Escolar Documentos
Profissional Documentos
Cultura Documentos
BCN-21374-52
USA-E99991-070-*
1
!
FR-SD
MAINTENANCE MANUAL
c
leu publication effective July, 1982 Translated from Jananese manual RCN 21.17641
r
C O N T E N T S
GENERAL
. . . . . . . . . . . . . . . . . . . .
SPECIFICATIONS
. . . . . . . . . . . . . . . . . . . .
Spindle III
CHAPTER 3.1
. . . . . . . . . . . . . . . . . . . . . . . . .
9 9 9 10 11 11 11 12
Preparation
Operation
3.2 Turning on the power source 3.3 3.4 Adjustment Initial Operation PERIODIC MAINTENANCE
. . . . . . . . . . . . . . .
..... ..... . . . . . . . . . . . . . . . . . . . . . . . . .
15 15 16 17 18 18 18 19
Main Control Card FRS-SA2 Control Snubber Optional Card Card Card TROUBLESHOOTING FRS-GBl FRS-SN
before
Regular
Troubleshooting
. . . . .
- l/2 -
I-
Indicator Typical
Lamp
List
20 22
Troubles Practice
Troubleshooting
. . . . . 23
CHAPTER
VII
36 36 38
Control
Transistor
39 39 42
. . . . . 42
CHAPTER
11X
PARTS
LIST
. . . . . 4.5
8.1
45
50 56 61
- 2/2
I-
CHAPTER
GENERAL
1.1
Scope of ,Maintenance Manual FR-SD Series is a line of regenerative type inverters used to drive a machine tool spindle on the AC power source. IhisMaintenance Manual mainly describes the information necessary to perform the periodic maintenance and troubleshooting. To assure long life and trustworthy operation of the FR-SD inverter, read the manual carefully and practice the periodic maintenance and troubleshooting. and Maintenance Personnel
1.2
Safety
Provisions
In order to assure safety in maintenance and adjustment, the following cautions are very important.
. -
Start-up, maintenance and checking should be performed . by qualified electrician. Note that it is very hazard-
ous that unqualified persons handle the unit. - Remove ring, wrist watch, tie tack, and other metallic objects from the body when the unit under live condition
is handled. - Electric shock is very dangerous, and may result in fatal accident. Carefully select and use testing apparatus because some parts of the unit are at high voltage no matter whether the power source is grounded or not.
When test appartus is applied to the unit, testing should take care not to touch any grounded object.
person
- l _ -
Usually, testing apparatus case is not grounded and therefor high voltage is produced between the testing apparatus case and the ground during the testing. - Do not wear loose working wears that may be involved into a rotating body of the machine when you gains access to
the working machine in maintenance or setting up. - Do not load or unload a PC board (card) while the unit is fed with the power source, or in operation, otherwise the unit may be damaged. - Immediately after the power source is turned off, do not touch the unit, but wait for at least one minute ( time taken for discharge of capacitor) and then start the maintenance or adjustment. 1.3 Storage When the unit is not immediately installed nor used, store it in a clean, dry environment at moderate temperature. Since vapor and dust in the unit cause deterioration to the insulated parts of the unit, keep the unit away from vapor and dust. When the unit is left out of use for any length of time, maintain the unit under the ambient conditions same as those while the unit is in operation. It is recommended in same
cases to use a space heater in the room where the unit is stored.
- 2-
CHAPTER II 2.1
SPECIFICATIONS
AC Spindle Motor Standard Specifications 3.7 5.5 5.5 1500 5.5 7.5 7.5 7.5 11
11
$ Continuous rating (kW) g-4 2: 30 min. rating (kW) @a g: 50% ED rating (kWY -0 Basic speed : (RPM) (RPM)
11 15
15
$ Max. speed
Frame No. Rated torque (cont. rating) GD2 Weight Allowable radial
Note 1
6000 All2 B112 3.57 0.12 80 200 75 VlO ~132 4.87 0.22 110 300 7.15 0.25 120
(dB)(A)
75 Vertical or horizontal
80
Installation Overload
f-
120% of 30min. rating, for lmin. 0 F Munsell Brushless detector JIS C4004 5.5K (kVA) 9 7.5K 12 11K 17 15K 23 18.5K 28 N5.5 tacho-generator, overheat - 40
Ambient
applied
Power supply
200/200- 230vi10%,
50/60H~+3%
Note 1:
-3-
When the line power source other than specified above is employed, use a suitable power transformer.
.-
-4-
Standard
Specifications
Adapt the following specifications (basic speed: a large gear reduction ratio is not available. xContinuous rating Q.f: 2: 30min. rating c, a' 2: 50% ED rating z 'Basic speed 8 Max. speed -1 Frame No. Rated torque (cont. rating) CD2 Weight Allowable Cooling fan radial (kg-m) (kg.m') (kg) load (kW) (kW) (kW) (RPM) (RPM) 1 B112 3.13 0.12 80 3.7 5.5 5.5 5.5 7.5 7.5 1,150 4,600 B132 4.66 0.22 110 6.35 0.25 120 300 75 VlO (dB)(A)
I I (OC) ) I
7.5 11 11
11 15 15
15 18.5 18.5
(kg) ) 200 1
I I
(W) 1
2oo
80
I
40
I I
5.5K 9
11K 17
15K 23 50/60Hz_+3%
18.5K 28
200/200-23OV+lO%,
-5-
I Output
"Output il cl
capacity current
(kW) (A)
z I
Slip control (Optimized V/F pattern control) Regenerative 35 - 6000 RPM Below 0.2% of the max. speed (at load regulation ranging form 10 to 100%) braking
Speed control command signal voltage Acceleration/deceleration control Ambient temperature/ humidity Environmental ments Vibration Standard Cooling applied require-
*lOV DC (Input impedance: 10Kohm) Slip regulation (Time constant at accel./decel.:0.5-10sec. -5 - 50C/below 85% To be free from detrimental gas and dust (JEM 1103, Grade C)
I below 0.5G I
-6-
Full scale: 150% of rated load (adjustable within a range from 100% to 150%) Speed meter signal Speed meter Connected to DC ammeter single-swing
Full scale: Max. speed Zero speed signal Speed arrival signal Speed detect siganl Interlock Contacts open when motor speed goes down below SO*lOrpm. Contacts close when speed is within *15% of the preset speed. Contacts close if motor speed goes down below 500 rpm (adjustable from 50 to ll!jOrpm). Contacts close if slippage reaches near slip limit value (120% of output) Can be set within a range from 50% to 120%. Override can be reset by opening the circuit connected to controller terminals "DEF"
Override
- 7 -
2.3
Speed
Controller
Composition
The speed controller unit mainly consists of the following seven (1) (2) (3) (4) (5) (6) (7) components: Front Main panel control card, FRS-SA2
FRS-SN
Converter Inverter
FRS-SA2 card -
Converter partsc I\
- 8 -
OPERATION for
AND
ADJUSTMENT
Operation
When the controller is fed with the power source for the first time, perform the following checking before turning on the power switch. (1) Is the wiring in conformity with the corresponding wiring (2) (3) diagram?
