Você está na página 1de 28

D I g S I L E N T T e c h n i c a l

D o c u m e n t a t i o n
Static Generator

S t a t i c G e n e r a t o r - 2 -

Rev. Nr. Author Date Reviewed by Date PF Version
01 S.Weigel 15.04.2010 14.0.516


DIgSILENT GmbH
Heinrich-Hertz-Strasse 9
D-72810 Gomaringen
Tel.: +49 7072 9168 - 0
Fax: +49 7072 9168- 88
http://www.digsilent.de
e-mail: mail@digsilent.de

Static Generator
Published by
DIgSILENT GmbH, Germany
Copyright 2009. All rights
reserved. Unauthorised copying
or publishing of this or any part
of this document is prohibited.
T a b l e o f C o n t e n t s

S t a t i c G e n e r a t o r - 3 -

Table of Contents

1 General Description ............................................................................................................................. 4
1.1 Basic Data ............................................................................................................................................. 4
1.1.1 Zero/Negative Sequence Model........................................................................................................... 5
1.2 Load-Flow Analysis ................................................................................................................................. 6
1.2.1 Local Voltage Controller Options ......................................................................................................... 6
1.2.2 External Station Controller .................................................................................................................. 8
1.2.3 Primary frequency bias ...................................................................................................................... 9
1.2.4 Reactive Power Limits ........................................................................................................................ 9
1.2.5 Active Power Limits ......................................................................................................................... 10
1.3 Short-Circuit Calculations ...................................................................................................................... 10
1.3.1 VDEC/IEC Short Circuit .................................................................................................................... 10
1.3.2 Complete Short Circuit ..................................................................................................................... 13
1.3.3 ANSI Short Circuit ........................................................................................................................... 15
1.3.4 IEC 61361 ...................................................................................................................................... 17
1.4 Harmonics ........................................................................................................................................... 17
1.5 RMS Simulation .................................................................................................................................... 18
1.5.1 Current Source Model ...................................................................................................................... 18
1.5.2 Voltage Source Model ...................................................................................................................... 19
1.5.3 Negative/Zero Sequence Model......................................................................................................... 20
1.6 EMT Simulation .................................................................................................................................... 20
1.6.1 Current Source Model ...................................................................................................................... 21
1.6.2 Voltage Source Model ...................................................................................................................... 22
1.6.3 Zero Sequence? .............................................................................................................................. 22
2 Input/Output Definition of Dynamic Models .................................................................................... 23
2.1 Stability Model (RMS) ........................................................................................................................... 23
2.1.1 Current Source Model ...................................................................................................................... 23
2.1.2 Voltage Source Model ...................................................................................................................... 24
2.2 EMT-Model .......................................................................................................................................... 25
2.2.1 Current Source Model ...................................................................................................................... 25
2.2.2 Voltage Source Model ...................................................................................................................... 26
3 Input Parameter Definitions .............................................................................................................. 27
3.1 *.ElmGenstat ....................................................................................................................................... 27
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 4 -

1 General Description
The Static Generator is an easy-to-use model of any kind of static (no rotating) generator. Applications are:
- Photovoltaic Generators
- Fuel Cells
- Storage devices
- HVDC Terminals
- Reactive Power Compensators
- Wind Generators
Wind generators, which are connected through a full-size converter to the grid, can also be modelled as static
generators, because the behaviour of the plant (from the view of the grid side) is determined by the converter.
1.1 Basic Data

Figure 1: Basic Data for the Static Generator
The specific application of the static generator can be selected in the category box.
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 5 -


Figure 2: Categories
The number of parallel machines can be entered, as well as the MVA rating of a single generator. In general, the
total MW and Mvar outputs of the static generator will be the rating of a single generator multiplied by the
number of parallel machines specified. In the specific case of the Wind Generator category, the output will
additionally be affected by the Wind Generation Scaling Factor of the zone to which it belongs.

