Power Fuse

LG Current Limiting Power Fuse


LFL Power Fuse Series (P,G,J,M Type)

CONTENTS

Safety Precautions -------------------------------------------------------

INSTRUCTION MANUAL

Receiving & Unpacking, Service Conditions -----------------------

Moving, Storage and Disposal -----------------------------------------

P Type Current Limiting Power Fuses -----------------------------1.Ratings ------------------------------------------------------------------2.Installation --------------------------------------------------------------3.Change of fuse links ---------------------------------------------------4.Maintenance and Inspection -----------------------------------------

5 5 5 5 5

G Type,J Type Current Limiting Power Fuses ------------------1.Operating indication of fuse links ---------------------------------2.Fitting and change of fuse links ------------------------------------3.Installation -------------------------------------------------------------4.Operations --------------------------------------------------------------5.Maintenance and Inspection -----------------------------------------

6 6 6 6 7 8

Before making any operation, make sure to use this product after reading the article of Safety Precautions in this complete set of instruction. Reserve this manual at visible place where any personnel to operate it can see it easily.

M Type Current Limiting Power Fuses ---------------------------1.Operating indication of fuse links ---------------------------------2.Fitting and change of fuse links ------------------------------------3.Installation -------------------------------------------------------------4.Operations --------------------------------------------------------------5.Maintenance and Inspection ----------------------------------------6.Life expectancy and Replacement --------------------------------- Quality Guarantee -----------------------------------------------------1.Quality Guarantee Certificate ---------------------------------------

9 9 9 9 9 11 11 13 13

LG Industrial Systems
http://www.lgis .com

Current Limiting
Safety Precautions
Please follow this Safety Precautions surely so that any failure to observe these precautions could result in severe personal injury, death or equipment damage. The safety precautions are consist of the following special message may appear throughout this manual to warn of potential hazards and to call attention to additional information which clarifies or simplifies a procedure.

Power Fuse
WARNING
1. Only a qualified electrical workers with training and experience high voltage circuits should perform any operation, maintenance and inspection. may result in malfunction, severe bodily injury or electric shock . 2. Before performing any inspection or maintenance on this device, disconnect all sources of electric power and take every precautions to see that all connections are de-energized and grounded.
may result in severe bodily injury or electric shock.

DANGER

Used where there is a hazard of severe bodily injury or death. Failure to follow a DANGER instruction will result in severe bodily injury or death.

3. When making bolts and screw assembling, follow the instruction with recommended torque values
may result in over heating or burns.

WARNING Used where there is a hazard of severe bodily injury or


death. Failure to follow a WARNING instruction may result in bodily injury or death.

4. After performing installation, maintenance, inspection, remove some foreign objects like tools, test leads or bolts, instruments.
may cause short circuit or burn.

CAUTION

Used where there is a hazard of equipment damage. Failure to follow a CAUTION instruction may result in damage of equipment.

5. When making any inspection, perform this procedure after disconnecting main circuit perfectly by visual or insulated ground stick.
may cause electric shock.

The meaning of following signal on the products and in this inst ruction describes as below ; This signal means to call a persons attention for any operation or subjects which makes a hazard of bodily injury or equipment damage. Read it carefully and follow the instruction at this signal. This signal means to call a persons attention for electric shock under the special environment condition.

6. When the trip mechanism has operated, always replace all three fuses in a three phase or two phase circuit even though only one or two are open circuited
may result in explosion by the possibility of internal elements damage.

CAUTION
1. The fuse must be stored in clean, dry, dust and condensationfree environment.
may cause a weakness of insulation.

DANGER
Do not make any touch to charged parts electrically like conductors, terminals and disconnects etc., under any of energized condition.
Can cause electric shock, severe bodily injury or electrocution.

2. The products must be stored at the place with no corrosive gas.


may cause a damage of product s (discoloration)

3. Do not impact on the products when moving.


may cause a damage of products.

Current Limiting
Receiving & Unpacking, Service Conditions
Receiving & Unpacking
1. Fuse links and fuse holders are packed in corrugated cardboard boxes separately to prevent from any damage during shipment. When using them, do insert fuse links into fuse holders. 2. Before performing any installation make sure to check the ratings again indicated on name plate and cap of fuse links. 3. If damage or breakage of products are founded, immediately notify LGIS sales office or service representatives. 4. If damage or breakage of products by the carrier are founded, immediately file a claim with the carrier and notify the shipping company.

