Você está na página 1de 156

IEC Contactors & Starters

June 2005
Vol. 2, Ref. No. [0265]

34-1

IEC Contactors & Starters

Contents
Description IT. Electro-Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Contactors Full Voltage, Non-reversing and Reversing . . . . . . . . . . . . Starters Full Voltage, Non-reversing and Reversing. . . . . . . . . . . . . . . IT. Electro-Mechanical Enclosed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starters Non-combination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starters Fusible and Non-fusible Combination . . . . . . . . . . . . . . . . . . Starters Combination, HMCP/HMCPE . . . . . . . . . . . . . . . . . . . . . . . . . . Modication Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Miniature Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Contactors Non-reversing and Reversing . . . . . . . . . . . . . . . . . . . . . . . Freedom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Contactors Non-reversing and Reversing . . . . . . . . . . . . . . . . . . . . . . . Starters Fixed Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Relays Fixed Heater Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starters Interchangeable Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Relays Interchangeable Heater Overload . . . . . . . . . . . . . . . . . . . . . . . Freedom, Full Voltage Enclosed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starters Non-combination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starters Fusible Combination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starters Combination, GMCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 34-2 34-4 34-7 34-30 34-32 34-34 34-36 34-44 34-49 34-59 34-61 34-73 34-75 34-79 34-83 34-86 34-89 34-122 34-126 34-130 34-138 34-146

34

IEC Contactors and Starters

CA08102001E

For more information visit: www.EatonElectrical.com

34-2

IEC Contactors & Starters IT. Electro-Mechanical


June 2005

Product Family Overview

Vol. 2, Ref. No. [0266]

ISO 9002 Certication


When you turn to Eatons Cutler-Hammer Products, you turn to quality. The International Standards Organization (ISO) has established a series of standards acknowledged by 91 industrialized nations to bring harmony to the international quest for quality. The ISO Certication process covers 20 quality system elements in design, production and installation that must conform to achieve registration. This commitment to quality will result in increased product reliability and total customer satisfaction.

34

Publications
Pub. 49601 Pub. 49602 Pub. 49320 Pub. 49640 Pub. 49650 Pub. 49660 Pub. 49670 Pub. 49680 Pub. 49321 Pub. 49641 Pub. 49651 Pub. 49661 Pub. 49671 Pub. 49681 Pub. 49322 Pub. 49642 Pub. 49652 Pub. 49662 Pub. 49672 Pub. 49682 Pub. 49323 Pub. 49643 Pub. 49653 Pub. 49663 Pub. 49673 Pub. 49683 Pub. 49645 Pub. 49665 IT. IEC Overload Relay 27 mm (A-Frame) Quick Setup Guide IT. IEC Overload Relay (B F Frames) Quick Setup Guide IT. IEC Non-reversing Contactor 27 mm (A-Frame) Installation Guide IT. IEC Non-reversing Contactor 45 mm (B-Frame) Installation Guide IT. IEC Non-reversing Contactor 54 mm (C-Frame) Installation Guide IT. IEC Non-reversing Contactor 76 mm (D-Frame) Installation Guide IT. IEC Non-reversing Contactor 105 mm (E-Frame) Installation Guide IT. IEC Non-reversing Contactor 140 mm (F-Frame) Installation Guide IT. IEC Reversing Contactor 27 mm (A-Frame) Installation Guide IT. IEC Reversing Contactor 45 mm (B-Frame) Installation Guide IT. IEC Reversing Contactor 54 mm (C-Frame) Installation Guide IT. IEC Reversing Contactor 76 mm (D-Frame) Installation Guide IT. IEC Reversing Contactor 105 mm (E-Frame) Installation Guide IT. IEC Reversing Contactor 140 mm (F-Frame) Installation Guide IT. IEC Non-reversing Starter 27 mm (A-Frame) Installation Guide IT. IEC Non-reversing Starter 45 mm (B-Frame) Installation Guide IT. IEC Non-reversing Starter 54 mm (C-Frame) Installation Guide IT. IEC Non-reversing Starter 76 mm (D-Frame) Installation Guide IT. IEC Non-reversing Starter 105 mm (E-Frame) Installation Guide IT. IEC Non-reversing Starter 140 mm (F-Frame) Installation Guide IT. IEC Reversing Starter 27 mm (A-Frame) Installation Guide IT. IEC Reversing Starter 45 mm (B-Frame) Installation Guide IT. IEC Reversing Starter 54 mm (C-Frame) Installation Guide IT. IEC Reversing Starter 76 mm (D-Frame) Installation Guide IT. IEC Reversing Starter 105 mm (E-Frame) Installation Guide IT. IEC Reversing Starter 140 mm (F-Frame) Installation Guide IT. IEC Non-reversing Contactor Assembly Instructions (45 mm & 54 mm) IT. IEC Non-reversing Contactor & Starter Assembly Instructions (76 mm Contactor/Starter) (45 mm & 54 mm Starter) Pub. 49325 IT. IEC Non-reversing Starter 27 mm (A-Frame) Assembly Instructions Pub. 49685 IT. IEC Non-reversing Starter 140 mm (F-Frame) Assembly Instructions Pub. 49326 IT. IEC Reversing Starter 27 mm (A-Frame) Assembly Instructions Pub. 49686 IT. IEC Reversing Contactor & Starter 140 mm (F-Frame) Assembly Instructions Pub. 49410 IT. Front Mountable Auxiliary Contact Assembly Instructions Pub. 49415 IT. IEC Contact Blocks (B E Frames) Pub. 282782 IT. Sinking Control Input Connections Pub. 282719 IT. Overload Trip/Alarm Output (Sourcing/Sinking) For copies of these and other publications, contact the Literature Fulllment Center at 800-957-7050, Fax: 877-840-2371 or nd on-line at: www.eatonelectrical.com.
For International, call: (630) 377-9738 (English only), Fax: (630) 377-1753.

IEC, A Frame, Full Voltage Non-reversing and Reversing Starters

Product Description
Eatons Cutler-Hammer Intelligent Technologies (IT.) Electro-Mechanical line of Contactors and Starters is the result of a substantial engineering, manufacturing and marketing effort involving extensive customer input, combined with new advances in solidstate technology. IT. Electro-Mechanical products have greatly increased functionality, signicantly reduced size and utilize the benets of 24V DC control. The exclusive Pulse Width Modulation (PWM) control and digital microprocessor generate a minimized DC value which reduces energy to the contact block and provides the most compact system available.

Standards and Certications


Designed to meet or exceed UL, IEC and CSA UL Listed: UL File #E1491, Guide #NLDX Open, UL 508 CSA Certied: CSA File #156828, Class #3211 04 Open, C22.2 No. 14-95 IEC: A F Frames, IEC 60947-4-1, EN 60947-4-1 45 mm 76 mm CSA Certied for Elevator Duty CE EMC IEC 61000-4 KEMA

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical


June 2005
Vol. 2, Ref. No. [0267]

34-3

Catalog Number Selection

Catalog Number Selection (Open Components)


Table 34-1. IT. Electro-Mechanical Catalog Numbering System

E 101 A 12 A 3 A
Standard E = IEC Configuration (Open Type) 02N = FVNR Coil Controller 03N = FVR Coil Controller 04N = Contact Block 05N = Solid-State Non-reversing Overload Relay 06N = Solid-State Reversing Overload Relay 101 = FVNR Starter 111 = FVNR Contactor 501 = FVR Starter 511 = FVR Contactor Frame Size A = 27 mm B = 45 mm C = 54 mm D = 76 mm E = 105 mm F = 140 mm Designator (IEC) (A) 06 = 6 Amps. 09 = 9 Amps. 12 = 12 Amps. (B) 18 = 18 Amps. 25 = 25 Amps. 32 = 32 Amps. (C) 40 = 40 Amps. 50 = 50 Amps. (D) 65 = 65 Amps. 85 = 85 Amps. 10 = 100 Amps. (E) 12 = 125 Amps. 16 = 160 Amps. 20 = 200 Amps. (F) 25 = 250 Amps. 31 = 315 Amps. 42 = 420 Amps. XC = Coil Controller XR = Overload Pole Selection 3 = 3-Pole Overload Amperes Adjustment (27 mm) A = .25 .8 B = .59 1.9 C = 1.4 4.4 D = 2.8 9.0 E = 3.8 12 (45 mm) A = .25 .8 B = .59 1.9 C = 1.4 4.4 D = 2.8 9.0 G = 6.3 20 J = 10 32 (54 mm) A = .25 .8 B = .59 1.9 C = 1.4 4.4 D = 2.8 9.0 F = 5.0 16 H = 8.4 27 L = 16 50 (76 mm) F = 5.0 16 H = 8.4 27 K = 14 45 N = 31 100 (105 mm) K = 14 45 M = 28 90 P = 42 135 R = 63 200 Overload Type A = Standard (3-phase, 45 mm 105 mm; 1- or 3-phase, 27 mm) N = Contactor or Not Applicable

34

(140 mm) P = 42 135 S = 84 270 T = 131 420 X = Contact Block, Coil Controller, Contactor or Not Applicable

Note: When using the Catalog Numbering System for Eatons Cutler-Hammer IT. Electro-Mechanical products, care should be exercised to assure that the Catalog Number for the Overload Relay aligns with the IT. Contact Block selected for type, frame size and ampacity, if purchased as separate components. Example: Select an E05N_XR_3A IT. Overload Relay for an IEC non-reversing application or an E06N_XR_3A for an IEC reversing application. Examples: E02NCXCXNN FVNR Coil Controller, 54 mm E04NB18X3N Contact Block, 45 mm, 18 Amps E05NCXRL3A Solid-State Non-reversing Overload Relay, 16 50 Amps E101B32J3A FVNR B-Frame Starter, 32 Amps, with Solid-State Overload, 10 32 Amps E111F25X3N FVNR F-Frame Contactor, 250 Amps E501D10K3A FVR D-Frame Starter, 100 Amps, with Solid-State Overload, 14 45 Amps E511B18X3N FVR B-Frame Contactor, 18 Amps

CA08102001E

For more information visit: www.EatonElectrical.com

34-4

IEC Contactors & Starters IT. Electro-Mechanical


June 2005

Contactors Full Voltage, Non-reversing and Reversing

Vol. 2, Ref. No. [0268]

Contents
Description Product Family Overview Product Description . . . . . . . Standards and Certications . . . . . . . . . . . Publications . . . . . . . . . . . . . Catalog Number Selection . . . . . . . . . . . . . . Contactors Non-reversing and Reversing Product Description . . . . . . . Application Description. . . . Features . . . . . . . . . . . . . . . . Product Selection . . . . . . . . Technical Data and Specications . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . Auxiliary Contacts . . . . . . . . Renewal Parts . . . . . . . . . . . . . . Wiring Diagrams. . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . Page 34-2 34-2 34-2 34-3

Product Description
The Cutler-Hammer Intelligent Technologies (IT.) Electro-Mechanical Contactor from Eatons electrical business consists of an IT. ElectroMechanical Contact Block and IT. Electro-Mechanical Coil Controller as a Full Voltage Non-reversing (FVNR) or Full Voltage Reversing (FVR) device. B-Frame (45 mm) to E-Frame (105 mm) Contact Blocks combined with Coil Controllers (factory or eld assembled) are stand-alone Contactors. Only the A-Frame (27 mm) and F-Frame (140 mm) Contactors have internal factory assembled coil controllers. Also available are the IT. Manual and Combination Motor Controllers which combine a Manual Motor Protector, Wiring Connector Link and IT. Contactor. See Tab 38 for more information.

34

34-4 34-4 34-4 34-5 34-14 34-18 34-20 34-22 34-23 34-24

Application Description
When selecting an IEC Contactor, the user must consider the specic load, utilization category and required electrical life. Actual application life may vary depending on environmental conditions and duty cycle.

Features

IEC Full Voltage Non-reversing Contactor, C-Frame Cat. No. E111C50X3N

115V AC 600V AC, 1/4 350 hp/ 3/4 250 kW, 50/60 Hz 24V DC Coil Control safe, reliable global standard Most compact DC operated contactors available e.g., A-Frame 27 mm wide, 7-1/2 hp @ 12A, 460V Frame sizes (mm): 27, 45, 54, 76, 105, 140 No laminations, shading coils or magnet noise -40 to 149F (-40 to 65C) operating temperature No seal in auxiliary contacts required control wiring is not needed between the contactor and overload relay

Unique Pulse Width Modulated (PWM) coil controller minimizes energy and coil power consumption Conformal coated PWM board (coil controller) for environmental toughness Microprocessor-based control 95% humidity non-condensing (99% consult factory) Easily accessible mounting feet for panel mounting High immunity to ESD, harmonics minimal Total Harmonic Distortion Front and side mounted Auxiliary Contacts: 1NO, 1NC, 2NO, 2NC, 1NO/1NC and logic level Built-in logic to provide either 2- or 3-wire control, eliminating the need to provide and wire auxiliary contacts to seal in and interlock the contactor coils Easy eld assembly of control wiring plug and unplug lockable control connector DIN rail mounting, 6 100A (A D Frames) Common accessories Long-life silver nickel (A B Frames) and silver tin oxide (C F Frames) contacts provide excellent conductivity and superior resistance to welding and arc erosion Environmentally friendly materials IP20 Finger Protection Low wattage coils and minimal heat dissipation

Reversing Contactors

Includes Reversing Power Wiring and bus bars Mounting plates for B-Frame (45 mm) to E-Frame (105 mm) Exclusive internal electronic interlock for reversing Unique coil controller energizes both forward and reverse contactors one control point for wiring

IEC Full Voltage Reversing Contactor, D-Frame Cat. No. E511D10X3N

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical


June 2005
Vol. 2, Ref. No. [0269]

34-5

Contactors Full Voltage, Non-reversing and Reversing

Product Selection
When Ordering
Select required contactor by amp rating, frame size, kW/hp, voltage and nonreversing or reversing.

Non-reversing Contactors
Note:
An E111 (45 105 mm) consists of an E04N

34

(Contact Block) and an E02N (FVNR Coil Controller), factory assembled. An E111 (27 and 140 mm) has an internal coil controller, factory assembled.

IEC A-Frame FVNR Contactor Cat. No. E111A12X3N

IEC B-Frame FVNR Contactor Cat. No. E111B32X3N

Table 34-2. 3-Pole DC-Operated Full Voltage Non-reversing Contactors


Max. AC-3 Amp. Rating 480V AC (le) 6 9 12 18 25 32 40 50 65 85 100 125 160 200 250 315 420 IEC 60947-4-1 AC-1 Thermal Current 480V AC and (Ith) 12 16 20 25 40 50 63 85 100 115 130 200 225 250 300 375 450 Frame Maximum kW Rating @ Ue (V) 50/60 Hz Size 3-Phase

(A F Frames)
Maximum UL Horsepower (hp) 50/60 Hz 1-Phase 3-Phase 230V/ 240V 380V/ 460V/ 415V 480V 575V/ 600V Catalog Number Price U.S. $ 3-Pole Open Type

220V/ 380V 400V/ 440V/ 500V 550V/ 115V/ 220V/ 200V/ 240V 415V 460V 575V 120V 230V 208V

A A A B B B C C D D D E E E F F F

1.1 2.2 3 4 5.5 9 11 12.5 18.5 25 25 33 45 59 75 90 110

2.2 4 5.5 7.5 12.5 15 18.5 22 30 45 51 63 80 100 132 160 220

2.2 4 5.5 9 12.5 15 22 25 33 45 55 63 80 110 140 160 220

3 4 6.5 9 13 18.5 22 30 40 51 59 80 100 110 160 200 257

3 4 6.5 10 15 18.5 22 30 40 51 59 80 100 110 160 200 257

3 4 6.5 11 15 18.5 25 33 45 55 63 80 100 132 160 200 257

1/4 1/3 1/2 1 2 2 3 3

1/2 1 2 3 3 5 7-1/2 10

1 2 3 5 5 7-1/2 10 15 20 25 30 40 50 60 75 100 150

1-1/2 2 3 5 7-1/2 10 10 15 20 30 30 40 60 75 100 125 150

3 3 5 10 10 15 20 25 40 50 50 60 75 100 150 150 200

3 5 7-1/2 10 15 20 25 30 50 60 75 100 125 150 200 250 350

3 E111A06X3N 5 E111A09X3N 7-1/2 E111A12X3N 10 15 20 25 30 50 60 75 100 125 150 200 250 350 E111B18X3N E111B25X3N E111B32X3N E111C40X3N E111C50X3N E111D65X3N E111D85X3N E111D10X3N E111E12X3N E111E16X3N E111E20X3N E111F25X3N E111F31X3N E111F42X3N

113. 115. 147. 167. 185. 212. 246. 268. 393. 443. 650. 1,010. 1,425. 1,600. 2,080. 2,550. 3,555.

5 10 7-1/2 15 10 20 10 15 25 30 40 50

24V DC coil voltage. Frame Size A = 27 mm B = 45 mm C = 54 mm D = 76 mm E = 105 mm F = 140 mm

Note:
If required, accessories are available starting on Page 34-18. Integral solid-state auxiliary hold-in circuit. 3 main contacts. See Table 34-11 for 24V DC power supply requirements. Control inputs (P, F) are rated 24V DC (3 5 mA).

Accessories . . . . . . . . . . . . . Technical Data . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Pages 34-18 34-21 Pages 34-14 34-17 Pages 34-24 34-26 1CD7

34-6

IEC Contactors & Starters IT. Electro-Mechanical


June 2005

Contactors Full Voltage, Non-reversing and Reversing

Vol. 2, Ref. No. [0270]

Reversing Contactors
Note:
An E511 (45 105 mm) consists of two E04N

34

(Contact Blocks), an E03N (FVR Coil Controller), Mechanical Interlock, Fanning Strips and Mounting Plate, factory assembled. An E511F (140 mm) consists of two E111F (Contactors), Mechanical Interlock, Crossover Bus Bars and Wiring Harness, factory assembled. An E511A (27 mm) Contactor is factory assembled only.

IEC B-Frame FVR Contactor Cat. No. E511B32X3N

Table 34-3. 3-Pole DC-Operated Full Voltage Reversing Contactors


Max. AC-3 Amp. Rating 480V AC (le) 6 9 12 18 25 32 40 50 65 85 100 125 160 200 250 315 420

(A F Frames)
Maximum UL Horsepower (hp) 50/60 Hz 1-Phase 3-Phase 230V/ 240V 380V/ 415V 460V/ 480V 575V/ 600V Catalog Number Price U.S. $ 115V/ 220V/ 200V/ 120V 230V 208V 3-Pole Open Type

Frame Maximum kW Rating @ Ue (V) 50/60 Hz IEC 60947-4-1 Size 3-Phase AC-1 220V/ 380V 400V/ 440V/ 500V 550V/ Thermal 240V 415V 460V 575V Current 480V AC and (Ith) 12 16 20 25 40 50 63 85 100 115 130 200 225 250 300 375 450 A A A B B B C C D D D E E E F F F 1.1 2.2 3 4 5.5 9 11 12.5 18.5 25 25 33 45 59 75 90 110 2.2 4 5.5 7.5 12.5 15 18.5 22 30 45 51 63 80 100 132 160 220 2.2 4 5.5 9 12.5 15 22 25 33 45 55 63 80 110 140 160 220 3 4 6.5 9 13 18.5 22 30 40 51 59 80 100 110 160 200 257 3 4 6.5 10 15 18.5 22 30 40 51 59 80 100 110 160 200 257 3 4 6.5 11 15 18.5 25 33 45 55 63 80 100 132 160 200 257

1/4 1/3 1/2 1 2 2 3 3

1/2 1 2 3 3 5 7-1/2 10

1 2 3 5 5 7-1/2 10 15 20 25 30 40 50 60 75 100 150

1-1/2 2 3 5 7-1/2 10 10 15 20 30 30 40 60 75 100 125 150

3 3 5 10 10 15 20 25 40 50 50 60 75 100 150 150 200

3 5 7-1/2 10 15 20 25 30 50 60 75 100 125 150 200 250 350

3 E511A06X3N 5 E511A09X3N 7-1/2 E511A12X3N 10 15 20 25 30 50 60 75 100 125 150 200 250 350 E511B18X3N E511B25X3N E511B32X3N E511C40X3N E511C50X3N E511D65X3N E511D85X3N E511D10X3N E511E12X3N E511E16X3N E511E20X3N E511F25X3N E511F31X3N E511F42X3N

280. 285. 388. 418. 455. 505. 645. 680. 930. 1,410. 1,835. 2,600. 3,560. 4,140. 5,380. 6,390. 9,240.

5 10 7-1/2 15 10 20 10 15 25 30 40 50

24V DC coil voltage. Frame Size A = 27 mm B = 45 mm C = 54 mm D = 76 mm E = 105 mm F = 140 mm

Note:
If required, accessories are available starting on Page 34-18. Integral solid-state auxiliary hold-in circuit. 3 main contacts. See Table 34-11 for 24V DC power supply requirements. Control inputs (P, F, R) are rated 24V DC (3 5 mA).

Accessories . . . . . . . . . . . . . Technical Data . . . . . . . . . . Dimensions . . . . . . . . . . . . . Discount Symbol . . . . . . . . . For more information visit: www.EatonElectrical.com

Pages 34-18 34-21 Pages 34-14 34-17 Pages 34-24 34-26 1CD7 CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical


June 2005
Vol. 2, Ref. No. [0271]

34-7

Starters Full Voltage, Non-reversing and Reversing

Contents
Description Product Family Overview Product Description . . . . . . Standards and Certications . . . . . . . . . . Publications . . . . . . . . . . . . Catalog Number Selection . . . . . . . . . . . . . Starters Non-reversing and Reversing Product Description . . . . . . Features . . . . . . . . . . . . . . . Product Selection . . . . . . . . Technical Data and Specications . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . Auxiliary Contacts . . . . . . . Renewal Parts . . . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . Page

34-2

34-2 34-2

34-3

34-7 34-7 34-8 34-14 34-18 34-20 34-22 34-23 34-24

IEC Full Voltage Reversing Starter, E Frame Cat. No. E501E20R3A

Product Description
The Cutler-Hammer Intelligent Technologies (IT.) Electro-Mechanical Starter from Eatons electrical business consists of an IT. Electro-Mechanical Contact Block or Contactor and IT. Electro-Mechanical Solid-State Overload Relay as a Full Voltage Nonreversing (FVNR) or Full Voltage Reversing (FVR) device. A-Frame (27 mm) to F-Frame (140 mm) Starters are factory or eld assembled.

IEC FVNR Starter, C Frame Cat. No. E101C50L3A

Features

Overload Relay with Cover Open FLA/Trip Class/ Phase Protection Dial TEST Button RESET Button

115V AC 600V AC, 1/4 350 hp/ .75 250 kW, .25A 420A Overload Amperes range, 50/60 Hz 24V DC coil control power safe, reliable, global standard Unique Pulse Width Modulated (PWM) coil controller minimizes energy and coil power consumption Microprocessor based control Phase loss and current unbalance protection, user selectable Standard user-selectable Trip Class 10 (factory default), 20 or 30 no individual part numbers no programming software Ambient compensated Motor temperature and power-up protection with thermal memory Easily accessible mounting feet for panel mounting For use on the load side of an Adjustable Frequency Drive, consult the factory.

LED status indication trip, trip class, motor thermal state, reset, overload state Unique Alarm without Trip option for critical must run applications Lockable overload cover protects against unauthorized adjustment and reset functions No control wiring needed between contactor and overload relay eliminates seal in auxiliary contacts Minimal heat no full voltage coils -40 to 149F (-40 to 65C) operating temperature Wide 3.2:1 current adjustment range Exclusive internal 24-bit oating point math calculations with RMS calibrated current measurement High immunity to ESD, harmonics minimal Total Harmonic Distortion IP20 Finger Protection Motor running thermal utilization indication Manual, Automatic or Remote Reset Easy eld assembly of control wiring plug and unplug lockable control connector DIN rail mounting, 6A 100A (A D Frames) Communication Interface with Starter Network Adapter Product (SNAP) 2- or 3-wire control Solid-state alarm output indication Front and side mounted Auxiliary Contacts: 1NO, 1NC, 2NO, 2NC, 1NO/1NC, logic level (1NO/1NC) Type 2 Coordination Conformal coated PWM overload board for environmental toughness

34

Reversing Starters

Includes Reversing Power Wiring and bus bars Mounting plates for B-Frame (45 mm) to E-Frame (105 mm) Built-in electronic interlock for FVR units Unique overload board energizes both forward and reverse starters one control point for wiring

Overload Relay with Cover Closed (front view)

CA08102001E

For more information visit: www.EatonElectrical.com

34-8

IEC Contactors & Starters IT. Electro-Mechanical


June 2005

Starters Full Voltage, Non-reversing and Reversing

Vol. 2, Ref. No. [0272]

Product Selection
When Ordering
Select required Starter by kW/hp rating, voltage, phase and overload adjustment range (amperes).

34

IEC A-Frame, Full Voltage Non-reversing Starter

IEC B-Frame, Full Voltage Non-reversing Starter

Non-reversing Starters
Table 34-4. Full Voltage Non-reversing DC-Operated, Open Type Starters (A B Frames), with 3-Pole Solid-State Overload Protection
Max. AC-3 Amp. Rating 480V AC (le) Maximum kW Rating @ Ue (V) Maximum UL Horsepower (hp) Rating Overload Adjustment 50/60 Hz 50/60 Hz Range 3-Phase 1-Phase 3-Phase (Amperes) 220V/ 380V 400V/ 460V 500V 550V/ 115V/ 220V/ 200V/ 230V/ 380V/ 460V/ 240V 415V 575V 120V 230V 208V 240V 415V 480V .25 .8 .59 1.9 1.4 4.4 2.8 9.0 3.8 12 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 3.8 12 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 3.8 12 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 6.3 20 10 32 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 6.3 20 10 32 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 6.3 20 10 32 1.1 2.2 2.2 3 3 3 1/4 1/2 1 1-1/2 3 3 Catalog Number 575V/ 600V 3 E101A06A3A E101A06B3A E101A06C3A E101A06D3A E101A06E3A E101A09A3A E101A09B3A E101A09C3A E101A09D3A E101A09E3A E101A12A3A E101A12B3A E101A12C3A E101A12D3A E101A12E3A E101B18A3A E101B18B3A E101B18C3A E101B18D3A E101B18G3A E101B18J3A E101B25A3A E101B25B3A E101B25C3A E101B25D3A E101B25G3A E101B25J3A E101B32A3A E101B32B3A E101B32C3A E101B32D3A E101B32G3A E101B32J3A 233. 233. 233. 233. 233. 235. 235. 235. 235. 235. 246. 246. 246. 246. 246. 258. 258. 258. 258. 258. 258. 284. 284. * 284. 284. 284. 318. 318. * 318. 318. 318. Price U.S. $

A-Frame 27 mm
6

2.2

1/3

12

5.5

5.5

6.5

6.5

6.5

1/2

7-1/2

7-1/2

B-Frame 45 mm
18 4 7.5 9 9 10 11 5 5 10 10 10

25

5.5

12.5

12.5

13

15

15

7-1/2 10

15

15

32

15

15

18.5

18.5

18.5

7-1/2 10

15

20

20

Note:
If required, accessories are available starting

Class 10 (factory default), 20 and 30 Trip

See Table 34-11 for 24V DC power supply

on Page 34-18. A-Frame 27 mm IT. Starter is for 1 or 3-phase applications. The standard B F-Frame (45 mm to 140 mm) IT. Starters are for 3-phase applications.

Times see Figure 34-3 on Page 34-17. An E101 (27 105 mm) consists of an E04N (Contact Block) or E111A (Contactor) and an E05N (Non-reversing Overload Relay), factory assembled. An E101F (140 mm) consists of an E111 (Contactor) and an E05N (Non-reversing Overload Relay), factory assembled.

requirements.
Control inputs (P, F, 1) are rated 24V DC

(3 5 mA). *Please contact your local Eaton sales ofce.

Accessories . . . . . . . . . . . . . Technical Data . . . . . . . . . . Dimensions . . . . . . . . . . . . . Discount Symbol . . . . . . . . .

Pages 34-18 34-21 Pages 34-14 34-17 Pages 34-27 34-29 1CD7 CA08102001E

For more information visit: www.EatonElectrical.com

IEC Contactors & Starters IT. Electro-Mechanical


June 2005
Vol. 2, Ref. No. [0273]

34-9

Starters Full Voltage, Non-reversing and Reversing

34

IEC C-Frame FVNR Starter

Non-reversing Starters, continued


Table 34-5. Full Voltage Non-reversing DC-Operated, Open Type Starters (C D Frames), with 3-Pole Solid-State Overload Protection
Max. AC-3 Amp. Rating 480V AC (le) Maximum kW Rating @ Ue (V) Maximum UL Horsepower (hp) Rating Overload Adjustment 50/60 Hz 50/60 Hz Range 3-Phase 1-Phase 3-Phase (Amperes) 220V/ 380V 400V/ 460V 500V 550V/ 115V/ 220V/ 200V/ 230V/ 380V/ 460V/ 240V 415V 575V 120V 230V 208V 240V 415V 480V .25 .8 .59 1.9 1.4 4.4 2.8 9.0 5.0 16 8.4 27 16 50 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 5.0 16 8.4 27 16 50 5.0 16 8.4 27 14 45 31 100 5.0 16 8.4 27 14 45 31 100 5.0 16 8.4 27 14 45 31 100 11 18.5 22 22 22 25 10 10 20 25 Catalog Number 575V/ 600V 25 E101C40A3A E101C40B3A E101C40C3A E101C40D3A E101C40F3A E101C40H3A E101C40L3A E101C50A3A E101C50B3A E101C50C3A E101C50D3A E101C50F3A E101C50H3A E101C50L3A E101D65F3A E101D65H3A E101D65K3A E101D65N3A E101D85F3A E101D85H3A E101D85K3A E101D85N3A E101D10F3A E101D10H3A E101D10K3A E101D10N3A 423. 423. 423. 423. 423. 423. * 447. 447. 447. 447. 447. 447. * 620. 620. 620. * 715. 715. 715. 715. 1,055. 1,055. 1,055. 1,055. Price U.S. $

C-Frame 54 mm
40

50

12.5

22

25

30

30

33

15

15

25

30

30

D-Frame 76 mm
65 18.5 30 33 40 40 45 20 20 40 50 50

85

25

45

45

51

51

55

25

30

50

60

60

100

25

51

55

59

59

63

30

30

50

75

75

Note:
If required, accessories are available starting

Class 10 (factory default), 20 and 30 Trip

See Table 34-11 for 24V DC power supply

on Page 34-18. A-Frame 27 mm IT. Starter is for 1 or 3-phase applications. The standard B F-Frame (45 mm to 140 mm) IT. Starters are for 3-phase applications.

Times see Figure 34-3 on Page 34-17. An E101 (27 105 mm) consists of an E04N (Contact Block) or E111A (Contactor) and an E05N (Non-reversing Overload Relay), factory assembled. An E101F (140 mm) consists of an E111 (Contactor) and an E05N (Non-reversing Overload Relay), factory assembled.

requirements.
Control inputs (P, F, 1) are rated 24V DC

(3 5 mA). *Please contact your local Eaton sales ofce.

Accessories . . . . . . . . . . . . . Technical Data . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Pages 34-18 34-21 Pages 34-14 34-17 Pages 34-27 34-29 1CD7

34-10

IEC Contactors & Starters IT. Electro-Mechanical


June 2005

Starters Full Voltage, Non-reversing and Reversing

Vol. 2, Ref. No. [0274]

34

IEC F- and E-Frame (105 mm and 140 mm) Full Voltage Non-reversing Starters

Non-reversing Starters, continued


Table 34-6. Full Voltage Non-reversing DC-Operated, Open Type Starters (E F Frames) with 3-Pole Solid-State Overload Protection
Max. AC-3 Amp. Rating 480V AC (le) Maximum kW Rating @ Ue (V) Maximum UL Horsepower (hp) Rating Overload Adjustment 50/60 Hz 50/60 Hz Range 3-Phase 1-Phase 3-Phase (Amperes) 220V/ 380V 400V/ 460V 500V 550V/ 115V/ 220V/ 200V/ 230V/ 380V/ 460V/ 240V 415V 575V 120V 230V 208V 240V 415V 480V 14 45 28 90 42 135 63 200 14 45 28 90 42 135 63 200 14 45 28 90 42 135 63 200 42 135 84 270 131 420 42 135 84 270 131 420 42 135 84 270 131 420 33 63 63 80 80 80 40 40 60 100 Catalog Number 575V/ 600V 100 E101E12K3A E101E12M3A E101E12P3A E101E12R3A E101E16K3A E101E16M3A E101E16P3A E101E16R3A E101E20K3A E101E20M3A E101E20P3A E101E20R3A E101F25P3A E101F25S3A E101F25T3A E101F31P3A E101F31S3A E101F31T3A E101F42P3A E101F42S3A E101F42T3A 1,485. 1,485. 1,485. 1,485. 1,910. 1,910. 1,910. 1,910. 2,020. 2,020. 2,020. 2,020. 2,720. 2,720. 2,720. 3,855. 3,855. 3,855. 4,875. 4,875. 4,875. Price U.S. $

E-Frame 105 mm
125

160

45

80

80

100

100

100

50

60

75

125

125

200

59

100

110

110

110

132

60

75

100

150

150

F-Frame 140 mm
250 75 132 140 160 160 160 75 100 150 200 200

315

90

160

160

200

200

200

100

125

150

250

250

420

110

220

220

257

257

257

150

150

200

350

350

Note:
If required, accessories are available starting

Class 10 (factory default), 20 and 30 Trip

See Table 34-11 for 24V DC power supply

on Page 34-18. A-Frame 27 mm IT. Starter is for 1 or 3-phase applications. The standard B F-Frame (45 mm to 140 mm) IT. Starters are for 3-phase applications.

Times see Figure 34-3 on Page 34-17. An E101 (27 105 mm) consists of an E04N (Contact Block) or E111A (Contactor) and an E05N (Non-reversing Overload Relay), factory assembled. An E101F (140 mm) consists of an E111 (Contactor) and an E05N (Non-reversing Overload Relay), factory assembled.

requirements.
Control inputs (P, F, 1) are rated 24V DC

(3 5 mA).

Accessories . . . . . . . . . . . . . Technical Data . . . . . . . . . . Dimensions . . . . . . . . . . . . . Discount Symbol . . . . . . . . . For more information visit: www.EatonElectrical.com

Pages 34-18 34-21 Pages 34-14 34-17 Pages 34-27 34-29 1CD7 CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical


June 2005
Vol. 2, Ref. No. [0275]

34-11

Starters Full Voltage, Non-reversing and Reversing

34

IEC A-Frame Reversing Starter

Reversing Starters
Table 34-7. Full Voltage Reversing DC-Operated, Open Type Starters (A B Frames) with 3-Pole Solid-State Overload Protection
Max. AC-3 Amp. Rating 480V AC (le) Maximum kW Rating @ Ue (V) Maximum UL Horsepower (hp) Rating Overload Adjustment 50/60 Hz 50/60 Hz Range 3-Phase 1-Phase 3-Phase (Amperes) 220V/ 380V 400V/ 440V/ 500V 550V/ 115V/ 220V/ 200V/ 230V/ 380V/ 460V/ 240V 415V 460V 575V 120V 230V 208V 240V 415V 480V .25 .8 .59 1.9 1.4 4.4 2.8 9.0 3.8 12 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 3.8 12 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 3.8 12 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 6.3 20 10 32 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 6.3 20 10 32 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 6.3 20 10 32 1.1 2.2 2.2 3 3 3 1/4 1/2 1 1-1/2 3 3 Catalog Number 575V/ 600V 3 E501A06A3A E501A06B3A E501A06C3A E501A06D3A E501A06E3A E501A09A3A E501A09B3A E501A09C3A E501A09D3A E501A09E3A E501A12A3A E501A12B3A E501A12C3A E501A12D3A E501A12E3A E501B18A3A E501B18B3A E501B18C3A E501B18D3A E501B18G3A E501B18J3A E501B25A3A E501B25B3A E501B25C3A E501B25D3A E501B25G3A E501B25J3A E501B32A3A E501B32B3A E501B32C3A E501B32D3A E501B32G3A E501B32J3A 515. 515. 515. 515. 515. 520. 520. 520. 520. 520. 525. 525. 525. 525. 525. 550. 550. * 550. 550. 550. 625. 625. * 625. 625. 625. 710. 710. * 710. 710. 710. Price U.S. $

A-Frame 27 mm
6

2.2

1/3

12

5.5

5.5

6.5

6.5

6.5

1/2

7-1/2

7-1/2

B-Frame 45 mm
18 4 7.5 9 9 10 11 5 5 10 10 10

25

5.5

12.5

12.5

13

15

15

7-1/2 10

15

15

32

15

15

18.5

18.5

18.5

7-1/2

10

15

20

20

24V DC coil voltage.

An E501 (45 105 mm) consists of two E04N

See Table 34-11 for 24V DC power supply

Note:
If required, accessories are available starting

on Page 34-18.
A-Frame 27 mm IT. Starter is for 1 or

3-phase applications.
The standard B F-Frame (45 mm to 140 mm)

IT. Starters are for 3-phase applications.

(Contact Blocks), an E06N (Reversing Overload Relay), Fanning Strips, Mechanical Interlock and Mounting Plate. An E501F (140 mm) consists of two E111F (Contactors), an E06NF (Reversing Overload Relay), Mechanical Interlock, Crossover Bus Bars and Reversing Wiring Harness. An E501A (27 mm) consists of an E511A (Contactor) and E06NA (Reversing Overload Relay).

requirements.
Control inputs (P, F, R, 1) are rated 24V DC

(3 5 mA). *Please contact your local Eaton sales ofce.

Accessories . . . . . . . . . . . . . Technical Data . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . Discount Symbol . . . . . . . . .

Pages 34-18 34-21 Pages 34-14 34-17 Pages 34-27 34-29 1CD7

CA08102001E

For more information visit: www.EatonElectrical.com

34-12

IEC Contactors & Starters IT. Electro-Mechanical


June 2005

Starters Full Voltage, Non-reversing and Reversing

Vol. 2, Ref. No. [0276]

34

IEC C-Frame Reversing Starter

Reversing Starters, continued


Table 34-8. Full Voltage Reversing DC-Operated, Open Type Starters (C D Frames) with 3-Pole Solid-State Overload Protection
Max. AC-3 Amp. Rating 480V AC (le) Maximum kW Rating @ Ue (V) Maximum UL Horsepower (hp) Rating Overload Adjustment 50/60 Hz 50/60 Hz Range 3-Phase 1-Phase 3-Phase (Amperes) 220V/ 380V 400V/ 440V/ 500V 550V/ 115V/ 220V/ 200V/ 230V/ 380V/ 460V/ 240V 415V 460V 575V 120V 230V 208V 240V 415V 480V .25 .8 .59 1.9 1.4 4.4 2.8 9.0 5.0 16 8.4 27 16 50 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 5.0 16 8.4 27 16 50 5.0 16 8.4 27 14 45 31 100 5.0 16 8.4 27 14 45 31 100 5.0 16 8.4 27 14 45 31 100 11 18.5 22 22 22 25 10 10 20 25 Catalog Number 575V/ 600V 25 E501C40A3A E501C40B3A E501C40C3A E501C40D3A E501C40F3A E501C40H3A E501C40L3A E501C50A3A E501C50B3A E501C50C3A E501C50D3A E501C50F3A E501C50H3A E501C50L3A E501D65F3A E501D65H3A E501D65K3A E501D65N3A E501D85F3A E501D85H3A E501D85K3A E501D85N3A E501D10F3A E501D10H3A E501D10K3A E501D10N3A 880. * 880. 880. 880. 880. * 990. 990. 990. 990. 990. 990. * 1,340. 1,340. 1,340. 1,340. 1,680. 1,680. 1,680. 1,680. 2,340. 2,340. 2,340. 2,340. Price U.S. $

C-Frame 54 mm
40

50

12.5

22

25

30

30

33

15

15

25

30

30

D-Frame 76 mm
65 18.5 30 33 40 40 45 20 20 40 50 50

85

25

45

45

51

51

55

25

30

50

60

60

100

25

51

55

59

59

63

30

30

50

75

75

24V DC coil voltage.

An E501 (45 105 mm) consists of two E04N

See Table 34-11 for 24V DC power supply

Note:
If required, accessories are available starting

on Page 34-18.
A-Frame 27 mm IT. Starter is for 1 or

3-phase applications.
The standard B F-Frame (45 mm to 140 mm)

IT. Starters are for 3-phase applications.

(Contact Blocks), an E06N (Reversing Overload Relay), Fanning Strips, Mechanical Interlock and Mounting Plate. An E501F (140 mm) consists of two E111F (Contactors), an E06NF (Reversing Overload Relay), Mechanical Interlock, Crossover Bus Bars and Reversing Wiring Harness. An E501A (27 mm) consists of an E511A (Contactor) and E06NA (Reversing Overload Relay).

requirements.
Control inputs (P, F, R, 1) are rated 24V DC

(3 5 mA). *Please contact your local Eaton sales ofce.

Accessories . . . . . . . . . . . . . Technical Data . . . . . . . . . . Dimensions . . . . . . . . . . . . . Discount Symbol . . . . . . . . . For more information visit: www.EatonElectrical.com

Pages 34-18 34-21 Pages 34-14 34-17 Pages 34-27 34-29 1CD7 CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical


June 2005
Vol. 2, Ref. No. [0277]

34-13

Starters Full Voltage, Non-reversing and Reversing

34

IEC E-Frame FVR Starter Cat. No. E501E20P3A

IEC F-Frame Reversing Starter

Reversing Starters, continued


Table 34-9. Full Voltage Reversing DC-Operated, Open Type Starters (E F Frames) with 3-Pole Solid-State Overload Protection
Max. AC-3 Amp. Rating 480V AC (le) Maximum kW Rating @ Ue (V) Maximum UL Horsepower (hp) Rating Overload Adjustment 50/60 Hz 50/60 Hz Range 3-Phase 1-Phase 3-Phase (Amperes) 220V/ 380V 400V/ 440V/ 500V 550V/ 115V/ 220V/ 200V/ 230V/ 380V/ 460V/ 240V 415V 460V 575V 120V 230V 208V 240V 415V 480V 14 45 28 90 42 135 63 200 14 45 28 90 42 135 63 200 14 45 28 90 42 135 63 200 42 135 84 270 131 420 42 135 84 270 131 420 42 135 84 270 131 420 33 63 63 80 80 80 40 40 60 100 Catalog Number 575V/ 600V 100 E501E12K3A E501E12M3A E501E12P3A E501E12R3A E501E16K3A E501E16M3A E501E16P3A E501E16R3A E501E20K3A E501E20M3A E501E20P3A E501E20R3A E501F25P3A E501F25S3A E501F25T3A E501F31P3A E501F31S3A E501F31T3A E501F42P3A E501F42S3A E501F42T3A 3,140. 3,140. 3,140. 3,140. 4,235. 4,235. 4,235. 4,235. 4,475. 4,475. 4,475. 4,475. 5,770. 5,770. 5,770. 8,550. 8,550. 8,550. 10,830. 10,830. 10,830. Price U.S. $

E-Frame 105 mm
125

160

45

80

80

100

100

100

50

60

75

125

125

200

59

100

110

110

110

132

60

75

100

150

150

F-Frame 140 mm
250 75 132 140 160 160 160 75 100 150 200 200

315

90

160

160

200

200

200

100

125

150

250

250

420

110

220

220

257

257

257

150

150

200

350

350

24V DC coil voltage.

An E501 (45 105 mm) consists of two E04N

See Table 34-11 for 24V DC power supply

Note:
If required, accessories are available on

Page 34-18.
A-Frame 27 mm IT. Starter is for 1 or

3-phase applications.
The standard B F-Frame (45 mm to 140 mm)

IT. Starters are for 3-phase applications.

(Contact Blocks), an E06N (Reversing Overload Relay), Fanning Strips, Mechanical Interlock and Mounting Plate. An E501F (140 mm) consists of two E111F (Contactors), an E06NF (Reversing Overload Relay), Mechanical Interlock, Crossover Bus Bars and Reversing Wiring Harness. An E501A (27 mm) consists of an E511A (Contactor) and E06NA (Reversing Overload Relay).

requirements.
Control inputs (P, F, R 1) are rated 24V DC

(3 5 mA).

Accessories . . . . . . . . . . . . . Technical Data . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Pages 34-18 34-21 Pages 34-14 34-17 Pages 34-27 34-29 1CD7

34-14

IEC Contactors & Starters IT. Electro-Mechanical


June 2005

Technical Data and Specications


Table 34-10. Specications
Description A-Frame 27 mm 1.1 x 3.0 x 2.4 (27 x 75 x 60) 2.4 x 2.9 x 2.4 (60 x 73 x 60) 1.2 x 4.0 x 3.1 (31 x 102 x 79) 2.5 x 4.0 x 3.1 (64 x 102 x 79) .76 x 2.64 (19.2 x 67) 1.31 x 2.52 (33.2 x 64) .76 x 3.70 (19.3 x 94.0) 1.31 x 3.52 (33.2 x 89.4) Yes Yes Yes .3 (.14) .6 (.27) .4 (.18) .9 (.40) 6/sec 23,000,000 B-Frame 45 mm C-Frame 54 mm 2.1 x 4.4 x 2.4 (54 x 113 x 60) 4.5 x 5.9 x 2.6 (114 x 149 x 67) 2.1 x 5.4 x 2.5 (54 x 138 x 63) 4.5 x 5.9 x 2.6 (114 x 149 x 67) 1.46 x 4.10 (37 x 104) 3.15 x 5.35 (80 x 136) 1.46 x 5.04 (37 x 128) 3.15 x 5.35 (80 x 136) Yes Yes Yes .9 (.42) 2.6 (1.17) 1.2 (.53) 2.6 (1.20) 3/sec 10,000,000 95% non-condensing 690V 6 kV 85 50 50 D-Frame 76 mm 3.0 x 5.9 x 3.1 (76 x 150 x 79) 6.2 x 7.4 x 3.3 (158 x 188 x 84) 3.0 x 5.9 x 3.1 (76 x 150 x 79) 6.2 x 7.4 x 3.3 (158 x 188 x 84) .94 x 2.87 (24 x 73) 5.51 x 6.89 (140 x 175) .94 x 2.87 (24 x 73) 5.51 x 6.89 (140 x 175) Yes Yes Yes 2.8 (1.27) 6.9 (3.13) 2.9 (1.32) 7.1 (3.20) 2/sec 8,000,000 95% non-condensing 690V 6 kV 130 100 100 E-Frame 105 mm 4.1 x 8.0 x 3.5 (105 x 203 x 90) 8.5 x 9.5 x 3.8 (216 x 242 x 97) 4.1 x 8.0 x 3.5 (105 x 203 x 90) 8.5 x 9.5 x 3.8 (216 x 242 x 97) 1.33 x 4.13 (33.8 x 105) 7.87 x 9.06 (200 x 230) 1.33 x 4.13 (33.8 x 105) 7.87 x 9.06 (200 x 230) Yes Yes No 6.7 (3.05) 16.9 (7.67) 7.1 (3.20) 16.8 (7.60) 2/sec 8,000,000 95% non-condensing 690V 6 kV 250 200 150

Vol. 2, Ref. No. [0278]

F-Frame 140 mm 5.6 x 14.0 x 7.0 (142 x 356 x 178) 11.7 x 17.2 x 7.0 (297 x 437 x 178) 5.7 x 19.4 x 7.0 (145 x 493 x 178) 11.8 x 21.0 x 7.0 (300 x 533 x 178) 1.75 x 13.0 (44.5 x 330) 7.82 x 13.0 (199 x 330) 1.75 x 18.3 (44.5 x 465) 7.82 x 18.3 (198.5 x 465) Yes Yes No 20 (9.1) 48 (21.8) 27 (12.3) 55 (25.0) 1/sec 5,000,000 95% non-condensing 690V 6 kV 450 420 270

Overall Dimensions in Inches (mm)


Non-reversing Contactor

wxhxd
1.8 x 4.4 x 2.4 (45 x 111 x 60) 3.8 x 5.9 x 2.7 (96 x 149 x 69) 1.8 x 5.0 x 2.5 (45 x 127 x 63) 3.8 x 5.9 x 2.7 (96 x 149 x 69) 1.33 x 4.0 (33.8 x 101) 3.15 x 5.35 (80 x 136) 1.33 x 4.62 (33.8 x 117.3) 3.15 x 5.35 (80 x 136) Yes Yes Yes .7 (.31) 1.9 (.86) .9 (.40) 2.0 (.90) 3/sec 10,000,000 95% non-condensing 690V 6 kV 50 32 32

34

Reversing Contactor Non-reversing Starter Reversing Starter Non-reversing Contactor Reversing Contactor Non-reversing Starter Reversing Starter

Mounting Hole Spacing in Inches (mm) w x h

Mounting Positions
Panel-Vertical Panel-Horizontal DIN Rail Mountable

Weights in Lb. (kg)


Non-reversing Contactor Reversing Contactor Non-reversing Starter Reversing Starter Maximum

Mechanical Operating Rate Mechanical Life Humidity


95% non-condensing

Insulation Voltage (Ui)


690V

Impulse Withstand Voltage (Uimp)


6 kV

Max. Current Ratings @ 480V Ue


AC-1 Thermal Current (Ith) 20

AC-2, AC-3 12 Operating Current (Ie) AC-4 10 Operating Current (Ie)

Max. Current Ratings @ 600V Ue


AC-1 Thermal Current (Ith) AC-2, AC-3 Operating Current (Ie) AC-4 Operating Current (Ie) 16 9 8 40 25 18 68 40 34 104 80 68 200 160 120 360 336 150

Auxiliaries add approximately 1.0" (25 mm) to depth for single, 1.2" (30 mm) for dual. Non-reversing contactors and starters only. 99% by application.

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical


June 2005
Vol. 2, Ref. No. [0279]

34-15

Technical Data and Specications

Table 34-10. Specications (Continued)


Description A-Frame 27 mm IP20 IP20 IP20 B-Frame 45 mm IP20 IP10 IP20 C-Frame 54 mm IP20 IP10 IP10 D-Frame 76 mm IP20 IP00 IP10 E-Frame 105 mm IP20 IP00 IP00 F-Frame 140 mm IP20 IP00 IP00

Finger Protection
Front At Terminals At Terminals with max. size wire installed 1 Wire per Terminal (stranded or solid) 2 Wires per Terminal (stranded or solid) Strip Length Torque (max.)

34

Terminals L1, L2, L3/T1, T2, T3


16 12 AWG (1.5 2.5 mm2) 16 12 AWG (1.5 2.5 mm2) .32" (8 mm) 18 lb-in (2.0 Nm) 14 8 AWG (1.5 10 mm2) 14 10 AWG (1.5 4 mm2) .45" (11 mm) 20 lb-in (2.2 Nm) for 14 10 AWG (1.5 6 mm2); 25 lb-in (2.8 Nm) for 8 AWG (10 mm2) 14 4 AWG (1.5 16 mm2) 14 6 AWG (1.5 16 mm2) .5" (12 mm) 35 lb-in (4.0 Nm) for 14 10 AWG (1.5 6 mm2); 40 lb-in (4.5 Nm) for 8 AWG (10 mm2); 45 lb-in (5.0 Nm) for 6 4 AWG (16 mm2) 3 mm 24V DC 20 28 14 1 AWG (1.5 35 mm2) 14 2 AWG (1.5 25 mm2) .7" (18 mm) 45 lb-in (5.0 Nm) for Single 14 8 AWG (1.5 10 mm2); 100 lb-in (11 Nm) for Single 6 1 AWG (16 35 mm2) and Dual Wire Combinations 6 250 MCM (16 120 mm2) 6 3/0 AWG (16 70 mm2) .8" (21 mm) 250 lb-in (28 Nm) 4 750 MCM (25 420 mm2) 1/0 300 MCM (50 150 mm2) 1.5" (40 mm) 550 lb-in (62 Nm)

Driver Flat Hex Key

PZ1 or 3/16" 24V DC 20 28

2.5 mm 24V DC 20 28

4 mm [5/32"] 24V DC 20 28

8 mm [5/16"] 24V DC 20 28

8 mm [5/16"] 24V DC 20 28

Operation Performance
Coil Voltage (nominal) Coil Operating Voltage Range (VDC)

Control Terminals
(- and +) 1 Wire per Terminal (- and +) 2 Wires per Terminal (P, F, R, 1, 2, 3) 1 Wire per Terminal (P, F, R, 1, 2, 3) 2 Wires per Terminal Torque (max.) Strip Length Driver (Flat) 14 12 AWG (1.5 2.5 mm2) 14 AWG (1.5 mm2) 22 12 AWG (0.5 2.5 mm2) 14 12 AWG (1.5 2.5 mm2) 14 AWG (1.5 mm2) 22 12 AWG (0.5 2.5 mm2) 14 12 AWG (1.5 2.5 mm2) 14 AWG (1.5 mm2) 22 12 AWG (0.5 2.5 mm2) 18 14 AWG (0.75 1.5 mm2) 4.5 lb-in (.5 Nm) .25 (7 mm) .13 (3.5 mm) -40 to +149F (-40 to +65C) -58 to +176F (-50 to +80C) 14 12 AWG (1.5 2.5 mm2) 14 AWG (1.5 mm2) 22 12 AWG (0.5 2.5 mm2) 18 14 AWG (0.75 1.5 mm2) 4.5 lb-in (.5 Nm) .25 (7 mm) .13 (3.5 mm) -40 to +149F (-40 to +65C) -58 to +176F (-50 to +80C) 14 12 AWG (1.5 2.5 mm2) 14 AWG (1.5 mm2) 22 12 AWG (0.5 2.5 mm2) 14 12 AWG (1.5 2.5 mm2) 14 AWG (1.5 mm2) 22 12 AWG (0.5 2.5 mm2)

18 14 AWG 18 14 AWG (0.75 1.5 mm2) (0.75 1.5 mm2) 4.5 lb-in (.5 Nm) 4.5 lb-in (.5 Nm) .25 (7 mm) .13 (3.5 mm) -40 to +149F (-40 to +65C) -58 to +176F (-50 to +80C) .25 (7 mm) .13 (3.5 mm) -40 to +149F (-40 to +65C) -58 to +176F (-50 to +80C)

18 14 AWG 18 14 AWG (0.75 1.5 mm2) (0.75 1.5 mm2) 4.5 lb-in (.5 Nm) 4.5 lb-in (.5 Nm) .25 (7 mm) .13 (3.5 mm) -40 to +149F (-40 to +65C) -58 to +176F (-50 to +80C) .25 (7 mm) .13 (3.5 mm) -40 to +149F (-40 to +65C) -58 to +176F (-50 to +80C)

Temperature
Operating Storage

Use Class B 75C copper wire only (or 90C copper wire sized for 75C operation per NEC). Not applicable to starter T1, T2, T3. One wire per terminal. 27 mm Non-reversing Starter (- and +) 14 AWG (1.5 mm2) only P, F, 1, A: 1 wire per terminal only, 22 14 AWG (0.5 1.5 mm2) Torque: 2.25 lb-in (.25 Nm) Driver: .09 in (2.5 mm) Consult factory for higher ratings.

CA08102001E

For more information visit: www.EatonElectrical.com

34-16

IEC Contactors & Starters IT. Electro-Mechanical


June 2005

Technical Data and Specications


Table 34-10. Specications (Continued)
Description A-Frame 27 mm 15G/5G 2 1 6600 (2000) 15 67 8 60 B-Frame 45 mm 15G/5G 2 1 6600 (2000) 15 75 5 65 C-Frame 54 mm 15G/5G 2 1 6600 (2000) 15 80 5 70 D-Frame 76 mm 15G/5G 2 1 6600 (2000) 25 88 12 75 E-Frame 105 mm 15G/5G 2 1 6600 (2000) 30 95 15 80

Vol. 2, Ref. No. [0280]

F-Frame 140 mm 15G/5G 2 1 6600 (2000) 70 200 120 250 50 150 70 200

Environmental
Shock/Vibration Pollution Degree EMC Environment Altitude in Ft. (m)

34

Pull-In Time (mS) @ 24V DC


Excl. Debounce Time Incl. Debounce Time Excl. Debounce Time Incl. Debounce Time

Dropout Time (mS) @ 24V DC

Consult factory for higher ratings. Add 50 mS for 27 and 140 mm Starters for additional microprocessor. The Non-reversing Starter requires the use of all six mounting screws for the maximum rating.

Note:
Response time for Control Inputs = Debounce Time The time between operating forward and reverse must be greater than

the Debounce Time.

Note: At other temperatures expressed in C, for either inrush or sealed, use the 20C value from the table in the following:
Watts = W20 [1.1 .005(T) and Amps = A20 [1.1 .005(T)] For example, inrush requirements for a D-Frame Starter at -25C would be: Watts = 130 [1.1 .005 (-25)] = 160 Amps = 5.4 [1.1 .005 (-25)] = 6.6

Table 34-11. 24V DC Power Supply Requirements @ 68F (20C) (see Note at bottom left)
Contactor/Starter Size Catalog Number E_11A__X3N E_01A___3A E_11B__X3N E_01B___3A E_11C__X3N E_01C___3A E__1D___3_ E__1E___3_ E__1F__X3N E_01F___3A Frame/ mm A/27 A/27 B/45 B/45 C/54 C/54 D/76 E/105 F/140 F/140 Sealed In Inrush Wattage Amps Wattage Amps Duration (mS) 1.3 2.0 3.7 3.2 4.2 3.6 5.0 5.6 12.0 13.0 .054 .083 .15 .13 .18 .15 .21 .23 .50 .54 20 20 80 80 90 90 130 140 200 200 .83 .83 3.3 3.3 3.8 3.8 5.4 5.8 8.3 8.3 30 30 50 50 50 50 65 85 250 250

The sum of the sealed in values of the contactors/starters must be less than the power supply sealed in value. The largest contactor/starter inrush value must be less than the power supply inrush value. Refer to Tab 44 for further power supply information. _ indicates missing digit/character of the Catalog Number; may have multiple values.

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical


June 2005
Vol. 2, Ref. No. [0281]

34-17

Technical Data and Specications

Electrical Life AC-1, AC-2, AC-3 and AC-4 Utilization Categories


Table 34-12. Utilization Categories
The International Electrotechnical Commission (IEC) has developed utilization categories for contactors and auxiliary contacts. The categories describe the type of electrical load and the conditions for making and breaking the current. Category AC-1 AC-2 AC-3 AC-4 Typical Application Non-inductive or slightly inductive loads: Resistance furnaces, heating. Slip-ring motors: Starting and stopping of running motors Squirrel cage motors: Starting, switching off motors during running (motors in most industrial applications typically fall into this category). Squirrel cage motors: Starting, plugging , inching (very few applications in industry are totally AC-4).

34

Plugging is stopping or reversing the motor rapidly by reversing the connections while the motor is running. Inching or jogging is energizing the motor once or repeatedly for short durations to obtain small movements of the motor driven load.

Trip Time (Seconds)

Life Load Curves Eatons CutlerHammer IT. Electro-Mechanical Series IEC contactors have been designed and manufactured for superior life performance. All testing has been based on requirements as found in IEC 60947-4-1 and conducted by us. When selecting a contactor designed to IEC requirements, the specier must give attention to the specic load, utilization category and the required electrical life. For a denition of Utilization Categories, see Table 34-12 above.

Note: AC-3 tests are conducted at rated device currents and AC-4 tests are conducted at six-times rated device currents. All tests have been run at 460V, 60 Hz.

Trip Times
1000.0

Actual application life may vary, depending on environmental conditions and application duty cycle.
100.0

10,000,000

Frame Size D E F

10.0

5 3 6 1 4

Operations

1,000,000

1.0

100,000 0.1 1 10,000 1 6 9 12 18 32 50 85 125 200 315 10 25 40 65 100 160 250 420 Operational Current 2 3 4 5 6 7 8 9 10

Multiples of FLA 1 2 3 4 5 6 Trip Class 10 Cold Trip Class 10 Hot Trip Class 20 Cold Trip Class 20 Hot Trip Class 30 Cold Trip Class 30 Hot

Note: Preliminary data.

Figure 34-1. Electrical Life AC-3 Utilization Category

10,000,000

Frame Size D E F

Figure 34-3. Class 10, 20 and 30 Trip Curves

Contactor Choice
Operations 1,000,000

100,000

10,000 0.1

Note: Preliminary data.

6 9 18 32 50 85 125 250 10 25 40 65 100 148 320 Operational Current

Decide what utilization category the application is and choose the appropriate curve from Figure 34-1 or Figure 34-2. Locate the intersection of the lifeload curve with the operational current (le) of the application, as found on the horizontal axis. Read the estimated contact life along the vertical axis in number of operations.

Figure 34-2. Electrical Life AC-4 Utilization Category


CA08102001E For more information visit: www.EatonElectrical.com

34-18

IEC Contactors & Starters IT. Electro-Mechanical


June 2005

Accessories

Vol. 2, Ref. No. [0282]

Modular Components Contactor Field Assembly


IEC Contact Block Non-reversing Coil Controller FVNR Contactor

34
EXAMPLE FOR A FULL VOLTAGE NON-REVERSING CONTACTOR: E04NC50X3N + E02NCXCXNN = E111C50X3N Reversing Kit

(2) IEC Contact Blocks

Reversing Coil Controller

Mechanical Interlock

(2) Fanning Strips

Mounting Plate

FVR Contactor

EXAMPLE FOR A FULL VOLTAGE REVERSING CONTACTOR: (2) E04NC50X3N + E03NCXCXNN + EMRKTC (REVERSING KIT) = E511C50X3N

Figure 34-4. Modular Contactor Assembly

Modular Components Starter Field Assembly


IEC Contact Block Non-reversing Overload Relay FVNR Starter

EXAMPLE FOR A FULL VOLTAGE NON-REVERSING STARTER: E04NC50X3N + E05NCXRL3A = E101C50L3A (2) IEC Contact Blocks Reversing Overload Relay Mechanical Interlock

Reversing Kit

(2) Fanning Strips

Mounting Plate

FVR Starter

EXAMPLE FOR A FULL VOLTAGE REVERSING STARTER: (2) E04NC50X3N + E06NCXRL3A + EMRKTC (REVERSING KIT) = E501C50L3A

Figure 34-5. Modular Starter Assembly

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical


June 2005
Vol. 2, Ref. No. [0283]

34-19

Accessories

IEC Contact Block

IEC Solid-State Overload Relay

B Frame

34
Non-reversing Reversing

Table 34-13. IEC Contact Block


Frame B-Frame 45 mm C-Frame 54 mm D-Frame 76 mm E-Frame 105 mm Amperes 18 25 32 40 50 65 85 100 125 160 200 Catalog Number E04NB18X3N E04NB25X3N E04NB32X3N E04NC40X3N E04NC50X3N E04ND65X3N E04ND85X3N E04ND10X3N E04NE12X3N E04NE16X3N E04NE20X3N Price U.S. $ 121.00 141.00 167.00 179.00 201.00 292.00 341.00 545.00 875.00 1,290.00 1,460.00

Table 34-15. IEC Solid-State Overload Relay


Frame Overload Adjustment Range (Amperes) .25 .8 .59 1.9 1.4 4.4 2.8 9.0 3.8 12 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 6.3 20 10 32 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 5.0 16 8.4 27 16 50 5.0 16 8.4 27 14 45 31 100 14 45 28 90 42 135 63 200 42 135 84 270 131 420 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 6.3 20 10 32 .25 .8 .59 1.9 1.4 4.4 2.8 9.0 5.0 16 8.4 27 16 50 5.0 16 8.4 27 14 45 31 100 14 45 28 90 42 135 63 200 Catalog Number Price U.S. $

Non-reversing
A-Frame 27 mm E05NAXRA3A E05NAXRB3A E05NAXRC3A E05NAXRD3A E05NAXRE3A E05NBXRA3A E05NBXRB3A E05NBXRC3A E05NBXRD3A E05NBXRG3A E05NBXRJ3A E05NCXRA3A E05NCXRB3A E05NCXRC3A E05NCXRD3A E05NCXRF3A E05NCXRH3A E05NCXRL3A E05NDXRF3A E05NDXRH3A E05NDXRK3A E05NDXRN3A E05NEXRK3A E05NEXRM3A E05NEXRP3A E05NEXRR3A E05NFXRP3A E05NFXRS3A E05NFXRT3A E06NBXRA3A E06NBXRB3A E06NBXRC3A E06NBXRD3A E06NBXRG3A E06NBXRJ3A E06NCXRA3A E06NCXRB3A E06NCXRC3A E06NCXRD3A E06NCXRF3A E06NCXRH3A E06NCXRL3A E06NDXRF3A E06NDXRH3A E06NDXRK3A E06NDXRN3A E06NEXRK3A E06NEXRM3A E06NEXRP3A E06NEXRR3A 130.00 130.00 130.00 130.00 130.00 131.00 131.00 131.00 131.00 131.00 * 234.00 234.00 234.00 234.00 234.00 234.00 * 309.00 309.00 309.00 309.00 515.00 515.00 515.00 515.00 890.00 890.00 890.00 * * * * * * * * * * * * * * * * * * * * *

B-Frame 45 mm

Note:
E04N + E05N = E101; E04N + E02N = E111 (45 105 mm) E04N + E06N = E501; E04N + E03N = E511 (45 105 mm)

IEC Coil Controller

C-Frame 54 mm

D-Frame 76 mm

B Frame Non-reversing

E-Frame 105 mm

Table 34-14. IEC Coil Controller


Frame Catalog Number E02NBXCXNN E02NCXCXNN E02NDXCXNN E02NEXCXNN EMUCCF E03NBXCXNN E03NCXCXNN E03NDXCXNN E03NEXCXNN EMUCCF Price U.S. $ 45.25 68.50 102.00 137.00 * * * * * * F-Frame 140 mm

Non-reversing
B-Frame 45 mm C-Frame 54 mm D-Frame 76 mm E-Frame 105 mm F-Frame 140 mm

Reversing
B-Frame 45 mm

Reversing
B-Frame 45 mm C-Frame 54 mm D-Frame 76 mm E-Frame 105 mm F-Frame 140 mm C-Frame 54 mm

D-Frame 76 mm

E-Frame 105 mm

*Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 CA08102001E For more information visit: www.EatonElectrical.com

34-20

IEC Contactors & Starters IT. Electro-Mechanical


June 2005

Accessories

Vol. 2, Ref. No. [0284]

Auxiliary Contacts

34

Auxiliary Contacts are available for mounting on IT. Electro-Mechanical Contactors and Starters. The various choices available for non-reversing models are shown in Tables 34-16 and 34-17, and their ratings in Tables 34-18 34-20. For reversing models, the number of auxiliaries indicated is for each of the contactors/starters in the assembly.

Table 34-18. IEC Ratings


DC-13
Ue le

AC-15
Ue le

Voltage 24 48 125 250

Amps. 5 2.5 1.1 .55

Voltage 48 120 240 440

Amps. 8 6 4 2

Table 34-19. NEMA A600 Ratings


Current Make and Interrupting Break Continuous Thermal AC Voltage 120 240 60 6 10 10 30 3 10 10 480 15 1.5 10 10 600 12 1.2 10 10

Table 34-16. Auxiliary Contact Availability A F Frames


Front Mounted (Maximum Auxiliaries per Contactor/Starter) Contactor/Starter Size A-Frame 27 mm 1 1 1 B-Frame 45 mm 3 3 2 2 2 2 C-Frame 54 mm 3 3 2 2 2 3 D-Frame 76 mm 3 3 3 3 3 3 E-Frame 105 mm 3 3 3 3 3 3 F-Frame 140 mm 3 Contact Type Catalog Number Price U.S. $

1NO 1NC 1NO-1NC 2NO 2NC Logic Level 1NO-1NC

EMA13 EMA14 EMA15 EMA16 EMA17 EMA70

* 23.30 31.50 31.50 31.50 *

Table 34-20. NEMA P300 Ratings


Current Make and Interrupting Break Continuous Thermal DC Voltage 125 1.1 1.1 5 5 250 .55 .55 5 5

Other combinations: Single, dual, single; Dual, single, dual; Dual, logic level, dual. For reversers, multiply quantities by two. EMA13 3 NO 4 EMA14 1 NC 2 EMA15 13 NO 14 21 NC 22 EMA16 13 NO 14 23 NO 24 EMA17 11 NC 12 21 NC 22 4 NO EMA70 2 NC

Table 34-21. EMA70 Auxiliary Contact


DC-12 Ue 30 Ie .1 AC-12 Ue 250 Ie .1

1 1 Common

Figure 34-6. Connecting Diagram A F Frames Table 34-17. Auxiliary Contact Availability F-Frame 140 mm
Auxiliary Contacts per Non-reversing and Reversing Contactor or Starter Max. 2 2 6 2 6 2 2 2 3 Contact Type 1NO 1NO-1NC 1NO 1NO Logic Level 1NC 1NC Logic Level 1NO-1NC 1NO-1NC Logic Level 1NO-1NC Logic Level Description Base auxiliary (max. 1 per side) Base auxiliary (max. 1 per side) C320KGS41 or C320KGS42 required (max. 3 Add-on auxiliaries per side) C320KGS41 or C320KGS42 required (max. 1 Add-on auxiliary per side) C320KGS41 or C320KGS42 required (max. 2 Add-on auxiliaries per side) C320KGS41 or C320KGS42 required (max. 1 Add-on auxiliary per side) C320KGS41 or C320KGS42 required (max. 1 Add-on auxiliary per side) C320KGS41 or C320KGS42 required (max. 1 Add-on auxiliary per side) Front Mounted Only Catalog Number C320KGS41 C320KGS42 C320KGS20 C320KGS20L C320KGS21 C320KGS21L C320KGS22 C320KGS22L EMA70 Price U.S. $ 51.50 70.00 51.50 51.50 70.00 *

Starter Network Adapter Product (SNAP)

Cat. No. D77B-DSNAP-X1 with 54 mm IT. Starter

Form C Contacts. For reversers, multiply quantities by two.