Figure 3: Zone
1.1.1 Zero/Negative Sequence Model
The negative sequence current is always set to zero. The zero sequence depends on the settings:
Input Parameter:
- iearthed : Earthed (option)
- r0 : Zero-sequence Resistance, r0 (hidden if ieathed is disabled)
- x0 : Zero-sequence Reactance, x0 (hidden if ieathed is disabled)

Figure 4: Negative Sequence Model
u2
i2 = 0
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 6 -


Figure 5: Zero-sequence Model if option Earthed is enabled
If the option is disabled the zero-sequence current is zero.
1.2 Load-Flow Analysis
1.2.1 Local Voltage Controller Options
The local voltage controller could be set to three different modes (cos, V, droop) that are described in the the
following sub chapters.
1.2.1.1 Power Factor control
This option corresponds to a PQ bus type and its block diagram is shown in Figure 7 (1). With the power factor
control the user can specify active and reactive power outputs at which the static generator will be operated (PQ
bus). The way to specify these values will depend on the Input Mode selected.

Figure 6: Input Mode
The voltage and droop value boxes are disabled for the Power Factor control option. P
sum
and Q
sum
will be
controlled in unbalanced load flow.
u0
i0 r0 x0
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 7 -

U
U o ,
x
I
i r
U U ,
) cos( , ) 1 ( P
U P, ) 2 (
droop U, ) 3 (
max
Q
min
Q
U
U o ,
x
I
i r
U U ,
) cos( , ) 1 ( P
U P, ) 2 (
droop U, ) 3 (
max
Q
min
Q

Figure 7: Voltage Controller - Options
1.2.1.2 Voltage control
This option correspondes to a PV bus type and its block diagram is shown in Figure 7 (2). Voltage control can be
done locally, i.e. the reactive power output of the generator is controlled to achieve the specified local voltage at
its terminal. The active power output is constant for the dispatch.
When this option is selected, the voltage setpoint box is enabled and its value must be entered.
1.2.1.3 Droop control
This option corresponds to a DV bus type and its block diagram is shown in Figure 7 (3). The generator can be
set to control the local voltage at its terminal to a specified setpoint. With droop control the setpoint is not
reached in any case because the setpoint is moved (by du
droop
) as more reactive power is needed to reach the
original voltage setpoint of the static generator. The advantage of the droop control is that more than one
machine at one busbar could control the voltage. As well as the participation of the single machine could be
configured with the setting of the droop value.
When set to voltage control, a droop value can be entered. The voltage at the local busbar is then controlled
according to the following equations this equations are shown graphically in Figure 8:
droop
S
Q
Q
Q Q
du
du u u
nom
droop
droop
setpoint
droop
droop setpoint
100
=

=
=

G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 8 -

Where:
u is the actual voltage value at the terminal busbar
u
setpoint
is the specified voltage setpoint of the stataic generator
Q is the actual reactive power output of the static generator
Q
setpoint
is the specified dispatch reactive power of the static generator
S
nom
is the nominal apparent power
droop is the droop value specified in percentage.
| | pu u
setp
u
u
setp
Q
Q
| | pu Q
droop
| | pu u
setp
u
u
setp
Q
Q
| | pu Q
droop

Figure 8: Droop Voltage Control
1.2.2 Static Generator as Slack
For load flow only it is also possible to use the static gernator as slack. For that the Active Power Control on the
load flow command has to be set as Dispatched, the balancing has to be set by Static Generator at Reference
Bus, a static generator has to be connected to the selected busbar. The local voltage controller of the slack-static
generator has to be set either to Voltage or to Droop.
1.2.3 External Station Controller
The static generator can also be part of a station controller. In such a case, the external station controller has
priority over the local voltage controler of the static generator.
The way the station controller dispatches the static generators depends on the settings of the Load Flow page for
the station controller. See technical reference of the station controller.
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 9 -

1.2.4 Primary frequency bias
Shortly following a disturbance, the governors of the units participating in primary control will increase/decrease
their turbine power and drive the frequency close to its nominal value. The change in the generator power is
proportional to the frequency deviation and is shared among participating units according to the gain (Kpf) of
their primary controllers, this is depicted in Figure 9. If the Active Power Control According to Primary
Control option is selected in PowerFactory's load flow command, the power balance is established by all
generators having a primary controller gain (parameter Prim. Frequency Bias from the Load Flow tab of
the static generator), according to the corresponding frequency droop.
| | pu f
n
f
f
disp
P
P
| | pu P
P A
f A
| | pu f
n
f
f
disp
P
P
| | pu P
P A
f A

