Escolar Documentos
Profissional Documentos
Cultura Documentos
STANDARDS - National
AS/NZS5033 revised and will be out for public comment mid May. Committee meeting end of July to discuss comments AS/NZS4777.1 revised will be out for public comment probably June. AS/NZS4777.2 still being revised.
STANDARDS- International
MOST IMPORTANT DEVELOPMENTS
International version of 5033 is now out for public comment internationally. Inverter safety standard IEC62109-2 will be published 2nd half of 2011
Protection against fire hazards Inverter backfeed current onto the array Audible noise Fault Indication and ALARM + many more fine details
Why do we earth?
To provide bonding of the metal frame of a system to ground so that a dangerous voltage is not achieved. To allow fault currents to flow if an earth fault occurs somewhere in the system. To provide shielding ie to allow a path for leakage currents to flow. To prevent a system floating to a dangerous voltage that may be undefined. Where particularly required for equipment or operational reasons. i.e. Functional Earthing.
Functional Earthing
Isolated
+ +
Isolated
Protection
under normal conditions is provided by basic Provides SAFETY protection. Facilitates Detection
E.g. Basic insulation, barriers, limitation of Voltage and or current etc.
Enhanced protective provisions provide protection Action taken to remove under both conditions. threat Eg double insulation...Class II.
Conducting frame
N AC
Earth return
Conducting frame
Modules
Extract from New Aust Draft Standard AS/NZS 5033: Modules of class A according to IEC 61730 are not considered to be safety class II and should be treated as safety class I.
Insulation Class I
Class I equipment
Equipment in which protection against electric shock does not rely on basic insulation only, but which includes an additional safety precaution in that accessible conductive parts are connected to the protective earthing conductor in the fixed wiring of the electrical installation in such a way that accessible parts cannot become live in the event of a failure of the basic insulation.
Inverters Isolation/separation
Inverters used for grid connected systems with LV d.c. Inputs are only required to have simple separation between the a.c and the d.c sides. So A single fault condition can connect the a.c to the d.c.
Earthing in PV Systems
To reduce the chance of shock hazard To aid in detection of faults Because module manufacturers require it (Functional earthing)
Faults
Once a fault occurs in a system the second one is generally only one to two weeks away. Chuck Whitaker PV expert USA & IEC and many other consultants Food for thought!
Before looking at earthing cases it is important to look at the new inverter safety standard to see what detection and safety features it adds. IEC 62109-2 New Inverter Safety Functions
Isolated/Separated Inverter
Array grounding Ungrounded or Functionally Grounded with Resistor Test before Startup If Fault alarm and if inverter is a high leakage type then also disconnect If High leakage type requires leakage step change detection shutdown and alarm
Isolated/Separated Inverter
Array grounding Array ground insulation resistance measurement Direct Grounded (No resistor) N/A THIS IS A PROBLEM!
Array residual current If inverter is High detection leakage type -requires leakage step change detection shutdown and alarm
Test before Startup If Fault disconnect and alarm Either RCD on a.c Prescribed by inverter manuf Or Leakage detection on array inside inverter If Fault- shutdown & alarm
Residual Current Monitoring Either an RCD between inverter & grid OR Inverter has both absolute value and step change leakage detection.
+ +
2nd Fault
A N
1st Fault
Earthing of the module frames enables the inverter to detect module faults. ie detect a first fault.
Isolated
+
Isolated
A
1st Fault
N Re E
2nd Fault
Re > Voc/0.030A
Earthing of the module frames enables the inverter to detect module faults. ie detect a first fault.
+ +
Isolated
Isolated
+ +
A
1st Fault
+ +
2nd Fault
1st Fault
Non - Isolated A
1st Fault
N
1st Fault
Either fault location could cause dangerous fault currents. Detection requirements in inverter or external on a.c. Side are required to have double pole separation from the mains
Earthing
Installation and inverter safety standard need to be brought into play together as they have complementary functions to improve safety.
Protective Earthing
Old Standard does not require earthed frames if Modules Class II. CEC Guidelines require PV module frames to be earthed for non-separated inverter systems New Draft 5033 Standard does not recognise Class II Modules. ALL Module Frames Earthed .