique water management are:
Alternatesourcesoffreshwater
Reclaimedandgraywater
Eliminate Faucet and Pipe Leaks
Similar to hot water conservation, this is one of the easiest
and frst actions that should be taken. Leaks in both the
cold and hot water piping should be repaired as well as any
leaking faucets. This will reduce the amount of water being
wasted and avoid more expensive repairs later.
Reduce Fixture Flow Rates
Replacing old plumbing fxtures can save huge quantities of
water. The standards established for water consumption by
the EPAct restrict showerheads to 2.5 gpm (9.5 lpm), urinals
to 1 gpf (3.8 lpf), faucets to 2.2 gpm (8.3 lpm) at 60 psi (410
kPa), and toilets to 1.6 gpf (6 lpf) at 80 psi (550 kPa).
Alternate Sources of Fresh Water
Rainwater harvesting is the collection, storage, treat-
ment, and use of rainwater. Harvested water can be used
for irrigation, nonpotable, and potable uses. A rainwater
harvesting system typically starts with a catch area that
collects rainwater, usually on a buildings roof. To ensure
that potential contaminants and pollutants do not enter
the systems storage tank, a wash system is installed
that diverts the initial portion of the rainfall away from
the storage tank while cleaning the catch area. A screen
usually is installed in the catch area to keep out debris.
Piping routes the collected rainwater to a storage tank,
which can be located indoors, outdoors, aboveground, or
underground. It is important to provide a lid on the storage
tank to keep light out to discourage algae growth. Water
typically is delivered to the building through the use of
a domestic water booster pump system, and fnal water
treatment may be needed depending on the application
and quality of water collected.
Reclaimed and Graywater
Reclaimed water and graywater collection systems can be
used to reduce the amount of domestic water consumed by
a building. Graywater typically is collected from showers,
tubs, lavatories, washing machines, and drinking fountains.
It contains a minimal amount of contamination and is re-
used in certain landscape applications such as subsurface
irrigation of lawns, fowers, trees, and shrubs, but it should
not be used for vegetable gardens because of the potential
absorption of cleaning and washing chemicals.
Similar to rainwater harvesting, graywater is collected,
stored, and fltered prior to use. A graywater storage contain-
er should be ftted with overfow protection that is connected
10 Read, Learn, Earn JUNE 2012
READ, LEARN, EARN: Energy and Resource Conservation in Plumbing Systems
to the sanitary sewer system in the event the amount of water
collected is more than the amount of water being consumed,
a distribution pipe becomes clogged, or collected water is not
used in a timely manner.
Wastewater treatment plants are constructed to provide
reclaimed or recycled water to buildings through a second
municipal water system where two water lines enter a build-
ing. One line is used to deliver potable water for domestic use,
and a second provides treated wastewater that can be used for
nonpotable applications such as landscape irrigation, cooling
tower makeup, toilet fushing, and fre protection.
WATER MANAGEMENT EQUIPMENT
The goal of effective water management is to reduce water
consumption without compromising the performance of
equipment and fxtures. Replacing or retroftting water clos-
ets, urinals, showerheads, and faucets with low-fow versions
can considerably lower a buildings water consumption.
Water Closets
Americans fush about 4.8 billion gallons (18.2 billion liters)
of water down toilets each day, according to the U.S. Envi-
ronmental Protection Agency. According to the Plumbing
Foundation, replacing all existing toilets with 1.6-gpf (6-lpf)
ultra-low-flow models would save almost 5,500 gallons
(25,000 liters) of water per person each year. A widespread
toilet replacement program in New York City apartment
buildings found an average 29 percent reduction in total
water use for the buildings studied. The entire program, in
which 1.3 million toilets were replaced, is estimated to be sav-
ing 6080 million gallons (230300 million liters) per day.
Ultra-low-fow water closets consume 1.6 gpf (6 lpf) and
are available in three different classifcations:
1. Tank type
2. Flush valve
3. Specialty
While the problems associated with ultra-low-fow toilets
when they frst became available have been corrected, some
low-cost models continue to exhibit poor performance.
Tank Type Water is drained from this water closet by
gravity and is most commonly used in residential applica-
tions. Prior to ultra-low-fow models, these fxtures consumed
3.5 gpf. A low-cost method of conserving water in these earlier
models and in todays ultra-low-fow version is using a refll
diverter. When a tank-type water closet is fushed, water
starts to refll the tank as it is emptying. The time elapsed
between the open and closed position of the fapper allows
excess water to fow through the bowl, into the bowl, and
consequently to the drain. While reflling the tank, this water
is wasted. A diverter keeps this water in the tank, saving
to 1 gallon when installed on older toilets and gallon on
ultra-low-fow models.
Flush Valve Flush valve water closets use the build-
ings water pressure to exert a force when operating. They
typically require 25 to 40 pounds per square inch gauge
(psig) to operate and are most commonly used in commercial
buildings. Older models can be retroftted by adjusting the
fush valve, but care must be taken to not overly constrain
the valve, which could cause it to malfunction. Early closure
devices also can be used to cause the fush valve to stop the
fow of water sooner than normal, limiting the amount of
water discharged.
Specialty Some specialty water closets are pressure-as-
sisted tank type, dual fush, and composting. Pressure-assisted
tank-type water closets can be used in applications where it
is desired to use a gravity tank-type water closet, but there is
concern about fushing performance. When water conserva-
tion beyond ultra-low-fow is desired, dual-fush water closets
can be used. These have two fush settings: one for normal
operation to fush solids and a second, reduced amount for
liquids, saving approximately 1 gpf. Composting systems are
high-capital ventures that require a lot of space and typically
are used in unique locations where no water supply exists.
They are popular choices in parks and camping facilities.
Composting toilets are gaining acceptance in other areas of
the world for mainstream use in households.
High-effciency Toilets (HET) The HET is defned as
a fxture that fushes at 20 percent below the 1.6 gpf ultra-
low-fow toilet. This includes dual-fush technology.
Urinals
Ultra-low-fow urinals consume 1 gpf, but water conservation
methods can go beyond this level. Flush valves that consume
as low as 1 pint per fush have been employed with success.
Waterless urinals that do not consume any water also are
being used. Waterless urinals utilize a specially designed
trap insert that prevent odors from passing through the
urinal trap. Traps can be mechanical or flled with a liquid
sealant. The lighter-than-water sealant foats on top of the
urine collected in the U-bend. The cartridge and/or sealant
must be replaced periodically. A waterless urinal could save
anywhere between 15,000 and 45,000 gallons (approximately
between 56,800 and 170,000 liters) of water per urinal per
year. Waterless urinals can be installed in high-traffc facili-
ties and in situations where providing a water supply may
be diffcult or where water conservation is desired.
Showerheads
The 1992 EPAct set the maximum fow rates for showerheads
and faucets at 2.5 gpm. Prior to this act, showerhead fow
rates were between 3 and 7 gpm. Water-conserving shower-
heads incorporate a more narrow spray jet and introduce a
greater volume of air when compared to conventional heads.
The use of fow restrictors in conventional showerheads is not
recommended because they typically restrict the showerhead
too much, providing poor water pressure from the head.
Faucets
Faucets manufactured after 1993 consume no more than 2.5
gpm at 80 psig, meeting the requirements of the 1992 EPAct.
Replacing the faucets tip with an aerator, which mixes air
into the faucets discharge and reduces its fow rate to 2.5
gpm, can retroft older faucets, which consume between 3
and 5 gpm.
With manual valve faucets, replacing the screw-in tip
of the faucet is all that typically is necessary to reduce wa-
ter use. While faucet aerators that mix air into the water
stream are commonly used in residential faucets, they are
specifcally prohibited in health facilities because they can
JUNE 2012 Read, Learn, Earn 11
harbor germs and pathogens. Instead, these facilities use
nonaerating, low-fow faucet tips (including those providing
a smooth, laminar stream of water). Choose 2.2- to 2.5-gpm
(8.3- to 9.5-lpm) devices for kitchens. In washrooms, 0.5- to
1.25-gpm (1.9- to 4.7-lpm) models often prove adequate for
personal washing purposes. Metered (metered valve or elec-
tronic sensor) faucets deliver a preset amount of water and
then shut off. For water management purposes, the preset
amount of water can be reduced by adjusting the fow valve.
The Americans with Disabilities Act requires a 10-second
minimum on-cycle time. To maximize water savings, choose
the lowest-water-use modelstypically 0.5 gpm (1.9 lpm).
GLOSSARY
British thermal unit (Btu) A heat unit equal to the
amount of heat required to raise 1 pound of water 1 degree
Fahrenheit.
Coeffcient of performance (COP) The ratio of the rate of
heat removal to the rate of energy input, in consistent units,
generally relating to a refrigeration system under designated
operating conditions.
Condenser A heat exchanger that removes heat from a
vapor, changing it to its liquid state.
Delta T (T) Temperature differential.
Domestic water heating Supply of hot water for domestic
or commercial purposes other than comfort heating.
Domestic water heating demand The maximum design
rate of energy withdrawal from a domestic water heating
system in a specifed period of time.
Effciency, thermal (overall system) The ratio of useful
energy at the point of ultimate use to the energy input.
Energy The force required for doing work.
Energy, non-depletable Energy derived from incoming
solar radiation and phenomena resulting therefrom, includ-
ing wind, waves, tides, and lake or pond thermal differences,
and energy derived from the internal heat of the earth
(geothermal)including nocturnal thermal exchanges.
Energy, recovered A by-product of energy used in a pri-
mary system that otherwise would be wasted from an energy
utilization system.
Heat, latent The quantity of heat required to effect a
change in state.
Heat, sensible Heat that results in a temperature change
but not a change in state.
Life-cycle cost The cost of the equipment over its entire
life, including operating and maintenance costs.
Makeup Water supplied to a system to replace that lost by
blowdown, leakage, evaporation, etc.
Solar energy source Source of chemical, thermal, or elec-
trical energy derived from the conversion of incident solar
radiation.
System An arrangement of components (including controls,
accessories, interconnecting means, and terminal elements)
by which energy is transformed to perform a specifc func-
tion.
Terminal element The means by which the transformed
energy from a system is ultimately delivered.
RESOURCES
1. Cassidy,VictorM.1982.Energysavingandtheplumb-
ingsystem.Specifying Engineering(February).
2. SanDiegoGas&ElectricCompany.CommercialEnergy
ConservationManual.
3. U.S.DepartmentofEnergy:energy.gov.
12 Read, Learn, Earn JUNE 2012
READ, LEARN, EARN: Energy and Resource Conservation in Plumbing Systems
CE Questions
Energy and Resource Conservation in Plumbing Systems
(CEU 188)
What was the frst major piece of 1.
legislation addressing federal energy
management?
EPAct a.
EPCA b.
RCRA c.
FEMIA d.
The domestic hot water system in a 2.
new building should be set at ________
according to many energy codes.
140F a.
120F b.
110F c.
105F d.
How much hot water is needed to provide 3.
0.084 L/s of 43C mixed water with 68.5C
hot water and 23.9C cold water?
0.037 L/s a.
0.059 L/s b.
56 gph c.
none of the above d.
Thermal insulation is benefcial because it 4.
________.
retards heat loss a.
reduces noise b.
controls condensation c.
all of the above d.
Delta T is calculated by subtracting the 5.
air temperature surrounding the piping
system from ________.
hot water circulating temperature a.
length of pipe b.
thickness of insulation c.
diameter of pipe d.
A condensing water heater operates at 6.
approximately ________ effciency.
80 percent a.
85 percent b.
90 percent c.
95 percent d.
Readingthearticleandcompletingtheformwill
allowyoutoapplytoASPEforCEUcredit.Ifyou
earnagradeof90percentorhigheronthetest,
youwillbenotifiedthatyouhavelogged0.1
CEU,whichcanbeappliedtowardCPDrenewal
ornumerousregulatory-agencyCEprograms.
(Pleasenotethatitisyourresponsibilitytodeter-
minetheacceptancepolicyofaparticularagency.)
CEUinformationwillbekeptonfleattheASPE
ofceforthreeyears.
ASPE Continuing Education Application Form
This form is valid up to one year from date of publication. Expiration date: Continuing education credit will be given for this examination
through June 30, 2013. Applications received after that date will not be processed.
Submit this form with payment via mail (ASPE Read, Learn, Earn, 2980 S. River Road, Des Plaines, IL 60018), fax (847-296-2963), or email
aspeeducation@aspe.org.
Please print or type; this information will be used to process your credits.
Name ______________________________________________________________________ ASPE Membership No. ______________
Organization ___________________________________________________ Daytime telephone _____________________________
Billing Address ________________________________________________________________________________________________
City _________________________________________ State/Province ________________________ Zip ______________________
E-mail _______________________________________________________________________ Fax ____________________________
PE State _____________________________________________ PE No. _________________________________________________
Notice for North Carolina Professional Engineers: State regulations for registered PEs in North Carolina now require you to complete ASPEs online CEU validation form
to be eligible for continuing education credits. After successfully completing this quiz, just visit ASPEs CEU Validation Center at aspe.org/CEUValidationCenter.
I certify that I have read the article indicated
above.
Signature
Payment:
Member: Free
Nonmember: Each examination: $35
Personal Check (payable to ASPE)
Business or government check
DiscoverCard VISA MasterCard AMEX
If rebilling of a credit card charge is necessary, a $25
processing fee will be charged.
ASPE is hereby authorized to charge my CE
examination fee to my credit card
Account Number
Expiration date
Signature
Cardholders name (Please print)
What type of water heater is best when 7.
several hundred gallons of hot water are
needed per minute?
tankless a.
steam fred b.
direct fred c.
condensing d.
________ solar water heating systems 8.
rely on the natural convection of warm
water rising to circulate water through
the collectors and to the tank.
drainback a.
thermosyphon b.
direct-circulation c.
indirect-circulation d.
Waste heat can be recovered from 9.
________.
steam condensate a.
wastewater b.
heat pumps c.
all of the above d.
Approximately how much of all hot 10.
water energy is wasted?
7080 percent a.
8090 percent b.
95 percent c.
none of the above d.
A high-effciency toilet fushes at _______ 11.
below the 1.6 gpf toilet.
5 percent a.
10 percent b.
15 percent c.
20 percent d.
________ is the quantity of heat required 12.
to effect a change in state.
recovered energy a.
sensible heat b.
latent heat c.
British thermal unit d.
Circle the correct answers below.
JUNE 2012 Read, Learn, Earn 13
C
E
U
1
8
9
Vent Systems
Continuing Education from the
American Society of Plumbing Engineers
JULY 2012
ASPE.ORG/ReadLearnEarn
Flow of air is the primary consideration in the design of a venting
system for the ventilation of the piping and protection of the f xture
trap seals of a sanitary drainage system. Since air is of such primary
importance, it is essential that the plumbing engineer be familiar with
certain physical characteristics that are pertinent to its behavior in a
plumbing system.
Density of any substance is its mass per unit volume. Te density of
air is its weight in pounds per cubic foot of volume. Te density of air
is afected by temperature, moisture content, and pressure. Te den-
sity of standard air is taken at atmospheric pressure and 68.4F. It is
equal to 0.075 lbm/ft3. With a rise in temperature, the density of air
decreases and with a lowering of temperature its density increases. Te
moisture content of air in the plumbing system has a negligible efect
on its density and can be disregarded in all calculations. Pressure has
an appreciable efect; the higher the pressure the greater the density,
and the lower the pressure the less the density.
Specif c Weight of a f uid is not an absolute property, but depends
upon the local gravitational f eld (gravitational acceleration on earth is
g=32.2 ft/sec2) and the properties of the f uid itself. Commonly called
density when concerning gravitational force, the numerical value of
specif c weight (lbf/ft3) is equal to density (lbm/ft3).
Elasticity is the ability of a substance to assume its original character-
istics after the removal of a force that has been applied. Air is a perfectly
elastic substance. From the scientif c def nition of elasticity it becomes
clear that a rubber band is really a very inelastic material. If a weight is
suspended from a rubber band and left for a few hours, then the weight
is removed, the rubber band will spring back, but def nitely not to its
original length. If a force is applied to air, the force can be applied for
days or years, and when it is removed, the air will return exactly to its
original condition.
Air is compressible. Tere is an increase in pressure when air is com-
pressed. In the plumbing system, only an extremely small change in
pressure can be tolerated. For a pressure of 1 in. of water column (0.036
psi), the volume of air will be compressed by 1400 of its original volume.
Assuming an original volume of 400 ft3 of air at atmospheric pressure
and the application of a pressure of 1 in. of water column, the air will
be compressed by 400 1400 = 1 ft3. It is obvious that a comparatively
small change in volume can very easily cause the accepted design limi-
tation of 1 in. of pressure to be exceeded with the consequent danger
of destroying the trap seals. Te vent piping must be designed to permit
the air to f ow freely without compression or expansion except for the
small amount necessary to overcome friction.
Static Head
Static head is the pressure exerted at any point by the weight of the
substance above that point. Te pressure can be stated in feet of the
substance, i.e., when the substance is water the static head is 100 ft of
water, or if the substance is air, 100 ft of air. To convert from feet of head
to pounds-force per square inch:
(8-1)
p = h/144 and h = 144p/
where p = Pressure, lbf./in
2
= Specifc weight of substance, lbf/ft
3
h = Static head, ft
Pneumatic effectS in Sanitary SyStemS
As water fows in contact with air in vertical or horizontal piping, there
is friction between the air and water. Te frictional efect causes the air
to be dragged along with the water and at practically the same veloc-
ity as the water. When the cross-sectional area of the water occupy-
ing the pipe is suddenly increased, such as at the hydraulic jump or
where a branch discharges into the stack, the air passage is constricted.
Tis constriction acts exactly the same as a stoppage or a blockage to
the fow of air. Tis causes a buildup of pressure, the highest pressure
occurring at the constriction and diminishing upstream. It is for this
reason that excessive pressure usually develops at the lower foors of a
building and at ofsets of the stack. It is important to always be aware
that protection from the entry of sewer gases is aforded by the 2-in.
trap seal, and the design of plumbing systems must be such as to main-
tain pressure variations within 1 in. column of water.
rate of flow from outletS
Te velocity at which air fows out of an outlet to the atmosphere (at the
roof terminal of a stack) is due to the total pressure available in the vent
pipe at the outlet. Tis pressure is the fow pressure, which is equal to
the static pressure less the pressure lost in friction. Te maximum rate
of discharge in practice is expressed as:
(8-2)
q
D
= c
D
q
1
where q
D
= Actual quantity of discharge, gpm
q
1
= Ideal quantity of discharge, gpm
c
D
= Coefcient of discharge
Utilizing the formula q = AV and substituting,
(8-3)
q
D
= c
D
(2.448 d
O
2
V
1
)
where d
O
= Outlet diameter, in.
V
1
= Ideal velocity, fps
2gh Velocity is equal to
_______
, where g = acceleration due to gravity and h =
height (or head) of air column.
2gh
(8-4)
q
D
= c
D
(2.448 d
O
2
_______
)
h
(8-5)
= c
D
(19.65 d
O
2
___
)
Using 0.67 as an acceptable coefcient of discharge, per Equation 6-1,
q
D
= 13.17 d
O
2
h
Reprinted from Engineered Plumbing Design II. 2004, American Society of Plumbing Engineers.
Note: In determining your answers to the CE questions, use only the material presented in the corresponding continuing education
article. Using information from other materials may result in a wrong answer.
2 Read, Learn, Earn JULY 2012
read, learn, earn
Static PreSSure of air
Te design criterion of maintaining pneumatic pressure fuctuations
within l in. of water column is constantly stressed throughout this
book. It should prove interesting to state this pressure in terms of an
equivalent column of air. Te formula for any substance is, per Equa-
tion 8-1:
P = h/144
then
(8-6)
P =
W
h
W
/144 =
A
h
A
/144
where
W
= Specifc weight of water, lbf/ft
3
h
W
= Static head of water, ft
A
= Specifc weight of air, lbf/ft
3
h
A
= Static head of air, ft
Transposing and using 1 in. of water column,
h
A
W
h
W
(62.408) (1/12)
= _____ = ________________
A
0.07512 (at 70 F.)
h
A
= 69.23 ft of air column
A column of air 69.23 ft will exert the same pressure as a column of
water 1 in. high. Stated another way, a static head of 1 in. of water will
support a column of air 69.23 ft high.
Te rate of discharge from a vent outlet can now be determined when
the pressure at the outlet is 1 in. of water or 69.23 ft of air.
q
D
= 13.17 d
O
2
h
= 13.17 d
O
2
(69.23)
= (13.17) (8.32) d
O
2
= 109.57 d
O
2
Te gallons per minute (cubic feet per minute) discharge rate for var-
ious diameters of vent pipe at a fow pressure of 1 in. of water column
is given in Table 8-1.
Table 81 Discharge Rates of Air
(1 Inch Water Pressure)
Outlet Diam,
d
O
inches
Air Discharge,
q
D
gpm (cfm)
2 438.3 (58.6)
2 684.8 (91.5)
3 986.1 (131.8)
4 1753.0 (234.3)
5 2739.0 (366.1)
friction Head loSS
When air fows in a pipe there is a pressure loss which occurs due to
the friction between the air and pipe wall. Tis loss of pressure can be
expressed by the Darcy formula:
(8-7)
h = f L V
2
D2g
where h = friction head loss, ft. of air column
f = coefcient of friction
L = length of pipe, ft.
D = diameter of pipe, ft.
V = velocity of air, ft/sec
g = gravitational acceleration 32.2 ft./sec
2
air flow in StackS
Te complete venting of a sanitary drainage system is very compli-
cated as evidenced by the variety of vents employed. Tere are so many
variables that produce positive and negative pneumatic pressure fuc-
tuations that it is not feasible to prepare tables of vent sizing for each
particular design. Recognizing this, authorities base the formulation
of venting tables for vent stacks and horizontal branches on the worst
conditions that may reasonably be expected. To determine the maxi-
mum lengths and minimum diameters for vent stacks it would be valu-
able to review the conditions of fow in the drainage stack.
At maximum design fow, the water fows down the stack as a sheet
of water occupying 724 of the cross-sectional area of the stack. Te
remaining 1724 is occupied by a core of air. As the water falls down
the stack, it exerts a frictional drag on the core of air and as this air is
dragged down it must be replaced by an equivalent quantity of air so
as not to develop negative pressures in excess of 1 in. of water. Tis is
accomplished by extending the soil stack through the roof so that air
may enter the stack to replenish the air being pulled down the stack.
Tis is why stacks must be extended full size through the roof and also
why soil stacks may not be reduced in size even though the load is less
on the upper portions of the stack than it is at the lower portions. Any
restriction in the size before terminating at the atmosphere would
cause violent pressure fuctuations.
As the water fows down the stack and enters the horizontal drain
there is a severe restriction to the fow of air as the hydraulic jump
occurs. Te air is compressed and pressure buildup may become very
high. A vent stack is provided in this area of high pressure to relieve
the pressure by providing an avenue for the fow of air. Obviously, the
vent stack must be large enough to permit the maximum quantity of
air dragged down the drainage stack to discharge through it and to the
atmosphere without exceeding 1 in. of water fuctuation Te rate of
air discharge that must be accommodated for various sizes of drainage
stacks fowing at design capacity is tabulated in Table 8-2.
Table 82 Air Required by Attendant Vent
Stacks
(Drainage Stack Flowing 7/24 Full)
Diameter
of Drainage
Stack, inches
Water Flow,
gpm
Air Flow,
gpm (cfm)
2 23.5 57.1 (7.6)
3 70 170.1 (22.7)
4 145 352.4 (47.1)
5 270 656.1 (87.7)
6 435 1057.1
(141.3)
8 920 2235.6
(298.9)
10 1650 4009.5 (536)
12 2650 6439.5
(860.8)
air flow in Horizontal drainS
It is assumed that the drainage branch fows half full at design condi-
tions and the air in the upper half of the pipe is fowing at the same
velocity and capacity. Table 8-3 tabulates these values for various
slopes of drain.
