ComAp, spol s.r.

o Kundratka 2359/17 180 00, Praha 8 Czech Republic

InteliNano NT AMF
Typical wiring diagram
LOAD GCB DIESEL / GASOLINE ENGINE GENERATOR MCB

Fast User Guide

Dimensions
Case dimensions: 118mm x108mm x 40mm Panel Cutout: 96mm x 96mm
L1

ECU

L2 L3 N

GENERATOR VOLTAGE MEASUREMENT T16 = Neutral T17 = Phase 1 T18 = Phase 2 T19 = Phase 3

MAINS VOLTAGE MEASUREMENT T20 = Neutral T21 = Phase 1 T22 = Phase 2 T23 = Phase 3

Fuel Solenoid Fuel Level Analog Coolant Temperature Analog Oil Pressure Analog

CAN INTERFACE
L COM H

Battery

+
Sarter

USB interface
CAN L COM H

D+

POWER SUPPLY, D+ T01 = BATT T02 = D+ T03 = BATT +

USB COM Remote Start And Load Emergency Stop Starter Fuel Solenoid MCB GCB Alarm Ready To Load Battery D+ Battery +
PC

INTPUT TERMINALS T10 = COM for analog inputs T11 = binary input T12 = binary input T13 = binary/analog input Low Fuel Level T14 = binary/analog input Coolan Temperature T15 = binary/analog input Oil Pressure

OUTPUT TERMINALS T04 = binary output Starter (6A) T05 = binary output - Fuel Solenoid (6A) T06 = binary output (500 mA) T07 = binary input/output (500 mA) T08 = binary output (500 mA) T09 = binary output (500 mA)

WARNING! If D+ is not used, connect this terminal to battery positive!

Accessing the setup mode


Ensure the engine is stopped and the controller is in Manual mode (green LED above button Auto is turned off). If you have not configured the custom initialization (init) screen then press and hold Stop button, then briefly press button and then Auto button. Then press to switch LCD to default init screen, and then press Auto . To move up and down in the setup menu use and buttons. Press Start button to select or Stop button for exit. Basic settings Engine parameters and protections Generator protections AMF(Auto Mains Failure) settings Output settings Input settings ECU setting Info

If you have already created your own init screen then press and hold Stop button and then briefly press , the custom init screen will appear, keep holding the Stop

Outputs and inputs


Output code O00 O01 O02 O03 O04 O05 O06 O07 O08 O09 O10 O11 Output source Not Used Starter Fuel Solenoid Stop Solenoid Alarm GCB Close/Open MCB Close/Open Ready To Load Prestart ECU Power Relay Choke Glow Plugs Normally Open Contact output Normally Closed Contact output User curves I23 VDO 5 Bar VDO 10 Bar Datcon 5 Bar Datcon 7 Bar Datcon 10 Bar Not selected Not selected Not selected 1 Type binary binary binary binary binary binary binary binary binary binary binary binary Terminal assignment T04, T05, T06, T07, T08, T09 T04 T04, T05, T06, T07, T08, T09 T04, T05, T06, T07, T08, T09 T04, T05, T06, T07, T08, T09 T04, T05, T06, T07, T08, T09 T04, T05, T06, T07, T08, T09 T04, T05, T06, T07, T08, T09 T04, T05, T06, T07, T08, T09 T04, T05, T06, T07, T08, T09 T04, T05, T06, T07, T08, T09 T04, T05, T06, T07, T08, T09 Input code I00 I01 I02 I03 I04 I05 I06 I07 I10 I11 I12 I13 I14 I15 I20 I21 I22 I23 I24 I25 Input source Not Used Emergency Stop Remote Start/Stop Remote Start And Load Access Lock AMF Blocked MCB Feedback GCB Feedback External Warning 1 External Warning 2 External Warning 3 External Shutdown 1 External Shutdown 2 External Shutdown 3 Low Fuel Level Fuel Level Analog Low Oil Pressure Oil Pressure Analog High Coolant Temperature Coolant Temperature Analog Type binary binary binary binary binary binary binary binary binary binary binary binary binary binary binary analog binary analog binary analog Terminal assignment T07, T11, T12, T13, T14, T15 T07, T11, T12, T13, T14, T15 T11 T11 T07, T11, T12, T13, T14, T15 T07, T11, T12, T13, T14, T15 T07, T11, T12, T13, T14, T15 T07, T11, T12, T13, T14, T15 T07, T11, T12, T13, T14, T15 T07, T11, T12, T13, T14, T15 T07, T11, T12, T13, T14, T15 T07, T11, T12, T13,T14, T15 T07, T11, T12, T13, T14, T15 T07, T11, T12, T13, T14, T15 T07, T11, T12, T13, T14, T15 T13, T14, T15 T07, T11, T12, T13, T14, T15 T13, T14, T15 T07, T11, T12, T13, T14, T15 T13, T14, T15

