Service Manual

Commercial Air Conditioning 24 28 Universal Outdoor Unit air conditioning

AB242ACBEA+AU242AHBEA AC242ACBEA+AU242AHBEA AD242AMBEA+AU242AHBEA AD242AHBEA+ AU242AHBEA AP242ACBEA+ AU242AHBEA AB28NACBEA+AU28NAHBEA AC28NACBEA+AU28NAHBEA AD28NAMBEA+AU28NAHBEA AU282AHBEA

Features
Auto-Restart function Group control(with a group controller) Auto-changeover The same outdoor unit can match with cassette \convertible\ duct type indoor unit With new environment friendly refrigerant R407C
Remotoe control and Wired remote control(Optional)

Weekly timing(with a weekly timer)

Haier Group
.

MANUAL CODE: SYJS-005 -03 Rev.0

CONTENTS

CONTENTS Contents.....................................................1 1. Description of Products & Features....2 2. Specifications. ...8 3. Safety precaution...12 4. Net dimensions of indoor and outdoor unit...14 5. Installation instructions . . 16 6. Parts and functions .. ...19 7. Remote controller functions.22 8. Refrigerant diagram......24 9. Electrical control functions25 10. Diagnostic information(trouble shooting).29 11. Electrical data..........................................35 12. Exploded views and parts lists................ ...41 13. Performance curves............................... 57 14. Noise level charts....... ............................... 48 15. Air velocity distribution ............................... 48

-1-

1 .Description of Products & Features


Products coding direction
United Outdoor unit: A U 24 2 A H B E A
Climate type: T1 (see table 1) Design number E Product type: A stands for heat pump type, refrigerant is R22 B stands for heat pump type, refrigerant is R407 M stands for cool only type, refrigerant is R22 N stands for cool only type, refrigerant is R407 Appearance character Product series: common icon-shelled outdoor unit type Applicable voltage: 2 stands for 220-240V/50Hz 4 stands for 220v/60Hz N stand for 380V/50Hz Cooling / Heating capacity,24=24000BTU/h Product type : B stands for cassette type C stands for convertible type D stands for duct S stands for split type Q stands for chiller system U stands for outdoor unit Abbreviation of Air conditioner

Indoor units of Cassette type: A C 24 2 A C B E A


Climate type: T1 (see table 1) Design number E Product type: A stands for heat pump type, refrigerant is R22 B stands for heat pump type, refrigerant is R407 M stands for cool only type, refrigerant is R22 N stands for cool only type, refrigerant is R407 Appearance character Product series: common icon-shelled outdoor unit type Applicable voltage: 2 stands for 220-240V/50Hz 4 stands for 220v/60Hz N stand for 380V/50Hz Cooling / Heating capacity,24=24000BTU/h Product type : B stands for cassette type C stands for convertible type D stands for duct S stands for split type Q stands for chiller system U stands for outdoor unit Abbreviation of Air conditioner

-2-

a) Description of the coding rule of the models A U 28 N A H B E A


Climate type:T1 Design serial number Product type: heat pump R407C Appearance features Product series:one-to-one Adaptive voltage:380-400V/50Hz
Cooling capacity:28=28000BTU/h

Outdoor unit Air conditioner

A B

28

B E

A
Climate type:T1 Design serial number Product type: heat pump R407C Appearance features Product series:one-tag-one Adaptive voltage:380-400V/50Hz
Product specification:valid digit above kilobi

Product type:indoor unit P:Cabinet typeC:Convertible type B:Cassette type D:Duct type Air conditioner

b). Standard working condition


No. 1 2 Operating Mode Nominal Cooling Nominal Heating Indoor Operating Mode Temp. Humidity DB:27 WB:19 DB:20 WB:15 Outdoor Operating Mode Temp. Humidity DB:35 WB:24 DB:7 WB:6

-3-

c)Brief introduction of the series: Convertible type: AC242ACBEA AC28NACBEA (1).Ceiling convertible,flexible installation,convenient maintenance,saving the users' expenditures (2)Adopting single-phase & three-phase power supply,applicable for household and commercial usage (3).Dual air outlet design,floor air blowing,accelerating the indoor air circulation, quick temperature adjustment (4).Long-distance air blowing,large power,large cooling/heating ratio (5).Intelligent remote control,convenient and flexible control (6).Super-slim indoor unit design,luxury and nice-looking,saving space,harmonious and unitive with the indoor environment (7).Adopting screw-fastening for the air inlet grill,firmly fixed;adopting slipway insert-lock fastening method for the filter screen,convenient cleaning or replacing the filter screen without opening the air inlet grill. (8).Group control,units up to 128 sets can be controlled . Duct type : AD242AMBHA AD242AHBEA AD28NAMBEA Totally concealed machine body All the machine body is to be installed inside the ceiling, having no effect on the beauty of the room and without taking any room space. Air intake via the rear air intake duct
This new design has changed the former unique pattern of air intake, and a larger distance between air intake and air return cycles as well as better air quality can be achieved.

Flexible and easier installation The machine body is to be installed in a totally concealed way,its fan system has a longer distance coverage so as to supply its airflow to several rooms, and the indoor unit may be installed inside the ceiling of a room or corridor. The installation is simple and flexible, and there is no need to have specified personnel for management, thus cutting down the expenses; the machine is lighter and smaller, and convenient for installation, it takes an extremely small building space, thus lower the construction cost; the indoor unit is to be concealed inside the ceiling, and hence the usable space can be saved and the room decoration will not be affected.

-4-

Cassette type: AB242ACBEA AB28NACBEA Products characteristic: Completely invisible machine body:
The whole machine body is completely concealed inside the ceiling. Due to its compact size it neither breaks the harmonization of indoor decoration nor occupies the indoor spaces. The stylish look of air conditioner allows it to blend right into ceiling.

Superbly efficient healthy filter: Superbly efficient antibiotic materials are utilized and can prevent germs from breeding efficiently . Flexible and easy installation
Slim design with machine body, completely ceiling concealing and portable shape, all make it greatly easier to install. Moreover, it occupies least constructional spaces, which help to reduce constructional cost prices. It also features a specific drainage system with up to 600mm lift , which allows reducing installation spaces and ensures to drain smoothly. Thanks to its "smudge-free" mobile outlet grill, the ceiling can be protected from pollution effectively and allow the airflow to fit people's comfortable need much more.

Compensation function of power failure:


When meeting a power failure during running, no matter how long it will be, once the power is restored, air conditioner will automatic restart with the previous status.

Safety and reliable control due to various signal controls


1 Inputting with press buttons on the panel 2 Inputting with temperature sensors (indoor ambient temperature sensors, indoor coil pipe temperature sensors, 3 Piping pressure signals 4 Compressor current signals 5 Testing signals 6 System time-shorten signal 7 Water overflowing signal 8 Communication signals between indoor unit and front plate or between indoor unit and outdoor unit .

Silent design

The use of radial outward flow turbine fan produces larger cyde airflow volume and acts to significantly decrease operating noise.

NEW

Advanced wire-controller and convenient remote-controller


The new wired controller can connect with 16 indoor units without any device such as detectors. The new remote controller can be used for single unit or muti-free unit, or H-MRV,very convenient. In addition, it can be compatible with the old remote controllers.

When using remote-controlling mode, it is comfortable and convenient to operate.

NEW

Low ambient temperature cooling function (optional) Equipped with high/low pressure protection switch The indoor units of AU282AHBEA and AU28NAHBEA are the same.

d). Brief Introduction for T1\

T2\ T3 working condition


Climate type T1 18 -7 43 0 43 43 10 -7 T2 35 35 35 21 -7 T3 52 52 52

Type of Air Conditioner Cool only Heat pump Electricity heating

-6-

2 Specifications
Model AU242AHBEA AC242ACBEA AB242ACBEA AD242AMBEA AD242AHBEA E Item 24000 24000 24000 24000 24000 Cooling capacity Btu/h 27000 27000 27000 27000 27000 Heating capacity Btu/h 1PH 220-230V 50Hz Power 2700 2700 2700 2700 2700 Cooling power(W) 8.89 8.89 8.89 8.89 8.89 Cooling EER(Btu/W) Cooling operation current 12.5 12.5 12.5 12.5 12.5 (A) 0.95 0.95 0.95 0.95 0.95 Power factor(%) 2700 2700 2700 2700 2700 Heating power (W) 10 10 10 10 10 Heating COP(Btu/W) Cooling operation current 12.5 12.5 12.5 9.5 9.5 (A) 0.95 0.95 0.95 0.95 0.95 Power factor(%) Noise levelhigh-mid-low 58 48-44-38 39-37-35 35-32-29 42-41-40 dB(A) Dimension External 948x340x830 990655199 840840240 990650300 820830360 mmmmmm (LWH) Package 1050x440x979 1150750300 910910300 1137800320 9401051510 (LWH) Weight Kg/Kg 74/89 30/39 28/30 40/57 48/58 (net/gross) \ \ \ \ Compressor Model ZR34K3E-PFJ-522 Copeland \ \ \ \ Manufacture PSC \ \ \ \ Starting method Starting 75 \ \ \ \ current(A) Protection IOL \ \ \ \ devices \ \ \ \ Crankcase heater power (W) \ 2 2 2 2 2 0.92m 0.084 m 0.199m 0.199m 0.199m Heat exchanger capillary capillary capillary capillary capillary Refrigerant control R407C \ \ Refrigerant Type 2400 \ \ \ Charge(g) Auto Auto Auto Auto Auto Defrost method Axial fan1 Axial fan2 Cross flow fan2 Cross flow fan2 Cross flow fan2 Fan TypeNumber 130 45 40 100 130 Fan motor Motor output (W) 3 Air-flow 4000 900/840/790 1300/1100/870 1470/1300/1100 900/1250/1500 high-mid-low /h m Anti-vibration and sound XPE XPE XPE XPE XPE insulation devices Control method Remote Remote Wired Wired \ remote/wire-controlled controlled controlled controlled controlled Fuse Fuse Fuse Fuse Fuse Safety devices 9.52 9.52 9.52 9.52 9.52 Dimension Liquid pipe:(mm) Gas pipe:(mm) of 15.88 15.88 15.88 15.88 15.88 refrigerant pipe Bugle joint Bugle joint Bugle joint Bugle joint Bugle joint Connection method Drainage pipe(material , \ PVC 26/32 PVC 25/32 PVC 25/32 PVC 26/32 I.D./O.D.)Mm white white white white white Appearance colour To see manual To see manual To see manual To see manual To see manual Accessories Operation data

-7-

item Function Capacity Capacity Total power input Max. power input EER or COP Dehumidifying capacity Power cable Power source Running /Max.Running current Start Current Fuse Unit model (color) Type Number Fan Speed(H-M-L) Fan motor output power Air-flow(H-M-L) Type / Diameter Indoor unit Heat exchanger Total Area Temp. scope Dimension External Package (Remote /wired) LWH LWH

Model BTU/h kW W W W/W 10m/h NVHz A/A A A

AP242ACBEA cooling 24000 7.1 2.7 3.2 2.6 3.0 3*3.0 heating 28000 7.9 2.7 3.2 2.9

1, 220~230, 50
13.5/16 60 21 AP242ACBEA centrifugal*1 56030/ 49040/38050 0.04 1000/900/800 14.5/19.5

r/min kW m/h mm m
mmmmmm mmmmmm

TP2M/9.52 0.338
2-7

1821532300 1920625377 PVC 26/32 remote type


1.8

Drainage pipe (material , I.D./O.D.) Control type Noise level Weight Refrigerant PIPING Pipe Electricity Heater (H-M-L) (Net / Shipping) Type / Charge Recharge quantity Liquid Gas MAX.Drop MAX.Piping length

mm kW dB(A) kg / kg g g/m mm mm m m

48/46/44 45/57
R407C/2400 65 9.52 15.88 flared 20 30

Connecting Method Between I.D &O.

Norminal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20DB Outdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB

item Function Capacity Total power input Max. power input EER or COP Dehumidifying capacity Power cable Power source
Running /Max.Running current

Model BTU/h W W BTU/W 10m/h NVHz A/A A Cooling 28000 3200 4500 8.75

AU28NAHBEA Heating 32000 3300 5500 9.7 3 /

3N 380V-400V 50HZ
Cooling 5.5/8.0 Heating 5.8/9.5 30

Start Current Unit model (color) Fan Type Number Speed(H-M-L) Fan motor output power Air-flow(H-M-L) Heat exchanger Type / Diameter Total Area Temp. scope Dimension External LWH Package LWH Drainage pipe (material , I.D./O.D.) Control type (Remote /wired) Fresh air hole dimension Electricity Heater Noise level (H-M-L) Weight (Net / Shipping) Dimension External LWH Package LWH Weight (Net / Shipping) Unit model (color) Compressor Model / Manufacture Type Fan Type Number Speed Fan motor output power Air-flow(H-M-L) Heat exchanger Type / Diameter Total area Temp. scope Dimension External LWH Package LWH Drainage pipe (material , I.D./O.D.) Refrigerant control method Defrosting Volume of Accumulator Noise level Type of Four way valve material of reduce noise crankcase heater power Weight (Net / Shipping) Refrigerant Type / Charge Recharge quantity Liquid Pipe Gas Connecting Method MAX.Drop Between I.D &O.D MAX.Piping length Indoor unit Panel Outdoor unit PIPING

r/min kW m/h mm m
mmmmmm mmmmmm

mm mm kW dB(A) kg / kg
mmmmmm mmmmmm

kg / kg

r/min kW m/h mm m
mmmmmm mmmmmm

/ / / AU28NAHBEA(WHITE ZR40K3E-TFD-522 Copelan Scroll Axial-flow1 1180+30 130 4000


TP2M/9.52

mm mm/mm L dB(A)

W kg / kg g g/m mm mm m m

0.92 43-60 948x340x830 1050x440x979 / main capillary 2.4x220 auxiliary capillary Auto / 58/--/50 / XPE / 74/89
R407C 2400 60 9.52 15.88 flared 20 30

-8-

Item Function Capacity Capacity Sensible heat ratio Total power input Max. power input EER or COP Dehumidifying capacity Power cable Power source Running /Max.Running current Start Current Unit model (color) Compressor Model / Manufacture Type Type Number Fan Speed Fan motor output power Air-flow(H-M-L) Type / Diameter Outdoor unit Heat exchanger Total area Temp. scope Dimension External Package LWH LWH

Model cooling BTU/h kW W W W/W 10m/h N, V, Hz A/A A 28000 8.2 75% 3400 4300 2.41

AU282AHBEA
heating 34000 10 3600 4600 2.77 2.47 3*3.0

1, 220-240, 50
cooling: 16A/20A heating: 17A/22A 80

AU282AHBEAWHITE C-SBN261H5A(Sanyo scroll axial1


r/min kW m/h mm m
mmmmmm mmmmmm

920r/min 0.06 3200/-/TP2M/9.52 0.92 43-60 948x340x830 1050x440x979 / capillary 4.0X2.5X600 auto 3.5 56 / XPE

Drainage pipe (material , I.D./O.D.) Refrigerant control method Defrosting Volume of Accumulator Noise level Type of Four way valve material of reduce noise crankcase heater power Weight Refrigerant (Net / Shipping) Type / Charge Recharge quantity Liquid Gas

mm mm/mm L dB(A)

W kg / kg g g/m mm mm m m

without 74/89
R407C 2600 65 9.52 15.88 flared 15 30

PIPING

Pipe

Connecting Method MAX.Drop Between I.D &O. MAX.Piping length

Norminal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20DB Outdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB

item Function Capacity Total power input Max. power input EER or COP Dehumidifying capacity Power cable Power source Running /Max.Running Start Current Unit model (color) Fan Type Number Speed(H-M-L) Fan motor output power Air-flow(H-M-L) Heat exchanger Type / Diameter Total Area Temp. scope Dimension External LWH Package LWH Drainage pipe (material , I.D./O.D.) Control type (Remote /wired) Fresh air hole dimension Electricity Heater Noise level (H-M-L) Weight (Net / Shipping) Dimension External LWH Package LWH Weight (Net / Shipping) Unit model (color) Compressor Model / Manufacture Type Fan Type Number Speed Fan motor output power Air-flow(H-M-L) Heat exchanger Type / Diameter Total area Temp. scope Dimension External LWH Package LWH Drainage pipe (material , I.D./O.D.) Refrigerant control method Defrosting Volume of Accumulator Noise level Type of Four way valve material of reduce noise crankcase heater power Weight (Net / Shipping) Refrigerant Type / Charge Recharge quantity Liquid Pipe Gas Connecting Method Between I.D &O.DMAX.Drop MAX.Piping length Indoor unit Panel Outdoor unit PIPING

Model BTU/h W W BTU/W 10m/h NVHz A/A A Cooling 28000 3200 4500 8.75

AD28NAMBEA Heating 32000 3300 5500 9.7 3 /

3N 380V-400V 50HZ
Cooling 5.5/8.0 Heating 5.8/9.5 30 AD28NAMBEA(WHITE) CentrifugalX 2 980 +30/890 +30/810 +50 0.13 1470/1300/1100

r/min kW m/h mm m
mmmmmm mmmmmm

TP2M/9.52 0.199
2-7

mm mm kW dB(A) kg / kg
mmmmmm mmmmmm

990650300 1137800320 PVC 26/32 Wired+Remote


/ /

kg / kg

r/min kW m/h mm m
mmmmmm mmmmmm

mm mm/mm L dB(A)

W kg / kg g g/m mm mm m m

35/32/29 40/57 / / / / / / / / / / / / / / / / / / / / / / / /
R407C 2550 60 9.52 15.88 flared 20 30

-9-

item Function Capacity Total power input Max. power input EER or COP Dehumidifying capacity Power cable Power source Running /Max.Running Start Current Unit model (color) Fan Type Number Speed(H-M-L) Fan motor output power Air-flow(H-M-L) Heat exchanger Type / Diameter Total Area Temp. scope Dimension External LWH Package LWH Drainage pipe (material , I.D./O.D.) Control type (Remote /wired) Fresh air hole dimension Electricity Heater Noise level (H-M-L) Weight (Net / Shipping) Dimension External LWH Package LWH Weight (Net / Shipping) Unit model (color) Compressor Model / Manufacture Type Fan Type Number Speed Fan motor output power Air-flow(H-M-L) Heat exchanger Type / Diameter Total area Temp. scope Dimension External LWH Package LWH Drainage pipe (material , I.D./O.D.) Refrigerant control method Defrosting Volume of Accumulator Noise level Type of Four way valve material of reduce noise crankcase heater power Weight (Net / Shipping) Refrigerant Type / Charge Recharge quantity Liquid Pipe Gas Connecting Method Between I.D &O.DMAX.Drop MAX.Piping length Indoor unit Panel Outdoor unit PIPING

Model BTU/h W W BTU/W 10m/h NVHz A/A A Cooling 28000 3200 4500 8.75

AC28NACBEA Heating 32000 3300 5500 9.7 3 /

3N 380V-400V 50HZ
Cooling 5.5/8.0 Heating 5.8/9.5 30 AC28NACBEA(WHITE) CentrifugalX2 1300 +30/1250 +40/1150 +50 0.04 1300/1250/1150

r/min kW m/h mm m
mmmmmm mmmmmm

TP2M/9.52 0.199
2-7

mm mm kW dB(A) kg / kg
mmmmmm mmmmmm

1320715235 1380770300 PVC 18/20 Remote


/ /

kg / kg

r/min kW m/h mm m
mmmmmm mmmmmm

mm mm/mm L dB(A)

W kg / kg g g/m mm mm m m

42/40/38 40/57 / / / / / / / / / / / / / / / / / / / / / / / /
R407C 2550 60 9.52 15.88 flared 20 30

-10--

item Function Capacity Total power input Max. power input EER or COP Dehumidifying capacity Power cable Power source Running /Max.Running Start Current Unit model (color) Fan Type Number Speed(H-M-L) Fan motor output power Air-flow(H-M-L) Heat exchanger Type / Diameter Total Area Temp. scope Dimension External LWH Package LWH Drainage pipe (material , I.D./O.D.) Control type (Remote /wired) Fresh air hole dimension Electricity Heater Noise level (H-M-L) Weight (Net / Shipping) Dimension External LWH Package LWH Weight (Net / Shipping) Unit model (color) Compressor Model / Manufacture Type Fan Type Number Speed Fan motor output power Air-flow(H-M-L) Heat exchanger Type / Diameter Total area Temp. scope Dimension External LWH Package LWH Drainage pipe (material , I.D./O.D.) Refrigerant control method Defrosting Volume of Accumulator Noise level Type of Four way valve material of reduce noise crankcase heater power Weight (Net / Shipping) Refrigerant Type / Charge Recharge quantity Liquid Pipe Gas Connecting Method Between I.D &O.DMAX.Drop MAX.Piping length Indoor unit Panel Outdoor unit PIPING

Model BTU/h W W BTU/W 10m/h NVHz A/A A Cooling 28000 3200 4500 8.75

AB28NACBEA Heating 32000 3300 5500 9.7 3 /

3N 380V-400V 50HZ
Cooling 5.5/8.0 Heating 5.8/9.5 30 AB28NACBEA(WHITE) Centrifugal1 700+30/590+40/470+50 0.04 1300/1100/870

r/min kW m/h mm m
mmmmmm mmmmmm

TP2M/7 0.199
2-7

mm mm kW dB(A) kg / kg
mmmmmm mmmmmm

840840240 910910300 PVC 26/32 Remote


/ /

kg / kg

r/min kW m/h mm m
mmmmmm mmmmmm

mm mm/mm L dB(A)

W kg / kg g g/m mm mm m m 11-

39/37/35 28/30 950x950x80 980x980x100 6/9 / / / / / / / / / / / / / / / / / / / / /


R407C 2550 60 9.52 15.88 flared 20 30

SAFETY PRECAUTIONS

3 SAFETY PRECAUTIONS
Please read these "Safety Precautions" first then accurately execute the installation work. Though the precautionary points indicated herein are divided under two headings, WARNING and CAUTION those points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the WARNING section. However, there is also a possibility of serious consequences in relationship to the points listed in the CAUTION section as well. In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned. After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's manual. Moreover, ask the customer to keep this sheet together with the owner's manual.

WARNING
This system should be applied to places of office, restaurant, residence and the like. Appliaction to inferior environment such as engineering shop could cause equipment malfunction. Please entrust installation to either the company which sold you the equipment or to a professional contractor. Defects from improper installations can be the cause of water leakage, electric shocks and fires. Execute the installation accurately, based on following the installation manual. Again, improper installations can result in water leakage, electric shocks and fires. When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration. In regards to preparing this countermeasure, consult with the company from which you purchased the equipment, and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold concentration does occur,there is the danger of a resultant oxygen deficiency accident. For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient, injury can result from a falling of the unit. Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit. For electrical work, please see that a licensed electrician executes the work while following the safety standards related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive use circuits are used. Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and fires. Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to the terminal connection part, through properly securing it. Improper connection or securing can result in heat generation or fire.
Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can also result in heat generation or fire.

