Selection Guide...................................J-2 MicroSmart PLCs CPU Modules . . . . . . . . . . . . . . . . .J-3 Expansion Modules . . . . . . . . . . .J-10 Dimensions and Specications . .J-16 OpenNet Controller ONC . . . . . . . . . . . . . . . . . . . . . . .J-23 Interbus. . . . . . . . . . . . . . . . . . . . .J-51 DeviceNet. . . . . . . . . . . . . . . . . . .J-61 LONWorks . . . . . . . . . . . . . . . . . .J-71 Original Micro PLCs Micro3 and Micro3C. . . . . . . . . . .J-81 Other PLCs Micro-1. . . . . . . . . . . . . . . . . . . . .J-99 FA2J . . . . . . . . . . . . . . . . . . . . . .J-101 FA3S. . . . . . . . . . . . . . . . . . . . . .J-103 Programming Software WindLDR . . . . . . . . . . . . . . . .J-105

Programmable Logic Controllers


Selection Guide

Selection Guide

IDEC, a pioneer in the micro-PLC market, is proud to offer so many quality micro programmable logic controllers, from the original Micro-1 to the brand new MicroSmart series. Not all information about our older PLCs has been included in this catalog. Please refer to previous catalogs or call IDEC Technical Support with any questions.

Series

Appearance

Specifications

Page

MicroSmart

W! NE

2 types of CPU modules 4 types of Expansion modules

J-3

ONC

W! NE

Available with SX5 Smart I/O modules to communicate with Interbus, DeviceNet, and LONWorks

J-23

J
Micro3 and Micro3C
J-81

Micro-1

The original micro-PLC

J-99

FA2J

Flat-Pak Modular

J-101

FA3S

J-103

WindLDR

Software for programming all of IDECs PLCs

J-105

J-2

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


MicroSmart

MicroSmart Series

The Next Generation of PLC


Key features of the MicroSmart series include: 10, 16, or 24 I/O All-in-one type CPU modules with Sink/ Source DC input and Relay Output 20 I/O Slim type CPU modules with Sink/Source DC input and Transistor Sink or Source Output 20 I/O Slim type CPU modules with Sink/Source DC input and Relay Output with high-speed Transistor Sink or Source Output 40 I/OSlim type CPU module with Sink/Source DC input and Transistor Sink or Source Output DC Input, Relay Output, Transistor Output, Combination I/O and Analog I/O expansion modules available 24 I/O All-in-one CPU expandable to 88 I/O points; 20 I/O slim types expandable up to 148 or 244 I/O; 40 I/O slim type expandable up to 264 I/O points Standard RS232 port, optional plug-in RS485/RS232 port Optional memory cartridge or real-time clock and calendar cartridge Data link to other MicroSmart modules, PLCs, PCs or HG series operator interfaces UL1604 approved for Class 1Div. 2 hazardous locations Compact size UL Listed File No. E211795 CE Certied

CPU MODULES

INPUT MODULES

COMBINATION I/O MODULES

OUTPUT MODULES

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-3

Programmable Logic Controllers


Part Numbers: MicroSmart
Item Description 10 I/O All-in-one Type 16 I/O All-in-one Type 24 I/O All-in-one Type 20 I/O Slim Type, Transistor Sink Output CPU modules 20 I/O Slim Type, Transistor Source Output 20 I/O Slim Type, Relay Sink Output 20 I/O Slim Type, Relay Source Output 40 I/O Slim Type, Transistor Sink Output 40 I/O Slim Type, Transistor Source Output 8-point 24V DC Input, Removable Terminal Block Input Modules 16-point 24V DC Input, Removable Terminal Block 16-point 24V DC Input, MIL Connector 32-point 24V DC Input, MIL Connector 8-point Relay Output, Removable Terminal Block 16-point Relay Output, Removable Terminal Block 8-point Transistor Sink Output, Removable Terminal Block Output Modules 8-point Transistor Source Output, Removable Terminal Block 16-point Transistor Sink Output, MIL Connector 16-point Transistor Source Output, MIL Connector 32-point Transistor Sink Output, MIL Connector 32-point Transistor Source Output, MIL Connector Combination I/O Modules 4-point 24V DC Input, 4-point Relay Output 16-point 24V DC Input, 8-point Relay Output 2-point DC Input, 1-point DC Output Analog I/O Modules 2-point Thermocouple Resistance Input, 1-point DC Output 2-point DC Input 1-point DC Output Programming Software HMI Module HMI Base Module WindLDR 4.10 For displaying and changing required operands For mounting HMI module with Slim type CPU module

MicroSmart Series

Part Number
FC4A-C10R2 FC4A-C16R2 FC4A-C24R2 FC4A-D20KS FC4A-D20S3 FC4A-D20RK1 FC4A-D20RS1 FC4A-D40K3 FC4A-D40S3 FC4A-N08B1 FC4A-N16B1 FC4A-N16B3 FC4A-N32B3 FC4A-R081 FC4A-R161 FC4A-T08K1 FC4A-T08S1 FC4A-T16K3 FC4A-T16S3 FC4A-T32K3 FC4A-T32S3 FC4A-M08BR1 FC4A-M24BR2 FC4A-L03A1 FC4A-L03AP1 FC4A-J2A1 FC4A-K1A1 FC9Y-LP2CDW FC4A-PH1 FC4A-HPH1

ANALOG MODULES

HMI MODULE

MEMORY CARTRIDGE

CLOCK CARTRIDGE

COMMUNICATION ADAPTERS

J-4

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Part Numbers: MicroSmart Options
Description RS232C Communication Adapter (mini DIN type) RS485 Communication Adapter (mini DIN type) RS485 Communication Adapter (screw terminal type) RS232C Communicator Adapter for Slim Type CPU (mini DIN type) RS485 Communication Adapter for Slim Type CPU (mini DIN type) RS485 Communication Adapter for Slim Type CPU (terminal block type) Clock Cartridge Memory Cartridge (32KB) RS232C/RS485 Converter (modem connectable) 26-position Connector Socket, MIL Connector for Slim Type CPU (package quantity: 2) 26-position Connector Socket, MIL Connector for I/O Modules (package quantity: 2) 10-position Terminal Blocks for I/O Modules (package quantity: 2) 11-position Terminal Blocks for I/O Modules (package quantity: 2) 13-position Terminal Blocks for Slim Type CPU Modules FC4A-D20RK1 and FC4A-D20RS1 (package quantity: 2) 16-position Terminal Blocks for Slim Type CPU Module FC4A-D20RK1 (package quantity: 2) 16-position Terminal Blocks for Slim Type CPU Module FC4A-D20RS1 (package quantity: 2) Analog Voltage Input Cable - 1m (3.28 ft) Computer LInk Cable 4C - 3m (9.84 ft.) Modem Cable 1C - 3m (9.84 ft.) RS232C Cable (4-wire) - 1.5m (4.92 ft.) PLC to IDECs HG series Connection Cable - 3m (9.84 ft.) (for 2nd RS232 port only) User Communication Cable 1C - 2.4m (7.87 ft.) O/I Communication Cable IC - 5m (16.4 ft) O/I Communication Cable 2C - 5m (16.4 ft) Direct Mounting Strips (package quantity: 2) 35mm DIN Rails (aluminum, 1m) Mounting Clips Screwdriver (3.5) Screwdriver (2.5) 14-point input switch simulator 9-point input switch simulator 6-point input switch simulator
20-wire Shielded Non-shielded Shielded Non-shielded 2m 2m 2m 2m

MicroSmart Series

Part Number
FC4A-PC1 FC4A-PC2 FC4A-PC3 FC4A-HPC1 FC4A-HPC2 FC4A-HPC3 FC4A-PT1 FC4A-PM32 FC2A-MD1 FC4A-PMC26P FC4A-PMC20P FC4A-PMT10P FC4A-PMT11P FC4A-PMT13P FC4A-PMTK16P FC4A-PMTS16P FC4A-PMAC2P FC4A-KC4C FC2A-KM1C HD9Z-C52 HG9Z-XC183 FC2A-KP1C FC4A-KC1C FC4A-KC2C FC4A-PSP1P BNDN1000 BAA1000 BNL6 FC9Z-SD1 FC9Z-SD2 FC4A-DS824-SW14 FC4A-DS824-SW9 FC4A-DS824-SW6 FC9Z-H200A20 FC9Z-H200B20 FC9Z-H200A26 FC9Z-H200B26 MM-SMART-10 MM-SMART-16 MM-SMART-24

I/O Cables
26-wire

MicroSmart Starter Kit with FC4A-C10R2, WindLDR 4.10, cables, simulator switch, screwdrivers, manual MicroSmart Starter Kit with FC4A-C16R2, WindLDR 4.10, cables, simulator switch, screwdrivers, manual MicroSmart Starter Kit with FC4A-C24R2, WindLDR 4.10, cables, simulator switch, screwdrivers, manual

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-5

Programmable Logic Controllers


FC4A-D20K3 FC4A-D20S3

MicroSmart Series

FC4A-C10R2 Rated Voltage Allowable Range Rated Frequency Maximum Input Current Max. Power Consumption Allowable Momentary Power Interruption Dielectric Strength
0.25A (85V AC) 30VA/264V AC * 20VA/100V AC

FC4A-C16R2
100-240V AC 85-264V AC 50/60 Hz (47-63 Hz) 0.30A (85V AC)

FC4A-C24R2

FC4A-D20RK1 FC4A-D20RS1
24V DC

FC4A-D40KS FC4A-D40S3

20.4 to 26.4V DC (including ripple) 0.45A (85V AC) ** 0.56A (26.4V DC) # 15W/26.4V DC # 0.70A (26.4V DC) # 19W/26.4V DC # 10 msec (at 24V DC) Between power and terminal: 500V AC, 1 min Between I/O and terminal: 1500V AC, 1 min Between power and Between I/O and terminal: 10 m (min) terminal: 10 m (min)

31VA/264V AC * 40VA/264V AC ** 22VA/100V AC 33VA/100V AC

20 msec maximum, Level PS-2 (IEC61131) Between power and terminal: 1500V AC, 1 min Between I/O and terminal: 1500V AC, 1 min Between power and terminal: 10 m (min), 500V DC Between I/O and terminal: 10 m (min), 500V DC AC power terminal: 1.5 kV, 50ns to 1s I/O terminal (coupling clamp): 1.5 kV, 50ns to 1s 35A max. 35A max. 40A max. UL1015, AWG22, UL1007, AWG18 0 to 55C 25 to +70C 30-95% Level RH1 (no condensation) Operation: 0 to 2,000m (0 to 6,595 ft) Transport: 0 to 3,000m (0 to 9.840 ft) 2 (IEC60664) Free from corrosive gases IP20 Grounding resistance 100 maximum

CPU General Specifications

Insulation Resistance Noise Resistance Inrush Current Power Supply Wire Operating Temperature Storage Temperature Operating Humidity Altitude Pollution Degree Corrosion Immunity Degree of Protection Ground

DC power terminals: 1.0 kV, 50 nsec to 1sec I/O terminals (coupling clamp): 1.5 kV, 50 nsec to 1sec 50A maximum (24V DC)

Vibration Resistance Shock Resistance

DIN rail mounted: 10 to 57Hz / amplitutde 0.075mm, 57 to 150Hz / acceleration 9.8m/s2 (1G) Direct mounted: 2 to 25Hz / amplitude 1.6mm, 25 to 100Hz / acceleration 39.2m/s2 (4B) in each of 3 axes 15G, 11ms, 3 shocks in each of 3 axes

* CPU module power consumption includes 250 mA sensor power. ** CPU module (including 250 mA sensor power) + 4 I/O modules # CPU module + 7 I/O modules

Communication Port 1 Specications EIA RS232C Standards Maximum Baud Rate Maintenance Communication User Communication Modem Communication Data Link Communication Cable Isolation between Internal Circuit and Communication Port
19200 bps Possible Possible Not possible Not possible Special Cables: FC2A-KC4C, FC2A-KP1C, FC4A-KC1C, FC4A-KC2C Not isolated

J-6

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


FC4A-C10R2 Control System Instruction words
38 advanced 4,800 bytes (800 steps) 40 advanced 15,000 bytes (2,500 steps)

MicroSmart Series

FC4A-C16R2

FC4A-C24R2

FC4A-D20K3 FC4A-D20S3

FC4A-D20RK1 FC4A-D20RS1

FC4A-D40KS FC4A-D40S3

Stored program system 35 basic instructions 46 advanced 27,000 bytes (4,500 steps) 53 advanced 27,000 bytes (4,500 steps) 70 advanced 31,200 bytes (5,200 steps)

Program Capacity User Program Storage Processing Time Expandable I/O Modules

Calculated 6 bytes per step Internal EEPROM, Memory cartridge (option: EEPROM) Basic instruction: 1.65 msec (1000 steps); END processing: 0.64 msec (does not include expansion I/O service, clock function processing, data link processing and interrupt processing) 4 modules 7 modules

RAM Backup

Backup Data: Internal relay, shift register, counter, data register Backup Duration: Approx. 30 days (typical) at 25 C after backup battery fully charged Battery: Lithium secondary battery Charging Time: Approx. 15 hours for charging from 0% to 90% of full charge Battery Life: 5 years Replaceability: Impossible to replace battery 6 input, 4 output 256 64 400 32 32 100 100 9 input, 7 output 14 input, 10 output Expansion: 64 I/O 12 input, 8 output Expansion: 128 I/O 1024 128 1300 6000 12 intput, 8 output Expansion: 224 I/O 24 input, 16 output Expansion: 224 I/)

I/O Points Internal Relay Shift Register Data Register Expansion Data Register Counter Timer (1-sec, 100-msec, 10-msec, 1-msec) Self-Diagnostic Function Input Filter Catch Input/ Interrupt Input High-Speed Counter Analog Potentiometer Analog Voltage Input Pulse Output Sensor Power Supply Port 1 Port 2 (optional) Clock Function (optional) Memory Cartridge (optional) HMI Module (optional)

CPU Function Specifications

Power failure check, watchdog timer, data link connection, user program EEPROM sum check, timer/counter preset value sum check, user program RAM sum check, keep data, user program syntax, user program writing, CPU module, clock IC, I/O bus initialize, user program execution 3 to 15 msec (1-msec increments) 4 input (I2 through I5) Minimum turn on pulse width: 40 sec maximum Minimum turn off pulse width: 150 sec maximum Total 4 points: Single/two-phase selectable: 20kHz (2 points) Single-phase: 5kHz (2 points)

Total 4 points: Single/two-phase selectable: 20kHz (1 point) Single-phase: 5kHz (3 points)

Counting Range 0 to 65535 (16 bits), Operation Mode: Rotary encoder mode and adding counter mode 1 point 2 points Data Range: 0 to 255 24V DC (+10% to -15%), 250 mA, no overload detection Isolated from the internal circuit 1 point, 0 to 10V DC Input Voltage Range, approx. 100k Input Impedance, data range 0-255 (8 bit) 2 points, max. frequency 20kHz 1 point

RS232C Maintenance Communication, User Communication, Modem Communication Possible: RS232C or RS485 (Maintenance communication, data link) Possible Year, month, day, day of week, hour, minute, second Possible Possible Possible using HMI Base Module

Possible Select either clock or memory cartridge

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-7

Programmable Logic Controllers


DC Input Specications for CPU modules FC4A-C10R2 FC4A-C16R2 FC4A-C24R2 Rated Input Voltage Allowable Range Rated Input Current Input Impedance OFF/ON OFF/ON Time ON/OFF Input Points On Mother Board Connector Insertion/Removal Durability Isolation Input Type External Load for I/O Interconnection Signal Determination Method Effect of Improper Input Connection Cable Length
Between input terminals: Not isolated Internal circuit: Photocoupler isolated Type 1 (IEC61131) Not needed Static 24V DC (both sink and source) 20.4 to 28.8V DC I0, I1: 11mA, I2 to I7, I10 to I15: 7mA I0, I1: 2.1k, I2 to I7, I10 to I15: 3.4k I0 to I5: 35sec + Filter Value I6, I7, I10 to I15: 40sec + Filter Value I0, I1: 45sec + Filter Value I2 to I7, I10 to I15: 150sec + Filter Value 6 inputs 6/1 common 9 inputs 9/1 common 14 inputs 14/1 common 20.4 to 26.4V DC

MicroSmart Series

FC4A-D20K3 FC4A-D20S3

FC4A-D20RK1 FC4A-D20RS1

FC4A-D40KS FC4A-D40S3

I0, I1, I6, I7: 5mA/point, I2 to I5, I10 to I27: 7mA/point I0, I1, I6, I7: 5.7k, I2 to I5, I10 to I27: 3.4k I0 to I7: 35sec + Filter Value I10 to I27: 40sec + Filter Value I0, I1, I6, I7: 45sec + Filter Value I2 to I5, I10 to I27: 150sec + Filter Value 12 inputs 12/1 common FL26A2MA (Oki Electric Cable) 12 inputs 12/1 common MC1.5/13-G-3.81BK (Phoenix Contact) 24 inputs, 12/1 common FL26A2MA (Oki Electric Cable)

100 times minimum

Both sinking and sourcing input signals can be connected. If any input exceeding the rated value is applied, permanent damage may be caused. 3m (9.84 ft)

Relay Output Specications for CPU modules FC4A-C10R2 Output Points


4 points

FC4A-C16R2
7 points 4 points 2 points 1 point

FC4A-C24R2
10 points 4 points 4 points 1 point 1 point 1NO

FC4A-D20RK1 FC4A-D20RS1
8 points 2 points (transistor output) 3 points 2 points 1 point

J
Output Points per Common

COM0 COM1 COM2 COM3 Type of Output Maximum Load Current Minimum Switching Load Initial Contact Resistance Electrical Life Mechanical Life Rated Load Current (resistive/inductive) Dielectric Strength On Mother Board Connector Insertion/ Removal Durability 1 point Common

3 points 1 point

2A 8A 0.1mA, 0.1V DC (reference value) 30m maximum 100,000 operations (rated load) @ 1,800 operations/hr 200,000 operations (no load) @ 18,000 operations/hr 240V AC/2A, 24V DC/2A (30V DC / 2A) Between output and terminals: 1500V AC, 1 minute Between output terminals and internal circuit: 1500V AC, 1 minute Between output terminals (COMs): 1500 V AC, 1 minute MC1.5/16-G-3.81BK (Phoenix Contact) 100 times minimum

J-8

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Transistor Sink and Source Output Specications for CPU modules FC4A-D20K3 FC4A-D20RK1 FC4A-D20S3 FC4A-D20RS1 Output Points and Common Line Type of Output Rated Load Voltage Operating Load Voltage Range Rated Load Current Maximum Load Current Voltage Drop (ON Voltage) Inrush Current Leakage Current Clamping Voltage Maximum Lamp Load Inductive Load External Current Draw Isolation On Mother Board Connector Insertion/Removal Durability Turn ON time Turn OFF time
8 points, 8/1 common 2 points, 2/1 common

MicroSmart Series

FC4A-D40K3 FC4A-D40S3
16 points, 8/1 common

FC4A-D20K3/D20RK1/D40K3 = Sink Output FC4A-D20S3/D20RS1/D40S3 = Source Output 24V DC 20.4 to 28.8V DC 0.3A per output point 1A per common line 1V maximum (voltage between COM and output terminals when output is on) 1A maximum 0.1 mA maximum 39V1V 8W L/R = 10ms (28.8V DC, 1Hz) 100mA maximum, 24V DC (power voltage at the +V or -V terminal) Between output terminal and internal circuit: Photocoupler isolated Between output terminals: Not isolated FL26A2MA (Oki Electric Cable) MC1.5/16-G-3.81BK (Phoenix Contact) 100 times minimum 5 s (Q0, Q1), 300 s max (Q2 to Q7, Q10 to Q17) 5 s (Q0, Q1), 300 s max (Q2 to Q7, Q10 to Q17) FL26A2MA (Oki Electric Cable)

Output Delay

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-9

Programmable Logic Controllers


Specications Expansion Modules
DC Input Module Specications FC4A-N08B1 Input Points Rated Input Voltage Input Voltage Range Rated Input Current Input Impedance Input Delay Time (24V DC) Isolation External Load for I/O Interconnection Signal Determination Method Effect of Improper Input Connection Cable Length On Mother Board Connector Insertion/Removal Durability All Inputs ON All Inputs OFF
25 mA (5V DC) 0 mA (24V DC) 5 mA (5V DC) 0 mA (24V DC) 85g 7mA/point (24V DC) 3.4 k ON time: 4 msec OFF time: 4 msec 8 points (8/1 common)

MicroSmart Series

FC4A-N16B1

FC4A-N16B3

FC4A-N32B3
32 points (16/1 common)

16 points (16/1 common) 24V DC sink/source input signal 20.4 to 28.8V DC

5mA/point (24V DC) 4.4 k

Between input terminals: Not isolated Internal circuit: Photocoupler isolated Not needed Static Both sinking and courcing input signals can be connected. If any input exceeding the rated value is applied, permanent damage may be caused. 3m (9.84 ft) in compliance with electromagnetic immunity MC1.5/10-G-3.81BK (Phoenix contact) 100 times minimum 40 mA (5V DC) 0 mA (24V DC) 5 mA (5V DC) 0 mA (24V DC) 100g 35 mA (5V DC) 0 mA (24V DC) 5 mA (5V DC) 0 mA (24V DC) 65g 65 mA (5V DC) 0 mA (24V DC) 10 mA (5V DC) 0 mA (24V DC) 100g FL20A2MA (Oki Electric Cable)

Internal Current Draw Weight

Relay Output Module Specications FC4A-R08B1 FC4A-R16B1


16 points (8/1 common) 1NO

Output Points and Common Lines Output Type Maximum Load Current Minimum Switching Load Initial Contact Resistance Electrical Life Mechanical Life Rated Load (resistive/inductive) Dielectric Strength On Mother Board Connector Insertion/Removal Durability All Inputs ON Internal Current Draw All Inputs OFF Weight per point per common

8 points (4/1 common)

2A 7A 8A

0.1 mA/0.1V DC (reference value) 30 m maximum 100,000 operations minimum (rated load 1,800 operations/hour) 20,000,000 operations minimum (no load 18,000 operations/hour) 240V AC/2A, 30V DC/2A Between output and terminals: 1500V AC, 1 minute Between output terminals and internal circuit: 1500V AC, 1 minute Between output terminals (COMs): 1500 V AC, 1 minute MC1.5/11-G-3.81BK (Phoenix contact) MC1.5/10-G-3.81BK (Phoenix contact)

100 times minimum 30 mA (5V DC) 40 mA (24V DC) 5 mA (5V DC) 0 mA (24V DC) 110g 45 mA (5V DC) 75 mA (24V DC) 5 mA (5V DC) 0 mA (24V DC) 145g

J-10

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Transistor Output Module Specications FC4A-T08K1 FC4A-T08S1 Output Points Output Type Rated Load Voltage Operating Load Voltage Range Rated Load Current Maximum Load Current Voltage Drop (ON Voltage) Inrush Current Leakage Current Clamping Voltage Maximum Clamping Load Inductive Load External Current Draw Isolation Type (on Mother Board) Insertion/Removal Durability All Inputs ON Internal Current Draw All Inputs OFF Output Delay Weight Turn ON time Turn OFF time
85g 10mA (5V DC) 20mA (24V DC) 5mA (5V DC) 0mA (24V DC) 0.3A per output point (at 28.8V DC) 8 points (8/1 common)

MicroSmart Series

FC4A-T16K3 FC4A-T16S3
FC4A-T K : Transistor sink output FC4A-T S : Transistor source output 24V DC 20.4 to 28.8V DC

FC4A-T32K3 FC4A-T32S3

16 points (16/1 common) 32 points (16/1 common)

0.1A per output point (at 28.8V DC) 0.12A (at 28.8V DC) 1A (at 28.8V DC)

per point per common

0.36A (at28.8V DC) 3A (at 28.8V DC)

1V maximum (between COM and output terminals when output is on) 1A maximum 0.1A maximum 39V 1V 8W L/R = 10 msec (DC 28.8V, 1Hz) FC4A-T K : 100mA maximum, 24V DC (power voltage at the +V) FC4A-T S : 100mA maximum, 24V DC (power voltage at the -V) Between output terminal and internal circuit: Photocoupler isolated Between output terminals: Not isolated MC1.5/10-G-3.81BK (Phoenix contact) FL20A2MA (Oki Electric Cable) 100 times minimum 10mA (5V DC) 40mA (24V DC) 5mA (5V DC) 0mA (24V DC) 300sec maximum 300sec maximum 70g 105g 20mA (5V DC) 70mA (24V DC) 10mA (5V DC) 0mA (24V DC)

Connector

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-11

Programmable Logic Controllers


Combination I/O Module Specications FC4A-M08BR1 Input Points Rated Input Voltage Input Voltage Range Range Input Current Input Impedance Turn ON Time Turn OFF Time Isolation External Load for I/O Interconnection Signal Determination Method Effect of Improper Input Connection Cable Length Output Points
4 points (4/1 common)

MicroSmart Series

FC4A-M24BR2
16 points (16/1 common)

24V DC sink/source input signal 20.4 to 28.8V DC 7 mA/point (24V DC) 3.4 k 4 msec (24V DC) 4 msec (24V DC) Between input terminals: Not isolated Internal circuit: Photocoupler isolated Not needed Static Both sinking and sourcing input signals can be connected. If any input exceeding the rated value is applied, permanent damage may be caused. 3m (9.84 ft) in compliance with electromagnetic immunity 4 points (4/1 common) 1NO 8 points (8/1 common)