Are the motor and control panel properly grounded? Are all shielding wires properly connected? - Are they correctly connected to shielding wire terminals? - Are shielding brades not looped?
Is there any wire chip or foreign matter in the unit? Do all PC boards ( cards) present good appearance?
Turning on the power source When the checking has been completed, apply the power source to the controller unit as follows:
(1)
Set the breaker (CBl) in the controller to OFF. Set the source frequency select switch -FREQf on the front panel to the frequency of the available power source.
(2)
(3)
Turn on the incoming power source and make sure the lamp IPHASE SEQUENCE1 lights. If the lamp does not light,
-9-
(4) Make sure no alarm lamp on the controller front panel lights. (5) Set the breaker (CBl) in the controller unit to ON. Now the controller unit is ready for opration. 3.3 Adjustment Although all potentiometers have been factory-adjusted,
__
readjust them to correct error that may be caused by connection with peripheral equipment. *Slip adjustment . . . . . . . ..a.... VR7 VR6 VR3
3.4
Initial
operation
After directly connecting the controller unit to the motor, start the initial operation for accommodation of the controller system and verification of the operation. If hunting or overshoot of motor speed occurs, adjust as follows: <IHunting -%Overshoot ............ ........... Somewhat turn VR2 counter-clockwise. Somewhat turn SW2 clockwise.
Then apply a load to the motor and start the regular operation to check the following: - Unusual sound - Foreign smell - Temperature rise on bearings
- 10 -
CHAPTER IV
PERIODIC
MAINTENANCE
Because it is imperative for long-lasting, trouble free operation of the controller unit to perform trustworthy checking, be sure to practice the periodic maintenance as follows:
Warning:
Electric shock may result in serious accident or death. Before starting the maintenance, do not fail to make sure the entire control system has been disconnected from the line power source.
Frequency Monthly
(2) Does the fan powerfully rotate? (2) Does unusual sound not occur in bear-
c
2. Cleanliness and looseness of screws 3. Miniature relay Every 3 months At suitaval
ings? Periodically clean each part and clamping screws and nuts.
(1) Are contacts not worn out? (2) Does the relay permit the main circuit contactor to close and open sat-
Replace relay.
the
isfactorily?
- 11 -
Item 4. Wiring
Frequency At suitaval
Remedy
4.2
the
motor Checking Check if unusal sound or vibration occurs. If yes, perform checking: (1) Are foundation and installation proper? (2) Are the shafts accurately aligned? (3) Is vibration not transmitted from the coupled machine or device (load)? (4) Is bearing not damaged? Is unusual sound not caused by bearing? (5) Is unusual vibration or noise not caused by speed reduction gear, belt, or transmission system? the following Remedy
Frequency Monthly
(6) Is there any trouble associated unit? (7) Is there any trouble associated with fan? (8) Check belt tension. with controller
- 12 -
Frequency Monthly
Checking Is temperature on bearings usual? (Usual temperature: +lOC 40C over ambient temperature) Is motor frame temperature usual? If not, perform the following checking: (1) Is cooling fan running as usual? (2) Is cooling air stream not obstructed by foreign matter (between frame and cover)?
Remedy
Clean.
(3) Does
load
not
abruptly
Every
months
motor from the controller and measure resistance across the entire circuit and the ground using a SOOV megger. (R esistance be over 1Mohm) If the resistance is below
1
should
- 13 -
Item
Frequency
Remedy
place it in a drying oven at a temperature below 90C. 4. Cooling fan Weekly Monthly Check if cooling fan runs properly, and if unusal sound or vibration occurs.
I
- 14 -
CHAPTER V
Note:
All
User should not change the settings of variable resistors used in the cards.
5.1 Main Control Card FSR-SA2 In the figure Wave form
Fig. 5.1 shows the main control card FRS-SA2. , lines shown in I] and r-1 are insulated.
CHl CH2
4 Cbr,r,,t
detect
-l2sv/roo%
a-
Fig. 5.1 Card FRS-SA2 CHlG . . . . . Current detect signal: -2.5V/lOO% current CHl9 . . . . . TG feedback: +lOV/CII max. speed, -lOV/C.CW max. speed CH26 . . . . . Speed command signal: -lOV/CW max. speed, +lOV/C.CW max. speed - 15 -
5.2 Control Card FRS-GBl Voltage wave form measured at each common of the card FRS-GBl
warning:
The terminal board TB102 of this card is at the main circuit voltage. tric shock. Carefully handle it avoiding elec-
CHl&CHl9
CH6
Modulation pulse
+2.5V/DC220V
\,cHll / ;yJ;er,voltage 1
hz-L!V
-0 - Ia-w
-5V/DC220V
TB102-
This s ignal is for driving the main transistor and its wave form is not measuredat NOl, but measured on eat h both sides of R 130, 134, 135, 136, 140 and 141.