- 12 -

SAFETY PRECAUTIONS

WARNING
When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated refrigerant (please see nameplate) within the refrigeration cycle. Rupture and injury caused by abnormal high pressure can result from such mixing. Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this company can result in water leakage, electric shock, fire and refigerant leakage. The position of indoor unit must be above the floor 2.5m.

CAUTION
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightening rod or a telephone ground wire. Improper placement of ground wires can result in electric shock. The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not installing an earth leakage breaker may result in electric shock. Do not install the unit where there is a concern about leakage of combustible gas. The rare event of leaked gas collecting around the unit could result in an outbreak of fire. For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.

- 13 -

4.Net dimensions of indoor and outdoor unit


Indoor unit Models 1) AB242ACBEA AB28NACBEA

2) AD242AMBEA
fresh air outlet

AD28NAMBEA
35 275 260 35 655

drainage pipe

B-B

A-A
liquid pipe gas pipe

A-A

-14-

3) AD242AHBEA

4) AC242ACBEA

6 5 5

2 0 0 240

5)AC28NACBEA

105

195

300
85

600
590 545

600
555

630 690

310.63

10

10
110

60 85 150

1320 1200
100

R15

180

85

60

150

100
85

6)AU242AHBEA AU28NAHBEA AU282AHBEA


185 18 70 55 580 185

380

18

Screw Hole (M10)

70

1024 70 Power Wiring Terminal

340

65 45

235

30

195

300

25

840

Power Wiring Distribution Hole

25

-15-

5.Installation Instructions
1. Installation Tools
1) Driver 2) Hacksaw 3) Hole core drill 4)Hexagon wrench(5mm) 24mm) 6) Torque wrench(17,22,24mm) 7) Pipe cutter 8) Flaring tool For example: use two spanner to joint the pipe 5) Spanner(14,17,19 and

2. Standard Accessories
The standard accessories includes : 1) Measuring type 2) Reamer leakage detector or soap-and-water solution 5) Knife 6) Nipper 3) Refrigerant oil 4) Gas

3. Installation Dimensions of Indoor & Outdoor units Please to see the Mechanical Data 4. Installation procedures & Points of attention 4.1 The Order of Installation Work
Work
Before installation Work Work division Make installation diagram Installation of indoor and outdoor unit Refrigerant pipe work Drain pipe work Heat insulation work Wiring work (control wire, power cord) Set every set switch Airtight test Vacuum drying Additional refrigerant Test run adjustment Training of use and maintenance

Main points
To ascertain the responsible for installation of pipes and wiring To ascertain the pipe installation dimension and position of electronic expansion valve, to make control wiring diagram To prevent the ventilation from short circuit and guarantee repair space Pay attention to dry, clean and seal Slant downward No gaps in the joint of heat insulation material Choose the proper wire and cord Should be complied with control wiring system diagram Close all the gas, liquid valve Should the vacuum pump that can reach 200Pa vacuity Wire down the additional refrigerant amount on the outdoor unit body and record table Do test run to indoor unit by one to verify if there is wrong pipes Explain to user, simultaneously provide all the documents

4.2

Attentive matters of safety

Before installing, do read this [Attention matter of safety] carefully to guarantee the proper installation. The below attentive matters are divided into [warning] and [note] two parts. When the wrong installation occurs, it is very possible lead to death and severe injury, and other serious accidents will happen. For those items are listed in [warning] part. But even the items very important contents related to safety, so they must be obeyed. After installation, do test operation to verify everything is normal, after that please explains the use method and maintenance method to the user according to the operation manual. Additionally, give the installation manual together with operation manual to the user and ask them to keep them properly.

<Heat Pump model/Cooling Only model >


WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE. BE SURE TO READ INSTALLATION MANUAL FOR INDOOR UNIT WITH THIS MANUAL.

1. Accessories
"Edging" for protection of electric wires from an opening edge.

Edging

2. Selection of the place of installation


Select the place of installation satisfying the following conditions and, at the same time, obtain a consent from the client or user. Place where air circulates. Place free from heat radiation from other heat sources. Place where drain water may be discharged. Place where noise and hot air may not disturb the neighborhood. Place where there is not heavy snowfall in the winter time. Place where obstacles do not exist near the air inlet and air outlet . Place where the air outlet may not be exposed to a strong wind. Place surrounded at four sides are not suitable for installation. A 1m or more of overhead space is needed for the unit. Mount guide-louvers to place where short-circuit is a possibility. When installing several units, secure sufficient suction space to avoid short circuiting. (1) Open space requirement around the unit
Unit: mm
Air inlet L3

L2
Air inlet Air outlet

500
(Servicing space)

Distance L1 L2 L3

Case

I open 300 150

II open 0 300

III 500 open 150

L1

(2) Installation where the area with strong winds. Install the unit so that the air outlet section of the unit must NOT be faced toward wind direction.

3. Installation of outdoor unit


(1) Installation
(a) Concrete foundation
Unit Unit Anchor bolt Concrete foundation Anchor bolt Concrete foundation

NO
Wind direction

Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following .
Foundation anchor
Unit

To fix by bolts

Note (1) Give enough room for the concrete foundation to fix by anchor bolts.

Note (1) Place the concrete foundation deep enough.

Install the unit so that the angle of inclination must be less than 3 degrees.

4. Refrigerant piping
(1) Outline piping (2) Piping size
Model Gas piping Liquid piping 14,18 series 15.88(5/8")x1.0mm 6.35(1/4")x0.8mm 24,28 series 15.88(5/8")x1.0mm 9.52(3/8")x0.8mm 36,42 series

Flare connection Gas pipe

Check joint Service valve

Indoor unit
Liquid pipe

Outdoor unit
Flare connection

19.05(3/4")x1.0mm
_ 90+0.5

9.52(3/8")x0.8mm

Install the removed flared nuts to the pipes to be connected, then flare the pipes.

(3) Limitations for one way piping length and vertical height difference.
One way piping length: less than 15m (for 14,18 series), less than 30m (for 24,28 series), less than 50m (for 36,42 series). Vertical height difference: Less than 5m (for 14,18 series), Less than 15m (for 24,28 series), less than 30m (for 36,42 series).

Precautions for refrigerant piping Do not twist or crush piping. Be sure that no dust is mixed in piping. Bend piping with as wide angle as possible. Keep insulating both gas and liquid piping. Check flare-connected area for gas leakage. (4) Purging method ( the refrigerant is R407C)
To use vacuum pump
1 Detach the service port's cap of 3-way valve, the valve rod's cap for 2-way valve and 3-way's, connect the service port into the projection of charge hose (low) for gaugemanifold. Then connect the projection of charge hose (center) for gaugemanifold into vacuum pump.
Gaugemanifold For series 24,28
2-way valve 3-way valve

Vacuum pump
2-way valve 3-way valve

2 Open the handle at low in gaugemanifold, operate vacuum pump. If the scale-moves of gause (low) reach vacuum condition in a moment, check 1 again. 3 Vacuumize for over 15min. And check the level gauge which should read -0.1 MPa (-76 cm Hg) at low pressure side. After the completion of vacuumizing, close the handle 'Lo' in gaugemanifold and stop the operation of the vacuum pump. Check the condition of the scale and hold it for 1-2min. If the scale-moves back in spite of tightening, make flaring work again, the return to the beginning of 3 .

Gaugemanifold For series 36,42

2 Open
Vacuum pump

3 Close
2-way valve 3-way valve

For series 24,28


Open

Service port
90 90 4

90 for 6 sec.

4
2-way valve

Open the valve rod for the 2-way valve to and angle ofanticlockwise 90 degree. After 6 seconds later, close the 2-way valve and malethe inspection of gas leakage.
90 Open 90

3-way valve

Service port
4 90 for 6 sec.

For series 36,42

5 No gas leakage?

In case of gas leakage, tighten parts of pipe connection. If leakage stops, then proceed 6 steps.

If it does not stop gas leakage, discharge whole refrigerants from the serice port. After flaring work again and vacuumize, fill up prescribed refrigerant from the gas cylinder.
6

2-way valve 3-way valve

6 Detach the charge hose from the service port, open 2-way valve and 3-way. Turn the valve rod anticlockwise until hitting lightly. 7 To prevent the gas leakage, turn the service port's cap, the valve rod'd cap for 2-way valve and 3-way's a lottle more than the point where the torque increases suddenly. 8 After attaching the each caps, check the gas leakage around the caps.
2-way valve 3-way valve
6 6

For series 24,28

2-way valve Liquid pipe 9.52mm 3-way valve Gas pipe 19.05mm

For series 36,42

2-way valve 3-way valve

For series 24,28

For series 36,42

CAUTION: If the refrigerant of the air conditioner leaks, it is necessary to make all the refrigerant out, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate.

7 Valve rod cap 7 Valve rod cap 7 Service port cap 7 Valve rod cap 7 Service port cap

If needing to remove the refrigerant gas when installation or repair , please refer to the following procedures: 1. Cut off the power 2. (After confirming the power is cut off) pull the power cable plug terminals of the low-pressure pressure-switch out. 3. (After confirming the power cable terminals of the low-pressure pressure-switch is cut off) After powering on the unit again and switch to COOLING mode,perform refrigerant gas removing according to the normal refrigerant gas removing procedure. 4. After finishing refrigerant gas removing , cut off the power , then insert the power cable terminals of the low-pressure pressure-switch properly.

5. Electric wiring
WARNING
DANGER OF BODILY INJURY OR DEATH TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS. (1) Selection of size of power supply and interconnecting wires. Precautions for Electric wiring Electric wiring work should be conducted only by authorized personnel. Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires. Use copper conductor only. Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.) Item
Phase

Circuit breaker
Switch breaker (A) Overcurrent protector rated capacity (A)

Model
36,42 series, 28 series (380-400V,3N~,50Hz) 14,18, 24, 28 series (1PH,220-230V,50Hz)

Power source wire size (minimum)

Earth leakage breaker


Switch breaker Leak current

3 1

30 40

20 26

2.5mm2 4.0mm2

30 40

30mA 30mA

Outdoor Unit Installation

1. Accessories
"Edging" for protection of electric wires from an opening edge.

Edging

2. Selection of the place of installation


Select the place of installation satisfying the following conditions and, at the same time, obtain a consent from the client or user. Place where air circulates. Place free from heat radiation from other heat sources. Place where drain water may be discharged. Place where noise and hot air may not disturb the neighborhood. Place where there is not heavy snowfall in the winter time. Place where obstacles do not exist near the air inlet and air outlet . Place where the air outlet may not be exposed to a strong wind. Place surrounded at four sides are not suitable for installation. A 1m or more of overhead space is needed for the unit. Mount guide-louvers to place where short-circuit is a possibility. When installing several units, secure sufficient suction space to avoid short circuiting.
(1) Open space requirement around the unit
Air inlet

L3 500
(Servicing space)

L2
Air inlet Air outlet

L1

Note : (1). Fix the parts with screws (2).Don't intake the strong wind directly to the outlet air-flow hole. (3).A one meter distance should be kept from the unit top (4).Don't block the surroundings of the unit with sundries
Unit: mm

Case Distance L1 L2 L3

I
open 300 150

II
open 0 300

III
500 open 150

NO
Wind direction

(2) Installation where the area with strong winds. Install the unit so that the air outlet section of the unit must NOT be faced toward wind direction.

(2) Piping size


AU242AHBEA
Liquid pipe 9.52x0.8mm
90+0.5

Gas pipe

15.88x1.0mm

Install the removed flare nuts to the pipes to be connected, then flare the pipes.

(3) Limitations for one way piping length and vertical height difference.
One way piping length: less than 30m (for AU242AHBEA ). Vertical height difference: less than 20m (for AU242AHBEA).

Precautions for refrigerant piping Do not twist or crush piping. Be sure that no dust is mixed in piping. Bend piping with as wide angle as possible. Keep insulating both gas and liquid piping. Check flare-connected area for gas leakage.

(4) Piping connection


Connecting method (indoor unit) Apply refrigerant oil at half union as large and flare nut. To bend a pipe, give the roundness as possible not to crush the pipe. When connecting pipe, hold the pipe centre to centre then screw nut on by hand, refer to Fig. Be careful not to let foreign matters, such as sands enter the pipe. Forced fastening without centering may damage the threads and cause a gas leakage. Pipe dia Liquid pipe 9.52mm Gas pipe 15.88mm Fastening torque 42N.m 98N.m

5. Air discharging method


After finishing connection of refrigerant pipe, it shall perform air tightness test. The air tightness test adopts nitrogen tank to give pressure according to the pipe connection mode as the following figure shown. The gas and liquid valve are all in close state. In order to prevent the nitrogen entering the circulation system of outdoor unit, tighten the valve rod before giving pressure (both gas and liquid valve rods).
Low pressure peizometer High pressure peizometer

Indoor

Outdoor

3-way valve totally closed (Gas side)

VL VH

Meter separator

Completely tightened

Flare part

Discharging valve

Completely tightened

Flare part

Manhole

Dropping valve
Nitrogen tank

Indoor units

Outdoor units
2-way valve totally closed (Liquid side)

First step: 0.3MPa (3. 0kg/cm2g) pressurize over 3 minutes. Second step: 1.5Mpa (15kg/cm2g) pressurize over 3 minutes. Large leakage will be found. Third step: 3.0 MPa (30kg/cm2g) pressurize about 24 hours. Little leakage will be found.

Check if the pressure drops


The pressure does not drop-passed The pressure drops-check the leaking point.
From pressurizing to 24 hours later, each 1* difference of ambient temperature will make 0.01MPa(0.1kg/cm2g) pressure change. It shall be corrected during test.

Checking the leaking point


In the first to third test steps, if the pressure drops, check the leakage in each joint use sense of hearing, feeling and soap water, etc. methods to find the leaking point. After confirming the leaking point, welding it again or tighten the nut tightly again.

6. Piping and indoor unit vacuumizing


Use vacuum pump to perform vacuumizing. It is strictly forbidden to use the refrigerant to remove the air inside the system. After air tightness test and discharging all the nitrogen, connect the vacuum pump as the following figure shown. Low pressure peizometer
High pressure peizometer Outdoor
3-way valve totally closed (Gas side)
V L VH

Indoor Completely tightened

Meter separator

Flare part

Discharging valve
P

Completely tightened

Flare part

Vacuum pump

Indoor units

Outdoor units
2-way valve totally closed (Liquid side)

It shall use the vacuum pump of (lower than -755mmHg)high vacuum degree and large air discharging (over 40l/min). The vacuumizing time depends on the length of the connecting pipe, generally is 1~2 hours. When vacuumizing, it shall be confirmed both gas and liquid side valves are closed. If after 2 hours vacuumizing, it cannot reach the vacuum degree below -755mmHg, it can be vacuumized for other 1 hour. If after 3 hours vacuumizing, it still cannot reach the vacuum degree below -755mmHg, check if there is any leaking point and repair the them. If after over 2 hours vacuumizing, the vacuum degree is below -755mmHg, close the VL and VH on the meter separator and stop vacuumizing. 1 hour later to confirm if the vacuum degree changes. If changes, it indicates there is leaking point in the system. Check the leaking point and repair. After finishing the above vacuumizing, change the vacuum pump into refrigerant pump to charge the refrigerant.

7. Charging amount of refrigerant


When the total length (L) of the two indoor units' connecting pipe is less than 5m, it is unnecessary to charge additional refrigerant. If the connecting pipe (L) exceeds 5m, it shall charge Mg additional refrigerant per meter. That is: Refrigerant charging amount = (L-5) x M (g) For AU242AHBEA, M=65 Only in COOLING operation can charge the additional refrigerant. When charging, the refrigerant shall be charged from the charging nozzle of low pressure vavle. Be carefull when charging refrigerant, do not let the air mix into the system,and must charge the additional refrigerant in liquid condition.

Warning
The distributing shop, where you brought the air conditioner, or the specified shops shall do the installation work. If you do the installation work by yourself, the improper installation will cause water leakage, electric shock fire and other accidents. The installation work shall be in line with what the installation manual specified. If installation is not proper, water leakage, electric shock, fire and other accidents will occur. Install the conditioner to a place where can definitely stand its weight. Please not firm enough, it will cause droop down of unit resulting in body hurt. The installation work shall be preventive to typhoon and earthquake. If the installation work is not met with the requirements, overturn of the unit will occur resulting in accidents. The wiring work should be down by a qualified person and referred to the technical standard of electric equipment , indoor wiring regulation and what the manual specified. Do use special circuit. If the capacity of the circuit is not enough or bad work, electric shock, fire and other accidents will happen. Using the specified cable to do wiring work and connecting firmly and properly. Fix the connecting part of the terminals to prevent it from the external force. Improper connection and fixing will cause heating and fire etc. accidents. Wring shall be kept in correct shape avoiding extrusion. After installation, the electric box cover and the external panel shall not nip the wire. Improper installation will cause heating and fire etc. accidents. when setting or moving the air conditioner do not let the air and things alike get into the refrigeration system except the specified refrigerant (R407C). If air and other things enter, abnormal high pressure will occur, which easily cause breaks and body injuries etc. accidents. When installing, do not use the accessories or specified parts. If not using the parts specified by our company, water leakage, electric shock, fire and refrigerant leakage will occur. Do not lead the drainpipe to where the sulphur gas may be involved. Otherwise, the poisonous gas will enter into the door. During installation, if refrigerant leakage occur, do the ventilation work immediately. As soon as the refrigerant gas meets fire, poisonous gas will be produce. If the refrigerant gas enter into room and meet the air blowing heater, heater or stove etc. fire source, the poisonous gas may be produced. After installation, confirm there is no leakage of refrigerant. Do not install the unit in a place where the combustible gas may be leaks. In any case the combustible gas leaks and accumulated around the unit, fire accident will occur. Do heat insulation work to the refrigerant gas pipes and liquid pipes to reach the purpose of heat preservation. If the heat insulation measure is not sufficient, water generated by condensing dew will drip leading to wet the floor and indoor articles. Do not damage the power line or change it arbitrarily to avoid occurrence of fire or electric shock. Do not extend the power line or using other electric appliance in the same power receptacle to avoid fire or electric shock.

Note
Do grounding work. Do not connect the grounding wire to gas pipe, tap, lighting rod or telephone line. Improper grounding will cause electric shock. In some places the electric leakage breaker shall be installed. If do not install the breaker, electric shock may occur. After installation, power on to do electric leakage detecting test.

5.3 Special Work and Main Points in Installation


Warning During installation, if refrigerant leakage occurs, After finishing installation, confirm the refrigerant take ventilation measurement immediately. gas dose not leak. If the refrigerant gas leaks in the room, once it soon as the leaked refrigerant gas meets fire, meets heater, burner and gas stove etc. fire As poisonous gas will generate. source, the poisonous gas will generate. A. Choosing of pipes According to the following indoor unit and unit installation diagram to choose the material and size of pipes and branch pipes. B. Connection of pipes 1. Method of pipe connection The pipe shall be as short as possible to guarantee efficiency Daub the refrigerant oil on the connection and flare nut When bending the pipes, give the roundness as large as possible, to avoid crashing the pipes To connect the pipe, fit the center and screw the nut with hand, the use spanner or torque wrench to tighten it. The fastening torque showed in below table, and shown in figure. Be careful alien matter, such as sands, water etc. shall not enter the pipes. Forced fastening without careful centering may damage the threads and cause gas leakage 2. Welding of pipes In welding, the nitrogen shall be used to avoid oxidation of the pipe inner part. The refrigerating pipe shall use clean new pipes. When working, it shall take steps to prevent water and dust from entering. When loosening and tightening the nuts, two spanners shall be used. If using one spanner, it can not reach the desired degree of tightness. Using the specified fastening torque to fasten nuts. Pipe diameter (mm) Installation torque(N.M.) 6.35 11.8(1.20kgf.m) 9.52 24.5(2.50kgf.m) 1 2.7 49.0(5.0kgf.m) 15.88 78.4(8.0kgf.m)

Fastening torque (N.M.) 13.7(1.4kgf.m) 29.4(3.0kgf.m) 53.9(5.5kgf.m) 98.0(10.0 kgf.m)

5 Checks after the installation


After the installation, please to check the connection of wire: If the wire have the same diameter in the two sides of the terminal If the wire placed on both the side of terminal but one side

To see the follow figure: means the right connection means wrong

INSTALLATION INSTRUCTIONS

5 INSTALLATION INSTRUCTIONS
5.1 Installation tools
1. Cross screwdriver 2 .Metal saw 3 .60,70mm drill 4. Inner hexagon spanner, shifting spanner 5 .Spanner(14, 17, 19,24,27mm diameter) 6. Pipe cutter 7. Pipe expander 8. Knife 9 .Pliers 10. Leak detector or soap liquor 11. Measuring tape 12 .Scraper 13. Refrigeration oil 14 .Vacuum pump 15 .Flat screwdriver

5.2 Standard accessories


Please check if your unit is delivered with following
Part name QTY
1

Clamp

Washer 8 Piece

Clamp 6 Piece

Drain hose 1 Piece

Paper pattern 6 Screw(M5 size) 1 Set 3 Piece For installation of paper pattern

2 Piece

Shape

Part name QTY

Insulator 1 Piece

Insulator 9 Dry battery 10Sealing pad 11 Sealing pad 12 Sealing pad 1 Piece 2 Piece
R03, 7#

[Other] Operation Manual Ornament panel Remote controller

1 Piece
Large size

1 Piece
Medium size

2 Piece
Small size

For gas pipe For liquid pipe

Shape

5.3 Installation of indoor unit


5.3.1 Before installation Determine the way kto carry unit to installation place. Don't remove packing until unit reaches installation place. If unpacking is unkavoidable, protect unit properly. 5.3.2 Selection of installation place (1) Installation place shall meet the following and agreed by customers: Place where proper air flow can be ensured. No block to air flow. Water drainage is smpoth. Place strong enough to support unit weight. Place where inclination is not evident on ceiling. Enough space for mainenance. Indoor and outdoor unit piping length is within limit. (Refer to Installation Manual for outdoor unit.) Indoor and outdoor unit, power cable, inter unit cable are at least 1 m away fromT.V. radio. This is helpful to avoid picture disturbance and noise. (Even if 1 m is kept, noise can still appear if radio wave is strong)

INSTALLATION INSTRUCTIONS

(2) Ceiling height Indoor unit can be installed on ceiling of 2.5-3m in height. (Refer to 8 Foeld setting and Installation Manual of ornament panel.) (3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take necessary measures in case it is not safe. (Distance between holes are marked on paper pattern. Refer to paper pattern for place need be reinforced) Installation space
260 260
Air inlet Air outlet Air inlet 1500 Over 1500 Over

2500 Over

Air outlet 1500 Over

Air inlet

Air outlet

1500 Over

5.3.3 Preparation
(1) Position of ceiling opening between unit and suspending bolt. AB14, 18
Ornament panel 630mm ceiling opening 600mm

Unit: mm

Indoor unit 570mm

Overlap between ceiling and ornament panel shall be 15mm Suspending bolts

210mm

suspending bolts 460mm

Ornament panel

Indoor unit 570mm Ceiling opening 600mm Ornament panel 630mm

35mm

Distance between

Ceiling

335mm

INSTALLATION INSTRUCTIONS

AB24,28
(Distance between suspending bolts)

950(Ornament panel)

890(Ceiling opening)

840(Indoor unit)

Refrigerant pipe

780

Suspending bracket
Suspending bolts
(160)

A (Distance between suspending bolts) 840(Indoor unit) 890(Ceiling opening) 950(Ornament panel)

Ceiling

A
AB36,42
890(Ceiling opening) 1070 (Distance between suspending bolts) 515
780(Distance between suspending bolts)

860(Ceiling opening)

Note: Dimension of ceiling opening marked with * can be as large as 910mm, but the matching part of ceiling with ornament panel shall be over 20mm.

