Escolar Documentos
Profissional Documentos
Cultura Documentos
VersionV1.00
Doc. Code: 0SF.492.050(E)
Issued Date2010.12
Copyright owner: Beijing Sifang Automation Co., Ltd
Note: the company keeps the right to perfect the instruction. If equipments do not agree with
the instruction at anywhere, please contact our company in time. We will provide you with
corresponding service.
is registered trademark of Beijing Sifang Automation Co., Ltd.
We reserve all rights to this document, even in the event that a patent is issued and a different
commercial proprietary right is registered. Improper use, in particular reproduction and
dissemination to third parties, is not permitted.
This document has been carefully checked. If the user nevertheless detects any errors, he is
asked to notify us as soon as possible.
The data contained in this manual is intended solely for the IED description and is not to be
deemed to be a statement of guaranteed properties. In the interests of our customers, we
constantly seek to ensure that our products are developed to the latest technological standards
as a result; it is possible that there may be some differences between the hardware/software
product and this information product.
Manufacturer:
Beijing Sifang Automation Co., Ltd.
Overview
CSC-101 is selective, reliable and high
speed comprehensive transmission line
protection IED (Intelligent Electronic
Device) for overhead lines, cables or
combination of them. It is a proper
solution for following applications:
Overhead lines and cables up to
1000kV voltage level
All type of station arrangement, such
as 1.5 breakers arrangement, double
bus arrangement, etc.
Extremely long lines
Short lines
Heavily loaded lines
Satisfy the requirement for single and
/or three pole tripping
Communication with station automation
system
The IED provides a highly sensitive and
reliable distance protection with
innovative and proven quadrilateral
characteristic. In addition to separated
zone extension functionality, five
distance zones have fully independent
measuring and setting values which
gives high flexibility for all types of lines
and fault resistances. Many other
functions are integrated to provide a
complete backup protection library.
The wide application flexibility makes the
IED an excellent choice for both new
installations and retrofitting of the
existing stations.
Features
Protection and monitoring IED with
extensive functional library, user
configuration possibility and
expandable hardware design to meet
with users special requirements
Redundant A/D sampling channels and
interlocked dual CPU modules
guarantee the high security and
reliability of the IED
Single and/or three tripping/reclosing
Highly sensitive startup elements,
which enhance the IED sensitivity in all
disturbance conditions and avoid
maloperation
Current sudden-change startup
element
Zero sequence current startup
element
Over current startup element
Undervoltage startup element for
weak-infeed end of line
Three kinds of faulty phase selectors
are combined to guarantee the
correction of phase selection:
Current sudden-change phase
selector
Zero sequence and negative
sequence phase selector
Undervoltage phase selector
Four kinds of directional elements
cooperate each other so as to
determine the fault direction correctly
and promptly:
Memory voltage directional
element
Zero sequence component
directional element
Negative sequence component
directional element
Impedance directional element
Full scheme phase-to-phase and
phase-to-earth distance protection with
five quadrilateral protection zones and
additional extension zone characteristic
(21, 21N)
Power swing function (68)
Proven and reliable principle of
power swing logic
Unblock elements during power
swing
All useful types of tele-protection
communication scheme (85)
Permissive Underreach Transfer
Trip (PUTT) scheme
Permissive Overreach Transfer
Trip (POTT) scheme
Blocking scheme
Inter-tripping scheme
Phase segregated tele-protection
communication scheme
Particular logic for tele-protection
communication scheme
Current reversal
Weak-infeed end
Functions
Protection functions
Description ANSI Code
IEC 61850
Logical Node
Name
IEC 60617
graphical symbol
Distance protection
Distance protection 21, 21N PDIS Z<
Power-swing function 68 RPSB Zpsb
Tele-protection
Communication scheme for distance
protection
8521,21N PSCH
Communication scheme for earth fault
protection
8567N PSCH
Current protection
Overcurrent protection 50,51,67 PTOC
3I
INV
>
3I >>
3I >>>
Earth fault protection 50N, 51N, 67N PEFM
I
0INV
>
I
0
>>
I
0
>>>
Emergency/backup overcurrent protection 50,51 PTOC
3I
INV
>
3I >
Emergency/backup earth fault protection 50N,51N PTOC
I
0INV
>
I
0
>
Switch-onto-fault protection 50HS PSOF
3I >HS
I
0
>HS
Overload protection 50OL PTOC 3I >OL
Voltage protection
Overvoltage protection 59 PTOV
3U>
3U>>
Undervoltage protection 27 PTUV
3U<
3U<<
Breaker protection and control function
Breaker failure protection 50BF RBRF
3I> BF
I
0
>BF
I
2
>BF
Dead zone protection 50SH-Z
STUB protection 50STUB PTOC 3I>STUB
Poles discordance protection 50PD RPLD
3I< PD
I
0
>PD
I
2
>PD
Synchro-check and energizing check 25 RSYN
Auto-recloser 79 RREC OI
Single- and/or three-pole tripping 94-1/3 PTRC
Secondary system supervision
CT secondary circuit supervision
VT secondary circuit supervision 97FF
Monitoring functions
Description
Redundant A/D sampling data self-check
Phase-sequence of voltage and current supervision
3I0 polarity supervision
The third harmonic of voltage supervision
Synchro-check reference voltage supervision
Auxiliary contacts of circuit breaker supervision
Broken conductor check
Self-supervision
Logicality of setting self-check
Fault locator
Fault recorder
Station communication
Description
Front communication port
Function arrangement
Figure 1 Function arrangement
Protection functions
Startup elements
The startup elements basically work as
sensitive detector to all type of faults. As
soon as fault or disturbance happens,
the highly sensitive startup elements will
operate immediately and initiate all
necessary protection functions for
selective clearance of the fault.