DC Input Specifications Relay Output Specifications

Output Type Maximum Load Current Minimum Switching Load Initial Contact Resistance Electrical Life Mechanical Life Rated Load (resistive/inductive) Dielectric Strength per point per common

2A 7A 0.1 mA/0.1V DC (reference value) 30 m maximum 100,000 operations minimum (rated load 1,800 operations/hour) 20,000,000 operations minimum (no load 18,000 operations/hour) 240V AC/2A, 30V DC/2A Between output and or terminals: 1,500V AC, 1 minute Between output terminal and internal circuit: 1,500V AC, 1 minute Between output terminal (COMs): 1,500V AC, 1 minute

J
on Mother Board Connector Insertion/Removal Durability All Inputs ON Internal Current Draw All Inputs OFF Weight

MC1.5/11-G-3.81BK (Phoenix contact) 100 times minimum 25 mA (5V DC) 20 mA (24V DC) 5 mA (5V DC) 0 mA (24V DC) 95g

Input: F6018-17P (Fujicon) Output: F6018-11P (Fujicon) 65 mA (5V DC) 45 mA (24V DC) 10 mA (5V DC) 0 mA (24V DC) 140g

J-12

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Analog I/O Module Specications FC4A-L03A1 Input Points Input Signal Type Output Points Output Signal Type Rated Power Voltage Allowable Voltage Range On Mother Board Connector Insertion/Removal Durability Internal Power External Power
50 mA (5V DC) 0 mA (24V DC) 40 mA (24V DC) 2 Voltage Input (0 to 10V DC) Current Input (4 to 20 mA DC) 1 Voltage Output (0 to 10V DC) Current Output (4 to 20 mA DC)

MicroSmart Series

FC4A-L03AP1
2 Thermocouple Resistance Thermometer 1 Voltage Output (0 to 10V DC) Current Output (4 to 20 mA DC) 24V DC 20.4 to 28.8V DC

FC4A-J2A1
2 Voltage Input (0 to 10V DC) Current Input (4 to 20 mA DC)

FC4A-K1A1
1 Voltage Output (0 to 10V DC) Current Output (4 to 20 mA DC)

MC1.5/11-G-3.81BK (Phoenix contact) 100 times minimum 50 mA (5V DC) 0 mA (24V DC) 40 mA (24V DC) 85g 50 mA (5V DC) 0 mA (24V DC) 40 mA (24V DC) 50 mA (5V DC) 0 mA (24V DC) 40 mA (24V DC)

Internal Current Draw Weight

Analog Output Specications FC4A-L03A1, FC4A-L03AP1, FC4A-K1A1 Output Signal Type Output Range Load Impedance Applicable Load Type Setting Time Total Output System Transfer Time Maximum Error at 25C Temperature Coefficient Repeatabliity after Stabilization Time Output Error Output Voltage Drop Non-lineality Output Ripple Overshoot Total Error Digital Resolution Output Value of LSB Data Data Type in Application Program Monotonicity Current Loop Open Maximum Termporary Deviation during Electrical Noise Tests Noise Cable Crosstalk Dielectric Strength Type of Protection Effect of Improper Output Connection Selection of Analog Output Signal Type Calibration or Verification to Maintain Rated Accuracy
2.5 mV 1% of full scale 0.2% of full scale 1 LSB maximum 0% 1% of full scale 4096 increments (12 bits) 4 A

Voltage Output
0 to 10V DC 2 k minimum Resistive load 20 msec

Current Output
4 to 20 mA DC 300 maximum

20 msec + 1 scan time 0.2% of full scale 0.015% of full scale/C 0.5% of full scale

0 to 4095 (12-bit data); -32768 to 32767 (optional range designation) See note on page J-14 Yes Detectable (See note on page J-14)

3% max. when a 500V clamp is applied to the power and I/O wiring Twisted pair shielded cable recommended for inproved noise immunity No crosstalk because of 1 channel output 500V between output and power circuit Photocoupler between output and internal circuit No damage Using software programming Impossible (approx. 10 years)

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-13

Programmable Logic Controllers


Analog Input Specications FC4A-L03A1, FC4A-J2A1, FC4A-L03AP1 Input Signal Type Input Range Input Impedance Allowable Conductor Resistance Input Detection Current Sample Duration Time Sample Repetition Time Total Input System Transfer Time Type of Input Operating Mode Conversion Method Maximum Error at 25C Temperature Coefficient Input Error Repeatabliity after Stabilization Time Non-lineality Maximum Error Digital Resoltuion Input Value of LSB Data Data Type in Application Program Monotonicity Input Data Out of Range Maximum Termporary Deviation during Electrical Noise Tests Common Mode Characteristics Common Mode Voltage Input Filter Cable Crosstalk Dielectric Strength Type of Protection Effect of Improper Input Connection Maximum Permanent Allowed Overload (No damage) Selection of Analog Input Signal Type Calibration or Verification to Maintain Rated Accuracy
13V DC 40 mA DC Twisted pair shielded cable recommended for improved noise immunity 2 LSB maximum 2.5 mV 4 A 0.2% of full scale

MicroSmart Series

FC4A-L03AP1 only Thermocouple


Type K (0 to 1300C) Type J (0 to 1200C) Type T (0 to 400C) 1 M minimum

Voltage Input
0 to 10V DC 1 M minimum

Current Input
4 to 20 mA DC 10

Resistance Thermometer
Pt 100 3-wire type (-100 to 500C) 1 M minimum 200 maximum 1.0 mA maximum

16 msec maximum 16 msec maximum 32 msec + 1 scan time * Single-ended input

50 msec maximum 50 msec maximum 100 msec + 1 scan time * Differential input Self scan type ADC 0.2% of full scale plus reference junction compensation accuracy (4C maximum) 0.006% of full scale / C 0.5% of full sclae 0.2% of full scale 1% of full scale 4096 increments (12 bits) K: 0.325C; J: 0.300C; T: 0.100C 0.15C 0.2% of full scale

0 to 4095 (12-bit data); -32768 to 32767 (optional range designation) ** Yes Detectable # 3% maximum when a 500V clamp voltage is applied to the power and I/O wiring Accuracy is not assured when noise is applied

J
Noise Resistance

Common mode reject ratio (CMRR): -50 dB 16V DC No

500V between input and power circuit Photocoupler between input and internal circuit No damage Using software programming Impossible (approx. 10 years)

NOTES FOR ANALOG EXPANSION UNITS: * Total input system transfer time = Sample repetition time x 2 + 1 scan time ** The 12-bit data (0 to 4095) processed in the analog I/O module can be linear-converted to a value between -32768 and 32767. Select the optional range designations and analog I/O data minumum and maximum values by using data registers allocated to analog I/O modules. # When an error is detected, a corresponding error code is sorted to a data register allocated to analog I/O operating status.

J-14

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Communication Adapter and Communication Module Specications FC4A-PC1 FC4A-PC2 FC4A-HPC1 FC4A-HPC2 Standards Maximum Baud Rate Maintenance Communication User Communication Modem Communication Data Link Communication Maximum Cable Length Quantity of Slave Stations Isolation between Internal Circuit and Communication Port Recommended Cable for RS485 Conductor Resistance Shield Resistance Optional HMI Module Specications FC4A-PH1 Power Voltage Internal Current Draw Weight Optional Memory Cartridge Specicaions FC4A-PM32 Memory Type Accessible Memory Capacity Hardware for Storing Data Software for Storing Data Quantity of Store Programs
EEPROM 32 KB CPU module WindLDR One user program can be stored on one memory cartridge 5V DC (supplied from the CPU module) 200mA DC 20g EIA RS232C 19200 bps Possible Possible Possible Impossible Use FC2A-KC4C, FC2A-KM1C, FC4A-KC1C, FC4A-KC2C EIA RS485 19200 bps Possible Impossible Impossible Impossible Use FC2A-KP1C Not isolated

MicroSmart Series

FC4A-PC3 FC4A-HPC3
EIA RS485 Computer link: 19200 bps Data link: 38400 bps Possible Impossible Impossible Possible 200m 31

Twisted-piar shielded cable with a minimum core wire of 0.3 mm2 85 /km maximum 20/km maximum

Optional Clock Cartridge Specicaions FC4A-PT1 Accuracy Backup Duration Battery Charging Time Replaceability
30 sec/month (typical) at 25C Approx. 30 days (typical) at 25C after backup battery fully charged Lithium secondary battery Approx. 10 hours for charging from 0% to 90% of full charge Impossible to replace battery

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-15

Programmable Logic Controllers


Dimensions CPU Modules:
FC4A-C10R2, FC4A-C16R2
80.0 70.0

MicroSmart Series

FC4A-C24R2
95.0 70.0

90.0

4.5*

FC4A-D20K3, FC4A-D20S3
35.4 11.3 70.0

FC4A-D20RK1, FC4A-D20RS1
47.5 14.6 70.0

90.0

FC4A-D40K3, FC4A-D40S3
47.5 11.3 70.0

90.0

Expansion Modules:
FC4A-N08B1, FC4A-T08K1, FC4A-M08BR1, FC4A-L03AP1, FC4A-K1A1, FC4A-R081 FC4A-T08S1, FC4A-L03A1, FC4A-J2A1
3.8 23.5 14.6 70.0

90.0

FC4A-N16B3, FC4A-T16K3, FC4A-T16S3


3.8 17.6 11.3 70.0

FC4A-HPC1, FC4A-HPC2, FC4A-HPC3


22.5 13.9 70.0

J
90.0 90.0 90.0

4.5*

90.0

FC4A-N16B1, FC4A-R161
3.8 23.5 14.6 70.0

FC4A-N32B3, FC4A-T32K3, FC4A-T32S3


3.8 29.7 11.3 70.0

FC4A-HPH1
38.0 13.9 71.0

90.0

4.5*
9.0 95.0

FC4A-M24BR2
3.8 39.1 1.0 70.0
23.5 23.5 9.0

90.0

EXAMPLE: This figure illustrates a system setup with the FC4A-C24R2 All-in-one type CPU, an 8-point relay output module, and a 16-point DC input module, mounted on a 35mm DIN rail using BNL6P mounting clips.

90.0

45.0

90.0

35.0

DIN Rail BNL6P Mounting Clip

J-16

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

4.5*

90.0

Programmable Logic Controllers


Mounting Hole Layout CPU Modules:
FC4A-C10R2 FC4A-C16R2
80.0

MicroSmart Series

FC4A-C24R2
95.0

FC4A-C20K3 FC4A-D20S3
35.4 24.1

FC4A-C20RK1, FC4A-D40K3 FC4A-C20RS1, FC4A-D40S3


47.5 24.1

2-

4.3

4.3 2-

90.0 83.0

90.0 83.0

90.0 103.0

2-

4.3

68.0

83.0
3.0
3.0

Expansion Modules:
FC4A-N08B1, FC4A-N16B1, FC4A-R081, FC4A-R161, FC4A-T08K1, FC4A-T08S1, FC4A-M08BR1, FC4A-L03A1 FC4A-L03AP1, FC4A-J2A1, FC4A-K1A1
6.3 23.5
2- 4.3

FC4A-N16B3 FC4A-T16K3 FC4A-T16S3


6.3 17.6
4 2- .3

FC4A-N32B3 FC4A-T32K3 FC4A-T32S3


6.3 29.7 4.3 2-

EXAMPLE: Mounting hole layout for FC4A-C24R2 and 23.5mm-wide I/O modules.
4.3 10 -

12.3

23.5 23.5

90.0 103.0
23.5

90.0 103.0

103.0

83.0

90.0 103.0

90.0 103.0

J
83.0 3.0 3.0 15.3 23.5 3.0 23.5 3.0 23.5

3.0

3.0

3.0 EXAMPLE: Mounting hole layout for, from left, FC4A-HPH1, FC4A-D20K3, FC4A-N16B3, FC4A-N32B3, and FC4A-M24R2 modules.
41.8 17.6 17.6 29.7

FC4A-M24BR2
39.1 4.3 2-

FC4A-HP1C FC4A-HPC2 FC4A-HPC3


4.8 22.5
4.3 2-

FC4A-HPH1
38.0 20.3
4.3 2-

6.3

90.0 103.0

90.0 103.0

90.0 103.0

103.0

3.0

3.0 41.8

3.0 3.0 17.6 17.6

3.0 29.7

3.0

3.0

3.0

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-17

Programmable Logic Controllers


Usage Limits I/O Usage Limits All-in-one Type CPU Modules:
Input Voltage (V DC) 28.8V 26.4V Ambient temperature 55C 28.8V 26.4V Input Voltage (V DC) Ambient temperature 45C Ambient temperature 55C 28.8V 26.4V Input Voltage (V DC) Ambient temperature 45C Ambient temperature 55C

MicroSmart Series

0 50% 100% I/O Simultaneous ON Ratio (%)

0 50% 100% I/O Simultaneous ON Ratio (%)

0 50% 100% I/O Simultaneous ON Ratio (%)

When using at an operating ambient temperature above 40C, reduce the input voltage or the quantity of I/O points that turn on simultaneously.

Slim Type CPU Modules:


26.4V 24.0V Input Voltage (V DC) Ambient temperature 40C Ambient temperature 55C 26.4V 24.0V Input Voltage (V DC) Ambient temperature 55C 26.4V 24.0V Input Voltage (V DC) Ambient temperature 40C Ambient temperature 55C

0 50% 100% I/O Simultaneous ON Ratio (%)

0 50% 100% I/O Simultaneous ON Ratio (%)

0 50% 100% I/O Simultaneous ON Ratio (%)

Input Usage Limits


28.8V 26.4V 24.0V Input Voltage (V DC) Ambient temperature Input Voltage (V DC) Ambient temperature 55C 45C 28.8V 26.4V Ambient 24.0V temperature 55C 0 50% 100% I/O Simultaneous ON Ratio (%) 0 50% 100% I/O Simultaneous ON Ratio (%) 28.8V 26.4V 24.0V Input Voltage (V DC) Ambient temperature Input Voltage (V DC) Ambient temperature 30C 55C 28.8V Ambient 26.4V temperature 24.0V 55C 28.8V 26.4V 24.0V Input Voltage (V DC) Ambient temperature 45C Ambient temperature 55C

0 50% 100% I/O Simultaneous ON Ratio (%)

0 50% 100% I/O Simultaneous ON Ratio (%)

0 50% 100% I/O Simultaneous ON Ratio (%)

Internal Circuits Input Internal Circuits


ALL-IN-ONE TYPE
I0, I1 Input 1.8 k Internal Circuit

Output Internal Circuit (Slim Type)


SLIM TYPE
I0, I1, I6, I7 Input 4.7 k Internal Circuit Internal Circuit Output

SINK OUTPUT

+V

COM

COM

COM(-) I2 to I15 Internal Circuit Input 3.3 k I2 to I5 and I10 to I27 Internal Circuit Input 3.3 k

SOURCE OUTPUT

COM(+)

COM

COM

Internal Circuit

Output

-V

J-18

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Input Internal Circuits (Expansion Modules)
FC4A-N081, FC4A-N16B1
Internal Circuit Input 3.3 k

MicroSmart Series

Output Internal Circuits


FC4A-T08K1, FC4A-T16K3, FC4A-T32K3
+V

COM

Internal Circuit

Output

FC4A-N16B3, FC4A-N32B3
Internal Circuit Input 4.3 k

COM(-)

FC4A-T08S1, FC4A-T16S3, FC4A-T32S3


COM(+)

COM

FC4A-M08BR1, FC4A-M24BR2
Internal Circuit Input 3.3 k Internal Circuit Output

COM

-V

Analog I/O Module Input Circuit


+V2 +V1 15 M Multiplexer NC(A) + (B') 10 1 k 1 k 1 k

J
Input Data

- (B) Input Selection Signal - V1

Output Circuit
+ Output Circuit

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-19

Programmable Logic Controllers


Programming Instructions Basic Instruction List
Symbol LOD LODN OUT OUTN SET RST AND ANDN OR ORN AND LOD OR LOD BPS BRD BPP TML TIM TMH TMS CNT Function
Stores intermediate results and reads contact status Stores intermediate results and reads inverted contact status Outputs the result of bit logical operation Outputs the inverted result of bit logical operation Sets output, internal relay, or shift register bit Resets output, internal relay, or shift register bit Series connection of NO contact Series connection of NC contact Parallel connection of NO contact Parallel connection of NC contact Series connection of circuit blocks Parallel connection of circuit blocks Saves the result of bit logical operation temporarily Reads the result of bit logical operation which was saved temporarily Restores the result of bit logical operation which was saved temporarily Subracting 1-sec timer (0 to 65535 sec) Subtracting 100-msec timer (0 to 6553.5 sec) Subtracting 10-msec timer (0 to 655.35 sec) Subtracting 1-msec timer (0 to 65.535 sec) Adding counter (0 to 65535) Dual pulse reversible counter (0 to 65535) Up/down selection reversible counter (0 to 65535) Equal to comparison of counter current value Greater than or equal to comparison of counter current value Equal to comparison of data register value Greater than or equal to comparison of data register value Forward shift register Reverse shift register Rising-edge differentiation output Falling-edge differentiation output Jumps a designated program area Ends a jump instruciton Starts a master control Ends a master control Ends a program

MicroSmart Series

Qty. of Bytes
6 6 6 6 6 6 4 4 4 4 5 5 5 3 2 4 4 4 4 4 4 4 7 7 8 8 6 6 5 5 4 4 4 4 2

CDP CUD CC= CC DC= DC SFR SFRN SOTU SOTD JMP JEND MCS MCR END

J-20

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Advanced Instruction List
All-in-one Type Symbol NOP MOV MOVN IMOV IMOVN IBMV IBMVN BMOV CMP= CMO<> CMP< CMP> CMP<= CMP>= ICMP>= ADD SUB MUL DIV ANDW ORW XORW SFTL SFTR BCDLS WSFT ROTL ROTR HTOB HTOA BTOH BTOA ATOH ATOB ENCO DECO TXD1 TXD2
No Operation Move Move Not Indirect Move Indirect Move Not Indirect Bit Move Indirect Bit Move Not Block Move Compare Equal To Compare Unequal To Compare Less Than Compare Greater Than Compare Less Than or Equal To Compare Greater Than or Equal To Interval Compare Greater Than or Equal To Addition Subtraction Multiplication Division AND Word OR Word Exclusive OR Word Shift Left Shift Right BCD Left Shift Word Shift Rotate Left Rotate Right Hex to BCD Hex to ASCII BCD to Hex BCD to ASCII ASCII to Hex ASCII to BCD Encode Decode Transmit 1 Transmit 2

MicroSmart Series

Slim Type FC4AC24R2 FC4A-D20K3 FC4A-D20S3 FC4A-D20RK1 FC4A-D20RS1 FC4A-D40K3 FC4A-D40S3

Function

Qty. of Bytes

FC4AC10R2

FC4AC16R2

2 16 16 24-28 24-28 24 24 18 20 20 20 20 20 20 22 20 20 20 20 20 20 20 12 12 14 18 12 12 14 18 14 18 18 18 16 16 21-819 21-819

Not applicable to previously released CPU modules FC4A-C10R2B, FC4A-C16R2B, or FC4A-C24R2B. Applicable only to newer MicroSmart All-in-one-type CPU modules.

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-21

Programmable Logic Controllers


Advanced Instruction List, continued
All-in-one Type Symbol RXD1 RXD2 LABEL LJMP LCAL LRET ROOT DISP DGRD WKTBL WKTIM PULS1 PULS2 PWM1 PWM2 RAMP ZRN1 ZRN2 XYFS CVXTY CVYTX PID IOREF BCNT ALT DTML DTIM DTMH DTMS TTIM DI EI
Receive 1 Receive 2 Label Label Jump Label Call Label Return Root Display Digital Read Week Table Week Timer Pulse Output 1 Pulse Output 2 Pulse Width Modulation 1 Pulse Width Modulation 2 Ramp Pulse Output Zero Return 1 Zero Return 2 XY Format Set Convert X to Y Convery Y to X PID Control I/O Refresh Bit Count Alternate Output 1-sec Dual Timer 100-msec Dual Timer 10-msec Dual Timer 1-msec Dual Timer Teaching Timer Disable Interrupt Enable Interrupt

MicroSmart Series

Slim Type FC4AC24R2 FC4A-D20K3 FC4A-D20S3 FC4A-D20RK1 FC4A-D20RS1 FC4A-D40K3 FC4A-D40S3

Function

Qty. of Bytes

FC4AC10R2

FC4AC16R2

21-819 21-819 8 10 10 6 14 16 20 13-89 24 12 12 24 24 14 18 18 24-124 18 18 26 16 18 10 22 22 22 22 10 8 8

Not applicable to previously released CPU modules FC4A-C10R2B, FC4A-C16R2B, or FC4A-C24R2B. Applicable only to newer MicroSmart All-in-one-type CPU modules.

J-22

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


OpenNet Controller
Digital I/O - 8, 16, and 32 point cards - 224 inputs and outputs, 480 with expansion power supply Analog I/O - up to 42 analog inputs or 14 analog outputs - 0-5V, 0-10V, 5V, 10V, 4-20mA Built-In Communications Ports - 2 RS232 (programming port, ASCII, printer and modem ready) - 1 RS485 (programming port and data link) Build-in High-Speed Counter - 1 channel, 10kHz, 16-bit resolution Memory - 16K words (8K steps) user program capacity - Flash miniature memory card slot (FC3A-CP2KM/SM only) Realtime Calendar/Clock, Y2K compliant Password Protection PID Algorithm Programming Instructions Transmit/Receive Built-in X/Y Conversion Sub-Routine Call/Return for Modular Programming Square Root 16- and 32-bit Math, Add, Sub, Mult, Div Data Conversion to/from Dec, Hex, BCD, ASCII Block Move Summation Averaging Day of Week Program Scheduling Built-in Hayes "AT" command set for modem dialup/ pager applications

ONC Series

FC3A-CP2K FC3A-CP2S

OpenNet Controller
(without memory card connector)

Networking ONC capable of communicating with various standard networks: DeviceNet INTERBUS LONWORKS Programming Software; WindLDR 4.10 Programs all IDEC PLCs Windows-based (compatible with Windows 3.10, 3.11, Win 95, Win-98, Win-2000, or Win-NT 4.0) UL Listed File No. E102342 CE Certied

Hardware Features FC3A-CP2K FC3A-CP2KM FC3A-CP2S FC3A-CP2SM Rated Voltage Maximum Input Current Reverse Polarity Protection Operating Temperature Storage Temperature Relative Humidity Vibration Resistance Shock Resistance Dielectric Strength
Flash memory card ready

High-speed counter sink output, no memory card connector High-speed counter sink output with memory card connector High-speed counter source output, no memory card connector High-speed counter source output with memory card connector 24V DC (19-30V DC, including ripple) 1.5A at 24V DC Prevents damage if incorrectly wired. 0 to +55C -25 to +70C 30 to 95% (non-condensing) 10 to 57 Hz, amplitude 0.075mm 57 to 150 Hz 9.8 m/sec2 10 sweep cycles/axis (IEC 1131) 147 m/sec2, 11 ms 3 shocks each in 3 axes (IEC 1131) Between power terminal and FG: 500V AC, 1 min Between I/O terminal and FG: 1500V AC, 1 min Grounding resistance 100 (maximum) 35mm DIN rail

FC3A-CP2KM FC3A-CP2SM

OpenNet Controller
(with memory card connector)

Electrical Specifications

CPUs

Ground Mounting Style

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-23

Programmable Logic Controllers

ONC Series

Powered by IDECs PS5R Series 50W Power Supply

PS5R Power Supply PS5R-D24 Wattage & Current Ratings Rating Mounting Available Instructions User Program Capacity Memory (Miniature Card) Average Scan Time Input Output Total I/O Points Internal Relay Special Internal Relay Shift Register Timer Counter Data Register Link Register Remote I/O Real-Time Calendar/Clock Runtime Program Protection External Run/Stop Control Power Failure Protection Self-Diagnostics Auto Start Function
50W, 2.1A UL 508 listed DIN rail mountable

Standard ONC CPU


37 basic, 65 advanced (PID, square root, subroutine calls, etc.) 16K words ash memory 2, 4 and 8MB; 5V type 1 ms or greater 224 points (I0-I277) 224 points (Q0-Q277) Using expansion power supply: 480 I/O points 2048 (M0-M2557) 192 (M8000-M8237) 256 (R0-R255) 256 (T0-T255; 1-sec, 100-msec, 10-msec, 1-msec) 256 (C0-C255; adding, dual pulse reversible, up/down selection reversible) 8000 (D0-D7999) 256 master (L1000 - L1317), 168 slave (L100 - L127, L200 - L227, ......, L700 - L727) 512 points Yes (Y2K complaint) Yes (password protected) Yes Yes Yes Yes

General ONC Specifications

The eighth slot must be expansion power supply module. (Above photo is only an example of the range of available modules.)

