Você está na página 1de 8

HD4 12-17.5kV up to 31.

5 kA

DATA SHEET CIRCUIT BREAKER

HD4 12-17.5 kV up to 31.5 kA and up to 1600 A (1600 A fixed version, 1250 A withdrawable version)

1.1 General Item 1 1.1 1.2 1.3 1.4 1.5 2 2.1 3 3.1 3.2 3.3 3.4 4 5 Description Manufacturer Standard product Quality certification Environmental Management System cert. Country City , Address Type of circuit breaker (SF6, Vacuum, etc) If SF6 which interrupting technology Type designation Fixed Withdrawable for CBE / CBF " for UniSafe switchboard " for UniGear type ZS1 switchboard Testing Authority (Accreditated by SINAL) Standards

ABB T&D S.p.A. - Unit Operativa Sace T.M.S. Yes ISO 9001 ISO 14001 Italy Dalmine (BG), via Friuli 4 CAP 24044 SF6 Autopuffer HD4 Ui.In.Isc HD4/C Ui.In.Isc HD4/W Ui.In.Isc HD4/P Ui.In.Isc CESI (Italy) , ABB SACE TMS , ABB SACE LV IEC 62271-100

1.2 Operating Characteristics Item 1 2 3 4 4.1 4.2 4.3 4.4 5 5.1 Description Rated Voltage (U) Rated normal current (In) at 40C Frequency Operating Duty Normal sequence High speed three phase Out of phase Make-break time (C-O) Rated Making and Breaking Current during Normal/Reclose Operating sequence Three phase terminal fault rating 5.1.1 Breaking current (symmetrical) 5.1.2 Breaking current (asymmetrical) 5.1.3 Making current 5.1.4 First pole to clear factor Single phase earth fault rating 5.2.1 Breaking current (symmetrical) 5.2.2 Making current Breaking current under out of phase conditions Short time rating - 3 sec Rated current 630 A Rated current 1250-1600 A Mechanical performances:

kV A Hz

12-17.5 630-1250-1600 (up to 1250 A for withdrawable version) 50/60 O - 0.3 sec - CO - 3 min - CO O - 0.3 sec - CO - 15 sec - CO CO 120

msec

kA %Idc kAp

16 - 25 - 31.5 30% at 31.5 kA 40 - 63 - 80 1.5 (see Annex 1) 16 - 25 - 31.5 40 - 63 - 80 4 - 6.25 - 8 16, 25 (3 sec) - 31.5 (1 sec) 16 - 25 - 31.5

5.2

kA kAp kA kA kA

5.3 6 6.1 6.2 7

rev. 29-jan-2002

Page 1 of 8

HD4 12-17.5kV up to 31.5 kA

7.1 7.2

7.3

7.4 7.5

7.6

7.7

7.8 7.9

7.10 8 8.1

8.2 8.3 8.4 8.5

8.6 8.7

8.8 8.9 9

10

Maximum total break time (trip start to final arc extinction) msec Opening time (trip start to contact separation) 7.2.1 100% of supply voltage msec 7.2.2 70% of supply voltage msec 7.2.3 110% of supply voltage msec Maximum time interval between opening of first and last phase of three phase circuit breaker msec Maximum time interval between opening of interrupters of one phase msec Closing time from energisation of close coil to latching of circuit breaker in fully close position msec Making time (energisation of close coil to contact touch) : 7.6.1 100% of supply voltage msec 7.6.2 85% of supply voltage msec 7.6.3 110% of supply voltage msec Maximum time interval between closure of first and last phase of three phase circuit breaker msec Maximum time interval between closure of interruptors of one phase msec Maximum time from separation of the contact to their remaking during auto reclosing duty (O-C) ("Dead time") sec Critical current on which maximum arc occour Switching Overvoltages: Maximum peak value of switching overvoltage when interrupting rated inductive current Interruption of no-load MV/LV trasformers A Interruption of compensation reactance currents A Interruption of MV motor rated currents A Maximum peak value of switching overvoltage when interrupting rated line and cable charging current Interruption of no-load cables and lines A Interruption of capacitive currents (C-O) 8.7.1 Single capacitor bank A 8.7.2 Back-to-back capacitor bank A 8.7.3 Capacitor bank inrush making kA (IEC 62271-100 class C2) Rated characteristic for short line fault Current chopping level Basic Insulation Level ( BIL 1.2/50 sec) phase to phase, phase to earth, across open contact kVp Power frequency withstand voltage phase-phase, to earth, across open contact kVrms/1min

55-60

45 65 42

2 N.A.

60

74 80 70

2 N.A.

0.3 (IEC 62271-100) Absent

=< 2.5 P.U. 10 480(630)-630(1250)-800(1600) 480(630)-630(1250)-800(1600)

=< 2.5 P.U. 31.5 400(630)-630(1250)-1000(1600) 400 20 at 4.25 kHz N.A. N.A. for SF6