20 Over

515

(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.) Refer to paper pattern for dimension of ceiling hole. Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation. Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration. Contact your real estate dealer
(3) Install a suspending bolt. (Use a M10 bolt) To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new ceiling, use built-in type bolt or parts prepared in the field. Before going on installing adjust space between ceiling. <Installation example>
Roof Anchor bolt Long nut Suspending bolt

50~100

Ceiling

Note: All the above mentioned parts shall be prepared in field.

INSTALLATION INSTRUCTIONS
5.3.4 Installation

In the case of new ceiling


(1) Install unit temporally Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket. (2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details. Center of the hole is marked on the paper pattern. Center of the unit is marked on the card in the unit and on the paper pattern. Mount paper pattern 4 onto unit using 3 screws 5 . Fix the corner of the drain pan at piping outlet.

< After installation on the ceiling >


(3) Adjust unit to its right position. (Refer to preparation for the installation-(1)) (4) Check unit's horizontal level. Watert pump and flating switch is installed inside indoor unit, check four corners of the unit for its level using horizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage, problem may occur on floating switch, causing water leakage.) (5) Remove the washer mounlting 7 , and tighten the nut above. (6) Remove the paper pattern.

In the case of ceiling already exists


(1) Install unit temporally Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket. Fix the bracket firmly. (2) Adjust the height and position of the unit. (Refer to preparation for the installation (1) ). (3) Proceed with 3 and 4 of "In the case of new ceiling".
Scrtews at the piping outlet is fixed at the corner of drain pan.

Center of ceiling hole Paper pattern

Paper pattern 4

Level

Polythene pipe
Screw 5 (accessory) Screw 5 (accessory)

[Fix the paper pattern]

5.3.5 Refrigerant piping

As for outdoor piping, please refer to installation Manual of outdoor unit.


Outdoor is precharged with refrigerant. Be sure to see the Fig.1, when connecting and removing piping from unit. For the size of the flare nut, please refer to Table 1. Apply refrigerant oil at both inside and outsid of lflare nut. Tighten it band tight 3-4 turns then tighten it. Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage). Check piping joints for gas leakage. Insulate piping as shown in Fig. below. Cover joint of gas piping and insulator 6 with seal 9 .
Table 1
Pipe size
Apple refrigerant oil
Medium size seal pad 9 (accessory) (Cover the piping joint with seal pad.)
(333~407kgf.cm) 6180~7540N.cm

Tighten torque
3270~3990N.cm

A(mm)

Flare shape

Torque spanner
Clip 3

15.88

(630~770kgf.cm) 9720~11860N.cm (990~1210kgf.cm)

18.6~19.0

spanner

Insulator (accessory) 7 (For liquid pipe) Insulator (accessory) 6 (For gas pipe)

19.05

22.9~23.3

Diameter of Pipe Liquid Pipe 6.35mm Gas Pipe 12.7mm

Piping joing Flare nut

Gas pipe Liquid pipe

90 0.5 45 2 A

9.52

12.0~12.4

R0.4 ~ 0.8

Tighten Torque 18 N. m 50N. m

INSTALLATION INSTRUCTIONS

5.3.6 Installation of drainage pipe


(1) Install water drainage pipe Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm) Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening. If downward slope can't be made, take other measures to lift it up. Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.
1-1.5m

Slope over 1/100

Waterring can of plastic

Use the self-provided stiff pipe and clip 2 with unit. Insert water pipe into water plug until it reaches the white tape. Tighten the clip until head of the screw is less than 4mm from hose. Large size seal pad 10 Wind the drain hose to the clip using seal pad 8 . (accessory) Insulate drain hose in the room.
Clip 2

Clip 2 (accessory)

Tape (White)

Self-provided stiff pipe

4mm below

<Cautions for the drain water lifting pipe>


Installation height shall be less than 280mm. There should be a right angle with unit, 300mm from unit.
1~1.5m

300mm below

Suspending bracket
220 280 below

drain water lifting pipe

(Note) The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it. If several water hoses join together, do as per following proceedures.
Over 100
Connect water hoses with a T joint.

Clip 2 (accessory)

Specifieations of the water hoses shall meet the requirements for the unit running.

(2) Check if water drainage is smooth after installation.


Charge, through air outlet or inspecting hole, 1200ccd water to see water drainage.

After wiring
Check water drainage in cooling operation. See also
11

500 below

test run.

When wiring is not complete


Remove cover of control box, short connect "CHECK" terminal of the indoor unit, which is on the uper part of indoor unit PCB. Connect 1PH power to terminal 1 and 2 on terminal block. Note, in this operation, fan will be running. Upon confirmation of a smooth water drainage, be sure to cut off power supply andremove short Indoor connection of "CHECK" terminal. 1 2 3 Method of water charging
Self-provided stiff pipe Water drainage port for maintenance (Drain water from this hole) Maintenance

75 below

Drain hose 1 (accessory)

500 below

Self-provided stiff pipe (accessory)

Connect with outdoor unit


Inspecting hole

Terminal block
L N
PCB on indoor Terminal

H05RN-F 2 4G 0.75mm
1 2 3
Outdoor Indoor
1 2 3

Power

H07RN-F 2 3G 4mm

100mm Watering can of plastic pipe should be about 100 mm long

Charge water from inspecting hole

H05RN-F 2 4G 0.75mm

R S T N 1 2 3
Charge water from air outlet

Cover of controll box

Power

Outdoor

H07RN-F 2 5G 2.5mm

INSTALLATION INSTRUCTIONS

5.3.7 Wiring
All supplied parts. materials and wiring operation must in appliance with local code and regulations. Use copper wire only. When make wiring, please refer to wiring diagram also. All wiring work must be done by qualified electricians. A circuit breaker must be installed, which can cut power supply to all system. See Installation Manual of outdoor unit for specifications of wires, circuit breaker, switches and wiring etc. Connecting of unit Remove cover of switch box (1) , drag wires into rubber tube A, then, after proper wiring with other wires, tighten clamp A. Connect wires of correct pole to the terminal block inside. Wind seal (12) around wires. (Be sure to do that, or, dew may occur). Upon connecting, replace control box cover (1) and (2).

Connect with outdoor unit

Terminal block

Terminal block Clip A

Cover of control box

Don't fail to seal it, or, water may come in. Rubber tube Note: Have it sealed, leaving no space.
12 Seal pad (small size)( ) (Wind around wire)

Grounding lead Rubber tube A


Cover of control box 1

In

Out Field wiring

Attach seal pad

<<WARNING>>
Connect wires of the same Don't connect wires of the Don't connect wires of the Obscrve the following when connecting power supply terminal block: specifications at two sides. same specifications at one side. different specifications. Don't connect wires of different specifications to the same terminal block. (Loose wire may cause overheating of circuit) Connect wires of same specifications as shown in right Fig.

5.3.8 Wiring example


As for outdoor unit circuit, please see Installation Manual of outdoor unit. Note: All electric wires have their own poles, poles must match that on terminal block.

5.3.9 Installation of ornament panel


Cautions for the installation

Be sure to show customers Operation Manual and guide them how to operate unit correctly. Before installation, read also the Installation Manual of indoor unit. With this ornament , 2 or 3 air flow direction is not available. Suitable height is 3 m.
Accessory Pad
Pad

1. Prepare ornament panel Handling of ornament panel


Ornament panel shall not be placed face down or against wall, neither on an uneven object. Don' t bend carelessly the swing flap, or, problem may occur.

(1) Remove air inlet grill from ornament panel: 1 Push in the bar on inlet grill and lift it up. (Refer to Fig. 1) 2 Lift it up for about 45 degree and remove it from ornament.

Tear off adhesive tape fixing air filter on the back of the air inlet grill. (Refer to Fig. 2)
Bar

INSTALLATION INSTRUCTIONS

(2) Remove cover plate at corner Tear off the adhesive tape, and slide it off. (Refer to Fig. 3)

Slide
Adhesive tape
45

2. Install ornament panel on indoor unit.


(1)

Fig. 3

For indoor unit installation, please refer to Installation Manual.

Fig. 2

1 As shown in Fig . 7, match the position of Holding ring swing flap motor with that of the indoor unit 2 Piping hole position piping hole , so that ormament panel can be placed on to indoor unit. (2) Installation of ornament panel 2 1 Place the holding ring on swing flao motor side teporarily on hooks of the indoor unit. Swing flap motor (2 pcs) 2 Put the other two holding rings on the hooks at 3 both side of the indoor unit. (Care should be taken not to push wiring of swing flap motor into seals). 4 3 Screw in all 4 screws under holding ring for Fig. 7 about 15mm. (Pancl will rise). Seal Indoor unit 4 Adjust the ornament panel as per Fig. 7 to Ceiling material cover opening on the ceiling. 5 _ 8mm 5 Tighten screws to redrce the thickness of seals between ornament and indoor unit to 5Ornament panel 8mm. Caution

Hook

If screws are not tighten tight, problems in Fig, 8 might occur. Tighten screws properly.
Gas leakage. Gas leakage from roof. Contamination

If there are still space after tightening of screws, please readjust the height of indoor unit. (Refer to Fig. 9)

If indoor unit is at horizontal level and water drainage is smooth, then, indoor unit height can be adjusted throrgh holes at corners of ornament panel.

Mist exists and drop down.

Fig. 8

Leave no space.

Fig. 9

3. Mounting on high ceiling (1) Ornament panel can be mounted on ceiling as high as 3 m.

(2) Please install pad as accessary. 1 Cut open the pad along cutting ling. Use part a only and discard part b . (Refer to Fig. 4) 2 Install part a of the pad on the place shown in Fig. 5. Refer to Fig. 6.
Cutting line

Leave no space.
Place it on the frame.

50

100

Fig. 4

Part a of the pad Swing flap motor Fig. 5

Part a of the pad

Fig. 6

(3)Wiring on ornament panel Connecting of wiring of the swing flap motor on ornament panel. (2 places) (Refer to Fit . 10)

Side of ornament panel

If connecting is not made, error code (A7) appears on remote controller. So, make proper connecting.

Side of indoor unit

Fig. 10 Wiring diagram

INSTALLATION INSTRUCTIONS

4. Installation of inlet grill and cover plate (1) Installation of inlet grill Install in reversed order of Prepare ornament pandl. Inlet grill can be adjusted into four directions by turning inlet grill. Inlet grill position can be adjusted as per customers request.
When installing inlet grill, take care not to twist wiring of swing flap motor. (2) Install cover plate on the corner 1 As shown in Fig. 11 tie the cover plate onto the bolt on ornament plate. 2 Install cover plate onto ornament plate. (Refer to Fig. 12)
bolt

Slide all five hold rings


to let them drop in holes on ornament plate, Fig. 11 Fig. 12

5.3.10 Test running


Refer to Take special care during installation, check after working Upon installation of piping, water drainage and wiring work, make test run to ensure proper unit operation. Conduct test run after installation of ornament panel
Procedure (1) (2) (3) (4) (5) (6) Conduct test run before installing ornament panel Procedure (1) (2) (3) (4) (5) Operation Open check valve on gas pipe. Open check valve on liquid pipe. Press ON/OFF button, select Cooling mode. Let it run for 3 min. Cut main power supply after operation.

Operation
Open check valve on gas pipe. Open check valve on liquid pipe. Press ON/OFF button, select Cooling mode. Let it run for 3 min. Press air flow adjust button to make unit run properly Confirm unit functions according to Operation Manual.

Note: If unit doesnt run due to certain problem, please see Note to unit maintenance.

Preparation before installing convertible type unit


Before installation of convertible type unit, please confirm which type will be selected: in the ceiling or on the floor. There is a dial switch K1 on the PCB, if you select D, that means the installation is in the ceiling. If you select L, that means installation position is on the floor.

D L K1
In the ceiling mode, there will a 4 degrees temperature compensation in heating mode. Because in heating mode, the warm air will rise and stay in higher position. If there is not temperature compensation, when the set temperature has arrived, it may happen that the air in higher position has become the set temperature, but the air in lower position has not arrived the set temperature. There is no different for the operation of swing and the heating capacity.

Installation procedure of convertible type unit


INSTALLATION PROCEDURE
Install the room air conditioning unit as follows: Wrap the insulation around the drain hose connection.(Fig.6)
(Fig. 6)
Drain pan

PREPARING INDOOR UNIT INSTALLATION


FIRST REMOVE THE INTAKE GRILL

A. FLOOR MOUNTING
(AC36/42 only suitable for exposed ceiling mounting) 1. DRILLING FOR PIPING The piping and drain can exit the unit in two directions as shown below in (Fig. 2) (Fig. 2)
down

Drain hose

Insulation (Drain hose)

rear

Be sure to arrange the drain hose correctly as shown in Fig. 7 so that it is lower than the drain hose connecting point of the indoor unit, if condensate pump is not fitted to system.
Fig. 7 OK NO NO

The drain hose must be connected to the right side as shown in (Fig.3).
(Fig. 3)
Arrange the drain hose lower than this portion. Drain hose

CAUTION!
Ensure that the unit is fixed level. Height A must be less than 5 mm.(Fig.8)

Drain hose (Right side)

Drain hose

After the piping and drainage exit has been selected, drill a 7 cm dia. hole through the wall so that the hole is slanting downward toward the outside to ensure good drainage. When the pipe is led out from the rear, make a hole as Fig.4, at the position shown.
(Fig. 4)
Wall 6mm 7cm Indoor unit outdoor unit

B. UNDER CEILING MOUNTING


Fig 9
247mm

Using the installation template, drill holes for piping and anchor bolts(for holes).(Fig.9)
40 B 40 A

147mm

(Fig. 5)

100mm

87.5mm

Drain pan Nylon fastener (supplied by others) Drain hose

Model AC24 AC28 AC36/42

A 990 1320 1920

B 500 1240 1840

1. DRILLING FOR PIPING Select piping and drain directions. (Fig.10) Fig 10
Rear (Install the drain hose in this direction.)

53 85

2. INSTALLING DRAIN HOSE The drain hose must be connected to the right side of the unit (Fig.3) Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener. (Fig.5)

720mm 326mm

Installation procedure of convertible type unit


CAUTION
Install the drain hose at the rear; it should not be installed on the top or right side.

4. INSTALLING INDOOR UNIT Reset the hex bolts as shown in Fig.14.

After the piping and drainage exit has been selected, drill 80mm and 50mm or 150mm dia. hole through the wall. So that the hole is slanting downward toward the outside for smooth water flow if a condensate pump is not fitted to system. Wall
6mm

Fig. 14 Indoor unit

Hex bolt 8 to 13mm

Fig. 11

2. DRILLING HOLES FOR ANCHOR BOLTS AND INSTALLING THE ANCHOR BOLTS using a masonry drill, drill four 12.5 mm dia. Holes.(Fig.11) Fig. 11

Apply the indoor unit to the brackets.(Fig.15)


Fig. 15

Bolt
12.5mm

Bracket

Indoor unit

Insert the anchor bolts into the drilled holes, and drive the pins completely into the anchor bolts with a hammer. (Fig. 12)
Fig. 12

Now, securely tighten the hex bolts in both sides.

3. INSTALLING BRACKETS Install the brackets with nuts, washers and spring washers.(Fig. 13)
Fig. 13

5. INSTALL THE DRAIN HOSE The drain hose will be connected to the right side.(Fig.3) Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener.(Fig.5) Wrap the insulation (drain hose)around the drain hose connection. (Fig.9) Be sure to arrange the drain hose correctly so that it is lower than the drain hose connecting port of the indoor unit (Fig.16) if condensate pump is not fitted to system.

Fig. 16
Remove the hole cover.

Arrange the drain hose lower than this portion

Drain hose

Spring washer Special nut Bracket

OK

NO

381 68 16 21 28 26.5

5 4-R

7.5

10

2-R2.5

26.5 232

18

232 26.5

18

7.5

2-R2.5
5 4-R

26.5 381

28 21 16

10
68

Wiring
ELECTRICAL WIRING

CAUTION
(1) Match the terminal block numbers and connection cable colours with those of the outdoor unit. Incorrect wiring may cause damage to the electrical parts. (2) Connect the connection cables firmly to the terminal block. Incorrect installation may result in a fire. (3) Always fasten the outside covering of the connection cable with the cable clamp.(If the insulation is chafed, a short curcuit may occur.) (4) Always connect the earth wire.

1. INDOOR UNIT SIDE (1) Remove the electrical component box.

Fig. 25

Electrical component box

INDOOR UNIT SIDE


Fig. 26
Electrical component box

Remove the four self tapping screws.

CAUTION
Do not remove the screws. If the screws are removed, the electrical component box will fall.

Wiring
(2) Pull out the electrical component box.
Fig. 27

Electrical component box

(3) Remove the electrical component box cover.


Fig. 28

Base
Electrical component box cover

Remove the three tapping screws

CAUTION
Be careful not to pinch the wiring between the electric component box and base.

(4) Wiring
See wiring diagrams for indoor unit.

ELECTRICAL WIRING

WARNING
(1) Ensure all wiring complies with current regulations. (2) It is recommended that a MCB of the correct rating is used to protect the system. (3) Always use a circuit breaker that can trip all the poles of the wiring is fitted and has an isolation distance of at least 3mm between the contacts of each pole.

CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating manual: (1) Starting and stopping method, operation switching, temperature adjustment, timer, air flow switching, and other remote control unit operations. (2) Air filter removal and cleaning, and how to use air louvres. (3) Give the operating and installation manuals to the customer.

Installation procedure of mid ESP duct type


NOTICE
All Wiring of this installation must comply with NATIONAL, STATE AND LOCAL REGULATIONS. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter should be referred to your local distributor.

WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE.

(1) Preparation of indoor unit Before or during the installation of the unit, assemble necessary optional panel etc. depending on the specific type. (2) Select places for installation satisfying following conditions and at the same time obtain the consent on the part of your client user. (a) Places where chilled or heated air circulates freely. When the installation height exceeds 3m warmed air stays close to the ceiling. In such cases, suggest your client users to install air circulators. (b) Places where perfect drainage can be prepared and sufficient drainage. (c) Places free from air disturbances to the suction port and blowout hole of the indoor unit, places where the fire alarm may not malfunction or short-circuit. (d) Places with the environmental dew-point temperature is lower than 28 and the relative humidity is less than 80%. (When installing at a place under a high humidity environment, pay sufficient attention to the prevention of dewing such as thermal insulation of the unit.) (e) Ceiling height shall have the following height. Installation space
1000 or more

14,18,24,28 series
Combination with silent panel

36,42 series 416mm

100 or more

100 or more 50 or more

366mm

Obstacle

Unit: mm

(a) Size of hole at ceiling and position of hanging bolts <Combination with silent panel>
75 70 545 (Hanging bolt position) 30 690 (Ceiling hole size) (Ceiling ~ panel 750 wrap dimensions) (Panel dimensions) (Pipe connection side)

Unit: mm Dimensions A B C

Model

14,18,24,28 series

986

1180

1240

57

A
(Hanging bolt position)

137

36,42 series

1406

1600

1660

B
(Ceiling hole size)

30

C
(Panel dimensions)

(Ceiling ~ panel wrap dimensions)

Hole-in anchor Hole-in plug

Insert

(b) Hanger bolts installation Use care of the piping direction when the unit is installed.
Concrete Hanging bolt M10

(5) Installation of indoor unit Fix the indoor unit to the hanger bolts.If required, it is possible to suspend the unit to the beam, etc. Directly by use of the bolts without using the hanger bolts. Note

Hanging bolt M10 nut M10 washer

Main unit

M10 spring washer

When the dimensions of main unit and ceiling holes does not match, it can be adjusted with the slot holes of hanging bracket. Adjusting to the levelness (a) Adjust the out-of levelness using a level or by the following method. Make adjustment so that the relation between the lower surface of the unit proper and water level in the hose becomes as given below.
Piping side Supply water Water level 0~5 mm (0~0.2") PVC hose

Bring the piping side slightly lower.

(b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of the float switch may occur. Tap selection on blower unit (When the high performance filter is used.)

Taps of blower unit are set at the standard selection at the shipping from factory. Where the static pressure is raised by employing such option as the high performance filter, etc., change the connection of connectors provided at the flank of control box as shown below.
Standard tap (at shipping)
Control box side Connector white White Blue Yellow Red White Moter side Blue White Yellow Red

High speed tap


Connector white White Blue Yellow Red White Red Blue Red Moter side
Avoid riding across an elevation Air vent Keep free from traps Do not pipe under water

Black

(6) Drain Piping (a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an elevation or making traps. Good piping Inproper piping
Suspension 1.5m ~ 2m bolts

A downhill grade Heat insulation of 1/100 or more

(b) When connecting the drain pipe to unit, pay suffcient attention not to apply excess force to the piping on the unit side. Also, fix the piping at a point as close as possible to the unit. (c) For drain pipe, use hard PVC general purpose pipe VP-25(I.D.1") which can be purchased locally. When connecting, insert a PVC pipe end securely into the drain socket before tightening securely using the attached drain hose and clamp. Adhesive must not be used connection of the drain socket and drain hose (accessory).

