Distribution Relays

Complete protection for distribution systems

ABB a global technology leader

ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering environmental impact. The ABB Group operates in around 100 countries and employs over 1,08,000 people. In India, ABB serves customers with a complete range of power and automation technologies. The company has a vast installed base, extensive manufacturing facilities and a countrywide marketing and service presence. The Power Technologies division offers electric, gas and water utilities as well as industrial and commercial customers a wide range of products, systems and services for power generation, transmission amd distribution. ABBs turnkey solution capabilities in the sector range from bulk power transmission, substations and complete electrification to utility automation and distribution systems.

The product offering includes a wide spectrum of technologies across the entire voltage range including indoor and outdoor circuit breakers, air and gas insulated switchgear, disconnectors, capacitor banks, reactive power compensators, power transformers, distribution transformers, instrument transformers, Compact Secondary Substations (CSS) and Ring Main Units (RMU).

Advantage ABB
120 years of technology and innovation Unparalleled domain competence Global experience Complete solution capabilities Large installed base Environment-friendly technologies

ABB

Innovative technology for complete protection of your distribution systems


With a wide range of products and systems based on electromechanical, static and numerical micro-processor based platforms, ABB offers complete protection solutions for utility and industry power distribution networks for improved performance, reliability and safety. ABB solutions include application engineering, testing & commissioning, after sales service, troubleshooting and training. Index Manufacturing and Testing facilities Training facilities Type of Relay ICM21 VHXm22_ /VHXm23 IRXm IKM2 RADSB FCX103b UBX117 UFX132 PPX 111-R IWX + YWX UVT92m TCS / RXTCS CV2 RXPQ8n, PQ8n, PN8n, RXPQ8n PSU6n, PSU14n, RXPSU6n, RXPSU14n SSX90m6C2J SRX90m5C2J NI 40/ 41 SPAJ140C SPAM150C SPAJ160C SPAU130C SPAE010 / 011 SPAD346C COM 600 InverseTime Overcurrent and Earth Fault Relay Instantaneous / Definite Time Under and Over Voltage Relay Instantaneous Circulating Current Relay Instantaneous Overcurrent and Earth Fault Relay Biased Transformer Differential Relay Frequency Relay Voltage Earth Fault / Neutral Displacement Relay Over Fluxing Relay Power Directional Relay Rotor Earth Fault Relay Fuse Failure Relay Trip Circuit Supervision Relay Voltage Operated Auxiliary Relay High Speed Trip / No Volt Relay Bistable Relay Time Delay ( Delay on Pick Up ) Relay Time Delay ( Delay on Drop Off ) Relay Numerical Combined Overcurrent and Earth Fault Relay Numerical Combined Overcurrent and Earth Fault Relay Numerical Composite Motor Protection Relay Numerical Capacitor Bank Protection Relay Numerical three phase Under voltage and Over voltage relay Numerical High impedance Protection Relay Numerical Stabilized Transformer Differential Relay Station Automation Mounting details and case dimensions High end terminals for protection, control and monitoring Protection relays from 610 series
ABB

The products manufactured are approved by leading consultants in the electrical engineering field such as EIL, MECON, PDIL, TCE, DCL, DESIN, HOLTAC, FISHNER, Technimont ICB, H&G, UDHE etc and are widely used by major utilities, industries and OEMs.

Page No. 4 5

6-7 8-9 10-11 12-13 14-15 16-17 18-19 20-21 22-23 24-25 26-27 28-29 30-31 32-33 34-35 36-37 38-39 40-41 42-43 44-45 46-47 48-49 50-51 52-54 55-56 57-65 66 67
3

State of the art manufacturing facilities

Manufacturing and testing facilities


The manufacturing setup is organized around the cellular manufacturing concept for maximum efficiency. Testing and calibration is carried out on state-of-the-art equipment. The manufacturing and testing of static / microprocessor based relays is carried out in an electro static discharge (ESD) protected area. Testing and calibration of numerical microprocessor based relays including wiring checks is carried out on a fully automated computerised test station.

Quality policy
Our quality policy is aimed at fulfilling customers requirement in terms of quality, on time delivery and services. All our products and services are seen as an expression of quality, and each delivery is aimed at creating a recommendation for further business. The latest edition of relevant IEC standards applies to continuous type test programme. All manufactured relays are type tested as per IEC 60255 standards.

Commitment to quality and sustainability


All ABB India manufacturing facilities confirm to the highest quality standards and environment norms. These are all ISO 9001 and ISO 14001 compliant and are certified by leading international authorities.

Customer support and after sales services


A dedicated after sales service support group provides commissioning and after sales services. A service centre for repair of relays has also been established at ABB's Vadodara premises.

ABB

Training facilities

A full fledged training facility is established for detailed training of customer personnel. ABB's training programmes are designed and structured to be an integral part of customer commitment. Our programmes focus on enhancing skills and developing the competence of customers personnel across functions and levels. ABB's expert team of trainers with unparalleled domain knowledge and experience gained over decades, offer well structured training programmes across a wide range of products and systems. Though interactive class room sessions, hands-on training and product demonstration, we create the ideal environment for our customers to familiarise themselves with various products and systems and enhance their skills. Regular training courses are organized based on standard products as well as tailor made programmes are conducted to cover various products as per customer requirement. Training programmes designed for distribution automation products cover an exhaustive range of subjects. Modules include topics such as: Fundamentals of Power System Protection Fundamentals of Generator Protection Basics of Communication System Operation and maintenance of IEDs

ABB

InverseTime Overcurrent and Earth Fault Relay type ICM21_

Features
Single pole Electromechanical draw out design Reliable, robust Ferraris measuring system without gearing / coupling Range of current setting 1:4, adjustable in 7 steps Plug-in active part, the CT connections being automatically short-circuited when the relay is withdrawn. Separate double-pole tripping relay with indicator, for high contact rating Temperature -compensated measuring system Range of time setting 10-100%

Model
ICM21NP ICM21P ICM21KP ICM21BNP ICM21BP ICM21BKP

Ansi
51 / 51N 50+51 / 50N+51N 50+51 / 50N+51N 51 / 51N 50+51 / 50N+51N 50+51 / 50N+51N

Function
Single pole IDMT O/C or E/F relay without Highset Instantaneous Unit Single pole IDMT O/C or E/F with Inst. unit with common contact of IDMT & Inst. Single pole IDMT O/C or E/F with Inst. unit with Seperate contact of IDMT & Inst. Single pole Very Inverse Time O/C or E/F relay without Highset Instantaneous Unit Single pole Very Inverse Time O/C or E/F unit with comm. contact of IDMT & Inst. Single pole Very Inverse Time O/C or E/F unit with Seperate contact of IDMT & Inst.

Specification
CT input ( In ) Setting range for IDMT unit ( Iset ) Setting range for Inst. Unit Rated Frequency Permissible sustained current (Thermal withstand) Pick up Operating Time Reset current Reset time Max. Overrun Max. Error CT Burden Number of Output Contacts Output Contact rating Rated Auxiliary Supply Burden on Aux. Supply Insulation Impulse Case Size
6

: : : : : : : : : : : : : : : : : : :

1 or 5 Amp. Phase O/C - 50 - 200% x In; Earth Fault - 10-40% or 20-80% x In 4-20 x Iset or 2.5-10 x Iset 50 Hz 2 x In continuous 100 x In for 1 Sec. 1.1 times of setting As per IDMT characteristics conf. BS142 > 0.9 x Iset 9.5 Sec 0.02 Sec 10% for 2 x I, 5% for 4 - 20 x I 3.5 VA at Min. and 4.8 VA at Max.Setting 2 NO or 1NO+1NC for ICM21NP & P, 4 NO or 2 NO+2NC for ICM21KP 10 Amp. Cont. & 30 Amp. Making 24, 30, 48, 110, 220,250 VDC 3W 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 Size -I Case
ABB

Wiring Diagrams

ICM21NP, ICM21BNP

ICM21KP, ICM21BKP

ICM21P, ICM21BP

ABB

Instantaneous / Definite Time Under and Over Voltage Relay type VHXm22_ / VHXm23
Features
Single pole Static draw-out type design Variable Voltage Settings Used for U/V and O/V protection of Generator, Motor, Capacitor Transformer Built in timer with variable time delay settings Hand reset flag for operation indication Separate built in tripping output relay for high contact rating Robust construction

Model
VHXm22A VHXm22B VHXm23A VHXm23B

Ansi
27 27+2 59 59+2

Function
Instantaneous Under Voltage relay with variable voltage settings w/o time delay Under Voltage relay with variable voltage settings and with built in time delay Instantaneous Over Voltage relay with variable voltage settings w/o time delay Over Voltage relay with variable voltage settings and with built in time delay

