Você está na página 1de 4

CYY (-F)

NYY

Cablu de energie din cupru cu


izolatie si manta de PVC

PVC insulated and sheathed power


cable

Standard de fabricatie: SR HD 603 S1/3G-2;IEC 502


Tensiune nominala Uo/U : 0.6/1 kV
Tensiune de incercare : 4 kV ca sau 12 kV cc, 5 min
Temperatura minima de instalare pe cablu:-5C
Temperatura maxima de lucru : 70C
Temperatura maxima de scurt-circuit :160C

Standard: SR HD 603 S1/3G-2; IEC 502


Rated voltage Uo/U : 0.6/1 kV
Test voltage : 4 kV ac or 12 kV dc , 5 min
The minim temperature of de cable during installation :-5C
Max.permissible operating temperature : 70C
Max. short-circuit temperature : 160C

Domeniul de utilizare
Cablurile sunt utilizate pentru transportul energiei
electrice la statii de putere.
Cablurile pot fi pozate in spatii inchise si deschise, in
pamant ,in canale ,in beton ,in apa

Applicability :
Power supply to power stations.
The cables can be installed in open or confined areas,
underground, in sewers, in concrete, under water

Conductor de cupru
Conductor unifilar (re)cl 1,conductor multifilar (rm),cl 2
Izolatia
PVC tip DIV 4
Manta
PVC tip DMV5 negru sau gri
Aceste cabluri sunt cu intarziere sau intarziere marita la
propagarea flacarii ;incercare conf SR EN 332-1-2 sau
SR EN 50266-2-4/cat 3
Marcaj pe manta
SC ELECTROPLAST SA ,simbol cablu ,tensiune de lucru, an
de fabricatie.
Raza minima de curbura la instalare
15xdiametrul cablului-cablu monofilar
12xdiametrul cablului-cablu multifilar
Forta maxima de tractiune la pozare: 50 N/mm2
Cod de culori
1 conductor - albastru, sau galben-verde
2 conductoare-albastru,maro
- galben-verde ,negru, pt sect >10mm
3 conductoare-maro,negru,gri
- galben-verde,albastru,maro
4 conductoare-albastru,maro,negru,gri
- galben-verde,maro,negru,gri
5 conductoare-albastru,maro,negru,,gri,negru
- galben-verde,albastru,maro,negru,gri
Mai mult de 5 conductoare
- conductoare negre numerotate
-v/g,conductoare numerotate

Copper conductor
Monowire (ru), multiwire (rm)
Insulation
PVC type DIV 4
Sheath
PVC type DMV5 black or gray
The cables are flame retardant or extra flame retardant ; test
according to SR EN 332-1-2 or SR EN 50266-2-4/
Category C
Sheath marking
SC ELECTROPLAST SA , cable symbol , operational voltage, year
of manufacture.
Min. bending radius at installation :
15 x cable diameter single-core cable
12 x cable diameter multicore cable
Max. tensile strain during installation :
Max 50 N/mm2
Color coding :
1 conductor-blue or yellow-green
2 conductors- blue,brown
- yellow-green,black for sect>10 mm
3 conductors- brown,black,grey
-yellow-green, blue,brown
4 conductors-blue, brown, black,grey
-yellow-green, brown,black,grey
5 conductors- blue, brown, black, grey, black
-yellow-green, blue, brown, black,grey
More than 5 conductors-numbered black conductors
-yellow-green and numbered conductors

CYY (-F)

NYY

Cablu de energie din cupru cu


izolatie si manta de PVC
Tipo dimensiune
cablu
Cable size

1x1.5
1x2.5
1x4
1x6
1x10
1x16
1x25
1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
2x1.5
2x2.5
2x4
2x6
2x10
2x16
2x25
2x35
3x1.5
3x2.5
3x4
3x6
3x10
3x16
3x25
3x25+16
3x35
3x35+16
3x35+25
3x50
3x50+25
3x50+35
3x70

PVC insulated and sheathed power


cable

Tip
conductor
Type of
conductor

Grosime
radiala
izolatie
Radial thickness of
insulation
mm

Grosime
radiala
manta
Radial
thickness
of sheath
mm

Rezistenta
electrica
max,la
20C
Max. resistance at
20C
/km

Diametru
exterior
inf
Auter diameter
inf
mm

Masa
inf
Mass
inf
kg/km

re
re
re
re
re
re
rm
rm
rm
rm
rm
rm
rm
rm
rm
rm
re
re
re
re
re
re
rm
rm
re
re
re
re
re
re
rm
rm/re
rm
sm/re
sm/rm
sm
sm/rm
sm/rm
sm

0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2;1.0
1.2
1.2;1.0
1.2;1.2
1.4
1.4/1.2
1.4/1.2
1.4

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
1.9
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
1.8
1.9
1.9
1.9

