Zeus 5.0 Quick Start Manual P/N 315-033875-11

Siemens Building Technologies Fire Safety

Copyright 20012007, Siemens Building Technologies, Inc. FireFinder XLS is a trademark of Siemens Building Technologies, Inc. Microsoft Windows, Windows Explorer and Internet Explorer are trademarks of Microsoft Corporation. Install Shield is a trademark of Sterling Technologies, Inc. and Installation Software Technologies, Inc.

Zeus 5.0 Quick Start Manual P/N 315-033875-11

Siemens Building Technologies Fire Safety

TABLE OF CONTENTS
Chapter 1 Title Page

INTRODUCTION AND OVERVIEW .......................................................................................1 What This Manual Covers .................................................................................................1 Getting Additional Help....................................................................................................1 What is Zeus?................................................................................................................... 1 Definitions of Important Terms......................................................................................... 2 Conventions Used in this Manual...................................................................................... 2 INSTALLING AND RUNNING ZEUS...................................................................................... 3 Installing Zeus ................................................................................................................. 3 Starting a Zeus Session ....................................................................................................3 Ending a Zeus Session...................................................................................................... 3 STEP-BY-STEP EXAMPLE....................................................................................................4 PHASE 1: Fire-Only System for Acme Manufacturing Co. ................................................... 4 Part 1-1: Start a New Zeus Project ...................................................................... 5 Part 1-2: Set Up Hardware in the Physical View ................................................... 6 Part 1-3: Set Up Groups in the Geographic View.................................................11 Part 1-4: Assign Elements to Logic Functions .....................................................13 Part 1-5: Check and Compile the System............................................................16 PHASE 2: Add Voice to Fire System for Acme Manufacturing Co. ......................................17 Part 2-1: Add Voice Components (Physical View) ...............................................17 Part 2-2: Group Voice Elements (Geographic View)............................................21 Part 2-3: Set Up Voice Controls (Control View) ................................................... 22 Part 2-4: Program Voice Functions (Function View)............................................24 Part 2-5: Check and Compile the Project ............................................................24 PHASE 2a: Using Bulk Amplification for Voice ..................................................................25 PHASE 3: Adding Fan Control..........................................................................................27 PHASE 4: Networking Multiple Systems ...........................................................................29 Part 4-1: Add Fire Finders XLS Node (Physical View) ...........................................29 Part 4-2: Add Finance Building FireFinder XLS Node ...........................................30 Part 4-3: Setup Groups in Geographic View........................................................33 Part 4-4: Setup Logic Functions for Node 2 ........................................................34 Part 4-5: Setup Inter-panel Logic Functions ........................................................36 Part 4-6: Adding Other Siemens Systems ...........................................................38 PHASE 5: Connecting FireFinder XLS to a Central or Remote Station .................................39 PHASE 6: Global PMI.......................................................................................................41 USER INTERFACE .............................................................................................................46 Main Screen ................................................................................................................... 46 View Windows ................................................................................................................47 Title Bar ..........................................................................................................................48 Menu Bar .......................................................................................................................48 Toolbar ..........................................................................................................................48 Status Bar.......................................................................................................................48 Help Menu Commands ....................................................................................................49 Help Screen Tabs ............................................................................................................49 Help Window Controls ....................................................................................................51 File Menu Commands .....................................................................................................52 Edit Menu Commands.....................................................................................................53 View Menu Commands ...................................................................................................54 Insert Menu Commands ..................................................................................................55 Build Menu Commands ...................................................................................................55 Tools Menu Commands...................................................................................................56

Zeus 5.0 Quick Start Manual P/N 315-033875-11

Siemens Building Technologies Fire Safety

CONCEPTS AND OPERATIONS....................................................................................... 57 Comparison of Zeus and Microsoft Windows Explorer ................................................... 57 Elements, Links and Sources........................................................................................ 57 FireFinder XLS Communications Protocols.................................................................... 58 Understanding the View Windows ............................................................................... 58

LIST OF NUMBERED FIGURES


Figure 2-1 2-2 2-3 3-1 4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10 4-11 4-12 4-13 4-14 4-15 5-1 5-2 5-3 Title Zeus Shortcut (Desktop Icon) User Login Dialog Zeus Main Screen ACME Manufacturing Co. Layout Zeus Main Screen Tree View Example Multiple View Windows Title Bar Menu Bar Toolbar Buttons Status Bar Help Menu and Sub-menu Help Tabs Help Window Controls File and Edit Menus View Menu and Sub-menus Examples of Insert Menu Selections Build Menu and Sub-menu Tools Menu and Sub-menus Link/Source Example Detail View Tabs Function View Example Page 3 3 3 4 43 44 44 45 45 45 45 46 46 47 48 49 50 50 51 57 58 59

Zeus 5.0 Quick Start Manual P/N 315-033875-11

Siemens Building Technologies Fire Safety

CHAPTER 1 INTRODUCTION AND OVERVIEW


What This Manual Covers
This manual provides basic operating information for the Zeus software package, which is used to program Siemens FireFinder XLSfire detection systems. The manual supplements the comprehensive instructions found in the Zeus Installation Manual (Siemens P/N 315-034686) and the online Help feature of the Zeus software itself. This manual consists of the following chapters: Chapter 1: Chapter 2: Chapter 3: Chapter 4: Chapter 5:

Introduction and Overview Installing and Running Zeus Step-By-Step Example User Interface Concepts and Operations

General information about Zeus and this manual Getting in and out of Zeus A short example of developing and configuring a system An overview of the Zeus menus and graphic interface Important concepts and operations for using Zeus

Getting Additional Help


The Zeus online Help feature provides more comprehensive information than this manual. See the Help Menu section of Chapter 4 for a general description of this feature. To access Help while the software is running: - Open the Help Menu and select a command such as Contents, Index or Search, or - Select a screen feature and press the F1 key, or - Click the Whats This? Button on the Toolbar, then click the screen feature you want to identify. Updated information is available through the Internet at www.sbt.siemens.com/FIS/technicalsupport/. Live support is available at 1-800-248-7976 Monday to Friday, 8 a.m. to 6 p.m. US Eastern time. For complete software installation and setup procedures, refer to the separate Zeus Installation Manual.

What is Zeus?
Zeus is a software application used to plan and configure installations of the FireFinder XLS fire detection system. With Zeus, you can: Graphically design a system configuration. View multiple system interrelationships, such as hardware or logical connectivity. Assign devices to convenient, intuitive groups by location or other criteria. Visually program system behavior. Compile and transfer the completed configuration to a FireFinder XLS control panel. Record wave-format sound files and assemble Voice files for XLS Voice systems Generate: Reports on system configuration differences Walk test results History Log records System power and battery requirements calculations Equipment lists Zeus features and capabilities include: Drag and Drop Operation: Zeus provides a graphical user environment similar to that of Microsoft Windows Explorer. You can construct and modify the system configuration simply by dragging and dropping elements representing components, hardware groups, logic functions, etc. Multiple Views: Zeus allows you to configure and examine a systems interrelationships through a series of sideby-side display windows (Views) that give you information on distinct aspects of the system.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

Siemens Building Technologies Fire Safety

Definitions of Important Terms


Child Compile Configuration An element in a tree view connected to, but on a lower level than, another element. A subordinate element. Condense a Project File (.zdb) that Zeus can manipulate into a Configuration File (.hrc) that can be transferred to a FireFinder XLS panel. The electronic represent ation of a system developed by Zeus, as saved to a compiled Configuration File (.hrc format). This is the file format stored in a FireFinder XLS panel. Expand a compiled Configuration File (.hrc) into a Project File (.zdb) that Zeus can manipulate. An item represented by an icon and label in a tree view. A Zeus element may represent a device, a logic function, a geographic grouping, etc. (noun) The physical fire system and its geographic setting. A FireFinder XLS central processing unit and the devices it operates. An element in a tree view with other elements on lower levels connected to it. A superior element. The electronic representation of a system developed by Zeus, stored to memory, sho wn on-screen or saved to a Project File (.zdb format). This is the file format that Zeus can manipulate. Settings that accompany an element, such as the elements label, device settings, etc. Properties are adjusted by editing fields in the Detail View window. An icon representing an element created in another place in the configuration. An element to which links are made elsewhere in the configuration. A Node element and the collection of devices and their interconnections (physical, logical, etc) under it. Multiple Nodes connected together via communications links would imply multiple systems. Copy a Configuration File (.hrc) from a host computer to a FireFinder XLS panel, or vice versa. Windows displaying distinct aspects of the system. The five Views are Detail, Physical, Geographic, Control and Function. An alarm method by which an event code is conveyed by pulsing the audibles such that the beats can be counted by listeners to determine the codes digits.

Decompile Element Installation Node Parent Project Properties

Link Source System Transfer Views Zone Coding

Conventions Used in this Manual


[Menu] > [Command] Underlined Text Ctrl+(key) Click Double-Click Right-Click Drag and Drop Click the menu and select the command from the resulting drop-down list. Example: File > Open means select the Open command from the File Menu. Refer to the adjoining figure used in Chapter 3 (Step by Step Example). Hold down Ctrl (control) on the keyboard while pressing the specified key. A single click of the left-hand button on the mouse. Two clicks, in rapid succession, of the left-hand button on the mouse. A single click of the right-hand button on the mouse. Click an item, hold down the left-hand mouse button, and move the mouse to move the item across the screen. Release the button to put the selection in the new location.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

Siemens Building Technologies Fire Safety

CHAPTER 2 INSTALLING AND RUNNING ZEUS


Installing Zeus
Zeus is a Siemens-proprietary software package that requires a series of password-exchange procedures to be installed and activated at a site or with an authorized agent, set up and installed on individual workstations. Refer to the Zeus Installation Manual for details on these procedures.

Starting a Zeus Session


To run Zeus after setup, simply double-click the Zeus desktop icon (Figure 2-1) and enter the appropriate user name and password in the User Login Dialog (Figure 2-2). Zeus will open to its main screen (Figures 2-3, 4-1).

Figure 2-1 Zeus Shortcut (Desktop Icon)

Figure 2-2

User Login Dialog

Ending a Zeus Session


To exit Zeus, click File, and then Exit from the resulting drop-down menu (File > Exit). You can also click the button marked X in the upper right corner of the window. If the currently open file has unsaved changes, you are prompted to save the file before exiting. The time that has elapsed during your session is displayed in the lower right corner of the Zeus window.

Figure 2-3 Zeus Main Screen (See also Figure 4-1, Chapter 4.)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

Siemens Building Technologies Fire Safety

CHAPTER 3 STEP-BY-STEP EXAMPLE


The fastest and easiest way to introduce you to Zeus is to show you step-by-step how to configure a simple project. Refer to Chapters 4 and 5 herein, and the Help feature in Zeus, for more detail about the features and operations presented here. NOTE: This project is a highly simplified example provided only to illustrate Zeus operations. It is not intended to represent a practical or code-compliant fire system. Phase 1: Fire-Only System for Acme Manufacturing Co.

Figure 3-1 ACME Manufacturing Co. Layout Functionality Required: One HFP-11 detector, one HMS-S Pull station for each room. All HFP-11 detectors use Intelligent Environmental Compensation (IEC) and Application Specific Detection (ASD). An event on first floor of the Main Building or in the Annex, at a detector or pull station, triggers the following: - A steady audible Evacuation level alarm on that floor, accompanied by synchronized strobes. - A temporal audible Alert level alarm on the other floors of the building of incident and other buildings, accompanied by synchronized strobes. The detectors and devices in the Annex are connected to the Main Building 1st-floor device loop. The XLS control panel, located in the Main Building Lobby, includes Function Keys (programmable buttons) for: - Alarm testing / fire drill simulating an event on each floor of the Main building and Annex. - Recall signal of 30 pulses per minute march tone, which always sounds throughout the complex. System Status Displays with control are used to monitor and acknowledge events in the Annex and on the Main Building 2nd floor. Alarm events activate a dialer to local authorities; trouble events activate a dialer to maintenance personnel. A single printer, located in the Main Building Lobby, is used to print out all system events. General Approach: Although there are a number of approaches, heres how youll build this configuration in the following exercise: 1) Start a new project. 2) Set up the system hardware by inserting and deleting hardware elements in the Physical View. 3) Assign hardware elements to appropriate location groupings in the Geographic View. 4) Set up the system behaviors by assigning devices and groups to logic elements in the Function View. 5) Perform a check to find errors, and then compile the project into a configuration file that can be transferred to the system control panel. Note: Normally, one would begin the design process by sketching a system in terms of components, locations and logic before programming in Zeus. For illustration purposes, we will explain the system as we build it here.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

Siemens Building Technologies Fire Safety

Part 1-1: Start a New Zeus Project NOTE: 1) 2) 3) Underlining refers to a figure on the right side of the page.

On the Windows Desktop, double-click the Zeus Shortcut. In the resulting Login dialog, enter a valid user name and password. Click OK. Open the File Menu and start a new project: Click File> New.. Or click the new button on the Zeus Toolbar . In the New Project dialog that pops up, fill in the project name. This example project is called Acme. As you type, notice that Acme is added to the folder address listed in the Location field below. Zeus adds the extra folder to keep files for the same project together. For this exercise, use the default directory: C:\Program Files\Siemens FireFinder XLS \Zeus 5.0\Acme. Click OK when you are done. The Zeus screen appears, with the gray Detail View window on the right, and at least one other View window on the left. (Refer to Figure 2-3.) If the Physical View window is not displayed somewhere to the left of the Detail View, click the Physical View button, , on the Toolbar. For now, we want only the Physical and Detail Views to be displayed. If other View windows are open, close them. In the Physical View, select the Project element (single-click the icon so it becomes highlighted). At the top of the Detail View, click the Properties Tab. The fields that appear are properties associated with the selected element in this case, identifying information on the project itself. You can enter this projects data in these fields. If the system is not an XNET system, the XNET Networked Configuration in Project Properties must be unchecked. Click the property NFPA System Type. From the resulting menu, select Local (NFPA 72A). Of particular note, the Contact Name and Contact Phone field entries will be displayed in the Alarm Details Screen of the control panel (PMI) during an event. As you construct this project, you may need to resize the Physical View window to see all the details. You can quickly make the windows the same width by clicking the Arrange button, , on the Zeus Toolbar. You can also move the cursor over the Physical View windows right border, where it will become a double arrow. With this symbol active, click, hold and drag to move the border.