JULY 2012 Read, Learn, Earn 3
Under conditions of natural draft, the rate of fow will be just great
enough to overcome losses due to friction.
Vent StackS
Every drainage stack should be extended full size through the roof. Te
pipe from the topmost drainage branch connection through the roof to
atmosphere is called the vent extension. Te vent extension provides
the air that is dragged down the stack and also provides means for the
gravity circulation of air throughout the system. Vent extensions may be
connected with the vent stack before extending through the roof or may
be connected together with other vent extensions or vent stacks in a vent
header and the header extended through the roof as a single pipe.
Every drainage stack should have an attendant vent stack. Te pur-
pose of installing a vent stack is to prevent the development of exces-
sive pressures in the lower regions of the drainage stack by relieving
the air as rapidly as it is carried down by the discharge of the drainage
stack. Te most efective location for the vent stack is below all drainage
branch connections and preferably at the top of the horizontal drain
immediately adjacent to the stack base ftting. It is at this location that
pressure is at its maximum and the danger of closure due to fouling is
at its minimum. Figure 8-1 illustrates acceptable methods of vent stack
connections.
Table 83 Rate of Air In Horizontal
Drains
Diameter of
Drain, inches
Slope, inches
per foot
Rate of Flow,
gpm (cfm)
1 6.0 (.80)
2 8.8 (1.2)
2 15.5 (2.1)
3 25.5 (3.4)
4
1
/8 38.0 (5.1)
5
1
/8 69.0 (9.2)
6
1
/8 112.0 (15)
8
1
/8 240.0 (32.1)
PermiSSible lengtH of Vent PiPe
Te maximum length of vent piping, for any particular size with a pres-
sure drop of 1 in. of water, is established by computing the pressure
loss for various rates of fow in vents of various diameters. Combining
Darcys pipe friction formula (Equation 8-7) and the fow for-
mula, and converting the terms of the equations to units gener-
ally used in plumbing:
h = f L V
2
D2g
(8-8)
q = 2.448 d
2
V
(8-9)
V = q
2.448d
2
Substituting V in the Darcy equation,
h = f Lq
2
(d/12)(64.4)(2.448)
2
(d)
4
Solving for L,
(8-10)
L = h d
5
= 2226 d
5
0.013109 f q
2
f q
2
where L = Length of pipe, ft
d = Diameter of pipe, in.
f = Coefcient of friction
q = Quantity rate of fow, gpm
graVity circulation
Te principle of gravity circulation of air is utilized to keep the
entire sanitary system free of foul odors and the growth of slime
and fungi. Te circulation is induced by the diference in head
(pressure) between outdoor air and the air in the vent piping.
Tis diference of head is due to the diference in temperature,
and thus the diference in density, of each and the height of the
air column in the vent piping. Te cool air, being more dense,
tends to displace the less dense air of the system and circulation
of the air is induced. Te formula is
H = 0.1925(
O
1
) H
S
where H = Natural draft pressure, in. of water
O
= Specifc weight of outside air, lbf/ft
3
1
= Specifc weight of air in pipe, lbf/ft
3
H
S
= Height of air column or stack, ft
4 Read, Learn, Earn JULY 2012
READ, LEARN, EARN: Vent Systems
Te vent stack should extend undiminished in size through the roof
or connect with the vent extension of the drainage stack at least 6 in.
above the overfow of the highest fxture or connect to a vent header.
Vent terminalS
Vent terminals should not be located within 10 ft of any door, window,
or ventilation intake unless they are extended at least 2 ft above such
openings. Terminals should be at least 6 in. above roof level and at least
5 ft above when the roof is used for other purposes. When it is impracti-
cal to extend the vent through the roof, it is permissible to terminate
through a wall, but the terminal must turn down and be covered with a
wire screen. Te terminal should never be located beneath a building
overhang.
fixture traP VentS
Te water seal of all fxture traps should be protected against siphonage
or blowout by the proper installation of a venting system. When drainage
stacks are provided with an adequate supply of air at the terminal and an
adequate vent stack is provided to relieve excess pressures at the base of
the drainage stack, the only additional vent protection required to prevent
water seal loss in fxture traps is that necessary to prevent self-siphonage
when the fxture discharges and to relieve excessive pneumatic efects in
the branch drains when other fxtures discharge into the branch. Some
municipalities require that every fxture trap be individually vented, but
most localities permit alternatemethods such as
1. Wet venting
2. Stack venting
3. Circuit and loop venting
4. Combination waste and vent venting
diStance of Vent from traP
Te most comprehensive investigations of conditions under which fx-
ture traps will be safe from self-siphonage have been conducted by the
National Bureau of Standards in the United States and by the Building
Research Station in England. Te recommended maximum distances
of a vent from the weir of the trap to the vent connection are tabulated
in Table 8-4.
As illustrated in Figure 8-2, the vent pipe opening, except for water
closets and similar fxtures, must never be below the weir of the fxture
trap. A fxture drain that slopes more than one pipe diameter between
vent opening and trap weir has a greater tendency to self-siphon the
trap seal than a fxture drain installed at a slope of not more than one
pipe diameter.
Table 84 Distance of Vent from
Fixture Traps
Size of Fixture
Drain, inches
Maximum
Distance of Vent
to Trap, inches
1 30
1 42
2 60
3 72
4 120
Self-Siphonage of Fixture Traps, National Bureau of Standards Build-
ing Materials and Structures Report BMS 126 (1951), prepared by John
L. French and Herbert N. Eaton, is a very thorough study of self-sipho-
nage Some of the conclusions drawn by French and Eaton as a result of
their investigations are very illuminating and are quoted herewith:
1. Increasing the diameter of the outlet orifce of a lavatory from 118
in. to 1 in. increases the trap seal loss greatly, frequently more
than 100%, owing to the increased discharge rate.
2. Flat-bottomed fxtures cause smaller trap seal losses than do
round fxtures, owing to the greater trail discharge from the
former.
3. With a 1-in. fxture trap and drain, an 18-in. by 20-in. lavatory
gave greater trap-seal losses than did a 20-in. by 24-in. lavatory,
presumably owing to the greater trail discharge of the latter.
When a 1 in. trap and drain were used, no particular diference
was noted in the trap seal losses caused by the two lavatories.
4. Te elimination of the overfow in lavatories will increase the trap
seal losses substantially.
5. Te efect on trap seal losses of varying the vertical distance from
the fxture to the trap from 6 in. to 12 in. appears to be negligible.
6. For a given rate of discharge from a lavatory, decreasing the
diameter of the drain will increase trap seal losses.
7. An increase in slope or a decrease in diameter of the fxture drain
will tend to cause increased losses due to self-siphonage, and
these two dimensions are fully as important as the length of fx-
ture drain in causing self-siphonage.
8. Trap seal losses are usually much greater when a long-turn stack
ftting is used than when a short-turn or straight-tee ftting is
used. No signifcant diference between the behavior of short-
turn and straight-tee fttings was observed. Tus, since it is known
that a long-turn ftting is more efective in introducing water from
a horizontal branch into the stack than is either the short-turn or
straight-tee ftting, the characteristics of these fttings are contra-
dictory in these respects. Te ftting that is most advantageous
from the standpoint of introducing the water into the stack is the
least advantageous from the standpoint of self-siphonage.
9. Trap seal losses are increased if the internal diameter of a P-trap
is less than that of the fxture drain. Tus, if we are to prevent
excessive trap seal losses for a P-trap due to self-siphonage, we
should use a trap having a fairly large internal diameter. Further-
more, siphonage of the trap due to pressure reductions caused by
the discharge of other fxtures on the system can be rendered less
harmful by using a trap with a large depth of seal. While increas-
ing the depth of seal may lead to greater trap seal losses, it also
results in a greater remaining trap seal than if a trap with a shal-
low seal were used.
10. Te test results on the self-siphonage of water closets have indi-
cated that the unvented length of drain for these fxtures need not
be limited because of self-siphonage.
11. Standardization of the dimensions of fxture traps and especially
of lavatory traps, with regard to internal diameter and depth of
trap seal is highly desirable. Minor restrictions on these dimen-
sions can lead to substantially increased lengths of fxture drains.
12. Standardization of the hydraulic characteristics of fxtures is
desirable, at least for lavatories, sinks, and combination fxtures.
Substantially increased permissible unvented lengths of fxture
drains can be obtained for a moderate decrease in the discharge
rates of the fxtures.
13. Increase in depth of trap seal above the 2-in. minimum com-
monly permitted by codes will make it possible to increase appre-
JULY 2012 Read, Learn, Earn 5
ciably the maximum permissible unvented lengths of fxture
drains.
Tese conclusions clearly illustrate various approaches in the efort
to make plumbing systems less costly without afecting efciency. Te
proper design of fxtures and fxture drain lines and limiting the maxi-
mum discharge rates of faucet-controlled fxtures could result in longer
unvented lengths of drains.
VariouS metHodS of fixture traP Venting
Figure 8-3 illustrates various fxture trap vents and their proper nomen-
clature. When venting one trap the vent is called an individual or
back vent. If fxtures are back to back or side by side and one vent is
used for the two traps, the vent is a common vent. Any connection
from the vent stack is a branch vent.
All vent piping should be graded to drain back to the drainage piping
by gravity. Te vent should be taken of above the centerline of the
drainpipe and rise vertically or at an angle of not more than 45 from
the vertical. Te horizontal run of the vent should be at least 6 in. above
the overfow level of the fxture. (See Figure 8-4.)
relief VentS
Pressures in the drainage and vent stacks of a multistory building are
constantly fuctuating. Te vent stack connection at the base of the
drainage stack and the branch vent connections to the branch drains
cannot always eliminate these fuctuations. It then becomes extremely
important to balance pressures throughout the drainage stack by
means of relief vents located at various intervals. Te fuctuations in
pressure may be caused by the simultaneous discharge of branches on
various separated foors. Drainage stacks in buildings having more than
ten branch intervals should be provided with a relief vent at each tenth
interval, counting from the topmost branch downward. Te lower end
of the relief vent should connect to the drainage stack below the drain-
age branch connection and the upper end should connect to the vent
stack at least 3 ft above the foor level. (See Figure 8-5.)
Relief vents are required where a drainage stack ofsets at an angle of
more than 45 to the vertical. Such ofsets are subject to high pneumatic
pressure increases and extreme surging fow conditions. Te methods
of installing relief vents are illustrated in Figure 8-6.
continuouS Venting
A system of individual or common vents for every trap is called con-
tinuous venting. Every fxture trap is provided with a vent. It is the most
expensive system but provides positive protection of all trap seals.
wet Venting
A wet vent is a vent that vents a particular fxture and at the same
time serves as a waste to receive the discharge from other fxtures. Te
objective of using wet vents is to minimize the vent piping required by
employing one pipe to serve two functions. Tere are three fundamen-
tal rules to follow when utilizing a wet vent:
At top foor:
1. No more than 1 FU is discharged into a 1-in. wet vent nor more
than 4 FU into a 2-in. wet vent.
2. Length of drain does not exceed maximum permissible distance
between trap and vent.
3. Branch connects to the stack at the water closet connection level
or below. (See Figure 8-7.)
At lower foors:
Te rules are the same except that the water closets must be vented
and the wet vent must be 2 in. minimum. Water closets below the top
story need not be individually vented if a 2-in. wet vented waste pipe
connects directly to the upper half of the horizontal water closet drain
at an angle no greater than 45 from the angle of fow. (See Figure 8-8.)
Stack venting fnds its general application in one-family homes
and the top foor of multistory buildings. (See Figures 8-7 and 8-9.)
combination waSte and Vent Venting
Combination waste and vent venting is used primarily for venting
foor drains and laboratory and work tables. Te drainage piping is
oversized at least two sizes larger than required for draining purposes
only and the drainage branch and stack should be provided with vent
piping. Tis type of venting is employed when it is impractical to employ
the other methods.
circuit and looP Venting
Tere has developed a tendency to call all circuit venting by the name
applicable to a special installation of circuit venting. A circuit vent is a
branch vent that serves two or more foor outlet fxtures, except blow-
out water closets, and extends from in front of the last fxture connec-
tion on the horizontal drain to the vent stack. A loop vent is the same,
except that it is employed on the topmost foor serving fxtures and is
connected to the vent extension of the drainage stack instead of to the
vent stack. (See Figure 8-10.) When wall outlet fxtures are connected
to the branch drain serving the foor outlet fxtures, the former must be
provided with individual vents that can connect to the circuit vent or
loop vent.
6 Read, Learn, Earn JULY 2012
READ, LEARN, EARN: Vent Systems
common VentS
Where two fxtures are connected to a vertical branch at the same level,
a common vent may be employed. When one of the fxtures connects
at a diferent level than the other, observe the following procedure. If
fxture drains are the same size, increase the vertical drain one size. If
fxture drains are of diferent sizes, connect the smaller above the larger
connection and maintain the vertical size up to the top connection.
SudS PreSSure
Te prevalent use of high-sudsing detergents in washing machines,
dishwashers, laundry trays, and kitchen sinks has created serious
problems in all residential buildings and especially in high-rise build-
ings. Until manufacturers are forced to market only detergents without
sudsing characteristics, the plumbing engineer must understand and
cope with the dangers created in the sanitary system by the presence of
suds. (An interesting sidelight is that suds, in and of themselves, do not
enhance the cleaning ability of soaps or detergents in any way.)
When the fow of wastes from upper foors contains detergents, the
sudsingredients are vigorously mixed with the water and air in the
stack as the waste fows down the stack and further mixing action
occurs as other branch waste discharges meet this fow. Tese
suds fow down the stack and settle in the lower sections drain-
age system and at any ofsets greater than 45 degrees in the stack.
Investigation has shown that when sudsing wastes are present,
the sanitary and vent stacks are laden with suds and this condi-
tion was found to exist for extended periods of time.
Liquid wastes are heavier than suds and easily fow through
the suds-loaded drainage piping without carrying the suds along
with the fow. Everyone is aware of the difculty of fushing the
suds out of a sink. Te water simply fows through the suds and
out the drain, leaving the major portion of the suds behind. Te
same action occurs in the lower sections of the drainage system
except for one important diferenceair, as well as water, is now
fowing in the piping. Tis air, which is carried down with the
waste discharge, compresses the suds and forces them to move
through any available path of relief. Te relief path may be the
building drain, any branches connected to the building drain, the
vent stack, branch vents, individual vents or combinations of the
foregoing. A path of relief may not always be available or could
be cut of or restricted by the hydraulic jump, or a path may just
be inadequate because of location or size. If one or more of these
conditions exist, excessively high suds pressure can develop and
blow the seals of traps with the accompanying appearance of
suds in fxtures.
High suds pressure zones occur at every change in direction,
vertically or horizontally, that is greater than 45. Where vent
stack base connections, relief vents, branch vents, or individual
vents serve as the relief path for the high suds pressure, they are
usually found to be inadequate in size with resultant suds condi-
tions appearing at the fxtures. Te vent pipe sizing tables in prac-
tically every code are calculated on the basis of air fow capacity
and do not in any way provide for the more demanding fow of
suds. Sizes that are based on these code tables are inadequate
to accommodate suds fow and thus are incapable of providing
adequate suds pressure relief.
Suds are much heavier than air and consequently do not fow
with the same ease. Tey produce a much greater friction head
loss for the same rate of fow. Te density of old or regenerated
suds varies from 2 lb/ft3 to a high of 19 lb/ft3, depending upon
the detergent used. For equal rates of fow and pressure loss, the
vent pipe diameter for suds relief fow must be from 20 to 80%
greater than for air fow.
Whenever a soil or waste stack receives washing machines,
dishwashers, laundry trays, kitchen sinks, or other fxtures where
sudsing detergents are used, the drainage and vent piping for
the lower-foor fxtures or for the fx tures above ofsets must be
arranged to avoid connection to any zone where suds pressure
exists.
Suds pressure zones exist in the following areas:
1. At a soil or waste stack ofset greater than 45: 40 stack diameters
upward and 10 stack diameters horizontally from the base ftting
for the upper stack section. A pressure zone also exists 40 stack
diameters upstream from the top ftting of the lower stack sec-
tion.
2. At the base of a soil or waste stack: Te suds pressure zone
extends 40 stack diameters upward from the base ftting.
3. In the horizontal drain from the base of a stack: Te suds pressure
zone extends 10 stack diameters from the base ftting, and where
an ofset greater than 45 in the horizontal occurs, the pressure
zones extend 40 stack diameters upstream and 10 diameters
downstream from the ofset ftting.
4. In a vent stack connected to a suds pressure zone: Te suds pres-
sure zone exists from the vent stack base connection upward to
the level of the suds pressure zone in the soil or waste stack.
Figure 8-11 illustrates all the above zones.
JULY 2012 Read, Learn, Earn 7
VaPor VentS (local VentS)
Years ago water closets and urinals were equipped with connec-
tions for venting the fxture to the outdoors to eliminate foul odors.
Fixture design has been improved so that these vents are no longer
required. Te use of vapor vents is now applied to sterilizing
equipment and bedpan washers. Tis application is also rapidly dis-
appearing as new methods of condensing the foul vapors are being
built into the equipment. When a vapor vent is used, it must be
isolated from the sanitary venting system. Te base of a vapor vent
stack should terminate in a trap, to prevent the escape of vapors,
and spill to a trapped, vented, and water-supplied receptacle. Te
stack should extend through the roof.
An individual vapor vent drip can be connected through an
air gap to the inlet of the trap serving the fxture. Vapor vents for
bedpan washers and bedpan sterilizers must not connect with the
vapor vents of other fxtures.
Sizing of the vapor vent stack may be by empirical methods or
the rational approach may be used. Te minimum size of the stack
should be 1 in.
ejector and SumP VentS
Ejectors, other than the pneumatic type, operate at atmospheric
pressure and receive drainage discharge under gravity fow condi-
tions. An ejector is installed when the level of fxture discharge is
below the level of the public sewer. It is convenient to view an ejec-
tor system as being exactly similar to the gravity sanitary system and
all of the requirements for the proper design of the sanitary system
are applicable. Tus, the air required to be conveyed by the vent
piping is the same as the maximum rate at which sewage enters or
is pumped out of the receiver.
Te ejector vent can be determined by reference to Equation
8-10:
L = 2226 (d
5
/fq
2
)
and using Table 8-1, which gives air discharge in gpm for various
pipe diameters. It has been found in practice that 3 in. is adequate
except for extremely large installations.
froSt cloSure
Where the danger of frost closure of vent terminals is present, the
minimum size of the vent stack or vent extension through the roof
should be 3 in. When a vent stack must be increased in size going
through the roof, the increase should be made inside the building
at least 1 ft below the roof.
Te National Bureau of Standards has investigated the problem
of frost closure both theoretically and experimentally. It was dem-
onstrated that a 3-in. vent terminal froze up solidly at 30F only
over an extended period of time. Closure occurs at the rate of 1 in.
for every 24 hr. that the temperature remains at 30F.
It can be seen that frost closure presents a real problem only in
the far northern regions. Te problem is serious in Canada, and
they have devised various methods of overcoming it:
1. Vent terminal to extend only 1 in. or 2 in. above the roof. Te
more pipe exposed to the atmosphere, the greater the prob-
lem. Snow covering the vent terminal has proven to cause no
trouble. Te snow is porous enough for the passage of air and
melts rather rapidly at the outlet.
2. Enlargement of the stack below the roof. Te increased diam-
eter decreases the chance of complete closure and the stream
of air tends to fow through the enlarged portion without
touching the walls of the enlarged pipe.
3. Install cap fashing at the terminal and counterfashing to
leave an air space from the heated building.
Frost closure depends upon the: (1) outside temperature, (2)
temperature and humidity of inside air, (3) wind velocity, (4) length
of exposed pipe, (5) diameter of exposed pipe, and (6) velocity of
air fow. Tere is very little danger of frost closure unless the outside
8 Read, Learn, Earn JULY 2012
READ, LEARN, EARN: Vent Systems
temperature falls below 10F and remains there for several days. It has
been found that if frost closure does occur, siphonage of traps is reduced
or prevented by connecting the drainage and vent stacks together
before extending through the roof. An analysis of air fow under these
conditions will convince the plumbing engineer of its validity, as it can
be seen that air forced into the vent stack at its base will be introduced
into the soil stack at the top connection.
teStS of Plumbing SyStemS
Te complete storm and sanitary system should be subjected to a water
test and proven watertight upon completion of the rough piping instal-
lation and prior to covering or concealment. Te test pressure should
be a minimum of a 10-ft column of water except for the topmost 10 ft
of pipe. Te test pressure should never exceed a maximum of a 100-ft
column of water. Any greater pressure will cause the test plugs used
to seal temporarily open piping in the system to blow. If the system is
higher than 100 ft, test tees may be installed at appropriate heights so
as to test the building in sections. Very rarely in practice are more than
seven stories tested at one time.
If it is not possible to perform a water test, an air test is acceptable. Te
air test shall be made by attaching an air compressor testing apparatus
to any suitable opening, and, after closing all other inlets and outlets
to the system, forcing air into the system until there is a uniform gage
pressure of 5 psi (34.5 kPa) or a pressure sufcient to balance a column
of mercury 10 in. (254 mm) in height. Te pressure shall be held with-
out introduction of additional air for a period of at least 15 min.
Upon completion of the sanitary system and after all fxtures are
installed with traps flled with water, the system should be subjected to
an additional test and proved gastight.
An alternate test is the smoke test. Te smoke test is performed by
introducing pungent, thick smoke produced by smoke bombs or smoke
machines. When smoke appears at the roof terminals, each terminal is
sealed and a smoke pressure of 1-in. column of water is maintained to
prove the system gastight. Tis test is not practical and is seldom used.
Another alternate test is the peppermint vapor test. At least 2 oz. of
oil of peppermint are introduced into each roof terminal and vaporized
by immediately pouring 10 qt of boiling water down the stack. Te ter-
minals are promptly sealed. Oil of peppermint and any person coming
in contact or handling the oil must be excluded from the interior of the
building for the duration of the test. Leakages will be detected by the
peppermint odor at the source. However, it is very difcult to pinpoint
the leak by this method. Tis test is not practical and is seldom used.
JULY 2012 Read, Learn, Earn 9
10 Read, Learn, Earn JULY 2012
READ, LEARN, EARN: Vent Systems
CE Questions
Vent Systems (CEU 189)
________ is the pressure exerted at any 1.
point by the weight of the substance
above that point.
specifc weight a.
static head b.
density c.
fow pressure d.
At a fow pressure of 1 inch of water 2.
column, what is the air discharge rate of
a 3-inch vent pipe?
58.6 cfm a.
91.5 cfm b.
131.8 cfm c.
234.3 cfm d.
The Darcy formula expresses what? 3.
friction head loss a.
static pressure of air b.
rate of fow c.
none of the above d.
What is the rate of air fow in a 4-inch 4.
horizontal drain at a slope of 1/8 inch per
foot?
15.5 gpm a.
25.5 gpm b.
38.0 gpm c.
69.0 gpm d.
The pipe from the topmost drainage 5.
branch connection through the roof to
the atmosphere is called the ________.
vent terminal a.
vent extension b.
trap vent c.
vent stack d.
What is the recommended maximum 6.
distance of a 2-inch fxture drain trap to
the vent connection?
30 inches a.
42 inches b.
60 inches c.
72 inches d.