Stage difference Drain hose Drain socket part Drain socket


VP 25 joint Pipe cover(large) (field purchased) [for insulation] (accessory)

Main unit

Drain hose Clamp (accessory) (accessory) Adhesion Pipe cover(small) [for insulation] (accessory)

VP 25 (field purchased) Pipe cover [for insulation] (field purchased)

(d) When constructing drain piping for several units, position the common pipe about 100 mm below the drain outlet of each unit as shown in the sketch. Use VP-30(11/4") or thicker pipe for this purpose. (e) Be sure to provide heat insulation to hard PVC pipes of indoor placement. (f) Do not ever provide an air vent. (g) The height of the drain head can be elevated up to a point 500 mm above the ceiling, and when an obstacle exists in the ceiling space, elevate the piping to avoid the obstacle using an elbow or corresponding gadget. When doing this, if the stretch for the needed height is higher than 500 mm, the back-flow quantity of drain at the event of interruption of the operation gets too much and it may cause overflow at the drain pan. Therefore, make the height of the drain pipe within the distance (h) given in the sketch below. Avoid positioning the drain piping outlet at a place where generation of odor may be stimulated. Do not lead the drain piping direct into a sewer from where sulfur gas Drainage Test
1 2 3 4

Secure the elevation as high as possible (approx. 100 mm)

A downhill grade of 1/100 or more

VP 30

(Maximum local drain up dimension)

290~325mm

Drain hose

Right overhead

Joint for VP 25 (Local procurement)

Conduct a drainage test after completion of the electrical work. During the trial, make sure that drain flows properly through the piping and that no water leaks from connections. In case of a new building, conduct the test before it is furnished with the ceiling. Be sure to conduct this test even when the unit is installed in the heating season.

Procedures
1 2

Supply about 1000 cc of water to the unit through the air outlet using a feed water pump.

Pour water into a convex joint.

Insert water supply hose for 20 mm ~ 30 mm to supply water. (Insert hose facing toward bottom.)
Attached drain hose clamp

Remove grommet. Make sure to install it back after test.

Main unit

Drain piping

(In the electrical work has not been completed, connect a convex joint in the drain pipe connection to provide a water inlet. Then, check if water leaks from the piping system and that drain flows through

Drain situation can be checked with transparent socket

600

(7) Installation work for air outlet ducts

Air conditioner main unit

Ceiling surface

Heat insulation

inlet duct (optional or marketat item)

Suction panel (Silent panel)

B Special blowout A Blowout duct C special inlet (option) (Optional or marketed item) (with air filter) (Option) Hole for check

Calculate the draft and external static pressure and select the length, shape and blowout. A Blowout duct 2-spot, 3-spot and 4-spot with 200 type duct are the standard specifications. Determine the number of spots based on following table. Note (1) Shield the central blowout hole for 2-spot. (2) Shield the blowout hole around the center for 3-spot. Limit the difference in length between spots at less than 2:1. Reduce the length of duct as much as possible. Reduce the number of bends as much as possible. (Corner R should be as larger as possible.)
Bad example Bad example Good example

Use a band. etc. to connect the main unit and the blowout duct flange. Conduct the duct installation work before finishing the ceiling. (8) Connection of suction, exhaust ducts
State seeing from top of unit
Exhaust hole

Side fresh air inlet Rear fresh air inlet

(a) Duct connection position


Fig.1

Fig.2

i) Fresh air inlet Inlet can be selected from the side or rear faces depending on the working conditions. Use the rear fresh air inlet when the simultaneous intake and exhaust is conducted. (Side inlet cannot be used.) ii) Exhaust (Make sure to use also the suction.) Use the side exhaust port.

Indoor unit installation (High ESP duct)


1. Before installation [Before finishing installation, do not throw the attached parts installation needs]
Confirm the way to move the unit to the installation place. Before moving the unit to the installation place, do not remove their packages. When have to remove the package, use a soft material or protection board with rope to lift the unit assembly to avoid unit damage or bumping a scrape.

2. Choose installation place


(1) The chosen installation place should meet the following requirements and get the users consent. Place ensures ideal airflow distribution. The passage of airflow has no obstacles. When importing outside air, it should be imported directly from outdoors. (if the pipe can not be extended, it also can not be imported from top) Place ensures enough space for maintenance. The pipe length between indoor and outdoor unit is in the permitted limit (referring to outdoor unit installation part). The indoor unit, outdoor unit, electric wire and connection wire is at least 1m away from television and radio. This is to avoid the image disturbance and noise caused by the above-mentioned home appliance. (Even if 1m away, if the electromagnetic wave is too strong, it can also cause noise.) (2) The height of ceiling The indoor unit can install on the ceiling, which height is no more than 3m. (3) Install and use the hoisting screw. Check if the installation place can bear the weight of unit assembly. If not certain, strengthen it before install the unit.

Air out

(600x600)

Air in Ceiling

Over 200

Over 300

Over 100

Over 900 Checking meatus

3. Preparation before installation


(1) The position relation among hoisting screw (unit: mm)

370
250

628 603

Down side Up side 590

(2) If necessary, cut the opening installation and checking needed on the ceiling. (If has ceiling) Before installation, finish the preparation work of all the pipes (refrigerant, drainage) and wire (wire controller connection wire, indoor and outdoor unit connection wire) of indoor unit, so that after installation, they can be immediately connected with outdoor unit. Cut the opening on the ceiling. Maybe it needs to strengthen the ceiling to keep the ceiling even and flat and prevent the ceiling from vibration. For details, please consult to the builder.

(3) Hanger bolts installation Use care of the piping direction when the unit is installed. (Use M10 screw bolt) In order to bear the weight of the unit, for existed ceiling, using foundation screw bolt, for new ceiling, using burying embedded screw bolt, burying screw bolt or spot supplied other parts. Before going on installation, adjust the gaps with ceiling.
Hanging bolt M10 Hole-in anchor Hole-in plug Insert

910

AD242AHBEA

Concrete

4. Installation of indoor unit Fix the indoor unit to the hanger bolts. If required, it is possible to suspend the unit to the beam, etc. Directly by use of the bolts without using the hanger bolts.

Hanging bolt M10 nut M10 washer

Main unit

M10 spring washer

Note When the dimensions of main unit and ceiling holes does not match, it can be adjusted with the slot holes of hanging bracket. Adjusting to the levelness (a) Adjust the out-of levelness using a level or by the following method. Make adjustment so that the relation between the lower surface of the unit proper and water level in the hose becomes as given below.
Piping side Supply water Water level 0~5 mm (0~0.2") PVC hose

Bring the piping side slightly lower.

(b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of the float switch may occur.

5. Drain Piping
(a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an elevation or making traps. Good piping
Suspension bolts 1.5m ~ 2m
Air vent

Inproper piping
Avoid riding across an elevation Keep free from traps Do not pipe under water

A downhill grade Heat insulation of 1/100 or more

(b) When connecting the drain pipe to unit, pay suffcient attention not to apply excess force to the piping on the unit side. Also, fix the piping at a point as close as possible to the unit.
Stage difference Drain hose part

(c) For drain pipe, use hard PVC general purpose pipe VP-25(I.D.1") which can be purchased locally. When connecting, insert a PVC pipe end securely into the drain socket before tightening securely using the attached drain hose and clamp. Adhesive must not be used connection of the drain socket and drain hose (accessory).

Drain socket Drain socket

Main unit

Pipe cover(large) [for insulation] (accessory)

VP 25 joint (field purchased)

Drain hose Clamp (accessory) (accessory) Adhesion Pipe cover(small) [for insulation] (accessory)

VP 25 (field purchased) Pipe cover [for insulation] (field purchased)

(d) When constructing drain piping for several units, position the common pipe about 100 mm below the drain outlet of each unit as shown in the sketch. Use VP-30(11/4") or thicker pipe for this purpose. (e) The stiff PVC pipe put indoor side should be heat insulated.

Secure the elevation as high as possible (approx. 100 mm)

A downhill grade of 1/100 or more

VP 30

(f) Avoid putting the outlet of drain hose in the places with irritant gas generated. Do not insert the drain hose directly into drainage, where the gas with sulfur may be generated. (g) Backwater bend Because the drain spout is at the position, which negative pressure may occur. So with the rise of water level in the drain pan, water leakage may occur. In order to prevent water leakage, we designed a backwater bend. The structure of backwater bend should be able to be cleaned. As the below figure shown, use T type joint. The backwater bend is set near the air conditioner. As figure shown, set a backwater bend in the middle of drain hose.

H2 H1

H1=100mm or the static pressure of air sending motor H2=1/2H1 (or between 50~100mm)

Drainage Test Conduct a drainage test after completion of the electrical work. During the trial, make sure that drain flows properly through the piping and that no water leaks from connections. 3 In case of a new building, conduct the test before it is furnished with the ceiling. 4 Be sure to conduct this test even when the unit is installed in the heating season.
1 2

Procedures
1 2

Supply about 1000 cc of water to the unit through the air outlet using a feed water pump. Check the drain while cooling operation.

6. Installation of air suction and discharging duct


muffler cavity (air sending) Sacking joint Insulation Enlarging chart of profile chart A Vibration resistance hook Air volume adjuster

Air outlet

Air conditioner main unit Checking meatus

Ceiling Air suction grille with air filter

Please consult the after-sales service worker of Haier Air Conditioner for the choosing and installation of suction inlet, suction duct, discharging outlet and discharging duct. Calculating the design drawing and outer static pressure, and choose the discharging duct with proper length and shape.

26

The length difference among every duct is limited below 2:1. Reduce the length of duct as possible as can. Reduce the amount of bend as possible as can. Use heat insulation material to bind and seal the part connecting main unit and the flare part of air discharging duct. Perform duct installation work, before the fitment of ceiling.
Bad example Bad example Good example

7. Calculation method of the dimension of the simple quadrate air duct


Presuming the unit length friction impedance of the duct is 1Pa/m, when the dimension of one side of the air duct is fixed as 250mm, as shown below:
A

Air conditioner
Air volume
A
3 A 2400m /h (40m3/min) 3 /h B 600m3/min) (10m

B A

Static pressure box Equipped with air filter (bought)

The calculation of duct resistance (the simple calculation is as follow table)


Straight part Bend part Air out part Static pressure box Air inlet grille (with air filter) Calculate as per 1m length 1Pa, 1Pa/m Each bend takes as a3~4m long straight duct Calculate as 25Pa Calculate as 50Pa/each Calculate as 40Pa/each

The chosen chart of simple duct


Note:1Pa/m=0.1mmAg/m Shape Item Air volume
m /h(m /n)
100 200 300 400 500 600(10) 800 1,000 1,200(20) 1,400 1,600
3 3

Square duct Dimension


(mmxmm)
250 250 250 250 250 250 250 250 250 250 250 x x x x x x x x x x x 60 90 120 140 170 190 230 270 310 350 390

Shape Item Air volume


m /h(m /n)
1,800(30) 2000 2400 3,000(50) 3,500 4,000 4,500 5,000 5,500 6,000(100)
3 3

Square duct Dimension


(mmxmm)
250 250 250 250 250 250 250 250 250 250 x 430 x 470 x 560 x 650 x 740 x 830 x 920 x 1000 x 1090 x 1180

8. The attentive matters in installation of air suction and discharging duct


Recommend to use anti-frost and sound-absorbing duct. (locally bought) The duct installation work should be finished before the fitment of ceiling. The duct must be heat insulated. The specific air-discharging outlet should be installed at the place where the airflow can be reasonably distributed. The surface should leave a checking meatus for checking and maintenance. Special air discharging outlet Use screw bolt to fix

Duct Air

Air

9. The examples of improper installation


Do not use air in duct and take the ceiling inner side instead. The result is because of the irregular outer air mass, strong wind and sunshine, the humidity is increased. There may be water drop on the outside of duct. For cement and other new constructions, even if not taking ceiling inner side as duct, the humidity will also be so high. At this time, use glass fiber to perform heat preservation to the whole. (use iron net to bind the glass fiber)

Affected by the capacity of air discharging fan, the strong wind in the outer duct and wind direction, when unit air sending volume exceeds the limit, the discharged water of heat exchanger will overflow, leading to water leakage.

Air discharging fan Improper example

10. The operation method of fan controller


Through the fan controller switch in the electric box, the air volume of this unit can be continuously adjusted. It is unnecessary to adjust air volume through the duct side wind level (unit outside static adjustment). The air volume set should be in the operation air volume range. Figure I shows the position of fan controller in the electric box and operation method. After finishing the electric work, perform test run. According to the main points in Figure II making the chosen switch No. accordant. And confirm if it reaches the needed air volume.

Note:
1) When operating the fan controller, it is possible to touch the electric charging part, so do cut off the power supply. 2) Do not set the dial at the position less than 1. 3) The figure circled in Figure II indicate the capacity number of fan controller. The non-listed capacity number may exceed the permitted operation capacity range, so it is impossible to operate. 4) When delivering from factory, the capacity number of fan controller is set at No.5.
Rotate this switch
(capacity number setting: No. 1 ~ No. 8)
200
* * * * * * * *

High Low

Condition of standard air volume (air volume 100Pa)


* * *

Outer static pressure Pa

150

Example of duct

Once the fan controller has trouble, this linker can perform emergency assistant control. When this linker is connected to the linker from the PCB, it can operate with total load.

100
*

50

When this linker is connected to the linker from the PCB, through the fan speed adjustment panel to adjust speed.

26

30

34 35

40

43

Lower limit

Upper limit

Figure 1

Standard air volume(m3/min)

Figure 2

The example of the method of choosing capacity number:


1) If the unit is in high-speed operation, needing take outer static pressure is 180Pa in capacity air volume 34m /min as working condition point, according to Figure II The characteristic chart of air volume, the capacity number of fan controller is No. 2. 2) If the unit is in low speed operation, needing take outer static pressure is 60Pa in capacity air volume 32m /min as working condition point, according to Figure II The characteristic chart of air volume, the capacity number of fan controller is No. 4.
3 3

11. Refrigerant pipe


[The air side pipe, liquid side pipe must be faithfully heat insulated, if no heat insulation, it may cause water leakage.] The outdoor unit has been charged with refrigerant. When connect the pipe to the unit or dismantling the pipe from the unit, please follow the figure shown, use spanner and torque spanner together. When connect cone nut, the inner side and outside of cone nut should paste with refrigerant oil. Use hand to twist 3-4 rings, then fasten with spanner. Referring to Table I to confirm the fasten torque. (too tight may damage nut leading to leakage) Check if the connection pipe leaks, then do heat insulation treatment, as below figure shown. Only use seal cushion to bind the joint part of air pipe and heat insulation parts.
Paste the refrigerant oil here Middle size seal cushion (accessory) (Use seal cushion to bind the pipe joint) Clamp Heat insulation (accessory) (for liquid pipe) Heat insulation (accessory) (for gas pipe) Gas pipe Liquid pipe

Torque spanner

Spanner Pipe joint Cone nut

80

510

Liquid pipe

Gas pipe

Electric box Upper

Drain hose connection mouth VP25 PVC pipe

530

Specification of pipe Tighten torque


(mm)
9.52 3270~3990 N.cm (333~407 kgf.cm)

Cone dimension A (mm)


12.0~12.4

30

Down side

Cone
45 90 0.5
A

310

Air inlet

Air outlet

R0.4~0.8

19.05

9720~11860 N.cm (990~1210 kgf.cm)

22.9~23.3

6.PARTS AND FUNCTIONS

Discharge unit (built in) In cooling operation,to discharge the water from inside the room.

Drain Hose

Swing fender (located in the outlet)


3

Outlet Air filter


(located in the suction grill)

Refrigerant pipe Cable line Earthing line

Remote Controller

Air inlet

AB242ACBEA AB28NACBEA

High ESP duct type:


Air outlet Duct

Duct

Drainpipe Air inlet

PARTS AND FUNCTIONS


10 11

1
POWER OPER TIMER COMP

4 5 6 7 2 3

3 9 8

EMER

Fig.2
Fig.1 Indoor Unit
1 2 3 4 5 6 7 8 9 10 11

Fig.1

AC242ACBEA

Operating Control Panel (Fig.2) Emergency switch Remote Control Signal Receiver Power Indicator Lamp (Red) OPERATION Indicator Lamp (Green) TIMER Indicator Lamp (Yellow) Compressor Run Lamp (Green) Intake Grill (Fig.3) Air Filter UP/DOWN Air Direction Flaps RIGHT/LEFT Air Direction Louvers (behind UP/DOWN Air Direction Flaps)

1
EMER POWER OPER TIMER

Fig.1 Indoor Unit


1 2 3 4 5 6 Operating Control Panel (Fig.2) Emergency switch Remote Control Signal Receiver Power Indicator Lamp (Red) OPERATION Indicator Lamp (Green) TIMER Indicator Lamp (Yellow)
Fig.3

AC28NACBEA
Air outlet Duct

Air inlet

Air outlet

Air inlet

AD242AMBEA AD28NAMBEA

Compressor (inside)
AU242AHBEA AU28NAHBEA

7.Remote controller functions


Remote controller
29 30 31 32 33 34 35 36 1
M D A U T O
OFF

REMOTE CONTROLLER FUNCTIONS

4.Operation MODE
28 27 26 25

Used to select operation mode. Every time you press MODE button, operation mode changes according to following sequence:
AUTO COOL DRY HEAT FAN

24 23 22 21 20
TEMP

5.HEALTH Button
Used to set health mode, if the unit has the negative ion function and oxygen bar function.

19 18
FAN SLEEP

2 3 4
HEALTH SWING MODE

ON OFF

6.CLOCK Button
Used to set correct time.

17
FRESH

7.CLOCK Button

5
CLOCK SET

16 15

6 7
8

TIMER

HIGH/SO

Used to select TIMER ON, TIMER OFF. (Note: if time of TIMER ON is the same as TIMER OFF,TIMER ON/OFF cannot be set)

14 13

8. FILTER Button
Used to set up/down function of filter.

FILTER

RESET

CODE

LIGHT

LOCK

12
11

9. CODE Button
Used to select code A or B, for this unit, the code is A.

9 10

10.RESET Button
Press this button by using a sharp article to resume the correct operation of the remote controller in case of need, i.e. for example in case of malfunctions due to electromagnetic noise.

11.LOCK Button 1.TEMP Setting Button


(Used to set temperature. Setting ranges: 16 C to 30 C) In Up/Down function, for controlling up and down filter. Used to lock operation button and LCD display contents: by pressing this button, other buttons comes out of function and lock state display appears; if you press it again, lock state will be no more active and lock state display will disappear.

12.LIGHT Button
Used to light the control panel (only for cabinet unit)

2.SWING Button
If you press this button once, auto swing will be activated. If you press this button again, the louver will fix in the present position.

13.Up and down Button


Used to set TIMER and CLOCK up or down.

14.HIGH/SO Button
Used to select HIGH or SOFT operation.

3.Power ON/OFF Button


Used for unit start and stop After power on, the LCD of remote controller will display the previous operation state (except for TIMER,SLEEP and SWING state).

15.SET Button
Used to confirm TIMER and CLOCK settings.

16.FRESH Button
Used to set fresh mode, the unit will draw in fresh air.

17.SLEEP Button

(The clock must be corrected before setting sleep function) Used to set sleep mode.

NOTE: 1.Cooling only air conditioner does not have the displays and functions related to heating. 2.HIGH/SO button This button is activated in Cooling/Heating mode, the fan speed is in AUTO mode after pressing it and "high functon" will be cancelled automatically after 15 minutes running.

18.FAN Button
Used to select fan speed:LOW,MID,HIGH,AUTO.

19.TIMER OFF Display 20.CLOCK Display 21.FILTER Display 22.TEMPERATURE Display 23.AUTO SWING Display 24.HIGH/SO Display 25.SIGNAL SENDING Display 26.FRESH AIR Display 27.ELECTRICAL HEATING Display 28.Some other buttons
All these functions are not available now.

The distance between the remote controller and the receiver should be max 7m and there should be no obstacle between them. Do not throw the remote controller; prevent it from being damaged. When operating the remote controller in an area where electronically controlled lights are installed or wireless handsets are used, please move closer to the indoor unit as the function of the remote controller might be affected by signals emitted by the above mentioned equipments.

Battery loading
Battery loading Batteries are fitted as follows:
* * * *

29.HEALTH Display
Displays when healthy run function is set.

Remove the battery compartment lid Slightly press and disengage the battery compartment lid marked with and then hold the remote controller by the upper section and then remove the battery compartment lid by pressing in the direction of the arrow as shown in the figure above.

30.DEHUMIDIFICATION Display 31.Operation MODE Display


AUTO RUN COOL RUN DRY RUN HEAT RUN FAN RUN

Loading the battery Ensure that batteries are correctly placed in the compartment as required for positive and negative terminals. Replacing the battery compartment lid The battery compartment lid is reinstalled in the reverse sequence. Display review Press the button to see if batteries are properly fitted. If no display appears, refit the batteries.

32.SLEEP State Display 33.BATTERY Energy Display


Notify the user when it is time to change the batteries.

34.LOCK State Display 35.FAN SPEED Display


LO MID

Confirmation indicator
If no indication is displayed after press ON/OFF button, reload the batteries.

Caution: If the remote controller does not operate as designed after fitting new batteries of the same type, press the Reset button (marked ) with a pointed article. Note: It is recommended that the batteries be removed from the compartment if the remote controller is not used for an extended period. The remote controller is programmed for automatic test of operation mode after the batteries are replaced. When the test is conducted, all icons will appear on the screen and then disappear if the batteries are properly fitted.

HI
AUTO

AUTO

36.TIMER ON Display Remote Controller' Operation


When in use, direct signal transmission head to the receiver placed on the indoor unit

Clock Set
When unit is started for the first time and after replacing batteries in remote controller, clock should be adjusted as follows: 1.Press CLOCK button, clock indication of " AM " or " PM " flashes. 2.Press or to set correct time. Each press will increase or decrease 1 min. If the button is kept pressed, time will increase or decrease quickly. 3.After time setting is confirmed, press "SET" : AM or PM stop flashing, while clock starts working. Note:AM means morning and PM means afternoon.

MODE HEALTH FRESH

SLEEP

CLOCK

SET

1 TIMER
FILTER

HIGH/SO

RESET

CODE

LIGHT

LOCK

Fan Operation

1.Unit start
Press ON/OFF button to start your air conditioner. Previous operation status appears on LCD (except for TIMER, SLEEP, and SWING setting).

2.Select operating mode


Press MODE button. At each press, operation mode changes as follows:
A

AUTO
A U T O

COOL

DRY

HEAT

FAN

Then select FAN

TEMP

3. Adjust fan speed


FAN

SWING

ON OFF

MODE HEALTH FRESH

3
SLEEP

Press FAN button. At each press, fan speed changes as follows:

CLOCK TIMER

SET HIGH/SO

LOW

MID

HIGH

FILTER

RESET

CODE

LIGHT

LOCK

Air conditioner will run at the selected fan speed. When in AUTO mode, unit will adjust fan speed according to room temperature automatically.

4. Unit stop
Press ON/OFF button to stop unit.

About FAN mode When the air conditioner runs in FAN mode, it is not possible to select AUTO FAN or to set temperature.