12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.727;1.15
0.524
0.524;1.15
0.524;0.727
0.387
0.387;0.727
0.387;0.524
0.268

6.6
7.0
7.9
8.4
9.2
10.9
12.6
13.8
15.6
17.3
19.7
21.0
23.1
25.5
30.2
31.3
9.8
10.6
12.3
13.5
15.1
18.8
22.2
24.6
10.2
11.1
13.0
14.3
16.0
20.0
23.6
25.0
26.2
27.1
27.1
25.0
29.0
29.0
28.0

60
74
99
124
170
247
359
464
609
825
1112
1338
1643
2050
2708
3290
137
172
233
300
434
669
938
1265
158
203
283
369
538
830
1231
1418
1600
1765
1921
1842
2200
2323
2540

CYY (-F)

NYY

Cablu de energie din cupru cu


izolatie si manta de PVC
Tipo dimensiune cablu
Cable size

3x70+35
3x70+50
3x95
3x95+50
3x95+70
3x120
3x120+70
3x120+95
3x150
3x150+70
3x185
3x185+95
3x240
3x240+120
4x1.5
4x2.5
4x4
4x6
4x10
4x16
4x25
4x35
4x50
4x70
4x95
4x120
4x150
5x1.5
5x2.5
5x4
5x6
5x10

PVC insulated and sheathed power


cable

Tip
conductor
Type of
conductor

Grosime
radiala
izolatie
Radial thickness of
insulation
mm

Grosime
radiala
manta
Radial
thickness
of sheath
mm

Rezistenta
electrica
max,la
20C
Max. resistance at
20C
/km

Diametru
exterior
inf
Auter diameter
inf
mm

Masa
inf
Mass
inf
kg/km

sm/rm
sm/sm
sm
sm/sm
sm/sm
sm
sm/sm
sm/sm
sm
sm/sm
sm
sm/sm
sm
sm/sm
re
re
re
re
re
re
rm
rm
sm
sm
sm
sm
sm
re
re
re
re
re

1.4/1.2
1.4/1.4
1.6
1.6/1.4
1.6/1.4
1.6
1.6/1.4
1.6/1.6
1.8
1.8/1.4
2.0
2.0/1.6
2.2
2.2/1.6
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
0.8
0.8
1.0
1.0
1.0

2.0
2.0
2.1
2.2
2.2
2.0
2.3
2.3
2.2
2.4
2.3
2.6
2.5
2.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
2.0
2.1
2.3
2.4
1.8
1.8
1.8
1.8
1.8

0.268;0.524
0.268;0.387
0.193
0.193;0.387
0.193;0.268
0.153
0.153;0.268
0.153;0.193
0.124
0.124;0.268
0.0991
0.0991;0.193
0.0754
0.0754;0.153
12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
12.1
7.41
4.61
3.08
1.83

35.0
35.0
30.0
41.0
41.0
33.0
45.0
45.0
36.9
49.0
40.9
53.0
47.5
60.0
11.0
12.0
14.1
15.5
17.5
21.9
26.0
29.3
29.0
33.2
36.0
40.0
43.0
11.8
12.9
15.3
16.9
19.0

3008
3271
3295
3850
4059
4020
4881
5100
5013
5732
6120
7390
8113
9420
188
245
347
456
671
1038
1551
2058
2390
3330
4372
5766
6612
223
293
417
551
815

CYY (-F)

NYY

Cablu de energie din cupru cu


izolatie si manta de PVC
Tipo dimensiune cablu
Cable size

5x16
5x25
5x35
7x1.5
7x2.5
9x1.5
9x2.5
10x1.5
10x2.5
12x1.5
12x2.5
14x1.5
14x2.5
16x1.5
16x2.5
19x1.5
19x2.5

PVC insulated and sheathed power


cable

Tip
conductor
Type of
conductor

Grosime
radiala
izolatie
Radial thickness of
insulation
mm

Grosime
radiala
manta
Radial
thickness
of sheath
mm

Rezistenta
electrica
max,la
20C
Max. resistance at
20C
/km

Diametru
exterior
inf
Auter diameter
inf
mm

Masa
inf
Mass
inf
kg/km

re
rm
rm
re
re
re
re
re
re
re
re
re
re
re
re
re
re

1.0
1.2
1.2
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1.8
1.9
2.0
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8

1.15
0.727
0.524
12.1
7.41
12.1
7.41
12.1
7.41
12.1
7.41
12.1
7.41
12.1
7.41
12.1
7.41

23.9
28.7
32.5
12.7
13.9
15.5
17.0
16.1
17.7
16.6
18.3
17.3
19.1
18.2
20.1
19.1
21.1

1267
1914
2454
270
360
314
422
341
460
388
529
438
600
488
700
560
777

Você também pode gostar