Power Fuse
Moving, Storage and Disposal
Moving CAUTION
1. Do not impact on the products when moving.
may cause a damage of products 1. Do make a moving of fuse links with packed condition. 2. Do not impact on products or not drop products when assembling fuse holders.

Storage CAUTION

Operating conditions
1 Normal operating condition Design to IEC 60282-1, with the following limits values : Ambient temperature Maximum : +40 Maximum 24 hour average : +35 Minimum : -25 Maximum site altitude : 1000 m above sea level. Humidity 24 hour average value : 95% One month average value : 90% 2 Special operating conditions Special operating conditions are to be agreed on by the manufacturer and user. The manufacturer must be consulted in advance about each special operating conditions using at the following cases or places : Higher level of site altitude or ambient temperature exceeding the normal conditions Outdoor using At a wet place with high humidity usually At places with much water or oil vapors At places with an explosive, flammable or noxious gas At places with much dust At places with abnormal vibration or impact In case of using a special fuse holder made by users. In case of using at other special conditions besides above cases 3

1. The fuse must be stored in clean, dry, dust and condensation- free environment.
may cause a weakness of insulation.

2. The products must be stored at the place with no corrosive gas.


may cause a damage of product s (discoloration)

Disposal CAUTION
1. When making a disposal, dispose it at a designated place with no affection to environment.
may cause an environmental pollution 1.According to the ISO 14000, separate all of them as metallic or non-metallic material and dispose them at a designated place after dividing e all of material as renewable materials and other materials which may cause an environmental pollution. 2. In case of being materials whatever you want to remake please contact us. 3. In case of special materials making noxious gas when destroying by fire, be sure to dispose them at an approved place 4

Current Limiting
P Type Current limiting power fuses
1. Ratings
The ratings of fuse links are as follow :

Power Fuse
G & J Type Current limiting power fuses
1. Operating indication of fuse links
LFL-G,J- Type : When a power fuse blows, a striker pin extends from the load end of the fuse about 10mm length.(An initial operating load is over 0.5kg) LFL-20J-1 : No striker fin has fitted. LFL-G- B/C Type (DIN Type) : When a power fuse blows, a striker pin extends from the load end of the fuse about 10mmlength. (An in itial operating load is over 0.5kg)

Use PT

Type LFL-6P-1

Place Indoor

Rated voltage,kV Rated currnet,A Rated breaking capacity(3P),MVA

Length of fuse link,mm

3.6/7.2

1P

250/500

110

2. Fitting and replacement of fuse links 2. Installation


Make an installation of fuse links as same insulation distance with ones of a disconnecting switch because these fuse links having a complete insulated structure do not emit any gas. Always only fuse links can be replaced simply. For the part of hinge, loosen a bolt () as shown in figure 1 and insert the striker pin of fuse link. Then retighten this bolt ( ). For the part of clip tighten a hook ring( ) as shown in upper figure 2 on a fuse links cap correctly. In case of fuse checker of LFL-G- B/C Type (DIN Type), tighten a adhesive point of fuse checker as shown in upper figure 3 with two screws and then adhere it to let a striker pin of fuse link be to the direction of fuse checker. When a power fuse blows, replace fuse links only with new ones.

3. Replacement of fuse links


Replace fuse links only as new ones if after the fuse trip mechanism has operated

WARNING
1. When the trip mechanism has operated at short circuit fault, always replace all three fuses in a three phase or two phase circuit even though only one or two are open circuited
may result in explosion by the possibility of internal elements damage.

3. Installation
Make an installation of fuse links as same insulation distance with ones of a disconnecting switch because these fuse links having a complete insulated structure do not emit any gas.


tube

4. Maintenance & inspection


Perform the periodic inspection one time per a year for contact s, uncleanness on the surface of porcelain, looseness of screws (specially for clips).