AUTO, COOL , HEAT and DRY Operation 1. Unit start


A

Press ON/OFF button,unit starts. Previous operation status appears on LCD (except for TIMER, SLEEP and SWING setting)

A U T O

2.Select operation mode


Press MODE button. At each press, operation mode changes as follows:
TEMP

3
SWING
MODE

ON OFF

AUTO

COOL

DRY

HEAT

FAN

5
FRESH

4
SLEEP

FAN

Then select AUTO run or select COOL operation or select DRY operation or select HEAT operation

2 HEALTH
CLOCK

SET

3.Temperature setting
Press TEMP button. Every time the button is pressed, temp. setting increases 1 C; if the button is kept pressed, temp. setting will increase quickly. Every time the button is pressed, temp. setting decreases 1 C, if the button is kept pressed, temp. setting will decrease quickly. Set proper temperature

TIMER

HIGH/SO

FILTER

RESET

CODE

LIGHT

LOCK

4.Adjust FAN button


Press FAN button. At each press, fan speed changes as follows:
A U T O

AUTO
COOL operation starts when room temp.is higher than temp. setting.

LOW

MID

HIGH

Air conditioner will run at the selected fan speed.


Ultra-low air flow

5. Unit stop
Press ON/OFF button,unit stops.

Temp. setting +2 C Temp.setting


On reaching temp.setting +2 C, unit will run in mild DRY mode.

In ATUO mode, the temperature setting is not displayed on LCD. In this mode, during running air conditioner will select COOL, HEAT or FAN mode automatically according to the room temperature. In DRY mode, when room temperature becomes 2 C higher than temperature setting, unit will run intermittently at LOW speed regardless of FAN setting. When room temperature is lower than temperature setting, unit will only run FAN operation. In HEAT mode,warm air will blow out after a short period of time due to cold-draft prevention function.

Adjusting air flow direction AUTO SWING


Press SWING button. Up and down airflow varies upwards and downwards. Left and right airflow varies left and right sides.

AUTO SWING

When the automatic swing louver moves to the proper angle, press SWING button can fix the airflow direction.

Always use SWING button on the remote controller to adjust flaps. Adjusting them by hand may result in air conditioner's abnormally running.

A U T O

In COOL or DRY mode, do not leave the louver in downward position for a long time, as the water vapor close to the grille may condense and water may drop from the air conditioner.
TEMP

SWING MODE HEALTH

ON OFF

FAN SLEEP

Please carefully set temperature when children, old or infirm people ues the air conditioner.

FRESH

CLOCK TIMER

SET HIGH/SO

FILTER

In case of great humidity, If the vertical flaps are completely turned towards left or right, the louver will drop water. Never adjust the louver directly by hand, as this could make it work abnormally.If the louver work abnormally, stop unit, restart and adjust the louver by remote controller.

RESET

CODE

LIGHT

LOCK

After unit stops:


Displays on the LCD disappear. All indicators on the indoor unit go out. Swing louver automatically close the air outlet.

Hints:
As in COOL mode air flows downwards, adjusting airflow horizontally will be much more helpful for a better air circulation As in HEAT mode air flows upwards, adjusting airflow downward will be much more helpful for a better air circulation. Be careful not to catch a cold when cold air blows downward directly.

Sleep Function
Before going to bed you can press down the SLEEP button and the air conditioner will run so as to make you sleep more comfortably. Before using this function, the clock must be set.

Use of SLEEP function


After the unit's start, set running mode and then press SLEEP button once to make the air conditioner have the previous-set sleep time (first power-on is "1h"). The sleep symbol will appear. Press time button / : you can choose the time in 1~8 hours. Each time the button is pressed, the time increases/decreases 1 hour: "xh" and "OFF" indications appear on the display.

Operation Mode
1.In COOL, DRY mode
One hour after sleeping operation start, the temperature is 1 C higher than the setting one. After another hour, temperature rises 1 C: sleep run continuously for another 6 hours and then stops. The actual temperature is higher than the setting one which is to prevent from being too cold to your sleep.
SETTING T SLEEP RUN BEGINS SLEEP RUN STOPS

about 6 hrs
increase 1 C

1 hrs

increase 1 C

2.In HEAT mode


One hour after sleeping operation start, the temperature is 2 C lower than the setting one. After another hour, temperature decreases by 2 C more. Temperature will automatically rise by 1 C after another 3 hours' continuous operation. The actual temperature is lower than the setting one which is to prevent from being too hot to your sleep.

SHUT DOWN

In COOL,DRY mode

SETTING T 1 hrs
decrease 2 C

SHUT DOWN

1 hrs

decrease 2 C

3.In AUTO mode.


The air conditioner will run in corresponding sleep operation according to the automatically selected operation mode.
3 hrs SLEEP RUN BEGINS

about 6 hrs
increase 1 C

SLEEP RUN STOPS

In HEAT mode

A U T O

Notes:
After setting SLEEP function, it is not possible to set clock. If set-sleep time does not reach 8 hours, unit will automatically stop operation after set time is reached. Set " TIMER ON " or " TIMER OFF "In COOL,DRY mode function first, then set SLEEP. After set SLEEP function, the TIMER function cannot be set.
SWING MODE HEALTH

OFF

TEMP

ON OFF

FAN SLEEP

FRESH

CLOCK TIMER

SET HIGH/SO

FILTER

RESET

CODE

LIGHT

LOCK

Timer ON/OFF Function


Set clock correctly before starting TIMER operation

1.Unit start
A

After unit start, select your desired operation mode (operation mode will be displayed on LCD)

2.TIMER mode selection


Press TIMER button on the remote controller to change TIMER mode. Every time the button is pressed, display of TIMER mode changes as follows:
ON
TEMP
AM

OFF
PM

ON
AM

OFF
PM

blank

12:00

12:00

12:00

12:00

SWING
MODE

ON OFF

TIMER ON

TIMER OFF

TIMER ON-OFF

1
FRESH

FAN

SLEEP

Then select TIMER mode as needed (TIMER ON or TIMER OFF). Now ON or OFF will flash.

HEALTH

3.TIMER setting (press time adjust buttons


SET

CLOCK

TIMER

HIGH/SO

2 FILTER
RESET
CODE
LIGHT

Every time the button is pressed, time increases 10 minuts. If the button is kept pressed, time changes quickly. Every time the button is pressed, time decreases 10 minuts. If the button is kept pressed, time changes quickly. It can be adjusted within 24 hours at will.

LOCK

4.Confirm setting
After setting correct time, press SET button to confirm time. Now ON or OFF stop flashing. Time displayed: unit starts or stops at X hour X min (TIMER ON or TIMER OFF)

5.Cancel TIMER mode


Just press TIMER button several times until TIMER mode disappears.

Hints:
After replacing batteries or if a power failure occurs, TIMER setting must be reset. Remote controller has memory function. When you use TIMER mode next time, just press SET button after mode selection if timer setting is the same as the previous one.

Note:
After setting TIMER function, the remote controller displays TIMER time. If you want to see clock time, just press CLOCK button once: clock time will be displayed (if you press the button again continuously,you can adjust clock). 5 seconds later, the display will show TIMER time again.

Timer ON-OFF Function


Set clock correctly before starting TIMER operation 1.Unit start
After unit start, select your desired operation mode (operation mode will be displayed on LCD)
A

2.TIMER mode selection


Press TIMER button on the remote controller to change TIMER mode. Every time the button is pressed, display of TIMER mode changes as follows:
ON
OFF
PM

ON
AM

OFF
PM

blank

OFF

AM

12:00

12:00

12:00

12:00

TIMER ON
TEMP

TIMER OFF

TIMER ON-OFF

SWING
MODE

ON OFF

Then select TIMER ON-OFF mode. ON


FAN

will flash.

1
SLEEP

3.Time setting for TIMER ON


Press time button Every time the button is pressed, time increases 10 minuts. If the button is kept pressed, time will changes quickly.

HEALTH

FRESH

CLOCK

SET

TIMER

3HIGH/SO 6

4 FILTER 5
RESET
CODE
LIGHT

Every time the button is pressed, time decreases 10 minuts. If the button is kept pressed ,time will changes quickly. It can be adjusted within 24 hours at will. AM refers to morning and PM refers to afternoon.

LOCK

4.Timer confirming for TIMER ON


After setting correct time, press TIMER button to confirm time. Now ON stops to flash, while OFF starts flashing. Time displayed : unit starts at X hour X min.

5.Timer setting for TIMER OFF


Press time buttons for TIMER ON" and follow the same procedures in " Time setting

6.Time confirming for TIMER OFF


After time setting, press SET button to confirm time. OFF stops to flash. Time displayed: unit starts at X hour X min.

7.Canel TIMER mode


Just press TIMER button several times until TIMER mode disappears. According to the time setting sequence of TIMER ON and TIMER OFF, either start-stops or stops-start can be realized. If the time setting of TIMER ON is the same as TIMER OFF, TIMER ON-OFF function cannot be set.

Filter Up/Down
(Only for AB182ACBEA)

After the air conditioner has operated for a certain period, dust has accumulated on the filter, and the filter up/down function can be used to clean it.
A

1.Whether unit starts or stops, continuously press FILTER button for 3 seconds, and enter the filter up/down waiting status (when unit stops, the yellow TIMER indicator flashes, and filter and clock indication are displayed on the remote controller. Only the FILTER button, the temperature buttons " " " " and time buttons are active).
TEMP

SWING
MODE

ON OFF

FAN

SLEEP

2.Press temperature " " button or time " " button in filter up/down waiting status: the up/down mechanism makes the filter moving downward and does not stop until it has reached the maximum limit. 3.Press temperature " " button or time " " button in filter up/down waiting status: the up/down mechanism makes the filter to moving upward till near the surface board and then automatically adjusts it to reset (when adjusting to reset, it will not be controlled by the remote controller till the adjustment is finished).

HEALTH

FRESH

CLOCK

SET

TIMER

HIGH/SO

FILTER

RESET

CODE

LIGHT

LOCK

4.During moving downward, press temperature " " button or time " " button: moving stops. 5.During moving downward, press temperature " " button or time " " button: moving stops. 6.Continuously press FILTER button 3 seconds again to cancel the filter up/down waiting mode (unit stops, the yellow timer indicator stops flashing, the filter goes back to the original position, the remote controller goes back to off status and only clock is displayed).

Note: If the filter does not thoroughly go back to the original position, only needs to operate several times repeatedly.

" High mode " Operation


Outline of operation in "High Mode"

This function is suitable when the set temperature must be reached in the shortest delay. The button "HIGH/SO", referred to this function, is effective in Cooling/Heating mode (not in Auto/Dry/Fan modes).

A U T O

ON
TEMP

SWING MODE HEALTH

ON OFF

Press the HIGH/SO button noce


FAN SLEEP

FRESH

The indication appears on the display of the remote controller and operation in "High Mode" starts. The AUTO fan speed is automatically set and the corresponding indication is also displayed.

CLOCK TIMER

SET HIGH/SO

FILTER

1
LIGHT LOCK

RESET

CODE

OFF
Press the HIGH/SO button twice

If the button is pressed once, the indication is displayed on the remote controller. If you press the button once again, the indication disappears, regular operation is restored and fan speed goes back to the mode set before "High Mode" operation.

NOTICE: When the air conditioner is operating in " High Mode " , unevenness of room air temperature may occur due to the intensive operation in a short time. Anyway, operation in "High Mode", does not last for more than 15 minutes, then regular operation is automatically restored.

" Soft mode " Operation

Outline of operation in "Soft Mode"


A U T O
OFF

Operation in "Soft Mode", more silent, is suitable when noises should be reduced, e.g.. for reading or sleeping. The button "HIGH/SO", referred to this operation, is effective in Cooling/Heating mode (not in Auto/Dry/Fan modes).

TEMP

SWING MODE HEALTH

ON OFF

FAN SLEEP

ON
Press the HIGH/SO button twice

FRESH

CLOCK TIMER

SET HIGH/SO

The indication appears on the display of the remote controller and operation in "Soft Mode" starts. The AUTO fan speed is automatically set and the corresponding indication is also displayed.

FILTER

1
LIGHT LOCK

RESET

CODE

OFF
Press the HIGH/SO button twice

If the button is pressed once, the indication is disappears from the remote controller's display. If you press the button once again, regular operation is restored and fan speed goes back to the mode set before "Soft Mode" operation.

NOTICE: When the air conditioner is operating in " High Mode " , unevenness of room air temperature may occur due to the intensive operation in a short time. Anyway, operation in "High Mode", does not last for more than 15 minutes, then regular operation is automatically restored.

Auto restart function setting

A U T O

TEMP

SWING MODE HEALTH

ON OFF

FAN SLEEP

FRESH

CLOCK TIMER

SET HIGH/SO

FILTER

RESET

CODE

LIGHT

LOCK

Setting method (to be applied for a necessary situation) : After the power failure compensation is set, if power failure suddenly occurs while the air conditioner is working, it will resume the previous working state when the power is supplied again. Setting Method: When the remote controller is on (excluding timer mode and fan mode), press the "Sleeping" button on the remote controller 10 times within 5 seconds, and after the buzzer rings 4 times, the air conditioner will enter the state of power failure compensation. Cancel Method: Press the "Sleeping" button on the remote controller 10 times within 5 seconds, and after the buzzer rings 2 timer, the power failure compensation mode will be cancelled. Notes: When a power failure suddenly occurs during the air conditioner is working after the power failure compensation is set, if the air conditioner will not be used for a long time, please cut off the power supply to prevent its operation from being resumed after the power is supplied again, or press the "Switch On/Off" button after the power comes again.

Wired controller functions:


Buttons and functions of the wired controller
CLOCK
Used to adjust time.

MODE
Used for select indoor operation mode.

TIMER
Used to set timer mode.

FAN SPEED
Used for select indoor air flow.

CHECK
Auto-diagnostic button.

SWING
Used for setting indoor swing mode.
HEALTH

HEALTH
C
F
SET RECOVERY

CHECK

Used for setting indoor health function. TEMP + -

+stands for time plus/minus, used to adjust time.

Used for changing set temperature.

RECOVERY
used to switch over airexchanging mode.

FILTER
Filter-cleaned button.

RESET POWER ON/OFF


Used for unit start and stop.

Reset correct mode button.

Cautions: On cooling only unit, heating mode is not available.

Note: The above information is the explanation of the displayed information therefore varies with those displayed in actual operation.

Buttons function MODEused for select indoor operation mode. FANused for select indoor air flow. SWINGused for setting indoor swing mode. HEALTHused for setting indoor health function. TEMP + -used for changing set temperature. CLOCKused to adjust time. +-stands for time plus/minus, used to adjust time. TIMERused to set timer mode. RECOVERYused to switch over air-exchanging mode. CHECKauto-diagnostic button. FILTERfilter-cleaned button. RESETreset correct mode button. Display description [MODE] [AUTO]auto operation mode [MODE] [FAN ONLY]air-throwing mode [MODE] [COOL]Cooling operation mode [MODE] [DRY]Dehumidification mode [MODE] [HEAT]Heating operation mode [MODE] [HEAT] [TES]In heating mode, auxiliary electric heater is running. Only when the unit with auxiliary electric heater is in auxiliary electric heating mode, it will display. [FAN] [AUTO]auto fan running

[FAN] [HIGH]high fan speed [FAN] [MED] medium fan speed [FAN] [LOW] low fan speed [FAN] [FIX] fixed fan speed, it will display only when fixed fan speed is requested to main indoor unit. [CENTRAL] central control mode [OPERATION] running mode [STAND BY] waiting mode [PRE-HEAT] pre-heating mode [DEFROST] defrosting mode [FILTER] request of filter to be cleaned [HEALTH]health function [UNIT NO.] [CEN.ADD]central control address, the address number will display on 88 [SYS.ADD.]system address, the address number will display on 88 [CHECK]auto-diagnostic, trouble shooting [DEMAND]compulsory operation function, when it works, [CENTRAL] will flash [SWING]swing mode [ROOM TEMP.]indoor ambient temperature [SET TEMP.]set admired temperature [TIMER][ON] timer function is on, it will switch over in the sequence below: [ON][OFF] [ON][OFF][DAILY] [ ] [TIMER][OFF] timer function is off [TIMER][ON][OFF] timer function ON-OFF [TIMER][ON][OFF][DAILY]timer ON-OFF will switch over in turn daily [CLOCK]clock display, the displaying time is the current time of the clock. [UP][DOWN]indicator of filter elevating [VENTILATION][AUTO]auto ventilation mode [VENTILATION][RECOVERY]fully heat exchanging ventilation mode [VENTILATION][NORMAL]normal ventilation mode FAN ONLY OPERATION 1Start up operation: press the button of ON/OFF, the system will start up, and will display [MODE][AUTO][FAN][AUTO][ROOM TEMP.]+24 [CLOCK]+1200. 2 Select MODE: press the MODE button, then you will see in the display section [MODE] switch over in below sequence:[FAN ONLY][COOL][DRY][HEAT][AUTO] [FAN ONLY]. Select [FAN ONLY]. 3 Select fan speed: press FAN button, then you see in the display section [FAN] switch over in below sequence: [HIGH][MED][LOW][HIGH]. Select proper fan speed. 4Power off: press ON/OFF button, indoor unit will be powered off, there are only time and the ambient temperature in the screen.

AUTO operation, COOLING, HEATING and DEHUMIDIFICATION operation 1) Start up operation: press the button of ON/OFF, the system will start up, and will display [MODE][AUTO][FAN][AUTO][ROOM TEMP.]+24 [CLOCK]+1200. 2) Select MODE: press the MODE button, then you will see in the display section [MODE] switch over in below sequence:[FAN ONLY][COOL][DRY][HEAT][AUTO][FAN ONLY]. Select [FAN ONLY]. 3) Change set temperature: press TEMP + or every time, [SET] will display, and set temperature will increase/reduce 1F. 4) Select fan speed: press FAN button, then you see in the display section [FAN] switch over in below sequence: [HIGH][MED][LOW][HIGH]. Select proper fan speed. 5) Select [SWING]: press [SWING] button, swing function is valid. Press again, swing function is invalid. 6) Set [HEALTH]: used to set the indoor health function. Press it once, [HEALTH] will display in the display section, then indoor health function is valid. Press it again, [HEALTH] will disappear, then the health function is invalid. This function is valid only for the unit with health function. 7) Power off: press ON/OFF button, indoor unit is powered off. There are only time and the ambient temperature in the screen. Set TIMER operation: Adjust clock: when powered on, for the first time to set timer function, the clock will be adjusted. Press CLOCK button, and set the current clock. Now, CLOCK will flash at the frequency of 2Hz every minute. Press the clock +/- button; the current clock can be adjusted. Until the proper time comes, press [SET]. TIMER ON operation: Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below sequence: [ON][OFF][ON][OFF] [ON][OFF][DAILY] [ ]. Select [TIMER] [ON], then [TIMER] [ON] flashes, press the clock +/- button to adjust the time of TIMER ON, press [SET] button. TIMER OFF operation: Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below sequence: [ON][OFF][ON][OFF] [ON][OFF][DAILY] [ ]. Select [TIMER] [OFF], then [TIMER] [OFF] flashes, press the clock +/- button to adjust the time of TIMER OFF, press [SET] button. TIMER ON-OFF operation: Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below sequence: [ON][OFF][ON][OFF] [ON][OFF][DAILY] [ ]. Select [TIMER] [ON] [OFF]. Firstly, [TIMER][ON] flashes, press the clock +/- button to adjust the time of

TIMER ON, press [TIMER]. [TIMER][ON] will be constant on. Then [TIMER] [OFF] flashes, press the clock +/- button to adjust the time of TIMER OFF, press [SET]. The time sequence of timer on and timer off will determine the mode is [TIMER] [ON] [OFF] or [TIMER] [OFF] [ON]. If you want the current time, press [CLOCK] once, current time will display; press again, [CLOCK] will flash, and press [+][-] to adjust the time. Note: 1. If the two times are same, the timer state which is set later will flash, in this case, timer can not be set. 2. When entering TIMER setting state, if you do not input any button in continuous 10 seconds, the unit will quit from the TIMER mode. Cancel TIMER operation: In the timer operation state, press [TIMER] button, the unit will quit from the current timer operation state, and the set data will be memorized, then enter the next timer mode. [FILTER] function When the wired controller receives the filter-cleaned signal from indoor unit, [FILTER] will display. After finishing clean, press [FILTER], the sign [FILTER] disappears, and the controller will send the filter reset signal to indoor unit. When the sign [FILTER] not display, it is invalid to press [FILTER] in short time. FILTER ELEVATING function: (only for the unit with elevating function) When the filter needs to be cleaned, the panel can be lowered to the admired height by the [FILTER][UP][DOWN] function. Method is below: In power off state, press [HEALTH] for 15 seconds to enter filter elevating set state. In this state, the sign [FILTER] will flash and [UP] [DOWN] will display simultaneously, Press TEMP [+], in timer section [UP] will display, while press TEMP [-], in timer section [DOWN] will display. When it arrives the appropriate position, press [UP], [UP][DOWN] will display simultaneously, filter will stop going down. Press [UP] again, filter will go up. Press [FILTER] button to quit the mode. DEMAND operation function: By this function, all the indoor units can be made in nominal mode. Set the operation mode in cooling and then shut off the unit. In the stop state, press [ON/OFF] button for 5 seconds to enter cooling trial operation state. If it is in heating mode before shut off the unit, then press [ON/OFF] button for 5 minutes, it will enter heating trial operation state. In cooling, there will be LL in the position where the set temperature displays. In heating, there will be HH in the position where the set temperature displays. The wired controller will send the [DEMAND] signal to indoor unit. In the [DEMAND] operation, COOL or HEAT will display at 1Hz frequency. Indoor fan motor will be fixed at AUTO mode. The indoor units in the same group will quit the [DEMAND] in turn. At this time, only the buttons of [ON/OFF] and temperature [+] [-] are valid. Press [ON/OFF] to quit [DEMAND] mode.

