short - circuit current calculation

1- Isc at secondary terminas of a HV/LV distribution transformer


I sc = In / Usc
where
Isc

short circuit Fault current In Amps .


Usc In %

Usc :

Short-Circuit Impedance Voltage Of Transformer In %

KVA
50 - 630
800-2500

In

Nominal current In Amps .

In

Nominal current In Amps .

In = P ( KVA )*1000 / U20


U20 : Secondary Volts At Open Circuit.

transfomer rated power (KVA)


transfomer current Ir (A)
oil - immersed transformer Isc (KA)
cast - resin transformer Isc (KA)

Psc = 250 MVA


Psc = 500 MVA
Psc = 250 MVA
Psc = 500 MVA

50
69
1.71
1.71
1.14
1.14

100
137
3.40
3.42
2.28
2.28

tables H1-33 : Isc at the LV terminals of 3-phase HV/LV transformers supplied from a HV system w
* Note
the case of several transformers in parallel feeding a busbar

the value of Isc can be estimated as the sum of the Isc from each transformer calculated

Data Must Be Known


Power

Usc

Rated Voltage

In KVA

In %

in volt

1000

420

RESULTS
Rated Current In Amps

In

Short Circuit Fault Current In Amps

1375

Isc =

22.91

3 - phase short - circuit (Isc) at any point within a LV installation


in a 3-phase installation Isc at any point is given by
Isc = U20/ ZT

U20 = phase -to-phase voltage of the open circuited secondary , windings of the power s
ZT = total impedance per phase of the installation upstream of the fault loctin (in ohms)
________________________________________________________________________
method of caculating ZT
Each component of an installation (HV network,transformer, cable,circuit breaker,busbar,

ZT = RT2 +XT2
________________________________________________________________________
determination of the impedance of the HV network
Zs = U0/Psc

Zs = impedance of the HV voltage network,expressed in milli-o


Uo = phase-to-phase no load LV voltage, expressed in volts.
Ra is generally found to be negligible compared with Xa
for accurate calculation Ra = 0.15 Xa

Psc
250 MVA
500 MVA

Uo (V)
420
420

tables H1-36 : the impedance of the HV network referred to the LV side of the HV/LV transformer
circuit brakers

while the resistance is neglected , Rc.b= 0 , Xc.b = 0.15 m per circuit break
busbars

while the resistance is neglected , Rb.b= 0 , Xb.b = 0.15 m per meter length
circuit conductors
Rc = x L / S where

Note
for c.s.a of less than 50 mm reactance may be ignored

= 22.5 m .mm /
= 36 m .mm / m

Xc =0.08 m / m
Xc =0.096 m /

for prefabricated bus-trunking and similar pre-wired ducting systems, the manfacturer should

R
HV network
Psc = 500 MVA
transformer
20 KV/420V , Pn = 1000 KVA
Usc = 6 % , Pcu = 13.3 x 10 watts
single-core cables
5m copper
4 x 240 mm / phase
main
circuit breaker
busbar
10 meter
three-core cable
100 m
95 mm copper
three-core cable
20 m
10 mm copper

R (m)

X (m)

0.053

0.353

2.35

10.34

Rc = (22.5/4) x (5/240)
= 0.12

Xc = 0.08 x 5
= 0.40

RD = 0

XD = 0.15

RB = 0

XB = 1.5

Rc = 22.5 x (100/95)
= 23.68

Xc = 100x 0.08
=8

Rc = 22.5 x (20/10)
=45

Xc = 20x 0.08
= 1.6

final circuits

three-core cable
20 m
10 mm copper
final circuits

Rc = 22.5 x (20/10)
= 45

xc = 20x 0.08
= 1.6

table H1-39 : example of short-circuit current calculations for a LV installation supplied at 400 V (nom

ulation

sformer

Usc In %

oil
4
6

160
220
5.41
5.45
3.63
3.65

Cast-Resin
6
6

250
344
8.38
8.49
5.63
5.68

315
433
10.5
10.7
7.07
7.14

400
550
13.2
13.5
8.93
9.04

500
687
16.4
16.8
11.1
11.3

630
866
20.4
21.0
13.9
14.1

800
1100
17.4
17.9
17.4
17.9

1000
1375
21.5
22.2
21.5
22.2

1250
1718
26.4
27.5
26.4
27.5

plied from a HV system with a 3-phase faults level of 500 MVA,or 250 MVA at 420 V no load voltage

ch transformer calculated separately

22.91

KA

windings of the power supply transformers


the fault loctin (in ohms)
___________________________________

e,circuit breaker,busbar, and so on . )