Reading the article and completing the form will
allow you to apply to ASPE for CEU credit. If you
earn a grade of 90 percent or higher on the test,
you will be notified that you have logged 0.1
CEU, which can be applied toward CPD renewal
or numerous regulatory-agency CE programs.
(Please note that it is your responsibility to deter-
mine the acceptance policy of a particular agency.)
CEU information will be kept on fle at the ASPE
ofce for three years.
ASPE Continuing Education Application Form
this form is valid up to one year from date of publication. Expiration date: Continuing education credit will be given for this examination
through july 31, 2013. Applications received after that date will not be processed.
Submit this form with payment via mail (ASPE Read, Learn, Earn, 2980 S. River Road, Des Plaines, IL 60018), fax (847-296-2963), or email
aspeeducation@aspe.org.
Please print or type; this information will be used to process your credits.
Name ______________________________________________________________________ ASPE Membership No. ______________
Organization ___________________________________________________ Daytime telephone _____________________________
Billing Address ________________________________________________________________________________________________
City _________________________________________ State/Province ________________________ Zip ______________________
E-mail _______________________________________________________________________ Fax ____________________________
PE State _____________________________________________ PE No. _________________________________________________
Notice for North Carolina Professional Engineers: State regulations for registered PEs in North Carolina now require you to complete ASPEs online CEU validation form
to be eligible for continuing education credits. After successfully completing this quiz, just visit ASPEs CEU Validation Center at aspe.org/CEUValidationCenter.
I certify that I have read the article indicated
above.
Signature
Payment:
Member: Free
Nonmember: Each examination: $35
Personal Check (payable to ASPE)
Business or government check
DiscoverCard VISA MasterCard AMEX
If rebilling of a credit card charge is necessary, a $25
processing fee will be charged.
ASPE is hereby authorized to charge my CE
examination fee to my credit card
Account Number
Expiration date
Signature
Cardholders name (Please print)
A ________ is required where a drainage 7.
stack offsets at an angle of more than 45
degrees to the vertical.
branch vent a.
back vent b.
wet vent c.
relief vent d.
A ________ vents a particular fxture and 8.
at the same time serves as a waste to
receive the discharge from other fxtures.
branch vent a.
back vent b.
wet vent c.
relief vent d.
A ________ is used on the topmost foor 9.
serving fxtures and is connected to the
vent extension of the drainage stack
common vent a.
circuit vent b.
combination waste and vent c.
loop vent d.
Where frost closure is possible, the vent 10.
extension through the roof should be
_______ minimum.
1 inch a.
2 inches b.
3 inches c.
4 inches d.
During a water test, the test pressure 11.
should never exceed ________.
10 feet of water column a.
20 feet of water column b.
50 feet of water column c.
100 feet of water column d.
Which of the following tests is seldom 12.
used?
smoke test a.
air test b.
peppermint vapor test c.
both a and c d.
Circle the correct answers below.
JULY 2012 Read, Learn, Earn 11
C
E
U
1
9
0
The Properties
of Water and
Hydraulics
Continuing Education from the
American Society of Plumbing Engineers
AUGUST 2012
ASPE.ORG/ReadLearnEarn
Water is indispensable to the survival of humans, animals, and plants.
A person can live without food for a month or more, but can survive
only a few days without water. Te human body needs water to wash
out and dissolve toxins, which are continually produced as waste sub-
stances. If not eliminated, these toxins will poison the body. Water is
also necessary for digestion, metabolism, and many other functions in
the human body.
Water in humans and other animals must be replaced due to con-
tinuous elimination through exhalation, perspiration, and urination.
Lack of water may have a harmful efect upon bodily functions. As a
rule of thumb, a person should consume half an ounce of water per
pound of body weight every day, so a person weighing 150 lb requires
75 oz of water (nine to ten 8-oz glasses) daily. Tis may seem like a lot
of water, but it is the amount medically recommended for a correct bal-
ance. Water intake should be evenly distributed during the day, and
the water we drink must be safe. Te US has the safest domestic water
supply in the world.
Potable Water
To become potable (drinkable), water must be treated. Treatment
generally includes fltration and chlorination; however, there are other
specifc water-treatment processes that reduce or neutralize excess
acidity, alkalinity, or dissolved matter.
Harmful and non-harmful organic bacteria are generally found in
surface-water reservoirs. If not destroyed, harmful bacteria (patho-
gens) may cause diseases like typhoid and cholera in humans who
ingest the contaminated water. Non-harmful bacteria encourage the
growth of algae and slime, which discolor the water and produce odors.
Both non-harmful and harmful bacteria can be controlled through the
use of chlorine or ozone.
Chlorine rids a water supply of contaminants through a chemical
reaction, which produces hypochlorous acid. Tis acid has disinfecting
properties. Small amounts of pathogens may be destroyed by simply
boiling the water prior to consumption. Potable water must have an
agreeable taste, be colorless and odorless, and contain no more than
0.001 lb (0.4 mg)/gal of chlorine.
Neither the water occurring in nature nor the water used for domestic
purposes is pure. Water contains a number of naturally dissolved mate-
rials and chemicals (generally in very small amounts), as well as certain
chemicals that are purposely added through treatment. One of these
added chemicals may be fuoride, which could prevent or reduce the
incidence of tooth decay in those who drink that water.
To prevent contamination and diseases, any new and/or refurbished
potable water-supply system must be disinfected after installation, in
accordance with strict and detailed rules, before it is ready for con-
sumption. Te pipes, fttings, and appurtenances as they arrive from
factories could possibly contain bacteria as well as dust and harm-
ful impurities. Tese impurities must be neutralized and washed out
before the system becomes operational. Te specifcation located in
Appendix H gives the details to be followed for this process.
Water SuPPly
Fresh water is a national treasure and must be managed properly rather
than wasted. Te fact that numerous countries around the world lack
surface or underground fresh water should force those in the US to rec-
ognize the importance of this natural resource.
Two categories of water exist in nature: fresh water and sea water. Sea
water is found in oceans and open seas, which occupy approximately
75% of the earths surface. Fresh water can be found in natural springs,
rivers, and lakes (or any inland natural surface reservoir), but most
fresh water is located in underground reservoirs, or aquifers. Humans
have traditionally lived near surface water. Such a location provides a
source of drinking water as well as a supply of fsh and game animals.
Trough the years, humans have learned to tap into the fresh water
located in underground reservoirs.
Water evaporates from plants, soil, and surface bodies of water. Te
water then accumulates in the upper part of the earths atmosphere in
the form of clouds. Under certain meteorological conditions, the water
returns to the earth in the form of rain or snow, depending upon the
geographical location and time of year. Rain and snow are the sources
of surface and underground water. Tis movement of water in nature is
called the hydrological cycle (see Figure 3-1).
Precipitation from the atmosphere percolates through the ground,
which acts as a flter. When the water reaches a saturated geological
formation or an impermeable stratum (like clay), it forms aquifers. A
geologist or hydrologist, both of whom specialize in underground geo-
logical formations, can locate subsurface water. Underground water
reservoirs represent 97% of the fresh water in nature, while surface
water represents only 3% of the fresh water available. Underground
water fows slowly toward the lowest point of discharge.
Not all the water that infltrates the soil becomes ground water. Water
may be pulled back to the surface by the capillary force of plants. Tis
capillary force also contributes to the above-ground evaporation of
water. Water percolation through the upper strata of the ground com-
bined with waters capability to dissolve materials gives the stored
underground water certain qualities, which may render it more or less
acceptable for human consumption or other applications.
When a source of water is needed for domestic use, there are a few
things a plumbing specialist should know:
Amountneeded.
Accessibility.
Quality.
Quantityavailable.
Amount needed
Te amount of water needed depends upon the proposed building
occupancy. In the process of project development, occupancy needs
must be determined frst, since there are vast diferences among an
industrial establishment (which might need process water), a com-
mercial institution, and a residential user. Each user has specifc
requirements, which are either already known or required by code.
Tese requirements can be determined by calculations based on avail-
able information. In considering the demand for water, the plumbing
specialist has to determine the current amount needed as well as any
expected future increases in the amounts, based on the owners devel-
opment plans. Practical knowledge and prior experience are useful
when estimating and selecting these data.
Reprinted from Plumbing Technology. 2001, American Society of Plumbing Engineers.
note: In determining your answers to the Ce questions, use only the material presented in the corresponding continuing education
article. using information from other materials may result in a wrong answer.
2 Read, Learn, Earn AUGUST 2012
reaD, learN, earN
ACCessIbIlIty
Surface water can be observed and measured, and its availability can be
determined by studying historical data (e.g., droughts, rain, snow, tem-
perature) for the particular location. Natural underground reservoirs
are not always readily available, due to depth. With todays technology,
any water location can be made accessible, but, if the price is exces-
sive, then the location will be considered impractical and economically
disadvantaged.
From a hydrological point of view, it is possible to illustrate a section
of ground (see Figure 3-2). Water found in the saturation zone is called
ground water. Ground water can be found in natural reservoirs of var-
ious sizes and at diferent depths or in various layers. Te formation, or
strata, above the saturation zone from which water can be pumped for
usage is called an aquifer.
WAter QuAlIty/QuAntIty
Based on many sources of information, such as satellite pictures and
test wells, geologists and hydrologists can determine the possible exis-
tence of underground water. Te quality of water available, however,
cannot be determined without actual laboratory testing. Laboratory
testing determines what substances are dissolved in water. Only after
testing can the necessary treatment and cost be determined, in accor-
dance with the intended purpose, industrial or potable use.
To determine the quantity of water available, pumping tests must
be performed. Te geologist and hydrologist usually work together to
prepare a map of the underground strata, called a geological map.
Tis map shows areas where water may exist. Test wells then confrm
whether or not water is available. Some information may come from
an analysis of existing water wells and their yields. However, in an area
where development is planned but no wells exist, drilled test wells or
test holes are required to obtain the necessary information. Te sam-
ples brought to the surface during drilling provide sound geological
and hydrological information to be analyzed by specialized persons.
With this information and the pumping results, the quantity of water
can be determined.
Te approximate costs of producing potable water from ground,
surface, and sea water are given below. (Tese are general fgures, for
information only; locations and numerous other characteristics may
infuence the price.)
Groundwater:$1.50per1000gal.
Surfacewater:$4.00per1000gal.
Seawater(desalinated):$6.00per1000gal.
Te water availability, in certain locations, may determine the devel-
opment of a particular site or the preference for another. Other factors
that must be considered include the proper use, protection, and con-
servation of the water source, as well as socioeconomic conditions.
ProPertieS of Water
As previously described, water, in its natural cycle, evaporates from the
surface of natural bodies of water, then clouds form, and rain or snow
develops. Upon reaching the ground, water percolates very slowly
through the upper layers of the earths crust, which is called perme-
able strata. During this slow, natural, downward movement, water
comes in contact with various naturally occurring substances (miner-
als). Tis process flters the water while adding minerals, mostly in the
form of salts. At some point, an equilibrium is reached.
Dissolved minerals in ground water may afect its potential usage. If
the concentration of a certain mineral is excessive for the specifc water
usage, it may need to be removed during water treatment. Due to natu-
ral fltration, most ground water contains virtually no bacteria and no
suspended matter, which means most underground water needs little
treatment to become domestic (potable).
Te natural chemical properties of water (H
2
0) are solubility (it dis-
solves a variety of substances), hardness, specifc electrical conduc-
tance, hydrogen-ion concentration (pH, which at the value of 7 shows
that the water is neutral, at a value between 7 and 14 shows that it is
alkaline, and at a value between 0 and 7 shows that it is acid), dissolved
carbon dioxide, and dissolved solids. Some of the physical properties of
water include: density, viscosity, compressibility, its boiling point, and
its freezing point. It is important to recognize these properties because,
in one way or another, they infuence the fow of water in a plumbing
system.
densIty
By defnition, density is the ratio of mass (weight) of a substance to
the volume it occupies. Density is given in pounds per cubic foot, which
can be written as lb/ft
3
or lb/cu ft. In plumbing calculations, water den-
sity is usually considered to be 62.3 lb/ft
3
. Tis value represents the
density of water at a temperature of 70F (room temperature). Water
Figure 3-1 Hydrological Cycle
AUGUST 2012 Read, Learn, Earn 3
WAter FloW
Te fow of water can be characterized as laminar or turbulent. In
laminar fow, streams of water molecules fow naturally parallel to each
other up to a certain velocity. Above that velocity, the fow becomes
turbulent. Tis characteristic was demonstrated by Osborne Reynolds,
who developed a simple formula to determine the Reynolds number
(R), which classifes the fow as laminar or turbulent. If R is less than
2000, the fow is laminar. Te simplifed formula is as follows:
Equation 3-1
R = VD
v
where: R = Reynolds number (no unit of measurement)
V = Water velocity (ft/sec)
D = Pipe diameter (ft)
v = Kinematic viscosity (ft
2
/sec)
Example 3-1 Compute the Reynolds number based on the follow-
ing information:
Water velocity = 4 ft/sec
Pipe diameter = 4 in. (0.33 ft)
Viscosity = 0.00052 lb/ft-sec
Solution 3-1 R = (4) (0.33) = 16.510
4
0.00052
In the above example, R is much larger than 2000, so the fow is tur-
bulent. If the velocity in a 4-in.diameter pipe were less than 0.072 ft/
sec, the Reynolds number would be smaller than 2000 and the fow
would be laminar. Tis simple calculation tells us that the fow of water
in pipes at normal velocities of 4 to 8 ft/sec is always turbulent. Tur-
bulent fow does not adversely afect plumbing design. It is also true
that the velocity of fowing water in a cross section of the pipe is not
uniform.
Te velocity of water is greatest at the center of a pipe. More friction
exists along the walls, where water molecules rub against pipe walls
(see Figure 3-3). Te velocity used in these problems is an average
velocity, which represents 80% of the maximum velocity at the center
of the pipe. To facilitate the understanding of water fow in a plumb-
ing system, this book includes sample problems based on a pumped
system and a gravity system.
density varies slightly with the temperature; the warmer the water, the
less dense it becomes, as shown by the values in Table 3-1:
Table 3-1 Water TemperatureDensity Correlation
Water Temperature (F) Water Density (lb/ft3)
32 62.416
50 62.408
70 62.300
100 61.998
150 61.203
210 59.843
VIsCosIty
Viscosity, as applied to plumbing, concerns the friction of water mol-
ecules among themselves, as well as along the walls of the pipes and
fttings. It is the physical property that directly infuences the fow of
water in pipes. Te forces at work between the water molecules them-
selves are called cohesion and adhesion. Tese forces can be mea-
sured in the laboratory.
Cold water is more cohesive than warm water, thus its viscosity is
greater. Tis greater viscosity increases the friction of the fow of cold
water through pipes. Warm water fows somewhat more easily through
pipes because it is not as cohesive. However, the actual diference in
viscosity between domestic cold and hot water is so small that it is con-
sidered insignifcant for practical purposes and is negligible in calcula-
tions.
Viscosityismeasuredincentistokesorcentipoise.At60F,waterhas
an absolute viscosity equal to 1.12 centipoise, which corresponds to a
measurementofkinematicviscosityof0.00001216ft
2
/sec.
CompressIbIlIty
As noted previously, water at ambient temperature is considered non-
compressible for all practical purposes.
boIlIng/FreezIng poInts
Water boils at 212F (100C) at sea level (atmospheric pressure). If the
pressure varies, the boiling temperature point will also vary. Te lower
the pressure exerted upon the surface, the lower the boiling point. For
example, atmospheric pressure is lower on top of a mountain, so water
boils at a lower temperature there. Te changes in the boiling point as a
function of pressure are shown in Table 3-2.
Table 3-2 Water Boiling Point/Pressure Correlation
Absolute Pressure (psi) Water Boiling Point (F)
1 101.8
6 170.1
14.7 (atmospheric) 212.0
Figure 3-2 Ground Section
4 Read, Learn, Earn AUGUST 2012
READ, LEARN, EARN: The Properties of Water and Hydraulics
Figure 3-3 Flow of Water in Pipes
Te basic formula for fuid fow is:
Equation 3-2
Q = AV
where: Q = Flow (ft
3
/sec)
A = Cross section of the pipe (ft
2
)
V = Water velocity in pipe (ft/sec)
Another item often used in plumbing calculations is the velocity
head. Tis is defned as the decrease in head (or the loss of pressure),
which corresponds to the velocity of fow. Te formula for velocity head
is as follows:
Equation 3-3
hv = V
2
____
2g
where: hv = Velocity head (ft)
V
2
= Velocity in pipe (ft/sec)
2
g = Acceleration of gravity (ft/sec
2
)
As a dimensional verifcation:
hv = (
ft
2
) (
sec
2
) = ft
___ ___
sec
2
ft
When performing plumbing calculations, consideration needs
to be given to factors that afect the fow of water through the pipes.
Tese factors include friction or pressure losses that occur when
water fows through pipe, pipe fttings, or equipment (e.g., water
meters or heaters) (see Figure 3-4). Another factor is static head,
which is the amount of potential energy due to the elevation of water
above a certain reference point. Static head is measured in feet of
water and can be converted into pounds per square inch (psi).
Plumbing calculations are important to ensure that pipes are sized
correctly. If the pipes are not sized correctly and the fow of water
stops suddenly, the dynamic force of the fow may produce water
hammer, shock, or noise. If the velocity is constantly too high when
water is fowing, erosion also might occur in the pipes.
HyDraulicS
Hydraulics is part of a larger branch of physics called fuid
mechanics. Plumbing, which deals with the fow of fuids in pipes,
is a practical application of hydraulics. Hydraulic principles are based
on the chemical, physical, and mechanical properties of water. Tese
properties, which were discussed earlier, include density, viscos-
ity, and type of fow (laminar or turbulent) as a function of velocity,
water temperature, and pressure.
Plumbing deals with two types of fuids: gas and liquid. Te main
diference between these two fuids is that gas is compressible. Liq-
uids, mainly water in plumbing applications, are essentially non-
compressible at room temperature. Water fows in pipes by gravity
from a higher to a lower elevation. Te diference in elevation, or
water level, in a system is called static head. If the water is required
to fow in the opposite direction, it must be assisted by a mechanical
device, such as a pump.
A piping system, or network, includes pipes, fttings, and valves. As
discussed earlier, water fowing through these pipes, fttings, valves,
and other equipment produces friction or a loss of pressure. Tis pres-
sure loss, or resistance to fow, occurs because the molecules of water
rub against the walls of the pipes and fttings. Te types of energy
involved in the fow of water include kinetic and potential energy. Fol-
lowing are some examples.
Example 3-2 What is the outlet pressure for water fowing in a
straight pipe having the following characteristics?
Pipe material: Schedule 40 steel
Pipe diameter: 2 in.
Flow: 40 gpm
Length of pipe: 50 ft
Inlet water pressure 25 ft = 10.82 psi
Solution 3-2 Remember that when water fows along the pipe, fric-
tion, loss of head, or loss of power result. Also realize that while data is
provided for calculations in this book, in an actual plumbing applica-
tion, this data must either be calculated (e.g., required fow) or selected
(e.g., piping material and limiting water velocity in pipes).
Based on the information in Appendix B, at a fow of 40 gpm the
velocity of water is 3.82 ft/sec and the head loss is 3.06 ft per 100 ft of
pipe. Te pipe length in this problem is only 50 ft, so the head loss is:
(
50 ft
) (
3.06ft
) = 1.53 ft 100 ft
Te pressure available at the pipe exit is 25 ft 1.53 ft = 23.47 ft, or
10.16psi(seeFigure3-5).
Figure 3-4 Friction in Fittings
AUGUST 2012 Read, Learn, Earn 5
Figure 3-5 Straight Pipe
Example 3-3 Based on the data given in Example 3-2, what is the
outlet pressure for water fow in pipe with fttings (see Figure 3-6)?
(Tere is no diference in elevation.)
Figure 3-6 Pipe with Fittings
Solution 3-3 Remember, the total friction in the system consists of
the friction in the pipe plus the friction in the fttings.
Te velocity head, which may be found in Appendix B, is calculated
as follows:
hv = V
2
= 3.82
2
= 0.227 ft ___ _______
2g (2)(32.17)
Te friction in fttings (hf ) can be found in Appendix B and is based
on the velocity head calculation. Te K factor is a resistance coefcient,
which helps calculate the friction in fttings. It represents the coef-
cients for each individual ftting, the sum of which equals total friction
in fttings (e.g., K1 + K2 + ..., where K represents each ftting) when mul-
tiplied with the velocity head. For the problem at hand, the K value for
a 2-in., 90 standard elbow is 0.57. Te K value for a 2-in. gate valve is
0.15. Tus, the friction loss in fttings is as follows:
Equation 3-4
hf = [Kl (elbow) + K2 (elbow) + K3 (valve)] (
V
2
)
__
2g
= (0.57 + 0.57 + 0.15) (0.227) = 0.293 ft
where: hf = Friction in fttings (ft)
K = Resistance coefcient for each ftting
V = Velocity in pipe (ft/sec)
g = Acceleration of gravity (ft/sec
2
)
We already calculated the friction in this length of pipe (see Example
3-2), so just add it to the friction in fttings:
1.53 ft + 0.293 ft = 1.823 ft
Te pressure available at the pipe exit is now:
25 ft 1.823 ft = 23.177 ft (round to 23.18) or 10.03 psi
In this example, the available pressure is lower because of the added
friction in the fttings.
Example 3-4 Based on the data given in Examples 3-2 and 3-3, what
is the outlet pressure for water fow in a pipe with a vertical portion (see
Figure 3-7)?
Figure 3-7 Pipe with Vertical Portion
Solution 3-4 Te calculations made in Example 3-3 remain
unchanged since the data is the same. However, there is now some
pressure loss due to a 10-ft vertical section.
Te friction in pipe and fttings remains the same at 1.823 ft. From
the inlet pressure, deduct the diference in elevation:
25 ft 1.823 ft 10 ft = 13.177 ft
(round to 13.18) or 5.70 psi
Example 3-5 Storm water must be transferred from a holding tank
located at a low elevation to a reservoir located at a higher elevation
(see Figure 3-8). Calculate the total head loss in the system to select
the appropriate pump size to do the job. Use the following data for this
calculation:
Pipe material: Schedule 40, standard weight, steel
Pipe diameter: 3 in.
Flow: 130 gpm
Watervelocity:5.64ft/sec(fromTable3-3)
(see note #2)
Friction: 3.9 ft/100 ft of pipe (from Table 3-3)
Limitingvelocity:6fps
Figure 3-8 Transfer of Water from a Lower Elevation
to a Higher Elevation
Solution 3-5 Te system shown in Figure 3-8 can be divided into two
sections: the suction side of the pump and the discharge side of the
pump. Te head loss in the suction side of the pump includes: friction
loss in the pipe; friction loss in the fttings and valve; and static head
(since the fow is against gravity, it is considered a loss). Static head
must be added to the friction loss, since the pump must overcome both
of these factors to push the column of water up through the pipes.
Te friction loss in the pipe can be calculated with Darcys formula,
which is discussed later in this chapter. For the purposes of this calcu-
lation, however, the corresponding values can be taken directly from
Table 3-3.