Figure 9: Primary Freqncy Bias
The actual dispatched real power of the generator is calculated as:
P = P
dispatch
+ dP
where
dP = dF * Kpf
dP is the change in generator output
dF is the change in frequency
Kpf is the primary controller gain parameter for the generator
1.2.5 Reactive Power Limits
The reactive power limits can be specified in two ways:
Minimum/maximum constant limits. In the case of the minimum/maximum limits, these are originally set equal to
the minimum and maximum value of the nominal reactive power. Note that the reactive power limits are
operational data and will be saved to the operation scenario if active. Along these values, a scaling factor for each
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 1 0 -

limit can be specified, which can be used in conjunction with the option Consider Reactive Power Limits Scaling
Factor in the Basic Options of the Load Flow Calculation dialog.
Capability Curve objects (IntQlim) allows the consideration of distinct minimum / maximum values of the
reactive power at different levels of active power injection. Capability curves are stored inside the 'Mvar Limits
Curves' folder in the Operational Library. Synchronous generators (ElmSym) and static generators (ElmGenstat)
defined in the network model can use the same Capability Curve object that is stored in the operational library.
When a capability curve is used, the dispatch of the generator always stays within its minimum and maximum
range if the option Consider Reactive Power Limits on the Load Flow command is activated.
How to create a new capability curve object is explained in the help of PowerFactory.
1.2.5.1 Applying Mvar Limits Curve from Operational Library
To apply an existing generator capability curve to a generator:
- Locate the Reactive Power Limit section in the load flow page of the static generator dialog.
- Press next to Capability Curve.
- Choose Select to look for a suitable curve in the Mvar Limit Curves folder in the Operational
library folder.
1.2.6 Active Power Limits
There are two ways to set a limit for the active power. If one of the two limits is exceeded during a load flow
calculation a warning massage will be dispayed in the output window.
The Active Power: Operational Limits are the minimum and maximum MW output limits of the generator from
an operational perspective. They have a higher prirority than the Active Power Rating limits.
The Active Power: Ratings is the maximum active power output of the generator and it is established by
multiplying the generator nameplate MVA rating by the power factor and the rating factor.
1.3 Short-Circuit Calculations
1.3.1 VDEC/IEC Short Circuit
There are three different possibilities to consider a static generator in the VDE/IEC short circuit calculation:
- No Short-Circuit Contribution (according to the standard)
- Static Converter-Fed Drive
- Individual Max. Fault Contribution
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 1 1 -


Figure 10: VDE/IEC Short Circuit Page
1.3.1.1 No Short-Circuit Contribution
In the VDEC/IEC short circuit calculations, the static generators are normally disregarded, according to the
standard (Option: No Short-Circuit Contribution).
1.3.1.2 Static Converter-Fed Drive
With the option Static Converter-Fed Drive activated the Static Gernator behaves during the VDE/IEC short
circuit calculation like a static converter-fed drive according to the IEC 60909 (VDE 0102). The static converter-
fed drives are considered for three-phase short circuits only. They only contribute to the initial symmetrical short-
circuit current I
k
and to the peak short-circuit current i
p
. They do not contribute to the symmetrical short-circuit
breaking current I
b
and to the steady-state short-circuit current I
k
. As a result, static converter-fed drives are
treated for the calculation of short-circuit currents in a similar way as asynchronous motors. The equivalent model
is shown in Figure 11.
The impedance is calculated as follow:
rM
rM
rM LR
rM
rM
rM LR
M
S
U
I I
I
U
I I
Z
2
1
3
/
1
= =
with:
3 / =
rM LR
I I
1 . 0 / =
M M
X R with
M M
Z X 995 . 0 =
where:
- U
rM
is the rated voltage
- I
rm
is the rated current
- S
rM
is the rated apparent power
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 1 2 -

The Index rM specifies the rating of the static converter transformer on the network side, or the rating of the
static converter if no transformer is present.
2
) / ( 1
1
M M
M
X R
Z
X

=
1 / 1 X X R R
M M
=

Figure 11: Equivalent Generator Model, for Static Converter-Fed Drive Option
1.3.1.3 Individual Max. Fault Contribution
If neither No Short Circuit Contribution nor Static Converter-Fed Drive is enabled then the user can input the
Maximum Short Circuit Contribution. It is calculated according to a equivalent generator model.

