PRESSURE REDUCING VALVE (KVS 701)

DESCRIPTION KVS 701 pressure reducing valve is a kind of intelligent valve that can adjust the pressure in the pipe line. It is widely used in civil feeding system, fire protection and other industrial system. By adjusting the pressure reducing pilot valve, can adjust the outlet pressure of main valve. Epoxy resin coating of whole body. This control valve reduces: Delivery pressure when supplying by gravity from a source with a high elevation. Pressure to a desirable operating value within a given area. Working pressure when the pump discharge is too high. Pressure to an irrigation system.

APPLICATIONS Suitable for water, oil.

SPECIFICATION End connection: Operating pressure: Shell test pressure: Seal Test Pressure: Outlet Pressure Adjustment Range: Temperature rating: Flanges are according to BS 4504 PN16 16 Bar Up to 24 Bar 17.6 Bar 112 Bar 0~80 0C

PRESSURE REDUCING VALVE (KVS 701)


DRAWING

MATERIALS
No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Component Body Shaft O-ring Disc Seal Ring Diaphragm Plate Nut Spring Bonnet Filter Ball Valve Pressure Gause Needle Valve Tube Fitting Lift Lug Pilot Valve Bolt Nut Material Cast Iron 2Gr13 NBR WCB NBR NRB+Nylon WCB Q235 ST Cast Iron Copper Copper Assembly Copper Copper Q235 Copper Q235 Q235

67

PRESSURE REDUCING VALVE (KVS 701)


DIMENSIONS
Size DN 50 65 80 100 125 150 200 250 300 350 400 INCH 2" 2. 1/2" 3" 4" 5" 6" 8" 10 12 14 16 D (mm) 165 185 200 220 250 285 340 405 460 520 580 D1 (mm) 125 145 160 180 210 240 295 355 410 470 525 D2 (mm) 102 122 133 158 184 212 268 320 370 430 480 n-d 4-19 4-19 8-19 8-19 8-19 8-23 12-23 12-28 12-28 16-28 16-31 b (mm) 19 19 19 19 19 19 20 22 24.5 26.5 28 f (mm) 3 3 3 3 3 3 3 3 4 4 4 L (mm) 203 216 240 270 300 335 400 480 500 620 690 H (mm) 278 298 313 350 365 385 505 590 620 650 690

WORKING PRINCIPLE

When downstream pressure is lower than setting pressure, Pilot M opens automatically, the pressure contained in the by-pass circuit doesnt apply any force on the membrane of main valve . Thus the closing system is released and lifted. The valve throttles to open position to increase downstream pressure to The desired level.

When downstream pressure is higher than setting pressure, Pilot M is closed automatically, the pressure contained in the by-pass circuit exerts a force on the membrane of main valve. Thus the closing system drops down and the valve Throttles to closed position to reduce Downstream pressure to the desired Level.

KVS VALVE, INC. 34572 Hoca Hanim v Karaky / Istanbul/TRKIYE Tel: +90.212.259.6687 ; Fax : +90 (252) 316 88 43 (pbx) Website: http://www.kvsvalve.com