Note:
Side Mounted: Maximum (10) total circuits. Front Mounted: Maximum (6) total circuits. Maximum 4 auxiliaries per side (base + 3 side mounted). EMASA/B_ have been superseded by the above Catalog Numbers.

The Starter Network Adapter Product (SNAP) is a front-mount device that serves as a single DeviceNet node, providing communication capability, control and monitoring to Eatons Cutler-Hammer Intelligent Technologies (IT.) Electromechanical Starters (B F Frames) as well as the IT. S75X SoftStart. When HAND-OFF-AUTO is required, the HOA option will allow for the connection of hard wired operators. This option allows for Hand Control even if the DSNAP is not connected. For more information and pricing, see Tab 50.

*Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical


June 2005
Vol. 2, Ref. No. [0285]

34-21

Accessories

IEC Reversing Mounting Plates

IEC Mechanical Interlock


Table 34-24. IEC Mechanical Interlock
Frame Size BE F Catalog Number EMMB C321KM50 Price U.S. $ * 65.00

The A-Frame 27 mm does not have a separate mechanical interlock due to its embedded design and board requirements. The F-Frame 140 mm uses the Freedom Series Mechanical Interlock.

34

Table 34-22. IEC Reversing Mounting Plates


Frame Size BC D E Catalog Number EMA9B EMA9D EMA9E Price U.S. $ * * *

IEC 2-Wire Reversing Interface


Table 34-25. IEC 2-Wire Reversing Interface
Description 8-Pin for 45 140 mm (IEC 6A 420A Reversing Starters) 8-Pin for 45 105 mm (IEC 18A 200A Reversing Contactors) Catalog Number EMA2WR8 Price U.S. $ 104.00

IEC Reversing Kits


Table 34-23. IEC Reversing Kits
Frame Size B C D E F Description For Contactor and Starter For Contactor and Starter For Contactor and Starter For Contactor and Starter For Contactor Catalog Number EMRKTB EMRKTC EMRKTD EMRKTE EMRKTF Price U.S. $ * * * * *

Includes Fanning Strips, Mechanical Interlock, Mounting Plate and hardware. Includes Fanning Strips (Bus Bar Set), Mechanical Interlock and hardware.

IEC Control Terminals

Table 34-26. IEC Control Terminals


No. of Pins 8 Terminal Markings IEC Size Coil Controller Nonreversing Contactor Overload Reversing Nonreversing Starter Reversing Nonreversing X X X X X X X X X X X X X X X X X X X EMA81 EMA80L * * X X X X X X X X X X X X X X X X X X X X X X X X X X Reversing Nonreversing Catalog Reversing Number X X X X X X EMA77L EMA77LR EMA78L * * * EMA76L Price U.S. $

-+PFR123

A B C D E F

5 5 4

-+PFR RFP+-+PF

F F A B C

6 (2) 5

-+PF1A -+PFR and RFP+-

A F

Non-locking. Consists of (1) EMA77L and (1) EMA77LR inter-wired. *Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 CA08102001E For more information visit: www.EatonElectrical.com

34-22

IEC Contactors & Starters IT. Electro-Mechanical


June 2005

Renewal Parts

Vol. 2, Ref. No. [0286]

IEC Contact Kits

Lug Kits

34
Table 34-29. Lug Kits
Frame Size C D Description 3 pc. 1 pc. Catalog Number EMLUGKTC EMLUGKTD Price U.S. $ * * * * * *

Table 34-27. IEC Contact Kits


Frame Size C Description 3-Pole, 40A Hold Open 3-Pole, 40A Non-hold Open 3-Pole, 50A Hold Open 3-Pole, 50A Non-hold Open D 3-Pole, 65A Hold Open 3-Pole, 65A Non-hold Open 3-Pole, 85A Hold Open 3-Pole, 85A Non-hold Open 3-Pole, 100A Hold Open 3-Pole, 100A Non-hold Open E 3-Pole, 125A 3-Pole, 160A 3-Pole, 200A F 3-Pole, 250A 3-Pole, 315A 3-Pole, 420A Catalog Number EMCKT40 EMCKT40NH EMCKT50 EMCKT50NH EMCKT65 EMCKT65NH EMCKT85 EMCKT85NH EMCKT100 EMCKT100NH EMCKT125 EMCKT160 EMCKT200 EMCKT250 EMCKT315 EMCKT420 Price U.S. $ * * * * * * * * * * * * * * * *

1 pc. For Contactor and Line EMLUGKTLE Side Starter 1 pc. For Load Side Starter EMLUGKTTE EMLUGKTFA EMLUGKTFB Horizontal Box Lug Vertical Box Lug

Kit includes Lug Cover required for contactors only.

Fanning Strips
Table 34-30. Reversing Fanning Strips
Frame Size A B C D E F Description Line and Load Side Wire Sets Line Side Load Side Line Side Load Side Line Side Load Side Line Side Load Side Line Side Bus Bar Set Load Side Bus Bar Set Catalog Number EMFRA EMFRLB EMFRTB EMFRLC EMFRTC EMFRLD EMFRTD EMFRLE EMFRTE EMFRLF EMFRTF Price U.S. $ * * * * * * * * * * *

24V DC Coils

DIN Rail Catch

Table 34-28. 24V DC Coils


Frame Size B C D E F Catalog Number EMCB EMCC EMCD EMCE EMCF Price U.S. $ * 105. 145. 178. 289.

Table 34-31. DIN Rail Catch


Frame Size BC D Description Catch with Leaf Spring and Pad Catch with Leaf Spring and Pad Catalog Number EMDRCB EMDRCD Price U.S. $ * *

*Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical


June 2005
Vol. 2, Ref. No. [0287]

34-23

Wiring Diagrams

Permissive

Permissive

24V DC

24V DC

Forward

Forward

3-Wire Control Power Supply 24V DC E-Stop

2-Wire Control Power Supply 24V DC E-Stop

1L1

3L2

5L3 24V DC

M P 2T1 4T2 6T3 24V DC Connections Control Terminal Block M 3~ F

34

Optional

Stop

Optional

Start

= Momentary

= Maintained

* Maintained Only 2-Wire Remote Pilot Device

Disconnect AC Power Before Working on this Product

Figure 34-7. Wiring Non-reversing Contactor


Alarm Output A Permissive Forward Forward 3-Wire Control Power Supply 24V DC E-Stop 2-Wire Control Power Supply 24V DC E-Stop Permissive 24V DC 24V DC 1L1 Alarm Reset 3L2 5L3 24V DC P F 1 A

Alarm A

Reset

A 2T1 4T2 6T3 24V DC Connections Control Terminal Block Note: Load side wires pass through the overload and are secured with the contactor terminals, T1, T2 and T3.

Optional

Optional

Stop

Optional

* Reset (Optional)

Optional

TEST STATUS Auto RESET Manual M 3~

Start

Reset (Optional)

Alarm Output (Optional) Permissive Not Used Not Used Forward Forward 3-Wire Control Power Supply 24V DC E-Stop 2-Wire Control Power Supply 24V DC E-Stop Permissive 24V DC Alarm 24V DC 1L1 Reset Alarm 3L2 5L3

N 1

Reset 2

N 1

Optional

* Reset (Optional)

Optional

Optional

Stop

Optional

STATUS TEST Auto

RESET Manual

Start

Reset (Optional)

24V DC P F N 1 2 3 Note: Remove Control Terminal Block before wiring of T1, T2 and T3.

M 3~

= Momentary = Maintained * Maintained Only 2-Wire Remote Pilot Device 24V DC Connections Control Terminal Block

Disconnect AC Power Before Working on this Product

Figure 34-8. Wiring Non-reversing Starters

CA08102001E

For more information visit: www.EatonElectrical.com

34-24

IEC Contactors & Starters IT. Electro-Mechanical


June 2005

Dimensions

Vol. 2, Ref. No. [0288]

Non-reversing and Reversing Contactors (Frame A)


Table 34-32. Approximate Dimensions in Inches (mm)
Frame Size Overall Width A Height B 3.0 (75) 2.9 (73) Depth C 2.4 (60) 2.4 (60) Depth w/ Auxiliary D 3.5 (88) 3.5 (88) Depth added w/DIN Rail E .2 (5) .2 (5) Mounting Holes Width F .76 (19.2) 1.31 (33.2) Height G 2.64 (67) 2.52 (64) Mtg. Hole to Top H .1 (3.5) .2 (5) DIN Rail to Top J .6 (15) .5 (13) Req. Mtg. Screws K (3) #8 M4 (3) #8 M4 Terminals Control P .6 (16) .6 (16) Line Q 1.7 (43) 1.7 (43) Load R 1.7 (43) 1.7 (43)

34

Non-reversing
A 1.1 (27) 2.4 (60)

Reversing
A

D C Line Terminals (1 L1, 3 L2, 5 L3) Q Logic Level Auxiliary Reduce Dim D .28 (7) for the Single Auxiliaries H A F J A J

Standard DIN Rail 1.38 x .3 (35 x 7.5) (Optional Mounting) E Control Terminal Block P R

B G

B G

F Reversing Contactors

Load Terminals (2 T1, 4 T2, 6 T3)

Non-reversing Contactors

Figure 34-9. Approximate Dimensions Inches (mm)

Non-reversing Contactors (Frames B & C)


Table 34-33. Approximate Dimensions in Inches (mm)
Frame Size Overall Width A B C 1.8 (45) 2.1 (54) Height B 4.4 (111) 4.45 (113) Depth C 2.4 (60) 2.4 (60) Depth w/ Auxiliary D 3.6 (91) 3.6 (91) Depth added w/DIN Rail E .1 (3) .1 (3) Mounting Holes Width F 1.33 (33.8) 1.46 (37) Height G 4.0 (101) 4.1 (104) Mtg. Hole to Top H .2 (5) .2 (5) DIN Rail to Top J .9 (23) .8 (20) Req. Mtg. Screws K (3) #8 M4 (3) #8 M4 Terminals Control P .7 (19) .7 (19) Line Q 1.2 (30) 1.2 (30) Load R 1.2 (30) 1.2 (30)

Line Terminals (1 L1, 3 L2, 5 L3)

A F J

Standard DIN Rail 1.38 x .3 (35 x 7.5) (Optional Mounting)

Dual Auxiliary Reduce Dim D .31 (8) for the Single Auxiliaries B G

Load Terminals (2 T1, 4 T2, 6 T3)

Control Terminal Block

K C-Frame Pictured (B-Frame Has Two Lower Mtg. Feet, Reference F Width)

Figure 34-10. Approximate Dimensions Inches (mm)


For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical


June 2005
Vol. 2, Ref. No. [0289]

34-25

Dimensions

Non-reversing Contactors (Frames D & E)


Table 34-34. Approximate Dimensions in Inches (mm)
Frame Size Overall Width A D E 3.0 (76) 4.1 (105) Height B 5.9 (150) 8.0 (203) Depth C 3.1 (79) 3.5 (90) Depth w/ Auxiliary D 4.2 (107) 4.7 (119) Depth added w/DIN Rail E .2 (4) Mounting Holes Width F .94 (24) 1.33 (33.8) Height G 2.87 (73) 4.13 (105) Mtg. Hole to Top H .5 (13) .6 (15) DIN Rail to Top J .9 (23) Req. Mtg. Screws K (4) #6 x 2 M3.5 x 50 (4) #8 x 1.5 M4 x 40 Terminals Control P 2.4 (60) 2.8 (72) Line Q 1.5 (37) 1.7 (42) Load R .6 (14) .3 (8)

34

Line Terminals (1 L1, 3 L2, 5 L3) E

D Q H A F J Dual Auxiliary Reduce Dim D .31 (8) for the Single Auxiliaries B

Standard DIN Rail 1.38 x .3 (35 x 7.5) (Optional Mounting) 76 mm (D-Frame) Only

G K

Load Terminals (2 T1, 4 T2, 6 T3) E-Frame Shown

R P C

Control Terminal Block

2 T1

4 T2

6 T3

Figure 34-11. Approximate Dimensions Inches (mm)

Non-reversing Contactors (Frame F)


Table 34-35. Approximate Dimensions in Inches (mm)
Frame Size Overall Width A F 5.6 (142) Height B 14.0 (356) Depth C 7.0 (178) Depth w/Logic Level Auxiliary D 8.2 (208) Width w/Side Auxiliaries E 6.70 (170) Mounting Holes Width F 1.75 (44.5) Height G 13.0 (330) Mounting Hole to Top H 0.58 (14.7) Req. Mtg. Screws K (4) 5/16 M8 Terminals Control P .8 (20) Line Q 4.4 (112) Load R 4.4 (112)

D C Line Terminals (1 L1, 3 L2, 5 L3) Q K

E A F

G B Side Auxiliary Logic Auxiliary

P R

Control Terminal Block Load Terminals (2 T1, 4 T2, 6 T3)

Figure 34-12. Approximate Dimensions in Inches (mm)


CA08102001E For more information visit: www.EatonElectrical.com

34-26

IEC Contactors & Starters IT. Electro-Mechanical


June 2005

Dimensions

Vol. 2, Ref. No. [0290]

Reversing Contactors (Frames B E)


Table 34-36. Approximate Dimensions in Inches (mm)
Frame Size Overall Width A Height B 5.9 (149) 5.9 (149) 7.4 (188) 9.5 (242) Depth C 2.7 (69) 2.6 (67) 3.3 (84) 3.8 (97) Depth w/ Auxiliary D 3.8 (96) 3.8 (96) 4.4 (112) 4.9 (125) Mounting Holes Width Height F 3.15 (80) 3.15 (80) 5.51 (140) 7.87 (200) G 5.35 (136) 5.35 (136) 6.89 (175) 9.06 (230) Mtg. Hole to Top H .3 (7) .3 (7) .2 (6) .2 (6) Req. Mtg. Screws K (3) #10 M5 (3) #10 M5 (3) #10 M5 (3) #10 M5 Terminals Control P 2.0 (50) 2.0 (50) 2.6 (67) 3.1 (80) Line Q 1.5 (38) 1.5 (38) 1.9 (48) 2.1 (54) Load R .9 (22) .6 (16) .9 (22) .7 (17)

34

B C D E

3.8 (96) 4.5 (114) 6.2 (158) 8.5 (216)

D Line Terminals (1 L1, 3 L2, 5 L3) Q

Dual Auxiliary Reduce Dim D .31 (8) for the Single Auxiliaries

B G

Load Terminals (2 T1, 4 T2, 6 T3)

R P C

Control Terminal Block

F A

Figure 34-13. Approximate Dimensions Inches (mm)

Reversing Contactors (Frame F)


Table 34-37. Approximate Dimensions in Inches (mm)
Frame Size Overall Width A F 11.7 (297) Height B 17.2 (437) Depth C 7.0 (178) Depth w/Logic Level Auxiliary D 8.2 (208) D C Q K Width w/Side Auxiliaries E 12.8 (325) Mounting Holes Width Height F 7.8 (198.5) G 13.0 (330) Mounting Hole to Top H 2.19 (55.5) E A F H Req. Mtg. Screws K (4) 5/16 M8 Terminals Control Line P .8 (20) Q 4.4 (112) Load R 4.4 (112)

Line Terminals (1 L1, 3 L2, 5 L3)

Side Auxiliary Logic Auxiliary

G B

Control Terminal Block P R Load Terminals (2 T1, 4 T2, 6 T3)

Figure 34-14. Approximate Dimensions in Inches (mm)

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical


June 2005
Vol. 2, Ref. No. [0291]

34-27

Dimensions

Non-reversing and Reversing Starters (Frame A)


Table 34-38. Approximate Dimensions in Inches (mm)
Frame Overall Mounting Holes Req. Mtg. Reset Button Terminals Size Width Height Depth Depth w/ Depth added Width Height Mtg. Hole DIN Rail Screws Width Height Depth Control Line Load Auxiliary w/DIN Rail to Top to Top A B 4.0 (102) 4.0 (102) C 3.1 (79) 3.1 (79) D 3.5 (89) 3.5 (89) E .2 (5) .2 (5) F .76 (19.3) 1.31 (33.2) G 3.70 (94.0) 3.52 (89.4) H .1 (3.5) .2 (5) J .6 (15) .5 (13) K (3) #8 M4 (3) #8 M4 L .3 (8.0) .9 (24) M 2.9 (72.4) 3.0 (76.0) N 3.1 (78) 3.1 (78) P 2.2 (55) 2.2 (55) Q 1.7 (43) 1.7 (43) R 1.8 (45) 1.8 (45)

Non-reversing
A 1.20 (31) 2.50 (64)

34

Reversing
A

D Line Terminals (1 L1, 3 L2, 5 L3) Q

Logic Level Auxiliary (Reduce Dim. D .28 (7) for the Single Auxiliaries) H F K J K J

Standard DIN Rail 1.38 x .30 (35 x 7.5) (Optional Mounting)

B G

B G

E Load Terminals (2 T1, 4 T2, 6 T3) Control Terminal Block R P N C

Reset Button .015 (.4) Deflection to Reset

Reset Button L A Non-reversing Starter L B A Reversing Starter

Reset Button

Figure 34-15. Approximate Dimensions Inches (mm)

CA08102001E

For more information visit: www.EatonElectrical.com

34-28

IEC Contactors & Starters IT. Electro-Mechanical


June 2005

Dimensions

Vol. 2, Ref. No. [0292]

Non-reversing Starters (Frames B E)


Table 34-39. Approximate Dimensions in Inches (mm)
Frame Size Overall Width Height A B 5.0 (127) 5.4 (138) 5.9 (150) 8.0 (203) Depth C 2.5 (63) 2.5 (63) 3.1 (79) 3.5 (90) Depth w/ Auxiliary D 3.6 (91) 3.6 (91) 4.2 (107) 4.7 (119) Depth added w/DIN Rail E .1 (3) .1 (3) .2 (4) Mounting Holes Width Height F 1.33 (33.8) 1.46 (37) .94 (24) 1.33 (33.8) G 4.62 (117.3) 5.04 (128) 2.87 (73) 4.13 (105) Req. Mtg. Screws K (3) #8 M4 (3) #8 M4 (4) #6 x 2 M3.5 x 50 (4) #8 x 1.5 M4 x 40 Reset Button Width Height L .6 (14) .7 (17) .7 (17) .7 (17) M 3.6 (91) 3.7 (93) 4.2 (106) 5.7 (146) Depth N 2.5 (63) 2.4 (62) 3.1 (78) 3.5 (88) Terminals Control Line P 1.7 (44) 1.8 (45) 2.4 (60) 2.8 (72) Q 1.2 (30) 1.2 (30) 1.5 (37) 1.7 (42) Load R .6 (16) .3 (8) .6 (14) .3 (8)

34

B C D E

1.8 (45) 2.1 (54) 3.0 (76) 4.1 (105)

D Line Terminals (1 L1, 3 L2, 5 L3) Q Dual Auxiliary Reduce Dim D .3 (7) for the Single Auxiliaries

A F J M

Standard DIN Rail 1.38 x .3 (35 x 7.5) (Optional Mounting) R P N C

B G Reset Button .015 (0.4) Deflection to Reset Load Terminals (2 T1, 4 T2, 6 T3) L

K (D and E Frames)

Reset Button K (B and C Frames)

Control Terminal Block E

Figure 34-16. Approximate Dimensions Inches (mm)

Non-reversing Starter (Frame F)


Table 34-40. Approximate Dimensions in Inches (mm)
Frame Overall Size Width Length Depth Depth w/Logic Level Auxiliary A B C D F 5.7 (145) 19.4 (493) 7.0 (178) 8.2 (208) Width w/Side Auxiliaries E 6.7 (170) Mounting Holes Req. Mtg. Reset Button Terminals Width Height Mntg. Screws Width Height Depth Control Line Load Load Hole to Top F G I K L M N P Q R S 1.75 (44.5) 18.3 (465) .58 (14.7) (4) 5/16 M8 2.4 (61) 12.4 (315) 5.3 (135) 5.0 (126) 4.4 (112 ) 3.0 (75) 4.0 (101)

Line Terminals (1 L1, 3 L2, 5 L3)

D C Q K

E F H

M Side Auxiliary Logic Auxiliary G B

Control Terminal Block

Reset Button .015 (.4) Deflection to Reset

Load Terminals (2 T1, 6 T3) (4 T2)

R S P N

L A

Figure 34-17. Approximate Dimensions in Inches (mm)


For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical


June 2005
Vol. 2, Ref. No. [0293]

34-29

Dimensions

Reversing Starters (Frames B E)


Table 34-41. Approximate Dimensions in Inches (mm)
Frame Size Overall Width Length Depth Depth w/ Auxiliary D 3.8 (96) 3.8 (96) 4.4 (112) 4.9 (125) Mounting Holes Width Height Mtg. Hole to Top H .28 (7) .28 (7) .24 (6) .24 (6) Req. Mtg. Screws Reset Button Width Height Depth Terminals Control Line Load

A B C D E 3.8 (96) 4.5 (114) 6.2 (158) 8.5 (216)

B 5.9 (149) 5.9 (149) 7.4 (188) 9.5 (242)

C 2.7 (69) 2.6 (67) 3.3 (84) 3.8 (97)

F 3.15 (80) 3.15 (80) 5.51 (140) 7.87 (200)

G 5.35 (136) 5.35 (136) 6.89 (175) 9.06 (230)

K (3) #10 M5 (3) #10 M5 (3) #10 M5 (3) #10 M5

L 1.6 (40) 1.7 (43) 2.3 (58) 2.9 (73)

M 3.8 (97) 4.1 (104) 5.5 (139) 7.2 (182)

N 2.7 (68) 2.6 (65) 3.3 (83) 3.7 (94)

P 2.0 (50) 2.0 (50) 2.6 (67) 3.1 (80)

Q 1.5 (38) 1.5 (38) 1.9 (48) 2.1 (54)

R .9 (22) .6 (16) .9 (22) .7 (17)

34

D Line Terminals (1 L1, 3 L2, 5 L3) Q Dual Auxiliary Reduce Dim D .3 (7) for the Single Auxiliaries Reset Button .015 (0.4) Deflection to Reset Load Terminals (2 T1, 4 T2, 6 T3) R P N C Control Terminal Block

B G

Reset Button L F A

Figure 34-18. Approximate Dimensions Inches (mm)

Reversing Starter (Frame F)


Table 34-42. Approximate Dimensions in Inches (mm)
Frame Overall Mounting Holes Size Width Length Depth Depth w/Logic Width Width H1 Mntg. H2 Level Auxiliary w/Side Hole Auxiliaries to Top A B C D E F G H I F 11.8 (300) 21.0 (533) 7.0 (178) 8.2 (208) 12.8 (325) 7.82 (199) 18.3 2.19 (465) (55.5) Req. Reset Button Terminals Mtg. Width Height Depth Control Line Screws K L 5.4 (138) M 12.4 (315) N 5.3 (135) P 5.0 (126) Q Load Load

S 4.0 (101)

13 (5) 5/16 (330) M8

4.4 3.0 (112) (75)

Line Terminals (1 L1, 3 L2, 5 L3)

D C Q K

E F H

I Side Auxiliary Logic Auxiliary

M G B

Control Terminal Block Load Terminals (2 T1, 6 T3) (4 T2) R S P N L F A

Reset Button .015 (.4) Deflection to Reset

Figure 34-19. Approximate Dimensions in Inches (mm)


CA08102001E For more information visit: www.EatonElectrical.com

34-30

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Product Family Overview

Vol. 2, Ref. No. [0294]

Contents
Description Product Family Overview Product Description . . . . . . . Standards and Certications . . . . . . . . . . . Cover Control . . . . . . . . . . . Catalog Number Selection . . . . . . . . . . . . . . Contactors. . . . . . . . . . . . . . . . . Non-combination Starters. . . . Fusible and Non-fusible Combination Starters . . . . . . Combination HMCP/HCPE Starters . . . . . . . . . . . . . . . . . . Modication Codes . . . . . . . . . Page 34-30 34-30 34-30 34-31 34-32 34-34 34-36 34-44 34-49

Cover Control
Non-reversing and Reversing
Factory Installed Pilot Devices
To order factory installed pilot devices, change the 9th character of the Catalog Number to the alpha shown in Table 34-43. Example: to order an ECR0514CAA with START/STOP pushbuttons and a red RUN pilot light, change the A to a C, i.e. ECR0514CCA. Table 34-43. Pilot Devices for IT. IEC
Description

Flange Control Kits


For on-the-job conversion of Type 1, 3R, 4X and 12 enclosed starters. Knockouts are provided on the Type 1 ange. Type 3R, 4X and 12 have prepunched holes with removable hole plugs. Cover Mounted Field Installable Kits are specied in Table 34-43.

34

Factory Installed Flange Control Position 9 Alpha Code Adder U.S. $ A B C D E F G H J K L M N P Q R S T U V W X A B C D E F H J K P Q R V W X * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Cover Mounted Field Installation Kits Non-combination and Combination Catalog Price Number U.S. $ C400T1 C400T2 C400T12 C400T3 C400T4 C400T5 C400T9 C400T10 C400T11 C400T13 C400T14 70. 70. 70. 48. 48. 48. * * * * 70. 216. 146. * *

Non-reversing
No Cover Mounted Pilot Devices START/STOP Pushbuttons with Red RUN Pilot Light with Red RUN/Green OFF Lights ON/OFF Pushbuttons with Red RUN Pilot Light with Red RUN/Green OFF Lights HAND/OFF/AUTO Selector Switch with Red RUN Pilot Light with Red RUN/Green OFF Lights START Pushbutton ON Pushbutton OFF Pushbutton Red RUN Pilot Light Green OFF Red RUN/Green OFF Pilot Lights START/STOP Selector Switch with Red RUN Pilot Light with Red RUN/Green OFF Lights ON/OFF Selector Switch with Red RUN Pilot Light with Red RUN/Green OFF Lights

Type 1 Non-combination IT. Contactor

Product Description
The Cutler-Hammer Intelligent Technologies (IT.) Electro-Mechanical line of Contactors and Starters from Eatons electrical business is the result of a substantial engineering, manufacturing and marketing effort involving extensive customer input, combined with new advances in solid-state technology. IT. Electro-Mechanical products have greatly increased functionality, signicantly reduced size and utilize the benets of 24V DC control. The exclusive Pulse Width Modulation (PWM) control and digital microprocessor generate a minimized DC value which reduces energy to the contact block and provides the most compact system available.

Reversing
No Cover Mounted Pilot Devices FOR/REV/STOP Pushbuttons with 2 Red Pilot Lights with 2 Red/1 Green Pilot Lights UP/STOP/DOWN Pushbuttons with 2 Red Pilot Lights FOR/OFF/REV Selector Switch with 2 Red Pilot Lights with 2 Red/1 Green Pilot Lights Two Red Pilot Lights One Green Pilot Light Two Red/One Green Pilot Lights OPEN/OFF/CLOSE Selector Switch with 2 Red Pilot Lights with 2 Red/1 Green Pilot Lights C400T6 * C400T15 * * * * * * * * C400T10 C400T16

Standards and Certications


Add Code Letter from the table below to Catalog Number for voltage Kits only. Example: C400T9B. Rating Code Letter A E Rating 240V 60 Hz 380V 50 Hz Code Letter B L Rating 480V 60 Hz 600V 60 Hz Code Letter C D

IEC 947-4-2 UL Listed cUL Listed (indicates appropriate CSA Standard investigation) ABS Type Approval CE Mark available

120V 60 Hz 208V 60 Hz

Order Quantity (2) of C400T10. Type 3R/4X only for combination Reversing IT. Starters. *Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005
Vol. 2, Ref. No. [0295]

34-31

Product Family Overview

Catalog Number Selection


Table 34-44. IEC Intelligent Technologies (IT.) Line Enclosed Control Catalog Numbering System

EC R
Design R = IT. IEC Class 01 = 02 = 05 = 06 = 16 = 17 = 22 = 23 = Contactors Reversing Contactors Non-combination FVNR Starter Non-combination FVR Starter Combination Non/Fusible FVNR Starter Combination Non/Fusible FVR Starter Combination HMCPE FVNR Starter Combination HMCPE FVR Starter Frame Size A = 27 mm B = 45 mm C = 54 mm

22 B 1 B A C - J
Modification Codes (See Page 34-49) Solid-State Overload Range Disconnect Fuse Clip A= B= C= D= E= F= None 30A/250V 30A/600V 60A/250V 60A/600V 100A/250V G= H= J= K= L= 100A/600V 200A/250V 200A/600V 400A/250V 400A/600V

34

HMCP/E or Breaker Ratings A= B= C= D= E= F= None 3A 7A 15A 30A 50A W= G= X= H= J= K= 70A 100A/RC3 100A/TC3 150A 250A 400A

D = 76 mm E = 105 mm F = 140 mm

Enclosure Type 1= 2= 3= 4= 6= 8= 9= Type 1 General Purpose Type 3R Rain Type 4 Painted Steel Type 4X Watertight (304-Grade SS) Type 7/9 Explosion Proof Type 12 Dust-Tight Type 4X 316-Grade Stainless Steel

Cover Control (See Page 34-30) Motor Voltage/ Power Supply B= C= D= E= Q= L= 230V 460V 575V 200V 24V DC 380V/50 Hz

If CPT is selected, Power Supply to be 120V AC 24V DC. Power supply omitted. See Table 34-45, Solid-State Overload Range Codes.

Table 34-45. Solid-State Overload Range Codes


FLA Range Frame Size/AC-3 Amps A 12A .25 .8 .59 1.9 1.4 4.4 2.8 9.0 3.8 12 5.0 16 6.3 20 8.4 27 10 32 14 45 16 50 31 100 42 135 63 200 84 270 131 420 A B C D E B 32A D G J C 50A H L D 100A K N E 200A P R F 400A S T

For Overload Sizes for starters with other AC-3 Amp Ratings, contact your Eaton Representative.

CA08102001E

For more information visit: www.EatonElectrical.com

34-32

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Contactors

Vol. 2, Ref. No. [0296]

Product Selection
Table 34-46. Class ECR01 IT. IEC Contactors Non-reversing
Motor Voltage Max. hp Coil Voltage 3-Pole Type 1 3-Pole Type 3R 3-Pole Type 4X 3-Pole Type 12 3-Pole Component Contactor (Open) Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Catalog Number E111A12Q3N E111A12E3N E111A12B3N E111A12C3N E111A12D3N E111A12L3N E111B32Q3N E111B32E3N E111B32B3N E111B32C3N E111B32D3N E111B32L3N E111C50Q3N E111C50E3N E111C50B3N E111C50C3N E111C50D3N E111C50L3N E111D10Q3N E111D10E3N E111D10B3N E111D10C3N E111D10D3N E111D10L3N E111E20Q3N E111E20E3N E111E20B3N E111E20C3N E111E20D3N E111E20L3N E111F40Q3N E111F40E3N E111F40B3N E111F40C3N E111F40D3N E111F40L3N

34
Frame Size A 12A
200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 3 3 7-1/2 7-1/2 5 7-1/2 10 20 20 15 15 15 30 30 25 30 30 75 75 50 60 75 150 150 100 150 150 350 350 200 24V DC 24V DC 24V DC

Catalog Number ECR01A1QAA ECR01A1EAA ECR01A1BAA ECR01A1CAA ECR01A1DAA ECR01A1LAA ECR01F1QAA ECR01F1EAA ECR01F1BAA ECR01F1CAA ECR01F1DAA ECR01F1LAA ECR01H1QAA ECR01H1EAA ECR01H1BAA ECR01H1CAA ECR01H1DAA ECR01H1LAA ECR01L1QAA ECR01L1EAA ECR01L1BAA ECR01L1CAA ECR01L1DAA ECR01L1LAA ECR01P1QAA ECR01P1EAA ECR01P1BAA ECR01P1CAA ECR01P1DAA ECR01P1LAA ECR01T1QAA ECR01T1EAA ECR01T1BAA ECR01T1CAA ECR01T1DAA ECR01T1LAA

Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Catalog Number ECR01A2QAA ECR01A2EAA ECR01A2BAA ECR01A2CAA ECR01A2DAA ECR01A2LAA ECR01F2QAA ECR01F2EAA ECR01F2BAA ECR01F2CAA ECR01F2DAA ECR01F2LAA ECR01H2QAA ECR01H2EAA ECR01H2BAA ECR01H2CAA ECR01H2DAA ECR01H2LAA ECR01L2QAA ECR01L2EAA ECR01L2BAA ECR01L2CAA ECR01L2DAA ECR01L2LAA ECR01P2QAA ECR01P2EAA ECR01P2BAA ECR01P2CAA ECR01P2DAA ECR01P2LAA ECR01T2QAA ECR01T2EAA ECR01T2BAA ECR01T2CAA ECR01T2DAA ECR01T2LAA

Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Catalog Number ECR01A4QAA ECR01A4EAA ECR01A4BAA ECR01A4CAA ECR01A4DAA ECR01A4LAA ECR01F4QAA ECR01F4EAA ECR01F4BAA ECR01F4CAA ECR01F4DAA ECR01F4LAA ECR01H4QAA ECR01H4EAA ECR01H4BAA ECR01H4CAA ECR01H4DAA ECR01H4LAA ECR01L4QAA ECR01L4EAA ECR01L4BAA ECR01L4CAA ECR01L4DAA ECR01L4LAA ECR01P4QAA ECR01P4EAA ECR01P4BAA ECR01P4CAA ECR01P4DAA ECR01P4LAA ECR01T4QAA ECR01T4EAA ECR01T4BAA ECR01T4CAA ECR01T4DAA ECR01T4LAA

Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Catalog Number ECR01A8QAA ECR01A8EAA ECR01A8BAA ECR01A8CAA ECR01A8DAA ECR01A8LAA ECR01F8QAA ECR01F8EAA ECR01F8BAA ECR01F8CAA ECR01F8DAA ECR01F8LAA ECR01H8QAA ECR01H8EAA ECR01H8BAA ECR01H8CAA ECR01H8DAA ECR01H8LAA ECR01L8QAA ECR01L8EAA ECR01L8BAA ECR01L8CAA ECR01L8DAA ECR01L8LAA ECR01P8QAA ECR01P8EAA ECR01P8BAA ECR01P8CAA ECR01P8DAA ECR01P8LAA ECR01T8QAA ECR01T8EAA ECR01T8BAA ECR01T8CAA ECR01T8DAA ECR01T8LAA

Frame Size B 32A

Frame Size C 50A

Frame Size D 100A


24V DC

Frame Size E 200A


24V DC

Frame Size F 420A


24V DC

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECR01P4QAA. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. For each Frame Size, enclosed contactors with lower Amp Ratings are available. Contact your Eaton Representative for component contactors and their horsepower choices. *Please contact your local Eaton sales ofce.

Type 1 Non-combination IT. Contactor

Technical Data . . . . . . . . . . . . . . . . . . . . Page 34-14 Accessories . . . . . . . . . . . . . . . . . . . . . . . Page 34-18 Renewal Parts . . . . . . . . . . . . . . . . . . . . . Page 34-22 Cover Control . . . . . . . . . . . . . . . . . . . . . . Page 34-30 Wiring Diagrams . . . . . . . . . . . . . . . . . . . Page 34-48 Discount Symbol . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005
Vol. 2, Ref. No. [0297]

34-33

Contactors

Table 34-47. Class ECR02 IT. IEC Contactors Reversing


Motor Voltage Max. hp Coil Voltage 3-Pole Type 1 3-Pole Type 3R 3-Pole Type 4X 3-Pole Type 12 3-Pole Component Contactor (Open) Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Catalog Number E511A12Q3N E511A12E3N E511A12B3N E511A12C3N E511A12D3N E511A12L3N E511B32Q3N E511B32E3N E511B32B3N E511B32C3N E511B32D3N E511B32L3N E511C50Q3N E511C50E3N E511C50B3N E511C50C3N E511C50D3N E511C50L3N E511D10Q3N E511D10E3N E511D10B3N E511D10C3N E511D10D3N E511D10L3N E511E20Q3N E511E20E3N E511E20B3N E511E20C3N E511E20D3N E511E20L3N E511F42Q3N E511F42E3N E511F42B3N E511F42C3N E511F42D3N E511F42L3N

Catalog Number

Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Catalog Number ECR02A2QAA ECR02A2EAA ECR02A2BAA ECR02A2CAA ECR02A2DAA ECR02A2LAA ECR02F2QAA ECR02F2EAA ECR02F2BAA ECR02F2CAA ECR02F2DAA ECR02F2LAA ECR02H2QAA ECR02H2EAA ECR02H2BAA ECR02H2CAA ECR02H2DAA ECR02H2LAA ECR02L2QAA ECR02L2EAA ECR02L2BAA ECR02L2CAA ECR02L2DAA ECR02L2LAA ECR02P2QAA ECR02P2EAA ECR02P2BAA ECR02P2CAA ECR02P2DAA ECR02P2LAA ECR02T2QAA ECR02T2EAA ECR02T2BAA ECR02T2CAA ECR02T2DAA ECR02T2LAA

Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Catalog Number ECR02A4QAA ECR02A4EAA ECR02A4BAA ECR02A4CAA ECR02A4DAA ECR02A4LAA ECR02F4QAA ECR02F4EAA ECR02F4BAA ECR02F4CAA ECR02F4DAA ECR02F4LAA ECR02H4QAA ECR02H4EAA ECR02H4BAA ECR02H4CAA ECR02H4DAA ECR02H4LAA ECR02L4QAA ECR02L4EAA ECR02L4BAA ECR02L4CAA ECR02L4DAA ECR02L4LAA ECR02P4QAA ECR02P4EAA ECR02P4BAA ECR02P4CAA ECR02P4DAA ECR02P4LAA ECR02T4QAA ECR02T4EAA ECR02T4BAA ECR02T4CAA ECR02T4DAA ECR02T4LAA

Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Catalog Number ECR02A8QAA ECR02A8EAA ECR02A8BAA ECR02A8CAA ECR02A8DAA ECR02A8LAA ECR02F8QAA ECR02F8EAA ECR02F8BAA ECR02F8CAA ECR02F8DAA ECR02F8LAA ECR02H8QAA ECR02H8EAA ECR02H8BAA ECR02H8CAA ECR02H8DAA ECR02H8LAA ECR02L8QAA ECR02L8EAA ECR02L8BAA ECR02L8CAA ECR02L8DAA ECR02L8LAA ECR02P8QAA ECR02P8EAA ECR02P8BAA ECR02P8CAA ECR02P8DAA ECR02P8LAA ECR02T8QAA ECR02T8EAA ECR02T8BAA ECR02T8CAA ECR02T8DAA ECR02T8LAA

Frame Size A 12A


200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 3 3 7-1/2 7-1/2 5 7-1/2 10 20 20 15 15 15 30 30 25 30 30 75 75 50 60 75 150 150 100 150 150 350 350 200 24V DC 24V DC 24V DC ECR02A1QAA ECR02A1EAA ECR02A1BAA ECR02A1CAA ECR02A1DAA ECR02A1LAA ECR02F1QAA ECR02F1EAA ECR02F1BAA ECR02F1CAA ECR02F1DAA ECR02F1LAA ECR02H1QAA ECR02H1EAA ECR02H1BAA ECR02H1CAA ECR02H1DAA ECR02H1LAA ECR02L1QAA ECR02L1EAA ECR02L1BAA ECR02L1CAA ECR02L1DAA ECR02L1LAA ECR02P1QAA ECR02P1EAA ECR02P1BAA ECR02P1CAA ECR02P1DAA ECR02P1LAA ECR02T1QAA ECR02T1EAA ECR02T1BAA ECR02T1CAA ECR02T1DAA ECR02T1LAA

34

Frame Size B 32A

Frame Size C 50A

Frame Size D 100A


24V DC

Frame Size E 200A


24V DC

Frame Size F 420A


24V DC

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECR02P4QAA. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. For each Frame Size, enclosed contactors with lower Amp Ratings are available. Contact your Eaton Representative for component contactors and their horsepower choices. *Please contact your local Eaton sales ofce.

Technical Data . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . Renewal Parts . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-14 Page 34-18 Page 34-22 Page 34-30 Page 34-48 1CD1C

34-34

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Non-combination Starters

Vol. 2, Ref. No. [0298]

Product Selection
Table 34-48. Class ECR05 IT. IEC Non-combination Starters Non-reversing
Motor Voltage Max. hp 3-Pole Coil Voltage Type 1 3-Pole Type 3R 3-Pole Type 4X 3-Pole Type 12 3-Pole Component Starter (Open) Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Catalog Number E101A12Q3A E101A12E3A E101A12B3A E101A12C3A E101A12D3A E101A12L3A E101B32Q3A E101B32E3A E101B32B3A E101B32C3A E101B32D3A E101B32L3A E101C50Q3A E101C50E3A E101C50B3A E101C50C3A E101C50D3A E101C50L3A E101D10Q3A E101D10E3A E101D10B3A E101D10C3A E101D10D3A E101D10L3A E101E20Q3A E101E20E3A E101E20B3A E101E20C3A E101E20D3A E101E20L3A E101F40Q3A E101F40E3A E101F40B3A E101F40C3A E101F40D3A E101F40L3A

34
Frame Size A 12A
24V DC 200/208 3 230/240 3 460/480 7-1/2 575/600 7-1/2 380/50 Hz 5

Catalog Number ECR05A1QAA-E ECR05A1EAA-E ECR05A1BAA-E ECR05A1CAA-E ECR05A1DAA-E ECR05A1LAA-E ECR05F1QAA-J ECR05F1EAA-J ECR05F1BAA-J ECR05F1CAA-J ECR05F1DAA-J ECR05F1LAA-J

Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Catalog Number ECR05A2QAA-E ECR05A2EAA-E ECR05A2BAA-E ECR05A2CAA-E ECR05A2DAA-E ECR05A2LAA-E ECR05F2QAA-J ECR05F2EAA-J ECR05F2BAA-J ECR05F2CAA-J ECR05F2DAA-J ECR05F2LAA-J ECR05H2QAA-L ECR05H2EAA-L ECR05H2BAA-L ECR05H2CAA-L ECR05H2DAA-L ECR05H2LAA-L ECR05L2QAA-N ECR05L2EAA-N ECR05L2BAA-N ECR05L2CAA-N ECR05L2DAA-N ECR05L2LAA-N ECR05P2QAA-R ECR05P2EAA-R ECR05P2BAA-R ECR05P2CAA-R ECR05P2DAA-R ECR05P2LAA-R ECR05T2QAA-T ECR05T2EAA-T ECR05T2BAA-T ECR05T2CAA-T ECR05T2DAA-T ECR05T2LAA-T

Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Catalog Number ECR05A4QAA-E ECR05A4EAA-E ECR05A4BAA-E ECR05A4CAA-E ECR05A4DAA-E ECR05A4LAA-E ECR05F4QAA-J ECR05F4EAA-J ECR05F4BAA-J ECR05F4CAA-J ECR05F4DAA-J ECR05F4LAA-J ECR05H4QAA-L ECR05H4EAA-L ECR05H4BAA-L ECR05H4CAA-L ECR05H4DAA-L ECR05H4LAA-L ECR05L4QAA-N ECR05L4EAA-N ECR05L4BAA-N ECR05L4CAA-N ECR05L4DAA-N ECR05L4LAA-N ECR05P4QAA-R ECR05P4EAA-R ECR05P4BAA-R ECR05P4CAA-R ECR05P4DAA-R ECR05P4LAA-R ECR05T4QAA-T ECR05T4EAA-T ECR05T4BAA-T ECR05T4CAA-T ECR05T4DAA-T ECR05T4LAA-T

Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Catalog Number ECR05A8QAA-E ECR05A8EAA-E ECR05A8BAA-E ECR05A8CAA-E ECR05A8DAA-E ECR05A8LAA-E ECR05F8QAA-J ECR05F8EAA-J ECR05F8BAA-J ECR05F8CAA-J ECR05F8DAA-J ECR05F8LAA-J ECR05H8QAA-L ECR05H8EAA-L ECR05H8BAA-L ECR05H8CAA-L ECR05H8DAA-L ECR05H8LAA-L ECR05L8QAA-N ECR05L8EAA-N ECR05L8BAA-N ECR05L8CAA-N ECR05L8DAA-N ECR05L8LAA-N ECR05P8QAA-R ECR05P8EAA-R ECR05P8BAA-R ECR05P8CAA-R ECR05P8DAA-R ECR05P8LAA-R ECR05T8QAA-T ECR05T8EAA-T ECR05T8BAA-T ECR05T8CAA-T ECR05T8DAA-T ECR05T8LAA-T

Frame Size B 32A


24V DC 200/208 7-1/2 230/240 10 460/480 20 575/600 20 380/50 Hz 15

Frame Size C 50A


200/208 15 230/240 15 460/480 30 575/600 30 380/50 Hz 25 24V DC ECR05H1QAA-L ECR05H1EAA-L ECR05H1BAA-L ECR05H1CAA-L ECR05H1DAA-L ECR05H1LAA-L 24V DC ECR05L1QAA-N ECR05L1EAA-N ECR05L1BAA-N ECR05L1CAA-N ECR05L1DAA-N ECR05L1LAA-N 24V DC ECR05P1QAA-R ECR05P1EAA-R ECR05P1BAA-R ECR05P1CAA-R ECR05P1DAA-R ECR05P1LAA-R 24V DC ECR05T1QAA-T ECR05T1EAA-T ECR05T1BAA-T ECR05T1CAA-T ECR05T1DAA-T ECR05T1LAA-T

Frame Size D 100A


200/208 30 230/240 30 460/480 75 575/600 75 380/50 Hz 50

Frame Size E 200A


200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 60 75 150 150 100 150 150 350 350 200

Frame Size F 420A

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECR05P4QAA. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. The eleventh position of the Catalog Numbers is the Solid-State Overload Range Code referred to in Table 34-45. For each Frame Size, enclosed starters with lower Amp Ratings are available. Contactor your Eaton Representative for component starters and their horsepower and overload range choices. *Please contact your local Eaton sales ofce.

Type 3R IT. IEC Non-combination Starter

Technical Data . . . . . . . . . . . . . . . . . . . . Page 34-14 Accessories . . . . . . . . . . . . . . . . . . . . . . . Page 34-18 Renewal Parts . . . . . . . . . . . . . . . . . . . . . Page 34-22 Cover Control . . . . . . . . . . . . . . . . . . . . . . Page 34-30 Wiring Diagrams . . . . . . . . . . . . . . . . . . . Page 34-48 Discount Symbol . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005
Vol. 2, Ref. No. [0299]

34-35

Non-combination Starters

Table 34-49. Class ECR06 IT. IEC Non-combination Starters Reversing


Motor Voltage Max. hp Coil 3-Pole Voltage Type 1 3-Pole Type 3R 3-Pole Type 4X 3-Pole Type 12 3-Pole Component Starter (Open) Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Catalog Number E501A12Q3A E501A12E3A E501A12B3A E501A12C3A E501A12D3A E501A12L3A E501B32Q3A E501B32E3A E501B32B3A E501B32C3A E501B32D3A E501B32L3A E501C50Q3A E501C50E3A E501C50B3A E501C50C3A E501C50D3A E501C50L3A E501D10Q3A E501D10E3A E501D10B3A E501D10C3A E501D10D3A E501D10L3A E501E20Q3A E501E20E3A E501E20B3A E501E20C3A E501E20D3A E501E20L3A E501F40Q3A E501F40E3A E501F40B3A E501F40C3A E501F40D3A E501F40L3A

Catalog Number

Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Catalog Number ECR06A2QAA-E ECR06A2EAA-E ECR06A2BAA-E ECR06A2CAA-E ECR06A2DAA-E ECR06A2LAA-E ECR06F2QAA-J ECR06F2EAA-J ECR06F2BAA-J ECR06F2CAA-J ECR06F2DAA-J ECR06F2LAA-J ECR06H2QAA-L ECR06H2EAA-L ECR06H2BAA-L ECR06H2CAA-L ECR06H2DAA-L ECR06H2LAA-L ECR06L2QAA-N ECR06L2EAA-N ECR06L2BAA-N ECR06L2CAA-N ECR06L2DAA-N ECR06L2LAA-N ECR06P2QAA-R ECR06P2EAA-R ECR06P2BAA-R ECR06P2CAA-R ECR06P2DAA-R ECR06P2LAA-R ECR06T2QAA-T ECR06T2EAA-T ECR06T2BAA-T ECR06T2CAA-T ECR06T2DAA-T ECR06T2LAA-T

Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Catalog Number ECR06A4QAA-E ECR06A4EAA-E ECR06A4BAA-E ECR06A4CAA-E ECR06A4DAA-E ECR06A4LAA-E ECR06F4QAA-J ECR06F4EAA-J ECR06F4BAA-J ECR06F4CAA-J ECR06F4DAA-J ECR06F4LAA-J ECR06H4QAA-L ECR06H4EAA-L ECR06H4BAA-L ECR06H4CAA-L ECR06H4DAA-L ECR06H4LAA-L ECR06L4QAA-N ECR06L4EAA-N ECR06L4BAA-N ECR06L4CAA-N ECR06L4DAA-N ECR06L4LAA-N ECR06P4QAA-R ECR06P4EAA-R ECR06P4BAA-R ECR06P4CAA-R ECR06P4DAA-R ECR06P4LAA-R ECR06T4QAA-T ECR06T4EAA-T ECR06T4BAA-T ECR06T4CAA-T ECR06T4DAA-T ECR06T4LAA-T

Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Catalog Number ECR06A8QAA-E ECR06A8EAA-E ECR06A8BAA-E ECR06A8CAA-E ECR06A8DAA-E ECR06A8LAA-E ECR06F8QAA-J ECR06F8EAA-J ECR06F8BAA-J ECR06F8CAA-J ECR06F8DAA-J ECR06F8LAA-J ECR06H8QAA-L ECR06H8EAA-L ECR06H8BAA-L ECR06H8CAA-L ECR06H8DAA-L ECR06H8LAA-L ECR06L8QAA-N ECR06L8EAA-N ECR06L8BAA-N ECR06L8CAA-N ECR06L8DAA-N ECR06L8LAA-N ECR06P8QAA-R ECR06P8EAA-R ECR06P8BAA-R ECR06P8CAA-R ECR06P8DAA-R ECR06P8LAA-R ECR06T8QAA-T ECR06T8EAA-T ECR06T8BAA-T ECR06T8CAA-T ECR06T8DAA-T ECR06T8LAA-T

Frame Size A 12A


24V DC 200/208 3 230/240 3 460/480 7-1/2 575/600 7-1/2 380/50 Hz 5 ECR06A1QAA-E ECR06A1EAA-E ECR06A1BAA-E ECR06A1CAA-E ECR06A1DAA-E ECR06A1LAA-E ECR06F1QAA-J ECR06F1EAA-J ECR06F1BAA-J ECR06F1CAA-J ECR06F1DAA-J ECR06F1LAA-J

34

Frame Size B 32A


24V DC 200/208 7-1/2 230/240 10 460/480 20 575/600 20 380/50 Hz 15

Frame Size C 50A


200/208 15 230/240 15 460/480 30 575/600 30 380/50 Hz 25 24V DC ECR06H1QAA-L ECR06H1EAA-L ECR06H1BAA-L ECR06H1CAA-L ECR06H1DAA-L ECR06H1LAA-L 24V DC ECR06L1QAA-N ECR06L1EAA-N ECR06L1BAA-N ECR06L1CAA-N ECR06L1DAA-N ECR06L1LAA-N 24V DC ECR06P1QAA-R ECR06P1EAA-R ECR06P1BAA-R ECR06P1CAA-R ECR06P1DAA-R ECR06P1LAA-R 24V DC ECR06T1QAA-T ECR06T1EAA-T ECR06T1BAA-T ECR06T1CAA-T ECR06T1DAA-T ECR06T1LAA-T

Frame Size D 100A


200/208 30 230/240 30 460/480 75 575/600 75 380/50 Hz 50

Frame Size E 200A


200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 60 75 150 150 100 150 150 350 350 200

Frame Size F 420A

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECR06P4QAA. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. The eleventh position of the Catalog Numbers is the Solid-State Overload Range Code referred to in Table 34-45. For each Frame Size, enclosed starters with lower Amp Ratings are available. Contactor your Eaton Representative for component starters and their horsepower and overload range choices. *Please contact your local Eaton sales ofce.

Technical Data . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . Renewal Parts . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-14 Page 34-18 Page 34-22 Page 34-30 Page 34-48 1CD1C

34-36

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Combination Starters Fusible and Non-fusible

Vol. 2, Ref. No. [0300]

Product Selection
Table 34-50. Class ECR16 IT. IEC Fusible Combination Starters Non-reversing
Motor Voltage Max. hp Coil Voltage Disconnect 3-Pole Type 1 Catalog Number ECR16A1QAB-J ECR16A1QAC-J ECR16A1EAB-J ECR16A1BAB-J ECR16A1CAC-J ECR16A1DAC-J ECR16A1LAC-J ECR16F1QAB-J ECR16F1QAC-J ECR16F1EAB-J ECR16F1BAB-J ECR16F1CAC-J ECR16F1DAC-J ECR16F1LAC-J ECR16H1QAD-L ECR16H1QAE-L ECR16H1EAD-L ECR16H1BAD-L ECR16H1CAE-L ECR16H1DAE-L ECR16H1LAE-L ECR16L1QAF-N ECR16L1QAG-N ECR16L1EAF-N ECR16L1BAF-N ECR16L1CAG-N ECR16L1DAG-N ECR16L1LAG-N ECR16P1QAH-R ECR16P1QAJ-R ECR16P1EAH-R ECR16P1BAH-R ECR16P1CAJ-R ECR16P1DAJ-R ECR16P1LAJ-R 3-Pole Type 3R Catalog Number * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ECR16A2QAB-J ECR16A2QAC-J ECR16A2EAB-J ECR16A2BAB-J ECR16A2CAC-J ECR16A2DAC-J ECR16A2LAC-J ECR16F2QAB-J ECR16F2QAC-J ECR16F2EAB-J ECR16F2BAB-J ECR16F2CAC-J ECR16F2DAC-J ECR16F2LAC-J ECR16H2QAD-L ECR16H2QAE-L ECR16H2EAD-L ECR16H2BAD-L ECR16H2CAE-L ECR16H2DAE-L ECR16H2LAE-L ECR16L2QAF-N ECR16L2QAG-N ECR16L2EAF-N ECR16L2BAF-N ECR16L2CAG-N ECR16L2DAG-N ECR16L2LAG-N ECR16P2QAH-R ECR16P2QAJ-R ECR16P2EAH-R ECR16P2BAH-R ECR16P2CAJ-R ECR16P2DAJ-R ECR16P2LAJ-R 3-Pole Component Starter (Open) Catalog Number * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * E101A12Q3A E101A12Q3A E101A12E3A E101A12B3A E101A12C3A E101A12D3A E101A12L3A E101B32Q3A E101B32Q3A E101B32E3A E101B32B3A E101B32C3A E101B32D3A E101B32L3A E101C50Q3A E101C50Q3A E101C50E3A E101C50B3A E101C50C3A E101C50D3A E101C50L3A E101D10Q3A E101D10Q3A E101D10E3A E101D10B3A E101D10C3A E101D10D3A E101D10L3A E101E20Q3A E101E20Q3A E101E20E3A E101E20B3A E101E20C3A E101E20D3A E101E20L3A Price U.S. $ Price U.S. $

34

Frame Size A 12A


200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 3 3 7-1/2 7-1/2 5 7-1/2 10 20 20 15 15 15 30 30 25 30 30 75 75 50 60 75 150 150 100 24V DC 60A 24V DC 30A 24V DC 30A

Frame Size B 32A

Frame Size C 50A

Frame Size D 100A


24V DC 100A

Frame Size E 200A


24V DC 200A

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. The eleventh position of the Catalog Numbers is the Solid-State Overload Range Code referred to in Table 34-45. For each Frame Size, enclosed starters with lower Amp Ratings are available. Contactor your Eaton Representative for component starters and their horsepower and overload range choices. *Please contact your local Eaton sales ofce.

Technical Data . . . . . . . . . . . . . . . . . . . . Page 34-14 Accessories . . . . . . . . . . . . . . . . . . . . . . . Page 34-18 Renewal Parts . . . . . . . . . . . . . . . . . . . . . Page 34-22 Cover Control . . . . . . . . . . . . . . . . . . . . . . Page 34-30 Wiring Diagrams . . . . . . . . . . . . . . . . . . . Page 34-48 Discount Symbol . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005
Vol. 2, Ref. No. [0301]

34-37

Combination Starters Fusible and Non-fusible

Table 34-50. Class ECR16 IT. IEC Fusible Combination Starters Non-reversing (Continued)
Motor Voltage Max. hp Coil Voltage Disconnect 3-Pole Type 4X Catalog Number ECR16A4QAB-J ECR16A4QAC-J ECR16A4EAB-J ECR16A4BAB-J ECR16A4CAC-J ECR16A4DAC-J ECR16A4LAC-J ECR16F4QAB-J ECR16F4QAC-J ECR16F4EAB-J ECR16F4BAB-J ECR16F4CAC-J ECR16F4DAC-J ECR16F4LAC-J ECR16H4QAD-L ECR16H4QAE-L ECR16H4EAD-L ECR16H4BAD-L ECR16H4CAE-L ECR16H4DAE-L ECR16H4LAE-L ECR16L4QAF-N ECR16L4QAG-N ECR16L4EAF-N ECR16L4BAF-N ECR16L4CAG-N ECR16L4DAG-N ECR16L4LAG-N ECR16P4QAH-R ECR16P4QAJ-R ECR16P4EAH-R ECR16P4BAH-R ECR16P4CAJ-R ECR16P4DAJ-R ECR16P4LAJ-R 3-Pole Type 12 Catalog Number * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ECR16A8QAB-J ECR16A8QAC-J ECR16A8EAB-J ECR16A8BAB-J ECR16A8CAC-J ECR16A8DAC-J ECR16A8LAC-J ECR16F8QAB-J ECR16F8QAC-J ECR16F8EAB-J ECR16F8BAB-J ECR16F8CAC-J ECR16F8DAC-J ECR16F8LAC-J ECR16H8QAD-L ECR16H8QAE-L ECR16H8EAD-L ECR16H8BAD-L ECR16H8CAE-L ECR16H8DAE-L ECR16H8LAE-L ECR16L8QAF-N ECR16L8QAG-N ECR16L8EAF-N ECR16L8BAF-N ECR16L8CAG-N ECR16L8DAG-N ECR16L8LAG-N ECR16P8QAH-R ECR16P8QAJ-R ECR16P8EAH-R ECR16P8BAH-R ECR16P8CAJ-R ECR16P8DAJ-R ECR16P8LAJ-R 3-Pole Component Starter (Open) Catalog Number * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * E101A12Q3A E101A12Q3A E101A12E3A E101A12B3A E101A12C3A E101A12D3A E101A12L3A E101B32Q3A E101B32Q3A E101B32E3A E101B32B3A E101B32C3A E101B32D3A E101B32L3A E101C50Q3A E101C50Q3A E101C50E3A E101C50B3A E101C50C3A E101C50D3A E101C50L3A E101D10Q3A E101D10Q3A E101D10E3A E101D10B3A E101D10C3A E101D10D3A E101D10L3A E101E20Q3A E101E20Q3A E101E20E3A E101E20B3A E101E20C3A E101E20D3A E101E20L3A

Price U.S. $

Price U.S. $

Frame Size A 12A


200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 3 3 7-1/2 7-1/2 5 7-1/2 10 20 20 15 15 15 30 30 25 30 30 75 75 50 60 75 150 150 100 24V DC 60A 24V DC 30A 24V DC 30A

34

Frame Size B 32A

Frame Size C 50A

Frame Size D 100A


24V DC 100A

Frame Size E 200A


24V DC 200A

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECR16P4QAB. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. The eleventh position of the Catalog Numbers is the Solid-State Overload Range Code referred to in Table 34-45. For each Frame Size, enclosed starters with lower Amp Ratings are available. Contactor your Eaton Representative for component starters and their horsepower and overload range choices. *Please contact your local Eaton sales ofce.

Type 12 IT. IEC Fusible Combination Starter

Technical Data . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . Renewal Parts . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-14 Page 34-18 Page 34-22 Page 34-30 Page 34-48 1CD1C

34-38

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Combination Starters Fusible and Non-fusible


Table 34-51. Class ECR16-NF IT. IEC Non-fusible Combination Starters Non-reversing
Motor Voltage Max. hp Coil Voltage Disconnect 3-Pole Type 1 Catalog Number Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 3R Catalog Number ECR16A2QAA-J ECR16A2EAA-J ECR16A2BAA-J ECR16A2CAA-J ECR16A2DAA-J ECR16A2LAA-J ECR16F2QAA-J ECR16F2EAA-J ECR16F2BAB-J ECR16F2CAA-J ECR16F2DAA-J ECR16F2LAA-J ECR16H2QAA-L ECR16H2EAA-L ECR16H2BAA-L ECR16H2CAA-L ECR16H2DAA-L ECR16H2LAA-L ECR16L2QAA-N ECR16L2EAA-N ECR16L2BAA-N ECR16L2CAA-N ECR16L2DAA-N ECR16L2LAA-N ECR16P2QAA-R ECR16P2EAA-R ECR16P2BAB-R ECR16P2CAA-R ECR16P2DAA-R ECR16P2LAA-R Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Vol. 2, Ref. No. [0302]

3-Pole Component Starter (Open) Catalog Number E101A12Q3A E101A12E3A E101A12B3A E101A12C3A E101A12D3A E101A12L3A E101B32Q3A E101B32E3A E101B32B3A E101B32C3A E101B32D3A E101B32L3A E101C50Q3A E101C50E3A E101C50B3A E101C50C3A E101C50D3A E101C50L3A E101D10Q3A E101D10E3A E101D10B3A E101D10C3A E101D10D3A E101D10L3A E101E20Q3A E101E20E3A E101E20B3A E101E20C3A E101E20D3A E101E20L3A

Frame Size A 12A

34

200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz

3 3 7-1/2 7-1/2 5 7-1/2 10 20 20 15 15 15 30 30 25 30 30 75 75 50 60 75 150 150 100

24V DC

30A

ECR16A1QAA-J ECR16A1EAA-J ECR16A1BAA-J ECR16A1CAA-J ECR16A1DAA-J ECR16A1LAA-J ECR16F1QAA-J ECR16F1EAA-J ECR16F1BAB-J ECR16F1CAA-J ECR16F1DAA-J ECR16F1LAA-J ECR16H1QAA-L ECR16H1EAA-L ECR16H1BAA-L ECR16H1CAA-L ECR16H1DAA-L ECR16H1LAA-L ECR16L1QAA-N ECR16L1EAA-N ECR16L1BAA-N ECR16L1CAA-N ECR16L1DAA-N ECR16L1LAA-N ECR16P1QAA-R ECR16P1EAA-R ECR16P1BAB-R ECR16P1CAA-R ECR16P1DAA-R ECR16P1LAA-R

Frame Size B 32A


24V DC 30A

Frame Size C 50A


24V DC 60A

Frame Size D 100A


24V DC 100A

Frame Size E 200A


24V DC 200A

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. The eleventh position of the Catalog Numbers is the Solid-State Overload Range Code referred to in Table 34-45. For each Frame Size, enclosed starters with lower Amp Ratings are available. Contactor your Eaton Representative for component starters and their horsepower and overload range choices. *Please contact your local Eaton sales ofce.

Technical Data . . . . . . . . . . . . . . . . . . . . Page 34-14 Accessories . . . . . . . . . . . . . . . . . . . . . . . Page 34-18 Renewal Parts . . . . . . . . . . . . . . . . . . . . . Page 34-22 Cover Control . . . . . . . . . . . . . . . . . . . . . . Page 34-30 Wiring Diagrams . . . . . . . . . . . . . . . . . . . Page 34-48 Discount Symbol . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005
Vol. 2, Ref. No. [0303]

34-39

Combination Starters Fusible and Non-fusible

Table 34-51. Class ECR16-NF IT. IEC Non-fusible Combination Starters Non-reversing (Continued)
Motor Voltage Max. hp Coil Voltage Disconnect 3-Pole Type 4X Catalog Number Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 12 Catalog Number ECR16A8QAA-J ECR16A8EAA-J ECR16A8BAA-J ECR16A8CAA-J ECR16A8DAA-J ECR16A8LAA-J ECR16F8QAA-J ECR16F8EAA-J ECR16F8BAB-J ECR16F8CAA-J ECR16F8DAA-J ECR16F8LAA-J ECR16H8QAA-L ECR16H8EAA-L ECR16H8BAA-L ECR16H8CAA-L ECR16H8DAA-L ECR16H8LAA-L ECR16L8QAA-N ECR16L8EAA-N ECR16L8BAA-N ECR16L8CAA-N ECR16L8DAA-N ECR16L8LAA-N ECR16P8QAA-R ECR16P8EAA-R ECR16P8BAB-R ECR16P8CAA-R ECR16P8DAA-R ECR16P8LAA-R Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Component Starter (Open) Catalog Number E101A12Q3A E101A12E3A E101A12B3A E101A12C3A E101A12D3A E101A12L3A E101B32Q3A E101B32E3A E101B32B3A E101B32C3A E101B32D3A E101B32L3A E101C50Q3A E101C50E3A E101C50B3A E101C50C3A E101C50D3A E101C50L3A E101D10Q3A E101D10E3A E101D10B3A E101D10C3A E101D10D3A E101D10L3A E101E20Q3A E101E20E3A E101E20B3A E101E20C3A E101E20D3A E101E20L3A

Frame Size A 12A


200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 3 3 7-1/2 7-1/2 5 7-1/2 10 20 20 15 15 15 30 30 25 30 30 75 75 50 60 75 150 150 100 24V DC 60A 24V DC 30A 24V DC 30A ECR16A4QAA-J ECR16A4EAA-J ECR16A4BAA-J ECR16A4CAA-J ECR16A4DAA-J ECR16A4LAA-J ECR16F4QAA-J ECR16F4EAA-J ECR16F4BAB-J ECR16F4CAA-J ECR16F4DAA-J ECR16F4LAA-J ECR16H4QAA-L ECR16H4EAA-L ECR16H4BAA-L ECR16H4CAA-L ECR16H4DAA-L ECR16H4LAA-L ECR16L4QAA-N ECR16L4EAA-N ECR16L4BAA-N ECR16L4CAA-N ECR16L4DAA-N ECR16L4LAA-N ECR16P4QAA-R ECR16P4EAA-R ECR16P4BAB-R ECR16P4CAA-R ECR16P4DAA-R ECR16P4LAA-R

34

Frame Size B 32A

Frame Size C 50A

Frame Size D 100A


24V DC 100A

Frame Size E 200A


24V DC 200A

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECR16P4QAA. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. The eleventh position of the Catalog Numbers is the Solid-State Overload Range Code referred to in Table 34-45. For each Frame Size, enclosed starters with lower Amp Ratings are available. Contactor your Eaton Representative for component starters and their horsepower and overload range choices. *Please contact your local Eaton sales ofce.