Specification
PT input ( Un ) Setting range for U/V VHXm22A / B Setting range for O/V VHXm23 A / B Operating time for Inst. VHXm22A / 23 A Time Delay Range for VHXm22B / 23 B Rated Frequency Reset Ratio for Over Voltage for Under Voltage Max. Error VT Burden No. of Output Contact Output Contact rating Rated Auxiliary Supply Burden on Aux. Supply Insulation Impulse Case Size : : : : : : : : : : : : : : : : : 63.5V, 110V, 240V AC 40-80% of Un 80-140% of Un < 60 mSec 0.1-1Sec, 0.5-5Sec, 1-10 Sec 50 Hz > 90% x Un < 110% x Un 5% 0.5 VA 3 NO + 3 NC or 6NO 5 Amp. Cont. & 25 Amp. Making 24, 30, 48, 110, 220 VDC 8W /11W (quiescent / operation cond.) 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 Size -I Case

ABB

Wiring Diagrams

VHXm 22_ / VHXm23_

ABB

Instantaneous Circulating Current Relay type IRXm

Features
Single pole Static draw-out type design Sensitive High speed protection on internal faults Operation largely immune to DC components and harmonics Plug-in active part, the CT connections being automatically short-circuited when the relay is withdrawn. Used as Sensitive E/F, High Imp. Restricted E/F protection of Transformer & Generator, High Imp. Differential protection of Motor, Generator, Busbar Also suitable for Sensitive definite time E/F when used with timer

Model
IRXm + Stab. Resistor 3* (IRXm + Stab. Resistor) IRXm + SSX90M6C2J

Ansi
64R 87M 50NS

Function
Single pole High Impedance based Restricted Earth Fault Protection Relay Three pole High Impedance based Motor / Generator Diff. Protection Relay Single pole Instantaneous Earth Fault Relay with time delay

Specification
CT input ( In ) Setting range Rated Frequency Permissible sustained current (Thermal withstand) Pick up Operating Time Reset current Max. Error CT Burden Number of Output Contacts Output Contact rating Rated Auxiliary Supply Burden on Aux. Supply Insulation Impulse Case Size : 1 and 5 Amp. : 0.05 - 50% x In ( 0.05 - 5% x In in 10 equal steps and 5 - 50% x In in 10 equal steps both setting ranges selectable at site ) : 50 Hz : 4 x In continuous 100 x In for 1 Sec. : 1.1 times of setting : < 25 mSec : > 0.9 x Iset : 5% : < 0.5 VA : 2 NO + 1NC : 5 Amp. Cont. & 10 Amp. Making : 24, 30, 48, 110, 220,250 VDC : 5.3 W Max. : 2.0 kV as per IEC 60255-5 : 5.0 kV as per IEC 60255-5 : Size -I Case

Note : The external stabilizing resistor is supplied along with relay. The total impedance of the relay and series stabilising resistor is usually low enough to prevent the CT developing voltages over 2 kV during max. internal faults, but in some applications a non-linear resistor is required to limit this voltage. 10 ABB

Wiring Diagrams

IRXm

ABB

11

Instantaneous Overcurrent and Earth Fault Relay type IKM2

Features
Single pole Electromechanical draw out design Wide current setting range Used to protect elect.installations & line systems against short circuit. Plug-in type active part, the CT connections being automatically short-circuited when the relay is withdrawn. Separate double-pole tripping contactor with indicator, for high cont. rating Also suitable for definite time operation when used with timer. Robust construction

Model
IKM2 IKM2 + SSX90M6C2J

Ansi
50 / 50N 50+2 / 50N+2

Function
Single pole Instantaneous Overcurrent and Earth Fault relay Single pole Definite time Overcurrent and Earth Fault relay

Specification
CT input ( In ) Setting range for O/C Setting range for E/F Rated Frequency Permissible sustained current (Thermal withstand) Pick up Operating Time Time Delay Range for DMT Reset current Max. error CT Burden Number of Output Cont. Output Contact rating Rated Auxiliary Supply Burden on Aux. Supply Insulation Impulse Case Size : : : : : : : : : : : : : : : : : : 1 or 5 Amp. (50-200%) x 5 x In or (50-200%) x 10 x In (10-40%) x 5 x In or (10-40%) x 10 x In or (20-80%) x 5 x In or (20-80%) x 10 x In 50 Hz 2 x In continuous 100 x In for 1 Sec. 1.1 times of setting Max. 70 mSec 0.1-1Sec, 0.5-5Sec, 1-10 Sec ( with timer ) 1.2-2.5 x Iset 10% 3.5 VA at Min. and 4.8 VA at Max.Setting 2 NO or 1NO+1NC 10 Amp. Cont. & 30 Amp. Making 24, 30, 48, 110, 220,250 VDC 3W 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 Size -I Case

12

ABB

Wiring Diagrams

KM2

ABB

13

Biased Transformer Differential Relay type RADSB

Features
Triple pole Static 2 winding differential relay for phase & ground faults Variable percentage restraint for external fault security and on-load tap changer transformer protection Second harmonic restraint from all three phases for inrush security Fifth harmonic restraint from all 3 phases for overexcitation security Harmonic restrained operating time 30 ms at 3 times pick-up current Unrestrained operation does not respond to dc offset and can be set at 8, 13 or 20 times

Model
RADSB

Ansi
87T

Function
2 Winding Biased Transformer Differential relay

Specification
CT input ( In ) Restrained Operating Value Isr Unrestrained Operating Value Isu Rated Frequency Permissible sustained current (Thermal withstand) Operating Time Max. Error CT Burden Number of Output Cont. Output Contact rating Rated Auxiliary Supply Burden on Aux. Supply Insulation Impulse Case Size : : : : : : : : : : : : : : : 1 or 5 Amp. 20, 25, 35, or 50% of In Reconnectible : 8, 13 and 20 of In 50 Hz 10 x In Cont. and 100 x In for 1 Sec. For 1A 20 x In Cont. and 250 x In for 1 Sec. For 5A 30 ms at Id=3xIsr & 10-20 ms at Id=2xIsu 5% < 0.2 VA 3 NO + 2CO 5 Amp. Cont. & 10 Amp. Making 24, 30, 48, 110, 220,250 VDC 10W /14W ( quiescent / operation cond. ) 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 RHGX12 Case with Screw terminals

14

ABB

Wiring Diagrams

RADSB (SCREW TYPE)

ABB

15

Frequency Relay type FCX103b

Features
Static design with High accuracy ( 0.03 Hz at 50 Hz ) 1 to 4 independently adjustable tripping stages, two of which can be rate of change df/dt Wide setting range 39.1 to 65 Hz for U/F & O/F, 0.1 to 9.9 Hz/Sec for df/dt Under voltage interlock ( 0.2 or 0.6 Un ) Largely insensitive to Harmonics and transients in the system Digital measuring principle with resolution due to 1.25 MHz quartz reference Used for graded load shedding and protection of generators to avoid damage to turbines and auxiliary drives.

Model
FCX103b-00 FCX103b-10 FCX103b-01 FCX103b-20 FCX103b-11 FCX103b-02 FCX103b-30 FCX103b-21 FCX103b-12

Ansi
81 81 81+ 81 81+ 81+ 81 81+ 81+

Function
1 Stg. relay with U/F or O/F stage 2 Stg. relay with U/F or O/F stage 2 Stg. relay with 1 U/F or O/F and 1 df/dt stg. 3 Stg. relay with U/F or O/F stage 3 Stg. relay with 2 U/F or O/F and 1 df/dt stg. 3 Stg. relay with 1 U/F or O/F and 2 df/dt stg. 4 Stg. relay with U/F or O/F stage 4 Stg. relay with 3 U/F or O/F and 1 df/dt stg. 4 Stg. relay with 2 U/F or O/F and 2 df/dt stg.

df/dt df/dt df/dt df/dt df/dt

Specification
PT input ( Un ) Setting range for U/F & O/F Setting range for df/dt Rated Frequency Operating time for U/F & O/F Tripping delay for df/dt Evaluation per period Reset ratio Reset time Max. Error PT Burden Number of Output Cont. Output Contact rating Rated Auxiliary Supply Burden on Aux. Supply Insulation Impulse Case Size
16

: : : : : : : : : : : : : : : : : :

63.5, 110, 200, 220V AC 39.1 - 65 Hz in step of 0.1 Hz 0.1 - 9.9 Hz / Sec in step of 0.1 Hz / Sec 50 Hz 0.15-1.5 Sec or 0.5-5 Sec or 1-10 Sec or 0.3-3 Sec 33 / 66 / 99 or 132 msec 26 msec 100% 70 msec for U/F & 25 msec for O/F 0.03 Hz for Freq. & 5% for timing 11VA + 2VA / Stage in reset condition / 11VA + 6VA / Stage in tripped condition 3 NO or 2 CO per stage 10 Amp. Cont. & 20 Amp. Making 24, 30, 48, 110, 220,250 VDC 6W+0.75W/additional stage in reset condition & 8W+1W/additional stage in tripped condition 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 Size -II Case Horizontal
ABB

Wiring Diagrams

FCX 103b

FCX 103b

ABB

17

Voltage Earth Fault / Neutral Displacement Relay type UBX117

Features
Single pole Static draw-out type design Built in filter with very high attenuation of 3rd and 5th harmonics. Used to detect stator earth faults of Generators and motors equipped with high impedance groundings at star points. Able to detect 95% of stator winding from machine terminal towards its star point. Also suitable for capacitor bank protection. Definite time operation.