- 16 -
5.3 Snubber
Card
FRS-SN
This card has the snubber circuit with thyristor on the converter side, and requires no adjustment.
Warning:
The terminals of this card areatthe main circuit voltage. Carefully handle the card avoiding electric shock.
5.4 Optional
Cards
Optional cards are available for special specification. For details of optional cards, refer to the respective instruction manual.
1)
2)
- 17 -
CHAMPTER
VI
TROUBLESHOOTING
6.1
General If any trouble to occurs perform the with the the controller unit, it is re-
preliminary
checking
instructed
before
regular
preliminary
checking
will
manufacturer's
service
personnel.
Preliminary 1. Does
checking alarm
in lamp
case that
of
any
yes,
identify possible?
the
fuse.
3. 4. 5*
trouble
interior during
temperatures acceleration,
proper? or decelera-
speed
6.
Is
difference
between
eration?
7. 8.
Did Does or
power
interruption occurs
not a
trouble
under
9.
What
trouble unit
when
part
replaced
before
touble?
- 18 -
12.
How may years has been used the unit? Is the source voltage proper? at a certain interval? Is there voltage change
13.
6.2
Checking
before
regular
troubleshooting
(1)
2OOV~lO%, 22ov,
50/60Hz;
21ov,
23OV*lO%,
60~2 (2oov
(2)
Check if equipment and devices associated with the controller unit are satisfactory. Ex.: NC, sequence contol circuit, wiring, etc.
(3)
(4)
Visually check the unit exterior for damage. Ex.: Damaged card component, burnt circuit pattern, etc. Loose connection, damage, foreign matter, etc.
- 19 -
6.3
Indicator
Lamp
List
The indicator lamps used in the controller unit are as listed below. indicating) Card No. Among them, LED1 _ LED10 are alarm (trouble
lamps. Name Description Lights when the line power source is correctly connected.
FRS-SA2 PLl
PHASE
SEQUENCE
LED1
IOC TRIP(INVERTER)
LED2
OVER
REGENERATION
Lights when voltage across the capacitor in the main circuit goes over 400V.
LED3
IOC
TRIP(CONVERTER)Lights
when
overcurrent
flows
into the converter. LED4 OVER HEAT (CONLights when temperature at heatsink of semiconductor in the main circuit goes over 1OOOC. LED5 LED~ LED7 MOTOR
OVER
TROLLER)
BREAKER
TRIP
Not
used
H EA T
(MOTOR) TRIP
Lights when motor overheats. Lights when overcurrent flows into the main circuit.
BREAKER
LED8
OVER
SPEED
LED9
UNDER VOLTAGE (P15) Lights when l!jV power source goes down below 14V.
Lights when the line power source goes down below 170V. Two LEDs light when slip adjustment is optimized during operation at the maximum speed.
- 20 -
Card
No.
FRS-SA2 LEDLJ
LED15 DEF
LED16
CURRENT
DETECTION
LED20 READY
cLED52 GATE PULSE(V-PHASE) Lights when V-phase gate pulse is output. LED53 GATE PULSE(W-PHASE) Lights when W-phase gate pulse is output. LED54 GATE PULSE(X-PHASE) Lights when X-phase gate pulse is output. LED55 GATE PULSE(Y-PHASE) Lihgts when Y-phase gate pulse is output. LED56 GATE PULSE(Z-PHASE) Lights when Z-phase gate pulse is output.
- 21 -
6.4
Typical
Troubles
There may be many kinds of trouble associated with the controller unit and it is impossible to foresee or predict all possible troubles.
In this section, description is restricted only to the most likely troubles. In the troubleshooting described here, the card should be judged to be defective and therefore replaced with a new one if the required adjustment is impossible on potentiometers in the card. 1. Alarm lamp will light when the following troubles occur. (1)
OVER HEA T
( CO N T RO L L ER,
MOTOR)
(2) BREAKER TRIP (3) IOC TRIP (INVERTER, CONVERTER) (4) OVER REGENERATION
(5) UNDER VOLTAGE (PlS) (6) UNDER VOLTAGE (LINE) (7) OVER SPEED 2. 3. Many alarm lamps light at the same time. No alarm lamp ligths, but the motor does not start at all , or stops from time to time. 4. No alarm lamp lights, but the motor does not run at high speed. The motor does not run at the commanded speed within a specific speed range. 6. Sufficient torque is not obtainable.
- 22 -
7. 8.
The motor comes to delay in starting and stopping. Acceleration/deceleration not output. end signal (UP-TO SPEED) is
Feed motion commanded by the NC does not occur. Speed detect signal (SPEED DETECT) is not output. Zero speed signal (ZERO SPEED) is not output. Speed range change-over is impossible. The motor runs clockwise, but does not run counterclockwise, or vice versa, or braking is impossible.
Motor speed cannot be accelerated over a certain speed. Reading of the load meter or speed meter is not stable. Large noise or vibration occurs.
6.5
Troubleshooting
Practice
for
Each
Trouble
6.5.1
Troubles A. The thermal protector in the controller was tripped....... Install heatsink to thyristor B. The thermal protector in the controller was not tripped, but that used in the motor was tripped . .
. . . . . . . OHSl- OHS2 is not conductive. C. Both the thermal protectors in the controller and the motor were not tripped..... Resumption of operation will be possible by once turningoffthe power source and then turning on again.
- 23 -
Trouble A
Checking 1. Check loading condition of the motor. 2. Check if start and, stop are too frequent.