Technical Data . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . Renewal Parts . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-14 Page 34-18 Page 34-22 Page 34-30 Page 34-48 1CD1C

34-40

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Combination Starters Fusible and Non-fusible


Table 34-52. Class ECR17 IT. IEC Fusible Combination Starters Reversing
Motor Voltage Max. hp Coil Voltage Disconnect 3-Pole Type 1 Catalog Number Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 3R Catalog Number ECR17A2QAB-J ECR17A2QAC-J ECR17A2EAB-J ECR17A2BAB-J ECR17A2CAC-J ECR17A2DAC-J ECR17A2LAC-J ECR17F2QAB-J ECR17F2QAC-J ECR17F2EAB-J ECR17F2BAB-J ECR17F2CAC-J ECR17F2DAC-J ECR17F2LAC-J ECR17H2QAD-L ECR17H2QAE-L ECR17H2EAD-L ECR17H2BAD-L ECR17H2CAE-L ECR17H2DAE-L ECR17H2LAE-L ECR17L2QAF-N ECR17L2QAG-N ECR17L2EAF-N ECR17L2BAF-N ECR17L2CAG-N ECR17L2DAG-N ECR17L2LAG-N ECR17P2QAH-R ECR17P2QAJ-R ECR17P2EAH-R ECR17P2BAH-R ECR17P2CAJ-R ECR17P2DAJ-R ECR17P2LAJ-R Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Vol. 2, Ref. No. [0304]

3-Pole Component Starter (Open) Catalog Number E501A12Q3A E501A12Q3A E501A12E3A E501A12B3A E501A12C3A E501A12D3A E501A12L3A E501B32Q3A E501B32Q3A E501B32E3A E501B32B3A E501B32C3A E501B32D3A E501B32L3A E501C50Q3A E501C50Q3A E501C50E3A E501C50B3A E501C50C3A E501C50D3A E501C50L3A E501D10Q3A E501D10Q3A E501D10E3A E501D10B3A E501D10C3A E501D10D3A E501D10L3A E501E20Q3A E501E20Q3A E501E20E3A E501E20B3A E501E20C3A E501E20D3A E501E20L3A

Frame Size A 12A

34

200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz

3 3 7-1/2 7-1/2 5 7-1/2 10 20 20 15 15 15 30 30 25 30 30 75 75 50 60 75 150 150 100

24V DC

30A

ECR17A1QAB-J ECR17A1QAC-J ECR17A1EAB-J ECR17A1BAB-J ECR17A1CAC-J ECR17A1DAC-J ECR17A1LAC-J ECR17F1QAB-J ECR17F1QAC-J ECR17F1EAB-J ECR17F1BAB-J ECR17F1CAC-J ECR17F1DAC-J ECR17F1LAC-J ECR17H1QAD-L ECR17H1QAE-L ECR17H1EAD-L ECR17H1BAD-L ECR17H1CAE-L ECR17H1DAE-L ECR17H1LAE-L ECR17L1QAF-N ECR17L1QAG-N ECR17L1EAF-N ECR17L1BAF-N ECR17L1CAG-N ECR17L1DAG-N ECR17L1LAG-N ECR17P1QAH-R ECR17P1QAJ-R ECR17P1EAH-R ECR17P1BAH-R ECR17P1CAJ-R ECR17P1DAJ-R ECR17P1LAJ-R

Frame Size B 32A


24V DC 30A

Frame Size C 50A


24V DC 60A

Frame Size D 100A


24V DC 100A

Frame Size E 200A


24V DC 200A

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. The eleventh position of the Catalog Numbers is the Solid-State Overload Range Code referred to in Table 34-45. For each Frame Size, enclosed starters with lower Amp Ratings are available. Contactor your Eaton Representative for component starters and their horsepower and overload range choices. *Please contact your local Eaton sales ofce.

Technical Data . . . . . . . . . . . . . . . . . . . . Page 34-14 Accessories . . . . . . . . . . . . . . . . . . . . . . . Page 34-18 Renewal Parts . . . . . . . . . . . . . . . . . . . . . Page 34-22 Cover Control . . . . . . . . . . . . . . . . . . . . . . Page 34-30 Wiring Diagrams . . . . . . . . . . . . . . . . . . . Page 34-48 Discount Symbol . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005
Vol. 2, Ref. No. [0305]

34-41

Combination Starters Fusible and Non-fusible

Table 34-52. Class ECR17 IT. IEC Fusible Combination Starters Reversing (Continued)
Motor Voltage Max. hp Coil Voltage Disconnect 3-Pole Type 4X Catalog Number Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 12 Catalog Number ECR17A8QAB-J ECR17A8QAC-J ECR17A8EAB-J ECR17A8BAB-J ECR17A8CAC-J ECR17A8DAC-J ECR17A8LAC-J ECR17F8QAB-J ECR17F8QAC-J ECR17F8EAB-J ECR17F8BAB-J ECR17F8CAC-J ECR17F8DAC-J ECR17F8LAC-J ECR17H8QAD-L ECR17H8QAE-L ECR17H8EAD-L ECR17H8BAD-L ECR17H8CAE-L ECR17H8DAE-L ECR17H8LAE-L ECR17L8QAF-N ECR17L8QAG-N ECR17L8EAF-N ECR17L8BAF-N ECR17L8CAG-N ECR17L8DAG-N ECR17L8LAG-N ECR17P8QAH-R ECR17P8QAJ-R ECR17P8EAH-R ECR17P8BAH-R ECR17P8CAJ-R ECR17P8DAJ-R ECR17P8LAJ-R Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Component Starter (Open) Catalog Number E501A12Q3A E501A12Q3A E501A12E3A E501A12B3A E501A12C3A E501A12D3A E501A12L3A E501B32Q3A E501B32Q3A E501B32E3A E501B32B3A E501B32C3A E501B32D3A E501B32L3A E501C50Q3A E501C50Q3A E501C50E3A E501C50B3A E501C50C3A E501C50D3A E501C50L3A E501D10Q3A E501D10Q3A E501D10E3A E501D10B3A E501D10C3A E501D10D3A E501D10L3A E501E20Q3A E501E20Q3A E501E20E3A E501E20B3A E501E20C3A E501E20D3A E501E20L3A

Frame Size A 12A


200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 3 3 7-1/2 7-1/2 5 7-1/2 10 20 20 15 15 15 30 30 25 30 30 75 75 50 60 75 150 150 100 24V DC 60A 24V DC 30A 24V DC 30A ECR17A4QAB-J ECR17A4QAC-J ECR17A4EAB-J ECR17A4BAB-J ECR17A4CAC-J ECR17A4DAC-J ECR17A4LAC-J ECR17F4QAB-J ECR17F4QAC-J ECR17F4EAB-J ECR17F4BAB-J ECR17F4CAC-J ECR17F4DAC-J ECR17F4LAC-J ECR17H4QAD-L ECR17H4QAE-L ECR17H4EAD-L ECR17H4BAD-L ECR17H4CAE-L ECR17H4DAE-L ECR17H4LAE-L ECR17L4QAF-N ECR17L4QAG-N ECR17L4EAF-N ECR17L4BAF-N ECR17L4CAG-N ECR17L4DAG-N ECR17L4LAG-N ECR17P4QAH-R ECR17P4QAJ-R ECR17P4EAH-R ECR17P4BAH-R ECR17P4CAJ-R ECR17P4DAJ-R ECR17P4LAJ-R

34

Frame Size B 32A

Frame Size C 50A

Frame Size D 100A


24V DC 100A

Frame Size E 200A


24V DC 200A

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECR17P4QAB. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. The eleventh position of the Catalog Numbers is the Solid-State Overload Range Code referred to in Table 34-45. For each Frame Size, enclosed starters with lower Amp Ratings are available. Contactor your Eaton Representative for component starters and their horsepower and overload range choices. *Please contact your local Eaton sales ofce.

Technical Data . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . Renewal Parts . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-14 Page 34-18 Page 34-22 Page 34-30 Page 34-48 1CD1C

34-42

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Combination Starters Fusible and Non-fusible


Table 34-53. Class ECR17-NF IT. IEC Non-fusible Combination Starters Reversing
Motor Voltage Max. hp Coil Voltage Disconnect 3-Pole Type 1 Catalog Number Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 3R Catalog Number ECR17A2QAA-J ECR17A2EAA-J ECR17A2BAA-J ECR17A2CAA-J ECR17A2DAA-J ECR17A2LAA-J ECR17F2QAA-J ECR17F2EAA-J ECR17F2BAB-J ECR17F2CAA-J ECR17F2DAA-J ECR17F2LAA-J ECR17H2QAA-L ECR17H2EAA-L ECR17H2BAA-L ECR17H2CAA-L ECR17H2DAA-L ECR17H2LAA-L ECR17L2QAA-N ECR17L2EAA-N ECR17L2BAA-N ECR17L2CAA-N ECR17L2DAA-N ECR17L2LAA-N ECR17P2QAA-R ECR17P2EAA-R ECR17P2BAB-R ECR17P2CAA-R ECR17P2DAA-R ECR17P2LAA-R Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Vol. 2, Ref. No. [0306]

3-Pole Component Starter (Open) Catalog Number E501A12Q3A E501A12E3A E501A12B3A E501A12C3A E501A12D3A E501A12L3A E501B32Q3A E501B32E3A E501B32B3A E501B32C3A E501B32D3A E501B32L3A E501C50Q3A E501C50E3A E501C50B3A E501C50C3A E501C50D3A E501C50L3A E501D10Q3A E501D10E3A E501D10B3A E501D10C3A E501D10D3A E501D10L3A E501E20Q3A E501E20E3A E501E20B3A E501E20C3A E501E20D3A E501E20L3A

Frame Size A 12A

34

200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz

3 3 7-1/2 7-1/2 5 7-1/2 10 20 20 15 15 15 30 30 25 30 30 75 75 50 60 75 150 150 100

24V DC

30A

ECR17A1QAA-J ECR17A1EAA-J ECR17A1BAA-J ECR17A1CAA-J ECR17A1DAA-J ECR17A1LAA-J ECR17F1QAA-J ECR17F1EAA-J ECR17F1BAB-J ECR17F1CAA-J ECR17F1DAA-J ECR17F1LAA-J ECR17H1QAA-L ECR17H1EAA-L ECR17H1BAA-L ECR17H1CAA-L ECR17H1DAA-L ECR17H1LAA-L ECR17L1QAA-N ECR17L1EAA-N ECR17L1BAA-N ECR17L1CAA-N ECR17L1DAA-N ECR17L1LAA-N ECR17P1QAA-R ECR17P1EAA-R ECR17P1BAB-R ECR17P1CAA-R ECR17P1DAA-R ECR17P1LAA-R

Frame Size B 32A


24V DC 30A

Frame Size C 50A


24V DC 60A

Frame Size D 100A


24V DC 100A

Frame Size E 200A


24V DC 200A

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. The eleventh position of the Catalog Numbers is the Solid-State Overload Range Code referred to in Table 34-45. For each Frame Size, enclosed starters with lower Amp Ratings are available. Contactor your Eaton Representative for component starters and their horsepower and overload range choices. *Please contact your local Eaton sales ofce.

Technical Data . . . . . . . . . . . . . . . . . . . . Page 34-14 Accessories . . . . . . . . . . . . . . . . . . . . . . . Page 34-18 Renewal Parts . . . . . . . . . . . . . . . . . . . . . Page 34-22 Cover Control . . . . . . . . . . . . . . . . . . . . . . Page 34-30 Wiring Diagrams . . . . . . . . . . . . . . . . . . . Page 34-48 Discount Symbol . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005
Vol. 2, Ref. No. [0307]

34-43

Combination Starters Fusible and Non-fusible

Table 34-53. Class ECR17-NF IT. IEC Non-fusible Combination Starters Reversing (Continued)
Motor Voltage Max. hp Coil Voltage Disconnect 3-Pole Type 4X Catalog Number Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 12 Catalog Number ECR17A8QAA-J ECR17A8EAA-J ECR17A8BAA-J ECR17A8CAA-J ECR17A8DAA-J ECR17A8LAA-J ECR17F8QAA-J ECR17F8EAA-J ECR17F8BAB-J ECR17F8CAA-J ECR17F8DAA-J ECR17F8LAA-J ECR17H8QAA-L ECR17H8EAA-L ECR17H8BAA-L ECR17H8CAA-L ECR17H8DAA-L ECR17H8LAA-L ECR17L8QAA-N ECR17L8EAA-N ECR17L8BAA-N ECR17L8CAA-N ECR17L8DAA-N ECR17L8LAA-N ECR17P8QAA-R ECR17P8EAA-R ECR17P8BAB-R ECR17P8CAA-R ECR17P8DAA-R ECR17P8LAA-R Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Component Starter (Open) Catalog Number E501A12Q3A E501A12E3A E501A12B3A E501A12C3A E501A12D3A E501A12L3A E501B32Q3A E501B32E3A E501B32B3A E501B32C3A E501B32D3A E501B32L3A E501C50Q3A E501C50E3A E501C50B3A E501C50C3A E501C50D3A E501C50L3A E501D10Q3A E501D10E3A E501D10B3A E501D10C3A E501D10D3A E501D10L3A E501E20Q3A E501E20E3A E501E20B3A E501E20C3A E501E20D3A E501E20L3A

Frame Size A 12A


200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 200/208 230/240 460/480 575/600 380/50 Hz 3 3 7-1/2 7-1/2 5 7-1/2 10 20 20 15 15 15 30 30 25 30 30 75 75 50 60 75 150 150 100 24V DC 60A 24V DC 30A 24V DC 30A ECR17A4QAA-J ECR17A4EAA-J ECR17A4BAA-J ECR17A4CAA-J ECR17A4DAA-J ECR17A4LAA-J ECR17F4QAA-J ECR17F4EAA-J ECR17F4BAB-J ECR17F4CAA-J ECR17F4DAA-J ECR17F4LAA-J ECR17H4QAA-L ECR17H4EAA-L ECR17H4BAA-L ECR17H4CAA-L ECR17H4DAA-L ECR17H4LAA-L ECR17L4QAA-N ECR17L4EAA-N ECR17L4BAA-N ECR17L4CAA-N ECR17L4DAA-N ECR17L4LAA-N ECR17P4QAA-R ECR17P4EAA-R ECR17P4BAB-R ECR17P4CAA-R ECR17P4DAA-R ECR17P4LAA-R

34

Frame Size B 32A

Frame Size C 50A

Frame Size D 100A


24V DC 100A

Frame Size E 200A


24V DC 200A

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECR17P4QAA. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. The eleventh position of the Catalog Numbers is the Solid-State Overload Range Code referred to in Table 34-45. For each Frame Size, enclosed starters with lower Amp Ratings are available. Contactor your Eaton Representative for component starters and their horsepower and overload range choices. *Please contact your local Eaton sales ofce.

Technical Data . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . Renewal Parts . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-14 Page 34-18 Page 34-22 Page 34-30 Page 34-48 1CD1C

34-44

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Combination Starters HMCP or HMCPE

Vol. 2, Ref. No. [0308]

Product Selection
Table 34-54. Class ECR22 IT. IEC Combination Starters with HMCP/E Non-reversing
Motor Voltage Max. hp Magnet Coil Voltage Circuit Breaker Type 3-Pole Type 1 General Purpose Catalog Number ECR22A1EAF-J ECR22A1BAF-J ECR22A1CAF-J ECR22A1DAF-J ECR22F1EAF-J ECR22F1BAF-J ECR22F1CAF-J ECR22F1DAF-J ECR22H1EAC-L ECR22H1EAD-L ECR22H1EAE-L ECR22H1EAF-L ECR22H1BAC-L ECR22H1CAE-L ECR22H1DAE-L ECR22L1EAF-N ECR22L1BAW-N ECR22L1CAF-N ECR22L1DAF-N ECR22P1EAG-R ECR22P1EAX-R ECR22P1DAJ-R 3-Pole Type 3R Rainproof Catalog Number * * * * * * * * * * * * * * * * * * * ECR22A2EAF-J ECR22A2BAF-J ECR22A2CAF-J ECR22A2DAF-J ECR22F2EAF-J ECR22F2BAF-J ECR22F2CAF-J ECR22F2DAF-J ECR22H2EAC-L ECR22H2EAD-L ECR22H2EAE-L ECR22H2EAF-L ECR22H2BAC-L ECR22H2CAE-L ECR22H2DAE-L ECR22L2EAF-N ECR22L2BAW-N ECR22L2CAF-N ECR22L2DAF-N 3-Pole Component Starter (Open) Catalog Number * * * * * * * * * * * * * * * * * * * E111A12E3N E111A12B3N E111A12C3N E111A12D3N E111B32E3N E111B32B3N E111B32C3N E111B32D3N E111C50E3N

Price U.S. $

Price U.S. $

34

Frame Size A 12A


200 230 460 575/600 200 230 460 575/600 200 3 3 7-1/2 7-1/2 7-1/2 10 20 20 15 24V DC HMCPE 15A

Frame Size B 32A


24V DC HMCPE 30A

Frame Size C 50A


24V DC HMCPE 50A

230 460 575/600 200 230 460 575/600 200 575/600

15 30 30 30 30 75 75 60 60

24V DC

HMCPE 50A

E111C50B3N E111C50C3N E111C50D3N E111D10E3N E111D10B3N E111D10C3N E111D10D3N

Frame Size D 100A


24V DC HMCPE 100A

Frame Size E 200A


24V DC 24V DC HMCPE 200A HMCPE 200A * ECR22P2EAG-R * ECR22P2EAX-R * ECR22P2DAJ-R * E111E20E3N * * E111E20D3N

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. The eleventh position of the Catalog Numbers is the Solid-State Overload Range Code referred to in Table 34-45. For each Frame Size, enclosed starters with lower Amp Ratings are available. Contactor your Eaton Representative for component starters and their horsepower and overload range choices. *Please contact your local Eaton sales ofce.

Technical Data . . . . . . . . . . . . . . . . . . . . Page 34-14 Accessories . . . . . . . . . . . . . . . . . . . . . . . Page 34-18 Renewal Parts . . . . . . . . . . . . . . . . . . . . . Page 34-22 Cover Control . . . . . . . . . . . . . . . . . . . . . . Page 34-30 Wiring Diagrams . . . . . . . . . . . . . . . . . . . Page 34-48 Discount Symbol . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005
Vol. 2, Ref. No. [0309]

34-45

Combination Starters HMCP or HMCPE

Product Selection
Table 34-54. Class ECR22 IT. IEC Combination Starters with HMCP/E Non-reversing (Continued)
Motor Voltage Max. hp Magnet Coil Voltage Circuit Breaker Type 3-Pole Type 4X Watertight Catalog Number ECR22A4EAF-J ECR22A4BAF-J ECR22A4CAF-J ECR22A4DAF-J ECR22F4EAF-J ECR22F4BAF-J ECR22F4CAF-J ECR22F4DAF-J ECR22H4EAC-L ECR22H4EAD-L ECR22H4EAE-L ECR22H4EAF-L ECR22H4BAC-L ECR22H4CAE-L ECR22H4DAE-L ECR22L4EAF-N ECR22L4BAW-N ECR22L4CAF-N ECR22L4DAF-N ECR22P4EAG-R ECR22P4EAX-R ECR22P4DAJ-R 3-Pole Type 12 Dust-Tight Catalog Number * * * * * * * * * * * * * * * * * * * ECR22A8EAF-J ECR22A8BAF-J ECR22A8CAF-J ECR22A8DAF-J ECR22F8EAF-J ECR22F8BAF-J ECR22F8CAF-J ECR22F8DAF-J ECR22H8EAC-L ECR22H8EAD-L ECR22H8EAE-L ECR22H8EAF-L ECR22H8BAC-L ECR22H8CAE-L ECR22H8DAE-L ECR22L8EAF-N ECR22L8BAW-N ECR22L8CAF-N ECR22L8DAF-N 3-Pole Component Starter (Open) Catalog Number * * * * * * * * * * * * * * * * * * * E111A12E3N E111A12B3N E111A12C3N E111A12D3N E111B32E3N E111B32B3N E111B32C3N E111B32D3N E111C50E3N

Price U.S. $

Price U.S. $

Frame Size A 12A


200 230 460 575/600 200 230 460 575/600 200 3 3 7-1/2 7-1/2 7-1/2 10 20 20 15 24V DC HMCPE 15A

34

Frame Size B 32A


24V DC HMCPE 30A

Frame Size C 50A


24V DC HMCPE 50A

230 460 575/600 200 230 460 575/600 200 575/600

15 30 30 30 30 75 75 60 60

24V DC

HMCPE 50A

E111C50B3N E111C50C3N E111C50D3N E111D10E3N E111D10B3N E111D10C3N E111D10D3N

Frame Size D 100A


24V DC HMCPE 100A

Frame Size E 200A


24V DC 24V DC HMCPE 200A HMCPE 200A * ECR22P8EAG-R * ECR22P8EAX-R * ECR22P8DAJ-R * E111E20E3N * * E111E20D3N

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECR22P4EAG. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. The eleventh position of the Catalog Numbers is the Solid-State Overload Range Code referred to in Table 34-45. For each Frame Size, enclosed starters with lower Amp Ratings are available. Contactor your Eaton Representative for component starters and their horsepower and overload range choices. *Please contact your local Eaton sales ofce.

Type 12 IT. IEC Starter with HMCPE

Technical Data . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . Renewal Parts . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-14 Page 34-18 Page 34-22 Page 34-30 Page 34-48 1CD1C

34-46

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Combination Starters HMCP or HMCPE


Table 34-55. Class ECR23 IT. IEC Combination Starters with HMCP/E Reversing
Motor Voltage Max. hp Magnet Coil Voltage Circuit Breaker Type 3-Pole Type 1 General Purpose Catalog Number HMCPE 15A ECR23A1EAF-J ECR23A1BAF-J ECR23A1CAF-J ECR23A1DAF-J ECR23F1EAF-J ECR23F1BAF-J ECR23F1CAF-J ECR23F1DAF-J ECR23H1EAC-L ECR23H1EAD-L ECR23H1EAE-L ECR23H1EAF-L ECR23H1BAC-L ECR23H1CAE-L ECR23H1DAE-L ECR23L1EAF-N ECR23L1BAW-N ECR23L1CAF-N ECR23L1DAF-N ECR23P1EAG-R ECR23P1EAX-R ECR23P1DAJ-R Price U.S. $ * * * * * * * * * * * * 3-Pole Type 3R Rainproof Catalog Number ECR23A2EAF-J ECR23A2BAF-J ECR23A2CAF-J ECR23A2DAF-J ECR23F2EAF-J ECR23F2BAF-J ECR23F2CAF-J ECR23F2DAF-J ECR23H2EAC-L ECR23H2EAD-L ECR23H2EAE-L ECR23H2EAF-L Price U.S. $ * * * * * * * *

Vol. 2, Ref. No. [0310]

3-Pole Component Starter (Open) Catalog Number E511A12E3N E511A12B3N E511A12C3N E511A12D3N E511B32E3N E511B32B3N E511B32C3N E511B32D3N

Frame Size A 12A

34

200 230 460 575/600 200 230 460 575/600 200

3 3 7-1/2 7-1/2 7-1/2 10 20 20 15

24V DC

Frame Size B 32A


24V DC HMCPE 30A

Frame Size C 50A


24V DC HMCPE 50A * E511C50E3N * * * * E511C50B3N * E511C50C3N * E511C50D3N * * * * E511D10E3N E511D10B3N E511D10C3N E511D10D3N

230 460 575/600 200 230 460 575/600 200 575/600

15 30 30 30 30 75 75 60 60

24V DC

HMCPE 50A

* ECR23H2BAC-L * ECR23H2CAE-L * ECR23H2DAE-L * * * * ECR23L2EAF-N ECR23L2BAW-N ECR23L2CAF-N ECR23L2DAF-N

Frame Size D 100A


24V DC HMCPE 100A

Frame Size E 200A


24V DC 24V DC HMCPE 200A HMCPE 200A * ECR23P2EAG-R * ECR23P2EAX-R * ECR23P2DAJ-R * E511E20E3N * * E511E20D3N

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. The eleventh position of the Catalog Numbers is the Solid-State Overload Range Code referred to in Table 34-45. For each Frame Size, enclosed starters with lower Amp Ratings are available. Contactor your Eaton Representative for component starters and their horsepower and overload range choices. *Please contact your local Eaton sales ofce.

Technical Data . . . . . . . . . . . . . . . . . . . . Page 34-14 Accessories . . . . . . . . . . . . . . . . . . . . . . . Page 34-18 Renewal Parts . . . . . . . . . . . . . . . . . . . . . Page 34-22 Cover Control . . . . . . . . . . . . . . . . . . . . . . Page 34-30 Wiring Diagrams . . . . . . . . . . . . . . . . . . . Page 34-48 Discount Symbol . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005
Vol. 2, Ref. No. [0311]

34-47

Combination Starters HMCP or HMCPE

Table 34-55. Class ECR23 IT. IEC Combination Starters with HMCP/E Reversing (Continued)
Motor Voltage Max. hp Magnet Coil Voltage Circuit Breaker Type 3-Pole Type 4X Watertight Catalog Number HMCPE 15A ECR23A4EAF-J ECR23A4BAF-J ECR23A4CAF-J ECR23A4DAF-J ECR23F4EAF-J ECR23F4BAF-J ECR23F4CAF-J ECR23F4DAF-J ECR23H4EAC-L ECR23H4EAD-L ECR23H4EAE-L ECR23H4EAF-L ECR23H4BAC-L ECR23H4CAE-L ECR23H4DAE-L ECR23L4EAF-N ECR23L4BAW-N ECR23L4CAF-N ECR23L4DAF-N ECR23P4EAG-R ECR23P4EAX-R ECR23P4DAJ-R Price U.S. $ * * * * * * * * * * * * 3-Pole Type 12 Dust-Tight Catalog Number ECR23A8EAF-J ECR23A8BAF-J ECR23A8CAF-J ECR23A8DAF-J ECR23F8EAF-J ECR23F8BAF-J ECR23F8CAF-J ECR23F8DAF-J ECR23H8EAC-L ECR23H8EAD-L ECR23H8EAE-L ECR23H8EAF-L Price U.S. $ * * * * * * * * 3-Pole Component Starter (Open) Catalog Number E511A12E3N E511A12B3N E511A12C3N E511A12D3N E511B32E3N E511B32B3N E511B32C3N E511B32D3N

Frame Size A 12A


200 230 460 575/600 200 230 460 575/600 200 3 3 7-1/2 7-1/2 7-1/2 10 20 20 15 24V DC

34

Frame Size B 32A


24V DC HMCPE 30A

Frame Size C 50A


24V DC HMCPE 50A * E511C50E3N * * * * E511C50B3N * E511C50C3N * E511C50D3N * * * * E511D10E3N E511D10B3N E511D10C3N E511D10D3N

230 460 575/600 200 230 460 575/600 200 575/600

15 30 30 30 30 75 75 60 60

24V DC

HMCPE 50A

* ECR23H8BAC-L * ECR23H8CAE-L * ECR23H8DAE-L * * * * ECR23L8EAF-N ECR23L8BAW-N ECR23L8CAF-N ECR23L8DAF-N

Frame Size D 100A


24V DC HMCPE 100A

Frame Size E 200A


24V DC 24V DC HMCPE 200A HMCPE 200A * ECR23P8EAG-R * ECR23P8EAX-R * ECR23P8DAJ-R * E511E20E3N * * E511E20D3N

All IT. Contactors and Starters are furnished with 24V DC coil and control power supply. The eighth digit Q denotes separate 24V DC control source. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECR23P4EAG. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. The eleventh position of the Catalog Numbers is the Solid-State Overload Range Code referred to in Table 34-45. For each Frame Size, enclosed starters with lower Amp Ratings are available. Contactor your Eaton Representative for component starters and their horsepower and overload range choices. *Please contact your local Eaton sales ofce.

Technical Data . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . Renewal Parts . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-14 Page 34-18 Page 34-22 Page 34-30 Page 34-48 1CD1C

34-48

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Wiring Diagrams

Vol. 2, Ref. No. [0312]

Wiring Diagrams
(If Used) 1 2 1 2 3 Circuit Breaker L1 L2 L3 L1 Fuse (2) L11 Fuse X1 L12 X2 Ground L2 IT./EM M Motor

34

Terminal Block (+) L1 L2 Power Supply 120V AC - 24V DC (+) Terminal Board () + 1 (+ Customer Control Device P F 2 = 24V DC Permissive Forward M 2

1 2 4 3

Reset + Alarm

Reset

Figure 34-20. IT. Combination Starter with CPT and Power Supply
(If Used) 1 2 3 1 2 3 Circuit Breaker L1 L2 L3 /EM Terminal Block (+) 1 2 Terminal Board () + 1 (+ Customer Control Device P F 2 1 Reset 4 2 3 Reset + Alarm = 24V DC Permissive Forward M M Motor

L2 L1 Power Supply 480V AC - 24V DC (+)

Figure 34-21. IT. Combination Starter with Power Supply

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005
Vol. 2, Ref. No. [0313]

34-49

Modication Codes

Modication Codes
Table 34-56. A Ammeters, Auxiliary Contacts, Accelerating Relays, Autotransformers
Modication Catalog Description Number Sufx Ammeter A1 Panel Type Wired to Current Transformer in Line 1, Type 1, 12 Panel Type Wired to Current Transformer in Line 1, Type 3R, 4X A2 Panel Type, Selector Switch and 3 Current Transformers Wired to Ammeter via Switch, Type 1, 12 Panel Type, Selector Switch and 3 Current Transformers Wired to Ammeter via Switch, Type 3R, 4X A3 A4 A5 A6 Miniature (Single-Phase), Type 1, 12 Miniature with Selector Switch, Type 1, 12 Switchboard (Single-Phase), Type 1, 12 Switchboard (Single-Phase), Type 3R, 4X Switchboard with Selector Switch, Type 1, 12 Switchboard with Selector Switch, Type 3R, 4X A7 A10 A11 3-Panel Type (Single-Phase), Type 1, 12 3-Panel Type (Single-Phase), Type 3R, 4X 3 Miniature (Single-Phase), Type 1, 3R, 4X, 12 3 Switchboard Type (Single-Phase), Type 1, 12 3 Switchboard Type (Single-Phase), Type 3R, 4X A12 AutoA8 transformers A9 Top Mounted A13 Auxiliary A14 Contacts (Unwired) A15 A16 Type Sizes 00 2 only (Unwired) IEC Sizes A K Only (Unwired) Freedom Series A17 A18 A19 A20 A21 A22 A23 A24 A25 A26 Side Mounted Auxiliary Contacts Freedom Series A27 A28 A29 A30 A31 A32 A33 A34 Ammeter Order by Description, Type 1, 3R, 4X, 12 hp Rating selection, see Enclosed Control Product Guide Order by Description 1NO 1NC 1NO-1NC 2NO 2NC 2NO-1NC 1NO-2NC 3NO 3NC 3NO-1NC 2NO-2NC 1NO-3NC 4NO 4NC 1NO 1NC 1NO-1NC 2NO 2NC 2NO-1NC 1NO-2NC 3NO * * * * * * * * * * * * * * * * * * * * * * * * Bell Alarm Bus Choke (MVX) B16 B20 B15 Backspin Timer B8 B9 B10 B11 B12 B6 Adder U.S. $ * * *

Table 34-56. A Ammeters, Auxiliary Contacts, Accelerating Relays, Autotransformers (Continued)


Modication Catalog Description Number Sufx Side Mounted Auxiliary Contacts Freedom Series, continued Auxiliary Contacts A35 A36 A37 A38 A39 A40 A42 A43 A44 Accelerating Relay A46 A47 3NC 3NO-1NC 2NO-2NC 1NO-3NC 4NO 4NC Contacts Mounted on Operating Mechanism of Disconnect Switch, 1NO-1NC Contacts Mounted on Operating Mechanism of Disconnect Switch, 2NO-2NC With Auxiliary Contact Omitted For 2-Speed 2NO/2NC 24V DC Auxiliary Relay IT. Only Adder U.S. $ * * * * * * * * * * *

34

* * * * * * * * * * * Breaker

Not available for IT. Starters.

Table 34-57. B Breaker Modications, Backspin Timer, Undervoltage Release, Bell Alarm, Bus Choke
Modication Catalog Number Sufx B1 B2 B3 B4 B5 Description Adder U.S. $ * * * * * * * * * * * * * *

1NO-1NC Auxiliary Contact on Breaker 2NO-2NC Auxiliary Contacts on Breaker Shunt Trip on Circuit Breaker 48 127V AC or DC Shunt Trip on Circuit Breaker 9 24V AC or DC Shunt Trip on Circuit Breaker 208 380V AC Shunt Trip on Circuit Breaker 415 600V AC or 220 250V DC Undervoltage Release for Breaker Current Limiter Mounted to Breaker Breaker Order by Description Thermal Magnetic Breaker 180 Seconds Undervoltage Release for Circuit Breaker 208 240V AC Undervoltage Release for Circuit Breaker 380 480V AC Undervoltage Release for Circuit Breaker 525 600V AC Bell Alarm for Circuit Breaker DC Bus Choke, Open Core and Coil

Undervoltage B13 Release B14

A DC bus choke may be used in place of an AC line reactor for line harmonic current reduction and for power source exceeding 500 kVA. The DC bus choke will not provide any protection for line voltage unbalance or transients. Consult Eaton. *Please contact your local Eaton sales ofce.

Oversize enclosure will be provided for IT. Starters. Consult Eaton. Top mounted auxiliary contacts cannot be added to contactors in Box 1 (Type 1). Not available for IT. Starters.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C

CA08102001E

For more information visit: www.EatonElectrical.com

34-50

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Modication Codes
Table 34-58. C Control Power Transformer, IT. Power Supplies, Control Relays, Cover Control (not elsewhere dened), Current Transformers, Compelling Relay, Control Wiring, Control Circuit Breaker, Separate Control, Customer-Supplied Components, Contactors, Counter, E-Stop Relay, DC/AC Interface, Separate Source Disconnect, Bypass Contactors
Modication Catalog Description Number Sufx Control C1 Power Transformers Make sure 8th character species primary/ C2 secondary voltage. See Page 33-101. Standard Size Control Transformer, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse 00 1 AH * 2 JK * 3 LM * 4 N * 5 PS * 69 * Adder U.S. $

Vol. 2, Ref. No. [0314]

Table 34-58. C Control Power Transformer, IT. Power Supplies, Control Relays, Cover Control (not elsewhere dened), Current Transformers, Compelling Relay, Control Wiring, Control Circuit Breaker, Separate Control, Customer-Supplied Components, Contactors, Counter, E-Stop Relay, DC/AC Interface, Separate Source Disconnect, Bypass Contactors (Continued)
Modication Catalog Description Number Sufx Power Supplies (IT. Only) Control Relays C27 C28 C12 C13 C14 Separate Control 120V AC to 24V DC Power Supply with Extra Capacity Order by Description 4-Pole Interposing Relay, 600V (2NO/2NC) Run Relay, 24V DC (MVX) 4-Pole, Unwired, A600 Rtg. 2NO-2NC 8-Pole, Unwired, A600 Rtg. 4NO-4NC Control Relay Order by Description 2-Wire Control Relay for Mechanical/ Magnetic Lighting Contactors Convert Position 7 to E30 Type Cover Control Lock-Off Attachment Added on Cover Control In Phase 1 In Phases 1 and 2 In 3 Phases Omit Control Wiring With Separate Control Wiring and Two 250V Fuses in Holder With Common Control Wiring and Two 600V (Class C) Fuses in Holder Control Wiring Type Order by Description Order by Description * * * * N/C * * * * * * * * Adder U.S. $ *

34

Standard Size Control Transformer, 24V/60 Hz Secondary with 2 Primary and 1 Secondary Fuse 00 1 AH * 2 JK * 3 LM * 4 N * 5 PS * 69 *

C15 C16

C42

50 VA Extra Capacity CPT 120V/60 Hz, 110V/50 Hz with 2 Primary and1 Secondary 00 1 AH * 2 JK * 3 LM * 4 N * 5 PS * 69 * Cover Control

C20 C17 C19

C3

100 VA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse 00 1 AH * 2 JK * 3 LM * 4 N * 5 PS * 69 *

Current Transformer(s) Compelling Relay

C21 C22 C23 C25 C26 C30 C31

C4

100 VA Extra Capacity CPT, 24V/60 Hz Secondary with 2 Primary and 1 Secondary Fuse 00 1 AH * 2 JK * 3 LM * 4 N * 5 PS * 69 *

Control Wiring

C5

200 VA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse 00 1 AH * 2 JK * 3 LM * 4 N * 5 PS * 69 * Control Circuit Breaker Separate Control

C33 C32

C6

200 VA Extra Capacity CPT, 24V/60 Hz Secondary with 2 Primary and 1 Secondary Fuse 00 1 AH * 2 JK * 3 LM * 4 N * 5 PS * 69 *

C35

Wired for Separate Control (Reduced Voltage) Customer Supplied Components to Be Installed Customer Supplied Wiring Diagram to Use

C7

300 VA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse 00 1 AH * 2 JK * 3 LM * 4 N * 5 PS * 69 *

Customer C36 Supplied Components C37

Not available for IT. Starters. Consult Eaton. *Please contact your local Eaton sales ofce.

C8

400 VA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse 00 1 AH * 2 JK * 3 LM * 4 N * 5 PS * 69 * *

C9

1 kVA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse 2 kVA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse Control Transformer Order by Description CPT with Power Supply for IT.

C10

C11 C34

Not available for IT. Starters. Consult Eaton.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005
Vol. 2, Ref. No. [0315]

34-51

Modication Codes
Table 34-59. D Device Labels, Deceleration Relay, Drain and Breather, DeviceNet, Duplex Modications
Modication Catalog Number Sufx Description Adder U.S. $ (each label) 2-Speed Drain and Breather Drain Only Breather Only DSNAP DN65 Alternator Omitted (Deduct Price) START/STOP Pushbuttons Supplied for Each Motor HAND/OFF/AUTO Selector Switch Supplied for Each Motor No. 1 Lead - No. 2 Lead Selector Switch for Manual Selection of Lead Pump (Alternator is Omitted) Red RUN Pilot Light Supplied for Each Motor Push-to-Test Red RUN Pilot Light Supplied for Each Motor TEST Pushbutton for Each Motor CPT, 120V Secondary, 2 Pri. Fuses & 1 Sec. Fuse Supplied for Ea. Motor 00 1 * 66A * * 66A * * 105 135A * 850A * 105 135A * 850A * * D23 D24 D25 D26 D27 D28 D29 D30 D31 D32 D22 D21 * * 37A * * 2 * 3 * 49 * * * * * * * * * * * *

Table 34-58. C Control Power Transformer, IT. Power Supplies, Control Relays, Cover Control (not elsewhere dened), Current Transformers, Compelling Relay, Control Wiring, Control Circuit Breaker, Separate Control, Customer-Supplied Components, Contactors, Counter, E-Stop Relay, DC/AC Interface, Separate Source Disconnect, Bypass Contactors (Continued)
Modication Catalog Description Number Sufx C40 C41 C43 C44 C45 Contactor/Starter Order by Description Operations Counter E-Stop Relay (DeviceNet) DC/AC Interface Module IEC Separate Source Disconnect for Control Circuitry * * Adder U.S. $

Device Labels D1 Decel. Relay Drain and Breather (Type 7/9 Enclosure) DeviceNet Duplex Modications D2 D5 D6 D7 D8 D9 D12 D14 D15 D16

34

Contactor/ Starter Counter E-Stop Relay DC/AC Interface Separate Source Disconnect Bypass Contactors for IT./MVX Starters (MVX: 1/2 to 5 hp Only)

C46/J1 Isolation Contactor MVX * * C46/J2 Output Contactor MVX * * C46/J3 Bypass Contactor MVX * * MVX * * 37A 37A * * 66A * * 105 135A * 850A * 37A * * 66A * * 105 135A * 850A *

80 240A 304 500A 650 720A

D17 D18 D19 D20

* * *

80 240A 304 500A 650 720A

80 240A 304 500A 650 720A C46/J4 Isolation/Output/Bypass Contactor

CPT w/100VA Extra Capacity, 120V Sec., 2 Pri. Fuses & 1 Sec. Fuse Supplied for Each Motor 00 1 * 2 * 3 * 49 *

CPT w/200VA Extra Capacity, 120V Sec., 2 Pri. Fuses & 1 Sec. Fuse Supplied for Each Motor 00 1 * 2 * 3 * 49 *

80 240A 304 500A 650 720A C46/J5 3-Contactor Bypass Pkg. for MVX

Not available for IT. Starters. Includes CPT, Pilot Lights, Selector Switch, Auxiliary Contacts and Control Relay. Consult Eaton.

CPT for Duplex Order by Description Add 2 Relays to Modify Controller to Operate w/Single-Pole Pilot Devices Add 3 Relays to Modify Controller to Operate w/Single-Pole Pilot Devices Green OFF for each starter Green Push-to-Test OFF for ea. starter Green RUN Light Red STOP Light P-T-T green RUN Light P-T-T red STOP Light Elapsed Time Meter * * * * * * * * *

Not available for IT. Starters. Consult Eaton. *Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C CA08102001E For more information visit: www.EatonElectrical.com

34-52

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Modication Codes
Table 34-60. E Enclosure Modications, Elapsed Time Meter, Duplex Outlet, Starter
Modication Catalog Description Number Sufx Enclosure E3 Modications E4 E5 E7 Oversize Enclosure Enclosure Order by Description Enclosure w/Pole Mounting Hardware Service Entrance Rating with Ground/Neutral for Lighting Contactors (30 200A) 65K AIC Rated Explosion Proof Enclosure Service Entrance Rating w/Ground Bar Safety Door Interlock Wired Across Coil, Type 1, 12 Wired Across Coil, Type 3R, 4X Elapsed Time Meter Order by Description Convenience Duplex Outlet Mounted in Side of Enclosure Horizontal Combination Starter, Size 0 2 Narrow Combination Starter, Size 0 2 * * * * H2 4 N 180A * 00 1 AH 37A Adder U.S. $ * 4 N 180A * 5 PS * * Install Heater H5 Packs (Freedom Series) Class 20 /D1 /D2 /D3 /D4 /D5 /D6 /D7 /D8 /D9 /D10 /D11 /D12 /D13 /D14 /D15 /D16 /D17 /D18 /D19 /D20 /D21 /D22 /D23 /D24 H2001B-3 H2002B-3 H2003B-3 H2004B-3 H2005B-3 H2006B-3 H2007B-3 H2008B-3 H2009B-3 H2010B-3 H2011B-3 H2012B-3 H2013B-3 H2014B-3 H2015B-3 H2016B-3 H2017B-3 H2018-3 H2019-3 H2020-3 H2021-3 H2022-3 H2023-3 H2024-3 * * * * Space Heater * Consult Eaton. Adder U.S. $ *

Vol. 2, Ref. No. [0316]

Table 34-62. G Ground Fault Relay, Grounding


Modication Catalog Description Number Sufx Ground Fault G1 Relay G3 Grounding G5 Ground Fault Relay (Wired) Ground Fault Relay (Unwired) Special Grounding Order by Description Adder U.S. $ * *

34

E65K E8 E11 Elapsed Time E9 Meter E10 Duplex Outlet E12 Starter E13 E14

Table 34-63. H Heater (Space), Heater Packs Installed


Modication Cat. Description No. Sufx H1 Space Heater and Thermostat 00 1 AH 37A 2 JK 66 105A MVX * 5 PS 240 304A * 2 JK 66 105A MVX * 5 PS 240 304A * /D25 /D26 /D27 /D28 /D29 /D30 /D31 /D32 /D33 /D34 /D35 /D36 /D37 /D38 /D39 /D40 /D41 * 69 360 850A * Class 10 H2101B-3 H2102B-3 H2103B-3 H2104B-3 H2105B-3 H2106B-3 H2107B-3 H2108B-3 H2109B-3 H2110B-3 H2111B-3 H2112B-3 H2113B-3 H2114B-3 H2115-3 H2116-3 H2117-3 * * 69 360 850A * 3 LM 135A 3 LM 135A Adder U.S. $

Not available for IT. Starters. Consult Eaton.

Space Heater and NC Interlock

Table 34-61. F Fuse Clips, Fuse Blocks, Fungus Protection, Fingerproof Covers, EMI Filter
Modication Catalog Description Number Sufx Fuse Clips F1 Change Fuse Clips in Position 8 to Class J 00 1 AH * F2 Fuse Blocks F4 F5 2 JK * 3 LM * 4 N *

Change Fuse Clips in Position 8 to Class H & K (30 & 60 Ampere Only) Power Fuses Included Order by Description 30 Ampere Control Circuit Fuseholder (KTK) Mounted on Panel (Unwired), Fuse Not Supplied 30 Ampere Control Circuit Fuseholder Mounted on Panel (Unwired), FNQR Fuse Supplied 3-Pole Power Fuseholder Mounted on Front Contactor Separate Fusing of Control Power Supply IT. Blown Fuse Indicator (Not for PFC) Class CC Fuses 3-Phase 240V U.S. $ 480V U.S. $ 1/2 hp * 1/2 hp * 1 hp * 1 hp * 1 hp * 2 hp * 2 hp * 2 hp * 3 hp * 3 hp * 3 hp * 5 hp * 5 hp *

F6

F7 F8 F10 F21 EMI Filter (MVX) F22

* * *

*Please contact your local Eaton sales ofce.

F23

1-Phase 240V U.S. $

The EMI lter is not necessary to meet the CE mark requirements for EMC when installing the MVX in an EC country. Consult Eaton.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005
Vol. 2, Ref. No. [0317]

34-53

Modication Codes Table 34-65. L Lightning Arrestor, Lugs, Labels, Line and Load Reactors, Lighting Contactors (Continued)
Modication Catalog Description Number Sufx Lighting Contactors L21 L22 L23 L24 L25 L26 L27 L28 Adder U.S. $ * * L29A L29B L29C L29D L29E L29F L29G 1 NC Pole 2 NC Pole 3 NC Pole 4 NC Pole 5 NC Pole 6 NC Pole 7 NC Pole 8 NC Pole 3-Wire 120V AC 3-Wire 240V AC 3-Wire 24V AC 3-Wire 24V DC 2-Wire 120V AC 2-Wire 240V AC 2-Wire 24V AC Adder U.S. $ * * * * * * * * * * * * * * *

Table 34-64. K MVX Keypad


Modication Catalog Description Number Sufx Keypad (MVX) K1 K2 K3 K4 K5 Door-Mounted AFD Keypad (Type 1 and 12) Door-Mounted AFD Keypad (Type 3R) AFD Copy Keypad (mounted on drive) Door-Mounted AFD Copy Keypad (Type 1 and 12) Door-Mounted AFD Copy Keypad (Type 3R) Adder U.S. $ * * * * *

34

Table 34-65. L Lightning Arrestor, Lugs, Labels, Line and

Load Reactors, Lighting Contactors


Modication Catalog Description Number Sufx Lighting Arrestor Lugs Carton Label Line Reactors (MVX) L3 L9 L10 L12 Installed on Panel Special Lugs Order by Description Customer Marking Specify 3% Input Line Reactor, 3-Phase, Open Core and Coil 240V U.S. $ 480V U.S. $ L13 1/2 hp * * 1 hp * * 2 hp * 2 hp * 3 hp * 3 hp * 5 hp * 5 hp *

Table 34-66. M Solid-State Controllers


Modication Catalog Description Number Sufx Solid-State Controller M1 M2 M3 M4 M5 M6 S701 3.5A Solid-State Controller S701 15A Solid-State Controller S701 25 Solid-State Controller S701 25A with DB Solid-State Controller Torque Limiter 15A Torque Limiter 25A Adder U.S. $ * * * * * *

1/2 hp 1 hp

3% Input Line Reactor, 1-Phase, Open Core and Coil 480V U.S. $ 1/2 hp * 1 hp * 2 hp * 3 hp *

L14

5% Input Line Reactor, 3-Phase, Open Core and Coil 240V U.S. $ 480V U.S. $ 1/2 hp * * 1 hp * * 2 hp * 2 hp * 3 hp * 3 hp * 5 hp * 5 hp *

Table 34-67. N Nameplates


Modication Catalog Description Number Sufx Nameplates N1 Enclosure Nameplates Adder U.S. $ *

1/2 hp 1 hp

L15

5% Input Line Reactor, 1-Phase, Open Core and Coil 480V U.S. $ 1/2 hp * 1 hp * 2 hp * 3 hp *

*Please contact your local Eaton sales ofce.

L16 Load Reactors (MVX) L17

Line Reactor Order by Description Output Line DV/DT Filter, Open Core and Coil 480V U.S. $ 1/2 hp * 1 hp * 2 hp * 3 hp * 5 hp *

L18

Load Reactor Order by Description

If the power source exceeds 500 kVA, 3% line unbalance, or if transient voltages from power factor capacitor switching events are present, an input line reactor must be used. The input line reactor will also reduce line current harmonics. The output line DV/DT lter is required when the distance from the drive to the motor exceeds 33 feet (10m). The total cable run should not exceed 165 feet (50m). Consult Eaton.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C CA08102001E For more information visit: www.EatonElectrical.com

34-54

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Modication Codes
Table 34-68. P Pilot Lights, Pushbuttons, Phase Relays, Potential Transformers, Power Factor Correction Capacitors, Program Timer, Percentage Timer, Photocell
Modication Catalog Description Number Sufx Adder U.S. $ * * P60 * * * * * * * * * * * * * * * * * * * * * * * * * Potential Transformers P39 P40 P41 * * * * * * * Percentage Timers Photocell P47 P48 P70 Pump Controller Program Timers P42 P43 P44 P45 Illuminated Pushbutton Phase Loss Relay Phase Reversal Relay Phase Unbalance Relay Phase Monitoring Relay Power Factor Correction Capacitors P61 P62 P63 P64 P65 P66 P67 P68 P69 P27 P28 P30

Vol. 2, Ref. No. [0318]

Table 34-68. P Pilot Lights, Pushbuttons, Phase Relays, Potential Transformers, Power Factor Correction Capacitors, Program Timer, Percentage Timer, Photocell (Continued)
Modication Catalog Description Number Sufx Pilot Lights (Continued) P58 P59 Pilot Light Red BYPASS (MVX) Pilot Light Amber INVERTER ENABLE (MVX) Pilot Light Red INVERTER RUNNING (MVX) Pilot Light Green STOP FORWARD/REVERSE Red Pilot Lights UP/DOWN Red Pilot Lights OPEN/CLOSE Red Pilot Lights HIGH/LOW Red Pilot Lights FAST/SLOW Red Pilot Lights Green RUN Light LED Bulbs Blue OVERLOAD Light Illuminated Pushbutton Order by Description Phase Loss Relay Phase Reversal Relay * * Adder U.S. $ * * * * * * * * * * * *

34

Push-to-Test Pilot Lights

P1 P2 P3 P4 P49 P54 P55 P56 P57

Push-to-Test Pilot Light (Red RUN) Wired to Coil Push-to-Test Pilot Light (Green OFF) Wired in Series with Auxiliary Contact Combination of P1 and P2 Above Push-to-Test Pilot Light (Amber RUN) Wired to Coil Push-to-Test Pilot Light (Green RUN) Push-to-Test Pilot Light Red BYPASS (MVX) Push-to-Test Pilot Light Amber INVERTER ENABLE (MVX) Push-to-Test Pilot Light Red INVERTER RUNNING (MVX) Push-to-Test Pilot Light Green STOP EMERGENCY STOP Mushroom Head Pushbutton Omitted START/STOP ON/OFF START ON OFF FORWARD/REVERSE/STOP FAST/SLOW/STOP FAST/OFF/SLOW HIGH/LOW/STOP HIGH/LOW SLOW/FAST Pushbutton with Legend Plate UP/STOP/DOWN OPEN/STOP/CLOSE START/STOP Pushbuttons Located in Top 2 Holes With 1 Amber Pilot Light Marked POWER AVAILABLE Wired to Load Side of 2 Fuses or Circuit Breaker Pilot Light (Amber RUN) Wired to Coil With 1 Red Pilot Light Marked RUN Wired thru NO Auxiliary Contact With 1 Push-to-Test Red Light Marked RUN Wired thru NO Auxiliary Contact Pilot Light Red RUN Pilot Light Red ON Pilot Light Green OFF Pilot Light Order by Description Pilot Light Red STOP

Pushbuttons

P5 P6 P7 P8 P9 P10 P11 P12 P13 P14 P15 P16 P17 P18 P52 P53 P73

P32

Phase Unbalance Relay

P34

Phase Monitoring Relay

P38

/F1 /F2 /F3 /F4 /F5 /F6 /F7 /F8

20KVAR 25KVAR 30KVAR 35KVAR 40KVAR 45KVAR 50KVAR 60KVAR

/F9 /F10 /F11 /F12 /F13 /F14 /F15 /F16

70KVAR 75KVAR 80KVAR 90KVAR 100KVAR 125KVAR 150KVAR 175KVAR

/F17 /F18 /F19 /F20 /F21 /F22

200KVAR 225KVAR 250KVAR 300KVAR 350KVAR 400KVAR

Potential Transformer Wired L1 L2 Potential Transformer Wired L1 L2 and L2 L3 Potential Transformer 3 Phases Pump Controller for IT. 15-Minute Program Timer 24-Hour Program Timer 7-Day Program Timer with Day Omission Feature 15-Minute Percentage Timer 60-Minute Percentage Timer Photoelectric Receptacle with Photocell

* * * * * * * * * *

Pilot Lights

P19

P20 P21 P22 P23 P24 P25 P26 P29

Not available for IT. Starters. Consult Eaton.

Not available for IT. Starters. Consult Eaton. *Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005
Vol. 2, Ref. No. [0319]

34-55

Modication Codes
Table 34-70. R Ramp, Relays, Resets, Overload Relay Modications, DeviceNet Interface (Continued)
Modication Catalog Number Sufx Fixed Heater Overload Relay, continued R40 R41 R42 R43 R55 R56 R57 R58 R59 Description Adder U.S. $ 355.00 500.00A 465.00 650.00A 610.00 850.00A * * *

Table 34-69. Q IQ Products, DN50


Modication Catalog Description Number Sufx IQ Products Q14 Q1 Q3 Q5 IQ Data Metering Module DN50 Q12 Q14 Q13 IQ 220 with cable IQ 500 MP3000 IQ 4000 IQ Data Metering Module IQ 220 with Cable DeviceNet Input/Output Module Adder U.S. $ * * * * * * *

C316UNA3A C316UNA3B C316UNA3C

34

Fixed Heater Overload Relay Order by Description C316FNA3F w/Current Trans. C316FNA3G w/Current Trans. C316FNA3H w/Current Trans. C316FNA3J w/Current Trans. C316FNA3K w/Current Transformer C316FNA3L w/Current Transformer NEMA Full Load Size Current Adjustment Range (A) 00 0.1 0.3 0.3 1.0 1.0 2.9 1.6 5.0 3.7 12 0&1 0.1 0.3 0.3 1.0 1.0 2.9 1.6 5.0 3.7 12 12 32 2 12 37 14 45 26 85 57 180 96 300 192 600 4 5 6 60.00 84.00 FLA 78.00 108.00 FLA 102.00 144.00 FLA 132.00 186.00 FLA 168.00 240.00 FLA * * * * *

Not available for IT. Starters.

Table 34-70. R Ramp, Relays, Resets, Overload Relay Modications, DeviceNet Interface
Modication Catalog Description Number Sufx Ramp Relay R1 R2 R4 Extended Ramp of IT. Overvoltage Relay Omit Overload Relay (Deduct Price) 00 0 AF -30. R7 Fixed Heater Overload Relay R8 R9 R10 R11 R12 R13 R14 R15 R16 R17 R18 R19 R20 R21 R22 R23 R24 R25 R26 R27 R28 R29 R30 R31 R32 R33 R34 R35 R36 R37 R38 R39 1 GH -30. 2 JK -54. 3 LM -90. 4 N -138. Adder U.S. $ * * * 59 PS -504. * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Reversing DeviceNet Interface Resets Electronic Relay

R60

210.00 310.00 FLA

IEC Frame

3-Phase Manual Reset Overload Class 10 G101 G102 G103 G104 G105 G101 G102 G103 G104 G105 G106 G107 G108 G109 G112 G104 G104 R52_ * Class 20 G81 G82 G83 G84 G85 G81 G82 G83 G84 G85 G86 G87 G88 G89 G92 G84 G84 R50_ *

3-Phase Automatic/ Manual Reset Class Class 10 20 G141 G142 G143 G144 G141 G142 G143 G144 G121 G122 G123 G124 G121 G122 G123 G124

Overload Relay Order by Description C316FNA3C C316FNA3D C316FNA3E C316FNA3F C316FNA3G C316FNA3H C316FNA3J C316FNA3K C316FNA3L C316FNA3M C316FNA3N C316FNA3P C316FNA3Q C316FNA3R C316FNA3S C316FNA3T C316KNA3A C316KNA3B C316KNA3C C316KNA3D C316KNA3E C316KNA3F C316PNA3A C316PNA3B C316PNA3C C316PNA3D C316PNA3E C316PNA3F C316SNA3A C316SNA3B C316SNA3C C316SNA3D .25 .40A .40 .63A .63 1.00A 1.00 1.40A 1.30 1.80A 1.70 2.40A 2.20 3.10A 2.80 4.00A 3.50 5.00A 4.50 6.50A 6.00 8.50A 7.50 11.00A 10.00 14.00A 13.00 19.00A 18.00 24.00A 24.00 32.00A 18.00 25.00A 22.00 32.00A 29.00 42.00A 36.00 52.00A 45.00 63.00A 60.00 80.00A 65.00 90.00A 80.00 100.00A 100.00 135.00A 110.00 150.00A 130.00 175.00A 150.00 200.00A 130.00 185.00A 165.00 235.00A 220.00 310.00A 285.00 400.00A A A A A A,B,C A A A A A,B,C D,E D,E,F,H G,H

G145 G125

G145 G125 G146 G126 G147 G127 G148 G128 G149 G129 G152 G132 G144 G124 G144 G124 R53_ R51_ * * N/C N/C * * *

G,H,J,K,L 3 M,N,L N/A N/A

Catalog Number Sufx Adder U.S. $ R5 R6 R44 R45 R71 R54 R69

Change External Reset to Internal Reset Hole Covered with Plug Internal Reset No Hole Plug Manual Reset Only on Overload Relay Auto Reset Only on Overload Relay N3R Reset Boot Added (Type 1/12 Only) Reversing Contactor/Starter DeviceNet Interface

Not available for IT. Starters. Consult Eaton.

Not available for IT. Starters. Features: Self-Powered Phase Loss Protection Current Adjustment Knob 1% Repeat Accuracy 1NO and 1NC Isolated Contacts Complete Modication Code includes reset code. Example R52/G102. Consult Eaton. *Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C CA08102001E For more information visit: www.EatonElectrical.com

34-56

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Modication Codes
Table 34-71. S System Voltage, Selector Switches, Suppressor, Incomplete Sequence Protection, Single-Phase Jumper, Surge Capacitor, Speed Potentiometer
Modication Catalog Description Number Sufx Adder U.S. $ N/C

Vol. 2, Ref. No. [0320]

Table 34-71. S System Voltage, Selector Switches, Suppressor, Incomplete Sequence Protection, Single-Phase Jumper, Surge Capacitor, Speed Potentiometer (Continued)
Modication Catalog Description Number Sufx Surge Suppression Sequence Timer Sequence Protection Pump Single Phase S20 S26 S27 S28 S29 MOV (IT.) Sequence Timer (Pump Panels) Incomplete Sequence Protection 480V BP9000 Pump Convert Contactor or Starter from Three-Phase to Single-Phase Install Jumper Single-Phase Rev. 120V Single-Phase Rev. 240V Surge Capacitor Wired to Disconnect Line Side Speed Potentiometer (MVX) Adder U.S. $ * * * * *

34

System Voltage Selection

S1

S2 Selector Switches S3 S4 S5 S6 S7 S8 S9

S10 S11 S12 S13 S14 S15 S16 S17 S18 S21 S38 S41 S42 S43 S45 S46 S19 S40 S24

Suppressor

System Voltage Selection for Internal Components /H1 208V 60 Hz /H2 240V 60 Hz /H3 277V 60 Hz, 1-Ph /H4 480V 60 Hz /H5 600V 60 Hz /H6 796V 60 Hz /H7 220V 50 Hz /H8 380V 50 Hz /H9 415V 50 Hz /H10 550V 50 Hz /H11 660V 50 Hz /H12 380V 60 Hz /H13 1500V 60 Hz System Voltage Selection Specify on Order HAND/OFF/AUTO HAND/AUTO HAND/OFF/AUTO Selector Switch with 1 Red RUN Pilot Light RUN/OFF/AUTO AUTO/OFF/TEST AUTO/OFF/TEST Selector Switch with 1 Red RUN Pilot Light AUTO/OFF/TEST Selector Switch with 1 Red RUN Pilot Light and 1 Green Pilot Light OFF/AUTO START/STOP OFF/ON HIGH/LOW FAST/OFF/SLOW SLOW/FAST FORWARD/REVERSE HIGH/OFF/LOW HIGH/LOW/OFF/AUTO HAND/OFF/AUTO Spring Return from Left INVERTER/OFF/BYPASS (MVX) OPEN/OFF/CLOSE FORWARD/OFF/REVERSE FAST/OFF/SLOW/AUTO LOCAL/REMOTE RUN/OFF Selector Switch Omitted (Pump Panels Only) Selector Switch Order by Description Transient Suppressor Mounted on Magnet Coil

N/C * * * * * * *

Surge Capacitor Speed S39 Potentiometer

S30 S31 S37

* * * *

Not available for IT. Starters. *Please contact your local Eaton sales ofce.

* * * * * * * * * * * * * * * * * *

When using 3-position selector switch with magnetic lighting contactor, mod C20 must also be used (ECL04, ECL13, ECL15). Not available for IT. Starters. Consult Eaton.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005
Vol. 2, Ref. No. [0321]

34-57

Modication Codes
Table 34-72. T Timers, Time Delay Relays, Terminal Blocks, Terminal Points, Ring Lug Connections (Continued)
Modication Catalog Description Number Sufx IT./EM, continued T60 T61 T62 T63A * * * * * * T75 * * * * * * T76 T77 T63D T64 T70 T71 T72 T73 T74 Reset Only (DeviceNet) STOP with Reset (DeviceNet) FORWARD/REVERSE/STOP with Reset (DeviceNet) FORWARD/REVERSE/STOP with Reset 120V AC (DeviceNet) FORWARD/REVERSE/STOP with Reset 24V DC (DeviceNet) ON/OFF Reset Only START/STOP with Reset HAND/OFF/AUTO START with Reset FORWARD/REVERSE/STOP with Reset HAND/OFF/AUTO FORWARD/ REVERSE with Reset ON/OFF with Reset FAST/SLOW/STOP with Reset HAND/OFF/AUTO FAST/SLOW with Reset Adder U.S. $ * * * * * * * * * * * * * *

Table 34-72. T Timers, Time Delay Relays, Terminal Blocks, Terminal Points, Ring Lug Connections
Modication Catalog Description Number Sufx Timers T1 T2 T3 T25 Time Delay Relays T6 T7 T8 Terminal Blocks T9 T10 T24 Terminal Points T11 T12 T13 T14 T15 T21 Pneumatic Timer Installed on Contactor, Unwired, 30 Sec. Max. Pneumatic Timer Installed on Contactor, Unwired, 180 Sec. Max. Pneumatic Timer Mounted in Enclosure, Unwired, 180 Sec. Max. Timer Order by Description Time Delay Relay, 3 Minutes Maximum, Unwired, ON DELAY Time Delay Relay, 3 Minutes Maximum, Unwired, OFF DELAY Time Delay Low Voltage Release Relay With 1 Single Circuit Terminal Block, Unwired With 2 Single Circuit Terminal Block, Unwired Power Terminal Block for DeviceNet Overload With 6 Terminal Points, Unwired With 12 Terminal Points, Unwired With 18 Terminal Points, Unwired Terminal Point per Customer Specication, Unwired (Price Each) Terminal Point per Customer Specication, Wired (Price Each) 3 Terminals Mounted Between Contactor and Overload for Power Factor Capacitors Sizes 0 2 3 Terminals Mounted Between Contactor and Overload for Power Factor Capacitors Sizes 3 4 Quick-Connect Terminals Added to DP Contactor/Starter Ring Lug Connections on Power Wires Ring Lug Connections on Control Wires Reset Only STOP with Reset START/STOP with Reset HAND/OFF/AUTO with Reset 120V AC HAND/OFF/AUTO with Reset 24V DC ON/OFF Reset Only (DeviceNet) STOP with Reset (DeviceNet) START/STOP with Reset (DeviceNet) HAND/OFF/AUTO with Reset 120V AC (DeviceNet) HAND/OFF/AUTO with Reset 24V DC (DeviceNet) ON/OFF Reset Only STOP with Reset FORWARD/REVERSE/STOP with Reset FORWARD/REVERSE/STOP with Reset 120V AC FORWARD/REVERSE/STOP with Reset 24V DC ON/OFF * * * * * * * * * * * * * * * * * * Adder U.S. $ * * *

34

*Please contact your local Eaton sales ofce.

T22

T23 Ring Lug Connectors IT./EM T16 T17 T30 T31 T32 T33A T33D T34 T40 T41 T42 T43A T43D T44 T50 T51 T52 T53A T53D T54

* *

Not available for IT. Starters. Consult Eaton.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C CA08102001E For more information visit: www.EatonElectrical.com

34-58

IEC Contactors & Starters IT. Electro-Mechanical Enclosed


June 2005

Modication Codes
Table 34-73. U Undervoltage Relay, Time Delay Undervoltage Relay
Modication Catalog Description Number Sufx Undervoltage Relays U2 U4 U5 U7 Undervoltage Relay, Adjustable Time Delay Undervoltage Relay, Non-adjustable Time Delay Undervoltage Relay, Adjustable Under- and Overvoltage Relay Adder U.S. $ * * * * W9 WYE-Delta hp Wiring Diagram Adder U.S. $ * * W10 W12

Vol. 2, Ref. No. [0322]

Table 34-75. W Wattmeter, Watt-Hour Meter, Wiremarkers, Wiring Diagram


Modication Catalog Description Number Sufx Wattmeter Watt-Hour Meter W1 W5 Wattmeter Watt-Hour Meter with Demand Attachment Wiremarkers Wiremarkers Order per Customer Diagram or Specications Wiremarkers Order by Description See Enclosed Control Product Guide Reduced Copy of Custom Wiring Diagram Laminated on Inside of Door * * Adder U.S. $ * * *

34

Time Delay Undervoltage Relays Under- and Overvoltage Relay

Wiremarkers W7 W8

Not available for IT. Starters.

Table 34-74. V Voltmeter


Modication Catalog Description Number Sufx Voltmeters V1 V2 1 Panel Type Voltmeter Wired L1 L2 Panel Type Voltmeter and Selector Switch Wired to Read Three Line Voltages Miniature Voltmeter Wired L1 L2 Miniature Voltmeter and Selector Switch Wired to Read Three Line Voltages Switchboard Type Voltmeter Wired L1 L2 Switchboard Type Voltmeter and Selector Switch Wired to Read Three Line Voltage 3 Panel Type Voltmeters Wired in Each Phase 3 Miniature Voltmeters Wired in Each Phase 3 Switchboard Type Voltmeters Wired in Each Phase Voltmeter Order by Description

Type 1/12 only. Consult Eaton. *Please contact your local Eaton sales ofce.

V3 V4 V5 V6

* * * *

V7 V8 V9 V10 Type 1/12 only. Consult Eaton.

* * *

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Miniature Controls


June 2005
Vol. 2, Ref. No. [0323]

34-59

Product Family Overview

Contents
Description Page Product Family Overview Product Description . . . . . . 34-59 Features . . . . . . . . . . . . . . . 34-59 Standards and Certications . . . . . . . . . . 34-59 Instructional Leaets . . . . . 34-59 Catalog Number Selection . . . . . . . . . . . . . 34-60 Contactors Non-reversing and Reversing Contactors with Screw Pressure Terminals . . . . . 34-61 Contactors with Quick Connect Terminals. . . . . . 34-62 Contactors with Solder Pin Terminals . . . . . . . . . . 34-63 Technical Data . . . . . . . . . . . . . 34-64 Accessories Auxiliary Contacts Front and Side Mounted . . . . . . 34-67 Overload Relays . . . . . . . . . 34-68 ID Markers, Reversing Connection Links and Surge Suppressors . . . . . 34-69 Terminal Markings . . . . . . . . . 34-69 Dimensions . . . . . . . . . . . . . . . 34-71

Overload Relays (Bimetallic Type C312)


Mini Contactor with Screw Pressure Plate Terminals Catalog Number CE12BNC310B

11 Settings to cover .10 to 12.0 Amps Phase loss compensated Ambient temperature compensated Class 10 Bimetallic type O.L. Stop and test buttons included 1NO-1NC auxiliary contacts included as standard

34

Accessories

Side and front mounted auxiliary contacts Identication clips Surge suppressors Reversing connection links

Standards and Certications


Mini Contactor Reversing Pair with Screw Pressure Plate Terminals Catalog Number CE52CNC310H

Meet or exceed the North American and International standards:


Product Description
Eaton offers a complete line of CutlerHammer Miniature Control Products that includes mini contactors (mechanically interlocked and non-reversing), overload relays and snap-on accessories. A wide range of applications are possible, including small electrical motors fractional to 5 hp (480V AC). Because of its compact size, the line is best suited to be applied in light duty loads such as hoisting, packaging, material handling, heating, lighting and automation systems.