On the suction side of the pump, the head loss due to friction (hp) in
an 8-ft length of pipe is calculated as follows:
hp = (8 ft)(
3.9 ft
) = 0.312 ft 100 ft
To calculate the friction loss in the fttings, use the same formula
usedinSolution3-3,Equation3-4(perTable3-3,V=5.64ft/sec):
hf = (K) (
V
2
)
___
2g
where: hf = Friction in fttings (ft)
K = Resistance coefcient for each ftting
6 Read, Learn, Earn AUGUST 2012
READ, LEARN, EARN: The Properties of Water and Hydraulics
V = Velocity in pipe (5.64 ft/sec) (see Table 3-1)
g = Acceleration of gravity (32.174 ft/sec
2
)
therefore:
hf = (K)(
5.64
2
) = (K)(0.494)
________
232.174
On the suction side of the pump, the fttings are a foot valve (a type of
check valve) and a 90 elbow at the entrance into the pump (see detail
A-A in Figure 3-8). Based on the tables listing the values of resistance
coefcients included in Appendix B, the applicable value of these K
coefcients is 1.4 for the foot valve and 0.54 for the 90 elbow. Insert
these values to complete the equation above:
hf = (1.4 + 0.54) (0.494) = 0.958 ft
To calculate total head loss on the suction side, add the static head to
the friction losses (pipes and fttings). Remember that the static head
in this case is the diference in elevation between the center line eleva-
tion of the pump and the water level
3
in the holding tank. (Since we are
calculating the losses by dividing the system into the suction and the
discharge sides of the pump, the pump center line becomes the refer-
ence point between the two sides in this case.)
From Figure 3-8, it is possible to calculate the diference in
elevation:
31ft25ft = 6ft
Te total suction head, or pressure loss, which is measured in ft, thus
becomes:
6ft(statichead)+0.312ft(frictioninpipe)
+ 0.958 ft (friction in fttings) = 7.27 ft
Now it is necessary to calculate the friction, or head, loss in the dis-
charge side of the pump. For the 1350-ft length of the 3-in. diameter
discharge pipe, the friction in the pipe is:
(1350 ft)(
3.90 ft
) = 52.65ft
100 ft
Before calculating the friction in fttings, frst tabulate the applicable
K coefcient values, Table 3-4.
Table 3-4 Friction in Fittings Resistance Coeffcient
Fitting Value of K Pipe Diameter
45 elbow 0.29 3
90 standard elbow 0.54 3
Gate valve 0.14 3
Swing-check valve 1.80 3
Pipe exit 1.00 Sharp edge
It is then possible to calculate the friction loss in fttings:
hf = (K) (
V
2
)
__
2g
hf = (0.54 + 0.14 + 1.8 + 0.29 + 0.29 + 0.54 + 0.54 + 1.0) (
V
2
)
__
2g
Table 3-3 Friction of Water in 3-Inch Pipe
Asphalt-dipped Cast Iron and New Steel Pipe (Based on Darcys Formula)
Flow, Asphalt-Dipped Cast Iron Standard Wt. Steel Sch 40 Extra Strong Steel Sch 80 Schedule 160 Steel
US 3.0 inside dia. 3.068 inside dia. 2.900 inside dia. 2.624 inside dia.
gal Velocity, Velocity Head loss, Velocity, Velocity Head loss, Velocity, Velocity Head loss, Velocity, Velocity Head
loss,
per ft per head, ft ft per ft per head, ft ft per ft per head, ft ft per ft per head, ft ft per
min sec 100 ft sec 100 ft sec 100 ft sec 100 ft
10 0.454 0.000 0.042 0.434 0.003 0.038 0.49 0.00 0.050 0.593 0.005 0.080
15 0.681 0.010 0.088 0.651 0.007 0.077 0.73 0.01 0.101 0.89 0.012 0.164
20 0.908 0.010 0.149 0.868 0.012 0.129 0.97 0.02 0.169 1.19 0.022 0.275
25 1.13 0.02 0.225 1.09 0.018 0.192 1.21 0.02 0.253 1.48 0.034 0.411
30 1.36 0.03 0.316 1.3 0.026 0.267 1.45 0.03 0.351 1.78 0.049 0.572
35 1.59 0.04 0.421 1.52 0.036 0.353 1.70 0.04 0.464 2.08 0.067 0.757
40 1.82 0.05 0.541 1.74 0.047 0.449 1.94 0.06 0.592 2.37 0.087 0.933
45 2.04 0.06 0.676 1.95 0.059 0.557 2.18 0.07 0.734 2.67 0.111 1.16
50 2.27 0.08 0.825 2.17 0.073 0.676 2.43 0.09 0.86 2.97 0.137 1.41
55 2.50 0.10 0.990 2.39 0.089 0.776 2.67 0.11 1.03 3.26 0.165 1.69
60 2.72 0.12 1.17 2.6 0.105 0.912 2.91 0.130 1.21 3.56 0.197 1.99
65 2.95 0.14 1.36 2.82 0.124 1.06 3.16 0.15 1.4 3.86 0.231 2.31
70 3.18 0.16 1.57 3.04 0.143 1.22 3.40 0.18 1.61 4.15 0.268 2.65
75 3.40 0.18 1.79 3.25 0.165 1.38 3.64 0.21 1.83 4.45 0.307 3.02
80 3.63 0.21 2.03 3.47 0.187 1.56 3.88 0.23 2.07 4.75 0.35 3.41
85 3.86 0.23 2.28 3.69 0.211 1.75 4.12 0.26 2.31 5.04 0.395 3.83
90 4.08 0.26 2.55 3.91 0.237 1.95 4.37 0.29 2.58 5.34 0.443 4.27
95 4.31 0.29 2.83 4.12 0.264 2.16 4.61 0.33 2.86 5.63 0.493 4.73
100 4.54 0.32 3.12 4.34 0.293 2.37 4.85 0.36 3.15 5.93 0.546 5.21
110 4.99 0.39 3.75 4.77 0.354 2.84 5.33 0.44 3.77 6.53 0.661 6.25
120 5.45 0.46 4.45 5.21 0.421 3.35 5.81 0.52 4.45 7.12 0.787 7.38
130 5.90 0.54 5.19 5.64 0.495 3.90 6.30 0.62 5.19 7.71 0.923 8.61
140 6.35 0.63 6.00 6.08 0.574 4.50 6.79 0.71 5.98 8.31 1.07 9.92
150 6.81 0.72 6.87 6.51 0.659 5.13 7.28 0.82 6.82 8.90 1.23 11.3
160 7.26 0.82 7.79 6.94 0.749 5.80 7.76 0.93 7.72 9.49 1.40 12.8
Source: Courtesy, Cameron Hydraulic Data Book.
AUGUST 2012 Read, Learn, Earn 7
hf = (5.14) (0.494) = 2.54 ft
Te static head, or diference in elevation, is 310 ft 31 ft = 279 ft. Te
static head, in this case, is considered a loss. (As mentioned earlier, the
lower reference point in this case is the pump center line.)
Since the fow is against gravity and the static head must be over-
come, the total discharge head loss (h
d
) is:
h
d
= 52.65ft(lossinpipe)+2.54ft(lossinfttings)
+ 279 ft (static head) = 334.19 ft
Adding together the losses on both sides of the pump, the total pres-
sure loss in the system (h
T
) is as follows:
h
T
= 7.27 ft (suction head) + 334.19 ft (discharge head)
= 341.46ft
tAble VerIFICAtIon
In Example 3-5, we obtained the pipe friction value from a neat and
orderly table. Tese tables, however, are the result of a great deal of cal-
culation based on the Darcy-Weisbach formula. Another similar for-
mula is the Hazen and Williams empirical formula. Te Hazen-Williams
formula is referred to as empirical because it is based on laboratory and
feld observation. Te Hazen and Williams pressure loss formula is as
follows:
Equation 3-5
hf = (0.002083)(L)(
100
)
1.85
(
Q
1.85
)
___
____
C
d
4.8655
where: hf = Friction in pipe, ft/100 ft
0.002083 = Empirically determined coefcient
L = Length of pipe, ft (in this case, 100 ft)
C = Roughness coefcient based on the
pipe material (see Table 3-5)
Q = Flow, gpm
d = Pipe diameter, in.
Example 3-6 To ensure that the values given in the tables for Exam-
ple 3-5 are correct, calculate the friction loss using the Hazen and Wil-
liams formula and the following data:
L = 100 ft
C = 150
d = 3 in.
Q = 130gpm
Solution 3-6 Plug the data into the Hazen and Williams formula:
hf = (0.002083)(100)(
100
)
1.85
(
130
1.85
) = 3.8 ft
150
_____
3
4.8655
Te value used from the table was 3.90 ft per 100 ft, which is very
close to the one just calculated (3.80 ft per 100 ft). Tis exercise dem-
onstrates that, for all practical purposes, the table may be used with
confdence.
AlternAtIVe solutIon
Tere is another, easier and faster way to solve the hydraulic prob-
lem given in Example 3-5. It involves using equivalent length for ft-
tings(seeTable3-6).Tiseasieralternativeisdefnedasanequivalent
length of straight pipe that has the same friction loss as the respective
ftting or valve.
Various piping books and publications may indicate slightly diferent
equivalent length values for the same ftting. Tese diferences are usu-
ally small and, therefore, negligible. If a certain type of ftting cannot
be found in an available table, an approximate value can be estimated
based on a similar ftting. Te equivalent value (length) can also be
obtained from the fttings manufacturer.
Example 3-7 Solve the same problem given in Example 3-5, but use
the equivalent length for fttings and valves and make the calculation
for the total head loss for the entire system (suction and discharge). Te
system data remain the same.
Solution 3-7 Te developed length of pipe, or the actual measured
length, is:
1350 ft (discharge) + 8 ft (suction) = 1358 ft
Forthisapplication,andbasedonTable3-6,theequivalentlengths
for fttings and valves are listed below:
Fittings Number
Equivalent
Length Each
Fitting (ft)
Total
Equivalent
Length (ft)
3-in. foot valve (same as
swing-check valve)
1 25.50 25.50
90 elbow 4 7.67 30.68
45 elbow (long radius) 2 4.09 8.18
3-in. gate valve 1 2.04 2.04
3-in. swing-check valve 1 25.50 25.50
Sharp pipe exit (estimate) 1 17.50 17.50
Total 109.40
Now add the total equivalent length for fttings to the actual pipe
length as follows:
1358ft+109.4ft = 1467.4ft=totalequivalentlengthofpipe
Terefore, the total friction loss in pipe and fttings is:
(1467.4ft)(
3.9 ft
) = 57.22 ft
100 ft
Te total diference in elevation of the water levels (static head) is
equal to 310 ft 25 ft = 285 ft; therefore, the total head (pressure) loss is
57.22 ft + 285 ft = 342.22 ft.
Compare the previous value of 341.46 ft, which was obtained in
Example 3-5 using the K resistance coefcients, to the value of 342.22
ft, which was obtained using the equivalent length method. Te cal-
culations are equivalent; therefore, it is easier to use the equivalent
length method when solving plumbing problems. Keep in mind that
these results are based on an engineering calculation in which minor
approximations are acceptable.
Tese examples have shown that by knowing the fow, pipe diameter,
system confguration, and pipe material, it is possible to calculate the
head, or friction, loss in the system. When calculating a problem like
this, consider that the piping system will age, so add in a safety factor of
10 to 15% to establish the correct value for selecting the pump. Tus, a
value of approximately 380 ft is required for the selection of the pump
head (342.22 ft + 37.78 ft). Te pump head value and the pump fow
(previously given as 130 gpm) are used in the selection of the pump.
PumP SelectioN
Te objective of the examples given above was to determine the correct
pump size for a system. A pump is a mechanism that is used to push
a liquid with a specifc force to overcome system friction loss and any
existing diference in elevation. Te pump produces this force with the
help of a motor or driver and consumes energy in this process. Te type
of pump usually employed in plumbing systems is a centrifugal pump
with all wetted parts made of nonferrous material.
8 Read, Learn, Earn AUGUST 2012
READ, LEARN, EARN: The Properties of Water and Hydraulics
Te pumps housing is referred to as the casing.
Te casing encloses the impeller and collects
the liquid being pumped. Te liquid enters at the
center, or eye, of the impeller. Te impeller rotates
and, due to the centrifugal force created, pushes
the liquid out. Te velocity is the greatest at the
impellers periphery where the liquid is discharged
through a spiral-shaped passage called the volute.
Tis shape is designed so that there is an equal
velocity of the liquid at all circumference points.
Tecapacity(Q)ofapumpistherateoffuidfow
delivered, which is generally expressed in gallons
per minute (gpm).
Te total head (H) developed by a pump is the
discharge head (hd) minus the suction head (hs):
Equation 3-6
H = hd hs
Te suction head may be a negative or positive
value depending on the pump location, water level,
and the pressure of water entering the pump. Te
data obtained for head loss and fow of the system
are the two elements used in pump selection.
To select a pump for the system described in
Example 3-5, look at the pump curve in Figure 3-9.
For this system, we need a pump that will deliver
130 gpm against a head of 380 ft (or 380 0.433 =
164psi).Tepumpinthiscasewillbeacentrifugal
pump.
On this pump curve, the fow delivery capacity in
gallons per minute (gpm) is located on the horizontal axis (abscissa).
Te pump head (measured in ft and/or psi) is located on the vertical
axis (ordinate). Te pumps efciency percentage is shown on parallel
curves on the upper part of the diagram. In our case, the efciency of
theselectedpumpiscloseto60%.Teelectricmotorhorsepower(hp)
is marked on the lines slanted down to the right. Since our value falls
between two lines, we will choose the higher value of 30 hp. Te impel-
ler diameter along the vertical lines helps us select a 7b in. diameter
impeller. Te possibility that more capacity may be required at a later
date must be considered in pump selection.
Each pump manufacturer provides a serial or model number
for easy pump identifcation. Pump data sheets, such as the
one shown in Figure 3-9, also indicate the number of revolu-
tions per minute (rpm). In our case, it is 3500 rpm. Another
element in pump selection is the Net Positive Suction Head
(NPSH) (see Appendix B). Tis element is connected with the
pump priming. If necessary, the pump manufacturer can ofer
help with the pump selection, usually free of charge. For such
assistance, contact the local representative.
If we calculate the fow and the head required in a plumb-
ing system design and take into account the available city
water pressure (city water pressure must be deducted from the
required pump head), it is possible to determine if a pump is
needed.
When there is some initial, incoming pressure, but the system
requires a higher operating pressure, the pump required is
a booster pump. For example, if the pressure required by a
system is 100 psi and 50 psi is received from the city, the booster pump
must have a head of at least 50 psi. Add 10% of the total pressure as a
safetyfactor,andthepumpselectedshouldbefor60psihead.
Example 3-8 Calculate the outlet pressure in the system shown in
Figure 3-10, in which water fows by gravity. Te technical data is as
follows:
Waterfow(Q):50gpm
Pipe diameter: 2 in.
Pipe material: Type K copper tubing
Pipe length: 380 linear ft (developed length)
Fittings: Two gate valves; one sudden contraction (from the
tank into the pipe); one sudden enlargement (discharge
open to the atmosphere); one 30 elbow; one 45 elbow
Diference in elevation: 150 ft (static head)
Solution 3-8 From the table in Appendix B, the fow of 50 gpm of
water in a 2-in. diameter, Type K copper tubing (pipe) has a velocity of
5.32 ft/sec: and a friction loss of 5.34 ft per 100 ft.
Te following table shall help in calculating using the equivalent
length of pipe method described earlier:
4
Te total equivalent length of the pipe and fttings is:
380 ft + 29 ft = 409 ft
Friction loss in the pipe and fttings is:
(409 ft)(
5.34 ft
) = 21.84 ft
100 ft
Table 3-5 Values of the Constant C Used in
Hazen and Williams Formula
Values of C
Pipe Material Average Normally
Range Value Used Value
Bitumastic-enamel-lined steel 130160 148 140
centrifugally applied
Asbestos-cement 140160 150 140
Cement-lined iron or steel 150 140
centrifugally applied
Copper, brass, or glass, as well as 120150 140 130
tubing
Welded and seamless steel 80150 140 100
Wrought iron, cast iron 80150 130 100
Tar-coated cast iron 50145 130 100
Concrete 85152 120 100
Full riveted steel (projecting rivets in 115 100
girth and horizontal seams)
Corrugated steel 60 60
Value of C 150 140 130 120 110 100 90 80 70 60
For (100/C) at 1.85 power is 0.47 0.54 0.62 0.71 0.84 1 1.22 1.5 1.93 2.57
Equiv. Length, Total Equiv.
Fittings Quantity Each Fitting (ft) Length (ft)
2-in. gate valve 2 1.38 2.76
Sudden contraction
(estimated length as a standard
tee through the branch) 1 10.30 10.30
Sudden enlargement
(estimated length as a standard
tee through the branch) 1 10.30 10.30
45 elbow 1 2.76 2.76
30 elbow (estimated to be the
same as 45 elbow) 1 2.76 2.76
Total Equivalent Length for Fittings 28.88 ft
AUGUST 2012 Read, Learn, Earn 9
Given the diference in elevation of 150 feet, the outlet pressure is:
150ft21.84ft = 128.16ft
128.16 = 55.48 psi
2.31
Te diference in elevation (static head) in this gravity-fow example
(or in any other downhill fow) assists the fow because the weight of
the water column pushes the water down toward the discharge. Tis is
the reason the friction is deducted from the static head.
Example 3-9 Calculate the same problem given in Example 3-8,
only this time with a fow of 200 gpm. All other data remains the same.
Based on the table in Appendix B, the velocity is 21.3 ft/sec, and the
frictionis65.46ft/100ft.Note: A velocity of 21.3 ft/sec is unacceptable,
but it is used here for illustrative purposes.
Solution 3-9 From Example 3-9, we determined that the equivalent
length of the pipe and fttings is 409 ft. Terefore, the friction loss in the
pipe and fttings is:
(409 ft)(
65.46ft
) = 267.73ft
100 ft
Given the diference in the elevation of 150 feet, the outlet pressure
has a negative value:
150ft267.73ft = 117.73ft
Te result of the calculations means that 200 gpm cannot fow through
the system because the pipe diameter is too small and the friction is too
high for such fow. Water will fow, but only at a maximum rate of 145
gpm. Tis value can be mathematically calculated as follows:
(
x ft
)(409 ft) = 150 ft static head
100 ft
x = (150 ft)(100 ft) = 36.67ft
409 ft
From Appendix B, for a 2-in. Type K copper tube at the friction calcu-
lated above, the corresponding fow is approximately 145 gpm.
meaSuremeNtS
Te following is a short list of some useful units of measurement:
Acceleration of gravity = 32.2 ft/sec
2
Table 3-6 Equivalent Lengths for Pipe Fittings
Nominal Gate Globe Butterfy Angle Swing- 90 Long Close Standard Standard Mitre Bend
Pipe Valve Valve Valve Valve Check Elbow Radius Return Tee Tee ______ __________
Size Valve, 90 & 45 Bend
Full Full Full Full Std Elbow Through Branch 45 90
Open Open Open Open Flow Flow
0.41 17.6 7.78 5.18 1.55 0.83 2.59 1.0 3.1
0.55 23.3 10.3 6.86 2.06 1.10 3.43 1.4 4.1
1 0.70 29.7 13.1 8.74 2.62 1.40 4.37 1.8 5.3
1 0.92 39.1 17.3 11.5 3.45 1.84 5.75 2.3 6.9
1 1.07 45.6 20.1 13.4 4.03 2.15 6.71 2.7 8.1
2 1.38 58.6 7.75 25.8 17.2 5.17 2.76 8.61 3.5 10.3 2.6 10.3
2 1.65 70.0 9.26 30.9 20.6 6.17 3.29 10.3 4.1 12.3 3.1 12.3
3 2.04 86.9 11.5 38.4 25.5 7.67 4.09 12.8 5.1 15.3 3.8 15.3
4 2.68 114 15.1 50.3 33.6 10.1 5.37 16.8 6.7 20.1 5.0 20.1
5 3.36 143 18.9 63.1 42.1 12.6 6.73 21.0 8.4 25.2 6.3 25.2
6 4.04 172 22.7 75.8 50.5 15.2 8.09 25.3 10.1 30.3 7.6 30.3
8 5.32 226 29.9 99.8 33.3 20.0 10.6 33.3 13.3 39.9 10.0 39.9
10 6.68 284 29.2 125 41.8 25.1 13.4 41.8 16.7 50.1 12.5 50.1
12 7.96 338 34.8 149 49.7 29.8 15.9 49.7 19.9 59.7 14.9 59.7
14 8.75 372 38.3 164 54.7 32.8 17.5 54.7 21.8 65.6 16.4 65.6
16 10.0 425 31.3 188 62.5 37.5 20.0 62.5 25.0 75.0 18.8 75.0
18 16.9 478 35.2 210 70.3 42.2 22.5 70.3 28.1 84.4 21.1 84.4
20 12.5 533 39.2 235 78.4 47.0 25.1 78.4 31.4 94.1 23.5 94.1
24 15.1 641 47.1 283 94.3 56.6 30.2 94.3 37.7 113 28.3 113
30 18.7 70 37.3 117 46.7 140 35 140
36 22.7 85 45.3 142 56.7 170 43 170
42 26.7 100 53.3 167 66.7 200 50 200
48 30.7 115 61.3 192 76.7 230 58 230
Figure 3-10 Gravity System
10 Read, Learn, Earn AUGUST 2012
READ, LEARN, EARN: The Properties of Water and Hydraulics
Figure 3-9 Pump Curves
1 ft
3
H
2
0=62.3lb
1 gal = 0.1337 ft
3
1 gal H
2
0 = 8.33 lb (at 70F)
1 ft
3
= 7.48 gal
Terefore:
1 ft
3
=(7.48)(8.33)=62.3lb
1atm=14.696~14.7lb/in.
2
or psi = 29.92 in. Hg (mercury)
1atm=33.96ftofwater
1 ft of H
2
00.433=1psi(seenote#5)
notes
1
Standard M20, Water Chlorination Principles and Practice, issued
by the American Water Works Association (AWWA) gives all the
required details for chlorination and disinfection.
2
Inmostplumbingapplications,avelocityof6ft/secorlessisadvis-
able. Pipe sizes based on this velocity usually give years of trouble-free
operation.
3
Normally, the diference in elevation (static head) is from water
level to water level or to a water discharge outlet elevation.
4
Some manuals give slightly diferent equivalent lengths for copper
tubing fttings than for steel, but the diference is small enough that
the same table may be used.
5
Te conversion value of 0.433 is derived from the following:
0.433 = 14.7 psi Reciprocal: l psi = 2.31 ft of H
2
O
33.96ft
AUGUST 2012 Read, Learn, Earn 11
READ, LEARN, EARN: The Properties of Water and Hydraulics
CE Questions
The Properties of Water and Hydraulics (CEU 190)
_______ describes the movement of water 1.
in nature.
evaporation a.
transpiration b.
precipitation c.
hydrological cycle d.
During project development, you must 2.
frst determine _______ to calculate the
amount of water needed for a building.
occupancy needs a.
building size b.
type of building c.
ratio of men to women d.
The upper layers of the Earths crust is 3.
called what?
impermeable strata a.
permeable strata b.
water table c.
bedrock d.
Which of the following is a physical 4.
property of water?
density a.
boiling point b.
viscosity c.
all of the above d.
What is the density of water at 70F? 5.
62.408 lb/ft a.
3
62.300 lb/ft b.
3
61.998 lb/ft c.
3
61.203 lb/ft d.
3
_______ is the amount of potential energy 6.
due to the elevation of water above a
certain reference point.
velocity head a.
kinematic viscosity b.
static head c.
laminar fow d.
Reading the article and completing the form will
allow you to apply to ASPE for CEU credit. If you
earn a grade of 90 percent or higher on the test,
you will be notified that you have logged 0.1
CEU, which can be applied toward CPD renewal
or numerous regulatory-agency CE programs.
(Please note that it is your responsibility to deter-
mine the acceptance policy of a particular agency.)
CEU information will be kept on fle at the ASPE
ofce for three years.