2. Decrease start and stop frequency. 3. If the temperature is over 50C, prove imventilation.
Measure the ambient temperature around the controller. Check if the cooling fan
1. Check
loading
condition
of the motor. 2. Check if start and stop are too freqeunt. Cooling fan Check if the cooling fan trouble Clogged motor air inlet Thermal protector Check if condition is improved after the motor fan 1. Short-circuit tween OHS1 and OHS2 for provisional remedy. 2. Replace the motor. Replace card. FRS-SA beis working satisfactorily. Check if sufficient air is fed into the motor. 2. Decrease start and stop frequency. Repair or replace the fan. Clean
semiconduc- is operated for several tor trouble minute while the spindle motor is kept in standstill.
C
1.f trouble occurs although voltage across TH and NO2 is OV, the card is defective.
- 24 -
(2)
BREAKER
TRIP
The lamp BREAKER TRIP lights when the main (line source) input NFB trips. Troubles A. B. The main input NFB tripped. Although the NFB did not trip, the lamp BREAKER TRIP lights. Trouble A Refer to description TRIP". B FX-SA trouble card If trouble occurs although the NFB does not trip and voltage across terminals TH and NO2 is OV, the FRSSA2 card is defective. Replace FRS-SA2 card. "IOC Checking Refer to description "IOC TRIP". Remedy Refer to description "IOC TRIP".
.(3) IOC
TRIP
(INvERTER,
CO N V E RT ER )
IOC TRIP is caused either on the inverter side, or converter side and each one alarm lamp is provided for inverter and converter. The lamps light when overcurrent flows. Cause Defective transistor power Checking Check if lamp IOC TRIP lights when only controller disconnected from the motor is operated. - If yes; the power transistor is defective. Replace the power transistor. Remedy
- 25 -
Cause
Remedy
Check if lamp PHASE SEQUENCE light. If not, the phase rotation is not correct.
Check the motor wiring, and Correct the wiring. the terminal screws for looseness. Retighten loose terminal screws. resisReplace the motor.
Measure
insulation
tance using a megger. If the resistance is less than 1 Mohm, the motor is defective.
180~ should be assured dur- Increase the power ing acceleration and deceleration as well as loaded operation. capacity.
Deformed form
source
Measure the source voltage wave form in acceleration and deceleration as well. 1. If voltage partly fails. Collect the wave form. 1. Increase the power capacity or use power cable of large To be shorter than 100 S. size. 2. Also remedy other
voltage wave
- 26 -
Trouble
Checking
Chopped crest should be less than 2 - 3%. Large source frequency gulation Speed detect circuit trouble If lamp IOC TRIP lights while CHlO is not defective, the speed detect circuit is defective. reFrequency regulation should Improve frequency
be less than +3% of the rated frequency. Check that -2.5v/ioo% is measured at CHlO.
regulation.
- 27 -
(4)
OVER
the incorporated smoothing capactor exceeds the permissible Cause Over load voltage. Remedy
.ILighten the load.
Checking Check the load if the lamp OVER LOAD lights while the motor is in deceleration.
Check GD2 if the alarm lamp lights while the motor is in deceleration,
Decrease GD2.
The time taken for decelera- Turn VR27 in FRStion to Orpm from the maximun speed should be longer than 2 sec. If it is shorter than 2sec., , prolong the time. SA2 card clockwise.
Speed
detect trouble
If the trouble cannot be re- Replace medied, one of the most likely causes of the trouble is defective speed detect circuit. card.
FRS-SA2
circuit
(5)
UNDER
VOLTAGE
The lamp UNDER VOLTAGE lights when +15V power source in the control circuit goes down below 14V. Cause Speed detect trouble Checking Check that +lSV is measured across CH2- CH4 of FRS-SA2 card. The speed detect circuit is defective. Remedy Replace FRS-SA2 card.
circuit
- 28 -
Checking If +lSV is not measured across CH2 and CH4 of FRSSA2 and FRS-GBl cards, the power source circuit is defective. (6) UNDER VOLTAGE (LINE)
trouble
even mo-
fect is given to the controller unit. - When the lamp lights continuously . . . . Increase the source voltage. - When the lamp lights at speed change or heavy duty operation (7) OVER SPEED . . . . . . Increase the power capacity.
115% of the rated speed and the over speed detect circuit gets into function. Cause Checking Measure voltage across CH26 and CH4 of FRS-SA2 card Remedy If voltage is over
&lOV, the clamp cirduring high speed operation. cuit is defective. Replace FRS-SA2 card.
c
Unsatisfactory adjustment on TG feedback When operation is at the maximum speed, measure voltage across CHl9 and CH4 of FRS-SA2 card.
- 29 -
Checking
Remedy If voltage is within +lOV, the speed detect circuit is defective. Replace FRS-SA2 card.
6.5.2 When many alarm lamps light at the same time . . . . . . The most likely cause of the trouble is loose plugging at connectors CON1 and CON2. are locked. 6.5 3 When no alarm lamp lights, but the motor does not run at all, or stops from time to time . . . . . . .
L
Checking
Remedy
Check the wiring. Voltage should be 200V 50~~j200, 60HZ. 210, 220, 230~
Wrong
phase
If not, correct phase rotation sequence. If any one of them does not light, FRSGBl card is defective. Replce FRS-GBl card.
Check light.
that
1EDs 51-56
If lights, FRS-SA2 card is defective. If not, the external sequence is not satisfactory.
- 30 -
6.5.4 When no alarm lamp lights, but the motor does not run at high speed . . . . . . Cause Wrong motor cable connection Checking Check if the motor cable is connected in correct phase sequence Input source voltage trouble (U,V,W). Restore input source voltage. Remedy Correct motor cable connection.