UL CSA Mini Contactors and Surge Suppressors UL File No. E19224, Category NLDX and NLDX2; CSA File No. LR353, Class 3211-07 Accessories UL File No. E19223, Category NKCR and NKCR2; CSA File No. LR353, Class 3211-07 Overload Relays UL File No. E19223, Category NKCR and NKCR2; CSA File No. LR353, Class 3211-03 IEC, VDE, CE and most other International standards

Features
Mini Contactors

Instructional Leaets
49097 Minicontactors, Overloads and Accessories

Available in three different terminal congurations: Screw Pressure Plate Quick Connect Solder Pin Mechanically interlocked or non-reversing Panel or DIN rail mounting (35 mm) Fingerproof protection Low noise operation AC or DC operation possible

CA08102001E

For more information visit: www.EatonElectrical.com

34-60

IEC Contactors & Starters Miniature Controls


June 2005

Catalog Number Selection

Vol. 2, Ref. No. [0324]

Catalog Number Selection


Table 34-76. IEC Miniature Controls Catalog Numbering System

CE 12 B N C 3 1 0 W1 34
Designation CE - IEC Contactor Type 12 - Non-reversing 52 - Mechanically Interlocked Power B - 4 kW (3 hp @460V AC) C - 5.5 kW (5 hp @460V AC) Enclosure N - Open Connections B - Quick Connects C - Screw Pressure Plate P - Solder Pin No. of Poles 3 - 3 Poles 4 - 4 Poles NOTE: No renewal parts (coils, contact kits) available for the Mini Control line. No. of NO Aux. Contacts 0 - None 1 - One No. of NC Aux. Contacts 0 - None 1 - One Coil Designations AC Coil Voltage (Frequency 40 450 Hz) T - 24V W - 48V A - 110 127V 3.5 VA B - 220 240V H - 227V L - 380 415V DC Coil Voltage R1 - 12V T1 - 24V W1 - 48V 3.5 Watts A1 - 110 125V B1 - 220 240V DC Low Power Consumption Coils T2 - 24V (1.4 Watts) V2 - 17 32V (2.4 Watts) T3 - 24V (1.7 Watts with Surge Suppressor) V3 - 17 32V (2.8 Watts with Surge Suppressor)

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Miniature Controls


June 2005
Vol. 2, Ref. No. [0325]

34-61

Contactors Non-reversing and Reversing

Product Selection
Non-reversing/Reversing Contactors with Screw Pressure Terminals

34

Screw Pressure Plate Terminals Non-reversing Contactor

Screw Pressure Plate Terminals Reversing Contactor

Table 34-77. Non-reversing Contactor Screw Pressure Plate Terminals


Max. AC-3 Amp Rating (400V) 9 9 9 12 12 12 IEC 947 AC-1 Thermal Current (400V) 16 16 16 20 20 20 kW Rating AC-3 400/440V 4 4 4 5.5 5.5 5.5 Maximum UL Horsepower 1-Phase Horsepower Ratings 110/ 220/ 480/ 120V 240V 600V 1/2 1/2 1/2 3/4 3/4 3/4 1 1 1 1-1/2 1-1/2 1-1/2 None None None 2 2 2 No. of Power 3-Phase Horsepower Ratings Poles 110/ 200/ 220/ 440/ 550/ 120V 208V 240V 480V 600V 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 3 3 3 5 5 5 3 3 3 5 5 5 3 3 4 3 3 4 Aux. Contacts Catalog Number Price U.S. $ AC DC Coil Coil

1NO 1NC None 1NO 1NC None

CE12BNC310_ CE12BNC301_ CE12BNC400_ CE12CNC310_ CE12CNC301_ CE12CNC400_

75.00 75.00 75.00 97.00 97.00 97.00

83.00 83.00 83.00 102.00 102.00 102.00

Table 34-78. Reversing Contactor Screw Pressure Plate Terminals


Max. AC-3 Amp Rating (400V) 9 9 12 12 IEC 947 AC-1 Thermal Current (400V) 16 16 20 20 kW Rating AC-3 400/440V 4 4 5.5 5.5 Maximum UL Horsepower 1-Phase Horsepower Ratings 110/ 220/ 480/ 120V 240V 600V 1/2 1/2 3/4 3/4 1 1 1-1/2 1-1/2 None None 2 2 No. of Power 3-Phase Horsepower Ratings Poles 110/ 200/ 220/ 440/ 550/ 120V 208V 240V 480V 600V 1 1 1 1 1 1 2 2 2 2 3 3 3 3 5 5 3 3 5 5 3 3 3 3 Aux. Contacts Catalog Number Price U.S. $ AC DC Coil Coil

1NO 1NC 1NO 1NC

CE52BNC310_ CE52BNC301_ CE52CNC310_ CE52CNC301_

168.00 168.00 215.00 215.00

184.00 184.00 224.00 224.00

Screw pressure plate terminal contactors are supplied standard with reversing connection links included.

Table 34-79. AC Coil Selection Table


Coil Voltage Frequency 40 450 Hz 24 48 110 127 220 240 277 380 415 3.5 VA 3.5 VA 3.5 VA 3.5 VA 3.5 VA 3.5 VA Sufx Code T W A B H L

Table 34-80. DC Coil Selection Table


Coil Voltage 12 24 48 110 125 220 240 3.5 Watts 3.5 Watts 3.5 Watts 3.5 Watts 3.5 Watts Sufx Code R1 T1 W1 A1 B1 T2 V2 T3 V3

DC Low Power Consumption Coils: Non-reversing Mini Contactors


24 (1.4 Watts) 17 32 (2.4 Watts) 24 (1.7 Watts with Surge Suppressor) 17 32 (2.8 Watts with Surge Suppressor)

AC coils have an integrated protective circuit-rectier bridge and varistor included.

Auxiliary contacts can not be used with Low Power Consumption DC Coils Sufx designations: T2, V2, T3 and V3. For DC coils with Sufx designations T2, V2, T3 and V3, a Price Adder must be applied to the DC Coil List Price in Tables 34-77 and 34-78. See Table 34-81 below.

Table 34-81. Price Adder for Low Wattage DC Coils


Devices 4 kW 5 kW Sufx Designations T2 & V2 T3 & V3 T2 & V2 T3 & V3 Adder U.S. $ 37.50 42.50 38.50 43.50

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . 1CD7 CA08102001E For more information visit: www.EatonElectrical.com

34-62

IEC Contactors & Starters Miniature Controls


June 2005

Contactors Non-reversing and Reversing

Vol. 2, Ref. No. [0326]

Non-reversing/Mechanically Interlocked Contactors with Quick Connect Terminals

34

Quick Connect Terminals Non-reversing Contactor

Quick Connect Terminals Mechanically Interlocked Contactor


No. of Power Poles Aux. Contacts Catalog Number Price U.S. $ AC Coils 75.00 75.00 75.00 97.00 97.00 97.00

Table 34-82. Non-reversing Contactor Quick Connect Terminals


Max. AC-3 Amp Rating (400V) 9 9 9 12 12 12 IEC 947 AC-1 Thermal Current (400V) 16 16 16 20 20 20 kW Rating AC-3 400/440V Maximum UL Horsepower 1-Phase Horsepower Ratings 110/ 220/ 480/ 120V 240V 600V 1/2 1/2 1/2 3/4 3/4 3/4 1 1 1 1-1/2 1-1/2 1-1/2 None None None 2 2 2 3-Phase Horsepower Ratings 110/ 200/ 220/ 440/ 550/ 120V 208V 240V 480V 600V 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 3 3 3 5 5 5 3 3 3 5 5 5

DC Coils 83.00 83.00 83.00 102.00 102.00 102.00

4 4 4 5.5 5.5 5.5

3 3 4 3 3 4

1NO 1NC None 1NO 1NC None

CE12BNB310_ CE12BNB301_ CE12BNB400_ CE12CNB310_ CE12CNB301_ CE12CNB400_

Table 34-83. Mechanically Interlocked Contactor Quick Connect Terminals


Max. AC-3 Amp Rating (400V) 9 9 12 12 IEC 947 AC-1 Thermal Current (400V) 16 16 20 20 kW Rating AC-3 400/440V Maximum UL Horsepower 1-Phase Horsepower Ratings 110/ 120V 1/2 1/2 3/4 3/4 220/ 240V 1 1 1-1/2 1-1/2 480/ 600V None None 2 2 3-Phase Horsepower Ratings 110/ 200/ 220/ 440/ 550/ 120V 208V 240V 480V 600V 1 1 1 1 1 1 2 2 2 2 3 3 3 3 5 5 3 3 5 5 3 3 3 3 1NO 1NC 1NO 1NC CE52BNB310_ CE52BNB301_ CE52CNB310_ CE52CNB301_ No. of Power Poles Aux. Contacts Catalog Number Price U.S. $ AC Coils DC Coils

4 4 5.5 5.5

168.00 168.00 215.00 215.00

184.00 184.00 224.00 224.00

Table 34-84. AC Coil Selection Table


Coil Voltage Frequency 40 450 Hz 24 48 110 127 220 240 277 380 415 3.5 VA 3.5 VA 3.5 VA 3.5 VA 3.5 VA 3.5 VA Sufx Code T W A B H L

Table 34-85. DC Coil Selection Table


Coil Voltage 12 24 48 110 125 220 240 3.5 Watts 3.5 Watts 3.5 Watts 3.5 Watts 3.5 Watts Sufx Code R1 T1 W1 A1 B1 T2 V2 T3 V3

DC Low Power Consumption Coils: Non-reversing Mini Contactors


24 (1.4 Watts) 17 32 (2.4 Watts) 24 (1.7 Watts with Surge Suppressor) 17 32 (2.8 Watts with Surge Suppressor)

AC coils have an integrated protective circuit-rectier bridge and varistor included.

Auxiliary contacts can not be used with Low Power Consumption DC Coils Sufx designations: T2, V2, T3 and V3. For DC coils with Sufx designations T2, V2, T3 and V3, a Price Adder must be applied to the DC Coil List Price in Tables 34-82 and 34-83. See Table 34-86 below.

Table 34-86. Price Adder for Low Wattage DC Coils


Devices 4 kW 5 kW Sufx Designations T2 & V2 T3 & V3 T2 & V2 T3 & V3 Adder U.S. $ 37.50 42.50 38.50 43.50

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD7 For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Miniature Controls


June 2005
Vol. 2, Ref. No. [0327]

34-63

Contactors Non-reversing and Reversing

Non-reversing/Mechanically Interlocked Contactors with Solder Pin Terminals

34

Solder Pin Terminals Non-reversing Contactor

Solder Pin Terminals Mechanically Interlocked Contactor

Table 34-87. Non-reversing Contactor Solder Pin Terminals


Max. AC-3 Amp Rating (400V) 9 9 12 12 IEC 947 AC-1 Thermal Current (400V) 16 16 20 20 kW Rating AC-3 400/440V 4 4 5.5 5.5 Maximum UL Horsepower 1-Phase Horsepower Ratings 110/ 120V 1/2 1/2 3/4 3/4 220/ 240V 1 1 1-1/2 1-1/2 480/ 600V None None 2 2 3-Phase Horsepower Ratings 110/ 200/ 220/ 440/ 550/ 120V 208V 240V 480V 600V 1 1 1 1 1 1 2 2 2 2 3 3 3 3 5 5 3 3 5 5 No. of Power Poles Aux. Contacts Catalog Number Price U.S. $ AC Coils DC Coils

3 3 3 3

1NO 1NC 1NO 1NC

CE12BNP310_ CE12BNP301_ CE12CNP310_ CE12CNP301_

75.00 75.00 97.00 97.00

83.00 83.00 102.00 102.00

Table 34-88. Mechanically Interlocked Contactor Solder Pin Terminals


Max. AC-3 Amp Rating (400V) 9 9 12 12 IEC 947 AC-1 Thermal Current (400V) 16 16 20 20 kW Rating AC-3 400/440V 4 4 5.5 5.5 Maximum UL Horsepower 1-Phase Horsepower Ratings 110/ 120V 1/2 1/2 3/4 3/4 220/ 240V 1 1 1-1/2 1-1/2 480/ 600V None None 2 2 3-Phase Horsepower Ratings 110/ 200/ 220/ 440/ 550/ 120V 208V 240V 480V 600V 1 1 1 1 1 1 2 2 2 2 3 3 3 3 5 5 3 3 5 5 No. of Power Poles Aux. Contacts Catalog Number Price U.S. $ AC Coils DC Coils

3 3 3 3

1NO 1NC 1NO 1NC

CE52BNP310_ CE52BNP301_ CE52CNP310_ CE52CNP301_

168.00 168.00 215.00 215.00

184.00 184.00 224.00 224.00

Table 34-89. AC Coil Selection Table


Coil Voltage Frequency 40 450 Hz 24 48 110 127 220 240 277 380 415 3.5 VA 3.5 VA 3.5 VA 3.5 VA 3.5 VA 3.5 VA Sufx Code T W A B H L

Table 34-90. DC Coil Selection Table


Coil Voltage 12 24 48 110 125 220 240 3.5 Watts 3.5 Watts 3.5 Watts 3.5 Watts 3.5 Watts Sufx Code R1 T1 W1 A1 B1 T2 V2 T3 V3

DC Low Power Consumption Coils: Non-reversing Mini Contactors


24 (1.4 Watts) 17 32 (2.4 Watts) 24 (1.7 Watts with Surge Suppressor) 17 32 (2.8 Watts with Surge Suppressor)

AC coils have an integrated protective circuit-rectier bridge and varistor included.

Auxiliary contacts can not be used with Low Power Consumption DC Coils Sufx designations: T2, V2, T3 and V3. For DC coils with Sufx designations T2, V2, T3 and V3, a Price Adder must be applied to the DC Coil List Price in Tables 34-87 and 34-88. See Table 34-91 below.

Table 34-91. Price Adder for Low Wattage DC Coils


Devices 4 kW 5 kW Sufx Designations T2 & V2 T3 & V3 T2 & V2 T3 & V3 Adder U.S. $ 37.50 42.50 38.50 43.50

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD7 CA08102001E For more information visit: www.EatonElectrical.com

34-64

IEC Contactors & Starters Miniature Controls


June 2005

Technical Data and Specications

Vol. 2, Ref. No. [0328]

Mini Contactors Technical Data


Conformity to Standards

Table 34-94. Shock Resistance CE12 (B or C)


Shock Directions Contactor ON A 20g B1 20g 20g B2 20g 20g C1 20g 20g C2 20g
B1

Standard Mounting Position


C1

IEC 947-4-1, 947-5-1, CE UL 508, CSA, 22.2 Insulation Voltage VI: 690V Ambient Temperature: Contactor: -13 to 131F (-25 to +55C) Contactor and Overload Relay: -13 to 122F (-25 to +50C) Storage: -40 to 176F (-40 to +80C) Finger Protection: IP20 Impulse Withstand Voltage (Uimp): 6 kV Climatic Resistance: Acc. to DIN 50 017 Acc. to UTE C 63 100: Alternating climate proof 30 cycles, version I Mounting Position: Vertical/horizontal (any position) Max. Switching Frequency: AC-1 cyc./h: 300 DC-1, DC-3, DC-5, AC-2, AC-3 cyc./h: 600
CE12B (4 kW) CE12C (5.5 kW)

Specications

Contactor OFF 10g

20g
A

34

B2 C2

1/2 Sinusoidal Shock, 10 ms: No Change in Contact Position

Table 34-95. Utilization Categories, DC Loadings for Both CE12 (B or C)


Utilization Category DC-1 L/R 1 ms Ie Amps
+ -

DC-3 L/R 2 ms

DC-5 L/R 7.5 ms

24V 16.0 48V 16.0 60V 16.0 110V 7.0 220V .8 24V 48V 60V 110V 220V
-

16.0 8.0 4.0 1.5 .25 16.0 16.0 15.0 7.0 1.5 16.0 16.0 16.0 15.0 4.0

16.0 2.0 1.25 .40 .20 16.0 16.0 12.0 2.0 .5 16.0 16.0 16.0 8.0 2.0

16.0 16.0 16.0 16.0 5.0 16.0 16.0 16.0 16.0 14.0

Table 34-92. Switching Times


AC DC AC DC Contactor Contactor Contractor Contactor Closing Delay NO Closing Delay NC ms 14 to 26 4 to 10 4 to 10 14 to 26 16 to 40 16 to 40 4 to 10 4 to 10

24V 48V 60V 110V 220V

Coil Technical Data


Table 34-96. Coil for AC and DC Operations
Rated Power Contactors: CE12, CE52 (4 and 5.5 kW) for AC Operation Inrush 3.5 VA 3.5W Seal 3.5 VA 3.5W

Opening Delay NO ms 16 to 40 ms 16 to 40 Opening Delay NC ms

14 to 26

14 to 26

Table 34-93. Current Ratings (I) IEC 947-4-1


AC-1 Thermal Current Ith CE12B (4 kW) Ie 131F (55C) 220/240V 380/440V 500V AC-2, AC-3 (Ie) 220/240V 380/440V 500V AC-4 16A 16A 12A kW 2.2 4.0 3.0 104F (40C) 20A 20A 12A Ie 9A 9/8A 5.5A CE12C (5.5 kW) Ie 131F (55C) 16A 16A 12A kW 3 5.5 4.0 104F (40C) 20A 20A 12A Ie 12/11A 12/11A 7.0A

Contactors: CE12B, CE52 (4 and 5.5 kW) for DC Operation Contactors with Low Power Consumption Power Coils: CE12B (1.4W, 24V DC Coil Sufx T2) CE12B (2.4W, 17 32V DC Coil Sufx V2)

1.4W 2.4W

1.4W 2.4W

AC coils have an integrated protective circuit-rectier bridge and varistor included. Low Power Consumption DC Coils can not be used with Reversing Mini Contactors.

Table 34-97. Mini Contactors to Connect to PLCs


Cold I mA CE12B (1.7W, 24V DC Coil Sufx T3) CE12B (2.8W, 17 32V DC Coil Sufx V3) Coil Voltage Range 77 125 PW 1.75 2.8 Hot I mA 60 94 PW 1.35 2.10

Refer to Specic Load Life Curves

Electrical Life Details: See endurance curves on Page 34-65 Mechanical Life: 10,000,000 operations Power Loss per Pole: 2W at 20A Backup Fuse, Type gG, Type 1: 20A (CE12B); 25A (CE12C) Backup Fuse, Type gG, Type 2: 20A Terminal Capacity Stranded Copper 167F (75C) or Equivalent, Single Wire: 12 22 AWG; Two Wires: 12 18 AWG Terminal Capacity for Reversible Pair Stranded Copper 167F (75C) or Equivalent: 12 16 AWG

.85 1.1 x Us

Low Power Consumption DC Coils can not be used with Reversing Mini Contactors. Us = coil voltage rating.

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Miniature Controls


June 2005
Vol. 2, Ref. No. [0329]

34-65

Technical Data and Specications

AC Electrical Endurance Curves Mini Contactors CE12 and CE52


AC-1/AC-3 for CE12B
10 8 6 5 4 3 2 10 8 6 5 4 3 2

AC-1/AC-3 for CE12C

34

Millions of Operations

0.2 0.1 0.08 0.06 0.05 0.04 0.03 0.02

Millions of Operations
AC-3 AC-1

1 0.8 0.6 0.5 0.4 0.3

1 0.8 0.6 0.5 0.4 0.3 0.2 0.1 0.08 0.06 0.05 0.04 0.03 0.02

AC-3
0.01 1 1.5 2 3 4 56

AC-1

0.01 1 1.5 2 3 4 56 8 10 15 20 30

8 10 15 20 30

Rated Operating Current Ic(A)

Rated Operating Current Ic(A)

AC-4 for CE12B


10 8 6 5 4 3 2 10 8 6 5 4 3 2

AC-4 for CE12C

Millions of Operations

Millions of Operations

1 0.8 0.6 0.5 0.4 0.3 0.2 0.1 0.08 0.06 0.05 0.04 0.03 0.02 0.01 1 1.5 2 3 4 56 8 10 15 20 30

1 0.8 0.6 0.5 0.4 0.3 0.2 0.1 0.08 0.06 0.05 0.04 0.03 0.02 0.01 1 1.5 2 3 4 56

AC-4

AC-4

8 10 15 20 30

Breaking Current Ic(A)

Breaking Current Ic(A)

Figure 34-22. AC Electrical Endurance Curves


Note: Catalog Numbers used are not complete, see Catalog Number Selection, Page 34-60.

DC Utilization Curve
Mini Contactors CE12 and CE52 Load-Life Curves for DC-1, DC-3 and DC-5 Load Conditions
If only one current path is used, the service life read-off for the related breaking capacity must be multiplied by .33, and, if there are 2 current paths, it must be multiplied by .66. The time constants L/R (ms) which differ for the individual utilization categories have been accounted for on the curves. A = 3 poles in series DC-1 B = 3 poles in series DC-3 C = 3 poles in series DC-5

10

5 4 3

Millions of Operations

2 1.5 1

A
0.5 0.4 0.3 0.2 0.15 0.1

B C

0.05 0.04 0.03 15 20 30 40 50 100 150 200 300 400 500 1000

Watts(W) CE12 and CE52

Figure 34-23. DC Load-Life Curves

CA08102001E

For more information visit: www.EatonElectrical.com

34-66

IEC Contactors & Starters Miniature Controls


June 2005

Technical Data and Specications

Vol. 2, Ref. No. [0330]

Lighting Load Switching Ratings Table


Mini Contactors CE12 and CE52 Reversing and Mechanically Interlocked
The following table shows the number of lamps which can be connected per circuit at 230V/50 Hz. Please note the following: If the specied capacitor load is exceeded, this may result in admissibly high peak inrush currents. Other factors which inuence the magnitude of peak inrush currents are:

34
Table 34-98. Lighting Load Switching Ratings
Lamp Type Lamp Data Watt In A Capacitor Permissible Number Load of Lamps per Circuit in F (230V, 50 Hz) in the Case of Contactor Types CE12B, CE12C and CE52B 20 12 6 4 2 1 25 23 20 16 12 5 5 2 x 26 2 x 20 2 x 16 2 x 12 2x5 2x5 4.5 4.5 4.5 7 7 18 18 7 6 7 5 4 1 1 10 7 5 3 2 1 7 8 10 18 25 45 60 4 3 2 1 1 17 8 11 6 11 6 (Lamp Pairs)

Length and cross-section of installed supply cables. Type of electronic ballast units. Lamp make.

Lamp Type

Lamp Data Watt In A

Capacitor Permissible Number Load of Lamps per Circuit in F (230V, 50 Hz) in the Case of Contactor Types CE12B, CE12C and CE52B

Incandescent Lamps

60 100 200 300 500 1000 15 20 40 58 65 115 140 2 x 20 2 x 40 2 x 58 2 x 65 2 x 115 2 x 140 15 20 40 58 65 115 140

.26 .43 .87 1.30 2.17 4.35 .33 .37 .43 .67 .67 1.5 1.5 2 x .13 2 x .22 2 x .32 2 x .34 2 x .65 2 x .75 .11 .13 .22 .32 .34 .65 .75 .61 .8 1.15 2.15 3.25 5.40 .28 .41 .65 1.22 1.95 3.45 4.8

Metal Halogen Lamps e.g. HQI, HPI

p.f. Uncorrected 35 70 150 250 400 35 70 150 250 400 .53 1 1.8 3 3.5 .25 .45 .75 1.5 2.5 1.5 1.5 2.4 3.5 3.3 3.3 2.3 .31 .42 .63 .94 1.0 1.16 1.32 1.8 3.0 3.7 4.7 .83 1.5 2.0 2.4 6.3 20 33 40 48 106 20 20 30 45 40 40 25 6 12 20 33 35 10 5 3 2 1 6 3 1 1 1 4 4 2 2 2 2 2 3 2 2 1

Fluorescent Lamps

p.f. Uncorrected and Series p.f. Correction

Parallel p.f. Correction

Lead-Lag Circuit

Low Pressure Sodium Vapor Lamps

p.f. Uncorrected 35 55 90 135 150 180 200 35 55 90 135 150 180 200

Parallel p.f. Correction

Parallel p.f. Correction

High Pressure Mercury Vapor Lamps e.g. HQL, HPL

p.f. Uncorrected 50 80 125 250 400 700 50 80 125 250 400 700 1000

High Pressure Sodium Vapor Lamps

p.f. Uncorrected 150 250 330 400 150 250 330 400 1000

Parallel p.f. Correction

Parallel p.f. Correction

Transformers for Halogen Low Volt Lamps

Transformers for Wattage Watt 20 50 75 100 150 200 300

Permissible Number of Transformers per Circuit (230V, 50 Hz) in the Case of Contactor Types CE12B, CE12C and CE52B 40 20 13 10 7 5 3

Lamps with Electronic Ballast Units

1 x 18 2 x 18 1 x 36 2 x 36 1 x 56 2 x 58

Note: The values provided above for switching lamp loads are estimates and are non-binding.

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Miniature Controls


June 2005
Vol. 2, Ref. No. [0331]

34-67

Accessories Application Notes

Auxiliary Contacts Front and Side Mounted


A total of six auxiliary contacts are available to be used with the mini control line. Front mounted auxiliary contacts are available in three contact congurations (1NO-1NC, 2NO and 2NC) and can be screw mounted to non-reversing and reversing contactors with screw pressure plate terminals only. Side mounted auxiliary contacts are available for the miniature control product line in three terminal versions: screw pressure plate, quick connect and solder pin. The side mounted auxiliary is mounted to the left side of nonreversing contactors without tools. Only one side mounted auxiliary can be mounted on these products. Table 34-99. Front Mount Auxiliary Contacts for Screw Pressure Plate Terminals Only Mini Contactor and Control Relay
Add-On Auxiliary Contacts Conguration 1NO-1NC 2NO 2NC Catalog Number C320MCF11 C320MCF20 C320MCF02 Price U.S. $ 18.10 18.10 18.10

Side mounted auxiliary contacts can not be used simultaneously with front mounted auxiliary contacts. Auxiliary contacts can not be used with low power DC Coil Sufx designations T2, T3, V2 or V3. Side mounted auxiliary contacts can not be used with mechanically interlocked contactors. Auxiliary contacts used with devices having screw pressure plate terminals are UL Listed and side mounted auxiliary contacts used with devices having quick connect or solder pin terminals are UL Recognized.

34

Front Mounted Auxiliary Contact with Pressure Plate Terminals Catalog Number C320MCF20

Table 34-100. Side Mount Auxiliary Contacts for Screw Pressure Plate, Quick Connect, Solder Pin Terminals and Control Relays
Add-On Terminal Type Contactor/Control Relay Auxiliary Contacts Conguration Screw Pressure Plate Quick Connect Solder Pin 1NO-1NC 1NO-1NC 1NO-1NC Catalog Number Price U.S. $

Side Mounted Auxiliary Contact with Pressure Plate Terminals Catalog Number C320MCS11

C320MCS11 C320MBS11 C320MPS11

18.10 18.10 18.10

Side Mounted Auxiliary Contacts with Quick Connect Terminals Catalog Number C320MBS11

Side Mounted Auxiliary Contact with Solder Pin Terminals

Catalog Number C320MPS11

Figure 34-24. Mini Contactor and Side Mounted Auxiliary Contact Being Assembled Table 34-101. Technical Data of Auxiliary Contacts
Description Rated Operating Voltage Ue Conventional rated thermal current Ith Rated operating current Ie, AC-15 at Ue Rated operating current Ie, DC-13 at Ue Voltage 220/240V 380/440V 500 V 24V 60V 110V 220/240V Specication 12 to 240V DC 12 to 500V AC 6A 4A 3A 2A 2.5A 1.2A .7A .4A

Screw Pressure Plate Mini Contactor and Front Mounted Auxiliary Contact Catalog Number C320MCF02

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD7 CA08102001E For more information visit: www.EatonElectrical.com

34-68

IEC Contactors & Starters Miniature Controls


June 2005

Accessories

Vol. 2, Ref. No. [0332]

Overload Relays

40% ED max. ops./h: 60 (if 6X in startup time 1 s) Overvoltage Category/Pollution Degree: III/3 Table 34-103. Terminal Capacities
Description

Safe Isolation to IEC 536: 300V AC Conventional Free Air Thermal Current (Ith): 6.0A

Specication mm 2X (.75X 2.5) mm 2X (.5X 1.5) AWG 2X (18X 12)

34

Solid Flexible with Ferrule Solid or Stranded

Table 34-104. Trip Contact Ratings AC-15


Operating Voltage (Ue) 120V 220/240V 380/415V 500V

Overload Relay

Table 34-102. Bimetallic Overload Relay Class 10


Motor FLA in Amperes .10 .16 .16 .24 .24 .40 .40 .60 .60 1.00 1.00 1.60 1.60 2.40 2.40 4.0 4.0 6.0 6.0 9.0 9.0 12.0 Catalog Number C312AN3A C312AN3B C312AN3C C312AN3D C312AN3E C312AN3F C312AN3G C312AN3H C312AN3J C312AN3K C312AN3L Price U.S. $ 73.50 73.50 73.50 73.50 73.50 73.50 73.50 73.50 73.50 73.50 73.50

Rated Operational Current (Ie) Contacts 95 96 NC (Break) Contacts 97 98 NO (Make)

1.5A 1.5A

.7A .5A

.5A .3A

Table 34-105. Trip Contact Ratings DC-13


Operating Voltage (Ue) Rated Operational Current (Ie) Contacts 95 96 NC (Break) Contacts 97 98 NO (Make) 24V DC 60V DC 110V DC 220V DC

.9A .9A

.5A .5A
120 100 80 60 40 20

.3A .3A

.1A .1A

Table 34-106. Additional Technical Data


Catalog Number Amp Range Max. Wt. Fuse Lbs. (kg) Type gL A .5 1.0 2.0 2.0 4.0 6.0 6.0 10.0 10.0 10.0 20.0 .154 (.070) .154 (.070) .154 (.070) .154 (.070) .154 (.070) .154 (.070) .154 (.070) .154 (.070) .154 (.070) .154 (.070) .154 (.070) Minutes

From Cold State


10 8 6 4 2

Tripping Time

Note: Overload relays to be used with Pressure Plate Terminal type Mini Contactors only.

Thermal Overload Relay C312 Technical Data Conformity to Standards


IEC 947-4-1, 947-5-1, CE UL 508, CSA 22.2

C312AN3A C312AN3B C312AN3C C312AN3D C312AN3E C312AN3F C312AN3G C312AN3H C312AN3J C312AN3K C312AN3L

.10 .16A .16 .24A .24 .40A .40 .60A .60 1.00A 1.00 1.60A 1.60 2.40A 2.4 4.0A 4.0 6.0A 6.0 9.0A 9.0 12.0A

3 Phases
1 40

Seconds

20

2 Phases
10 8 6 4 2 1 0.8 1 1.2 1.5 2 3 4 5 6 7 8 910

Thermal (Bimetallic) Overload Relay, C312 OL Relay


Insulation Voltage (Ui): 690V AC Rated Operational Voltage (Ue): 690V AC Ambient Temperature: -13 to 122F (-25 to +50C) temperature compensated Storage: -40 to 158F (-40 to +70C) Impulse Withstand Voltage (Uimp): 6 kV Climatic Resistance Acc. to DIN 50 017 Acc. to UTE C 63 100: IEC 68-2-3, IEC 68-2-30 Mounting Position: 30 from vertical position, not horizontal, not upside down, 5 mm side by side mounting distance Switching Frequency with Avoidance of Nuisance Trippings max. ops./h: 15

Operating Current as a Multiple of the Setting Current

Figure 34-25. Overload Relay C312 Trip Curves


Setting Variances 1. 1 3 2 Adjust knob for setting to rated current of the motor Reset: Hand manual reset Position A: Auto without manual reset Position H: Reset OFF Test
Pull NO97 NO95 NO98 NO96 Position of Reset Push

2.

3.
1/L1 3/L2 5/L3 R T 95 96 2/T1 4/T2 6/T3 97 98

Figure 34-26. Setting Variances

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD7 For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Miniature Controls


June 2005
Vol. 2, Ref. No. [0333]

34-69

Accessories and Terminal Markings

Identication Markers, Reversing Connection Links and Surge Suppressors

34
Reversing Connection Links Surge Suppressors

Table 34-107. Other Accessories


Description Identication Markers Surge Suppressors to use with Screw Pressure Plate Control Relays and Mini Contactors: Surge Suppressor 24 60V DC Surge Suppressor 50 250V DC Surge Suppressor 200 420V DC Surge Suppressors to use with Quick Connect Control Relays and Mini Contactors: Surge Suppressor 24 60V DC Surge Suppressor 50 250V DC Surge Suppressor 200 420V DC Reversing Connection Links (2 Pieces) To be used with mechanically interlocked screw pressure plate terminal contactors. Catalog Number C320MCM1 C320MSS1 C320MSS2 C320MSS3 C320MSS4 C320MSS5 C320MSS6 C320MCR1 Price U.S. $ 48.50 30.75 30.75 30.75 30.75 30.75 30.75 18.10

Terminal Markings
Contactors
Non-reversing Contactors with Screw Pressure Plate, Quick Connect and Solder Pin Terminals 1 3 5 7 A1 1 3 5 13 A1 1 3 5 21 A1

Side Mounted Auxiliary Contacts


1 3 5 7

2 4 6 8 CE12(B or C)N(B or C or P)400 2 4 6 8 A2 Four-Pole 2 4 6 14 A2 Three-Pole with 1NO Auxiliary Contact 2 4 6 22 A2 Three-Pole with 1NC Auxiliary Contact 53 61 1 3 5 13

Mechanically Interlocked Contactors with Screw Pressure Plate, Quick Connect and Solder Pin Terminals A1 13 1 3 5 1 3 5 13 A1

62 54 C320MCS11 C320MBS11 C320MPS11

2 4 6 14 CE12(B or C)N(B or C or P)310 1 3 5 21

A2 14 2 4 6 2 4 6 14 A2 Three-Pole with 1NO Auxiliary Contact A1 21 1 3 5 1 3 5 21 A1

22

CE12(B or C)N(B or C or P)301

Figure 34-28. Terminal Markings for Side Mounted Auxiliary Contact Blocks
Notes: To be used with non-reversing mini contactors with terminal types: Screw Pressure Plate Terminals, Quick Connect, Solder Pin. Side mounted auxiliary contacts to be tted on the left hand side of mini contactors. Side mounted auxiliary contacts can not be used with special low power DC coils less than 3.5W. Side mounted auxiliary contacts can not be tted on mechanically interlocked contactors. Catalog Numbers used are not complete, see Catalog Number Selection, Page 34-60.

A2 22 2 4 6 2 4 6 22 A2 Three-Pole with 1NC Auxiliary Contact

Figure 34-27. Pole Congurations and Terminal Locations


Note: Catalog Numbers used are not complete, see Catalog Number Selection, Page 34-60.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD7 CA08102001E For more information visit: www.EatonElectrical.com

34-70

IEC Contactors & Starters Miniature Controls


June 2005

Terminal Markings

Vol. 2, Ref. No. [0334]

Front Mounted Auxiliary Contacts


1 3 5 7

CE12(B or C)NC400

C320MCF 2 1 4 3 6 5 8 13 53 63 C320MCF20 54 2 1 4 3 6 5 14 21 51 52 64 61 C320MCF02 62 53 54 61 C320MCF11 62

34

Mini Contactor with Screw Pressure Plate Terminals

CE12(B or C)NC310 CE52(B or C)N310

C320MCF

CE12(B or C)NC301 CE52(B or C)N301 2 4

C320MCF

22

Figure 34-29. Terminal Markings for Front Mounted Auxiliary Contact Blocks
Notes: To be screwed onto the front of non-reversing and mechanically interlocked Contactors with Screw Pressure Plate terminals. Front and side mounted auxiliary contacts can not be tted simultaneously. Front mounted auxiliary contacts (C320MCF_) can only be used with reversing contactors with screw pressure plate terminals. Catalog Numbers used are not complete, see Catalog Number Selection on Page 34-60.

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Miniature Controls


June 2005
Vol. 2, Ref. No. [0335]

34-71

Dimensions

Non-reversing/Reversing with/without Auxiliary Contacts


1.83 (46.5) 1.71 (43.5) 1.32 (33.5) 2.26 (57.5) 1.77 (45.0) .18 (4.5) Mini Contactor CE12(B or C) (AC and DC Operated) for Pressure Plate Terminals 1.87 (47.5) 1.75 (44.5) 1.32 (33.5) 1.65 (42.0) 1.10 (28.0) 1.83 (46.5) 1.71 (43.5) 1.32 (33.5)

2.07 (52.5) 1.87 (47.5) 2.26 (57.5) 1.77 (45.0) 1.65 (42.0) 1.00 (25.4)

2.07 (52.5) 1.87 (47.5)

34

.18 (4.5) Mini Contactor CE12(B or C) (AC and DC Operated) for Quick Connect Terminals 1.83 (46.5) 1.71 (43.5) 1.32 (33.5)

1.87 (47.5) 1.65 (42.0)

.16 (4.0) 2.26 (57.5) 1.65 1.00 (42.0) (25.4)

2.68 (68.0)

.04 (1.0)

1.77 (45.0)

Mini Contactor CE12(B or C) (AC and DC Operated) for Solder Pin Terminals 1.83 (46.5) 1.71 (43.5) 1.32 (33.5) 2.26 (57.5) 1.77 (45.0)

.18 (4.5) Mini Contactor CE12(B or C) (AC and DC Operated) with Auxiliary Contact Block C320 (Side Mounted) for Screw Pressure Plate and Quick Connect Terminals 1.87 (47.5) 1.75 (44.5) 1.32 (33.5)

3.80 (96.5) 2.26 (57.5)

3.80 (96.5)

.16 (4.0) .04 (1.0)

1.65 (42.0) 1.00 1.77 (25.4) (45.0)

1.65 (42.0)

Mechanically Interlocked Contactors CE52BNC with Screw Pressure Plate and Quick Connect Terminals Drilling Plans for Mini Contactors for Screw Mounting M4 .18 (4.5) 3.54 (90.0)

.18 (4.5) Mechanically Interlocked Contactors CE52BNP with Solder Pin Terminals Drilling Plans for Mini Contactors with Solder Pin Terminals for PC Board Mounting 5 x .40 = 2.00 7 x .40 = 2.80 (5 x 10.2 = 51) (7 x 10.2 = 71.1) .40 .40 (10.2) .40 (10.2) (10.2)

1.97 (50.0)

1.97 (50.0)

.06 (1.5) .80 (20.3) 1.20 (30.5)

1.00 (25.4) .06 (1.5) 2.30 (58.4)

1.00 (25.4) .06 (1.5) 3.40 (86.4) Mechanically Interlocked Contactor

1.00 (25.4)

.18 1.38 (4.5) (35.0) Mechanically Interlocked 1.57 Contactors CE52BN(C or B or P) (40.0) with Screw Pressure Plate, 1.77 Quick Connect and (45.0) Solder Pin Terminals CE12(B or C) Mini Contactor with Screw Pressure Plate, Quick Connect and Solder Pin Terminals

1.50 (38.1) Basic Devices 4-Pole Mini Contactor

Basic Devices with Auxiliary Switch Block Mini Contactor

Figure 34-30. Approximate Dimensions in Inches (mm)


Note: Catalog Numbers used are not complete, see Catalog Number Selection, Page 34-60.

CA08102001E

For more information visit: www.EatonElectrical.com

34-72

IEC Contactors & Starters Miniature Controls


June 2005

Dimensions

Vol. 2, Ref. No. [0336]

Mini Contactor with Overload Relay


1.381.77 (3545) 1.87 (47.5) .36 (9.1)

.18 (4.5)

34

.18 (4.5)

1.83 (46.5)

1.97 1.00 (50.0) (25.4) 1.65 (42.0)

1.85 (47.0)

4.13 (105.0)

1.26 (32.0) 1.77 (45.0)

.16 (4.0)

.26 (6.5)

2.2 (56.0)

Mini Contactor with Screw Pressure Plate Terminals and Overload Relay CE12(B or C)NC + C312AN3

Figure 34-31. Approximate Dimensions in Inches (mm)

Auxiliary Contacts
1.83 (46.5) 1.71 (43.5) 1.32 (33.5) 1.87 (47.5) 1.75 (44.5) 1.32 (33.5) 1.83 (46.5) 1.71 (43.5) 1.32 (33.5)

.80 (20.3)

.80 (20.3)

.16 (4.0) Min.

.80 (20.3)

1.91 1.65 (48.5) (42.0)

1.00 (25.4)

1.91 1.65 (48.5) (42.0)

.04 (1.0)

1.91 1.65 (48.5) (42.0)

1.10 (28.0)

Side Mounted to Use with Screw Pressure Plate Terminal Contactor C320MCS11

Side Mounted to Use with Solder Pin Contactor C320MPS11

Side Mounted to Use with Quick Connect Contactor C320MBS11

.36 (9.1)

.18 (4.5)

2.87 (73.0) 2.32 (59.0) 1.71 (43.5) 1.32 (33.5) .39 1.14 (10.1) (29.0) .38 (9.6) .22 (5.5)

1.87 (47.5) 1.73 (44.0) 1.43 (36.4)

1.04 (26.5) .61 .39 (15.5) (10.0) 1.14 .39 (10.1) (29.0)

1.77 (45.0)

1.65 (42.0) 1.97 (50.0) 2.26 (57.5) .39 (10.0) .18 (4.5)

.36 (9.1)

1.38 (35.0) 1.57 (40.0) 1.77 (45.0)

C320MCF Front Mounted Auxiliary Contact to Be Used with Contactor or Control Relay with Pressure Plate Terminals

Mini Contactor with Screw Pressure Plate Terminals CE12(B or C)NC with Screwed-On Auxiliary Contact C320MCF (Front Mounted Auxiliary Contact)

Figure 34-32. Approximate Dimensions in Inches (mm)


Note: Catalog Numbers used are not complete, see Catalog Number Selection, Page 34-60.

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0337]

34-73

Product Family Overview


state-of-the-art technology and the latest in high strength, impact and temperature resistant insulating materials. Eaton is the only manufacturer to offer IEC Starters with two different overload options: Fixed Bimetallic Overload and Interchangeable Heater Overload with Heater Packs. Contactors and Overloads can also be ordered separately or as completely assembled starters with either overload relay option. specier must give attention to the specic load, utilization category and the required electrical life. For a denition of Utilization Categories, see Page 34-99.
Note: AC-3 tests are conducted at rated device currents and AC-4 tests are conducted at six-times rated device currents. All tests have been run at 460V, 60 Hz.

34

Actual application life may vary, depending on environmental conditions and application duty cycle.

IEC AE17KNS0AFE IEC Size K, 50 hp/460V

Application Description
Electrical Life AC-3 and AC-4 Utilization Categories
Life Load Curves The Cutler-Hammer Freedom Series IEC contactors have been designed and manufactured for superior life performance in any worldwide application. All testing has been based on requirements as found in IEC 947-4-1 and conducted by Eaton. When selecting a contactor designed to IEC requirements, the
100,000,000

Contactor Choice

Product Description
Eatons electrical business has been supplying quality Industrial Control products for more than 100 years the Cutler-Hammer Freedom Series line of Contactors and Starters continue in this tradition. The IEC Freedom Series Contactors and Starters feature a compact space-saving design, using

Decide what utilization category the application is and choose the appropriate curve from Figure 34-33 (below). Locate the intersection of the lifeload curve of the appropriate contactor with the operational current (le) of the application, as found on the horizontal axis. Read the estimated contact life along the vertical axis in number of operational cycles.

100,000,000 10,000,000 Operations Operations 10,000,000


Si ze

1,000,000

Size C

Size K

1,000,000
Size A

Size G

100,000
Size A Size B Size C Size D Size F Size G Size H Size J Size K

Size D

Size H

Size B

Size E Size F

100,000

Size J

12 18 25 32 44 60 37 73 1 10 100 Break Amperes IEC AC-3 Load Life Size A K, 480V 60 Hz

10,000

42 72 150 264 414 60 108 222 360 1 100 1000 10 Break Amperes IEC AC-4 Load Life Size A K, 480V 60 Hz

10,000,000

10,000,000

Operations

Operations

1,000,000

1,000,000

100,000
Size L Size M Size N Size P Size R Size S

100,000
Size L Size M Size N Size P Size R Size S

10,000

10,000

85 140 200 105 170 300 1 10 100 Break Amperes IEC AC-3 Load Life Size L S, 480V 60 Hz

438 768 515 900 630 1020

1000

100 Break Amperes IEC AC-4 Load Life Size L S, 480V 60 Hz

10

1000

Figure 34-33. Electrical Life AC-3 and AC-4 Utilization Categories

CA08102001E

For more information visit: www.EatonElectrical.com

34-74

IEC Contactors & Starters Freedom


June 2005

Product Family Overview

Vol. 2, Ref. No. [0338]

Certied Type 2 Coordination


Eatons Cutler-Hammer Freedom Series IEC starters are now UL Certied to achieve IEC 947 Type 2 coordination against 100,000A short circuit fault currents. Any brand of properly selected fuse can be used. Type 2 coordination means that the starter will be suitable for further use following a short circuit fault.

34

AE17 Fixed Heater IEC Starter Size B

ISO 9000 Certication


IEC AE17DNS0AFE IEC Size D, 10 hp/460V

Features
Freedom IEC Features
Freedom IEC contactors and starters are designed to IEC standards and comply with the International Standard IEC 947-4-1. IEC products are a perfect choice when electrical and mechanical application parameters are known. They are typically smaller in size and provide higher ratings in a smaller package. They are available in 22 sizes to match the contactor to the application.

AE17 Fixed Heater IEC Starter Size K

When you turn to Eatons CutlerHammer Products, you turn to quality. The International Standards Organization (ISO) has established a series of standards acknowledged by 91 industrialized nations to bring harmony to the international quest for quality. The ISO Certication process covers 20 quality system elements in design, production and installation that must conform to achieve registration. This commitment to quality will result in increased product reliability and total customer satisfaction.

Series B Heater Pack

Contactor Terminal Markings


Contactors are identied by a two digit number in accordance with International Standards approved by CENELEC (European Committee for Electrotechnical Standardization). This distinctive number is marked on the top nameplate and designates the type and quantity of built-in auxiliary contacts. The rst digit indicates the quantity of NO and the second digit indicates the quantity of NC contacts. Example: 10E indicates a contactor with 1NO and no NC auxiliary contacts factory supplied. In addition, all terminals conform to both CENELEC and NEMA requirements. Auxiliary contact terminals use the rst digit to indicate location and the second digit to indicate status (1-2 means NC and 3-4 means NO). Example: 13-14 indicates the rst auxiliary contact and it is a NO.

Freedom Enhancements
Larger IEC Contactors
There are three additional frame sizes a 220 mm contactor (CE15T and U) rated 250 and 350 hp respectively; a 280 mm contactor rated 400 600 hp at 460V; and a 330 mm contactor rated 900 hp at 460V.

Complies with IEC 947-4-1, EN, CENELEC, UL and CSA standards. 22 Sizes of contactors through 900 hp. DIN rail mountable through 20 hp. Adjustable bimetal overload relays xed or interchangeable heater. Available in Open and NEMA 1, 3R, 4/4X and 12 enclosures.

AE17/57 IEC Fixed Heater Starters, IEC 947-4-1


Completely assembled IEC 947-4-1 starters can be ordered in non-reversing and reversing, open or enclosed. This starter line is composed of CE15 contactors and C316 xed heater overload relays.

Standards and Certications

Standard: Designed to meet or exceed UL, NEMA, IEC, CSA, VDE and BS UL Listed: UL File #E1491, Guide #NLDX Open CSA Certied: CSA File #LR353, Class #321104 Open IEC: Sizes A S, IEC 947-4-1; Sizes T Z, IEC 158 (IEC 947 Pending)

3-Pole 1 L1 A1 A2 3 L2 5 L3

When Supplied 13

A2 T1 2 T2 4 T3 6 14

Figure 34-34. Contact Example

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0339]

34-75

Contactors Non-reversing and Reversing

Contents
Description Product Family Overview Product Description . . . . . . Application Description . . . Features . . . . . . . . . . . . . . . Standards and Certications . . . . . . . . . . Contactors Non-reversing and Reversing Product Description . . . . . . Features . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . Product Selection 3-Pole Contactors . . . . . . Product Selection 2-, 4- and 5-Pole Contactors . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . Auxiliary Contacts . . . . . . . DC Magnet Coils . . . . . . . . Special Modications . . . . . . . Renewal Parts . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . Page 34-73 34-73 34-74 34-74

Product Description
Non-reversing
Contactors are most commonly used to switch motor loads in applications where running over current protection is either not required or is provided separately. Contactors consist of a magnetically actuated switch which can be remotely operated by a pushbutton station or pilot device such as a proximity switch, limit switch, oat switch, auxiliary contacts, etc.

34-75 34-75 34-75 34-76

Reversing
Reversing contactors are used primarily for reversing single- or three-phase motors in applications where running over current protection is either not required or is provided separately. They consist of two contactors mechanically and electrically interlocked to prevent line shorts and energization of both contactors simultaneously.

IP20 nger protection shields available. Contactor and terminal markings conform to CENELEC EN50011. Holding circuit contact(s) supplied as standard: Sizes A N have a NO auxiliary contact block mounted on right hand side (on Sizes A C, contact occupies 4th power pole position no increase in width). Sizes P S have a NO-NC contact block mounted on the left hand side. Sizes T Z have a 2NO-2NC contact block mounted on the top left between arc chutes.

34

Lugs supplied standard on Sizes A S. On Sizes T Z, lugs must be ordered separately.

34-78 34-95 34-100 34-100 34-102 34-107 34-108 34-114

Reversing

Features

EN60947-4-1 IEC 947-4-1 Compliance new International Standard for low voltage switchgear and control devices. Long life twin break, silver cadmium oxide contacts provide excellent conductivity and superior resistance to welding and arc erosion. Designed to 2,000,000 electrical and 20,000,000 mechanical operations at maximum hp ratings through 20 hp at 460V. Adequate for most general duty control applications.

Non-reversing
IEC Size B Cat. No. CE15BNS3AB

IEC Size D Cat. No. CE55DN3AB

UL listed and CSA certied. Highest horsepower rating in a compact, space-saving design, 45 mm frame rated maximum 20 hp at 460V, 65 mm frame rated maximum 50 hp, 90 mm frame rated 100 hp, 180 mm frame rated 200 hp, 220 mm frame rated 350 hp, 280 mm frame rated 600 hp, and 334 mm frame rated 900 hp. 45 mm open contactors, Sizes A F, have DIN rail or universal base mounting, 65 mm open contactors have molded feet for panel mounting, and 90 mm to 334 mm have steel mounting plates (optional on smaller sizes). DIN rail release mechanism conveniently located on line side of contactor.

Highest horsepower rating in a compact, space-saving design, 45 mm frame rated maximum 20 hp, 65 mm frame rated maximum 50 hp and 90 mm frame rated maximum 75 hp at 460V. If larger devices are required, order components. 45 mm open type reversing contactors, Sizes A F, have DIN rail or panel mounting capability. DIN rail release mechanism conveniently located on line side of contactor. A steel mounting plate is optional. 65 mm reversing contactors, Sizes G K and 90 mm Sizes L N are supplied with steel mounting plate as standard. Sizes A K have a wired NC top mounted electrical interlock on each contactor. Sizes L N have one NONC side mounted electrical interlock on each contactor.

Technical Data
Table 34-108. AC-4 (Ie) Plugging and Jogging Service Horsepower Ratings
IEC Size B C D E F G H J K L M N 200V 1 1-1/2 2 3 5 5 7-1/2 7-1/2 10 15 20 25 230V 1 1-1/2 2 3 5 7-1/2 10 10 15 20 25 30 460V 2 3 5 7-1/2 10 15 20 25 30 40 50 60 575V 3 5 7-1/2 10 15 20 25 30 40 40 50 75

Note: For Reversing Contactors, 100 400 hp, refer to Catalog Number CE15 Contactors, Page 34-76 and Mechanical Interlocks, Page 34-105.

CA08102001E

For more information visit: www.EatonElectrical.com

34-76

IEC Contactors & Starters Freedom


June 2005

Contactors Non-reversing and Reversing

Vol. 2, Ref. No. [0340]

Product Selection 3-Pole Contactors


When Ordering Specify

34

Select required contactor by Catalog Number and replace the magnet coil alpha designation in the Catalog Number (_) with the proper Code Sufx from Tables 34-110 and 34112, on Page 34-77. For Sizes A K, the magnet coil alpha designation is the second-tolast digit of the Catalog Number. Example: for a 240V/60 Hz coil, order CE15ANS3BB.

IEC Size E Cat. No. CE15ENS3AB

IEC Size N Cat. No. CE15NN3A

Table 34-109. Type CE15/CE55 IEC Product Selection 3-Pole Contactors


Max. UL AC-3 Amp. Rating 600V AC 7 10 12 18 25 32 37 44 60 73 85 105 140 170 200 300 420 520 550 700 810 1215 IEC 947 Maximum kW Rating Maximum UL Horsepower AC-1 Thermal 3-Phase 1-Phase 3-Phase Current 220V 380V 415/ 500/ 660V 115V 230V 200V 230V 600V 440V 550V 3-Pole Non-reversing 460V 575V Catalog Number Price U.S. $ 3-Pole Reversing Catalog Number Price U.S. $

20 20 20 32 32 32 50 60 75 80 100 135 175 185 220 315 600 760 1000 1000 1100 1350

1.1 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 90 129 160 220 220 270 380

2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 160 220 280 375 375 475 650

2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 160 240 315

4 5.5 7.5 11 15 18.5 22 30 30 37 55 75 90 90 110 160 300 375 500 500 600 840

1.5 2.2 4 5.5 7.5 10 11 15 18.5 22 37 45 45 45 55 75 300 375 500 500 600 840

1/4 1/2 1/2 1 2 2 3 3 5 5 7-1/2 10 10

1/2 1 2 3 3 5 5 7-1/2 10 10 10 10 10

1-1/2 2 3 5 5 7-1/2 7-1/2 10 15 20 25 30 40 50 60 75 125 150 150 200 250 450

1-1/2 2 3 5 7-1/2 10 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 450

3 5 7-1/2 10 15 20 25 30 40 50 60 75 100 125 150 200 250 350 400 500 600 900

5 7-1/2 10 15 20 25 30 40 40 50 75 100 125 125 150 200 250 350 400 500 600 900

CE15ANS3_B CE15BNS3_B CE15CNS3_B CE15DNS3_B CE15ENS3_B CE15FNS3_B CE15GNS3_B CE15HNS3_B CE15JNS3_B CE15KNS3_B CE15LN3_ CE15MN3_ CE15NN3_ CE15PN3_ CE15RN3_ CE15SN3_ CE15TN3_80 CE15UN3_80 CE15VN3_80 CE15WN3_80 CE15XN3_80 CE15ZN3_80

119. 121. 154. 175. 195. 221. 259. 281. 298. 410. 461. 675. 1,065. 1,490. 1,670. 2,260. 2,760. 4,930. 7,260. 8,500.

CE55AN3_B CE55BN3_B CE55CN3_B CE55DN3_B CE55EN3_B CE55FN3_B CE55GN3_B CE55HN3_B CE55JN3_B CE55KN3_B CE55LN3_ CE55MN3_ CE55NN3_

293. 298. 405. 437. 475. 535. 665. 715. 755. 980. 1,470. 1,925. 2,715.

10,700. 22,130.

IEC Sizes A N are supplied with a NO auxiliary contact. On IEC Sizes A C, the 4th power pole position is used as the auxiliary contact and adds no additional width. Open type Sizes A K can be ordered with a top mounted auxiliary contact instead of a side mounted contact. To order, change the 7th digit of the listed Catalog Number from S to T Example: CE15ANT3AB. On open type Sizes A K, if the NO auxiliary contact is not required, . drop the S from the listed Catalog Number. Auxiliary contacts: Sizes P S have 1NO-1NC, Sizes T X have 2NO-2NC, Size Z has 2NO-1NC. Sizes T Z are supplied without lugs order appropriate lug kits from Table 34-111 on Page 34-77. Sizes A K IEC contactors do not include holding circuit contacts. For factory installed NO auxiliary contacts, insert S (side mounted) or T (top mounted) after 6th digit of listed Catalog Number. Example: Change CE55AN3AB to CE55ANS3AB. For T top mounted NC contact blocks are , replaced with NO-NC blocks for S they are replaced with NO-NC side mounted blocks. ,

Technical Data . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . Discount Symbol . . . . . . . . . For more information visit: www.EatonElectrical.com

Pages 34-95 34-99 Pages 34-114 34-121 Pages 34-100 34-107 1CD7 CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0341]

34-77

Contactors Non-reversing and Reversing


Table 34-111. Line/Load Lug Kits IEC Sizes T Z Only
Lugs come standard on all contactors except sizes T Z. If lugs are required, order separately from below. Each kit consists of three line and three load side lugs and hardware. Contactor Size T U VW X Z Cable Range (2) #2/0 600 kcmil (2) #2/0 600 kcmil (2) #3/0 750 kcmil (3) #3/0 750 kcmil (4) #1/0 750 kcmil Catalog Number C325KAL15 C325KAL16 C325KAL17 C325KAL18 C325KAL19 Price U.S. $ 73.00 73.00 86.50 307.00 338.00

Table 34-110. AC Coil Sufxes


Coil Volts and Hertz 120/60 or 110/50 240/60 or 220/50 480/60 or 440/50 600/60 or 550/50 208/60 277/60 208-240/60 240/50 380-415/50 550/50 380/60 24/60, 24/50 24/50 32/50 48/60 48/50 Code Sufx A B C D E H J K L N P T U V W Y

34

IEC Sizes A F only. IEC Sizes A F only. Sizes G V are 24/60 only.

Table 34-112. DC Coil Sufxes


Contactor or Starter Size IEC Volts NCI Interlock C320KGD1 C320KGD1 C320KGD1 C320KGD1 C320KGD2 C320KGD2 C320KGD2 C320KGD2 C320KGD5 C320KGD5 C320KGD5 C320KGD5 C320KGD3 C320KGD3 C320KGD3 C320KGD3 C320KGD3 C320KGD3 C320KGD3 C320KGD3 (2) C320KGD1 (2) C320KGD1 (2) C320KGD1 (2) C320KGD1 (2) C320KGD3 (2) C320KGD3 (2) C320KGD3 (2) C320KGD3 Code Sufx

Non-reversing
AF 12 24 48 120 12 24 48 120 12 24 48 120 12 24 48 120 24 48 120 240 12 24 48 120 12 24 48 120 R1 T1 W1 A1 R4 T4 W4 A4 R4 T4 W4 A4 R1 T1 W1 A1 T1B W1B A1B B1B R1 T1 W1 A1 R1 T1 W1 A1

AF

GK

LN

PS

Reversing
AF

GK

These kits are supplied with a NO/NCI side mounted auxiliary contact in place of the NCI contact. Factory installed DC coils on IEC contactors and starters include a NC top mounted auxiliary contact on each contactor for electrical interlocking.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C CA08102001E For more information visit: www.EatonElectrical.com

34-78

IEC Contactors & Starters Freedom


June 2005

Contactors Non-reversing and Reversing

Vol. 2, Ref. No. [0342]

Product Selection 2-, 4- and 5-Pole Contactors


When Ordering Specify

34

Select required contactor by Catalog Number and replace the magnet coil alpha designation in the Catalog Number (_) with the proper Code Sufx from the adjacent table. For Sizes A K, the magnet coil alpha designation is the second-tolast digit of the Catalog Number. Example: for a 240V/60 Hz coil, order CE15ANS3BB. For DC Magnet Coils, see Accessories, Page 34-102.
Max. UL AC-3 Ampere Rating 600V AC IEC 947 AC-1 Thermal Current 600V Maximum kW Rating 3-Phase 220V 380V 415/ 440V 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 2.2 4 5.5 7.5 11 15 18.5 22 30 37 15 18.5 22 30 37 500/ 550V 4 5.5 7.5 11 15 18.5 22 30 30 37 55 75 90 4 5.5 7.5 11 15 18.5 22 30 30 37 18.5 22 30 30 37

IEC Size G 4-Pole Contactor Cat. No. CE15GN4AB

Table 34-113. Type CE15 IEC Product Selection 2-, 4- and 5-Pole Contactors Non-reversing
Maximum UL Horsepower 1-Phase 660V 115V 230V 3-Phase 200V 230V 460V 575V Catalog Number Price U.S. $

2-Pole
7 10 12 18 25 32 37 44 60 73 85 105 140 20 20 20 32 32 32 50 60 75 80 100 135 175 20 20 20 32 32 32 50 60 75 80 32 50 60 75 80 1.1 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 1.1 1.5 2.2 4 5.5 7.5 11 15 18.5 7.5 11 15 18.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 2.2 4 5.5 7.5 11 15 18.5 22 30 37 15 18.5 22 30 37 1.5 2.2 4 5.5 7.5 10 11 15 18.5 22 37 45 45 1.5 2.2 4 5.5 7.5 10 11 15 18.5 22 10 11 15 18.5 22 1/4 1/2 1/2 1 2 2 3 3 5 5 7-1/2 10 10 1/4 1/2 1/2 1 2 2 3 3 5 5 2 3 3 5 5 1/2 1 2 3 3 5 5 7-1/2 10 10 10 10 10 1/2 1 2 3 3 5 5 7-1/2 10 10 5 5 7-1/2 10 10 1-1/2 2 3 5 5 7-1/2 7-1/2 10 15 20 25 30 40 1-1/2 2 3 5 5 7-1/2 7-1/2 10 15 20 7-1/2 7-1/2 10 15 20 1-1/2 2 3 5 7-1/2 10 10 15 20 25 30 40 50 1-1/2 2 3 5 7-1/2 10 10 15 20 25 10 10 15 20 25 3 5 7-1/2 10 15 20 25 30 40 50 60 75 100 3 5 7-1/2 10 15 20 25 30 40 50 20 25 30 40 50 5 7-1/2 10 15 20 25 30 40 40 50 75 100 125 5 7-1/2 10 15 20 25 30 40 40 50 25 30 40 40 50 CE15ANS2_B CE15BNS2_B CE15CNS2_B CE15DNS2_B CE15ENS2_B CE15FNS2_B CE15GNS2_B CE15HNS2_B CE15JNS2_B CE15KNS2_B CE15LN2_ CE15MN2_ CE15NN2_ CE15AN4_B CE15BN4_B CE15CN4_B CE15GN4_B CE15HN4_B CE15JN4_B CE15GN5_B CE15HN5_B CE15JN5_B 111. 114. 147. 166. 188. 212. 250. 271. 291. 404. 454. 665. * 119. 121. 154. 365. 377. 440. 456. 600. 790.

4-Pole
7 10 12 18 25 32 37 44 60 73

5-Pole
32 37 44 60 73

Sizes A N 2-pole contactors are supplied with a NO auxiliary contact. On Sizes A C, the 4th power pole is used as the auxiliary contact and adds no additional width. Open type Sizes A K can be ordered with a top mounted auxiliary contact instead of a side mounted contact. To order, change the S to a T.

Table 34-114. AC Coil Sufxes


Coil Volts and Hertz 120/60 or 110/50 240/60 or 220/50 480/60 or 440/50 600/60 or 550/50 208/60 277/60 208-240/60 240/50 380-415/50 550/50 Code Sufx A B C D E H J K L N Coil Volts and Hertz 380/60 24/60, 24/50 24/50 32/50 48/60 48/50 Code Sufx P T U V W Y

For DC Magnet Coils, see Accessories, Page 34-102.


*Please contact your local Eaton sales ofce.

IEC Sizes A F only. IEC Sizes A F only. Sizes G V are 24/60 only.

Technical Data . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . Discount Symbol . . . . . . . . .

Pages 34-95 34-99 Pages 34-114 34-121 Pages 34-100 34-107 1CD7 CA08102001E

For more information visit: www.EatonElectrical.com

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0343]

34-79

Starters Fixed Heater

Contents
Description Product Family Overview Product Description . . . . . . Application Description . . . Features . . . . . . . . . . . . . . . Standards and Certications . . . . . . . . . . Fixed Heater Starters Product Description . . . . . . Features . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . Product Selection . . . . . . . . Technical Data . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . Auxiliary Contacts . . . . . . . DC Magnet Coils . . . . . . . . Special Modications . . . . . . . Renewal Parts . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . Page 34-73 34-73 34-74 34-74 34-79 34-79 34-80 34-81 34-95 34-100 34-100 34-102 34-107 34-108 34-114

Features

IEC Size D Cat. No. AE17DNS0AFE

IEC Size C Cat. No. AE57CN0AFE

EN60947-4-1 IEC 947-1 Compliance new International Standard for low voltage switchgear and control devices. UL listed and CSA certied. C316 Bimetallic Ambient Compensated Overload Relays available in three basic sizes covering applications up to 200 hp (150 hp Reversing) reducing number of different contactor/overload relay combinations that have to be stocked. These overload relays feature: Direct heated bimetal elements Class 10. Single-phase and phase unbalance sensitivity. Ambient temperature compensated. Adjustable trip current. Overload trip indication. Contact test lever. Manual/automatic reset. Electrically isolated NO-NC contacts.

34

Product Description
Non-reversing
Eatons Cutler-Hammer Fixed Heater Starters utilize a Class 10 Bimetallic Overload Relay and are available for 3-phase motor applications from fractional horsepower motors up to 900 hp at 480V.

Long life twin break, silver cadmium oxide contacts provide excellent conductivity and superior resistance to welding and arc erosion. Designed to 2,000,000 electrical operations and 20,000,000 mechanical operations through 20 hp at 460V. Adequate for most general duty motor control applications.

Reversing
Three-phase, full voltage magnetic starters are used primarily for reversing of 3-phase squirrel cage motors. They consist of two contactors and a single overload relay assembled together. The contactors are mechanically and electrically interlocked to prevent line shorts and energization of both contactors simultaneously.

CA08102001E

For more information visit: www.EatonElectrical.com

34-80

IEC Contactors & Starters Freedom


June 2005

Starters Fixed Heater

Vol. 2, Ref. No. [0344]

Features (Continued)
Non-reversing

Technical Data
Table 34-115. AC-4 (Ie) Plugging and Jogging Service Horsepower Ratings
IEC Size B C D E F G H J K L M N 200V 1 1-1/2 2 3 5 5 7-1/2 7-1/2 10 15 20 25 230V 1 1-1/2 2 3 5 7-1/2 10 10 15 20 25 30 460V 2 3 5 7-1/2 10 15 20 25 30 40 50 60 575V 3 5 7-1/2 10 15 20 25 30 40 40 50 75

Table 34-116. Wire (75C) Sizes AWG or kcmil IEC Sizes A S, Open
IEC Size A, B, C D, E, F G, H, J, K Wire Size 12 16 Stranded 12 14 Solid, Cu Only 8 16 Stranded, 10 14 Solid, Cu Only 3 14 (Upper) and/or 6 14 (Lower) Stranded or Solid , Cu Only 1/0 14 Cu/Al 1/0 8 Cu/Al 3/0 8 Cu/Al 350 kcmil 6

34

Highest horsepower rating in compact, space-saving designs. 45 mm frame rated maximum 20 hp at 460V, 65 mm frame rated maximum 50 hp, 90 mm frame rated maximum 100 hp and 180 mm frame rated maximum 200 hp. NO side mounted auxiliary contact supplied as standard on Sizes A N. Sizes P, R and S have NO-NC. 45 mm open type starters, Sizes A F, have DIN rail or universal base mounting. A steel mounting plate is optional. Sizes G S supplied with steel mounting plate as standard. Four basic starter frame widths 45 mm, 65 mm, 90 mm and 180 mm simplifying panel layout. 45 mm DIN rail release mechanism conveniently located on line side of starter.

Power Terminals Line

L M N PS

Contactor Control Terminals Cu Only


12 16 AWG Stranded, 12 14 AWG Solid

Maximum horsepower where operation is interrupted more than 5 times per minute, or more than 10 times in a 10 minute period.

Overload Relay Power Terminals Load


Current Range Amperes 0 11.0 11.1 18.0 18.1 25.0 25.1 34.0 34.1 45.0 45.1 61.0 61.1 78.0 78.1 91.0 91.1 106.0 106.1 143.0 143.1 166.0 166.1 193.0 193.1 247.0 247.1 276.0 276.1 328.0 328.1 390.0 Wire Size 16 AWG 14 AWG 12 AWG 10 AWG 8 AWG 6 AWG 4 AWG 3 AWG 2 AWG 1/0 AWG 2/0 AWG 3/0 AWG 250 kcmil 300 kcmil 400 kcmil 500 kcmil

Note: For Reversing Starters 100 400 hp, refer to CE15 Contactors, Pages 34-76 34-78, C316 Overload Relays, Page 34-85 and Mechanical Interlock Kits, Page 34-105.

Reversing

Highest horsepower rating in compact, space-saving designs. 45 mm frame rated maximum 20 hp at 460V, 65 mm frame rated maximum 50 hp at 460V, and 90 mm frame rated a maximum 100 hp at 460V. 65 mm reversing starters, Sizes G K and 90 mm reversing starters Sizes L N are supplied with steel mounting plate as standard. Sizes A K have a wired NC top mounted electrical interlock on each contactor. Sizes L N have one NONC side mounted electrical interlock on each contactor.

Overload Relay Control Terminals (M3.5 No. 1 Pozidrive +/- Screws w/Captive Clamps)
(2) 18 13 AWG Stranded, (2) 18 11 AWG Solid Two compartment box lug. A calibration shift of approximately 5% can be expected using wires of a larger or smaller size than the recommended, especially when connected to maximum rated relays.