CENTRAL control function When the central controller selects [CENTRAL] mode, the buttons in the wired controller except for [CHECK] will be invalid. VENTILATION mode (only for the unit with fresh air function or heat recovery function) Press [RECOVERY] button, then the unit will switch over the ventilation mode: [ ] [VENTILATION][AUTO] [VENTILATION][RECOVERY] [VENTALATION][NORMAL] [ ], please select appropriate ventilation mode. Query indoor malfunction history: In the state of power on or power off, press [CHECK] button, enter the malfunction-querying mode of all indoor units in the group. Then [CHECK] and [UNIT NO.] will display, and the actual indoor numbers will be displayed in some sequence (unit number is in decimals). At the same time, in the time region, there will be the current malfunction and the latest time malfunction, the displaying format is [XX YY], in which XX stands for the current malfunction, if normal, it will display ; YY stands for the latest time malfunction. The failure code of every unit will display for 3 seconds. After the failure codes of all indoor units in the whole group are displayed, the mode will quit automatically. Clear abnormal state and malfunction history: In normal state, press [CHECK] button for 5 seconds to clear abnormal states, at the same time, wired controller will send the data of clear abnormal state, but the malfunction history still retains. In normal state, press [CHECK] button for 15 seconds, except for malfunction states, the malfunction history in wired controller will be cleared. Query indoor performance state: In normal state, press both buttons of [CHECK] and [FILTER] for 5 seconds, in the set temperature region in the screen, [XX] will display, XX is indoor number, which can be selected by pressing [TEMP] [+] [-]. In the timer region in the screen, [YZZZ] will display, in which Y stands for data type, ZZZ stands for the corresponding data. which can be selected by pressing [CLOCK] [+] [-]. Y A B C d E F ZZZ Indoor capacity (W) Request of indoor capacityHz Temperature of indoor ambient temp. sensor TA Temperature of indoor gas pipe sensor TC1 Temperature of indoor liquid pipe sensor TC2 Open degree of indoor PMV Type Nominal cooling capacity/10, decimal Actual value, decimal Actual value, decimal Actual value, decimal Actual value, decimal Actual value, decimal

g H

Preset Outdoor total capacity

Actual value, decimal

In check mode, press [CHECK] to quit the check mode, and go into normal running mode. How to change the function switches? No. Type State of switch Changeover of Wired Connected J01
controller controller and central Cut off Connected Cut off Connected Cut off

Function description
Central controller Wired controller Set as simple controller Set as standard controller Use the sensor in the wired controller Use the sensor in the indoor unit Common control Auto restart after power failure Yes No Set as slave controller Set as master controller Indoor unit in shorted time function Common control Send compulsorily defrost signal to indoor unit Common control

J02 J06

Changeover of type of wired controller Selection of room temp. sensor Auto restart after power failure Display of temperature room

J07 J03 SW01 SW01 D1

Connected Cut off Connected Cut off ON OFF ON OFF Connected Cut off

Changeover of master or slave controller or Shorten time function

D2

Compulsorily defrost

Connected Cut off

Note: 1. The switches in grey can be operated after opening the cover of wired controller. 2. Switches or jumper wire must be adjusted when the wired controller is powered off. If the wired controller is powered on, the above operations will be invalid. 3. Shorten time function In normal operation, D1 is in short circuit, it will enter shorten time mode, and the time will be shortened in the proportion of 60:1. In shorten time mode, LED will flash at the frequency of 0.5 second. Cut off D1, it will quit the shorten time mode and return to the normal operation mode. 4. Compulsorily defrost In heating mode, D2 is in short circuit, it will enter compulsorily defrost mode; cut off D2, it will quit. 5. Lock function There is no lock function only in the wired controller. But when it is connected with a central

controller, if the central controller is set to central, the buttons in the wired controller will be invalid, or the buttons will be valid. Failure code:
For remote type, flash times 10 Failure code on wired controller 08(08H) For central control, failure code 21D

Failure description

Reason

Remarks

Drainage abnormal

system

Float switch broken down for more than 25m continuously sensor broken down or short circuit for more than 2m continuously sensor broken down or short circuit for more than 2m continuously sensor broken down or short circuit for more than 2m continuously Sensor broken down or short circuit for more than 2m continuously

01(01H)

01D

Indoor ambient temp. sensor failure Indoor coil sensor failure temp.

02(02H)

02D

74(4AH)

11D

Outdoor ambient temp. sensor failure Outdoor coil temp. sensor failure (compressor discharging temp. sensor) Over-current protection High abnormal Power abnormal pressure supply

73(49H)

12D

5 6 7

72(48H) 83(53H) 71(47H)

10D 14D 22D

CT check abnormal 3 times in 30m High pressure switch acts 3 times in 30m Fault phase, short of phase, out of balance greatly Communication abnormal for more than 4m continuously Communication abnormal for more than 4m continuously Outside signal broken down for more than 10s Sensor broken down or short circuit for more than

07(07H)

06D

Communication between wired controller and indoor abnormal Communication between indoor and outdoor abnormal Outside alarm signal input Gas pipe temp. sensor abnormal

06(06H)

05D

11 12

11(0BH) 03(03H)

30D 20D

2m continuously 13 13(0DH) 31D Solenoid abnormal valve Solenoid valve incorrectly 3 continuously act times

14

76(4CH)

15D

Discharging temp. sensor abnormal EEPROM abnormal

Sensor broken down or short circuit for more than 2m continuously EEPROM data missing

15

05(05H)

17D

Run as the default value

16

84(54H)

26D

Pressure abnormal(low pressure) Compressor overheat

Low pressure switch acts in normal running the discharging temperature is higher than 120degree Indoor operation mode is different with the running indoor unit. Sensor broken down or short circuit for more than 2m continuously Sensor broken down or short circuit for more than 2m continuously

17

80 50H

15D

Resumable if lower than 100degree

18

12 0CH

23D

Abnormal mode

19

75 4BH

18D

Outdoor coil B(suction temp sensorfor MRV II) Outdoor discharging B(oil temp sensorfor MRV II)

20

77 4DH

15D

shows resumable fault, shows it is not resumable fault. Setting address method: The address setting can be realized by setting indoor PCB. If you use the group control function, there should be a master unit and 15 sets of slave units. For the master unit, the SW5-3 should be at 1. For the slave units, the SW5-3 should be at 0. Please refer the below table, Indoor unit SW1-4 SW1-3 SW1-2 SW1-1 address 1 OFF OFF OFF OFF 2 OFF OFF OFF ON 3 OFF OFF ON OFF 4 OFF OFF ON ON 5 OFF ON OFF OFF 6 OFF ON OFF ON 7 OFF ON ON OFF

8 9 10 11 12 13 14 15 16

OFF ON ON ON ON ON ON ON ON

ON OFF OFF OFF OFF ON ON ON ON

ON OFF OFF ON ON OFF OFF ON ON

ON OFF ON OFF ON OFF ON OFF ON

If you use central control type, SW1, SW2 will be used simultaneously. Wiring request in central control type: port A-B is connected with indoor through 2-core shield wire. Requirements: 1. Port A connects with port CN16Aof all indoor units. 2. Port B connects with port CN16Bof all indoor units. Address on Indoor unit SW2-3 SW2-2 SW2-1 SW1-4 SW1-3 central address controller 1 1 ON OFF OFF OFF OFF 2 2 ON OFF OFF OFF OFF 3 3 ON OFF OFF OFF OFF 4 4 ON OFF OFF OFF OFF 5 5 ON OFF OFF OFF ON 6 6 ON OFF OFF OFF ON 7 7 ON OFF OFF OFF ON 8 8 ON OFF OFF OFF ON 9 9 ON OFF OFF ON OFF 10 10 ON OFF OFF ON OFF 11 11 ON OFF OFF ON OFF 12 12 ON OFF OFF ON OFF 13 13 ON OFF OFF ON ON 14 14 ON OFF OFF ON ON 15 15 ON OFF OFF ON ON 16 16 ON OFF OFF ON ON 17 -------ON OFF ON OFF OFF 18 -------ON OFF ON OFF OFF 19 -------ON OFF ON OFF OFF 20 -------ON OFF ON OFF OFF 21 -------ON OFF ON OFF ON 22 -------ON OFF ON OFF ON 23 -------ON OFF ON OFF ON 24 -------ON OFF ON OFF ON 25 -------ON OFF ON ON OFF

port CN16A-B

SW1-2 SW1-1

OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF

OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF

26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67

--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF OFF OFF OFF

ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF OFF OFF OFF

ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF

OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF

OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON

ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON

--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF

OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON

ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON

OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON

OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF

128

------------------------------------------------------------------------------------------------------------------------

ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON

ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON

ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON

ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON

Electrical functions of wired controller:


1.Function difference between master wired controller and slave one:
Contrastive items Function Master wired controller All of functions Slave wired controller Only with below functions: ON/OFF, MODE, FAN SPEED, SET TEMP., SWING

2. Wiring connections of wired controller:


A
indoor 1
wired controller

indoor 2
wired controller

indoor N
wired controller

indoor 15
wired controller

indoor 16
(master unit) wired controller

control wiring of wired controller, polar.

wired controller

indoor 1
wired controller

C
1 2 3
polar wire

indoor 1
wired controller

polar wire polar wire

B C

wired controller

wired controller

wired controller

There are three methods to connection wired controller and the indoor units: A. One wired controller can control max. up to 16 sets of indoor units, and 3 pieces of polar wire must connect the wired controller and the master unit (the indoor unit connected with wired controller directly), the others connect with the master unit through 2 pieces of polar wire.

B. One wired controller controls one indoor unit, and the indoor unit connects with the wired controller through 3 pieces of polar wire. C. Two wired controllers control one indoor unit. The wired controller connected with indoor unit is called master one, the other is called slave one. Master wired controller and indoor unit; master and slave wired controllers are all connected through 3 pieces of polar wire. 3. Communication wiring: The wired controller is equipped with special communication wiring in the accessories. 3-core terminal (1-white 2-yellow 3-red) is connected with the terminal ABC of wired controller respectively. The communication wiring is 4 meter long; if the actual length is more than it, please distribute wiring according to below table:
Communication wiring lengthm <100 100 and <200 200 and <300 300 and <400 400 and <600 Dimensions of wiring 0.3mm2X3-core shielded wire 0.5mm2X3-core shielded wire 0.75mm2X3-core shielded wire 1.25mm2X3-core shielded wire 2mm2X3-core shielded wire

One side of the shielded sheet of communication wire must be earthed.

8.Refrigerant

Diagram
Outdoor unit Indoor unit

muffler

one way vavle

4-way vavle compressor

heat exchanger of indoor unit

air-liquid departor

Cooling operation Heating operation

-44-

9.Electrical Control Functions


Flow Chart for Operation 1) Turn on/off unit

Control function treat module

Off On/off On Ye Trouble Off Mode determinati

Power indicator turn off, operation indicator turn off Trouble indication

Ye Abnormal operation No Chose mode

Buzzer sound twice, refuse to receive signal

Cooling operation

Heating operation

Dehumidifying operation

Fan motor turn off, electronic expansion valve close, louver motor turn off

-45-

2) Cooling operation Cooling No Swing Yes Swing action Swing flap in the cooling standard position

Yes Automatic fan speed No Operate in fan speed set

Adjust fan speed according to temperature set and in

Yes Test No Rated operation Yes

Electronic expansion valve: overheat control Swing flap: cooling standard position Fan motor: high speed Electronic expansion valve: overheat control Swing flap: cooling standard position Fan motor: rated speed Electronic expansion valve: overheat control Swing flap: cooling standard position Fan motor: auto

No Yes Emergenc y No According to the state of thermostat Open

Electronic expansion valve: overheat control, send turning on unit signal to Electronic expansion valve: close, send turning off unit signal to outdoor unit

Close

-46-

Note: When abnormal phenomenon occur, the indoor unit indicator will indicate abnormality according to the abnormal parts. When temperature of the evaporator inlet is lower than 0 and keeps for 5 minutes, unit will operate in anti-icing mode.

3)Dehumidifying operation

Dehumidifying No Swing Yes Swing action Swing flap in the cooling standard position

Yes If enter cooling operation No

Adjust fan speed according to temperature set and in

No

Determine if dehumidify according to air temperature

Yes Electronic expansion valves open, indoor unit fan motor weak wind Electronic expansion valves open, indoor unit fan motor weak wind

Yes Anti-defro sting n No Electronic expansion valve totally open

Send indoor Operation State outdoor unit

unit to

-47-

4) Heating operation

Heating operation No Swing Yes Swing action Swing flap in set fan speed position

Defrosting

Yes

No Rated

No

On side: wind off, expansion valve steady Off side: Electronic expansion valve totally open

Fan motor operate in rated fan speed

According to temperature sensor to adjust state and valve open degree Yes

Overload protection

If stop unit protection Yes

No No (not rated Auto fan Yes Operate in set fan speed According to room temp and set temp to determine fan speed Electronic valve close

expansion

Protect according to temperature difference section value

Send indoor Operation State outdoor unit

unit to

-48-

10. Diagnostic information 10.1 Failure code remote control type unit: failure description
indoor ambient temp. sensor failure indoor coil temp.sensor failure outdoor ambient temp. sensor failure or 4-way valve broken down in heating mode outdoor coil temp. sensor failure over-current protection failure or phase sequence fault refrigerant system pressure too high or low communication between indoor PCB and receiver panel failure communication between indoor PCB and outdoor PCB drainage failure Note: For convertible type unit, drainage failure is not available.

indoor running lamp flash times


1 2 3 4 5 6 8 9 10

Wired control type unit failure code: Failure code on wired controller Indoor ambient temp. sensor abnormal E1 Indoor coil temp. sensor abnormal E2 Outdoor ambient temp. sensor abnormal E3 Outdoor coil temp. sensor abnormal E4 Over current protection E5 Over high or low pressure protection E6 Communication between panel and indoor E8 abnormal Communication between indoor and outdoor E9 abnormal Water pump failure E0 Failure description

Failure code with wired controller YR-E12:


For remote type, flash times 10 1 2 3 4 Failure code wired controller 08 01 02 4A 49 21 01 02 11 12 Drainage system failure Indoor ambient temp. sensor failure Indoor coil temp. sensor failure Outdoor ambient temp. sensor failure Outdoor failure 5 6 8 9 11 12 13 15 48 53 07 06 0B 03 0D 05 10 14 06 05 30 20 31 17 coil temp. sensor (compressor Float switch broken down for more than 25m continuously sensor broken down or short circuit for more than 2m continuously sensor broken down or short circuit for more than 2m continuously sensor broken down or short circuit for more than 2m continuously Sensor broken down or short circuit for more than 2m continuously CT check abnormal 3 times in 30m High pressure switch acts 3 times in 30m Communication abnormal for more than 4m continuously Communication abnormal for more than 4m continuously Outside signal broken down for more than 10s Gas pipe temp. sensor Sensor broken down or short circuit for more than 2m continuously Solenoid valve act incorrectly 3 times continuously EEPROM abnormal EEPROM data missing abnormal Solenoid valve abnormal on For central Failure description Reason control, failure code

discharging temp. sensor) Over-current protection High pressure abnormal Communication between wired controller and indoor abnormal Communication between indoor and outdoor abnormal Outside alarm signal input

10.2 Trouble Shooting - Detailed for engineer


Malfunction flow chart: analyze and diagnose If the air-condition fails to cooling or heating function and other functions, please check the system as follows: 1.Cooling
begining fails in cooling the enactment TEMP. right or not N the cooling load beyond the allowable arange Y change the designed TEMP.

use arange is right or not

redesign the TEMP.

condensate flowage failure

fault in 4-way vavle N

change the 4-way vavle

quantity of condensate charge is not enough N compressor fault Y

superaddition condensate

replacing compressor

airiness circle improperly

fan speed at low-speed


N air entrance filter obstruct

enact fan speed of high or middle speed

clear the filter

heat insulation of condensate pipeline between indoor unit and outdoor unit is normal

insulate the two pipeline respective

Figure 7-1

-50-

2. Heating
begining fails in heating the enactment TEMP. right or not N the heating load beyond the allowable arange Y change the designed TEMP.

use arange is right or not

redesign the TEMP.

condensate flowage failure

fault in 4-way vavle N quantity of condensate charge is not enough N compressor fault

change the 4-way vavle

superaddition condensate

replacing compressor

airiness circle improperly

fan speed at low-speed


N air entrance filter obstruct

enact fan speed of high or middle speed

clear the filter

heat insulation of condensate pipeline between indoor unit and outdoor unit is normal

insulate the two pipeline respective

blowing cold air

fault in 4-way vavle

replacing the 4-way vavle

prevent cold air failure

pipe sensor of indoor unit is fault

replacing the 4-way vavle

Figure 7-2

-51-

3 Malfunction and Solution of Wired controller 1) There is nothing on display of wire control organ, and the air-conditioner failure to operate
begining

if the diode on indoor unit is lumines Y if there s voltage on the primary side of tranaformer Y check the port row of power supply Y if power supply and communication line are connected correctly N if there's AC 220V of power suplay on PCB. of indoor unit Y redo the connection work N if the transform of PCB.socket is normal Y N if the fuse of indoor unit PCB.is normal Y if the primary side of power supply transformer is short Y replacing the transformer replacing the PCB. of indoor unit N Y repacing the wire control organ

'

if there'e DC 12V between the four ports:A,B,C and D which on wire control organ

replacing the transformer

if there's AC 15V on transformer subside of indoor unit PCB.

Figure 7-3

-52-

2) The wire control organ displays the alarm signal with E0 E0 means the floater switch of indoor unit is abnormal
begining the alarm signal of wire control organ is E0

if the floater swith is orientated correctly Y if the function of the floater is normal N replacing the switch

amend the oritation of the floater switch

Figure 7-4 3) The wire control organ displays the alarm signal with E1 E1 means indoor ambient temperature sensor is abnormal
begining wire control organ displays the alarm signal with E1

if the indoor ambient sensor is orientated correctly


Y if the resistance of sensor is right N replacing the sensor

amend the position of the sensor

Figure 7-5 Notation: The resistance of indoor ambient sensor is 23K

-53-

4) The wire control organ displays the alarm signal with E2 E2 means indoor piping temperature sensor is abnormal
begining the alarm signal of wire control organ is E2

if the position of piping Temp.sensor is right Y if the resistance of the sensor is right N replacing the sensor

amend the position of sensor

Figure 7-6 Notation: The resistance of piping temperature sensor is 10K 8) The wire control organ displays the alarm signal with E8 E8 means malfunction of communication between control panel and indoor units
begining

if the wire control organ can matches the PCB of indoor units

replacing the wire control organ

if the four ports on wire control connected corresponding with the port on PCB of indoor unit

connect the wire correctly

if the ports:A,B,C and D are connected well


Y

connect the wire correctly

if the potrs A and B,or C and D are short

connect the wire correctly

Figure 7-7

-54-

11. Electrical Data


11.1 Wiring Diagram 11.1.1 Outdoor unit

single phase outdoor wiring diagram

NOTE: 1. Dashed parts is not available for only Cooling type 2. Dashed parts is optional for Low Ambient Temp. Cooling,and there is no relay in only Cooling type

3-phase outdoor wiring diagram

NOTE: 1. Dashed parts 2. Dashed parts

is not available for Cooling capacity below 42000Btu/h are not available for only Cooling type

3. Dashed parts is optional for Low Ambient Temp. Cooling,and there is no relay in only Cooling type

11.1.2 Indoor unit

over 24000BTU/h convertible type wiring diagram

NOTE: are not availble in convertible type 1. Dashed parts 2. Dashes part is not avaliable below Cooling capacity 42000Btu type 3. Remote central controller is optional 4. P16 and P17 are used for room card function

over 24000BTU/h cassette type wiring diagram

NOTE: in dashed frame are not available for cassette type 1. Parts unit 2. Central controller is optional 3. P16 and P17 are used for room card function

over 24000BTU/h mid ESP duct type wiring diagram

W Y R

Note: 1.Dashed parts are not available in duct type. 2. Dashed part is ont avaliable below Cooling capacity 28000Btu type 3.Remote central controller is optional. 4.P16 and P17 are used for room card function

High ESP duct type wiring diagram

W Y R

Note: 1.Dashed parts are not available in duct type 2.Dashed part is fan speed controller kit. 3.Remote central controller is optional 4.P16 and P17 are used for room card function

Cabinet unit wiring diagram:


Wiring Diagram For 24000/42000BTU/h cabinet Unit
TRANS. PIPING TEMP ROOM TEMP.

CN6 TERMINAL BLOCK


R Y/G
Y/G R B W

CONTROLLER CN3 CN12

TO OUTDOOR UNIT

CN5

CN11 CN8 CN9 DOOR SWITCH

W B

N S(N-W)

FUSE

CN7

CN1

T3.15A/250VAC SWING MOTOR FAN MOTOR

FAN MOTOR CAP.

