Você está na página 1de 7

Return to contents page

Service Engineers Section

Bulletin No 17

R410A HANDLING, PROPERTIES, DESIGN, INSTALLATION AND SERVICING

1. INTRODUCTION R410A is now a recognised refrigerant for air conditioning and comfort heating heat pumps in Europe. Many major Original Equipment Manufacturers (OEMs) in this application field, represented in the EU, now supply systems using R410A. R410A is a near azeotropic mixture consisting of two HFC components, R32 and R125 in the proportions 50%/50% by weight. R410A has much higher pressures than R22. System condensing pressures will be 9 to 10 bar higher than with R22. System performance will be similar to R22. To gain the full benefits of R410A the system should be designed to take full advantage of its better heat transfer properties. Servicing with R410A should be straightforward provided the guidelines given below are followed. Systems which use R410A normally have compressors charged with a polyolester (POE) lubricant. There are many manufacturers and grades of POE lubricant. It is therefore very important that any oil added to a system is of the correct grade. Consult the system or compressor manufacturer for guidance on which specific oil to use.

2. PROPERTIES OF R410A 2.1 Vapour Pressure The high pressure of R410A requires that all system components, gauges and refrigerant cylinders are specified for the proper pressures. System test pressures must be set accordingly. When this is done, the safety risk associated with an R410A system is the same as for any other pressurised system. Retrofitting R22 systems with R410A is not normally possible. 2.2 Critical Temperature R410A has a critical temperature of 72.5C, significantly lower than that of R22. Tests of air conditioning systems carried out at high ambient temperatures have shown that the performance is not unduly affected however (when compared with that of R22). 2.3 Specific Volume and Mass Flow R410A has higher density (lower specific volume) than R22 under normal A/C system conditions. A similar mass flow is required to achieve the same cooling effect.

Table 1 Properties of R410A Property Vapour Pressure @ 25C, bar gauge Vapour Pressure @ 40C, bar gauge Boiling Point at 1 Atmosphere Pressure, C Critical Temperature, C Specific Volume of Saturated Vapour @ 5C, gm3/kg Specific Mass Flow per kW Cooling @ 5/50C*, g/s/kW

R22 9.4 14.3 -40.8 96.2 0.040 6.60

R410A 15.5 23.1 -52.7 72.5 0.028 6.75

* EN12900 Rating point 5C Evaporating, 50C Condensing, 10K superheat, no subcooling SES Technical Bulletin 17 1 of 7 April 2004

Return to contents page


The lower R410A volume flow rate means that smaller displacement compressors are required for equivalent system capacities, and smaller tubing diameters and associated fittings can be used. The overall result is a smaller refrigerant side system and consequent lower refrigerant charge. Because, in many condensers and evaporators the airside heat transfer coefficient is the limiting one, the surface areas required to transfer heat to the air or water will remain similar to those for R22, as will the compressor motor size. Nevertheless, designing to take advantage of the properties of R410A can lead to reductions in overall heat exchanger size and tubing. accordance with BS EN378:2000. High pressure reduces the impact of pressure drop on system performance. Because there is a much larger pressure difference between the high side and the low side of the system than with R22, longer lines and smaller diameters can be used for vapour flow. For example, there will be 0.35K R410A saturated suction pressure reduction per 100mb pressure drop compared with 0.55K with R22. Manufacturing R410A equipment (as well as installation and maintenance) simply requires good refrigeration practice, as is the case for traditional R22 installations. Suitable components (compatible with working pressure, refrigerants and lubricants) should always be used. The components and tools suited for R410A must never be used with other HCFC or CFC refrigerants to avoid any possible risk of contamination in the circuit. 3.1 Compressors Dedicated R410A compressors should always be used because they will be designed for the higher pressures and incorporate motors of correct size relative to the displacement. Compressors designed for other refrigerants should not be used. Manufacturers can provide information on performance, lubricants, and application details. 3.2 Heat Exchangers Heat exchanger coils (evaporator or condenser) designed for R410A service will, due to the properties of R410A, utilise smaller diameter tubing than ones of equivalent service for R22. In practice it is possible to reduce the number of circuits in a heat exchanger for a given duty when using R410A.