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0345]

34-81

Starters Fixed Heater

Product Selection
When Ordering Specify

Select required starter by Catalog Number and replace the magnet coil alpha designation in the Catalog Number (_) with the proper Sufxes from the tables on Page 34-82. First, select the Magnet Coil Sufx and then add the two digit Overload Relay Sufx code. Example: for a Size A starter for 120V/60 Hz and full load current is 2.0A, order AE17ANS0AFH. For DC Magnet Coils, see Accessories, Page 34-102.
Max. UL AC-3 Ampere Rating IEC 947 AC-1 Thermal Current 600V 20 20 20 32 32 32 50 60 75 80 100 135 175 185 220 315 600 760 1000 1000 1100 1350 20 20 20 32 32 32 50 60 75 80 100 135 175 Maximum kW Rating 3-Phase 220V 380V 415/440V 2.2 4 5.5 7.5 11 15 18.5 22 11 30 15 18.5 37 45 22 55 30 75 37 90 45 110 55 160 90 220 129 280 160 375 220 375 220 475 270 650 380 1.1 1.5 2.2 4 5.5 7.5 1.1 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 160 240 315 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75

34

IEC Size K Cat. No. AE17KNS0AKB

IEC Size E Cat. No. AE57EN0AFM

Table 34-117. Type AE17/AE57 Starters Fixed Heater Overload Relay 3-Pole
Maximum UL Horsepower 1-Phase 3-Phase 660V 115V 230V 208V 240V 1.5 2.2 4 5.5 7.5 10 11 15 18.5 22 37 45 45 45 55 75 300 375 500 500 600 840 1/4 1/2 1/2 1 2 2 3 3 5 5 7-1/2 10 10 1/2 1 2 3 3 5 5 7-1/2 10 10 10 10 10 1/2 1 2 3 3 5 5 7-1/2 10 10 10 10 10 1-1/2 2 3 5 5 7-1/2 7-1/2 10 15 20 25 30 40 50 60 75 125 150 150 200 250 450 1-1/2 2 3 5 5 7-1/2 7-1/2 10 15 20 25 30 40 1-1/2 2 3 5 7-1/2 10 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 450 Catalog Number 480V 3 5 7-1/2 10 15 20 25 30 40 50 60 75 100 125 150 200 250 350 400 500 600 900 600V 5 7-1/2 10 15 20 25 30 40 40 50 75 100 125 125 150 200 250 350 400 500 600 900 AE17ANS0_ AE17BNS0_ AE17CNS0_ AE17DNS0_ AE17ENS0_ AE17FNS0_ AE17GNS0_ AE17HNS0_ AE17JNS0_ AE17KNS0_ AE17LN0_ AE17MN0_ AE17NN0_ AE17PN0_ AE17RN0_ AE17SN0_ AE17TN0_ AE17UN0_ AE17VN0_ AE17WN0_ AE17XN0_ AE17ZN0_ AE57AN0_ AE57BN0_ AE57CN0_ AE57DN0_ AE57EN0_ AE57FN0_ AE57GN0_ AE57HN0_ AE57JN0_ AE57KN0_ AE57LN0_ AE57MN0_ AE57NN0_ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Price U.S. $

500/550V 4 5.5 7.5 11 15 18.5 22 30 30 37 55 75 90 90 110 160 300 375 500 500 600 4 5.5 7.5 11 15 18.5 22 30 30 37 55 75 90

Non-reversing
7 10 12 18 25 32 37 44 60 73 85 105 140 170 200 300 420 550 630 700 860 1215

Reversing
7 10 12 18 25 32 37 44 60 73 85 105 140 1/4 1.5 1/2 2.2 1/2 4 5.5 1 7.5 2 2 10 3 11 3 15 18.5 5 5 22 7-1/2 37 10 45 10 45 5 3 1-1/2 7-1/2 5 2 10 7-1/2 3 15 10 5 20 15 7-1/2 25 20 10 30 25 10 40 30 15 40 40 20 50 50 25 75 60 30 100 75 40 125 100 50

Underscore (_) indicates Magnet Coil Sufx and Overload Relay Sufx code. IEC Sizes A K are supplied with a NO auxiliary contact. On IEC Sizes A C, the 4th power pole position is used as the auxiliary contact and adds no additional width. Open type sizes A K can be ordered with a top mounted auxiliary contact instead of a side mounted contact. To order, change the 7th digit of the listed Catalog Number from S to T Example: AE17ANT0AFC. On open type sizes A K, if the NO auxiliary contact is not required, . drop the S from the listed Catalog Number. Example: AE17AN0AFC. IEC Sizes L N open are supplied with a NO side mounted auxiliary contact. On IEC Sizes P S, a NO-NC side mounted is standard. Sizes T X have 2NO-2NC, Size Z has 2NO-1NC. Starters include xed heater overload relay. AE17 is only an ordering number. Assembled starter consists of individually marked CE15 contactor and C316 overload relay. Sizes A K IEC starters do not include holding circuit contacts. For factory installed NO auxiliary contacts, insert S (side mounted) or T (top mounted) after 6th digit of listed Catalog Number. Example: Change AE57AN0AFC to AE57ANS0AFC. For T top mounted NC contact blocks are , replaced with NO-NC blocks for S they are replaced with NO-NC side mounted blocks. , *Please contact your local Eaton sales ofce.

Dimensions. . . . . . . . . . . . . Pages 34-114 34-121 Accessories . . . . . . . . . . . . Pages 34-100 34-107 Discount Symbol . . . . . . . . 1CD7 CA08102001E For more information visit: www.EatonElectrical.com

34-82

IEC Contactors & Starters Freedom


June 2005

Starters Fixed Heater


Table 34-118. Maximum Horsepower Rating of Starters for 380V 50 Hz Application
IEC Size hp A 3 B 5 C 5 D E F G 20 H 25 J 30 K 40 L 50 M 60 N 75 P 100 R 125 S 150 10 10 15

Vol. 2, Ref. No. [0346]

Table 34-119. AC Coil Sufxes


Coil Volts and Hertz Code Sufx A B C D E H J K L N T U V W Y

Table 34-120. Fixed Heater Overload Relay Sufx Codes


Motor Full Load Amperes .25 .40 .40 .63 .63 1.0 1.0 1.4 1.3 1.8 1.7 2.4 2.2 3.1 2.8 4.0 18 25 22 32 29 42 65 90 80 100 100 135 60 84 78 108 102 144 120 168 156 216 204 288 200 280 260 360 340 480 300 420 390 540 510 720 Sufx Letter Motor Full Load Amperes 3.5 5.0 4.5 6.5 6.0 8.5 7.5 11 10 14 13 19 18 24 24 32 36 52 45 63 60 80 110 150 130 175 132 186 168 240 210 300 264 372 336 480 420 600 440 620 560 800 700 1000 660 930 840 1200 1050 1500 Sufx Letter

34

120/60 or 110/50 240/60 or 220/50 480/60 or 440/50 600/60 or 550/50 208/60 277/60 208-240/60 240/50 380-415/50 550/50 24/60, 24/50 24/50 32/50 48/60 48/50

Sizes AE17A AE17F


FC FD FE FF FG FH FJ FK KA KB KC PA PB PC FF FG FH FF FG FH FF FG FH FH FG FH FL FM FN FP FQ FR FS FT KD KE KF PD PE FJ FK FL FJ FK FL FJ FK FL FJ FK FL

Sizes AE17G AE17K

IEC Sizes A F only. IEC Sizes A F only. Sizes G V are 24/60 only.

Sizes AE17L AE17N

For DC Magnet Coils, see Accessories, Page 34-102.

Sizes AE17P AE17S with 300/5 CT

Sizes AE17T AE17V with 600/5 CT

Sizes AE17W AE17X with 1000/5 CT

Size AE17Z with 1500/5 CT

Overload relay range can not exceed contactor ampere rating.

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0347]

34-83

Relays Fixed Heater Overload

Contents
Description Product Family Overview Product Description . . . . . . Application Description . . . Features . . . . . . . . . . . . . . . Standards and Certications . . . . . . . . . . Fixed Heater Overload Relays Product Description . . . . . . Features . . . . . . . . . . . . . . . Standards and Certications . . . . . . . . . . Technical Data . . . . . . . . . . Accessories. . . . . . . . . . . . . Trip Curves . . . . . . . . . . . . . Dimensions. . . . . . . . . . . . . Product Selection . . . . . . . . Technical Data . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . Auxiliary Contacts . . . . . . . DC Magnet Coils . . . . . . . . Special Modications . . . . . . . Renewal Parts . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . Page 34-73 34-73 34-74 34-74

Features

Standards and Certications


34-83 34-83 34-83 34-83 34-84 34-84 34-85 34-85 34-95 34-100 34-100 34-102 34-107 34-108 34-114

EN60947-4-1 IEC 947-4-1 Compliance the International Standard for low voltage switchgear and control devices. Direct heated bimetal elements. Class 10 trip characteristics through 200 amperes and Class 30 on 400 and 850 ampere relays. Single-phase and phase unbalance sensitive. Ambient temperature compensated. Adjustable trip current, overload trip indication. NO-NC electrically isolated contacts, contact test lever. Manual/automatic reset. DIN rail and panel mounting adapter.

UL listed File E130332 CSA certied File LR15332M94

Technical Data
Table 34-121. Contact Ratings (35% Power Factor)
Rating Insulation Voltage 660V AC (IEC) 600V AC (UL & CSA) Thermal Rating 10A Volts 120 230 480 600 Make 30.0A 15.0A 7.5A 6.0A Break 3.0A 1.5A .75A .6A

34

Table 34-122. Power Terminal Torque in lb-in


Catalog Number C306TB1/C316F C316TB1/C316K Line 20 21.2 Load 12 40 (14 8 AWG) 45 (6 4 AWG) 50 (3 AWG)

Table 34-123. Overload Relay UL/CSA Contact Ratings Control Circuit


AC Volts 120V 30 3 5 15 1.5 2.5 240V 15 1.5 5 7.5 .75 2.5 480V 7.5 .75 5 3.375 .375 2.5 600V 6 .6 5 3 .3 2.5

NC Contact B600
Make and Break Amps Break Amps Continuous Amps

NO Contact C600
Make and Break Amps Break Amps Continuous Amps

DC ratings cover Freedom Series coils only.

Table 34-124. Overload Congurations C316 Overload


Size Overload F Contactor AF Connecting links are provided for close coupling. For independent mounting, an accessory kit C306TB1 is required. Connecting links are provided for close coupling. For independent mounting, an accessory kit C316TB1 is required which replaces the connectors and repositions the calibration marks with an additional label. Connecting links are provided for close coupling with a calibration label to reposition the marks. Mounting Arrangements

GK

Frame Size F Overload Relay Cat. No. C316FNA3

Product Description
Eatons Cutler-Hammer Integral Overload Relays are for use with Freedom Series contactors. They are designed and manufactured to meet IEC (International Electrotechnical Commission) recommendations and other international standards necessary for acceptance in many countries around the world.

LN

CA08102001E

For more information visit: www.EatonElectrical.com

34-84

IEC Contactors & Starters Freedom


June 2005

Relays Fixed Heater Overload


Table 34-125. STOP/RESET Push Functions C316 Overload
Stroke of Blue Push = .18 inch(4.6 mm) O/R posn. NC closed @ D = <.02 inch(.5 mm) O/R posn. NC open @ D = >.06 inch (1.5 mm) O/R & R posn. OL must reset @ D = <.14 inch (3.6 mm)

Vol. 2, Ref. No. [0348]

Trip Curves
1.05 1.125 1.2 10000 5000

Button pressed on R position RESET only.


R O R

Manual Mode

Auto Mode

Trip Time (Seconds)

34

Overload Relay Tripped Condition

1000 500

120

100 50

RESET 95 96 (NC) (Open) 97 98 (NO) (Closed) Button pressed on O/R position. STOP/RESET
R O R

NO FUNCTION

Closes when button is pressed. Opens when button is pressed.

10 5 2 1 0.70.8 1

3 Phase Cold

3 Phase Hot
1.5 2 3 4 5 6 8 10 7.2 20

Multiples of Full Load Current C316FNA3 RESET NO FUNCTION


1.05 1.125 1.2 10000 5000

95 96 (NC) (Open) 97 98 (NO) (Closed)

Closes when button is released. Opens when button is pressed. Manual

Relay in Operational Condition


Button pressed on R position. RESET only.
R O R

Auto

Trip Time (Seconds)

1000 500

120

100 50

NO FUNCTION 95 96 (NC) 97 98 (NO) Button pressed on O/R position. STOP/RESET


R O R

Remains closed. Remains open.

10 5 2 1 0.70.8 1 1.5 2

3 Phase Cold

3 Phase Hot
3 4 5 6 8 10 7.2 20

Multiples of Full Load Current C316KNA3 95 96 (NC) Opens when button is pressed. Closes when button is released. NO FUNCTION Opens when button is pressed. Closes when button is released.

Figure 34-35. Trip Curves

97 98 (NO)

Accessories
Table 34-126. Accessories
Description DIN Rail and Panel Mounting Adapters for separate mounting of overload relays Application Frame Size C316F Frame Size C316K Catalog Number C306TB1 C316TB1 Price U.S. $ 13.00 39.75

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD7 For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0349]

34-85

Relays Fixed Heater Overload

Dimensions
Table 34-127. Approximate Dimensions and Shipping Weights
Frame Dimensions in Inches (mm) Size Wide High Deep Mounting A B C D E F K P 1.71 (43.4) 2.13 (54.1) 2.62 (66.5) 3.70 (94.0) 3.66 (93.0) Ship. Wt. Lbs. (kg) .37 (.17) .71 (.32)
1.31 (33.2) 1.72 (43.6)

.20 (5)

3.98 (101)

.18 (4.5)

4.17 (106)

2.01 (51) .36 (9.2) (4) 3.74 (95) 35 mm DIN Rail

C306TB1

F Frame C316F

34

4.41 (112.0)

4.09 5.51 4.88 2.65 1.46 2.01 (103.9) (140.0) (124.0) (67.3) (37.1) (.91)

3.74 (95) .20 (5.2) C316F and C306TB1

C
2.36 (60) .55 C L (14) 2.05 (52) 1.91 (48.5) C L 2.95 (75) K Frame C316K 5.03 (127.7) C316K and C306TB1 .18 (4.5) Push (2) M4 Fixings

4.41 (112) C316TB1

1.97 (50) Independent Overload Relay

Frame Sizes F and K D C


3.86 (98)

Figure 34-37. Stand-Alone Overload Relays Approximate Dimensions in Inches (mm)


A Frame Size P

Figure 34-36. Approximate Dimensions

Product Selection
Freedom Series Integral Overload Relays
Table 34-128. Bimetal Class 10 IEC Sizes A F
Trip Class Motor FLA Manual/Automatic Reset NO-NC Electrically Separated Catalog Number Price U.S. $ 77.00 77.00 77.00 77.00 77.00 77.00 77.00 77.00 77.00 77.00 79.50 79.50 79.50 79.50 86.50 92.50 10 18.0 25.0 22.0 32.0 29.0 42.0 36.0 52.0 45.0 63.0 60.0 80.0 65 90 80 100 100 135 110 150 130 175 150 200

Table 34-129. Bimetal Class 10 IEC Sizes G K and IEC Sizes L S


Trip Class Motor FLA Manual/Automatic Reset NO-NC Electrically Separated Catalog Number Price U.S. $ 119.00 119.00 126.00 138.00 138.00 163.00 243.00 393.00 393.00 393.00 393.00 393.00

For IEC Contactor Sizes A F


10 .25 .40 .40 .63 .63 1.00 1.00 1.40 1.30 1.80 1.70 2.40 2.20 3.10 2.80 4.00 3.50 5.00 4.50 6.50 6.00 8.50 7.50 11.0 10.0 14.0 13.0 19.0 18.0 24.0 24.0 32.0 C316FNA3C C316FNA3D C316FNA3E C316FNA3F C316FNA3G C316FNA3H C316FNA3J C316FNA3K C316FNA3L C316FNA3M C316FNA3N C316FNA3P C316FNA3Q C316FNA3R C316FNA3S C316FNA3T

For IEC Contactor Sizes G K


C316KNA3A C316KNA3B C316KNA3C C316KNA3D C316KNA3E C316KNA3F C316PNA3A C316PNA3B C316PNA3C C316PNA3D C316PNA3E C316PNA3F

Frame Size K Overload Relay Cat. No. C316KNA3

For IEC Contactor Sizes L N


10

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD7 CA08102001E For more information visit: www.EatonElectrical.com

34-86

IEC Contactors & Starters Freedom


June 2005

Starters Interchangeable Heater

Vol. 2, Ref. No. [0350]

Contents
Description Product Family Overview Product Description . . . . . . . Application Description. . . . Features . . . . . . . . . . . . . . . . Standards and Certications . . . . . . . . . . . Interchangeable Heater Starters Product Description . . . . . . . Features . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . Product Selection . . . . . . . . Technical Data. . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . Auxiliary Contacts . . . . . . . . DC Magnet Coils . . . . . . . . . Special Modications. . . . . . . . Renewal Parts . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . Page 34-73 34-73 34-74 34-74

Features

34

34-86 34-86 34-87 34-87 34-95 34-100 34-100 34-102 34-107 34-108 34-114

EN60947-4-1 IEC 947-4-1 Compliance International Standard for low voltage switchgear and control devices. UL listed and CSA certied. Bimetallic Ambient Compensated Overload Relays available in three basic sizes covering applications up to 200 hp (100 hp Reversing) reducing number of different contactor/overload relay combinations that have to be stocked. These overload relays feature: Selectable Manual or Automatic Reset operation. Interchangeable Heater Packs adjustable 24% to match motor FLA and calibrated for 1.0 and 1.15 service factors. Heater packs for smaller overload relay will mount in larger overload relay useful in derating applications such as jogging. Meets UL508 Single-Phasing requirements, Class 20 or Class 10 trip time. Overload trip indication. Electrically isolated NO-NC contacts (pull RESET button to test).

One NO right-side mounted auxiliary contact supplied as standard on Sizes A N (on Sizes A C, contact occupies 4th power pole no increase in width). Sizes P S have NO-NC. 45 mm open type starters, sizes A F, have DIN rail or universal base mounting. DIN rail release mechanism conveniently located on line side of starter. A steel mounting plate is optional. 65 mm starters, sizes G K; 90 mm starters, sizes L N; and P S 180 mm supplied with steel mounting plate as standard. Four basic starter frame widths 45 mm, 65 mm, 90 mm and 180 mm simplifying panel layout.

Reversing

IEC Size D Cat. No. AE16DN0BC

Long life twin break, silver cadmium oxide contacts provide excellent conductivity and superior resistance to welding and arc erosion. Designed to 2,000,000 electrical and 20,000,000 mechanical operations through 20 hp at 460V. Adequate for most general duty motor control applications.

Product Description
Non-reversing
IEC Freedom Series Starters utilize an Interchangeable Heater Pack Overload Relay which allows increased exibility. Starters are available to cover 3-phase motors with fractional horsepower ratings up to 900 hp at 480V.

Non-reversing

Reversing
Three-phase, full voltage magnetic starters are used primarily for reversing of 3-phase squirrel cage motors. They consist of two contactors and a single overload relay assembled together. The contactors are mechanically and electrically interlocked to prevent line shorts and energization of both contactors simultaneously.

Highest horsepower rating in compact, space-saving designs, 45 mm frame rated maximum 20 hp at 460V, 65 mm frame rated maximum 50 hp, 90 mm frame rated maximum 100 hp, and 180 mm rated maximum 200 hp. IP20 nger protection shields available. Contactor and terminal markings conform to CENELEC EN50011.

Highest horsepower rating in compact, space-saving designs. 45 mm frame rated maximum 20 hp at 460V, 65 mm frame rated maximum 50 hp, and 90 mm frame rated maximum 100 hp. 45 mm open type reversing starters, Sizes A F, have DIN rail or universal base mounting. DIN rail release mechanisms conveniently located on line side of starters. A steel mounting plate is optional. 65 mm reversing starters, Sizes G K, and 90 mm reversing starters, Sizes L N, are supplied with steel mounting plate as standard. Sizes A K have a wired NC top mounted electrical interlock on each contactor. Sizes L N have one NONC side mounted electrical interlock on each contactor. A full time of snap-on accessories top and side mounted auxiliary contacts, solid-state and pneumatic timers, etc. Straight-through wiring line lugs at top, load lugs at bottom. Horizontal of vertical mounting on upright panel for application freedom. Screw type power terminals have captive, backed-out self-lifting pressure plates with screws reducing wiring time.

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0351]

34-87

Starters Interchangeable Heater


Table 34-131. Wire (75C) Sizes AWG or kcmil Open
IEC Sizes A S IEC Size Cu Only 12 16 Stranded 12 14 Solid 8 16 Stranded, 10 14 Solid 3 14 (Upper) and/or 6 14 (Lower) Stranded or Solid Wire Size 1/0 14 Cu/Al 1/0 8 Cu/Al 3/0 8 Cu/Al 350 mcm 6 Cu/Al IEC Sizes A S IEC Size Cu Only

Technical Data
Table 34-130. AC-4 (Ie) Plugging and Jogging Service Horsepower Ratings
IEC Size B C D E F G H J K L M N 200V 1 1-1/2 2 3 5 5 7-1/2 7-1/2 10 15 20 25 230V 1 1-1/2 2 3 5 7-1/2 10 10 15 20 25 30 460V 2 3 5 7-1/2 10 15 20 25 30 40 50 60 575V 3 5 7-1/2 10 15 20 25 30 40 40 50 75

Power Terminals Line


A, B, C D, E, F G, H, J, K

Power Terminals Load


Cat. No. C306DN3B C306GN3B Terminal Wire Size 32A 14 6 AWG 75A 14 2 AWG

Control Terminals Cu Only


12 16 AWG Stranded, 12 14 AWG Solid Two compartment box lug.

34

Power Terminals Line and Load


IEC Size L M N P, R & S

Maximum horsepower where operation is interrupted more than 5 times per minute, or more than 10 times in a 10 minute period.

Product Selection
When Ordering Specify

Select required starter by Catalog Number and replace the magnet coil alpha designation in the Catalog Number (_) with the proper Code Sufx from Table 34-135 on Page 34-88.
IEC 947 AC-1 Thermal Current 600V 20 20 20 32 32 32 50 60 75 80 100 135 175 185 220 315 600 760 1000 1000 1100 1350

Example: for a Size B starter with a 480V/60 Hz coil, order AE16BNS0CC. For DC Magnet Coils, see Accessories, Page 34-102.

Table 34-132. Type AE16/AE56 Starters Interchangeable Heater Overload Relay 3-Pole Non-reversing
Max. UL AC-3 Ampere Rating Maximum kW Rating 3-Phase 220V 1.1 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 90 129 160 220 220 270 380 380V 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 160 220 280 375 375 475 650 415/ 440V 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 160 240 315 500/ 550V 4 5.5 7.5 11 15 18.5 22 30 30 37 55 75 90 90 110 160 300 375 500 500 600 840 660V 1.5 2.2 4 5.5 7.5 10 11 15 18.5 22 37 45 45 45 55 75 300 375 500 500 600 840 Maximum UL Horsepower 1-Phase 115V 1/4 1/2 1/2 1 2 2 3 3 5 5 7-1/2 10 10 230V 1/2 1 2 3 3 5 5 7-1/2 10 10 10 10 10 3-Phase 208V 1-1/2 2 3 5 5 7-1/2 7-1/2 10 15 20 25 30 40 50 60 75 125 150 150 200 250 450 240V 1-1/2 2 3 5 7-1/2 10 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 450 480V 3 5 7-1/2 10 15 20 25 30 40 50 60 75 100 125 150 200 250 350 400 500 600 900 600V 5 7-1/2 10 15 20 25 30 40 40 50 75 100 125 125 150 200 250 350 400 500 600 900 AE16ANS0_C AE16BNS0_C AE16CNS0_C AE16DNS0_C AE16ENS0_C AE16FNS0_C AE16GNS0_B AE16HNS0_B AE16JNS0_B AE16KNS0_B AE16LN0_ AE16MN0_ AE16NN0_ AE16PN0_ AE16RN0_ AE16SN0_ AE16TN0_ AE16UN0_ AE16VN0_ AE16WN0_ AE16XN0_ AE16ZN0_ 209. 212. 244. 267. 287. 313. 448. 469. 488. 610. 775. 970. 1,445. 1,980. 2,170. 2,895. 4,090. 6,240. 8,630. 9,870. * * Catalog Number Price U.S. $

7 10 12 18 25 32 37 44 60 73 85 105 140 170 200 300 450 550 630 700 860 1215

IEC Sizes A N, open are supplied with a NO auxiliary contact. On IEC Sizes A C, the 4th power pole position is used as the auxiliary contact and adds no additional width. Open type Sizes A K can be ordered with a top mounted auxiliary contact instead of a side mounted contact. To order, change the 7th digit of the listed Catalog Number from S to T Example: AE16ANT0AC. On open type Sizes A K, if the NO auxiliary contact is not . required, drop the S from the listed Catalog Number. Example: AE16AN0AC. On IEC Sizes P S, a NO-NC side mounted is standard. Sizes T X have 2NO-2NC, Size Z has 2NO-1NC. *Please contact your local Eaton sales ofce.

Dimensions. . . . . . . . . . . . . . Pages 34-114 34-121 Accessories . . . . . . . . . . . . . Pages 34-100 34-107 Discount Symbol . . . . . . . . . 1CD7 CA08102001E For more information visit: www.EatonElectrical.com

34-88

IEC Contactors & Starters Freedom


June 2005

Starters Interchangeable Heater When Ordering Specify

Vol. 2, Ref. No. [0352]

34

Select required starter by Catalog Number and replace the magnet coil alpha designation in the Catalog Number (_) with the proper Code Sufx from Table 34-135 below. Example: for a Size B starter with a 480V/60 Hz coil, order AE16BNS0CC. For DC Magnet Coils, see Accessories, Page 34-102.
IEC Size F Cat. No. AE56DN0BC IEC Size G Cat. No. AE56GN0BB

Table 34-133. Type AE16/AE56 Starters Interchangeable Heater Overload Relay 3-Pole Reversing
Max. UL AC-3 Ampere Rating IEC 947 AC-1 Thermal Current 600V 20 20 20 32 32 32 50 60 75 80 100 135 175 Maximum kW Rating 3-Phase 220V 1.1 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 380V 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 415/ 440V 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 500/ 550V 4 5.5 7.5 11 15 18.5 22 30 30 37 55 75 90 660V 1.5 2.2 4 5.5 7.5 10 11 15 18.5 22 37 45 45 Maximum UL Horsepower 1-Phase 115V 1/4 1/2 1/2 1 2 2 3 3 5 5 7-1/2 10 10 230V 1/2 1 2 3 3 5 5 7-1/2 10 10 10 10 10 3-Phase 208V 1-1/2 2 3 5 5 7-1/2 7-1/2 10 15 20 25 30 40 240V 1-1/2 2 3 5 7-1/2 10 10 15 20 25 30 40 50 480V 3 5 7-1/2 10 15 20 25 30 40 50 60 75 100 600V 5 7-1/2 10 15 20 25 30 40 40 50 75 100 125 AE56AN0_C AE56BN0_C AE56CN0_C AE56DN0_C AE56EN0_C AE56FN0_C AE56GN0_B AE56HN0_B AE56JN0_B AE56KN0_B AE56LN0_ AE56MN0_ AE56NN0_ 443. 449. 530. 585. 640. 715. 970. 1,010. 1,050. 1,335. 1,605. 2,080. 3,130. Catalog Number Price U.S. $

7 10 12 18 25 32 37 44 60 73 85 105 140

Sizes A K IEC starters do not include holding circuit contacts. For factory installed NO auxiliary contacts, insert S (side mounted) or T (top mounted) after 6th digit of listed Catalog Number. Example: Change AE56AN0AC to AE56ANS0AC. For T top mounted NC contact blocks are , replaced with NO-NC blocks for S they are replaced with NO-NC side mounted blocks. ,

Table 34-134. Maximum Horsepower Rating of Starters for 380V 50 Hz Application


IEC Size hp IEC Size hp A 3 J B 5 K C D E F 15 P G 20 R H 25 S 5 10 10 L M N

Table 34-135. AC Coil Sufxes


Coil Volts and Hertz 120/60 or 110/50 240/60 or 220/50 480/60 or 440/50 600/60 or 550/50 208/60 277/60 208-240/60 240/50 380-415/50 550/50 24/60, 24/50 24/50 32/50 48/60 48/50 Code Sufx A B C D E H J K L N T U V W Y

For DC Magnet Coils, see Accessories on Page 34-102.

30 40 50 60 75 100 125 150

IEC Sizes A F only. IEC Sizes A F only. Sizes G V are 24/60 only.

Dimensions . . . . . . . . . . . . . . Pages 34-114 34-121 Accessories . . . . . . . . . . . . . Pages 34-100 34-107 Discount Symbol . . . . . . . . . 1CD7 For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0353]

34-89

Relays Interchangeable Heater Overload

Contents
Description Product Family Overview Product Description . . . . . . Application Description . . . Features . . . . . . . . . . . . . . . Standards and Certications . . . . . . . . . . Interchangeable Heater Overload Relays Product Description . . . . . . Features . . . . . . . . . . . . . . . Standards and Certications . . . . . . . . . . Operation . . . . . . . . . . . . . . Technical Information . . . . Trip Curves . . . . . . . . . . . . . Technical Data . . . . . . . . . . Factory Modications . . . . Accessories. . . . . . . . . . . . . Replacement Parts . . . . . . . Dimensions. . . . . . . . . . . . . Product Selection . . . . . . . Heater Pack Selection . . . . Technical Data . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . Auxiliary Contacts . . . . . . . DC Magnet Coils . . . . . . . . Special Modications . . . . . . . Renewal Parts . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . Page 34-73 34-73 34-74 34-74

Features

34-89 34-89 34-89 34-89 34-90 34-90 34-90 34-91 34-91 34-92 34-92 34-93 34-93 34-95 34-100 34-100 34-102 34-107 34-108 34-114

Selectable manual or automatic reset operation. Interchangeable heater packs adjustable 24% to match motor FLA and calibrated for use with 1.0 and 1.15 service factor motors. Heater packs for 32 ampere overload relay will mount in 75 ampere overload relay useful in derating applications such as jogging. Class 10 or 20 heater packs. Load lugs built into relay base. Bimetallic, ambient compensated operated. Trip free mechanism. Electrically isolated NO-NC contacts (pull RESET button to test). Overload trip indication. Shrouded or ngerproof terminals to reduce possibility of electrical shock. Meets UL508 single-phasing requirements.

For motors having a 1.0 service factor, or to meet IEC 947 requirements, rotate the FLA dial one-half position counterclockwise (CCW).

34
M Example of setting for manual reset.

Figure 34-39. Manual/Automatic Reset The overload relay is factory set at M for manual reset operation. For automatic reset operation, turn the reset adjustment dial to the A position as shown in the illustration. Automatic reset is not intended for two-wire control devices.

Test for Trip Indication


To test overload relay for trip indication when in manual reset, pull out the blue RESET button. An orange ag will appear indicating that the device has tripped. Push RESET button in to reset. Warning To provide continued protection against re or shock hazard, the complete relay must be replaced if burnout of the heater element occurs.

Standards and Certications


UL listed CSA certied NEMA compliance and EN60947-4-1 IEC 947-4-1 and (CE) Mark

Operation
C306 Overload Relay Setting
1.0 1.15 Service Service Factor Factor B A C D

Example of 12.0 FLA setting for heater pack number H2011B showing position for 1.0 or 1.15 service factor motors.

Figure 34-38. FLA Dial Adjustment


32 Ampere Overload Cat. No. C306DN3B

Product Description
C306 Overload Relays are designed for use with CE or CN non-reversing and reversing contactors. Four sizes are available for overload protection up to 144 amperes.

For motors having a 1.15 service factory, rotate the FLA adjustment dial to correspond to the motors FLA rating. Estimate the dial position when the motor FLA falls between two letter values as shown in the example.

CA08102001E

For more information visit: www.EatonElectrical.com

34-90

IEC Contactors & Starters Freedom


June 2005

Relays Interchangeable Heater Overload

Vol. 2, Ref. No. [0354]

Technical Information
General
Overload relays are provided to protect motors, motor control apparatus and motor-branch circuit conductors against excessive heating due to motor overloads and failure to start. This denition does not include: 1) motor circuits over 600 volts, 2) short circuits, 3) ground faults and 4) re pump control. (NEC Art. 430-31)

Trip Curves
10,000 5000 4000 3000 2000 1000 500 400 300 200 Trip Time (Seconds) 100 50 40 30 20 10 5 4 3 2 1 0 2 4 6 8 Multiples of Current Setting 10 From Cold Start 10,000 5000 4000 3000 2000 1000 500 400 300 200 Trip Time (Seconds) 100 50 40 30 20 10 5 4 3 2 1 0 2 4 6 8 Multiples of Current Setting 10 From Cold Start

34

From Hot Start

From Hot Start

Time Current Characteristics


The time-current characteristics of an overload relay is an expression of performance which denes its operating time at various multiples of its current setting. Tests are run at Underwriters Laboratory (UL) in accordance with NEMA Standards and the NEC.

Class 10 Overload Relay 25C Open Rating

Class 20 Overload Relay 25C Open Rating

Figure 34-40. Class 10 and Class 20 Trip Curves

UL requires

Technical Data
Table 34-136. Wire (75C) Sizes AWG or kcmil NEMA Sizes 00 2, IEC A K Open and Enclosed
IEC Size NEMA Size 00 0 1 2 Cu Only 12 16 Stranded, 12 14 Solid 8 16 Stranded, 10 14 Solid 8 14 Stranded or Solid 3 14 (Upper) and/or 6 14 (Lower) Stranded or Solid Wire Size 14 6 AWG 14 2 AWG

When tested at 100 percent of its current rating, the overload relay shall trip ultimately. When tested at 200 percent of its current rating, the overload relay shall trip in not more than 8 minutes. When tested at 600 percent of its current rating, the overload relay shall trip in not more than 10 or 20 seconds, depending on the Class of the relay. Current Rating is dened as the minimum current at which the relay will trip. Per NEC, an overload must ultimately trip at 125% of FLA current (heater) setting for a 1.15 service factor motor and 115% FLA for a 1.0 service factor motor. Current Setting is dened as the FLA (Full Load Amperes) of the motor and thus the overload heater pack setting. Example: 600% of current rating is dened as 750% (600 x 1.25) of FLA current (heater) setting for a 1.15 service factor motor. A 10 ampere heater setting must trip in 20 seconds or less at 75 amperes motor current for a Class 20 relay.

Power Terminals Line


A, B, C D, E, F G, H, J, K

Power Terminals Load Cu Only (Stranded or Solid)


Catalog Number C306DN3B C306GN3B Terminal 32A 75A

Control Terminals Cu Only


12 16 AWG Stranded, 12 14 AWG Solid Two compartment box lug. Minimum per NEC. Maximum wire size: Sizes 00 0 to 8 AWG and Sizes 1 2 to 2 AWG.

Table 34-137. Wire (75C) Sizes AWG or kcmil NEMA Sizes 3 8, IEC L N Open and Enclosed
IEC Size NEMA Size 3 4 5 67 8 Wire Size 1/0 14 Cu/Al 1/0 8 Cu/Al 3/0 8 Cu/Al Open 3/0 8 Cu Enclosed 250 kcmil 6 Cu/Al 750 kcmil 2 or (2) 250 kcmil 3/0 Cu/Al (2) 750 kcmil 3/0 Cu/Al (2) 750 kcmil 1/0 Cu/Al

Power Terminals Line


L M N

Control Terminals Cu Only


12 16 AWG Stranded, 12 14 AWG Solid

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0355]

34-91

Relays Interchangeable Heater Overload

Table 34-138. Power Terminal Torque Line and Load Terminals


Terminal 32A 75A Catalog Number C306DT3B C306GT3B Torque in lb-in

Accessories
Table 34-141. DIN Rail and Panel Mounting Adapter
These adapters are required when component overload relays are to be separately mounted. The terminal base adapter includes line terminals and connects with the overload relays listed above. Description For 32 Ampere Overload Relay For 75 Ampere Overload Relay Catalog Number C306TB1 C306TB2B Price U.S. $ 13.00 25.75

20 35 (14 10 AWG) 40 (8 AWG) 45 (6 4 AWG) 50 (3 2 AWG) Socket Head Screw 120 (3/16) 200 (1/4) 250 (5/16) Socket Head Screw 120 (3/16) 200 (1/4) 250 (5/16) Slotted Head Screw 35 (14 10 AWG) 40 (8 AWG) 45 (6 4 AWG) 50 (3 1/0 AWG)

34

105A

C306KN3

This Series B adapter will accept Series A or B overload relays (C306GN3 or C306GN3B). C306TB2 can only be used with C306GN3.

144A

C306NN3

Table 34-139. Overload Relay UL/CSA Contact Ratings Control Circuit


AC Volts 120V 30 3 5 15 1.5 2.5 240V 15 1.5 5 7.5 .75 2.5 480V 7.5 .75 5 3.375 .375 2.5 600V

NC Contact B600
Make and Break Amps Break Amps Continuous Amps 6 .6 5 3 .3 2.5

Table 34-142. Locking Cover for Overload Relay C306 Only


Snap-on transparent or opaque plastic panel for covering access port to the overload relay trip setting dial helps prevent accidental or unauthorized changes to trip and reset setting. Description Min. Order Quantity (Std. Pkg.) 50 50 50 50 Catalog Number C320PC3 C320PC4 C320PC5 C320PC6 Price U.S. $ 1.15 1.15 1.15 *

NO Contact C600
Make and Break Amps Break Amps Continuous Amps

Clear cover, no accessibility Gray cover, no accessibility, with Auto only nib Gray cover, no accessibility, with Manual only nib Gray cover with FLA dial accessibility, A, B, C, D positions and Auto only nib Gray cover with FLA dial accessibility, A, B, C, D positions and Manual only nib

DC ratings cover Freedom Series coils only.

Factory Modications

50

C320PC7

1.15

Overload Lug Adapter Kit


Cat. No. C306TB1

Table 34-140. C306 Thermal Overload Relays with Mounting Adapter


Consists of a thermal overload relay mounted to a terminal base adapter permits fast and easy installation. Description C306DN3B + C306TB1 C306GN3B + C306TB2B Catalog Number C306DT3B C306GT3B Price U.S. $ 104.00 180.00

These kits are used in conjunction with Catalog Numbers H2001B H2014B or H2101B H2114B heater packs as a means of utilizing these Series B heater packs in Catalog Cat. No. C306KAL1-3 Numbers C306DN3 and Overload Relay Lug C306GN3 Series A1 overload Adapter Kit relays. The kit consists of 3 lug adapters and installation instructions. When installing Series B heater packs plus lug adapters in Series A overload relays, refer to heater pack FLA adjustment tables originally supplied with equipment (also supplied with kit). Table 34-143. Product Selection
Description Series A1 Overload Relay Lug Adapter Kit Catalog Number C306KAL1-3B Price U.S. $ 9.30

*Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C CA08102001E For more information visit: www.EatonElectrical.com

34-92

IEC Contactors & Starters Freedom


June 2005

Relays Interchangeable Heater Overload

Vol. 2, Ref. No. [0356]

Replacement Parts
Heater Pack Replacement
The heater pack series is determined by the 6th character of the Catalog Number. Series A or prior heater packs (identied by either A or - as the 6th character) have built-in load lugs. Series B or later heater packs do not (load lugs are on overload relay). Replacement of Series A or earlier heater packs with Series B or later heater packs, requires the one time addition of Lug Adapter Kit C3606KAL1-3B to the Series A1 overload relay.

Dimensions
Table 34-146. Stand-Alone Overload Relays Approximate Dimensions and Shipping Weights
Size Dimensions in Inches (mm) Wide A High B Deep C Mounting D 1.36 (34.5) 2.00 (50.8) 3.00 (76.2) E 3.74 (95.0) 3.45 (87.6) 6.62 (168.1) F (Slot) .18 x .30 (4.6 x 7.6) .22 x .26 (5.6 x 6.6) G (Hole) .18 (4.6) Dia. .21 (5.3) Dia. Ship. Wt. Lbs. (kg) .8 (.4) 1.4 (.6) 4.0 (1.8)

34

32A 75A 105 & 144A

1.77 (45.0) 2.54 (64.5) 4.00 (101.6)

4.13 (104.9) 4.69 (119.1) 7.17 (182.1)

3.69 (93.7) 3.74 (95.0) 4.91 (124.7)

A C

Superseded Series A Heater Pack

Series B Heater Pack

BE

Table 34-144. Heater Pack Replacement Requirements


Existing Heater Pack Catalog Numbers H2001-3 H2013-3 H2001A-3 H2013A-3 H2001B-3 H2013B-3 H2014-3 H2014A-3 H2014B-3 H2015-3 H2017-3 H2015A-3 H2017A-3 Replacement Product Required

Mtg. Holes for (3) 1/4-20 Screws

32A and 75A Sizes C306DT3B/C306GT3B Lug Adapter Kit C3606KAL1-3B and Series B Heater Pack Series B Heater Pack When inventory is exhausted, replace with Lug Adapter Kit C3606KAL1-3B and Series B Heater Pack Series B Heater Pack When inventory is exhausted, replace with heater pack chosen from Table 34-148 When inventory is exhausted, replace with Lug Adapter Kit C3606KAL1-3B and Series B Heater Pack Series B Heater Pack

105A and 144A Sizes C306KN3/C306NN3

Figure 34-41. Approximate Dimensions

Overload Relay Replacement Series A Only


When replacing a Catalog Number C306DN3 (Part Number 10-6044) or C306GN3 (10-6319) Series A overload relay on a starter, order a Series B overload relay and Series B heater packs.

H2015B-3 H2017B-3

Table 34-145. Heater Pack Ratings


Motor Full Load Ampere Rating Dial Position A 29.0 39.6 53.9 B 32.5 44.3 60.4 C 36.0 49.1 66.8 D 39.5 53.8 74.9 Order Price Heater Pack U.S. $ Catalog Number H2015A-3 H2016A-3 H2017A-3 * * *

*Please contact your local Eaton sales ofce.

Superseded 32 Ampere Series A Overload Relay Cat. No. C306DN3

Superseded 75 Ampere Series A Overload Relay Cat. No. C306GN3

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0357]

34-93

Relays Interchangeable Heater Overload

Product Selection

34

32A Overload Cat. No. C306DN3B

75A Overload Cat. No. C306GN3B

Table 34-147. C306 Thermal Overload Relays


For Use with Freedom Series Contactors NEMA 00, 0 1, 2 3 4 58 IEC AF GK LM N Maximum Ampere Rating Number of Poles Open Type Catalog Number C306DN3B C306GN3B C306KN3 C306NN3 Price U.S. $ 90. 157. 223. 308. Open Type with Adapter for DIN Rail or Panel Mount Catalog Number C306DT3B C306GT3B Price U.S. $ 104. 180. NEMA 1 Enclosed Catalog Number C306DG3B C306GG3B Price U.S. $ 115. 205.

32 75 105 144

3 3 3 3

NEMA Sizes 5 8 use the 32 ampere overload in conjunction with CTs. Series B overload relays have load lugs built into relay base and will only accept Series B heater packs. These relays can be directly attached to contactor or they can be DIN rail mounted using adapter on Page 34-91. These relays can be panel mounted only.

Heater Pack Selection

Heater Pack H2001B H2017B

Heater Pack H2101B H2117B

Heater Pack H2018 H2024

Heater packs H2001B to H2017B and H2101B to H2117B are to be used only with Series B overload relays Catalog Numbers C306DN3B (Part No. 107016) and C306GN3B (Part No. 107020). The load lugs are built into the overload relay base to allow load wiring prior to heater pack installation. The previous heater design had integral load lugs. The Series B heater packs are electrically equivalent to the previous heater design. Heaters H2018-3 to H2024-3 have not changed.

Table 34-148. Starters with Series B Overload Relays


NEMA AN Type Size 00 0 12 5 6 78 Series C B B C B IEC AE Type Size AF GK Series C B

Note: The series of a starter is the last digit of the listed Catalog Number. EXAMPLE: AE16DN0AB.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C CA08102001E For more information visit: www.EatonElectrical.com

34-94

IEC Contactors & Starters Freedom


June 2005

Relays Interchangeable Heater Overload


Table 34-149. Standard Trip Class 20
Overload Relay Size Motor Full Load Ampere Rating Dial Position A B C D Catalog Number (Includes 3 Heater Packs) Price U.S. $

Vol. 2, Ref. No. [0358]

Table 34-150. Fast Trip Class 10


Overload Relay Size Motor Full Load Ampere Rating Dial Position A B C D Catalog Number (Includes 3 Heater Packs) Price U.S. $

34

For Use with NEMA Sizes 00 0 Series C, NEMA Sizes 1 2 Series B; IEC Sizes A F Series C, IEC Sizes G K Series B
32A or 75A .254 .375 .560 .814 1.20 1.79 2.15 3.23 4.55 6.75 9.14 14.0 18.7 23.5 75A 29.0 39.6 53.9 8.0 11.4 14.3 18.0 24.6 33.5 45.7 62.2 84.7 106.0 32A 49 72 107 129 194 144 215 258 388 163 240 358 430 646 244 360 537 645 969 .306 .452 .676 .983 1.45 2.16 2.60 3.90 5.50 8.17 10.8 16.9 22.7 28.5 34.0 45.5 60.9 9.2 12.8 15.7 20.2 27.6 37.5 51.2 69.7 95.0 118.0 59 87 130 156 234 174 259 312 468 197 290 432 520 780 295 435 648 780 1170 .359 .530 .791 1.15 1.71 2.53 3.04 4.56 6.45 9.58 12.4 19.9 26.7 33.5 39.1 51.5 67.9 10.3 14.3 17.4 22.3 30.5 41.5 56.7 77.1 105.0 131.0 69 103 152 182 274 205 304 365 547 230 342 506 608 912 345 513 759 912 1368 .411 .607 .907 1.32 1.96 2.90 3.49 5.23 7.40 11.0 14.0 22.8 30.7 38.5 44.1 57.4 74.9 11.5 15.7 19.0 24.5 33.4 45.6 62.1 84.6 115.0 144.0 79 118 174 209 235 348 419 627 264 392 580 698 396 588 870 1047 H2001B-3 H2002B-3 H2003B-3 H2004B-3 H2005B-3 H2006B-3 H2007B-3 H2008B-3 H2009B-3 H2010B-3 H2011B-3 H2012B-3 H2013B-3 H2014B-3 H2015B-3 H2016B-3 H2017B-3 H2025-3 H2026-3 H2027-3 H2018-3 H2019-3 H2020-3 H2021-3 H2022-3 H2023-3 H2024-3 H2004B-3 H2005B-3 H2006B-3 H2007B-3 H2008B-3 H2005B-3 H2006B-3 H2007B-3 H2008B-3 H2004B-3 H2005B-3 H2006B-3 H2007B-3 H2008B-3 H2004B-3 H2005B-3 H2006B-3 H2007B-3 H2008B-3 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25

For Use with NEMA Sizes 00 0 Series C, NEMA Sizes 1 2 Series B; IEC Sizes A F Series C, IEC Sizes G K Series B
32A or 75A .260 .384 .570 .846 1.28 1.92 2.30 3.38 4.96 7.07 9.60 14.4 18.7 23.5 75A 28.3 36.6 53.8 51 77 115 138 203 154 230 276 406 169 256 384 460 676 254 384 576 690 1014 .313 .464 .688 1.02 1.55 2.33 2.79 4.10 6.03 8.58 11.2 17.5 21.8 27.3 32.6 42.3 60.8 61 93 140 167 246 186 280 335 492 204 310 466 558 820 306 465 699 837 1230 .367 .543 .806 1.20 1.83 2.74 3.28 4.82 7.09 10.1 12.8 20.7 25.0 31.0 37.0 48.1 67.9 72 110 164 197 289 220 329 394 578 240 366 543 656 360 549 822 984 .420 .623 .924 1.37 2.10 3.15 3.77 5.54 8.16 11.6 14.4 23.8 28.1 34.8 41.3 53.8 74.9 82 126 189 226 252 378 452 274 420 630 754 411 630 945 1131 H2101B-3 H2102B-3 H2103B-3 H2104B-3 H2105B-3 H2106B-3 H2107B-3 H2108B-3 H2109B-3 H2110B-3 H2111B-3 H2112B-3 H2113B-3 H2114B-3 H2115B-3 H2116B-3 H2117B-3 H2104B-3 H2105B-3 H2106B-3 H2107B-3 H2108B-3 H2105B-3 H2106B-3 H2107B-3 H2108B-3 H2104B-3 H2105B-3 H2106B-3 H2107B-3 H2108B-3 H2104B-3 H2105B-3 H2106B-3 H2107B-3 H2108B-3 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25 39.25

For Use with NEMA Size 2, IEC Sizes G K Only Series B

For Use with NEMA Size 2, IEC Sizes G K Only Series B

For Use with NEMA Sizes 3 4, IEC Sizes L N Only Series A


105A or 144A

For Use with Size 5 Starters Only Series B and IEC P, R and S with 300/5 CT
32A

For Use with Size 6 Starters Only Series B and IEC T V with 600/5 CT
32A

For Use with Size 5 Starters Series B and IEC P, R and S with 300/5 CT

For Use with Size 7 Starters Only Series B and IEC W X with 1000/5 CT
32A

For Use with Size 6 Starters Only Series B and IEC T V with 600/5 CT
32A

For Use with Size 8 Starters Only Series B and IEC Z with 1500/5 CT
32A

For Use with Size 7 Starters Only Series B and IEC W X with 1000/5 CT
32A

Sizes 5 8 and IEC P Z use the 32A overload relay with current transformers.

Note: Heater packs are shipped 3 to a carton. Catalog Numbers and prices are for 3 heater packs.

For Use with Size 8 Starters Only Series B and IEC Z with 1500/5 CT
32A

Sizes 5 8 and IEC P Z use the 32A overload relay with current transformers.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0359]

34-95

Technical Data and Specications


All data is based on a standard contactor with no auxiliary devices and a 120V AC or 24V DC magnet coil. Coil data has a 5% range depending on the application, therefore specic data may vary.

Table 34-151. Coil Data Notes


P.U. Pick-up time is the average time taken from closing of the coil circuit to main contact touch. Drop-out time is the average time taken from opening of the coil circuit to main contact separation. Coil data with a hot coil.

D.O.

Cold Coil data with a cold coil. Hot

34
Contactor Catalog Number/Frame CE15A IEC Frame A CE15B IEC Frame B 2, 3, 4 4th Pole NO (1) Top (4) or Side (4) 45 mm IP20 690V 6 kV CE15C IEC Frame C 2, 3, 4 4th Pole NO (1) Top (4) or Side (4) 45 mm CE15D IEC Frame D 2, 3 Side NO (1) Top (4) or Side (3) 45 mm CE15E IEC Frame E 2, 3 Side NO (1) Top (4) or Side (3) 45 mm IP10

Table 34-152. Specications IEC Frames A E


Description

Conguration: Number of Poles Aux. Contacts, Std. Add-On Aux. Contacts Frame Size Finger Protection Insulation Voltage (Ui) Impulse Withstand Voltage (Uimp) Current Ratings (I) IEC 947-4-1 AC-1 Thermal Current Ith 230-380-460-575V AC-3 (le) 230V 380V 460V 575V AC-4 (le) 230V 380V 460V 575V AC Magnet Coil Data Pick-Up Volts Cold Pick-Up Volts Hot Pick-Up Voltamperes Pick-Up Watts Sealed Voltamperes Sealed Watts Drop-Out Volts Cold Drop-Out Volts Hot Max. Operation Rate Ops/Hour Pick-Up Time (mS) Drop-Out Time (mS) Coil Operating Range % of Rated Voltage DC Magnet Coil Data Mechanical Life Electrical Life (440/460V) AC-3 AC-4 AWG Wire Range Power Terminals Control Terminals Power Terminal Torque lb-in Contact Kit Part No. Auxiliary Contact Ratings

2, 3, 4 4th Pole NO (1) Top (4) or Side (4) 45 mm

20 Amperes kW 1.1 2.2 2.2 4.0 1.1 2.2 2.2 4.0 74% 78% 80 49 7.5 2.4 45% 46% 12,000 12 12 -15% to +10% hp 1-1/2 3 5 I 5.2A 5.2A 4.8A 6.9A 5.2A 5.2A 4.8A 6.9A

20 Amperes kW 1.5 4.0 4.0 5.5 1.5 4.0 4.0 5.5 74% 78% 80 49 7.5 2.4 45% 46% 12,000 12 12 -15% to +10% hp 2 5 7-1/2 1 2 3 I 6.8A 9.1A 7.8A 9.4A 6.8A 9.1A 7.8A 9.4A

20 Amperes kW 2.2 5.5 5.5 7.5 3.0 5.5 5.5 7.5 74% 78% 80 49 7.5 2.4 45% 46% 12,000 12 12 -15% to +10% hp 3 7-1/2 10 1.5 3 5 I 9.6A 12A 11A 12A 9.6A 12A 11A 9.4A

32 Amperes kW 4.0 7.5 7.5 11 4.0 7.5 7.5 11 74% 78% 100 65 10 3.1 45% 46% 12,000 12 12 -15% to +10% hp 5 10 15 2 5 7.5 I 16A 16A 14A 17A 16A 16A 14A 12A

32 Amperes kW 5.5 11 11 15 5.5 11 11 15 74% 78% 100 65 10 3.1 45% 46% 12,000 12 12 -15% to +10% hp 7-1/2 15 20 3 7-1/2 10 I 22A 23A 21A 23A 22A 23A 21A 17A

For DC Magnet Coils (and coil data), see Accessories Page 34-102. 20,000,000 2,000,000 46,000 12 16 Stranded 12 14 Solid Cu 12 16 Stranded 12 14 Solid Cu 7 None 20,000,000 2,000,000 70,000 12 16 Stranded 12 14 Solid Cu 12 16 Stranded 12 14 Solid Cu 7 None 20,000,000 2,200,000 50,000 12 16 Stranded 12 14 Solid Cu 12 16 Stranded 12 14 Solid Cu 7 None A600, P300, AC-15, DC-13 20,000,000 1,300,000 60,000 8 16 Stranded 10 14 Solid Cu 12 16 Stranded 12 14 Solid Cu 15 None 20,000,000 1,600,000 50,000 8 16 Stranded 10 14 Solid Cu 12 16 Stranded 12 14 Solid Cu 15 None

Without optional IP20 nger shields. See Pages 34-100 34-101 for ratings.

CA08102001E

For more information visit: www.EatonElectrical.com

34-96

IEC Contactors & Starters Freedom


June 2005

Technical Data and Specications


Table 34-153. Specications IEC Frames F K
Description Contactor Catalog Number/Frame CE15F IEC Frame F Conguration: Number of Poles Aux. Contacts, Std. Add-On Aux. Contacts Frame Size Finger Protection Insulation Voltage (Ui) Impulse Withstand Voltage (Uimp) Current Ratings (I) IEC 947-4-1 AC-1 Thermal Current Ith 230-380-460-575V AC-3 (le) 230V 380V 460V 575V AC-4 (le) 230V 380V 460V 575V AC Magnet Coil Data Pick-Up Volts Cold Pick-Up Volts Hot Pick-Up Voltamperes Pick-Up Watts Sealed Voltamperes Sealed Watts Drop-Out Volts Cold Drop-Out Volts Hot Max. Operation Rate Ops/Hour Pick-Up Time (mS) Drop-Out Time (mS) Coil Operating Range % of Rated Voltage DC Magnet Coil Data Mechanical Life Electrical Life (440/460V) AC-3 AC-4 AWG Wire Range Power Terminals 20,000,000 1,500,000 55,000 8 16 Stranded 10 14 Solid Cu 12 16 Stranded 12 14 Solid Cu 15 2, 3 Side NO (1) Top (4) or Side (3) 45 mm CE15G IEC Frame G 2, 3, 4, 5 Side NO (1) Top (4) or Side (3) 65 mm CE15H IEC Frame H 2, 3, 4, 5 Side NO (1) Top (4) or Side (3) 65 mm IP10 690V 6 kV CE15J IEC Frame J 2, 3, 4, 5 Side NO (1) Top (4) or Side (3) 65 mm

Vol. 2, Ref. No. [0360]

CE15K IEC Frame K 2, 3 Side NO (1) Top (4) or Side (3) 65 mm

34

32 Amperes kW 7.5 15 15 18.5 5.5 11 11 15 74% 78% 100 65 10 3.1 45% 46% 12,000 12 12 -15% to +10% hp 10 20 25 5 10 15 I 28A 30A 27A 28A 22A 23A 21A 19A

50 Amperes kW 18.5 18.5 22 18.5 18.5 22 74% 78% 230 95 28 7.8 49% 50% 12,000 20 14 -15% to +10% hp 10 25 30 7.5 15 20 I 36A 37A 34A 34A 36A 37A 34A 34A

60 Amperes kW 11 22 22 30 11 22 22 30 74% 78% 230 95 28 7.8 49% 50% 12,000 20 14 -15% to +10% hp 15 30 40 10 20 25 I 42A 44A 40A 45A 42A 44A 40A 45A

75 Amperes kW 15 30 30 30 15 30 30 37 74% 78% 230 95 28 7.8 49% 50% 12,000 20 14 -15% to +10% hp 20 40 40 10 25 30 I 54A 59A 52A 45A 54A 59A 52A 45A

80 Amperes kW 18.5 37 37 37 15 30 30 37 74% 78% 230 95 28 7.8 49% 50% 12,000 20 14 -15% to +10% hp 25 50 50 15 30 40 I 68A 73A 65A 55A 54A 59A 52A 45A

For DC Magnet Coils (and coil data), see Accessories Page 34-102. 10,000,000 1,400,000 70,000 2 14 (Upper) and/or 6 14 (Lower) Stranded or Solid Cu 12 16 Stranded 12 14 Solid Cu 40 (14 8 AWG) 45 (6 4 AWG) 50 (3 AWG) 6-65-4 10,000,000 1,500,000 75,000 2 14 (Upper) and/or 6 14 (Lower) Stranded or Solid Cu 12 16 Stranded 12 14 Solid Cu 40 (14 8 AWG) 45 (6 4 AWG) 50 (3 AWG) 6-65-6 A600, P300, AC-15, DC-13 10,000,000 1,600,000 40,000 2 14 (Upper) and/or 6 14 (Lower) Stranded or Solid Cu 12 16 Stranded 12 14 Solid Cu 40 (14 8 AWG) 45 (6 4 AWG) 50 (3 AWG) 6-65-8 10,000,000 1,600,000 32,000 2 14 (Upper) and/or 6 14 (Lower) Stranded or Solid Cu 12 16 Stranded 12 14 Solid Cu 40 (14 8 AWG) 45 (6 4 AWG) 50 (3 AWG) 6-65-17

Control Terminals Power Terminal Torque lb-in

Contact Kit Part No. Auxiliary Contact Ratings

None

Without optional IP20 nger shields. See Pages 34-100 34-101 for ratings.

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0361]

34-97

Technical Data and Specications

Table 34-154. Specications IEC Frames L R


Description Contactor Catalog Number/Frame CE15L IEC Frame L Conguration: Number of Poles Aux. Contacts, Std. Add-On Aux. Contacts Frame Size Finger Protection Insulation Voltage (Ui) Impulse Withstand Voltage (Uimp) Current Ratings (I) IEC 947-4-1 AC-1 Thermal Current Ith 230-380-460-575V AC-3 (le) 230V 380V 460V 575V AC-4 (le) 230V 380V 460V 575V AC Magnet Coil Data Pick-Up Volts Cold Pick-Up Volts Hot Pick-Up Voltamperes Pick-Up Watts Sealed Voltamperes Sealed Watts Drop-Out Volts Cold Drop-Out Volts Hot Max. Operation Rate Ops/Hour Pick-Up Time (mS) Drop-Out Time (mS) Coil Operating Range % of Rated Voltage DC Magnet Coil Data Mechanical Life Electrical Life (440/460V) AC-3 AC-4 AWG Wire Range Power Terminals Control Terminals Power Terminal Torque lb-in 6,000,000 420,000 41,000 1/0 14 Cu 12 16 Stranded 12 14 Solid Cu 35 (14 10 AWG) 40 (8 AWG) 45 (6 4 AWG) 50 (3 1/0 AWG) 6-43-4 2, 3 Side NO (1) Left Side (4) or Right (3) 90 mm CE15M IEC Frame M 2, 3 Side NO (1) Left Side (4) or Right (3) 90 mm IP10 690V 6 kV CE15N IEC Frame N 2, 3 Side NO (1) Left Side (4) or Right (3) 90 mm CE15P IEC Frame P 3 Side NO-NC (1) Left Side (2) or Right (4) 180 mm CE15R IEC Frame R 3 Side NO-NC (1) Left Side (2) or Right (4) 180 mm IP00

34

100 Amperes kW 22 45 45 55 72% 76% 390 112 49.8 13 50% 52% 7,200 14 11 -15% to +10% hp 30 60 75 20 40 40 I 86A 86A 86A 81A 68A 73A 65A 55A

135 Amperes kW 30 55 55 75 72% 76% 390 112 49.8 13 50% 52% 7,200 14 11 -15% to +10% hp 40 75 100 25 50 50 I 106A 106A 106A 105A 86A 86A 86A 55A

175 Amperes kW 37 75 75 90 72% 76% 390 112 49.8 13 50% 52% 7,200 14 11 -15% to +10% hp 50 100 125 30 60 75 I 140A 140A 140A 105A 106a 106A 106A 81A

185 Amperes kW 45 90 90 90 37 65 65 65 72.5% 76% 1040 216 116 17 54% 56% 2,400 23 15 -15% to +10% hp 60 125 125 I 170A 170A 170A 130A 128A 128A 128A 98A

220 Amperes kW 55 110 110 110 45 75 75 75 72.5% 76% 1040 216 116 17 54% 56% 2,400 23 15 -15% to +10% hp 75 150 150 I 200A 200A 200A 160A 150A 140A 140A 105A

For DC Magnet Coils (and coil data), see Accessories Page 34-102. 6,000,000 420,000 37,000 2/0 14 Cu/Al 12 16 Stranded 12 14 Solid Cu 40 (8 AWG) 45 (6 4 AWG) 50 (3 1/0 AWG) 6-43-2 5,000,000 510,000 36,000 3/0 8 Cu/Al 12 16 Stranded 12 14 Solid Cu 200 5,000,000 500,000 58,000 350 kcmil 6 12 16 Stranded 12 14 Solid Cu 375 5,000,000 400,000 56,000 350 kcmil 6 12 16 Stranded 12 14 Solid Cu 375

Contact Kit Part No. Auxiliary Contact Ratings

6-43-6 A600, P300, AC-15, DC-13

6-294

6-288

Without optional IP20 nger shields. See Pages 34-100 34-101 for ratings.

CA08102001E

For more information visit: www.EatonElectrical.com

34-98

IEC Contactors & Starters Freedom


June 2005

Technical Data and Specications


Table 34-155. Specications IEC Frames S V
Description Contactor Catalog Number/Frame CE15S IEC Frame S Conguration: Number of Poles Aux. Contacts, Std. Add-On Aux. Contacts Frame Size Finger Protection Insulation Voltage (Ui) Impulse Withstand Voltage (Uimp) Current Ratings (I) IEC 947-4-1 AC-1 Thermal Current Ith 230-380-460-575V AC-3 (le) 230V 380V 460V 575V 690V 6 kV 3 Side NO-NC (1) Left Side (2) or Right (4) 180 mm CE15T IEC Frame T 3 Top Left 2NO-2NC (1) Top Right 2NO-2NC (1) 220 mm CE15U IEC Frame U 3 Top Left 2NO-2NC (1) Top Right 2NO-2NC (1) 220 mm IP00 1000V N/A

Vol. 2, Ref. No. [0362]

CE15V IEC Frame V 3 Top Left 2NO-2NC (1) Top Right 2NO-2NC (1) 280 mm

34

315 Amperes kW 90 160 160 160 hp 100 200 200 I 300A 300A 300A 210A

600 Amperes, 1000V kW 129 220 240 300 300 220 55 95 95 95 110 75% 75% 950 798 11 10 I 450A 450A 450A 420A 350A 170A 180A 180A 180A 140A 140A hp/V

760 Amperes, 1000V kW 160 280 315 375 375 355 60 105 105 100 132 75% 75% 950 798 11 10 I 550A 550A 550A 520A 450A 260A 200 200 200 145 145 hp/V

1000 Amperes, 1000V kW 220 375 400 500 500 500 65 110 110 105 140 75% 75% 1600 1345 25 22 I 700A 700A 700A 630A 630A 350A 220A 220A 220A 150A 150A hp/V

125/220V 125/230V 250/460V 250/575V

150/200V 150/230V 350/460V 350/575V

150/200V 200/230V 400/460V 400/575V

AC-4 (le) 230V 380V 460V 575V AC Magnet Coil Data Pick-Up Volts Cold Pick-Up Volts Hot Pick-Up Voltamperes Pick-Up Watts Sealed Voltamperes Sealed Watts Drop-Out Volts Cold Drop-Out Volts Hot Max. Operation Rate Ops/Hour Pick-Up Time (mS) Drop-Out Time (mS) Coil Operating Range % of Rated Voltage DC Magnet Coil Data Mechanical Life Electrical Life (440/460V) AC-3 AC-4 AWG Wire Range Power Terminals Control Terminals Power Terminal Torque lb-in Contact Kit Part No. Auxiliary Contact Ratings

50 90 90 110

170A 170A 170A 160A

72.5% 76% 1040 216 116 17 54% 56% 2,400 23 15 -15% to +10%

N/A 100 170 -15% to +10%

N/A 100 170 -15% to +10%

N/A 105 200 -15% to +10%

For DC Magnet Coils (and coil data), see Accessories Page 34-102. 5,000,000 300,000 52,000 350 kcmil 6 12 16 Stranded 12 14 Solid Cu 375 6-286 5,000,000 420,000 4,200 (2) 600 kcmil 2/0 12 16 Stranded 12 14 Solid Cu 375 6-621 5,000,000 420,000 4,200 (2) 600 kcmil 2/0 12 16 Stranded 12 14 Solid Cu 375 6-622 A600, P300, AC-15, DC-13 5,000,000 420,000 4,200 (2) 750 kcmil 3/0 12 16 Stranded 12 14 Solid Cu 550 6-601

Without optional IP20 nger shields. See Pages 34-100 34-101 for ratings. 20 30% of rated coil voltage.

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0363]

34-99

Technical Data and Specications

Table 34-156. Specications IEC Frames W Z


Description Contactor Catalog Number/Frame CE15W IEC Frame W Conguration: Number of Poles Aux. Contacts, Std. Add-On Aux. Contacts Frame Size Finger Protection Insulation Voltage (Ui) Impulse Withstand Voltage (Uimp) Current Ratings (I) IEC 947-4-1 AC-1 Thermal Current Ith 230-380-460-575V AC-3 (le) 220/240V 380V 415/440V 500/550V 660V 1000V AC-4 (le) 220/240V 380V 415/440V 500/550V 660V AC Magnet Coil Data Pick-Up Volts Cold Pick-Up Volts Hot Pick-Up Voltamperes Pick-Up Watts Sealed Voltamperes Sealed Watts Drop-Out Volts Cold Drop-Out Volts Hot Max. Operation Rate Ops/Hour Pick-Up Time (mS) Drop-Out Time (mS) Coil Operating Range % of Rated Voltage Mechanical Life Electrical Life (440/460V) AC-3 AC-4 AWG Wire Range Power Terminals Control Terminals Power Terminal Torque lb-in Contact Kit Part No. Auxiliary Contact Ratings 20 30% of rated coil voltage. (2) 750 kcmil 3/0 12 16 Stranded 12 14 Solid 550 6-601 600,000 60,000 (3) 750 kcmil 3/0 12 16 Stranded 12 14 Solid 550 6-613 A600, P300, AC-15, DC-13 3 Top Left 2NO-2NC (1) Top Right 2NO-2NC (1) 280 mm CE15X IEC Frame X 3 Top Left 2NO-2NC (1) Top Right 2NO-2NC (1) 280 mm IP00 1000V N/A CE15Z IEC Frame Z 3 Outside Left 2NO-1NC 6NO-7NC 334 mm

34

1000 Amperes kW 220 375 400 500 500 500 65 110 110 105 140 75% 75% 1000 23 I 700A 700A 650A 680A 515A 220A 220A 220A 150A 150A hp/V 250/230V 500/460V 500/575V

1100 Amperes kW 270 475 500 600 600 550 80 150 160 185 185 75% 75% 1000 23 I 850A 850A 820A 260A 280A 280A 265A 200A hp/V 300/230V 600/460V 600/575V

1350 Amperes kW 380 650 700 840 132 220 230 257 257 75% 75% 2400 70 I 1180A 425A 400A 400A 365A 280A hp/V 450/230V 900/460V 900/575V

100 150 1000

100 150 1000 -15% to +10% 10,000,000

100 25 50

600,000 10,000 (4) 750 kcmil 3/0 12 16 Stranded 12 14 Solid 500 6-571

Table 34-157. Utilization Categories


The International Electrotechnical Commission (IEC) has developed utilization categories for contactors and auxiliary contacts. The categories describe the type of electrical load and the conditions for making and breaking the current. Category AC-1 AC-2 AC-3 AC-4 AC-11 Typical Application Non-inductive or slightly inductive loads: Resistance furnaces, heating. Slip-ring motors: Starting, plugging. Squirrel cage motors: Starting, switching off motors during running (motors in most industrial applications typically fall into this category). Squirrel cage motors: Starting, plugging , inching (very few applications in industry are totally AC-4). Control of alternating current electromagnetic circuits (auxiliary contacts).

Plugging is stopping or reversing the motor rapidly by reversing the connections while the motor is running. Inching or jogging is energizing the motor once or repeatedly for short durations to obtain small movements of the motor driven load.

CA08102001E

For more information visit: www.EatonElectrical.com

34-100

IEC Contactors & Starters Freedom


June 2005

Accessories

Vol. 2, Ref. No. [0364]

Auxiliary Contacts
NEMA Sizes 00 2 IEC Sizes A K
The auxiliary contacts listed below are designed for installation on Freedom Series starters and contactors. Snap-on design facilitates quick, easy installation.