___________________________________

etwork,expressed in milli-ohms
tage, expressed in volts.

e compared with Xa

Ra (m-ohm)
0.106
0.053

Xa ( m-ohm)
0.71
0.353

the HV/LV transformer

.15 m per circuit breaker

0.15 m per meter length

= 22.5 m .mm / m for copper


= 36 m .mm / m for aluminium
Xc =0.08 m / m for 50 HZ system
Xc =0.096 m / m for 60 HZ system

s, the manfacturer should be consulted .

X (m)

RT (m)

XT (m)

Isc = 420 / 3 * ( RT + XT )
Zs = Uo / Psc ,
Ra = 0.15 Xa

0.353

10.34

Xc = 0.08 x 5
2.523

11.1

Isc1 = 21.3 KA

Rtr = Pcu x 10 / 3 In
Xa = Ztr - Rtr
avec Ztr = ( U 2o/Pn ) * ( Usc / 10
Rc = L / S
Xc = 0.08 m / meter
RD = 0
XD = 0.15 Per Circuit Breaker

XD = 0.15

XB = 1.5

2.523

12.75

Isc2 = 18.6 KA

RB = 0
XB = 0.15 m / meter

26.2

20.75

Isc3 = 7.24 KA

Rc = L / S
Xc = 0.08 m / meter

Isc4 = 3.24 KA

Rc = L / S
Xc = 0.08 m / meter

Xc = 100x 0.08

Xc = 20x 0.08
71.2

22.35

71.2

22.35

Isc4 = 3.24 KA

71.2

22.35

Isc4 = 3.24 KA

xc = 20x 0.08

on supplied at 400 V (nominal) from a 1000 KVA HV/LV transformer

Rc = often negligible for S 200 m


R=L/S
Xc = 0.08 m / meter

1600
2199
33.1
34.8
33.1
34.8

no load voltage

2000
2749
40.4
43.0
40.4
43.0

2500
3437
49.1
52.9
49.1
52.9

COMMENT
Zs = Uo / Psc ,
Ra = 0.15 Xa

Zs = HV impedance in milli - ohm


Uo = phase-to-phase no- load LV in volts
Psc = HV 3-phase short-circuit fault level in KVA .
Rtr = Pcu x 10 / 3 In
Rtr = is often negligible compared to Xtr for trn 100 KVA
Xa = Ztr - Rtr
avec Ztr = ( U 2o/Pn ) * ( Usc / 100 )
or Isc = In x100/Usc
Rc = L / S
Xc = 0.08 m / meter
where = 22.5 milli-ohms x mm for copper .
where = 36 milli-ohms x mm for aluminium .
RD = 0
XD = 0.15 Per Circuit Breaker
RB = 0
XB = 0.15 m / meter
Rc = L / S
Xc = 0.08 m / meter

Rc = L / S
Xc = 0.08 m / meter

where = 22.5 milli-ohms x mm for copper .


where = 36 milli-ohms x mm for aluminium .

where = 22.5 milli-ohms x mm

for copper .

where = 36 milli-ohms x mm

for aluminium .

Rc = often negligible for S 200 mm in the formula below


R=L/S
Xc = 0.08 m / meter

B.B1
B.B2

Uo (V)
230
230
230
230
230
230

230
230
230
230

(1) determination of the impedance of


DATA
Psc
500
300

RESULTS
Uo
420
400

X(m)
0.353
0.320

R(m)
0.053
0.048

Z(m)
0.357
0.324

(2) determination of Isc at secondary terminals of a HV/L


DATA
TRN1
TRN2

Pn(KVA)
1000
1000

Uo(V)
230
420

Usc(%)
6
6

RESULTS
Pcu(W)
15
13.3

X(m)
2.47
10.1

R(m)
1.99
3.22

Z(m)
3.17
10.58

(2) quick estimation

(2) quick estimation


DATA

RESULTS

P(KVA) Usc(%) Uo(V)


1000

230

In (A)

Isc(KA)

