International Journal of Mechanical and Production Engineering Research and Development (IJMPERD) ISSN 2249-8001 Vol.

2 Issue 4 Dec - 2012 31-42 TJPRC Pvt. Ltd.,

OPTIMIZATION OF SUSTAINABLE SOLAR-WIND HYBRID SYSTEM FOR DOMESTIC ELECTRIFICATION


1 1 2

KARAN SOOD, 2PROF PRAVEEN SINGH & 3PRASHANT BAREDAR

Assistant Professor, Patel Institute of Technology, Ratibad, Bhopal-462044, India

Associate Professor, B.U. University Institute of Technology, Hoshangabad Road, Bhopal, India
3

Associate Professor, Maulana Azad National Institute of Technology, Bhopal, India

ABSTRACT
Solarwind hybrid energy systems allow improving the system efficiency, power reliability and reduce the energy storage requirements for stand-alone applications. Good compensation characters are usually found between solar energy and wind energy. These hybrid systems are now becoming popular in urban area for power generation applications due to advancements in renewable energy technologies and substantial rise in prices of petroleum products. This paper recommend an optimal design model for hybrid solarwind systems employing battery bank for calculating the system optimum configurations and ensuring that the annualized cost of the systems is minimized while satisfying the custom requirements. The main decision variables included in this analysis are A.C. Primary Load Calculation, Global Solar Resources, Wind Resources, Output of solar and Wind energy systems, Excess Electricity and State of battery charge. First, we analyse above variables and finally we conclude the optimum design of the hybrid system along with its cost estimation with expected life of battery bank. The optimization results of the hybrid system has good complementary characteristics between the solar and wind energy and this system is expecting to perform very well throughout the year with generally no battery over-discharge condition. The study presented here is also an attempt to promote the domestic use of Solar-wind energy in this region of Bhopal, India (Longitude 77.35and Latitude 23.28).

KEYWORDS: Solar-wind hybrid system, Wind turbine, Solar-PV, Homer, Optimization INTRODUCTION
The main benefit of solar-wind hybrid system is that when solar and wind powers are used together, the reliability of the system is enhanced. Additionally, the size of battery storage can be reduced as there is less dependence on only one source of power generation. Often, when there is no sun, there is plenty of wind in India (as in Monsoon season). Winds are usually relatively strong in winter and solar radiations have higher intensity in summer. Muralikrishna & Lakshminarayana (2008) have shown; for the same level of deficiency of power supply probability, the Solar-wind hybrid energy system gives the lowest unit cost values as compared to standalone solar and wind energy systems. Ding & Buckeridge (2000) presented a balanced system for getting stable output from available resources of renewable energy, which minimized the dependency of the output upon the weather changes; moreover, it optimised the exploitation of the renewable energy resources. Shaahid and Elhadidy (2007) used the Homer tool for minimizing of the NPC of a SolarDieselBattery system to deliver the uninterrupted electricity to a shopping complex situated in Dhahran (Saudi Arabia). Dalton et al. (2008) have also done the optimization for minimizing NPC by using Homer tool in a Solar WindDieselBattery system in Australia. Muljadi & Butterfied (2001) and Ched et al. (1998) represented the useful techniques, which were helpful for optimum sizing of solar-wind hybrid systems.

32

Karan Sood, Praveen Singh & Prashant Baredar

PROBLEM FORMULATION
Muselli M et al. (1999) and Bagan & Billinton R. (2005) have shown in their study that the hybrid systems are more consistent for uninterrupted power supply and less costly than the systems which are depend on single renewable energy resource. But hybrid systems have higher failure rate due to improper optimization, components failure, poor maintenance and inadequate support by suppliers after installation of the system. Although it has observed that generally component failure occurs because of improper optimization of the system. The Homer tool from NREL (www.nrel.gov/homer/) is the one of the best platform for optimizing of Solar-Wind hybrid system. The main motive of this paper is to reduce such failures of the hybrid systems by implementing proper optimization techniques.

SYSTEM DESIGN AND ITS OBJECTIVES


Yang et al. (2007, 2009) give the optimization approach for hybrid SolarWindBattery systems which is able to reduce the LCE. Koutroulis et al. (2006) present a paper for economic optimization

by means of Genetic Algorithms on PVWindBattery systems. The main objective for designing a Solar-wind-battery system is the optimum mixing of wind system and solar PV system to fulfil the load requirement of the consumer, at a minimum cost of installation and maintenance. In order to accomplish this, the hybrid system has been designed based on the following steps: (i) Power requirement, (ii) Availability of Solar and Wind Resources, (iii) Configure the inputs for generating sustainable conditions (iv) Simulations of the sustainable Hybrid Systems, (v) Chosen of the optimum system for fulfilling the consumer requirement.