ASPE Continuing Education Application Form
this form is valid up to one year from date of publication. expiration date: Continuing education credit will be given for this examination
through august 31, 2013. Applications received after that date will not be processed.
submit this form with payment via mail (Aspe read, learn, earn, 2980 s. river road, des plaines, Il 60018), fax (847-296-2963), or email
aspeeducation@aspe.org.
please print or type; this information will be used to process your credits.
name ______________________________________________________________________ Aspe membership no. ______________
organization ___________________________________________________ daytime telephone _____________________________
billing Address ________________________________________________________________________________________________
City _________________________________________ state/province ________________________ zip ______________________
e-mail _______________________________________________________________________ Fax ____________________________
pe state _____________________________________________ pe no. _________________________________________________
notice for north Carolina professional engineers: state regulations for registered pes in north Carolina now require you to complete Aspes online Ceu validation form
to be eligible for continuing education credits. After successfully completing this quiz, just visit Aspes Ceu Validation Center at aspe.org/CeuValidationCenter.
I certify that I have read the article indicated
above.
signature
payment:
member: Free
nonmember: each examination: $35
personal Check (payable to Aspe)
business or government check
DiscoverCard VISA MasterCard AMEX
If rebilling of a credit card charge is necessary, a $25
processing fee will be charged.
Aspe is hereby authorized to charge my Ce
examination fee to my credit card
Account number
expiration date
signature
Cardholders name (please print)
________ is a resistance coeffcient for 7.
pipe fttings.
Reynolds number a.
K factor b.
Manning coeffcient c.
none of the above d.
What is the head loss per 100 feet of 8.
Schedule 80 steel pipe fowing at 50
gallons per minute?
1.21 feet a.
1.03 feet b.
0.86 feet c.
0.734 feet d.
What is the K factor for a 90-degree 9.
standard elbow?
0.29 a.
0.54 b.
0.14 c.
1 d.
What is the normally used C value for 10.
concrete pipe?
60 a.
120 b.
115 c.
100 d.
What is the equivalent length of a 11.
90-degree elbow for a 2-inch pipe?
5.17 feet a.
6.17 feet b.
7.67 feet c.
10.1 feet d.
The center of a pump impeller is called 12.
the _______.
volute a.
casing b.
eye c.
none of the above d.
Circle the correct answers below.
12 Read, Learn, Earn AUGUST 2012
C
E
U
1
9
1
Solar
Energy
Continuing Education from the
American Society of Plumbing Engineers
SEPTEMBER 2012
ASPE.ORG/ReadLearnEarn
OUR SUN
Diameter: 864,000 miles (1,390,473 km)
Mass: 438 trillion, trillion, billion pounds (1.99 trillion,
trillion, billion kg)
Surface temperature: 5,800K (9,980F)
Core temperature: 15,600,000K (28,079,540F)
Energy output: 386 billion, billion mega watts per sec-
ond
Distance from Earth: 93,000,000 miles (149,668,992
km)
Power level at Earth: 1.4 kilowatts per square meter or
440 British thermal units (Btu) per square foot
The Sun hits Earth with enough energy every minute to
meet the needs of the worlds population for an entire year.
Earth is populated with more than 6.5 billion people, and
the population is growing at a rapid rate, even though the
rate of increase actually has been declining since the 1980s.
It is estimated that the global population will reach 9 billion
people around 2045. Beyond the increase in the population
itself are higher rates of increase in industry to support this
population and the nations that are emerging into the indus-
trial age. One of the downsides to this industrial growth is
its insatiable appetite for energy. Fossil resources are fnite,
while appetites for consumption are not.
The biggest leap in energy consumption will come from
emerging economies such as China and India, where popula-
tions are expected to grow by 25 percent over the next two
decades and economic output and standards of living also will
rise dramatically. Energy demand in China and India alone
is expected to double by 2025, but the issue isnt limited to
developing countries.
Canada is the No. 1 country for use of energy per capita.
The United States is in second place per capita and uses a
tremendous amount of energy. The United States is home to
4 percent of the worlds population but consumes 25 percent
of the worlds energy. As the more developed countries con-
tinue to prosper, it is only natural that their energy needs
will continue to grow accordingly.
A POSSible SOlUtiON
To reduce dependence on fossil fuels, the use of renewable
energy sources must increase. Some progress is being made.
For instance, solar panels are now compulsory on all new
and renovated buildings in Spain as part of the countrys
efforts to update its building codes and to meet the growing
demand for energy.
The sun bombards Earth with an enormous amount of
energy continuously. If this energy source is tapped, it could
provide free energy.
WHAt iS SOlAR eNeRGY?
The Earth bathes in a variety of energy wavelengths and par-
ticles from the sun, but for the purposes of this chapter, solar
energy is a renewable, environmentally friendly resource in
the form of heat and light. Solar energy is available every-
where on Earth, at least part of the time, and this energy is
provided free of charge. It just needs to be harvested and used
to provide heat, lighting, mechanical power, and electricity.
Various methods of harnessing the suns abundant and
clean energy are available. Energy from the sun, for these
purposes, can be categorized in two ways:
Thermal energy (heat)
Light energy (photovoltaics)
Solar thermal technologies use the suns heat energy to
heat substances (such as transfer fuids or panels) for ap-
plications such as space heating, pool heating, and domestic
water heating. Many products are on the market that utilize
thermal energy. Often the products used for this applica-
tion are called solar thermal collectors and can be mounted
on the roof of a building or in some other sunny location.
The suns heat also can be used to produce electricity on a
large utility-scale by converting the suns heat energy into
mechanical energy.
Light energy can be converted directly into electrical
current through photovoltaic devices. Photovoltaics (PV)
is a technology often confused with solar thermal and is in
fact what many people mean when they refer to solar en-
ergy. Photovoltaics (photo = light, voltaics = electricity) is
a semiconductor-based technology (similar to the microchip)
that converts light energy directly into an electric current
that can be used either immediately or stored, such as in a
battery or capacitor, for later use. PV panels and modules
are very versatile and can be mounted in a variety of sizes
and applications (e.g., on a roof or awning of a building, on
roadside emergency phones, or as very large arrays consisting
of multiple panels and modules). Currently they are being
integrated into building materials, such as PV roofng mate-
rial, which replaces conventional roofng shingles.
How much energy is needed to heat water?
1 kilowatt will raise 4.1 gallons of water 100 degrees in
one hour (4.1 gph at 100T).
1 watt is approximately 3.41 Btuh.
1 kilowatt is 3,412 Btuh.
1,000 Btuh is approximately 293 watts.
1 Btu will heat 1 pound of water 1 F.
Reprinted from Plumbing Engineering Design Handbook, Volume 3. 2011, American Society of Plumbing Engineers.
Note: In determining your answers to the CE questions, use only the material presented in the corresponding continuing education
article. Using information from other materials may result in a wrong answer.
2 Read, Learn, Earn SEPTEMBER 2012
READ, LEARN, EARN
How Can Solar Help?
Research shows that an average household with an electric
water heater spends about 25 percent of its home energy
costs on heating water. Solar water heaters offer the largest
potential savings, with solar water heater owners saving as
much as 50 percent to 85 percent annually on their utility
bills over the cost of electric water heating. A simple payback
of four to eight years can be expected on a well-designed and
properly installed solar water heater. (Simple payback is the
length of time required to recover the investment through
reduced or avoided energy costs.)
The United States spends more than $13 billion a year on
energy for home water heating. That is the equivalent of 11.4
barrels of oil per householdmore than the amount of oil (in
the form of gasoline) burned by a medium-size automobile
driven 12,000 miles. See Figure 10-1 for a breakdown of how
the use of solar energy compares to other energy sources.
Solar water heaters do not pollute. Specifying a solar wa-
ter heater system prevents carbon dioxide, nitrogen oxides,
sulfur dioxide, and the other air pollution and wastes created
when the utility generates power or fuel is burned to heat
the domestic water. When a solar water heater replaces an
electric water heater, the electricity displaced over 20 years
represents more than 50 tons of avoided carbon dioxide
emissions alone.
environmental impact: What is being Saved?
Consider a family of four with a hot water demand of 60 us-
ages per day. They install a solar collector system with two
collectors and an 80-gallon storage tank and an expected
minimum system lifetime of 20 years. The solar energy
supplied is 11,010,000 Btu per year, so the energy supplied
in 20 years is 220,200,000 Btu. The emissions reduction in
20 years is:
16.5 tons of carbon dioxide
3330 lbs of nitrous oxides
1950 lbs of carbon monoxide
Does it Work for Commercial Applications?
Solar is being used by more businesses every day in applica-
tions ranging from heating water to providing a reliable and
clean power source. A business can save 40 to 80 percent on
electric or fuel bills by replacing a conventional water heater
with a solar water-heating system. Solar energy also provides
other benefts to business such as power security, enabling
a business to continue operating even when outside utility
power is disrupted.
Concentrating solar power plants generate electricity by
using the heat from solar thermal collectors to heat a fuid
that produces steam used to power the generator.
Why Use Solar?
A solar energy system can be used to help earn two LEED
credits:
SS Credit 7.1: Heat Island, Non-roof, one credit
E&A Credit 2: Renewable Resources, one to seven
credits
Solar energy also reduces reliance on natural gas or elec-
tricity for water heating with a sustainable source of free
energy and reduces pollution emissions.
tax Credits
Tax credits are constantly changing and evolving. Be sure
to check for the current local, state, and federal incentives.
Many sources for this information are available, including:
On-site Renewables Tax Incentives: energytaxincentives.
org/business/renewables.php
Database of State Incentives for Renewables and Ef-
fciency: dsireusa.org
Guide to Federal Tax Incentives for Solar Energy: seia.
org (member login required)
DeFiNitiONS
The following terms are frequently employed in solar energy
technology and related applications.
Figure 10-1 The Role of Renewable Energy in the U.S. Energy Supply
Source: U.S. Energy Information Administration
SEPTEMBER 2012 Read, Learn, Earn 3
Collector, transpired A south-facing exterior wall covered
by a dark sheet-metal collector. The collector heats outside
air, which is then drawn into the buildings ventilation
system through perforations in the collector. They have
been used for preheating ventilation air and crop drying.
They are inexpensive to make, and commercially have
achieved effciencies of more than 70 percent.
Collector, trickle A fat-plate collector over which non-
pressurized liquids fow
Collector effciency The ratio of the energy collected (or
absorbed) to the total solar energy incident on the collec-
tor, expressed in percent
Collector subsystem That portion or assembly of the solar
system used for absorbing incident solar radiation, con-
verting it to thermal energy and transferring this thermal
energy to a heat-transfer fuid. The collector subsystem
includes the solar collectors, related piping or ducts, and
regulating devices.
Collector tilt The angle above the horizontal plane at which
a solar collector is mounted, in degrees
Concentrating ratio The ratio of the aperture area to the
absorber of a solar collector
Concentrator A refector, lens, or other optical device in
concentration solar collectors used to focus the incident
solar energy on the reduced absorber area
Conduction A heat-transfer process by which heat fows
from a region of higher temperature to a region of lower
temperature within a solid, liquid, or gaseous medium
by molecular contact or between different media having
a direct physical contact
Convection A heat-transfer process in which heat is trans-
ferred from one region to another by motion of a fuid
Convection, forced A convection transfer process caused
by mechanical devices, such as fans and injectors
Convection, free A convection transfer process caused by
density differential within a fuid, without involvement
of any mechanical devices
Cooling system The complete assembly of subsystems re-
quired to convert solar energy into other forms of energy
for space cooling purposes
Cover, collector The transparent material placed over the
aperture or absorber area of a solar collector to provide
protection from the environment and reduce thermal
losses from radiation or convection
Distribution subsystem The portion of a solar system from
the storage subsystem to the point of ultimate use, includ-
ing the related piping or ducts and regulating devices
emittance The fraction of heat radiated by the solar col-
lector, measured in percent of the absorbed energy by
the panel
emissivity The ratio of the radiation emitted by a surface
to the radiation emitted by a black body at the same
temperature
energy transport subsystem The portion of a solar system
that contains the heat-transfer media and transports the
energy throughout the solar system, including related
piping and regulating devices
Heat exchanger A device designed for transferring heat
between two physically separated fuids
Absorber area The total heat transfer area from which the
absorbed solar radiation heats the transfer fuid or the
absorber media if both transfer fuid and solid surfaces
jointly perform the absorbing function, in square feet
(m
2
)
Absorber (plate) The part of the solar collector that re-
ceives the incident solar radiation energy and transforms
it into thermal energy. In some cases, the heat transfer
fuid itself could be the absorber.
Absorptance The ratio of the absorbed fux to the total
incident fux, measured in terms of percent
Angle of incidence The angle between the line of direct
solar irradiation and the perpendicular to the aperture
plane, in degrees
Angle of refection The angle between the refected rays
propagation direction and the perpendicular to the surface
at the point of refection, in degrees
Angle of refraction The angle between the refracted rays
propagation direction and the perpendicular to the inter-
face at the point of refraction, in degrees
Area, aperture The maximum projected area of a solar
collector through which un-concentrated solar radiant
energy is admitted, in square feet
(m
2
)
Area, gross collector The maximum projected area of a
solar collector module including any integral mounting
devices, in square feet
(m
2
)
Auxiliary energy subsystem A confguration of equip-
ment and components, utilizing conventional energy
sources, to supplement the output of the solar system
Collector A device used to absorb the suns energy
Collector, concentrating A collector that uses refectors,
lenses, or other optical devices to concentrate the radi-
ant solar energy passing through the aperture onto an
absorber of which the surface area is smaller than the
aperture area. Parabolic trough-shaped refectors concen-
trate sunlight onto an absorber or receiver to provide hot
water and steam, usually for industrial and commercial
applications.
Collector, fat plate A non-concentrating collector in which
the absorbing surface is essentially planar and usually
with approximately the same area as the aperture. Small
tubes run through the box and carry fuideither water
or another fuid such as an antifreeze solution. The tubes
attach to a black absorber plate. As heat builds up in the
collector, the fuid passing through the tubes is heated.
The hot transfer liquid goes to a storage tank, and water
is heated as it passes through a tube inside the storage
tank full of hot fuid. This is the most common type of
collector for solar water heating.
Collector, evacuated tube (vacuum tube) A collector
consisting of rows of parallel transparent glass tubes,
each containing an absorber and covered with a selective
coating. Sunlight enters the tube, strikes the absorber,
and heats the liquid fowing through the absorber. These
collectors are manufactured with a vacuum between the
tubes, which helps them achieve extremely high tempera-
tures (170350F). Their high effciency makes them a
good choice for commercial uses.
4 Read, Learn, Earn SEPTEMBER 2012
READ, LEARN, EARN: Solar Energy
Heat pump A device designed to simultaneously or alter-
nately use the heat extracted at a low temperature and
the heat rejected at a high temperature for cooling and
heating purposes
Heat-transfer medium A fuid used in the transport of
thermal energy
Heating and cooling system The complete assembly of
subsystems required to convert solar energy into ther-
mal energy and utilize this energy, in combination with
auxiliary energy (if necessary), for combined heating and
cooling purposes
Heating system The complete assembly of subsystems
required to convert solar energy into thermal energy and
utilize this energy, in combination with auxiliary energy
(if necessary), for heating purposes
Hot water system The complete assembly of subsystems
required to convert solar energy into thermal energy and
utilize this energy, in combination with auxiliary energy
(if necessary), for service water heating
infrared radiation Radiation with wavelengths greater
than 70 millionths centimeter (7,000 Angstrom units)
but less than radio waves, about 5.5 centimeters
irradiation (insolation), instantaneous The quantity of
solar radiation incident on a unit surface area in a unit of
time, in Btuh per square foot (W/m
2
)
insolation The solar radiation striking the surface of Earth
or another planet. Also the rate of delivery of solar radia-
tion per unit of horizontal surface (see irradiation).
Performance factor effciency The ratio of the useful
output capacity of a system to the input required to
obtain it
Radiant emittance (exitance) The quotient of the radi-
ant fux leaving an element of the surface containing the
point by the area of that element
Radiant fux Power emitted, transferred, or received in the
form of electromagnetic waves or photons
Radiant intensity The quotient of the radiant fux emitted
by a source (or by an element of a source in an infni-
tesimal cone containing the given direction) by the solid
angle of the cone
Radiation The heat-transfer process by which heat fows
from a body at a higher temperature to a body at a lower
temperature, when the bodies are separated in space
or when a vacuum exists between them (emission or
transfer of energy in the form of electromagnetic waves
or photons)
Selective surface A coating applied to a solar collector, or
its absorber area, having a high absorptance and a low
emittance
Solar absorptance The fraction of the solar irradiance
that is absorbed
Solar constant The solar radiation intensity that is incident
on a surface normal to the suns rays, outside the Earths
atmosphere, at a distance from the sun equal to the mean
distance between the Earth and the sun. The accepted
valued of the solar constant is equal to 428.8 Btuh per
square foot (1,353 W/m
2
).
Solar degradation The process by which exposure to sun-
light deteriorates the properties of materials
Solar energy The photon (electromagnetic) energy origi-
nating from the sun
Solar system Equipment and components arranged in a
manner to collect, convey, store, and convert solar en-
ergy
Solar system, air A solar system that uses air as the pri-
mary heat-transfer fuid
Solar system, active A solar system in which the inci-
dent solar radiation is absorbed by the solar collectors,
transferred to an independent thermal storage unit,
and distributed to the point of ultimate use by means of
mechanical devices powered by conventional fuels (i.e.,
pumps and fans)
Solar system, closed A solar system that has a completely
enclosed collector subsystem circulating the heat-transfer
fuid under pressure above atmospheric and shut off from
the atmosphere, except for an expansion tank
Solar system, liquid A solar system that uses liquid as the
primary heat-transfer fuid
Solar system, open A solar system that exchanges heat
directly with the end-use application
Solar system, passive A solar system in which solar energy
utilization becomes the prime objective of engineering
and architectural design. The fow of heat is achieved by
natural convention, conduction, and radiation
Solar system, thermosyphon A passive solar system in
which fuids circulate due to their temperature differen-
tials, rather than under the infuence of pumps or fans
Storage device (thermal) The containers, including all
contents of such containers, used for storing thermal
energy. Heat-transfer fuid, heat exchangers, fow-control
devices, valves, baffes, etc. that are integral with the
thermal storage container are regarded as parts of the
storage device.
Storage medium (thermal) The material in the thermal
storage device, independent of the containing structure,
in which the major portion of the energy is stored
Storage subsystem The assembly of components neces-
sary for storing energy so it can be used when required,
including all related regulating devices used in connec-
tion thereof
Subsystem A major, separable, and functional assembly or
portion of a system
thermosyphon The natural circulation of a fuid caused by
temperature differentials within the fuid system
transfer fuid, heat The medium that fows through a
solar collector and carries the absorbed energy away from
the collector
transmittance The ratio of fux transmitted through a
material to the incident fux
Ultraviolet radiation Radiation with wavelengths from
180 to 400 m (Angstrom units)
Watt An energy per second unit (1 watt = 1 joule per sec-
ond)
SOMe QUiCK eStiMAtiNG
CAlCUlAtiONS
Following are some estimates that can be used in calcula-
tions:
SEPTEMBER 2012 Read, Learn, Earn 5
One direct hour of sunlight = 1 kilowatt-
hour per square meter
1 kilowatt-hour = 3,412 Btu
1 gallon of #2 fuel oil = 150,000 Btu
1 square meter = 10.6 square feet
One 4x8 collector (approximately) = 3
square meters
One 4x8 collector (approximately) =
1215 kilowatt-hours per day
QUiCK COSt COMPARiSONS
Tables 10-1 and 10-2 illustrate two simple
spreadsheets used to estimate costs for differ-
ent solar systems. Many variables and other
project-specifc items are not taken into ac-
count within these calculations, so the actual
cost of a system will be higher. This is only
to provide a general idea of the magnitude of
the differences among the systems.
A plethora of information is available via
the Internet, books, and magazines to assist
in the design of solar systems. Some of this
information can be found within this chapter;
however, a more complete understanding will
come only through further research.
SYSteM SiZiNG RUleS OF
tHUMb
Approximately 440 Btuh per square foot of
energy generated by the sun could potentially
reach the Earth (see Figure 10-2). Of that
potential energy, 30 to 60 percent is lost in
the journey through the atmosphere, and
170 to 315 Btuh per square foot eventually
reaches the surface.
For example, Chicago receives 1,260 to
1,575 Btu per square foot per day of energy
from the sun. For optimum output, panels should be installed
at a 45-degree angle and face south. The optimum output
from a panel is roughly 220 Btuh per square foot. The amount
of energy disbursed by the sun fuctuates with sunspot ac-
tivity and solar storms, but the maximum available energy
from a collector is generally considered to be 220 Btuh per
square foot.
SOlAR iRRADiAtiON COlleCtiON
MetHODS
The solar collector is the main component of the active solar
irradiation collection subsystem (see Figure 10-3). It is the
device that absorbs the incoming solar energy, converts it to
heat, and transfers this heat to a fuid (liquid or air) fowing
through the solar collector. To absorb or collect this energy,
several different panel or collector styles are available, which
can be classifed into three general categories:
Flat-plate solar collectors: Non-concentrating collectors
in which the absorbing surface is essentially planar and
is approximately equal to the gross collector area
Concentrating solar collectors: Collectors that use
mirrors, lenses, refectors, or other optical devices to
concentrate the radiant solar energy passing through
the collectors aperture onto an absorber of which the
absorber area is smaller than the aperture area
Vacuum tube solar collectors: Collectors that use sealed
vacuum tubes, which operate via a self-contained vapor
reaction to heat a condenser at the end of the tube and
transmit heat through a small, integral heat exchanger
through a manifold through which the fuid (water and/
or glycol) circulates
Flat-plate Solar Collectors
A typical fat-plate solar collector unit consists of the follow-
ing basic elements:
One or more collector covers (glazing), transparent to
the incoming incident solar radiation and opaque to
the infrared radiation from the absorber plate. These
are intended to protect the absorber plate from the
environment and to act as a shield to reduce radiative
and convective heat losses from the absorbing surface.
Glass and plastic typically are the materials utilized for
collector covers.
An absorber plate (surface), usually incorporating chan-
nels (conduits) containing the heat-transfer fuid, used
to absorb the suns incident radiation and to transfer
Table 10-1 Solar Cost Comparison, Method A
Solar Collector (Flat Plate) Cost Total Cost
Total kilowatts
Watts per
square foot
Square
feet
Cost per watt
200 63 3,200 1 $200,000
PV Panel Cost Total Cost
Total kilowatts
Watts per
square foot
Square
feet
Cost per watt
200 16 12,500 10 $2,000,000
PV Roof Material Cost Total Cost
Total kilowatts
Watts per
square foot
Square
feet
Cost per watt
200 4 50,000 10 $2,000,000
Table 10-2 Solar Cost Comparison, Method B
Solar Collector (Flat Plate) Cost Total Cost
Square feet
Watts per
square foot
Total
kilowatts
Cost per watt
3,200 63 200 1 $200,000
PV Panel Cost Total Cost
Square feet
Watts per
square foot
Total
kilowatts
Cost per watt
12,500 16 200 10 $2,000,000
PV Roof Material Cost Total Cost
Square feet
Watts per
square foot
Total
kilowatts
Cost per watt
50,000 4 200 10 $2,000,000
6 Read, Learn, Earn SEPTEMBER 2012
READ, LEARN, EARN: Solar Energy
the energy (heat) to the fuid medium in the channels.
Metals and plastics have been used in the construction
of absorber plates, which are sometimes coated with
a selective surface fnish having high-absorptivity and
low-emissivity factors. Extreme care should be exercised
when selecting a metal for the construction of the ab-
sorber plates. Each material has its own characteristics,
which may induce galvanic corrosion. Also, it should be
noted that the thermal conductivities of plastics are less
than those of metals. Therefore, plastic materials should
be limited to low-temperature applications (e.g., swim-
ming pool heating).