2.4 Stability and Material Compatibility R410A stability in the presence of metals is excellent. Laboratory tests have shown that it is compatible with steel, copper, aluminium and brass. As with all HFCs the behaviour of R410A in the presence of plastic materials and elastomers varies. Some materials have been evaluated to be completely suitable, some depending on their composition and process may not be suitable. Compatibility data is readily available from wholesalers and component or refrigerant suppliers

3. DESIGN AND INSTALLATION OF R410A SYSTEMS Designers must take into account that the higher design pressures may raise the PED category of the system or component. The maximum allowable pressure for design purposes must be at equal to or above the values shown in Table 2, in

Table 2 Maximum Allowable Pressures (minimum) for which R410A systems must be designed (adapted from BS EN378-2:2000).
Ambient condition 32C 38C 43C 55C High pressure side with air cooled 33.4 bar(g) 36.6 bar(g) 40.0 bar(g) 43.7 bar(g) condenser High pressure side with water cooled 25.1 bar(g) 25.1 bar(g) 25.1 bar(g) 33.4 bar(g) or evaporative condenser Low pressure side 18.9 bar(g) 22.1 bar(g) 25.1 bar(g) 33.4 bar(g) Note: for the high pressure side of a heat pump with water cooled condenser the design pressure should be at least equivalent to the saturation pressure at the maximum leaving water temperature +8K.

SES Technical Bulletin 17

2 of 7

April 2004

Return to contents page


The number of circuits in the coil can typically be reduced by 1/3 compared to R22. In other words, an R410A coil only needs 2/3 of the number of circuits required for R22. This, combined with smaller diameter tubing may give the additional benefit of a lower air side pressure drop. R410A has a significantly higher heat transfer coefficient than R22 and R407C, during both evaporation and condensation, leading to improved performance. For same thermal capacity (refrigeration capacity) the coils need a lower refrigerant side heat exchange surface, leading to more compact design and less material required.

Figure 1. Refrigerant side pressure drop for the evaporation process. Given the same pressure drop the R410A coil permits a higher refrigerant mass flux

Figure 2. Refrigerant side pressure drop for the condensation process. Given the same pressure drop the R410A coil permits a higher refrigerant mass flux

3.3 Connecting Tubing As with heat exchangers, smaller diameters may be used for the vapour lines, when designing for for oil return. The higher working pressures of R410A could require thicker-walled tubes (see below). The miscibility between HFCs and POE oils is lower than that of HCFCs with traditional oils and it is even more important to ensure the required velocity of the refrigerant for the oil return and to avoid possible oil traps when designing the pipework and accumulator. Tubing and
SES Technical Bulletin 17 3 of 7

fittings must be properly pressure rated for R410A use; see Table 2 above. BS 1306:1975 gives the methodology for determining the pressure rating of copper tubing. Based on this the following currently available copper tubing meets pressure requirements for R410A use. (Note: It is important that the pressure ratings of fittings be verified as appropriate before being used)

April 2004

Return to contents page


Table 3 Copper Tube Coil Stock Suitability for R410A, based on Pressures in Table 2 and Design Stress 40N/mm2 high side, 41N/mm2 low side, according to BS 1306:1975 and BS EN 13480-3:2002.
Copper Tube Coil stock Wall Thick -ness mm 0.7 0.7 0.9 0.7 0.8 0.7 0.8 0.8 0.9 0.9 0.9 1 1 R410A 32C Ambient Condition High Low Side Air Side Cooled 18.9 bar 33.4 bar g g 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 R410A 38C R410A 43C R410A 43C Ambient Ambient Condition Ambient Condition Condition High Side Low High Low High Side Water Cooled Air Side Side Air Side or Evaporative Cooled 22.1 bar Cooled Condenser 25.1 bar g 36.6 bar g g 40.0 bar g 25.1 bar g 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 x 9 9 9 9 9 9 9 9 9 x

3/16 x 22g x 22g x 20g 5/16 x 22g 5/16 x 21g 3/8 x 22g 3/8 x 21g x 21g 5/8 x 20g 5/8 x 20g x 20g x 19g 7/8 x 19g