2510.3

41.84

Usc = 6 %
Usc = 4 %

for 800 to 630 KVA


for 50 to 2500 KVA

(3) determination of Isc for low voltage


DATA
CABLE1
CABLE2
CABLE3

L (m)
10
50
10

S (mm)
300
120
25

RESULTS

Uo(V)
230
230
230

N (n)
5
2
1

22.5
22.5
22.5

R(m)
0.15
4.69
9.00

X(m)
0.80
4.00
0.80

(4) determination of Isc for circuit bre


DATA
N (n)
1
1
1
1

CB1
CB2
CB3
CB4

RESULTS
R(m)
0.00
0.00
0.00
0.00

Uo(V)
0
0
0
0

X(m)
0.15
0.15
0.15
0.15

(5) determination of Isc for busba


DATA
L (m)
10
5

B.B1
B.B2

RESULTS
R(m)
0.00
0.00

Uo(V)
0
0

X(m)
1.50
0.75

DATA
Uo (V)
230
230
230
230
230
230

NO
1
2
3
4
5
6

Item
transformer
cable (1)
circuit breaker (1)
busbar (1)
circuit breaker (2)
cable (2)

RESULTS
R(m)
1.99
0.15
0
0
0
4.69

X(m)
2.47
0.8
0.15
1.5
0.15
4

Z(m)
3.17
0.81
0.15
1.5
0.15
6.16

0
1.99
2.14
2.14
2.14
2.14
6.83

230
230
230
230

7
8
9
10

circuit breaker (3)


busbar (2)
circuit breaker (4)
cable (3)

0
0
0.00
9.00

0.15
0.75
0.15
0.80

0.15
0.75
0.15
9.04

6.83
6.83
6.83
15.83

on of the impedance of the HV network

ULTS

COMMENT
Isc
679.74
713.72

Psc 500/250 MVA


Uo = 420 v , 400 v , for rated load 400v , 380 v
X,R,Z in milli ohm (m) and Isc in KA

dary terminals of a HV/LV distribution transformer

RESULTS

COMMENT
In(A)
2510.29
1374.68

) quick estimation

Isc(KA)
41.84
22.91

For roughly estimation


Isc = In/Usc
In= nominal current in amp.
Usc = sc impedance voltage in %

) quick estimation
COMMENT
Usc = 6 %
Usc = 4 %

for 800 to 630 KVA


for 50 to 2500 KVA

on of Isc for low voltage cables


RESULTS
Z(m)
0.81
6.16
9.04

COMMENT
Isc(KA)
163.15
21.55
14.70

L : length of cable in meter


S : c.s.a of cable in mm

:22.5 / 36 mxmm/m for copper / alumimuim


N : no. of conductor /phase

ation of Isc for circuit breaker


RESULTS
Z(m)
0.15
0.15
0.15
0.15

COMMENT
Isc(KA)
0.00
0.00
0.00
0.00

N : no of pole
Rd = 0 ( negligible )

Xd = 0.15 m / pole

mination of Isc for busbars


RESULTS
Z(m)
1.50
0.75

COMMENT
Isc(KA)
0.00
0.00

L : length of busbar in meter


Rb = 0 ( negligible )

Xb = 0.15 m / m

RESULTS
0
2.47
3.27
3.42
4.92
5.07
9.07

COMMENT
Rt(m)
1.99
2.14
2.14
2.14
2.14
6.83

Xt(m)
2.47
3.27
3.42
4.92
5.07
9.07

Zt(m)
3.17
3.91
4.04
5.37
5.50
11.35

Isc(KA)
41.84
33.96
32.90
24.74
24.12
11.70

9.22
9.97
10.12
10.92

6.83
6.83
6.83
15.83

9.22
9.97
10.12
10.92

11.47
12.09
12.21
19.23

11.57
10.99
10.88
6.91

CABLE AND BREAKER SIZE TABLE ACCORDING TO SCECO


connected Amp Range

Minimum (cu)
Cable Size

Maximum (cu)
Cable Size

GT

LE

mm2

mm2

30

4x25

4x25

30

72

4x35

4x35

72

130

4x35

4x50

130

198

4x70

4x95

198

250

4x95

4x120

250

350

4x150

4x185

350

400

4x240

4x240

400

500

4x240

2x4x240

500

600

2x4x240

2x4x300

600

700

2x4x300

2x4x300

700

800

2x4x300

2x4x300

800

1000

3x4x240

3x4x240

1000

1250

7x1x630

7x1x630

1250

1600

7x1x630

7x1x630

1600

2000

11x1x630

11x1x630

2000

2500

14x1x630

14x1x630

2500

3000

14x1x630

14x1x630

NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION (T-1)


