Chiller Sizing
ChillersaresizedonthetotalCooling load(orRefrigerationload)forthebuildingorthatpartofthebuildingbeing cooledbythechiller. Cooling loadisthesumofsensible and latent heat gains, fresh heat gain, supply fan power heat gain, supply duct heat gain, return air fan power heat gain, return air duct gain. Whenusingwaterchillersasmallallowanceforpumppowerandheatgainstochilledwaterpipesisadded,thisallowance maybe1%to2%. Whenusingfancoilunitsfanpowermaybeadded. Thereturnairductgainsareusuallynegligible. ThesensibleandlatentheatgainsaredealtwithinHeatGainsnotesintheAirConditioningsection. ThelargestCooling loadusuallyoccursat15.00hoursinJuly. Another way to find the total chiller output is to add the output of all chilled water cooling coils together. Theheatgainsmaybederivedfromapsychrometricchartasshownbelow.
Return Air Fan and duct gains hM Total Cooling Load Sensible and Latent room gains hW hD Supply fan and supply duct heat gains hR hR hS Fresh air heat gain

100% Saturation Curve

O - Outside Air

r.r.l.

R - Room Air ADP W D S R


Return Air Temperature rise in Supply duct and fan Dry Bulb Temperature (oC) Temperature rise in Return air duct and fan

http://www.arca53.dsl.pipex.com/index_files/chillersize.htm

13.03.2013

Chiller Sizing

Page 2 of 2

Theformulabelowisusedtodeterminethetotalcoolingload; Qcooling=Qs+Ql+Qfa+Qsfd+Qrfd Where;Qcooling=Totalcoolingorrefrigerationload(kW). Qs=Sensibleheatgaintoroom(kW). Ql=Latentheatgainstoroom(kW). Qfa=FreshAirheatgain(kW). Qsfd=Supplyfanandductheatgain(kW). Qrfd=Returnair(orRecirculatedair)fanandductheatgain(kW). Thesensibleheatgainshouldalreadybecalculated. Thelatentheatgainisfrompeopleandfromfreshairdeliveredinsummer. ThelatentheatgainfromoccupantscanbedeterminedfromtheCIBSEguide. Thelatentgaininthefreshaircanbedeterminedfromthepsychrometricchart. TheFreshairloadmaybeobtainedfromthepsychrometricchart.

http://www.arca53.dsl.pipex.com/index_files/chillersize.htm

13.03.2013

Você também pode gostar