Figure 12: Equivalent Generator Model, Positive sequence circuit diagram
The impedance is calculated as follow:
( )
2
max
1
1
X R S
c
x
k
' ' +

=
1 1 x X R r ' ' =
c
max
is the voltage factor c.
i1 R1 X1
~
c*U
n
/3
i1 r1 x1
F
~
c*Un/3
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 1 3 -

Note that c
max
in the calculation of x1 is needed because the current is calculated with x1 and c
max
*u. The factor
c
max
will cancel down. So that finally the subtransient short circuit apparent power is equal to the entered value.
The model is considered for the symmetrical short-circuit breaking current I
b
like an external grid:
Ik Ik Ib = =
' '

For the steady-state short-circuit current I
k
is the same value as for Ik used. This is the same approach as for
the asynchronous machine.
The Inputparameters are:
- I
k
or S
k

- X/R or R/X
For minimum short-circuits is the model completely neglected and has no short-circuit contribution.
MODEL FOR UNBALANCED FAULTS
For unbalanced faults uses the static generator the zero and negative sequence model that is already described in
section 1.1.1 Zero/Negative Sequence Model.
For minimum short-circuits is the model completely neglected and has no short-circuit contribution.
1.3.2 Complete Short Circuit
With the Complete Mehod is it possible to define a user-specific level for the subtransient and the transient short
circuit. Either as short circuit power or as short circuit current, and the R/X ratio (alternatively the X/R ratio).
The static generator model for the short-circuit calculation using the complete method is adapted as follows:

Figure 13: Model for Complete Short Circuit Calculation
The short-circuit impedance is calculated as follow for the transient and sub-transient
u1
i1 r1 x1
u
int

Y
ldf

G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 1 4 -

( )
2
1
1
X R S
c
x
k
' ' +
= for S
k
= S
k


or S
k
respectively
X R x r ' ' = 1 1
The c factor and the Y
ldf
admittance are only used for the complete method with load flow initialization. So the c
factor reflects the actual voltage at the static generator from load flow in per unit.
ldf
u c = and
ldf
u u =
int

ldf
ldf
ldf
u
i
Y =
For a short-circuit at the terminal of the generator the short-circuit current is equal to the entered value of the I
k

and I
k
. For short-circuit far away the short-circuit current is nearly equal to the load flow current.
MODEL FOR UNBALANCED FAULTS
For unbalanced faults uses the static generator the zero and negative sequence model that is already described in
section 1.1.1 Zero/Negative Sequence Model.
For minimum short-circuits is the model completely neglected and has no short-circuit contribution.
1.3.2.1 Complete without load flow initialization
If the Complete Short-Circuit method is used without the option Load Flow Initialisation on the Advanced
Options page of the short-circuit calculation command the following model is used.

Figure 14: Positive sequence circuit diagram for sub-transient faults
The positive sequence transient impedance is calculated as follow:
u1
i1 r1 x1
uo
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 1 5 -

( )
2
1
"
" 1
X R S
c
x
k
' ' +

=
X R x r ' ' = " 1 " 1
" " c uo =
c is the c-factor (voltage factor)
If the transient short-circuit level (I
k
, S
k
) is zero, the model is represented only through the subtransient
impedance. The transient impedance and the internal voltage source uo are ignored.

Figure 15: Positive sequence circuit diagram for transient faults
The positive sequence transient impedance is calculated as follow:
( )
2
1
'
' 1
X R S
c
x
k
' ' +
'
=
X R x r ' ' = ' 1 ' 1
c is the c-factor (voltage factor)
MODEL FOR UNBALANCED FAULTS
For unbalanced faults uses the static generator the zero and negative sequence model that is already described in
section 1.1.1 Zero/Negative Sequence Model.
For minimum short-circuits is the model completely neglected and has no short-circuit contribution.
u1
i1 r1 x1
uo
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 1 6 -

1.3.3 ANSI Short Circuit
There are two possibilities to use the static generator in an ANSI short circuit calculation:
- No Short-Circuit Contribution (according to the standard)
- Individual Fault Contribution
If No Short-Circuit Cinstribution is activated the static generator will be neglected in the calculation.
If the option No Short-Circuit Contribution is not enabled the Maximum Short Circuit Contribution could be
entered.

