Escolar Documentos
Profissional Documentos
Cultura Documentos
Function Description
Firmware: 080618
SELCO A/S Betonvej 10 - DK-4000 Roskilde Denmark Phone: 45 7026 1122 - Fax: 45 7026 2522 e-mail: selco.dk@selco.com Web site: www.selco.com
SELCO A/S
C6200 Module
Table of Contents 1 2 3 3.1 3.2 4 4.1 4.2 Preface.......................................................................................................................................... 3 Front view of C6200 .................................................................................................................... 4 Generator protection functions .................................................................................................... 5 Reverse power protection ........................................................................................................ 5 Excitation Loss protection ....................................................................................................... 5 Parallel operation of generators ................................................................................................... 6 Voltage matching ..................................................................................................................... 6 Synchronization ....................................................................................................................... 6
4.2.1 Static synchronization .......................................................................................................... 7 4.2.2 Dynamic synchronization .................................................................................................... 7 4.2.3 Synchroscope ....................................................................................................................... 7 4.2.4 Check Synchronizer function ............................................................................................... 7 4.3 Load sharing............................................................................................................................. 7 4.3.1 Active load (kW) sharing ..................................................................................................... 7 4.3.2 Reactive load (kVAr) sharing .............................................................................................. 8 4.3.3 Unloading a generator .......................................................................................................... 8 4.3.4 Automatic/ semi-automatic mode ........................................................................................ 8 5 Applications ................................................................................................................................. 9 5.1 5.2 6 6.1 6.2 Synchronization and load sharing between parallel running generators. ................................ 9 Synchronization of busbar sections ....................................................................................... 10 Grid parallel operation of generators ......................................................................................... 12 Auto-Synchronization ............................................................................................................ 12 Load Sharing .......................................................................................................................... 12 Fixed import ....................................................................................................................... 13 Peak Import ........................................................................................................................ 14 Fixed Export....................................................................................................................... 15 Excess Export..................................................................................................................... 16 Unloading ........................................................................................................................... 16
Revision: 20.11.2008
Page 2 of 17
SELCO A/S
C6200 Module
1 Preface
The SELCO C6200 GENCONTROLLER module is intended for paralleling of generators with each other or with the grid. The module offers automatic and semi-automatic synchronizing, active and reactive load sharing, frequency and voltage control, reverse power protection and excitation loss protection. Voltage measurements from the generator and busbar are taken from phases L1 and L2. The generator current is taken from L3. For remote control of the generator, a range of user programmable functions is available. These functions can be triggered from programmable inputs and outputs or via RS485. The unit can be used in connection with a SELCO S6500 User Interface. The user interface will show measurements and status of the C6200 module. It can also be used for programming of the C6200 module.
Revision: 20.11.2008
Page 3 of 17
SELCO A/S
C6200 Module
Revision: 20.11.2008
Page 4 of 17
SELCO A/S
C6200 Module
The module offers reverse power protection and excitation loss protection of the generator. All protection functions will trip the circuit breaker via the protection trip relay of C6200.
Revision: 20.11.2008
Page 5 of 17
SELCO A/S
C6200 Module
4.2 Synchronization
Two different synchronization schemes are available with C6200, static and dynamic synchronization. The static synchronization scheme is used in case the frequency of the generator is controlled by the analogue output signal for speed control. The dynamic synchronization scheme will be used in case the frequency of the generator is controlled by the speed up/ down pulse output signals.
Revision: 20.11.2008
Page 6 of 17
SELCO A/S
C6200 Module
4.2.1 Static synchronization In case of static synchronization, frequency and phase angle will be adjusted so that the parameters of the incoming generator match the parameters of the bus bar (frequency of the incoming generator = frequency of the busbar, phase deviation within acceptable limits). This is possible as the regulation is much faster when using the analogue outputs. The load sharer will load the generator immediately after connection thus avoiding a reverse power situation. 4.2.2 Dynamic synchronization This means that the incoming generator will be connected with a slightly higher frequency than the bus bar frequency. The purpose of this function is to make sure that the incoming generator will be loaded immediately in order not to take reverse power. In automatic mode, the synchronization function will start immediately when enabled and generator and busbar voltages are within the voltage ok window (+/- 10% in default configuration). In semi-automatic mode, the C6200 must get a start command via the programmable I/O or RS485 before it starts synchronization. 4.2.3 Synchroscope The front side of the C6200 contains a synchroscope for making commissioning easier. 4.2.4 Check Synchronizer function The check synchronizer function can be used as synchronizing aid for manual synchronization where voltage and frequency are adjusted by the operator to roughly the values required, and the unit will provide a closing signal to the circuit breaker at phase accordance. The C/B close relay will close the circuit breaker when voltage, frequency and phase deviation are within acceptable limits. This function is available in both automatic and semi-automatic mode.
