Escolar Documentos
Profissional Documentos
Cultura Documentos
EARTH RODS.
When earth rods are used, they should be driven into the ground beneath, or as close as practicable to, the structure and down conductor. The practice of siting terminations away from the building is normally unnecessary and uneconomical. Where ground conditions are favourable for the use of rods in parallel, the reduction in earth resistance is small when the separation between the rods becomes less than their driven length. Lightning protection system for tall buildings(over 20m high) showing air terminations, down conductors, bonds to projections above roof.
Air termination bonded to steel reinforcing or steel frame of buliding.
Earth electrode Air termination mesh should be not greater than 10m X 20m. Down conductor should be not more than 10m apart.
J2
www.dongabestech.com
www.dongabestech.com
J3
NOTE 1 If S > 10 +2H, additional longitudinal conductors are needed so that the distance between conductors NOTE 1does not exceed 10m. NOTE 2 If the length of the roof exceeds 20m. additional transverse conductors are necessary. NOTE 3 Down conductors are omitted for clarity.
J4
www.dongabestech.com
The air termination network for a tall reinforced concrete or steel structure should be as follows: a) horizontal conductors on roofs from a 10m X 20m network; b) bonds to steelwork at comers, at 20m intervals around the b) periphery and on the tower 0.5m above the lower roof level; c) key bonding to the building steelwork.
www.dongabestech.com
J5
J6
www.dongabestech.com
To prevent flashover between mast/conductor and protected building, the minimum clearance distance has to be 2m, whichever is the greater. This clearance has to be as given in note 1, under maximum sag conditions, i.e. snow ice on the aerial conductor.
CORROSION.
Electrolytic corrosion between dissimilar metals : The contact of dissimilar metals, unless the contact surfaces are kept completely dry and protected against the ingress of moisture, is likely to initiate and accelerate corrosion. Chemical corrosion of copper : Although copper is highly resistant to many types of chemical attack, lead coating is recommended where it is subject to serve corrosion due to the presence of sulphur compounds.
INSPECTION.
All lightning protection systems should be visually inspected by a competent person during installation, after completetion and after alteration or extension, in order to verify that they conform to the recommendations in BS6651, Visual inspections should be repeated at fixed intervals, preferably not exceeding 12 months.
www.dongabestech.com
J7