J-24

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Part Numbers: OpenNet Controller
Item Description High-speed counter, source output type, No memory card available High-speed counter, source output type, With memory card connector High-speed counter, sink output type, No memory card available High-speed counter, sink output type, With memory card connector 16 points 24V DC input, sink/source compatible, terminal block 16 points 24V DC input, sink/source compatible, nylon connector (10P*2) 32 points 24V DC input, sink/source compatible, nylon connector (10P*2) 32 points 24V DC input, sink/source compatible, FUJITSU connector AC Input Analog Input Analog Output Relay Output Output Modules Transistor Output 8 points 100V AC input, terminal block 6 channels, 4-20mA,selectable by DIP sw, terminal block 2 channels, 4-20mA, selectable by DIP sw, terminal block 16 points relay output, terminal block 16 points relay output, nylon connector (5P*4) 16 points transistor output sink, terminal block 16 points transistor output sink, nylon connector 16 points transistor output protect source, terminal block 32 points transistor output sink, nylon connector 32 points transistor output sink, FUJITSU connector Expansion Module Expansion power supply Part Number
FC3A-CP2K FC3A-CP2KM FC3A-CP2S FC3A-CP2SM FC3A-N16B1 FC3A-N16B3 FC3A-N32B4 FC3A-N32B5 FC3A-N08A11 FC3A-AD1261 FC3A-DA1221 FC3A-R161 FC3A-R162 FC3A-T16K1 FC3A-T16K3 FC3A-T16P1 FC3A-T32K4 FC3A-T32K5 FC3A-EA1

ONC Series

CPU Modules

DC Input Input Modules

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-25

Programmable Logic Controllers


Part Numbers: SX/IO
For Use With Description DC-16 Inputs, Source DC-16 Inputs, Sink Relay Output, 8 points INTERBUS Transistor Output, 16 points Transistor Output, 16 points, Protect Source DC-8 points Source Input / Transistor 8 points SInk Output DC-8 points Sink Input / Transistor 8 points Protect Source Output DC-16 Inputs, Source DC-16 Inputs, Sink Relay Output, 8 points DEVICENET Transistor Output, 16 points Transistor Output, 16 points, Protect Source DC-8 points Source Input / Transistor 8 points SInk Output DC-8 points Sink Input / Transistor 8 points Protect Source Output DC-16 Inputs, Source DC-16 Inputs, Sink Relay Output, 8 points LONWORKS Transistor Output, 16 points Transistor Output, 16 points, Protect Source DC-8 points Source Input / Transistor 8 points SInk Output DC-8 points Sink Input / Transistor 8 points Protect Source Output Upper terminal block for SX5*-SBN16*, -SBT16*, -SBM16* Lower terminal block for SX5*-SBN16*, -SBT16* Lower terminal block for SX5*-SBN16* Lower terminal block for SX5*-SBN16* Common Unit Lower terminal block for SX5*-SBN16* SX5D (DeviceNet connector), comes with mounting screws SX5L (LON connector), comes with mounting screws LonWorks slave interface module ONC Remote I/O Master module

ONC Series

Part Number
SX5S-SBN16S SX5S-SBN16K SX5S-SBR08 SX5S-SBT16K SX5S-SBT16P SX5S-SBM16K SX5S-SBM16P SX5D-SBN16S SX5D-SBN16K SX5D-SBR08 SX5D-SBT16K SX5D-SBT16P SX5D-SBM16K SX5D-SBM16P SX5L-SBN16S SX5L-SBN16K SX5L-SBR08 SX5L-SBT16K SX5L-SBT16P SX5L-SBM16K SX5L-SBM16P SX9Z-SS1 SX9Z-SS2 SX9Z-SS3 SX9Z-SS4 SX9Z-SS5 SX9Z-CN5G2 SX9Z-CN22 FC3A-SX5LS1 FC3A-SX5SM1

J-26

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


OpenNet Controller, Networking & Applications

ONC Series

PC Communication The ONC is programmed by our intuitive WindLDR 3.0 software -use RS232 or RS485 ports -upload, download and monitor programs

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

RS232C Port 1 or Port 2

Computer Link Cable 4C FC2A-KC4C 3m (9.84 ft.) long D-sub 9-pin Female Connector

For RS485 programming, use FC2A-KC6C cable.

Master Station

Slave Station 1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Slave Station 2

Slave Station 31
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Data Link - Superiority in Networking Connect up to 32 ONC, Micro3, FA Series PLCs or the HG Series operator interface on the data link network.

HG Series Operator Interface

Communication Selector DIP Switch

RS232C/RS485 Converter FC2A-MD1

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

1st Unit

Computer Link - Power & Versatility Connect 32 ONCs on a 1:N computer link system. Upload, download, monitor, and update data.

D-sub 9-pin Female Connector

RS232C Cable HD9Z-C52 1.5m (4.92 ft.) long

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

2nd Unit

J
Twist-pair Shielded Cable
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

32nd Unit

RS485

POWER RUN ERROR HSC OUT

Communication Flexibility Easy connections to any R232C equipment through the user dened RS232C port 1 or 2. Built-in Hayes AT command set for direct modem dialup and pager applications.

1 2 3

Modem

COM A B Z HSC A RS485 G +24V 0V OUT B

O N DIP Switch

Printer

Barcode Reader

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-27

Programmable Logic Controllers


Network Communication System The ONC offers versatility and power with the unique capability to inferface with standard networks such as INTERBUS, DeviceNet and LONWORKS.

ONC Series

LONWORKS DeviceNet INTERBUS

POWER RUN ERROR HSC OUT

NO H/L DR1 DR0 NA5 NA4 NA3 NA2 NA1 NA0

V.24 Interface

REMOTE IN

SERVICE REQUPST

COM A B HSC Z OUT A RS485 G +24V 0V B

NET WORK

REMOTE OUT

REMOTE OUT

idec

idec

idec

idec

Remote I/O Master Module

CPU Module

OpenNet Interface Modules

I/O Modules

INTERBUS

Add 8 or 16 I/O points to the remote I/O network with a simple connection: SX5S communication terminals offer a simple and low cost method of system expansion.
REMOTE IN REMOTE IN

REMOTE OUT

Remote I/O

REMOTE OUT

Remote I/O

SX5S Communication Terminals

OpenNet Interface Modules


Expansion Connector Expansion Connector Expansion Connector

(1) Module ID (5) Status LED (2) FG Terminal (3) Connector 1

(1) Module ID (4) Status LED


SERVIOSE REQUESI

(1) Module ID (5) Status LED (2) FG Terminal (3) Service Request (4) Connector

(2) DIP Switch

NETWORK

(4) Connector 2

(3) Connector

INTERBUS

DeviceNet

LONWORKS

J-28

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Analog Input and Output Modules

ONC Series

Analog Input Module FC3A-AD1261

Analog Output Module FC3A-DA1221

Key features include: One card handles 5 different signal types, [5V, 10V, 0-5V, 0-10V, or 4-20mA], switch selectable Input module has 6 inputs per card, 7 cards per CPU, 42 analog input points maximum Output module has 2 outputs per card, 7 cards per CPU, 14 analog output points maximum 12-bit resolution, 0-4000 counts, count range divides evenly Fast input scan, 3ms + 1 scan time I/O error 0.6% full scale @25C Convenient input termination, Phoenix Contact type connector

Analog Type
Point Per Card Part Number Connector Type Input Signal

Input
6 Points FC3A-AD1261 Phoenix Contact 0-10V DC, 10V DC, 0-5V DC, 5V DC, 4-20mA 12 bits 0-4000 counts 0.6% of full scale @ 25C NA 3ms per point NA Voltage: 1 M minimum Current: 250 NA 120mA@24V DC

Output
2 Points FC3A-DA1221 Phoenix Contact 0-10V DC, 10V DC, 0-5V DC, 5V DC, 4-20mA 12 bits 0-4000 counts NA 0.6% of full scale @ 25C NA 3ms NA Voltage=2 k minimum (Current=250, 300 max.) 120mA@24V DC

Specifications

Resolution Range Input Error Output Error Conversion Time Settling Time Input Impedance Output Load Impedance Internal Current Draw

Type of Protection

Analog Input Module


+V +V

Analog Output Module

Voltage Output Voltage Input Current Input COM 250

+
Differential Amplifier V V

Current Output

COM

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-29

Programmable Logic Controllers


FC3A-AD1261 Analog Input Module Terminal Arrangement 6-Channel - Screw Terminal Type Applicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact) Terminal No.
1 2
A/D

ONC Series

Channel
Channel 0

Name
+V (voltage) +I (current) COM (-V, -I) +V (voltage)

3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Channel 5 Channel 4 Channel 3 Channel 2 Channel 1

PCW

+I (current) COM (-V, -I) +V (voltage) +I (current) COM (-V, -I) +V (voltage) +I (current) COM (-V, -I) +V (voltage) +I (current) COM (-V, -I) +V (voltage) +I (current) COM (-V, -I) NC NC

FC3A-DA1221 Analog Output Module Terminal Arrangement 2-Channel - Screw Terminal Type Applicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact) Terminal No.

Channel

Rotary Switch Position


0

Name
Voltage Output (0 to 10V) COM (GND) Voltage Output (10V) COM (GND) Voltage Output (0 to 5V) COM (GND) Voltage Output (5V) COM (GND) Current Output (4 to 20mA) COM (GND) Voltage Output (0 to 10V) COM (GND) Voltage Output (10V) COM (GND) Voltage Output (0 to 5V) COM (GND) Voltage Output (5V) COM (GND) Current Output (4 to 20mA) COM (GND)

J
D/A
PCW

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Channel 1 Channel 0

J-30

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


16-Point DC Input Modules

ONC Series

DC Input Module FC3A-N16B1

DC Input Module FC3A-N16B3

Key features include: One card handles sink (NPN) or source (PNP) type input signals 16 points per card, 7 cards local, 8 cards expansion, 15 cards max. per CPU 19-30V DC input voltage range Software selectable input ltering, 0-32 msec High-speed catch inputs, rst 8 points user denable, pulse detection within 20-120sec range Termination connector -FC3A-N16B1 - removable Phoenix Contact type -FC3A-N16B3 - removable Nylon type

Input Type Part Number Connector Type Input Voltage Range Rated Input Voltage Current Per Point Internal Current - all inputs ON Input Impedance On/Off Voltage On/Off Time

DC Sink/Source
FC3A-N16B1 Phoenix Contact 19-30V DC 24V DC 7mA 40mA 3.4k 15/5V DC 20/120s FC3A-N16B3 Nylon 19-30V DC 24V DC 7mA 40mA 3.4k 15/5V DC 20/120s

16-Point DC

Input Operating Range


The input operating range of the Type 1 (EN61131) input module is shown below:
30 Input Voltage (V DC) 24 ON Area Input 15 Transition Area 5 0 4.4 7 1.5 Input Current (mA) 8.8 OFF Area COM

Input Internal Circuit

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Internal Circuit

J-31

Programmable Logic Controllers


FC3A-N16B1 Input Module Terminal Arrangement 16-Point DC - Screw Terminal Type Applicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact) Terminal No.
1 2
DC IN

ONC Series

Name
COM COM I0 I1 I2 I3 I4 I5 I6 I7 COM COM I10 I11 I12 I13 I14 I15 I16 I17

3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17

FC3A-N16B3 Input Module Terminal Arrangement 16-Point DC - Nylon Connector Type Applicable Connectors: VHR-10N (J.S.T. Mfg.) SVH-21T-P1.1 (J.S.T. Mfg.)

Terminal No.
1 2

CN1
COM COM I0 I1 I2 I3 I4 I5 I6 I7

CN1

DC IN

3 4

0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17

5 6 7 8 9 10

CN2

Terminal No.
1 2 3 4 5 6 7 8 9 10

CN2
COM COM I10 I11 I12 I13 I14 I15 I16 I17

J-32

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


32-Point DC Input Modules

ONC Series

DC Input Module FC3A-N32B4

DC Input Module FC3A-N32B5

Key features include: One card handles sink (NPN) or source (PNP) type input signals 32 points per card, 7 cards local, 8 cards expansion, 15 cards max. per CPU 20-28V DC input voltage range Software selectable input ltering, 0-32 msec High-speed catch inputs, rst 8 points user denable, pulse detection within 20-120sec range Termination connector -FC3A-N32B4 - removable Nylon type -FC3A-N32B5 - removable Fujitsu type

Input Type Part Number Connector Type Input Voltage Range Rated Input Voltage Current Per Point Internal Current -all inputs ON Input Impedance On/Off Voltage On/Off Time

DC Sink/Source
FC3A-N32B4 Nylon 20-28V DC 24V DC 5mA 50mA 4.7k 15/5V DC 20/120s FC3A-N32B5 Fujitsu 20-28V DC 24V DC 5mA 50mA 4.7k 15/5V DC 20/120s

32-Point DC

Input Operating Range


The input operating range of the Type 1 (EN61131) input module is shown below:
27.6 Input Voltage (V DC) 24 ON Area Input 15 Transition Area 5 0 1 4.4 5.4 4.9 OFF Area COM

Input Internal Circuit

Input Current (mA)

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Internal Circuit

J-33

Programmable Logic Controllers


FC3A-N32B4 Input Module Terminal Arrangement 32-Point DC - Nylon Connector Type Applicable Connectors: H18-SHF-AA (J.S.T. Mfg.) SHF-001T-0.8BS (J.S.T. Mfg.)
CN1
DC IN

ONC Series

Terminal No.
18 17 16 15

CN1
I0 I1 I2 I3 I4 I5 I6 I7 I10 I11 I12 I13 I14 I15 I16 I17 COM COM

CN2
I20 I21 I22 I23 I24 I25 I26 I27 I30 I31 I32 I33 I34 I35 I36 I37 COM COM

CN2

0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17 20 21 22 23 24 25 26 27 30 31 32 33 34 35 36 37

14 13 12 11 10 9 8 7 6 5 4 3 2 1

FC3A-N32B5 Input Module Terminal Arrangement 32-Point DC - Fujitsu Connector Type Applicable Connector: FCN-367J040-AU (Fujitsu)

Terminal No.
B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4

Name
I0 I1 I2 I3 I4 I5 I6 I7 I10 I11 I12 I13 I14 I15 I16 I17 NC NC COM COM

Terminal No.
A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1

Name
I20 I21 I22 I23 I24 I25 I26 I27 I30 I31 I32 I33 I34 I35 I36 I37 NC NC NC NC

DC IN

0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17 20 21 22 23 24 25 26 27 30 31 32 33 34 35 36 37

FOR MODULE FC3A-N32B5 ONLY: Accessory Part No.


RIbbon Cable Breakout Modules FC3A-KUSA1 BX1D-T40A BX1D-S40A

B3 B2 B1

J-34

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


8-Point AC Input Module

ONC Series

AC Input Module FC3A-N08A11

8-Point AC

Key features include: 8 points per card, 7 cards local, 8 cards expansion, 15 cards max. per CPU 100-120V AC rated input voltage 85-132V AC input voltage range On/off detection set at 20ms Convenient termination connector, removable Phoenix Contact type

Input Type Part Number Connector Type Input Voltage Range Rated Input Voltage Current Per Point Internal Current - all inputs ON Input Impedance On/Off Voltage On/Off Time

AC
FC3A-N08A11 Phoenix Contact 85-132V AC 100-120V AC 8mA 30mA 12k (60Hz) 79/20V AC 20ms

Input Operating Range


The input operating range of the Type 1 (EN61131) input module is shown below:
COM 132 Input Voltage (V AC) 100 79 Transition Area 20 0 6.5 8.3 1.6 Input Current (mA) 11 OFF Area ON Area Input

Input Internal Circuit


Internal Circuit

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-35

Programmable Logic Controllers


FC3A-N08A11 Input Module Terminal Arrangement 8-Point AC - Screw Terminal Type Applicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact) Terminal No.
1 2
AC IN

ONC Series

Name
COM0 I0 COM1 I1 COM2 I2 COM3 I3 COM4 I4 COM5 I5 COM6 I6 COM7 I7 NC NC NC NC

3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

0 1 2 3 4 5 6 7

J-36

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


16-Point Relay Output Modules

ONC Series

Relay Output Module FC3A-R161

Relay Output Module FC3A-R162

Key features include: 16 points per card, 4 points per common, 15 cards max. per CPU Outputs rated 240V AC/2A or 24V DC/2A Turn On/Off delay 6-10ms 20,000,000 operations per relay minimum Termination connector -FC3A-R161 - removable Phoenix Contact type -FC3A-R162 - removable Nylon type

Output Type Part Number Connector Type Rated Output Voltage Rated Current Per Point Internal Current - all inputs ON On/Off Time 16-Point Relay

Relay Output
FC3A-R161 Phoenix Contact 240V AC/24V DC 2A 170mA 6/10ms FC3A-R162 Nylon 240V AC/24V DC 2A 170mA 6/10ms

Output Delay
Command Output Status

OFF delay: 10 msec maximum Chatter: 6 msec maximum ON delay: 6 msec maximum

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-37

Programmable Logic Controllers


FC3A-R161 Output Module Terminal Arrangement 16-Point Relay - Screw Terminal Type Applicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact) Terminal No.
1
Ry OUT

ONC Series

Name
COM0 Q0 Q1 Q2 Q3 COM1 Q4 Q5 Q6 Q7 COM2 Q10 Q11 Q12 Q13 COM3 Q14 Q15 Q16 Q17

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17

FC3A-R162 Output Module Terminal Arrangement 16-Point Relay - Nylon Connector Type Applicable Connectors: VHR-5N (J.S.T. Mfg.) SVH-21T-P1.1 (J.S.T. Mfg.)

Terminal No.
1 2

CN1
COM0 Q0 Q1 Q2 Q3

Terminal No.
1 2 3 4 5

CN3
COM2 Q10 Q11 Q12 Q13

CN1
Ry OUT

3 4

CN2

CN3

0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17

Terminal No.
1 2 3 4

CN2
COM1 Q4 Q5 Q6 Q7

Terminal No.
1 2 3 4 5

CN1
COM3 Q14 Q15 Q16 Q17

CN4

J-38

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


16-Point DC Sink Output Modules

ONC Series

DC Sink Output Module FC3A-T16K1

DC Sink Output Module FC3A-T16K3

Key features include: 16 transistor sink outputs per card, 15 cards max. per CPU Outputs rated 19-30V DC/0.5A Turn On/Off delay 500sec max. Opto-isolated outputs Termination connector -FC3A-T16K1 - removable Phoenix Contact type -FC3A-T16K3 - removable Nylon type

Output Type Part Number Connector Type Rated Output Voltage Rated Current Per Point Internal Current - all inputs ON On/Off Time

DC Sink
FC3A-T16K1 Phoenix Contact 19-30V DC 500mA@ 24V DC 60mA 500/500s FC3A-T16K3 Nylon 19-30V DC 500mA@ 24V DC 60mA 500/500s

16-Point DC

Output Delay

Output Internal Circuit


+V

Command Output Status


Internal Circuit

Output

OFF delay 500 sec maximum ON delay 500 sec maximum

COM ()

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-39

Programmable Logic Controllers


FC3A-T16K1 Sink Output Module Terminal Arrangement 16-Point DC - Screw Terminal Type Applicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact) Terminal No.
1 2
Tr OUT

ONC Series

Name
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 COM(-) +V Q10 Q11 Q12 Q13 Q14 Q15 Q16 Q17 COM(-) +V

3 4

0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17

5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

FC3A-T16K3 Sink Output Module Terminal Arrangement 16-Point DC - Nylon Connector Type Applicable Connectors: VHR-10N (J.S.T. Mfg.) SVH-21T-P1.1 (J.S.T. Mfg.)

Terminal No.
1 2

CN1
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 COM(-) +V

CN1

Tr OUT

3 4

0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17

5 6 7 8 9 10

CN2

Terminal No.
1 2 3 4 5 6 7 8 9 10

CN2
Q10 Q11 Q12 Q13 Q14 Q15 Q16 Q17 COM(-) +V

J-40

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


16-Point DC Protect Source Output Module

ONC Series

Protect Source Output Module FC3A-T16P1

Key features include: 16 transistor protect source outputs per card, 15 cards max. per CPU Outputs rated 19-30V DC/0.5A Turn On/Off delay 500sec max. Opto-isolated outputs Termination connector, removable Phoenix Contact type

Output Type Part Number Connector Type Rated Output Voltage Rated Current Per Point Internal Current - all inputs ON On/Off Time 16-Point DC

DC Source
FC3A-T16P1 Phoenix Contact 19-30V DC 500mA @ 24V DC 70mA 500s/500s

Output Delay
Command

Output Internal Circuit


COM (+)

Output Protect Device

Output Status
Internal Circuit

Output

OFF delay 500 sec maximum ON delay 500 sec maximum

Overload Signal

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-41

Programmable Logic Controllers


FC3A-T16P1 Protect Source Output Module Terminal Arrangement 16-Point DC - Screw Terminal Type Applicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact) Terminal No.
1 2
Tr OUT

ONC Series

Name
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 COM(+) -V Q10 Q11 Q12 Q13 Q14 Q15 Q16 Q17 COM(+) -V

3 4

0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17

5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

J-42

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


32-Point DC Sink Output Modules

ONC Series

DC Sink Output Module FC3A-T32K4

DC Sink Output Module FC3A-T32K5

Key features include: 32 transistor sink outputs per card, 15 cards max. per CPU Outputs rated 20.4-27.6V DC/0.1A Turn On/Off delay 500sec max. Opto-isolated outputs Termination connector -FC3A-T32K4 - removable Nylon type -FC3A-T32K5 - removable Fujitsu type

Output Type Part Number Connector Type Rated Output Voltage Rated Current Per Point Internal Current - all inputs ON On/Off Time

DC Sink
FC3A-T32K4 Nylon 20.4-27.6V DC 100mA@24V DC 90mA 500/500s FC3A-T32K5 Fujitsu 20.4-27.6V DC 100mA@24V DC 90mA 500/500s

32-Point DC

Output Delay
Command Output Status
Internal Circuit

Output Internal Circuit


+V

Output

OFF delay 500 sec maximum ON delay 500 sec maximum

COM ()

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-43

Programmable Logic Controllers


FC3A-T32K4 Sink Output Module Terminal Arrangement 32-Point DC - Nylon Connector Type Applicable Connectors: H18-SHF-AA (J.S.T. Mfg.) SHF-001T-0.8BS (J.S.T. Mfg.)
CN1
Tr OUT

ONC Series

Terminal No.
18 17 16 15

CN1
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q10 Q11 Q12 Q13 Q14 Q15 Q16 Q17 COM(-) +V

CN2
Q20 Q21 Q22 Q23 Q24 Q25 Q26 Q27 Q30 Q31 Q32 Q33 Q34 Q35 Q36 Q37 COM(-) +V

CN2

0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17 20 21 22 23 24 25 26 27 30 31 32 33 34 35 36 37

14 13 12 11 10 9 8 7 6 5 4 3 2 1

FC3A-T32K5 Sink Output Module Terminal Arrangement 32-Point DC - Fujitsu Connector Type Applicable Connector: FCN-367J040-AU (Fujitsu)

Terminal No.
B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1

Name
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q10 Q11 Q12 Q13 Q14 Q15 Q16 Q17 NC NC +V +V

Terminal No.
A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1

Name
Q20 Q21 Q22 Q23 Q24 Q25 Q26 Q27 Q30 Q31 Q32 Q33 Q34 Q35 Q36 Q37 NC NC COM(-) COM(-)

Tr OUT

0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17 20 21 22 23 24 25 26 27 30 31 32 33 34 35 36 37

J-44

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Expansion Power Supply Module

ONC Series

Expansion Power Supply Module FC3A-EA1

Expansion Power Supply

Key features include: Expands the ONC from 224 up to 480 I/O points Increases I/O and functional modules by 8 Comes with a cable connector and contacts Simple, easy and convenient mounting Install in the 8 slot only

Specifications Part Number Connector Type Input Voltage Range Rated Input Voltage Internal Current Momentary Power Interruption
FC3A-EA1 Nylon - 5 pin 19 - 30V DC (including ripple) 24V DC 30mA 10 msec (24V DC), Level PS-2 (EN61131)

Power Supply Wiring


Connector 1: NC 2: NC 3: 24V DC (red) 4: 0V (blue) 5: FG (green) Ground

Power Voltage: 24V DC Inrush Current: 50A (same power source for CPU)

Fuse

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-45

Programmable Logic Controllers


FC3A-EA1 Expansion Power Supply Module Mounting Position Mount the expansion power supply module in the eighth slot.

ONC Series

CPU Module

7 modules (I/O and functional) 8 modules (I/O and functional) Expansion Power Supply Module A maximum of 7 functional modules can be mounted in any of 15 slots

Mount the expansion power supply module only in the eighth slot, otherwise correct allocation of I/O and link register numbers may not occur.

J-46

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


SX5 Series Smart I/O (General Information) Designed to communicate with major industrial networks: INTERBUS, DeviceNet and LONWORKS.
Key features: INTERBUS I/O compatible with IDEC ONC remote I/O Removable terminal blocks for easy maintenance Finger-safe spring-up screw terminals Compact body 75 132 48 mm Mounting on a 35-mm-wide DIN rail or on a panel surface Both inputs and outputs are available in sink or source types. Relay outputs are also available. The source output is protected against overload.

SX5 Smart I/O

UL/c-UL Listed File No. E102542

DeviceNet and LONWORKS are trademarks of ODVA and Echelon, USA, respectively.