Figure 16: Positive sequence circuit diagram
The impedance is calculated as follow:
( )
2
1
1
X R S
u
x
k
prefault
' ' +

=
1 1 x X R r ' ' =
u
prefault
is the prefault voltage in p.u.
The static generator is considered as follows for the corresponding short-circuit currents:
- Momentary Current (First-cycle)
r1, x1 is used (as defined in the equations above)
- Interrupting Current
like for the first-cycle study and always considered as remote contribution
- 30-cycle short-circuit
No short-circuit contribution, the model is neglected (disconnected)
i1 r1 x1
F
~
u
prefault

G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 1 7 -

1.3.4 IEC 61361
The IEC 61361 short circuit for the static generator is calculated according to the specification. The specification
could be found in the chapter for IEC 61361 in the handbook.
1.4 Harmonics
The static generator behaves like a current source during harmonic analysis. The used equivalent model is
therefore a current source.
The harmonics tab allows to specify or select the harmonic sources object. The spectrum of harmonic infeeds
may be entered according to one of two options: balanced or unbalanced.

Figure 17: Harmonics Balanced - Unbalanced
Also, the harmonic current can refer to either the Fundamental Current or to the Rated Current.
If Rated Current is selected (Figure 18) then the phase angle is used from the initial bus voltage angle obtained
from load flow.

Figure 18: Harmonic current referred to
More information about the definition of harmonic current sources could be found in the corresponding chapter of
the handbook.
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 1 8 -

1.5 RMS Simulation
The static generator supports two different models:
- current source model
- voltage source model
Depending on which input signals are connect the current or the voltage source model is used. If both signal
combinations are connected the voltage source model is used. If no input signal is connected the static generator
behaves like a constant current source. The current values from the load flow are used.

Figure 19: Model Input (RMS)
The user can specify in both models a Minimum Operation Voltage threshold. For unbalanced simulation the
zero/negative sequence is calculated as described in chapter 1.1.1.
1.5.1 Current Source Model
Input Signals:
id_ref: d-Axis Current Reference in p.u.
iq_ref: q-Axis Current Reference in p.u.
cosref: Cos(dq-Reference-Angle)
sinref: Sin(dq-Reference-Angle)
The cosref, sinref signal can be connected from a PLL model.
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 1 9 -


Figure 20: Current Source Model
The following equations are used:
( ) ( ) u i u i j u i u i i
ref q ref d ref q ref d
cos sin sin cos 1
_ _ _ _
+ + =
If the input signals cosref and sinref are connected:
ref u cos cos = and ref u sin sin =
If the input signals are not connected the sinu and cosu quantities are internally calculated by using the terminal
positive sequence voltage u1:
| 1 |
) 1 Re(
cos
u
u
u = and
| 1 |
) 1 Im(
sin
u
u
u =
If the voltage under-runs the Min. Operating Voltage:
0 1= i
The machine is switched on again, if the voltage is 5% higher as the Min. Operating Voltage.
1.5.2 Voltage Source Model
Input Signals:
- u1r_in : Voltage Input, pos. Sequence Real Part in p.u.
- u1i_in : Voltage Input, pos. Sequence Imaginary Part in p.u.
Input Parameter:
- uk : Series Reactor, Short Circuit Impedance in %
i1
id_ref
iq_ref
u1
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 2 0 -

- Pcu : Series Reactor, Copper Losses in kW
The voltage source model is used if the two input signals u1r_in and u1i_in are connected otherwise the
current source model is used.