4)

5)

6) 7)

8)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

Siemens Building Technologies Fire Safety

Part 1-2: Set Up Hardware in the Physical View 1) With the Project element selected, insert a FireFinder XLS Node under it by clicking Insert > FireFinder XLS. Select the FireFinder XLS Node element in the Physical View. Click the Properties tab in the Detail View window. Click the property field Base Language Cust. Message, type Acme Manufacturing Co., and press the Enter key. This becomes the Node elements label in the Physical View, and the title shown on the PMI control panel during system startup. Toward the bottom of the Detail View, set Battery Capacity Factor to Total Amp x 4 Hours, and Battery Capacity Reserved to 25%. Click the box next to the Node property FireFinder XLS Map Names. The resulting dialog allows you to select the floor plans that can be shown on the Nodes PMI (control panel), to display event locations. Select the three Acme example maps already in Zeus Acme 1st Floor, 2nd Floor, Annex and click Add to make these files available to this Node. Close the dialog. Note the properties On Site Contact Name / Phone. This information is prominently displayed on the PMI when the user requests event details. Expand the Node element by clicking the small plus sign next to it. The elements History Log and System Flags, which are part of the Node element, appear. Click History Log and press the F1 Key to view help topics on this important element and its properties. The System Flags element will be explained when it is used a little later, in the Function View section of this tutorial Select the FireFinder XLS Node again and click Insert > CAB-1 . A CAB-1 (one-row enclosure) is inserted as a child of the Node element. Lets look at correcting a mistake. The specification calls for using a double-row CAB-2, not a CAB-1. You can either undo the insertion operation, or delete the element you just inserted. To undo the insertion, you can either click Undo, , on the Toolbar, press Ctrl +Z, or click Edit > Undo. To delete the CAB-1 element, first select it. Then you can either click Delete, , on the Toolbar, press the Delete key, or click Edit > Delete . Use one of these methods to remove the CAB-1 element.

2)

3)

4)

5)

6)

7)

8)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

Siemens Building Technologies Fire Safety

9)

Select the FireFinder XLS Node element and insert the new CAB-2 element under it (replacing the CAB-1): Insert > CAB-2. Change the CAB-2 element in the Detail View to read 1st Flr Enclosure Lobby.

10) The system uses a PSC-12 power supply card. Four relays are packaged with the PSC. Two are fixeduse: they connect to the systems common alarm and trouble buses. Two others, which we will not use here, are programmable. Zeus has already inserted a PSC-12 under the CAB-2; click the small plus sign to the left of the CAB to show the PSC. Click the small plus sign to the left of the PSC to expand it. The two fixed PSC Relays are already under the PSC. Label the PSC Power Supply - 1st Flr CAB, and the PSC relays 1) Common Alarm - 1st Flr CAB, and 2) Common Trouble - 1st Flr CAB. Set the property Battery Size to 31 AH. 11) Select the CAB-2 and insert its inner door: Insert > Inner Door. (Notice that the Insert menu has changed with the new selection.) 12) Select the Inner Door and click Insert > PMI to add a control panel/central processor (a PMI PersonMachine Interface). Label the PMI Control Panel Lobby. Its default HNet Address, 253, is reserved for a Nodes PMI only. 13) The project requires five Function Key operations for manual system testing. On the PMI screen, these keys are listed on the Function Key Screen; a user will press these graphical buttons on the touch screen to run and stop tests. Right-click the PMI, and select Insert > Function Key from the resulting pop-up menu. A Function Key is inserted as a child of the PMI. Add four more, and label the Function Keys Test 1st Floor, Test 2nd Floor, Test Annex, Recall Signal and STOP. You will set up the logic to program these keys a little later. 14) Select the PMI again. Click the box next to the PMIs PMI Event Map Name 1 property. The resulting dialog allows you to mark the PMIs position on one or more of the map files selected for this Node. For Select Bitmap, choose the Acme 1st Floor map. Drag the blue dot to the desired location, in this the Lobby. When a 1st-floor event map is displayed on the PMI, a You Are Here icon is added at this mark. Note that you can click and drag it to adjust its position.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

Siemens Building Technologies Fire Safety

15) Select the 2nd Floor map for PMI Event Map 2 (you can do this by setting Position to 2 in the dialog), and the Acme Annex map for Position 3. Do not mark a position on these other two maps, since the PMI is located on the 1st Floor, Click OK when done. 16) Use these properties to set the PMIs display: Group Level Displayed to Device/Primitive to show individual devices, Display Type to Display With Control, and MORE INFO View to Map so a graphical map will be first displayed when MORE INFO is pressed. 17) The main enclosure requires a card cage into which circuit cards will plug. Add a five-slot CC-5 card cage as a child under the CAB-2 enclosure. Change the CC-5 custom message to Fire System Cards 1st Flr. (The Inner Door and PSC are shown collapsed for clarity. Note that they are on the same tree branch / level as the CC-5.) 18) Select the CC-5 and insert a NIC-C (HNet) under it. The NIC will communicate with the other enclosures in the system. Label the NIC Network Interface Card 1st Flr. In the Detail View Properties tab, make sure CAN Bus Enabled is NOT checked. This system will use its DACs, not NICs, to host CAN bus devices. 19) The 1st floor requires three output circuits to drive 1st floor audibles, 1st floor strobes, and the separate any-alarm default audible required by regulation. Insert a ZIC-4A Zone Indication Card under the CC-5. Label the ZIC-4A Notification Apps 1st Flr. Insert three Out Ckts under the ZIC. Label these 1st Flr Audibles, 1st Floor Strobes and 1st Flr Default Audible. 20) In the Out Ckt Detail Views, set the property ZIC Circuit Usage to NACCoded for the Audibles and Default Audible circuits, and Strobe Synch for the Strobe circuit. (You will code the audibles later.) On all Out Ckts, check the Silenceable box and set Wiring Type to Class A. Set Total Current drawn to 2.0 amps each. This last property allows Zeus to determine whether there is an adequate power supply to operate the system as designed. 21) We need another ZIC under the CC-5, this time for the Annex. You can create this quickly by copying and modifying the 1st Flr ZIC. Select the 1st Flr ZIC; copy it (use Edit > Copy, press click Ctrl + C, or click ). Select the CC-5 element. Paste the copied ZIC (Edit > Paste, Ctrl + V, or ). Delete the Default Audible Out Ckt and change all the other labels from 1st Flr to Annex.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

Siemens Building Technologies Fire Safety

22) Insert a DLC (Device Loop Card) under the CC-5. Label it 1st Flr Device Loop. Select the DLC, insert an HMS-S pull station and label this 1st Flr Stairwell Pull Sta. 23) Under the DLC, insert and label an HMS pull station 1st Flr Stairwell Pull Sta. Then insert and label an HFP-11 detector (1st Flr Detector) and another HMS pull station (1st Flr Pull Sta.). Duplicating these two new elements will populate the device loop. All HFPs will use Intelligent Environmental Compensation (IEC), so make sure that property is checked on this HFP. Also, most of the detectors will have an Application Specific Detection (ASD) setting of Office, so set that property on this HFP as well. 24) Click the HFP, hold down the Shift key, and click the second HMS to select both devices. Copy these elements to the Windows Clipboard. (Use Ctrl+C, Edit > Copy, or .) Select the DLC. Click Edit > Paste Special. In the resulting dialog, set Multiple Paste to 8 and click Paste. Eight more HFP / HMS pairs are inserted under the DLC, one pair for each room on the Main Building 1st floor and the Annex. 25) Select the DLC. In the Detail View Elements tab, use the table to change the elements as shown, filling in the Base Language Custom Message with the individual Zones. Note the amount of work that has been saved by using Paste Special to generate and label repetitious elements. 26) You will now set up the 2nd floor enclosure simply by copying, pasting and modifying the 1st floor enclosure. Select the 1st floor CAB-2, copy it and paste it. A duplicate of the entire 1st floor setup is added to the system. Move one of the CABs so the copy (Enclosure 2) is below the original. 27) Select the copied CAB, and then click (or Edit > Find/Replace Text or Ctrl + F). In the resulting dialog (next page), enter 1st for Find What and 2nd for Replace With. Click Replace All, and then Close. Fully expand the CAB. Note that for the CAB and all elements under it, 1st Flr becomes 2nd Flr. In the CAB label, change Lobby to Hallway. Modify the CAB children as follows: 28) Delete the PMI from under the Inner Door. 29) Delete the default audible Out Ckt on the first ZIC, and the entire second (Annex) ZIC.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

Siemens Building Technologies Fire Safety

30) Taking advantage of the similar layouts of the 1st and 2nd floors, select the DLC and use Find/Replace Text to replace all occurrences of Lobby to Office, Shipping to Test Lab, Shop to QA Room. 31) Delete the copied Annex loop devices i.e., the devices at addresses 14 through 19. 32) Select the first HMS in the device loop (Stairwell). Click Edit > Find/Replace Tree Node (Ctrl + H). In the resulting dialog, select HFP for Replace With, then Replace. In the next dialog, set up the 2nd floor Stairwell detector: Device Address 1, 2nd Flr Stairwell Detector, IEC checked, ASD Application of Lobby. Click OK and Close, and the HMS from the bottom stairwell landing becomes the detector at the top landing. The 2nd floor device loop is complete. 33) Select the Node element and insert two SSDs (System Status Displays). Note that Zeus applies HNet Address 9 to the first SSD, filling the gap left by the deleted ZIC at that address. Label the SSDs 2nd Flr Display - Hallway and Annex Display Annex Office. For PSC Power Supply Address, set the 2nd floor SSD to 6 (the HNet address of the 2nd floor CABs PSC) and the Annex SSD to 1 (the 1st floor CABs PSC). 34) Again select the Node element, and insert a Remote Printer Module (RPM) that will communicate with a PAL-1 printer to make printouts of system events and histories. Label the RPM System Printer Interface. Set the property PSC Power Supply Address to 1, which is the HNet address of the PSC in Enclosure 1. The RPM and printer will be located near this CAB, in the Main Buildings Lobby. 35) Expand the RPM and label its Parallel Port System Printer 1st Flr Lobby. Set the property Print Level to Device/Primitive so the event details will be printed out at the individual device level, as opposed to a higher Group Level. 36) Select the Nodes PMI (under the 1st flr CAB door). Set the property Report RPM Address to the RPMs HNet address (12), and Report RPM Port to Parallel Port. Set Group Level Displayed to Device/Primitive to match the RPM. 37) Save the project by clicking File > Save, or the Toolbar. on

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

10

Siemens Building Technologies Fire Safety

Part 1-3: Set Up Groups in the Geographic View 1) Click the Geographic View button, , to insert that View. Keep the Physical View open. You will now organize the devices in the Physical View into Groups Which are used in creating system logic (Function View) and Voice controls (Control View) and determining what graphics and messages the PMI displays during an event. 2) Select the Project element in the Geographic View, and look at its Properties Tab in the Detail View. The five Group levels (1-5) and their default names (Campus, Building, Floor, Area, Zone) are displayed. Note that you can change the names of the Group levels here, to best suit your particular project. Keep these default labels for this example project. Insert three Floor (Level 3) elements under the Geographic Views Project element. Label these elements 1st Floor, 2nd Floor and Annex. Under the 1st Floor, insert 7 Zones (Level 1), one for the stairwell and each room. Label these accordingly: Stairwell - 1st Flr, Lobby, Hallway, etc. Assign the 1st Floor devices in the Physical View to their corresponding Groups. For example, select the Lobby devices, then drag and drop these onto the Zone Lobby. Note that links of the elements are placed under the Zone; the device icons are replaced by light-yellow boxed arrows. Try using the right mouse button to make some of the assignments. When you release the button, a menu prompts you to Assign to Here, or Cancel; Move and Copy are unavailable, since assignment is the only action possible. Click Assign to Here for each link. Add and label one more Zone under the 1st Floor: 1st Flr Components. This Group will allow you to work separately with such system components as the power supply and electronics cards. This Group will enable the PMI to display detailed messages and maps when a card or module is activated or is in a trouble state. To this last Zone, assign the HNet-addressable electronic components located on the 1st Floor: PSC, PMI, cards and modules. Note that these module links are white, not light yellow as before. This indicates that the links are used only to set PMI display information, and do not affect any other kind of system functionality.

3)

4)

5)

6)

7)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

11

Siemens Building Technologies Fire Safety

8)

Select a Zone on the 1st Floor, and examine its properties. Many of these determine what information will be displayed on the PMI during an event. On the PMIs Alarm Details Screen, the properties Base Language Detail Message, Fire Service Equipment Icon Names, and Hazards / People Icon Names are shown. On the PMIs Map Screen, the Group Event Map Name graphic, and marked position on that graphic specified by Group Location, is displayed. The Zone Coding properties determine at what Group level and with what response an event in this Zone will sound, when Zone Coding is used in a system. Acme will not use these.

9)

Select each of the Zones under the 1st Floor Group, and click the button on the right of the Group Event Map Name field. In the resulting dialog, use Select Bitmap to select the 1st Floor map for each 1st Floor Zone. This time, mark each Zones position on the map by clicking in the room the current Group represents. The blue dot will show up on the PMI as an alarm icon (flame) or trouble icon (lightning bolt) when the map is called up and displayed during an event. You can click and drag the dot to move it. (The position of the dot on the map, in pixels, is shown in the property Group Location, which in turn can be used to adjust that position.) Note that without closing this dialog, you can move from Zone to Zone by clicking the tree graphic on the right side. Note also that if you click Display All on the right, all the marked positions on the Acme 1st Floor map are shown.