SX5 Communication Terminals


Bus I/O Type
DC Input Relay Output INTERBUS Transistor Output

Specifications
16-point source input (24V DC) 16-point sink input (24V DC) 8-point relay output (240V AC/24V DC, 5A) 16-point transistor sink output (24V DC, 0.5A/point, 6.0A/common) 16-point transistor protect source output (24V DC, 0.5A/point, 6.0A/common) 8-point source input (24V DC) 8-point transistor sink output (24V DC, 0.5A/point, 4.0A/common) 8-point sink input (24V DC) 8-point transistor protect source output (24V DC, 0.5A/point, 4.0A/common) 16-point source input (24V DC) 16-point sink input (24V DC) 8-point relay output (240V AC/24V DC, 5A) 16-point transistor sink output (24V DC, 0.5A/point, 6.0A/common) 16-point transistor protect source output (24V DC, 0.5A/point, 6.0A/common) 8-point source input (24V DC) 8-point transistor sink output (24V DC, 0.5A/point, 4.0A/common) 8-point sink input (24V DC) 8-point transistor protect source output (24V DC, 0.5A/point, 4.0A/common) 16-point source input (24V DC) 16-point sink input (24V DC) 8-point relay output (240V AC/24V DC, 5A) 16-point transistor sink output (24V DC, 0.5A/point, 6.0A/common) 16-point transistor protect source output (24V DC, 0.5A/point, 6.0A/common) 8-point source input (24V DC) 8-point transistor sink output (24V DC, 0.5A/point, 4.0A/common) 8-point sink input (24V DC) 8-point transistor protect source output (24V DC, 0.5A/point, 4.0A/common)

Part No.
SX5S-SBN16S SX5S-SBN16K SX5S-SBR08 SX5S-SBT16K SX5S-SBT16P SX5S-SBM16K SX5S-SBM16P SX5D-SBN16S SX5D-SBN16K SX5D-SBR08 SX5D-SBT16K SX5D-SBT16P SX5D-SBM16K SX5D-SBM16P SX5L-SBN16S SX5L-SBN16K SX5L-SBR08 SX5L-SBT16K SX5L-SBT16P SX5L-SBM16K SX5L-SBM16P

DC input Transistor Output

DC Input Relay Output DeviceNet Transistor Output

DC Input Transistor Output

DC Input Relay Output LonWorks Transistor Output

DC Input Transistor Output

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-47

Programmable Logic Controllers


Options (For INTERBUS, DeviceNet, and LONWORKS)
Name
Terminal Block 1 Terminal Block 2 Terminal Block 3 Terminal Block 4 Terminal Block 5 DIN Rail Mounting Clip Aluminum (1m) Steel (1m) Aluminum (1m)

SX5 Smart I/O

Part No.
SX9Z-SS1 SX9Z-SS2 SX9Z-SS3 SX9Z-SS4 SX9Z-SS5 BNDN1000 BAP1000 BAA1000 BNL5

Remarks
Upper terminal block for SX5*-SBN16*, -SBT16*, -SBM16* Lower terminal block for SX5*-SBN16*, SBT16* Lower terminal block for SX5*-SBM16* Upper terminal block for SX5*-SBR08 Lower terminal block for SX5*-SBR08 35-mm-wide DIN rail available in US and Canada markets 35-mm-wide DIN rail available in other than US and Canada markets 35-mm-wide DIN rail available in other than US and Canada markets Used on DIN rail to fasten SX5 communication terminals

One upper and one lower terminal blocks are supplied with every SX5 communication terminal.

Option (For DeviceNet)


Name
SX5D Network Connector

Part No.
SX9Z-CN5G2

Remarks
Mounting screws are attached

One network connector and connector mounting screws are supplied with every SX5D communication terminal.

Option (For LONWORKS)


Name
SX5L Network Connector

Part No.
SX9Z-CN22

Remarks
Mounting screws are attached

One network connector and connector mounting screws are supplied with every SX5L communication terminal.

General Specications
Rated Pow er Voltage Allow able Voltage Range I/O Control Circuit Isolation Control Circuit C o m m . Interface 24V DC 19 to 30V DC (including 5% ripple) Not isolated I N T E R B U S , DeviceNet,Photocoupler L O N W O R K S :Transformer coupling Between pow er terminals and ground: 100 M minimum (500V DC megger) Between pow er terminals and ground: 1000V AC , 1 minute Between relay outputs and other live parts: 2000V AC , 1 minute Amplitude: 0.35 mm, 10 to 55 Hz Amplitude: 0.35 mm, 10 to 55 Hz (contact opening 1 msec when energized) 294 m/sec 2 , 11 m/sec, sine half-wave pulse 59 m/sec 2 (in the direction of relay contact movement) 98 m/sec 2 (in other 5 directions) 0 to +55C 30 to 90% RH (non-condensing) 20 to +75C 30 to 90% RH (non-condensing) Snap-on mount on 35-mm DIN rail P anel-mount with M4 screw s 280g

Network Status Indicators INTERBUS


Indicator
UL RC BA ER RD Green Green Green Red Red

Status
ON ON Flash ON ON ON

Description
Pow er ON Remote-in cable connected correctly Ready for transmitting data Transmitting data Module error (available on protect output module only; protection is reset when overload is removed) Remote-out cable disabled or network error

Insulation Resistance

Dielectric Strength Damage Limits Operating Extremes (relay output) Damage Limits S h o ck Resistance Operating Extremes (relay output)

Vibration Resistance

POW

DeviceNet
Indicator
Green

Status
OFF ON OFF Flash ON Flash ON OFF Flash ON ON

Description
Pow er OFF Pow er ON Pow er OFF or Dup_MAC_ID test not completed Nor mal operation (communication not established) Nor mal operation (communication established) Minor fault (temporary network error) Cr itical fault I/O inactive ( c o m m unication not established) I/O idle ( c o m m unication established) I/O active I/O error or communication interrupted

Operating Te m p e rature Operating Humidity Storage Te m p e rature Storage Humidity Mounting W eight (approx.)

MNS

Green Red

IO

Green Red

I/O Terminals
Terminal Style Rated Insulation Voltage Terminal Screw Number of Poles Rated Operating Current Damage Limits Finger Protection R e m o vable 250V M3 (center to center: 7.62 mm) 10 7A 100 insertion/removal cycles Yes

POW RUN ERR I/O SER

LonWorks
Indicator
Green Green Red Red Yellow

Status
ON ON ON ON ON Flash

Description
Pow er ON Nor mal operation C o m m unication error I/O communication error Application program not congured N e t work management not congured

J-48

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


SX5 Series Smart I/O (General Information) Wiring SX5D and SX5L Cable Connector
For wiring the communication cable connector on the SX5D and SX5L, use a cable of 24 AWG to 14 AWG (0.2 to 2.5 mm2). Strip the cable 7 mm from the end as shown below. Each communication terminal can accommodate up to two cables.

SX5 Smart I/O

Terminal Symbols
SX5*-SBR08 SX5*-SBM16* SX5*-SBN16*/SBT16* + + + 0 C0 1 C1 2 C2 3 C3 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7

7 mm

When connecting two cables to one terminal, use cables of 24 AWG to 16 AWG (0.2 to 1.5 mm2). Do not solder the cable end for connection. Tighten terminal screws on the communication cable connector to a torque of 0.5 to 0.6 N-m. Tighten mounting screws on the communication cable connector to a torque of 0.3 to 0.5 N-m.

SX5*-SBN16*/SBT16* SX5*-SBM16* SX5*-SBR08

POWER 8 + POWER 0

9 10 11 12 13 14 15 1 2 3 4 5 6 7 + POWER 4 C4 5 C5 6 C6 7 C7 +

Insertion Pin Positions


When purchasing terminal blocks separately, set the insertion pins as shown below.

Dimensions
132mm (5.24in) 75mm (2.95in) 48mm (1.89in) 19.3mm (0.76in)

C
A B

D
C D E F

E
G H

SX5 Type No. SX5*-SBN16* SX5*-SBR08 SX5*-SBT16* SX5*-SBM16*

Terminal Block Upper Lower Upper Lower Upper Lower Upper Lower

Type No. SX9Z-SS1 SX9Z-SS2 SX9Z-SS4 SX9Z-SS5 SX9Z-SS1 SX9Z-SS2 SX9Z-SS1 SX9Z-SS3

Pin Positions BDFH ACEG BDEG ACFH BCEG ADFH BCFH ADEG

3.6mm (0.14in)

J
19mm (0.75in)

Safety Precautions
Turn power off to the SX5 communication terminals before starting installation, removal, wiring, maintenance, and inspection of the SX5. Failure to turn power off may cause electrical shocks or re hazard. Wire the SX5 correctly. Improper wiring may cause malfunction, abnormal heat, and re hazard. Use wires of a proper size to meet voltage and current requirements of the SX5. Tighten the terminal screws to a proper tightening torque. A loose screw may cause abnormal heat and re hazard. Check periodically to see if the screws are tightened securely. All SX5 communication terminals are manufactured under IDECs rigorous quality control system, but users must add a backup or fail safe provision to the control system using a SX5 communication terminal in applications where heavy damage or personal injury might result should the SX5 fail.

Mounting Hole Layout (Top view)


(3.94in 0.05) 100mm+ 0.5 (1.3in 0.05) 33mm + 0.5 4.5mm (0.18 in)

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

(1.97 in min) 50mm min.

(2.36in 0.05) 60mm + 0.5

J-49

Programmable Logic Controllers


Input/Output Requirements
When connecting DC two-wire sensors to the SX5, the sensors must meet the following specications. Operating voltage: 12 to 24V DC Leakage current: 1 mA maximum Residual voltage: 6V maximum ON output current: 5.5 mA minimum (at 24V DC) The sensor must have an ON output current of 4 mA at the minimum. If the sensor does not meet this lower limit, connect a bleeder resistor as shown below. But if the residual voltage is 6V or less, the sensor can still be used although the ON output may be less than 3.5 mA.
Source Input Type Sink Input Type

SX5 Smart I/O Operating Instructions


Installation and Wiring (All SX5 Modules) Turn power off to the SX5 before installing or removing the connector or the detachable terminal block. Tighten the terminal screws to a torque of 0.6 to 1.0 N-m. When mounting the SX5 on a panel, tighten the mounting screws to a torque of 1.0 to 1.3 N-m. Recommended mounting screw: M4 When mounting the SX5 on a 35-mm-wide DIN rail, put the SX5 on the DIN rail and press the SX5 towards the rail to lock. To remove, pull out the latch from the bottom of the module using a screwdriver and release the SX5. To re-attach, push back the latch into place and snap on the SX5 again. The upper-right mounting hole has a FG terminal. Connect the FG terminal and control box. Use a wire of 4 mm2 at the minimum to connect the relay terminal block with the safety ground. When mounting on a 35-mm-wide DIN rail, a steel DIN rail is recommended for easy grounding. Mounting on Steel DIN Rail (Recommended) A metal grounding clip is provided on the back of the SX5S and SX5L to contact with a DIN rail. When mounting the SX5 on a steel DIN rail, the metal grounding clip comes in electrical contact with the DIN rail. Connect the DIN rail to a proper ground. Mounting on Aluminum DIN Rail The upper-right mounting hole has a FG terminal. When mounting the SX5 on an aluminum DIN rail, connect the FG terminal to the panel using the attached M4 screw and nut, and connect the panel to a proper ground. Panel Mounting When mounting the SX5 on a panel surface, attach a crimping terminal of a grounding wire to the FG terminal on the upper-right mounting hole of the SX5, and insert a screw through the mounting hole. Connect the grounding wire to the panel and connect the panel to a proper ground. Note: For secure electrical connection, remove coating from the grounding area on the panel. Terminal Block The SX5 uses detachable terminal blocks. To remove and attach the terminal block, follow the procedures below. To remove the terminal block, squeeze both latches on top of the block inward to unlock the block from the socket. To reattach the terminal block, place the block in the socket with the latches opened and press the block until it bottoms in the socket, then the latches snap outward to lock the terminal block. Insertion pins are positioned on the base of the terminal block and inside the socket to prevent insertion of invalid blocks into the socket. The pins are keyed to ensure correct matching of block and socket, and prevent swapping of upper and lower blocks. When the block does not t into the socket properly, check to see if the pin positions on the block agree with the pin-slot arrangement in the socket. If the pins and the pin slots are in matching positions, check for any chips and obstacles in the socket. When cutting cables or wires, keep the SX5 out of the way to prevent ingress of wire chips and fragments. When wiring the screw terminals using crimping terminals, use crimping terminals of the dimensions shown below. Each screw terminal can accommodate up to two crimping terminals.
3.2 min. 6 max. 3.0 max. 5.2 min.
(Dimensions are in mm)

+
R

Input

+
R

Input

I DC two-wire sensor DC two-wire sensor

Use the following formula for calculating the bleeder resistance if needed. Vcc 6 R (k) = -----------------I4 Vcc: Power voltage I: Lower limit of DC two-wire sensor ON output (mA) Do not apply a DC power voltage to the output circuit without connecting a load, otherwise internal elements will be damaged (except for the protect source output type). When an overload or short circuit occurs, the protect source output shuts down the output immediately to protect the internal elements from permanent damage. When the cause of the overload or short circuit is removed, the SX5 will restore normal operation automatically. When the capacity of main power supply is small, the overcurrent protection of the main supply may reduce power supply to the SX5, then the SX5 will stop operation, causing a network error. When using the relay output in environments where extraneous noises exist or inductive loads are switched frequently, generating high reverse emf, connect contact protection elements to the output terminals and across the load as shown below.
Varistor System Diode and Zener Diode System

C0 Load Load Power OUT0

C0 Load + Load Power

OUT0

SX5*-SBR08

SX5*-SBR08

For both AC and DC power voltages

For DC power voltage only

Response Time The response time of the SX5 system varies greatly depending on such factors as the quantity of modules and cable length. The accurate response time can be conrmed on the actual network system. Terminators DeviceNet and LONWORKS networks require terminators. For details about the terminators, see publications on DeviceNet or LONWORKS, or consult IDEC.

Note: Spade crimping terminals can also be used.

J-50

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


16-PointTransistor Input Modules (INTERBUS)

SX5 Smart I/O (INTERBUS)

Key features include: Communicate with INTERBUS network 16-point input modules (sink/source) Removable terminal blocks Use as remote I/O on ONC

Input Type
Source Sink

Part Number
SX5S-SBN16S SX5S-SBN16K

DC Input Type
Part No.
Input Type Input Logic Input Points Input Type Rated Input Voltage Input Voltage Range Turn ON Voltage Turn OFF Voltage Input Current Common Current Draw

Terminal Arrangement
SX5SSBN16S
DC source input Active Low 16 points No-voltage input (2-wire DC sensor, 3-wire NPN sensor, no-voltage contact) 24V DC 0 to the power voltage 6V maximum 10V minimum 6 mA/24V DC 1 common 200 mA

SX5SSBN16K
DC sink input Active High No-voltage input (2-wire DC sensor, 3-wire PNP sensor, no-voltage contact)

Upper Terminal Block (SX9Z-SS1)


Symbol + 0 1 2 3 4 5 6 7 Signal COM (+) COM () IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7

Lower Terminal Block (SX9Z-SS2)


Symbol + 8 9 10 11 12 13 14 15 Signal POWER (+) POWER () IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15

10V minimum 6V maximum 6 mA/24V DC 200 mA

Communication Cable
Bus
INTERBUS

Communication Speed and Distance


Cable
INTERBUS cable

Network I/F Connector (on the module)


9-pin D-sub connector Remote-in: Male Remote-out: Female

Bus
INTERBUS

Baud Rate
500 kbps

Transmission Distance
400m (between slaves) 12.8 km (total length)

Communication Conguration
Type No.
SX5S-SBN16S SX5S-SBN16K

ID Code
02hex

Station Type
Remote Bus Station with Digital Inputs

Data Length
1 word (16 inputs)
Byte 1 7

Data Address
Byte 0 0 15 8

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-51

Programmable Logic Controllers


Wiring INTERBUS Cable
Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources. Turn power off before wiring the INTERBUS cable. Make sure of correct wiring before turning power on. Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plating. Connect the cable shield with the connector housing electrically. INTERBUS Cable Connector Pinouts
D-sub 9-pin Male Connector
/DO DO /DI DI COM 6 1 7 2 3 9 5 Housing Green Yellow Pink Gray Brown

SX5 Smart I/O (INTERBUS)


16-Point Source Input

SX5S-SBN16S

DC Brown (Red) 3-wire Sensor Black (White) NPN IN0 Output Blue (White) Brown (Black) IN1 Blue (Black)

3.8 k

+ + DC Power

3.8 k

D-sub 9-pin Female Connector


6 1 7 2 3 /DO DO /DI DI COM

DC 2-wire Sensor
1

Control Circuit

6 9

6 9

3.8 k
5

Contact Switch
Housing Soldered Side

IN14 3.8 k IN15

Communication Network Interface

Soldered Side

Bridge pins 5 and 9 inside the housing of the male connector.

Contact Switch

Stripping and Clamping Cable Ends

3 20

First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm. Bare the core ends 3 mm.

Next, place the braided screen evenly around the cable sheath. Clamp the shield under the cable grip in the connector housing for conductive connection with the housing.

16-Point Sink Input

SX5S-SBN16K

Leave open the remote out connector at the last station in the network. Supply power to each slave station or to each group of stations separately. Master and slave stations may be powered up in any order. But, if a slave station is not powered up while the master is in preparation for transmission, a network error will result. Causes of network errors include disconnection or short-circuit of the network cable, strong external noise, invalid command sent to the master station, momentary power voltage drop below the minimum power voltage, faulty transmission line, incorrect cable, and transmission longer than the rated distance. When a network error occurs, all outputs are turned off. For further information on INTERBUS, read documents published by the INTERBUS CLUB.

DC Brown (Red) 3-wire Sensor Black PNP IN0 (White) Output Blue (Black) Blue (Black) DC IN1 2-wire Sensor Brown (White)

+ + 3.8 k Control Circuit DC Power

3.8 k

Contact Switch

IN14 3.8 k

Communication Interface

Network

Contact Switch

IN15 3.8 k

J-52

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


8-Point Relay Output Module (INTERBUS)

SX5 Smart I/O (INTERBUS)

Key features include: Communicate with INTERBUS network 8-point relay output module Handles current up to 5A per point Removable terminal blocks Use as remote I/O on ONC

Output Type
Relay Output

Part Number
SX5S-SBR08

Relay Output Type


Part No.
Output Type Output Points Output Type Rated Load Voltage Maximum Load Current Commons/Current Current Draw Built-in Relay

Terminal Arrangement
Upper Terminal Block (SX9Z-SS4) Symbol Signal
+ 0 C0 1 C1 2 C2 3 C3 COM (+) COM () OUT0 COM0 OUT1 COM1 OUT2 COM2 OUT3 COM3

SX5SSBR08
Relay output 8 points 1NO relay contact 250V AC, 24V DC 5A/point 8 commons/5A 140 mA PCB mount, not replaceable

Lower Terminal Block (SX9Z-SS5) Symbol Signal


+ 4 C4 5 C5 6 C6 7 C7 POWER (+) POWER () OUT4 COM4 OUT5 COM5 OUT6 COM6 OUT7 COM7

Rated Relay Contact


Maximum Applicable Voltage Maximum Current Rated Load (resistive load) Minimum Applicable Load Mechanical Life Electrical 250V AC, 125V DC 5A 250V AC/5A, 24V DC/5A 1V DC / 1mA 20,000,000 operations minimum (18,000 operations/hour) See Electrical Life Curve on next page (1,800 operations/hour)

Communication Cable
Bus
INTERBUS

Communication Speed and Distance


Cable
INTERBUS cable

Network I/F Connector (on the module)


9-pin D-sub connector Remote-in: Male Remote-out: Female

Bus
INTERBUS

Baud Rate
500 kbps

Transmission Distance
400m (between slaves) 12.8 km (total length)

Communication Conguration
Type No.
SX5S-SBR08

ID Code
01hex

Station Type
Remote Bus Station with Digital Outputs

Data Length
1 word (8 outputs)
Byte 1 7

Data Address
0 Unused

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-53

Programmable Logic Controllers


Wiring INTERBUS Cable
Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources. Turn power off before wiring the INTERBUS cable. Make sure of correct wiring before turning power on. Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plating. Connect the cable shield with the connector housing electrically. INTERBUS Cable Connector Pinouts
D-sub 9-pin Male Connector
/DO DO /DI DI COM 6 1 7 2 3 9 5 Housing Green Yellow Pink Gray Brown

SX5 Smart I/O (INTERBUS)


8-Point Relay Output

SX5S-SBR08
Load Power + + DC Power OUT0 COM0 Load Power OUT1 COM1 Pilot Light Pilot Light

D-sub 9-pin Female Connector


6 1 7 2 3 /DO DO /DI DI COM

Control Circuit
1

6 9

6 9

Load Power Network Communication Interface OUT6 COM6 Solenoid

Load Power
Housing Soldered Side

Soldered Side

OUT7 COM7

Solenoid

Bridge pins 5 and 9 inside the housing of the male connector.

Stripping and Clamping Cable Ends Reference Data x Electrical Life Curve: Relay in SX5S-SBR08
AC Load First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm. Bare the core ends 3 mm. Next, place the braided screen evenly around the cable sheath. Clamp the shield under the cable grip in the connector housing for conductive connection with the housing.
500 Life (x 10000 operations) 110V AC Resistive 220V AC Resistive 100 50 110V AC Inductive 10 0.05 0.1 220V AC Inductive 0.2 0.3 0.5 1 2 3 Load Current (A) 5

3 20

Life (x 10000 operations)

Leave open the remote out connector at the last station in the network. Supply power to each slave station or to each group of stations separately. Master and slave stations may be powered up in any order. But, if a slave station is not powered up while the master is in preparation for transmission, a network error will result. Causes of network errors include disconnection or short-circuit of the network cable, strong external noise, invalid command sent to the master station, momentary power voltage drop below the minimum power voltage, faulty transmission line, incorrect cable, and transmission longer than the rated distance. When a network error occurs, all outputs are turned off. For further information on INTERBUS, read documents published by the INTERBUS CLUB.

DC Load
500 24V DC Resistive 110 DC Resistive 100 50 48V DC Resistive 24V DC Inductive

110V DC Inductive 10 48V DC Inductive 0.05 0.1 0.2 0.3 0.5 1 2 3 Load Current (A) 5

Note 1: AC/DC Resistive Load Operating frequency: 1800 operations/hour Duty ratio: 40% Note 2: AC Inductive Load
Making Breaking Frequency Current Current Solid 10 I, cos = 0.7 I, cos = 0.3 to 0.4 1800 operations/h Dashed 5 I, cos = 0.7 I, cos = 0.3 to 0.4 300 operations/h Line Duty Ratio 40%

Note 3: DC Inductive Load Operating frequency: 1800 operations/hour Duty ratio: 40% Time constant: L/R =15 msec

J-54

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers

SX5 Smart I/O (INTERBUS)

16-Point Transistor Output Modules (INTERBUS)

Key features include: Communicate with INTERBUS network 16-point transistor output modules (sink/source) The source output is protected against overload Removable terminal blocks Use as remote I/O on ONC

Output Type Sink Source

Part Number
SX5S-SBT16K SX5S-SBT16P

Transistor Output Type


Part No. Output Type Output Points Output Type Rated Load Voltage Load Voltage Range Maximum Load Current Commons/Current Short-circuit Protection Current Draw SX5SSBT16K
Sink output 16 points N-channel MOS open drain 3 to 30V DC 0.5A/point 1 common/6A No 155 mA Yes 180 mA P-channel MOS open drain 19 to 30V DC

Terminal Arrangement
SX5SSBT16P
Protect source output

Upper Terminal Block (SX9Z-SS1) Symbol Signal


+ 0 1 2 3 4 5 6 7 COM (+) COM () OUT0 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7

Lower Terminal Block (SX9Z-SS2) Symbol Signal


+ 8 9 10 11 12 13 14 15 POWER (+) POWER () OUT8 OUT9 OUT10 OUT11 OUT12 OUT13 OUT14 OUT15

24V DC

Communication Cable
Bus
INTERBUS

Communication Speed and Distance


Cable
INTERBUS cable

Network I/F Connector (on the module)


9-pin D-sub connector Remote-in: Male Remote-out: Female

Bus
INTERBUS

Baud Rate
500 kbps

Transmission Distance
400m (between slaves) 12.8 km (total length)

Communication Conguration
Part No.
SX5S-SBT16K SX5S-SBT16P

ID Code
01hex

Station Type
Remote Bus Station with Digital Outputs

Data Length
1 word (16 outputs)
Byte 1 7

Data Address
Byte 0 0 15 8

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-55

Programmable Logic Controllers


Wiring INTERBUS Cable
Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources. Turn power off before wiring the INTERBUS cable. Make sure of correct wiring before turning power on. Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plating. Connect the cable shield with the connector housing electrically. INTERBUS Cable Connector Pinouts
D-sub 9-pin Male Connector
/DO DO /DI DI COM 6 1 7 2 3 9 5 Housing Green Yellow Pink Gray Brown

SX5 Smart I/O (INTERBUS)


16-Point Transistor Sink Output

SX5S-SBT16K

SX5*-SBT16K

+ + DC Power

OUT0

Relay

D-sub 9-pin Female Connector


6 1 7 2 3 /DO DO /DI DI COM

OUT1

Relay

6 9

6 9

Control Circuit Communication Interface

Network

Soldered Side

Housing

Soldered Side

Bridge pins 5 and 9 inside the housing of the male connector.

OUT15 Pilot Light

Stripping and Clamping Cable Ends

3 20

First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm. Bare the core ends 3 mm.

Next, place the braided screen evenly around the cable sheath. Clamp the shield under the cable grip in the connector housing for conductive connection with the housing.