Check if lamp PHASE SEQUENCE Correct the phase rota lights. Check if the line source frequency switch. meets the setting of the phase change-over tion sequence.
Improper
exteranl
Check that motor speed increases in proportion to the external speed command signal voltage.
command
6.5.5 When the motor does not run at the command speed within a specific speed range . . . . .
Checking Check that the external speed command signal voltage increases linearly from OV to 1OV.
I
command
6.5.6
When sufficient torque is not obtainable . . . . . Perform the checking according to para. 6.5.3, 4 and 5.
- 31 -
6.5.7 When the motor comes to delay in starting and stopping . . . . . . . Cause Large load Checking Check the load. Remedy Lighten the load.
the checking per 6.5.8. 6.5.10 When speed detect signal (SPEED DETECTION) is not output . . . . . . Cause FRS-SA2 card relay (RA4) touble Checking Check if LED18 lights when set speed. If yes, the relay is defective. Remedy Replace relay (RA4)
- 32 -
is defective. 6.5.11 When zero seed signal (ZERO SPEED) is not output Cause FRS-SA2 card relay (RA6) trouble Checking Check if LED17 lights when motor speed is below 25rpm. If signal is not output although LED17 lights, the relay is defective. Zero speed detect circuit trouble If LED17 does not light, the zero speed detect circuit is defective. 6.5.12 When speed range change-over is impossible . . . . . . Replace FRS-SA2 card. Remedy Replace relay (RA6) or FRS-SA2 card.
. . . . .
The cause of the trouble is the SPEED DETECT function or ZERO SPEED function does not work satisfactorily. Perform the checking per para. 6.5.10 and 6.5.11. 6.5.13 When the motor runs clockwise, but does not run counterclockwise, or vice versa, or braking is impossible . . . .
The most likely cause of the trouble is defective thyristor switching circuit in FRS-GBl card. Replace the FRS-GBl card.
- 33 -
6.5.15 When reading of the load meter or speed meter is not suitable . . . . . Cause Low tacho-generator output voltage Checking Check the output voltage from the tacho-generator. Check if 2'~O%V/lOOOrpm (motor speed) is measured across PGl and PG2 of connector CONl. Check if ripple of tachogenerator becomes 3%. Card trouble If reading of the load meter or speed meter is not stabilized although the
.
output
voltage
large.
generator.
tacho-generator satisfactorily,
likely cause of the trouble is defective FRS-SA2 card. 6.5.16 When Cause Too high or low converter age voltlarge noise or vibration occurs ...... Trouble across Adjust converter voltage by turning VR52 If the adjustment is FRS-GBl card.
GBl card while the motor is of FRS-GBl card. within a range from ~~28 to impossible, replace
Check if voltage at CHSA of Adjsut the voltage by FRS-SA2 card is +5.5V when measured while the motor runs at the maximum speed. turning VR24 of FRSSA2 card.
- 34 -
If not, the phase sequence is inverse. Decreased tion insulaDisconnect the power cable If insulation resistat R, S and T phases and measure between, CH17 and Ground CH4 and Ground All I/O terminals and Ground (Resistance should be larger than 1 Mohm when measured by SOOV megger.)
/
resistance
resistances
Defective bearing
motor
Check that the motor shaft Replace defective can be turned lightly by hand. bearing if found.
Check if any motor mounting bolt is loose. Check if any trace of physical impact is found on the motor shaft.
c
Irregular sine wave reference
ced.
- 35 -
CHAPTER VII
7.1 Replacement 7.1 .l
COMPONENT of Each
REPLACEMENT Card
Control
following
potentiometers
VR12
(DCCT
zero
adjustment)
Set these potentiometers so that voltages at CH~ and CH9 are Olt5mV while the motor is in standstill. (2) VR7 (TG feedback adjustment)
Set this variable resistor so that LED11 or LED12 lights while the system is in operation with command signal of about 1V. Then gradually increase command
signal voltage and set the variable resistor so that the LED11 and LED12 light at the same time when the voltage reaches 1OV. (3) VR29 (CW speed command signal adjsutment)
Turn this potentiometer when the maximum speed deviates from the speed preset for speed command in CW operation. Since the VR has been factory-adjusted, no readjustment is required for usual operation. (4) ~~28 (C.CW speed command signal adjustment)
Turn this potentiometer when the maximum speed deviates from the speed preset for speed command in C.CW operation. No readjustment is required for usual operation.
- 36 -
(5)
VRS (Speed detect setting) This potentiometer is used to set the speed to be detected. Usually this is set at 500rpm.
(6)
VR6 (Speed meter calibration) Set this potentiometer so that the speed meter reads 100% when the motor speed reaches the maximum speed. To verify that the motor is actually running
7.1.2
FRS-GBl card In general, no adjustment is required. Care should be taken, however, to assure secure plugging of connectors.
7.1.3
FRS-SN card No particular adjustment is required. Care should be taken to securely tighten terminal screws.
7.1.4
Option cards For details of option cards including DL-FM or DL-AE card, refer to the respective instruction manual.
c
(1) DL-FM card . . . . . BCN-21374-S2 (2) DL-AE card . . . . . BCN-18564-S2
l-
- 37 -
7.2 Thyristor Module and Transistor Module 1. Removal of defective module Disconnect wires from the defective module and remove the module from the heatsink. In the removal, it should be noted that thyristor gate terminal "G", transistor module base terminal "B" and
emitter terminal "El' are of plug type. 2. Greasing Uniformly apply silicon of each module. grease to the reverse surface
3.
Installation To install module again, tighten the mounting screw with the specified torque and connect the wires. Be sure to cover the thyristor gate terminal, transistor module base terminal and emitter terminal with silicon tube.
~~~
Note:
Since the thyristors and transistors based on our specifications are used in the unit, be sure to place order with us for spares or replacement.