Fuse link striker pin

Figure 1. Hinge of fuse link (Operating indication of fuse link)

Figure 2. Opening of fuse link

Current Limiting
G & J Type Current limiting power fuses G & J Type Current limiting power fuses
5. Item of maintenance and inspection

Item Method Visual Fuselinks
Adhesive point of screw (2 points) in DIN type of Fuse link

Power Fuse

sandard No crack on fuse links No dusty points on fuse links A striker pin shound not be extended Joint and screws should not be loosen No broken or no crack on the surface No dusty points on surface No overheating, no discoloration and no variation
Joint of bolts and nuts should not be loosn

Period
One/year

Remarks

cleaning

Porcelain

Spanner Visual Spanner Visual

Fuse holder Frictional s parts Joints Others Insulated resistance

cleaning
Micro carbon Grease

Figure 3. Fuse checker of DIN type

Bolts and nuts should not be loosen

Figure 4. DIN type of fuse

Over 1000between an eath and a conductive 1000V Mega parts

4. Close-open operation
Make a close-open operation by inserting a hook-bar into a hook hole () as shown in Figure 2, 4. The opening angle is 45 . LFL-G- B/C Type (DIN Type) : Make a close-open operating a spring of in Figure 4 by using a hook bar.

CAUTION
1. When using for protection of transformers or condensers, replace all phase of fuse links after over 1000 close-open operation.
There may be a possibility of weakness by heating at elements inside fuse links.

CAUTION
1. When making a close-open operation, be careful not to impact on products with light operation.
may cause a broken of fuse links because of making of porcelain material.

2. Be careful for using fuse links so that the life expectancy may be reduces according to the operating conditions

WARNING
1. When the trip mechanism has operated at short circuit fault, always replace all three fuses in a three phase or two phase circuit even though only one or two are open circuited
may result in explosion by the possibility of internal elements damage.

Current Limiting
M Type Current limiting power fuses
1. Operating indication of fuse links
When a power fuse blows, a striker pin extends from the load end of the fuse about 10mm length.(An initial operating load is over 0.5kg)
Striker pin of fuse link

Power Fuse
M Type Current limiting power fuses

2. Fitting and replacement of fuse links


For the part of hinge, loosen a bolt () as shown in figure 5 and insert the striker pin of fuse link. Then retighten this bolt ( ). For the part of clip tighten a hook ring( ) as shown in upper figure6 on a fuse links cap correctly in case of under 3.6kV 100A and 7.2kV 50A. In case of over the above current ratings, tighten hook ring( ) as shown in Figure 7 by attaching it on tube inside a cup of fuse link with no gap.
Under 7.2kV M50 A

Figure 5. Hinge part of fuse link (Operating indication status of fuse link)

When a power fuse blows, replace fuse links only with new ones.

Under 3.6kV M100 A

7.2 kV M200 A

Tube

3. Installation
Make an installation of fuse links as same insulation distance with ones of a disconnecting switch because these fuse links having a complete insulated structure do not emit any gas Figure 6. Fuse link

Figure 7. Close position of fuse link

4. Close-open operation
Make a close-open operation by inserting a hook-bar into a hook hole () as shown in Figure 2, 7. The opening angle is 55 for 3.6kV and 45 for 7.2kV.

CAUTION
1. When making a close-open operation, be careful not to impact on products with light operation.
may cause a broken of fuse links because of making of porcelain material.

10

Current Limiting
M Type Current limiting power fuses
5. Item of maintenance and inspection
Item Method Visual Fuselinks Spanner
Porcelain

Power Fuse
M Type Current limiting power fuses

sandard No crack on fuse links No dusty points on fuse links A striker pin shound not be extended Joint and screws should not be loosen No broken or no crack on the surface No dusty points on surface No overheating, no discoloration and no variation
Joint of bolts and nuts should not be loosn

Period
One/year

Remarks

WARNING
1. When the trip mechanism has operated at short circuit fault, always replace all three fuses in a three phase or two phase circuit even though only one or two are open circuited
may result in explosion by the possibility of internal elements damage.

cleaning

Visual Spanner Visual 1000V Mega

Fuse holder Frictional s parts Joints Others Insulated resistance

cleaning
Micro carbon Grease

Bolts and nuts should not be loosen Over 1000between an eath and a conductive parts

Make a cleaning a time per a half year at least in place with much dust.

6. Life expectancy and Replacement


The fuse links have an life expectancy of 30,000 operations at a normal operating conditions of electric motor circuit (Rated current x 5, 10 sec) When a fuse link has reached a specified life or when is damaged, it is recommended that it be replaced.

CAUTION
1. When using for protection of transformers or capacitors, replace all phase of fuse links with new fuse links after 30,000 operations.
There may be a possibility of weakness by heating at elements inside fuse links

2. Be careful that fuse links may have a possibility of short- life expectancy according to the operating conditions.

11

12

http://www.lgis .com
HEAD OFFICE