NEMA Sizes 3 8 IEC Sizes L Z


Table 34-159. Product Selection
Circuit Contact Conguration Code Catalog Number Price U.S. $

Base Auxiliary Contacts NEMA Sizes 3 5, IEC Sizes L S


NEMA Size 3 IEC Sizes L N NO NO-NC 10 11 C320KGS31 C320KGS32 Catalog Number NO NC NO-NC 10 01 11 C320KGS20 C320KGS21 C320KGS22 Size NO-NC 2NO-2NC 2NO-2NC 11 22 22 NEMA 8, IEC Z NEMA 6 7 IEC T X Catalog Number C320KA5 C320KA6 C320KA8 186.00 186.00 210.00 51.50 51.50 70.00 NEMA Sizes 4 5 IEC Sizes P S C320KGS41 C320KGS42 51.50 70.00

34

These bifurcated design contact blocks, featuring silver cadmium alloy contacts, are well suited for use in very low energy (logic level) circuits.

Auxiliary Contacts NEMA Sizes 3 5, IEC Sizes L S

Auxiliary Contacts NEMA Sizes 6 8, IEC Sizes T Z

Side Mounted

Top Mounted

Table 34-158. Selection Product


Description Contact Conguration Code 10 10 01 11 11 20 20 02 N/A N/A N/A 10 01 11 11 20 02 N/A N/A N/A 30 21 12 03 40 31 22 22 13 04 N/A N/A N/A N/A Catalog Number Price U.S. $

For reference only not part of Catalog Number. See below left. NO-NC occupies two positions L2 and L3, or R2 and R3. See next page.

Side Mounted
1NO 1NO (Logic Level) 1NC 1NO-1NC 1NO-1NC (Logic Level) 2NO 2NO (Logic Level) 2NC 1NO-1NCI 1NO (EC)-1NC (LO) 1NCI C320KGS1 C320KGS1L C320KGS2 C320KGS3 C320KGS3L C320KGS4 C320KGS4L C320KGS5 C320KGS6 C320KGS7 C320KGS8 C320KGT1 C320KGT2 C320KGT3 C320KGT3L C320KGT4 C320KGT5 C320KGT6 C320KGT7 C320KGT8 C320KGT9 C320KGT10 C320KGT11 C320KGT12 C320KGT13 C320KGT14 C320KGT15 C320KGT15L C320KGT16 C320KGT17 C320KGT18 C320KGT19 C320KGT20 C320KGT21 25.75 51.50 25.75 34.75 70.00 34.75 70.00 34.75 34.75 34.75 34.75 25.75 25.75 34.75 70.00 34.75 34.75 34.75 34.75 34.75 70.00 70.00 70.00 70.00 70.00 70.00 70.00 70.00 70.00 70.00 70.00 70.00 70.00 70.00

Base Auxiliary Contact Cat. No. C320KGS42

Auxiliary Contact Cat. No. C320KGS22

Auxiliary Contact Ratings (Amperes)


Table 34-160. NEMA A600
Current AC Volts 120V Make and Interrupting Break Continuous 60 6 10 240V 30 3 10 480V 15 1.5 10 600V 12 1 10

Top Mounted
1NO 1NC 1NO-1NC 1NO-1NC (Logic Level) 2NO 2NC 1NO-1NCI 1NO (EC)-1NC (LO) 1NCI 3NO 2NO-1NC 1NO-2NC 3NC 4NO 3NO-1NC 2NO-2NC 2NO-2NC (Logic Level) 1NO-3NC 4NC 3NO-1NCI 2NO-1NCI-1NC 2NO-1NO (EC)-1NC (LO) 1NO-1NC-1NO (EC)-1NC (LO)

Table 34-161. NEMA P300


Continuous Thermal Rating: 5A DC Volts 125 250 Make/Break Amperes 1.10 .55

Table 34-162. Logic Level


Minimum Ratings for Logic Level and Hostile Atmosphere Application Minimum Amperes Minimum Volts 20 mA 24V AC/DC

Note: NCI = Normally Closed early opening designed for use in reversing applications. EC = Early Closing. LO = Late Opening.
For reference only not part of Catalog Number. See below.

Contact Conguration Code


This two-digit code is found on the auxiliary contact to assist in identifying the specic contact conguration. The rst digit indicates the quantity of NO contacts and the second indicates the quantity of NC contacts.
For more information visit: www.EatonElectrical.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0365]

34-101

Accessories NEMA Sizes 3 8, IEC Sizes L Z


The sketches below illustrate the maximum number of auxiliary contacts that can be assembled to a contactor and their locations.
Note: A Base Auxiliary Contact must be added in position R1 before additional auxiliary contacts can be mounted on NEMA Size 3 and IEC Sizes L N, or in L1 on NEMA Sizes 4 5 and IEC Sizes P S.

Auxiliary Contact Location


NEMA Sizes 00 2, IEC Sizes A K
The sketches below illustrate the maximum number of auxiliary contacts that can be assembled to a contactor or starter and their locations. Table 34-163. Auxiliary Contacts
Catalog Number AE16 AN16 AE56 AN56 CE15 Size Poles Available Mounting Positions Open Type AK 00 02 AK 00 2 AC DK GJ GJ 00 02 1, 2 1, 2 10A 20 60A 60A 60A AK 00 2 3 3 3 3 3 24 3 4 5 24 23 4 5 24 23 4 5 3 3 T1, L1 T1, L1, R1 T1, L1 L1, R1 T1, T2 T1, L1, R1 T1, L1 T1, R1 T1 T1, L1, R1 T1, L1 T1, L1 T1, L1 T1, L1, R1 T1, L1 T1, L1 T1, L1 L1, R1 T1, T2 Enclosed L1 L1 L1 L1, R1 L1, R1 L1 L1 L1 L1 L1 L1, R1

Table 34-164. Auxiliary Contacts


Size NEMA Size 3, IEC Sizes L N NEMA Sizes 4 5, IEC Sizes P S NEMA Sizes 6 7, IEC Sizes T X NEMA Size 8, IEC Size Z Available Mounting Positions R2, R3, L1, L2, L3 L2, L3, R1, R2, R3 R1 L2, R2

34

Available positions on contactors or starters other than what is factory installed.

CN15

L1 Rear

L2

L3

R3

R2

R1 Rear

CN35

Base Aux. Aux. Aux. Cont. Cont. Cont. Left Side of Contactor Front of Contactor NEMA Sizes 3 5 IEC Sizes L S

Aux. Aux. Base Cont. Cont. Aux. Cont. Right Side of Contactor

CE55 CN55

Available positions on contactors or starters other than what is factory installed. When a pneumatic timer is mounted on contactor, only side mounted auxiliary contact positions are available. The solid-state timer, when added, takes up side mounted auxiliary contact position.

L1

R1

L1

R1

L1

R1

NEMA Sizes 6 7 IEC Sizes T, U, V, W and X

T1 Top View

T1 Top View

T2 L1 L2 R1 R2

L1

T1

R1

L1

T1

T2

R1 NEMA Size 8 IEC Size Z

Front View Non-reversing Contactors and Starters

Front View Reversing Contactors and Starters

Figure 34-43. Auxiliary Contact Location

Figure 34-42. Auxiliary Contact Location

CA08102001E

For more information visit: www.EatonElectrical.com

34-102

IEC Contactors & Starters Freedom


June 2005

Accessories

Vol. 2, Ref. No. [0366]

DC Magnet Coils
When Ordering Specify
Conversion Kit for Field Assembly Catalog Number

Non-reversing Kit Consists of:

1 Encapsulated DC magnet coil 1 NCI or NO/NCI side mounted auxiliary contact


Note: These kits are supplied with a NO/ NCI side mounted auxiliary contact in place of the NCI contact.

Note: For NEMA Sizes 00 and 0 and IEC Sizes A F, contactors may utilize either sufx 1 or 4 DC coil kits; starters may utilize sufx 4 DC coil kits only. For NEMA Sizes 1 and 2 and IEC Sizes G K, both contactors and starters may utilize a sufx 4 DC coil kit only.

34

Factory Installed DC Coil For factory installed DC magnet coil on AC contactors or non-combination starters (open type only), substitute the Code Sufx from table below for the magnet coil identier in the device Catalog Number. EXAMPLE: For Size 0 AC contactor with a 24V DC coil, change CN15BN3AC to CN15BN3T1C.

2 Blue colored connection wires 1 Instruction publication

Operation
These DC coil kits have separate pickup and seal windings. A special (side mounted) early-break NCI auxiliary contact is used to either disconnect the pick-up winding or insert the seal winding in series with the pick-up winding, depending on the frame size of the contactor. DC coil kits come in two styles, a sufx 1 and a sufx 4. The 1 sufx contains only the special (side mounted) early break NCI auxiliary contact. The 4 sufx contains a NO contact in the same package as the special (side mounted) early-break NCI auxiliary contact.

On the above sizes only, when the special auxiliary package is mounted on the side of a contactor or starter, no standard auxiliary contact may be mounted on the same side.
Note: For NEMA Sizes 3 5 and IEC Sizes L S, the special coil NCI clearing contact is an add-on auxiliary (must mount on a base mount auxiliary contact; normally a 1NO). This arrangement will normally account for two of the three contact positions on the side of each contactor or starter.

Application

Connect for separate control Not for use with cover control switch operators Use twin break, heavy-duty pilot devices Designed for +10%, -20% rated voltage, continuous duty operation Table 34-165. Product Selection DC Magnet Coils
Contactor or Starter Size NEMA IEC Conversion Data Volts Magnet Coil Coil Number 12 24 48 120 12 24 48 120 12 24 48 120 12 24 48 120 24 48 120 240 12 24 48 120 12 24 48 120 9-2988-11 9-2988-12 9-2988-13 9-2988-14 9-2988-11 9-2988-12 9-2988-13 9-2988-14 9-2990-1 9-2990-2 9-2990-3 9-2990-4 9-3002-1 9-3002-2 9-3002-3 9-3002-4 9-2026-4 9-2026-3 9-2026-2 9-2026-1 9-2988-1 9-2988-2 9-2988-3 9-2988-4 9-2990-1 9-2990-2 9-2990-3 9-2990-4

See Figure 34-44, Page 34-103.

Complete Conversion Kit Amps P.U./Seal 6.4/.28 3.2/.14 1.6/.07 .64/.028 6.4/.28 3.2/.14 1.6/.07 .64/.028 15.4/.42 7.7/.21 3.9/.11 1.5/.041 24/.40 12/.20 6.1/.097 2.5/.038 18/.22 9/.11 3.3/.05 1.7/.02 6.4/.28 3.2/.14 1.6/.07 .64/.028 15.4/.42 7.7/.21 3.9/.11 1.5/.041 Watts P.U./Seal 76.8/3.36 76.8/3.36 76.8/3.36 76.8/3.36 76.8/3.36 76.8/3.36 76.8/3.36 76.8/3.36 185/4.98 185/4.96 185/5.04 185/4.87 293/4.84 288/4.75 295/4.67 298/4.57 400/5.3 400/5.2 450/5.4 440/4.9 76.8/3.36 76.8/3.36 76.8/3.36 76.8/3.36 185/4.98 185/4.96 185/5.04 185/4.87 NCI Interlock Number Catalog Number C335KD3R1 C335KD3T1 C335KD3W1 C335KD3A1 C335KD3R4 C335KD3T4 C335KD3W4 C335KD3A4 C335KD4R4 C335KD4T4 C335KD4W4 C335KD4A4 C335KD5R1 C335KD5T1 C335KD5W1 C335KD5A1 C335KA3T1 C335KA3W1 C335KA3A1 C335KA3B1 C335KD3R1 C335KD3T1 C335KD3W1 C335KD3A1 Price U.S $

Factory Installed Ship Wt. Code Lbs. (kg) Sufx R1 T1 W1 A1 R4 T4 W4 A4 R4 T4 W4 A4 R1 T1 W1 A1 T1B W1B A1B B1B R1 T1 W1 A1 R1 T1 W1 A1 Adder U.S $ 36.25 36.25 36.25 36.25 57.00 57.00 57.00 57.00 62.50 62.50 62.50 62.50 95.50 95.50 95.50 95.50 337.00 337.00 337.00 337.00 130.00 130.00 130.00 130.00 228.00 228.00 228.00 228.00

Non-reversing Kit includes NCI Side Mounted Auxiliary Contact


00 and 0 CN35 A, B, D D15 Relays AF C320KGD1 C320KGD1 C320KGD1 C320KGD1 C320KGD2 C320KGD2 C320KGD2 C320KGD2 C320KGD5 C320KGD5 C320KGD5 C320KGD5 C320KGD3 C320KGD3 C320KGD3 C320KGD3 C320KGD3 C320KGD3 C320KGD3 C320KGD3 C320KGD1 C320KGD1 C320KGD1 C320KGD1 C320KGD3 C320KGD3 C320KGD3 C320KGD3 39.25 1.0 (.5) 39.25 39.25 39.25 65.00 1.0 (.5) 65.00 65.00 65.00 65.00 1.0 (.5) 65.00 65.00 65.00 97.00 2.0 (.9) 97.00 * 97.00 457.00 2.5 (1.1) 457.00 457.00 457.00 39.25 1.0 (0.9) 39.25 39.25 39.25

AF 00 and 0 CN35 A, B, D D15 Relays 1 and 2 CN35 G GK

3 CN35 K

LN

4 and 5 CN35 N, S

PS

Reversing
00 and 0 CN35 A, B, D D15 Relays 1 and 2 CN35 G AF

GK

These kits are supplied with a NO/NCI side mounted auxiliary contact in place of the NCI contact. Kit does not include mechanical interlock or crossover wiring. Two NO/NCI top mounted auxiliary contacts are supplied for electrical interlocking. Factory installed DC coils on NEMA contactors and starters include a NO/NC top mounted auxiliary contact on each contactor for electrical interlocking. On IEC contactors and starters, a NC top mounted auxiliary contact is supplied on each contactor for electrical interlocking. Available factory assembled only. Two required per reversing assembly. *Please contact your local Eaton sales ofce. Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0367]

34-103

Accessories

A1 Hold NCI 3 Pick-Up

A2

A1 Hold

A2 Top

Important Incoming DC must be connected between A1 and Top A2 Terminal. Auxiliary Contact

Metal Mounting Plates

2 2 NO 3 Pick-Up NO 3 A2 Bottom DC Coil Elementary Diagram for NEMA Sizes 1 3 and IEC Sizes G N Contactors and Starters

NCI

34

DC Coil Elementary Diagram for NEMA Sizes 00, 0, 4 & 5 and IEC Sizes A F & P S Contactors and Starters

Figure 34-44. Elementary Diagrams


1NO available in Sufx 4 kits only.

Table 34-167. For Use on IEC Style Contactors, Starters and Overload Relays
Application Contactors IEC Sizes A F IEC Sizes G K Non-reversing Starters IEC Sizes A F IEC Sizes G K Overload Relays 32A 75A
3.06 (77.7)

Remote Reset Module (32A Overload Relay)


The C316RR remote reset module for the C316F, C316S and C316U overload relays allows remote resetting of tripped (32A) overload relays by means of an electrical solenoid attachment which mounts on the side of the overload relay.
1.97 (50.1)

Catalog Number C321MP1 C321MP2 C321MP3 C321MP4 C321MP5 C321MP6 C321MP7 C321MP12 C321MP11 C321MP8 C321MP9 C321MP13

Price U.S. $ 13.00 21.60 21.60 34.75 13.00 21.60 34.75 51.50 80.00 25.75 34.75 *

Table 34-166. Product Selection


Remote Reset Module Operating Voltage 24V 50/60 Hz 110V 50/60 Hz Catalog Number C316RR1U C316RR1A Price U.S. $ 53.50 *

Reversing Starters IEC Sizes A F IEC Sizes G K IEC Sizes L N Reversing Contactors IEC Sizes A F IEC Sizes G K IEC Sizes L N

For use with DIN rail and base mounting adapters listed on Page 34-91.
3.89 (98.7) 3.08 (78.3) 2.51 (63.7) 1.48 (37.7)

For dimensions, see Page 34-104.


*Please contact your local Eaton sales ofce.

1.71 (43.5)

.96 (24.5)

.47 (12)

2.62 (66.5)

Note The operating coil is not suitable for a continuous duty. Recommended impulse duration .2 .35 seconds with 15 operations maximum per hour.

Figure 34-45. Remote Reset Module Approximate Dimensions in Inches (mm)

Discount Symbol (Remote Reset) . . . . . . . . 1CD7 Discount Symbol (Mounting Plates) . . . . . . 1CD1C CA08102001E For more information visit: www.EatonElectrical.com

34-104

IEC Contactors & Starters Freedom


June 2005

Accessories
Table 34-168. Metal Mounting Plates Approximate Dimensions and Shipping Weights
Catalog Number C321MP1 C321MP2 C321MP3 C321MP4 C321MP5 C321MP6 C321MP7 C321MP8 C321MP9 C321MP11 C321MP12 C321MP13 Dimensions in Inches (mm) Wide 2.00 (50.8) 2.56 (65.0) 1.80 (45.7) 2.56 (65.0) 1.77 (45.0) 2.52 (64.0) 4.20 (106.7) 4.20 (106.7) 5.66 (143.8) 8.70 (221.0) 5.71 (145.0) 8.70 (221.0) High 3.88 (98.6) 5.05 (128.3) 6.60 (167.6) 8.08 (205.2) 4.63 (117.6) 5.14 (130.6) 7.38 (187.5) 4.35 (110.5) 5.05 (128.3) 11.35 (288.3) 8.08 (205.2) 7.17 (182.1) Mounting 1.50 x 3.38 (38.1 x 85.9) 2.00 x 4.50 (50.8 x 114.3) 6.07 (154.2) 2.00 x 7.63 (50.8 x 193.8) 4.27 (108.5) 2.00 x 4.59 (50.8 x 116.6) 3.50 x 6.87 (88.9 x 174.5) 3.50 x 3.86 (88.9 x 98.0) 5.25 x 3.63 (133.4 x 92.2) 7.00 x 10.81 (177.8 x 274.6) 5.25 x 6.75 (133.4 x 171.5) 7.00 x 6.63 (177.8 x 168.4) Ship Wt. Lbs. (kg) .2 (.1) .4 (.2) .7 (.3) .6 (.3) .3 (.1) .4 (.2) .8 (.4) .5 (.2) .8 (.4) 1.2 (.5) .9 (.4) .9 (.4)

Vol. 2, Ref. No. [0368]

34

2-hole mounting. 3-hole mounting.

3-Pole Top Mounted Fuse Block Kit


IEC Sizes A K, NEMA Sizes 00 2
Field mount to Freedom Series starters and contactors. Designed to save space and reduce installation costs. They provide short circuit protection for branch circuits. Table 34-170. Fuse Block Kit Approximate Dimensions
Fuse Block Class G H J R T Catalog Number 30A 250V 30A 250V 15A 300V 20A 300V 30A 300V 60A 300V C350KH21 C350KR21 C350KG37 C350KG38 C350KG31 C350KG32 C350KT31 C350KT32 C350KJ61 C350KJ62 C350KM61 C350KC63 C350KT61 C350KT62 Price U.S. $ 82. 96. 104. 104. 104. 156. * * 133. 156. 82. 82. 121. 133. Dimensions in Inches (mm) High B Deep C D Amperes Volts Wide A 15, 20, 30 300 60 300 30 30, 60 30 30, 60 30 60 250 600 600 250 300 600 600 2.40 (61.0) 2.62 (66.5) 3.00 (76.2) 2.40 (61.0) 3.00 (76.2)

3.00 (76.2) 2.04 (51.8) 4.25 (108.0) 2.08 (52.8) 3.10 (78.7) 3.00 (76.2) 3.10 (78.7) 2.23 (56.6) 3.62 (91.9) 2.04 (51.8) 2.23 (56.6) 3.62 (91.9) 2.33 (59.2) 2.26 (57.4) 2.58 (65.5)

4.81 (122.2) 4.12 (104.6) 2.82 (71.6)

M, CC 30

Table 34-169. Selection Product


Fuse Type Class H Class R Class G Class G Class G Class G Class T Class T Class J Class J Type M Class CC Class T Class T

3.44 (87.4) 3.00 (76.2) 3.75 (95.3) 3.31 (84.1) 4.87 (123.7) 3.00 (76.2)

D A

30A 300V 60A 300V 30A 600V 60A 600V 30A 600V 30A 600V

30A 600V 60A 600V

Mounting Plate

Type M fuse block not approved for branch circuit protection. *Please contact your local Eaton sales ofce.

Figure 34-46. Fuse Block Kit Approximate Dimensions

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0369]

34-105

Accessories

Mechanical Interlock and Reversing Kits


Mechanical interlocks and reversing kits are designed for eld assembly of reversing contactors or starters from Freedom Series components. The Reversing Kits include a Mechanical Interlock, stabilizer bar and a pre-cut, trimmed and formed wire set. Auxiliary contacts, if required, must be ordered separately. See Page 34-100.

Solid-State Timers
Solid-State ON DELAY Timer Side Mounted on Freedom Series NEMA 00 2, IEC A K and C25D, C25E and C25F Frame
This timer is designed to be wired in SERIES with the load (typically a coil). When the START button is pushed (power applied to timer), the ON DELAY timing function starts. At the completion of the set timing period, timer and series wired load will both be energized. Table 34-173. Product Selection Mounted Timer
Timing Range .1 1.0 Seconds 1 30 Seconds 30 300 Seconds 5 30 Minutes Catalog Number C320TDN1_ C320TDN30_ C320TDN300_ C320TDN2000_ Price U.S. $ 109.00 109.00 109.00 *

34

Cat. No. C321KM60B

Part No. 23-7165

Wire Set

Table 34-171. Reversing Kits (Horizontal Contactor Mounting Only)


Application NEMA Size 00 0 1 2 3 4 5 IEC Size AC DF GK L and M N PS Catalog Number C321KM60K14B C321KM60K13B C321KM60K15B C321KM60K16B C321KM60K17 C321KM60K21 C321KM60K18 C321KM60K19 C321KM60K20 C321KM60K44 Price U.S. $ 43.00 43.00 65.00 65.00 86.50 86.50 86.50 86.50 86.50 86.50

Add operating voltage Sufx to Catalog Number. A = 120V, B = 240V, E = 208V Rated .5 ampere pilot duty not to be used on larger contactors. Terminal connections are quick connects only. Two per side.

Shorting Bar Kits


These kits provide phase-to-phase power connections of contactors for eld assembly. The kits include bus connections and mounting hardware. The shorting bars connect all three phases of a single contactor. Table 34-174. Product Selection
Description NEMA Size 3, IEC Sizes L N NEMA Size 4, IEC Sizes P S NEMA Size 5 NEMA Size 6, IEC Sizes T and U Catalog Number C321SB18 C321SB19 C321SB21 C321SB22 Price U.S. $ 21.60 25.75 * *

Kit includes (2) NC auxiliary contacts.

Table 34-172. Mechanical Interlock Only


Application NEMA Size 00 2 3 3 to 4 4 4 to 5 4 to 6 5 5 to 6 6 6 to 7 7 4 or 5 to 5 5 to 6 6 6 to 7 IEC Size AK LN N to P PS S to T/U T and U T/U to V X V, W and X P S to 5 T and U T/U to V X Contactor Mounting Horizontal Horizontal Horizontal Horizontal Horizontal Horizontal Horizontal Horizontal Horizontal Horizontal Horizontal Vertical Vertical Vertical Vertical Catalog Number Price U.S. $

C321KM60B C321KM30 C321KM43 C321KM40 C321KM45 C321KM80 C321KM50 C321KM56 C321KM70 C321KM90 C321KM34 C321KM55 C321KM65 C321KM66 C321KM67

19.30 65.00 70.50 65.00 65.00 86.50 65.00 * 86.50 86.50 331.00 63.00 70.50 83.00 *

Pneumatic Timers Top Mounted


Attachment mounts on top of any NEMA Size 00 2 or IEC Size A K Freedom Series starter or contactor (top mounted auxiliary contacts can not be installed on device when timer is used). Timer unit has 1NO-1NC isolated timed contacts circuits in each pole must be the same polarity. Units are convertible from OFF to ON DELAY or vice-versa. Table 34-175. Maximum Ampere Ratings
Description Volts AC 120 Make Break 30 3 240 15 1.5 480 7.5 .75 600 6 .6

Table 34-176. Product Selection


Timing Range .1 to 30 Seconds 10 to 180 Seconds Catalog Number C320TP1 C320TP2 Price U.S. $ 207.00 207.00

Without cross-wiring. For use with latest series product.

*Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C CA08102001E For more information visit: www.EatonElectrical.com

34-106

IEC Contactors & Starters Freedom


June 2005

Accessories

Vol. 2, Ref. No. [0370]

Locking Cover for Overload Relay C306 Only


Snap-on transparent or opaque plastic panel for covering access port to the overload relay trip setting dial helps prevent accidental or unauthorized changes to trip and reset setting. Table 34-177. Product Selection
Description Min. Ordering Catalog Qty. (Std. Pkg.) Number 50 50 50 50 50 C320PC3 C320PC4 C320PC5 C320PC6 C320PC7 Price U.S. $ 1.15 1.15 1.15 * 1.15

Adapter to DIN Rail Mount


NEMA 1 2 and IEC G K Contactors
Designed to allow DIN rail mounting of NEMA 1 2 and IEC G K contactors. Includes all hardware required to convert contactors from panel mounting to 35 mm DIN rail mounting. Table 34-181. Product Selection
Catalog Number C320DN65 Price U.S. $ 24.00

34
Clear cover, no accessibility Gray cover, no accessibility, with Auto only nib Gray cover, no accessibility, with Manual only nib Gray cover with FLA dial accessibility, A, B, C, D positions an Auto only nib Gray cover with FLA dial accessibility, A, B, C, D positions and Manual only nib

Transient Suppressor Kits


NEMA Sizes 00 2, IEC Sizes A K
These kits limit high voltage transients produced in the control circuit when power is removed from the contactor or starter coil. There are three separate suppressors for use on 24 120V, 208 240V or 277 480V coils respectively.

Control Circuit Fuse Block


These panel mounted fuse holders, designed for control circuit protection or other similar low current requirements, have extractor type fuse caps. The Class CC rejection type fuses (KTK-R) used in these holders are intended for use with equipment designated as being suitable for use on systems having high available fault currents. If branch circuit protective device is 45A or greater, C320FBR fuse kit may be required for control circuit protection per NEC 430-72. Table 34-178. Product Selection
Type Fuse Holder Only Max. Amperes 15 30 Catalog Number C320FB C320FBR Price U.S. $ 21.60 43.00

DIN Rail Mounting Channel 35 mm


Designed for DIN rail mounting of IEC style contactors and starters.
Cat. No. C320TS2

DIN Rail

Table 34-179. Product Selection


Description 1 Meter Length Catalog Number MC382MA1 Price U.S. $ 8.65

These devices mount directly to the coil terminals of Freedom Series contactors or starters NEMA Sizes 00 2, IEC Sizes A K and lighting contactors 10 60A. Reversing devices will require two. Table 34-182. Product Selection
Description Coil Voltage 50/60 Hz 24 120V 208 240V 277 480V Catalog Number C320TS1 C320TS2 C320TS3 Price U.S. $ 51.50 51.50 51.50

Finger Protection Shields


Snap-on shields for both contactors and starters provide IEC Type IP20 Finger Protection. Prevents accidental contact with line/load terminals. Table 34-180. Product Selection
Application NEMA Size 00, IEC Sizes A C NEMA Size 0, IEC Sizes D F Catalog Number C320LS1 C320LS2 Price U.S. $ 4.45 4.45

Transient Suppressor

A fuse is not supplied, but holder will accept a Bussman Type KTK or KTK-R (13/32" x 1-1/2") fuse, 600V maximum. Includes a 5A, 600V KTK-R fuse.

Suppressor is compatible with coil voltages/ ranges as shown, 50 and 60 Hz.

NEMA Sizes 3 5, IEC Sizes L S


This device mounts on top of any side mounted auxiliary contact on Freedom Series NEMA Sizes 3 5, IEC Sizes L S and lighting contactors 100 300A. It connects across coil terminals on any 120V contactor or starter magnet coil (reversing starters or contactors require 2). Limits high voltage transients produced in the circuit when power is removed from the coil. Table 34-183. Product Selection
Description Transient Suppressor Coil Voltage 120V Catalog Number C320AS1 Price U.S. $ 74.50

1.88 (47.8) 1.25 (31.8) .97 (24.6)

.88 1.19 (22.4) (30.2) Fuse

NEMA Sizes 1 2, IEC Sizes G K Contactors Reversing Contactors NEMA Size 1 Starters Reversing Starters

C320LS3 C320LS4 C320LS5 C320LS6

5.90 8.65 5.90 *

2.06 (52.3)

NEMA Size 2, IEC Sizes G K Starters Reversing Starters

C320LS7 C320LS8

5.90 *

*Please contact your local Eaton sales ofce.

Figure 34-47. Approximate Dimensions in Inches (mm)


For more information visit: www.EatonElectrical.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0371]

34-107

Accessories

DC/AC Interface Module


The Catalog Number C320DC Interface Module is an optically isolated solid-state switch which provides a means of operating AC coils with a 5 48V DC control signal. It Cat. No. acts as a space saving C320DC interposing relay which can switch a specied 50/60 Hz AC source to the contactor or starter coil. The module may be directly attached to the coil terminals of any Freedom Series contactor or starter NEMA Sizes 00 3, IEC Sizes A N and lighting contactors 10 100A. It also has provisions for DIN rail mounting. The module will operate coils within the voltage ranges shown below.

Adhesive Dust Cover


NEMA Sizes 00 2, IEC Sizes A K
These adhesive stickers come 25 to a package and provide extra protection from contaminants when applied to the sides of Freedom NEMA Sizes 00 2 and IEC Sizes A K. Adhesive covers are easily applied to side opening where auxiliaries are not installed and provide extra protection from metal lings and other debris. Table 34-186. Product Selection
Catalog Number C320DSTCVR (25 to a package) Price U.S. $ *

34

Add-On Power Pole Kit


NEMA Sizes 00 2, IEC A K
This device mounts on the side of Freedom NEMA Size 00 2 and IEC Size A K contactors. One unit can be mounted on each side and carries UL, cUL and IEC ratings. The device is rated for resistive, inductive and lighting applications. Table 34-187. Product Selection Add-On Power Pole Kit
UL Ampere Rating Inductive Resistive hp 600V 600V 1-Phase IEC 947 Ampere Rating Locked Lighting AC-1 Rotor Ballast 600V Tungsten 115V 230V 240V 480V 1/2 2 96 20 20 AC-3 600V AC-5a AC-5b 480V 18 1NO Power Pole Catalog Number C320PPD10 Price U.S. $

Design Characteristics

DC Input: 5 48V DC 10% at mA nominal AC Operating Voltage: 240V AC max. (360 VA) 10% 50/60 Hz DC Operating Voltage: 30V DC max. (5A) AC Current Rating: 10A make (inrush) 1A break (sealed) Table 34-184. Controller Coil Voltage Ranges
Controller Catalog Number Prex AE16, AE17, AE56, AE57, CE15, CE55 AN16, AN56, CN15, CN55 CN35 Controller Coil Size or Range Rating Volts AC AF GK LN 00 0 12 3 10 30A 60A 100A 24 240 48 240 110 240 24 _ 240 48 240 110 240 24 240 48 240 110 240

15

20

12

36.25

Special Modications
Table 34-188. For Catalog Numbers AE16, AE17, AN16, AE56, AE57, AN56, CE15, CN15, CN35, CE55, CN55
Addition or Special Feature Starter Size and Price Adder (U.S. $) NEMA/IEC 00/ AC 0/ DF 1 2/ 3/ GK LN 4/ PS 5/ TU 6/ V 7/ W, X 8/ Z

Control Circuit
Extra Auxiliary Circuit, Factory Installed NO or NC each contact Transient Suppressor

Power Circuit
Contactor/Starter for Ring Lug Capability Add Mod Code T16 to Catalog Number (Power Terminals Only, Control Terminals as Standard) Stand-Alone Overload Relays Cannot Accept Ring Lugs on Line Side.

Factory Installed Dust Covers


Factory Installed C320DSTCVR Add Mod Code -53 to Catalog Number NA NA NA NA NA NA

Contactor Coil 5 48V DC Input Observe Polarity on Module 24 240V AC 50/60 Hz

Solid-State Switch

These modications are generally available in Kit form at lower cost. See specic product sections for Kit listings. Consult factory for price. *Please contact your local Eaton sales ofce.

Figure 34-48. Typical Application Table 34-185. Product Selection


Coil Voltage 6V DC 9V DC 12V DC 24V DC 48V DC Catalog Number C320DC2V6 C320DC2V9 C320DC2V12 C320DC2V24 C320DC2V48 Price U.S. $ * * * * *

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C CA08102001E For more information visit: www.EatonElectrical.com

34-108

IEC Contactors & Starters Freedom


June 2005

Renewal Parts
Table 34-189. For Catalog Numbers AE16, AE17, AE56, AE57, CE15 and CE55 IEC Frames A F
Description IEC Frames AF Series A1 Part No. Renewal Parts Publication Number None 9-2650-1 9-2650-2 9-2650-3 9-2650-4 9-2650-5 9-2650-13 9-2650-12 9-2650-6 9-2650-7 9-2650-14 9-2650-9 9-2650-8 9-2650-10 86. 86. 86. * 86. 86. * 86. 86. 86. * * * 9-2875-1 9-2875-2 9-2875-3 9-2875-4 9-2875-5 9-2875-12 9-2875-37 9-2875-11 9-2875-6 9-2875-36 9-2875-13 9-2875-16 9-2875-8 9-2875-9 9-2875-1 9-2875-2 9-2875-3 9-2875-4 9-2875-5 9-2875-12 9-2875-37 9-2875-11 9-2875-6 9-2875-36 9-2875-13 9-2875-16 9-2875-8 9-2875-9 Price U.S. $ IEC Frames AC Series B1 Part No. None Series C1 Part No. None 86. 86. 86. 86. 86. 86. 86. 86. 86. 86. 86. 86. 86. 86. 9-2876-1 9-2876-2 9-2876-3 9-2876-4 9-2876-5 9-2876-12 9-2876-37 9-2876-11 9-2876-6 9-2876-36 9-2876-13 9-2876-16 9-2876-8 9-2876-9 9-2876-1 9-2876-2 9-2876-3 9-2876-4 Price U.S. $ IEC Frames DF Series B1 Part No. None

Vol. 2, Ref. No. [0372]

Price U.S. $ Series C1 Part No. None 86. 86. 86. 86. 86. 86. 86. 86. 86. 86. 86. 86. 86. 86.

34

Contact Kits
2-Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Magnet Coils
120V 60 Hz or 110V 50 Hz 240V 60 Hz or 220V 50 Hz 480V 60 Hz or 440V 50 Hz 600V 60 Hz or 550V 50 Hz 208V 60 Hz . . . . . . . . . . . . . 277V 60 Hz . . . . . . . . . . . . . 208/240V 60 Hz . . . . . . . . . . 240V 50 Hz . . . . . . . . . . . . . 380 415V 50 Hz . . . . . . . . . 24V 60 Hz 24V 50 Hz 24V 60 Hz . . . . . . . . . . . . . . . 24V 50 Hz . . . . . . . . . . . . . . . 32V 50 Hz . . . . . . . . . . . . . . . 48V 60 Hz . . . . . . . . . . . . . . . 48V 50 Hz . . . . . . . . . . . . . . .

Coil Sufx
A B C D E H J K L T T U V W Y

9-2876-1 9-2876-2 9-2876-37 9-2876-3 9-2876-4 9-2876-36 9-2876-13 9-2876-16 9-2876-8 9-2876-9

Overload Relays
For replacement on existing starters: 3-Pole Ambient Compensated Bimetallic . . . . . . . . . . . .

C306DN3B

90. C306DN3B

C306DN3B

90. C306DN3B

C306DN3B

90.

Current Transformer
Transformer . . . . . . . . . . . . . . . . . . . . . . . .

Magnet Frame Armature


Lower Magnet Frame . . . . . . . . . . . . . . . . Upper Magnet Frame . . . . . . . . . . . . . . . . Non-encapsulated coils. Replace with complete contactor. *Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0373]

34-109

Renewal Parts

Note: For a complete listing of parts, refer to the Renewal Parts Publication Number referenced below.

Table 34-190. For Catalog Numbers AE16, AE17, AE56, AE57, CE15 and CE55 IEC Frames G and H
Description IEC Frame G Series A1 Part No. Renewal Parts Publication Number 20862 6-65-3 6-65-4 6-65-11 6-65-12 9-2703-1 9-2703-2 9-2703-3 9-2703-4 9-2703-9 9-2703-7 9-2703-14 9-2703-8 9-2703-6 9-2703-12 9-2703-10 9-2703-11 9-2703-13 Series B1 Part No. 22178 6-65-3 6-65-4 6-65-11 6-65-12 9-2703-1 9-2703-2 9-2703-3 9-2703-4 9-2703-9 9-2703-7 9-2703-14 9-2703-8 9-2703-6 9-2703-12 9-2703-10 9-2703-11 9-2703-13 117.00 175.00 233.00 289.00 102.00 102.00 * 102.00 102.00 102.00 * 102.00 102.00 102.00 * 102.00 102.00 Price U.S. $ IEC Frame H Series A1 Part No. 20862 6-65-5 6-65-6 6-65-13 6-65-14 9-2703-1 9-2703-2 9-2703-3 9-2703-4 9-2703-9 9-2703-7 9-2703-14 9-2703-8 9-2703-6 9-2703-12 9-2703-10 9-2703-11 9-2703-13 Series B1 Part No. 22178 6-65-5 6-65-6 6-65-13 6-65-14 9-2703-1 9-2703-2 9-2703-3 9-2703-4 9-2703-9 9-2703-7 9-2703-14 9-2703-8 9-2703-6 9-2703-12 9-2703-10 9-2703-11 9-2703-13 127.00 189.00 252.00 313.00 102.00 102.00 * 102.00 102.00 102.00 * 102.00 102.00 102.00 * 102.00 102.00 Price U.S. $

Contact Kits
2-Pole 3-Pole 4-Pole 5-Pole ............................. ............................. ............................. .............................

34

Magnet Coils
120V 60 Hz or 110V 50 Hz 240V 60 Hz or 220V 50 Hz 480V 60 Hz or 440V 50 Hz 600V 60 Hz or 550V 50 Hz 208V 60 Hz . . . . . . . . . . . . . . 277V 60 Hz . . . . . . . . . . . . . . 240V 50 Hz . . . . . . . . . . . . . . 380 415V 50 Hz . . . . . . . . . 24V 60 Hz 24V 50 Hz 24V 60 Hz . . . . . . . . . . . . . . . 24V 50 Hz . . . . . . . . . . . . . . . 32V 50 Hz . . . . . . . . . . . . . . . 48V 60 Hz . . . . . . . . . . . . . . . 48V 50 Hz . . . . . . . . . . . . . . .

Coil Sufx
A B C D E H K L T T U V W Y

Overload Relays
For replacement on existing starters: 3-Pole Ambient Compensated Bimetallic . . . . . . . . . . . .

C306GN3B 17-18200 48-1936

C306GN3B 17-18200 48-1936

157.00 C306GN3B 23.50 17-18200 21.80 48-1936

C306GN3B 17-18200 48-1936

157.00 23.50 21.80

Current Transformer
Transformer . . . . . . . . . . . . . . . . . . . . . . . .

Magnet Frame Armature


Lower Magnet Frame . . . . . . . . . . . . . . . . Upper Magnet Frame . . . . . . . . . . . . . . . .

*Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C CA08102001E For more information visit: www.EatonElectrical.com

34-110

IEC Contactors & Starters Freedom


June 2005

Renewal Parts
Note: For a complete listing of parts, refer to the Renewal Parts Publication Number referenced below.

Vol. 2, Ref. No. [0374]

Table 34-191. For Catalog Numbers AE16, AE17, AE56, AE57, AE800, CE15 and CE55 IEC Frames J and K
Description IEC Frame J Series A1 Part No. Renewal Parts Publication Number 20862 6-65-7 6-65-8 6-65-15 6-65-16 9-2703-1 9-2703-2 9-2703-3 9-2703-4 9-2703-9 9-2703-7 9-2703-14 9-2703-8 9-2703-6 9-2703-12 9-2703-10 9-2703-11 9-2703-13 Series B1 Part No. 22178 6-65-7 6-65-8 6-65-15 6-65-16 9-2703-1 9-2703-2 9-2703-3 9-2703-4 9-2703-9 9-2703-7 9-2703-14 9-2703-8 9-2703-6 9-2703-12 9-2703-10 9-2703-11 9-2703-13 157.00 233.00 308.00 * 102.00 102.00 * 102.00 102.00 102.00 * 102.00 102.00 102.00 * 102.00 102.00 Price U.S. $ IEC Frame K Series A1 Part No. 20862 6-65-18 6-65-19 9-2703-1 9-2703-2 9-2703-3 9-2703-4 9-2703-9 9-2703-7 9-2703-14 9-2703-8 9-2703-6 9-2703-12 9-2703-10 9-2703-11 9-2703-13 Series B1 Part No. 22178 6-65-18 6-65-19 9-2703-1 9-2703-2 9-2703-3 9-2703-4 9-2703-9 9-2703-7 9-2703-14 9-2703-8 9-2703-6 9-2703-12 9-2703-10 9-2703-11 9-2703-13 163.00 * 102.00 102.00 * 102.00 102.00 102.00 * 102.00 102.00 102.00 * 102.00 102.00 Price U.S. $

34

Contact Kits
2-Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Magnet Coils
120V 60 Hz or 110V 50 Hz 240V 60 Hz or 220V 50 Hz 480V 60 Hz or 440V 50 Hz 600V 60 Hz or 550V 50 Hz 208V 60 Hz . . . . . . . . . . . . . 277V 60 Hz . . . . . . . . . . . . . 240V 50 Hz . . . . . . . . . . . . . 380 415V 50 Hz . . . . . . . . . 24V 60 Hz 24V 50 Hz 24V 60 Hz . . . . . . . . . . . . . . . 24V 50 Hz . . . . . . . . . . . . . . . 32V 50 Hz . . . . . . . . . . . . . . . 48V 60 Hz . . . . . . . . . . . . . . . 48V 50 Hz . . . . . . . . . . . . . . .

Coil Sufx
A B C D E H K L T T U V W Y

Overload Relays
For replacement on existing starters: 3-Pole Ambient Compensated Bimetallic . . . . . . . . . . . .

C306GN3B 17-18200 48-1936

C306GN3B 17-18200 48-1936

157.00 C306GN3B 23.50 17-18200 21.80 48-1936

C306GN3B 17-18200 48-1936

157.00 23.50 21.80

Current Transformer
Transformer . . . . . . . . . . . . . . . . . . . . . . . .

Magnet Frame Armature


Lower Magnet Frame . . . . . . . . . . . . . . . . Upper Magnet Frame . . . . . . . . . . . . . . . .

*Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0375]

34-111

Renewal Parts

Note: For a complete listing of parts, refer to the Renewal Parts Publication Number referenced below.

Table 34-192. For Catalog Numbers AE16, AE17, AE56, AE57, AE800, CE15 and CE55 IEC Frames L N
Description Renewal Parts Publication Number IEC Frame L Part No. 20427 6-43-3 6-43-4 9-2756-1 9-2756-2 9-2756-3 9-2756-4 9-2756-5 9-2756-9 9-2756-13 9-2756-12 9-2756-8 9-2756-14 9-2756-6 9-2756-11 9-2756-10 9-2756-15 9-2756-7 254.00 380.00 165.00 165.00 165.00 165.00 165.00 165.00 165.00 Price U.S. $ IEC Frame M Part No. 20427 6-43 6-43-2 9-2756-1 9-2756-2 9-2756-3 9-2756-4 9-2756-5 9-2756-9 9-2756-13 254.00 380.00 165.00 165.00 165.00 165.00 165.00 165.00 165.00 Price U.S. $ IEC Frame N Part No. 20427 6-43-5 6-43-6 9-2756-1 9-2756-2 9-2756-3 9-2756-4 9-2756-5 9-2756-9 9-2756-13 254.00 380.00 165.00 165.00 165.00 165.00 165.00 165.00 165.00 165.00 165.00 * 165.00 165.00 165.00 * * Price U.S. $

Contact Kits
2-Pole 3-Pole 4-Pole 5-Pole ............................. ............................. ............................. .............................

34

Magnet Coils
120V 60 Hz or 110V 50 Hz 240V 60 Hz or 220V 50 Hz 480V 60 Hz or 440V 50 Hz 600V 60 Hz or 550V 50 Hz 208V 60 Hz . . . . . . . . . . . . . . 277V 60 Hz . . . . . . . . . . . . . . 240V 50 Hz . . . . . . . . . . . . . . 380 450V 50 Hz . . . . . . . . . 340V 60 Hz . . . . . . . . . . . . . . 415V 60 Hz . . . . . . . . . . . . . . 550V 50 Hz . . . . . . . . . . . . . . 24V 60 Hz 24V 50 Hz 24V 60 Hz . . . . . . . . . . . . . . . 24V 50 Hz . . . . . . . . . . . . . . . 32V 50 Hz . . . . . . . . . . . . . . . 48V 60 Hz . . . . . . . . . . . . . . . 48V 50 Hz . . . . . . . . . . . . . . .

Coil Sufx
A B C D E H K L L M N T T U V W Y

165.00 9-2756-12 165.00 9-2756-8 * 9-2756-14 165.00 165.00 165.00 * * 9-2756-6 9-2756-11 9-2756-10 9-2756-15 9-2756-7

165.00 9-2756-12 165.00 9-2756-8 * 9-2756-14 165.00 165.00 165.00 * * 9-2756-6 9-2756-11 9-2756-10 9-2756-15 9-2756-7

Overload Relays
For replacement on existing starters: 3-Pole Ambient Compensated Bimetallic . . . . . . . . . . . .

10-6530 17-8955-2 48-1902

268.00 10-6530-2 56.50 17-8955-2 23.20 48-1902

268.00 10-6530-3 56.50 17-8955-2 23.20 48-1902

268.00 56.50 23.20

Current Transformer
Transformer . . . . . . . . . . . . . . . . . . . . . . . .

Magnet Frame Armature


Lower Magnet Frame . . . . . . . . . . . . . . . . Upper Magnet Frame . . . . . . . . . . . . . . . .

*Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C CA08102001E For more information visit: www.EatonElectrical.com

34-112

IEC Contactors & Starters Freedom


June 2005

Renewal Parts
Note: For a complete listing of parts, refer to the Renewal Parts Publication Number referenced below.

Vol. 2, Ref. No. [0376]

Table 34-193. For Catalog Number CE15 Contactors IEC Frames P S


Description Renewal Parts Publication Number Contact Kits Size IEC Frame P Part No. 22278 6-294 9-1891-1 9-1891-2 9-1891-3 9-1891-4 9-1891-13 9-1891-26 9-1891-20 9-1891-14 9-1891-21 9-1891-15 Price U.S. $ IEC Frame R Part No. 22278 725.00 6-288 177.00 177.00 177.00 177.00 177.00 177.00 177.00 177.00 177.00 177.00 9-1891-1 9-1891-2 9-1891-3 9-1891-4 9-1891-13 9-1891-26 9-1891-20 9-1891-14 9-1891-21 9-1891-15 Price U.S. $ IEC Frame S Part No. 22278 725.00 6-286 177.00 177.00 177.00 177.00 177.00 177.00 177.00 177.00 177.00 177.00 9-1891-1 9-1891-2 9-1891-3 9-1891-4 9-1891-13 9-1891-26 9-1891-20 9-1891-14 9-1891-21 9-1891-15 725.00 177.00 177.00 177.00 177.00 177.00 177.00 177.00 177.00 177.00 177.00 Price U.S. $

34

Magnet Coils
120V 60 Hz or 110V 50 Hz. . . . 200V 50 Hz or 118V 60 Hz. . . . 240V 60 Hz or 220V 50 Hz. . . . 254V 50 Hz or 277V 60 Hz. . . . 380V 50 Hz or 415V 60 Hz. . . . 480V 60 Hz or 440V 50 Hz. . . . 600V 60 Hz or 550V 50 Hz. . . . 208V 60 Hz . . . . . . . . . . . . . . . 277V 60 Hz . . . . . . . . . . . . . . . 240V 50 Hz . . . . . . . . . . . . . . . 380V 50 Hz . . . . . . . . . . . . . . . 415V 50 Hz . . . . . . . . . . . . . . . 24V 60 Hz . . . . . . . . . . . . . . . . .

Coil Sufx
A E B H L C D E H K L M T

Overload Relays Reference C316 Overload Relays Magnet Frame Armature


Lower Magnet Frame . . . . . . . . . . . . . . . . . . . . Upper Magnet Frame . . . . . . . . . . . . . . . . . . . . 48-1030 48-1029-2 * 48-1030 * 48-1029-2 * 48-1030 * 48-1029-2 * *

Table 34-194. For Catalog Number CE15 Contactors IEC Frames T V


Description Renewal Parts Publication Number Contact Kits Size IEC Frame T Part No. 22275 6-621 9-3006 9-3006-5 9-3006-2 9-3006-6 9-3006-7 9-3006-3 9-3006-4 Price U.S. $ IEC Frame U Part No. 22276 2,190.00 6-622 825.00 * 825.00 * 825.00 825.00 825.00 9-3006 9-3006-5 9-3006-2 9-3006-6 9-3006-7 9-3006-3 9-3006-4 Price U.S. $ IEC Frame V Part No. 22586 2,935.00 6-601 825.00 * 825.00 * 825.00 825.00 825.00 9-2698 9-2698-2 9-2698-2 9-2698-6 9-2698-3 9-2698-4 9-2698-5 3,990.00 1,175.00 1,175.00 1,175.00 * 1,175.00 1,175.00 1,175.00 Price U.S. $

Magnet Coils
120V 60 Hz or 110V 50 Hz. . . . 200V 50 Hz or 118V 60 Hz. . . . 240V 60 Hz or 220V 50 Hz. . . . 254V 50 Hz or 277V 60 Hz. . . . 380V 50 Hz or 415V 60 Hz. . . . 480V 60 Hz or 440V 50 Hz. . . . 600V 60 Hz or 550V 50 Hz. . . . 208V 60 Hz . . . . . . . . . . . . . . . 277V 60 Hz . . . . . . . . . . . . . . . 240V 50 Hz . . . . . . . . . . . . . . . 380V 50 Hz . . . . . . . . . . . . . . . 415V 50 Hz . . . . . . . . . . . . . . . 24V 60 Hz . . . . . . . . . . . . . . . . .

Coil Sufx
A E B H L C D E H K L M T

Overload Relays Reference C316 Overload Relays Magnet Frame Armature


Lower Magnet Frame . . . . . . . . . . . . . . . . . . . . Upper Magnet Frame . . . . . . . . . . . . . . . . . . . . IEC Size T Series A1 Series B1 9-3007 9-3007-2 9-3007-3 9-3007-4 9-3007-5 9-3007-7 9-3007-6 Price U.S. $ IEC Size U Series A1 Series B1 9-3007 9-3007-2 9-3007-3 9-3007-4 Price U.S. $ IEC Size V Series A1 Series B1 9-2705 9-2705-2 9-2705-3 9-2705-4 Price U.S. $

Feeder Group Renewal


Volts Hertz

110 120 220 240 440 480 550 600 208 380 415 48 52

50/60 50/60 50/60 50/60 50/60 50/60 50/60

1,025.00 1,025.00 1,025.00 1,025.00

1,025.00 1,025.00 1,025.00 1,025.00

1,095.00 1,095.00 1,095.00 1,095.00 * * *

1,025.00 9-3007-5 * 9-3007-7 1,025.00 9-3007-6

1,025.00 9-2705-5 * 9-2705-6 1,025.00 9-2705-8

Voltage ratings of the main coils must match those of the feeder group for proper operation of the starter/contactor. *Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0377]

34-113

Renewal Parts

Note: For a complete listing of parts, refer to the Renewal Parts Publication Number referenced below.

Table 34-195. For Catalog Number CE15 Contactors IEC Frames W Z


Description Renewal Parts Publication Number Contact Kits Size IEC Frame W Part No. 22586 6-601 9-2698 9-2698-2 9-2698-6 9-2698-3 9-2698-4 9-2698-5 Price U.S. $ IEC Frame X Part No. 3,990. 6-613 1,175. 1,175. * 1,175. 1,175. 1,175. 9-2698 9-2698-2 9-2698-6 9-2698-3 9-2698-4 9-2698-5 Price U.S. $ IEC Frame Z Part No. 22586 5,410. 6-571 1,175. 1,175. * 1,175. 1,175. 1,175. 9-2654 9-2654-2 9-2654-5 9-2654-3 9-2654-4 9-2654-6 6,570. 1,935. * * * * * Price U.S. $

Magnet Coils
120V 60 Hz or 110V 50 Hz . . . . 200V 50 Hz or 118V 60 Hz . . . . 240V 60 Hz or 220V 50 Hz . . . . 254V 50 Hz or 277V 60 Hz . . . . 380V 50 Hz or 415V 60 Hz . . . . 480V 60 Hz or 440V 50 Hz . . . . 600V 60 Hz or 550V 50 Hz . . . . 208V 60 Hz . . . . . . . . . . . . . . . . 277V 60 Hz . . . . . . . . . . . . . . . . 240V 50 Hz . . . . . . . . . . . . . . . . 380V 50 Hz . . . . . . . . . . . . . . . . 415V 50 Hz . . . . . . . . . . . . . . . . 24V 60 Hz . . . . . . . . . . . . . . . .

Coil Sufx
A E B H L C D E H K L M T

34

Overload Relays Reference C316 Overload Relays Magnet Frame Armature


Lower Magnet Frame . . . . . . . . . . . . . . . . . . . . Upper Magnet Frame . . . . . . . . . . . . . . . . . . . . IEC Size W Series A1 Series B1 9-2705 9-2705-2 9-2705-3 9-2705-4 9-2705-5 9-2705-6 9-2705-8 Price U.S. $ 1,095. 1,095. 1,095. 1,095. IEC Size X Series A1 Series B1 9-2705 9-2705-2 9-2705-3 9-2705-4 Price U.S. $ 1,095. 1,095. 1,095. 1,095. IEC Size Z Series A1 Series B1 9-2664 9-2664-2 9-2664-3 9-2664-4 Price U.S. $ * * * * * *

Feeder Group Renewal


Volts Hertz

110 120 220 240 440 480 550 600 208 380 415 48 52

50/60 50/60 50/60 50/60 50/60 50/60 50/60

* 9-2705-5 * 9-2705-6 * 9-2705-8

* 9-2664-6 * 9-2664-5 *

Voltage ratings of the main coils must match those of the feeder group for proper operation of the starter/contactor. *Please contact your local Eaton sales ofce.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C CA08102001E For more information visit: www.EatonElectrical.com

34-114

IEC Contactors & Starters Freedom


June 2005

Dimensions

Vol. 2, Ref. No. [0378]

Non-reversing Contactors
Table 34-196. Approximate Dimensions and Shipping Weights Open Type
IEC Size Number of Poles 24 23 23 4 5 23 23 Dimensions in Inches (mm) Wide A 1.80 (45.7) 1.80 (45.7) 2.56 (65.0) 3.44 (87.4) 4.32 (109.7) 4.08 (103.6) 7.05 (179.1) High B 2.96 (75.2) 2.96 (75.2) 4.27 (108.5) 4.27 (108.5) 4.27 (108.5) 7.17 (182.1) 9.11 (231.4) Deep C 3.25 (82.6) 3.25 (82.6) 4.22 (107.2) 4.22 (107.2) 4.22 (107.2) 5.94 (150.9) 7.25 (184.2) Mounting D 1.36 (34.5) 1.36 (34.5) 2.17 (55.1) 2.17 (55.1) 2.17 (55.1) 3.00 (76.2) 6.00 (152.4) E 1.96 (49.8) 1.96 (49.8) 3.74 (95.0) 3.74 (95.0) 3.74 (95.0) 6.63 (168.4) 8.50 (215.9) 4.49 (114.0) 4.49 (114.0) 5.58 (141.7) 5.58 (141.7) 5.58 (141.7) .54 (13.7) .54 (13.7) .54 (13.7) .54 (13.7) .54 (13.7) .54 (13.7) F G Ship. Wt. Lbs. (kg) 1.3 (.6) 1.4 (.6) 2.8 (1.3) 3.2 (1.5) 3.6 (1.6) 8.5 (3.9) 20.0 (9.1)

34

AC DF GK GJ GJ LN PS

F C

F C

A U X

Top Mtd. Aux.

A U X

E E1

Top Mtd. Aux.

Side Mtd. Aux.

A U X

Top Mtd. Aux.

A U X

Top Mtd. Aux.

Side Mtd. Aux.

D Mtg. Holes for M4 or #8 Screws Auxiliary Contacts

D Mtg. Holes for #10-32 Screws Auxiliary Contacts

IEC Sizes A F, 2- and 3-Pole Sizes A C, 4-Pole

IEC Sizes G K, 2- and 3-Pole

F C

F C

A U X

Top Mtd. Aux.

A U X

Top Mtd. Aux.

Side Mtd. Aux.

A U X

Top Mtd. Aux.

A U X

Top Mtd. Aux.

Side Mtd. Aux.

D Mtg. Holes for #10-32 Screws Auxiliary Contacts

D Mtg. Holes for #10-32 Screws Auxiliary Contacts

IEC Sizes G J, 4-Pole

IEC Sizes G J, 5-Pole

A U X

Side Mtd. Aux.

Mtg. Holes for (3) Screws IEC Sizes L N

Mtg. Holes for (3) Screws IEC Sizes P S

Figure 34-49. Approximate Dimensions

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0379]

34-115

Dimensions

Table 34-197. Approximate Dimensions and Shipping Weights Open Type


IEC Size Dimensions in Inches (mm) Wide A 8.63 (219.2) 8.63 (219.2) 11.20 (284.5) 11.02 (279.9) 13.00 (330.2) High B 12.50 (317.5) 13.54 (343.9) 16.19 (411.2) 19.30 (490.2) 24.50 (622.3) B1 Deep C 8.88 (225.6) 8.88 (225.6) 11.50 (292.1) 11.48 (291.6) 13.62 (345.9) Mounting D 4.33 (110.0) 4.33 (110.0) 6.88 (174.8) 6.89 (175.0) 4.72 (119.9) E 8.63 (219.2) 8.63 (219.2) 11.02 (279.9) 11.02 (279.9) 14.96 (380.0) Ship. Wt. Lbs. (kg) 29 (13.2) 30 (13.6) 85 (38.6) 100 (45.4) 160 (72.6)

T U V&W X Z

9.17 (232.9) 10.16 (258.1) 12.13 (308.1) 14.16 (359.7) 19.25 (489.0)

34

Mtg. Holes for (2) 5/16-18 Screws C

Mtg. Holes for (2) 3/8-16 Screws

B1

B1

D A

Mtg. Slots for (2) 5/16-18 Screws

D A

Mtg. Slots for (2) 3/8-16 Screws

IEC Sizes T and U

IEC Sizes V and W

Mtg. Holes for (2) 3/8-16 Screws

Mtg. Holes for (4) 1/2-13 Screws

B1 E

B1

D A

Mtg. Slots for (2) 3/8-16 Screws

D A

IEC Size X

IEC Size Z

Figure 34-50. Approximate Dimensions

CA08102001E

For more information visit: www.EatonElectrical.com

34-116

IEC Contactors & Starters Freedom


June 2005

Dimensions

Vol. 2, Ref. No. [0380]

Reversing Contactors
Table 34-198. Approximate Dimensions and Shipping Weights Open Type
IEC Size Dimensions in Inches (mm) Wide A 4.20 (106.7) 5.71 (145.0) 8.70 (221.0) High B 2.96 (75.2) 5.05 (128.3) 7.17 (182.1) Deep C 3.28 (83.3) 4.44 (112.8) 5.94 (150.9) Mounting D 2.36 (59.9) 5.25 (133.4) 7.00 (177.8) E 1.96 (49.8) 3.63 (92.2) 6.63 (168.4) .54 (13.7) .54 (13.7) .54 (13.7) G Ship. Wt. Lbs. (kg) 2.6 (1.2) 10.1 (4.6) 17.0 (7.7)

34

AF GK LN

F G A G C G A G

A U X

Top Mtd. Aux.

Top Mtd. Aux.

A U E E1 X

Top Mtd. Aux.

Side Mtd. Aux.

A U X

Top Mtd. Aux.

Top Mtd. Aux.

A U X E

Top Mtd. Aux.

Side Mtd. Aux.

.21 (5.3)

Auxiliary Mtg. Holes for Contacts M4 or #8 Screws IEC Sizes A F

D Mtg. Holes for (3) #10-32 Screws

Auxiliary Contacts IEC Sizes G K

.24 (6.1) G A C

B E

Mtg. for (3) 1/4-20 Screws IEC Sizes L N

Figure 34-51. Approximate Dimensions


See catalog listings for type and location of auxiliary contacts supplied with particular contactor.

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0381]

34-117

Dimensions

Non-reversing Fixed Heater Starters


Table 34-199. Approximate Dimensions and Shipping Weights Open Type
IEC Size Dimensions in Inches (mm) Wide A 1.80 (45.7) 2.56 (65.0) 4.36 (110.7) 7.37 (187.2) High B 5.32 (135.1) 7.12 (180.8) 12.12 (307.8) 16.01 (406.7) B1 1.50 (38.1) Deep C 3.66 (93.0) 4.65 (118.1) 5.89 (149.6) 7.31 (185.7) Mounting D 1.36 (34.5) 2.00 (50.8) 1.77 (45.0) 3.00 (76.2) D1 3.00 (76.2) 6.00 (152.4) E 1.96 (49.8) 6.63 (168.4) 10.81 (274.6) 8.50 (215.9) E1 2.36 (59.9) 3.54 (89.9) 4.66 (118.4) 5.83 (148.1) .55 (14) .54 (13.7) .54 (13.7) F G Ship. Wt. Lbs. (kg) 1.8 (.8) 4.0 (1.8) 12.0 (5.4) 36.0 (16.3)

AF GK LN PS

34

A D Top Mtd. Aux. B For #8 or M4 Mtg. Screws C B1 .13 (3.3) D

Top A Mtd. U Aux. X

Top Mtd. Aux.

Side Mtd. Aux. B

E1

A U X E

Top Mtd. Aux.

Side Mtd. Aux.

Size F Terminal Optional Block Auxiliary Contacts

C Optional Auxiliary Contacts IEC Starters Sizes G K

3 Mtg. Holes for M5 or #10-32 Screws

IEC Starters Sizes A F

F D C

Mtg. Holes for (3) 1/4-20 Screws D

Side Mtd. Aux. B E

E B

D1 A

Mtg. Holes for (3) 1/4-20 Screws

D1 A

Non-reversing Starter AE17 IEC Series L N

Non-reversing Starter AE17 IEC Series P S

Figure 34-52. Approximate Dimensions

CA08102001E

For more information visit: www.EatonElectrical.com

34-118

IEC Contactors & Starters Freedom


June 2005

Dimensions

Vol. 2, Ref. No. [0382]

Non-reversing Fixed Heater Starters (Continued)


Table 34-200. Approximate Dimensions and Shipping Weights Open Type
IEC Size Dimensions in Inches (mm) Wide A 9.47 (240) 15.11 (384) 15.11 (384) 15.11 (384) High B 21.69 (551) 27.51 (698) 29.15 (740) 33.54 (852) B1 Deep C 9.90 (251) 12.69 (322) 12.66 (321) 14.80 (368) Mounting D 3.10 (79) 13.25 (336) 13.25 (336) 13.25 (336) D1 E 18.00 (457) 21.25 (540) 21.25 (540) 16.75 (425) E1 F G Ship. Wt. Lbs. 75.0 (34.1) 90.0 (40.9) 120.0 (54.5) 210.0 (95.3)

34

TU VW X Z

D D C

B E B E

A IEC Starters Sizes T U

A IEC Starters Sizes V W

E B E B

A IEC Starters Size X

A IEC Starters Size Z

Figure 34-53. Approximate Dimensions

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0383]

34-119

Dimensions

Reversing Fixed Heater Starters


Table 34-201. Approximate Dimensions and Shipping Weights Open Type
IEC Size Dimensions in Inches (mm) Wide A 4.13 (104.9) 5.71 (145.0) 8.44 (214.4) High B 5.88 (149.4) 7.12 (180.8) 12.11 (307.6) Deep C 3.30 (83.8) 4.42 (112.3) 5.89 (149.6) Mounting D 3.72 (94.5) 5.25 (133.4) 3.81 (96.8) D1 7.00 (177.8) E 2.36 (59.9) 5.75 (146.1) 10.81 (274.6) E1 1.00 (25.4) 4.90 (124.5) 5.83 (148.1) .55 (14.0) .54 (13.7) .54 (13.7) F G Ship. Wt. Lbs. (kg) 2.9 (1.3) 8.3 (3.8) 20.0 (9.1)

AF GK LN

34

F C

D E1

Top Mtd. Aux.

Side Auxiliary Contact B

Optional Auxiliary Contacts Size F Terminal Block IEC Sizes A F G A G F C

Mtg. Holes for M4 or #8 Screws

Top Mtd. Aux. E Optional Auxiliary Contacts Mtg. Holes for (3) #10 Screws D IEC Sizes G K

Side Auxiliary Contact B

E1

Side Mtd. Aux. B E

Mtg. Holes for (3) 1/4-20 Screws D1 A Reversing Starter AE57 IEC Series L N

Figure 34-54. Approximate Dimensions


CA08102001E For more information visit: www.EatonElectrical.com

34-120

IEC Contactors & Starters Freedom


June 2005

Dimensions

Vol. 2, Ref. No. [0384]

Non-reversing Interchangeable Heater Overload Starters


Table 34-202. Approximate Dimensions and Shipping Weights Open Type
IEC Size Dimensions in Inches (mm) Wide A 1.80 (45.7) 2.56 (65.0) 4.00 (101.6) 7.37 (187.2) 9.47 (240.0) 15.11 (384.0) 15.11 (384.0) 15.11 (384.0) High B 5.86 (148.8) 8.08 (205.2) 11.35 (288.3) 16.01 (406.7) 21.69 (551.0) 27.51 (698.0) 29.15 (740.0) 33.54 (852.0) Deep C 3.28 (83.3) 4.44 (112.8) 5.94 (150.9) 7.25 (184.2) 9.90 (251.0) 12.69 (322.0) 12.66 (321.0) 14.80 (368.0) Mounting D 1.36 (34.5) 2.00 (50.8) 3.00 (76.2) 3.00 (76.2) 3.10 (79.0) 13.25 (336.0) 13.25 (336.0) 13.25 (336.0) D1 6.00 (152.4) E 5.19 (131.8) 7.63 (193.8) 10.81 (274.6) 8.50 (215.9) 18.00 (457.0) 21.25 (540.0) 21.25 (540.0) 16.75 (425.0) E1 5.39 (136.9) 4.66 (118.4) 5.80 (147.3) .54 (13.7) .54 (13.7) 4.08 (103.6) F G Ship. Wt. Lbs. 1.8 (.8) 4.0 (1.8) 11.0 (5.0) 36.0 (16.3) 75.0 (34.1) 90.0 (40.9) 120.0 (54.5) 210.0 (95.3)

34

AF GK LN PS TU VW X Z

F C

F C

A Top U Mtd. X Aux.

A U X

E E1

Top Mtd. Aux.

Side Mtd. Aux.

A U X

Top Mtd. Aux.

A U X

Top Mtd. Aux.

Side Mtd. Aux.

A U X

Aux. Cont.

Auxiliary Contacts .18 x .3 (4.6 x 7.6) Slot D Mtg. Holes for M4 or #8 Screws .13 (3.3) D

Auxiliary Contacts Mtg. Holes for #10-32 Screws D A Mtg. Holes for (3) 1/4-20 Screws

IEC Starters Sizes A F

IEC Starters Sizes G K

IEC Starters Sizes L N

Mtg. Holes for (3) 1/4-20 Screws

D D C

E B B E E B

D1 A IEC Starters Sizes P S

A A IEC Starters Sizes T U IEC Starters Sizes V W

E B

A IEC Starters Size X

A IEC Starters Size Z

Figure 34-55. Approximate Dimensions


For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom


June 2005
Vol. 2, Ref. No. [0385]

34-121

Dimensions

Reversing Interchangeable Heater Overload Starters


Table 34-203. Approximate Dimensions and Shipping Weights Open Type
IEC Size Dimensions in Inches (mm) Wide High A B 4.20 (106.7) 5.71 (145.0) 8.70 (221.0) 5.90 (149.9) 8.08 (205.2) 11.35 (288.3) Deep C 3.28 (83.3) 4.44 (112.8) 5.94 (150.9) Mounting D 2.36 (59.9) 5.25 (133.4) 7.00 (177.8) F E 5.39 (136.9) 6.75 (171.5) 10.81 (274.6) E1 5.19 (131.8) 4.66 (118.4) 5.80 (147.3) .54 (13.7) .54 (13.7) G Ship. Wt. Lbs. (kg) 2.9 (1.3) 8.3 (3.8) 20.0 (9.1)

AF GK LN

34

A D

F C

A U X E E1

Top Mtd. Aux.