16-Point Transistor Protect Source Output

SX5S-SBT16P

Protection Circuit

Leave open the remote out connector at the last station in the network. Supply power to each slave station or to each group of stations separately. Master and slave stations may be powered up in any order. But, if a slave station is not powered up while the master is in preparation for transmission, a network error will result. Causes of network errors include disconnection or short-circuit of the network cable, strong external noise, invalid command sent to the master station, momentary power voltage drop below the minimum power voltage, faulty transmission line, incorrect cable, and transmission longer than the rated distance. When a network error occurs, all outputs are turned off. For further information on INTERBUS, read documents published by the INTERBUS CLUB.

+ + DC Power

Protection Circuit

Relay OUT0

Control Circuit

Network

Communication Interface

OUT15

Pilot Light

J-56

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers

SX5 Smart I/O (INTERBUS)

8-Point Source Input & 8-Point Transistor Sink Output Module (INTERBUS)

Key features include: Communicate with INTERBUS network 8-point source input and 8-point sink output module Removable terminal blocks Use as remote I/O on ONC

Input/Output Type
Source Input/Sink Output

Part Number
SX5S-SBM16K

DC Input / Transistor Sink Output Type


Part No. I/O Type Input Input Logic Input Points Input Type Rated Input Voltage Input Voltage Range ON Voltage OFF Voltage Input Current Common Output Output Points Output Type Rated Load Voltage Load Voltage Range Maximum Load Current Commons/Current Short-circuit Protection Current Draw SX5SSBM16K
Source input / sink output Active Low 8 points No-voltage input (2-wire DC sensor, 3-wire NPN sensor, no-voltage contact) 24V DC 0 to the power voltage 6V maximum 10V minimum 6 mA/24V DC 1 common 8 points N-channel MOS open drain 24V DC 3 to 30V DC 0.5A/point 1 common/4A No 180 mA

Terminal Arrangement
Upper Terminal Block (SX9Z-SS1) Symbol Signal
+ 0 1 2 3 4 5 6 7 COM (+) COM () IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7

Lower Terminal Block (SX9Z-SS3) Symbol Signal


+ 0 1 2 3 4 5 6 7 POWER (+) POWER () OUT0 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7

Communication Speed and Distance


Bus
INTERBUS

Baud Rate
500 kbps

Transmission Distance
400m (between slaves) 12.8 km (total length)

Communication Cable
Bus
INTERBUS

Network I/F Connector (on the module)


9-pin D-sub connector Remote-in: Male Remote-out: Female

Cable
INTERBUS cable

Communication Conguration
Type No. ID Code Station Type Data Length
7 Byte 0 (Output) 7 0

Data Address
Byte 0 (Input) 0

SX5S-SBM16K

03hex

Remote Bus Station with Digital I/Os

1 byte (8 in / 8 out)

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-57

Programmable Logic Controllers


Wiring INTERBUS Cable
Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources. Turn power off before wiring the INTERBUS cable. Make sure of correct wiring before turning power on. Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plating. Connect the cable shield with the connector housing electrically. INTERBUS Cable Connector Pinouts
D-sub 9-pin Male Connector
/DO DO /DI DI COM 6 1 7 2 3 9 5 Housing Green Yellow Pink Gray Brown

SX5 Smart I/O (INTERBUS)


8-Point Source Input

DC Brown (Red) 3-wire Sensor Black (White) NPN IN0 Output Blue (White) Brown (Black) IN1 Blue (Black)

3.8 k

+ + DC Power

3.8 k

D-sub 9-pin Female Connector


6 1 7 2 3 /DO DO /DI DI COM

DC 2-wire Sensor
1

Control Circuit

6 9

6 9

3.8 k
5

Contact Switch
Housing Soldered Side

IN6 3.8 k IN7

Communication Network Interface

Soldered Side

Bridge pins 5 and 9 inside the housing of the male connector.

Contact Switch

Stripping and Clamping Cable Ends

3 20

First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm. Bare the core ends 3 mm.

Next, place the braided screen evenly around the cable sheath. Clamp the shield under the cable grip in the connector housing for conductive connection with the housing.

8-Point Transistor Sink Output

Leave open the remote out connector at the last station in the network. Supply power to each slave station or to each group of stations separately. Master and slave stations may be powered up in any order. But, if a slave station is not powered up while the master is in preparation for transmission, a network error will result. Causes of network errors include disconnection or short-circuit of the network cable, strong external noise, invalid command sent to the master station, momentary power voltage drop below the minimum power voltage, faulty transmission line, incorrect cable, and transmission longer than the rated distance. When a network error occurs, all outputs are turned off. For further information on INTERBUS, read documents published by the

+ + DC Power

OUT0

Relay

OUT1

Relay

Control Circuit Communication Interface

Network

OUT7 Pilot Light

J-58

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers

SX5 Smart I/O (INTERBUS)

8-Point Sink Input & 8-Point Transistor Source Output Module (INTERBUS)

Key features include: Communicate with INTERBUS network 8-point sink input and 8-point source output module Removable terminal blocks Use as remote I/O on ONC Source output short circuit and overload protected

Input/Output Type
Sink Input/Source Output

Part Number
SX5S-SBM16P

DC Input / Transistor Source Output Type


Part No. I/O Type Input Input Logic Input Points Input Type Rated Input Voltage Input Voltage Range ON Voltage OFF Voltage Input Current Common Output Output Points Output Type Rated Load Voltage Load Voltage Range Maximum Load Current Commons/Current Short-circuit Protection Current Draw SX5SSBM16P
Sink input / protect source output Active High 8 points No-voltage input (2-wire DC sensor, 3-wire PNP sensor, no-voltage contact) 24V DC 0 to the power voltage 10V minimum 6V maximum 6 mA/24V DC 1 common 8 points P-channel MOS open drain 24V DC 19 to 30V DC 0.5A/point 1 common/4A Yes 180 mA

Terminal Arrangement
Upper Terminal Block (SX9Z-SS1) Symbol Signal
+ 0 1 2 3 4 5 6 7 COM (+) COM () IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7

Lower Terminal Block (SX9Z-SS3) Symbol Signal


+ 0 1 2 3 4 5 6 7 POWER (+) POWER () OUT0 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7

Communication Cable
Bus
INTERBUS

Network I/F Connector (on the module)


9-pin D-sub connector Remote-in: Male Remote-out: Female

Cable
INTERBUS cable

Communication Speed and Distance


Bus
INTERBUS

Baud Rate
500 kbps

Transmission Distance
400m (between slaves) 12.8 km (total length)

Communication Conguration
Type No. ID Code Station Type Data Length
7 Byte 0 (Output) 7 0

Data Address
Byte 0 (Input) 0

SX5S-SBM16P

03hex

Remote Bus Station with Digital I/Os

1 byte (8 in / 8 out)

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-59

Programmable Logic Controllers


Wiring INTERBUS Cable
Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources. Turn power off before wiring the INTERBUS cable. Make sure of correct wiring before turning power on. Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plating. Connect the cable shield with the connector housing electrically. INTERBUS Cable Connector Pinouts
D-sub 9-pin Male Connector
/DO DO /DI DI COM 6 1 7 2 3 9 5 Housing Green Yellow Pink Gray Brown

SX5 Smart I/O (INTERBUS)


8-Point Sink Input

DC Brown (Red) 3-wire Sensor Black PNP IN0 (White) Output Blue (Black) Blue (Black) DC IN1 2-wire Sensor Brown (White)

+ + 3.8 k Control Circuit DC Power

D-sub 9-pin Female Connector


6 1 7 2 3 /DO DO /DI DI COM

3.8 k

6 9

6 9

Contact Switch
Housing Soldered Side

IN6 3.8 k

Communication Interface

Network

Soldered Side

Bridge pins 5 and 9 inside the housing of the male connector.

Contact Switch

IN7 3.8 k

Stripping and Clamping Cable Ends

3 20

First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm. Bare the core ends 3 mm.

Next, place the braided screen evenly around the cable sheath. Clamp the shield under the cable grip in the connector housing for conductive connection with the housing.

8-Point Transistor Protect Source Output

Leave open the remote out connector at the last station in the network. Supply power to each slave station or to each group of stations separately. Master and slave stations may be powered up in any order. But, if a slave station is not powered up while the master is in preparation for transmission, a network error will result. Causes of network errors include disconnection or short-circuit of the network cable, strong external noise, invalid command sent to the master station, momentary power voltage drop below the minimum power voltage, faulty transmission line, incorrect cable, and transmission longer than the rated distance. When a network error occurs, all outputs are turned off. For further information on INTERBUS, read documents published by the INTERBUS CLUB.

+ + DC Power

Protection Circuit

Relay OUT0

Control Circuit

Network

Communication Interface Protection Circuit

OUT7

Pilot Light

J-60

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


16-Point Transistor Input Modules (DeviceNet)

SX5 Smart I/O (DeviceNet)

Key features include: Communicate with DeviceNet network 16-point input module (sink/source) Removable terminal blocks

Input Type Source Sink

Part Number
SX5D-SBN16S SX5D-SBN16K

DC Input Type
Part No. Input Type Input Logic Input Points Input Type Rated Input Voltage Input Voltage Range Turn ON Voltage Turn OFF Voltage Input Current Common Current Draw SX5DSBN16S
DC source input Active Low 16 points No-voltage input No-voltage input (2-wire DC sensor, (2-wire DC sensor, 3-wire NPN sensor, 3-wire PNP sensor, no-voltage contact) no-voltage contact) 24V DC 0 to the power voltage 6V maximum 10V minimum 6 mA/24V DC 190 mA 10V minimum 6V maximum 6 mA/24V DC 170 mA

Terminal Arrangement
SX5DSBN16K
DC sink input Active High

Upper Terminal Block (SX9Z-SS1) Symbol Signal


+ 0 1 2 3 4 5 6 7 COM (+) COM () IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7

Lower Terminal Block (SX9Z-SS2) Symbol Signal


+ 8 9 10 11 12 13 14 15 POWER (+) POWER () IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15

1 common

Communication Cable
Bus
DeviceNet

Communication Speed and Distance


Cable
DeviceNet cable

Network I/F Connector (on the module)


Phoenix Contact 5-pin connector MSTBV2.5/5-GF-5.08AU

Bus

Transmission Rate
125k baud 250k baud 500k baud

Transmission Distance Thick Cable Thin Cable


500m 250m 100m 100m 100m 100m

DeviceNet

Communication Conguration
[Baud Rate Selection]
Baud Rate 125 kbps 250 kbps 500 kbps (Selection Prohibited) DR0 OFF ON OFF ON DR1 OFF OFF ON ON

[Output Hold or Load Off]


Output/Load LOAD OFF HOLD H/L OFF ON

[System Reserve]
System Reserve Fixed to (Selection Prohibited) NO OFF ON

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-61

Programmable Logic Controllers


Node Address Selection
Node Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 NA0 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON NA1 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON NA2 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON NA3 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON NA4 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON NA5 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Node Address 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63

SX5 Smart I/O (DeviceNet)

NA0 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON

NA1 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON

NA2 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON

NA3 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON

NA4 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

NA5 ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

Wiring DeviceNet Cable


DeviceNet requires two power voltages; one for communication and the other for internal circuit and load. Use a special DeviceNet cable for connecting to the DeviceNet network. Connect the core wires of the cable to terminals identied by labels of matching colors. DeviceNet Cable

J
16-Point Source Input

Cable
Thick Cable Thin Cable

Part No.
1485C-P1A50 1485C-P1-C150

Maker
Rockwell Automation

16-Point Sink Input

SX5D-SBN16S

SX5D-SBN16K

DC Brown (Red) 3-wire Sensor Black (White) NPN IN0 Output Blue (White) Brown (Black) IN1 Blue (Black)

3.8 k

+ + DC Power

3.8 k DC 2-wire Sensor

DC Brown (Red) 3-wire Sensor Black PNP IN0 (White) Output Blue (Black) Blue (Black) DC IN1 2-wire Sensor Brown (White)

+ + 3.8 k Control Circuit DC Power

Control Circuit

3.8 k

3.8 k Contact Switch IN14 3.8 k IN15 Communication Network Interface Contact Switch IN14 3.8 k Communication Interface Network

Contact Switch

Contact Switch

IN15 3.8 k

J-62

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


8-Point Relay Output Module (DeviceNet)

SX5 Smart I/O (DeviceNet)

Key features include: Communicate with DeviceNet network 8-point relay output module Handles current up to 5A per point Removable terminal blocks

Output Type
Relay Output

Part Number
SX5D-SBR08

Relay Output Type


Part No.
Output Type Output Points Output Type Rated Load Voltage Maximum Load Current Commons/Current Current Draw Built-in Relay

Terminal Arrangement
Upper Terminal Block (SX9Z-SS4) Symbol Signal
+ 0 C0 1 C1 2 C2 3 C3 COM (+) COM () OUT0 COM0 OUT1 COM1 OUT2 COM2 OUT3 COM3

SX5DSBR08
Relay output 8 points 1NO relay contact 250V AC, 24V DC 5A/point 8 commons/5A 120 mA PCB mount, not replaceable

Lower Terminal Block (SX9Z-SS5) Symbol Signal


+ 4 C4 5 C5 6 C6 7 C7 POWER (+) POWER () OUT4 COM4 OUT5 COM5 OUT6 COM6 OUT7 COM7

Rated Relay Contact


Maximum Applicable Voltage Maximum Current Rated Load (resistive load) Minimum Applicable Load Mechanical Life Electrical 250V AC, 125V DC 5A 250V AC/5A, 24V DC/5A 1V DC / 1mA 20,000,000 operations minimum (18,000 operations/hour) See Electrical Life Curve on next page (1,800 operations/hour)

Communication Cable
Bus
DeviceNet

Communication Speed and Distance


Cable
DeviceNet cable

Network I/F Connector (on the module)


Phoenix Contact 5-pin connector MSTBV2.5/5-GF-5.08AU

Bus

Transmission Rate
125k baud 250k baud 500k baud

Transmission Distance Thick Cable Thin Cable


500m 250m 100m 100m 100m 100m

DeviceNet

Communication Conguration
[Baud Rate Selection]
Baud Rate 125 kbps 250 kbps 500 kbps (Selection Prohibited) DR0 OFF ON OFF ON DR1 OFF OFF ON ON

[Output Hold or Load Off]


Output/Load LOAD OFF HOLD H/L OFF ON

[System Reserve]
System Reserve Fixed to (Selection Prohibited) NO OFF ON

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-63

Programmable Logic Controllers


Node Address Selection
Node Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 NA0 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON NA1 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON NA2 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON NA3 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON NA4 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON NA5 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Node Address 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63

SX5 Smart I/O (DeviceNet)

NA0 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON

NA1 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON

NA2 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON

NA3 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON

NA4 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

NA5 ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

Wiring DeviceNet Cable


DeviceNet requires two power voltages; one for communication and the other for internal circuit and load. Use a special DeviceNet cable for connecting to the DeviceNet network. Connect the core wires of the cable to terminals identied by labels of matching colors. DeviceNet Cable

Reference Data
x Electrical Life Curve: Relay in SX5D-SBR08

AC Load
500 Life (x 10000 operations) 110V AC Resistive 220V AC Resistive 100 50 110V AC Inductive 10 0.05 0.1 220V AC Inductive 0.2 0.3 0.5 1 2 3 Load Current (A) 5

DC Load
500 Life (x 10000 operations) 24V DC Resistive 110 DC Resistive 100 50 48V DC Resistive 24V DC Inductive

Cable
Thick Cable Thin Cable

Type No.
1485C-P1A50 1485C-P1-C150

Maker
Rockwell Automation

8-Point Relay Output

110V DC Inductive 10 48V DC Inductive 0.05 0.1 0.2 0.3 0.5 1 2 3 Load Current (A) 5

SX5D-SBR08
Load Power + + DC Power OUT0 COM0 Load Power OUT1 COM1 Pilot Light Pilot Light

Note 1: AC/DC Resistive Load Operating frequency: 1800 operations/hour Duty ratio: 40% Note 2: AC Inductive Load Line
Solid Dashed

Making Current
10 I, cos = 0.7 5 I, cos = 0.7

Breaking Current
I, cos = 0.3 to 0.4 I, cos = 0.3 to 0.4

Frequency
1800 operations/h 300 operations/h

Duty Ratio
40%

Control Circuit

Load Power Network Communication Interface OUT6 COM6 Solenoid

Load Power OUT7 COM7 Solenoid

Note 3: DC Inductive Load Operating frequency: 1800 operations/hour Duty ratio: 40% Time constant: L/R =15 msec

J-64

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


16-Point Transistor Output Modules (DeviceNet)

SX5 Smart I/O (DeviceNet)

Key features include: Communicate with DeviceNet network 16-point transistor output module (sink/source) Removable terminal blocks Source output short circuit and overload protected

Output Type
Sink Source

Part Number
SX5D-SBT16K SX5D-SBT16P

Transistor Output Type


Part No. Output Type Output Points Output Type Rated Load Voltage Load Voltage Range Maximum Load Current Commons/Current Short-circuit Protection Current Draw SX5DSBT16K
Sink output

Terminal Arrangement
SX5DSBT16P
Protect source output 16 points P-channel MOS open drain 19 to 30V DC 0.5A/point 1 common/6A

Upper Terminal Block (SX9Z-SS1) Symbol Signal


+ 0 1 2 3 4 5 6 7 COM (+) COM () OUT0 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7

Lower Terminal Block (SX9Z-SS2) Symbol Signal


+ 8 9 10 11 12 13 14 15 POWER (+) POWER () OUT8 OUT9 OUT10 OUT11 OUT12 OUT13 OUT14 OUT15

N-channel MOS open drain 3 to 30V DC

24V DC

No 70 mA

Yes 100 mA

Communication Cable
Bus
DeviceNet

Communication Speed and Distance


Cable
DeviceNet cable

Network I/F Connector (on the module)


Phoenix Contact 5-pin connector MSTBV2.5/5-GF-5.08AU

Bus

Transmission Rate
125k baud 250k baud 500k baud

Transmission Distance Thick Cable Thin Cable


500m 250m 100m 100m 100m 100m

DeviceNet

Communication Conguration
[Baud Rate Selection]
Baud Rate 125 kbps 250 kbps 500 kbps (Selection Prohibited) DR0 OFF ON OFF ON DR1 OFF OFF ON ON

[Output Hold or Load Off]


Output/Load LOAD OFF HOLD H/L OFF ON

[System Reserve]
System Reserve Fixed to (Selection Prohibited) NO OFF ON

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-65

Programmable Logic Controllers


Node Address Selection
Node Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 NA0 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON NA1 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON NA2 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON NA3 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON NA4 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON NA5 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Node Address 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63

SX5 Smart I/O (DeviceNet)

NA0 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON

NA1 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON

NA2 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON

NA3 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON

NA4 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

NA5 ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

Wiring DeviceNet Cable


DeviceNet requires two power voltages; one for communication and the other for internal circuit and load. Use a special DeviceNet cable for connecting to the DeviceNet network. Connect the core wires of the cable to terminals identied by labels of matching colors. DeviceNet Cable Cable Type No.
1485C-P1A50 1485C-P1-C150

Maker
Rockwell Automation

J
16-Point Transistor Sink Output

Thick Cable Thin Cable

16-Point Transistor Protect Source Output

SX5D-SBT16K

SX5D-SBT16P

+ + DC Power

+ +
OUT0 Relay

DC Power

Protection Circuit

Relay OUT0

OUT1

Relay

Control Circuit Communication Interface

Control Circuit

Network

Network

Communication Interface Protection Circuit

OUT15 Pilot Light

OUT15

Pilot Light

J-66

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers

SX5 Smart I/O (DeviceNet)

8-Point Source Input & 8-Point Transistor Sink Output Module (DeviceNet)

Key features include: Communicate with DeviceNet network 8-point source input and 8-point sink output module Removable terminal blocks

Input/Output Type
Source Input/Sink Output

Part Number
SX5D-SBM16K

DC Input / Transistor Sink Output Type


Part No. I/O Type Input Input Logic Input Points Input Type Rated Input Voltage Input Voltage Range ON Voltage OFF Voltage Input Current Common Output Output Points Output Type Rated Load Voltage Load Voltage Range Maximum Load Current Commons/Current Short-circuit Protection Current Draw SX5DSBM16K
Source input / sink output Active Low 8 points No-voltage input (2-wire DC sensor, 3-wire NPN sensor, no-voltage contact) 24V DC 0 to the power voltage 6V maximum 10V minimum 6 mA/24V DC 1 common

Terminal Arrangement
Upper Terminal Block (SX9Z-SS1) Symbol Signal
+ 0 1 2 3 4 5 6 7 COM (+) COM () IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7

Lower Terminal Block (SX9Z-SS3) Symbol Signal


+ 0 1 2 3 4 5 6 7 POWER (+) POWER () OUT0 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7

Communication Cable
8 points N-channel MOS open drain 24V DC 3 to 30V DC 0.5A/point 1 common/4A No 130 mA DeviceNet

Bus

Network I/F Connector (on the module)


Phoenix Contact 5-pin connector MSTBV2.5/5-GF-5.08AU

Cable
DeviceNet cable

Communication Speed and Distance


Bus Transmission Rate
125k baud 250k baud 500k baud

Transmission Distance Thick Cable Thin Cable


500m 250m 100m 100m 100m 100m

DeviceNet

Communication Conguration
[Baud Rate Selection]
Baud Rate 125 kbps 250 kbps 500 kbps (Selection Prohibited) DR0 OFF ON OFF ON DR1 OFF OFF ON ON

[Output Hold or Load Off]


Output/Load LOAD OFF HOLD H/L OFF ON

[System Reserve]
System Reserve Fixed to (Selection Prohibited) NO OFF ON

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-67

Programmable Logic Controllers


Node Address Selection
Node Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 NA0 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON NA1 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON NA2 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON NA3 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON NA4 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON NA5 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Node Address 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63

SX5 Smart I/O (DeviceNet)

NA0 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON

NA1 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON

NA2 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON

NA3 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON

NA4 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

NA5 ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

Wiring DeviceNet Cable


DeviceNet requires two power voltages; one for communication and the other for internal circuit and load. Use a special DeviceNet cable for connecting to the DeviceNet network. Connect the core wires of the cable to terminals identied by labels of matching colors. DeviceNet Cable Cable Type No.
1485C-P1A50 1485C-P1-C150

Maker
Rockwell Automation

J
8-Point Source Input

Thick Cable Thin Cable

8-Point Transistor Sink Output

DC Brown (Red) 3-wire Sensor Black (White) NPN IN0 Output Blue (White) Brown (Black) DC IN1 2-wire Sensor Blue (Black)

3.8 k

+ + DC Power

+ + DC Power

OUT0

Relay

3.8 k

OUT1 Control Circuit

Relay

Control Circuit Communication Network Interface Communication Interface

3.8 k Contact Switch IN6 3.8 k OUT7 Contact Switch IN7 Pilot Light Network

J-68

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers

SX5 Smart I/O (DeviceNet)

8-Point Sink Input & 8-Point Transistor Source Output Module (DeviceNet)

Key features include: Communicate with DeviceNet network 8-point sink input and 8-point source output module Removable terminal blocks Source output short circuit and overload protected

Input/Output Type
Sink Input/Source Output

Part Number
SX5D-SBM16P

DC Input / Transistor Source Output Type


Part No. I/O Type Input Input Logic Input Points Input Type Rated Input Voltage Input Voltage Range ON Voltage OFF Voltage Input Current Common Output Output Points Output Type Rated Load Voltage Load Voltage Range Maximum Load Current Commons/Current Short-circuit Protection Current Draw SX5DSBM16P
Sink input / protect source output Active High 8 points No-voltage input (2-wire DC sensor, 3-wire PNP sensor, no-voltage contact) 24V DC 0 to the power voltage 10V minimum 6V maximum 6 mA/24V DC 1 common

Terminal Arrangement
Upper Terminal Block (SX9Z-SS1) Symbol Signal
+ 0 1 2 3 4 5 6 7 COM (+) COM () IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7

Lower Terminal Block (SX9Z-SS3) Symbol Signal


+ 0 1 2 3 4 5 6 7 POWER (+) POWER () OUT0 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7

Communication Cable
8 points P-channel MOS open drain 24V DC 19 to 30V DC 0.5A/point 1 common/4A Yes 140 mA DeviceNet

Bus

Network I/F Connector (on the module)


Phoenix Contact 5-pin connector MSTBV2.5/5-GF-5.08AU

Cable
DeviceNet cable

Communication Speed and Distance


Bus Transmission Rate
125k baud 250k baud 500k baud

Transmission Distance Thick Cable Thin Cable


500m 250m 100m 100m 100m 100m

DeviceNet

Communication Conguration
[Baud Rate Selection]
Baud Rate 125 kbps 250 kbps 500 kbps (Selection Prohibited) DR0 OFF ON OFF ON DR1 OFF OFF ON ON

[Output Hold or Load Off]


Output/Load LOAD OFF HOLD H/L OFF ON

[System Reserve]
System Reserve Fixed to (Selection Prohibited) NO OFF ON

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-69

Programmable Logic Controllers


Node Address Selection
Node Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 NA0 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON NA1 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON NA2 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON NA3 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON NA4 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON NA5 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Node Address 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63

SX5 Smart I/O (DeviceNet)

NA0 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON

NA1 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON

NA2 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON

NA3 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON

NA4 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

NA5 ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON

Wiring DeviceNet Cable


DeviceNet requires two power voltages; one for communication and the other for internal circuit and load. Use a special DeviceNet cable for connecting to the DeviceNet network. Connect the core wires of the cable to terminals identied by labels of matching colors. DeviceNet Cable Cable Type No.
1485C-P1A50 1485C-P1-C150

Maker
Rockwell Automation

J
8-Point Sink Input

Thick Cable Thin Cable

8-Point Transistor Protect Source Output

DC Brown (Red) 3-wire Sensor Black PNP IN0 (White) Output Blue (Black) Blue (Black) IN1 Brown (White)

+ + 3.8 k Control Circuit DC Power

+ + DC Power

Protection Circuit

Relay OUT0

DC 2-wire Sensor

3.8 k

Control Circuit

3.8 k

Contact Switch

IN7 3.8 k

Protection Circuit

Contact Switch

IN6

Communication Interface

Network

Network

Communication Interface

OUT7

Pilot Light

J-70

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers

SX5 Smart I/O (LONWORKS)

16-Point Transistor Input Modules (LONWORKS)

Key features include: Communicate with LONWORKS network 16-point transistor input module (sink/source) Removable terminal blocks

Input Type
Source Sink

Part Number
SX5L-SBN16S SX5L-SBN16K

DC Input Type
Part No. Input Type Input Logic Input Points Input Type Rated Input Voltage Input Voltage Range Turn ON Voltage Turn OFF Voltage Input Current Common Current Draw SX5LSBN16S
DC source input Active Low 16 points No-voltage input (2-wire DC sensor, 3-wire NPN sensor, no-voltage contact) No-voltage input (2-wire DC sensor, 3-wire PNP sensor, no-voltage contact)

Terminal Arrangement
SX5LSBN16K
DC sink input Active High

Upper Terminal Block (SX9Z-SS1) Symbol Signal


+ 0 1 2 3 4 5 6 7 COM (+) COM () IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7

Lower Terminal Block (SX9Z-SS2) Symbol Signal


+ 8 9 10 11 12 13 14 15 POWER (+) POWER () IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15

24V DC 0 to the power voltage 6V maximum 10V minimum 6 mA/24V DC 150 mA 10V minimum 6V maximum 6 mA/24V DC 130 mA

1 common

Communication Conguration
All SX5L Modules: The application program of the LonWorks is installed in the Neuron chip of the SX5L module. When wink is executed, the RUN LED ashes for 3 seconds in 500msec increments. In the off-line mode, the RUN and ERR LEDs go off and all outputs also go off. The SX5L does not use SNVT. SX5L-SBN16S/SX5L-SBT16K: Output network variables are updated only at the transition of the input status. (When all inputs are off at power-up, network variables are not updated.) When nv_update_fails is TRUE(1) while using the data acknowledged service (ACKD), the ERR LED goes on. The ERR LED goes off when nv_update_succeeds is TRUE(1). (When an attempt to send network variables fails, resending does not occur until the input changes status. continued

Communication Cable
Bus
LonWorks

Network I/F Connector (on the module)


Phoenix Contact 2-pin connector MSTBV2.5/2-GF-5.08

Cable
Single twisted-pair cable AWG24 to 14 0.2 to 2.5 mm2

Communication Speed and Distance


Bus
LonWorks

Baud Rate
78 kbps

Transmission Distance
500m (total length) 400m (between nodes)

Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-71

Programmable Logic Controllers


Communication Conguration Continued
SX5L-SBN16S SX5L-SBN16K 0
Input to SX5L
Input

SX5 Smart I/O (LONWORKS)


16-Point Source Input

SX5L-SBN16S
nv_o8[0]

nv_o16
8
Input to SX5L
Input

Output Network Variables


DC Brown (Red) 3-wire Sensor Black (White) NPN IN0 Output Blue (White) Brown (Black) IN1 Blue (Black)

nv_o8[1]

3.8 k

15

+ + DC Power

When modifying the application program, please consult IDEC.