10) Back in the Detail View, clicking on the buttons next to Fire Service Equipment Icon Names and Hazards / People Icon Names brings up a similar dialog that allows you to select icons that will be displayed in the PMIs Alarm Details Screen, which will aid firefighters in determining resources and hazards in the affected Zone. The Hazards / People dialog includes a feature for generating custom 3digit HazMat icons. You can press the F1 Key to get the Zeus Help feature, which will provide more details. 11) Repeat the setup process for the 2nd floor and for the Annex. The Annex does not currently contain its own equipment, so no Annex Components Group is needed. 12) Save the project: File > Save, or .

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

12

Siemens Building Technologies Fire Safety

Part 1-4: Assign Elements to Logic Functions 1) Click the Function View button, , to open that window. If the Physical and Geographic Views are closed, open them as well. Click the Arrange button, , to make all Views the same width. Expand the Function View project element to see the automatically added link, Logic Functions for FireFinder XLS Node. All the logic of this single Node installation will be listed under this link. Each Node of a multiple-Node installation would have its own Logic for Node link. This links properties include three Audible Control Function Priority Action fields. These set the responses for NAC Coded ZIC output circuits. As youll see, they also correspond to the three inputs of all Audible Control Functions for this Node. The Zone Coding properties listed after these fields are not used in this project. For Priorities 1-3 respectively, select Steady Audibles, Temporal / Uniform and March Time 30 SPM. These settings correspond to the required project alarm, alert and recall states. 4) The first logic function to be created will be the Audible Control Function for the default audible, on the third output circuit of the 1st Floor ZIC. Select the Logic Functions for Node element and insert an Audible Control Function. Select this function element. In the Detail View, enter DEFAULT AUDIBLE for the property Function Label, and 1st Flr Lobby for Comment. Expand the function and note the light-yellow inputs Priority 1-3, and the light-blue output. On this function, each input can have a single device, Group, System Flag or Function linked to it. The state of the linked element determines the state of the input. Each Priority input corresponds to a different audible output, as you set up in the Logic for Node link earlier. 5) From the Physical View, drag and drop the generic System Flags element (directly under the Node) onto the functions Priority 1 input in the Function View. Select the resulting link. Set the property Flag Name to Any Alarm. Drag and drop the ZIC Out Ckt Default Audible from the Physical View to the Audible Control Functions output. When an alarm occurs anywhere in this system, this Audible Control Function will cause the default audible on the 1st floor ZIC to produce a steady tone, as you selected in the Logic Functions for Node link.

2)

3)

6)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

13

Siemens Building Technologies Fire Safety

7)

Now you will create the logic for the PMIs Function Keys (touch screen graphical buttons). A Function Key produces a short pulse output when the screen is touched, but well want a panel user to be able to momentarily touch the key, and have the resulting operation latch on or off. Therefore, youll use D Latch functions to connect the Function Keys to the system logic. Insert a D Latch under the Logic Functions for Node element. Label it TEST 1ST FLOOR / Toggle/Latch. This D Latch will be used as the Test 1st Floor Function Keys toggling latch, with the output becoming and staying true with the first screen touch. For this role, the D Latch requires its output to be inverted (changed to the opposite state) and then fed back to its own Data input. To set this up, drag the D Latch itself to its own Data input list. Select the resulting yellow function link, and in the Detail View check the Invert box. The yellow links F turns red to indicate that it is an inverted input.

D Latch in Toggle/Latch Application:

8)

9)

10) Drag the Function Key Test 1st Floor from the Physical View onto the Clock input. This Function Key will now cause the output to become true at the first touch, then to toggle between false (off) and true (on) for additional touches. 11) A Clear input resets the D Latch output to false (off). We will use the Function Key STOP to do this. Drag and drop this Function Key from the Physical View onto the Clear input. The TEST 1ST FLOOR toggle/latch is complete. You have not assigned any links to the blue D Latch output, because the D Latch will be assigned to the input to another function. Zeus allows functions to be assigned to the inputs of other functions, but not their outputs. You assign one function to the input of another by dragging the input function itself, not its output. 12) Insert three more D Latches for the TEST 2ND FLOOR, TEST ANNEX and RECALL functions. Format as before: STOP Key on Clear, inverted output of each D Latch itself on its own Data input, and the respective Function Key on Clock. 13) Three different audible tones are required: EVAC, Alert and Recall. The only way to activate the recall tone is to press the Recall Function Key. However, multiple conditions an alarm or a Function Key press will sound EVAC in one facility location, and Alert in the others.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

14

Siemens Building Technologies Fire Safety

To program this behavior, insert six OR functions under the Logic for Node link and set them up:
OR Function Label 1ST FLR EVAC 1ST FLR ALERT Inputs Group: 1st Floor D Latch: TEST 1ST FLOOR Group: 2nd Floor Group: Annex D Latch: TEST 2ND FLOOR D Latch: TEST ANNEX Group: 2nd Floor D Latch: TEST 2ND FLOOR Group: 1st Floor Group: Annex D Latch: TEST 1ST FLOOR D Latch: TEST ANNEX Group: Annex D Latch: TEST ANNEX Group: 1st Floor Group: 2nd Floor D Latch: TEST 1ST FLOOR D Latch: TEST 2ND FLOOR

2ND FLR EVAC 2ND FLR ALERT

ANNEX EVAC ANNEX ALERT

Note that the OR allows multiple links on its input. An ORs output becomes true when one or more of the links on its input become true. Here, ORs will be used to activate the proper response from the audibles and strobes from the true input of a particular Function Key or Group. Select one of the inputs Group links, and in the Detail View examine the property Input Criterion. You can select different criteria to make the Group input true. Keep the Active default setting for all the input Group links. 14) Insert three new Audible Control functions, fully expand them, and name them 1ST FLR APPLIANCES, 2ND FLR APPLIANCES, and ANNEX APPLIANCES. 15) Drag the EVAC OR functions to their respective Audible Control Priority 1 Inputs for example, 1ST FLR EVAC to the 1ST FLR APPLIANCES Audible Control Function input Priority 1. Assign the Alert ORs to the Priority 2 Inputs, and the RECALL D Latch to all Priority 3 Inputs. 16) From the Physical View, assign the 1st Floor ZIC Audibles and Strobes Out Ckts to the 1st Floor Audible Control Function output. Repeat for the 2nd Floor and the Annex. Save the project. You should note two things. Although the strobes are lumped in with the audibles, the ZIC will drive the strobe circuits in a non-coded way. Also, as an alternative, the Out Ckts could have been assigned to their respective Floor Groups, and those Groups could have gone on the function outputs instead of the circuits themselves.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

15

Siemens Building Technologies Fire Safety

Part 1-5: Check and Compile the System 1) In the Physical View, select the 2nd Floor SSD. Change its HNet Address from 11 to 9, the same as the Annex SSD. This is an intentional error. You will now check the project for errors before compiling it into a configuration file to be loaded into the systems PMI. Click Build > Check, . If you configured the system as outlined in these steps, you will see one error message in the resulting Check Result window for the intentional error we just introduced. Double-click on the message; the 2nd floor SSD is highlighted in gray in the Physical View. Select that SSD and change its HNet address back to 11. Re-run the check. You should now receive no error or non-fatal warning messages. To compile this project, first save it. Click Build > Compile, . The FireFinder XLS Compiled (.hrc) version of the system is saved to the project directory along with the Zeus Database (.zdb) version. Zeus adds HdbNode01 to the .hrc file name to indicate that this is the compiled file for Node 1, and therefore is to be transferred to the physical PMI for Node 1. If this example used multiple nodes, there would be multiple .hrc files, each to be transferred separately to the different nodes. You might also have used the Compile All command instead of Compile to create those files. In this case, the compiled .hrc file is larger than the .zdb file, but that is because the projects graphics and audio files are included in the compilation, while the original files are stored in another directory. The file etuser.lst is the record of the project elapsed time, the total amount of time the project has been open, which is displayed in the bottom right corner of the Zeus main screen. 6) To transfer the Acme configuration to its physical control panel, you would connect a cable from the serial port of a host computer to the Upload jack of the Nodes control panel. You would then run Zeus and use Build > Transfer , , to upload the compiled file to the panel, with the option of transferring the panels current history data to the host computer.

2)

3)

4) 5)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

16

Siemens Building Technologies Fire Safety

PHASE 2: Add Voice to Fire System for Acme Manufacturing Co. The Acme fire system will now be upgraded to include Fire Finder XLS Voice components. The additional requirements for this upgrade are as follow: Voice stations on both Main Bldg floors and in the Annex, with control transferable between all three stations. Three Voice channels for emergency pages, evacuation messages, and alert messages. Voice stations are capable of paging to any of these channels. Pre-recorded Evac and Alert messages will be broadcast from the 1st-floor enclosure, with backup message files stored in the 2nd floor enclosure. These messages will be the same for all locations. For example, the same Evac message plays in any location in the facility that is in an Evacuation state. Emergency telephone system with master phone at the Lobby enclosure, using separate circuits for Main Bldg 1st and 2nd Floors and the Annex. Emergency phones plug into jacks located along each circuit, in all rooms. Voice system will use existing enclosures (CABs), with an additional Remote Box (REMBOX) used for the Annex components. Annex Voice service will be hosted by the 1st floor enclosure.

Part 2-1: Add Voice Components (Physical View) 1) Open the completed Acme fire-only system. Close all Views except the Physical. Select the Node element. Set the DNet Wiring Style (bottom of the Detail View Properties Tab) to Style 4. Select the Inner Door on the 1st floor CAB. Insert and label an FMT as Firefighter Master Tel - 1st Flr, an LVM as Live Voice Module - 1st Flr, and an SCM as Switch Control Module - 1st Flr. Ignore the CAN Address of ^0 on these devices for now. Expand the FMT and label its Master Phone as Master Phone 1st Flr Lobby. Expand the LVM a nd label its Microphone as Page Mike - 1st Flr. Expand the SCM. The multiple switches under the LVM and SCM will be used for such functions as selecting the channels and speakers to which pages will be directed; requesting, granting and denying transfers of control from one Voice Command Station to another; and enabling Warden Pages. Label and set up the LVM switches as follows:
Switch 1 2 3 4 5 6 9 Device Usage Request Access Grant Access Deny Access All Call Page to Evac Page to Alert Microphone Label 1st Flr Request Acc 1st Flr Grant Acc 1st Flr Deny Acc 1st Flr All Call 1st Flr to All Evac 1st Flr to All Alert Page Mike - 1st Flr

2)

3)

Switches 1-3 will enable control transfers to and from this station; 4-6 will direct pages to the Emergency Page, Evacuation and Alert channels. You will soon set up these Voice functions. For all switches, check the property Active. For the MIC, set Cough Delay the pause between un-keying the mike and the end of a page to 5 seconds.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

17

Siemens Building Technologies Fire Safety

4)

The eight switches under the SCM will be used to complete the capabilities needed at this station. Label and set up these switches as follows:
Switch 1 2 3 4 5 6 7 8 Device Usage Speaker Group Speaker Group Speaker Group Telephone Group Telephone Group Telephone Group Warden Page Lamp Test Label 1st Flr to 1st Flr 1st Flr to 2nd Flr 1st Flr to Annex 1st Flr to 1st Flr 1st Flr to 2nd Flr 1st Flr to Annex Warden Page 1st Flr 1st Flr Lamp Test

Switches 1-3 will allow the user to page to the speaker circuits that you will soon add to the Groups 1st Floor, 2nd Floor and Annex. Switches 46 will connect emergency phone circuits to the Master Phone on the FMT. Switch 7 will allow the user to make a Warden Page, a page from the firefighter telephone system. Switch 8 will be used to test the panel LEDs. For all switches, the property Active must be checked. 5) Select the 1st-floor CAB-2, and insert a second CC-5 Card Cage under it. Label this CC-5 Voice System Cards - 1st Flr. Insert a DAC-NET (DAC) under the new CC-5. Label it Digital Audio Card - 1st Flr. In the Detail View, check the property First DAC because this is the first DAC in the system. Note: DACs accept HNet addresses of only 1 through 99. A good practice for Nodes with many DACs (up to 32 are allowed) is to reserve the lower HNet addresses for them. 7) In the Detail View, uncheck the DAC property Use Default PMFs, so that the properties Tones File Name and Message File Name become available. For each of these properties, you select a PMF file, with the extension .pmf, that contains a collection of pre-recorded tones or messages. The individual tones or messages in these .pmf collections are standard wave (.wav) files. Once a PMF is selected, its .wav files are available to this DAC. (The default PMFs is selected in the Node elements Detail View.) 8) With the DAC still selected, click the button to the right of Tones File Name. In the resulting dialog, click System Folder for the field Look In, and select the Default Tones PMF. Similarly, select an appropriate Default Message PMF for the property Message File Name.

6)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

18

Siemens Building Technologies Fire Safety

9)

Insert three Prerecorded Messages under the DAC. These are .wav messages that will be selected from the .pmfs stored in the DAC. Label these Emergency Page Tone, Evac MSG - Primary, and Alert Msg - Primary. They are primary because this DAC will be the primary source of these messages for the system.