Model
UBX117-C

Ansi
59N

Function
Voltage Earth Fault / Neutral Displacement Relay

Specification
VT input ( Un ) Setting range Operating Time Rated Frequency Reset ratio PT Burden Max. Error Number of Output Contact Output Contact rating Rated Auxiliary Supply Burden on Aux. Supply Insulation Impulse Case Size : : : : : : : : : : : : : : 110 or 240V AC 2.5 - 6% x Un or 5 - 12% x Un 0.5 Sec 50 Hz / 60 Hz 100% 10 VA 5% 3 CO 5 Amp. Cont. & 10 Amp. Making 24, 30, 48 - 250 VDC 1 W Max. 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 Size -I Deep Case

18

ABB

Wiring Diagrams

UBX 117

ABB

19

Over Fluxing Relay type UFX132

Features
Single pole Static draw-out type design Used to protect power transformer, generator transformer against excessive flux ( over fluxing ). Also used to protect generator from overfluxing during start-up and shutdown when generator is not connected to network, during faulty operation of voltage regulator. Also offers protection in the event of sudden load shedding. Definite time operation.

Model
UFX132-C

Ansi
40

Function
Over fluxing relay

Specification
VT input ( Un ) Voltage Range Frequency Range Load Capacity Setting Range Operating Time ( time lag ) Rated Frequency Permissible sustained voltage ( Thermal ) Reset ratio PT Burden Max. Error Number of Output Contact Output Contact rating Rated Auxiliary Supply Burden on Aux. Supply Insulation Impulse Case Size : : : : : : : : : : : : : : : : : : 110 V AC 2V - 400V 10 Hz - 100 Hz 4.5 x f 0.1 - 4.0 V/Hz in step of 0.1 0.1-1Sec or 0.2-2Sec or 0.5-5 Sec or 1-10 Sec 50 Hz 100 x Un for 1 Sec. > 98% 4 VA 3% 3 CO 5 Amp. Cont. & 10 Amp. Making 30, 48 - 250 VDC 3 W Max. 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 Size -I Deep Case

20

ABB

Wiring Diagrams

UFX 132 - C

ABB

21

Power Directional Relay type PPX 111-R

Features
Three Phase Static relay in modular construction 2 or 3 Phase Power measurement Operating ranges for all three phases individually adjustable Reconnectable from maximum power ( over power ) to minimum power ( under power ) measurement Can be used for active or reactive power measurement. Used as reverse power, Low forward power relay and power oscillation relay up to slip frequencies of about 2 Hz, in which power flow between network and generator oscillates i.e. generator falls out of step and swings between motor and generator operation

Model
PPX111-R PPX111-R

Ansi
32R 32P

Function
Three Phase Reverse Power Relay Three Phase Low Forward Power Relay

Specification
CT input ( In ) : PT input ( Un ) : Setting range : Timer Setting range : Permissible sustained current / voltage ( Thermal withstand) : Characteristic angle : Measurement of power : Rated Frequency : Reset ratio : Max. Error : CT Burden : PT Burden : Number of Output : Output Contact rating : Rated Auxiliary Supply : Burden on Aux. Supply : Insulation : Impulse : Case Size : 1 or 5 Amp. 110/3, 110, 240/3, 240V AC 0.5 - 100% x PN ( Rated Power ) 0.5 - 5 Sec in steps of 0.5 Sec 5 - 50 Sec in steps of 5.0 Sec 4 x In continuous, 100 x In for 1 Sec. 2 x Un continuous 0 or 90 degree electrical up to factor of cos = 0.005 50 Hz 0.6-0.95 dependent on set operating value 5% < 0.5 VA < 0.15 VA 3 CO for tripping T1 & T2 stage each 10 Amp. Cont. & 30 Amp. Making 24, 48, 110, 220 V DC 6W 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 19" Rack Mounting

22

ABB

Wiring Diagrams

PPX 111-R

ABB

23

Rotor Earth Fault Relay type IWX + YWX

Features
Single / Two Stage Static relay in modular construction Adjustable pick up value in ohms ( fault resistance ) Adjustable trip delay Simple testing facility Bridge form assuring the impedance of the insulation, with a band pass filter at the output for the test frequency and low pass filter with good attenuation of the higher harmonics. Used for detection of earth faults on the rotor windings of turbo alternator synchronous motors.

Model
IWX + YWX IWX + YWX

Ansi
64R 64R

Function
Single stage Rotor Earth Fault Relay Two stage Rotor Earth Fault Relay

Specification
AC Aux. Input for YWX111 Fault Resistance setting Time Delay setting Reset ratio Excitation operating volt. Rated Frequency Max. Error Burden on Aux. AC of YWX No. of Output Contact Output Contact rating Rated Auxiliary Supply Burden on Aux. Supply Insulation Impulse Case Size : : : : : : : : : : : : : : : 110V, 230V AC 0 - 5000 ohms 0.5 - 5 Sec 100% 1.0 kV DC Max. 50 Hz or 60 Hz 5% 1.1 VA 2 CO for Stage 1 & 3 CO for Stage 2 5 Amp. Cont. & 25 Amp. Making 24, 110, 220 V DC 8W /11W (quiescent / operation cond.) 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 19 rack mounting

24

ABB

Wiring Diagrams

IWX+YWX

ABB

25

Fuse Failure Relay type UVT92m

Features
Three Phase Static draw out design Reliable and Fast operation Sensitivity down to 2.5 VA load on PT Secondary No continuous drain on DC auxiliary supply Used for monitoring the fuses continuously against blowing out / rupturing and inadvertent removals. The relay can be used to give blocking signals to voltage operated protection schemes such as distance, under impedance and under voltage to avoid mal operation. Also can be used for alarming purpose in synchronizing circuits. Hand reset LED for operation indication. Operating time less than 15 msec

Model
UVT92m

Ansi
97

Function
Three Phase Fuse Failure Relay

Specification
PT input ( Un ) Operating time Rated Frequency PT Burden Permissible sustained current (Thermal withstand) Number of Output Output Contact rating Rated Auxiliary Supply Burden on Aux. Supply Max. Error Max. load impedance allowable in series Insulation Case Size : : : : : : : : : : : : : 110V AC 15 msec or less 50 Hz 0.5 VA per phase 2 x In continuous 100 x In for 1 Sec. 2 NO or 1NO+1NC or 2 NC 10 Amp. Cont. & 20 Amp. Making 30, 110, 220 V DC 3W 5% 2000 ohms 2.0 kV as per IEC 60255-5 Size -I Deep Case

26

ABB

Wiring Diagrams

UVT 92m

ABB

27

Trip Circuit Supervision Relay type TCS / RXTCS

Features
Static design Continuous supervision of complete trip circuit independent of the circuit breaker position. Detects faults in the supervised circuits, such as loss of voltage, circuit breakage, contact degeneration in connections and resistivity increases in wires, contacts and coils. Low measuring current enables use in sensitive or high resistance circuit Operation delayed to avoid spurious signals, for instance, on circuit breaker operation Very low burden on auxiliary source Galvanic isolation between auxiliary source and supervised circuit. Also available in combiflex version

Model
TCS RXTCS

Ansi
95 95

Function
Trip Circuit Supervision Relay with flush mounting Trip Circuit Supervision Relay with combiflex mounting

Specification
Rated voltage ( Uaux ) Pick-up and Drop-off current at rated voltage Operate ( drop-off ) time at rated voltage Burden on Aux. Supply Burden on supervised circuit No. of Output Contact Output Contact rating Max. Error Supervision in condition Insulation Impulse Case Size : : : : : : : : : : : : 24, 30, 48, 110, 220,250 V DC 0.3 - 0.7 mA 0.6 - 0.7 Sec 3.5 W Max. 0.7 W Max. 1 NO + 1 NC + 2CO 5 Amp. Cont. & 10 Amp. Making for 3 Sec 5% suitable for supervision in both breaker Pre closed and post closed 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 Size -1/2 Case for TCS, 2U x 6C Size for RXTCS mounted in combiflex case as per requirement