The control circuit of tripping relays is
controlled by the startup elements. Only
when one of the startup elements is
triggered, the tripping relays can be
energized to trip. Thus, the maloperation,
due to fatal internal hardware fault, is
avoided in this way.
Based on different principle, there are
four kinds of startup elements listed
below, which are used to enhance the
sensitivity, and to guarantee the security
in case of IEDs internal hardware faults.
Sudden-change current
startup element
Sudden-change phase to phase or zero
sequence current elements are the main
startup element that can sensitively
detect most of faults. The criteria are as
follows:
AI
qq
> I_Abrupt
or
A3I
> I_Abrupt
where:
i=|| i (K) - i (K-T) | - |i (K-T) - i
(K-2T) ||
: AB,BC or CA, e.g. iAB= iA-iB
K: The present sample
T: The sample quantity of one power cycle
3i
0
: Sudden-change zero sequence
current
I_Abrupt: The setting value of current
sudden-change elements
Zero sequence current startup
element
Zero sequence current startup element is
applied to improve the fault detection
sensitivity at the high resistance earth
faults. As an auxiliary startup element, it
operates with a short time delay.
Overcurrent startup element
If overcurrent protection function is
enabled, over current startup element is
used to improve the fault detection
sensitivity. As an auxiliary startup
element, it operates with short time
delay.
Low-voltage startup element
When one end of the protected line is a
weak-source system, and the fault
sudden-change phase to phase current
is too low to startup the IED, low-voltage
startup element can be in service to
startup the tele-protection
communication scheme with weak-echo
logic.
10
Phase selector
The IED applies different phase
selectors to determine the faulty phase to
make tripping or auto-recloser initiation
correctly. There are three kinds of phase
selectors based on different principle for
different fault stages.
Sudden-change current
phase selector
It operates as soon as the
sudden-change current startup element
starts up. It makes a phase selection for
fast tripping by comparison amongst
changes of phase-phase currents, i
AB
,
i
BC
and i
CA
.
Symmetrical component
phase selector
During the whole period of fault, the
phase selector checks the angle
between negative sequence current and
zero sequence current vectors to
determine faulty phases. In addition,
phase to phase faults will be
discriminated through impedance
characteristic.
Low voltage phase selector
Both current sudden-change phase and
symmetric component phase selector
are not applicable for weak-infeed end of
protected line, so low-voltage phase
selector is employed in this condition
without VT failure. Theoretically, when
one, two or three phase voltages reduce,
the relevant phase(s) is selected as
faulty phase.
Directional elements
Four kinds of directional elements are
employed for reliable determination of
various faults direction. The related
protection modules, such as distance
protection, tele-protection schemes and
overcurrent and earth fault protections,
utilize the output of the directional
elements as one of their operating
condition. All the following directional
elements cooperate with the mentioned
protection functions.
Memory voltage directional
element
The IED uses the memory voltage and
fault current to determine the direction of
the fault. Therefore transient voltage of
short circuit conditions doesnt influence
the direction detection. Additionally, it
improves the direction detection
sensitivity for symmetrical or
asymmetrical close-in faults with
extremely low voltage. But it should be
noted that the memory voltage cannot be
effective for a long time. Therefore, the
following directional elements work as
supplement to detect direction correctly.