10) Select the PreRecorded Message for the Emergency Page channel. Click the button at the right of its property Audio Source Wave Filename. In the resulting dialog, note that the two .pmf files you chose earlier for the DAC are available in the Tones/Message File field: default tones and default messages. Select the default tones .pmf to list its individual .wav files below. For the Emergency Page Tone, select 900 Hz from the Default Tones .pmf. This tone will play at the start of a page on the Emergency Page channel. Select the Evac message, and use the same process to assign one of the Evac1. wavs (male or female) from the Messages .pmf. Repeat this process for the Alert Message. 11) Insert a Local Page Board (LPB) under the DAC, and label it Local Page Board - 1st Flr. The LPB is required for the LVM and FMT to operate. 12) All within the Physical View drag the FMT, LVM and SCM to the DAC. Links are created under the DAC indicating that it will host these Control Area Network (CAN) modules. (The ^ in the element labels indicate CAN addresses.) 13) Insert the following components under the Voice CC-5: ZAC-40 (Zone Amp Card - 1st Flr), ZAC-40 (Bkup) (ZAC Backup - 1st Flr) and TZC-8B (Telephone Zone Card). Drag these to the DAC to create CAN links. Note that a dialog will ask whether these cards will be assigned to the DAC, or simply placed above it on the branch under the Card Cage. Select assign in each case. 14) Select the ZAC-40. This will be a distributedamplifier system; make sure that the property Bulk Amplification Riser Channel is set to Not Used. Repeat this step for the ZAC Backup. 15) Drag the ZAC Backup to the ZAC-40. The resulting link assigns this ZAC Backup to this ZAC-40. (Note: The ZACs cannot be backup-linked until after they are both linked to the DAC.) 16) Expand the ZAC-40 and label its Amplifier Circuit 1st Flr Speakers. Enter 40 for the circuits property Speaker Wattage (40 Watts). Zeus will use this information at compile time to determine whether the configuration includes sufficient power supply capacity.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

19

Siemens Building Technologies Fire Safety

17) Expand the TZC and label its first three Telephone Circuits 1st Flr Tel Ckt, 2nd Flr Tel Ckt and Annex Tel Ckt. For each circuit, set the property Device Usage to Telephone Circuit. The remaining circuits will not be used. 18) A second ZAC and ZAC Backup are needed in the 1st floor enclosure to support the Annex Voice components, since the Annex will not have a full enclosure (CAB) of its own. Select the 1st floor CAB-2. Insert and label a CC-2 Card Cage, Voice System Cards - Annex. Under the CC -2, insert another ZAC-40 (Zone Amp Card - Annex) and ZAC-40 Backup (ZAC Backup - Annex). Again, Bulk Amplification Riser Channel must be Not Used on both. Drag both ZAC-40s to the 1st floor DAC for their CAN links. Assign the Annex ZAC Backup to the Annex ZAC. Expand the Annex ZAC-40 and label its Amp Ckt Annex Speakers. Set Speaker Wattage to 20. 19) The Annex LVM / SCM pair will be mounted in a 2place Remote Box. Select the Node element. Insert a REMBOX-2; it will appear at the bottom of the Physical View. Label it Annex REMBOX Annex Office. For its property Power Supply PSC Address, enter 1, the HNet Address of the 1st Floor PSC which will power the REMBOX components. 20) To save effort, you will copy the 1st floor LVM and SCM for the Annex. Select the 1st Floor LVM and SCM, hold down the Ctrl key, and drag them to the REMBOX Inner Door to copy them. Select the REMBOX and use Find/Replace Text to change the Annex component labels from 1st Flr to Annex. Afterward, change the first SCM Switch label to Annex to 1st Flr. 21) The Telephone Group switches on the Annex SCM are not applicable, since there is no FMT in the Annex. Change the Telephone Group switch Usages and labels to Annex Alarm ACK, Annex Supervisory ACK and Annex Trouble ACK. These Acknowledgement switches will be useful, since an Annex user will not have a PMI with which to perform these functions. 22) The Annex LVM and SCM require CAN hosting by a DAC, which cannot be mounted in a REMBOX. Assign the LVM and SCM to the 1st floor DAC to assign CAN addresses to them. To do this over the long distance in the Physical View, select both elements, copy them (Ctrl + C, ), right-click the DAC, and select Assign To in the menu. Note: Communication between the DAC and the REMBOX is enabled by the RNI Remote Network Interface under the REMBOX.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

20

Siemens Building Technologies Fire Safety

23) Taking advantage of the floor plan similarities, you will now add Voice to the Main Building 2nd Floor by copying the Annex Voice elements. Delete the current Inner Door on the 2nd Floor CAB. Select the REMBOX Inner Door, hold down the Ctrl key, and drag it to the 2nd Floor CAB. Select the copied door, and use Find/Replace to change all occurrences of Annex to 2nd Flr. 24) Expand the SCM. Similar to the Annex SCM, change and re-label its Telephone Group switches to Alarm, Supervisory and Trouble Ack. Change the Switch 3 label to 2nd Flr to Annex. 25) Copy the 1st Floor Voice Card Cage (CC-5) to the 2nd Floor CAB. Expand the copied Card Cage and delete the TZC, since only one telephone system host is required. Select the Card Cage, and use Find/Replace to change all occurrences of 1st to 2nd and Primary to Backup. 26) Assign the LVM, SCM, and ZACs to the 2nd Floor DAC. Assign the ZAC Backup to the ZAC. 27) Select the 2nd Floor DAC. Uncheck the property First DAC and check Last DAC, since this is the second and last DAC on the DAC network. (This is necessary for this Style 4-wired system, but not for Style 7.) For the properties Tones File Name and Message File Name, selected the same PMFs as used for the 1st floor DAC. 28) Delete the Emergency Page PreRecorded Message, since page-type channels do not have backup sources. Change the Evac and Alert Message addresses to 1 and 2. Select the same .wav files for Audio Source Wave Filename as for the 1st floor. These Messages will become the backup sources for their respective channels. Part 2-2: Group Voice Elements (Geographic View) 1) 2) Open and fully expand the Geographic View, while leaving the Physical View open as well. Add a Zone, Annex Components, under the Annex Floor-level Group, with the Detail Message Annex Voice components supported by 1st Flr Enclosure. Select the Annex map for the Zones Group Event Map Name. Assign these elements to their respective Components Zones: DACs, Amp Ckts, Tel Ckts. The other Voice elements (CAN modules) can not be added to Groups. Save the project.

3)

4)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

21

Siemens Building Technologies Fire Safety

Part 2-3: Set Up Voice Controls (Control View) 1) 2) Open the Control View, , leaving the Physical and Geographic displayed as well. Select the Project element in the Control View, and insert the element System Audio Channels. Its property Audio Distr. Topology must be set to Distributed, since this is a distributed-amplifier system using ZACs. For this 3-channel Voice system, insert three Audio Channels under System Audio Channels. Set these channels up as follows:
Channel ID Emergency Page Evac1 Alert1 Channel Type System Channel System Channel System Channel Channel Quality Improve, 11 kHz (8 BW) Standard, 11 kHz (4 BW) Standard, 11 kHz (4 BW)

3)

The Channel Quality BW figures represent bandwidth, the amount of resources the channel will consume. A total of 16 BW is available. For each channel, set Channel Type to System Channel. The tones and messages for this system will come from the 1st floor DAC, with similar PMFs and .wavs stored in the 2nd floor DAC as Evac and Alert channel backups. If Local Channel were selected, each floor would use the messages in its own DAC. 4) Drag the Prerecorded Messages, under the 1st- and 2nd-floor DACs, from the Physical View to their respective Audio Channels in the Control View. For example, assign the Evac messages (primary and backup) to the Evac1 channel. Page-type channels do not allow backups; therefore, assign only the message Emergency Page Tone on the 1st floor DAC to the Emergency Page channel. Select each of these Prerecorded Message links (Device Audio Sources). Check the property box Back Up Audio Source for each backup source. Make sure it is unchecked for each primary source. That is, each Prerecorded Message on the backup DAC on the 2nd floor must be checked as a backup source. The Emergency Page channel source, Emergency Page Tone, is a primary source and therefore unchecked. From the Physical View, drag the Node element to the Project element in the Control View, to create the Control for FireFinder XLS Node 1 link.

5)

6)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

22

Siemens Building Technologies Fire Safety

7)

Select the Control for Node link. In the Detail View, check Telephone Tones Enabled so that emergency phone users will hear call-status tones. Set Emergency Page Pre Tone Duration to 3 so the Prerecorded Message Emergency Page Tone will play for 3 seconds before a live page starts. Convenience Page Duration can be left at 0, and Voice Zone Coded System must be unchecked, since both are not used. Check Telephone Through Reset so that panel resets will not cut off conversations. Check all Strobe During boxes so that strobes will flash during Voice operation. (Note that strobes will flash when an Emergency Page is made, even without an Evac or Alert state.) Set Speaker Group Default to Emergency Page so pages play over those speakers receiving the Emergency Page channel, when no channel is activated. Uncheck all Auto Page properties so that the user is required to select the Evac or Alert channel before a page will play over that channel. Select the Control for Node link. Insert and label a Command Station, 1st Flr CMD Sta Lobby. Command Stations are sets of Voice, Fan and/or Damper controls. This Command Station will be made up of the FMT phone, LVM mike, and the LVM and SCM switches on the 1st floor CAB door. Drag all three Floors from the Geographic View to the Command Station. The Groups include Voice elements that this station will operate.

8)

9)

10) Select the 1st flr Command Station. Check the property Master Command Station so that this station by default has system access, and a user at another station must initially request access from the station in control by pressing the request button on the requesting station. 11) Copy, paste and re-label this Command Station to create the 2nd floor and Annex stations. For all stations, check Access Control Required, as well as the Access Required properties that apply to this system: Access Reqd for Emergency Page, Evac, Alert and Telephone. 12) Drag each Speaker Group SCM Switch from the Physical View to the Control View, to its respective Floor under its respective Command Station. Repeat this process for the Telephone Group SCM Switches (1st floor Command Station only). Each switch will activate the Group items that match its Usage, and ignore all others. 13) For each floor, drag all LVM switches and all remaining SCM switches directly to that Floors Command Station. These switches apply directly to the operation of the Command Station itself.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

23

Siemens Building Technologies Fire Safety

14)

Drag each LVMs MIC from the Physical View to the Control View, directly to its respective Command Station. For the 1st floor Command Station, assign the Master Phone as well. Save the project. Manual Voice controls are complete. (Previous page; the Annex station, not shown, is similar to the 2nd floor station.)

15)

Part 2-4: Program Voice Functions (Function View) 1) Automatic Voice operations will now be added. Open the Function View, with the Geographic and Physical Views open as well. The system must be programmed so that during an Evac-level condition, the Evac message automatically plays over the affected speaker zone, or an Alert message automatically plays during an Alert condition. This is readily set up using the Speaker Control Function. Insert and label a Speaker Control Function under the Logic Functions for Node element, 1ST FLR SPEAKERS. Drag the OR function 1ST FLR EVAC to the Evac 1 input, the 1ST FLR ALERT OR to Alert 1, and the 1st Floor Group to the output. When the EVAC OR is true, the Evac1 channel will play the EVAC message. The Alert1 channel will work similarly, unless the higher-priority Evac1 channel is active. The Emergency Page channel (Local Emg Page input) is strictly manual and hence not used here. 3) Set up similar Speaker Control Functions for the 2nd Floor and the Annex. Save the project.

2)

Part 2-5: Check and Compile the Project 1) Click to run a compile-check of the project. This should result in the following error: the 1st Floor CAB-2 requires additional power to drive the new Voice components. Select the CAB-2. Insert and label a PSX, Power Supply Extender - 1st Floor, to supplement the PSC. (Only one PSC is allowed per enclosure, with a maximum of three PSXs.) Another check will show the 1st flr CAB-2 is now too small for the additional components. Select the CAB-2. Change it to a CAB-3 using Edit > Find/Replace Tree Node. You will need to re-enter the label, 1st Flr Enclosure - Lobby. Run the check again. There should be no further errors. The project can now be compiled.

2)

3)

4)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

24

Siemens Building Technologies Fire Safety

PHASE 2a: Using Bulk Amplification for Voice The Voice setup just presented consisted of a Distributed amplification system, in which each amplifier (ZAC) was dedicated to a speaker zone. For a system larger than this simple example, this approach can provide great flexibility, but also may require a significant amount of hardware. A Bulk Amplification setup allows the use of only one or two amplifiers to drive speakers over multiple zones. The tradeoff is that only one or two channels can be played at the same time within that system. While all Audio Channels can be accessed, if the system is so designed, only the two highest priority channels will play if three or more channels are requested. For example, if a two-channel bulk system is broadcasting over the Evac1 and Alert1 channels, and an Emergency Page is made, the Alert1 broadcast will be suspended during the page. In a two-channel Bulk Amplification setup, speakers are connected to two risers, Channel A and B. Each amplifier (ZAC or ZAM Zone Amplification Module) is associated with a ZIC Output Circuit in order to be switched in and out of its riser. In the Zeus Geographic View, each ZAMs Amplifier Circuit is linked multiple times, once to the each applicable Group in the system, along with the specific ZIC Output Circuit for that Group. The following procedure shows the steps relevant to converting the Acme Voice setup, which uses two ZACs in a Distributed Amplification scheme, to a Bulk Amplification scheme using two ZAMs, two ZAM Backups and one dedicated ZIC in the Lobby enclosure. The system will be consolidated to minimize enclosure sizes and the number of components. 1) Open the Physical View. In the 1st floor CAB-3, delete the 2 ZACs and 2 ZAC Backups, move the TZC and DAC to the CC-2 card cage, and delete the Voice CC-5 card cage. Change the CC-2 label to read Voice System Cards - 1st Flr. In the 2nd floor CAB-2, delete the ZAC and ZAC Backup. Move the DAC to the Fire CC-5 card cage. Delete the Voice CC-5. Change the Fire CC5 label to Fire and Voice Cards - 2nd Flr. Select the Node and insert a CAB-1. Change the Enclosure Number to 2 and label it 2nd Flr Enclosure - Hallway. Delete the PSC in this CAB -1. Expand the original 2nd flr CAB-2 and move its components to the CAB-1. Delete the CAB-2. This completes the system consolidation. Select the 1st floor CAB. Insert and label a ZAM and ZAM Backup, Channel A Zone Amp Module and Channel A ZAM Backup. Insert another ZAM/ZAM Backup pair, labeled Channel B. Drag the ZAMs and ZAM Backups to the 1st floor DAC for their CAN links. Drag the ZAM Backups to the ZAMs for the backup links. Set property Bulk Amplification Channel Riser to Channel A on the Channel A ZAM and ZAM Backup. Use Channel B for the other pair. Expand the ZAMs and label their Amp Ckts Channel A Speakers and Channel B Speakers. For each, set the property Speaker Wattage to 100, the combined wattages of the 1st floor, 2nd floor and Annex speakers.