127/220 V
RESIDENTIAL CUSTOMERS ( T-1 )
COVERED AREA
SQ METER

TOTAL
CONNECTED
LOAD (KVA)

UNIT A/C
CONNECTED
LOAD (KVA)

CONTRACTED LOAD
C.B RATING
(KVA)
(Amps)

KWH Meter

25
50
74

4
8
11

2.5
5
7.4

30

11.43

3x25 (100)

75
100
125
150
174

12
16
20
24
27

7.5
10
12.5
15
17.4

60

22.86

3x25 (100)

175
200
225
250
275
300
324

28
32
36
40
43
46
49

17.5
20
22.5
25
27.5
30
32.4

100

38.11

3x25 (100)

325
350
375
400
425
450
475
500
524

50
53
56
60
63
66
70
73
75

32.5
35
37.5
40
42.5
45
47.5
50
52.4

150

57.16

3x40 (160)

525
550
575
600
625
650
674

76
80
83
86
90
93
95

52.5
55
57.5
60
62
65
67.4

200

76.21

C.T.

Size (Amps)

NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION


127/220 V
RESIDENTIAL CUSTOMERS ( T-1 )
675
700
725
750
775
800
825
850
875
900
925
950

96
100
103
106
110
113
116
120
123
126
130
133

67.5
70
72.5
75
77.5
80
82.5
85
87.5
90
92.5
95

300

114.32

C.T.

951
975
1000
1025
1050
1075
1100

134
136
140
143
146
150
152

95.1
97.5
100
102.5
105
107.5
110

400

152.42

C.T.

1101
1125
1150
1175
1200
1300
1400
1500
1600
1658

153
156
160
163
166
180
193
206
220
228

110.1
112.5
115
117.5
120
130
140
150
160
165.8

500

190.53

C.T.

1659
1700
1800
1900
2000
2100
2200
2236

229
233
246
260
273
286
300
305

165.9
170
180
190
200
210
220
223.6

800

304.84

C.T.

NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION


127/220 V
COMMERCIAL CUSTOMERS ( T-2 )
COVERED AREA
SQ METER

TOTAL
CONNECTED
LOAD (KVA)

UNIT A/C
CONNECTED
LOAD (KVA)

CONTRACTED LOAD
C.B RATING
(KVA)
(Amps)

KWH Meter

25
50
55

6
10
11

3
6
6.6

30

11.43

3x25 (100)

56
75
100
125

12
16
22
27

6.7
9
12
15

60

22.86

3x25 (100)

126
150
175
200
225
230

28
32
36
40
43
49

15.1
18
21
24
27
27.6

100

38.11

3x25 (100)

231
250
275
300
325
350

50
54
59
64
70
75

27.7
30
33
36
39
42

150

57.15

3x40 (160)

351
375
400
425
449

76
80
86
91
95

42.1
45
48
51
53.9

200

76.21

C.T.

450
475
500
525
550
575

96
102
107
112
118
123

54
57
60
63
66
69

300

114.3

C.T.

Size (Amps)

300
600
624

128
133

114.3

C.T.

72
74.9

NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION


127/220 V
COMMERCIAL CUSTOMERS ( T-2 )
COVERED AREA
SQ METER

TOTAL
CONNECTED
LOAD (KVA)

UNIT A/C
CONNECTED
LOAD (KVA)

625
650
675
700
711

134
139
144
150
152

75.5
78
81
84
85.3

712
725
750
775
800
825
850
875
900
925
950
975
1000
1025
1050
1069

153
155
160
166
171
176
182
187
192
198
203
208
214
219
224
228

85.4
87
90
93
96
99
102
105
108
111
114
117
120
123
126
128

1070
1075
1100
1125
1150
1175
1200
1300
1400
1429

229
230
235
240
246
250
256
278
299
305

128.4
129
132
135
138
141
144
156
168
171.5

CONTRACTED LOAD
C.B RATING
(KVA)
(Amps)

400

500

800

KWH Meter
Size (Amps)

152.4

C.T.

190.5

C.T.