Zero sequence component
directional element
Zero-sequence directional element has
efficient features in the solidly grounded
system. The directional characteristic
only relates to zero sequence impedance
angle of the zero sequence network of
power system, regardless of the quantity
11
0_Char
: The settable characteristic angle
Negative sequence
component directional
element
Negative sequence directional element
can make an accurate directional
discrimination in any asymmetric fault.
The directional characteristic only relates
to negative sequence impedance angle
of the negative sequence network of
power system, regardless the quantity of
load current and/or fault resistance
throughout the fault. The characteristic of
the negative sequence directional
element is illustrated in Figure 3.
Figure 3 Direction detection characteristic of
negative sequence directional element
where:
2_Char
: The settable characteristic angle
Impedance directional
elements
The characteristic of the impedance
directional element (shown in Figure 4) is
same with that of distance protection.
Figure 4 Direction detection characteristic of
impedance directional element
where:
R
SET
: The resistance setting of relevant
12
13
14
function
Under either auto reclosing or manual
closing process, the protection function
is able to discriminate these conditions to
give an instantaneous tripping once the
circuit breaker is closed on permanent
faulty line.
Power swing function (68)
The IED provides a high reliable power
swing detector which discriminates
between fault and power swing with
different algorithm.
Power swing blocking logic
According to the slow behavior of power
swing phenomenon, once one of the two
following conditions is met, the protection
program will switch to power swing logic
process:
Without operation of sudden-change
current startup element, all
phase-to-phase impedances, Z
AB
,
Z
BC
and Z
CA
enter into the largest
zone of distance protection
Without operation of sudden-change
current startup element, all phase
currents are bigger than the power
swing current setting
In addition, according to the
experimental results of power swing, it is
not possible for impedance vector to
come into protected zones in 150 ms
after triggering of the current
sudden-change startup element. After
150 ms, the protection program will be
switched to power swing logic process if
no tripping is issued.
Therefore, according to the above
condition, the IED program enters the
power swing logic process and the
distance protection is blocked until
removing of the mentioned conditions or
until a fault occurrence in the protected
line.
Power swing unblocking
logic
The unblocking logic provides possibility
for selective tripping of faults on
transmission lines during system
oscillations, when the distance protection
function is normally blocked. In order to
unblock distance protection and
therefore, fast clearing of the faults, the
following elements are in service to
discriminate between an internal fault
and power swing conditions.
Asymmetric faults detection element
The zero and negative sequence
current are always the key features of
the asymmetric fault. By comparison
amongst the positive, negative and
zero sequence component of phase
current, the element distinguishes the
asymmetric fault from power swing.
Three phase fault detection element
Based on the experimental results
and practical proof, the change rate
of measuring resistance and the
change vector of measuring
impedance are combined to detect
the three phase fault during the
power swing.
15
16
17
Forward
Ph_Char
Bisector
Figure 9 Direction detection characteristic of
overcurrent protection directional element
where:
Ph_Char
: The settable characteristic angle
The assignment of the applied measuring
values used in direction determination has
been shown in Table 1 for different types of
faults.
Table 1 Assignment of applied current and
reference voltage for directional element
Phase Current Voltage
A
a
I
bc
U
B
b
I
ca
U
C
c
I
ab
U
For three-phase short-circuit fault,
without any healthy phase, memory
voltage values are used to determine
direction clearly if the measured voltage
values are not sufficient. The detected
direction is based on the memory voltage
of previous power cycles.
Earth fault protection (50N, 51N, 67N)
The earth fault protection can be used to
clear phase to earth faults as system
back-up protection.
The protection provides following
features:
Two definite time stages
One inverse time stage
11 kinds of the IEC and ANSI inverse
time characteristic curves as well as
optional user defined characteristic
Zero sequence directional element
Negative sequence directional element
is applied as a complement to zero
sequence directional element. It can be
enabled/disabled by setting
Each stage can be set individually as
directional/non-directional
Settable directional element
characteristic angle, to satisfy the
different network conditions and
applications
Each stage can be set individually for
inrush restraint
Settable maximum inrush current
VT secondary circuit supervision for
directional protection function. Once
VT failure happens, the directional
stage can be set to be blocked
CT secondary circuit supervision for
earth fault protection. Once CT failure
happens, all stages will be blocked
Zero-sequence current is measured
from earth phase CT
Directional element
18
0_Char
: The settable characteristic angle
For earth fault protection, users can
choose negative sequence directional
element as the complement of zero
sequence directional element. It can be
used in case of too low zero sequence
voltage due to some fault condition e.g.
the unfavorable zero-sequence voltage.