2)

3)

4)

5)

6)

7)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

25

Siemens Building Technologies Fire Safety

8)

The ZAMs will be physically wired to a new ZIC, which will perform the switching of the ZAMs into the Channel A and B risers. Insert and label this ZIC, Speaker Circuits, under the CC-5 in the 1st floor CAB.

9)

Insert four Out Ckts under the new ZIC. Label the first three 1st Flr Speakers, 2nd Flr Speakers and Annex Speakers. For all four, set the property ZIC Circuit Usage to 25V Speaker. The fourth Out Ckt is not used directly. However, Speaker-usage Out Ckts must be set in pairs, Circuits 1 and 2 or Circuits 3 and 4. If Circuit 4 were not inserted and set to Speaker usage, an error would result during Check or Compile.

10) Open the Geographic View and leave the Physical View open. Expand the Project element until the Zone Groups are visible. 11) From the Physical View, drag the Amp Ckts under the ZAMs to all three Components Zones in the Geographic View. Do this so that the 1st Flr, 2nd Flr and Annex Components Zones each include links to both the Channel A and B Amp Ckts. (Note: The Amp Ckt is the only element that can be assigned to multiple Groups in the Geographic View. This is done only for Bulk Amplification.) 12) From the Physical View, drag each of the first 3 Out Ckts under the Speaker Circuits ZIC to its respective Components Zone in the Geographic View. Do this so that the Out Ckt labeled 1st Flr Speakers is assigned to the 1st Flr Components Zone, etc. Do not assign the fourth Out Ckt. 13) Open the Control View. Expand the Project element. Select System Audio Channels. In the Detail View, set Audio Distribution Topology to Bulk and Bulk Amplification Channel Count to Two. Close the Control View. The Function View does not need modification. 14) Run Check, . If errors or warnings appear, make the necessary corrections . 15) Save the project.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

26

Siemens Building Technologies Fire Safety

PHASE 3: Adding Fan Control This section shows how fan control would be added to the original Acme fire/voice system. Both manual fan controls, using a Fan Control Module at each Command Station, and automatic controls are shown. The requirements for this addition are as follows: - The Main Building floors and the Annex each have an air handler unit (AHU) with fan and indication switch. - Each AHU is actuated and monitored using an HTRI-R Addressable Interface with Relay on existing device loops. - An alarm on a Main Building floor or in the Annex shuts down its AHU. - AHUs may also be shut down manually at each Command Station, using Fan Control Modules (FCMs). - Access control is required for manual fan control. 1) In the Physical View, select the Inner Door of the 1st floor CAB. Insert and label an FCM, Fan Control Module - 1st Flr. Expand the FCM, and label its first 3 switches 1st Flr AHU Off, 2nd Flr AHU Off and Annex AHU Off. The other switches are not used. Drag the FCM to the 1st floor DAC for its CAN link. Make sure each FCM switch property Device Usage is set to Fan so the switches operate fans only, and the switch LEDs to properly indicate fan status. Make sure the property Active is checked. Repeat this process for the 2nd floor CAB and the Annex REMBOX. For the Annex FCM, use the 1st floor DAC for the CAN link. Select the 1st floor DLC. Insert and label an HTRI-R, 1st Flr AHU Control. The HTRI-R consists of a supervised switch input and a separate relay. The input will indicate AHU fan operation (via a switch on the fan itself) to the 1st floor FCM. The relay controls the power to the AHU fan. For the HTRI-R property Switch 1 Base Language Custom Message (label), enter 1st Flr AHU Monitor Switch. For the Relay label, enter 1st Flr AHU Actuation Relay. These items and labels do not appear in the Physical View tree, but may be displayed on the PMI. Set the Switch 1 Display Category to Fan. Set Switch 1 Usage to Fan Monitor On and Relay Usage to Fan Actuator Off. Copy and paste this HTRI-R under the same DLC (1st Flr). Change the element, switch and relay labels from 1st Flr to Annex. Paste another copy of the HTRI under the 2nd flr DLC. Change its labels from 1st Flr to 2nd Flr. (In each case, Find/Replace Text can be used to quickly change all three labels: element, switch and relay.) Open the Geographic View. Assign each HTRI-R from the Physical View to its respective Components Zone.

2)

3)

4)

5)

6) 7)

8)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

27

Siemens Building Technologies Fire Safety

9)

Keep the Physical View open. Open the Control View.

10) In the Control View, select each Command Station and check its property Access Required for Fans. 11) Under the 1st floor Command Station, assign each switch from the 1st floor FCM to the respective Group it will control. The FCM switches now address the HTRI-Rs controlling the AHU fans. 12) Repeat this process for the 2nd floor Command Station and FCM, then for the Annex. Manual fan control is now set up. 13) Close the Control View. Open the Function View and the Geographic View. 14) Select the Logic Functions for Node link. Insert and label an OR Function, 1ST FLR AHU. 15) From the Geographic View, drag the 1st Floor Group to the OR input. Select the new input link. Set the property Input Criterion to Active. The OR will become true when any part of the 1st floor goes into alarm. Invert must be unchecked. 16) Drag the 1st Floor Components Zone to the OR output. Select the new output link. Set the property Output Selector to Fan. When the OR becomes true, the Fan-usage components on the 1st floor (the HTRI-R) will be activated. 17) Repeat this process for the 2nd floor and Annex. An alarm on a floor or in the Annex will automatically shut down the AHU fan for that zone. The automatic fan controls are now programmed. 18) A compile check should indicate no errors. Save the project.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

28

Siemens Building Technologies Fire Safety

PHASE 4: Networking Multiple Systems This section shows how multiple Fire Finder XLS Nodes and other Siemens systems would be added to and networked with the original Acme fire/voice system. The requirements for this addition are as follows: A third building (Finance Building) is added to the fire protection plan. A FireFinder XLS Node is added to the Finance building. The Finance buildings shipping area currently has an MXL-V for Fire and Voice protection. Network the new FireFinder XLS and the existing MXL-V to the Main Buildings XLS-V. Events in the Main building must send Alert signal to the Finance building. Events in the Finance building will trigger an Alert message in the Main building and the Annex.

Part 4-1: Add FireFinder XLS Node (Physical View) 1) Open the completed Acme FireFinder Voice system configuration (for the Main Building and Annex). Close all views except the Physical view. Select the project. Make sure that the XNet Networked Configuration is checked at the bottom of the Detail View Properties Tab. Select the Node element. Set the XNet Address (Top of the Detail View Properties Tab) to 1. This will be the First Node in the Multiple System Configuration. Note: Set the XNet address to 1 on the PMI (Person Machine Interface) using the address switch. Set Switch 4 of S17 to ON; set Switches 1-3 of S17 to OFF. Refer to the PMI Installation Instructions, P/N 315-033070, for further information on setting the PMI to XNet Mode. 3) Insert a CC-5 card cage. Move the Speaker Circuits ZIC-4A from the first CC-5 and the modules from the CC-2 to the new CC-5. Label the new CC-5 as Voice System Cards 1st Flr. Delete the CC-2. Select the CC-5 Fire System card cage under CAB-3 1st Floor Enclosure Lobby. Insert and label a NIC-C (XNet) as Ntwrk Interface (XNet) Main Bldg. This NIC-C Card will communicate to other Siemens systems using XNet. Select the Node element. Insert and label a Pseudo Module as Pseudo Module Main Bldg. Insert 3 Pseudo Devices to the Pseudo Module and label them Pseudo Alarm Main Bldg. 1st Flr, Pseudo Alarm Main Bldg. 2nd Flr, Pseudo Alarm Main Bldg. Annex, respectively. Change the usage of each Pseudo device to Status Only. Note: Pseudo modules and Pseudo devices are not physical modules and devices. They are generally used for logic function purposes only.

2)

4)

5)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

29

Siemens Building Technologies Fire Safety

Part 4-2 Add Finance Bldg. FireFinder XLS Node 1) With the Project element selected, insert a FireFinder XLS Node under it by clicking Insert > FireFinder XLS Node. Select the FireFinder XLS Node element in the Physical View. Click the Properties tab in the Detail View window. Click the property field Base Language Cust. Message, type Acme Mfg Co. Finance Bldg., and press the Enter key. This becomes the Node elements label in the Physical View, and the title shown on the PMI control panel. With the Detail View Properties still selected, notice that Zeus has already assigned XNet Address 2 for the newly inserted XLS in our XNet system. Toward the bottom of the Detail View, set Battery Capacity Factor to Total Amp x 24 Hours, and Battery Capacity Reserved to 25%. Click the box next to the node property FireFinder XLS Map Names. The resulting dialog allows you to select the floor plans that can be shown on the Nodes PMI (control panel) to display event locations. Select the Acme example maps already in Zeus Acme Floor 1, Floor 2, Annex and Finance and click Add to make these files available to this Node. Close the dialog. Note the property On Site Contact Name/Phone. This information is prominently displayed on the PMI when the user requests event details. This is similar to what was done in the previous Fire System for the Main Building. Note: Expand the Node element by clicking the small plus sign next to it. The elements History Log and System Flags, which are part of the Node element, appear. 6) Select the FireFinder XLS Node element and insert the new CAB-2 element under it. Insert > CAB-2. Change the CAB-2 base language custom message to read Finance Bldg Lobby. Zeus has already inserted a PSC-12 under the CAB-2; Expand the CAB-2 by clicking the small plus sign to the left of the CAB once to show the PSC. Expand the PSC. The two fixed PSC Relays are already under the PSC. Label the PSC Power Supply - Finance Bldg, and the PSC relays 1) Common Alarm - Finance Bldg and 2) Common Trouble - Finance Bldg Set the property Battery Size to 31 AH.

2)

3)

4)

5)

7)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

30

Siemens Building Technologies Fire Safety

8) 9)

Select the CAB-2 and insert its inner door: Insert > Inner Door. Select the Inner Door and Click Insert > PMI to add a PMI (PMI Person-Machine Interface). Label the PMI Control Panel Lobby Finance Bldg. Set the PMIs Display Group Level Display property to Device/Primitive, and MORE INFO View to Map so a graphical map will be first displayed when MORE INFO is pressed.

10) The project requires two Function Key operations for manual system testing. On the PMI screen, these keys are listed on the Function Key Screen; a user will press these graphical buttons on the touch screen to run and stop tests. Right-click the PMI, and select Insert > Function Key from the resulting pop-up menu. A Function Key is inserted as a child of the PMI. Add one more function key, and label the Function Keys Test Finance Bldg and STOP. You will set up the logic to program these keys a little later. 11) Select the PMI again. Click the box next to the PMIs PMI Event Map Name 1 property. The resulting dialog allows you to mark the PMIs position on one or more of the map files selected for this Node. For Select Bitmap, choose the Acme Finance map. Drag the blue dot to the desired location in the Lobby. When a Finance Building event map is displayed on the PMI, a You Are Here icon is added at this mark. Note that you can click and drag it to adjust its position. 12) Add a five-slot CC-5 card cage as a child under the CAB-2 enclosure. Change the CC-5 custom message to Finance Building. 13) Select the CC-5 and insert a NIC-C (XNet) under it. The NIC will communicate with the other Node in the system. Label the NIC Finance Bldg. 14) The Finance Building requires three output circuits to drive audibles, strobes, and the separate any-alarm default audible required by regulation. Insert a ZIC4A Zone Indication Card under the CC-5. Insert three Out Ckts under the ZIC. Label these Finance Bldg Audibles, Finance Bldg Strobes and Finance Bldg Default Audible.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

31

Siemens Building Technologies Fire Safety

15) In the Out Ckt Detail View, set the property ZIC Circuit Usage to NACCoded for the Audibles and Default Audible circuits, and Strobe Synch for the Strobe circuit. (You will code the audibles later.) On all Out Ckts, check the Silenceable box and set Wiring Type to Class A. 16) Insert a DLC (Device Loop Card) under the CC-5. Label it Device Loop Finance Bldg. Select the DLC, insert an HFP detector and label this Lobby Detector Finance Bldg. Under the DLC, insert and label an HMS-S pull station (Lobby Pull Sta. Finance Bldg.). Check the property Intelligent Environmental Compensation (IEC) for the HFP11 and set the Application Specific Detection (ASD) setting to Office. 17) Duplicating these two new elements (HFP-11 and HMS-S) will populate the device loop required for our example. Click the HFP, hold down the Shift key, and click the HMS to select both devices. Copy these elements to the Windows Clipboard. (Use Ctrl + C, Edit > Copy, or .) Select the DLC. Click Edit > Paste Special. In the resulting dialog, set Multiple Paste to 4 and click OK. Four more HFP / HMS pairs are inserted under the DLC, one pair for each room on the Finance Building protected by XLS Node 2. 18) Select the DLC. In the Detail View Elements tab, use the table to change the elements as shown, filling in the Base Language Custom Message with the individual names. Note the amount of work that has been saved by using Paste Special to generate and label repetitious elements. 19) Insert a CDC-4 (Conventional Detector Card) and label it Conventional Det. Card Finance. The CDC-4 is a module that allows conventional smoke detectors to be used with the Fire FinderXLS system. Notice that when a CDC-4 card is inserted into a card cage, all 4 CDC zones will be automatically inserted under the module. Only the First two Zones will be used in our example. Label them Finance Bldg Lobby and Finance Bldg Hall. 20) Select FireFinder XLS Node 2 and insert a Pseudo Module at module address 6. Insert a Pseudo Device at address 1 under the Pseudo Module. Change the devices Base Language Cust. Message property to Pseudo Alarm Finance Bldg. Set Device Usage to Status Only. This Pseudo Device will be used for logic in Part 4-4.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

32

Siemens Building Technologies Fire Safety

Part 4-3: Set Up Groups in the Geographic View 1) Click the Geographic View button, , to insert that View. Keep the Physical View open. You will now organize the devices in the Physical View of Node 2 into Groups that are used for creating system logic (Function View) and determining what graphics and messages the PMI displays during an event. 2) Select the Project element in the Geographic View, and look at its Properties Tab in the Detail View. The five Group levels (1-5) and their default names (Campus, Building, Floor, Area, Zone) are displayed. Note that you can change the names of the Group levels here to best suit your particular project. Keep these default labels for this example project. Insert a Floor (Level 3) element under the Geographic Views Project element. Label this element Finance Bldg. Under the Finance Building insert 6 Zones (Level 1), one for the CDC Zones and for each room. Label these CDC Zones Finance Bldg., Lobby Finance Bldg., Hall Finance Bldg., MensRm Finance Bldg., WomensRm Finance Bldg, and CnfRm Finance Bldg. Assign the Finance Building devices in the Physical View to their corresponding Groups. For example, select the Lobby devices, then drag and drop these onto the Zone Lobby. Note that links of the elements are placed under the Zone; the device icons are replaced by light-yellow boxed arrows. Try using some of the features we discussed in previous sections like clicking the right mouse button to make some of the assignments. Click Assign to Here for each link. Select a Zone on the Finance Building and examine its properties. Many of these determine what information will be displayed on the PMI during an event. On the PMIs Alarm Details Screen, the properties Base Language Detail Message, Fire Service Equipment Icon Names, and Hazards / People Icon Names are shown. On the PMIs Map Screen, the Group Event Map Name graphic and marked position on that graphic specified by Group Location is displayed. If you need information or help on any of this section, select that section and press the F1 key for Zeus Help.