28

ABB

Wiring Diagrams

TCS

RXTCS

ABB

29

Voltage Operated Auxiliary Relay type CV2

Features
Electromechanical design with Compact Size High degree of reliability, even when it has been idle for long time Mechanical operation indicator High contact rating 2 or 4 Nos. contacts with double interruption Three mounting variants - Flush, Plug in base and sheet metal base Wide range of voltage Lower power consumption

Model
CV2DJ CV2D2J CV2AJ CV2A2J CV2DRM CV2DM CV2DRN CV2DN

Ansi
30x, 30x, 30x, 30x, 30x, 30x, 30x, 30x, 63x 63x 63x 63x 63x 63x 63x 63x

Function
Single element aux. relay with flush mounting arrangement Two element aux. relay with flush mounting arrangement Single element aux. relay with flush mounting arrangement with AC Voltage Two element aux. relay with flush mounting arrangement with AC Voltage Single element aux. relay with Sheet metal base mounting arrangement Two element aux. relay with Sheet metal base mounting arrangement Single element aux. relay with Plug in base mounting arrangement Two element aux. relay with Plug in base mounting arrangement

Specification
Rated voltage ( Uaux ) Pick-up voltage ( % Un ) Drop-off voltage ( % Un ) Operate time at Un Operating range Burden on Aux. Supply No. of Output Contact Output Contact rating Max. Error Insulation Impulse Case Size : : : : : : : : : : : : 24, 30, 48, 110, 220, 250 V DC, 110, 240V AC for CV2AJ & CV2A2J model < 75% > 15% 20 - 35 msec -20% to +10% of Un 3.0 W for DC & 2.5VA for AC 2NO / 1 NO+1 NC for 1 element relay 4NO / 2NO+1NC / 3NO+1NC for 2 element 10A continuous & 30A making current. 5% 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 Size -1/2 Case for Flush mounting, Size -PB1 mounting for CV2DRN, CV2DN, Size -SM1 mounting for CV2DRM, CV2DM

30

ABB

Wiring Diagrams

CV2DJ, CV2DRM, CV2DRN, CV2AJ

CV2D2J, CV2DM, CV2DN, CV2A2J

ABB

31

High Speed Trip / No Volt Relay type P8n, PQ8n, PN8n, RXPQ8n, RXP8n

Features
Electromechanical design with Compact Size High degree of reliability, even when it has been idle for long time Mechanical operation indicator High contact rating 7 Nos. contacts with double interruption 4 mounting variants - Flush, Plug in, Sheet metal base and combiflex Wide range of voltage Lower power consumption

Model
P8nCH2JS PQ8nCH2JS PN8nCH2JS P8nAHXS P8nAH2YS PN8nAH2YS RXP8n RXPQ8n

Ansi
30x, 52x 86 80 30x, 52x 30x, 52x 80, 52x 86S, 52x 86

Function
High speed tripping relay with flush mounting arrangement High speed tripping relay with mech. latching with flush mounting arrangement No voltage relay with fixed ( 20% ) setting with flush mounting arrangement High speed tripping relay with plug in base mounting arrangement High speed tripping relay with Sheet metal base mounting arrangement No voltage relay with fixed setting with Sheet metal base mounting arrangement High speed tripping relay with combiflex mounting arrangement High speed tripping relay with mech. latching with combiflex mounting

Specification
Rated voltage ( Uaux ) Pick-up voltage ( % Un ) Drop-off voltage ( % Un ) Operate time at Un Operating range Burden on Aux. Supply No. of Output Contact Output Contact rating Max. Error Insulation Impulse Case Size : : : : : : : : : : : : 24, 30, 48, 110, 220,250 V DC, 110, 240V AC for flush mounted models < 80% for P8n & PN8n, < 70% for PQ8n > 4% for P8n & 20% for PN8n 20-30mSec for P8N & PN8N and 12-15mSec for PQ8n -20% to +10% of Un for P8n & PN8, -30% to +10% of Un for PQ8n 9.0 W for DC & 7.5VA for AC 7NO, 6NO+1NC, 5NO+2NC, 4NO+3NC 5A continuous & 50A making for 0.5 Sec 5% 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 Size -1/2 Case for Flush mounting, Size -PB1 mounting for P8nAHXS Size -SM1 mounting for P8 / PN8nAH2YS 2U x 12C Size for RXPQ/RXP8 mounted in combiflex case as per requirement

32

ABB

Wiring Diagrams

P8nAHXS

P8nCH2JS, PQ8nCH2JS, PN8nCH2JS P8nAH2YS, PN8nAH2YS

ABB

33

Bistable Relay type PSU6n, PSU14n, RXPSU6n, RXPSU14n

Features
Electromechanical design with Compact Size High degree of reliability, even when it has been idle for long time Mechanical operation indicator for PSU14 & RxPSU14 relay High contact rating 6 or 14 Nos. contacts with double interruption Three mounting variants - Plug in base, sheet metal base and combiflex Wide range of voltage Lower power consumption

Model
PSU6n2Y PSU14n4Y PSU6nX PSU14n2X PSU14nX RXPSU6n RXPSU14n

Ansi
52x 52x 52x 52x 52x 52x 52x

Function
Auxiliary relay with 6 Nos. contacts without operation indicator with sheet metal base with 2 sets of terminal blocks Auxiliary relay with 14 Nos. contacts with operation indicator with sheet metal base with 4 sets of terminal blocks Auxiliary relay with 6 Nos. contacts without operation indicator with one sets of plug in base Auxiliary relay with 14 Nos. contacts with operation indicator with two sets of plug in base Auxiliary relay with 7 Nos. contacts with operation indicator with one sets of plug in base Auxiliary relay with 6 Nos. contacts without operation indicator with combiflex mounting Auxiliary relay with 14 Nos. contacts without operation indicator with combiflex mounting

Specification
Rated voltage ( Uaux ) Pick-up voltage ( % Un ) Operate time at Un Operating range Burden on Aux. Supply No. of Output Contacts for PSU14n and RXPSU14n No. of Output Contacts for PSU6n and RXPSU6n No. of Output Contacts for PSU14nX Output Contact rating Max. Error Insulation mpulse Case Size : : : : : : : : : : : : : : 24, 30, 48, 110, 125, 220, 250 V DC < 80% 20 - 40 msec -20% to +10% of Un 65 W 7NO+7NC, 8NO+6NC, 9NO+5NC, 10NO+4NC, 11NO+3NC, 12NO+2NC, 13NO+ 1NC or 14NO 3NO+3NC, 4NO+2NC, 5NO+ 1NC or 6NO 4NO+3NC, 5NO+2NC, 6NO+1NC, or 7NO 5 A continuous & 50 A making for 0.5 Sec 5% 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 Size -PB2 mounting for PSU6nX, PSU14nX Size -PB3 mounting for PSU14n2X, Size -SM2 mounting for PSU6n2Y Size -SM3 mounting for PSU14n4Y
ABB

34

Wiring Diagrams

PSU14n2X, PSU14n4Y

PSU6nX, PSU6n2Y

ABB

35

Time Delay ( Delay on Pick Up ) Relay type SSX90m6C2J

Features
Static design with Compact Size Used for Protection, Control of industrial systems Pick up delay function Wide range of continuously adjustable time setting High repetition accuracy Indication by hand-reset flag Multiple 6 Nos. output contacts

Model
SSX90m6C2J

Ansi
2

Function
Time Delay ( Delay on Pick Up ) Relay

Specification
Rated voltage ( Uaux ) Operating range Time Delay range Burden on Aux. Supply Accuracy Setting Accuracy Repeat No. of Output Contacts Output Contact rating Insulation Impulse Case Size : : : : : : : : : : : 24, 30, 110, 220, 250 V DC -20% to +10% of Un 0.1-1.0 Sec, 0.3-3.0 Sec, 0.5-5.0 Sec, 1.0-10.0 Sec, 3.0-30.0 Sec, 6.0-60.0 Sec, 12.0-120.0 Sec, 30-300 Sec 7W / 13W ( quiescent / operation cond. ) 10 msec or 5% of setting which ever is greater at Un < 1.0% or 5 msec which ever is higher 3NO + 3NC, 6NO 5 A continuous & 50 A making for 0.5 Sec 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 Size - 1/2 deep case