Top Mtd. Aux.

A 1.96 2.36 U (49.8) (59.9) X

Top Mtd. Aux.

Side Mtd. Aux. B

Mtg. Holes for M4 or #8 Screws .21 (5.3) D

Auxiliary Contacts

.18 x .3 (4.6 x 7.6) Slot

IEC Sizes A F G A G F C

A U X

Top Mtd. Aux.

Top Mtd. Aux.

A U X E

Top Mtd. Aux.

Side Mtd. Aux. B

.13 (3.3)

Auxiliary Contacts

Mtg. Holes for (3) #10-32 Screws IEC Sizes G K

.24 (6.1)

Mtg. Holes for (3) 1/4-20 Screws D IEC Sizes L N

Figure 34-56. Approximate Dimensions


See catalog listings for type and location of auxiliary contacts supplied with particular contactor.

CA08102001E

For more information visit: www.EatonElectrical.com

34-122

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Product Family Overview

Vol. 2, Ref. No. [0386]

Contents
Description Page Product Family Overview Product Description . . . . . . . . . . . . 34-122 Standards and Certications . . . . . . . . . . . 34-123 Options . . . . . . . . . . . . . . . . . 34-123 Cover Control . . . . . . . . . . . . 34-124 Catalog Number Selection . . . . . . . . . . . . . . 34-125 Contactors. . . . . . . . . . . . . . . . . 34-126 Non-combination Starters . . . . . . . . . . . . . . . . . . 34-130 Fusible Combination Starters . . . . . . . . . . . . . . . . . . 34-138 Combination GMCP Starters . . . . . . . . . . . . . . . . . . 34-146 Modication Codes . . . . . . . . . 34-49 Dimensions . . . . . . . . . PG03300001E

34

Type 1 Non-combination Starter Catalog Number ECE0511ABA

Type 1 Combination Starter Catalog Number ECE25A1AJB-R8

Product Description
The Cutler-Hammer Freedom Line of Enclosed Control from Eatons electrical business includes IEC Contactors and Starters with xed heaters, interchangeable heaters and solidstate overload relays.

Non-reversing

Interchangeable Heater Starters

Highest horsepower rating in compact, space-saving designs. 45 mm frame rated maximum 20 hp at 460V, 65 mm frame rated maximum 50 hp, and 90 mm frame rated maximum 100 hp. Bimetallic ambient compensated overload relays available in three sizes, covering applications up to 100 hp. These overload relays feature: Selectable manual or automatic reset operation. Interchangeable heater packs adjustable 24% to match motor FLA and calibrated for 1.0 and 1.15 service factors. Heater packs for smaller overload relay will mount in larger overload relay useful in derating applications such as jogging. Overload trip indication. Electrically isolated NO-NC contacts (pull RESET button to test).

IP20 nger protection shields available. Contactor and terminal markings conform to CENELEC EN50011. One NO right-side mounted auxiliary contact supplied as standard on Sizes A N (on Sizes A C, contact occupies 4th power pole no increase in width). Three basic starter frame widths 45 mm, 65 mm and 90 mm.

Reversing

Sizes A through M have a wired NO-NC side mounted electrical interlock on each contactor. A full line of snap-on accessories top and side mounted auxiliary contacts, solid-state and pneumatic timers, etc. Straight-through wiring line lugs at top, load lugs at bottom. Screw-type power terminals have captive, backed-out, self-lifting pressure plates with screws reduced wiring time.

Long life twin break, silver cadmium oxide contacts provide excellent conductivity and superior resistance to welding and arc erosion. Designed to 2,000,000 electrical and 20,000,000 mechanical operations through 20 hp at 460V. Adequate for most general duty motor control applications.

For more information visit: www.EatonElectrical.com

CA08102001E

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0387]

34-123

Product Family Overview Non-reversing

Fixed Heater Starters

Standards and Certications


IEC 947-4-1 compliance International Standard for low voltage switchgear and control devices. UL listed and CSA certied. C316 bimetallic ambient compensated overload relays available in three basic sizes, covering applications up to 150 hp. These overload relays feature: Direct heated bimetal elements Class 10. Single-phase and phase unbalance sensitivity. Ambient temperature compensated. Adjustable trip current. Overload trip indication and contact test lever. Manual/automatic reset. Electrically isolated NO-NC contacts. Long life twin break, silver cadmium oxide contacts provide excellent conductivity and superior resistance to welding and arc erosion. Designed to 2,000,000 electrical and 20,000,000 mechanical operations through 20 hp at 460V. Adequate for most general duty motor control applications.

Highest horsepower rating in compact, space-saving designs. 45 mm frame rated maximum 20 hp at 460V, 65 mm frame rated maximum 50 hp, 90 mm frame rated maximum 100 hp, and 180 mm frame rated maximum 150 hp. NO side mounted auxiliary contact supplied as standard on Sizes A N. Sizes P and R have NO-NC contacts. Four basic starter frame widths 45 mm, 65 mm, 90 mm and 180 mm.

UL Listed cUL Listed (indicates appropriate CSA Standard investigation) ABS Type Approved CE Mark available

34

Options

Reversing

Highest horsepower rating in compact, space-saving designs. 45 mm frame rated maximum 20 hp at 460V, 65 mm frame rated maximum 50 hp at 460V, and 90 mm frame rated a maximum 75 hp at 460V. Sizes A through K have a wired NO-NC top mounted electrical interlock on each contactor. Sizes L through M have one NO-NC side mounted electrical interlock on each contactor. Table 34-204. Plugging and Jogging Service Horsepower Ratings
Size 200V 1 1-1/2 2 3 5 5 7-1/2 7-1/2 10 15 20 230V 1 1-1/2 2 3 5 7-1/2 10 10 15 20 25 460V 2 3 5 7-1/2 10 15 20 25 30 40 50 575V 3 5 7-1/2 10 15 20 25 30 40 40 50

Solid-State Overload Relay with Freedom Contactor

Solid-State Overload Relay


IEC Style
B C D E F G H J K L M

Self powered Phase loss protection Class 10 or Class 20 Manual or automatic reset Visible trip indicator 1NO and 1NC isolated contacts Ambient compensated Test button Wide adjustment range (3.2:1) 1% repeats accuracy Current adjustment knob

Available thru Size N. See Page 34-49 for this and other Modication Codes.

Maximum horsepower where operation is interrupted more than 5 times per minute, or more than 10 times in a 10 minute period.

CA08102001E

For more information visit: www.EatonElectrical.com

34-124

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Product Family Overview

Vol. 2, Ref. No. [0388]

Cover Control
Non-combination Starters
For Non-combination Starter Cover Control, see Page 33-99.

Table 34-206. Combination Starter Cover Control


Description Factory Installed Position 9 CombiCover nation Control Only Code Adder U.S. $ * * * * * * * * * * CE400T01 CE400T02 CE400T03 CE400T04 CE400T05 CE400T06 CE400T10 CE400T11 CE400T12 CE400T07 * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Field Kits Catalog Number Price U.S. $

34

Combination Starters

Kits for J Enclosure Non-reversing


START/STOP Pushbuttons (PB) START/STOP PB & Red RUN Light START/STOP PB, Red RUN, & Green STOPPED Light HAND/OFF/AUTO Selector Switch (SS) H-O-A SS & Red RUN Light H-O-A SS, Red RUN, & Green STOPPED Light Red RUN Pilot Light Green Off Pilot Light Red RUN/Green OFF Pilot Light ON/OFF Selector Switch (SS) ON/OFF SS, Red RUN Light ON/OFF SS, Red RUN, & Green STOPPED Light B C D H J K P Q R S T U B C D H J K P Q R S T U B C D H J K V W X

Cover control for Combination Starters uses E22 style (22 mm). Selector switches are maintained with lever operators. Pushbuttons are momentary type with extended pushbutton. The kit includes hardware and connecting wires (where possible). For factory installed control devices other than shown below, refer to Modication Codes, Page 34-49. Use Table 34-205 to nd the correct enclosure for the starter size and type.
Enclosures J K L Starter Size

* CE400T08 * CE400T09 * * * * * * * * * * CE400T21 CE400T22 CE400T23 CE400T24 CE400T25 CE400T26 CE400T10 CE400T11 CE400T12 CE400T27

Kits for K and L Enclosure Non-reversing


START/STOP Pushbuttons (PB) START/STOP PB & Red RUN Light START/STOP PB, Red RUN, & Green STOPPED Light HAND/OFF/AUTO Selector Switch (SS) H-O-A SS & Red RUN Light H-O-A SS, Red RUN, & Green STOPPED Light Red RUN Pilot Light Green OFF Pilot Light Red RUN/Green OFF Pilot Light ON/OFF Selector Switch (SS) ON/OFF SS, Red RUN Light ON/OFF SS, Red RUN, & Green STOPPED Light

Table 34-205. Combination Starter Enclosures


Catalog Number

ECE16 ECE17 ECE18 ECE19 ECE20 ECE21 ECE22 ECE23 ECE24 ECE25 ECE26

AE AE AE AE AE AF AF AF

AE AF AF

FH FH FH FH FH FH GH GH GH GH GH

* CE400T28 * CE400T29 * * * * * * * * * CE400T50 CE400T51 CE400T52 CE400T53 CE400T54 CE400T55 CE400T56 CE400T57 CE400T58

Kits for Full Voltage Reversing (All)


FWD/REV/STOP Pushbuttons (PB) FWD/REV/STOP PB + Red FWD & REV Lights FWD/REV/STOP PB, Red FWD/REV, & Green STOPPED FOR/OFF/REV Selector Switch (SS) FOR/OFF/REV SS + Red FWD & REV Lights FOR/OFF/REV SS, Red FWD/REV, & Green STOPPED OPEN/OFF/CLOSE Selector Switch (SS) OPEN/OFF/CLOSE SS + Red FWD & REV Lights OPEN/OFF/CLOSE SS, Red FWD/REV, & Green STOPPED

To include any of the above cover controls, place the control code character in position 9 of your Catalog Number. Example: ECE16A1ADA Full voltage non-reversing fusible starter with interchangeable heater OLR and START/STOP pushbutton with red RUN and green OFF pilot lights. Sufx for lights (required for eld installed kits only) in chart below: Rating 120V 60 Hz 208V 60 Hz 240V 60 Hz Catalog Rating Sufx A E B 277V 60 Hz 380V 50 Hz 460V 60 Hz 600V 60 Hz Catalog Sufx H L C D

Figure 34-57. Cover Control


Maximum (4) 22 mm Devices

*Please contact your local Eaton sales ofce.

Figure 34-58. Cover Control


Maximum (6) 22 mm Devices

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0389]

34-125

Product Family Overview

Catalog Number Selection


Table 34-207. IEC Enclosed Control Catalog Numbering System

EC E
Design E = Freedom IEC Class 01 = FVNR Contactors 02 = Reversing Contactors 05 = FVNR Starter, Non-combination, Interchangeable Heater OLR 06 = Reversing Starter, Non-combination, Interchangeable Heater OLR 09 = FVNR Starter, Non-combination, Fixed Heater OLR 10 = Reversing Starter, Non-combination, Fixed Heater OLR 16 = Fusible Switch, Interchangeable Heater O.L. Relay FVNR 17 = Fusible Switch, Interchangeable Heater O.L. Relay FVR 19 = Fusible Switch, Fixed Heater O.L. Relay FVNR 20 = Fusible Switch, Fixed Heater O.L. Relay FVR 22 = GMCP, Interchangeable Heater O.L. Relay FVNR 23 = GMCP, Interchangeable Heater O.L. Relay FVR 25 = GMCP, Fixed Heater O.L. Relay FVNR 26 = GMCP, Fixed Heater O.L. Relay FVR Frame Size Combination (Class 16 74) IEC Size A H A= B= C= D= E= F= G= Page 34-126 34-128 34-130 34-132 34-134 34-136 34-138 34-140 34-142 34-144 34-146 34-148 34-150 34-152

05 D 1 A A A Modification Codes (See Page 34-49) Disconnect Fuse Clip Ratings A= B= C= E= None 30A/600V CC 30A/600V J 60A/600V J GMCP Ratings A= B= C= D= E= F= None 3A 7A 15A 30A 50A

34

Cover Control (Starters Only) (See Pages 33-99, 34-124) Number of Poles (Contactors Only) Coil Voltage and/or Control Transformer (See Tables Below)

Non-combination (Class 01 11) Ampere Rating (UL 600V) 7A 10A 12A 18A 25A 32A 37A H= J= K= L= M= N= P= 44A 60A 73A 85A 105A 140A 170A R= S= T= U= V= 200A 300A 420A 520A 550A

Enclosure Type 1 2 3 4 6 8 9 = = = = = = = Type 1 General Purpose Type 3R Rainproof Type 4 Painted Steel Type 4X Watertight (304-Grade Stainless Steel) Type 7/9 Explosion Proof Type 12 Dust-Tight Type 4X Watertight (316-Grade Stainless Steel)

GMCP Type Disconnect Maximum Rating 480V (use Fusible for 575/600V).

Table 34-209. Control Power Transformer Codes (System Voltage)


Code Primary Magnet Coil 24/50 32/50 48/60 104 120/60 48/50 By Description B C D E H L M Q R Secondary Code Primary S T U V W X Y Z Secondary 240/480 220/440 120/60 Wired for 240V 110/50 240/480 220/440 120/60 Wired for 480V 110/50 600/60 550/50 120/60 110/50 208/60 120/60 277/60 120/60 380/50 110/50 415/50 110/50 208/60 24 240/480 220/440 24 Wired for 240V 240/480 220/440 24 Wired for 480V 600/60 24 277/60 24 380/50 24 415/50 24 240/480/600 120 Wired for 480V 240/480/600 24 Wired for 480V By Description

Table 34-208. Magnet Coil Codes (System Voltage)


Code A B C D E G H J Magnet Coil 120/60 110/50 240/60 220/50 480/60 440/50 600/60 550/50 208/60 550/50 277/60 208 240/60 Code K L M P Q R S T Magnet Coil 240/50 380/50 415/50 12V DC 24V DC 48V DC 125V DC 24/60 Code U V W X Y Z

When control power transformer modication codes (C1 C11) are used or when starter class includes CPT (i.e. ECE07, 18) see Table 34-209 for system voltage code.

CA08102001E

For more information visit: www.EatonElectrical.com

34-126

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Contactors

Vol. 2, Ref. No. [0390]

Product Selection
Table 34-210. Class ECE01/CE15 IEC Rated Non-reversing
Max. General Purpose UL Amp. Rating 600V AC 7 IEC 947 AC-1 Thermal Current 600V Maximum Horsepower Motor Volt. 1-Ph 3-Ph Magnet Coil Voltage (60 Hz) 3-Pole Type 1 General Purpose Catalog Number Price U.S. $ 3-Pole Type 3R Rainproof Catalog Number Price U.S. $ 3-Pole Component Contactor (Open) Catalog Number

34

Frame Size A 45 mm
20 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 ECE01A1A3A ECE01A1E3A ECE01A1B3A ECE01A1C3A ECE01A1D3A ECE01B1A3A ECE01B1E3A ECE01B1B3A ECE01B1C3A ECE01B1D3A ECE01C1A3A ECE01C1E3A ECE01C1B3A ECE01C1C3A ECE01C1D3A ECE01D1A3A ECE01D1E3A ECE01D1B3A ECE01D1C3A ECE01D1D3A ECE01E1A3A ECE01E1E3A ECE01E1B3A ECE01E1C3A ECE01E1D3A ECE01F1A3A ECE01F1E3A ECE01F1B3A ECE01F1C3A ECE01F1D3A ECE01G1A3A ECE01G1E3A ECE01G1B3A ECE01G1C3A ECE01G1D3A * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ECE01A2A3A ECE01A2E3A ECE01A2B3A ECE01A2C3A ECE01A2D3A ECE01B2A3A ECE01B2E3A ECE01B2B3A ECE01B2C3A ECE01B2D3A ECE01C2A3A ECE01C2E3A ECE01C2B3A ECE01C2C3A ECE01C2D3A ECE01D2A3A ECE01D2E3A ECE01D2B3A ECE01D2C3A ECE01D2D3A ECE01E2A3A ECE01E2E3A ECE01E2B3A ECE01E2C3A ECE01E2D3A ECE01F2A3A ECE01F2E3A ECE01F2B3A ECE01F2C3A ECE01F2D3A ECE01G2A3A ECE01G2E3A ECE01G2B3A ECE01G2C3A ECE01G2D3A * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * CE15ANS3AB CE15ANS3EB CE15ANS3BB CE15ANS3CB CE15ANS3DB CE15BNS3AB CE15BNS3EB CE15BNS3BB CE15BNS3CB CE15BNS3DB CE15CNS3AB CE15CNS3EB CE15CNS3BB CE15CNS3CB CE15CNS3DB CE15DNS3AB CE15DNS3EB CE15DNS3BB CE15DNS3CB CE15DNS3DB CE15ENS3AB CE15ENS3EB CE15ENS3BB CE15ENS3CB CE15ENS3DB CE15FNS3AB CE15FNS3EB CE15FNS3BB CE15FNS3CB CE15FNS3DB CE15GNS3AB CE15GNS3EB CE15GNS3BB CE15GNS3CB CE15GNS3DB

Frame Size B 45 mm
10 20

Frame Size C 45 mm
12 20

Frame Size D 45 mm
18 32

Frame Size E 45 mm
25 32

Frame Size F 45 mm
32 32

Frame Size G 65 mm
37 50

For denitions of AC-1, AC-2 and AC-3 ratings, see Page 34-99. Maximum horsepower rating of contactors for 380V 50 Hz applications: IEC Size A B C D E F G H J K L M N Horsepower 3 5 5 10 10 15 20 25 30 40 50 60 75

IEC Sizes A N are supplied with a NO side mounted auxiliary contact. On IEC Sizes A C, the 4th power pole position is used as the side mounted contact. IEC Sizes H V are available. Contact Eaton. For additional coil voltages, see Page 34-125.

Contactors available in other poles. 2-Pole Sizes A N 4-Pole Sizes A C, G H, J 5-Pole Sizes G H, J To order these, change the 9th Catalog Number digit to 2, 4 or 5; i.e. Size C, 120V, 2-pole, Type 1 Enclosure would be ECE01C1A2A. *Please contact your local Eaton sales ofce.

Modications . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . For more information visit: www.EatonElectrical.com

Page 34-49 Page 34-95 Page 34-100 PG03300001E 1CD1C CA08102001E

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0391]

34-127

Contactors
(Continued)
3-Pole Type 12 Dust-Tight Industrial External Reset Catalog Number Price U.S. $ 3-Pole Component Contactor (Open) Catalog Number

Table 34-210. Class ECE01/CE15 IEC Rated Non-reversing


Max. General Purpose UL Amp. Rating 600V AC 7 IEC 947 AC-1 Thermal Current 600V Maximum Horsepower Motor Volt. 1-Ph 3-Ph Magnet Coil Voltage (60 Hz)

3-Pole Type 4X Watertight & Dust-Tight Stainless Steel Catalog Number Price U.S. $

Frame Size A 45 mm
20 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 ECE01A4A3A ECE01A4E3A ECE01A4B3A ECE01A4C3A ECE01A4D3A ECE01B4A3A ECE01B4E3A ECE01B4B3A ECE01B4C3A ECE01B4D3A ECE01C4A3A ECE01C4E3A ECE01C4B3A ECE01C4C3A ECE01C4D3A ECE01D4A3A ECE01D4E3A ECE01D4B3A ECE01D4C3A ECE01D4D3A ECE01E4A3A ECE01E4E3A ECE01E4B3A ECE01E4C3A ECE01E4D3A ECE01F4A3A ECE01F4E3A ECE01F4B3A ECE01F4C3A ECE01F4D3A ECE01G4A3A ECE01G4E3A ECE01G4B3A ECE01G4C3A ECE01G4D3A * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ECE01A8A3A ECE01A8E3A ECE01A8B3A ECE01A8C3A ECE01A8D3A ECE01B8A3A ECE01B8E3A ECE01B8B3A ECE01B8C3A ECE01B8D3A ECE01C8A3A ECE01C8E3A ECE01C8B3A ECE01C8C3A ECE01C8D3A ECE01D8A3A ECE01D8E3A ECE01D8B3A ECE01D8C3A ECE01D8D3A ECE01E8A3A ECE01E8E3A ECE01E8B3A ECE01E8C3A ECE01E8D3A ECE01F8A3A ECE01F8E3A ECE01F8B3A ECE01F8C3A ECE01F8D3A ECE01G8A3A ECE01G8E3A ECE01G8B3A ECE01G8C3A ECE01G8D3A * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * CE15ANS3AB CE15ANS3EB CE15ANS3BB CE15ANS3CB CE15ANS3DB CE15BNS3AB CE15BNS3EB CE15BNS3BB CE15BNS3CB CE15BNS3DB CE15CNS3AB CE15CNS3EB CE15CNS3BB CE15CNS3CB CE15CNS3DB CE15DNS3AB CE15DNS3EB CE15DNS3BB CE15DNS3CB CE15DNS3DB CE15ENS3AB CE15ENS3EB CE15ENS3BB CE15ENS3CB CE15ENS3DB CE15FNS3AB CE15FNS3EB CE15FNS3BB CE15FNS3CB CE15FNS3DB CE15GNS3AB CE15GNS3EB CE15GNS3BB CE15GNS3CB CE15GNS3DB

34

Frame Size B 45 mm
10 20

Frame Size C 45 mm
12 20

Frame Size D 45 mm
18 32

Frame Size E 45 mm
25 32

Frame Size F 45 mm
32 32

Frame Size G 65 mm
37 50

For denitions of AC-1, AC-2 and AC-3 ratings, see Page 34-99. Maximum horsepower rating of contactors for 380V 50 Hz applications: IEC Size A B C D E F G H J K L M N Horsepower 3 5 5 10 10 15 20 25 30 40 50 60 75

IEC Sizes A N are supplied with a NO side mounted auxiliary contact. On IEC Sizes A C, the 4th power pole position is used as the side mounted contact. IEC Sizes H V are available. Contact Eaton. For additional coil voltages, see Page 34-125.

Contactors available in other poles. 2-Pole Sizes A N 4-Pole Sizes A C, G H, J 5-Pole Sizes G H, J To order these, change the 9th Catalog Number digit to 2, 4 or 5; i.e. Size C, 120V, 2-pole, Type 1 Enclosure would be ECE01C1A2A. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECE01A4A3A. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. *Please contact your local Eaton sales ofce.

Modications . . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-49 Page 34-95 Page 34-100 PG03300001E 1CD1C

34-128

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Contactors
Table 34-211. Class ECE02/CE55 IEC Rated Reversing
Max. General Purpose UL Amp. Rating 600V AC IEC 947 AC-1 Thermal Current 600V Maximum Horsepower Motor Volt. 1-Ph 3-Ph Magnet Coil Voltage (60 Hz) 3-Pole Type 1 General Purpose Catalog Number Price U.S. $ 3-Pole Type 3R Rainproof Catalog Number Price U.S. $

Vol. 2, Ref. No. [0392]

3-Pole Component Contactor (Open) Catalog Number

34

Frame Size A 45 mm
7 20 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 ECE02A1A3A ECE02A1E3A ECE02A1B3A ECE02A1C3A ECE02A1D3A ECE02B1A3A ECE02B1E3A ECE02B1B3A ECE02B1C3A ECE02B1D3A ECE02C1A3A ECE02C1E3A ECE02C1B3A ECE02C1C3A ECE02C1D3A ECE02D1A3A ECE02D1E3A ECE02D1B3A ECE02D1C3A ECE02D1D3A ECE02E1A3A ECE02E1E3A ECE02E1B3A ECE02E1C3A ECE02E1D3A ECE02F1A3A ECE02F1E3A ECE02F1B3A ECE02F1C3A ECE02F1D3A ECE02G1A3A ECE02G1E3A ECE02G1B3A ECE02G1C3A ECE02G1D3A * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ECE02A2A3A ECE02A2E3A ECE02A2B3A ECE02A2C3A ECE02A2D3A ECE02B2A3A ECE02B2E3A ECE02B2B3A ECE02B2C3A ECE02B2D3A ECE02C2A3A ECE02C2E3A ECE02C2B3A ECE02C2C3A ECE02C2D3A ECE02D2A3A ECE02D2E3A ECE02D2B3A ECE02D2C3A ECE02D2D3A ECE02E2A3A ECE02E2E3A ECE02E2B3A ECE02E2C3A ECE02E2D3A ECE02F2A3A ECE02F2E3A ECE02F2B3A ECE02F2C3A ECE02F2D3A ECE02G2A3A ECE02G2E3A ECE02G2B3A ECE02G2C3A ECE02G2D3A * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * CE55AN3AB CE55AN3EB CE55AN3BB CE55AN3CB CE55AN3DB CE55BN3AB CE55BN3EB CE55BN3BB CE55BN3CB CE55BN3DB CE55CN3AB CE55CN3EB CE55CN3BB CE55CN3CB CE55CN3DB CE55DN3AB CE55DN3EB CE55DN3BB CE55DN3CB CE55DN3DB CE55EN3AB CE55EN3EB CE55EN3BB CE55EN3CB CE55EN3DB CE55FN3AB CE55FN3EB CE55FN3BB CE55FN3CB CE55FN3DB CE55GN3AB CE55GN3EB CE55GN3BB CE55GN3CB CE55GN3DB

Frame Size B 45 mm
10 20

Frame Size C 45 mm
12 20

Frame Size D 45 mm
18 32

Frame Size E 45 mm
25 32

Frame Size F 45 mm
32 32

Frame Size G 65 mm
37 50

For denitions of AC-1, AC-2 and AC-3 ratings, see Page 34-99. Maximum horsepower rating of contactors for 380V 50 Hz applications: IEC Size A B C D E F G H J K L M N Horsepower 3 5 5 10 10 15 20 25 30 40 50 60 75

IEC Sizes H V are available. Contact Eaton. For additional coil voltages, see Page 34-125. *Please contact your local Eaton sales ofce.

Sizes A M have a NO-NC side mounted electrical interlock on each contactor.

Modications . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . For more information visit: www.EatonElectrical.com

Page 34-49 Page 34-95 Page 34-100 PG03300001E 1CD1C CA08102001E

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0393]

34-129

Contactors

Table 34-211. Class ECE02/CE55 IEC Rated Reversing (Continued)


Max. General Purpose UL Amp. Rating 600V AC 7 IEC 947 AC-1 Thermal Current 600V Maximum Horsepower Motor Volt. 1-Ph 3-Ph Magnet Coil Voltage (60 Hz) 3-Pole Type 4X Watertight & Dust-Tight Stainless Steel Catalog Number Price U.S. $ 3-Pole Type 12 Dust-Tight Industrial External Reset Catalog Number Price U.S. $ 3-Pole Component Contactor (Open) Catalog Number

Frame Size A 45 mm
20 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 ECE02A4A3A ECE02A4E3A ECE02A4B3A ECE02A4C3A ECE02A4D3A ECE02B4A3A ECE02B4E3A ECE02B4B3A ECE02B4C3A ECE02B4D3A ECE02C4A3A ECE02C4E3A ECE02C4B3A ECE02C4C3A ECE02C4D3A ECE02D4A3A ECE02D4E3A ECE02D4B3A ECE02D4C3A ECE02D4D3A ECE02E4A3A ECE02E4E3A ECE02E4B3A ECE02E4C3A ECE02E4D3A ECE02F4A3A ECE02F4E3A ECE02F4B3A ECE02F4C3A ECE02F4D3A ECE02G4A3A ECE02G4E3A ECE02G4B3A ECE02G4C3A ECE02G4D3A * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ECE02A8A3A ECE02A8E3A ECE02A8B3A ECE02A8C3A ECE02A8D3A ECE02B8A3A ECE02B8E3A ECE02B8B3A ECE02B8C3A ECE02B8D3A ECE02C8A3A ECE02C8E3A ECE02C8B3A ECE02C8C3A ECE02C8D3A ECE02D8A3A ECE02D8E3A ECE02D8B3A ECE02D8C3A ECE02D8D3A ECE02E8A3A ECE02E8E3A ECE02E8B3A ECE02E8C3A ECE02E8D3A ECE02F8A3A ECE02F8E3A ECE02F8B3A ECE02F8C3A ECE02F8D3A ECE02G8A3A ECE02G8E3A ECE02G8B3A ECE02G8C3A ECE02G8D3A * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * CE55AN3AB CE55AN3EB CE55AN3BB CE55AN3CB CE55AN3DB CE55BN3AB CE55BN3EB CE55BN3BB CE55BN3CB CE55BN3DB CE55CN3AB CE55CN3EB CE55CN3BB CE55CN3CB CE55CN3DB CE55DN3AB CE55DN3EB CE55DN3BB CE55DN3CB CE55DN3DB CE55EN3AB CE55EN3EB CE55EN3BB CE55EN3CB CE55EN3DB CE55FN3AB CE55FN3EB CE55FN3BB CE55FN3CB CE55FN3DB CE55GN3AB CE55GN3EB CE55GN3BB CE55GN3CB CE55GN3DB

34

Frame Size B 45 mm
10 20

Frame Size C 45 mm
12 20

Frame Size D 45 mm
18 32

Frame Size E 45 mm
25 32

Frame Size F 45 mm
32 32

Frame Size G 65 mm
37 50

For denitions of AC-1, AC-2 and AC-3 ratings, see Page 34-99. Maximum horsepower rating of contactors for 380V 50 Hz applications: IEC Size A B C D E F G H J K L M N Horsepower 3 5 5 10 10 15 20 25 30 40 50 60 75

Sizes A M have a NO-NC side mounted electrical interlock on each contactor.

IEC Sizes H V are available. Contact Eaton. For additional coil voltages, see Page 34-125. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECE02A4A3A. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. *Please contact your local Eaton sales ofce.

Modications . . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-49 Page 34-95 Page 34-100 PG03300001E 1CD1C

34-130

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Non-combination Starters

Vol. 2, Ref. No. [0394]

Product Selection
Table 34-212. Class ECE05/AE16 IEC Rated Non-combination C306 Interchangeable Heater OLR Non-reversing
Max. General Purpose UL Ampere Rating 600V AC IEC 947 AC-1 Thermal Current 600V Maximum Horsepower Motor Voltage 1-Ph 3-Ph Magnet Coil Voltage (60 Hz) 3-Pole Type 1 General Purpose Catalog Number Price U.S. $ 3-Pole Type 3R Rainproof Catalog Number Price U.S. $ 3-Pole Component Starter (Open) Catalog Number

34

Size A 45 mm
7 20 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 ECE05A1AAA ECE05A1EAA ECE05A1BAA ECE05A1CAA ECE05A1DAA ECE05B1AAA ECE05B1EAA ECE05B1BAA ECE05B1CAA ECE05B1DAA ECE05C1AAA ECE05C1EAA ECE05C1BAA ECE05C1CAA ECE05C1DAA ECE05D1AAA ECE05D1EAA ECE05D1BAA ECE05D1CAA ECE05D1DAA ECE05E1AAA ECE05E1EAA ECE05E1BAA ECE05E1CAA ECE05E1DAA ECE05F1AAA ECE05F1EAA ECE05F1BAA ECE05F1CAA ECE05F1DAA ECE05G1AAA ECE05G1EAA ECE05G1BAA ECE05G1CAA ECE05G1DAA 233. 233. 233. 233. * 235. * 235. 235. * 279. * 279. 279. * * 300. 300. 300. * 319. * * 319. * * 344. 344. 344. * 520. 520. * 520. * ECE05A2AAA ECE05A2EAA ECE05A2BAA ECE05A2CAA ECE05A2DAA ECE05B2AAA ECE05B2EAA ECE05B2BAA ECE05B2CAA ECE05B2DAA ECE05C2AAA ECE05C2EAA ECE05C2BAA ECE05C2CAA ECE05C2DAA ECE05D2AAA ECE05D2EAA ECE05D2BAA ECE05D2CAA ECE05D2DAA ECE05E2AAA ECE05E2EAA ECE05E2BAA ECE05E2CAA ECE05E2DAA ECE05F2AAA ECE05F2EAA ECE05F2BAA ECE05F2CAA ECE05F2DAA ECE05G2AAA ECE05G2EAA ECE05G2BAA ECE05G2CAA ECE05G2DAA 297. * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * AE16ANS0AC AE16ANS0EC AE16ANS0BC AE16ANS0CC AE16ANS0DC AE16BNS0AC AE16BNS0EC AE16BNS0BC AE16BNS0CC AE16BNS0DC AE16CNS0AC AE16CNS0EC AE16CNS0BC AE16CNS0CC AE16CNS0DC AE16DNS0AC AE16DNS0EC AE16DNS0BC AE16DNS0CC AE16DNS0DC AE16ENS0AC AE16ENS0EC AE16ENS0BC AE16ENS0CC AE16ENS0DC AE16FNS0AC AE16FNS0EC AE16FNS0BC AE16FNS0CC AE16FNS0DC AE16GNS0AC AE16GNS0EC AE16GNS0BC AE16GNS0CC AE16GNS0DC

Size B 45 mm
10 20

Size C 45 mm
12 20

Size D 45 mm
18 32

Size E 45 mm
25 32

Size F 45 mm
32 32

Size G 65 mm
37 50

Starters do not include heater packs. Select 1 carton of 3 heater packs. For Heater Pack Selection, see Page 34-93. Starters with Electronic Overload, see Page 34-55 of Modication Codes. For denitions of AC-1, AC-2 and AC-3 ratings, see Page 34-99. Maximum horsepower rating of starters for 380V 50 Hz applications: IEC Size A B C D E F G H J K L M N Horsepower 3 5 5 10 10 15 20 25 30 40 50 60 75

IEC Sizes A N are supplied with a NO side mounted auxiliary contact. On IEC Sizes A C, the 4th power pole position is used as the side mounted contact. For additional coil voltages, see Page 34-125. IEC Sizes H V are available. Contact Eaton. *Please contact your local Eaton sales ofce.

Cover Control . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . Heater Pack Selection . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . For more information visit: www.EatonElectrical.com

Page 33-99 Page 34-49 Page 34-93 Page 34-95 Page 34-100 PG03300001E 1CD1C CA08102001E

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0395]

34-131

Non-combination Starters

Table 34-212. Class ECE05/AE16 IEC Rated Non-combination C306 Interchangeable Heater OLR Non-reversing (Continued)
Max. General Purpose UL Ampere Rating 600V AC IEC 947 AC-1 Thermal Current 600V Maximum Horsepower Motor Voltage 1-Ph 3-Ph Magnet Coil Voltage (60 Hz) 3-Pole Type 4X Watertight & Dust-Tight Stainless Steel Catalog Number Price U.S. $ 3-Pole Type 12 Dust-Tight Industrial External Reset Catalog Number Price U.S. $ 3-Pole Component Starter (Open) Catalog Number

Size A 45 mm
7 20 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 ECE05A4AAA ECE05A4EAA ECE05A4BAA ECE05A4CAA ECE05A4DAA ECE05B4AAA ECE05B4EAA ECE05B4BAA ECE05B4CAA ECE05B4DAA ECE05C4AAA ECE05C4EAA ECE05C4BAA ECE05C4CAA ECE05C4DAA ECE05D4AAA ECE05D4EAA ECE05D4BAA ECE05D4CAA ECE05D4DAA ECE05E4AAA ECE05E4EAA ECE05E4BAA ECE05E4CAA ECE05E4DAA ECE05F4AAA ECE05F4EAA ECE05F4BAA ECE05F4CAA ECE05F4DAA ECE05G4AAA ECE05G4EAA ECE05G4BAA ECE05G4CAA ECE05G4DAA * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ECE05A8AAA ECE05A8EAA ECE05A8BAA ECE05A8CAA ECE05A8DAA ECE05B8AAA ECE05B8EAA ECE05B8BAA ECE05B8CAA ECE05B8DAA ECE05C8AAA ECE05C8EAA ECE05C8BAA ECE05C8CAA ECE05C8DAA ECE05D8AAA ECE05D8EAA ECE05D8BAA ECE05D8CAA ECE05D8DAA ECE05E8AAA ECE05E8EAA ECE05E8BAA ECE05E8CAA ECE05E8DAA ECE05F8AAA ECE05F8EAA ECE05F8BAA ECE05F8CAA ECE05F8DAA ECE05G8AAA ECE05G8EAA ECE05G8BAA ECE05G8CAA ECE05G8DAA 297. * * * * 301. * * * * 333. * * * * * * * * * * * 371. * * * * * 424. * 665. * * * * AE16ANS0AC AE16ANS0EC AE16ANS0BC AE16ANS0CC AE16ANS0DC AE16BNS0AC AE16BNS0EC AE16BNS0BC AE16BNS0CC AE16BNS0DC AE16CNS0AC AE16CNS0EC AE16CNS0BC AE16CNS0CC AE16CNS0DC AE16DNS0AC AE16DNS0EC AE16DNS0BC AE16DNS0CC AE16DNS0DC AE16ENS0AC AE16ENS0EC AE16ENS0BC AE16ENS0CC AE16ENS0DC AE16FNS0AC AE16FNS0EC AE16FNS0BC AE16FNS0CC AE16FNS0DC AE16GNS0AC AE16GNS0EC AE16GNS0BC AE16GNS0CC AE16GNS0DC

34

Size B 45 mm
10 20

Size C 45 mm
12 20

Size D 45 mm
18 32

Size E 45 mm
25 32

Size F 45 mm
32 32

Size G 65 mm
37 50

Starters do not include heater packs. Select 1 carton of 3 heater packs. For Heater Pack Selection, see Page 34-93. Starters with Electronic Overload, see Page 34-55 of Modication Codes. For denitions of AC-1, AC-2 and AC-3 ratings, see Page 34-99. Maximum horsepower rating of starters for 380V 50 Hz applications: IEC Size A B C D E F G H J K L M N Horsepower 3 5 5 10 10 15 20 25 30 40 50 60 75 IEC Sizes H V are available. Contact Eaton. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECE05A4AAA. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. *Please contact your local Eaton sales ofce.

IEC Sizes A N are supplied with a NO side mounted auxiliary contact. On IEC Sizes A C, the 4th power pole position is used as the side mounted contact. For additional coil voltages, see Page 34-125.

Cover Control . . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . . Heater Pack Selection . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 33-99 Page 34-49 Page 34-93 Page 34-95 Page 34-100 PG03300001E 1CD1C

34-132

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Non-combination Starters
Table 34-213. Class ECE06/AE56 IEC Rated Non-combination C306 Interchangeable Heater OLR Reversing
Max. General Purpose UL Ampere Rating 600V AC IEC 947 AC-1 Thermal Current 600V 20 Maximum Horsepower Motor Voltage 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1-Ph 3-Ph Magnet Coil Voltage (60 Hz) 3-Pole Type 1 General Purpose Catalog Number ECE06A1AAA ECE06A1EAA ECE06A1BAA ECE06A1CAA ECE06A1DAA ECE06B1AAA ECE06B1EAA ECE06B1BAA ECE06B1CAA ECE06B1DAA ECE06C1AAA ECE06C1EAA ECE06C1BAA ECE06C1CAA ECE06C1DAA ECE06D1AAA ECE06D1EAA ECE06D1BAA ECE06D1CAA ECE06D1DAA ECE06E1AAA ECE06E1EAA ECE06E1BAA ECE06E1CAA ECE06E1DAA ECE06F1AAA ECE06F1EAA ECE06F1BAA ECE06F1CAA ECE06F1DAA Price U.S. $ * * * * * 464. * 464. * * * * * * * 650. * * * * 705. * * * * * * * * * 3-Pole Type 3R Rainproof Catalog Number ECE06A2AAA ECE06A2EAA ECE06A2BAA ECE06A2CAA ECE06A2DAA ECE06B2AAA ECE06B2EAA ECE06B2BAA ECE06B2CAA ECE06B2DAA ECE06C2AAA ECE06C2EAA ECE06C2BAA ECE06C2CAA ECE06C2DAA ECE06D2AAA ECE06D2EAA ECE06D2BAA ECE06D2CAA ECE06D2DAA ECE06E2AAA ECE06E2EAA ECE06E2BAA ECE06E2CAA ECE06E2DAA ECE06F2AAA ECE06F2EAA ECE06F2BAA ECE06F2CAA ECE06F2DAA Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Vol. 2, Ref. No. [0396]

3-Pole Component Starter (Open) Catalog Number AE56AN0AC AE56AN0EC AE56AN0BC AE56AN0CC AE56AN0DC AE56BN0AC AE56BN0EC AE56BN0BC AE56BN0CC AE56BN0DC AE56CN0AC AE56CN0EC AE56CN0BC AE56CN0CC AE56CN0DC AE56DN0AC AE56DN0EC AE56DN0BC AE56DN0CC AE56DN0DC AE56EN0AC AE56EN0BC AE56EN0CC AE56EN0DC AE56EN0EC AE56FN0AC AE56FN0EC AE56FN0BC AE56FN0CC AE56FN0DC AE56GN0AC AE56GN0EC AE56GN0BC AE56GN0CC AE56GN0DC

Size A 45 mm

34

1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5

1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25

120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600

Size B 45 mm
10 20

Size C 45 mm
12 20

Size D 45 mm
18 32

Size E 45 mm
25 32

Size F 45 mm
32 32

Size G 65 mm
115 3 120 ECE06G1AAA * ECE06G2AAA 200 7-1/2 208 ECE06G1EAA * ECE06G2EAA 230 5 10 240 ECE06G1BAA * ECE06G2BAA 460 25 480 ECE06G1CAA * ECE06G2CAA 575 30 600 ECE06G1DAA * ECE06G2DAA Starters do not include heater packs. Select 1 carton of 3 heater packs. For Heater Pack Selection, see Page 34-93. Starters with Electronic Overload, see Page 34-55 of Modication Codes. For denitions of AC-1, AC-2 and AC-3 ratings, see Page 34-99. Maximum horsepower rating of starters for 380V 50 Hz applications: IEC Size A B C D E F G H J K L M N Horsepower 3 5 5 10 10 15 20 25 30 40 50 60 75 37 50

IEC Sizes A M have a NO-NC side mounted electrical interlock on each contactor. For additional coil voltages, see Page 34-125. IEC Sizes H M are available. Contact Eaton. *Please contact your local Eaton sales ofce.

Cover Control . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . Heater Pack Selection . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . For more information visit: www.EatonElectrical.com

Page 33-100 Page 34-49 Page 34-93 Page 34-95 Page 34-100 PG03300001E 1CD1C CA08102001E

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0397]

34-133

Non-combination Starters

Table 34-213. Class ECE06/AE56 IEC Rated Non-combination C306 Interchangeable Heater OLR Reversing (Continued)
Max. General Purpose UL Ampere Rating 600V AC IEC 947 AC-1 Thermal Current 600V 20 Maximum Horsepower Motor Voltage 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1-Ph 3-Ph Magnet Coil Voltage (60 Hz) 3-Pole Type 4X Watertight & Dust-Tight Stainless Steel Catalog Price Number U.S. $ ECE06A4AAA ECE06A4EAA ECE06A4BAA ECE06A4CAA ECE06A4DAA ECE06B4AAA ECE06B4EAA ECE06B4BAA ECE06B4CAA ECE06B4DAA ECE06C4AAA ECE06C4EAA ECE06C4BAA ECE06C4CAA ECE06C4DAA ECE06D4AAA ECE06D4EAA ECE06D4BAA ECE06D4CAA ECE06D4DAA ECE06E4AAA ECE06E4EAA ECE06E4BAA ECE06E4CAA ECE06E4DAA ECE06F4AAA ECE06F4EAA ECE06F4BAA ECE06F4CAA ECE06F4DAA * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 12 Dust-Tight Industrial External Reset Catalog Price Number U.S. $ ECE06A8AAA ECE06A8EAA ECE06A8BAA ECE06A8CAA ECE06A8DAA ECE06B8AAA ECE06B8EAA ECE06B8BAA ECE06B8CAA ECE06B8DAA ECE06C8AAA ECE06C8EAA ECE06C8BAA ECE06C8CAA ECE06C8DAA ECE06D8AAA ECE06D8EAA ECE06D8BAA ECE06D8CAA ECE06D8DAA ECE06E8AAA ECE06E8EAA ECE06E8BAA ECE06E8CAA ECE06E8DAA ECE06F8AAA ECE06F8EAA ECE06F8BAA ECE06F8CAA ECE06F8DAA * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Component Starter (Open) Catalog Number AE56AN0AC AE56AN0EC AE56AN0BC AE56AN0CC AE56AN0DC AE56BN0AC AE56BN0EC AE56BN0BC AE56BN0CC AE56BN0DC AE56CN0AC AE56CN0EC AE56CN0BC AE56CN0CC AE56CN0DC AE56DN0AC AE56DN0EC AE56DN0BC AE56DN0CC AE56DN0DC AE56EN0AC AE56EN0BC AE56EN0CC AE56EN0DC AE56EN0EC AE56FN0AC AE56FN0EC AE56FN0BC AE56FN0CC AE56FN0DC AE56GN0AC AE56GN0EC AE56GN0BC AE56GN0CC AE56GN0DC

Size A 45 mm
7 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600

34

Size B 45 mm
10 20

Size C 45 mm
12 20

Size D 45 mm
18 32

Size E 45 mm
25 32

Size F 45 mm
32 32

Size G 65 mm
115 3 120 ECE06G4AAA * ECE06G8AAA 200 7-1/2 208 ECE06G4EAA * ECE06G8EAA 230 5 10 240 ECE06G4BAA * ECE06G8BAA 460 25 480 ECE06G4CAA * ECE06G8CAA 575 30 600 ECE06G4DAA * ECE06G8DAA Starters do not include heater packs. Select 1 carton of 3 heater packs. For Heater Pack Selection, see Page 34-93. Starters with Electronic Overload, see Page 34-55 of Modication Codes. For denitions of AC-1, AC-2 and AC-3 ratings, see Page 34-99. Maximum horsepower rating of starters for 380V 50 Hz applications: IEC Size A B C D E F G H J K L M N Horsepower 3 5 5 10 10 15 20 25 30 40 50 60 75 37 50

IEC Sizes A M have a NO-NC side mounted electrical interlock on each contactor. For additional coil voltages, see Page 34-125. IEC Sizes H M are available. Contact Eaton.

These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECE06A4AAA. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. *Please contact your local Eaton sales ofce.

Cover Control . . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . . Heater Pack Selection . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 33-100 Page 34-49 Page 34-93 Page 34-95 Page 34-100 PG03300001E 1CD1C

34-134

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Non-combination Starters
Table 34-214. Class ECE09/AE17 IEC Rated Non-combination Fixed Heater OLR Non-reversing
Max. General Purpose UL Ampere Rating 600V AC IEC 947 AC-1 Thermal Current 600V 20 Maximum Horsepower Motor Voltage 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1-Ph 3-Ph Magnet Coil Voltage (60 Hz) 3-Pole Type 1 General Purpose Catalog Number ECE09A1AAA_ ECE09A1EAA_ ECE09A1BAA_ ECE09A1CAA_ ECE09A1DAA_ ECE09B1AAA_ ECE09B1EAA_ ECE09B1BAA_ ECE09B1CAA_ ECE09B1DAA_ ECE09C1AAA_ ECE09C1EAA_ ECE09C1BAA_ ECE09C1CAA_ ECE09C1DAA_ ECE09D1AAA_ ECE09D1EAA_ ECE09D1BAA_ ECE09D1CAA_ ECE09D1DAA_ ECE09E1AAA_ ECE09E1EAA_ ECE09E1BAA_ ECE09E1CAA_ ECE09E1DAA_ ECE09F1AAA_ ECE09F1EAA_ ECE09F1BAA_ ECE09F1CAA_ ECE09F1DAA_ ECE09G1AAA_ ECE09G1EAA_ ECE09G1BAA_ ECE09G1CAA_ ECE09G1DAA_ Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 3R Rainproof Catalog Number ECE09A2AAA_ ECE09A2EAA_ ECE09A2BAA_ ECE09A2CAA_ ECE09A2DAA_ ECE09B2AAA_ ECE09B2EAA_ ECE09B2BAA_ ECE09B2CAA_ ECE09B2DAA_ ECE09C2AAA_ ECE09C2EAA_ ECE09C2BAA_ ECE09C2CAA_ ECE09C2DAA_ ECE09D2AAA_ ECE09D2EAA_ ECE09D2BAA_ ECE09D2CAA_ ECE09D2DAA_ ECE09E2AAA_ ECE09E2EAA_ ECE09E2BAA_ ECE09E2CAA_ ECE09E2DAA_ ECE09F2AAA_ ECE09F2EAA_ ECE09F2BAA_ ECE09F2CAA_ ECE09F2DAA_ ECE09G2AAA_ ECE09G2EAA_ ECE09G2BAA_ ECE09G2CAA_ ECE09G2DAA_ Price U.S. $

Vol. 2, Ref. No. [0398]

3-Pole Component Starter (Open) Catalog Number * AE17ANS0_ * * * * * AE17BNS0_ * * * * * AE17CNS0_ * * * * * AE17DNS0_ * * * * * AE17ENS0_ * * * * * AE17FNS0_ * * * * * AE17GNS0_ * * * *

Size A 45 mm

34

1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5

1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30

120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600

Size B 45 mm
10 20

Size C 45 mm
12 20

Size D 45 mm
18 32

Size E 45 mm
25 32

Size F 45 mm
32 32

Size G 65 mm
37 50

For denitions of AC-1, AC-2 and AC-3 ratings, see Page 34-99. Maximum horsepower rating of contactors for 380V 50 Hz applications: IEC Size A B 5 C 5 D 10 E 10 F 15 G 20 H 25 J 30 K 40 L 50 M 60 N 75

Horsepower 3

Starter includes xed heater overload. For Enclosed IEC Starters, select sufx code -R_ from the table below. Overload relay range can not exceed contactor amperage rating. For Open IEC Starters, use sufx code -F_ or -K_ from the table below. Sufx Overload Enclosed/ Range Open R8/FC R9/FD R10/FE R11/FF R12/FG R13/FH R14/FJ .25 .40A .40 .63A .63 1.0A 1.0 1.4A 1.8 1.8A 1.7 2.4A 2.2 3.1A Sufx Overload Enclosed/ Range Open R15/FK R16/FL R17/FM R18/FN R19/FP R20/FQ R21/FR 2.8 4.0A 3.5 5A 4.5 6.5A 6.5 8.5A 7.5 11A 10.5 14A 13.5 19A Sufx Overload Enclosed/ Range Open R22/FS R23/FT R24/KA R25/KB R26/KC R27/KD 18 24A 24 32A 18 25A 22 32A 29 42A 36 52A

IEC Sizes A N are supplied with a NO side mounted auxiliary contact. On IEC Sizes A C, the 4th power pole position is used as the side mounted contact. For separate 120V control circuit, select size per Maximum Horsepower columns above. For additional coil voltages, see Page 34-125. *Please contact your local Eaton sales ofce.

Cover Control . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . For more information visit: www.EatonElectrical.com

Page 33-99 Page 34-49 Page 34-95 Page 34-100 PG03300001E 1CD1C CA08102001E

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0399]

34-135

Non-combination Starters

Table 34-214. Class ECE09/AE17 IEC Rated Non-combination Fixed Heater OLR Non-reversing (Continued)
Max. General Purpose UL Ampere Rating 600V AC IEC 947 AC-1 Thermal Current 600V 20 Maximum Horsepower Motor Voltage 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1-Ph 3-Ph Magnet Coil Voltage (60 Hz) 3-Pole Type 4X Watertight & Dust-Tight Stainless Steel Price Catalog U.S. $ Number ECE09A4AAA_ ECE09A4EAA_ ECE09A4BAA_ ECE09A4CAA_ ECE09A4DAA_ ECE09B4AAA_ ECE09B4EAA_ ECE09B4BAA_ ECE09B4CAA_ ECE09B4DAA_ ECE09C4AAA_ ECE09C4EAA_ ECE09C4BAA_ ECE09C4CAA_ ECE09C4DAA_ ECE09D4AAA_ ECE09D4EAA_ ECE09D4BAA_ ECE09D4CAA_ ECE09D4DAA_ ECE09E4AAA_ ECE09E4EAA_ ECE09E4BAA_ ECE09E4CAA_ ECE09E4DAA_ ECE09F4AAA_ ECE09F4EAA_ ECE09F4BAA_ ECE09F4CAA_ ECE09F4DAA_ ECE09G4AAA_ ECE09G4EAA_ ECE09G4BAA_ ECE09G4CAA_ ECE09G4DAA_ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 12 Dust-Tight Industrial External Reset Catalog Price Number U.S. $ ECE09A8AAA_ ECE09A8EAA_ ECE09A8BAA_ ECE09A8CAA_ ECE09A8DAA_ ECE09B8AAA_ ECE09B8EAA_ ECE09B8BAA_ ECE09B8CAA_ ECE09B8DAA_ ECE09C8AAA_ ECE09C8EAA_ ECE09C8BAA_ ECE09C8CAA_ ECE09C8DAA_ ECE09D8AAA_ ECE09D8EAA_ ECE09D8BAA_ ECE09D8CAA_ ECE09D8DAA_ ECE09E8AAA_ ECE09E8EAA_ ECE09E8BAA_ ECE09E8CAA_ ECE09E8DAA_ ECE09F8AAA_ ECE09F8EAA_ ECE09F8BAA_ ECE09F8CAA_ ECE09F8DAA_ ECE09G8AAA_ ECE09G8EAA_ ECE09G8BAA_ ECE09G8CAA_ ECE09G8DAA_ 3-Pole Component Starter (Open) Catalog Number * AE17ANS0_ * * * * * AE17BNS0_ * * * * * AE17CNS0_ * * * * * AE17DNS0_ * * * * * AE17ENS0_ * * * * * AE17FNS0_ * * * * * AE17GNS0_ * * * *

Size A 45 mm
7 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600

34

Size B 45 mm
10 20

Size C 45 mm
12 20

Size D 45 mm
18 32

Size E 45 mm
25 32

Size F 45 mm
32 32

Size G 65 mm
37 50

For denitions of AC-1, AC-2 and AC-3 ratings, see Page 34-99. Maximum horsepower rating of contactors for 380V 50 Hz applications: IEC Size A B 5 C 5 D 10 E 10 F 15 G 20 H 25 J 30 K 40 L 50 M 60 N 75

Horsepower 3

Starter includes xed heater overload. For Enclosed IEC Starters, select sufx code -R_ from the table below. Overload relay range can not exceed contactor amperage rating. For Open IEC Starters, use sufx code -F_ or -K_ from the table below. Sufx Overload Enclosed/ Range Open R8/FC R9/FD R10/FE R11/FF R12/FG R13/FH R14/FJ .25 .40A .40 .63A .63 1.0A 1.0 1.4A 1.8 1.8A 1.7 2.4A 2.2 3.1A Sufx Overload Enclosed/ Range Open R15/FK R16/FL R17/FM R18/FN R19/FP R20/FQ R21/FR 2.8 4.0A 3.5 5A 4.5 6.5A 6.5 8.5A 7.5 11A 10.5 14A 13.5 19A Sufx Overload Enclosed/ Range Open R22/FS R23/FT R24/KA R25/KB R26/KC R27/KD 18 24A 24 32A 18 25A 22 32A 29 42A 36 52A

These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECE09A4AAA. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. IEC Sizes A N are supplied with a NO side mounted auxiliary contact. On IEC Sizes A C, the 4th power pole position is used as the side mounted contact. For separate 120V control circuit, select size per Maximum Horsepower columns above. For additional coil voltages, see Page 34-125. *Please contact your local Eaton sales ofce.

Cover Control . . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . For more information visit: www.EatonElectrical.com

Page 33-99 Page 34-49 Page 34-95 Page 34-100 PG03300001E 1CD1C

CA08102001E

34-136

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Non-combination Starters
Table 34-215. Class ECE10/AE57 IEC Rated Non-combination Fixed Heater OLR Reversing
Max. General Purpose UL Ampere Rating 600V AC IEC 947 AC-1 Thermal Current 600V Maximum Horsepower Motor Voltage 1-Ph 3-Ph Magnet Coil Voltage (60 Hz) 3-Pole Type 1 General Purpose Catalog Number Price U.S. $ 3-Pole Type 3R Rainproof Catalog Number Price U.S. $

Vol. 2, Ref. No. [0400]

3-Pole Component Starter (Open) Catalog Number

34

Size A 45 mm
7 20 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 ECE10A1AAA_ ECE10A1EAA_ ECE10A1BAA_ ECE10A1CAA_ ECE10A1DAA_ ECE10B1AAA_ ECE10B1EAA_ ECE10B1BAA_ ECE10B1CAA_ ECE10B1DAA_ ECE10C1AAA_ ECE10C1EAA_ ECE10C1BAA_ ECE10C1CAA_ ECE10C1DAA_ ECE10D1AAA_ ECE10D1EAA_ ECE10D1BAA_ ECE10D1CAA_ ECE10D1DAA_ ECE10E1AAA_ ECE10E1EAA_ ECE10E1BAA_ ECE10E1CAA_ ECE10E1DAA_ ECE10F1AAA_ ECE10F1EAA_ ECE10F1BAA_ ECE10F1CAA_ ECE10F1DAA_ ECE10G1AAA_ ECE10G1EAA_ ECE10G1BAA_ ECE10G1CAA_ ECE10G1DAA_ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ECE10A2AAA_ ECE10A2EAA_ ECE10A2BAA_ ECE10A2CAA_ ECE10A2DAA_ ECE10B2AAA_ ECE10B2EAA_ ECE10B2BAA_ ECE10B2CAA_ ECE10B2DAA_ ECE10C2AAA_ ECE10C2EAA_ ECE10C2BAA_ ECE10C2CAA_ ECE10C2DAA_ ECE10D2AAA_ ECE10D2EAA_ ECE10D2BAA_ ECE10D2CAA_ ECE10D2DAA_ ECE10E2AAA_ ECE10E2EAA_ ECE10E2BAA_ ECE10E2CAA_ ECE10E2DAA_ ECE10F2AAA_ ECE10F2EAA_ ECE10F2BAA_ ECE10F2CAA_ ECE10F2DAA_ ECE10G2AAA_ ECE10G2EAA_ ECE10G2BAA_ ECE10G2CAA_ ECE10G2DAA_ * AE57AN0_ * * * * * AE57BN0_ * * * * * AE57CN0_ * * * * * AE57DN0_ * * * * * AE57EN0_ * * * * * AE57FN0_ * * * * * AE57GN0_ * * * *

Size B 45 mm
10 20

Size C 45 mm
12 20

Size D 45 mm
18 32

Size E 45 mm
25 32

Size F 45 mm
32 32

Size G 65 mm
37 50

For denitions of AC-1, AC-2 and AC-3 ratings, see Page 34-99. Maximum horsepower rating of contactors for 380V 50 Hz applications: IEC Size A B 5 C 5 D 10 E 10 F 15 G 20 H 25 J 30 K 40 L 50 M 60 N 75

Sizes A M have a NO-NC side mounted electrical interlock on each contactor. For additional coil voltages, see Page 34-125. *Please contact your local Eaton sales ofce.

Horsepower 3

Starter includes xed heater overload. For Enclosed IEC Starters, select sufx code -R_ from the table below. Overload relay range can not exceed contactor amperage rating. For Open IEC Starters, use sufx code -F_ or -K_ from the table below. Sufx Overload Enclosed/ Range Open R8/FC R9/FD R10/FE R11/FF R12/FG R13/FH R14/FJ .25 .40A .40 .63A .63 1.0A 1.0 1.4A 1.8 1.8A 1.7 2.4A 2.2 3.1A Sufx Overload Enclosed/ Range Open R15/FK R16/FL R17/FM R18/FN R19/FP R20/FQ R21/FR 2.8 4.0A 3.5 5A 4.5 6.5A 6.5 8.5A 7.5 11A 10.5 14A 13.5 19A Sufx Overload Enclosed/ Range Open R22/FS R23/FT R24/KA R25/KB R26/KC R27/KD 18 24A 24 32A 18 25A 22 32A 29 42A 36 52A

Cover Control . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . .

Page 33-100 Page 34-49 Page 34-95 Page 34-100 PG03300001E 1CD1C CA08102001E

For more information visit: www.EatonElectrical.com

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0401]

34-137

Non-combination Starters

Table 34-215. Class ECE10/AE57 IEC Rated Non-combination Fixed Heater OLR Reversing (Continued)
Max. General Purpose UL Ampere Rating 600V AC IEC 947 AC-1 Thermal Current 600V Maximum Horsepower Motor Voltage 1-Ph 3-Ph Magnet Coil Voltage (60 Hz) 3-Pole Type 4X Watertight & Dust-Tight Stainless Steel Catalog Number Price U.S. $ 3-Pole Type 12 Dust-Tight Industrial External Reset Catalog Number Price U.S. $ 3-Pole Component Starter (Open) Catalog Number

Size A 45 mm
7 20 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 ECE10A4AAA_ ECE10A4EAA_ ECE10A4BAA_ ECE10A4CAA_ ECE10A4DAA_ ECE10B4AAA_ ECE10B4EAA_ ECE10B4BAA_ ECE10B4CAA_ ECE10B4DAA_ ECE10C4AAA_ ECE10C4EAA_ ECE10C4BAA_ ECE10C4CAA_ ECE10C4DAA_ ECE10D4AAA_ ECE10D4EAA_ ECE10D4BAA_ ECE10D4CAA_ ECE10D4DAA_ ECE10E4AAA_ ECE10E4EAA_ ECE10E4BAA_ ECE10E4CAA_ ECE10E4DAA_ ECE10F4AAA_ ECE10F4EAA_ ECE10F4BAA_ ECE10F4CAA_ ECE10F4DAA_ ECE10G4AAA_ ECE10G4EAA_ ECE10G4BAA_ ECE10G4CAA_ ECE10G4DAA_ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ECE10A8AAA_ ECE10A8EAA_ ECE10A8BAA_ ECE10A8CAA_ ECE10A8DAA_ ECE10B8AAA_ ECE10B8EAA_ ECE10B8BAA_ ECE10B8CAA_ ECE10B8DAA_ ECE10C8AAA_ ECE10C8EAA_ ECE10C8BAA_ ECE10C8CAA_ ECE10C8DAA_ ECE10D8AAA_ ECE10D8EAA_ ECE10D8BAA_ ECE10D8CAA_ ECE10D8DAA_ ECE10E8AAA_ ECE10E8EAA_ ECE10E8BAA_ ECE10E8CAA_ ECE10E8DAA_ ECE10F8AAA_ ECE10F8EAA_ ECE10F8BAA_ ECE10F8CAA_ ECE10F8DAA_ ECE10G8AAA_ ECE10G8EAA_ ECE10G8BAA_ ECE10G8CAA_ ECE10G8DAA_ * AE57AN0_ * * * * * AE57BN0_ * * * * * AE57CN0_ * * * * * AE57DN0_ * * * * * AE57EN0_ * * * * * AE57FN0_ * * * * * AE57GN0_ * * * *

34

Size B 45 mm
10 20

Size C 45 mm
12 20

Size D 45 mm
18 32

Size E 45 mm
25 32

Size F 45 mm
32 32

Size G 65 mm
37 50

For denitions of AC-1, AC-2 and AC-3 ratings, see Page 34-99. Maximum horsepower rating of contactors for 380V 50 Hz applications: IEC Size A B 5 C 5 D 10 E 10 F 15 G 20 H 25 J 30 K 40 L 50 M 60 N 75

Horsepower 3

Starter includes xed heater overload. For Enclosed IEC Starters, select sufx code -R_ from the table below. Overload relay range can not exceed contactor amperage rating. For Open IEC Starters, use sufx code -F_ or -K_ from the table below. Sufx Overload Enclosed/ Range Open R8/FC R9/FD R10/FE R11/FF R12/FG R13/FH R14/FJ .25 .40A .40 .63A .63 1.0A 1.0 1.4A 1.8 1.8A 1.7 2.4A 2.2 3.1A Sufx Overload Enclosed/ Range Open R15/FK R16/FL R17/FM R18/FN R19/FP R20/FQ R21/FR 2.8 4.0A 3.5 5A 4.5 6.5A 6.5 8.5A 7.5 11A 10.5 14A 13.5 19A Sufx Overload Enclosed/ Range Open R22/FS R23/FT R24/KA R25/KB R26/KC R27/KD 18 24A 24 32A 18 25A 22 32A 29 42A 36 52A

These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECE10A4AAA_. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. Sizes A M have a NO-NC side mounted electrical interlock on each contactor. For additional coil voltages, see Page 34-125. *Please contact your local Eaton sales ofce.

Cover Control . . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . .

Page 33-100 Page 34-49 Page 34-95 Page 34-100 PG03300001E 1CD1C

CA08102001E

For more information visit: www.EatonElectrical.com

34-138

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Combination Starters Fusible

Vol. 2, Ref. No. [0402]

Product Selection
Table 34-216. Class ECE16 IEC Rated Fusible Combination Interchangeable Heater OLR Non-reversing
Motor Voltage Max. hp Rating Magnet Coil Voltage Fuse Clip Amps 3-Pole Type 1 General Purpose Catalog Number ECE16A1AAB ECE16A1EAB ECE16A1BAB ECE16A1CAB ECE16A1DAB ECE16B1AAB ECE16B1EAB ECE16B1BAB ECE16B1CAB ECE16B1DAB ECE16C1AAB ECE16C1EAB ECE16C1BAB ECE16C1CAB ECE16C1DAB ECE16D1AAC ECE16D1EAC ECE16D1BAC ECE16D1CAC ECE16D1DAC ECE16E1AAC ECE16E1EAC ECE16E1BAC ECE16E1CAC ECE16E1DAC ECE16F1AAE ECE16F1EAE ECE16F1BAE ECE16F1CAE ECE16F1DAE ECE16G1AAE ECE16G1EAE ECE16G1BAE ECE16G1CAE ECE16G1DAE Price U.S. $ 555. * * 555. * 570. * * 570. * * * 605. 605. * 630. 630. 630. 630. * 640. * * * * * * * * * 875. 875. * 875. 875. 3-Pole Type 3R Rainproof Catalog Number ECE16A2AAB ECE16A2EAB ECE16A2BAB ECE16A2CAB ECE16A2DAB ECE16B2AAB ECE16B2EAB ECE16B2BAB ECE16B2CAB ECE16B2DAB ECE16C2AAB ECE16C2EAB ECE16C2BAB ECE16C2CAB ECE16C2DAB ECE16D2AAC ECE16D2EAC ECE16D2BAC ECE16D2CAC ECE16D2DAC ECE16E2AAC ECE16E2EAC ECE16E2BAC ECE16E2CAC ECE16E2DAC ECE16F2AAE ECE16F2EAE ECE16F2BAE ECE16F2CAE ECE16F2DAE ECE16G2AAE ECE16G2EAE ECE16G2BAE ECE16G2CAE ECE16G2DAE Price U.S. $ 720. 720. * 720. 720. 725. * * 725. * * * * * * * * * * * * * * * * 1,135. 1,135. * * * 1,175. 1,175. 1,175. 1,175. 1,175. * 1,215. * 1,215. 1,215. 3-Pole Component Starter (Open) Catalog Number AE16ANS0AC AE16ANS0EC AE16ANS0BC AE16ANS0CC AE16ANS0DC AE16BNS0AC AE16BNS0EC AE16BNS0BC AE16BNS0CC AE16BNS0DC AE16CNS0AC AE16CNS0EC AE16CNS0BC AE16CNS0CC AE16CNS0DC AE16DNS0AC AE16DNS0EC AE16DNS0BC AE16DNS0CC AE16DNS0DC AE16ENS0AC AE16ENS0EC AE16ENS0BC AE16ENS0CC AE16ENS0DC AE16FNS0AC AE16FNS0EC AE16FNS0BC AE16FNS0CC AE16FNS0DC AE16GNS0AB AE16GNS0EB AE16GNS0BB AE16GNS0CB AE16GNS0DB AE16HNS0AB AE16HNS0EB AE16HNS0BB AE16HNS0CB AE16HNS0DB

1-Phase

3-Phase

34

Size A 45 mm
115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 30

Size B 45 mm
30

Size C 45 mm
30

Size D 45 mm
30

Size E 45 mm
30

Size F 45 mm
60

Size G 65 mm
60

Size H 65 mm
115 3 120 60 ECE16H1AAE 930. ECE16H2AAE 200 10 208 ECE16H1EAE * ECE16H2EAE 230 7-1/2 15 240 ECE16H1BAE * ECE16H2BAE 460 30 480 ECE16H1CAE * ECE16H2CAE 575 40 600 ECE16H1DAE * ECE16H2DAE Starters do not include heater packs. Select 1 carton of 3 heater packs. For Heater Pack Selection, see Page 34-93. Starters with Electronic Overload, see Page 34-55 of Modication Codes. For additional coil voltages, see Page 34-125. Fuse clips will accept both 250 and 600V. *Please contact your local Eaton sales ofce.