0010451167 PCB information circuit diagram

P15 1 187

R2 LED3 10K/0.5W R3 10K/0.5W


CN23 1 2 CN22 2 1

R5 C4
5 4

33K 103
6

IC6 TLP371
1 2
CN10 1 2

+5

104 103 C29 C22

100uF E4

+5 470uF/16V C33 104 E3

W2 OUT IN 7805

+12

W1 OUT IN 7812

VDD

D1-D4 T1 1 C34 104 4

0.1UF/275V
LB1

0.1UF/275V 187
1

P2-P6

330 R10
+5

4.7K R30 N9 1K R21



C8 102

E1 2200uF

C1
CN1
TRAN1-2 +12 RL6

RV1
T3.15A/250V

D10
1N4007

+5

R41 10K N1 9013 C21 103 R64 56K R34 4.7K

2.2K

C3 1K 103 R58

D9 R4

LED2 TLP521 IC7 4 1


2 3

R36 10K

R43 10K R24 1K

D12 4148 D13 4148

CN4

C2
FUSE1

187

P1

JQ1AP-A 1 A B C JQ1P-A RL8 187

1 P14

to
CN14 4 1 +5 N6 R54 R53 10K N8 10K +12 D18 1N4148 9013 +5 R55 4.7K R31 +5 10K R39 10K R33 E9 4.7K R29 1uF C27 104 R22 1K C7 102 1K N2 9013 R11 330 N3 9013

+5

IC10

103 R63 C24 27K


LED4 D16 4148

CN5

187

1 P13

+5 R32 4.7K

TLP741/541

R8

10 D15 4148 D14 4148

R7

10

CN20

JQ1P-A

1 2 3 4 5

RL7

RC3 0.033uF+120 187

4.7K R28

1 P12

9013

N7

9013

VDD IC1 1 2 3 4 5 6 7 8 16 15 14 13 12 11 10 9 104 IC2 1 2 3 4 5 6 7 8 16 15 14 13 12 11 10 9 104 +12

1 2 3 4 5

IC9

R25

2.4K

CN19

JQ1AP-A

RL5

RC1 0.033uF+120 187

1 P11

TLP521

LED5

+5 CN13

R23 1K LED1 C23 103 C5 102

IC3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

D C B A

2003

JQ1AP-A

RL4

RC2 0.033uF+120 187

+5V 1 GND 7

IRQ/50Hz RESET NOP BEEP IR

R19 1K

R12 560

/ 487
NET-O NET-I

C6 102

to
9013 N10 D19 4148 R51 R59 R56 R52 24C01A R50 10K 10K 10K 10K 10K +5

OSC1 OSC2 CGMXFC VSSA VDDA VREFH

2 1 CN17 +12

R57 4.7K

C26 IC5 1 2 3 4

104

+5

/ P/G P/G / NOP / / NOP


NOP Vss Vdd SCL SDA A B C D AVss VDDAREF

IC4 MAX487

8 7 6 5

CN16 2 1
DL1 DL2

5 6 7 8 +5

GND DI A DE B /RE VCC RO C25 104

4 3 2 1

EEPROM

A B C D

AB32

/ 1 1 3 2 1
NOP

64 63 62 61 60 59 58 57 C28 104 R66 56 1M 55 +5 54 53 52 51 50 49 48 47 10K 46 R49 45 44 +5 43 42 41 40 39 38 R48 37 R47 36 R40 35 34 33

1 P10

C32 XT1

+12

JQ1AP-A

RL3

187 RL2

1 P9

JQ1AP-A

8.00M

2003

187 RL1

1 P8

JQ1AP-1

C31 R27 4.7K N5 9013

187

1 P7

C35 104 BUZ1 CN7 1 +12

C36 R67 100 +5 R65 200K R35 4.7K

10K 10K 10K

R26 4.7K

104

N4 9013

IC8 680 1N4007 R6 D11

187 1 P16

C14 C15 C16 1K R14 1K R13

103 103 103

R20 1K

R9 220 E8 2.2uF

+5 R44 10K C10 103 C11 103 RB4 1K R15 C9 103 CN12

C20 103

TLP521-1

R18 1K C17 103 RB1 RB2 RB3

C12 103 RB5 C13 103 E5 4.7uF

R1 100K/1W 1 187 P17

1 CN11 2 1 CN15 1

D17 1N4148 4.7uF E6

R45 10K

R17 1K C18 103 R16 1K C19 103

R61 R62 R60 4.7uF E7

20K 20K 20K +5

J1

J2

J3

J4

J5

J6

J7

J8

J9

J10

R58,CN22

2P

R46 10K

+5v

SW2

SW1

+5v

J6 J5 CHECK 1/60

J10 J9 J8 J7

J4 J3 J2 J1

CN8

CN6

R4,R5,C3,C4,D9,D10 CN23

KFR-120Q 0010451167
5

2 1

()

()

0010451167 PCB information characters on boardhorizontal

0010451167 characters on boardvertical

Condition for the PCB data:


1.Working ambient temperature:1070, relative humidity:30%95% 2.Preserved ambient temperature:2080relative humidity30%95% 3.Power supply:220VAC50/60Hzvoltage range:160V250V 4.Precise of temperature control:1

0010451167 PCB information port and definition


P1connect to external power supply, live line: L (220VAC) P2connect to external power supply, neutral line: N (0VAC) P3456control external load, neutral line: N1N2N3N4(0VAC) P7control external load, electrical heat: HEAT (control output 220VAC) P8control external load, health function: OXYGEN (control output 220VAC) P9control external load, humidification: HUMI (control output 220VAC) P10control external load, SWING(control output 220VAC) P11control external load, WATER PUMP(control output 220VAC) P12control external load, indoor fan motor low speed: L(control output 220VAC) P13control external load, indoor fan motor mid speed: M(control output 220VAC) P14control external load, indoor fan motor high speed: H(control output 220VAC) P15communication with fixed frequency single outdoor unit: COMM(0~220VAC) P16input control, signal live line: L(220VAC) P17input control, signal neutral line: N(0VAC) CN1input port of transformer (220VAC) CN2input port 1 of transformer (no use) CN3input port 2 of transformer (no use) CN4input port 3 of transformer (1-214VAC3-412VAC) CN5input control, connecting port to wired controller: CONTROLLERthree bits: 1. power supply: 12VAC, 2. power supply: 0VAC, 3. communication: COMM.. CN6input control, ambient temp.-coil temp. sensor connecting port: ROOM/PIPE1-2ROOM 3-4PIPE Indoor ambient temp. sensor: R25=23K+-2.5%B25/50=4200K+-3%range:-4080 Indoor coil temp. sensor: R25=10K+-3%B25/50=3700K+-3%range:-2090 CN7control external load, fresh air control: FRESH1. blank, 2. power supply 0VDC, 3. control output: 12VDC. CN8input signal: FREEZEno use CN9input controlno use CN10communication with fixed frequency single outdoor unit: (0~12VDC) CN11input signal, door switch: DOOR1-2 short circuit is normal, cut off P8 output CN12input signal, external alarm input: ALARM1-3 short circuit is normal, if cut off, air conditioner stops work. Note: For convertible type, cassette type, duct type units, CN11 and CN12 must be in short circuit, or PCB will display failure information. CN13input signal, wiring port of remote receiver board: RECEIVE BOARD 1. power supply 5VDC, 2. power supply 0VDC, 3. remote signal, 4. signal output of running lamp 0VDC, 5. signal output of timer

lamp 0VDC,6. signal output of power lamp 0VDC, 7. signal output of water pump running lamp 0VDC CN14control external load, auto elevating function 1. signal of door switch close, 2. output of elevating direction control 0VDC, 3. output of elevating power control 0VDC, 4. power supply 12VDC CN15input signal, detecting water level of float switch 1-3 short circuit is normal, cut off shows that level exceeds the limitation.If float switch cuts off or occurs other failure, LED1 will flash 10 times. CN16input control, wiring port of central controller: REMOTE1RS485-B2RS485-A CN17output signal, output signal of failure alarm, control external load, 12V/ALM 1. control output 0VDC, 2. power supply 12VDC CN18output signal (no use) CN19control external load, swing 1116VDC20VDC30VDC40VDC50VDC. CN20control external load, swing 2116VDC20VDC30VDC40VDC50VDC. CN21input signal, spring switch, CHECK1input signal of earthing, 2. power supply 0VDC CN22short circuit means selecting single split communication type. CN23short circuit means selecting multi split communication type.

0010451167 PCB information function selectionON is 1, OFF is 0


The standard condition for PCB in factory SW14 bits are OFF SW24 bits are OFF SW34 bits are ON SW42 bits are ON SW54 bits are ON SW1-SW2: used for indoor unit to set unit address from 1 to 16 SW3-SW5: used for indoor unit to select different functions.(every dip switches are corresponding to J1-J10. SW2-4logistic relationship of control functiondoor card control and remote/ wired control0 means logistic relationship is and, 1 means the later coming is preferential. J1SW3-1function selection-control type: 1 means remote control, 0 means wired control. J2SW3-2function selection-temperature compensation in heating mode: 1means yes, 0means no. J3SW3-3function selection-outdoor communication: 1means yes, 0means no. This PCB must be 1. J4SW3-4function selection-heat pump unit: 1means heat pump, 0means cooling only. 1/60test in short circuit, but in operation short circuit mustnt be permitted. CHECKshort spring switch control, it also can be used as switch of convertible type except for testing. J5SW4-1function selection-elevating function: 1means yes, 0means no. J6SW4-2function selection health function: 1means common (indoor fan motor running); 0 means special (indoor, outdoor running). J7SW5-1function selection swing mode: 1 means commonsimultaneous motor, 0 means special (swing motor). J8SW5-2function selection system combination: 1means fixed frequency single unit, 0 means fixed frequency multi split. J9SW5-3function selection group control: 1 stands for the master unit (its address in wired controller is 0), 0 stands for the slave units (the address should be set by the dip switch, their addresses only can be in the range: 1~15) J10SW5-4function selection preset: 1 no meaning, 0 no meaning

0010451167 PCB information- control type


Control type selection between remote and wired: select by dip switch J1, SW3-1 means remote control 1 0means wired control. For remote control type, please use remote controller YR-H71, and a remote receiver is equipped with indoor unit. For wired control type, wired controller YR-E12 will be used, 3-core shied wire is equipped with indoor unit. Door card control: controls ON/OFF, the start up setting will comply with last time request memorized according to condition memorize function. Its difference with emergency switch of convertible type unit lies: the emergency switch control will perform in the condition: 24degrees, auto fan speed in auto mode. The function combination between door card and remote/wired control type: select by dip switch: SW2-40 means and, 1 means later coming is preferential. Dip switch position in wired control type: Only one indoor unit of all indoor units connected with wired controller is the master unit, whose address is 0, function selection switch J9 SW5-3 1. The others are is slave units, and the quantity can be 0~15, whose addresses areSW1:1~4from 1 ~15, and cannot repeat. Wiring request in wired control type: the wired controller ports A-B-C are connected with indoor port CN5 1-2-3 through 3-core shield wire. Requirements: 1. Port A only connects with either of indoor port CN51 2. Port B connects with port CN5 (2) of all indoor units. 3. Port C connects with port CN5 (3) of all indoor units. Dip switch position in central control type: the addresses SW1:1~4SW2:1~4of indoor units connected with central controller can not repeat. In principle, they should be in the order from small to big. Wiring request in central control type: port A-B is connected with indoor port CN16A-Bthrough 2-core shield wire. Requirements: 1. Port A connects with port CN16Aof all indoor units. 2. Port B connects with port CN16Bof all indoor units. When only use remote control type, please select remote control unit, and install according to installation manual, there is no other special request. When only use wired control type, please select wired control unit, and install according to installation manual. When control multi indoor units, take care the requirements of dip switch and wiring, there is no other special request. When only use central control type, please firstly install according to air conditioner requests and set the dipswitch, there is no other special request. When central control type128and remote control type are used simultaneously, set the dip switch according to central control type, there is no other special request. When central control type 128 and wired control type 16 used simultaneously, max. indoor are

units sets: 12816 can be controller. Address setting of central controller can be met firstly, and then modulate the address setting of slave unit wired controlled.

LED in indoor PCB: 1. LED1is the state lamp for remote receiver as well as failure lamp. If indoor unit is normal, LED1 is on, or if failure occurs, LED1 flashes regularly, and you can adjust failure type according to the flash times. 2. LED2is used for multi split units as communication lamp. If communication between indoor and outdoor is normal, LED2 will be on. 3. LED3is used for single split units as communication lamp. If communication between indoor and outdoor is normal, LED3 will be on. 4. LED4LED5is the lamp that shows the data receiving or sending between wired controller and PCB, If LED4LED5 be on in turn, communication between wired controller and PCB is normal.

12 Exploded Views & Part Lists


12.1 Outdoor Units-24\28

Parts list
Spare parts No. number 1 2 3 4 5 6 7 8 9 001A0100122 001A1436160 001A0100261 001A5402022 0010450687 001A1301321 0010750926 001A1301708 001A5745009 Spare parts description in English Front grille handle Front panel Axial fan Fan motor Bracket for fan motor Condenser assy. Electric box cable clamp Capacitor for fan motor Resumable transformer clip for sensor ambient temp. sensor Capacitor for compressor Capacitor clamp PCB AC contactor Terminal block 4-way valve coil of 4-way valve High pressure switch Assistant capillary pipe temp. sensor discharging temp. sensor filter capillary 3-way stop valve 2-way stop valve muffle Compressor Accumulator Partition plate Front panel Bottom cover assy. branch triby Valve pedestal Top cover assy. Back grille Junction box Qty . Model 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 the proportion of the Failure rate spare-part stock Remark X AU242AHBEA 0.0000% 0.0000% X AU242AHBEA 0.0000% 0.0000% 0.0000% 0.0200% 0.0200% 0.0000% 0.0200% 0.0100% 0.0000% 0.0400% 0.0500% 0.0100% 0.0100% 0.0400% 0.0000% 0.0200% 0.0300% 0.0100% 0.0100% 0.0000% 0.0100% 0.0000% 0.0000% 0.0100% 0.0100% 0.0000% 0.0000% 0.0000% 0.0000% 0.0000% 0.0600% 0.0000% 0.0000% 0.0000% 0.0000% 0.0000% 0.0000% 0.0000% 0.0000% 0.0000% 0.0000% 0.0240% 0.0240% 0.0000% 0.0240% 0.0120% 0.0000% 0.0480% 0.0600% 0.0120% 0.0120% 0.0480% 0.0000% 0.0240% 0.0360% 0.0120% 0.0120% 0.0000% 0.0120% 0.0000% 0.0000% 0.0120% 0.0120% 0.0000% 0.0000% 0.0000% 0.0000% 0.0000% 0.0720% 0.0000% 0.0000% 0.0000% 0.0000% 0.0000% 0.0000% 0.0000% 0.0000% 0.0000% X X X X X * X X X X X X X X X X X X X * * X * * X * * X * * X *

AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA AU242AHBEA

10 001A3600018 11 0010451346 12 001A5736055 13 001A3900110 14 001A3600030 15 0010100001 16 0010451293 17 0010451291 18 0010451265 19 0010451258 20 0010850849 21 001A2500076 22 0010451039 23 001A2611255 24 0010451312 24 0010451313 25 001A2411023 26 001A2611288 27 001a2500154 28 001a2500153 29 0010751079 30 001A2000201 31 001A2101857 32 001A0100350 33 001A0100524 34 001A0100351 35 001A1301117 36 001A1301506 37 001A0100264 38 001A0100109 39 001A0100394

1 electrical source connection blo 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1

40 001A0100390 Slide plate(right) 1 AU242AHBEA 0.0000% 0.0000% 0010451430 41 wire assy. 1 AU242AHBEA 0.0100% 0.0120% 1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spareparts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3 months later. 2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and should be marked with"*" 3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock in the spare-part warehouse accord with the actual case,should be marked with " ". 4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the sparepart warehouse,should be marked with " x ". 5,Above should be improved accord with the reply of the market half a year per time. 6.The spare parts price on net is FOB Qingdao term.

Parts list
the proportion of the Spare parts Spare parts description in Qty Remark No. number English . Model Failure rate spare-part stock 1 001A0100122 Front grille 1 AU28NAHBEA 0.0000% 0.0000% X 2 001A1436160 handle 2 AU28NAHBEA 0.0000% 0.0000% X 3 001A0100261 Front panel 1 AU28NAHBEA 0.0000% 0.0000% X 4 001A5402022 Axial fan 1 AU28NAHBEA 0.0200% 0.0240% * 5 0010450687 Fan motor 1 AU28NAHBEA 0.0200% 0.0240% * 6 001A1301321 Bracket for fan motor 1 AU28NAHBEA 0.0000% 0.0000% X 7 0010750926 Condenser assy. 1 AU28NAHBEA 0.0200% 0.0240% * 8 001A1301453 Electric box 1 AU28NAHBEA 0.0100% 0.0120% 9 001A5745009 cable clamp 1 AU28NAHBEA 0.0000% 0.0000% X 10 001A3600134 Capacitor for fan motor 1 AU28NAHBEA 0.0400% 0.0480% * 11 0010451346 Resumable transformer 1 AU28NAHBEA 0.0500% 0.0600% * 12 001A5736055 clip for sensor 1 AU28NAHBEA 0.0100% 0.0120% 13 001A3900110 ambient temp. sensor 1 AU28NAHBEA 0.0100% 0.0120% * 14 / / / AU28NAHBEA / / / 15 / / / AU28NAHBEA / / / 16 0010451295 PCB 1 AU28NAHBEA 0.0200% 0.0240% * 17 0010451291 AC contactor 1 AU28NAHBEA 0.0300% 0.0360% * 18 001A4000158 Terminal block 1 AU28NAHBEA 0.0100% 0.0120% 19 0010451258 electrical source connection block 1 AU28NAHBEA 0.0100% 0.0120% 20 0010850849 4-way valve 1 AU28NAHBEA 0.0000% 0.0000% X 21 001A2500076 coil of 4-way valve 1 AU28NAHBEA 0.0100% 0.0120% 22 0010451039 High pressure switch 1 AU28NAHBEA 0.0000% 0.0000% X 23 001A2611255 Assistant capillary 1 AU28NAHBEA 0.0000% 0.0000% X 24 0010450243 pipe temp. sensor 1 AU28NAHBEA 0.0100% 0.0120% 24 0010450398 discharging temp. sensor 1 AU28NAHBEA 0.0100% 0.0120% 25 001A2411023 filter 1 AU28NAHBEA 0.0000% 0.0000% X 26 001A2611288 capillary 1 AU28NAHBEA 0.0000% 0.0000% X 27 001a2500154 3-way stop valve 1 AU28NAHBEA 0.0000% 0.0000% X 28 001a2500153 2-way stop valve 1 AU28NAHBEA 0.0000% 0.0000% X 29 0010751079 muffle 1 AU28NAHBEA 0.0000% 0.0000% X 30 0010700989 Compressor 1 AU28NAHBEA 0.0600% 0.0720% * 31 001A2101857 Accumulator 1 AU28NAHBEA 0.0000% 0.0000% X 32 001A0100350 Partition plate 1 AU28NAHBEA 0.0000% 0.0000% X 33 001A0100524 Front panel 1 AU28NAHBEA 0.0000% 0.0000% X 34 001A0100351 Bottom cover assy. 1 AU28NAHBEA 0.0000% 0.0000% X 35 001A1301117 branch triby 2 AU28NAHBEA 0.0000% 0.0000% X 36 001A1301506 Valve pedestal 1 AU28NAHBEA 0.0000% 0.0000% X 37 001A0100264 Top cover assy. 1 AU28NAHBEA 0.0000% 0.0000% X 38 001A0100109 Back grille 1 AU28NAHBEA 0.0000% 0.0000% X 39 001A0100394 Junction box 1 AU28NAHBEA 0.0000% 0.0000% X 40 001A0100390 Slide plate(right) 1 AU28NAHBEA 0.0000% 0.0000% X 41 0010451355 wire assy. 1 AU28NAHBEA 0.0100% 0.0120% 1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spareparts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3 months later. 2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and should be marked with"*" 3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock in the spare-part warehouse accord with the actual case,should be marked with " ". 4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part warehouse,should be marked with " x ". 5,Above should be improved accord with the reply of the market half a year per time. 6.The spare parts price on net is FOB Qingdao term.

Parts list
the proportion of Spare parts Qty No. number Spare parts description in English . Model Failure rate the spare-part stock Remark 1 001A0100122 Front grille 1 AU282AHBEA 0.0000% 0.0000% X 2 001A1436160 handle 2 AU282AHBEA 0.0000% 0.0000% X 3 001A0100261 Front panel 1 AU282AHBEA 0.0000% 0.0000% X 4 001A5402022 Axial fan 1 AU282AHBEA 0.0200% 0.0240% * 5 0010450687 Fan motor 1 AU282AHBEA 0.0200% 0.0240% * 6 001A1301321 Bracket for fan motor 1 AU282AHBEA 0.0000% 0.0000% X 7 0010750926 Condenser assy. 1 AU282AHBEA 0.0200% 0.0240% * 8 001A1301453 Electric box 1 AU282AHBEA 0.0100% 0.0120% 9 001A5745009 cable clamp 1 AU282AHBEA 0.0000% 0.0000% X 10 001A3600018 Capacitor for fan motor 1 AU282AHBEA 0.0400% 0.0480% * 11 0010451346 Resumable transformer 1 AU282AHBEA 0.0500% 0.0600% * 12 001A5736055 clip for sensor 1 AU282AHBEA 0.0100% 0.0120% 13 001A3900110 ambient temp. sensor 1 AU282AHBEA 0.0100% 0.0120% * 14 / / / AU282AHBEA / / / 15 / / / AU282AHBEA / / / 16 0010451293 PCB 1 AU282AHBEA 0.0200% 0.0240% * 17 0010400334 AC contactor 1 AU282AHBEA 0.0300% 0.0360% * 18 0010451265 Terminal block 1 AU282AHBEA 0.0100% 0.0120% 19 0010451258 electrical source connection block 1 AU282AHBEA 0.0100% 0.0120% 20 001A2500155 4-way valve 1 AU282AHBEA 0.0000% 0.0000% X 21 001A2500076 coil of 4-way valve 1 AU282AHBEA 0.0100% 0.0120% 22 0010400127 High pressure switch 1 AU282AHBEA 0.0000% 0.0000% X 23 001A0500365 Assistant capillary 1 AU282AHBEA 0.0000% 0.0000% X 24 0010451314 pipe temp. sensor 1 AU282AHBEA 0.0100% 0.0120% 24 0010450398 discharging temp. sensor 1 AU282AHBEA 0.0100% 0.0120% 25 001A2411023 filter 1 AU282AHBEA 0.0000% 0.0000% X 26 0010753601 capillary 1 AU282AHBEA 0.0000% 0.0000% X 27 001a2500154 3-way stop valve 1 AU282AHBEA 0.0000% 0.0000% X 28 001a2500153 2-way stop valve 1 AU282AHBEA 0.0000% 0.0000% X 29 0010751079 muffle 1 AU282AHBEA 0.0000% 0.0000% X 30 0010753600 Compressor 1 AU282AHBEA 0.0600% 0.0720% * 31 0010751125 Accumulator 1 AU282AHBEA 0.0000% 0.0000% X 32 001A0100350 Partition plate 1 AU282AHBEA 0.0000% 0.0000% X 33 001A0100524 Front panel 1 AU282AHBEA 0.0000% 0.0000% X 34 001A0100351 Bottom cover assy. 1 AU282AHBEA 0.0000% 0.0000% X 35 001A1301117 branch triby 2 AU282AHBEA 0.0000% 0.0000% X 36 001A1301506 Valve pedestal 1 AU282AHBEA 0.0000% 0.0000% X 37 001A0100264 Top cover assy. 1 AU282AHBEA 0.0000% 0.0000% X 38 001A0100109 Back grille 1 AU282AHBEA 0.0000% 0.0000% X 39 001A0100394 Junction box 1 AU282AHBEA 0.0000% 0.0000% X 40 001A0100390 Slide plate(right) 1 AU282AHBEA 0.0000% 0.0000% X 41 0010451430 wire assy. 1 AU282AHBEA 0.0100% 0.0120% 1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spareparts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3 months later. 2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and should be marked with"*" 3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock in the spare-part warehouse accord with the actual case,should be marked with " ". 4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part warehouse,should be marked with " x ". 5,Above should be improved accord with the reply of the market half a year per time. 6.The spare parts price on net is FOB Qingdao term.