36

ABB

Wiring Diagrams

SSX90m6C2J

ABB

37

Time Delay ( Delay on Drop Off ) Relay type SRX90m5C2J

Features
Static design with Compact Size Used for Protection, Control of industrial systems Drop off delay function Wide range of continuously adjustable time setting High repetition accuracy Indication by hand-reset flag Multiple 6 Nos. output contacts

Model
SRX90m5C2J

Ansi
2

Function
Time Delay ( Delay on Drop Off ) Relay

Specification
Rated voltage ( Uaux ) Operating range Time Delay range Burden on Aux. Supply Accuracy Setting Accuracy Repea No. of Output Contacts Output Contact rating Insulation Impulse Case Size : : : : : : : : : : : 24, 30, 110, 220, 250 V DC -20% to +10% of Un 0.1-1.0 Sec, 0.3-3.0 Sec, 0.5-5.0 Sec, 1.0-10.0 Sec, 3.0-30.0 Sec, 6.0-60.0 Sec, 12.0-120.0 Sec, 30-300 Sec 7W / 13W ( quiescent / operation cond. ) 10 msec or 5% of setting which ever is greater at Un < 1.0% or 5 msec which ever is higher 3NO + 2NC 5 A continuous & 50 A making for 0.5 Sec 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 Size - 1/2 deep case

38

ABB

Wiring Diagrams

SRX90m5C2J

ABB

39

Numerical combined Overcurrent and Earth Fault Relay type NI 40/ 41

Model Ansi

NI 40, NI 41 51/ 51N, 50/ 51/ 50N/ 51N relay without instantaneous element (NI 40). Numerical three phase over current and earth fault relay with instantaneous element (NI 41). For protection of feeders, transformers, capacitors of utility power plant & industry against short circuit & earth fault.

Function Numerical three phase over current and earth fault

Features
Numerical microprocessor based cost efficient feeder protection relay 3-phase low set O/C stage (IDMT or DMT) 3-Phase high set O/C stage (DMT or Inst) Earth fault protection - Low set stage (IDMT or DMT) Earth fault protection - High set stage (DMT or Inst) Low set stage have option of choosing four inverse time characteristics curve Measurement of 3 phase current in primary or secondary terms Measurement of Neutral current in primary or secondary terms Last five fault data recording 16x2 Alpha Numeric LCD display with backlit Indication LED's for Supply ON, Alarm/Trip, Internal Relay Failure Display of fault cause indication Extensive relay internal supervision monitoring relay hardware and software Normally open heavy duty output contact Two changeover signaling output contacts Low burden on current transformer Degree of protection IP54 Design confirming to requirements of IEC 60255 / IS 3231 standards Design immune to any kind of electromagnetic interference Used for feeder, transformer and backup protection

Specification
NI40 CT input ( In ) Over current a) Current range for I> b) Operate time range at DMT mode for I> c) Time-Current Characteristics at inverse mode for I> d) Time multiplier k for IDMT e) Current range for I>> f) Operate time range for Inst mode I>> g) Operate time range at DMT mode for I>> 1A or 5 A 50-200%x In 0.05 - 64 Sec Normal Inverse Very Inverse Extreme Inverse Long time Inverse 0.05, 0.1-1.0 NA NA CT input ( In ) Over current a) Current range for I> b) Operate time range at DMT mode for I> c) Time-Current Characteristics at inverse mode for I> Long time Inverse d) Time multiplier k for IDMT e) Current range for I>> f) Operate time range for Inst mode I>> g) Operate time range at DMT mode for I>> a) Current range for Io> b) Operate time range for Io Time-current characteristics at inverse mode for Io NI41 1A or 5 A 50-200%x In 0.05 - 64 Sec Normal Inverse Very Inverse Extreme Inverse 0.05, 0.1-1.0 50-4000% x In 50 mSec

NA

0.05 - 64 Sec 10 - 80% x In 0.05 - 64 sec. Normal Inverse Very Inverse Extremely inverse Long time inverse 0.05 - 1.0 10 - 1000% x In 50 msec 0.05 - 64 sec 18-80 V DC or 80-265 V AC/DC 50 Hz 4 x In <0.5VA 1 NO heavy duty, 2 Nos. NO Signaling & 1 No C/O for Internal relay failure 5A cont and 30A for 0.5 sec for heavy duty and 5A cont and 10A for 0.5 sec for Signaling contact.

Earth fault a) Current range for Io> 10 - 80% x In b) Operate time range for Io 0.05 64 sec. c) Time-current characteristics at inverse mode for Io

d) Time multiple k for IDMT e) Current range for Io>> f) Operate time range at inst. mode for Io>> g) Operate time range at DMT mode for Io>> Rated voltage Rated frequency Thermal withstand (Continuous) CT Burden Number of output contacts

c) Normal Inverse Very Inverse Extremely inverse Long time inverse 0.05 - 1.0 d) NA e) NA NA

Time multiple k for IDMT Current range for Io>>

f) Operate time range at inst. mode for Io>> g) Operate time range at DMT mode for Io>> Rated free voltage Rated frequency Thermal withstand (Continuous) CT burden Number of output

18-80 V DC or 80-265 V AC/DC 50 Hz 4xI <0.5VA 1 NO heavy duty, 2 Nos. NO Signaling & 1 No C/O for Internal relay failure 5A cont and 30A for 0.5 sec for heavy duty and 5A cont and 10A for 0.5 sec for Signaling contact.

Output contact rating

40

ABB

Wiring Diagrams

Connection diagram for three phase Numerical overcurrent and earth fault relay type NI 40/41 with residual connection of CTs for earth fault.

ABB

41

Numerical combined Overcurrent and Earth Fault Relay type SPAJ140C


Model Ansi
SPAJ140C 50, 51, 50N, 51N, 50LBB relay with instantaneous highset stage with built in circuit breaker failure protection

Function Combined three phase over current and earth-fault

Features
Numerical microprocessor relay with communication facility 3 phase Low set O/C stage with definite time or IDMT characteristic. 3 phase high set O/C stage with instantaneous or definite time characteristic. Low set earth fault stage with definite time or IDMT characteristic. High set earth fault stage with instantaneous or definite time characteristic. Low set stage have option of choosing six inverse or definite time characteristics - four standard inverse time curves as per IEC and BS. Two specific inverse time characteristics called RI & RXIDG. Integrated circuit breaker failure protection. Possibilities for two sets of relay settings. Memory of fault history for previous five numbers faults. 2 Heavy duty capable of direct breaker tripping & 4 signalling contacts High system reliability and availability due to continuous self-supervision. Digital display for measured and recorded values and status information. Ample programming, blocking and routing possibilities. Very high degree of protection IP54. High immunity to electrical and electromagnetic interference. Dual current input rating 1A and 5A Extremely low VA burden on current transformer High accuracy of the order 2% due to high sampling rate. Used for feeder, transformer & back up protections Long life time -MTBF > 200 years based on delivery and fault statistics.

Specification
: 1 and 5 Amp. Stage I> Stage I>> : 50% - 500% x In 50% - 4000% x In & : 50% - 250% x In : 0.05300 s 0.04300 s : 40 ms : Extremely Inverse Very Inverse Normal Inverse Long time Inverse RI type inverse RXIDG type inverse f) Time multiplier k for IDMT : 0.051.0 g) Retardation time : < 30 msec h) Reset ratio, typically : 0.96 i) Operation accuracy : 3% of set value 3% of set value Rated frequency : 50 Hz Permissible sustained : 4 x In continuous current (Thermal withstand ) : 100 x In for 1 Sec. Number of output : 2 NO Heavy Duty, 3 NO Signalling & contacts 1 CO for internal relay failure Output contact rating : 5 A Cont. & 30 A make for 0.5 Sec for heavy duty & 5 A cont. & 10 A make for 0.5 sec for signalling contact Earth fault stage Stage Io> Stage Io>> a) Start current : 10% - 80% x In 10% - 1000% x In & b) Operate time at DMT : 0.05300 s 0.05300 s c) Operate time at Instant. : 50 ms d) Time/current characteristic at : Extremely Inverse inverse mode Very inverse Normal inverse Long time inverse RI type inverse RXIDG type inverse e) Time multiplier k for IDMT : 0.051.0 f) Retardation time : < 30 msec g) Reset ratio, typically : 0.96 h) Operation accuracy : 3% of set value 3% of set value CT Burden : < 0.5 VA Rated auxiliary supply : 18-80V DC or 80-265V AC / DC Burden on aux. supply : 4W / 6W ( quiescent / operation cond. ) Number of binary input : 1 No. Insulation : 2.0 kV as per IEC 60255-5 Impulse : 5.0 kV as per IEC 60255-5 Case size : SPACOM 100 size case CT input ( In ) Over current stage a) Start current at DMT b) Start current at IDMT c) Operate time at DMT d) Operate time at Instantaneous e) Time/current characteristic at inverse mode