The negative sequence directional
element characteristic is shown in Figure
11.
Figure 11 Direction detection characteristic of
negative sequence directional element
where:
2_Char
: The settable characteristic angle
Furthermore, under the VT failure
situation, it can be set to block directional
earth fault protection.
Inrush restraint function
The protection relay may detect large
magnetizing inrush currents during
transformer energizing. In addition to
considerable unbalance fundamental
current, Inrush current comprises large
second harmonic current which doesnt
appear in short circuit current. Therefore,
the inrush current may affect the protection
functions which operate based on the
fundamental component of the measured
current. Accordingly, inrush restraint logic
is provided to prevent earth fault protection
from mis-tripping.
Since inrush current cannot be more than a
specified value, the inrush restraint
provides an upper current limit in which
blocking does not occur.
19
20
21
22
Figure 12 Tripping logic when applying bus
side CT
When one line side CT is applied, when
a fault occurs in the dead zone,
protection relay sends a transfer trip to
remote end relay to isolate the fault.
Tripping logic is illustrated in Figure 13.
Figure 13 Tripping logic when applying line
side CT
STUB protection (50STUB)
The VT is mostly installed at line side of
transmission lines. Therefore, for the cases
that transmission line is taken out of
service and the line disconnector is
opened, the distance protection will not be
able to operate and must be blocked.
The STUB protection protects the zone
between the CTs and the open
disconnector. The STUB protection is
enabled when the open position of the
disconnector is connected to IED binary
input. The function supports one definite
stage which related concept is shown in
Figure 14.
23
Figure 14 Tripping logic of STUB protection
Poles discordance protection (50PD)
The phase segregated operating circuit
breakers can be in different positions
(close-open) due to electrical or
mechanical failures during the system
normal operation.
The protection operates based on
information from auxiliary contacts of the
circuit breaker with additional criteria.
The protection performs following
features:
3 phase CB Aux contacts supervision
Current criteria checking (including
phase current, zero and negative
sequence current)
Synchro-check and energizing check (25)
The synchro-check function checks the
both side voltages of the circuit breaker
for synchronism conditions.
The synchronization function ensures the
stability of the network in three phase
reclosing condition. To do this, the two
side voltages of the circuit breaker are
compared in terms of magnitude, phase
angle and frequency differences.
Additionally, closing can be done safely
in conditions that at least one side of the
CB has dead voltage.
Available for automatic reclosing
(internally or externally)
Based on voltage/ angle/ frequency
difference
Synchro-check modes:
Synch-check
Energizing check, and synch-check if
energizing check failure
24
Override
Modes of energizing check:
Dead V
4
and dead V
3Ph
Dead V
4
and live V
3Ph
Live V
4
and dead V
3Ph
Synchro-check reference
voltage supervision
If the automatic reclosing is set for
synchronization check or energizing
check, during the automatic reclosing
period, the synchronization condition of
the voltages between both sides of CB
cannot be met, an alarm will be issued
after default time delay.
Auto-recloser (79)
For restoration of the normal service
after a fault an auto reclosing attempt is
mostly made for overhead lines.
Experiences show that about 85% of
faults have transient nature and will
disappear after an auto reclosing attempt
is performed. This means that the line
can be re-energized in a short period.
The reconnection is accomplished after a
dead time via the automatic reclosing
function. If the fault is permanent or short
circuit arc has not been extinguished, the
protection will re-trip the breaker. Main
features of the auto-recloser are as
follows:
4 shots automatic recloser (selectable)
Individually settable dead time for three
phase and single phase fault and for
each shot
Internal/external AR initiation
Single/three phase AR operation
CB status supervision
CB Aux. contact supervision
Cooperation with internal synch-check
function for reclosing command
25
26
Monitoring functions
Phase-sequence of voltage and
current supervision
The phase-sequence of three phase
voltage and current are monitored in the
normal condition to determine that the
secondary circuit of CT or VT is connected
with IED correctly.
3I0 polarity supervision
The IED compare the magnitude and
phase angle of the calculated zero
sequence current with the measured one
to determine that the polarity is connected
in a right way.
The third harmonic of voltage
supervision
If the third harmonic voltage is excessive,
the alarm without blocking protection will
be given with delay time for checking of the
secondary circuit of voltage transformer.
Auxiliary contacts of circuit
breaker supervision
Current flowing through the transmission
line and connected CB aux. contacts are
monitored in phase segregated. Therefore,
the conflict condition is reported as alarm.