Thermal insulation, placed behind the absorber plate
and channel assembly and surrounding the perimeter
of the solar collector module, used to reduce heat losses
and increase radiation on the absorber plates and chan-
nel assembly
A backplate, which is placed behind the insulation and
acts as a refector surface, used to reduce heat losses and
increase radiation on the absorber plates and channel
assembly. Aluminum and foil refectors are the materials
generally used in the construction of backplates.
Headers (manifolds), which are used to convey the
absorbed energy. To ensure steady fow conditions, the
headers should have a cross-sectional area larger than
the area served by the channels. Metals and plastics are
the materials commonly utilized in the construction of
the headers.
A frame, including angle-fxing and mounting devices,
etc., enclosing the complete solar collector module
Many confgurations of fat-plate solar collectors are avail-
able. For example, the absorber plate/channel assembly could
be of fn design or corrugated sheets, with channels above,
channels below, or channels as integral parts with the absorber
plate. Also, fat-plate modules used in swimming pool heat-
ing applications (low temperature/high water volume) do not
normally require a covers, backplate, or insulation by design.
The absorber plate, channel assembly, and headers are the
only elements necessary.
The amount of incident solar energy (radiation) collected
is governed by the following criteria:
Transmittance of the collectors covers, which should
exceed 90 percent of the solar spectrum
Absorptivity factor of the absorber plate to the incident
solar radiation, which should exceed 95 percent
Emissivity factor of the absorber plate in the infrared
spectrum
Thermal resistance between the absorber plate and the
heat-transfer medium
Reduction of the conductive, convective, and radiative
heat (thermal) losses from the panel, which depends on
the operating temperature of the panel, usually ranging
from 90210F (32.298.8C) or higher
The most widely used measure of the performance of fat-
plate collectors is thermal effciency (q), which is defned as
the ratio of delivered heat to the incident solar radiation.
However, it should be noted that the thermal effciency of
a fat-plate solar collector is not a suffciently descriptive
index to select a unit module. The most important proper-
ties of a fat-plate solar collector are the collector operating
temperature, type of collector surface, and type and number
of collector covers.
The steps for determining the thermal effciency of a
fat-plate solar collector, including the necessary data, are
as follows:
To calculate the incident beam component of insolation
normal to the collector (Ib,coll) and the diffuse com-
ponent of insolation (Ih,d), obtain the insolation on a
horizontal surface (Ih), cloud cover (CC), solar altitude
angle (a), collector tilt angle (E), and latitude (L).
To calculate the absorbed radiation (Icoll), obtain the
number of collector covers (n).
To calculate the delivered energy to working fuid (qa),
obtain the wind speed (v) in knots (m/s), collector temper-
ature (Tcoll) in R, and collector physical properties.
The following equations should be used in calculating the
thermal effciency:
Equation 10-1
l
b,coll =
I
h,b(cos i)/sin a
Equation 10-2
I
h,d = 0.78 + (1.07) a + (6.17) CC
Equation 10-3
I
coll =
I
b,coll(l Pbn)
s,b +
I
h,d (l Pd)
s,d
Equation 10-4
qa =
I
coll L
t
Equation 10-5
= q/(
I
b,coll +
I
h,d)
where:
I
b,coll = Incident beam component of insolation normal to
the collector surface, Btuh per square foot (W/m
2
)
I
h,b = Horizontal beam component of insolation, Btuh per
square foot (W/m
2
)
i = Angle of incidence, degrees
a = Solar altitude angle, degrees
I
h,d = Diffuse component of insolation, Btuh per square
foot (W/m
2
)
CC = Cloud cover, tenths (1/10) of sky covered
I
coll = Absorbed radiation, Btuh per square foot (W/m
2
)
Pbn = Refectance from several covered sources
F
c
=
A
p
=
I
F
c
di
A
i
1
where:
= Incidence angle i at mirror sunrise
The value of the concentration factor obtained from Equa-
tion 10-6 does not take into account surface irregularities in
the refecting mirror. In actual practice, the absorber may be
fve or six times greater than the theoretical value to compen-
sate for surface irregularities in the refecting mirror and to
absorb some diffuse radiation on cloudy or hazy days.
When comparing a fat-plate collector system and a SRTA
system, it is imperative that a complete system analysis be
performed. One does not pay for the surface area, but rather
for the amount of heat or useful energy delivered per unit
surface area. A cost comparison between a fat-plate collector
and a SRTA system can be made on the following:
Equation 10-7
(
Afp
)
(cost per ft
2
of fat-plate collector)
fp
Equation 10-8
d
2
a
cost per ft
2
of mirror surface
SRTA
= Effciency of stationary refector tracking absorber
collector, percent
Figure 10-3 How Solar Energy Is Collected
Figure 10-2 Amount of Suns Energy that Reaches the Earth
8 Read, Learn, Earn SEPTEMBER 2012
READ, LEARN, EARN: Solar Energy
The cost of the SRTA absorber is prorated on a mirror sur-
face area basis. For complete cost comparisons, the cost of the
entire solar system for each design should be considered.
Compound Parabolic Concentrator
The compound parabolic concentrator (CPC) system was de-
veloped by Roland Winston (Argonne National Laboratories
in Argonne, Illinois). The CPC is a non-tracking solar collec-
tor consisting of two sections of a parabola of second degree,
symmetrically located about the mid-plane of a collector. The
two sections form a single curvature solar concentrator with
an angular acceptance of 2 (
max
). The acceptance depends on
the ratio of aperture area (W
c
) to the absorber area (W
a
) and
is expressed by the relation:
Equation 10-9
max
= sin
-1
(
W
a
)
W
c
where
max
= Maximum acceptance
W
a
= Absorber area, square feet (m
2
)
W
c
= Aperture area, square feet (m
2
)
The concentration ratio (CR) of the CPC system can be
determined by the expression:
Equation 10-10
CR =
W
e
W
a
This collector system should be oriented in an east-west
direction and tilted toward the south at an angle (E) from
the horizontal plane. When the angle (y) is less than A
max
,
the CPC collector accepts both direct and diffuse components
of sunlight. When the angle is greater than A
max
, the CPC
collector accepts only diffuse sunlight over the portion of the
aperture area equal to the absorber area. Beam insolation
incident on a CPC collector outside the acceptance angle does
not reach the absorber area, but is refected from the side
walls back through the aperture.
The theoretical depth of the CPC collector (dcoll) depends
on the concentration ratio and is defned by the expres-
sion:
Equation 10-11
d
coll
= W
a[
(CR+1)
]
[(CR1)
]
2
In actual practice, it has been found advantageous to use
a value of dcoll that is one-third smaller than that calculated
from Equation 10-11.
SYSteM SiZiNG AND CAlCUlAtiONS
Several computer simulation design programs are cur-
rently available for sizing solar-assisted service water- and
space-heating systems. In this chapter, the f-chart method
developed by the University of Wisconsin is used for sizing
such systems. The f, expressed in terms of percent, is the
fraction of the heating load supplied by solar energy or the
percentage of the total heating load furnished by the solar
system. These design charts are calculated utilizing double-
glazed, selective-surface collector panels. Other types of solar
collectors (e.g., single-glazed selective surface; double-glazed
non-selective surface; single-glazed non-selective surface)
could be used. However, the data for developing the charts
must be varied accordingly.
The following data is required when employing the f-chart
method in the sizing procedures: number of degree days,
ambient temperature, building heat loss (if space heating is
being considered), hot water demand, collector orientation,
and design parameters of the system.
Solar-assisted Service Water Heating
Solar-assisted service water-heating systems generally
provide maximum savings when the system is designed to
deliver 45 to 70 percent of the load (f = 45 to 70 percent). To
determine the amount of energy required to heat the service
water, the following information is needed:
Hot water supply temperature
Cold water supply temperature
Daily hot water demand
To meet the requirements set forth in the Federal Housing
Administrations Minimum Property Standards, the hot water
supply temperature must be 140F (60C) minimum. This
also helps reduce waterborne pathogens such as Legionella.
Depending on the season and geographical location, the cold
water supply temperature may vary from 40F to 70F (4.4C
to 21.1C), although it is possible to have lower or higher tem-
peratures. This should always be considered when calculating
water heating or cooling applications.
Although many system types, applications, and design
techniques may be considered for various service water-
heating requirements, a few basic guidelines should be
followed in all cases.
Systems should be designed to be as simple and as fea-
sible as possible for each specifc application.
Match system design to load patterns and magnitude,
and avoid misuse of design rules of thumb.
Consider system efficiency, as well as collector effi-
ciency.
All phases of a systems control cycle should be examined
for potential operational and energy waste problems.
Plan for component expansion, movement, and service
during system design.
Sizing Procedure for Service Water Heating
The following steps should be followed when sizing a solar-
assisted service water-heating system.
1. Determine the daily hot water demand.
2. Determine the hot water supply temperature. Generally,
this temperature can be taken as 140F (60C).
3. Determine the cold water supply temperature. This
temperature typically ranges from 40F to 70F (4.4C to
21.1C), depending on the season and geographical loca-
tion. In the absence of such data, assume this temperature
to be 45F (7.2C) as a year-round average.
4. Determine the closest weather station location and pre-
pare an f-chart. A sample f-chart is illustrated in Figure
10-4. Data on degree days and percent f at the collection
point may be obtained from the ASHRAE Handbook of
Fundamentals and the Solar Decision Handbook.
SEPTEMBER 2012 Read, Learn, Earn 9
5. Determine the percent f to be delivered by the solar
system.
6. Using the f-chart, determine the size of the collector
array (in square feet [m2]) required to provide the de-
sired percent f. The following calculations will provide
approximate values, as indicated.
To determine the fow rate of the heat-transfer fuid in
the collector loop, multiply the collector area by 0.039
(0.027 in SI units).
To determine the maximum heat transfer to the heat
exchanger, multiply the collector area by 225 (709.6 in
SI units).
To determine the size of the preheater tank, multiply
the collector area by 2 (81.4 in SI units).
7. Determine the pump head in the collector loop.
8. Determine the pump head in the storage loop.
9. Determine the volume of heat-transfer fuid required.
10. To determine the size of the expansion tank needed,
multiply the volume of the heat-transfer fuid by 10
percent.
Figures 10-5 and 10-6 illustrate typical installations of
solar-assisted service water-heating systems.
Example 10-1
Location: Memphis, Tennessee
Family of four, standard kitchen and bathroom
Step 1: Determine the daily hot water demand, approxi-
mated as 15 gallons per person per day (56.8 L per person
per day). For four persons, the daily hot water demand
would be 60 gallons (227.2 L).
Step 2: Determine the hot water supply temperature. To
meet FHA requirements, this temperature should be 140F
(60C).
Step 3: Determine the cold water supply temperature. This
temperature can be assumed to be 45F (7.2C).
Step 4: Develop an f-chart. See Figure 10-7.
If 60 percent of the load is to be supplied by the solar
system, approximately 35 square feet (3.3 m
2
) of collector
area is required. The fow rate of the heat-transfer fuid in
the collector loop would be 35 ft
2
0.039 = 1.4 gpm (3.3
m
2
0.027 = 0.09 L/s). The maximum heat transfer to the
heat exchanger would be 35 ft
2
225 = 7,875 Btuh (3.3 m
2
709.6 = 2,341.7 W).
Sizing Procedure for Service Water and Space
Heating
The following steps should be followed when sizing a
combined solar-assisted service water- and space-heating
system.
1. Calculate the building heat loss. ASHRAE-recommended
methods should be used.
2. Determine the buildings design temperature. This tem-
perature is the lowest outside air temperature, in F (C),
at which the building must be heated to 65F (18.3C).
3. Calculate the buildings design load. This load is the
product of the buildings heat loss and the buildings
design temperature.
4. Determine the daily hot water demand, hot water sup-
ply temperature, and cold water supply temperature.
Follow steps 1, 2, and 3 given for service water-heating
systems.
5. Determine the closest weather station and prepare an
f-chart.
6. Determine the percent f to be delivered by the solar
system.
7. Determine the size of the collector array, in square feet
(m2), required to provide the desired percent f using the
chart.
8. Determine the fow rate of the heat-transfer fuid in the
collector loop, maximum heat-transfer fuid in the collec-
tor loop, maximum heat transfer to the heat exchanger,
and the size of the storage tank. Use step 6 of the service
water-heating procedure.
9. Determine the pump head in the collector loop and stor-
age loop.
10. Determine the pump head for the entire heat-delivery
loop (preheater, to and from storage tank, etc.).
11. Determine the fan coil size. The output of the fan coil
should be equal to or greater than the buildings design
load.
12. Select a heat pump with an output equal to or greater
than the buildings design load.
13. Select an auxiliary heater with an output equal to or
greater than the buildings design load.
Figure 10-8 provides illustrations of combined systems.
Keys to Sizing
Building load: What is the daily water demand?
Building occupancy: On average, how many days per
week is the building occupied?
Location
Safety measures/devices
Example 10-2
An apartment building occupied at all times has 64 units
using 30 gpd each (1,920 gpd total). If one 30-square-foot
panel generates 30,000 Btu per day in the summer, how
many panels are needed?
30,000 Btu / 8.34 pounds per gallon / (120F 60F) =
60 gallons at a 60F rise per panel
1,920 gpd / 60 = 32 solar panels
Example 10-3
For the same apartment building, how much storage is
needed?
30,000 Btu / 8.34 pounds per gallon / (150F 60F) =
40 gallons at a 90F rise per panel
40 x 32 panels = 1,280 gallons of storage
Keys to Performance
When laying out the panels, consider the following to ensure
peak performance.
What is the fow rate through a panel?
How do off-peak loads affect temperature and control?
What temperature does the sensor see?
10 Read, Learn, Earn SEPTEMBER 2012
READ, LEARN, EARN: Solar Energy
How big is the piping (heat loss, installation cost)?
How effcient is the system?
PANel lAYOUtS AND PiPiNG
ARRANGeMeNtS
Panels in Parallel/Arrays in Parallel
32 panels = Eight arrays (see Figure 10-9)
11.5 gpm per panel = 3248 gpm total
22-inch pipe
Vents on cold water
Sensor low at end
10F band in summer; 24F in lower months
Panels in Series/Arrays in Parallel
32 panels = Eight arrays (see Figure 10-10)
11.5 gpm per panel = 3248 gpm total
22-inch pipe
One vent on hot water
Sensor high at end
10F band in summer; 24F in lower months
Panels in Series/Arrays in Series
32 panels = Eight arrays (see Figure 10-11)
11.5 gpm per panel = 812 gpm total
11-inch pipe
Vents at high points
Sensor high at end
40F band in summer; 1020F in lower months
illustrations
Figures 10-12, 10-13, and 10-14 illustrate a dual water
heater installation with one storage tank, a dual water
heater installation with two storage tanks, and a detail of
the solar panel array.
SPeCiFiCAtiONS
The specifcations are an important part of any system
design. Several formats are used today. Always coordinate
and verify the specifcation format that is to be used for a
project.
In the current Construction Specifcations Institute (CSI)
format, plumbing is found in the 220000 sections. Some of
the sections that may be included in a solar water heater
system specifcation follow. Note that a system may require
sections other than those listed. These are only listed as an
example.
220500 Common Work Results for Plumbing
22053 General Duty Valves for Plumbing
220529 Hangers and Supports for Plumbing
220533 Freeze Protection for Plumbing Piping
220548 Vibration and Seismic Controls for Plumbing
Piping and Equipment
220553 Identifcation for Plumbing Pipe and Equip-
ment
230993.13 Controls Point List
Regardless of the format used, the basic objectives and
requirements are the same. The following may serve as a
guideline to writing specifcations for a solar system.
Collectors
Manufacturer and model number
Number of covers
Performance characteristics
Testing agency and test method followed
Stagnation conditions
Recommended fow rate
Operating temperatures
Pressure drop at maximum fow rate
Materials
Glazing
Gaskets
Insulation
Absorber plate
Selective coating
Recommended heat-transfer fuid
Physical dimensions
Module size
Aperture area
Weight
Expected collector life
Warranty
Heat exchangers
Manufacturer and model number
Construction
Recommended heat-transfer fuid
Warranty
Expected life
Materials
Physical dimensions
Performance
Testing agency and test method followed
Operating conditions
Flow rate
SQUARE FEET (M
2
) OF COLLECTOR
50
(4.7)
100
(9.3)
150
(13.9)
200
(18.8)
250
(23.2)
10
20
30
40
50
60
70
80
90
100
6
0
G
A
L
L
O
N
S
(
2
2
7
.
1
L
)
8
0
G
A
L
L
O
N
S
(
3
0
2
.
8
L
)
1
2
0
G
A
L
L
O
N
S
4
5
4
.2
8
L
)
%
F
Figure 10-4 Sample f-chart, Service Water Heating Application
SEPTEMBER 2012 Read, Learn, Earn 11
Pressure drop
Temperature
Pressure
Pumps
Manufacturer and model number
Motor coupling
Mechanical seal
Warranty
Estimated life
Pump body and impeller Material
Gasketing materials
Motor voltage
Amperage
Operating conditions
Flow rate
Pressure drop
Temperatures
Pressure
Pump curves
Flange connections
Preheater tanks
Manufacturer and model number
Storage capacity
Body material
Lining
Insulation
Plumbing connections
Jacket
Sacrifcial anode
Physical size
Auxiliary heater
Pressures
Weight
Warranty
Estimated life
Operating temperatures
Storage tanks
Manufacturer and model number
Capacity
Operating temperatures
Storage medium
Freezing precautions
Lining
Working pressure
Materials of construction
Insulation
Plumbing connections
Jacket
Physical dimensions
Pressures
Weight
Drain valves
Manhole
Live and dead loads
Warranty
Estimated life
SOLAR
RADIATION
1. SOLAR COLLECTORS
2. CIRCULATING PUMP
3. TEMPERATURE/PRESSURE
RELIEF VALVE
4. PUMP CONTROLLER
5. SENSOR: COLLECTOR
TEMPERATURE
6. SENSOR: TANK TEMPERATURE
7. CHECK VALVE
8. HEAT EXCHANGER
9. STORAGE TANK
10. AUXILLARY HEAT SOURCE
11. WATER SUPPLY
12. TO BUILDING
1
3
9
12
11
10
3
LEGEND
7
5
8
6 4
2
Figure 10-6 Pump Circulating System, Service Water Heating
Application, Direct
SOLAR
RADIATION
1. SOLAR COLLECTORS
2. TEMPERATURE/PRESSURE
RELIEF VALVE
3. STORAGE TANK
4. HEAT EXCHANGER
5. WATER SUPPLY
6. AUXILLARY HEAT SOURCE
7. TO BUILDING
1
2
4 3
7
5
6
2
LEGEND
Figure 10-5 Thermosyphon System, Service Water Heating
Application, Indirect
12 Read, Learn, Earn SEPTEMBER 2012
READ, LEARN, EARN: Solar Energy
Controls
Manufacturer and model number
Differential thermostat
Sensor
Available functions
Power input
Approvals and listings
Ground provisions
Warranty
Estimated life
Heat Pumps
Manufacturer and model number
Pump type
Rated heat and cooling output
Rated heat and cooling coeffcient of performance and
energy-effciency ratio
Auxiliary heaters
Filters
Operating voltage and amperage
Condenser coil operating range and fow rate
Physical dimensions
Weight
Operating sequence
Warranty
Estimated life
insulation
Manufacturer and type (material)
Heat transfer characteristics/thickness
Flame spread and smoke-developed characteristics
Vapor barrier/cover
Method of application
Warranty
ADDitiONAl ReADiNG AND OtHeR
ReSOURCeS
A bounty of information is available to assist in the de-
sign of solar systems. A more complete understanding
will come through further research.
The Solar Hydrogen Civilization by Roy McAlister
Solar Energy Industries Association: seia.org
Energy Star: energystar.gov
Internal Revenue Service: irs.gov
TIAP: energytaxincentives.org
Solar Rating Certification Corporation (SRCC):
solar-rating.org
U.S. Department of Energy, Energy Effciency and
Renewable Energy: eere.energy.gov
Solar and Sustainable Energy Society of Canada:
sesci.ca
Canadian Solar Industries Association: cansia.ca
Kortright Centre for Conservation: kortright.org
ReFeReNCeS
ASHRAE Handbook 1989 Fundamentals, American
Society of Heating, Refrigerating, and Air-Conditioning
Engineers, Atlanta, GA.
Duffe, J. A. and Beckman, W. A., Solar Energy Thermal
Processes, Interscience Publishers, New York, NY, 1974.
Kreider, J. F. and Kreith, J., Solar Heating and Cooling,
McGraw-Hill, New York, NY, 1975.
ASHRAE 93: Standard of Testing to Determine the Performance
of Solar Collections, American Society of Heating, Refrig-
erating, and Air-Conditioning Engineers, Atlanta, GA,
1986.
Montgomery, R. H. and Budnick, J., Solar Decision Book, Dow
Coming Corporation, Midland, MI,1978.
ASHRAE 90A: Energy Conservation in New Building Design,
American Society of Heating, Refrigerating, and Air-Con-
ditioning Engineers, Atlanta,GA, 1975.
Beckman, W. A., Klein, S. A., and Duffe, J. A., Solar Heating
Design by the f-Chart Method, Wiley-Interscience, New
York, NY, 1977.
Kreider, J. F., The Solar Heating Design Process, McGraw-Hill,
New York, NY, 1982.
Solar Design Workbook, Solar Energy Research Institute,
Golden, CO, 1981.
Solar Energy System Design, American Society of Plumbing
Engineers, Westlake, CA, 1980.
Tully, G. F., Solar Heating Systems, McGraw-Hill, New York,
NY, 1981.
U. S. Department of Energy, Active Solar Energy System Design
Practice Manual, Solar/0802-79/01, NITS, Springfeld,
VA, 1979.
ASHRAE Handbook 1988 Equipment, American Society of
Heating, Refrigerating, and Air-Conditioning Engineers,
Atlanta, GA.
ASHRAE Handbook 1987 Systems and Applications, Ameri-
can Society of Heating, Refrigerating, and Air-Conditioning
Engineers, Atlanta, GA.
Solar Water Heaters: A Buyers Guide Natural Resources
Canada, Ottawa: Minister of Supply and Services, 1987.
SQUARE FEET (M
2
) OF COLLECTOR
50
(4.7)
100
(9.3)
150
(13.9)
200
(18.8)
250
(23.2)
10
20
30
40
50
60
70
80
90
100
P
E
R
C
E
N
T
O
F
L
O
A
D
P
R
O
V
I
D
E
D
B
Y
S
O
L
A
R
S
Y
S
T
E
M
,
%
F
Figure 10-7 f-chart for Memphis, Tennessee
SEPTEMBER 2012 Read, Learn, Earn 13
SOLAR
RADIATION
1
3
9
12
10
3
1. SOLAR COLLECTORS
2. CIRCULATING PUMP
3. TEMPERATURE/PRESSURE RELIEF VALVE
4. PUMP SWITCH
5. SENSOR: COLLECTOR TEMPERATURE
6. SENSOR: TANK TEMPERATURE
7. HEAT EXCHANGER
8. STORAGE TANK
9. WATER SUPPLY
10. AUXILLARY HEAT SOURCE
11. HOT WATER TO BUILDING
12. FORCED AIR FURNACE
13. HEATING COIL
14. DUCT
15. WARM AIR TO BUILDING
16. SERVICE WATER HEATER
LEGEND
7
6
8
5 4
2
3
10
9
7 16
11
7
13
2
Figure 10-8 Pump Circulating System, Combined Space and Service Water Heating Applications
14 Read, Learn, Earn SEPTEMBER 2012
READ, LEARN, EARN: Solar Energy
Noble, Duncan and Robert K. Swartman, The Canadian Renew-
able Energy Guide, Burnstown: General Store Publishing
House, 1995.