Figure 21: Voltage Source Model
The following equations are used:
1 1 _ 1 _ 1 i z u in i u j in r u + = +
with: X j R z + =
The quantities R and X are calculated from the input parameter uk and Pcu.
If the voltage under-runs the Min. Operating Voltage:
0 1= i
The machine is switched on again, if the voltage is 5% higher as the Min. Operating Voltage.
1.5.3 Negative/Zero Sequence Model
See chapter 1.1.1. Zero/Negative Sequence Model of the load flow calculation.
1.6 EMT Simulation
Fot the EMT Simulation are also two models available like in the RMS simulation.
u1r_in
u1i_in
u1
i1
~
U
R X
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 2 1 -

1.6.1 Current Source Model
The current source model is implemented as a voltage source with a controlled current. The current is controlled
with a build in current controller:

Figure 22: Build in Current Controller (Parameter)
The current controller is defined as follows:
|
|
.
|

\
|
+
s T
K
d
d
1
1
|
|
.
|

\
|
+
s T
K
q
q
1
1
du
i
qu
i
ref d
i
_
ref q
i
_
d
i
q
i
|
|
.
|

\
|
+
s T
K
d
d
1
1
|
|
.
|

\
|
+
s T
K
q
q
1
1
du
i
qu
i
ref d
i
_
ref q
i
_
d
i
q
i

Figure 23: Build in Current Controller
The voltage of the internal voltage source is calculated in the d-q-frame as follows:
q shc nom du
i l f i d u = t 2 1

d shc nom qu
i l f i q u + = t 2 1

with:
- l
shc
is the short circuit inductance in p.u.
The voltage is transformed back to the system coordinates and applied to the voltage source:
q u u d u u r u 1 sin 1 cos 1 =
q u u d u u i u 1 cos 1 sin 1 + =
G e n e r a l D e s c r i p t i o n

S t a t i c G e n e r a t o r - 2 2 -


Figure 24: Model used for EMT-current source
1.6.2 Voltage Source Model
The voltage source model of the EMT Simulation is equal to the model of the RMS Simulation (1.5.2 Voltage
Source Model).
1.6.3 Zero Sequence
See chapter 1.1.1. Zero/Negative Sequence Model of the load flow calculation.
u1r
u1i
u
Id
iq
~
U
2tf l
shc

I n p u t / O u t p u t D e f i n i t i o n o f D y n a m i c M o d e l s

S t a t i c G e n e r a t o r - 2 3 -

2 Input/Output Definition of Dynamic Models
2.1 Stability Model (RMS)
2.1.1 Current Source Model

Figure 25: Input/Output Definition of the HVDC converter model for stability analysis (RMS-
simulation)
Table 1: Input Definition of the RMS-Model
Parameter Description Unit
id_ref d-Axis Current Reference p.u.
iq_ref q-Axis Current Reference p.u.
cosref Cos(dq-Reference-Angle)
sinref Sin(dq-Reference-Angle)

Table 2: Output Definition of the RMS-Model
Parameter Description Unit
xspeed Frequency p.u.
id Current, d-Axis p.u.
iq Current, q-Axis p.u.

id_ref
iq_ref
cosref
xspeed
iq
sinref
id
I n p u t / O u t p u t D e f i n i t i o n o f D y n a m i c M o d e l s

S t a t i c G e n e r a t o r - 2 4 -

2.1.2 Voltage Source Model

Table 3: Input Definition of the RMS-Model
Parameter Description Unit
u1r_in Voltage Input, Real Part p.u.
u1i_in Voltage Input, Imaginary Part p.u.

Table 4: Output Definition of the RMS-Model
Parameter Description Unit
xspeed Frequency p.u.
id Current, d-Axis p.u.
iq Current, q-Axis p.u.

u1r_in
u1i_in
xspeed
iq
id
I n p u t / O u t p u t D e f i n i t i o n o f D y n a m i c M o d e l s

S t a t i c G e n e r a t o r - 2 5 -

2.2 EMT-Model
2.2.1 Current Source Model

Figure 26: Input/Output Definition of the HVDC converter model for stability analysis (EMT-
simulation)
Table 5: Input Definition of the EMT-Model
Parameter Description Unit
id_ref d-Axis Current Reference p.u.
iq_ref q-Axis Current Reference p.u.
cosref Cos(dq-Reference-Angle)
sinref Sin(dq-Reference-Angle)

Table 6: Output Definition of the EMT-Model
Parameter Description Unit
xspeed Frequency p.u.
id Current, d-Axis p.u.
iq Current, q-Axis p.u.

id_ref
iq_ref
cosref
xspeed
iq
sinref
id
I n p u t / O u t p u t D e f i n i t i o n o f D y n a m i c M o d e l s

S t a t i c G e n e r a t o r - 2 6 -

2.2.2 Voltage Source Model

Table 7: Input Definition of the EMT-Model
Parameter Description Unit
u1r_in Voltage Input, Real Part p.u.
u1i_in Voltage Input, Imaginary Part p.u.