For example, If CB aux. contacts indicate
that CB is open in phase A and at the same
time flowing current is measured in this
phase, related alarm is reported.
Broken conductor detection
The main purpose of the broken conductor
detection function is to detect the broken
conductors on protected transmission lines
and cables. Detection can initiate an alarm
or tripping.
Self-supervision
All modules can perform self-
supervision to its key hardware
components and program, as soon as
energizing. Parts of the modules are
self-supervised in real time. All internal
faults or abnormal conditions will
initiate an alarm. The fatal faults among
them will result in the whole IED
blocked
The sampled data from the redundant
A/D sampling channels compare with
each other in real time. If the difference
exceeds the specified threshold, it will
be considered as analog input channel
fault and the protection will be blocked
immediately
CPU module and communication
module perform real time
inter-supervision. Therefore
communication interruption between
them is detected and related alarm will
be given
CRC checks for the setting, program
and configuration, etc.
Fault locator
The built-in fault locator is an impedance
measuring function giving the distance
from the IED measuring location to the
fault position in km. The IED reports fault
location after the IED tripping.
27
Station communication
Overview
The IED is able to connect to one or
more substation level systems or
equipments simultaneously, through the
communication ports with
communication protocols supported.
(Shown in Figure 15)
Front communication port
There is a serial RS232 port on the front
plate of all the IEDs. Through this port,
the IED can be connected to the
personal computer for setting, testing,
and configuration using the dedicated
Sifang software tool.
RS485 communication ports
Up to 2 isolated electrical RS485
communication ports are provided to
connect with substation automation
system. These two ports can work in
parallel for IEC60870-5-103.
Ethernet communication
ports
Up to 3 electrical or optical Ethernet
communication ports are provided to
connect with substation automation system.
These two out of three ports can work in
parallel for protocol, IEC61850 or
IEC60870-5-103.
28
29
Remote communication
Binary signal transfer
The binary signals can be exchanged
through remote communication channels
between the two IEDs on the two end of
the transmission line or cable respectively.
This functionality is mainly used for the line
Tele-protection communication schemes,
e.g., POTT or PUTT schemes, blocking
scheme and inter trip and so on.
Remote communication
channel
The IEDs are able to communicate with
each other in two types:
Directly fiber-optical cable connection
mode at distances up to 100 km (see
Figure 17 and Figure 18)
Through the communication converter
with G.703 or G.703E1 interface
through the public digital
communication network (see Figure 19
and Figure 20)
Because there are up to two selectable
fiber-optical remote communication ports,
the IED can work in the redundant
communication channel mode, with
advantage of no time-delay channel switch
in case of the primary channel broken
(Figure 18, Figure 20 and Figure 21).
Figure 17 Single channel, communication through dedicated fiber optical cable
30
31
32
Software tools
CSmart protection manager is a
user-friendly software tool for engineering,
parameter setting, disturbance handling
and monitoring. It provides versatile
functionalities required throughout the life
cycle of protection IEDs. Its features are as
follows:
Device administration in projects with
freely configurable hierarchies for any
substation and electrical power station
topology
Modification, import and export of
parameter sets sorted by protection
functions, with setting logicality check
Precise fault analysis by Fisewave
software: visualization of fault records
in curves over time, circle diagrams,
vector diagrams, bar charts and data
sheet
Intelligent plausibility checks rule out
incorrect input
Graphical visualization of
characteristics and zone diagrams with
direct manipulation of the curves