The same figures can be used for soft coil and half hard tube as once the half hard tube is subjected to brazing it becomes fully annealed. Table 4 Copper Tube Straight Lengths Suitability for R410A, based on Pressures in Table 2 and Design Stress 40N/mm2 high side, 41N/mm2 low side, according to BS 1306:1975 and BS EN 13480-3:2002.
Copper Tube Coil stock 3/8" x 20g " x 20g 5/8" x 20g " x 19g 7/8" x 18g 1 1/8 x 18g 1 1/8 x 16g 1 3/8 x 18g 1 3/8 x 16g 1 5/8 x 18g 1 5/8 x 16g 2 1/8 x 18g 2 1/8 x 16g 2 1/8 x 14g 2 5/8 x 18g 2 5/8 x 16g 2 5/8 x 14g 2 5/8 x 12g 3 1/8 x 16g 3 1/8 x 14g 3 1/8 x 12g 3 5/8 x 16g 3 5/8 x 14g 3 5/8 x 12g 4 1/8 x 16g 4 1/8 x 14g 4 1/8 x 12g Wall R410A 32C R410A 38C R410A 43C R410A 43C Thick- Ambient Condition Ambient Condition Ambient Condition Ambient Condition ness High Side Low Side High Side Low Side High Side Low Side High Side Water mm Air Cooled 18.9 bar g Air Cooled 22.1 bar g Air Cooled 25.1 bar g Cooled or Evaporative 33.4 bar g 36.6 bar g 40.0 bar g Condenser 25.1 bar g 9 9 9 9 9 9 9 0.9 9 9 9 9 9 9 9 0.9 9 9 9 9 9 9 9 0.9 9 9 9 9 9 9 9 1 9 9 9 9 9 9 x 1.2 9 9 9 9 9 x x 1.2 9 9 9 9 9 9 9 1.6 9 9 9 9 x x x 1.2 9 9 9 9 9 9 x 1.6 9 9 x x x x x 1.2 9 9 9 9 x x x 1.6 x x x x x x x 1.2 9 9 9 x x x x 1.6 9 9 9 9 x x x 2 x x x x x x x 1.2 9 9 x x x x x 1.6 9 9 9 x x x x 2 9 9 9 9 x x x 2.6 x x x x x x x 1.6 9 x x x x x x 2 9 9 9 9 x x x 2.6 x x x x x x x 1.6 x x x x x x x 2 9 9 x x x x x 2.6 x x x x x x x 1.6 x x x x x x x 2 9 x x x x x x 2.6

The same figures can be used for soft coil and half hard tube as once the half hard tube is subjected to brazing it becomes fully annealed.

SES Technical Bulletin 17

4 of 7

April 2004

Return to contents page


3.4 Fittings It is necessary to check that copper or brass fittings are rated for the correct pressures. Where not available carbon or stainless steel tube and fittings may be necessary. 3.5 Accessories A comprehensive well proven range of filter driers, expansion valves, pressure switches etc already exists in the market, and suppliers can provide details. These should be checked both for refrigerant compatibility and pressure as not all components are suitable. 3.6 Leak Testing Leak testing of new systems must be in accordance with current Codes of Practice for HFC refrigerants. Reference should be made to the Institute of Refrigeration Code of the Minimisation of Refrigerant Emissions. 4. HANDLING GUIDELINES 4.1 General Considerations for HFC Refrigerants a) POE lubricants used with HFCs have a strong affinity for moisture and will absorb water from the atmosphere if allowed to do so. It is very important to minimise the ingress of moisture into the system by following these simple procedural rules: Always keep system openings (tube ends, connections, etc.) and oil containers tightly capped until needed. Cap or close immediately after use. During and after brazing purge with Oxygen Free Nitrogen (OFN) to avoid oxidation, remove residual condensation, and dry the system. Since POE retains moisture chemically it is not possible to completely remove it by use of vacuum. The only way to remove excess (considered to be more than 50 ppm) moisture from the compressor lubricant is by the use of a filter-drier. b) The system should never be contaminated with mineral oils. Dedicated service gauge sets are used for R410A and this will prevent inadvertent contamination.
SES Technical Bulletin 17 5 of 7

c) Filter-driers specified for R410A should always be installed. The moisture adsorption effect of normal dessicant with R410A is less than with R22. d)Flammability. R410A is non-flammable at atmospheric pressure (i.e. in a leak situation) but it can become flammable when mixed with air under pressure. Therefore, R410A and air must never be mixed in cylinders or supply lines, nor accumulated in reservoirs. Never use R410A and air to test the tightness of circuits. 4.2 General Considerations for Near Azeotrope Refrigerants R410A is a near azeotropic refrigerant mixture. This is to say that, when the liquid and vapour are at equilibrium i.e. at any saturation Pressure-Temperature condition, the composition of the vapour differs very slightly from the composition of the liquid. R410A should be transferred as the liquid phase when charging a system from a cylinder. This is done via the dip tube. If the container does not have a dip tube (as in the case of some small refrigerant cylinders) the container should be inverted so that the valve is at the bottom. Only the liquid phase should be transferred. Transfer must be discontinued before all the liquid has been transferred. In an ideal situation when the last drop of liquid has been removed the container will still have around 5% by weight of its net contents present in the vapour phase. It is important that transfer is stopped before any vapour enters the system. The container will have a positive pressure and should not be evacuated. It should be returned to the supplier with its residual pressure. During transfer to a system it is perfectly acceptable to allow the liquid leaving the container to flash to vapour before entering the system (e.g. at the compressor suction). Maintenance of correct charge in a system is always necessary. Should systems require additional refrigerant this can be added without affecting the composition of the blend, provided there is a means of determining whether the system is correctly charged.
April 2004