42

ABB

Wiring Diagrams

ABB

43

Numerical Composite Motor Protection Relay type SPAM150C

Model Ansi

SPAM150C 49,14, 48, 51, 50, 51n, 46, 37 relay

Function Comprehensive multifunctional motor protection

Features
Numerical microprocessor multifunctional relay with communication. 3 Phase thermal overload protection, motor overload pre-alarm 3 phase high set O/C stage with Instantaneous or DMT for S/C protn. Negative phase sequence, loss of phase & single phasing protection with Inverse characteristic, Sensitive earth fault protection Lock rotor / stalling protection Under current protection for loss of load Cumulative start up counter and restart inhibit function Measurement principle based on 3 phase RMS measurement to consider the effect of harmonics in thermal image resulting in to better protection. Memory of fault history for previous faults. 2 Heavy duty capable of direct breaker tripping & 4 Signalling contacts High system reliability and availability due to continuous self-supervision Digital display for measured and recorded values and status information Ample programming, blocking and routing possibilities. Very high degree of protection IP54. High immunity to electrical and electromagnetic interference. Dual current input rating 1A and 5A Extremely low VA burden on current transformer High accuracy of the order 2% due to high sampling rate. Used for large & medium sized breaker & contactor controlled LT / HT motors Long life time -MTBF > 200 years based on delivery and fault statistics.

Specification
CT input ( In ) Thermal overload a) Full load current ( I ) b) Weighting factor ( P ) c) Cooling time multiplier ( Kc ) d) Thermal prior alarm level ( a) e) Motor restart inhibit level ( t ) Locked rotor / stalling a) Start up current Is b) Start up time ts c) Operation principle : : : : : : : : : 1 and 5 Amp 50% - 150% x In 20 - 100% 1 - 64 x Th 50 - 100% x Qt 20 - 80% x Qt 1.0 - 10 x In 0.3 - 80 Sec Definite time or thermal stress I2 x t

Inst. phase overcurrent (S/C) a) Start current I>> : 50 - 2000% x In or Infinite b) Operate time t>> : 0.0430.0 s Rated frequency : 50 Hz CT Burden : < 0.5 VA Permissible sustained cur: 4 x In continuous Rent (Thermal withstand ) : 100 x In for 1 Sec. Number of output : 2 No heavy duty, 3 No signalling & Contacts 1 CO for internal relay failure Output contact rating a) for heavy duty contact : 5 A continuous & 30 A make for 0.5 sec b) for signalling contact : 5 A continuous & 10 A make for 0.5 sec Earth fault unit a) Start current I0> : 1.0 - 100% x In b) Operate time t0> : 0.0530.0 s Negative phase sequence / incorrect phase sequence a) Start current I : 1040% x IL or b) Operate time T : 20120 s c) Operation characteristic : Inverse time d) Operate time at single phasing : 1 sec e) Operate time at Incorrect phase : 600 msec Under current unit a) Start current I< : 3080% of I or off b) Operation inhibit level : <12% of I c) Operate time t< : 2600 sec Cumulative start-up time counter unit a) Restart inhibit level : 5500 sec b) Countdown rate : 2250 s/h Rated auxiliary supply : 18-80V DC or 80-265V AC / DC Burden on aux. supply : 4W/6W ( quiescent/operation cond.) Number of binary input : 1 No. Insulation : 2.0 kV as per IEC 60255-5 Impulse : 5.0 kV as per IEC 60255-5 Case size : SPACOM 100 size case

44

ABB

Wiring Diagrams

ABB

45

Numerical Capacitor Bank Protection relay type SPAJ160C

Model Ansi

SPAJ160C 46,49,37,62,51N protection relay

Function Comprehensive multifunctional capacitor bank

Features
Numerical microprocessor multifunctional relay with communication. 3 phase 2 stage overload protection with one Inverse time characteristics and other with definite time characteristics 2 Stage phase unbalance protection with one Inverse time characteristics and other with definite time characteristics Undercurrent protection for detection of capacitor disconnection. Reconnection time with wide setting range Compensation for natural unbalance current Memory of fault history for previous faults. 2 Heavy duty capable of direct breaker tripping & 4 signalling contacts High system reliability and availability due to continuous self-supervision Digital display for measured and recorded values and status information Ample programming, blocking and routing possibilities. Very high degree of protection IP54. High immunity to electrical and electromagnetic interference. Dual current input rating 1A and 5A Extremely low VA burden on current transformer High accuracy of the order 2% due to high sampling rate. Used for large & medium sized breaker & contactor control LT / HT motors Long life time -MTBF > 200 years based on delivery and fault statistics. Used to protect capacitor bank intended for reactive power compensation and filtering of the harmonics.

Specification
CT Input ( In ) Overload stage Ib> a)Start current Ib> b)Operation characteristic c)Time multiplier k Overload stage Ia> a)Start current Ia> b)Operation characteristic c)Operate Time Undercurrent stage I< a)Start current I< b)Operate time c)Reconnection inhibit time trec Rated Frequency Number of output Contacts Output contact rating a)for Heavy duty contact b)for signalling contact Phase unbalance I1> a)Start current I1> b)Operate time t1 Phase unbalance I2> a)Start current I2> b)Time multiplier k 2> c)Shortest possible operate time Unbalance compensation a)Compensation current ICS Operation accuracy CT Burden Permissible sustained current (Thermal withstand ) Rated auxiliary supply Burden on aux. supply Number of binary input Insulation Impulse Case size : 0.0 - 20% x In* : 3% of set value : < 0.5 VA : 4 x In continuous : 100 x In for 1 sec. : 18-80V DC or 80-265V AC / DC : 4W / 6W ( quiescent / operation cond. ) : 1 No. : 2.0 kV as per IEC 60255-5 : 5.0 kV as per IEC 60255-5 : SPACOM 100 Size Case : 2.0 - 80% x In : 0.1 - 1.0 at Inverse time : ~100 ms : 1.0 - 100% x In : 1.0 - 300 sec at definite time : 5 A continuous & 30 A make for 0.5 sec : 5 A continuous & 10 A make for 0.5 sec : 10 - 70% x In : 1 - 100 Sec : 0.5 - 100 min : 50 Hz : 2 No heavy duty, 3 No signalling & 1CO for internal relay failure : 80-120% x Ib : Definite time : 0.5 - 100 min : 30 - 150% x In : Inverse ANSI : 0.2 - 2.0 : 1 and 5 Amp.

46

ABB

Wiring Diagrams

ABB

47

Numerical three phase Under voltage and Over voltage relay type SPAU130C
Model Ansi
SPAU130C 27+2 , 59+2 type SPAU130C

Function Three phase under voltage and over voltage relay

Features
Numerical microprocessor relay with communication facility Combined over voltage and under voltage protection relay 3 Phase definite time or inverse time over voltage stage 3 Phase definite time under voltage stage Control input for blocking the function of the undervoltage stage by means of an external control signal Automatic blocking of the undervoltage stage on loss of energizing voltage Memory of fault history for previous fault. 2 Heavy duty capable of direct breaker tripping & 3 signalling contacts High system reliability and availability due to continuous self-supervision. Digital display for measured and recorded values and status information. Ample programming, blocking and routing possibilities. Very high degree of protection IP54. High immunity to electrical and electromagnetic interference. Dual PT input rating 100V and 110V AC Extremely low VA burden on voltage transformer High accuracy of the order 2% due to high sampling rate. Used for over / under voltage protection of Motor, Capacitor banks and Feeder protections Feeder protections Long life time -MTBF > 200 years based on delivery and fault statistics.