3.8 k DC 2-wire Sensor

Control Circuit

Wiring LONWORKS Cable


Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately. The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be connected to either terminal of the connector. The LONWORKS network requires network management to enable communication between nodes, including the SX5L. The network management requires an XIF extension. For your XIF extension, nd your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.
Contact Switch IN14

3.8 k Communication Network Interface 3.8 k IN15

Contact Switch

16-Point Sink Input

SX5L-SBN16K

DC Brown (Red) 3-wire Sensor Black PNP IN0 (White) Output Blue (Black) Blue (Black) DC IN1 2-wire Sensor Brown (White)

+ + 3.8 k Control Circuit DC Power

3.8 k

Contact Switch

IN14 3.8 k

Communication Interface

Network

Contact Switch

IN15 3.8 k

J-72

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


8-Point Relay Output Module (LONWORKS)

SX5 Smart I/O (LONWORKS)

Key features include: Communicate with LONWORKS network 8-point relay output module Handles current up to 5A per point Removable terminal blocks

Output Type
Relay Output

Part Number
SX5L-SBR08

Relay Output Type


Part No. Output Type Output Points Output Type Rated Load Voltage Maximum Load Current Commons/Current Current Draw Built-in Relay SX5LSBR08
Relay output 8 points 1NO relay contact 250V AC, 24V DC 5A/point 8 commons/5A 80 mA PCB mount, not replaceable

Terminal Arrangement
Upper Terminal Block (SX9Z-SS4) Symbol Signal
+ 0 C0 1 C1 2 C2 3 C3 COM (+) COM () OUT0 COM0 OUT1 COM1 OUT2 COM2 OUT3 COM3

Lower Terminal Block (SX9Z-SS5) Symbol Signal


+ 4 C4 5 C5 6 C6 7 C7 POWER (+) POWER () OUT4 COM4 OUT5 COM5 OUT6 COM6 OUT7 COM7

Rated Relay Contact


Maximum Applicable Voltage Maximum Current Rated Load (resistive load) Minimum Applicable Load Mechanical Life Electrical
250V AC, 125V DC 5A 250V AC/5A, 24V DC/5A 1V DC / 1mA 20,000,000 operations minimum (18,000 operations/ hour) See Electrical Life Curve on next page (1,800 operations/ hour)

Communication Conguration
All SX5L Modules: The application program of the LonWorks is installed in the Neuron chip of the SX5L module. When wink is executed, the RUN LED ashes for 3 seconds in 500msec increments. In the off-line mode, the RUN and ERR LEDs go off and all outputs also go off. The SX5L does not use SNVT. SX5L-SBR08: Output is updated only when input network variables are received. (At power-up to the network, all outputs remain off until initial communication starts.)
SX5L-SBR08 0
Output from SX5L
Output

Communication Cable
Bus
LonWorks

Network I/F Connector (on the module)


Phoenix Contact 2-pin connector MSTBV2.5/2-GF-5.08

Cable
Single twisted-pair cable AWG24 to 14 0.2 to 2.5 mm2

Communication Speed and Distance


Bus
LonWorks

Baud Rate
78 kbps

Transmission Distance
500m (total length) 400m (between nodes)

nv_i8[0]
7

Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).

Input Network Variable

When modifying the application program, please consult IDEC.

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-73

Programmable Logic Controllers


Wiring LONWORKS Cable
Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately. The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be connected to either terminal of the connector. The LONWORKS network requires network management to enable communication between nodes, including the SX5L. The network management requires an XIF extension. For your XIF extension, nd your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.

SX5 Smart I/O (LONWORKS)


8-Point Relay Output

SX5L-SBR08
Load Power + + DC Power OUT0 COM0 Load Power OUT1 COM1 Pilot Light Pilot Light

Control Circuit

Load Power Network Communication Interface OUT6 COM6 Solenoid

Load Power OUT7 COM7 Solenoid

Reference Data
x Electrical Life Curve: Relay in SX5L-SBR08
AC Load
500 Life (x 10000 operations) 110V AC Resistive 220V AC Resistive 100 50 110V AC Inductive 10 220V AC Inductive 0.1 0.2 0.3 0.5 1 2 3 Load Current (A) 5

0.05

DC Load
500 Life (x 10000 operations) 24V DC Resistive 110 DC Resistive 100 50 48V DC Resistive 24V DC Inductive

110V DC Inductive 10 48V DC Inductive 0.05 0.1 0.2 0.3 0.5 1 2 3 Load Current (A) 5

Note 1: AC/DC Resistive Load Operating frequency: 1800 operations/hour Duty ratio: 40% Note 2: AC Inductive Load Line
Solid Dashed

Making Current
10 I, cos = 0.7 5 I, cos = 0.7

Breaking Current
I, cos = 0.3 to 0.4 I, cos = 0.3 to 0.4

Frequency
1800 operations/h 300 operations/h

Duty Ratio
40%

Note 3: DC Inductive Load Operating frequency: 1800 operations/hour Duty ratio: 40% Time constant: L/R =15 msec

J-74

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers

SX5 Smart I/O (LONWORKS)

16-Point Transistor Output Modules (LONWORKS)

Key features include: Communicate with LONWORKS network 16-point transistor output module (sink/source) Removable terminal blocks Source output short circuit and overload protected

Output Type
Sink Source

Part Number
SX5L-SBT16K SX5L-SBT16P

Transistor Output Type


Part No. Output Type Output Points Output Type Rated Load Voltage Load Voltage Range Maximum Load Current Commons/Current Short-circuit Protection Current Draw SX5LSBT16K
Sink output

Terminal Arrangement
SX5LSBT16P
Protect source output 16 points P-channel MOS open drain 19 to 30V DC 0.5A/point 1 common/6A

Upper Terminal Block (SX9Z-SS1) Symbol Signal


+ 0 1 2 3 4 5 6 7 COM (+) COM () OUT0 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7

Lower Terminal Block (SX9Z-SS2) Symbol Signal


+ 8 9 10 11 12 13 14 15 POWER (+) POWER () OUT8 OUT9 OUT10 OUT11 OUT12 OUT13 OUT14 OUT15

N-channel MOS open drain 3 to 30V DC

24V DC

No 30 mA

Yes 60 mA

Communication Cable
Bus
LonWorks

Communication Conguration
Cable
Single twisted-pair cable AWG24 to 14 0.2 to 2.5 mm2

Network I/F Connector (on the module)


Phoenix Contact 2-pin connector MSTBV2.5/2-GF-5.08

Communication Speed and Distance


Bus
LonWorks

Baud Rate
78 kbps

Transmission Distance
500m (total length) 400m (between nodes)

Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).

All SX5L Modules: The application program of the LonWorks is installed in the Neuron chip of the SX5L module. When wink is executed, the RUN LED ashes for 3 seconds in 500msec increments. In the off-line mode, the RUN and ERR LEDs go off and all outputs also go off. The SX5L does not use SNVT. SX5L-SBT16P/SX5L-SBT16K: Output is updated only when input network variables are received. (At power-up to the network, all outputs remain off until initial communication starts.) continued

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-75

Programmable Logic Controllers


Communication Conguration continued
SX5L-SBT16K SX5L-SBT16P 0
Output from SX5L
Output

SX5 Smart I/O (LONWORKS)


16-Point Transistor Sink Output

SX5L-SBT16K
nv_i8[0]

nv_i16
8
Output from SX5L
Output

Input Network Variables


DC Power

nv_i8[1]

+ +

15

OUT0

Relay

When modifying the application program, please consult IDEC.

OUT1 Relay

Wiring LONWORKS Cable


Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately. The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be connected to either terminal of the connector. The LONWORKS network requires network management to enable communication between nodes, including the SX5L. The network management requires an XIF extension. For your XIF extension, nd your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.
Network Communication Interface

Control Circuit

OUT15 Pilot Light

16-Point Transistor Protect Source Output

SX5L-SBT16P

+ + DC Power

Protection Circuit

Relay OUT0

Control Circuit

Network

Communication Interface Protection Circuit

OUT15

Pilot Light

J-76

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers

SX5 Smart I/O (LONWORKS)

8-Point Source Input & 8-Point Transistor Sink Output Module (LONWORKS)
Key features include: Communicate with LONWORKS network 8-point source input and 8-point sink output module Removable terminal blocks

Input/Output Type
Source Input/Sink Output

Part Number
SX5L-SBM16K

DC Input / Transistor Sink Output Type


Part No. I/O Type Input Input Logic Input Points Input Type Rated Input Voltage Input Voltage Range ON Voltage OFF Voltage Input Current Common Output Output Points Output Type Rated Load Voltage Load Voltage Range Maximum Load Current Commons/Current Short-circuit Protection Current Draw SX5LSBM16K
Source input / sink output Active Low 8 points No-voltage input (2-wire DC sensor, 3-wire NPN sensor, no-voltage contact) 24V DC 0 to the power voltage 6V maximum 10V minimum 6 mA/24V DC 1 common 8 points N-channel MOS open drain 24V DC 3 to 30V DC 0.5A/point 1 common/4A No 95 mA

Terminal Arrangement
Upper Terminal Block (SX9Z-SS1) Symbol Signal
+ 0 1 2 3 4 5 6 7 COM (+) COM () IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7

Lower Terminal Block (SX9Z-SS3) Symbol Signal


+ 0 1 2 3 4 5 6 7 POWER (+) POWER () OUT0 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7

Communication Conguration
All SX5L Modules: The application program of the LonWorks is installed in the Neuron chip of the SX5L module. When wink is executed, the RUN LED ashes for 3 seconds in 500msec increments. In the off-line mode, the RUN and ERR LEDs go off and all outputs also go off. The SX5L does not use SNVT. SX5L-SBM16K (inputs): Output network variables are updated only at the transition of the input status. (When all inputs are off at power-up, network variables are not updated.) When nv_update_fails is TRUE(1) while using the data acknowledged service (ACKD), the ERR LED goes on. The ERR LED goes off when nv_update_succeeds is TRUE(1). (When an attempt to send network variables fails, resending does not occur until the input changes status. continued

Communication Cable
Bus
LonWorks

Network I/F Connector (on the module)


Phoenix Contact 2-pin connector MSTBV2.5/2-GF-5.08

Cable
Single twisted-pair cable AWG24 to 14 0.2 to 2.5 mm2

Communication Speed and Distance


Bus
LonWorks

Baud Rate
78 kbps

Transmission Distance
500m (total length) 400m (between nodes)

Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-77

Programmable Logic Controllers


Communication Conguration Continued SX5L-SBM16K (outputs): Output is updated only when input network variables are received. (At power-up to the network, all outputs remain off until initial communication starts.)
SX5L-SBM16K 0
Input to SX5L
Input

SX5 Smart I/O (LONWORKS)


8-Point Source Input

nv_o8[0]
7 0

Output Network Variable Input Network Variable

DC Brown (Red) 3-wire Sensor Black (White) NPN IN0 Output Blue (White) Brown (Black) IN1 Blue (Black)

3.8 k

+ + DC Power

Output from SX5L

Output

nv_i8[0]
7

3.8 k DC 2-wire Sensor

Control Circuit

When modifying the application program, please consult IDEC.


Contact Switch

3.8 k IN6 3.8 k IN7 Communication Network Interface

Wiring LONWORKS Cable


Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately. The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be connected to either terminal of the connector. The LONWORKS network requires network management to enable communication between nodes, including the SX5L. The network management requires an XIF extension. For your XIF extension, nd your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.

Contact Switch

8-Point Transistor Sink Output

+ + DC Power

OUT0

Relay

OUT1

Relay

Control Circuit Communication Interface

Network

OUT7 Pilot Light

J-78

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers

SX5 Smart I/O (LONWORKS)

8-Point Sink Input & 8-Point Transistor Source Output Module (LONWORKS)
Key features include: Communicate with LONWORKS network 8-point sink input and 8-point source output module Removable terminal blocks Source output short circuit and overload protected

Input/Output Type Sink Input/Source Output


Part Number SX5L-SBM16P

DC Input / Transistor Source Output Type


Part No. I/O Type Input Input Logic Input Points Input Type Rated Input Voltage Input Voltage Range ON Voltage OFF Voltage Input Current Common Output Output Points Output Type Rated Load Voltage Load Voltage Range Maximum Load Current Commons/Current Short-circuit Protection Current Draw SX5LSBM16P
Sink input / protect source output Active High 8 points No-voltage input (2-wire DC sensor, 3-wire PNP sensor, no-voltage contact) 24V DC 0 to the power voltage 10V minimum 6V maximum 6 mA/24V DC 1 common 8 points P-channel MOS open drain 24V DC 19 to 30V DC 0.5A/point 1 common/4A Yes 100 mA

Terminal Arrangement
Upper Terminal Block (SX9Z-SS1) Symbol Signal
+ 0 1 2 3 4 5 6 7 COM (+) COM () IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7

Lower Terminal Block (SX9Z-SS3) Symbol Signal


+ 0 1 2 3 4 5 6 7 POWER (+) POWER () OUT0 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7

Communication Conguration
All SX5L Modules: The application program of the LonWorks is installed in the Neuron chip of the SX5L module. When wink is executed, the RUN LED ashes for 3 seconds in 500msec increments. In the off-line mode, the RUN and ERR LEDs go off and all outputs also go off. The SX5L does not use SNVT. SX5L-SBM16P (inputs): Output network variables are updated only at the transition of the input status. (When all inputs are off at power-up, network variables are not updated.) When nv_update_fails is TRUE(1) while using the data acknowledged service (ACKD), the ERR LED goes on. The ERR LED goes off when nv_update_succeeds is TRUE(1). (When an attempt to send network variables fails, resending does not occur until the input changes status. continued

Communication Cable
Bus
LonWorks

Network I/F Connector (on the module)


Phoenix Contact 2-pin connector MSTBV2.5/2-GF-5.08

Cable
Single twisted-pair cable AWG24 to 14 0.2 to 2.5 mm2

Communication Speed and Distance


Bus
LonWorks

Baud Rate
78 kbps

Transmission Distance
500m (total length) 400m (between nodes)

Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-79

Programmable Logic Controllers


Communication Conguration Continued SX5L-SBM16P (outputs): Output is updated only when input network variables are received. (At power-up to the network, all outputs remain off until initial communication starts.)
SX5L-SBM16P 0
Input to SX5L
Input

SX5 Smart I/O (LONWORKS)


8-Point Sink Input

nv_o8[0]
7 0

Output Network Variable Input Network Variable

DC Brown (Red) 3-wire Sensor Black PNP IN0 (White) Output Blue (Black) Blue (Black) DC IN1 2-wire Sensor Brown (White)

+ + 3.8 k Control Circuit DC Power

Output from SX5L

Output

nv_i8[0]
7

3.8 k

When modifying the application program, please consult IDEC.

Wiring LONWORKS Cable


Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately. The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be connected to either terminal of the connector. The LONWORKS network requires network management to enable communication between nodes, including the SX5L. The network management requires an XIF extension. For your XIF extension, nd your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.

Contact Switch

IN6 3.8 k

Communication Interface

Network

Contact Switch

IN7 3.8 k

8-Point Transistor Protect Source Output

+ + DC Power

Protection Circuit

Relay OUT0

Control Circuit

Network

Communication Interface Protection Circuit

OUT7

Pilot Light

J-80

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Micro3C

Micro3 Series

The True Micro PLC Ambassador


Key features of the Micro3C include: All the features of the Micro3 Talks both ASCII and binary Equipped with two serial ports, RS232 and RS485 Capable of connecting to dial-up modem, serial printer, and bar code reader Up to 500 data registers Handles a wide range of analog input signals Comes with an easy reset button Available in 2 sizes: 16- and 24-I/O with relay output UL Listed File No. E102542 CSA Certied File No. LR66809 CE Certied EMC Approved File No. B950913332312

Micro3

The Benchmark for Micro-PLCs


Key features of the Micro3 include: Built-in communications and networking Input/output analog capability User program password protection Catch input, pulse output Real-time clock and calendar available Built-in power supply for sensors Arithmetic, comparison, and Boolean computation High-speed: 400/100 steps, 10kHz

UL Listed File No. E102542 CSA Certied File No. LR66809 CE Certied EMC Approved File No. B950913332312

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-81

Programmable Logic Controllers


Standard Mode Program Capacity Processing Internal Relay Data Register Control Data Register Counter/Timer Shift Register
1012 steps 2.9ms/1k steps (average) 232 points Micro3: 100 points Micro3C: 500 points 10 points 32 points total 64 points Data link channel: RS485 Baud rate: 19,200 bps (xed) Cable length: 656' (200m) (maximum) Data link: 6 slave stations (maximum) Expansion: 1 unit (maximum)

Micro3 Series
High-Speed Mode
100 steps (approximately) 400s/100 steps (average) 40 points 32 points 16 points total 32 points

Communication Channel

General Specifications

Programming channel: complies with EIA RS485 (Micro3)/RS232 (Micro3C) standards Baud rate: 1,200/2,400/4,800/9,600/19,200 bps (selectable); Extension: 16.4' (5m) (maximum)

Instructions Memory I/O Catch Input Relays Special Internal Relay Power Failure Protection Self-Diagnostic Function Catch Input Input Filter Function (DC input type only) High-Speed Counter

Micro3: 22 basic, 33 advanced Micro3C: 22 basic, 35 advanced EEPROM See congurations shown on page J-85 8 points 16 points Internal relay, shift register, counter, data register; backup time, lithium battery fully charged With clock: 30 days at 25C (approximately); Without clock: 50 days at 25C (approximately) CPU error (WDT), user program CRC error, user program sum check error, communication error, sensor power overload, transistor output overload 8 points; Minimum detectable pulse width (when hard lter is set to 10); Input I0 ON pulse = 28s, OFF pulse = 30s; Inputs I1 to I7 ON pulse = 37s, OFF pulse = 120s (depending on input lter settings) Normal input: 0ms, 3ms, 7ms, 10ms; Catch input: Input I0 ON pulse = 4 to 616s, OFF pulse = 6 to 618s; Input I1 to I7 ON pulse = 20 to 625s, OFF pulse = 120 to 618s 1 point, single-phase, 10kHz (maximum), 32 bits Micro3: 1 point (10-point), 2 points (16-, 24-point) Micro3C: 1 point only 1 channel, frequency/PWM output (not available in Micro3C) Clock accuracy 30s/month (maximum) at 25C (typical); year, month, day, hour, minute, second 24V 3.6V DC, 150mA (maximum) including input current, overload detected

Analog Potentiometer Pulse Output Real Time Clock Sensor Power Supply
.

Micro3C only available in 16 I/O or 24

AC Power Rated Power Range Power Consumption Inrush Current Power Disruption Dielectric Strength Temperature Operating Humidity Vibration Resistance Shock Resistance Noise Resistance Insulation Resistance Ground Resistance
100 to 240V AC, 50/60Hz (85 to 264V) Approximately 30VA (240V AC) 40A (maximum) 25ms (momentary disruption) allowed Between power terminal and ground: 2,000V AC, 1 minute

DC Power
24V DC (19 to 30V DC) Approximately 14W (24V DC)

Electrical Specifications

Between power terminal and ground: 1,500V AC, 1 minute

Between I/O terminal and ground: 1,500V AC, 1 minute Operating: 0 to 60C, Storage: 20 to +70C 45 to 85% RH (avoid condensation) 5 to 55Hz, 6G, 2 hours in each of 3 axes 30G, 3 shocks in each of 3 axes Between power terminal and ground: 1.3kV, 1s; Between I/O terminal and ground: 1kV, 1s (with noise simulator) complies with IEC1131-2 Between power or I/O terminal and ground: 10M (minimum), 500V DC 100 (maximum)

J-82

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Part Numbers: Micro3 Item
Output: Relay 240V AC, 2A 30V DC, 2A Output: Transistor Sink 24V DC, 0.5A Output: Relay 240V AC, 2A 30V DC, 2A

Micro3 Series
Remarks
Inputs: 120V AC (85-132V AC) 50/60Hz (housing = 24 I/O size)

Part Number
FC2A-CA16A1 FC2A-C10A1 FC2A-C16A1 FC2A-C24A1 FC2A-C10B1 FC2A-C16B1 FC2A-C24B1 FC2A-C10A4 FC2A-C16A4 FC2A-C24A4 FC2A-C10B4 FC2A-C16B4 FC2A-C24B4 FC2A-C10D4 FC2A-C16D4 FC2A-C24D4 MM-MICRO1 MM-MICRO3-10 MM-MICRO3-16 MM-MICRO3-24 MM-MICRO3C-16 MM-MICRO3C-24 MM-Cables FC2A-HL1EC FC2A-KL1 FC2A-KL2 PSR-GA05005 FC2A-KC2 FC2A-MC1 FC2A-KE1 FC2A-LC1 FC2A-KC3 HD9Z-T11 HD9Z-T11-DS783

Description
16 I/O: 9 inputs and 7 outputs 10 I/O: 6 inputs and 4 outputs 16 I/O: 9 inputs and 7 outputs 24 I/O: 14 inputs and 10 outputs 10 I/O: 6 inputs and 4 outputs 16 I/O: 9 inputs and 7 outputs 24 I/O: 14 inputs and 10 outputs 10 I/O: 6 inputs and 4 outputs 16 I/O: 9 inputs and 7 outputs 24 I/O: 14 inputs and 10 outputs 10 I/O: 6 inputs and 4 outputs 16 I/O: 9 inputs and 7 outputs 24 I/O: 14 inputs and 10 outputs 10 I/O: 6 inputs and 4 outputs 16 I/O: 9 inputs and 7 outputs 24 I/O: 14 inputs and 10 outputs

100 to 240V AC 50/60Hz Power Micro3 CPU

Inputs: 24V DC sink/source Only the 16- and 24-I/O units have real-time clock/calendar

24V DC Power Micro3 CPU

Output: Transistor Sink 24V DC, 0.5A Output: Transistor Source 24V DC, 0.5A

Programming Starter Kits

Micro-1 PLC, WindLDR, computer link cable Micro3 10 I/O, WindLDR, computer link cable, input switch simulator Micro3 16 I/O, WindLDR, computer link cable, input switch simulator Micro3 24 I/O, WindLDR, computer link cable, input switch simulator Micro3C 16 I/O, WindLDR, computer link cable, input switch simulator Micro3C 24 I/O, WindLDR, computer link cable, input switch simulator WindLDR, 3 computer link cables for Micro-1, Micro3 and Micro3C Program loader with cable 6.56' (2m) long 16.4' (5m) long Connects program loader to Micro3

Program Loader Loader Cable Loader Adaptor Computer Link Cable Memory Card Expansion Cable 1:N Computer Link Interface Unit 1:N Computer Link Interface Cable 1:N RS232C/RS485 Converter 1:N RS232C/RS485 Converter 1:N PC Cable

5V power supply adaptor for using program loader when not connected to CPU Connects Micro3 or loader to PC (1:1 link), 6.56' (2m) Used with program loader to store user programs in SRAM memory Close proximity Micro3 link expansion, 9.84" (250mm) long One required to connect each Micro3 in a 1:N computer link system (all connected to one central RS232C/RS485 converter) One required to connect each Micro3 in a 1:N computer link system (connected to each interface unit), 32.8' (10m) long One required to connect all Micro3 units in a 1:N computer link system One required to connect all Micro3 units in a 1:N computer link system; Additionally, the DS783 should be used in applications requiring PC to Micro3 communications via modem Connects RS232C/RS485 converter to PC in a 1:N computer link system, 4.92' (1.5m) long (D-sub 9-pin female computer connector) 0 to 5V 0 to 10V 5V 4 to 20mA 10V 0 to 5V 0 to 10V 5V 4 to 20mA 10V Converts analog signals to digital and sends to input I0 of Micro3 (not for use with AC input type units) Converts digital (PWM) signal from output Q0 of Micro3 to analog (not for use with relay output type units)

HD9Z-C52 FC2A-AD1 FC2A-AD2 FC2A-AD3 FC2A-AD4 FC2A-AD5 FC2A-DA1 FC2A-DA2 FC2A-DA3 FC2A-DA4 FC2A-DA5 PFA-1U11 FC2A-SW6 FC2A-SW9 FC2A-SW14 WINDLDR

Analog Input Unit

Analog Output Unit Analog Timer Unit Input Switches WindLDR

For ne adjustment of analog timer preset value Input simulator switches (6) for 10 I/O Micro3s Input simulator switches (9) for 16 I/O Micro3s Input simulator switches (14) for 24 I/O Micro3s Windows-based application software, performs ladder programming and monitors all IDEC PLCs including the Micro series, FA series, and Open NET controllers.