Model 2: AC242ACBEA

Parts list
the proportion of the sparepart stock Remark 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.048% * 0.012% 0.024% * 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.024% * 0.024% * 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.024% * 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.012% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.012%

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

Spare parts number 001A2400087 001A0100330 001A1301398 001A1301395 001A1301399 0010451478 001A3600009B 0010451262 0010451167 0010451494 001A14311292 001A1431326 001A3900006 001A1301382 001A1301383 001A1301381 001A1443592 10450779 001A2300042 001A1436664 001A1431608 001A1431609 001A3900159 001A0500252 0010750130 001A1734862 001A1436606 001A1101104 001A1101041 001A1431593 001A1301394 001A1231180 001A1431599 001A0100329 001A1431586 001A1431827 001A3000107 0010450309 001A1431587 001A1431598 001A3000107 001A1301400 001A1233191 001A1301396 0010753604 001A1101099 001A1101103 001A1231192 001A1231182 001A1101098

Spare parts description in english Qty. air filter 2 inlet grill assy 1 fixing plate 2 strengthen tendon 1 pinch plate 2 wiring assembly 1 Fan motor capacitor 2uf 1 transformer 1 indoorPCB 1 termonal block 1 Power line clip 1 wiring block 1 environment temp. Sensor indoor 1 clamp plate of motor 1 connecting rod of motor 1 Fan motor bracket 1 small block 1 Indoor fan motor 1 centrifugal fan 2 drainage elbow 1 scroll case 1 2 scroll case 2 2 Pipe temp. sensor indoor 1 Air inlet tube assy. 1 liquid pipe 1 back framework 2 handle 4 right wallboard 1 plate assy right 1 longblade 1 strengthen tendon 1 outlet grill hold middle 1 mini fan blade 1 cover 1 display panel 1 Airflow oriented board affix 3 stepping motor 1 receive panel 1 Indicator light base 1 Prompting pole 2 curving connecting rod 2 fixing layering 1 Drain pan 1 Evaporator left holder 1 Evaporator assembly 1 plate assy left 1 left wallboard 1 assistant drain pan 1 cover assy 1 back framework 1 Evaporator right holder Remote Controller 1 1

Model Failure rate AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.04% AC242ACBEA 0.01% AC242ACBEA 0.02% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.02% AC242ACBEA 0.02% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.02% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.01% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA 0.00% AC242ACBEA AC242ACBEA 0.00% 0.01%

51 001A1301401 52 0010451255

Model 2: AC28NACBEA

Parts list
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 Spare parts number 001A1231278 001A2400108 001A1101174 001A17341062 001A3900006 001A1200185 001A1101179 001A1301574 001A1301581 001A2331071 001A1301580 0010450626 001A01001102 001A1301591 0010451167 001A1301378 001A1431750 0010451262 001A3600009B 0010451494 001A1301592 001A5701009 001A1301582 001A3900005 0010753606 0010753605 001A1301588 001A1301577 001A1301579 001A1231277 0010752959 001A1231276 001A1301578 001A1301575 001A1101178 001A1101176 001A1431746 001A1443745 001A3000198 001A1431878 0010400410 001A1231279 001A1431800 001A1231280 001A1231272 001A1231281 001A1231274 001A0100431 001A1101177 001A1231275 001A1231284 001A1231273 001A0100432 Spare parts description in english inlet grill assy air filter front panel assy pad Pipe temperature sensor drain pan assy mounting plate left scroll case motor holder centrifugal fan motor bracket motor electric box assy PCB bracket 1 indoor PCB Eletrical box Terminal block cover transformer capacitor termonal block PCB bracket 2 Power line clip scroll case right environment temperature sensor gas pipe liquid pipe partition plate plate assy right right wallboard ornamental plate right evaporator ornamental plate left left wallboard plate assy left rear guard plate blade assy fixing bracket right prompting pole Synchromotor Indicator light cover receive panel ornamental plate fixing bracket left middle ornamental plate left top cover assy ornamental plate right front top cover assy left fixing bracket blade assy2 top cover assy middle outlet grill hold right top cover assy outlet grill hold right Qty. 2 2 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 Model AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA AC28NACBEA the proportion of the Failure rate spare-part stock Remark 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.02% 0.00% 0.02% 0.00% 0.00% 0.02% 0.00% 0.00% 0.01% 0.04% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.01% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.02% 0.00% 0.02% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.024% 0.000% 0.024% 0.000% 0.000% 0.024% 0.000% 0.000% 0.012% 0.048% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.012% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.024% 0.000% 0.024% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% * * * * * *

Model 3: AD242AMBEA AD28NAMBEA

Parts list
Spare parts description in No. Spare parts number English 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 0010800086 0010100228 0010752516 0010800106 0010100016 001A1301988 001A2331089 001A5401035 0010200120 001A17341291 001A14311066 001A17341292 0010100017 001A17341292 0010200122 0010100224 0010100226 0010100227 0010451262 001A1101206 001A1452909 001A1452861 0010451167 0010451265 001A3600134 001A1301796 001A14341141 001A5002256 001A1301784 001A17511246 001A3000250 0010450169 001A1301786 001A1301782 001A1309785 001A1301783 001A3400076 001A1301789 001A1301790 001A1101205 0010800105 0010800085 0010200114 0010451521 Guard plate 1 Guard plate 2 Evaporator assembly Right fixing plate assembly Supporting plate assembly Seal ring for scroll case Centrifugal fan Cushion Cushion Cushion Air outlet Cushion Base plate assembly Cushion Cushion Long fixing tendon Enclosure Inlet wind connect frame Transformer Electrical box Rubber ring Rubber ring PCB Terminal block Fan capacitor Electrical box cover assembly Water drain pipe assembly Fixing bolt Water pump fixing stand Damping pad Dual shaft electric motor Water pump motor Floater fixing stand Connecting plate 1 Water pump support Connecting plate 2 Float switch Fixed handle 1 Fixed handle 2 Scroll case Left fixing plate assembly Water collecting pan assembly Cushion Wired controller Qty. Model 1 1 1 1 1 2 2 1 1 3 3 3 1 3 1 2 1 1 1 1 1 2 1 1 1 1 1 3 1 3 1 1 1 1 1 1 1 1 1 2 1 1 1 1 AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA AD242AMBEA Failure rate 0.000% 0.000% 0.010% 0.000% 0.000% 0.000% 0.020% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.010% 0.010% 0.000% 0.000% 0.020% 0.010% 0.040% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.020% 0.000% 0.000% 0.000% 0.000% 0.020% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.010% the proportion of the spare-part stock 0.000% 0.000% 0.012% 0.000% 0.000% 0.000% 0.024% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.012% 0.012% 0.000% 0.000% 0.024% 0.012% 0.048% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.024% 0.000% 0.000% 0.000% 0.000% 0.024% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.012% * X X X X X X * X X X X * X X X X X X X X * X X X * X X X X X X X X X X X Remark X X

1,The failure rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3 months later. 2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and should be marked with"*" 3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock in the sparepart warehouse accord with the actual case,should be marked with " ". 4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part warehouse,should be marked with " x ". 5,Above should be improved accord with the reply of the market half a year per time. 6.The spare parts price on net is FOB Qingdao term.

Parts list
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 Spare parts description in Spare parts number English 0010800086 0010100228 0010752957 0010800106 0010100016 001A1301988 001A2331089 001A5401035 0010200120 001A17341291 001A14311066 001A17341292 0010100017 001A17341292 0010200122 0010100224 0010100226 0010100227 0010451262 001A1101206 001A1452909 001A1452861 0010451167 0010451265 001A3600134 001A1301796 001A14341141 001A5002256 001A1301784 001A17511246 001A3000250 0010450169 001A1301786 001A1301782 001A1309785 001A1301783 001A3400076 001A1301789 001A1301790 001A1101205 0010800105 0010800085 0010200114 0010451521 Guard plate 1 Guard plate 2 Evaporator assembly Right fixing plate assembly Supporting plate assembly Seal ring for scroll case Centrifugal fan Cushion Cushion Cushion Air outlet Cushion Base plate assembly Cushion Cushion Long fixing tendon Enclosure Inlet wind connect frame Transformer Electrical box Rubber ring Rubber ring PCB Terminal block Fan capacitor Electrical box cover assembly Water drain pipe assembly Fixing bolt Water pump fixing stand Damping pad Dual shaft electric motor Water pump motor Floater fixing stand Connecting plate 1 Water pump support Connecting plate 2 Float switch Fixed handle 1 Fixed handle 2 Scroll case Left fixing plate assembly Water collecting pan assembly Cushion Wired controller Qty. Model 1 1 1 1 1 2 2 1 1 3 3 3 1 3 1 2 1 1 1 1 1 2 1 1 1 1 1 3 1 3 1 1 1 1 1 1 1 1 1 2 1 1 1 1 AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA AD28NAMBEA the proportion of the spareFailure rate part stock Remark 0.000% 0.000% 0.010% 0.000% 0.000% 0.000% 0.020% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.010% 0.010% 0.000% 0.000% 0.020% 0.010% 0.040% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.020% 0.000% 0.000% 0.000% 0.000% 0.020% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.010% 0.000% 0.000% 0.012% 0.000% 0.000% 0.000% 0.024% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.012% 0.012% 0.000% 0.000% 0.024% 0.012% 0.048% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.024% 0.000% 0.000% 0.000% 0.000% 0.024% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.012% * X X X X X X * X X X X * X X X X X X X X * X X X * X X X X X X X X X X X X X

Model 4: AD242AHBEA and AD28NAHBEA are the same.

Parts list
Spare parts No. number 1 0010150130 2 0010151123 3 4 5 6 7 8 9 0010851049 Spare parts description in english connection frame of inlet air hanging boarding assy. of liquid pipe Failure rate 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.01% 0.02% 0.02% 0.04% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.02% 0.01% 0.00% 0.02% 0.00% 0.00% 0.00% 0.02% 0.00% 0.00% 0.00% the proportion of the sparepart stock 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.012% 0.024% 0.024% 0.048% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.024% 0.012% 0.000% 0.024% 0.000% 0.000% 0.000% 0.024% 0.000% 0.000% 0.000% * * * * * *

Qty. 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 2 1 1 1 1

Model AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA AD242AHBEA

Remark

001A13011068 evaporator brackt 1 0010100502 bottom plate assy. 0010100511 0010100503 fix slot assy. air discharge framework

001A13011069 evaporator brackt 2 0010100504 evaporator fixing plate 1 cover board assy. 1 cover board assy. 2 fix tendon assy. 1 evaporator fixing plate 3 cover board assy.3 fix tendon assy. 2 transformer PCB fan speed adjusting board fan motor capacitor electrical box cover termianl block

10 0010800284 11 0010800285 12 0010800282 13 0010800290 14 0010800286 15 0010800283 16 0010451262 17 0010451167 18 001A3300352 19 001A3600254 20 0010850004 21 0010451265

22 001A13011036 electrical box assy. 23 001A13011050 bracket of floater 24 001A3400160 float switch 25 001A1436026 26 001A3900006 sensor bracket coil temp. sensor

27 001A1101236 supporting plate 28 001A13011043 snail shell 2 29 001A2301105 fan 2 30 0010750004 evaporator assy. 001A13011044 hermitic circle of snail shell 31 32 001A2301104 fan 1 33 001A13011042 snail shell 1 34 001A13011039 motor bracket 35 001A13011045 motor fixing bolt 36 001A3000290 37 0010201091 38 0010851049 39 0010100498 indoor motor drain pan assy. guarding plate assy.2 guarding plate assy.1

Cassette type -AB242ACBEA AB28NACBEA

Parts list
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 Spare parts number 001A0100708 001A1301741 001A1301743 001A1301668 001A3000219 001A1301742 001A2300088 001A1301752 001A1301751 001A1301710 001A5102015 001A3900006 0010752481 0010700299 001A0100711 001A1434920 0010450169 0010450154 0010752522 001A1301750 001A0900089 001A1301753 001A1232305 001A3600232 0010451265 0010451262 0010451167 001A1232306 001A1232307 001A1431661 001A3900159 001A1301756 001A13001077 0010451255 001A1434574A 001A1434925 001A6645007 Spare parts description in english Qty. Bottom plate assy. 1 Swing 4 Motor holder 1 Motor bracket 1 Indoor fan motor 1 wiring fix plate 1 Indoor fan 1 pipe holder plate 1 Evaporator holded plate 1 Fan in-built part 1 Flange screw nut 1 Pipe temp. sensor indoor 1 liquid pipe assy. 1 air pipe assy. 1 Pump Bracket assy. 1 Drainage pipe 1 Water pump motor 1 Float Switch 1 Evaporator assembly 1 Evaporator holder 2 Drain pan assy. 1 bottom plate of electrical box 1 Eletrical box 1 Fan motor capacitor 4.5 uf 1 Terminal block 1 Transformer 1 indoor PCB 1 Electrical box cover 1 1 Electrical box cover2 1 inlet circle 1 environment temp. Sensor indoor 1 guarding grill 1 hoop 1 Controller 1 Heat insulation pipe 1 1 Heat insulation pipe2 1 cable clamp 6 Failure Model rate AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.02% AB242ACBEA 0.00% AB242ACBEA 0.02% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.02% AB242ACBEA 0.00% AB242ACBEA 0.01% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.04% AB242ACBEA 0.00% AB242ACBEA 0.01% AB242ACBEA 0.02% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.01% AB242ACBEA 0.00% AB242ACBEA 0.00% AB242ACBEA 0.00% the proportion of the spare-part stock Remark 0.000% 0.000% 0.000% 0.000% 0.024% * 0.000% 0.024% * 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.024% * 0.000% 0.012% 0.000% 0.000% 0.000% 0.000% 0.048% * 0.000% 0.012% 0.024% * 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.012% 0.000% 0.000% 0.000%

1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spareparts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3 months later. 2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and should be marked with"*" 3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock in the spare-part warehouse accord with the actual case,should be marked with " ". 4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part warehouse,should be marked with " x ". 5,Above should be improved accord with the reply of the market half a year per time. 6.The spare parts price on net is FOB Qingdao term.

Parts list
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 Spare parts number 001A0100708 001A1301741 001A1301743 001A1301668 001A3000219 001A1301742 001A2300088 001A1301752 001A1301751 001A1301710 001A5102015 001A3900006 0010752919 0010700299 001A0100711 001A1434920 0010450169 0010450154 0010752958 001A1301750 001A0900089 001A1301753 001A1232305 001A3600232 0010451265 0010451262 0010451167 001A1232306 001A1232307 001A1431661 001A3900159 001A1301756 001A13001077 0010451255 001A1434574A 001A1434925 001A6645007 Spare parts description in english Qty. Bottom plate assy. 1 Swing 4 Motor holder 1 Motor bracket 1 Indoor fan motor 1 wiring fix plate 1 Indoor fan 1 pipe holder plate 1 Evaporator holded plate 1 Fan in-built part 1 Flange screw nut 1 Pipe temp. sensor indoor 1 liquid pipe assy. 1 air pipe assy. 1 Pump Bracket assy. 1 Drainage pipe 1 Water pump motor 1 Float Switch 1 Evaporator assembly 1 Evaporator holder 2 Drain pan assy. 1 bottom plate of electrical box 1 Eletrical box 1 Fan motor capacitor 4.5 uf 1 Terminal block 1 Transformer 1 indoor PCB 1 Electrical box cover 1 1 Electrical box cover2 1 inlet circle 1 environment temp. Sensor indoor 1 guarding grill 1 hoop 1 Controller 1 Heat insulation pipe 1 1 Heat insulation pipe2 1 cable clamp 6 Failure Model rate AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.02% AB28NACBEA 0.00% AB28NACBEA 0.02% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.02% AB28NACBEA 0.00% AB28NACBEA 0.01% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.04% AB28NACBEA 0.00% AB28NACBEA 0.01% AB28NACBEA 0.02% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.01% AB28NACBEA 0.00% AB28NACBEA 0.00% AB28NACBEA 0.00%

the proportion of the sparepart stock Remark 0.000% 0.000% 0.000% 0.000% 0.024% * 0.000% 0.024% * 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.024% * 0.000% 0.012% 0.000% 0.000% 0.000% 0.000% 0.048% * 0.000% 0.012% 0.024% * 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.012% 0.000% 0.000% 0.000%

1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spareparts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3 months later. 2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and should be marked with"*" 3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock in the spare-part warehouse accord with the actual case,should be marked with " ". 4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part warehouse,should be marked with " x ". 5,Above should be improved accord with the reply of the market half a year per time. 6.The spare parts price on net is FOB Qingdao term.

Parts list
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 Spare parts number 001A1231233 001A1301502 001A1231234 0010450638 001A1432687 001A1734970 001A0100357 001A1734832 001A1301508 001A0400118 001A1301440 001A1301441 0010150192 001A17341250 001A1231237 001A1742836 001A1734023 0010150193 001A0100828 001A1101145 001A1734842 001A5002078 001A0100575 001A1745106 0010402372 001A5739020 001A1101146 001A1752911 001A1452695 0010250163 001A1452695 001A5102050 001A2300062 001A1742931 001A1301445 001A1431647 001A1301437 001A1301438 0010200026 001A0100385 001A2400102 001A0100075 001A1734967 001A17621241 001A1757833 001A3000236 001A1301448 0010250201 001A4000151 0010450450 001A3600018 001A1452695 0010400911 / 001A13011074 001A1301444 001A1734967 001A1752840 001A3800128 001A0100407 Failure Spare parts description in english Qty. Model rate Inlet grill 1 AP242ACBEA 0.00% Inlet grill insert 2 AP242ACBEA 0.00% Front panel 1 AP242ACBEA 0.00% Operation panel 1 AP242ACBEA 0.00% Horizontal blade 6 AP242ACBEA 0.00% Vertical air outlet pad 2 AP242ACBEA 0.00% Vertical blade 1 AP242ACBEA 0.00% Air damper pad 1 AP242ACBEA 0.00% Air damper 1 AP242ACBEA 0.00% Heat exchanger assembly 1 AP242ACBEA 0.01% Evaporator left mounting plate 1 AP242ACBEA 0.00% Evaporator right mounting plate 1 AP242ACBEA 0.00% Left board 1 AP242ACBEA 0.00% Left board pad 1 AP242ACBEA 0.00% Top cover plate 1 AP242ACBEA 0.00% Cover 1 AP242ACBEA 0.00% Side board horizontal pad 1 AP242ACBEA 0.00% Right board 1 AP242ACBEA 0.00% Back guard 1 AP242ACBEA 0.00% Wiring plate 1 AP242ACBEA 0.00% Thermal insulation pipe 1 AP242ACBEA 0.00% Special nut 1 AP242ACBEA 0.00% Bottom plate 1 AP242ACBEA 0.00% Plastic cushion 1 AP242ACBEA 0.00% Motor 1 AP242ACBEA 0.02% Mounting wiring clamp 1 AP242ACBEA 0.00% Pipe press plate 1 AP242ACBEA 0.00% Cushion rubber 1 AP242ACBEA 0.00% Cushion rubber 1 AP242ACBEA 0.00% Drain pan 1 AP242ACBEA 0.00% Fan pad 1 AP242ACBEA 0.00% Nut 1 AP242ACBEA 0.00% Centrifugal fan 1 AP242ACBEA 0.02% Down shell press plate cushion 1 AP242ACBEA 0.00% Down shell press plate 1 AP242ACBEA 0.00% Wiring clamp (plasticizing) 1 AP242ACBEA 0.00% Reinforcing plate (left) 1 AP242ACBEA 0.00% Reinforcing plate (right) 1 AP242ACBEA 0.00% Air ring 1 AP242ACBEA 0.00% Down shell 1 AP242ACBEA 0.00% Filter 1 AP242ACBEA 0.00% Lock 1 AP242ACBEA 0.00% Sealing plate 1 AP242ACBEA 0.00% Sealing plate 1 AP242ACBEA 0.00% Cushion rubber 1 AP242ACBEA 0.00% Synchro-motor 1 AP242ACBEA 0.02% Electric box cover 1 AP242ACBEA 0.00% Wire clamp 1 AP242ACBEA 0.00% Terminal block 1 AP242ACBEA 0.00% Transformer 1 AP242ACBEA 0.01% Fan capacitor 1 AP242ACBEA 0.04% Cushion rubber 1 AP242ACBEA 0.00% Indoor PCB 1 AP242ACBEA 0.02% / AP242ACBEA Electric box 1 AP242ACBEA 0.00% Fixing horizontal plate 1 AP242ACBEA 0.00% Sealing cushion 1 AP242ACBEA 0.00% Supporting pad 1 AP242ACBEA 0.00% Pipe temp. sensor 1 AP242ACBEA 0.00% Supporting plate assembly 1 AP242ACBEA 0.00% the proportion of the spare-part stock 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.012% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.024% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.024% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% 0.024% 0.000% 0.000% 0.000% 0.012% 0.048% 0.000% 0.024% 0.000% 0.000% 0.000% 0.000% 0.000% 0.000% Remark * * * * *

13.Performance Curves
1 Cooling
When air conditioner operate on cooling status, the indoor air humid ball and outdoor air dry ball which means humid degree of indoor and dry degree of outdoor unit make important mean on cooling capacity. 1) Chart of humid ball of indoor unit air

modify coefficient

2) Chart of dry ball of outdoor unit air

modify coefficient

2 Heating
When air conditioner operate on heating status,the outdoor air humid ball and indoor air dry ball which means humid degree of outdoor and dry degree of indoor unit also make important mean on heating capacity. 1)Chart of humid ball of outdoor unit air

modify coefficient

2)Chart of dry ball of indoor unit air

modify coefficient

PERFORMANCE CURVES

Model: AD28NAMBEA
Cool capacity graph

12 10 8 6 4 2 0 -7 5 15 25 35 43 Outdoor DB( )
EER graph
DB(

20 22 25 27 30 32
Indoor )

Capacity(KW) 5 4 EER 3 2 1

20 22 25 27 30 32
Indoor DB( )

-7

15

25

35

43

Outdoor DB( )

Heat capacity graph

12 11 10 Capacity(KW) 9 8 7 6 5 4 -7 -5 0 7 10 15 Outdoor DB( ) 16 18 20 22 24 26 28


Indoor DB( )

COP graph

4 16 18 20 22 24 26 28
)

3 COP 2 1 -7 -5 0 7 10 15 Outdoor DB( )

PERFORMANCE CURVES

AC28NACBEA
Cool capacity graph

12 10 8 6 4 2 0 -7 5 15 25 35 43 Outdoor DB( )
DB(

20 22 25 27 30 32
Indoor )

EER graph

Capacity(KW) 5 4 EER 3 2 1

20 22 25 27 30 32
Indoor DB( )

-7

15

25

35

43

Outdoor DB( )

PERFORMANCE CURVES

AB28NACBEA

12 10 8 6 4 2 0 -5 5 15 25 35 43 Outdoor DB( )
DB(

20 22 25 27 30 32
Indoor )

EER graph

Capacity(KW) 5 4 EER 3 2 1

20 22 25 27 30 32
Indoor DB( )

-5

15

25

35

43

Outdoor DB( )

Noise level charts

15.AIR VELOCITY DISTRIBUTION

Model: AC28NACBEA a. Cooling / Air Velocity Distribution Cooling Blowy angle:25 Air Velocity Distribution

2.4

5.5

b. Cooling / Temperature Distribution


Cooling Blowy angle:25 Temperature Distribution

2.4

27 25 22

5.5

AIR VELOCITY DISTRIBUTION

Model: AB28NACBEA a. Cooling / Air Velocity Distribution Cooling Blowy angle:40 Air Velocity Distribution

m/s

m/s

0 4 2 1 0 1 2 4

b. Cooling / Temperature Distribution Cooling Blowy angle:40


Temperature Distribution

22 25

22 25

27

27

0 4 2 1 0 1 2 4

AIR VELOCITY DISTRIBUTION

AD28NAMBEA

cooling air discharge angle 5 Air Velocity distribution

2.4 1.8

0.5
0 5.5

cooling air discharge angle 5 Temperature distribution

2.4 1.8

22 25 27