POWER REQUIREMENT
Calculation of power requirement is essential for designing an sustainable hybrid system. AC Primary load is electrical load that must be met immediately in order to avoid unmet load. To synthesize the electric data in Homer tool, we must enter at least one load profile, which is the set of 24 hourly values of electric load, one for each hour of the day. We can enter different load profiles for different months and for weekdays and weekends too.

Figure 1: AC Primary Load By entering the whole year data in the Homer tool, we got the AC Primary load calculation graph for the whole year (Figure 1). In this load calculation we considered two variables: Day-to-day variable and time-step-to-time-step

Optimization of Sustainable Solar-Wind Hybrid System for Domestic Electrification

33

variable, where both variables are 15% and 20% respectively. Finally, we conclude that the scaled annual average and average load are 3.25 kWh/d and 135W respectively, with the peak load of 1.55kW. Thus we should design a Solar-wind hybrid system which can hold the 3.25kWh daily with the 135W average load and the peak load of 1.6kW.

AVAILABILITY OF SOLAR AND WIND RESOURCES


Solar Resource Hourly solar radiation data with clearness index for the year 2011 collected from official website of NREL [www.nrel.gov/homer/]. This online data for the particular year can gather by providing appropriate time zone, latitude and longitude. The time zone for India is GMT +05:30 and latitude and longitude for the proposed site in Bhopal is 23o28 and 77o35 respectively. The proposed site for installation of domestic hybrid system is Gandhi Nagar, Bhopal.

Figure 2: Average Daily Solar Radiation and Clearness Index In Figure 2, we can see that in summer season solar radiations are higher than winter and in rainy season clearness index and availability of solar radiations are lower than summer and winter season. From the above analysis of Solar resource, we conclude that scaled annual average of solar radiation is 5.18kWh/m2/d. Wind Resource

Figure 3: Wind Resource for Throughout the Year of 2011 Wind mast is used to measure the wind speed at a prospective wind turbine site. For this purpose anemometer is fitted to the top of a mast, which is placed at same height as a expected hub height of the wind turbine to be used. The two basic parameters: one is altitude from mean see level i.e. 530m and the height of anemometer i.e. 16m and the four advanced parameters: Weibull k, Autocorrelation factor, Diurnal pattern strength and Hour of peak wind speed are 2, 0.85, 0.25 and 15 respectively (Figure 3). All the data and parameters for optimization of wind resource were collected from weather monitoring station, UIT-RGPV, Gandhi Nagar, Bhopal.

34

Karan Sood, Praveen Singh & Prashant Baredar

CONFIGURE THE INPUTS FOR GENERATING SUSTAINABLE CONDITIONS


PV Inputs

Figure 4: PV Inputs Borowy & Salameh (1995) represent a methodology to optimize the size of the solar array and the capacity of the battery bank in Solarwindbattery system. The two main factors were considered when selecting of PV array for the sustainable hybrid system, are 1. The cost of the solar energy system is higher than the wind energy system for the same rated capacity (Wp). 2. There is plenty of wind in this region of city for the small domestic wind energy system. Thus, we have to choose the small Solar PV system for this site. We added the small sizes (i.e. 0kWp to 0.500kWp) of PV array in the Homer tool, which we want to consider for the optimum system. Now Homer will use the information which we entered in the cost table to calculate the costs of each PV array size, interpolating and extrapolating as necessary. Capital and replacement costs include the cost of PV panels, mounting hardware, tracking system, control system, wiring and installation. The cost analysis of the PV system in Figure 4. Wind Turbine Inputs The two main factors were considered when selecting a wind turbine for the sustainable hybrid system: 1. The rated capacity (Wp) of wind turbine should be larger because of expansive Solar PV system. 2. With the help of power curve and availability of wind resources, we have to select appropriate wind turbine for the small domestic wind electric system.

Figure 5: Wind Turbine Inputs First, we should select the appropriate size of turbine with the consideration of nature of wind and power curve of implemented turbine. If power curve (Figure 5) fulfils the load requirement then we have to move towards the effect of

Optimization of Sustainable Solar-Wind Hybrid System for Domestic Electrification

35

cost of turbine. Power curve represents the turbine's power output over a range of wind speeds. We used this curve to verify that the wind turbine which we have selected for the site is appropriate one or not. The turbine which is suitable for this site is 1.3kWp Whisper Turbine. Capital cost of this turbine including all mounting and transmission accessories in $1964 with O&M cost 30$/yr. The cost analysis for the Wind Turbine is shown in Figure 5. Battery Inputs Karaki et al. (1999) represented algorithms series for battery bank of solar wind hybrid system. These series show the economic value of battery bank with respect to battery capacity and charging/discharging cycle time. The role of battery is very important in off grid system because this is the only backup for the system. In case of day of autonomy, the system will fully depend on the battery bank. Protogeropoulos et al. (1998) performed the optimization of the system; adjust the size of the battery bank until an ultimate conguration occur that certified the enough autonomy. Kellogg et al. (1998) show an iterative optimization method for SolarwindBattery hybrid system. A 200AH, 12V Tubular battery of GTech India, is very effective and economic nowadays in the country. This battery is labelled with 2 year replacement warranty. It has been observed that if this battery is used under good maintenance and proper state of charge condition, the battery life may extend up to 5 to 9 years. The cost specified battery is $152 with the replacement cost of $40 and O&M cost of 1$/yr. (Figure 6).