304.8

C.T.

NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION


RESIDENTIAL CUSTOMERS 220/380 V

( T-3 )

COVERED AREA
SQ METER

TOTAL
CONNECTED
LOAD (KVA)

UNIT A/C
CONNECTED
LOAD (KVA)

CONTRACTED LOAD
C.B RATING
(KVA)
(Amps)

KWH Meter

25
50
75
100
124

4
8
12
16
19

2.5
5
7.5
10
12.4

30

19.74

3x25 (100)

125
150
175
200
225
250
275
300
312

20
24
28
32
36
40
43
46
47

12.5
15
17.5
20
22.5
25
27.5
30
31.2

60

39.48

3x25 (100)

313
325
350
375
400
425
450
475
500
525
550
575
599

48
50
53
56
60
63
66
70
73
76
80
83
85

31.3
32.5
35
37.5
40
42.5
45
47.5
50
52.5
55
57.5
59.9

100

65.8

3x25 (100)

600
625
650
675
700
725
750
775
800
825

86
90
93
96
100
103
106
110
113
116

60
62.5
65
67.5
70
72.5
75
77.5
80
82.5

150

98.7

3x40 (160)

Size (Amps)

850
875
900
930

120
123
126
130

85
87.5
90
93

NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION


RESIDENTIAL CUSTOMERS 220/380 V

( T-3 )

COVERED AREA
SQ METER

TOTAL
CONNECTED
LOAD (KVA)

UNIT A/C
CONNECTED
LOAD (KVA)

CONTRACTED LOAD
C.B RATING
(KVA)
(Amps)

KWH Meter

931
950
975
1000
1025
1050
1075
1100
1125
1150
1175
1188

131
133
136
140
143
146
150
152
156
160
163
164

93.1
95
97
100
102.5
105
107.5
110
112.5
115
117.5
118.8

200

131.6

C.T.

1189
1200
1300
1400
1500
1600
1679

165
166
180
193
206
220
230

118.9
120
130
140
150
160
167.9

300

197.4

C.T.

1680
1700
1800
1900
1923

231
233
246
260
263

168
170
180
190
192.3

400

263.2

C.T.

1924
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
2916

264
273
286
300
313
326
340
353
366
380
393
395

192.4
200
210
220
230
240
250
260
270
280
290
291.6

500

329

C.T.

2917

396

291.7
800

526.4

C.T.

Size (Amps)

3000
3890

406
526

800

300
389

526.4

C.T.

NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION


COMMERCIAL CUSTOMERS 220/380 V

( T-4 )

COVERED AREA
SQ METER

TOTAL
CONNECTED
LOAD (KVA)

UNIT A/C
CONNECTED
LOAD (KVA)

CONTRACTED LOAD
C.B RATING
(KVA)
(Amps)

KWH Meter

25
50
75
92

6
10
16
19

3
6
9
11

30

19.74

3x25 (100)

93
100
125
150
175
200
224

20
22
27
32
38
43
47

11.2
12
15
18
21
24
26.9

60

39.48

3x25 (100)

225
250
275
300
325
350
375
399

48
54
59
64
70
75
80
85

27
30
33
36
39
42
45
47.9

100

65.8

3x25 (100)

400
425
450
475
500
525
550
575
600
611

86
91
96
102
107
112
118
123
128
130

48
51
54
57
60
63
66
69
72
73.3

150

98.7

3x40 (160)

612
625
650
675
700
725

131
134
139
144
150
155

73.4
75
78
81
84
87

200

131.6

C.T.

Size (Amps)

200
750
772

160
164

131.6

C.T.

90
92.6

NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION


COMMERCIAL CUSTOMERS 220/380 V
COVERED AREA
SQ METER

TOTAL
CONNECTED
LOAD (KVA)

UNIT A/C
CONNECTED
LOAD (KVA)

773
775
800
825
850
875
900
925
950
975
1000
1025
1050
1075

165
166
171
176
182
187
192
198
203
208
214
219
224
230

92.8
93
96
99
102
105
108
111
114
117
120
123
126
129

1076
1100
1125
1150
1175
1200
1233

231
235
240
246
250
256
263

129.1
132
135
138
141
144
148

1234
1300
1400
1500
1600
1700
1800
1852

264
278
299
320
342
363
384
395

148.1
156
168
180
192
204
216
222.2

1853
1900
2000
2100
2200
2300
2400
2465

396
405
427
448
469
491
512
526

222.4
228
240
252
264
276
288
295.8

( T-4 )
CONTRACTED LOAD
C.B RATING
(KVA)
(Amps)

KWH Meter
Size (Amps)

300

197.4

C.T.