Figure 10-9 Panels in Parallel/Arrays in Parallel
Figure 10-10 Panels in Series/Arrays in Series
Figure 10-11 Panels in Series/Arrays in Series
SEPTEMBER 2012 Read, Learn, Earn 15
READ, LEARN, EARN: Solar Energy
Figure 10-12 Dual Water Heater with Solar Tank
Figure 10-13 Dual Water Heater with Dual Solar Tanks
16 Read, Learn, Earn SEPTEMBER 2012
Figure 10-14 Solar Panel Array Installation
SEPTEMBER 2012 Read, Learn, Earn 17
READ, LEARN, EARN: Solar Energy
CE Questions Solar Energy (CEU 191)
Energy from the sun can be categorized 1.
as ________.
thermal energy a.
light energy b.
fossil fuel c.
both a and b d.
Solar represents what percent of the total 2.
U.S. energy supply?
8 a.
7 b.
5 c.
1 d.
Which type of collector has achieved 3.
effciencies of 70 percent or more
commercially?
fat plate a.
evacuated tube b.
transpired c.
concentrating d.
_______ is power emitted, transferred, or 4.
received in the form of electromagnetic
waves or photons.
radiation a.
radiant fux b.
emittance c.
insolation d.
Which of the following is an important 5.
property of a fat-plate solar collector?
collector operating temperature a.
type of collector surface b.
type and number of collector covers c.
all of the above d.
An advantage of the concentrating 6.
collector over the fat-plate collector is
________.
lower maintenance costs a.
smaller absorber area b.
lower operating costs c.
none of the above d.
Solar-assisted service water-heating 7.
systems generally provide maximum
savings when f = ________.
Reading the article and completing the form will
allow you to apply to ASPE for CEU credit. If you
earn a grade of 90 percent or higher on the test,
you will be notified that you have logged 0.1
CEU, which can be applied toward CPD renewal
or numerous regulatory-agency CE programs.
(Please note that it is your responsibility to deter-
mine the acceptance policy of a particular agency.)
CEU information will be kept on fle at the ASPE
ofce for three years.
ASPE Continuing Education Application Form
This form is valid up to one year from date of publication. Expiration date: Continuing education credit will be given for this examination
through September 30, 2013. Applications received after that date will not be processed.
Submit this form with payment via mail (ASPE Read, Learn, Earn, 2980 S. River Road, Des Plaines, IL 60018), fax (847-296-2963), or email
aspeeducation@aspe.org.
Please print or type; this information will be used to process your credits.
Name ______________________________________________________________________ ASPE Membership No. ______________
Organization ___________________________________________________ Daytime telephone _____________________________
Billing Address ________________________________________________________________________________________________
City _________________________________________ State/Province ________________________ Zip ______________________
E-mail _______________________________________________________________________ Fax ____________________________
PE State _____________________________________________ PE No. _________________________________________________
Notice for North Carolina Professional Engineers: State regulations for registered PEs in North Carolina now require you to complete ASPEs online CEU validation form
to be eligible for continuing education credits. After successfully completing this quiz, just visit ASPEs CEU Validation Center at aspe.org/CEUValidationCenter.
I certify that I have read the article indicated
above.
Signature
Payment:
Member: Free
Nonmember: Each examination: $35
Personal Check (payable to ASPE)
Business or government check
DiscoverCard VISA MasterCard AMEX
If rebilling of a credit card charge is necessary, a $25
processing fee will be charged.
ASPE is hereby authorized to charge my CE
examination fee to my credit card
Account Number
Expiration date
Signature
Cardholders name (Please print)
40 a. percent
4570 percent b.
40 c. 75 percent
100 percent d.
When sizing a solar-assisted service 8.
water-heating system, multiply the
collector area by what to determine the
size of the preheater tank?
2 a.
10 b.
15 c.
20 d.
A pump circulating system for a direct 9.
service water-heating application
includes which of the following
components?
air vent a.
heating coil b.
heat exchanger c.
none of the above d.
When sizing a combined solar-assisted 10.
service water- and space-heating system,
the output of the fan coil should be
equal to or greater than what?
fow rate of heat transfer fuid a.
building design load b.
size of collector array c.
hot water demand d.
A pump circulating system for combined 11.
space and service water-heating
applications includes which of the
following components?
heat exchanger a.
temperature/pressure relief valve b.
storage tank c.
all of the above d.
Which of the following should be 12.
included in the specifcation for the
storage tanks?
capacity a.
working pressure b.
operating sequence c.
both a and b d.
Circle the correct answers below.
18 Read, Learn, Earn SEPTEMBER 2012
C
E
U
1
9
2
Acoustics in
Plumbing
Systems
Continuing Education from the
American Society of Plumbing Engineers
OCTOBER 2012
ASPE.ORG/ReadLearnEarn
Plumbing system noise is a common irritant to building own-
ers and tenants. Three main factors often contribute to this
problem: 1) Lack of awareness on the part of owners/developers
and design teams regarding application of specifc products and
practical installation solutions; 2) lack of contractor awareness
and training regarding application of specifc solutions; and
3) design teams fearful of uncertain solutions and seemingly
uncontrollable expenses. On many high-end projects, building
design teams and contractors have faced litigation as a result
of insuffcient or poorly installed attempts at plumbing noise
mitigation.
In the past few years, much advancement has been made
regarding the issue of plumbing noise mitigation. Resources
are now available from a product and service standpoint that
can assist the engineering community with identifcation of ap-
plication solutions, plumbing installation detail drawings, and
third-party laboratory test data to recognized ISO standards.
If commonly implemented, a holistic approach to this issue
ultimately will contribute to a marketplace more acceptable
to plumbing systems that include noise and vibration solution
components.
In the eyes of a building occupant or a perspective buyer,
the perceived quality of a building is based on numerous ob-
servations. A building that seems noisy likely is viewed as low
quality. In cases where building occupants are dissatisfed
with the comfort of a building, one of the common complaints
includes noise from adjoining tenants. Noise through foor
and ceiling systems and noise through walls are usually the
culprits. The noise sources and solutions are widely varied.
Some of the solutions are very diffcult and costly to remedy,
especially after the fact. Most engineers and architects would
agree that a quiet building does not happen accidentally and
that taking steps to ensure success must be planned from the
early stages of specifcation and building design.
Some noise issues have been addressed quite success-
fully through common methods for many years, such as
advancements in foor systems and a variety of party wall
confgurations. However, one area of noise mitigation that
continues to be addressed with inconsistent levels of success
is plumbing system noise. Plumbing noise is one of the most
intrusive and diffcult sounds to mitigate. It is this issue and
related solutions that this chapter addresses, including:
1. Why plumbing system noise is diffcult to remedy
2. Identifcation of common sources of plumbing system
noise
3. A review of common attempts to mitigate plumbing
system noise
4. Proven acoustical materials, techniques, and resources
5. Steps the engineer can take to ensure success on the
job
In many peoples eyes, varying levels of plumbing noise
are expected and tolerated without complaint. Most often, the
noise generated within a tenants own space and resulting from
ones own use of plumbing fxtures is tolerated. On the other
hand, when plumbing noise is a result of an adjoining space and
results in sleep disturbance or interruption of peace and quiet,
it quickly becomes an annoyance. In multifamily settings, it is
a main reason that tenants complain to their neighbors, move,
or, even worse, decide to sue the builder.
Most noise issues within a building relate to either airborne
noise or structure-borne noise. Airborne noise typically comes
from common sound sources such as voices, televisions, and
radios. The noise performance of a building system is called
the Sound Transmission Class (STC). The higher the STC,
the better the system is at isolating airborne noise. An STC
rating of 45 means that the element reduces the sound pass-
ing through it by 45 decibels (dB). (See Table 10-1.) Mass is
required to solve airborne noise.
Structure-borne noise, also referred to as impact noise, is
produced when part of the building fabric is directly or indirectly
impacted. Energy passes through the building structure and
creates noise in nearby rooms. Examples are heavy footsteps
(particularly on bare timber or hard foor surfaces like tile),
banging doors, scraping furniture, vibrations from loud music,
and plumbing noise. The Impact Insulation Class (IIC, see Table
10-2) is used to rate the impact noise insulation of foors. Solving
structure-borne noise is the complete opposite of solving airborne
noise: It is not so much the function of mass as it is the function
of isolation and vibration breaks.
Various building codes such as the Uniform Building Code
(UBC) and International Building Code (IBC) contain require-
ments for sound isolation between dwelling units in Group R
occupancy projects (including apartments and condominiums).
However, these criteria are not universally enforced. The codes
require walls and foor/ceiling assemblies to have both an STC
and IIC rating of 50 (if tested in a laboratory) or 45 (if tested in
the feld). The feld test evaluates the dwellings actual construc-
tion and includes all sound paths. (Note: Even if a particular
municipality has not adopted this part of the code, it typically
is recognized as an industry minimum standard.)
THE OVERALL MARKET IMPRESSION
OF THE PROBLEM
Plumbing system noise mitigation often is considered by en-
gineers, building owners, and contractors to be a complicated,
labor-intensive, and expensive problem to resolve. Thus, the is-
Reprinted from Plumbing Engineering Design Handbook, Volume 1. 2009, American Society of Plumbing Engineers.
Note: In determining your answers to the CE questions, use only the material presented in the corresponding continuing education
article. Using information from other materials may result in a wrong answer.
2 Read, Learn, Earn OCTOBER 2012
READ, LEARN, EARN
sue of controlling plumbing noise unfortunately is viewed as
economically unfeasible. Because many engineers and contrac-
tors are in a quandary as to best materials and best practices
and are often in disagreement as to what is considered fair
market value to perform the this work, many building owners/
developers shy away from including plumbing acoustics in the
projects scope of work.
The fact of the matter is that it does not have to be diffcult
or expensive. Recent advancements regarding the availability
of products and support services now make the mitigation of
plumbing system noise easier, more effective, and more afford-
able than ever before.
A WIDE VARIETY OF CONTRIBUTING
FACTORS
The fact that plumbing systems generate both airborne and
structure-borne noise makes the problem fairly complex. Follow-
ing are the four main categories comprising a buildings plumbing
system and how these systems create noise.
Drainage Systems
This category includes sanitary waste piping receiving drain-
age from plumbing fxtures and appliances at varying rates
and volumes, as well as rain leader/roof drain piping receiving
drainage from roof drains, deck drains, and similar receptacles
at varying rates and volumes.
Drainage piping is manufactured with a variety of materials
that each radiate airborne and structure-borne noise at vary-
ing levels. The most common pipe and ftting materials used in
these systems within buildings include Schedule 40 PVC or ABS
plastic DWV, type DWV copper, several weight classifcations of
cast iron (usually no hub), and tubular thin-wall PVC, ABS, or
chrome-plated brass (used in the fxture outlet connection/p-trap
location under sinks and similar fxtures).
Drainage piping receiving gravity fow includes roof
drains, rain leaders, deck drains, condensate drains, and
sanitary drains receiving fow from typical plumbing fxtures
such as sinks, wash basins, toilets, bathtubs and showers.
Drainage piping receiving liquids intermittently and under pres-
sure include discharge from laundry washers, dishwashers, and
funnel drains in mechanical rooms, foor sinks in commercial
food service establishments, and similar indirect waste recep-
tacles. In each of these cases, the density and wall thickness
of the pipe and fttings has a direct bearing on the amount
of both airborne and structure-borne noise generated. The
thicker and more dense the pipes wall construction, the
quieter is its performance.
In a gravity system, drainage liquid traveling vertically
adheres to the outside walls of the pipe and travels in a spiral
motion. In this mode, very little noise is generated. The fow of
the pipes contents generates the most noise when liquids and
solids hit fttings at changes in direction within the piping system,
especially when a vertical stack hits a horizontal pipe. It is most
noticeable in plastic drainage systems.
Drainage piping also generates noise, especially in plastic
systems, when it experiences thermal expansion and contrac-
tion due to temperature changes. (PVC and ABS pipe expands
and contracts at approximately fve to eight times the rate of
cast iron pipe.) The pipe can be heard creaking or squeaking
as it moves and rubs against various building components,
especially if the penetrations in the wall and ceiling framing
are cut or drilled to a size that results in a tight ft. An example
of this would be when a roof drain system within the warmth
of a building receives cold rainwater. In this case, the piping
contracts as the rainwater lowers the pipes temperature. After
the rainwater stops fowing, the pipe warms up and expands
once again. As this occurs, structure-borne noise transmits
to the interior of the building through various contact points
throughout the system, such as foor, wall, and ceiling penetra-
tions and at various support or hanger locations.
Water Distribution Systems
Water distribution systems include domestic/potable water
piping delivering water under pressure to plumbing fxtures
and appliances throughout a building, nonpotable water
piping delivering water under pressure to systems such as
irrigation and mechanical equipment, and industrial water,
process piping, and HVAC piping each delivering water under
pressure to various equipment components within a building.
Water piping/tubing is constructed from a variety of
materials that each radiate airborne and structure-borne
noise at varying levels. The most common pipe and ftting
materials used in these systems within buildings include cop-
per (Types M, L, or K), CPVC, PEX, PVC Schedule 40 or 80
(typically in nonpotable water systems), galvanized or black
iron, Schedule 10, 40, or 80 (typically nonpotable), corrugated
or smooth wall chrome-plated brass (for fxture connections),
and braided stainless steel (at fxture and equipment supply
connections).
A common cause for noise generation in a water system
is simply the fow of water due to the operation of a fxture or
faucet. In this scenario, several factors contribute to increased
levels of noise generation: water pressure, fow velocities, un-
dersized tubing, turbulence caused by changes in direction, and
obstructions in valves and equipment. The largest contributing
factor is direct contact between the water systems tubing and
the buildings various components.
Another common noise generator is water hammer, which
results when water moving at a high velocity stops suddenly.
This occurs when valves are closed quickly, producing a shock
wave in the system that causes the pipes to vibrate. Some
Table 10-2 Impact Insulation Classes
IIC
45 People walking around are clearly audible
50 People walking around are audible and noticeable
55 People walking around audible but acceptable
62 Walking heard as low frequency thump
70 Heavy walking heard as low frequency thump
Table 10-1 Decibel Reduction Effect on
Subjective Sound Perception
Reduction
in Decibel
%
Reduction in Sounds/Energy
Subjective Perception
3 50 Barely perceptible
45 70 Signifcant
6 75 Sound appears to be reduced by
about 1/4
79 87 Major reduction
10 90 Sound appears to be less than half
original
OCTOBER 2012 Read, Learn, Earn 3
One very common and effective method of controlling
noise generated from drain, waste, and vent systems is to
use cast iron pipe and fttings rather than plastic or copper
pipe and fttings. Ideally, the choice of cast iron rather than
plastic or copper also should be applied to the selection of
drainage system components such as roof drains, deck drains,
and foor drains. When mounting roof drain bodies on wood
sheathing or pan decking, isolate the drain body and under-
deck clamps from direct contact with the sheathing with the
use of -inch neoprene rubber padding. Engineers should
address these items within the body of the specifcation and/
or in plumbing installation detail drawings.
To minimize the amount of noise and vibration transferred
to the building, it is wise to break the contact between the
piping and the buildings components (drywall, studs, joists,
foor structure, etc., see Figures 10-1, 10-2, and 10-3). This
often is accomplished by the use of various types of isolating
materials such as felt or rubber when passing through studs,
joists, hangers, etc. The use of engineered and ISO 3822 lab-
oratory-tested products specifcally designed for this purpose
makes this task fast, easy, and affordable when compared to
makeshift or feld-devised attempts to isolate these pipelines
from contact with building components. Be careful to isolate
each and every possible contact point. Inconsistent success
in even a small percentage of contact points can result in an
overall failed attempt. Clearly express this requirement within
the project specifcations and installation detail pages.
When pipes pass through foors, noise transfer often is
minimized with the use of various types of rubber or neoprene
pads placed under the ears of riser clamps. On very large and
heavy riser pipes, the use of spring-loaded riser isolators is
popular and effective. Numerous manufacturers provide
these types of isolation pads in various thicknesses ranging
from inch to inch and even thicker. These often are made
of rubber or neoprene (neoprene being the more chemically
resistant). Others are also available with steel bearing plates,
which help evenly distribute the weight across the surface of
the pad. Use only lab-tested and proven materials.
Additionally, the piping must be isolated from contact
with the edges of the foor penetration, whether wood, con-
crete, or metal pan decking. This typically is done with the
use of acoustical sealant within the annular space surround-
ing the piping. When the foor system caries a fre rating,
the sealant used must meet or exceed the required rating.
Failure to eliminate contact in the annular space negates
any attempts at effective noise isolation. Clearly express this
requirement within the project specifcation and installation
detail pages. (See Figures 10-4 and 10-5.)
Regarding the isolation of noise transferred from piping
to support hangers and thus to the supporting structure, a
couple common methods can be used. One method is the
use of spring or rubber-isolated hanger rod attachments
at the structure above. Another method is by isolating the
noise transfer by installing felt, rubber, or neoprene mate-
rial within the hanger (between the pipe and the hanger).
When applying isolation lining between the hanger and the
piping, use only materials engineered and tested for this
application.
When drainage and vent piping is being sup-
ported at mi d-story or mi d-span l ocati ons, care
of the items in a common plumbing system that cause this
problem are laundry washing machines, ice makers, and dish-
washers, each of which have electric solenoid, or fast-closing,
valves. Other common contributors include fush valves on
urinals and water closets in commercial buildings.
Another noise source in pressurized water systems is
similar to that described in the drainage section. When water
tubing experiences thermal expansion and contraction due
to temperature changes, water piping can be heard creaking
or squeaking at contact points with various building com-
ponents and support points. This is especially pronounced
in plastic water systems such as CPVC, which expands and
contracts at a much higher rate than metallic tubing. (CPVC
tubing expands/contracts at nearly four times the rate of
copper tubing.)
Fixtures, Faucets, Appliances, and
Appurtenances
Fixtures are manufactured using a wide variety of materials
including vitreous china, plastic, cultured marble, fberglass,
stainless steel, cast iron, enameled steel, non-vitreous ceramic,
terrazzo, and various composite materials. Each material con-
tributes to both airborne and structure-borne noise differently.
A thin steel fxture can sound like a drum being struck when it is
hit with a fow of water. When fxtures are in direct contact with
building components, such as is often the case with a bathtub
or shower pan, they generate not only airborne noise, but a high
level of structure-borne noise as well.
Faucets typically are constructed of brass (with a variety of
plated fnishes), stainless steel, plastic, or cast metals. The wall
thickness of these items contributes to the level of noise genera-
tion as well as the degree of direct contact with the fxture they
serve or the building itself, such as a hard surface countertop or
ceramic tile tub deck. The level of noise generating turbulence
emitted from faucets varies greatly depending on the level of
attention each manufacturer has given to this issue.
Appliances vary widely in their ability to control the noise
each one emits. The cost of an appliance often relates to a
manufacturers published operating noise levels.
Valves, Pumps, and Equipment
Valves emit varying levels of noise depending on the amount
of friction and turbulence they generate. Globe valves, for in-
stance, are very noisy because they are designed in such a way
that turbulence is very high.
Pumps are often very loud, especially if they are in direct
contact with building components or are piped incorrectly,
resulting in turbulence and cavitation.
Equipment generates noise in a wide variety of frequencies
through vibration. Equipment noise isolation has been handled
by plumbing and mechanical consultants for many years and
is an area that is probably less of a mystery to most engineers
than many of the other components of a plumbing or piping
system.
MITIGATING NOISE FROM DRAINAGE
SYSTEMS
Regarding drainage systems, both engineers and plumbing
contractors can take several common approaches to mitigate
unwanted noise.
4 Read, Learn, Earn OCTOBER 2012
READ, LEARN, EARN: Acoustics in Plumbing Systems
must be taken to isolate the piping from contact with the
support brace as well as the pipe clamp used to attach the
pipe to the bracket itself through the use of rubber felt or
neoprene materials engineered and tested to be effective in
this application.
In seismic regions, be sure to avoid the use of rigid seis-
mic/sway bracing methods. Use systems that include aircraft
cable and accessories designed to allow minimal movement.
These aid in avoiding short-circuiting of vibration transfer
to the building. Several manufacturers provide these types
of materials and performance data. Clearly express these
requirements in the project specifcations and detail pages.
(See Figures 10-6, 10-7, and 10-8.)
Another noise isolation method involves the addition of
some form of insulation to the outside of the piping to minimize
the airborne noise. This often is done by wrapping the piping
with foam rubber or fberglass insulation. Unfortunately, in
some cases, makeshift methods are employed such as attaching
carpet padding or similar scrap materials poorly held in place
with wire tie, bailing wire, duct tape, or similar methods.
When attempting to block airborne noise, dense materials
work best. Use only materials and methods with tested and
proven results. Various insulation manufacturers provide test
data to indicate the level of noise reduction to be expected in
this application. Specifcally disallow makeshift attempts on
the jobsite, such as taping or wire-tying carpet padding around
piping.
MITIGATING NOISE IN WATER
DISTRIBUTION SYSTEMS
Three main factors affect the noise in water distribution
systems: water pressure, water velocity, and the number
and type of constrictions and fttings. Water piping noise
almost always is transmitted as structure-borne vibration
and eventually radiates from lightweight surfaces in many
different places.
The choice of water tubing materials can have some effect
on water distribution system noise. For instance, some inde-
pendent laboratory tests have shown that plastic tubing is up
to four times quieter that copper tube. However, local building
and plumbing code requirements may dictate which material
types are allowed.
Figure 10-1 Pipe Isolation Through Framing Member Figure 10-2 Resilient Pipe Isolation
Figure 10-4 Riser Clamp Isolation
Figure 10-3 Vertical Mid-span Support
OCTOBER 2012 Read, Learn, Earn 5
Very similar to drainage piping, steps should be taken to
break any direct contact between the water piping system and
a buildings components. Some contractors use plastic isolators
to break this contact, and others wrap tubing with some kind
of felt or install a rubber isolator. Use of tested and proven pipe
isolators and clamps for through-stud situations and surface-
mounted attachments is critical. Specifcations and plumbing
detail drawings should clearly disallow makeshift, feld-devised
attempts at isolating water lines from structure contact. Specify
products with proven performance. (See Figures 10-9, 10-10,
10-11, and 10-12.)
As with drainage systems, when passing through foors,
steps should be taken to isolate noise transfer to the wood,
metal, or concrete foor system by placing rubber or neoprene
pads under the ears of riser clamps. Additionally, the piping
must be isolated from contact with the edges of the foor
penetration with the use of acoustical sealant within the
annular space surrounding the piping. (See Figures 10-13
and 10-14.)
Another important factor is the isolation of water pip-
ing from hangers and other support systems. In the case
of hangers, this often is accomplished by the use of either
a spring-isolated hanger attachment point at the support-
ing structure or a hanger lining of felt or rubber/neoprene
material to break the connection between the hanger and
the water tube.
All chilled, condenser, domestic, and hot water equip-
ment, including the heat exchanger and the hot water storage
tank, should be isolated from the following:
1. All piping in the equipment room
2. All piping outside of the equipment room within 50
feet of the connected pump
3. All piping more than 2 inches in diameter (nominal
size) and any piping suspended below or near a noise-
sensitive area
Supports should be a pre-compressed type to
prevent a load transfer to the equipment when the piping
systems are flled. Vibration isolators should provide one-half
the defection of the pump isolators or 0.75 inch defection,
whichever is larger. All piping connected to plumbing equip-
ment should be resiliently supported or connected.