Password-protected access for
different jobs such as parameter setting,
commissioning and controlling
(authorized staff only)
Testing and diagnostic functions
decisive support in the commissioning
phase
33
Hardware
Human-machine Interface
(HMI)
The human-machine interface is simple
and easy to understand the whole front
plate is divided into zones, each of them
with a well-defined functionality:
Figure 22 IED front plate
1 Liquid crystal display (LCD)
2 LEDs
3 Shortcut function keys
4 Arrow keys
5 Reset key
6 Quit key
7 Set key
8 RS232 communication port
34
35
36
Typical connection
A. For one breaker of single or double busbar arrangement
Figure 25 Typical connection diagram for one breaker of single or double busbar arrangement
37
38
39
Rear terminals
The rear view of the protection IED
Figure 28 Rear view of the protection IED
40
41
42
43
44
45
46
47
48
49
Technical data
Basic data
Frequency
Item Data
System rated frequency 50 Hz or 60Hz
Internal current transformer
Item Data
Rated current I
r
1 or 5 A
Nominal current range (0.2 40)x I
r
Power consumption (per phase)
at I
r
= 1 A 0.5 VA
at I
r
= 5 A 1 VA
Thermal overload capability
at I
r
= 1 A 100 x I
r
for 1 s
30 x I
r
for 10 s
3 x I
r
continuous
at I
r
= 5 A 40 x I
r
for 1 s
30 x I
r
for 10 s
3 x I
r
continuous
Internal voltage transformer
Item Data
Rated voltage V
r
(ph-ph) 100 V /110 V
Nominal range (ph-e) 0.4 V to 120 V
Power consumption
at V
r
= 110 V 0.5 VA per phase
Thermal overload capability in voltage path
(phase-neutral voltage)
2V
r
, for 10s
1.5V
r
, continuous
50
Auxiliary voltage
Item Data
Rated auxiliary voltage V
aux
100~125V DC
195~250V DC
Permissible tolerance %20 U
aux
Power consumption
Normal operation 30 W
Tripping condition 50 W
Binary inputs
Item Data
Input voltage range 24 V DC
110/125 V DC
220/250 V DC
Response time/dropout time Software provides de-bounce time
Power consumption, energized 2mA
Binary outputs
Item Data
Max. system voltage 250V DC/AC
Current carrying capacity 5 A continuous
30 A for 0.5s making current
2000 switching cycles
Making capacity at inductive load with L/R>10 ms 1100 W(DC)
1250 VA(AC)
Breaking capacity 250 mA, 100 W resistive, for AC, cos > 0.4
50W, for DC at L/R < 40 ms
51
Type tests
Insulation test
Item Data
Standards IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Voltage test (100 % test)
All circuits besides auxiliary voltage and
RS485/RS232 and time synchronization
2KV,50Hz,1min
IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Auxiliary voltage 3.5 kV DC
IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Communication ports and time synchronization
terminals
500V,50Hz,1min
IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Impulse voltage test
all circuits, except communication ports and time
synchronization
5kV (U
i
63V) /1kV (U
i
<63V)
IEC 60255-5:2000 class III
GB/T 15145-2001
DL/T 478-2001
Insulation resistance
Insulation resistance >100 M at 500 VDC
IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Electromagnetic compatibility tests
Item Data
Standards GB/T 14598.9-2002
identify IEC 60255-22-3:2000, for radiated
electromagnetic field disturbance test
52
GB/T 14598.10-2007
identify IEC 60255-22-4:2002, for electrical fast
transient/burst immunity test
GB/T 14598.13-2008
Modify from IEC 60255-22-1:2007, for 1MHz
burst immunity test
GB/T 14598.14-1998
identify IEC 60255-22-2:1996, for electrostatic
discharge test
GB/T 14598.17-2005
Identify with IEC 60255-22-6:2002, for
Conducted electromagnetic field disturbance
tests
GB/T 14598.18-2007
Identify with IEC 60255-22-5:2002, for surge
immunity test
GB/T 14598.19-2007
Identify with IEC 60255-22-7:2003, for power
frequency immunity test
GB/T 14598.20-2007
Identify with IEC 60255-26:2004, for
electromagnetic compatibility requirements
High-frequency burst disturbance test 2.5 kV (peak value); 1 MHz
test duration 2 s
IEC 60255-22-1, class III
and VDE 0435 Part 303, class III
Electrostatic discharge 8 kV contact discharge
15 kV air gap discharge
both polarities; 150 pF; R
i
= 330
IEC 60255-22-2; class IV
and EN 61000-4-2; class IV
Radio-frequency electromagnetic field disturbance
non-modulated