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-83

Programmable Logic Controllers


Part Numbers: Micro3C Item Part Number FC2A-C24A1C AC Power (100 to 240V AC, 50/60Hz power supply) FC2A-C16A1C DC Power (24V DC, 19 to 30V DC) Program Loader
FC2A-C24A4C FC2A-C16A4C FC2A-HL1EC

Micro3 Series
Description 24 I/O (14 in, 10 out)

Base units: Input (24V DC sink/source) Relay output (240V AC/30V DC, 2A)
Version 2.0+; also compatible with Micro3C

16 I/O (9 in, 7 out) 24 I/O (14 in, 10 out) 16 I/O (9 in, 7 out)

Optional Item Loader Cable (2m) Loader Cable (2m) Modem Cable (3m) PC Interface Cable (3m) PC Interface Cable (2m) User Communication Cable (2.4m) PC Connect Cable (5m) Memory Card (RAM) AC Adaptor Expansion Cable (25cm) 1:N Link Adaptor RS232C Cable (4 lines, 1.5m) WindLDR

Part Number FC2A-KL3C


FC2A-KL4C FC2A-KM1C FC2A-KC4C FC2A-KC6C FC2A-KP1C HG9Z-XC183 FC2A-MC1 PSR-GA05005 FC2A-KE1 FC2A- MD1 HD9Z-C52 WINDLDR

Description Connects basic unit (loader port) and program loader


Connects basic unit (data link terminal) and program loader Connects basic unit (loader port) and modem (1:1 communications) Connects basic unit (loader port) and PC (1:1 communications) Connects basic unit (data link terminal) and PC (1:1 communications) Connects basic unit (loader port) and users equipment Connects basic unit (loader port) and Micro O/I Memory to store users programs (64K) Connects basic unit (data link terminal) and program loader/PC Connects basic unit and expansion function unit Connects basic unit (data link terminal) and PC Connects link adaptor and PC (1:N communications), D-sub 9-pin Windows-based application software, performs ladder programming and monitors IDECs Micro-1, Micro3, and Micro3C PLCs

J-84

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Micro3C I/O Expansion
9 Inputs 7 Outputs 1. These Micro3C expansions listed are examples. You may create your own combinations as well.

Micro3 Series

Micro3 and Micro3C Data Link A data link network is simple to3 set up. No special cables or junctions are required. Just wire up to 6 Micro s or Micro3Cs in a bus conguration, over a total distance of 656 (200m). Using a built-in data link, the master initiates communication automaticallyno special programming is required. Values from 2 read registers and 2 write registers are exchanged between the master and each slave.

16

24

14 Inputs 10 Outputs

Data link channel 19200, RS485 is xed.


3. The expansion link and data link cannot be used concurrently. 18 Inputs 14 Outputs Slave #1 Slave #2 Slave #3

32

40

23 Inputs 17 Outputs

Master Slave #6 Slave #5 Slave #4

48

28 Inputs 20 Outputs

Micro3 I/O Expansion

Micro3 and Micro3C Link with FA3S Master A high-performance FA3S CPU an PF3S-SIF4 interface module can manage data transfer with up to 6 Micro3s. Two interface modules can be used with each FA3S CP12 or CP13, making it possible to network up to 12 Micro3s total. Using a built-in data link, the master initiates communication automatically when executing a network communication program. Values from 2 read registers and 2 write registers are exchanged between the master and each slave.
Slave #1 Slave #2 Slave #3

10

6 Inputs 4 Outputs

2. These Micro3 expansions listed are examples. You may create your own combinations as well.

16

9 Inputs 7 Outputs

20

12 Inputs 8 Outputs Master: FA3S

J
Slave #6 Slave #5 Slave #4

24

14 Inputs 10 Outputs

26

15 Inputs 11 Outputs

32

18 Inputs 14 Outputs

34

20 Inputs 14 Outputs

40

23 Inputs 17 Outputs

48

28 Inputs 20 Outputs

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-85

Programmable Logic Controllers

Micro3 Series

WindLDR Software Solution One Application for All PLCs


WindLDR combines the logic of ladder programming with the intuitive approach of a Windows environment. IDEC provides the ideal PLC programming and monitoring solution. IDECs WindLDR includes all the advantages of our CLIP and CUBIQ software, plus a Window-based, graphic interface. With extensive new features such as an icon-driven toolbar, on-line help, cross reference cut and paste, program compass, line dialog screens, and debugging tools. At an enticingly low price, there is no questionWindLDR is the solution. Currently, WindLDR supports the programming conguration for IDECs Micro series. WindLDR is the bridge between older applications software/hardware and future generations of IDEC PLCs.
Tag Name Editor Advanced Instructions Multiplication (MUL)

Computer Link 1:1 Communication The Micro3 and Micro3C can be programmed from a PC using WindLDR ladder programming software. A computer link cable is required to connect the PCs RS232 serial port with the Micros programming port.

Micro3

Programming Port RS485

Computer Link Cable FC2A-KC2 7.87 (2m) long To RS232C Port Built-in RS232/RS485 Converter

Computer Link Cable FC2A-KC4C 9.84 (3m) long To RS232C Port To Loader Port (RS232C)

Micro3C

D-sub 9-pin Female Connector

Computer Link 1:N Communication (Micro3 only) A network of Micro3s can be set up for programming and monitoring with WindLDR. The network can also be used for supervisory control and data acquisition (SCADA). Up to 32 Micro3s can be networks with a PC as the master. Each Micro3 should be programmed with a specic device number in FUN9. FUN9 can be set with a program loader or with a PC in 1:1 mode running WindLDR.

RS232C/RS485 Converter HD9Z-T11 RS232 Cable HD9Z-C52 AC Adaptor or 24V DC P/S

N 32 Link Interface FC2A-LC1 Link Cable FC2A-KC3

Slave #1

Slave #2

Slave #3

Slave #N

J-86

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Computer Link 1:N Communication (Micro3C only)

Micro3 Series

To set up a 1:N computer link system, connect your PC to the RS232C/RS485 converter using RS232C cable HD9Z-C52. Connect the RS232C/RS485 converter to Micro3C units using shielded twisted pair cables. Supply power to the RS232C/RS485 converter by connecting a 24V DC source to terminals 6 and 7 or by plugging an AC adapter to the DC IN jack.

POWER SD

RS485
SERIAL PORT 1

RS232C/RS485 CONVERTER
Type FC2A-MD1

RS232C/RS485 Converter FC2A-MD1 (H x W x D) 5.92 x 4.33 x 1.34 (132 x 110 x 34mm)

RD

T
2 3

RS232C SERIAL PORT

A B
4

To RS232C Port

To RS232C Port

SG
5

FG
6

+
7

POWER SUPPLY 24V DC

DC IN

D-sub 25-pin Male Connector

RS232C Cable HD9Z-C52 4.92 (1.5m) long

D-sub 9-pin Female Connector

+
24V DC or AC Adapter (9V DC, 350 mA) 1st Unit Function selector switch: 0 Protocol selector switch: 2, 3, or 4 2nd Unit Function selector switch: 0 Protocol selector switch: 2, 3, or 4

J
A B SG A B SG

Shielded twisted pair cable 656 (200m) maximum Nth Unit (N32) Function selector switch: 0 Protocol selector switch: 2, 3, or 4 3rd Unit Function selector switch: 0 Protocol selector switch: 2, 3, or 4

A B SG

A B SG

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-87

Programmable Logic Controllers


Program Loader
Micro3 programs can be created or modied with the hand held program loader. The loader programs in Boolean commands and displays four lines. It can be programmed by using a PC or off line with a 5 volt adaptor (PSR-GA05005). The loader also can be used to monitor and change all internal registers including timers and counters. An optional SRAM memory card can also be used with the loader to store up to 31 programs with alphanumeric le names.

Micro3 Series

Display Program Key Control Switch Power Supply

4 lines 16 characters Back-lit LCD with auto turn-off 35 keys RUN/STOP for Micro operation From Micro through loader cable; From AC adaptor (5 to 6.5V DC, 4W) during off-line programming 1.5W Loader cable FC2A-KL1, 6.56' (2m) or FC2A-KL2, 16.4' (5m) Loader cable to RS232 loader port FC2A-KL3C Loader cable to RS485 data link port FC2A-KL4C Approximately 1 hour at 25C SRAM memory card stores up to 31 programs 0 to 50C Approximately 300g 7.283" 3.740" 1.181" (185 95 30mm)

Specifications

Power Consumption Connection to Micro3 Connection to Micro3C Connection to Micro3C Power Failure Protection User Program Storage Operating Temperature Weight Dimensions (HxWxD)

J
Micro3

Program Loader Cables for Micro3 and Micro3C Micro3C Micro3C

With Loader Cable FC2A-KL1 (2m) FC2A-KL2 (5m)

With Loader Cable 3C FC2A-KL3C The loader cable 3C has an RS232C/RS458 converter in the middle

With Loader Cable 4C FC2A-KL4C The loader cable 4C has a power supply box in the middle

Program Loader

AC Adapter (output: 5V DC) The loader cable 4C is not supplied with an AC adapter, which must be prepared by the user

FC2A-MC1 Optional memory card stores up to 31 programs

J-88

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Micro3C: Connecting the Modem through the Loader Port

Micro3 Series

To connect a modem to the loader port on the Micro3C, use the modem cable FC2A-KM1C. Set the protocol selector switch to 1 or 3 to select user protocol for the loader port.
Micro3C Modem Cable FC2A-KM1C 9.84 (3m) long To Loader Port (RS232C)

To RS232C Port Modem

D-sub 25=pin Male Connector

Cable Connector Pinouts Pin 1 2 3 4 5 6 7 8 20


FG TDX RXD RTS SG DCD DTR

Description
Frame Ground Transmit Data Receive Data Request to Send Signal Ground Data Carrier Detect Data Terminal Ready

Micro3C: Connecting RS232C Equipment through the Loader Port To connect equipment with an RS232C communication port to the loader port on the Micro3C, use the user communication cable FC2A-KP1C. One end of the user end communication cable 1C is not provided with a connector. It can be terminated with a proper connector to plug in to communicate with the RS232C port.
Micro3C User Communication Cable FC2A-KP1C 7.78 (2.4m) long To Loader Port (RS232C)

When the protocol selector switch is set to 1 or 3, the Micro3C can communicate with RS232C equipment through the loader port using the user protocol. When the protocol selector switch is set to 0, 2, or 4, the Micro3C can communicate through the loader port using the loader protocol.

RS232C Equipment
To RS232C Port

Attach a proper connector to the open end referring to the cable connector pinouts

Cable Connector Pinouts Pin 1 2 3 4 5 6 7 8 Cover


RTS DTR TDX RXD DSR SG SG NC

Description
Request to Send Data Terminal Ready Transmit Data Receive Data Data Set Ready Signal Ground Signal Ground No Connection Shield

AWG # #
28 28 28 28 28 28 26 26 Twisted Twisted

Color
Black Yellow Blue Green Brown Gray Red White


J-89

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Micro3C: User Communication TXD The system setup demonstrates a program to send data to a printer using the user communication TXD (transmit) instruction. Serial printers used in this example are Seiko Electronics DPU-201GS and Citizens iDP3110 printers.

Micro3 Series

System Setup

Protocol Selector Switch Set to 1 or 3 to select user protocol for the loader port
701 6 2 543

Micro3C

Printer User Communication Cable 1C FC2A-KP1C 7.87 (2.4m) long

To RS232C Port

To Loader Port (RS232C)

Attach a connector to the open end of the user communication cable 1C referring to the cable connector pinouts shown below

Cable Connections for Seiko Electronics DPU201GS Mini DIN Connector Pinouts Description
Shield NC NC TXD No Connection No Connection Transmit Data No Connection Data Set Ready Signal Ground Signal Ground No Connection Black Yellow Blue Green Brown Gray Red White

D-Sub 9-pin Connector Pinouts Color Pin Cover 1 2 3 4 5 6 7 8 Pin Description


NC NC DATA NC GND NC NC BUSY NC No Connection No Connection Receive Data No Connection Ground No Connection No Connection Busy Signal No Connection

1 2 3 4 5 6

NC DSR SG SG NC

7 8 9

J-90

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


CPU Input/Output

Micro3 Series

Key features of the Micro3 and Micro3C input include: AC or DC inputs (Micro3) or DC inputs (Micro3C) Expandable from 10 to 48 I/O points Congure inputs: Sink or source for NPN or PNP devices Each unit selectable: CPU or expansion I/O LED indicators Optical isolation

DC Input Rated Input Voltage (allowable range) Rated Input Current Input Impedance On/Off Current On/Off Voltage On/Off Time
24V DC (19 to 30V DC) 7mA (input I/0: 13mA) 3.3k (input I/0: 1.8k) On: 2.5mA (minimum) at 11V DC Off: 1.2mA (maximum) On: 11V DC (minimum) Off: 5V DC (maximum) Depends on input lter setting (see note)

AC Input (Micro3 only)


100 to 120V AC (85 to 132V AC) 10mA/point 13k On: 4mA (minimum) at 79V AC Off: 2mA (maximum) On: 79V AC (minimum) Off: 20V AC (maximum) On: 20ms (maximum) Off: 20ms (maximum)

Input Specifications

10 I/O (Micro3 only) 16 I/O

4 outputs: Independent NO = 1 point, Common NO = 3 points 7 outputs: Independent NO = 1 point Common NO = 2 points + 4 points 10 outputs: Independent NO = 2 points Common NO = 4 points + 4 points 7 outputs: Independent NO = 3 points Common NO = 4 points Independent contact: 240V AC or 30V DC, 2A (resistive load) Common contact: 240V AC or 30V DC, 2A output points (resistive load) 5V DC, 1mA (reference value) 30m maximum (initial value) Mechanical: 20,000,000 operations (no load) at 1,800 operations/hour Electrical: 100,000 operations (rated load) at 1,800 operations/hour

Relay Output Specifications

Configuration 24 I/O AC in (Micro3 only) Switching Capacity Minimum Applicable Load Contact Resistance Life Ratings

Each unit can be used as a CPU or expansion I/O using a selection switch. Sink/source inputs can be used with NPNor PNP-output sensors. Input on and off times can be selected using the input lter function (FUN7 setting).

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-91

Programmable Logic Controllers


DC Input Circuit Diagrams

Micro3 Series

Using Sensor P/S


Sensor
100 to 240V AC 100 to 240V AC

L N G D GN

24V 0V

CO

C 0 M

1 2 3 4 5

L N G D GN

24V 0V

C 0

1 2 3 4 5

CO

Using External P/S GND


100 to 240V AC

24V DC +
L N G D GN

GND
100 to 240V AC

24V DC

24V 0V

CO

C 0 M

1 2 3 4 5

L N G D GN

24V 0V

CO

C 0 M

1 2 3 4 5

DC Inputs (DC power)

External Power 24V DC +

GND

GND
External Power 24V DC

+ + G D GN
NC NC

G D GN

NC NC

CO

C 0 M

1 2 3 4 5

CO

C 0 M

1 2 3 4 5

AC Inputs (Micro3 only)

GND 100 to 240V AC

100 to 120V AC

L N G NC NC C 0 D M GN CO

2 3

J
Transistor Outputs (Micro3 only) +
CO M

Transistor and Relay Output Circuit Diagrams

0 1

2 3

CO

4 5 6 +V

+ +

CO

0 1

2 3

CO

4 5 6 -V

External Power 24V DC

L L

L L

L L

External Power 24V DC

L L

L L

L L

Relay Outputs
CO
C0

10 I/O
M CO M

0 1

C1

External Power 240V AC/30V DC 2A x Output Points

L L

16 I/O
CO
C0

24 I/O
CO
C0

0 1

2 3

CO
C1

4 5

CO
C2

0 1

2 3

CO
C1

4 5 6 7

C2

M M CO CO 10 C3 11

L L L L L L L L L

L L

L L

L L

J-92

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Sensor

DC Inputs (AC power)

GND

GND

Programmable Logic Controllers


CPU: Transistor Output (Micro3 only)

Micro3 Series

10 I/O

16 I/O

24 I/O

DC Input Specifications

Rated Input Voltage (allowable range) Rated Input Current Input Impedance On/Off Current On/Off Voltage On/Off Time 10 I/O 16 I/O 24 I/O

24V DC (19 to 30V DC) 7mA (input I0: 13mA) 3.3k (input I0: 1.8k) On: 2.5mA (minimum) at 11V DC Off: 1.2mA (maximum) On: 11V DC (minimum) Off: 5V DC (maximum) Depends on input lter setting (see note)

Transistor Output Specifications

4 outputs: Common NO = 4 points


7 outputs: Common NO = 3 points + 4 points 10 outputs: Common NO = 5 points + 5 points 0.5A, 24V DC Maximum: 0.625A/circuit (30V DC) 5A, 1ms (maximum) 0.1mA (maximum) Sink: 1.5V DC (maximum) On: 500s (output Q0: 5s), Off: 500s (output Q0: 5s) 24V DC, 100mA (maximum)

Configuration Rated Load Inrush Current Leakage Current On Voltage On/Off Time

External Current Draw

Each unit can be used as a CPU or expansion I/O using a selection switch. Sink/source inputs can be used with NPNor PNP-output sensors. Input on and off times can be selected using the input lter function (FUN7 setting).

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-93

Programmable Logic Controllers


Analog Input/Output Units
Key features of the analog input and output units include: Micro supports one analog in and one analog out Input/output units accept a variety of signals Units connect to input and/or output
Analog output is only available for the Micro3.

Micro3 Series

AD Converter Unit Number of Inputs Resolution Total Accuracy Conversion Time Maximum Applicable Input Maximum Applicable Output Output Short Circuit Recommended Output Load Impedance Input Frequency Output Ripple
1 channel 250 (see chart below) 1% of the maximum value 125ms 16V DC 30V DC Not allowed 1 channel

DA Converter Unit
245 (see chart below) 1% of the maximum value 0 to 95%: 500ms 30V DC Voltage output: 12V DC Current output: 12V DC or 0.6V DC Allowed (innite period of time) Voltage output: 5k or more Current output: 250 or less (300 maximum) 312.5Hz (PWM mode must be set to MODE3) 1 LSB or less

J
Analog/Digital Conversion Charts A/D Converted Value Type
249 250 Increments 0 Minimum Input

Specifications

Input Signal Range


0 to 5V DC 0 to 10V DC

AD
Maximum

5V DC 4 to 20mA DC 10V DC 0 to 5V DC

D/A Converted Value DA


Maximum 245 Increments Minimum 0 5 PWM Operand S1 249

0 to 10V DC 5V DC 4 to 20mA DC 10V DC

J-94

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Analog Input and Wiring Diagrams (Micro3 and Micro3C)

Micro3 Series

The A/D converter unit is used with the Micros to perform an 8-bit A/D conversion. The A/D converter unit reads an analog input signal from an analog output device such as an analog distance sensor. The output from the A/D converter unit is entered to the Micro input I0 and converted into a digital value (0 through 249) using the A/D (analog/digital conversion) instruction. If the input to the A/D converter unit exceeds the input range, then an overow occurs, and 250 is set to the destination operand of the A/D instruction. Only one A/D converter unit can be connected to the Micro base unit.
When the A/D converter unit is connected to the Micro, the HSC (high-speed counter) function cannot be used.

Source Input

24V DC + Power FG

3A Fuse
+

When using the Micro in the source input connection, select the sink output from the A/D converter unit.
24V DC

A/D UNIT
INPUT 4-20mA SINK SCE POWER

Set the output selector switch to SINK.

NPN

INPUT OUTPUT
ANALOG WIRE TO + IN 0

DC OUT 24V 0V

DC IN COM

Analog Input Shield Wire

Sink Input

24V DC + Power FG

3A Fuse
+

24V DC

A/D UNIT
INPUT 4-20mA SINK SCE POWER

When using the Micro in the sink input connection, select the source output from the A/D converter unit. Set the output selector switch to SCE.

PNP

INPUT OUTPUT
ANALOG WIRE TO + IN 0

DC OUT 24V 0V

DC IN COM

Analog Input Shield Wire

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-95

Programmable Logic Controllers


Analog Output and Wiring Diagrams (Micro3 only) The D/A converter unit is used with the transistor output type Micro3 base unit to perform an 8-bit D/A conversion. The pulse width modulation instruction is used to convert the 3 digital value to a pulse output signal. The output from the Micro output Q0 is entered to the D/A converter unit to generate an analog current or voltage output to control an inverter. Only one D/A converter unit can be connected to the Micro3 base unit.

Micro3 Series

Transistor Sink Output


When using a transistor sink output type Micro3 base unit, select the source input to the D/A converter unit.
+

Ground the FG terminal.

24V DC

D/A UNIT
OUT COM0()

OUT COM1()

+V

OUTPUT 4-20mA POWER

SCE SINK

Set the input selector switch to SCE.

OUTPUT

INPUT

ANALOG WIRE TO + OUT 0

FG + 24V DC Power Shield Wire

1A Fuse

Analog Output

Transistor Protection Source Output form Micro3

J
Ground the FG terminal.
+

When using a transistor protect source output type Micro3 base unit, select the sink input to the D/A converter unit.

24V DC

D/A UNIT
OUT COM0(+)

OUT COM1(+)

OUTPUT 4-20mA POWER

SCE SINK

OUTPUT

INPUT

Set the input selector switch to SINK.

ANALOG WIRE TO + OUT 0

1A Fuse Analog Output FG + 24V DC Power Shield Wire

J-96

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Instruction Set Steps
1 1 1 1 1 1 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 2 2 2

Micro3 Series

Instruction
AND AND LOD ANDN BPP BPS BRD CNT CC= CC END JEND JMP LOD LODN MCS MCR NOT OR OR LOD ORN OUT OUTN RST SET SFR SFRN SOTD SOTU TIM TM TMS

Description
And And load And not Bit pop Bit push Bit read Counter Counter compare = Counter compare End Jump end Jump Load Load not Master control set Master control reset Not Or Or load Or not Output Output not Reset Set Shift register Shift register not Single output falling Single output rising 100ms timer 10ms timer 1ms timer 1

Steps
34 34 56 56 45 45 45 45 45 45 45 45 45 45 45 45 45

Instruction
0 11 12 13 14 21 22 23 24 25 26 31 32 33 34 41 42 43 51 52 53 54 71 72 73 74 75 81 82 83 84 91 92 93 A1 A2 A3 A4 B1 B2 B3 NOP MOV MOVN IMOV IMOVN CMP= CMP<> CMP< CMP> CMP<= CMP>= ADD SUB MUL DIV ANDW ORW XORW SFTL SFTR ROTL ROTR CALR CALW CLKR CLKW ADJ DISP DGRD ANR0 ANR1 PULS PWM A/D HSC0 HSC1 HSC2 HSC3 TXD RXD COMP2

Description
No operation Word move Word move not Word indirect move Word indirect move not Equal compare Not equal compare Less than compare Greater than compare Less than or equal compare Greater than or equal compare Addition Subtraction Multiplication Division And word Or word Exclusive or word Shift left Shift right Rotate left Rotate right Calendar read* Calendar write* Clock read* Clock write* Adjust* Display Digital switch read Analog potentiometer 0 read Analog potentiometer 1 read* Pulse output Pulse width modulation Convert analog to digital H/S counter 0 (32 bits) H/S counter 1 (32 bits) H/S counter 2 (32 bits) H/S counter 3 (16 bits) Transmit (Micro3C only) Receive (Micro3C only) Double word compare (Micro3C only)

Basic Instructions

Advanced Instructions

3 3 3 3 2 2 2 2 1 4 4 2 2 3 3 2 4 2 4 2 5 404 5 404 45

Instructions designated by * are not affected by the change to the year 2000.