75(12) - 95(17.5) 28(12) - 38(17.5)

rev. 29-jan-2002

Page 2 of 8

HD4 12-17.5kV up to 31.5 kA

11 12 13 14 15

Radio influence voltage (RIV) level measured at 1.1Um 3 at 1MHz Insulation material of outer contact arms Maximum temperature rise test under normal load conditions Drop voltage with 200Adc at 20C (CB closed between upper and lower terminal) Test parameters of the short-circuit interrupting performances: current (rms), TRV (Uc),t3, td,U' , t' , RRRV

V C

N.A. Glass polyester mass According to IEC 62271-100 and IEC 60694 12 max Test Duties 1-2-3-4-5 all according IEC 62271-100 (see Annex 1)

mV

1.3 Constructional Features 1.3.1 Item 1 2 3 4 4.1 4.2 4.3 5 5.1 5.2 6 6.1 6.2 7 7.1 7.2 8 9 10 10.1 10.2 10.3 11 11.1 General

Description Number of poles Number of current interrupting break units in series per phase Method of controlling voltage distribution between break units (resistor, capacitor etc) Value of resistors where used: Breaking resistors Making resistors Insertion time of making resistors Type of power device (pneumatic, electro-pneumatic, hydraulic or spring) for closing for opening Number of opening trip device per phase Single phase mechanism Three phase mechanism Mass of complete CB Fixed version Withdrawable Live mass of circuit breaker complete Total load of heaters for circuit breakers Minimum clearence distance (withdrawable version C , W and P) Phase - Phase Phase - Earth Between upper and lower terminal Minimum creepage distance Fixed version 11.1.1 Phase - Earth 11.1.2 Between upper and lower terminal Withdrawable version 11.2.1 Phase - Earth 11.2.2 Between upper and lower terminal Length of break Stroke of moving contacts Type of main contacts (and material) Type of arcing contacts (and material) Type of arc control device 3 1 N.A. N.A. N.A. N.A.

Spring Spring N.A. on request up to 2 coils kg kg kg W 114 120 Depending on the panel type N.A.

mm mm mm

240 (pitch 150mm) - 240(p 210) 150 (p 150) - 153 (p 210) 297 (p 150) - 340 (p 210)

mm mm mm mm mm mm

288 405 395 613 30 65 Fingers (Cu silverplated) Plug - Pliers (Cu-W) N.A.

11.2

12 13 14 15 16

rev. 29-jan-2002

Page 3 of 8

HD4 12-17.5kV up to 31.5 kA

17

Type of device, if any, used to limit rate of rise of re-striking voltage 1.3.2 Sulphure Hexafluoride Circuit Breaker

N.A.

Item 1 2 3 4 5

Description Dead or live tank design 3 indipendent sealed insulated poles gr gr bar (abs) bar (abs) bar (abs) 225 Sealed for life (30 years) 3.8 at 20C 3.2 at 20C 2.8 at 20C (All dielectric and interrupting performances are guaranteed) Pressure switch 10 Yes Safety valve 1 per pole 16 >30 Epoxy resin Composite material Molecular sieves (synthetic zeolite)

Quantity of gas required to fill one three-phase circuit breaker Quantity of make-up gas required per year per three-phase circuit breaker Normal operating pressure of gas Low pressure alarm settings 5.1 First stage (alarm) 5.2 Second stage (block)

6 7 8 9

Type of pressure monitoring device Breaking capacity at 0 bar pressure Routine leakage test on each pole Overpressure device 9.1 Number of relief device 9.2 Rupturing pressure of the valve 9.3 Rupturing pressure of the envelope 10 Material of envelope 11 Material of moving contact driving rod 12 Type of filter employed for absorbtion of decompositions of SF6 product

kA Yes/No

bar (abs) bar (abs)

1.3.3 Item 1 2 3 4 5 6 7 8 8.1 8.2 9 9.1 9.2 9.3 10 11

Spring operating mechanism

Description Type Number of mechanism per circuit breaker Operating mechanism with solenoid or motor charged spring Trip springs separate from closing springs Is the CB trip free? Operating backup charging mechanism Number of closing operation stored in fully charged springs without rewinding Number of tripping and closing operations stored in a fully charged spring systems Circuit breaker initially in closed state Circuit breaker initially in open state Time to fully charge spring after: Close operation Close - trip operation Trip - close - trip operation Stored energy of tensioned closing spring Push button for switch ON/OFF ESH 1 Motor charged spring Yes Yes Manual (provided) 1

Yes/No Yes/No

O - CO CO sec sec sec J Yes/No 5...7 5...7 5...7 350 Yes (standard)

rev. 29-jan-2002

Page 4 of 8

HD4 12-17.5kV up to 31.5 kA

11.1 11.2 12

Mechanical ON/OFF indicator Mechanical indicator showing the closing springs positions (charged-discharged) Microswitch indicators of rack-in and rack-out positions

Yes/No Yes/No

Yes (standard) Yes (standard) On the c.b. roof cubicle for CBE, UniSafe and UniGear type ZS1. On the c.b. truck for CBF and UniGear type ZS1 (on request) Yes (standard) By means of truck tulip for CBE By means of truck wheels for UniSafe and UniGear type ZS1