3)

4)

5)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

33

Siemens Building Technologies Fire Safety

6)

Select each of the Zones under the Finance Building Group and click the button on the right of the Group Event Map Name field. In the resulting dialog, use Select Bitmap to select the Acme Finance map for each zone. Mark each Zones position on the map by clicking in the room the current Group represents. Setup Fire Service Equipment Icon Names and Hazards / People Icons in the Detail View. That allows you to select icons that will be displayed in the PMIs Alarm Details Screen, which will aid firefighters in determining resources and hazards in the affected Zone. The Hazards / People dialog includes a feature for generating custom 3-digit HazMat icons. You can press the F1 Key to get the Zeus Help feature, which will provide more details.

7)

Part 4-4: Setup Logic Functions For Node 2 1) Click the Tool bar button, to open the Function view window. If the Physical and Geographic Views are closed, open them as well. Click the Arrange button, , to make all Views the same width. Expand the Function View project element to see the automatically added link, Logic Functions for FireFinder XLS Node 2. Notice that there is one Logic Function link for each FireFinder XLS Node installed in the Physical tree. For the Logic Function for FireFinder XLS Node 2, we will need to set up the default system audible similar to Part 1-4, steps 1-3. First, we will select the sounds for NAC audibles. Click on Logic Function for FireFinder XLS Node 2 on the Function view, select Steady Audibles, Temporal / Uniform and March Time 30 SPM for the properties Audible Control Function Priority 1, Audible Control Function Priority 2, Audible Control Function Priority 3, respectively. These settings correspond to the required project alarm, alert and recall states. 4) To create the default audible, insert an Audible Control Function under the Logic function for FireFinder XLS Node 2. Label this function Default Audible Finance Bldg. Enter Audible Control Function for the Comment property. From the Physical View of FireFinder XLS Node 2, drag and drop the System Flag element (directly under the Node) onto the functions Priority 1 input in the Function View. Select the resulting link. Set the property Flag Name to Any Alarm.

2)

3)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

34

Siemens Building Technologies Fire Safety

Drag and drop the ZIC Out Ckt at address 2:3-3 Notification Apps Finance Bldg. from FireFinder XLS Node 2 in the Physical View to the output list of this function. With this logic, any alarm event in the Finance Building will cause the ZIC-4A default audible to produce a steady tone. 5) Similar to the logic for Node 1, we will also use the PMIs touch screen graphical buttons to test the logic for Node 2. We will use function key F1 to test the logic of the function EVAC Finance Bldg. Insert a D-Latch to Logic Functions for Node 2. Label it Test Finance Bldg. Click on the Test Finance Bldg D-Latch and drag it to the Data input. Select the resulting link, move the focus to the Detail view and check the Invert property. Drag the Function key Test Finance Bldg. from the Physical View of FireFinder XLS Node 2 onto the clock input. This Function Key will now cause the D-Latch output to become true at the first touch, then toggle between false (off) and true (on) with additional touches. Insert Function Key Stop from FireFinder XLS Node 2 to the Clear input of D-Latch. At the key press it will reset the D-latch output to false (off). 7) We will also set up this system so that an Alarm or Function Key press will sound an Evacuation signal at one location and an Alert at another location. To program this behavior, insert an OR Function under Logic functions for FireFinder XLS Node 2. Label it Evac Finance Bldg. Enter Priority 1 Finance Bldg. for the comment. Drag and drop the following inputs to the input of this function: Finance Building and Test Finance Building. Leave the output list empty as this function will be the Priority 1 input of the next Audible Control function that we are going to add to this node. D Latch in Toggle/Latch Application:

6)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

35

Siemens Building Technologies Fire Safety

8)

Insert an OR function. Label it EVAC Finance Bldg. Alert Main Bldg. Drag the function EVAC Finance Bldg. to the input of this function. Drag the Pseudo point at address 2:6-1 in the Physical View of FireFinder XLS Node 2 to the output of this function. Insert another Audible Control function to the Logic function for FireFinder XLS Node 2. Label it Finance Bldg and insert NAC CKTs for the comment. Drag and drop the OR Function EVAC Finance Bldg. to the Priority 1 input. From the physical tree, drag the ZIC-4A circuit Finance Bldg Audibles and Finance Bldg Strobes, 2:3-1 and 2:3-2 respectively, to the output list.

9)

Part 4-5: Setup Inter-panel Logic Functions 1) We are now ready to setup inter-panel logic for our XNET system example. For this we will be using Pseudo Devices under both FireFinder XLS Node 1 and Node 2. The logic written will send an Alert signal from one XLS node to the other XLS node when an event occurs. First we will set up Node 1 so that an event in Node 2 will cause an Alert signal by dragging and dropping the Pseudo device at address 2:6-1 from the Physical view FireFinder XLS Node 2 to the input of the OR functions 1st Floor Alert, 2nd Floor Alert and Annex Alert on Node 1. Now, we will set up for events on Node 1 to signal an Alert on Node 2. To do this we will add three new OR functions to Node 1. 3) Select the Logic Function for FireFinder XLS Node 1. Add three OR functions. Label them 1st Flr Evac Main Bldg., 2nd Flr Evac Main Bldg, and Annex Evac respectively. These three new functions will be used to alert the Finance building if an event occurs on any floor of the main building or annex. Give each of these OR functions the comment Finance Bldg Alert. Expand the 1st Flr Evac Main Bldg OR function. Select and drag the function labeled 1st Floor Evac to the input of this function. Select and drag the Pseudo point at address 1:18-1 on Node 1 to the output of this function. This pseudo point will be used to signal the main buildings evacuation events at the Finance building.

2)

4)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

36

Siemens Building Technologies Fire Safety

5)

Expand the 2nd Flr Evac Main Bldg. OR function. Select and drag the function labeled 2nd Floor Evac to the input of this function. Select and drag the Pseudo point at address 1:18-2 on Node 1 to the output of this function. This pseudo point will be used to signal the main buildings second floor evacuation events at the Finance building. Expand the Annex Evac OR function. Select and drag the function labeled Function Annex Evac to the input of this function. Select and drag the Pseudo point at address 1:18-3 on Node 1 to the output of this function. This pseudo point will be used to signal the annex buildings evacuation events at the Finance building. For Node 2 to sound an alert signal when events on Node 1 occur, we will need to bring those Pseudo points on Node 1 into Node 2. Select Node 2 and insert an OR function. Label it Alert For Event In Main Bldg. Drag Node 1 Pseudo point addresses 1:18-1, 1:18-2 and 1:18-3 from the Physical View of FireFinder XLS Node 1 to the input of this function. Leave the output empty. Drag the OR function Alert For Event in Main Bldg to the Priority 2 input of the Audible Control function Finance Bldg. NAC CKTs. This function will signal an alert audible on Node 2 ZIC circuits 2:3-1 and 2:3-2. Save the project. Compile and transfer the configuration file to both nodes.

6)

7)

8)

9)

The inter-panel logic setup just presented between a FireFinder XLS Node and a FireFinder XLSV Node shows how event messages are transmitted over XNET from one node to the other. Alarm events in the Main building and Annex will sound an Alert audible signal in the Finance building. Alarm events in the Finance building will sound an alert audible signal in the Main building and Annex. Note: Input devices and pseudo points can be used as external logic input references via XNet. This completes our Setup for inter-panel logic between the two Siemens FireFinder systems.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

37

Siemens Building Technologies Fire Safety

Part 4-6: Adding Other Siemens Systems Siemens MXL Nodes and NCC (Network Communication Center) Nodes can be added to our multi Node FireFinder XLS System. 1) In the Physical view, select the Project and insert an MXL Node by right clicking the mouse or by clicking Insert > MXL Node. Change the Base Language Cust. Message to Shipping Area Finance Bldg. This will be our XNet Node 3 in the multi Node System. A Networked Command Center (NCC) will also be installed at the Main building as a central command station for our multi Node system. With the Project element selected, insert an NCC Node under it by clicking Insert > NCC Node. This will be our XNet Node 4 in our Multi Node system. The Physical location of the NCC will be in the Main building. Change the Base Language Cust. Message to Main Building Command Station. The NCC Node will monitor and display all the events from FireFinder and MXL. Run Check, . An error will indicate that the Finance Building cabinet needs more Battery Capacity. Expand the CAB-2 and select the PSC-12. In the Properties tab, change the battery size from 31 AH to 100 AH. Run Check again. 3) In addition to configuring the system in Zeus, the MXL Node must also be configured in the CSG-M. Convert the MXL standalone node to a network node. Insert the MXL into the network map at XNET address 3. In the CSG-M, insert XLS nodes 1 and 2 and the NCC into the MXL network map at addresses 1, 2 and 4 respectively. Compile the configuration and transfer it to the MXL panel. Note: Either an NCC or an MXL with a global MKB MUST be used to satisfy the requirements of a 72A HIGH RISE SYSTEM.

2)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

38

Siemens Building Technologies Fire Safety

Phase 5: Connecting FireFinder XLS to a Central or Remote Station Note: The MDACT is used in XLS systems where point identification of alarm, supervisory, status and trouble events is required at Central or Remote Stations. In this example, we will set up XLS Node 2 on the Finance building to report a Dialer Group #3 event to the Central or Remote station if any event occurs on the Finance building lobby pull station or Finance building hall detector. Any events on all other devices will be reported as Dialer Group #2 to the Central or Remote station. In the event the dialers buffer is full, the MDACT should still queue the alarm messages. 1) Open the Physical view (if it is not visible) and select the Project element. In the project Detail View, select the Properties tab. Set the Project element property MDACT Dialer Mode to Contact ID (Ademco). Note: MDACT messages can be reported in two different formats: Contact ID Format and SIA Format. For our example, we will be using Contact ID format. 2) Select the CAB element in FireFinder XLS Node 2 where the MDACT will be installed (1 CAB-2 Finance Bldg. Lobby), then click on Insert -> MOM-2. Label it Card Cage, MOM-2. Insert an MDACT into the MOM-2. Notice that an XMI is automatically inserted at the same time. (An XMI is required when using MDACT with the XLS system.) Select the MDACT, then click on Detail View, Properties tab to give the MDACT the Custom Message Finance Bldg Lobby. Note that the Dialer Model/Manufacturer property is set to DS9602 / DS Inc. Because we want to queue the alarm message in the event the dialers buffer is full, click on the property Force Alarm to check it. Set up the Group in Control view. Open Control View by clicking on the tool bar Control View icon or by selecting View -> New View-> Control View. Select the Project element under Control View and Insert -> Digital Dialer Groups. Notice when you expand Digital Dialer Groups that Default MDACT Group #2 is already inserted and cannot be deleted. Note: By default, any devices that are not assigned to specific user-defined Dialer groups are assigned to Dialer Group #2. The user can create Group numbers from 3 to 999 for Contact ID format and from 3 to 9999 for SIA format.

3)

4)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

39

Siemens Building Technologies Fire Safety

5)

Insert another Group under Digital Dialer Groups. In the Detail View properties of the inserted group, type Finance Bldg. Lobby for Base Language Cust. Message and 3 for MDACT Group ID. Verify that there is a check in the box Report To Central Station because we want this Dialer Group to be reported to the Central Station. Drag and Drop the HMS at address 2:4-2 (Lobby Pull Sta. Finance Bldg) and the HFP-11 at address 2:4-3 (Hall Detector Finance Bldg) from the DLC Card under Physical View of FireFinder Node 2 to MDACT Group# 3 under Control View. These two devices belong to Group 3 of the Digital Dialer Card. The MDACT will report Group #3 to the Central station if any events occur on these two devices. Events on all other devices in Node 2 will be reported as Dialer Group #2. This completes our setup for XLS MDACT.

