Position indicating system fr remote indication of tap-changer position

The indicator is a moving-coil instrument, which is available with quadrant scale or ring scale. It is fed by a measuring transducer. The indicator is suitable for seriesconnection of more instruments, and it is controlled by a potentiometer in the motor-drive.

Technical data
Position transmitter The position transmitter is included in the motor-drive. Potentiometer type, 10 /step. Max 340 Measuring transducer (delivered earlier than w. 36, 2006) The measuring transducer is normally mounted in the motordrive, but it can also be placed in the control room. Type: WASS PRO RTD 24 240 V DC -20 % +10 % 24 240 V AC -15 % +10 % Output: 0 20 mA, 0 1 mA, 0 5 mA, 0 10 mA, 0 20 mA, 4 20 mA, 0-5 V, 0-10 V Input: Min. 0-40 W, Max. 0-100 kW Position indicator (delivered later than w. 36, 2006) Moving-coil instrument Input: see Measuring transducer Black frame Size 96 x 96 mm or 144x144 mm Further data on request.
POSITION
11 9 7 5 3 1 13 15 17 19
7 5 3 1 9 13 11 15 17 19 21 23 25 27 29 31 33 35

POSITION

Quadrant scale. Recommended for up to 19 positions.

Ring scale. For more than 19 positions.

Adjustment of measuring transducer


(Set at the factory) Measuring transducers delivered earlier than week 36, 2006. When adjusting, go from step 1 to 5, and skip step 6 and 7. 1. Adjust the indicator to show "0" position at voltage-free. 2. With the motor-drive in lowest position, the lowest output current is adjusted by potentiometer "zero" at the front of the transducer. 3. With the motor-drive in highest position, the highest output current is adjusted by potentiometer "max" at the front of the transducer. 4. Short-circuit connect tap 1 and 2 of the position transmitter by means of a jumper at the terminal blocks, and adjust one more time the lowest current by potentiometer "zero". 5. Disconnect the jumper and adjust once more the highest current by potentiometer "max". Measuring transducers delivered later than week 36, 2006. When adjusting, go from step 1 to 3, skip step 4 and 5, and finish with step 6 and 7. 6. Disconnect connection terminal X5:3 and adjust the lowest position one more time. 7. Connect connection terminal X5:3 again and adjust the highest position one more time. If needed, do step 6 and 7 all over again until the remote position indicator is set correctly.

Adjustment of remote position indicator (for OLTC)


The measuring transducer, which feeds the position indicator, is located in the motor-drive mechanism and is checked and calibrated at the tap-changer factory. Once connected to the position indicator at site, the transducer might require some adjustment. 1. Operate the OLTC to its max. position. 2. Check that the position indicator now shows the same position. If displaced, the pointer is adjusted by slightly turning the max. adjustment screw on the measuring transducer. 3. Operate the OLTC to its min. position. 4. Check that the position indicator also shows the min. position. If needed, adjust the pointer by a slight turn of the zero adjuster on the measuring transducer.

Ordering table
To ensure correct delivery, following information must be given: Measuring transducer 1. Number of positions 2. Desired supply voltage 3. Desired output

Position indicator 1. Number of positions and type of marking 2. Language

Dimensions: Position indicators

Dimensions: Measuring transducer

96/144

96/144

Max 90/110 97 Hole size 17.5 106

92/138

92/138

Principle diagram.

ABB AB Components SE-771 80 Ludvika, Sweden Phone: +46 240 78 20 00 Fax: +46 240 121 57 E-Mail: sales@se.abb.com www.abb.com/electricalcomponents

Copyright 2010 ABB, All rights reserved. 1ZSE 5492-161 en, Rev. 2, 2010-06-15