Racksyst accessory Power supply unit monitor ZB 470


Compatible Racksyst-plug-in board for monitoring two NT 470 power supply units

Racksyst plug-in board power supply unit monitoring module ZB 470. The high capacity diodes and the relays for fault signalling can be clearly seen.

Application The reliable operation of a measuring instrument depends upon having a reliable power supply. In Racksyst systems two power supply units can be used together (redundant circuit) to provide the necessary degree of reliability. The power supply monitor ZB 470 is used to interconnect two supplies. It ensures that if the first unit fails, the standby unit is unaffected. It signals if one of the two units has failed.

Endress + Hauser
Nothing beats know-how

Installation

Install outside the hazardous area, preferably in a rack. Ensure that the necessary contact protection is provided, observe the permissable ambient temperature and avoid excessively high atmospheric humidity which can result in condensation forming on the printed circuit board. We recommend the position next to the two Racksyst NT 470 power supply units as the best since in this position the clearance between the warm power units supply and the measuring instruments is increased.

If the rack has an external power supply the ZB 470 can be installed in any position. Racksyst measuring instruments can be mounted adjacent to the power supply unit monitoring module ZB 470 even when they feature an intrinsically safe signal input.

20.30 2.5 7.45

4 HP

160 15

3 HU 128.4

100

Multipoint connector, DIN 41612, Form F (28-pole)

Dimensions of the Racksyst plug-in board power supply unit monitoring ZB 470.

Fault signalling

Power supply unit

Power supply monitior

Transmitter power supply U = 24 V DC 24 V DC 24 V DC Connection diagram for ZB 470 power supply units.

Electrical Connection

The power supply unit monitor ZB 470 features a male multi-point connector in accordance with DIN 41 612, Type F. Refer to figure for pin assignments and wiring of the female multi-point connector in the rack.

Power supply units Rack viewed from the front NT 471 (7 HP) NT 471 (7 HP)

Total space requirement 20 HP

Suggestion for space saving insatllation which also provides optimum heat dissipation

Power supply monitoring module ZB 470 (4 HP)

Clearance for cooling (2 HP)

Viewing the contact blade of the ZB 470 or the connection side of the female multi-point connector in the rack

d10 d14
+ + +

L+ Input 24 V L L+ Input 24 V L L+ Output 24 V, max. 2 A L

Inputs and outputs


b10 b14 z10 z14

Fault signalling power supply unit Fault signalling power supply unit

The corresponding relay de-energizes in the case of failure of a power supply unit.

Pin assignment, ZB 470 Power Supply Unit Monitor.

Technical Data

Mechanical design: Racksyst plug-in board in accordance with DIN 41 4994, Part 2 and Part 4; h = 100 (European standard size pc board) Connector: Male multi-point connector in accordance with DIN 41 612, Part 3, Type F ( 28pole) Front panel: black plastic with blue control panel, with grip and labelling strip Width: 4 horizontal pitch units (20 mm) Protection class to DIN 40 050: Front panel IP 20, Plug in board IP 00 Dimensions: see page 2 Weight: 0.1 kg. Permissible ambient temperature (operation): 0 C+70 C Storage temperature: 20 C+85 C Inputs: 2 connections for 2 power units, or other DC voltage sources 20.6 V...28 V

Outputs: Output voltage: 0.6 V lower than input voltage Output current: max. 2 A Relay for fault signalling: one relay with potential-free change-over contact per supply unit Max. contact load: 250 VDC, 100 VDC, 2.5 A, 300 VA at cos = 0.7, 100 W Function indicators on the front panel: One LED per power supply unit; switches off if power unit fails. Test sockets on front panel: 2 sockets per power supply unit (+) and () for testing the input voltages

Subject to modification

Supplmentary Documentation

Racksyst System-Information SI 008 Racksyst planning information Adhesive labels to plan wiring Power Supply unit NT 470 Technical Information TI 004F

Endress+Hauser GmbH+Co. Instruments International P.O. Box 22 22 D-79574 Weil am Rhein Germany Tel. (0 76 21) 9 75-02 Tx 7 73 926 Fax (0 76 21) 9 753 45 http://www.endress.com