SELCO A/S
C6200 Module
4.3.2 Reactive load (kVAr) sharing The C6200 shares the reactive load between the parallel running generators by controlling the voltage of the generator. The voltage control can be done through the analogue voltage setting output (current, voltage or pulse width modulated (PWM) signal) or via the voltage up/ down pulse outputs. The reactive load is shared according to the proportional reactive load utilization of the generator. This means that the C6200 does not share according to a certain kVAr level, but to the relation between the current load/ nominal current of the generator. Thus reactive load sharing between generators of different size is possible without any further adjustment. The reactive load information between the generators is shared by an analogue voltage signal, the parallel lines. This voltage signal can be programmed to match reactive load sharers of other types, such as SELCO T4900 (see parallel lines in the configuration manual). 4.3.3 Unloading a generator In case a generator should be taken out of service and the circuit breaker should be tripped it is necessary to unload the generator first. This can be done either by the unload input or via RS485. After the C6200 has received the unload command it will decrease both active and reactive load. As soon as both loads pass below the unload trip level, the unload trip relay of the C6200 will trip the circuit breaker. 4.3.4 Automatic/ semi-automatic mode In automatic mode, all control functions of the C6200 will run automatically. In semi-automatic mode the C6200 will only control the speed and voltage regulation after it has received a command to do so. The command can be sent to the C6200 either by the programmable inputs and outputs or RS485.
Revision: 20.11.2008
Page 8 of 17
SELCO A/S
C6200 Module
5 Applications
5.1 Synchronization and load sharing between parallel running generators.
Fig. 1: Minimum connection for parallel operation between two or more generators
L1 L2 L3
com
com
1 com
29 31 + -
40 41 42 43 44
Unload Reset Alarm Freq. Ctrl. Disable MAN C/B
45 46 47 48 49 50 51 52 53
L1 L2 Busbar Voltage
Aux. Supply
C/B Close
Prot. Trip
Unload Trip
C/B
Gen. Voltage L1 L2 5 6 Gen. Current S2/ S1/ L3 L3 13 14 Analogue Out 1 Speed Control L1 L2 L1 L2 V/ ref pwm mA DC
C6200
Prg. Out. 1 Prg. Out. 2 Prg. Out. 3
Alarm
54 55 56
67 66 65
Governor
DG2
Engine
Revision: 20.11.2008
Page 9 of 17
SELCO A/S
C6200 Module
Revision: 20.11.2008
Page 10 of 17
SELCO A/S
C6200 Module
40 com
C/B feedback
C6200
Gov/ AVR ctrl
35 39 Ref
Section 1
Parallel lines
com
54
Section 2
Reverse synchronizing
Parallel lines
26 27 28
44
23 24 Ref
26 27 28
Parallel lines
C6200
Gov/ AVR ctrl
35 39 Ref
C6200
Gov/ AVR ctrl
35 39 Ref
AVR Governor
AVR Governor
DG2
Engine
DG2
Engine
Revision: 20.11.2008
Page 11 of 17
SELCO A/S
C6200 Module
6.1 Auto-Synchronization
When the grid is to be connected to a diesel generator, or multiple parallel running diesel generators, it is necessary to conduct reverse synchronization. Reverse synchronization is done by letting the C6200 module connected to the grid control the voltage/frequency of the diesel generator(s) through the FREQ. IN / VOLT IN. inputs of the diesel generator(s) C6200 module(s). The C6200 module of the grid will then close the grid circuit breaker when the parameters are matched. For the reverse synchronizing function it is necessary to program the speed and voltage control outputs (terminals 35 and 39) so they match the input signal of the Freq. In and Volt. In. inputs (terminals 23 and 25): WRITE SYS SPEEDCTRL ANAOUT VOLTMIN -1.000 WRITE SYS SPEEDCTRL ANAOUT VOLTMAX 1.000 WRITE SYS VOLTCTRL ANAOUT VOLTMIN -1.000 WRITE SYS VOLTCTRL ANAOUT VOLTMAX 1.000 It is also necessary to deactivate the frequency and voltage regulation function of the diesel generators that should be synchronized to the grid. This can be done by connecting the Freq. Ctrl. Input of the diesel generator unit to COM. The frequency and voltage control must be disabled as long as the generator runs in parallel with the grid.