Figure 6: Battery Inputs Inverter Inputs The inverter is an electronic device which converts the DC electricity that comes from the hybrid system into AC electricity, which matches the AC frequency of the power lines. The Cost analysis for the inverter is shown in Figure 7, where lifetime of a unit is 15 years with an efficiency of 90%. The capital cost of inverter is 100$ with replacement cost of 55$ and O&M of 1$/yr.

Figure 7: Inverter Inputs

36

Karan Sood, Praveen Singh & Prashant Baredar

RESULTS & DISCUSSIONS


Simulations of the Sustainable Hybrid Systems Homer simulates the operation of a system by making energy balance calculations for each of the 8,760 hours in a year. For each hour, Homer compares the electric demand in the hour to the energy that the system can supply in that hour, and calculates the flows of energy to and from each component of the system. All the resources and inputs simulated and we got the 360 sustainable configurations. This simulation results eliminate all infeasible combinations and rank the feasible systems according to increasing net present cost. There are 360 feasible designs for our site under desirable conditions.

Figure 8: Simulation Calculation Window Optimization of the Appropriate Hybrid System

Figure 9: Optimum Solar Wind Hybrid After simulating all the possible system configurations, we should select at least one optimum hybrid system, sorted by net present cost, battery life and payback period. A 1.6kW Solar wind hybrid system is the optimum system for this site because this system has lower net present cost, higher battery life with less payback period. System Architecture System Architecture which will bear 3.2kWh/day and 1.6kWp (Figure 9): (i) 1 Solar PV Array, 0.3kWp (iii) 5 G-Tech Tubular Batteries, each 200AH, 12V (ii) 1Whisper 200b Wind Turbine, 1.3kWp (iv) Inverter for 1.6kW peak load

Optimization of Sustainable Solar-Wind Hybrid System for Domestic Electrification

37

Annualized Cost Summary It is clearly marked in Figure 10 that PV module of 0.3kWp has the capital cost of $562 with $1/yr O&M. The total annual cost of PV module in first year is $563. Similarly we can observe the investment cost for wind turbine, batteries and converter. Thus total capital cost is $3386 and Total NPC is $3424 for the whole system.

Figure 10: Cost Flow Summary Electrical Output of the Whole System As we can see in the Figure 11, the optimum mixing for solar (PV array) and wind energy (Wind turbine) is 14% and 86% respectively, where PV array will generate 654kWh/yr and Wind turbine will generate 3918kWh/yr. The total power produced by both the systems is 4573 kWh/yr. On the other hand total AC primary load is 1186kWh/yr i.e. 3.25kWh/day with very few unmet load. In this way excess electricity is 3134kWh/yr. This excess electricity can supply to grid. Renewable fraction value is 1.00, which is the maximum fraction value for any renewable energy source.

Figure 11: Electrical Output

38

Karan Sood, Praveen Singh & Prashant Baredar

Solar Output of 0.3kwp Solar Array

Figure 12: Solar Output A 0.3kWp rated capacity solar array is used in the system. As we can clearly see in Figure 12, there is generally no power generation in between 06:00 PM to 06:00 AM and there is plenty of power generation in day time. Power generation by the PV array is less in monsoon season, which will compensated by the wind turbine (in Figure 13). This PV array works effectively from October to May. Some important solar outputs are: Quantity Rated capacity Mean output Mean output Capacity factor Total production Value 0.300 0.07 1.79 24.9 654 Units kW kW kWh/d % kWh/yr Quantity Minimum output Maximum output PV penetration Hours of operation Levelized cost Value 0.00 0.32 55.2 4,373 0.860 Units kW kW % hr/yr $/kWh

Wind Output of 1.3kwp wind Turbine

Figure 13: Wind Output Rated capacity of wind turbine is 1.3kWp. As we can see in the Figure 13, there is plenty of power output by wind resource in between April to September. This is the time when the seasonal changes take place in the country due to the monsoon.