Figure 10-5 Vertical Cast Iron Stacks and Water Risers Figure 10-6 Suspended Waste, Vent, or Other Piping
Figure 10-7 Horizontal Joist Bay Support Figure 10-8 Isolation of Toilet Fixture Waste Pipe
6 Read, Learn, Earn OCTOBER 2012
READ, LEARN, EARN: Acoustics in Plumbing Systems
When water tubing is supported by a mid-span or mid-
story brace attached to the buildings structure, steps must be
taken to keep the tubing from contacting the support brace or
the clamp that holds the tube to the support by the use of an
effective isolating material, such as felt, rubber, or neoprene.
Use only materials tested and proven to be effective in this
application. (See Figures 10-15 through 10-20.)
In seismic regions, avoid the use of rigid bracing meth-
ods. Instead, use systems that include aircraft cable and
accessories designed to allow minimal movement, which
aids in avoiding short-circuiting of vibration transfer to the
building.
Another common step taken is the addition of pipe insula-
tion or lagging to the outside of the tubing to help minimize
airborne noise transfer. To effectively isolated against air-
borne noise, dense materials are always best. Use materials
tested and proven to be effective for this purpose.
Another common source of water system noise is water
hammer, which occurs when valves are closed quickly, pro-
ducing a shock wave in the system and causing the pipes to
vibrate. Reducing pressure and velocity and avoiding quick-
closing valves helps reduce water hammer. Air-flled stubs
referred to as air chambers can be used, but they are effective
only for a very short time.
A better solution is the use of shock arrestors or water
hammer arrestors, which are mechanical devices similar to
spring-loaded shock absorbers. These should be introduced
in the piping near appliances or equipment with fast-closing
valves, such as washing machines. They act as cushions to
reduce the shock. Both the Uniform Plumbing Code (UPC)
and the International Plumbing Code (IPC) require water
hammer arrestors to be installed at the location of quick-
acting or quick-closing valves such as found in dishwashers,
laundry washers, and ice makers. IPC specifcally requires
Figure 10-11 Horizontal/Vertical Piping
Figure 10-12 Horizontal/Vertical Piping
Figure 10-10 Surface-mounted Pipe Clamp
Figure 10-9 Through Wall Stud or
Other Wood Framing Member
OCTOBER 2012 Read, Learn, Earn 7
that these devices shall conform to ASSE 1010: Performance
Requirements for Water Hammer Arrestors.
MITIGATING NOISE FROM FIxTURES
While addressing noise sources involving various piping
systems within a building, it is important to not overlook
fxture and faucet selection. Fixtures, faucets, and appliances
can be chosen based on third-party test data regarding their
inherent sound qualities. ISO 3822: Laboratory Tests on Noise
Emission from Appliances and Equipment Used in Water
Supply Installations sets out a test method and uniform
rating system for evaluating noise emissions from plumbing
fxtures. Other methods to reduce noise from fxtures and
faucets are as follows.
One common way to ensure that the fxtures will be
quieter than others is by choosing those made of materials
that absorb sound, such as vitreous china or cast iron rather
than thin-gauge stainless or enameled steel. As an example,
when choosing a kitchen sink consider various factors that
determine how much noise will result under normal opera-
tion. A stainless steel sink without the addition of a dense
sound pad applied to the bottom of the bowl will experience
a loud drumming sound when water hits the bowl, resulting
in both airborne and structure-borne noise. Additionally, if
the faucet is in direct contact with the upper surface of the
sink or the countertop, devoid of a gasket, putty, or similar
isolation, it will transfer noise generated from the operation
of water running through the faucet itself. Instead, consider
choosing a cast iron sink combined with a faucet made of
heavy gauge metal and rubber isolation gaskets at both the
base of the faucet and the attachment points under the ledge
of the sink. Another example is to use fush tank-type toilets
rather than fushometer valve toilets. Flush tank-type toilets
are much quieter, and some are nearly silent. (See Figures
10-21 through 10-32.)
Water supply connections between the wall and the
faucet constructed by rigid supply tubing will produce more
noise than those made with fexible or braided supply lines.
Flexible tubing made of corrugated stainless steel or braided
nylon will perform better than chrome or rigid brass supply
lines. (See Figure 10-33, in the case of a laundry washer.)
It is important to keep wall surface materials from con-
tacting fxture supply stub-outs or escutcheons positioned
behind angle stops. Provide rubber or dense foam isola-
tion spacers behind the escutcheons so that a slight void is
provided. Fill the void space around each escutcheon with
acoustical caulking compound, and use acoustical caulk or
-inch felt within the annular space between the stub-out
pipe and the wall surface material.
Tub and shower mixing valves and associated parts such
as showerheads and tub spouts should be treated much the
same as the water distribution system to which they are con-
nected. Tub and shower fxtures and faucets are among the
worst culprits regarding unwanted noise generation.
The attachment points between the supports within the
wall at the showerhead ftting, tub spout ftting, and supply
lines feeding the diverter valve must be isolated from hard
contact. Use only tested and proven isolating materials spe-
cifcally engineered to accomplish this.
The showerhead arm and the sub-spout supply lines must
be kept from contact with the wall surface as well. Provide a
-inch clear annular space around both pipe supply locations,
and fll this space with fexible caulking compound. Clearly
defne these isolation requirements within the specifcation
as well as on plumbing installation detail drawings.
Additional noise and vibration isolation can be provided
at tub and/or shower locations by selecting fxtures made
of dense materials such as cast iron, as well as eliminating
direct contact with the foor sheathing and the wall framing
surrounding the edges of the tub or shower. This should be
accomplished by the use of rubber or neoprene liner and
-inch rubber pads between heavy contact points and the
building structure. Provide clear specifcation language and
plumbing detail drawings to the installing contractor. (See
Figures 10-34 through 10-37.)
Figure 10-13 Riser Clamp Isolation Figure 10-14 Vertical Cast Iron Stacks and Water Risers
8 Read, Learn, Earn OCTOBER 2012
READ, LEARN, EARN: Acoustics in Plumbing Systems
Figure 10-15 Suspended Waste, Water, or Other Piping
Figure 10-16 Suspended Horizontal Overhead
Figure 10-17 Horizontal Overhead
Figure 10-18 Water, Vent, Waste
OCTOBER 2012 Read, Learn, Earn 9
MITIGATING NOISE FROM VALVES,
PUMPS, AND OTHER EqUIPMENT
Valves, pumps, and other equipment are common contrib-
utors of noise in a plumbing system. Most valve
manufacturers provide fow and turbulence data to assist
in the choice of valves. Typically, the quietest valves are
those with smooth waterways such as full-way ball valves
and full-way gate valves. Specify appropriate valves with
this in mind.
Pumps can be extremely loud and must be isolated in
several ways. Rubber or spring isolators commonly are used
when mounting pumps on foors. Concrete bases with spring
isolators or neoprene pads are preferred for all foor-mounted
pumps. Select the appropriate rubber or spring isolator based
on third-party testing and load data provided by various
manufacturers.
When connecting the piping system to pumps and
equipment, especially ones that generate a great deal of
vibration, pay special attention to the use of flexible con-
nectors and effective hanger isolation. Select and specify
flexible connectors that are appropriate for the pipe sys-
tems material and fluid content. Various manufacturers
can provide the necessary data on which to base decisions.
Table 10-3 contains the recommended static deflection for
the selection of pump vibration-isolation devices.
Vibration-control devices generally consist of steel
springs, air springs, rubber isolators, concrete housekeep-
ing pads or slabs of fibrous (or other resilient) materials,
isolation hangers, flexible pipe connectors, concrete in-
ertia bases, or any combination of these items.
Steel springs are available for almost any desired
deflection. These devices generally are used as vibration
isolators that must carry heavy loads where more isola-
tion performance is desired than rubber or glass fiber
Figure 10-19 Overhead Trapeze Piping
Figure 10-20 Horizontal Joist Bay Support
10 Read, Learn, Earn OCTOBER 2012
READ, LEARN, EARN: Acoustics in Plumbing Systems
provides or where environmental conditions make other
materials unsuitable. They are available for deflection
only up through 4 inches. The basic types of steel spring
mountings are housed-spring mountings, open-spring
mountings, and restrained-spring mountings. Because
steel springs have little inherent damping and can in-
crease their resonance in the audio frequency range, all
steel-spring mountings should be used in series with
pads of rubber, fibrous, or other resilient materials to
interrupt any possible vibration-transmission paths.
Air springs, as steel springs, are available for almost any
desired defection where 6 inches or more is required. By vary-
ing the air pressure in the bladder, air springs are capable of
carrying a wide range of loads. The shapes, rather than the
pressure, determine the spring frequency. Air springs have
the advantage of virtually no transmission of high-frequency
noise. They have the disadvantage of higher cost, higher
maintenance, failure rates, and low damping.
Rubber isolators generally are used where defections of
0.3 inch or less are required. These devices can be molded
in a wide variety of forms designed for several combina-
tions of stiffness in the various directions. The stiffness of
a rubber isolator depends on many factors, including the
elastic modules of the material used. The elastic modules
of the material vary with the temperature and frequency
and are usually a characteristic of a durometer number,
measured at room temperature. Materials in excess of 70
durometers are usually ineffective as vibration isolators.
Figure 10-21 Wall-hung Water Closet or Similar Figure 10-22 Wall-mounted Urinal, Sink, or Similar Fixture
Figure 10-23 Sink Isolation Detail
Figure 10-24 Wall-hung Fixture with Carrier Support System
OCTOBER 2012 Read, Learn, Earn 11
Rubber isolating devices can be relatively light, strong, and
inexpensive; however, their stiffness can vary considerably
with the temperature. They are effective primarily against
high-frequency disturbances with very limited performance
at low frequencies.
Pre-compressed glass-fber pads generally are used
where defections of 0.25 inch or less are required. They
are available in a variety of densities and fber diameters.
Although glass-fber pads usually are specifed in terms of
their densities, the stiffness of the pads supplied by differ-
ent manufacturers may differ greatly, even for pads of the
same density.
Sponge-rubber vibration-isolation materials are com-
mercially available in many variations and degrees of
stiffness. The stiffness of such a material usually increases
rapidly with increasing load and frequency. This material
rarely is used in manufactured isolators, but often is used
in jobsite-fabricated installations.
Concrete base devices are usually masses of con-
crete, poured with steel channel, weld-in reinforcing
bars, and other inserts for equipment hold-down and
vibration-isolator brackets. These devices maintain the
alignment of the component parts; minimize the effects
of unequal weight distribution; reduce the effects of
the reaction forces, such as when a vibration-isolating
device is applied to a pump; lower the center of gravity
of the isolated system, thereby increasing its stability;
and reduce motion. Concrete bases can be employed
with spring isolators, rubber vibration isolators, and
neoprene pads. Industrial practice is to make the base
in a rectangular configuration approximately 6 inches
larger in each dimension than the equipment being sup-
ported. The base depth needs not exceed 12 inches unless
specifically required for mass, rigidity, or component
Figure 10-25 Flush Valve Support
Figure 10-26 Typical Floor-mounted Toilet Flange
Figure 10-27 Floor-mounted Bathtub or Shower Isolation
Figure 10-28 Lavatory or Sink
12 Read, Learn, Earn OCTOBER 2012
READ, LEARN, EARN: Acoustics in Plumbing Systems
alignment. A concrete base should weigh at least as much
as the items being isolated. (Preferably, the base should
weigh twice as much as the items.) The plumbing designer
should utilize the services of a structural engineer when
designing the concrete base.
When providing vibration isolation for any plumb-
ing system or component, the engineer must consider
and treat all possible vibration-transmission paths that
may bypass (short-circuit or bridge) the primary vibra-
tion isolator. Flexible connectors commonly are used
in pipe connecting isolated and un-isolated plumbing
components. Flexible pipe connectors usually are used
to provide flexibility of the pipe and permit the vibration
isolators to function properly, to protect the plumbing
equipment from strains due to the misalignment and
expansion or contraction of the piping, and to attenuate
the transmission of the noise and vibration along the
piping system. Most commercially available flexible pipe
connectors are not designed primarily for noise reduc-
tion. For noise control, resilient pipe isolators should be
utilized. (See Figures 10-38 through 10-45.)
POSITIVE ENGINEERING INFLUENCE
OVER BOTH DESIGN AND
CONSTRUCTION
Once the engineer has a clear understanding of the own-
ers requirements regarding the level of noise abatement
Figure 10-29 Icemaker Box
Figure 10-30 Laundry Outlet Box
Figure 10-31 Hot Water Tank Rough-in
Figure 10-32 Mop/Service Sink Rough-in
OCTOBER 2012 Read, Learn, Earn 13
Figure 10-33 Flexible Connections for Clothes Washer
Figure 10-34 Typical Bathtub Spout
Figure 10-35 Showerhead Isolation
14 Read, Learn, Earn OCTOBER 2012
READ, LEARN, EARN: Acoustics in Plumbing Systems
expected for a particular project, a plan of attack can be
formulated. Though this chapter focused on the subject
of acoustics in plumbing systems, it is obvious that at-
tention must be given to a few elements in the building
itself to set the stage for success. These items must be
addressed with the project architect and the plumbing/
mechanical design team early in the design stage. In
some cases, it may be wise to consider hiring an acousti-
cal consulting frm with a proven track record of success.
These specialists, or acousticians, are typically members of
the Acoustical Society of America and/or the Institute of
Noise Control Engineering.
Infuence the Design and Location of Party
and Plumbing Walls
Ideally, encourage the architect to locate plumbing walls
away from quiet rooms. As an example, do not position
a bathroom or kitchen plumbing wall next to or above a
bedroom or adjoining tenant party wall.
Party walls should be constructed to minimize sound
transfer from one tenant to another or from common
areas to tenant spaces and visa versa. Multiple designs
and configurations are available to accomplish this, in-
cluding physical separation (air space) between walls,
staggered studs, dense insulation within wall cavities,
multiple layers of sheetrock, and a variety of resilient
channel configurations.
Influence Floor and Ceiling System
Construction and Configuration
Floor and ceiling systems built with attention to mini-
mizing noise transfer also can contribute to the level of
success with plumbing system noise mitigation. Be sure
that a proven, effective system is used.
Avoid routing plumbing system piping in ceiling
spaces that are positioned above sensitive areas such as
bedrooms. Also, avoid hard floor surfaces where possible.
Soft floor coverings help minimize noise transfer between
occupant levels. This aids in minimizing the transfer of
airborne noise generated by plumbing fixtures and appli-
ances from one level of a building to another.
In situations where pipes absolutely must be installed
in sensitive walls and ceilings, care must be taken to pro-
vide noise reduction with sound-absorbing materials.
Once these building-related design issues are re-
solved, the acoustical engineer can draft the needed
documents and establish means and methods that will
be required of the plumbing or mechanical contractor.
These documents typically include a project-specific
plumbing noise and vibration specification, which es-
tablishes submittal requirements and procedures and
specifies acoustical materials and methods required for
the project, and plumbing installation detail drawings,
which establish how quality control will be monitored
throughout construction.
On-site inspection during the building process often
reveals errors that can be corrected easily early in the pro-
cess. All too often these errors are concealed and cannot
be easily uncovered or repaired in a finished building.
Acoustical testing in a partially completed building is
an additional step that can be taken to ensure that errors
Figure 10-36 Bathtub/Shower Rough-in
Figure 10-37 Shower Rough-in
OCTOBER 2012 Read, Learn, Earn 15
are not needlessly repeated and to give the opportunity
for correction.
ACCOMPLISHING EFFECTIVE NOISE
MITIGATION IS EASIER THAN EVER
The engineer does not have to perform all of these tasks
alone. Thanks to increasing marketplace availability of
tested and proven products along with manufacturers
support services, the engineer has willing and capable
partners. Figures 10-46 and 10-47 show examples of
complimentary support documentation provided by
reputable manufacturers.
Engineers and acoustical consultants now can easily
and confidently do their part in providing a comprehen-
sive and holistic solution for the mitigation of plumbing
system noise for their clients buildings. The owners
concerns regarding high costs and legal exposure can
be dispelled. The contractors concerns regarding time-
consuming, confusing, and expensive materials and
methods also can be put to rest. Necessary materials
can be purchased through normal plumbing wholesale
channels throughout the United States and much of
Canada, rather than a long list of specialty suppliers,
as historically required by most plumbing noise and
vibration specifications in years past. When contrac-
tors are confident that plans and specifications point
them in a clear and understandable direction as to what
is expected, the results will be quality installations,
protection against litigation, and reasonable contract
pricing. Ultimately, happy building owners and building
occupants will be the result.
Low installed-cost acousti-
cal application solutions are
the result of the successful
specification inclusion and
implementation of products
that help the contractor to be
efficient and consistent with
each installation. The elimina-
tion of random unproven and
makeshift methods of instal-
lation with an insistence on
engineered solutions at the
jobsite level results in fast,
simple, and easily duplicated
installations and a win-win for
all parties concerned.
The availability of a clear,
concise, and affordable solu-
tion to plumbing system noise
provides up-sell opportunities
for buyers interested in an
improved quality of life in a
quiet environment. One study
recently showed that currently
about 30 percent of homebuild-
ers offer sound-attenuating
interior walls as standard pre-priced upgrades for pro-
spective buyers. Another opportunity involves green
building projects. More and more sustainable projects
are including specification requirements relating to
a peaceful environment. Noise both from indoor and
outdoor sources add to stress and discomfort for a build-
ings occupants.
REFERENCES
1. ISO 3822: Laboratory Tests of Noise Emissions from
Appliances and Equipment used in Water Supply
Installations. International Organization for Stan-
dardization
2. PPI TR-21: Thermal Expansion and Contraction in
Plastic Piping Systems. Plastic Pipe Institute.
3. Engineering Resource Binder. Hubbard Enterprises-
HOLDRITE.
4. FlowGuard Gold Connection. Issue 13, 1Q 2005.
5. Plumbing Appliance Noise Measurements, Sound
and Vibration.
6. UPC Section 609.10. International Association of
Plumbing and Mechanical Offcials.
7. IPC Section 604.9. International Code Council.
Table 10-3 Recommended Static Defection for Pump Vibration-Isolation Devices
Equipment
Location
Power Range,
HP (kW)
Speed,
RPM
Indicated Floor Span, in. (mm)
30 ft
(9.1 m)
40 ft
(12.2 m)
50 ft
(15.2 m)
Slab on grade Up to 7.5 (5.6) 1800 (19.1) (19.1) (19.1)
3600 (6.4) (6.4) (6.4)
Over 7.5 (5.6) 1800 1 (25.4) 1 (25.4) 1 (25.4)
3600 (19.1) (19.1) (19.1)
50-125 (37.3-93.2) 1800 1 (38.1) 1 (38.1) 1 (38.1)
3600 1 (25.4) 1 (25.4) 1 (25.4)
Upper foor above
noncritical areas
Up to 7.5 (5.6) 1800 (19.1) (19.1) 1 (38.1)
3600 (19.1) (19.1) 1 (25.4)
Over 7.5 (5.6) 1800 1 (25.4) 1 (38.1) 2 (50.8)
3600 (19.1) 1 (25.4) 1 (38.1)
50-125 (37.3-93.2) 1800 1 (38.1) 2 (50.8) 2 (63.5)
3600 1 (25.4) 1 (38.1) 2 (50.8)
Upper foor above
critical areas
Up to 7.5 (5.6) 1800 1 (25.4) 1 (38.1) 2 (50.8)
3600 (19.1) 1 (25.4) 1 (38.1)
Over 7.5 (5.6) 1800 1 (38.1) 2 (50.8) 3 (76.2)
3600 1 (25.4) 1 (38.1) 2 (50.8)
50-125 (37.3-93.2) 1800 2 (50.8) 3 (76.2) 4 (101.6)
3600 1 (38.1) 2 (50.8) 3 (76.2)
16 Read, Learn, Earn OCTOBER 2012
READ, LEARN, EARN: Acoustics in Plumbing Systems
Figure 10-40 Neoprene Mount, Double Defection
Figure 10-38 Neoprene Hanger Isolator
Figure 10-39 Sump Pumps
OCTOBER 2012 Read, Learn, Earn 17
Figure 10-45 Flex Connector Detail
Figure 10-46 Sample Specifcation Sheets
Figure 10-44 Examples of Flex Connectors
Figure 10-42 Neoprene Pad Isolator Figure 10-43 General Mounting Detail for End-suction,
Close-coupled Pump
Figure 10-41 Spring-mount Isolator
18 Read, Learn, Earn OCTOBER 2012
READ, LEARN, EARN: Acoustics in Plumbing Systems
Figure 10-45 Flex Connector Detail
Figure 10-46 Sample Specifcation Sheets
Figure 10-44 Examples of Flex Connectors
Figure 10-42 Neoprene Pad Isolator Figure 10-43 General Mounting Detail for End-suction,
Close-coupled Pump
Figure 10-41 Spring-mount Isolator
OCTOBER 2012 Read, Learn, Earn 19
Figure 10-47 Sample Installation Instruction Sheet
20 Read, Learn, Earn OCTOBER 2012
READ, LEARN, EARN: Acoustics in Plumbing Systems
CE Questions Acoustics in Plumbing Systems (CEU 192)
Which of the following is an example of impact noise? 1.
voices a.
heavy footsteps b.
vibrations from loud music c.
both b and c d.
The Impact Insulation Class for walking heard as a low- 2.
frequency thump is _______.
50 a.
55 b.
62 c.
70 d.
_______ pipe expands and contracts at approximately fve to 3.
eight times the rate of cast iron pipe.
PVC a.
PEX b.
ABS c.
both a and c d.
A cause of noise generation in a water distribution system is 4.
_______.
water fow due to fxture operation a.
thermal expansion and contraction of piping b.
water hammer c.
all of the above d.
_______ is a main factor affecting the noise in water 5.
distribution systems.
water pressure a.
water velocity b.
number and type of constrictions and fttings c.
all of the above d.
All domestic water equipment should be isolated from _______. 6.
all piping in the equipment room a.
all piping outside of the equipment room within 10 feet of b.
the connected pump
all piping more than 1 inch in diameter c.
all of the above d.
_______ sets out a test method for evaluating noise from 7.
emissions from plumbing systems.
International Building Code a.
ASSE 1010 b.
ISO 3822 c.
Uniform Plumbing Code d.
Which of the following fxture materials will absorb sound? 8.
enameled steel a.
vitreous china b.
stainless steel c.
brass d.
The quietest valves typically are _______. 9.
globe valves a.
full-way ball valves b.
full-way gate valves c.
both b and c d.
_______ can be used where defections of 6 inches or more are 10.
required.
rubber isolators a.
glass fber pads b.
air springs c.
none of the above d.
A concrete base should be approximately _______ larger in 11.
each dimension than the equipment it supports.
4 inches a.
6 inches b.
10 inches c.
12 inches d.
_______ can be used when constructing party walls to minimize 12.
sound transfer.
staggered studs a.
dense insulation b.
air space c.
all of the above d.
ASPE Read, Learn, Earn Continuing Education
You may submit your answers to the following questions online at aspe.org/readlearnearn. If you score 90 percent or higher on the test,
you will be notifed that you have earned 0.1 CEU, which can be applied toward CPD renewal or numerous regulatory-agency CE pro-
grams. (Please note that it is your responsibility to determine the acceptance policy of a particular agency.) CEU information will be kept
on fle at the ASPE ofce for three years.
Notice for North Carolina Professional Engineers: State regulations for registered PEs in North Carolina now require you to complete ASPEs
online CEU validation form to be eligible for continuing education credits. After successfully completing this quiz, just visit ASPEs CEU Valida-
tion Center at aspe.org/CEUValidationCenter.
Expiration date: Continuing education credit will be given for this examination through October 31, 2013.
OCTOBER 2012 Read, Learn, Earn 21