6)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

40

Siemens Building Technologies Fire Safety

Phase 6: Global PMI

Introduction Up until now, the system has consisted of two XLS nodes - one MXLV and one NCC - networked together. Each XLS node has its own PMI display with control and voice evacuation. The first XLS monitors, controls and annunciates events for the Main Building (2 floors and the Annex building). The second XLS node monitors, controls and annunciates events in the Finance Building. The MXLV node is an existing system in the Finance Buildings shipping area which is now networked to the XLS nodes. The NCC was added in Phase 4 in the Main Building Lobby Area as a main network command center. In Phase 6, we will convert the existing PMIs to global PMIs. The requirements for this addition are as follows: The PMI in the Main Building Lobby must annunciate and acknowledge events from all locations including events in the MXLV at the Finance Building. This Global PMIs scope will be to monitor, control and annunciate events for the Main Building, the Annex and the Finance Building. The PMI in the Finance Building Lobby must annunciate Alarm and Supervisory events from all locations in the XNET network but can only acknowledge events from its own node. Steps to perform: In the Physical view, select the Project Element. On the detail view, set the Project element property NFPA System Type to Local. This property choice used to be Vertical, Horizontal in previous Zeus versions (see Phase 6 Step 1). Select XLS node 1 FireFinder XLS Node Acme Manufacturing Co Local. On the node detail view, select the property GPMI System Display Name. Change the text Multi XNET to Acme Co. Multi XNET Main. This is the Global PMI system name that will display on the Global PMI home screen, navigation menus and report titles (see Phase 6 Step 2).

Phase 6 Step 1

Phase 6 Step 2

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

41

Siemens Building Technologies Fire Safety

Notice that there are two new XLS node properties: Unspecified Node Responding and Node Not Responding Troubles. These two properties by default are set to Display All Nodes. With this setting, this XLS will annunciate all Unspecified Node Responding and Node Not Responding trouble events (see Phase 6 Step 3). Expand CAB3 1st Floor Enclosure-lobby. Expand the Inner Door under this CAB3. Select the PMI under the Inner Door. On the detail view, make sure the PMI property Display Type is set to Display With Control. Click on the PMI property Global PMI to specify that this PMI is a global PMI. Notice that the PMI properties Display Alarm, Display Supervisory Events, Display Security Events, and Display Trouble Events are now selectable and checked by default to denote that this Global PMI will display all events in the system (see Phase 6 Step 4).

Phase 6 Step 3

Phase 6 Step 4

The table below shows which type of event this Global PMI will display:

Event Type Local Events Other Nodes Events

Alarms X X

Supervisory X X

Security X X

Trouble X X

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

42

Siemens Building Technologies Fire Safety

Select XLS node 2 FireFinder XLS Node Acme Mfg Co Finance Bld. On the nodes detail view, select the property GPMI System Display Name. Change the text Multi XNET to Acme Co. Finance Bld. . This is the Global PMI system name to be displayed on the Global PMI home screen, navigation menus and report titles. Click on the button next to the property FireFinder XLS Map File Name to make sure the Acme Finance bitmap files are assigned to this property (see Phase 6 Step 5). Expand CAB2 1st Floor Finance Bldg - Lobby. Expand the Inner Door under this CAB2. Select the PMI under the Inner Door. On the detail view, change the PMI property Display Type setting to Display Only. Check the PMI property Global PMI to specify that this PMI is a Global PMI (see Phase 6 Step 6). Select and check the Allow Local Control property to specify that although this Global PMI is Display Only, it will have full control of its local nodes events. Also notice that the PMI properties Display Alarm, Display Supervisory Events, Display Security Events, and Display Trouble Events are now selectable and checked by default to denote that this Global PMI will display all events in the system. Uncheck the property Display Security Events and Display Trouble Events so that this Global PMI will only annunciate Alarm and Supervisory events from the external nodes. Note that the PMI will always annunciate all event queues in the local node.

Phase 6 Step 5

Phase 6 Step 6

The table below shows which type of event this display only Global PMI will annunciate:

Event Type Local Events Other Nodes Events

Alarms X X

Supervisory X X

Security X

Trouble X

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

43

Siemens Building Technologies Fire Safety

Phase 6 Step 7a

Phase 6 Step 7

Click the box next to the PMIs property PMI Event Map Name 1. The resulting dialog allows you to mark this PMIs position. For Select Bitmap, choose the Acme Finance map. Drag the blue dot to the desired location, in this case the finance building Lobby. This is the You are here position for this PMI (see Phase 6 Steps 7 and 7a). At the PMI property Default Menu MORE INFO view, select Map so that a graphical map will be displayed first when MORE INFO is pressed (see Phase 6 Step 8). Since the Global PMIs need to annunciate events occurs at the existing MXL node, we will import the MXL points into the Project for the Global PMI. Note that the import does not result in showing all MXL points in the Physical tree. Since the Acme configuration already has the MXL node in the Physical tree, the Project Import function will update the MXL detail property based on the XML data file. During compile, Zeus will parse the XML data file to include all the MXL points into the Global PMIs database. In the real world, you would need to obtain the XML data file for the MXL from the MXLs configuration tool. For this example we will use the AcmeMXL.xml data file included in Zeus installation. In the Physical tree, select the Project, right mouse click and select Import from the popup menu. Click the Browse button and select the AcmeMXL.xml file in your installed Zeus folder. Click OK. Notice after the Import completes, the Projects property Import MXL XML data file has the name of the selected XML data file. This is a read only property. The property value updates when you perform the Import function. Select the MXL entity. Notice that all MXL properties in the detail view are now read-only. These data are updated based on the imported XML data file during import.

Phase 6 Step 8

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

44

Siemens Building Technologies Fire Safety

Compile the project and resolve all errors or warnings if they occur. Refer to Zeus online help for detailed information on compile or error message explanations. Once compilation is completed, in addition to the entire .hrc data file, there is one added file with the extension .hgc. This is the database file for the Global PMI which contains information for all nodes in the XNET network, including the MXL points data. Notice that after compil ation, Zeus also exports the physical data in the project to an .xml data file. This file is to be imported to the MXL-V configuration using the CSG-M tool. As is normally done, we will need to transfer the .hrc file to its appropriate XLS node. In addition, we need to transfer the .hgc file to the PCMCIA card for the Global PMI. For the first time upgrading to Phase 6, make sure that you have the latest PMI firmware files PMIPCMCIAxx.xx.xxxx.bin and ChildBootxx.xx.xxxx.bin in the \ATAFirmware folder. During the Configuration to PCMCIA transfer, Zeus will also transfer these two files to the PCMCIA card. Also make sure that you have the file PCMCIALoaderxx.xx.xxxxx.bin in the \PanelFirmware folder.

Phase 6 Step 9

Insert the PCMCIA card into the PCMCIA slot on your computer. Select Build | Transfer | Configuration to PCMCIA card menu. The Transfer Configuration To PCMCIA card dialog will display. Select the correct drive letter for the PCMCIA card and click Transfer. Zeus will format the card and the .hgc file will transfer to the PCMCIA card. Once the PCMCIA card programming is complete, eject the card from the computer and plug it into the PCMCIA slot on the Global PMI at the system (see Phase 6 Steps 9 and 9a). Steps to upgrade the existing PMI firmware: Remove power from the panel. Insert the programmed PCMCIA card to the PMI PCMCIA slot. Phase 6 Step 9a Place dip switch 2 in the ON (up) position. Restore power to the panel. Push the reset switch. Connect the PC to the panel. Select Build | Transfer | Transfer to Panel. Select the file PCMCIALoaderxx.xx.xxxx.BIN. Click on the Transfer button to transfer the loader firmware to the panel. Restore dip switch 2 to the OFF (down) position. Press the reset switch again to restart the panel. You will need to repeat these steps for each GPMI in the networked system. This completes the set up to convert an existing PMI to a Global PMI.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

45

Siemens Building Technologies Fire Safety

CHAPTER 4 USER INTERFACE


Main Screen (Figures 4-1 to 4-7)
Zeus closely follows Windows-based software conventions. The main screen displays up to six side-by-side windows of the five available Views; most windows function similar to those of Microsoft Windows Explorer. TITLE BAR Shows current project file. MENU BAR Click on titles for drop-down menus. TOOLBAR Shortcut buttons.
Window sizing controls.

STATUS BAR

STATUS BAR
Caps, Num Lock key status; User name; VIEW WINDOWS Session elapsed time. Active View in this example is Physical View; Current selection is the highlighted Fire Print detector. Detail View, on right, is always displayed; Window sizing grip. Currently shows detector settings.

Changing guidance Messages.

Figure 4-1 Zeus Main Screen


Zeus 5.0 Quick-Start Manual P/N 315-033875-11 46 Siemens Building Technologies Fire Safety

View Windows
The View windows present different aspects of the project. They appear side-by-side on the main screen, and can be opened, arranged or closed as needed. Multiple windows of the same View may be opened.
View Detail Physical Geographic Control Function Displays: Information on the currently selected element. Physical relationships between system hardware. Groupings of components by location in the installation. Voice system setup. Logic functions controlling system behaviors. Format Text Fields Graphical Tree Graphical Tree Graphical Tree Graphical Table

The Detail View, always displayed, shows information and allows setting changes for the currently selected element (Properties Tab) and its subordinate child elements (Elements Tab). To widen or narrow a View window, place the cursor over its border and drag left or right. To close a View window, click the Windows-style Close button in the upper right corner (X). Closing a View window does not erase the data it displays. Only one View window is active (selected) at a time. Title Bars of non-active View windows are dimmed.

Two Important View Window Tips


1. Collapse or expand tree branches to show the level of detail you need:

Figure 4-2 Tree View Example The CAB enclosure is shown collapsed (left) and expanded two levels to show its child elements.

To expand or collapse a tree branch, click the boxed plus or minus sign next to the icon of the parent element. 2. Use multiple windows of the same View to manage long trees:

Figure 4-3 Multiple View Windows Two overlapping sections of the same logic tree are shown being viewed at once.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

47

Siemens Building Technologies Fire Safety

Title Bar
The Title Bar displays the Windows filename / path of currently open project. Includes standard Windows Minimize, Maximize and Close buttons, on the right side. Right clicking on Title Bar produces a window-sizing menu. To reposition the Zeus window (when not maximized), click and drag the Title Bar.

Figure 4-4 Title Bar

Menu Bar
Click the headings for drop-down menus of commands. Dimmed commands are disabled. A command with an ellipsis () opens a pop-up window; one with an arrowhead opens a sub-menu. Access keys: Pressing ALT+(underlined letter) opens the respective menu (for example, Alt + F for File). In the resulting drop-down menu, press only the letter to perform the command (for example, x for Exit). Shortcut keys: Some commands have an additional shortcut that doesnt require going through a menu first. These special shortcuts often take the form Ctrl+(letter), such as Ctrl + O for Open. Some hot keys use the Function Keys F1 F12. On the menus, shortcut keys are listed to the right of the commands. Figure 4-5 Menu Bar

Toolbar
Toolbar buttons allow you to rapidly invoke important commands. Toolbar button functions are explained along with the menu commands in the rest of this chapter. Zeus has only one Toolbar, which can be hidden or restored by clicking View > Toolbar. A check mark next to this command indicates that the bar is displayed. To identify a button, place the cursor over it; dont click. The buttons label appears after a moment.

Figure 4-6 Toolbar Buttons

Status Bar
The Status Bar displays guidance messages in the bottom left corner of the main screen. Displayed in the bottom right corner are Caps Lock and Num Lock key status, the current users login name, and elapsed session time from file creation / opening. The Status Bar can be hidden or restored by clicking View > Status Bar. A check mark next to this command indicates the bar is displayed. To resize the Zeus window, click and drag the lower-right corner grip (or any edge of the window). Figure 4-7 Status Bar

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

48

Siemens Building Technologies Fire Safety

Help Menu Commands (Figures 4-8 and 4-9)


Understanding how to use the Zeus Help function is essential, since detailed instructions and guidance are provided only through Help. Therefore, the Help Menu is presented first; overviews of the other menus follow. Menu Summary: Provides on-screen assistance. Help is HTML-based, and enabled by Microsoft Internet Explorer; MSIE must therefore be loaded on the host computer. Help launches automatically in a separate re-sizeable window.

Zeus Help Contents Search Index Whats This?

Displays help topics in a graphical tree format. Displays a table of contents of help topics. Allows you to search for help topics via keyword(s). Displays an alphabetical index of help topics. Displays help on a software feature you select. Click the Whats This? command or icon, then click on the feature in question. Connects you with one of several World Wide Web pages for product support, via your computers Web browser. Web browser automatically launches in separate window. Displays the software version and copyright information.

Siemens on the Web

About Zeus

In addition, you can retrieve help on the currently selected Zeus feature by pressing the F1 key.

Figure 4-8 Help Menu and Sub-menu

Help Screen Tabs


The Help Screen presents five file folder tabs in its top left corner, allowing you to change the presentation and organization of Help topics, as shown in Figure 4-9:
Tab Contents Index Search Favorites Glossary Description Presents a Table of Contents, with Help topics presented in a tutorial order arranged by subject. Provides an alphabetized index of Help topics. Allows you to enter a word or phrase, and returns a list of relevant topics that you can choose from. Permits you to store the most often used or most important topics for quick access. Provides short definitions of terms and concepts for Zeus, FireFinder XLS and fire detection technology.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

49

Siemens Building Technologies Fire Safety

Figure 4-9 Help Tabs Clockwise from top right: Contents Tab (Table of Contents) Index Tab (Index of topics) Search Tab (Search by keywords) Favorites Tab (User-defined list) Glossary Tab (Definitions of terms)

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

50

Siemens Building Technologies Fire Safety

Help Window Controls (Figure 4-10)


The controls at the top of the Help window work in a way simi lar to an Internet browser. This should be no surprise, since the Help feature used is HTML-based, like a series of web pages. The main controls consist of four buttons: Button Hide/Show Back Print Options Function Hides or shows the left side of the Help window; i.e., the tabbed features that accompany the displayed Help topics. Returns Help to the previous topic viewed. Allows you to print the current Help topic, or those associated with the selected heading on the left side of the screen (for example, a heading in the Contents or Index listings). Provides additional viewing options. See below.

A set of left/right arrows allows you to scroll through the five tabs (Contents, Index, Search, Favorites, Glossary), which are too wide to be displayed all at once. The Options Menu provides these functions:
Hide/Show Tabs Back Forward Home Stop Refresh Internet Options Print Search Highlight Off/On Similar to Hide/Show button. Similar to Back button. Displays the next topic(s) visited after Back has been used. Displays the default Help topic. Stops the loading of a large Help topic. Reloads the Help window. Provides extensive options for Help-initiated Internet access. Similar to Print button. Controls the highlighting of the Search keyword(s) in displayed Help topics.