Max. clamp torque (kg-cm) Recommended clamp torque (kg-cm) 20*2
..
Screw size
M6 x 1.0
30 30
20
M6 x 1.0
MS x 0.8
20*2
17*2
- 38 -
7.3
Diode 1. Removal of defective diode Disconnect wires from the defective diode and remove the diode from the heatsink. 2. Greasing Uniformly apply silicon grease where the diode is in contact with the heatsink to assure good heat radiation. Since the silicon grease is non-conductive, do not apply it to the screw where conductivity is 3. Installation Install a new greased diode by tightening it mounting screw with the specified torque and connect the wires. Clamp torque: ZZOkg-cm required.
7.4
DCCT When the DCCT is replaced, use care not to turn the potentiometer in the DCCT because it has been factory-.adjusted.
Whenever the DCCT is replaced, be sure to perform the zero adjustment per para. 7.1.1. 7.5 Brushless Tacho-generator and Coupling
Replace tacho-generator and coupling, referring to Fig. 7.1, as follows: (1) Remove Terminal Box Cover 5 0 and disconnect the cables
- 39 -
I-
Three motor leads (U, V, W), two cooling fan leads (BU, BV), overheat detector leads (OHSl, OHS2), and plug of tacho-generator (TG) connector 4 0
(2)
(3)
0 and remove the connector from the TG connector block0 3 . Remove four cover mounting bolts 0 using hexagon 6 2 wrench key and remove the cover 0 together with the cooling fan 0 from the bracket 0 on the counter-load 1 9
Depress the lock lug of TG connector 4 side. Loosen two set screws 22 0 22 0 used to secure the coupling
(4)
in the bracket side wall of the tacho-generator 24 (5) Remove two tacho-generator mounting screws 21 0
0.
from
the tacho-generator bracket and remove the tacho-generator 24 0 from the bracket
0.
9 0
on the counter-load
Loosen another pair of coupling set screw to secure the coupling @ to the shaft
23 0
0 2 0
hexagon key wrench and remove the coupling the (7) (8) shaft the 0. tacho-generator 24 0 the
Replace
0.
(6) in
- 40 -
No.
No. 15 16 17 18 19 20 21
Name of part Bracket, load side Pre-load spring Shaft Bearing, load side Bracket mounting bolt, load side Bearing, counter-load side TG mounting screw Coupling Coupling set screw Tacho-generator (TG) Cooling fan terminal box Cooling fan leads Cooling fan mounting screw
1 2 3
i
Terminal box cover 5 6 Cover mounting bolt 7 8 9 10 Bearing hold plate screw
i-
Bracket mounting bolt, counter- 22 load side Bracket, counter-load side Bearing hold plate Rotor Stator Frame cover Frame Fig. 7.1 AC Spindle Motor Part List 23 24 2.5 26 27
11 12 13 14
- 41 -
7.6
Cooling
Fan
Disassemble the unit and replace the cooling fan, referring to Fig. 7.1 as follows:
(1)
Remove the screws securing the cooling fan terminal box 25 0 using a screwdriver and remove the ternial box 25
0 .
(2)
Remove two screws securing the cooling fan leads the cooling fan terminal box 26 0 from the cooling fan 1 0 5 0 .
26 0
in
(3)
Remove four cooling fan mounting screws 27 screwdriver and remove the cooling fan cover 2 .
(4) (5)
7.7
as instructed for disassembling of the brushless tachogenerator and coupling (7.5). (2) Remove four bracket mounting bolts 8 0 (counter-load
side) that secure the bracket @ on the counter-load side from the frame (3) Remove four bearing 14 0 hold using a spanner. plate mounting screws 7 0 using
a screwdriver and disconnect the bearing holding plate 10 0 from the bracket
09 .
- 42 -
(4)
Remove ing
the
bracket
00
out
9 0
from
the
frame
14
and
the
bear-
(5)
Draw the
stator 12
0.
Note: Make
sure
the
pre-load
the load side bracket 15 (6) Replace bearing the 20 0 load side
spring Q 6
installed in
bearing 0 and 8
00 is
re-
placed, make sure the bearing hold plate @ is positioned between the counter-load side bearing
00
(7) To assemble
0.
lightly
tighten
four bearing hold plate mounting screws 7 the counter-load side bearing 9 0
and position
0 0. (8) Align the motor leads with the Stead hole of the coanter-
load
side
bracket side
9 0
with the
counter-load
bracket
Note: Make sure the pre-load spring 16 bewteen the load side bracket load (9) Tighten four side bearing 0 . 8 side bracket
0 15 0
counter-load
mounting
screws
8 0
bracket
0 to
the
frame
14
0.
- 43 -
(10)
Tighten
four
bearing
hold
plate
mounting
screws
7 0
using a screwdriver and secure the bearing hold plate 10 0 Note: to the counter-load side bracket 9 . 0 can be lightly rotated
by hand without causing foreign sound. (11) For assembling of the coupling and cover
02 ,
0 22
, tacho-generator
0 24
refer to 7.5
"Brushless
Tacho-generator
and Coupling".