10V/m, 80 to 1000 MHz
IEC 60255-22-3, class III
Radio-frequency electromagnetic field disturbance
amplitude-modulated
10 V/m, 80MHz to 2.7GHz
80%AM; 1 kHz
IEC 61000-4-3, class III
Radio-frequency electromagnetic field disturbance
pulse-modulated
10 V/m, 900 MHz; repetition rate 200 Hz, on
duration 50 %
IEC 61000-4-3/ENV 50204, class III
Fast transient disturbance 4KV
53
54
IEC 60068-2-6
Shock Semi-sinusoidal
Acceleration 5 g, duration 11 ms; 6 shocks in both
directions of 3 axes
IEC 60255-21-2, class 1
IEC 60068-2-27
During transportation
Standards IEC 60255-21-2
Vibration Sinusoidal
5 to 8 Hz: 7.5 mm amplitude
8 to 150 Hz; 2 g acceleration
frequency sweep 1 octave/min
20 cycles in 3 perpendicular axes
IEC 60255-21-1, class 2
IEC 60068-2-6
Shock Semi-sinusoidal
Acceleration 15 g, duration 11 ms
6 shocks in both directions of 3 axes
IEC 60255-21-2, Class 1
IEC 60068-2-27
Continuous shock Semi-sinusoidal
Acceleration 10 g, duration 16 ms
2000 shocks in both directions
of 3 axes
IEC 60255-21-2, class 1
IEC 60068-2-29
Environmental tests
Item Data
Temperatures
Type-tested , test Bd, for 16 h -25 C to +70 C
IEC 60068-2-1
IEC 60068-2-2
Recommended permanent operating temperature -10 C to +55C
IEC 60255-6
(Legibility of display may be impaired above
+55 C /+131 F)
Storage and transport temperature limit -25C~+70C
55
Humidity
Permissible humidity 95 % of relative humidity
IED design
Item Data
Case size 4U19inch
Dimensions See outline and installation dimension
drawing
Weight 10kg
Protection level IP20 class I
EN 60529
IEC 60529
CE certificate
Item Data
EMC Directive
EN 61000-6-2 and EN61000-6-4 (EMC Council
Directive 2004/108/EC)
Low voltage directive EN 60255-27 (Low-voltage directive 2006/95 EC)
56
57
58
Remote communication
Fiber optic communication ports
Item Data
Number 1 ~ 2
Fiber optic cable type Single-mode
Optic wavelength 1310nm, when the transmission distance <60km
1550nm, when the transmission distance >60km
Optic received sensitivity -38dBm
Emitter electric level >-8dBm; (the transmission distance <40km)
>-4dBm; (the transmission distance 40~60km)
>-3dBm; (the transmission distance >60km)
Fiber optic connector type FC or SC, when the transmission distance <60km
SC, when the transmission distance >60km
Data transmission rate 64 kbit/s, G703
2,048 kbit/s, G703-E1
Max. transmission distance 100km
59
Functions
NOTE:
Ir: CT rated secondary current, 1A or 5A
In: nominal current of the reference side of transformer
Distance protection (ANSI 21, 21N)
Setting range
Number of settable zone 5 zones
Distance characteristic Polygonal
Resistance setting range 0.01120, step 0.01, when Ir=5A
0.05600, step 0.01, when Ir=1A
Reactance setting range 0.01120, step 0.01, when Ir=5A
0.05600, step 0.01, when Ir=1A
Delay time of distance zones 0.00 ~ 60.00s, step 0.01s
Time
Best Operation time 20ms for zone 1 of distance when fault occurs
within 0.7 time setting value
Operation time 30ms for zone 1 of distance when fault occurs
within 0.7 time setting value
Tolerance
Dynamic overreaching for zone 1 of distance
protection
5%
Tolerance of time 1% or +20 ms for other zones, when setting
time > 60ms
Measuring tolerance of fault locator (not including
errors caused by factors outside product)
+3% when fault current is greater than 0.01 Ir at
metal fault, error will become bigger when fault
occurs with greater path fault resistance
Power-swing logic (ANSI 68)
Setting range
Range of sudden-change current 0.05 A to 20 A , when Ir=1A
0.25 A to 100 A when Ir=5A
Current range of power swing detection 0.05 A to 20 A , when Ir=1A
0.25 A to 100 A when Ir=5A
60
61
62
63
64
65
Delay time 1% or 40 ms
Dead zone protection (ANSI 50SH-Z)
Setting range
Current 0.05 A to 20 A , when Ir=1A
0.25 A to 100 A when Ir=5A
Delay time 0.00s to 32.00s, step 0.01s
Tolerances
Pickup 3% of set value or 0.02Ir
Delay time 1% or +40 ms
Pole discordance protection (ANSI 50PD)
Setting range
Current 0.05 A to 20 A , when Ir=1A
0.25 A to 100 A when Ir=5A
Delay time 0.00s to 60.00s, step 0.01s
Tolerances
Pickup 3% of set value or 0.02Ir
Delay time 1% or +40 ms
STUB protection (ANSI 50STUB)
Setting range
Current 0.05 A to 20 A , when Ir=1A
