-1 -1 -2 -2 analog -> AMKA AMKA-T AXKA AXKA-T or NFA2X

Self - carrying insulated wires - 1 - 1 - 2 - 2 AMKA AMKA-T AXKA AXKA-T or NFA2X

The wires meet the requirements of Specification 16. 71-268-98 and International standard HD 626 S1 of European Committee of standardization in electric engineering (CENELEC). APPLICATION The wires are designed for using in aerial and lightening networks at nominal alternating voltages up to 0,6; 1 kV, nominal frequency 50 Hz. STRUCTURE Insulated cores are stranded around zero carrier. Cores: Zero carrier - thickened wire made of aluminium alloy or firmed with steel wire Phase cores - aluminium, stranded, thickened Core insulation: - 1, - 1 - photostabilized thermoplastic PE - 2, - 2 - photostabilized cross-linked PE SPECIFICATION The wires meet the requirements of Specification 16. 71-268-98 and International standard HD 626 S1 of European Committee of standardization in electric engineering (CENELEC). ADVANTAGES OF SELF - CARRYING WIRES 1. High reliability and uninterruptible power supply. 2. Reduction of running costs and due to exclusion of systematic routs cleaning and change of damaged insulators. 3. Reduction of power losses in line due to reduction of reactance (0,1 Ohm/km compared to 0,35 Ohm/km for bare wires). 4. Possibility of joint wire hanging on supporting piers with different voltage level and with telephone lines. 5. Easy installation and maintenance, especially under voltage. 6. Reduction of emergency an d reconstruction works. 7. Absence or slight covering of insulated wire surface with ice and wet snow. 8. Possibility of electric mains construction without deforestation. 9. Possibility of electric mains installation along building facades, so it can exclude installation of some supporting piers blocking up the pavements and improve aesthetics in city conditions.
121096 , 2- .5, .2 ./: +7 495 250 34 55 .: +7 495 104 5664 ,+7 495 231 6380 -mail: box@slorus.ru http//: www.slorus.ru : 123 056 , . , .17/19

2
10. Exception of fire hazard in case of wires falling on the ground. 11. Exception of short circuit hazard between phase wires or to the ground. 12. High service safety and lack of risk of electrical shock if touching phase wires under voltage. 13. Safe work near electric mains. 14. Reduction of possibility of electric power theft and destruction. WHAT DISTINGUISHES SELF-CARRYING WIRES BY JSC "SARANSKKABEL" PLANT? 1. Use of thickened steel wire increases strength. More comfortable for installation. Absence of sagging. 2. Use of cross-linked PE insulation allows to increase core heating permissible temperature by 2 times in normal conditions, in overload conditions - by 1,5 times, in short circuit conditions - by 2 times. 3. "Rosendahl" high-speed extrusion line allows to improve insulation quality and provides high technical characteristics. 4. "Rosendahl" take-up device provides good core grooming on take-up drum. 5. Set of measuring and control equipment provides precise geometrical and electrical parameters of insulated core. 6. Core stranding done on modern high-productive "Drum Twister" machine (England) provides observance of all technological stranding parameters. - 1, - 1 Nominal alternating voltage , at 50 Hz frequency , kV Operating core temperature, max C Core temperature in overload conditions, during 8 hrs, max. C Short circuit temperature, C Ambient temperature, min/max, C Installation at temperature, at least C Solidity at aluminium alloy wire tension before wire stranding 2 into zero carrier, at least N/mm Service life, years Operation warranty period, years 1,0 70 80 135 -50/+50 -20 295 25 3 - 2, - 2 1,0 90 130 250

Electric resistance of 1 km phase / zero carrier to direct current , Ohm , max cross section 16 mm cross section 25 mm
2 2 2 2 2 2

1,91 1,20

cross section 35 mm 0,868 cross section 50 mm 0,641 cross section 70 mm 0,443 cross section 95 mm 0,253 Electric resistance of 1 km zero carrier to direct current , Ohm , max cross section 16 mm cross section 25 mm
2 2

1,38 0,986
2

cross section 35 mm

0,720

121096 , 2- .5, .2 ./: +7 495 250 34 55 .: +7 495 104 5664 ,+7 495 231 6380 -mail: box@slorus.ru http//: www.slorus.ru : 123 056 , . , .17/19

3
cross section 50 mm cross section 70 mm
2 2

0,493 0,363

Cross section, mm2 1x16+1x25 3x16+1x25 3x25+1x35 3x35+1x50 3x50+1x70 3x70+1x95 3x120+1x95 4x16+1x25 4x25+1x35

Nominal core insulation thickness, mm - 1 -1 1,4 1,4 1,4 1,6 1,6 1,8 2,0 1,4 1,4 - 2 - 2 1,3 1,3 1,3 1,3 1,5 1,5 1,7 1,3 1,3

Max. external diameter, mm - 1 - 1 15 22 26 30 35 41 47 22 26 - 2 - 2 14 21 25 29 34 39 46 21 25

Design weight of 1 km cable, kg - 1 - 1 140 270 390 590 700 990 1510 330 530 - 2 - 2 135 260 380 570 690 960 1460 320 520