Specification
PT Input ( Un ) Over Voltage Protection a) Start voltage U> b) Start time, preset values : 80 - 160% x Un : 0.1 sec or 30 sec : 100, 110 V AC

c) Operate time at definite time operation: 0.05 - 100 sec characteristic d) Time multiplier k> at inverse time e) Reset time, typically f) Drop-off/pick-up ratio, typically g) Operation accuracy Rated Frequency PT Burden Number of output Contacts Output contact rating a) for heavy duty contact b) for signalling contact Under voltage protection a) Start voltage U< b) Start time, preset values c) Operate time d) Reset time, typically e) Drop-off/pick-up ratio f) Operation accuracy Permissible sustained voltage (Thermal withstand) Rated auxiliary supply Burden on aux. supply Number of binary input Insulation Impulse Case size : 40 - 120% x Un : 0.1 sec or 30 sec : 1 - 120 sec : 60 ms : 1.03 : 3% of set value : 4 x In continuous : 100 x In for 1 sec. : 18-80V DC or 80-265V AC / DC : 4W / 6W (quiescent / operation cond.) : 1 No. : 2.0 kV as per IEC 60255-5 : 5.0 kV as per IEC 60255-5 : SPACOM 100 Size Case : 5 A continuous & 30 A make for 0.5 Sec : 5 A Continuous & 10 A make for 0.5 Sec : 0.05 - 1.00 : 60 ms : 0.97 : 3% of set value : 50 Hz : < 0.5 VA : 2 NO heavy duty, 3 No signalling & : 1 CO for internal relay failure

48

ABB

Wiring Diagrams

ABB

49

Numerical High impedance Protection Relay type SPAE010 / 011

Model SPAE010 / 011 3*SPAE010 / 011

Ansi 64R 87M / 87G

Function High impedance based restricted earth fault protection for transformers and generators High impedance based 3 phase differential protection for motors / generators

Features
Numerical Microprocessor relay High impedance type differential current earthfault protection. Required stabilizing resistors built-in into the relay Short total operating time together and high stability 2 Heavy duty capable of direct breaker tripping & 2 Signalling contacts High system reliability and availability due to continuous self-supervision. Very high degree of protection IP54. High immunity to electrical and electromagnetic interference. Extremely low VA burden on voltage transformer High accuracy and long time stability due to Numerical based design with high sampling rate. Used for Restricted Earth Fault protection of Transformers, Generator and High Impedence based Differential protection of Motor and Generators. High immunity to electrical and electromagnetic interference. Long life time -MTBF > 200 years based on delivery and fault statistics.

Specification
Energizing input ( Un ) Setting ranges a) Voltage setting range, U>/Un b) Operating current c) Operating time d) Drop-off time e) Drop-off/pick-up ratio CT Burden Permissible sustained vol. Thermal withstand Rated frequency Number of output Contacts Output contact rating
a) for heavy duty contact b) for signalling contact : 5 A continuous & 30 A make for 0.5 sec : 5 A continuous & 10 A make for 0.5 sec : 18-80V DC ( SPAE011 ) or 80-265V AC / DC ( SPAE010 )

: 50, 100, 200 V AC

: 0.4 - 1.2 x Un : 927 mA : 17 - 80 ms : 120 ms : 0.8

: < 0.5 VA : 1.3 x Un continuous


: 10 x Un for 1 Sec. : 50 Hz : 2 No heavy duty, 2 No signalling & : 1 CO for internal relay failure

Rated auxiliary supply

Burden on aux. supply Insulation Case size

: 5W : 2.0 kV as per IEC 60255-5 : SPACOM 100 Size Case

Note : The external stabilising resistor is supplied along with relay. The total impedance of the relay and series stabilising resistor is usually low enough to prevent the CT developing voltages over 2 kV during max. internal faults, but in some applications a non-linear resistor is required to limit this voltage.

50

ABB

Wiring Diagrams

R31-R33 = stabilizing resistors Ru = voltage dependent resistor

ABB

51

Numerical Stabilized Transformer Differential Relay type SPAD346C

Model SPAD346C

Ansi

Function

87T, 64R, 51G, Three phase transformer differential protection 50, 51, 50N, 51N Restricted earth fault & stand by E/F protection Three phase over current & earth fault protection Three phase transformer differential protection Restricted earth fault & stand by E/F protection

SPAD346C1 87T, 84R, 51G

SPAD346C2 87T, Three phase transformer differential protection 50, 51, 50N, 51N Thee phase over current & earth fault protection SPAD346C3 87T Three phase transformer differential protection

Features
Numerical microprocessor relay with communication facility Integrated two winding transformer differential, three phase Overcurrent and multi configurable earth fault relay. Three phase transformer differential module: Biased differential protection stabilized against unwanted operations at faults occurring outside the protected area and at transformer inrush. Second harmonic restraint for prevention of unwanted trip during T/R inrush. Fifth harmonic restraint for prevention of unwanted trip during T/R Over excitation. Interposing CTs can be avoided as CT ratio matching and vector group matching can be programmed in the relay Sensitive phase current and phase angle displays facilitate checking of energizing circuit connections and vector group matching. In built disturbance recording facility is available. Restricted earth fault and stand by earth fault module : Four programmable operating principle for earth fault on LV & HV side as: - Neutral current principle, - high impedance principle, - Stabilized differential current principle, - zero sequence current principle CT Ratio matching In built disturbance recording facility is available. Back up Over current and Earth fault module : 3 Phase over current unit comprising of 3 stages - Low, High & Super high set Earth fault unit comprising of 2 stages - low, high set stage Phase discontinuity unit for protection against phase unbalance Integrated circuit breaker failure protection. 5 alarm channels for transformer mechanical faults like buchchholtz, wdg temp etc. Possibilities for two sets of relay settings. Memory of fault history for previous five numbers faults. 2 Heavy duty contact capable of direct breaker tripping & 4 signalling contacts High system reliability and availability due to continuous self-supervision. Digital display for measured and recorded values and status information. Ample programming, blocking and routing possibilities. Very high degree of protection IP54. High immunity to electrical and electromagnetic interference. Dual current input rating 1A and 5A Extremely low VA burden on current transformer High accuracy of the order 2% due to high sampling rate. Used for feeder, transformer & back up protections Long life time -MTBF > 200 years based on delivery and fault statistics.

52

ABB

Specification
CT Input ( In ) Stabilized differential current stage 3 I> a) Basic start ratio P/In b) Starting ratio setting S c) Second turning point I2tp/In of curve d) Harmonics blocking ratio Id2f/Id1f e) Harmonics blocking ratio Id5f/Id1f f) Harmonics deblocking ratio Id5f/Id1f g) Operate time at 1.5-4 x operate value h) Operate time at 4 x operate value Instantaneous differential current stage 3 I> a) Start ratio Id/In>> b) Operate time at 1.1-2.6 x Id/In>> c) Operate time at 2.6 x Id/In>> CT Ratio correction range on HV CT ratio correction range on LV Restricted & stand by earth fault stages a) Operating principle : : : : : : : : : : : : : : : 1 and 5 Amp. 05 - 50% 10 - 50% 1.0 - 3.0 07 - 20% 10 - 50% 10 - 50% < 40 msec < 30 msec 05-30% < 35 msec < 30 msec 0.40 - 1.50 x I1/In 0.40 - 1.50 x I2/In Stabilized differential principle. High Impedance differential principle. Neutral current principle 550% 0.03100 s 550% 0.03100 s 50 Hz 4 x In continuous 100 x In for 1 sec. 4No heavy duty, 5No signalling & IRF 5 A continuous & 30 A make for 0.5 Sec 5 A continuous & 10 A make for 0.5 Sec Stage I> Stage I>> 50% - 500% x In 50% - 4000% x In & 50% - 250% x In 0.05300 s 0.04 - 300 s 40 ms Extremely inverse Very inverse Normal inverse Long time inverse RI type inverse RXIDG type inverse 0.051.0 < 30 msec 0.96 Stage Io> Stage Io>> 10% - 80% x In 10-1000%xIn 0.05300 s 0.04 - 300 s Extremely inverse Very inverse Long time inverse RI type inverse RXIDG type inverse 0.051.0 < 30 msec 0.96 0.96 < 0.5 VA 18-80V DC or 80-265V AC / DC 10W / 15W ( quiescent / operation cond. ) 5 Nos. 2.0 kV as per IEC 60255-5 5.0 kV as per IEC 60255-5 SPACOM 300 Size Case

b) Basic start ratio on HV side P1/In c) Operate time on HV side t01> d) Basic start ratio on LV side P2/In e) Operate time setting on LV side t02> Rated frequency Permissible sustained current (thermal withstand ) Number of output contacts Output contact rating a) for heavy duty contact b) for signalling contact Over current stage a) Start current at DMT b) Start current at IDMT c) Operate time at DMT d) Operate time at instantaneous e) Time/current characteristic at inverse mode

: : : : : : : : : : : : : : : :

Stage I>>> 0.04 - 300 s 40 ms Stage I>>> 10-100%xIn 1-300 s 0.9

f) Time multiplier k for IDMT g) Retardation time h) Reset ratio, typically Earth fault stage a) Start current b) Operate time at DMT c) Operate time at instant. d) Time/current characteristic at inverse mode

: : : : : : :

e) Time multiplier k for IDMT f) Retardation time g) Reset ratio, typically CT Burden Rated auxiliary supply Burden on aux. supply Number of binary input Insulation Impulse Case size

: : : : : : : : : :

ABB

53

Wiring Diagram SPAD346C

54

ABB

Station Automation COM 600

Model

COM 605, COM 610, COM 615 a substation. Easy and powerful connectivity from the protection and control devices of a substation, with monitoring and control functionality, and the connection to NCC. Full station automation functionality combines the features and functionality of the control and monitoring unit COM 605 and communication gateway COM 610.

