Você está na página 1de 2

ZDEV

ZDEV

Electromagnetic safety valves for air and gas


Normally closed electromagnetic safety valves with quickly opening for air and non-aggressive gases (according to EN437).

C A B D

In

Passage Connection diameter type DN ZDEV10 ZDEV15 ZDEV20 ZDEV25 ZDEV32 ZDEV40 ZDEV50 ZDEVRF65 ZDEVRF80 10 15 20 25 32 40 50 65 80 threaded RP threaded RP threaded RP threaded RP threaded RP threaded RP threaded RP flanged DN flanged DN flanged DN

Connection Body

Maximum Absorption pressure mbar W 200 200 360 360 360 360 360 200 200 200 16 16 45 45 20/80* 20/80* 20/80* 45/180* 45/180* 70/280*

Dimensions A 30 30 88 88 B 58 58 C 95 95 D 110 110 164 164 220 220 Int h 4x18 8x18 8x18 8x18

3/8 1/2 3/4 1 1 1/4 1 1/2 2 65 80 100

brass brass aluminum aluminum aluminum aluminum aluminum aluminum aluminum aluminum

96 150 96 150

120 153 188 120 153 188 106 156 192 200 305 266 200 305 266 252 350 352

230 145 355 160 355 160 492 180

Unit weight Kg 0,4 0,4 2,5 2,5 5,7 5,7 6 14 14 36

ZDEVRF100 100

* operating/on opening

ELECTRICAL ChARACTERISTICS
Rated voltage: 230Vac - 50/60hz. Upon request valves are available with coils for the following voltages: 110V AC 50/60hz; 24V AC/DC; 12V AC/DC .

50

INSTALLATION
Check the correspondence between flow direction and the arrow printed on valve body, verify the correct alignment of connecting pipes and allow enough space from the walls to allow free air circulation. You should always install a filter before valve inlet (open <1 mm). The valve may be mounted with coil in horizontal or vertical position. The coil may be oriented 360 degrees in any direction. Install the valve in an area protected from rain and water splashes or drops. Remove coil fastening cap, turn on the adjustment screw under the locking dowel. The flow rate is adjustable from 0 m/h to the maximum indicated on the plate (except the models in brass and 4 ). It is recommended to make the flow adjustments while the burner is in operation and when the adjustment is completed screw back the locking dowel. Adjustments below 40% of the flow are unadvisable since they may cause turbulence.

MODEL Tmax Fmax ZDEV10 ZDEV15 ZDEV20 ZDEV25 Cmax ZDEV32 ZDEV40 ZDEV50 ZDEV65 ZDEV80 ZDEV100

Fmax t<10S (Nm) 70 105 225 340 475 610 1100 1600 2400 5000

Tmax (Nm) 35 50 85 125 160 200 250 -

Cmax (Nm) 50 50 50

OPERATION
Fast opening gas safety electromagnetic valve that is normally closed. When it is not energized, the spring works on the shutter keeping the gas passage closed. When the coil is feed the valve opens. When the power supply is interrupted the valve rapidly closes. This device is suitable for gas and air blocking and regulation commands in burners at atmospheric pressure or fan-assisted burners, in industrial ovens and in all applications which use gas solenoid valves (suitable for continuous service - 100% ED).
V max
+ -

TEChNICAL FEATURES
Connections: gas threaded ISO 7/1 from RP 3/8 to RP 2; flanged ISO 7005-PN16 from DN65 to DN100. Voltage tolerance: -15% / +10%. Environment temperature: -15C / +60C. Closing time < 1 second. Protection degree: IP54. Cable gland: PG 9. Pressure inlets: G1/4 on two sides (except models with brass body). Gas type: Air and non-aggressive gases (EN 437). Filter: 600 m (except models with brass body). Limit switch: by request from 3/4 to 4.