Normally Open Contact - input button Normally Closed Contact input button

I21 VDO Level % Datcon Level %

I25 VDO 40-120 C VDO 50-150 C Datcon High C Datcon Low C

InteliNano-NT AMF, SW version 1.2, ComAp June 2012 IN-NT-AMF-1.2-Fast User Guid.pdf

ComAp, spol s.r.o Kundratka 2359/17 180 00, Praha 8 Czech Republic

Setpoints
Use and buttons to move or change value. Start button to select setpoint or confirm changes and Stop button to go back. Basic settings Setpoint Setpoint name code B01 Nominal Voltage Ph-N B02 Nominal Voltage Ph-Ph B03 Nominal Frequency B04 B05 B06 B07 B08 Connection Type Units Format AMF Function Zero Power Mode Delay Light Tower Mode Generator protections Setpoint code G01 G02 G03 G04 Setpoint name Generator Overvoltage Shutdown Generator Undervoltage Shutdown Generator Overfrequency Shutdown Generator Underfrequency Shutdown G02 200 % 0 - G01 % G04 130 % 0 G03 % Setpoint code A01 A02 A03 A04 A05 A06 Setpoint code E01 E02 E03 E04 E05 E06 E07 E08 E09 E10 Engine parameters and protections Setpoint name Prestart Time Maximum Cranking Time Cooling Time Oil Pressure Shutdown Coolant Temperature Shutdown Battery Undervoltage Warning Maintenance Oil Pressure Starter Disengagement Choke Time Minimal Stabilization Time AMF(Auto Mains Failure) settings Setpoint name Emergency Start Delay Mains Return Delay Mains Overvoltage Mains Undervoltage Mains Overfrequency Mains Underfrequency 0 600 s 1 3600 s A04 150 % 50 A03 A06 150 % 50 A05 % 0-600 s 0-60 s 0-3600 s 0-10 Bar 0 -150 C 8 40 V 0 10000 h Disable (1), Enable (2) 0 3600 s 1 300 s

80 480 V 80 600 V 50 Hz (1), 60 Hz (2) Mono Phase (1), SplitPhase (2), 3Ph3Wire (3), 3Ph4Wire (4), Autodetect (5) Metric unit format (1), US unit format (2) Disable (1), Enable (2) 0-360 min Disable (1), Enable (2)

To apply all changes return to the main setup menu and restart the controller by pressing the Stop button.

Alarms and Events


Events Mains Return Mains Fail Manual Start Remote Start AMF Start Manual Stop Remote Stop AMF Stop Auto On Auto Off Power On Island Operation Warnings Warning Maintenance Low Battery Low Fuel Level External Warning 1 External Warning 2 External Warning 3 ECU Communication Error MCB Fail Mains CCW Rotation Shutdowns Emergency Stop Overspeed Underspeed Low Oil Pressure High Coolant temperature External Shutdown 1 External Shutdown 2 External Shutdown 3 GCB Fail Generator Overvoltage Generator Undervoltage Generator Overfrequency Generator Underfrequency Generator CCW Rotation Start Fail Stop Fail Battery Flat Voltage Autodetect

ECU
For ECU configuration use PC software NanoEdit. For more details see InteliNano AMF Reference Guide.

Technical data
Power supply range Power supply drop-out immunity Power consumption Zero Power Mode consumption 6-36 VDC 100 ms 35 295 mA 52 - 344 A Operating temperature Operating humidity Protection degree (front panel) Storage temperature Binary outputs (up to 6) Low current outputs (4) High current output (2) Total output current Analog inputs (up to 3) Galvanic insulation Electrical range Resolution Precision Binary inputs (up to 6) Input resistance Closed contact voltage Open contact voltage Generator/Mains measurements Measurement input Measurement type Voltage range Max. measured voltage Voltage accuracy Frequency range Frequency accuracy -20... 70 C 95 % non-condensing (IEC/EN 60068-2-30) IP65 with GASKET 4x405 only IP50 without gasket -30... 80 C 1,5 k <2 V >3,5 V

500 mA 6 A (long term) / 10 A (short term) 10 A (long term) / 16 A (short term)

Not insulated 0 - 2500 k 0,1 2%3

Charging alternator preexcitation circuit Excitation current 100 mA Charging fail threshold 80 % InteliNano-NT AMF, SW version 1.2, ComAp June 2012 IN-NT-AMF-1.2-Fast User Guid.pdf

3ph generator voltage, 3ph mains voltage True RMS 480 V Ph-Ph (277 V Ph-N) 340 V Ph-N 1% 40 70 Hz 1%