HCMC PC CABLE I.

SCOPE :

SPECIFICATION

TERMINATION FOR 22KV SINGLE PHASE XLPE (EPR) INSULATED

This specification should be applicable to termination with accessories used for 22KV- single phase XLPE(EPR) insulated cable. II. STANDARDS OF MANUFACTURE AND TEST : - VDE 0278 : Power cable accessories with rated voltage up to 30 KV. - ASTM D2303 : Inclined plane non-tracking test method. III. DESCRIPTION : 1. Type : cold or heat shrink type used for terminate 22KV underground single cable, outdoor. 2. Technical characteristics of terminated cable : - Basic construction of cable : Single core concentric compact stranded copper, extruded semi-conducting EPR or XLPE compound conductor screen, EPR or XLPE insulation, extruded semi-conducting EPR or XLPE compound insulation screen, copper shield tape, binder tape and PE oversheath. - Voltage rating : 22 KV phase to phase - Core size : 500 mm2 - Thickness of cable insulation : 6.6 mm 3. Technical requirement : - AC withstand voltage : + 1 minute/dry : 55 KV. + 4 hours/dry : 48 KV - Partial discharge: + at 15KV + at 24KV : maximum 3pc : maximum 20pc

- Impulse voltage withstand : + 10 positive impulses : 150 KV + 10 negative impulses : 150 KV

- Load cycling : + Cycles : 5 hours heating , 3 hours cooling . + Conductor temperature : 90C + Test : 63 cycle at 30 KV + Partial discharge:
/var/www/apps/conversion/tmp/scratch_6/137135228.doc 1/5

HCMC PC CABLE . at 15KV : maximum 3pc . at 24KV : maximum 20pc + Impulse voltage withstand : . 10 positive impulses : 150 KV . 10 negative impulses : 150 KV - DC Voltage withstand : 30 minutes : 96 KV - Humidity and condensation : + Insaturated air at 15KV : 100 hours + Water conductivity : 80 mS/m

SPECIFICATION

TERMINATION FOR 22KV SINGLE PHASE XLPE (EPR) INSULATED

- Non Tracking performance of outer insulation material : Minimum 400 minutes, no tracking , erosion through material or flame failure , under following inclined plane test conditions per ASTM D2303. - The termination shall be suitable for using in wet locations. 4. Accessories : 1 copper crimp lugs with two or four holes palm for copper conductor of 500 mm2 . IV. TESTING REQUIREMENTS : 1. Type testing items : AC voltage withstand test. DC voltage withstand test. Lightning impulse voltage withstand test. Cyclic current loading Continuous AC voltage test with cyclic current loading Corona discharge test on accessories Non tracking test.

2. Requirements : In order to ensure the quality of supplied goods , in case of bid winning , the Tenderer shall supply routine test and copies of type test reports met the following requirements : a. Routine test shall be performed for each equipment. b. Type test report shall be approved by an lawful, reputable, independent testing laboratory with the following content :

/var/www/apps/conversion/tmp/scratch_6/137135228.doc

2/5

HCMC PC CABLE

SPECIFICATION

TERMINATION FOR 22KV SINGLE PHASE XLPE (EPR) INSULATED

- Testing sample : the same as the supplied item (manufacturer, country of origin, manufactures code as specified in tender document). - Testing items : Including at least testing items as specified in Section IV.1 of this specification. - Testing values shall be corresponding values as stated in Section III of this specification. If in section III, there are no corresponding values, testing values will be selected according to the standard specified in section II of this specification. V. REQUIREMENT OF TENDER TECHNICAL DOCUMENTS : Detailed summary of deviations to inquiry specification. Completed inquiry data sheet expressed at section VI of this specification. Catalogues containing outline dimensions, electrical data and installation details. Certificate of quality management. Dimension drawings of cable drum. The proposal bidding has Type Test Report which meets the requirements as specified in item IV 2.b will be preferable .

VI. DATA SHEET : N 1. 2. 3. 4. 5. 6. 7. 8. SPECIFICATION Item No. Manufacturer Country Manufacturers code Standards of factory and test Standards of quality management Member approve of certificate of management In case of bid winning , the UNIT REQUIREMENT TENDER

VDE 0278 & ASTM D2303

Yes
3/5

/var/www/apps/conversion/tmp/scratch_6/137135228.doc

HCMC PC CABLE Tenderer shall supply routine test and copies of type test report met the requirements of section IV . 1. Type

SPECIFICATION

TERMINATION FOR 22KV SINGLE PHASE XLPE (EPR) INSULATED

9.

cold or heat shrink type used for terminate 22KV underground single cable, outdoor Single core concentric compact stranded copper, extruded semiconducting EPR or XLPE compound conductor screen, EPR or XLPE insulation, extruded semi-conducting EPR or XLPE compound insulation screen, copper shield tape, binder tape and PE oversheath. 22 KV phase to phase 500 mm2 6.6 mm

2. Technical characteristics of terminated cable : 10. - Basic construction of cable

11. Voltage rating 12. Core size 13. Thickness of cable insulation 3. Technical requirement : 14. - AC withstand voltage : + 1 minute/dry + 4 hours/dry 15. Partial discharge: + at 15KV + at 24KV 16. Impulse voltage withstand : + 10 positive impulses : + 10 negative impulses : 17. - Load cycling : + Cycles
/var/www/apps/conversion/tmp/scratch_6/137135228.doc

55 KV. 48 KV maximum 3pc maximum 20pc 150 KV 150 KV

5 hours heating , 3 hours cooling .


4/5

HCMC PC CABLE + Conductor temperature C + Test + Partial discharge: . at 15KV . at 24KV + Impulse voltage withstand KV . 10 positive impulses KV . 10 negative impulses 18. DC Voltage withstand for 30 KV minutes 19. Humidity and condensation : Hour + Insaturated air at 15KV s + Water conductivity mS/ m 20. Non Tracking performance of outer insulation material

SPECIFICATION

TERMINATION FOR 22KV SINGLE PHASE XLPE (EPR) INSULATED

90 63 cycle at 30 KV maximum 3pc maximum 20pc 150 150 96 100 80 Minimum 400 minutes, no tracking , erosion through material or flame failure , under following inclined plane test conditions per ASTM D2303 Yes 1 copper crimp lugs with two or four holes palm for copper conductor of 500 mm2

21. -The termination shall be suitable for using in wet locations. 22. 4. Accessories