Function Connectivity to the protection and control devices of

Features
Standard web - browser with diagnostic information & web HMI user management 3 phase 2 stage overload protection with one Inverse time characteristics and other with definite time characteristics The station automation COM 600 series is a dedicated system for the automation of utility and industrial Substation. COM 600 is a dedicated system for providing inter operability between industrial or utility substation IED's and local or higher level systems, such as a local operator interfaces or higher-level network control centers (NCC) or Distributed control systems (DCS). The COM 600 series includes three products: the control and monitoring unit COM605, the communication gateway COM610 and the station computer COM615 Each COM600 product is optimized for ABB protection and control devices and can be easily integrated with them. COM600 also facilitates for integration of third party devices. The innovative industrial design and extended communication capabilities make them ideal for harsh and demanding environment real-time process information is critical. COM600 has an embedded design with no moving parts, so it is maintenance free. The design is compact enough to fit in low voltage compartment of switchgear, saving both space and money. The various communication interfaces included minimize the need for external media converters. Electrical and optical interfaces are available in COM 600 products. The control and monitoring unit COM 605 provides connectivity to the protection and control devices of a substation. The communication gateway COM 610 provides easy and powerful connectivity from the protection and control devices of a substation, with monitoring and control functionality, and the connection to NCC. Station computer COM 615 provides full station automation functionality combines the features and functionality of the control and monitoring unit COM 605 and communication gateway COM 610. Communication over IEC61850 protocol is available for smooth interoperation. ABB

Specification
COM 605 COM 610 COM 615 Connectivity Master Protocols SPA, IEC 61850-8-1 client, IEC 60870-5-103, Modbus (RTU), LON (ABB Lag) Slave Protocol IEC 60870-5-101, IEC 60870-5-104, DNP 3.0 Serial & LAN/WAN SMPT server for local time synchronisation Support for remote parameter setting and disturbance file uploaded with ABB protection and control devices from microSCADA Pro Control and Monitoring Communication diagnostics Configuration and administration Single line diagram and busbar coloring Parameter setting Status monitoring and control Disturbance data upload Events and alarm list Measurements System Supervision Software HMI through Web server functionality Future proof - supporting IEC 61850 standards Efficient configuration supporting IEC 61850-6 (SCL) Unified protocol mapping based upon IEC 61850-7 Remote configuration and administration Hardware Communication ports : 2 x LAN (RJ-45 copper), 4 x RS-232 (one can be configured as RS-485; 2-wire), Other ports: VGA output, 4 x USB, audio output for audio alarm Optional cards: RS-232/485 (4 ports) or LAN (2 ports, RJ-45 copper) or fiber optic LAN (1 port) or LON (1 Port) Wide range power supply 24 - 220v DC(internal), 220v AC (external)                                          

 

 

 

 

 

 

55

Station Automation COM 600


Utility Application

Industry Application

56

ABB

Mounting details and case dimensions

Size - I Case
Dimensions

Legend: Aa : Terminals M5 Ir : Mounting frame Ge : Earthing lug Ob : Fixing screw Dimensions for mounting

Size - I deep case

Front View

Panel Cut-Out Side View

ABB

57

Size - II Case ( Horizontal )

Front View

Panel Cut-Out

Side View

Size - 1/2 Case


Dimensions

Rear view

Side view

Front view

Cutout

1/2S case mounting.

Legend: Aa : Terminals Db : Mounting hole Ls : Operation signal Ob : Mounting screw

58

ABB

Size 1/2 Case Deep

Rear view 1/2S case mounting.

Side view

Front view

Cutout

Required space for mounting

External resistors details

Legend: Aa : Terminals Db : Mounting hole Ls : Operation signal Ob : Mounting screw

ABB

59

Spacom series case - 100

Spacom series case - 300

60

ABB

Combiflex RHGX - 4 Case, 8 Case, 12 Case, 20 Case

Upper View

Front View

Side View

Type of Case RHGX4 RHGX8 RHGX12 RHGX20

Overall Cutout Dimensions (in mm) Dimensions (in mm) L L1 L2 L3 L4 132 216 300 468 110 194 278 446 135.5 219.5 303.5 471.5 112+1.0 196+1.0 280+1.0 448+1.0 190+1.0 190+1.0 190+1.0 190+1.0

ABB

61

COMBIFLEX relay mounting 6C Dimensions

References

Connection and installation components in COMBIFLEX Relay mounting systems

1MRK 513 003-BEN 1MRK 514 001-BEN

COMBIFLEX relay mounting systems 12C


Dimensions

Combiflex mounting

References

Connection and installation components in COMBIFLEX Relay mounting systems

1MRK 513 003-BEN 1MRK 514 001-BEN

62

ABB

Plug-in base mounting (PB1)


Dimensions

Plug-in base mounting

Sheet-metal base mounting (SM1)

Dimensions

Sheet-metal base mounting.

Legend Aa: Terminals Db: Mounting hole E01:Cut-out for rear wiring. *: Space for removing hood. Ls: Operation signal Ob: Fixing screw

ABB

63

Plug-in base (PB2)

Dimensions

Relay on one set of Plug-in base mounting

Plug-in relay(PB3)

Relay on two sets of Plug-in base mounting

64

ABB

Relay on sheet-metal base mounting ( SM2 & SM3 )

Relay on sheet-metal base mounting

Numerical three phase overcurrent & earth-fault relay NI 4_

Front View

Side View

Panel Cutout

Rear view

ABB

65

Terminals for protection, control and monitoring

REX 521 This feeder protection relay is designed for protection, control, measuring and supervision in distribution networks and for protection of large or medium-size three-phase a.c. motors in circuit breaker controlled motor drives.

REF 541, 543 and 545 These feeder terminals are designed for the protection, control, measurement and supervision of distribution networks.

REM 543 and 545 These machine terminals are intended to be the main protection system for generator and generator-transformer units in small and mediumpower diesel, hydroelectric and steam power plants.

RET 541, 543 and 545 These transformer terminals are designed for the protection, control, measurement and supervision of two-winding power transformers and power generator / transformer blocks in distribution networks.

REF 542plus This switchbay protection and control unit combines measurement, monitoring, protection, control and self diagnostics in one package.

66

ABB

REA 101, 103, 105 and 107 The REA Arc Protection System provides your substation with comprehensive protection against arc faults.

REC 501 and 523 These remote monitoring and control units offer functions for remote and local control, condition monitoring, protection and fault indication, supervision and automation of secondary substations in distribution networks.

Protection relays from 610 series


REM 610 The motor protection relay REM 610 is primary targeted at protecting large asynchronous lowvoltage motors and small and medium-sized highvoltage asynchronous motors.

REF 610 The protection relay REF 610 is primarily targeted at the protection of incoming and outgoing feeders in distribution substations. REF 610 is also used as back-up protection for motors, transformers and generators, in utility and industry applications.

REU 610 The voltage protection relay is primary designed for the under and over voltage protection of power system components, such as busbars, feeders, power transformers and capacitor batteries.

ABB

67

ABB Limited Distribution Automation Maneja, Vadodara 390 013, India. Tel: +91 265 2604385 +91 265 2604386 Fax:+91 265 2638922 E-mail: aicds@in.abb.com

Regional Marketing Offices: North


No.14, Mathura Road P.O. Amar Nagar Faridabad 121 003 Tel: +91 129 2275592, 2279627, 5049000 Fax: +91 129 2279692/5019 SCO No.13-14-15 (3rd Floor) Sector 34-A Chandigarh - 160 022 Tel: +91 172 2606093 Fax: +91 172 2601618

South
Embassy Star, 1st Floor No. 8, Palace Road Vasanth Nagar Bangalore 560 052 Tel: +91 80 22949779 Fax: +91 80 22949808 Century Plaza No. 3C, 3D & 3F, 3rd Floor 561 / 562, Anna Salai Teynampet (Mount Road) Chennai 600 018 Tel: +91 44 24340201 Fax: +91 44 24340282

Central
4th & 5th Floor Maruti Heights Aamanaka, G E Road Raipur 492 099 Tel: +91 771 4701016

West
ABB House Dr. S B Path Ballard Estate Mumbai 400 038 Tel: +91 22 56318231 39 Fax: +91 22 56318276/77

www.abb.co.in

FF- 9A, 1st Floor Manasarover Commercial Complex Hoshangabad Road Bhopal 462016 Tel: +91 755 4223572 Fax: +91 755 4253323

East
4th Floor No. 9, Elgin Road Kolkata 700 020 Tel: +91 33 22832906/8 Fax: +91 33 22832990