0.25 A to 100 A when Ir=5A
Delay time 0.00s to 60.00s, step 0.01s
Tolerances
Pickup 3% of set value or 0.02Ir
Delay time 1% or 40 ms
Undervoltage protection (ANSI 27)
Setting range
Voltage connection Phase-to-phase voltages or
phase-to-earth voltages
Pickup thresholds, phase to earth voltage 5 to 75 V , step 1 V
Pickup thresholds, phase to phase voltage 10 to 150 V, step 1 V
66
67
68
69
Ordering
Configuration of the pre-configure versions
Table 11 Functions list of the pre-configure versions
Description Selection
Pre-configure version M1 M2 M3
Application Full function
Double or
single busbar
arrangement
1
1
2
breaker
arrangement
Distance protection (21, 21N)
Power-swing function (68)
Communication scheme for distance protection
(8521,21N)
Communication scheme for earth fault protection
(8567N)
Phase segregated scheme communication logic
Overcurrent protection (50, 51, 67)
Earth fault protection (50N, 51N, 67N)
Emergency/backup overcurrent protection (50, 51)
Emergency/backup earth fault protection (50N, 51N)
Switch-onto-fault protection (50HS)
Overload protection (50OL)
Overvoltage protection (59)
Undervoltage protection (27)
Breaker failure protection (50BF)
Dead zone protection (50SH-Z)
STUB protection (50STUB)
Poles discordance protection (50PD)
Synchro-check and energizing check (25)
Auto-recloser (79)
Single and/or three pole tripping (94)
CT secondary circuit supervision
VT secondary circuit supervision (97FF)
Hardware Quantity
Analogue current input channels 5 5 5
Analogue voltage input channels 4 4 4
70
Binary inputs 30 30 30
Binary output relays for tripping and initiation 32 32 32
Binary output relays for signal 32 32 32
Programmable LEDs 6 6 6
Case, 4U,19 1 1 1
Note:
: Standard function
: Optional function
Ordering code
Product type
No. 1 2 3 4 5 6 7
Code C S
No. Code Description
Pre-configure version
8 M; N
9 0~9
10 0~9
Language
11
C:Chinese
E: English
F: French
R: Russia
S: Spanish
P: Portuguese
Frequency
12
A: 50Hz
B: 60Hz
Rated auxiliary voltage
13
1: 100 ~125V DC
2: 195 ~250V DC
LCD
14 M: Medium size
71
Case
15 A: 4U, 19"
Terminals of Analogue Input Module
16
A: Plug in type
B: Screw type with ring lug
Analogue Input Module (AIM)
17,18 AIM1
EA: Analogue input module EA (5I (1A)+4U)
EB: Analogue input module EB (5I (5A)+4U)
X: Null
19 Quantity
20,21 AIM2
22 Quantity
Binary Input Module (BIM)
23,24 BIM1
AA: Binary input module AA (30BI, 220V )
AB: Binary input module AB (30BI, 110V )
AC: Binary input module AB (30BI, 24V )
X: Null
25 Quantity
26,27 BIM2
28 Quantity
Binary Output Module (BOM)
29 BOM1
A: Binary output module A (16 output relays for tripping)
B: Binary output module B (32 output relays for tripping,
double boards )
C: Binary output module C (16 output relays for signal, 19
contacts )
X: Null
30 Quantity
31 BOM2
32 Quantity
33 BOM3
34 Quantity
35 BOM4
36 Quantity
Communication protocol
72
37
A: IEC61850-8 protocol and IEC60870-5-103 protocol
B: IEC60870-5-103 protocol
Communication ports
38
A: Two optical Ethernet ports and two RS485 ports
B: Two electric Ethernet ports and two RS485 ports
C: Three optical Ethernet ports and one RS485 port
D: Three electric Ethernet ports and one RS485 port
Remote communication ports quantity
39
1: one port
2: two ports
X: Null
Remote communication port type
40
A: One channel, SC type, transmission distance 60~100 km
B: One channel, SC type, transmission distance 40~60km
C: One channel, SC type, transmission distance <40 km or Multiplexed
channel
D: Two channels:
Channel A: SC type, transmission distance 60~100 km
Channel B: SC type, transmission distance 60~100 km
E: Two channels:
Channel A: SC type, transmission distance <40 km or Multiplexed
channel
Channel B: SC type, transmission distance <40 km or Multiplexed
channel
F: Two channels:
Channel A: SC type, transmission distance 40~60 km
Channel B: SC type, transmission distance <40 km or Multiplexed
channel
G: Two channels:
Channel A: SC type, transmission distance 60~100 km
Channel B:SC type, transmission distance <40 km or Multiplexed
channel
X: Null
Time synchronization port
41
A: IRIG-B mode
B: Pulse mode
Example:
The following ordering code means:
73
74