Modications . . . . . . . . . . . . . . . . . . . . Page 34-49 Heater Pack Selection . . . . . . . . . . . . Page 34-93 Technical Data . . . . . . . . . . . . . . . . . . . Page 34-95 Accessories . . . . . . . . . . . . . . . . . . . . . Page 34-100 Cover Control . . . . . . . . . . . . . . . . . . . . Page 34-124 Dimensions . . . . . . . . . . . . . . . . . . . . . . PG03300001E Discount Symbol . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0403]

34-139

Combination Starters Fusible

Table 34-216. Class ECE16 IEC Rated Fusible Combination Interchangeable Heater OLR Non-reversing (Continued)
Motor Voltage Max. hp Rating Magnet Coil Voltage Fuse Clip Amps 3-Pole Type 4X Watertight & Dust-Tight Stainless Steel Catalog Price Number U.S. $ ECE16A4AAB ECE16A4EAB ECE16A4BAB ECE16A4CAB ECE16A4DAB ECE16B4AAB ECE16B4EAB ECE16B4BAB ECE16B4CAB ECE16B4DAB ECE16C4AAB ECE16C4EAB ECE16C4BAB ECE16C4CAB ECE16C4DAB ECE16D4AAC ECE16D4EAC ECE16D4BAC ECE16D4CAC ECE16D4DAC ECE16E4AAC ECE16E4EAC ECE16E4BAC ECE16E4CAC ECE16E4DAC ECE16F4AAE ECE16F4EAE ECE16F4BAE ECE16F4CAE ECE16F4DAE ECE16G4AAE ECE16G4EAE ECE16G4BAE ECE16G4CAE ECE16G4DAE * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 12 Dust-Tight Catalog Number ECE16A8AAB ECE16A8EAB ECE16A8BAB ECE16A8CAB ECE16A8DAB ECE16B8AAB ECE16B8EAB ECE16B8BAB ECE16B8CAB ECE16B8DAB ECE16C8AAB ECE16C8EAB ECE16C8BAB ECE16C8CAB ECE16C8DAB ECE16D8AAC ECE16D8EAC ECE16D8BAC ECE16D8CAC ECE16D8DAC ECE16E8AAC ECE16E8EAC ECE16E8BAC ECE16E8CAC ECE16E8DAC ECE16F8AAE ECE16F8EAE ECE16F8BAE ECE16F8CAE ECE16F8DAE ECE16G8AAE ECE16G8EAE ECE16G8BAE ECE16G8CAE ECE16G8DAE Price U.S. $ 720. * * 720. * * * * * * * * * * * * * * * * 800. * * * * 1,135. * * * * 1,175. 1,175. 1,175. 1,175. 1,175. * * * * * 3-Pole Component Starter (Open) Catalog Number AE16ANS0AC AE16ANS0EC AE16ANS0BC AE16ANS0CC AE16ANS0DC AE16BNS0AC AE16BNS0EC AE16BNS0BC AE16BNS0CC AE16BNS0DC AE16CNS0AC AE16CNS0EC AE16CNS0BC AE16CNS0CC AE16CNS0DC AE16DNS0AC AE16DNS0EC AE16DNS0BC AE16DNS0CC AE16DNS0DC AE16ENS0AC AE16ENS0EC AE16ENS0BC AE16ENS0CC AE16ENS0DC AE16FNS0AC AE16FNS0EC AE16FNS0BC AE16FNS0CC AE16FNS0DC AE16GNS0AB AE16GNS0EB AE16GNS0BB AE16GNS0CB AE16GNS0DB AE16HNS0AB AE16HNS0EB AE16HNS0BB AE16HNS0CB AE16HNS0DB

1-Phase

3-Phase

Size A 45 mm
115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 30

34

Size B 45 mm
30

Size C 45 mm
30

Size D 45 mm
30

Size E 45 mm
30

Size F 45 mm
60

Size G 65 mm
60

Size H 65 mm
115 3 120 60 ECE16H4AAE * ECE16H8AAE 200 10 208 ECE16H4EAE * ECE16H8EAE 230 7-1/2 15 240 ECE16H4BAE * ECE16H8BAE 460 30 480 ECE16H4CAE * ECE16H8CAE 575 40 600 ECE16H4DAE * ECE16H8DAE Starters do not include heater packs. Select 1 carton of 3 heater packs. For Heater Pack Selection, see Page 34-93. Starters with Electronic Overload, see Page 34-55 of Modication Codes.

For additional coil voltages, see Page 34-125. Fuse clips will accept both 250 and 600V. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECE16A4AAB. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. *Please contact your local Eaton sales ofce.

Modications. . . . . . . . . . . . . . . . . . . . Heater Pack Selection . . . . . . . . . . . . Technical Data. . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . Dimensions. . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-49 Page 34-93 Page 34-95 Page 34-100 Page 34-124 PG03300001E 1CD1C

34-140

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Combination Starters Fusible


Table 34-217. Class ECE17 IEC Rated Fusible Combination Interchangeable Heater OLR Reversing
Motor Voltage Max. hp Rating Magnet Coil Voltage Fuse Clip Amps 3-Pole Type 1 General Purpose Catalog Number ECE17A1AAB ECE17A1EAB ECE17A1BAB ECE17A1CAB ECE17A1DAB ECE17B1AAB ECE17B1EAB ECE17B1BAB ECE17B1CAB ECE17B1DAB ECE17C1AAB ECE17C1EAB ECE17C1BAB ECE17C1CAB ECE17C1DAB ECE17D1AAC ECE17D1EAC ECE17D1BAC ECE17D1CAC ECE17D1DAC ECE17E1AAC ECE17E1EAC ECE17E1BAC ECE17E1CAC ECE17E1DAC ECE17F1AAE ECE17F1EAE ECE17F1BAE ECE17F1CAE ECE17F1DAE ECE17G1AAE ECE17G1EAE ECE17G1BAE ECE17G1CAE ECE17G1DAE ECE17H1AAE ECE17H1EAE ECE17H1BAE ECE17H1CAE ECE17H1DAE Price U.S. $ * * * * * * 945. * * 945. * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 3R Rainproof Catalog Number ECE17A2AAB ECE17A2EAB ECE17A2BAB ECE17A2CAB ECE17A2DAB ECE17B2AAB ECE17B2EAB ECE17B2BAB ECE17B2CAB ECE17B2DAB ECE17C2AAB ECE17C2EAB ECE17C2BAB ECE17C2CAB ECE17C2DAB ECE17D2AAC ECE17D2EAC ECE17D2BAC ECE17D2CAC ECE17D2DAC ECE17E2AAC ECE17E2EAC ECE17E2BAC ECE17E2CAC ECE17E2DAC ECE17F2AAE ECE17F2EAE ECE17F2BAE ECE17F2CAE ECE17F2DAE ECE17G2AAE ECE17G2EAE ECE17G2BAE ECE17G2CAE ECE17G2DAE ECE17H2AAE ECE17H2EAE ECE17H2BAE ECE17H2CAE ECE17H2DAE Price U.S. $ * * * * * 1,140. * 1,140. 1,140. * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Vol. 2, Ref. No. [0404]

3-Pole Component Starter (Open) Catalog Number AE56AN0AC AE56AN0EC AE56AN0BC AE56AN0CC AE56AN0DC AE56BN0AC AE56BN0EC AE56BN0BC AE56BN0CC AE56BN0DC AE56CN0AC AE56CN0EC AE56CN0BC AE56CN0CC AE56CN0DC AE56DN0AC AE56DN0EC AE56DN0BC AE56DN0CC AE56DN0DC AE56EN0AC AE56EN0EC AE56EN0BC AE56EN0CC AE56EN0DC AE56FN0AC AE56FN0EC AE56FN0BC AE56FN0CC AE56FN0DC AE56GN0AC AE56GN0EC AE56GN0BC AE56GN0CC AE56GN0DC AE56HN0AB AE56HN0EB AE56HN0BB AE56HN0CB AE56HN0DB

1-Phase

3-Phase

Size A 45 mm

34

115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575

1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 3 7-1/2

1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 10 15 30 40

120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600

30

Size B 45 mm
30

Size C 45 mm
30

Size D 45 mm
30

Size E 45 mm
30

Size F 45 mm
60

Size G 65 mm
60

Size H 65 mm
60

Starters do not include heater packs. Select 1 carton of 3 heater packs. For Heater Pack Selection, see Page 34-93. Starters with Electronic Overload, see Page 34-55 of Modication Codes. For additional coil voltages, see Page 34-125. Fuse clips will accept both 250 and 600V. *Please contact your local Eaton sales ofce.

Modications . . . . . . . . . . . . . . . . . . . . Page 34-49 Heater Pack Selection . . . . . . . . . . . . Page 34-93 Technical Data . . . . . . . . . . . . . . . . . . . Page 34-95 Accessories . . . . . . . . . . . . . . . . . . . . . Page 34-100 Cover Control . . . . . . . . . . . . . . . . . . . . Page 34-124 Dimensions . . . . . . . . . . . . . . . . . . . . . . PG03300001E Discount Symbol . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0405]

34-141

Combination Starters Fusible

Table 34-217. Class ECE17 IEC Rated Fusible Combination Interchangeable Heater OLR Reversing (Continued)
Motor Voltage Max. hp Rating Magnet Coil Voltage Fuse Clip Amps 3-Pole Type 4X Watertight & Dust-Tight Stainless Steel Catalog Number ECE17A4AAB ECE17A4EAB ECE17A4BAB ECE17A4CAB ECE17A4DAB ECE17B4AAB ECE17B4EAB ECE17B4BAB ECE17B4CAB ECE17B4DAB ECE17C4AAB ECE17C4EAB ECE17C4BAB ECE17C4CAB ECE17C4DAB ECE17D4AAC ECE17D4EAC ECE17D4BAC ECE17D4CAC ECE17D4DAC ECE17E4AAC ECE17E4EAC ECE17E4BAC ECE17E4CAC ECE17E4DAC ECE17F4AAE ECE17F4EAE ECE17F4BAE ECE17F4CAE ECE17F4DAE ECE17G4AAE ECE17G4EAE ECE17G4BAE ECE17G4CAE ECE17G4DAE ECE17H4AAE ECE17H4EAE ECE17H4BAE ECE17H4CAE ECE17H4DAE Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 12 Dust-Tight Catalog Number ECE17A8AAB ECE17A8EAB ECE17A8BAB ECE17A8CAB ECE17A8DAB ECE17B8AAB ECE17B8EAB ECE17B8BAB ECE17B8CAB ECE17B8DAB ECE17C8AAB ECE17C8EAB ECE17C8BAB ECE17C8CAB ECE17C8DAB ECE17D8AAC ECE17D8EAC ECE17D8BAC ECE17D8CAC ECE17D8DAC ECE17E8AAC ECE17E8EAC ECE17E8BAC ECE17E8CAC ECE17E8DAC ECE17F8AAE ECE17F8EAE ECE17F8BAE ECE17F8CAE ECE17F8DAE ECE17G8AAE ECE17G8EAE ECE17G8BAE ECE17G8CAE ECE17G8DAE ECE17H8AAE ECE17H8EAE ECE17H8BAE ECE17H8CAE ECE17H8DAE Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Component Starter (Open) Catalog Number AE56AN0AC AE56AN0EC AE56AN0BC AE56AN0CC AE56AN0DC AE56BN0AC AE56BN0EC AE56BN0BC AE56BN0CC AE56BN0DC AE56CN0AC AE56CN0EC AE56CN0BC AE56CN0CC AE56CN0DC AE56DN0AC AE56DN0EC AE56DN0BC AE56DN0CC AE56DN0DC AE56EN0AC AE56EN0EC AE56EN0BC AE56EN0CC AE56EN0DC AE56FN0AC AE56FN0EC AE56FN0BC AE56FN0CC AE56FN0DC AE56GN0AC AE56GN0EC AE56GN0BC AE56GN0CC AE56GN0DC AE56HN0AB AE56HN0EB AE56HN0BB AE56HN0CB AE56HN0DB

1-Phase

3-Phase

Size A 45 mm
115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 3 7-1/2 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 10 15 30 40 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 30

34

Size B 45 mm
30

Size C 45 mm
30

Size D 45 mm
30

Size E 45 mm
30

Size F 45 mm
60

Size G 65 mm
60

Size H 65 mm
60

Starters do not include heater packs. Select 1 carton of 3 heater packs. For Heater Pack Selection, see Page 34-93. Starters with Electronic Overload, see Page 34-55 of Modication Codes. For additional coil voltages, see Page 34-125. Fuse clips will accept both 250 and 600V. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECE17A4AAB. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. *Please contact your local Eaton sales ofce.

Modications. . . . . . . . . . . . . . . . . . . . Heater Pack Selection . . . . . . . . . . . . Technical Data. . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . Dimensions. . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-49 Page 34-93 Page 34-95 Page 34-100 Page 34-124 PG03300001E 1CD1C

34-142

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Combination Starters Fusible


Table 34-218. Class ECE19 IEC Rated Fusible Combination Fixed Heater OLR Non-reversing
Motor Voltage Max. hp Rating Magnet Coil Voltage Fuse Clip Amps 3-Pole Type 1 General Purpose Catalog Number ECE19A1AAB_ ECE19A1EAB_ ECE19A1BAB_ ECE19A1CAB_ ECE19A1DAB_ ECE19B1AAB_ ECE19B1EAB_ ECE19B1BAB_ ECE19B1CAB_ ECE19B1DAB_ ECE19C1AAB_ ECE19C1EAB_ ECE19C1BAB_ ECE19C1CAB_ ECE19C1DAB_ ECE19D1AAC_ ECE19D1EAC_ ECE19D1BAC_ ECE19D1CAC_ ECE19D1DAC_ ECE19E1AAC_ ECE19E1EAC_ ECE19E1BAC_ ECE19E1CAC_ ECE19E1DAC_ ECE19F1AAE_ ECE19F1EAE_ ECE19F1BAE_ ECE19F1CAE_ ECE19F1DAE_ ECE19G1AAE_ ECE19G1EAE_ ECE19G1BAE_ ECE19G1CAE_ ECE19G1DAE_ Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 3R Rainproof Catalog Number ECE19A2AAB_ ECE19A2EAB_ ECE19A2BAB_ ECE19A2CAB_ ECE19A2DAB_ ECE19B2AAB_ ECE19B2EAB_ ECE19B2BAB_ ECE19B2CAB_ ECE19B2DAB_ ECE19C2AAB_ ECE19C2EAB_ ECE19C2BAB_ ECE19C2CAB_ ECE19C2DAB_ ECE19D2AAC_ ECE19D2EAC_ ECE19D2BAC_ ECE19D2CAC_ ECE19D2DAC_ ECE19E2AAC_ ECE19E2EAC_ ECE19E2BAC_ ECE19E2CAC_ ECE19E2DAC_ ECE19F2AAE_ ECE19F2EAE_ ECE19F2BAE_ ECE19F2CAE_ ECE19F2DAE_ ECE19G2AAE_ ECE19G2EAE_ ECE19G2BAE_ ECE19G2CAE_ ECE19G2DAE_ ECE19H2AAE_ ECE19H2EAE_ ECE19H2BAE_ ECE19H2CAE_ ECE19H2DAE_ Price U.S. $

Vol. 2, Ref. No. [0406]

1-Phase

3-Phase

3-Pole Component Starter (Open) Catalog Number * AE17ANS0_ * * * * * AE17BNS0_ * * * * * AE17CNS0_ * * * * * AE17DNS0_ * * * * * AE17ENS0_ * * * * * AE17FNS0_ * * * * * AE17GNS0_ * * * * * AE17HNS0_ * * * *

Size A 45 mm

34

115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575

1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5

1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30

120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600

30

Size B 45 mm
30

Size C 45 mm
30

Size D 45 mm
30

Size E 45 mm
30

Size F 45 mm
60

Size G 65 mm
60

Size H 65 mm
115 3 120 60 ECE19H1AAE_ 200 10 208 ECE19H1EAE_ 230 7-1/2 15 240 ECE19H1BAE_ 460 30 480 ECE19H1CAE_ 575 40 600 ECE19H1DAE_ 1 set of 3 xed heater overload relays included. For additional coil voltages, refer to Page 34-125. Starter includes xed heater overload. For Enclosed IEC Starters, select sufx code -R_ from the table below. Overload relay range can not exceed contactor amperage rating. For Open IEC Starters, use sufx code -F_ or -K_ from the table below. Sufx Overload Enclosed/ Range Open R4 R8/FC R9/FD R10/FE R11/FF R12/FG R13/FH Omit OLR .25 .40A .40 .63A .63 1.0A 1.0 1.4A 1.8 1.8A 1.7 2.4A Sufx Overload Enclosed/ Range Open R14/FJ R15/FK R16/FL R17/FM R18/FN R19/FP R20/FQ 2.2 3.1A 2.8 4.0A 3.5 5A 4.5 6.5A 6.5 8.5A 7.5 11A 10.5 14A Sufx Overload Enclosed/ Range Open R21/FR R22/FS R23/FT R24/KA R25/KB R26/KC R27/KD 13 19A 18 24A 24 32A 18 25A 22 32A 29 42A 36 52A

Note: Overload relay range can not exceed contactor amperage rating.
*Please contact your local Eaton sales ofce.

Modications . . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . .

Page 34-49 Page 34-95 Page 34-100 Page 34-124 PG03300001E 1CD1C CA08102001E

For more information visit: www.EatonElectrical.com

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0407]

34-143

Combination Starters Fusible

Table 34-218. Class ECE19 IEC Rated Fusible Combination Fixed Heater OLR Non-reversing (Continued)
Motor Voltage Max. hp Rating Magnet Coil Voltage Fuse Clip Amps 3-Pole Type 4X Watertight & Dust-Tight Stainless Steel Catalog Price Number U.S. $ ECE19A4AAB_ ECE19A4EAB_ ECE19A4BAB_ ECE19A4CAB_ ECE19A4DAB_ ECE19B4AAB_ ECE19B4EAB_ ECE19B4BAB_ ECE19B4CAB_ ECE19B4DAB_ ECE19C4AAB_ ECE19C4EAB_ ECE19C4BAB_ ECE19C4CAB_ ECE19C4DAB_ ECE19D4AAC_ ECE19D4EAC_ ECE19D4BAC_ ECE19D4CAC_ ECE19D4DAC_ ECE19E4AAC_ ECE19E4EAC_ ECE19E4BAC_ ECE19E4CAC_ ECE19E4DAC_ ECE19F4AAE_ ECE19F4EAE_ ECE19F4BAE_ ECE19F4CAE_ ECE19F4DAE_ ECE19G4AAE_ ECE19G4EAE_ ECE19G4BAE_ ECE19G4CAE_ ECE19G4DAE_ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 12 Dust-Tight Catalog Number ECE19A8AAB_ ECE19A8EAB_ ECE19A8BAB_ ECE19A8CAB_ ECE19A8DAB_ ECE19B8AAB_ ECE19B8EAB_ ECE19B8BAB_ ECE19B8CAB_ ECE19B8DAB_ ECE19C8AAB_ ECE19C8EAB_ ECE19C8BAB_ ECE19C8CAB_ ECE19C8DAB_ ECE19D8AAC_ ECE19D8EAC_ ECE19D8BAC_ ECE19D8CAC_ ECE19D8DAC_ ECE19E8AAC_ ECE19E8EAC_ ECE19E8BAC_ ECE19E8CAC_ ECE19E8DAC_ ECE19F8AAE_ ECE19F8EAE_ ECE19F8BAE_ ECE19F8CAE_ ECE19F8DAE_ ECE19G8AAE_ ECE19G8EAE_ ECE19G8BAE_ ECE19G8CAE_ ECE19G8DAE_ ECE19H8AAE_ ECE19H8EAE_ ECE19H8BAE_ ECE19H8CAE_ ECE19H8DAE_ Price U.S. $ 3-Pole Component Starter (Open) Catalog Number * AE17ANS0_ * * * * * AE17BNS0_ * * * * * AE17CNS0_ * * * * * AE17DNS0_ * * * * * AE17ENS0_ * * * * * AE17FNS0_ * * * * * AE17GNS0_ * * * * * AE17HNS0_ * * * *

1-Phase

3-Phase

Size A 45 mm
115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 30

34

Size B 45 mm
30

Size C 45 mm
30

Size D 45 mm
30

Size E 45 mm
30

Size F 45 mm
60

Size G 65 mm
60

Size H 65 mm
115 3 120 60 ECE19H4AAE_ 200 10 208 ECE19H4EAE_ 230 7-1/2 15 240 ECE19H4BAE_ 460 30 480 ECE19H4CAE_ 575 40 600 ECE19H4DAE_ 1 set of 3 xed heater overload relays included. For additional coil voltages, refer to Page 34-125. Starter includes xed heater overload. For Enclosed IEC Starters, select sufx code -R_ from the table below. Overload relay range can not exceed contactor amperage rating. For Open IEC Starters, use sufx code -F_ or -K_ from the table below. Sufx Overload Enclosed/ Range Open R4 R8/FC R9/FD R10/FE R11/FF R12/FG R13/FH Omit OLR .25 .40A .40 .63A .63 1.0A 1.0 1.4A 1.8 1.8A 1.7 2.4A Sufx Overload Enclosed/ Range Open R14/FJ R15/FK R16/FL R17/FM R18/FN R19/FP R20/FQ 2.2 3.1A 2.8 4.0A 3.5 5A 4.5 6.5A 6.5 8.5A 7.5 11A 10.5 14A Sufx Overload Enclosed/ Range Open R21/FR R22/FS R23/FT R24/KA R25/KB R26/KC R27/KD 13 19A 18 24A 24 32A 18 25A 22 32A 29 42A 36 52A

Note: Overload relay range can not exceed contactor amperage rating.
These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECE19A4AAB. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. *Please contact your local Eaton sales ofce.

Modications . . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . .

Page 34-49 Page 34-95 Page 34-100 Page 34-124 PG03300001E 1CD1C

CA08102001E

For more information visit: www.EatonElectrical.com

34-144

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Combination Starters Fusible


Table 34-219. Class ECE20 IEC Rated Fusible Combination Fixed Heater OLR Reversing
Motor Voltage Max. hp Rating Magnet Coil Voltage Fuse Clip Amps 3-Pole Type 1 General Purpose Catalog Number ECE20A1AAB_ ECE20A1EAB_ ECE20A1BAB_ ECE20A1CAB_ ECE20A1DAB_ ECE20B1AAB_ ECE20B1EAB_ ECE20B1BAB_ ECE20B1CAB_ ECE20B1DAB_ ECE20C1AAB_ ECE20C1EAB_ ECE20C1BAB_ ECE20C1CAB_ ECE20C1DAB_ ECE20D1AAC_ ECE20D1EAC_ ECE20D1BAC_ ECE20D1CAC_ ECE20D1DAC_ ECE20E1AAC_ ECE20E1EAC_ ECE20E1BAC_ ECE20E1CAC_ ECE20E1DAC_ ECE20F1AAE_ ECE20F1EAE_ ECE20F1BAE_ ECE20F1CAE_ ECE20F1DAE_ ECE20G1AAE_ ECE20G1EAE_ ECE20G1BAE_ ECE20G1CAE_ ECE20G1DAE_ Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 3R Rainproof Catalog Number ECE20A2AAB_ ECE20A2EAB_ ECE20A2BAB_ ECE20A2CAB_ ECE20A2DAB_ ECE20B2AAB_ ECE20B2EAB_ ECE20B2BAB_ ECE20B2CAB_ ECE20B2DAB_ ECE20C2AAB_ ECE20C2EAB_ ECE20C2BAB_ ECE20C2CAB_ ECE20C2DAB_ ECE20D2AAC_ ECE20D2EAC_ ECE20D2BAC_ ECE20D2CAC_ ECE20D2DAC_ ECE20E2AAC_ ECE20E2EAC_ ECE20E2BAC_ ECE20E2CAC_ ECE20E2DAC_ ECE20F2AAE_ ECE20F2EAE_ ECE20F2BAE_ ECE20F2CAE_ ECE20F2DAE_ ECE20G2AAE_ ECE20G2EAE_ ECE20G2BAE_ ECE20G2CAE_ ECE20G2DAE_ ECE20H2AAE_ ECE20H2EAE_ ECE20H2BAE_ ECE20H2CAE_ ECE20H2DAE_ Price U.S. $

Vol. 2, Ref. No. [0408]

1-Phase

3-Phase

3-Pole Component Starter (Open) Catalog Number * AE57AN0_ * * * * * AE57BN0_ * * * * * AE57CN0_ * * * * * AE57DN0_ * * * * * AE57EN0_ * * * * * AE57FN0_ * * * * * AE57GN0_ * * * * * * * * * AE57HN0_

Size A 45 mm

34

115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575

1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5

1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30

120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600

30

Size B 45 mm
30

Size C 45 mm
30

Size D 45 mm
30

Size E 45 mm
30

Size F 45 mm
60

Size G 65 mm
60

Size H 65 mm
115 3 120 60 ECE20H1AAE_ 200 10 208 ECE20H1EAE_ 230 7-1/2 15 240 ECE20H1BAE_ 460 30 480 ECE20H1CAE_ 575 40 600 ECE20H1DAE_ 1 set of 3 xed heater overload relays included. For additional coil voltages, refer to Page 34-125. Starter includes xed heater overload. For Enclosed IEC Starters, select sufx code -R_ from the table below. Overload relay range can not exceed contactor amperage rating. For Open IEC Starters, use sufx code -F_ or -K_ from the table below. Sufx Overload Enclosed/ Range Open R4 R8/FC R9/FD R10/FE R11/FF R12/FG R13/FH Omit OLR .25 .40A .40 .63A .63 1.0A 1.0 1.4A 1.8 1.8A 1.7 2.4A Sufx Overload Enclosed/ Range Open R14/FJ R15/FK R16/FL R17/FM R18/FN R19/FP R20/FQ 2.2 3.1A 2.8 4.0A 3.5 5A 4.5 6.5A 6.5 8.5A 7.5 11A 10.5 14A Sufx Overload Enclosed/ Range Open R21/FR R22/FS R23/FT R24/KA R25/KB R26/KC R27/KD 13 19A 18 24A 24 32A 18 25A 22 32A 29 42A 36 52A

Note: Overload relay range can not exceed contactor amperage rating.
*Please contact your local Eaton sales ofce.

Modications . . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . .

Page 34-49 Page 34-95 Page 34-100 Page 34-124 PG03300001E 1CD1C CA08102001E

For more information visit: www.EatonElectrical.com

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0409]

34-145

Combination Starters Fusible

Table 34-219. Class ECE20 IEC Rated Fusible Combination Fixed Heater OLR Reversing (Continued)
Motor Voltage Max. hp Rating Magnet Coil Voltage Fuse Clip Amps 3-Pole Type 4X Watertight & Dust-Tight Stainless Steel Catalog Price Number U.S. $ ECE20A4AAB_ ECE20A4EAB_ ECE20A4BAB_ ECE20A4CAB_ ECE20A4DAB_ ECE20B4AAB_ ECE20B4EAB_ ECE20B4BAB_ ECE20B4CAB_ ECE20B4DAB_ ECE20C4AAB_ ECE20C4EAB_ ECE20C4BAB_ ECE20C4CAB_ ECE20C4DAB_ ECE20D4AAC_ ECE20D4EAC_ ECE20D4BAC_ ECE20D4CAC_ ECE20D4DAC_ ECE20E4AAC_ ECE20E4EAC_ ECE20E4BAC_ ECE20E4CAC_ ECE20E4DAC_ ECE20F4AAE_ ECE20F4EAE_ ECE20F4BAE_ ECE20F4CAE_ ECE20F4DAE_ ECE20G4AAE_ ECE20G4EAE_ ECE20G4BAE_ ECE20G4CAE_ ECE20G4DAE_ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 12 Dust-Tight Catalog Number ECE20A8AAB_ ECE20A8EAB_ ECE20A8BAB_ ECE20A8CAB_ ECE20A8DAB_ ECE20B8AAB_ ECE20B8EAB_ ECE20B8BAB_ ECE20B8CAB_ ECE20B8DAB_ ECE20C8AAB_ ECE20C8EAB_ ECE20C8BAB_ ECE20C8CAB_ ECE20C8DAB_ ECE20D8AAC_ ECE20D8EAC_ ECE20D8BAC_ ECE20D8CAC_ ECE20D8DAC_ ECE20E8AAC_ ECE20E8EAC_ ECE20E8BAC_ ECE20E8CAC_ ECE20E8DAC_ ECE20F8AAE_ ECE20F8EAE_ ECE20F8BAE_ ECE20F8CAE_ ECE20F8DAE_ ECE20G8AAE_ ECE20G8EAE_ ECE20G8BAE_ ECE20G8CAE_ ECE20G8DAE_ ECE20H8AAE_ ECE20H8EAE_ ECE20H8BAE_ ECE20H8CAE_ ECE20H8DAE_ Price U.S. $ 3-Pole Component Starter (Open) Catalog Number * AE57AN0_ * * * * * AE57BN0_ * * * * * AE57CN0_ * * * * * AE57DN0_ * * * * * AE57EN0_ * * * * * AE57FN0_ * * * * * AE57GN0_ * * * * * * * * * AE57HN0_

1-Phase

3-Phase

Size A 45 mm
115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 115 200 230 460 575 1/4 1/2 1/2 1 1/2 2 1 3 2 3 2 5 3 5 1-1/2 1-1/2 3 5 2 2 5 7-1/2 3 3 7-1/2 10 5 5 10 15 5 7-1/2 15 20 7-1/2 10 20 25 7-1/2 10 25 30 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 120 208 240 480 600 30

34

Size B 45 mm
30

Size C 45 mm
30

Size D 45 mm
30

Size E 45 mm
30

Size F 45 mm
60

Size G 65 mm
60

Size H 65 mm
115 3 120 60 ECE20H4AAE_ 200 10 208 ECE20H4EAE_ 230 7-1/2 15 240 ECE20H4BAE_ 460 30 480 ECE20H4CAE_ 575 40 600 ECE20H4DAE_ 1 set of 3 xed heater overload relays included. For additional coil voltages, refer to Page 34-125. Starter includes xed heater overload. For Enclosed IEC Starters, select sufx code -R_ from the table below. Overload relay range can not exceed contactor amperage rating. For Open IEC Starters, use sufx code -F_ or -K_ from the table below. Sufx Overload Enclosed/ Range Open R4 R8/FC R9/FD R10/FE R11/FF R12/FG R13/FH Omit OLR .25 .40A .40 .63A .63 1.0A 1.0 1.4A 1.8 1.8A 1.7 2.4A Sufx Overload Enclosed/ Range Open R14/FJ R15/FK R16/FL R17/FM R18/FN R19/FP R20/FQ 2.2 3.1A 2.8 4.0A 3.5 5A 4.5 6.5A 6.5 8.5A 7.5 11A 10.5 14A Sufx Overload Enclosed/ Range Open R21/FR R22/FS R23/FT R24/KA R25/KB R26/KC R27/KD 13 19A 18 24A 24 32A 18 25A 22 32A 29 42A 36 52A

Note: Overload relay range can not exceed contactor amperage rating.
These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECE20A4AAB. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. *Please contact your local Eaton sales ofce.

Modications . . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . .

Page 34-49 Page 34-95 Page 34-100 Page 34-124 PG03300001E 1CD1C

CA08102001E

For more information visit: www.EatonElectrical.com

34-146

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Combination Starters GMCP

Vol. 2, Ref. No. [0410]

Product Selection
Table 34-220. Class ECE22 IEC Rated Combination GMCP Interchangeable Heater OLR Non-reversing
Motor Voltage Max. hp Rating Magnet Coil Voltage GMCP Rating (trip range) Amperes 3-Pole Type 1 General Purpose Catalog Number ECE22A1AAB ECE22A1EAB ECE22A1BAB ECE22A1CAB ECE22B1AAC ECE22B1EAC ECE22B1BAC ECE22B1CAC ECE22C1AAD ECE22C1EAD ECE22C1BAD ECE22C1CAD ECE22D1AAE ECE22D1EAE ECE22D1BAE ECE22D1CAE ECE22E1AAE ECE22E1EAE ECE22E1BAE ECE22E1CAE ECE22F1AAF ECE22F1EAF ECE22F1BAF ECE22F1CAF ECE22G1AAF ECE22G1EAF ECE22G1BAF ECE22G1CAF ECE22H1AAF ECE22H1EAF ECE22H1BAF ECE22H1CAF Price U.S. $ * * * * * * * * * * * 825. * * * * * * * * * * * * * * * * * * * * 3-Pole Type 3R Rainproof Catalog Number ECE22A2AAB ECE22A2EAB ECE22A2BAB ECE22A2CAB ECE22B2AAC ECE22B2EAC ECE22B2BAC ECE22B2CAC ECE22C2AAD ECE22C2EAD ECE22C2BAD ECE22C2CAD ECE22D2AAE ECE22D2EAE ECE22D2BAE ECE22D2CAE ECE22E2AAE ECE22E2EAE ECE22E2BAE ECE22E2CAE ECE22F2AAF ECE22F2EAF ECE22F2BAF ECE22F2CAF ECE22G2AAF ECE22G2EAF ECE22G2BAF ECE22G2CAF ECE22H2AAF ECE22H2EAF ECE22H2BAF ECE22H2CAF Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Component Starter (Open) Catalog Number AE16ANS0AC AE16ANS0EC AE16ANS0BC AE16ANS0CC AE16BNS0AC AE16BNS0EC AE16BNS0BC AE16BNS0CC AE16CNS0AC AE16CNS0EC AE16CNS0BC AE16CNS0CC AE16DNS0AC AE16DNS0EC AE16DNS0BC AE16DNS0CC AE16ENS0AC AE16ENS0EC AE16ENS0BC AE16ENS0CC AE16FNS0AC AE16FNS0EC AE16FNS0BC AE16FNS0CC AE16GNS0AB AE16GNS0EB AE16GNS0BB AE16GNS0CB AE16HNS0AB AE16HNS0EB AE16HNS0BB AE16HNS0CB

1-Phase

3-Phase

34

Size A 45 mm
115 200 230 460 1/6 1/6 1/2 1/4 1/2 1/2 1-1/2 1/2 1-1/2 2 3 1 3 2 3 2 5 3 5 3 7-1/2 1/2 1/2 1-1/2 1-1/2 1-1/2 3 3 3 7-1/2 5 5 10 5 7-1/2 15 7-1/2 10 20 7-1/2 10 25 10 15 30 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 3 (15-30)

Size B 45 mm
115 200 230 460 7 (35-70)

Size C 45 mm
115 200 230 460 15 (75-150)

Size D 45 mm
115 200 230 460 30 (150-300)

Size E 45 mm
115 200 230 460 30 (150-300)

Size F 45 mm
115 200 230 460 50 (250-500)

Size G 65 mm
115 200 230 460 50 (250-500)

Size H 65 mm
115 200 230 460 50 (250-500)

Starters do not include heater packs. Select 1 carton of 3 heater packs. For Heater Pack Selection, see Page 34-93. Starters with Electronic Overload, see Page 34-55 of Modication Codes. For additional coil voltages, see Page 34-125. GMCP is rated for 480V maximum. *Please contact your local Eaton sales ofce.

Modications . . . . . . . . . . . . . . . . . . . . Page 34-49 Heater Pack Selection . . . . . . . . . . . . Page 34-93 Technical Data . . . . . . . . . . . . . . . . . . . Page 34-95 Accessories . . . . . . . . . . . . . . . . . . . . . Page 34-100 Cover Control . . . . . . . . . . . . . . . . . . . . Page 34-124 Dimensions . . . . . . . . . . . . . . . . . . . . . . PG03300001E Discount Symbol . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0411]

34-147

Combination Starters GMCP

Table 34-220. Class ECE22 IEC Rated Combination GMCP Interchangeable Heater OLR Non-reversing (Continued)
Motor Voltage Max. hp Rating Magnet Coil Voltage GMCP Rating (trip range) Amperes 3-Pole Type 4X Watertight & Dust-Tight Stainless Steel Catalog Number ECE22A4AAB ECE22A4EAB ECE22A4BAB ECE22A4CAB ECE22B4AAC ECE22B4EAC ECE22B4BAC ECE22B4CAC ECE22C4AAD ECE22C4EAD ECE22C4BAD ECE22C4CAD ECE22D4AAE ECE22D4EAE ECE22D4BAE ECE22D4CAE ECE22E4AAE ECE22E4EAE ECE22E4BAE ECE22E4CAE ECE22F4AAF ECE22F4EAF ECE22F4BAF ECE22F4CAF ECE22G4AAF ECE22G4EAF ECE22G4BAF ECE22G4CAF ECE22H4AAF ECE22H4EAF ECE22H4BAF ECE22H4CAF Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 12 Dust-Tight Catalog Number ECE22A8AAB ECE22A8EAB ECE22A8BAB ECE22A8CAB ECE22B8AAC ECE22B8EAC ECE22B8BAC ECE22B8CAC ECE22C8AAD ECE22C8EAD ECE22C8BAD ECE22C8CAD ECE22D8AAE ECE22D8EAE ECE22D8BAE ECE22D8CAE ECE22E8AAE ECE22E8EAE ECE22E8BAE ECE22E8CAE ECE22F8AAF ECE22F8EAF ECE22F8BAF ECE22F8CAF ECE22G8AAF ECE22G8EAF ECE22G8BAF ECE22G8CAF ECE22H8AAF ECE22H8EAF ECE22H8BAF ECE22H8CAF Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Component Starter (Open) Catalog Number AE16ANS0AC AE16ANS0EC AE16ANS0BC AE16ANS0CC AE16BNS0AC AE16BNS0EC AE16BNS0BC AE16BNS0CC AE16CNS0AC AE16CNS0EC AE16CNS0BC AE16CNS0CC AE16DNS0AC AE16DNS0EC AE16DNS0BC AE16DNS0CC AE16ENS0AC AE16ENS0EC AE16ENS0BC AE16ENS0CC AE16FNS0AC AE16FNS0EC AE16FNS0BC AE16FNS0CC AE16GNS0AB AE16GNS0EB AE16GNS0BB AE16GNS0CB AE16HNS0AB AE16HNS0EB AE16HNS0BB AE16HNS0CB

1-Phase

3-Phase

Size A 45 mm
115 200 230 460 1/6 1/6 1/2 1/4 1/2 1/2 1-1/2 1/2 1-1/2 2 3 1 3 2 3 2 5 3 5 3 7-1/2 1/2 1/2 1-1/2 1-1/2 1-1/2 3 3 3 7-1/2 5 5 10 5 7-1/2 15 7-1/2 10 20 7-1/2 10 25 10 15 30 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 3 (15-30)

34

Size B 45 mm
115 200 230 460 7 (35-70)

Size C 45 mm
115 200 230 460 15 (75-150)

Size D 45 mm
115 200 230 460 30 (150-300)

Size E 45 mm
115 200 230 460 30 (150-300)

Size F 45 mm
115 200 230 460 50 (250-500)

Size G 65 mm
115 200 230 460 50 (250-500)

Size H 65 mm
115 200 230 460 50 (250-500)

Starters do not include heater packs. Select 1 carton of 3 heater packs. For Heater Pack Selection, see Page 34-93. Starters with Electronic Overload, see Page 34-55 of Modication Codes. For additional coil voltages, see Page 34-125. GMCP is rated for 480V maximum. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECE22A4AAB. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. *Please contact your local Eaton sales ofce.

Modications. . . . . . . . . . . . . . . . . . . . Heater Pack Selection . . . . . . . . . . . . Technical Data. . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . Dimensions. . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-49 Page 34-93 Page 34-95 Page 34-100 Page 34-124 PG03300001E 1CD1C

34-148

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Combination Starters GMCP


Table 34-221. Class ECE23 IEC Rated Combination GMCP Interchangeable Heater OLR Reversing
Motor Voltage Max. hp Rating Magnet Coil Voltage GMCP Rating (trip range) Amperes 3-Pole Type 1 General Purpose Catalog Number 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 3 (15-30) ECE23A1AAB ECE23A1EAB ECE23A1BAB ECE23A1CAB ECE23B1AAC ECE23B1EAC ECE23B1BAC ECE23B1CAC ECE23C1AAD ECE23C1EAD ECE23C1BAD ECE23C1CAD ECE23D1AAE ECE23D1EAE ECE23D1BAE ECE23D1CAE ECE23E1AAE ECE23E1EAE ECE23E1BAE ECE23E1CAE ECE23F1AAF ECE23F1EAF ECE23F1BAF ECE23F1CAF ECE23G1AAF ECE23G1EAF ECE23G1BAF ECE23G1CAF ECE23H1AAF ECE23H1EAF ECE23H1BAF ECE23H1CAF Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 3R Rainproof Catalog Number ECE23A2AAB ECE23A2EAB ECE23A2BAB ECE23A2CAB ECE23B2AAC ECE23B2EAC ECE23B2BAC ECE23B2CAC ECE23C2AAD ECE23C2EAD ECE23C2BAD ECE23C2CAD ECE23D2AAE ECE23D2EAE ECE23D2BAE ECE23D2CAE ECE23E2AAE ECE23E2EAE ECE23E2BAE ECE23E2CAE ECE23F2AAF ECE23F2EAF ECE23F2BAF ECE23F2CAF ECE23G2AAF ECE23G2EAF ECE23G2BAF ECE23G2CAF ECE23H2AAF ECE23H2EAF ECE23H2BAF ECE23H2CAF Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Vol. 2, Ref. No. [0412]

3-Pole Component Starter (Open) Catalog Number AE56AN0AC AE56AN0EC AE56AN0BC AE56AN0CC AE56BN0AC AE56BN0EC AE56BN0BC AE56BN0CC AE56CN0AC AE56CN0EC AE56CN0BC AE56CN0CC AE56DN0AC AE56DN0EC AE56DN0BC AE56DN0CC AE56EN0AC AE56EN0EC AE56EN0BC AE56EN0CC AE56FN0AC AE56FN0EC AE56FN0BC AE56FN0CC AE56GN0AB AE56GN0EB AE56GN0BB AE56GN0CB AE56HN0AB AE56HN0EB AE56HN0BB AE56HN0CB

1-Phase

3-Phase

Size A 45 mm

34

115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460

1/6 1/6 1/2 1/4 1/2 1/2 1-1/2 1/2 1-1/2 2 3 1 3 2 3 2 5 3 5 3 7-1/2

1/2 1/2 1-1/2 1-1/2 1-1/2 3 3 3 7-1/2 5 5 10 5 7-1/2 15 7-1/2 10 20 7-1/2 10 25 10 15 30

Size B 45 mm
7 (35-70)

Size C 45 mm
15 (75-150)

Size D 45 mm
30 (150-300)

Size E 45 mm
30 (150-300)

Size F 45 mm
50 (250-500)

Size G 65 mm
50 (250-500)

Size H 65 mm
50 (250-500)

Starters do not include heater packs. Select 1 carton of 3 heater packs. For Heater Pack Selection, see Page 34-93. Starters with Electronic Overload, see Page 34-55 of Modication Codes. For additional coil voltages, see Page 34-125. GMCP is rated for 480V maximum. *Please contact your local Eaton sales ofce.

Modications . . . . . . . . . . . . . . . . . . . . Page 34-49 Heater Pack Selection . . . . . . . . . . . . Page 34-93 Technical Data . . . . . . . . . . . . . . . . . . . Page 34-95 Accessories . . . . . . . . . . . . . . . . . . . . . Page 34-100 Cover Control . . . . . . . . . . . . . . . . . . . . Page 34-124 Dimensions . . . . . . . . . . . . . . . . . . . . . . PG03300001E Discount Symbol . . . . . . . . . . . . . . . . . 1CD1C For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0413]

34-149

Combination Starters GMCP

Table 34-221. Class ECE23 IEC Rated Combination GMCP Interchangeable Heater OLR Reversing (Continued)
Motor Voltage Max. hp Rating Magnet Coil Voltage GMCP Rating (trip range) Amperes 3-Pole Type 4X Watertight & Dust-Tight Stainless Steel Catalog Number 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 3 (15-30) ECE23A4AAB ECE23A4EAB ECE23A4BAB ECE23A4CAB ECE23B4AAC ECE23B4EAC ECE23B4BAC ECE23B4CAC ECE23C4AAD ECE23C4EAD ECE23C4BAD ECE23C4CAD ECE23D4AAE ECE23D4EAE ECE23D4BAE ECE23D4CAE ECE23E4AAE ECE23E4EAE ECE23E4BAE ECE23E4CAE ECE23F4AAF ECE23F4EAF ECE23F4BAF ECE23F4CAF ECE23G4AAF ECE23G4EAF ECE23G4BAF ECE23G4CAF ECE23H4AAF ECE23H4EAF ECE23H4BAF ECE23H4CAF Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 12 Dust-Tight Catalog Number ECE23A8AAB ECE23A8EAB ECE23A8BAB ECE23A8CAB ECE23B8AAC ECE23B8EAC ECE23B8BAC ECE23B8CAC ECE23C8AAD ECE23C8EAD ECE23C8BAD ECE23C8CAD ECE23D8AAE ECE23D8EAE ECE23D8BAE ECE23D8CAE ECE23E8AAE ECE23E8EAE ECE23E8BAE ECE23E8CAE ECE23F8AAF ECE23F8EAF ECE23F8BAF ECE23F8CAF ECE23G8AAF ECE23G8EAF ECE23G8BAF ECE23G8CAF ECE23H8AAF ECE23H8EAF ECE23H8BAF ECE23H8CAF Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Component Starter (Open) Catalog Number AE56AN0AC AE56AN0EC AE56AN0BC AE56AN0CC AE56BN0AC AE56BN0EC AE56BN0BC AE56BN0CC AE56CN0AC AE56CN0EC AE56CN0BC AE56CN0CC AE56DN0AC AE56DN0EC AE56DN0BC AE56DN0CC AE56EN0AC AE56EN0EC AE56EN0BC AE56EN0CC AE56FN0AC AE56FN0EC AE56FN0BC AE56FN0CC AE56GN0AB AE56GN0EB AE56GN0BB AE56GN0CB AE56HN0AB AE56HN0EB AE56HN0BB AE56HN0CB

1-Phase

3-Phase

Size A 45 mm
115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 1/6 1/6 1/2 1/4 1/2 1/2 1-1/2 1/2 1-1/2 2 3 1 3 2 3 2 5 3 5 3 7-1/2 1/2 1/2 1-1/2 1-1/2 1-1/2 3 3 3 7-1/2 5 5 10 5 7-1/2 15 7-1/2 10 20 7-1/2 10 25 10 15 30

34

Size B 45 mm
7 (35-70)

Size C 45 mm
15 (75-150)

Size D 45 mm
30 (150-300)

Size E 45 mm
30 (150-300)

Size F 45 mm
50 (250-500)

Size G 65 mm
50 (250-500)

Size H 65 mm
50 (250-500)

Starters do not include heater packs. Select 1 carton of 3 heater packs. For Heater Pack Selection, see Page 34-93. Starters with Electronic Overload, see Page 34-55 of Modication Codes. For additional coil voltages, see Page 34-125. GMCP is rated for 480V maximum. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECE23B4AAC. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. *Please contact your local Eaton sales ofce.

Modications. . . . . . . . . . . . . . . . . . . . Heater Pack Selection . . . . . . . . . . . . Technical Data. . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . Dimensions. . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-49 Page 34-93 Page 34-95 Page 34-100 Page 34-124 PG03300001E 1CD1C

34-150

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Combination Starters GMCP


Table 34-222. Class ECE25 IEC Rated Combination GMCP Fixed Heater OLR Non-reversing
Motor Voltage Max. hp Rating Magnet Coil Voltage GMCP Rating (trip range) Amperes 3-Pole Type 1 General Purpose Catalog Number ECE25A1AAB_ ECE25A1EAB_ ECE25A1BAB_ ECE25A1CAB_ ECE25B1AAC_ ECE25B1EAC_ ECE25B1BAC_ ECE25B1CAC_ ECE25C1AAD_ ECE25C1EAD_ ECE25C1BAD_ ECE25C1CAD_ ECE25D1AAE_ ECE25D1EAE_ ECE25D1BAE_ ECE25D1CAE_ ECE25E1AAE_ ECE25E1EAE_ ECE25E1BAE_ ECE25E1CAE_ ECE25F1AAF_ ECE25F1EAF_ ECE25F1BAF_ ECE25F1CAF_ ECE25G1AAF_ ECE25G1EAF_ ECE25G1BAF_ ECE25G1CAF_ ECE25H1AAF_ ECE25H1EAF_ ECE25H1BAF_ ECE25H1CAF_ Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 3R Rainproof Catalog Number ECE25A2AAB_ ECE25A2EAB_ ECE25A2BAB_ ECE25A2CAB_ ECE25B2AAC_ ECE25B2EAC_ ECE25B2BAC_ ECE25B2CAC_ ECE25C2AAD_ ECE25C2EAD_ ECE25C2BAD_ ECE25C2CAD_ ECE25D2AAE_ ECE25D2EAE_ ECE25D2BAE_ ECE25D2CAE_ ECE25E2AAE_ ECE25E2EAE_ ECE25E2BAE_ ECE25E2CAE_ ECE25F2AAF_ ECE25F2EAF_ ECE25F2BAF_ ECE25F2CAF_ ECE25G2AAF_ ECE25G2EAF_ ECE25G2BAF_ ECE25G2CAF_ ECE25H2AAF_ ECE25H2EAF_ ECE25H2BAF_ ECE25H2CAF_ Price U.S. $

Vol. 2, Ref. No. [0414]

3-Pole Component Starter (Open) Catalog Number * AE17ANS0_ * * * * AE17BNS0_ * * * * AE17CNS0_ * * * * AE17DNS0_ * * * * AE17ENS0_ * * * * AE17FNS0_ * * * * AE17GNS0_ * * * * * * * AE17HNS0_

1-Phase

3-Phase

Size A 45 mm

34

115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460

1/6 1/6 1/2 1/4 1/2 1/2 1-1/2 1/2 1-1/2 2 3 1 3 2 3 2 5 3 5 3 7-1/2

1/2 1/2 1-1/2 1-1/2 1-1/2 3 3 3 7-1/2 5 5 10 5 7-1/2 15 7-1/2 10 20 7-1/2 10 25 10 15 30

120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480

3 (15-30)

Size B 45 mm
7 (35-70)

Size C 45 mm
15 (75-150)

Size D 45 mm
30 (150-300)

Size E 45 mm
30 (150-300)

Size F 45 mm
50 (250-500)

Size G 65 mm
50 (250-500)

Size H 65 mm
50 (250-500)

1 set of 3 xed heater overload relays included. For additional coil voltages, refer to Page 34-125. Starter includes xed heater overload. For Enclosed IEC Starters, select sufx code -R_ from the table below. Overload relay range can not exceed contactor amperage rating. For Open IEC Starters, use sufx code -F_ or -K_ from the table below. Sufx Overload Enclosed/ Range Open R4 R8/FC R9/FD R10/FE R11/FF R12/FG R13/FH Omit OLR .25 .40A .40 .63A .63 1.0A 1.0 1.4A 1.8 1.8A 1.7 2.4A Sufx Overload Enclosed/ Range Open R14/FJ R15/FK R16/FL R17/FM R18/FN R19/FP R20/FQ 2.2 3.1A 2.8 4.0A 3.5 5A 4.5 6.5A 6.5 8.5A 7.5 11A 10.5 14A Sufx Overload Enclosed/ Range Open R21/FR R22/FS R23/FT R24/KA R25/KB R26/KC R27/KD 13 19A 18 24A 24 32A 18 25A 22 32A 29 42A 36 52A

GMCP is rated for 480V maximum. *Please contact your local Eaton sales ofce.

Modications . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . For more information visit: www.EatonElectrical.com

Page 34-49 Page 34-95 Page 34-100 Page 34-124 PG03300001E 1CD1C CA08102001E

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0415]

34-151

Combination Starters GMCP

Table 34-222. Class ECE25 IEC Rated Combination GMCP Fixed Heater OLR Non-reversing (Continued)
Motor Voltage Max. hp Rating Magnet Coil Voltage GMCP Rating (trip range) Amperes 3-Pole Type 4X Watertight & Dust-Tight Stainless Steel Catalog Number ECE25A4AAB_ ECE25A4EAB_ ECE25A4BAB_ ECE25A4CAB_ ECE25B4AAC_ ECE25B4EAC_ ECE25B4BAC_ ECE25B4CAC_ ECE25C4AAD_ ECE25C4EAD_ ECE25C4BAD_ ECE25C4CAD_ ECE25D4AAE_ ECE25D4EAE_ ECE25D4BAE_ ECE25D4CAE_ ECE25E4AAE_ ECE25E4EAE_ ECE25E4BAE_ ECE25E4CAE_ ECE25F4AAF_ ECE25F4EAF_ ECE25F4BAF_ ECE25F4CAF_ ECE25G4AAF_ ECE25G4EAF_ ECE25G4BAF_ ECE25G4CAF_ ECE25H4AAF_ ECE25H4EAF_ ECE25H4BAF_ ECE25H4CAF_ Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 12 Dust-Tight Catalog Number ECE25A8AAB_ ECE25A8EAB_ ECE25A8BAB_ ECE25A8CAB_ ECE25B8AAC_ ECE25B8EAC_ ECE25B8BAC_ ECE25B8CAC_ ECE25C8AAD_ ECE25C8EAD_ ECE25C8BAD_ ECE25C8CAD_ ECE25D8AAE_ ECE25D8EAE_ ECE25D8BAE_ ECE25D8CAE_ ECE25E8AAE_ ECE25E8EAE_ ECE25E8BAE_ ECE25E8CAE_ ECE25F8AAF_ ECE25F8EAF_ ECE25F8BAF_ ECE25F8CAF_ ECE25G8AAF_ ECE25G8EAF_ ECE25G8BAF_ ECE25G8CAF_ ECE25H8AAF_ ECE25H8EAF_ ECE25H8BAF_ ECE25H8CAF_ Price U.S. $ 3-Pole Component Starter (Open) Catalog Number * AE17ANS0_ * * * * AE17BNS0_ * * * * AE17CNS0_ * * * * AE17DNS0_ * * * * AE17ENS0_ * * * * AE17FNS0_ * * * * AE17GNS0_ * * * * * * * AE17HNS0_

1-Phase

3-Phase

Size A 45 mm
115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 1/6 1/6 1/2 1/4 1/2 1/2 1-1/2 1/2 1-1/2 2 3 1 3 2 3 2 5 3 5 3 7-1/2 1/2 1/2 1-1/2 1-1/2 1-1/2 3 3 3 7-1/2 5 5 10 5 7-1/2 15 7-1/2 10 20 7-1/2 10 25 10 15 30 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 3 (15-30)

34

Size B 45 mm
7 (35-70)

Size C 45 mm
15 (75-150)

Size D 45 mm
30 (150-300)

Size E 45 mm
30 (150-300)

Size F 45 mm
50 (250-500)

Size G 65 mm
50 (250-500)

Size H 65 mm
50 (250-500)

1 set of 3 xed heater overload relays included. For additional coil voltages, refer to Page 34-125. Starter includes xed heater overload. For Enclosed IEC Starters, select sufx code -R_ from the table below. Overload relay range can not exceed contactor amperage rating. For Open IEC Starters, use sufx code -F_ or -K_ from the table below. Sufx Overload Enclosed/ Range Open R4 R8/FC R9/FD R10/FE R11/FF R12/FG R13/FH Omit OLR .25 .40A .40 .63A .63 1.0A 1.0 1.4A 1.8 1.8A 1.7 2.4A Sufx Overload Enclosed/ Range Open R14/FJ R15/FK R16/FL R17/FM R18/FN R19/FP R20/FQ 2.2 3.1A 2.8 4.0A 3.5 5A 4.5 6.5A 6.5 8.5A 7.5 11A 10.5 14A Sufx Overload Enclosed/ Range Open R21/FR R22/FS R23/FT R24/KA R25/KB R26/KC R27/KD 13 19A 18 24A 24 32A 18 25A 22 32A 29 42A 36 52A These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECE25A4AAB. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. *Please contact your local Eaton sales ofce.

GMCP is rated for 480V maximum.

Modications . . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-49 Page 34-95 Page 34-100 Page 34-124 PG03300001E 1CD1C

34-152

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Combination Starters GMCP


Table 34-223. Class ECE26 IEC Rated Combination GMCP Fixed Heater OLR Reversing
Motor Voltage Max. hp Rating Magnet Coil Voltage GMCP Rating (trip range) Amperes 3-Pole Type 1 General Purpose Catalog Number ECE26A1AAB_ ECE26A1EAB_ ECE26A1BAB_ ECE26A1CAB_ ECE26B1AAC_ ECE26B1EAC_ ECE26B1BAC_ ECE26B1CAC_ ECE26C1AAD_ ECE26C1EAD_ ECE26C1BAD_ ECE26C1CAD_ ECE26D1AAE_ ECE26D1EAE_ ECE26D1BAE_ ECE26D1CAE_ ECE26E1AAE_ ECE26E1EAE_ ECE26E1BAE_ ECE26E1CAE_ ECE26F1AAF_ ECE26F1EAF_ ECE26F1BAF_ ECE26F1CAF_ ECE26G1AAF_ ECE26G1EAF_ ECE26G1BAF_ ECE26G1CAF_ ECE26H1AAF_ ECE26H1EAF_ ECE26H1BAF_ ECE26H1CAF_ Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 3R Rainproof Catalog Number ECE26A2AAB_ ECE26A2EAB_ ECE26A2BAB_ ECE26A2CAB_ ECE26B2AAC_ ECE26B2EAC_ ECE26B2BAC_ ECE26B2CAC_ ECE26C2AAD_ ECE26C2EAD_ ECE26C2BAD_ ECE26C2CAD_ ECE26D2AAE_ ECE26D2EAE_ ECE26D2BAE_ ECE26D2CAE_ ECE26E2AAE_ ECE26E2EAE_ ECE26E2BAE_ ECE26E2CAE_ ECE26F2AAF_ ECE26F2EAF_ ECE26F2BAF_ ECE26F2CAF_ ECE26G2AAF_ ECE26G2EAF_ ECE26G2BAF_ ECE26G2CAF_ ECE26H2AAF_ ECE26H2EAF_ ECE26H2BAF_ ECE26H2CAF_ Price U.S. $

Vol. 2, Ref. No. [0416]

3-Pole Component Starter (Open) Catalog Number * AE57AN0_ * * * * AE57BN0_ * * * * AE57CN0_ * * * * AE57DN0_ * * * * AE57EN0_ * * * * AE57FN0_ * * * * AE57GN0_ * * * * * * * AE57HN0_

1-Phase

3-Phase

Size A 45 mm

34

115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460

1/6 1/6 1/2 1/4 1/2 1/2 1-1/2 1/2 1-1/2 2 3 1 3 2 3 2 5 3 5 3 7-1/2

1/2 1/2 1-1/2 1-1/2 1-1/2 3 3 3 7-1/2 5 5 10 5 7-1/2 15 7-1/2 10 20 7-1/2 10 25 10 15 30

120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480

3 (15-30)

Size B 45 mm
7 (35-70)

Size C 45 mm
15 (75-150)

Size D 45 mm
30 (150-300)

Size E 45 mm
30 (150-300)

Size F 45 mm
50 (250-500)

Size G 65 mm
50 (250-500)

Size H 65 mm
50 (250-500)

1 set of 3 xed heater overload relays included. For additional coil voltages, refer to Page 34-125. Starter includes xed heater overload. For Enclosed IEC Starters, select sufx code -R_ from the table below. Overload relay range can not exceed contactor amperage rating. For Open IEC Starters, use sufx code -F_ or -K_ from the table below. Sufx Overload Enclosed/ Range Open R4 R8/FC R9/FD R10/FE R11/FF R12/FG R13/FH Omit OLR .25 .40A .40 .63A .63 1.0A 1.0 1.4A 1.8 1.8A 1.7 2.4A Sufx Overload Enclosed/ Range Open R14/FJ R15/FK R16/FL R17/FM R18/FN R19/FP R20/FQ 2.2 3.1A 2.8 4.0A 3.5 5A 4.5 6.5A 6.5 8.5A 7.5 11A 10.5 14A Sufx Overload Enclosed/ Range Open R21/FR R22/FS R23/FT R24/KA R25/KB R26/KC R27/KD 13 19A 18 24A 24 32A 18 25A 22 32A 29 42A 36 52A

GMCP is rated for 480V maximum. *Please contact your local Eaton sales ofce.

Modications . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . For more information visit: www.EatonElectrical.com

Page 34-49 Page 34-95 Page 34-100 Page 34-124 PG03300001E 1CD1C CA08102001E

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0417]

34-153

Combination Starters GMCP

Table 34-223. Class ECE26 IEC Rated Combination GMCP Fixed Heater OLR Reversing (Continued)
Motor Voltage Max. hp Rating Magnet Coil Voltage GMCP Rating (trip range) Amperes 3-Pole Type 4X Watertight & Dust-Tight Stainless Steel Catalog Number ECE26A4AAB_ ECE26A4EAB_ ECE26A4BAB_ ECE26A4CAB_ ECE26B4AAC_ ECE26B4EAC_ ECE26B4BAC_ ECE26B4CAC_ ECE26C4AAD_ ECE26C4EAD_ ECE26C4BAD_ ECE26C4CAD_ ECE26D4AAE_ ECE26D4EAE_ ECE26D4BAE_ ECE26D4CAE_ ECE26E4AAE_ ECE26E4EAE_ ECE26E4BAE_ ECE26E4CAE_ ECE26F4AAF_ ECE26F4EAF_ ECE26F4BAF_ ECE26F4CAF_ ECE26G4AAF_ ECE26G4EAF_ ECE26G4BAF_ ECE26G4CAF_ ECE26H4AAF_ ECE26H4EAF_ ECE26H4BAF_ ECE26H4CAF_ Price U.S. $ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3-Pole Type 12 Dust-Tight Catalog Number ECE26A8AAB_ ECE26A8EAB_ ECE26A8BAB_ ECE26A8CAB_ ECE26B8AAC_ ECE26B8EAC_ ECE26B8BAC_ ECE26B8CAC_ ECE26C8AAD_ ECE26C8EAD_ ECE26C8BAD_ ECE26C8CAD_ ECE26D8AAE_ ECE26D8EAE_ ECE26D8BAE_ ECE26D8CAE_ ECE26E8AAE_ ECE26E8EAE_ ECE26E8BAE_ ECE26E8CAE_ ECE26F8AAF_ ECE26F8EAF_ ECE26F8BAF_ ECE26F8CAF_ ECE26G8AAF_ ECE26G8EAF_ ECE26G8BAF_ ECE26G8CAF_ ECE26H8AAF_ ECE26H8EAF_ ECE26H8BAF_ ECE26H8CAF_ Price U.S. $ 3-Pole Component Starter (Open) Catalog Number * AE57AN0_ * * * * AE57BN0_ * * * * AE57CN0_ * * * * AE57DN0_ * * * * AE57EN0_ * * * * AE57FN0_ * * * * AE57GN0_ * * * * * * * AE57HN0_

1-Phase

3-Phase

Size A 45 mm
115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 115 200 230 460 1/6 1/6 1/2 1/4 1/2 1/2 1-1/2 1/2 1-1/2 2 3 1 3 2 3 2 5 3 5 3 7-1/2 1/2 1/2 1-1/2 1-1/2 1-1/2 3 3 3 7-1/2 5 5 10 5 7-1/2 15 7-1/2 10 20 7-1/2 10 25 10 15 30 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 120 208 240 480 3 (15-30)

34

Size B 45 mm
7 (35-70)

Size C 45 mm
15 (75-150)

Size D 45 mm
30 (150-300)

Size E 45 mm
30 (150-300)

Size F 45 mm
50 (250-500)

Size G 65 mm
50 (250-500)

Size H 65 mm
50 (250-500)

1 set of 3 xed heater overload relays included. For additional coil voltages, refer to Page 34-125. Starter includes xed heater overload. For Enclosed IEC Starters, select sufx code -R_ from the table below. Overload relay range can not exceed contactor amperage rating. For Open IEC Starters, use sufx code -F_ or -K_ from the table below. Sufx Overload Enclosed/ Range Open R4 R8/FC R9/FD R10/FE R11/FF R12/FG R13/FH Omit OLR .25 .40A .40 .63A .63 1.0A 1.0 1.4A 1.8 1.8A 1.7 2.4A Sufx Overload Enclosed/ Range Open R14/FJ R15/FK R16/FL R17/FM R18/FN R19/FP R20/FQ 2.2 3.1A 2.8 4.0A 3.5 5A 4.5 6.5A 6.5 8.5A 7.5 11A 10.5 14A Sufx Overload Enclosed/ Range Open R21/FR R22/FS R23/FT R24/KA R25/KB R26/KC R27/KD 13 19A 18 24A 24 32A 18 25A 22 32A 29 42A 36 52A These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECE26B4AAC. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. *Please contact your local Eaton sales ofce.

GMCP is rated for 480V maximum.

Modications . . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.EatonElectrical.com

Page 34-49 Page 34-95 Page 34-100 Page 34-124 PG03300001E 1CD1C

34-154

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Wiring Diagrams

Vol. 2, Ref. No. [0418]

Wiring Diagrams
FVNR with Pushbutton Control With 3-Position Selector Switch Hand M OL A1 M 3/4 A2

34

T1 T2 Motor T3

01 02 03

L1 L2 L3

OFF 2/3 Auto

Motor Run Stop 1 2/3 61 M 62/7 OL Overload Tripped 98 1 M 3/4 Start A1 M A2 95 OL

Remote Auto Contact Control Power Transformer Option 96 M 01 02 03 L1 L2 L3 OL

Motor Stopped

97

96

Reversing Combination Starter Wiring R

3-Position Switch
F 01 02 03 L1 T2 L2 L3 T3 Motor OL T1 Fwd

3
OFF

5
Rev 96

OL

95

Fwd

2- and 3-Position Switch

For Stop 1 Rev 2 F (If Used) 1B RLS 4 R 5 7


Rev

FLS 3 6

A1

A2
Hand

Fwd

1B
OFF Rev

A1

A2

Auto Remote

Figure 34-59. Typical Wiring Diagram


For more information visit: www.EatonElectrical.com CA08102001E

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005
Vol. 2, Ref. No. [0419]

34-155

Wiring Diagrams

Non-combination Starters Non-reversing


Remote Pilot Devices 2-Wire Control 3/14 1 Not for Use with Auto Reset OL Relays 3-Wire Control Start 3/14 2/13 1 M 3/14 98 When More Than One Pushbutton Station is Used, Omit Connector A and Connect per Sketch Below Start Start 3/14 Stop A T1 Separate Control Remove Wire C if Supplied and Connect Separate Control Lines to the Number 1 Terminal on the Remote Pilot Device and to the Number 96 Terminal on the Overload Relay. T2 T3 T1 Stop 2/13 1 T1 2 T2 4 T3 T2 6 4 Conversion to 1-Phase Add Dotted Line Connections. T2 97 96 Reset 4/ T2 6/ T3 95 1 A1 A2 2/13 Connections for Non-reversing Starter Figure 1 Front View of Panel AC Lines 3 5 1 L3 L1 L2

34

Stop

OL 2/ T1

3-Phase Motor

1-Phase Motor

Local Control Options (If Used) Full Voltage Non-reversing Starters Figure A START/STOP Yellow Pushbuttons 2/13 Start Black 3/14 3 4 Stop Red 1 1 2 Red 1 2 Figure B START/STOP Selector Switch 3 4 Red 1 98 97 3 4 Black 3 1 Start Red 2 1 Figure E Pilot Light (Motor RUN) Connect to Coil Terminals A1 & A2 Black/White X1 X2 Black/White OL 96 Reset 95 Wire C 1 Figure D 2-Positon Selector Switch Yellow Hand Overload Tripped Black/White X1 X2 Black/White Figure G

Black Auto

Figure C 3-Position Selector Switch Yellow To Coil Hand Remote Switch Black To Coil 3 Auto 4 4 Red 1

Figure F Pilot Light (Motor Stop) Connect to NC Interlock Black/White X1 Connect to OL X2 Terminal No. 96 Black/White

Figure 34-60. Typical Wiring Diagram


CA08102001E For more information visit: www.EatonElectrical.com

34-156

IEC Contactors & Starters Freedom Full Voltage Enclosed


June 2005

Wiring Diagrams

Vol. 2, Ref. No. [0420]

Non-combination Starters Reversing


Remote Control Stations SPDT Switch For Hold Down Pushbutton For 3 Rev 1 5 Figure 1 Front View of Panel AC 3 2 Lines 1 3 5 L1 L2 L3 Wire F Used with Local Control Pushbuttons 5 4 Reversing Starter Elementary Diagram Lines L1 L2 L3 Contactors F and R are Mechanically Interlocked F 53 61 R F R Pushbutton For 3 2 4 5 Stop 1 OL 6 2 4 T3 T1 T2 T1 T2 T3 2 4 6 T1 T2 T3 A1 F A2 1 A1 R A2 F R C Stop 98 97 96 Reset 95 53 C 1 Rev. 2 53 4 For. F 3 62 54 F R 5 62 54 R 61 A1 R A2 61 A1 F A2 OL 95 96 OL OL T1 T2 T3 54 62 OL

34

3 1 5

C320KGT5 61 Auxiliary Contact 54 62 53

Rev

AC Motor

Rev

Pushbutton with FOR and REV Buttons Electrically Interlocked For 2 3 4 5 1

Separate Control Remove Wire C if Supplied and Connect Separate Control Lines to the Number 1 Terminal on the Remote Pilot Device and to the Number 96 Terminal on the Overload Relay.

Rev

Stop

AC Motor

Figure 34-61. Typical Wiring Diagram

For more information visit: www.EatonElectrical.com

CA08102001E