13 14

Mechanical operation counter Earthing method

Yes/No Yes/No

15 15.1 15.2 15.3 16 17 18 18.1 18.2 18.3 18.4 19 19.1 19.2 19.3 19.4 20 21 22 22.1

22.2

22.3

23 23.1 23.2 23.3 23.4 23.5 23.6 23.7

Standard supply voltage (motor, opening and closing coils, ) DC AC 50 Hz AC 60 Hz Antipumping device Power required during spring recharging (inrush/continuous service) Closing release coil (YC) Rated operating voltage Minimum operating voltage Maximum operating voltage Rated power (inrush/continuous service) Opening release coil (YO1) Rated operating voltage Minimum operating voltage Maximum operating voltage Rated power (duration less than 100ms) Undervoltage release (YU) (inrush/continuous service) Locking electromagnet on operating mechanism (YL1) (inrush/continuous service) Auxiliary contacts (c.b. fixed and withdrawable version) set of 10 aux.cont. (5 NO + 5 NC) Maximum number of free aux. contact (depending on the accessories) set of 15 aux.cont. (8 NO + 7 NC) Maximum number of free aux. contact (depending on the accessories) Auxiliary contacts characteristics 22.3.1 Rated voltage 22.3.2 Rated current 22.3.3 Breaking capacity (AC) 22.3.4 Breaking capacity (DC) 22.3.5 Insulating level 50Hz/1min Signalling contacts characteristics Rated voltage Rated current Breaking capacity (AC) Breaking capacity (AC) Breaking capacity (AC) Breaking capacity (DC) Breaking capacity (DC)

V V V Yes/No VA, W V % % VA, W V % % VA, W VA, W VA, W n

24-30-48-60-110-125-220 24-48-60-110-127-220-230-240 110-127-220-230-240 Yes, mechanical 1500 / 400 See point 15 85%Vn 110%Vn 250 / 5 See point 15 70%Vn for DC , 85%Vn for AC 110%Vn 125 250 / 5 250 / 5 10 or 15

3 NO + 4 NC

4 NO + 6 NC

V A A A V V A A A A A A

400 AC (50-60Hz) - 220 DC 10 15 A - 400 V - cosf 0.4 1.5 A - 220 V - T 10 ms 2000 400 AC (50-60Hz) - 220 DC 5 4 A - 110 V - cosf 0.3 3 A - 230 V - cosf 0.3 1.5 A - 400 V - cosf 0.3 0.25 A - 110 V - T 10 ms 0.13 A - 220 V - T 10 ms

rev. 29-jan-2002

Page 5 of 8

HD4 12-17.5kV up to 31.5 kA

23.8 24 24.1 24.2 24.3 24.4 24.5 24.6 24.7

Insulating level 50Hz/1min Routine tests on the assembly line on each pole and complete CB Leakage test Millivolt drop measurement Mechanical operations O/C speeds, time spread between poles (max 2msec) Strokes Insulating level test Auxiliary contacts insulating test

2000

Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No

Yes Yes Yes Yes Yes Yes Yes

This Data-Sheet refers to the standard version: for particular applications, requirements, performances ask to ABB T&D S.p.A. Unit Operativa SACE T.M.S.

rev. 29-jan-2002

Page 6 of 8

HD4 12-17.5kV up to 31.5 kA

Here below is shown in a bilogarithmic scale the graph of permissible number of switching fixed version HD4 12-17.5 kV 630-1250-1600 A 16-25-31.5 kA withdrawable version HD4/C HD4/P 12-17.5 kV 12-17.5 kV 630-1250 A 630-1250 A 16-25-31.5 kA 16-25-31.5 kA

HD4/W 12-17.5 kV 630-1250 A 16-25-31.5 kA

Permissible number of switching operations in relation to breaking current


100,000

10,000

Number of operation

1,000

100

10

1 0.1 1.0 10.0 16


25 31.5

100.0

Breaking current [kA]

rev. 29-jan-2002

Page 7 of 8

ANNEX 1
Standard values of transient recovery voltage (font IEC 62271-100)
Rated voltage Ur [kV] T100 T60 T30 T10 T100 T60 T30 T10 OP1-OP2 First-poleAmplitude TRV peak to-clear factor value factor Kpp [p.p.] 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 Kaf [p.p.] 1.4 1.5 1.5 1.5 1.4 1.5 1.5 1.5 1.25 1.25 Uc [kV] 20.6 22 22 22 30 32 32 32 30.6 45 Time delay td [s] 9 4 2 2 11 5 2 2 18 22

Time t3 [s] 61 26 13 13 71 31 15 15 118 145

Voltage u' [kV] 6.9 7.3 7.3 7.3 10 11 11 11 10 15

Time t' [s] 29 13 6 6 35 16 7 7 56 70

RRRV Uc/t3 [kV/s] 0.34 0.85 1.70 1.70 0.42 1.04 2.14 2.14 0.26 0.31

Type of test

Test duty

12

Terminal fault

17.5

Terminal fault

12 17.5

Out-of-phase

rev. 29-jan-2002 Page 8 of 8