Return to contents page


5. SERVICING SYSTEMS WITH R410A In R410A split A/C equipment, the external unit is provided with a three-way valve with schraeder valve (different diameter than R22 equipment) to avoid an accidental charge of the units with another refrigerant type. Additionally, to increase the pressure strength of copper tubes with a nominal diameter of 1/2" and 5/8", the sizes of the flared joints and hexagon sizes have been changed. Therefore, during installation or maintenance tools must be provided for exclusive use with R410A and others for general use. 5.1 Gauges As R410A has a higher working pressure than R22, conventional gauges cannot be used. Additionally, to prevent accidental charge with another refrigerant type, the dimensions of the fittings have been modified (see Table 5). Conventional service hoses cannot be connected to R410A systems because the fitting size on the units is different. Because of the generally smaller charges used with R410A systems it is recommended to use an electronic balance to charge R410A to ensure precise charging. 5.2 Flaring Tools Preferably the use of flared joints should be kept to a minimum. Where they are used care must be taken to ensure a good flare is produced. Skill is needed if conventional flaring tools are being used. Special tools are now available and these have two advantages: firstly there is a stop to set the tube in position to obtain the correct flare, and secondly there is a torque limiting device which stops the metal thickness being reduced as the flare is being made. The end result is that a better quality more consistent joint is produced. There are other components available such as premanufactured flare joints which can be brazed to the tube and hence make a more reliable joint. 5.3 Evacuating the System The use of an oil trap on the suction of the vacuum pump is required to prevent the oil (from the pump) from returning to the filling tube and contaminating the air conditioning circuit. The filling tube has two connections: one for the conventional refrigerant (7/16 UNF 20) and one for R410A (1/2" UNF 20). 5.4 Charging the System R410A should be transferred as the liquid phase when charging a system from a cylinder (see Section 4.2) 5.5 Refrigerant Recovery Refrigerant cylinders exclusively for R410A must be used and must be labelled with the name of the refrigerant (the conventional refrigerant identification colour, as prescribed by ARI, is Rose). Depending on the dimensions of the charging line, a connection of 1/2 UNF 20 with a suitable gasket is required for the filling connection. When recovering Refrigerant It is of critical importance that refrigerant recovery cylinders for use with R410A have the correct pressure rating (minimum 33.4 bar g). They must be clearly identified as being for recovered refrigerant (a yellow band), marked with the maximum charge content and identified as containing R410A.

Table 5 Conventional and R410A Equipment Conventional High Pressure Manifold Gauge (red) -0.01 to 35 bar g Compound Gauge (blue) -0.1 to 17 bar g Gauge Connection size 7/16 UNF Charging Hose Normal Pressure 34 bar g Charging Hose Rupture Pressure 172 bar g Charging Hose Material NBR Charging Hose Connections 7/16 UNF

Exclusive for R410A -0.01 to 53 bar g -0.01 to 38 bar g 1/2 UNF 51 bar g 274 bar g HNBR (Internal Nylon Coated) 1/2 UNF

SES Technical Bulletin 17

6 of 7

April 2004

Return to contents page


5.6 Leak Detection and System Recharge Reference should be made to the Institute of Refrigeration Code for Minimisation of Refrigerant Emissions for Refrigeration Systems for examples of methods. Severe depletion of refrigerant charge due to a leak can substantially affect system performance and then recharge will be necessary (refer to section 4.2). For some systems, for example critically charged systems or where no visual indicators are present, the only reliable method of ensuring correct charge level is removal and recharge by weight. As with all refrigerants overcharging can cause poor performance and may affect reliability.

The information contained in the Bulletin should be seen as a guide to interpretation of relevant industry standards, legislation and statutory information which should be consulted by the relevant competent person responsible for servicing refrigeration equipment. This bulletin does not represent a recommendation to use any specific refrigerant fluid for a specific application. The Service Engineers Section and the Institute of Refrigeration accept no liability for any errors or omissions. The material in this Bulletin was originally issued as an Institute of Refrigeration Guidance Note in March 2004.

Service Engineers Section of the Institute of Refrigeration, Kelvin House, 76 Mill Lane, Carshalton SM5 2JR

SES Technical Bulletin 17

7 of 7

April 2004

Você também pode gostar