Optimization of Sustainable Solar-Wind Hybrid System for Domestic Electrification

39

Some important wind outputs are: Quantity Total rated capacity Mean output Capacity factor Total production Value 1.30 0.45 34.4 3,918 Units kW kW % kWh/yr Quantity Minimum output Maximum output Wind penetration Hours of operation Levelized cost State of Battery Value 0.00 1.24 330 7,312 0.509 Units kW kW % hr/yr $/kWh

Figure 14: State of Battery Bank Charge For an optimum hybrid system, we should use 5 parallel strings in a battery bank and each string has one battery in it. Each battery should have the potential of 12V. We are designing this battery bank in such a way that both solar and wind energy systems are not supplying the power (i.e. power generation by the hybrid system is 0 W). In above condition of design consideration, we can take the whole load of primary load by battery bank. In a full charging condition, this battery bank will able to give the constant power supply to the system for 2 days, 5hrs and 12mins. We can see the detail state of battery bank charge for throughout the year in Figure 14 and state of battery bank charge on the monthly basis in Figure 15.

Figure 15: Monthly Statistics of State of Battery Bank Charge

40

Karan Sood, Praveen Singh & Prashant Baredar

Some important outputs for battery bank: Quantity (Units) String size Strings in parallel Batteries Bus voltage (V) Nominal capacity (kWh) Usable nominal capacity (kWh) Autonomy (hr) Value 1 5 5 12 12.0 7.20 53.2 Quantity (Units) Lifetime throughput (kWh) Battery wear cost ($/kWh) Energy in (kWh/yr) Energy out (kWh/yr) Losses (kWh/yr) Annual throughput (kWh/yr) Expected (life yr) Value 4,434 0.050 606 485 121 542 8.19

REFERENCES
1. Bagen, & Billinton, R. (2005). Evaluation of different operating strategies in small stand-alone power systems. IEEE Trans Energy Convers, 20(3), 654660 2. Borowy, B., & Salameh, Z. (1995). Methodology for optimally sizing the combination of a battery bank and PV Array in a Wind/PV Hybrid system. IEEE Trans Energy Convers, 11(2), 367375 3. Ched, R., Akiki, H., & Rahman, S. (1998). A decision support technique for the design of hybrid solar-wind power systems. IEEE Transactions on Energy Conversion, 13(1), 76-83 4. Dalton, G. J., Lockington, D. A., & Baldock, T. E. (2008). Feasibility analysis of stand-alone renewable energy supply options for a large hotel. Renew Energy, 33(7), 14751490 5. Ding, J. J., & Buckeridge, J. S. (2000). Design considerations for a sustainable hybrid energy system. IPENZ Transactions, 27(1), 1-5 6. HOMER (The Hybrid Optimization Model for Electric Renewables). Retrieved from: http://

www.nrel.gov/homer/ 7. Karaki, S. H., Chedid, R. B. & Ramadan, R. (1999). Probabilistic performance assessment of autonomous solarwind energy conversion systems. IEEE Trans Energy Convers, 14(3), 766772 8. Kellogg, W. D., Nehrir, M. H., Venkataramanan, G., & Gerez, V. (1998). Generation unit sizing and cost analysis for stand-alone wind photovoltaic and hybrid wind/PV systems. IEEE Trans Energy Convers, 13(1), 7075 9. Koutroulis, E., Kolokotsa, D., Potirakis, A., & Kalaitzakis, K. (2006). Methodology for optimalsizing of standalone photovoltaic/wind-generator systems using genetic algorithms. Solar Energy psychology, 80(9), 10721088 10. Muljadi, E., & Butterfied, C. P. (2001). Methodology for optimally sizing the combination of a battery bank and PV array in a Wind PV hybrid system. IEEE Transaction on Industry Applications, 37, 240 246 11. Muralikrishna, M., & Lakshminarayana, V. (2008). Hybrid (solar and wind) energy systems for rural electrification. ARPN Journal of Engineering and Applied Sciences, 3(5), 50-58 12. Muselli, M., Notton, G., & Louche, A. (1999). Design of hybrid-photovoltaic power generator with optimization of energy management. Solar Energy, 65(3), 143157 13. Protogeropoulos, C., Brinkworth, B. J., & Marshall, R. H. (1998). Sizing and techno-economical optimization for hybrid solar photovoltaic/wind power systems with battery storage. Int J Energy Res, 21(6), 465479

Optimization of Sustainable Solar-Wind Hybrid System for Domestic Electrification

41

14. Shaahid, S. M., & Elhadidy, M. A. (2007). Technical and economic assessment of grid independent hybrid photovoltaicdieselbattery power systems for commercial loads in desert environments. Renew Sustain Energy Rev, 11(8), 17941810 15. Yang, H., Lu, L., & Zhou, W. (2007). A novel optimization sizing model for hybrid solar-wind power generation system. Solar Energy, 81(1), 7684 16. Yang, H., Zhou, W., & Lou, C. (2009). Optimal design and techno-economic analysis of a hybrid solarwind power generation system. Appl Energy, 86(2), 163169