Table 8: Output Definition of the EMT-Model
Parameter Description Unit
xspeed Frequency p.u.
id Current, d-Axis p.u.
iq Current, q-Axis p.u.

u1r_in
xspeed
iq
id
u1i_in
I n p u t P a r a m e t e r D e f i n i t i o n s

S t a t i c G e n e r a t o r - 2 7 -

3 Input Parameter Definitions
3.1 *.ElmGenstat
Table 9: Input Parameter Definitions of the Static Generator Element
Parameter Description Unit
loc_name Name
bus1 Terminal (StaCubic)
bus1_bar Terminal
cpZone Zone
cpArea Area
outserv Out of Service
aCategory Category
ngnum Number of Parallel Machines
sgn Rated Apparent Power MVA
cosn Rated Power Factor
bustp Corresponding Bus Type
iv_mode Local Voltage Controller
c_pstac External Station Controller
mode_inp Dispatch: Input Mode
pgini Dispatch: Active Power MW
qgini Dispatch: Reactive Power Mvar
sgini Dispatch: Apparent Power MVA
cosgini Dispatch: Power Factor
pf_recap Dispatch: Power Factor
usetp Dispatch: Voltage p.u.
ddroop Dispatch: Droop %
Kpf Dispatch: Primary Frequency Bias MW/Hz
pQlimType Reactive Power Limits: Capability Curve
q_min Reactive Power Limits: Min. p.u.
q_max Reactive Power Limits: Max. p.u.
cQ_min Reactive Power Limits: Min. Mvar
cQ_max Reactive Power Limits: Max. Mvar
scaleQmin Reactive Power Limits: Scaling Factor (min.). %
scaleQmax Reactive Power Limits: Scaling Factor (max.). %
Pmin_uc Active Power: Operational Limits: Min. MW
Pmax_uc Active Power: Operational Limits: Max. MW
Pnom Active Power: Operational Limits: Pn. MW
P_max Active Power: Ratings: Max. MW
pmaxratf Active Power: Ratings: Rating Factor.
c_pCtrlHV Controlled HV-busbar
Uctrl HV-Voltage Setpoint kV
I n p u t P a r a m e t e r D e f i n i t i o n s

S t a t i c G e n e r a t o r - 2 8 -

Qmin_a Qmin (act.) Mvar
Qmax_a Qmax (act.) Mvar
Pmin_a Pmin (act.) MW
Pmax_a Pmax (act.) MW
iconfed Static Converter-fed Drive
Skss Fault Contribution: Subtransient Short-Circuit Level MVA
Sks Fault Contribution: Transient Short-Circuit Level MVA
Ikss Fault Contribution: Subtransient Short-Circuit Level kA
Iks Fault Contribution: Transient Short-Circuit Level kA
rtox Fault Contribution: R to X Ratio
xtor Fault Contribution: X to R Ratio
iearthed Earthed
r0 Earthed: Zero-sequence Resistance p.u.
x0 Earthed: Zero-sequence Reactance p.u.
iAstabint A-stable Integration Algorithm
umin Min. Operation Voltage p.u.
uk Short Circuit Impedance %
Kd Current Controller: Kd: d-Axis, Proportional Gain
Td Current Controller: Td: d-Axis, Integration Time Constant s
Kq Current Controller: Kq: q-Axis, Proportional Gain
Tq Current Controller: Tq: q-Axis, Integration Time Constant s
phmc Harmonic Injections
icurref Harmonic Current Referred to
ictqg Optimal Power Flow Controls: Reactive Power
iOPFCQmin Optimal Power Flow Reactive Power Limits: Min
iOPFCQmax Optimal Power Flow Reactive Power Limits: Max
pBMU Commitment Automatic Dispatch: Virtual Power Plant
iestp State Estimation: Estimate Active Power
iestq State Estimation: Estimate Reactive Power
pStoch Stochastic Model

Você também pode gostar