- 44 -
CHAPTER IIX
PARTS LIST
- 46 -
I,
-l
-1
ITEM
TYPE
MANUFACTURER
SYMBOL
Q'TY
NOTE
3PH8KVA BKO-C1736-HO5 YOSHIKAWA 3PH12KVA BKO-C1736-HO6 3PH15KVA BKO-C1736-HO7 3PHlOVA BKO-C1796-HO1 1PHlOOVA BKO-C1797-HO1 BKO-C1798-HO1 lPH4VA NNC-05AMS BKO-Cl734-HO1 150/0.05A BKO-cl268-~04 OHD-100B OHD-60B ZGB2202-1 MY2-DC24V MF60NR-5A-S YOSHIKAWA YOSHIKAWA YOSHIKAWA NANA ELECTRONIC YOSHIKAWA TOHOKU KINZOKU TOHOKU KINZOKU TDK TATEISHI ELECTRONIC TOY0 T3 T2 Tl CTl, 2 CT3 nlsl-3 THs4 FILl RAl Fl-3 1 1 1 2 1 3 1 1 1 3 0 0 0 0 0 0 0 0 0 3 0 0 01 01 T4 1 0 0 01
TRANSFORMER
kW 11 kW 15 kW -
9 10
I
v
I
11
0 0 1 0 0 0 01 01 13
0 1 1 0 1 1 0 1 3
3 3 6
ITEM
19
MANUFACTURER JAPAN RESISTOR MICRON SUIZUKI MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC TAMACAWA SEIKI
@'rn 2 1
6
NOTE
20 21
0 0 0 0 0 0
0 3 6
22
23 24
I
PRINTED CIRCUIT BOARD PRINTED CIRCUIT BOARD PRINTED CIRCUIT BOARD PRINTED CIRCUIT BOARD TACHOCENERATOR
1 1 1 1 1
0 0 0 0 0
0 1 1 0 1 1 0 1 1 0 1 1 0 01 OPTION CARD
25 26
P
al I
7.5 . 27
AC REACTOR
- CHUO DENKI
01
15
kW 28
29
O.lMHlOOA BKO-Cl793-HO5 M976Z104H03 PFA-600 NIHON MINIATURE COUPLING AKAMATSU ELECTRIC 1 1 0 0 0 1 1 1 1 2 FOR TACHOGENERATOR FPR MOTOR
COUPLING FAN
- 49 -
a.2
TYPE F'R-SD-2A
...... Maintenance Recommended spare spare spare parts parts parts for for for every every two five years. years. stock. B ...... Maintenance
machine
maker's
ITEM
DESCRIPTION
MANUFACTURLR
SYMBOL
Q'TY
NOTE
0 0 6 FOR INERTER
TRANSISTOR
11
kW
9 12
0 0
0 0 9 0 0 12
181;;
15 kW
5.5
I
cn c
I
CAPACITOR
0 2 2
0 3 3
0 4 4
FAN
TOOBISHI
1 1 3
r(
r(
0 0
0 0
0 0
0
0
0 0
0 0
0 0
ea
e4 .
E E
- 52 -
SPARE PARTS
ITEM
DEsCR~PTI@N
TYPE
MANUFACTURER
SYMROL
Q'TY
OPTION STAND. A H C 0 0 0 0
3
NOTE
14 15
DETECTOR THERMAL DETECTOR THERMAL FILTER RELAY FUSE RESISTOR RESISTOR CAPACITOR CIRCUIT BOARD PRINTED PRINTED CIRCUIT BOARD -
TOHOKU KINZOKU TOHOKU KINZOKU TDK TATEISHI ELECTRO. TGYO JAPAN RESISTOR MICRON SHIN-E1 TUSHIN MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC TAMAGAWA SEIKI
THSl-3
0 0
1 1 1
3
0 0 1 0 1 1 0
1 3
16
17 18 19
I
3 3 6
2
1 6
0
0 0
0 0 2
0 0 0 0 3 6
F2
I
20 21 22
23 24
1 1 1 1 1
0 0 0 0 0
0 1 1 0 1 1 0 1 1 0 1 1 0 1 1
25
26
ITEM
DESCRIPTION 5.5
TYPE
MANllFACTURER
SY HROL
QTY
NOTE
STAND. A B C
27
AC REACTOR
7:: kW ! 11 kW 15
kW kW
0.2HH50A BKO-C1793-HO2 _ CHUO DENKI 0.17MH60A BKO-Cl793-HO4 O.lMHlOOA BKO-C1793-HO5 0.08w1120~ BKO-Cl793-HO6 M976Z104H03 PFA-600 NIHON MINIATURE COUPLING AKAMATUS ELECTRIC 1 1 0 0 0 1 1 11 2 FOR TACHOGENERATOR FOR MOTOR 1 0 0 0 1
3o
(%ilitDE)
11 15 . 631022 kW
8 l l;ws 5i: 630622
0 1 1
FOR MOTOR
31
7ii
11 kW 1 ZW
18.5
FOR MOTOR
kW
-1
ITEM
DESCRIPTION
TYPE
MANUFACTURE3
SYHBOL ~~~
NOTE
H
II 5.5
kW
7.5
kW
32
CAPACITOR
MEUZ105K600A 11 kW BKO-NA1061-HO5 n
SHIZUKI
w3,w4
OPTION CARD
-
41 42 43
1 1 1
0 0 0
0 -
1 BMFRSDOOZ'JO I 1 BMFRSDOO I 1
0 0
-
0 -
8.3
TYPE FR-SD-2B
Maintenance Maintenance spare spare spare parts parts parts for for for every every tuo five years. years. stock. Option spare parts B ......
machine
maker's
56 _
Q'TY
,Ol'TI@N STAND. A B C 0 0 2 2
MITE
5.5 7:: 5 CAPACITOR kW 11 kW 4000UF BKO-Cl784HOl NITSUKO ' Cl-l Cl-2 Cl-3 Cl-4
3 4
0 0
0 3 3 0 4 4
5.5 7::
I
FAN
G
I
11 kW
kW
8550~
TOOBISHI
11 3
DC REACTOR
kW 7.5
kW
TRANSFQRMER
11 kW
T4
00 1
S P A R E PARTS I TEH
TYPE 3PH IOVA BKO-Cl796-HO1 1PH lOOVA BKO-C1797-HO1 1PH 4VA BKO-C1798-HO1 NNC-05AMS BKO-C1724-HlI 150/0.05A BKO-C1268-HO4
MANUFACTURER YOSHIKAWA CHINO CHINO NANA ELECTRONIC YOSHIKAWA TOHOKU KINZONKU TOHOKU KINZOKU TDK TATEISHI ELECTRONIC T O Y 0 JAPAN RESISTOR MICRON SHIN-E1 TUSHIN MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC
SYMBOL T3 T2 Tl CT1,2 CT3 THSl-3 THs4 FILl RAl Fl-3 R1,2 R3 ~3-8
Q'TY
STAND.
