Você está na página 1de 17

Gas-insulated medium voltage switchgear ZX

ABB 12.01.2012 ZX Family | 1

ZX Product range

Single busbar

Single busbar

Single busbar

Single busbar

Double busbar

up to 25 kA 1250 A
Voltage BIL level

up to 31.5 kA 2500 A

up to 31.5 kA 2500 A

up to 40 kA 2500 A

up to 40 kA 2500 A

12 kV

75 kV

24 kV 125 kV 36 kV 170 kV 40 kV 185 kV


ABB 12.01.2012 ZX Family | 2

ZX0

ZX0.2

ZX1.2

ZX2

ZX2

Gas-insulated medium voltage switchgear Type ZX0


Compact medium voltage switchgear type ZX0 12 kV, 1250 A, 25 kA 24 kV, 1250 A, 25 kA

ABB 12.01.2012 ZX Family | 3

Gas-insulated medium voltage switchgear Type ZX0


With IAC classification AFL 25 kA 1s AFLR 25 kA 1s

Rated voltage Rated current of busbars Rated current of tee-offs with circuit-breaker With switchdisconnector Rated short-circuit breaking current Width a Heigth b Depth c wall installation free standing

kV A

12 1250

24 1250

A A kA mm mm mm

1250 630 25 400 / 600 1)

1250 630 25

2100 or 2250 950 / 1100 1) 1185

1)

For Feeder currents > 800 A; with voltage metering

c a

ABB 12.01.2012 ZX Family | 4

Gas-insulated medium voltage switchgear Circuit-breaker panel 630 A


1 2 1 3 4 5 11 2 10 9 3 4 5 6 7 6 7 8 9 10 8 11 Multifunctional control and protection unit Measuring sockets for capacitive voltage indicator system Three position disconnector mechanism Circuit-breaker mechanism Cable plug Ring-type current transformer Pressure relief plate External cone Vacuum circuit-breaker Three-position disconnector Busbars

SF6

ABB 12.01.2012 ZX Family | 5

Gas-insulated medium voltage switchgear Type ZX0.2


Medium voltage switchgear type ZX0.2 Single busbar version 12 kV, 2500 A, 31.5 kA 24 kV, 2500 A, 31.5 kA 36 kV, 2500 A, 31.5 kA

ABB 12.01.2012 ZX Family | 6

Gas-insulated switchgear Type ZX0.2


With IAC classification AFL 31.5 kA 1s AFLR 31.5 kA 1s

Rated voltage Rated current of busbars Rated current of tee-offs with circuit-breaker
b

kV A

12

24

36

2500 2500 2500

A A kA mm mm mm

2500 2500 2500 80 31,5 63 31,5 31,5

with switch-disconnector/ fuse combination Rated short-circuit breaking current Width a Height b Depth c

600 / 1200 1) 2400 1330

1)

Dependent on current

c a

ABB 12.01.2012 ZX Family | 7

Gas-insulated switchgear Feeder ZX0.2


Circuit-breaker panel, 1250 A
13 12 1 1 2 3 4 5 6 7 8 9 10 11 12 13 Removable low voltage compartment Three position disconnector operating mechanism Mechanism bay with operator controls Circuit-breaker operating mechanism Cable connector Window-type current transformer Bushing with outer cone Isolatable voltage transformer on the cable Pressure relief disk Vacuum circuit-breaker Three position disconnector Busbars Plug-in busbar voltage transformers SF6

11

2 3

10

9 8

5 6 7

ABB 12.01.2012 ZX Family | 8

Gas-insulated medium voltage switchgear Type ZX1.2


Medium voltage switchgear type ZX1.2 Single busbar version 12 kV, 2500 A, 31.5 kA 24 kV, 2500 A, 31.5 kA 36 kV, 2500 A, 31.5 kA

ABB 12.01.2012 ZX Family | 9

Gas-insulated medium voltage switchgear Type ZX1.2


With IAC classification AFLR 31.5 kA 1s

Rated voltage Rated current of busbars Rated current of tee-offs Rated short-circuit breaking current Rated short-circuit making current
b

kV A A kA kA

12

24

36 1) 2500 2500 31.5 80 SF6 2) 600 / 800 4)

2500 2500 2500 2500 31.5 80 SF6 2) 31.5 80 SF6 2)

Insulation gas Width a Heigth b Depth c Heigth of cable fixing point


1) 2)

mm mm mm mm

600 / 800 3) 4) 2100

1300-1800 5) 1250

c a

3) 4) 5)

Higher values as per international standards on request Sulphur hexafluoride Double feeder panel up to 25 kA, 2 x 630 A Rated feeder current > 1250 A Depending on quantity of cables per phase

ABB 12.01.2012 ZX Family | 10

Gas-insulated medium voltage switchgear Feeder 1250 A


1 2 3 4 5 6 7 8 9 10 11 12 13 14 Density sensor Circuit-breaker operating mechanism Multifunctional protection and switchgear control unit Three position disconnector operating mechanism Three position disconnector Busbar Pressure relief disk Pressure relief duct (optional) Ring type current transformer Cable plug Cable socket Measuring sockets for capacitive voltage indicator system Test socket Circuit-breaker

SF6

ABB 12.01.2012 ZX Family | 11

Gas-insulated medium voltage switchgear Plug-in components

Dummy plug

Voltage transformer

Test plug Cable plug

Surge arrestor BB plug-in system

ABB 12.01.2012 ZX Family | 12

Gas-insulated medium voltage switchgear Type ZX2


Medium voltage switchgear type ZX2 12 kV, 2500 A, 40 kA 24 kV, 2500 A, 40 kA 36 kV, 2500 A, 40 kA

ABB 12.01.2012 ZX Family | 13

Gas-insulated medium voltage switchgear Type ZX2


With IAC classification AFLR 40 kA 1s

Rated voltage Rated current of busbars Rated current of tee-offs Rated short-circuit breaking current
b

kV A A

12

24

36 1) 2500 2500

2500 2500 2500 2500

kA

40 SF6 3)

40 2) SF6 3)

40 2) SF6 3) 600 / 800 4)

Insulating gas Width a Heigth b Depth c


1) 2)

mm mm mm

600 / 800 4) 5) 2300 1760

c a

3) 4) 5)

Higher values as per international standards on request 600 mm panel width up to 31.5 kA rated short-circuit breaking current Insulating gas: sulphuir hexafluoride (SF6) Rated feeder current above 1250 A Double feeder panel up to 25 kA, 2 x 630 A

ABB 12.01.2012 ZX Family | 14

Gas-insulated medium voltage switchgear Double busbar panel for 1250 A


12 11 15 1 2 3 4

1 2 3 4 5 6 7
5 6 7

HMI of multifunctional protection and control unit Three position disconnector operating mechanism Three position disconnector Pressure sensor (temperature-compensated) Circuit-breaker operating mechanism Cable socket Cable plug Electronic unit of multifunctional protection and control unit Dummy plug Combined current sensor with socket Pressure relief disk Pressure relief duct Circuit-breaker Measuring sockets for capacitive voltage indicator system Busbars

14 13 12 11 10

8 9 10

11 12 13 14 15

SF6
ABB 12.01.2012 ZX Family | 15

Gas-insulated medium voltage switchgear Plug-in components

Test plug

BB plug-in system

Cable plug Voltage transformer Dummy plug Surge arrestor

ABB 12.01.2012 ZX Family | 16

Você também pode gostar