Revision: 20.11.2008
Page 12 of 17
SELCO A/S
C6200 Module
connected to COM. In case the input is disconnected, the C6200 will return to normal generator load sharing. This is useful when parallel running generators should be connected to the grid. As long as the generators only run in parallel with each other, they run in normal load sharing mode (user programmable input for load sharing scheme deactivated). After synchronization to the grid, the input can be activated and the generators follow the load sharing scheme. In case the generator should not operate in parallel with the grid, the load sharing schemes must be disabled. WRITE IMPORTEXPORTSCHEME DISABLED This is the default setting.
6.2.1 Fixed import Fixed import means that the installation imports a fixed load level from the grid. In case the installation requires more load than the predefined import load level (configured as a percentage of the grid capacity), the diesel generators will supply the rest of the load demand. The C6200 of the grid controls the load by the parallel lines (LS signal). The C6200 modules of the diesel generators will adjust their loads according to the parallel lines signal. The blue line on the graph below shows the LS signal of the grid C6200. The red line shows the total load. The pink area shows the capacity provided by the shaft/grid. The grey line shows the capacity provided by the auxiliary generators.
Revision: 20.11.2008
Page 13 of 17
SELCO A/S
C6200 Module
6.2.2 Peak Import With this setup, the installation will load the connected generators up to a pre programmed load level. In case the load demand increases above this limit, the remaining power will be imported from the grid. The blue line on the graph below shows the LS signal of the grid C6200. The red line shows the total load. The pink area shows the capacity provided by the shaft/grid. The grey line shows the capacity provided by the auxiliary generators.
Revision: 20.11.2008
Page 14 of 17
SELCO A/S
C6200 Module
6.2.3 Fixed Export The scheme exports a certain amount of capacity to the grid. The 6200 of the grid forces the C6200 modules of the auxiliary generators to produce a certain amount of power into the grid C6200. The blue line on the graph below shows the LS signal of the grid C6200. The red line shows the total load. The pink area shows the capacity provided by the shaft/grid. The grey line shows the capacity provided by the auxiliary generators.
Revision: 20.11.2008
Page 15 of 17
SELCO A/S
C6200 Module
6.2.4 Excess Export This scheme exports excess power to the grid. The auxiliary generators are operated with a fixed load. In case the power supplied by the generators is more than the installation requires, the excess power will be exported to the grid. The blue line on the graph below shows the LS signal of the grid C6200. The red line shows the total load. The pink area shows the capacity provided by the shaft/grid. The grey line shows the capacity provided by the auxiliary generators.
6.2.5 Unloading Before disconnecting the grid, load should be transferred to the diesel generators. This is done by connecting the UNLOAD input of the grid C6200 module to COM. Activating the UNLOAD input of the grid C6200 module will make it transfer the load to the diesel generator, after which the grid C6200 will trip the breaker. Below drawing shows an application with 2 generators running parallel with the grid. For easy overview the drawing only shows the connections for reverse synchronizing.
Revision: 20.11.2008
Page 16 of 17
SELCO A/S
C6200 Module
Grid
Reverse synchronizing
Parallel lines
26 27 28
44
23 24 Ref
26 27 28
Parallel lines
C6200
Gov/ AVR ctrl
35 39 Ref
40 C/B com feedback com Close for synchronizing and grid parallel operation
C6200
Gov/ AVR ctrl
35 39 Ref
AVR Governor
AVR Governor
DG2
Engine
DG2
Engine
Revision: 20.11.2008
Page 17 of 17