Hides / shows the left side of the Help window.

Returns to the previous Help topic viewed.

Prints the selected topic or the selected heading and sub-topics.

Click arrows to scroll through the tabs.

Tabs

Figure 4-10 Help Window Controls

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

51

Siemens Building Technologies Fire Safety

File Menu Commands (Figure 4-11)


Menu Summary: Basic file management functions, very similar to those on most other Windows software. Note that Print / Print Preview apply to the active View only. Corresponding Toolbar buttons and shortcut keys are shown. Note: Zeus permits only one project to be open at a time. New Open Ctrl +N Ctrl +O Creates a new project file. Opens a dialog box prompting you for the Project Name. Opens an existing project file. Opens a dialog box prompting you for the Project Name, which can be typed in or found through graphic browsing (Browse). Closes the current project. If the project has been changed since the last Save, you are prompted to save it before closing. Ctrl +S Saves the current project to its current filename, with the extension .zdb. You are prompted only if the current project has not yet been saved to disk. Saves the current project to a new filename, with the extension .zdb. You are prompted for the new filename and its location on disk. Ctrl +P Prints the contents of the active View as text. A View is made active by clicking in it. Only one View can be active at any given time. Graphic trees are presented as indented lists. Print pops up a standard Windows Print window allowing normal printer control; including printer selection if more than one printer is available. Displays the page about to be printed. The window includes options for examining the printout. You can print directly from the preview page, or return to the open project. Configures the printer through the standard Windows Print Setup dialog. A list of the last several project files saved appears between Export and Exit. Click on a project to open that file. Closes the Zeus software. You are prompted only if the current project is not yet saved.

Close

Save Save As Print

Print Preview Print Setup (Most Recently Used Files) Exit

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

52

Siemens Building Technologies Fire Safety

Edit Menu Commands (Figure 4-11)


Menu Summary: Basic editing functions, very similar to those on most other Windows software. Corresponding Toolbar buttons and shortcut keys are shown.

Undo Cut Copy Paste Paste Special Assign To Delete Find/Replace Text Find/Replace Tree Node

Ctrl +Z Ctrl +X Ctrl +C Ctrl +V

Restores the project to its state before the previous command. Removes a selection and stores it on the Windows Clipboard. Copies a selection onto the Windows Clipboard. Pastes the item stored on the Windows Clipboard into the active View. Allows the pasting of multiple copies of an item stored on the Windows Clipboard.

Ctrl +R Del Ctrl +F

Creates a link at the selected point, if valid, using the element selection currently copied to the Windows Clipboard as the source. Removes the current selection from the project. Finds specified text in the details of the children of the selected element, and replaces that text if commanded to do so. Finds specified element among the children of the selected element, and replaces those found with a different insert-able element if commanded to do so. Example: in the Physical View, replace HFP detectors with HMS pull stations. Arranges the children of a selected element as they are ordered under the Elements tab of the Detail View.

Apply Order to Tree Select All Invert Selection


Ctrl +A

Selects all the elements at the same level on a tree-view branch. Selects all the elements at the same level on a tree-view branch except those already selected .

Figure 4-11 File and Edit Menus


Zeus 5.0 Quick-Start Manual P/N 315-033875-11 53 Siemens Building Technologies Fire Safety

View Menu Commands (Figure 4-12)


Menu Summary: Control of View windows, which show different aspects of the system under development. Views are explained in detail in Chapter 5 of this manual.

Physical View Geographic View Control View Function View

Each menu selection replaces the active View with the selected View. Active View is marked with a check. These selections are dimmed if the Detail View is the active View. Inserts a new View window next to the Detail View. A drop-down menu lists the Views to select from. Toolbar buttons at left are for inserting the following Views, respectively: Physical, Geographic, Control, Function Expands or collapses the tree in the active View, as follows: Expand One / Collapse One: Expand or collapse the tree one level below the currently selected element. Expand All / Collapse All: Expand or collapse the entire tree. Toolbar icons at left are Expand One / Collapse One. Makes all displayed View windows the same width. Expands the active View window to maximum width. When a source element is selected, command is Show Link(s) In, and it highlights the elements first link (reference). When a link is selected, the command is Show Source In, and it highlights the element the selection refers to. If the source or link to be shown is in a closed View, that View window is automatically opened and the tree is expanded as needed. Highlights the next link(s) after the first revealed by Show Link(s) In. The command is dimmed if there is only one link to the selection. Show, hide or reorder data columns in the Elements tab of the Detail View. Updates all displayed views. Displays or hides the Toolbar (at top of screen). Displays or hides the Status Bar (at bottom of screen).

New View

View Level

Arrange Maximize Show Link(s) In / Show Source In

Show Next Link Customize Refresh All Views Toolbar Status Bar

Figure 4-12 View Menu and Sub-menus Active View is Physical. Toolbar and Status Bar are displayed.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

54

Siemens Building Technologies Fire Safety

Insert Menu Commands (Figure 4-13)


Menu Summary: Provides a library of items that can be inserted into the system. The changing menu is context-sensitive: it presents you with only those items that can be inserted as a child of the currently selected element. Click a menu choice to insert that element. The element is added after any other existing children (i.e., at the bottom of the child list).

Figure 4-13 Examples of Insert Menu Selections

Build Menu Commands (Figure 4-14)


Menu Summary: Provides compilation and transfer functions for system configuration files.

Check Compile

Checks a project for configuration errors without creating a configuration file. Creates a configuration file (with an extension of .hrc) of the current system. A pop-up window displays warning and error messages. The configuration file is saved to the same directory folder as the project file. Compiles all the systems (nodes) within a project, and saves the multiple files to the same directory folder as the project file. Helps reconstruct a system in Zeus from an existing, compiled configuration file. Copies a configuration file or firmware for a system to and from a control panel.

Compile All Decompile Transfer

Figure 4-14 Build Menu and Sub-menu

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

55

Siemens Building Technologies Fire Safety

Tools Menu Commands (Figure 4-15)


Menu Summary: Provides miscellaneous functions.

Compare History Log Walktest Log Report Generation Create Tone/Message File Record Wave Sound Options User Administration

Compares a configuration file with the current project or another configuration file. Results of the comparison are presented in a pop-up window. Allows a history log file from a control panel (PMI) to be transferred and displayed. Allows a walktest log file from a control panel (PMI) to be transferred and displayed. Prints and displays pre-defined reports. Allows the assembly of PreRecorded Message Files (.pmfs) from individual Wave (.wav) sound files. Launches Windows Sound Recorder for creating custom .wav sound files. Modifies Zeus interface parameters: Fonts, Serial Port selection, Default Root Directory, Autosave, and Recently Used File List length. Sets up the authorized user accounts and passwords to run Zeus. Command available only if the user has account administration rights. Refer to the Zeus Installation Manual for details. Accepts a new user name and password to change the current user. The User Login window appears at the start of the software, as well as when commanded here. Allows an organization to request Siemens to provide a code that will enable it to access a control panel (PMI) that was programmed by a previous organization. Returns a code that the current organization provides to Siemens Fire Safety. Siemens can then provide a password that will permit access, if authorized. Refer to the Zeus Installation Manual for details. Displays a summary of total elapsed session times for all user accounts.

User Login

Installing Office Password

Project Elapsed Time

Figure 4-15 Tools Menu and Sub-menus

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

56

Siemens Building Technologies Fire Safety

CHAPTER 5 CONCEPTS AND OPERATIONS


Comparison of Zeus and Microsoft Windows Explorer
Common Windows Explorer operations that can be performed with Zeus elements: Drag-and-drop within and between View Windows (where permitted). Copy/Cut/Paste to/from the Windows Clipboard. Select a contiguous block of elements (Shift-select) or a scattered set (Ctrl-select). Right-clicking an element produces a menu of editing features. Notes specific to Zeus: The Detail View shows specific information for the currently selected element. The icon label can be entered or changed only in the Detail View window. (i.e., you can not change the label by pressing the F2 key or double-clicking on the label). Right-clicking on an element also produces Insert Menu choices and Show Source/Link functions.

Elements, Links and Sources (Figure 5-1)


As you use Zeus, it is important to distinguish between elements and links. Typically, you build a system by inserting elements, then assigning links , or references, of those elements elsewhere as needed. A link may also be considered analogous to a shortcut in MS Windows and Windows Explorer. The original element being referenced is called the links source. The process of making a link is called an assignment. You can create and assign a link simply by dragging and dropping the source to a valid location elsewhere in the project. Elements can be dragged and dropped within or, in many cases, between View windows to make assignments. For example, you would add a fire detector to your project by inserting a detector element into the Physical View. From there, you might then drag and drop the detector element a group in Geographic View, to assign a link to the detector there. Similarly, you might repeat the process to assign another link to a logic function input in Function View. Drag/drop is context-sensitive: Zeus will not permit you to drop an element into a window or location where it does not belong. The cursor becomes a crossed-out circle over such invalid locations.

Device source elements created in Physical View AND Function source element AND Inputs: Links to Fire Prints 1 & 2

Figure 5-1 Link/Source Example Physical devices (top left) and their logical links in Function View. Equivalent logical diagram is shown above.

OR Inputs: Links to AND Function & Fire Print 3

It is important to understand that this is different than copying / cutting / pasting the element. You can avoid this confusion by dragging and dropping while holding down the right mouse button. When you drop the icon, a popup menu gives you the choice to cut/paste or assign, as appropriate. When you drag and drop using the left mouse button, you can still tell whether you are about to cut/paste or assign by the cursor shown: an assignment produces a cursor object with the same box-and-arrow symbol as a link icon.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

57

Siemens Building Technologies Fire Safety

As your system becomes more complex, you will need to keep track of sources and their links. For that, the Show Source / Links In command in the View Menu is essential. Depending on whether the selected element is a source or a link, the command toggles to show you the corresponding element(s) in the same or another View.

FireFinder XLS Communications Protocols


FireFinder XLS system components use the following specialized protocols for communications and control: Network XNet HNet P2 CAN Connects: Multiple nodes (systems) to each other. Circuit cards to a system. Devices on a detector loop to the DLC. Usually corresponds to the Device Address. Door-mounted modules to a system. Standard Control Area Network protocol.

Understanding the View Windows

Detail View (Figure 5-2)


The Detail View window shows properties (settings and information) on the currently selected element and its immediate children. Hence, it changes with each new selection.

Figure 5-2 Detail View Tabs Top: Properties Tab shows information for a Device Loop Card. Bottom: Elements Tab shows information for the DLCs children.

Some of the most common properties that are edited in the Detail View are:
Property Field Base Language Custom Message CAN Address Device Address Device Usage Zone Coding HNet Address Relay Base Used Use Zone Code of Parent Group Field Type Text Numeric Numeric Menu Checkbox Numeric Checkbox Checkbox Description (checked condition for checkbox properties) The label that appears on the element in Zeus, and the identifier that will appear on the control panel (PMI) when the element is displayed there. Address of a Control Area Network device under a host card/module. Address of a Siemens P2 protocol device under a host card/module. Application of the device within the system logic. The element is part of a zone coded system. Address of a card or module linked by the HNet protocol within a Node. Device includes a relay actuated by the connected device or system logic. Elements zone code is set by the Geographic group to which it belongs.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

58

Siemens Building Technologies Fire Safety

Physical View
The Physical View displays the physical relationships of all system components: electronic, structural, etc. The upperhierarchy tree elements in the Physical View are Project, Node and Enclosure. Below the Enclosure level are the components comprising the physical system. Three important exceptions to this scheme are:
System Flags History Log Function Key This generic, stand-in element for system flags (system states) is an integral part of each FireFinder XLS Node element. To use a system flag in a logic function, you drag this element from the Physical View to the Function View, then set the Detail View properties of the resulting link . The Detail View settings of this element, an integral part of each FireFinder XLS Node element, determine which events the fire system will record at the PMI (control panel). This element represents a graphic on the PMIs (control panels) touch-sensitive screen that is used to initiate logical behavior. It is treated as a physical element under the PMI element.

Geographic View
The Geographic View allows devices to be organized into groups, and is generally intended to allow the system to be described in terms of location within the installation. The Geographic View elements are ordered in a hierarchy of Group Levels 5 to 1 (highest to lowest) with these corresponding default names: Campus, Building, Floor, Area, Zone.

Control View
This View manages the control of the fan-use, damper-use and Voice System outputs. It breaks systems down by Command Stations (also known as Voice Control Boundaries) to enable programming of user controls at a systems main and remote enclosures. These include such controls as Fan and Switch Control Modules and Live Voice Modules.

Function View (Figure 5-3)


Function View shows the programmed logic of a system as a tree view, with elements representing the binary logic functions. Although the Function View is set up as a tree, it is really a list of logic functions. All function elements are listed on the same hierarchical level, and connections between functions are not shown graphically. These links can best be traced using the Show Source/Link(s) In, and Show Next Link commands in the View menu. To link one function to another, you drag and drop a function element itself onto the Input List of another. Zeus does not allow functions to be assigned to Output Lists, or by dragging and dropping the Output List of one function onto the Input List of another. As such, Output Lists are reserved for output devices, such as annunciators or relays, and output system flags. When input devices, such as detectors, are assigned to an Output List, it is their output components, such as a basemounted relay or lamp, which are controlled.

Figure 5-3 Function View Example


Input links are ganged as OR.

Any one of the input links will activate both the output links. Assigned functions are linked via the ALL VISUALS Input List, not by assigning ALL VISUALS to the Output Lists of the functions.

Output links Are ganged as AND.

Zeus 5.0 Quick-Start Manual P/N 315-033875-11

59

Siemens Building Technologies Fire Safety

Siemens Fire Safety Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, NJ 07932 973-593-2600 www.sbt.siemens.com/FIS

P/N 315-033875-1 1