OPTION
A R C
NOTE
9 10 11
1 1 1 2 1 3 1 1 1 3 2 1 6 1 1
0 0 0 0 0 0 0 0 0 3 0 0 0 0 0
0 0
01 01
0 .o 1 0 0 01 01
12 CT 13 CT 14 15 16 17 18 19 20 21 22 23 TIlERHAL DETECTOR THERHAL DETECTOR FILTER RELAY FUSE RESISTOR RESISTOR CAPACITOR PRINTED CIRCUIT BOARD PRINTED CIRCUIT BOARD
- OHD-1009 - OHD-609 zMB2202-11 MY2-DC24V MF60NR-5A-S KHZlS30W2KOHM M04HA20W200HM-K CO921MlH103K FRS-SA2 IRS-G91
0 0 3 0 01
0 1 1 0 13
3 3 6 0 0 2 0 0 0 0 3 6 0 1 1 0 1 1
SPARE F.tRTS
ITEM
24 25
DEsCRIPTIGN
SYMBOL
Q'TY
OPTJON STAND. A B C 0 0 0 0 1 1 0 1 1 0 1 1
NOTE
5.5
1 1 1
26
27
I
AC REACTOR
7s
kW 11 kW
CHUO DENKI
0 1 1
3
I
28 29 30
NIHON MINIATURE COUPLING AKAMATSU ELECTRIC NIHON SEIKO OR NTN TOY0 BEARING
1 1
0 0
0 1 1 1 1 2
630722
0 1 1
FOR MOTOR
6310ZZ
31
-pp 5&i 630622 NIHON SEIKO OR 7ii? NTN TOY0 BEAR11 ING kW 630822
0 1 1
FOR MOTOR
ITEM
DESCRIPTION 5.5 kW
TYPE
MANUFACTURER
SYHROL
c241,u2,
Q'TY
NOTE
STAND. A R C
3 6 9 0 0 3 6 9 3 6 9
u3 32
CAPACITOR
7;; 11
kW
MEUZ105K600A BKO-NA1061-HO5
SHIZUKI
c2-Vl,V2,
v3
c2-Wl,W2, w3
OPTION CARD
I 8 I
41 42
1 1 1
0 0 0
00 00 00
1 1 1
BMFRSD002()0 BMFRSDOO
43
-l_
0 0 0
/-
4
z
E g
a
- 61 -
- 62 -
ITF?l
IVISCRI PTION
TYPE
5.5 7F 1MH
Mt\NllFACTllRb:R
SY MHOL
tJ'TY
SP.tRE
NOTE
kW
7
DC REACTOR
11 kW
15 18.5
CHINO
Ll
0 0 1
kW
kW
5.5
kW 7.5
I
l2
I
8'
kW 11
kW
CHINO
~
T4
01
15
kW kW
18.5
9
TRANSFORMER -
1 1 1 2 1 1
0 0 0 0 0 0
0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1
10 11 12 13 14
1PH lOOVA BKO-C1797-HO1 1PH 4VA BKO-C1798-HO1 NNC-05AMS BKO-C1724-Hll 150/0.05A BKO-CL~~~-HO~
OHD-1009
ITEM DESCRIPTION 15 16
17
TYPE
MANUFACTURER
SYMROL
QTY
NOTI-
ST.dND. A B C _ OHD-60B ZMB2202-11 MY~-DC~~V MF60NR-SA-S KHZlS30W2KOHM MO4HA20W20OHM-K ski CQ921MlH103K IRS-SA2 FRS-GBl FRS-SN2 FRS-vc TS3033NSE2 0.2bli50A BKO-C1793-HO2 0.17~60~ BKO-Cl793-HO4 O.lMHlOOA BKO-C1793-HO5 0.08~~120~ BKO-cl793-~06 CHUO DENKI 1 0 0 01
.
MmlAL DETECTOR FILTER RELAY FUSE RESISTOR RESISTOR CAPACITOR PRINTED CIRCUIT BOARD PRINTED CIRCUIT BOARD PRINTED CIRCUIT BOARD PRINTED CIRCUIT BOARD TACHOGENERATOR
TOHOKU KINZOKU TDK TATEISHI'ELECTRO. TOY0 JAPAN RESISTOR MICRON SHIN-E1 TUSHIN MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC TAMAGAWA SEIKI
THs4
1 1 1 3 2 1 6 1 1 1 1
0 8 0 3 0 0 0 0 0 0 0 0
01
0 1 1 0 1 3
18 19 20
I
3 3 6 0 0 2 0 0 .o 0 3 6 0 1 1 0 1 1 0 1 1 C l 1 0 1 1
p
I
21 22 23 24 2s 26
27
AC REACTOR
7kr5 11 kW 12 _ W 18.5 kW
TYPE 28
29 COUPLING
Q'T'
ST!\N
7-
: -
M976Z104HO3
FAN
I- 1
,
PFA-600
1 1
1 2 -
5.5
7k;. . 630722
kW 11 kW 15 ' 631022 kW
i?W
FOR MOTOR
I ul I
1
18.
kW 6 3 0 6 2 2
7d i
FOR MOTOR
3 6 9 12
0
SHIZUKI
u3, u4
c2-Vl, v2 v3, v4 c2-Wl, w2 W3, W4
3 tiGT !
TYPE
SYMBOL
Q'TY
NOTE
41 42 43
1 1 1
BMIWD00290 BMFRSDOO