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-97

Programmable Logic Controllers


Dimensions

Micro3 Series

Micro3 and Micro3C Base Units

Mounting Hole Layout

C 3.031" (77mm) 3.346" (85mm) M4 tapped or 0.177" ( 4.5mm)

W 2.362" (60mm)

A/D and D/A Analog Converters

Program Loader
3.740" (95mm) 2.76" (70mm) 1.181" (30mm)

1.38" (35mm)

1.77" (45mm)

0.17" (4.3mm) 2 holes

2.76" (70mm)

3.15" (80mm) 7.283" (185mm)

J
3.150" (80mm) 0.984" (25mm)

Key to Dimensions AC Input Units 10 I/O 16 I/O 24 I/O* W


4.134" (105mm) 5.315" (135mm) 6.496" (165mm)

C
3.386" (86mm) 4.567" (116mm) 5.748" (146mm)*

*Dimensions are the same for the 16 I/O AC input unit.

J-98

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Micro-1:The Original Micro-PLC
Key features of the Micro-1 PLC include: Intelligent control economically replaces hard-wired systems 8 inputs, 6 outputs DC inputs, relay or transistor outputs Expansion unit doubles I/O (16 inputs, 12 outputs) Micro-expansion I/O for incremental I/O increases 80 timers, 47 counters, 160 internal relays CPU base unit supplies power for input signals Program capacity 600 steps Computer link, networking Programming Available Instructions Program Capacity Memory Scan Time Input Output Total I/O Points Internal Relay Special Internal Relay Shift Register Catch Input Single Shot Output Timer Counter Reversible Counter Computer Link External Control Input Power Failure Protection Self-Diagnostics Auto Start Function FA Series Compatibility
Boolean or ladder logic 15 basic instructions, 2 FUN instructions 600 steps EEPROM memory built-in to base unit Average: 8s per basic instruction Base unit: 8 points, Expansion: 8, 4, or 2 points Base unit: 6 points, Expansion: 6, 3, or 2 points 28 points (maximum) 160 points (all points can be maintained) 96 points 128 points 1 point, 0.5ms pulse 96 points 80 points, subtracting (0 to 999.9s) 45 points, adding (0 to 9999) (all points can be maintained) 2 points (all points can be maintained) Via RS232 interface unit Start/stop using switch on program loader Capacitor back-up: 3 days; internal relay, shift register, counter, reversible counter CPU error (WDT), CRC error, check sum error, communication error Operation starts after power-up Program loaders are interchangeable using special cables The CPU base unit supplies power to the micro-expansion units and program loader. Micro-expansion units are not compatible with 12V DC CPU. CE Certied EMC Approved File No. E951113332321 UL Listed File No. E102542 CSA Certied File No. LR66809

Micro-1 Series

General Specifications

Rated Supply Voltage Voltage Range

AC CPU base unit and (8 in/6 out) expansion: 100 to 240V AC, 50/60Hz (47.563Hz) 24V DC base unit and all expansion units: 12V DC CPU base unit and (8 in/6 out) expansion AC: 85 to 110% of rated voltage 24V DC: 80 to 120%; 12V DC: 70 to 120% Between power or I/O terminal and ground: 1,500V AC, 1 minute Between power or I/O terminal and ground: 10M (500V DC megger) Operating: 0 to +55C; Storage: 20 to +70C 45 to 85% RH (avoid condensation) 5 to 55Hz, 6G for 2 hours in each of 3 axes 30G, 3 shocks in each of 3 axes Between power or I/O terminal and ground: AC: 1.3kV, 1s; 24V DC: 1.0kV, 1s; 12V DC: 500V, 1s 100 (maximum) 35mm DIN rail and panel mount

Electrical Specifications

Dielectric Strength Insulation Resistance Temperature Operating Humidity Vibration Resistance Shock Resistance Noise Resistance Ground Resistance Mounting Style

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-99

Programmable Logic Controllers


Part Numbers: Micro-1 CPU Base Unit Relay Output AC Transistor Output
Source Input Sink Input Source Input/Sink Output Sink Input/Source Output Source Input FC1A-C1A1E FC1A-C2A1E FC1A-C1B1E FC1A-C2C1E FC1A-C1A4E FC1A-C1A2E FC1A-C2A4E FC1A-C2A2E FC1A-C1B4E FC1A-C1B2E FC1A-C2C4E FC1A-C2C2E FC1A-E1A1E FC1A-E2A1E FC1A-E1B1E FC1A-E2C1E FC1A-E1A4E FC1A-E1A2E FC1A-E2A4E FC1A-E2A2E FC1A-E1B4E FC1A-E1B2E FC1A-E2C4E FC1A-E2C2E

Micro-1 Series

Relay Output
Sink Input

DC
Source Input/Sink Output

Transistor Output
Sink Input/Source Output

Power: 100240V AC; NPN transistor inputs, relay outputs Power: 100240V AC; PNP transistor inputs, relay outputs Power: 100240V AC; NPN transistor inputs, NPN transistor outputs Power: 100240V AC; PNP transistor inputs, PNP transistor outputs Power: 24V DC; NPN transistor inputs, relay outputs Power: 12V DC; NPN transistor inputs, relay outputs Power: 24V DC; PNP transistor inputs, relay outputs Power: 12V DC; PNP transistor inputs, relay outputs Power: 24V DC; NPN transistor inputs, NPN transistor outputs Power: 12V DC; NPN transistor inputs, NPN transistor outputs Power: 24V DC; PNP transistor inputs, PNP transistor outputs Power: 12V DC; PNP transistor inputs, PNP transistor outputs Power: 100240V AC, NPN transistor inputs, relay outputs Power: 100240V AC, PNP transistor inputs, relay outputs Power: 100240V AC; NPN transistor inputs, NPN transistor outputs Power: 100240V AC; PNP transistor inputs, PNP transistor outputs Power: 24V DC, NPN transistor inputs, relay outputs Power: 12V DC, NPN transistor inputs, relay outputs Power: 24V DC, PNP transistor inputs, relay outputs Power: 12V DC, PNP transistor inputs, relay outputs Power: 24V DC, NPN transistor inputs, NPN transistor outputs Power: 12V DC, NPN transistor inputs, NPN transistor outputs Power: 24V DC, PNP transistor inputs, PNP transistor outputs Power: 12V DC, PNP transistor inputs, PNP transistor outputs

Expansion I/O Relay Output Transistor Output


Source Input Sink Input Source Input/Sink Output Sink Input/Source Output Source Input

Relay Output
Sink Input Source Input/Sink Output

Transistor Output
Sink Input/Source Output

Accessories Program Loader Data Preset Loader


Standard Multi-Function FC1A-HL1E FC1A-PL1E FC1A-PL2E FC1A-KL1A FC1A-KL2A FC1A-KL3A FC1A-KL4A FC1A-KE1 PFA-1A* FC1A-M1XE FC1A-M2XE FC1A-MXAE FC1A-M1BE FC1A-M2CE FC1A-KM* FC1A-SM1E FC1A-KS*A 24 keys, 16-character LCD Change timer/counter presets, monitor I/O, internal relay, timer, counter Change preset values, monitor, direct set/reset, read program, and more 5' (1.5m), connects program loader to base unit 2.75" (70mm) curl cord (attached to loader) 5' (1.5m), connects FA series program loader to Micro-1 base unit 5' (1.5m), connects Micro-1 program loader to FA series CPU 1.57" (40mm) (attached to expansion unit) *21: 19.7" (0.5m), 22: 29.53" (0.75m), 23: 39.37" (1m) 4-point source input 4-point sink input 3-point relay output 2-point source input, 2-point sink output 2-point sink input, 2-point source output *1: 19.7" (0.5m), 2: 39.37" (1m) 8 inputs and 8 outputs with serial cable (order FC1A-KS*A separately) *1: 39.37" (1m), 2: 78.74" (2m), 3: 118.11" (3m) Connect serial I/O module to CPU base unit (with shield terminal one end) 20-pin interface to discrete terminal blocks (simplify installation of serial I/O) FC1A-TA1 PSR-AD07*E FC1A-PD1 PF2-CLA FC1A-KC1A PFA-1A54A WINDLDR MM-MICRO-1 Contains 4 analog timers (8 time ranges from 1 second to 10 minutes) *12: 12V DC, 0.63A output, 24: 24V DC, 0.32A output To mount a serial I/O module and digital displays such as IDECs DD33 series Interface PC to Micro-1 CPU base unit for 1:1 communication 5.91" (150mm) curl cord: CPU base unit to PFJ-U11, PFJ-U21, or PF2-CLA 78.74" (2m), connects PC to PFJ-U12, PFJ-U22, or PF2-CLA Windows-based programming software Micro-1 PLC, WindLDR software, computer link cable Connect expansion unit to base unit

Loader Extension Cable

I/O Expansion Cable

Micro Expansion Unit Micro Expansion Cable Serial I/O Module Serial Cable Serial I/O Transition Analog Timer Unit External Power Supply Digital Display Mother Board Link Adaptor Cable FC Link Cable Computer Link Cable Software Micro-1 Starter Kit

J-100

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


Flat-Pak Modular
Key features of the FA2J at-pack modular include: 6ms/K processing Up to 128 inputs, 128 outputs DC inputs, relay or transistor outputs Low prole for shallow panels 8-bit or 12-bit analog input, multiplexer Replaceable relays Memory: 1K, 4K High-speed counter Computer link, networking
UL Listed File No. E102542 CSA Certied File No. LR66809

FA2J Series

Programming Available Instructions Capacity Memory Processing Input Output Total I/O Internal Relay Special I/R Shift Register Single Shot Output 10ms Timer Counter

Boolean or ladder logic 15 basic, 57 advanced instructions [FA1J: 27 advanced instructions] 964 steps (1K memory) 3,300 steps (4K memory) 1K, 4K CMOS-RAM (with battery) 4K EEPROM 6ms per 1K (basic instructions) [FA1J: 32ms per 1K] 128 points (maximum) 128 points (maximum) 256 points (maximum) 608 points (240 can be maintained) [FA1J: 240 points; all can be maintained] 16 points 128 points (all can be maintained) 96 points 80 points, subtracting, 0 to 999.9s 80 points [FA1J: not available] 45 points, adding, 0 to 9,999 (all can be maintained) 2 points (all can be maintained) 400 points (all can be maintained) [FA1J: 100 points; all can be maintained] RS-232 link adaptor Start: input 0; Stop and reset: function settings Internal relay, shift register, counter, reversible counter, data register CPU error (WDT), communication error, CRC error in user programs, operation code error After power-up, automatic run state using function setting 100 to 240V AC 50/60Hz; Allowable: 85 to 110% of rated voltage; 24V DC 20% (ripple 10% maximum) Between power or I/O terminal and ground: 1,500V AC, 1 minute (500V AC for analog lines) Between power or I/O terminal and ground: 10M (500V DC megger) Operating: 0 to +55C; Storage: 20 to +70C 45 to 85% RH (avoid condensation) 2G, 1 hour in each of 3 axes 10G Between power or I/O terminal and ground: 1.3kV p-p, 1s (1kV DC pulse generator) 100 (maximum) Panel mount

Specifications

Reversible Counter Data Register Computer Interface External Control Power Failure Protection Diagnostics Auto Start Rated Voltage Dielectric Strength Insulation Resistance Temperature Operating Humidity Vibration Resistance Shock Resistance Noise Resistance Ground Resistance Mounting Style

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-101

Programmable Logic Controllers


Part Numbers: FA2J Item
AC

FA2J Series
Description
FA2J CPU; power: 100 to 240V AC FA1J CPU; power: 100 to 240V AC FA2J CPU; power: 24V DC FA1J CPU; power: 24V DC Internal power supply for I/O expansion (100 to 240V AC) Internal power supply for I/O expansion (24V DC) External power supply for DC inputs, sensors (24V DC/0.5A) For installing two I/O modules Mount CPU or expansion power, plus piggyback mounting capacity for two I/O modules (order one PFJ-EB1 separately) Mount two I/O modules, plus piggyback mounting capacity for two more I/O modules (order two PFJ-EB1s parts separately) 24V DC NPN transistor inputs 24V DC PNP transistor inputs 100 to 120V AC inputs, standard response 100 to 120V AC inputs, fast response 200 to 240V AC inputs, standard response 200 to 240V AC inputs, fast response 24V DC NPN transistor inputs 5V DC NPN transistor inputs 24V DC PNP transistor inputs 0 to 10V DC inputs, 8-bit resolution, fast response 0 to 10V DC inputs, 8-bit resolution, standard response 4 to 20mA DC inputs, 8-bit resolution, fast response 4 to 20mA DC inputs, 8-bit resolution, standard response 0 to 10V DC analog input, 1 point, 12-bit resolution 1 to 5V DC analog input, 1 point, 12-bit resolution 4 to 20mA DC analog input, 1 point, 12-bit resolution Analog multiplexer module, 4 points, voltage Analog multiplexer module, 4 points, current 1NO contact, rated load 110V AC, 5A; 220V AC, 2A Rated load 12 to 48V DC, 1A per point Rated load 100 to 240V AC 1A per point Rated load 12 to 28V DC, 0.5A per point Rated load 5 to 12V DC, 20mA per point Rated load 12 to 28V DC, 50mA per point Rated load 12 to 28V DC, 0.5A per point 0 to 10V DC output, 8-bit resolution 4 to 20mA DC output, 8-bit resolution Program loader with built-in PROM burner 59" (1.5m) not included with program loader 4K EEPROM (compatible with FA3S) 1K CMOS-RAM (compatible with FA3S) 4K CMOS-RAM (compatible with FA3S) Single-phase, for high-frequency inputs Two-phase, for quadrature rotary encoder inputs Occupies unused slot on base plate Link adaptor for 1:1 communications to IBM-compatible PC Link for 1:N communication (use with twisted-pair cable) Main unit for 1:N communication (use with twisted-pair cable) Link cable, FA series CPU to link adapter 12 (300mm) Link cable, PC to link adapter, 78.74 (2m) Ladder diagram software for programming and monitoring

Part Number
PF2J-CPU1E PFJ-CR1E PF2J-CPU1DCE PFJ-CR1DCE PFJ-PS1 PFJ-PS1DC PFJ-PU2 PFJ-EB1 PFJ-DP1 PFJ-DP2 PFJ-N081 PFJ-N082 PFJ-N083 PFJ-N083A PFJ-N084 PFJ-N084A PFJ-N161 PFJ-N161A PFJ-N162 PFJ-N012 PFJ-N012A PFJ-N013 PFJ-N013A PFJ-N112A PFJ-N113A PFJ-N114A PFJ-4MPV PFJ-4MPI PFJ-T081 PFJ-T082 PFJ-T083 PFJ-T162 PFJ-T162A PFJ-T162B PFJ-T162C PFJ-T012 PFJ-T013 PF2-2H4RE PFA-1A11 PFA-1M14 PFA-1M21 PFA-1M24 PFA-N011A PFA-N011B PFJ-DM PF2-CLA PFJ-U21 PFJ-U22 PFA-1A51 PFA-1A54A CLIP

CPU
DC AC DC External Base Plate Double-Stack Expansion 8-Point DC Transistor (source) Transistor (sink) 100V AC

Power

Expansion

Input

8-Point AC 200V AC 16-Point DC Transistor (source) Transistor (sink) Voltage 8-Bit

Analog Input
12-Bit

Current Voltage Current Voltage Current Relay Transistor (sink) SSR Transistor (sink) Transistor (source) Voltage Current Loader Extension Cable

Multiplexer

12-Bit Analog Input 8-Point

Output

16-Point Transistor Analog

Program Loader Memory Packs


(see details on page J-103)

High Performance Input Blank Module

High-Speed Counter

Computer Interface

J-102

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


FA3S: The Powerhouse

FA3S Series

UL Listed File No. E102542 CSA Certied File No. LR66809 CE Certied EMC Approved* File No. E9960513332 *Some modules excepted

Key features of the FA3S include: Up to 256 local I/O points Up to 1,024 ber optic remote I/O points, from up to 3,280 (1km) away 8-channel analog module RS232 and RS485 modules available Modem communications Real-time clock and calendar available High-speed interrupt I/O (16 or 32 points) Average Boolean scan: 0.3ms/K Up to 8K program steps Built-in programming/ASCII port

Standard CPUS Available Instructions Program Capacity Memory Average Scan Time Input Output Total I/O Points Internal Relay Special Internal Relay Shift Register Single Shot Output Timer 10ms Timer Counter Reversible Counter Data Register Forced I/O Remote I/O Runtime Program Modify Real-Time Clock/Calendar Runtime Program Protection High-Performance Modules External Control Power Failure Self-Diagnostics Auto Start Function
15 basic, 57 advanced CP11T: plus 6 clock and protect instructions CP11: 964 steps (1K memory) 3,300 steps (4K memory) CP11T: 3,300 steps (built-in EEPROM) CP11: 1K and 4K CMOS-RAM (with battery); 4K EEPROM; 4K EPROM CP11T: Built-in 4K EEPROM memory 6s per basic instruction 128 points (maximum) 128 points (maximum) 256 points 608 points (240 points can be maintained) CP11: 16 points; CP11T: 18 points 128 points 96 points 80 points, subtracting (0 999.9s) 80 points 45 points, adding (0 9,999) (all points can be maintained) 2 points (all points can be maintained) 400 points (all points can be maintained) Not available Not available Not available Available on CP11T only Available on CP11T only High-speed counter (PF3S-HSC2)

High-Performance CPU
15 basic 122 advanced 964 steps (1K memory) 4,036 steps (4K memory) CP13: 8,072 steps (8K memory) 1K and 4K CMOS-RAM (with battery); 4K EEPROM CP13: 8K CMOS-RAM or EEPROM 0.3s per basic instruction I/O congurable I/O congurable 256 points 1,024 points (240 points can be maintained) 32 points 224 points 256 points 256 points 80 points 100 points, adding (0 9,999) (all points can be maintained) 2 points (all points can be maintained) 1,000 points (all points can be maintained) Available (50 points simultaneously) 1,024 points (plus 256 points basic capacity) Available Not available Available High-speed counters (PF3S-HSC1 and -HSC2), high-speed interrupt I/O, remote I/O, RS232, RS485

General Specifications

Start: input 0 (release possible); Stop/reset: function designated Protected: Internal relay, shift register, counter, reversible counter, data register CPU error (WDT), communication error, CRC error in user programs, operation code error After power-up, automatic run, function designated

The FA2 loader (PF2-2H4RE) and FA3 loader (PF3S-HL161E) are compatible with all FA series PLCs and the Micro-1.

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-103

Programmable Logic Controllers


Part Numbers: FA3S Series Standard CPU Standard CPU with Clock Protection High-Performance CPUs In: 16-Point Transistor In: 32-Point Transistor In: 16-Point AC In: 8 Channel Analog Input In: Analog Multiplexer Combination I/O Out: 8-Point Relay Out: 16-Point Relay Out: 16-Point SSR Out: 16-Point Transistor Out: 32-Point Transistor Out: Analog High-Speed Counter High-Speed I/O Serial Interface Remote I/O Master Remote I/O Slave AC Power Supply (standard) AC Power Supply (large capacity) DC Power Supply External Power Supply Backplane 2 slot Backplane 3 slot PF3S-CP11 with program loader
PF3S-CP11T with program loader PF3S-CP12, -CP13 with program loader PF3S-N16B PF3S-N32B, -N325B PF3S-N16A1, -N16A2 PF3S-AD8B1, -AD8B2 PF3S-AD121, -AD122 PF3S-MP41 PF3S-M32K, -M325K PF3S-R081 PF3S-R161 PF3S-S161 PF3S-T16K, -T16S PF3S-T32K, -T325K, -T32S PF3S-DA121 PF3S-HSC1, -HSC2 PF3S-HSL1 PF3S-SIF2 PF3S-SIF4 PF3S-RMP1, -RMQ1 PF3S-RTP1, -RTQ1 PF3S-PSA1 PF3S-PSA2 PF3S-PSD1 PF3S-EPA1 PF3S-BP12 PF3S-BP13

FA3S Series

130mA 480mA
80mA 430mA 120mA 470mA 80mA 160mA 90mA 150mA 40mA 60mA 190mA 170mA 330mA 280mA 130mA 240mA 40mA 30mA 200mA 60mA 110mA 180mA 250mA 50VA 85VA 32W 85VA

Power Requirements

The power requirements listed are maximums. For input modules, all inputs are on. For output modules, all outputs are on. For combination I/O modules, all inputs and outputs are on.

J-104

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Programmable Logic Controllers


WindLDR Programming Software

Programming Software

Where Logic and Intuition Converge WindLDR, IDECs Windows-based, Ladder programming tool successfully combines logic and intuition. IDECs WindLDR includes a graphic interface, icondriven tool bar, on-line help, and debugging tools. In its rst release, WindLDR programs the Micro-1, Micro3, Micro3C, FA Series, ONC and MicroSmart. WindLDR is your icon-driven, multi-window, all-inclusive tool. Key features of the WindLDR software package include: Use the Tag Editor to access and edit all coil data in one convenient option Customize toolbars, ladder le characteristics, and more Access the most common commands with the context-sensitive right mouse button Open and use unlimited ladder les Monitor and de-bug PLC functionality on-line Edit ladders simply, with a drag and drop toolbar

Cut and Paste Function Tag Editor Customization Right Mouse Button On-Line Monitoring

Select one rung or multiple rungs Access and edit all coil data in one convenient option For toolbars, ladder le characteristics, and many program features Context-sensitive for convenient access to most commonly used commands De-bug and observe real-time PLC functionality, right from your PC. Write new values to counters, timers, and data registers. Open unlimited ladder les to compare and reuse instantly, even if they are written for different PLCs User friendly toolbar makes ladder creation and editing simple Searches for text in various ways; large ladder les are easy to manage Limited only by available memory Fully compatible for upgrade Context-sensitive; extensive coverage of WindLDR and PLC functionality The WindLDR Tutorial provides a quick, simple way to get up and running; the comprehensive WindLDR Reference Manual answers basic through advanced questions IDEC engineers maintain an excellent level of customer service and software support Microsoft Windows 95, 98, 2000, Me, NT 4.0 CPU: Pentium 75MHz or higher; 24MB available RAM on Win95 and Win98; 32MB available RAM on Win2000, NT 20MB free hard disk space CD-ROM

General Specifications

Multiple Ladder Files Drag and Drop Find String Multi-Level Undo CLIP and CUBIQ On-Line Help Manuals Support Platforms System Requirements

Tag Name Editor

Tag Name Editor

Installation Software

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-105

Programmable Logic Controllers


Programming Instruction Set

Programming Software

MicroSmart

Micro-3C

Micro-3

ONC

Instruction Set Basic Instruction List AND And ANDLOD And load ANDN And Not BPP Bit Pop BPS Bit Push BRD Bit Read CC= Counter Comparison (=) CC Counter Comparison () CDP Dual Pulse Reversible Counter CNT Counter DC= Data Register Comparison (=) DC Data Register Comparison () END End JEND Jump End JMP Jump LOD Load LODN Load Not MCR Master Control Reset MCS Master Control Set OR Or OR LOD Or Load ORN Or Not OUT Output OUTN Output Not RST Reset SET Set SFR Shift Register SFRN Shift Register Not SOTD Single Output Down SOTU Single Output Up TIM Timer Advanced Instruction List Group Symbol NOP NOP MOV MOVN IMOV Move IMOVN BMOV IBMV IBMVN CMP= CMP<> CMP< Data CMP> Comparison CMP<= CMP>= ICMP>= ADD SUB Binary MUL Arithmetic DIV ROOT ANDW Boolean ORW Computation XORW SFTL SFTR Shift and BCDLS Rotate WSFT ROTL ROTR

Instruction Set Advanced Instruction List, continued HTOB Hex to BCD BTOH BCD to Hex HTOA Hex to ASCII ATOH ASCII to Hex BTOA BCD to ASCII ATOB ASCII to BCD ENCO Encode DECO Decode BCNT Bit Count ALT Alternate Output WKTIM Week TImer WKTBL Week Table DISP Display DGRD Digital Read TXD Transmit RXD Receive LABEL Label LJMP Label Jump LCAL Label Call LRET Label Return IOREF I/O Refresh DI Disable Interrupt EI Enable Interrupt XYFS XY Format Set CVXTY Convert X to Y CVYTX Convert Y to X PULS Pulse Output PWM Pulse Width Modulation RAMP Ramp Pulse Output ZRN1 Zero Return 1 ZRN2 Zero Return 2 PID PID Control DTML 1-sec Dual Timer DTIM 100-msec Dual Timer DTMH 10-msec Dual Timer DTMS 1-msec Dual Timer TTIM Timer

J-106

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

MicroSmart

Micro-3C

Micro-3

ONC