400

263.2

C.T.

500

329

C.T.

800

526.4

C.T.

INDIVIDUAL EQUIPMENT DEMAND FACTORS


( TABLE - 5 )
CONTRACTED LOAD

S/N

TYPE OF LOAD

RESIDENTIAL

COMMERCIAL

INDUSTRIAL

AGR.FARMS

CENTRAL A/CS

WINDOW TYPE A/CS

0.6

0.6

0.7

0.7

LIGHTING ( INTERIOR / EXTERIOR )

REFRIGERATION / COOLING

0.6

0.6

0.6

0.6

FANS/BLOWERS

0.2

0.2

0.2

0.2

EQUIPMENT USED IN KITCKENS

0.2

0.2

0.2

___

WATER HEATERS

0.2

0.2

0.2

___

LAUNDARY EQUIPMENT

0.2

0.2

0.2

___

APPLIANCES USED FOR RECREATION

0.2

0.2

___

___

10

APPLIANCES USED FOR SEVICES

0.2

0.2

0.2

___

11

EQUIPMENT USED IN OFFICE/LABS

____

0.2

0.2

___

12

WELDING EQUIPMENT

____

0.15

0.15

___

13

ELECTRIC MOTORS USED FOR CRAFTS,


____

0.25

0.25

___

____

____

0.4

0.4

PROCESS AND MASS PRODUCTION

____

____

0.6

___

16

PROCESS HEATING USING OVENS

____

____

0.35

___

17

PROCESS HEATING USING FURNACES

____

____

0.75

___

18

MISCELLANEOUS ( NOT COVERED ABOVE )

0.1

0.1

0.1

0.1

WORKSHOPS & SERVICE CENTERS


14

ELECTRIC MOTORS USED FOR BATCH WORKS,


FLUCTUATING OR MULTIPLE PRODUCTION

15

ELECTRIC MOTORS USED FOR CONTINOUS

DIVERSITY FACTORS
( TABLE - 6 )
NO OF CUSTOMERS

APPLICABLE

NO OF CUSTOMERS

APPLICABLE

IN THE GROUP ( N)

DIVERSITY FACTOR ( DVF)

IN THE GROUP ( N)

DIVERSITY FACTOR ( DVF)

1.603

1.383

10

1.615

1.453

11--15

1.656

1.497

16--20

1.681

1.529

21--30

1.712

1.553

31--50

1.745

1.572

50--100

1.798

1.59

ABOVE 100

1.8

DVF = 1.25/(0.67+(.33/N ))

CF = (0.67+(.33/N )) / 1.25

DVF = DIVERSITY FACTOR

CF = COVERAGE FACTOR

CABLE AND BREAKER SIZE TABLE ACCORDING TO SCECO


connected Amp Range

Minimum (cu)

Maximum (cu)

Maximum

Cable Size

Cable Size

C.B. Size

GT

LE

mm2

mm2

Amp.

30

4x25

4x25

30

30

72

4x35

4x35

60

72

130

4x35

4x50

100

130

198

4x50

4x50

150

198

250

4x95

4x120

200

250

350

4x150

4x185

300

350

400

4x240

4x240

400

400

500

4x240

2x4x240

500

500

600

2x4x240

2x4x300

600

600

700

2x4x300

2x4x300

700

700

800

2x4x300

2x4x300

800

800

1000

3x4x240

3x4x240

1000

1000

1250

7x1x630

7x1x630

1250

1250

1600

7x1x630

7x1x630

1600

1600

2000

11x1x630

11x1x630

2000

2000

2500

14x1x630

14x1x630

2500

2500

3000

14x1x630

14x1x630

3000

Derating factors for low voltage cable ( Sauidi cable company )

Table 15
Derating factors for variation in ground temprature
Ground temperature ( C )

25

30

35

40

45

50

XLPE Insul.cable

1.09

1.04

1.00

0.95

0.90

0.85

PVC ( rated 85 C ) cable

1.10

1.05

1.00

0.95

0.89

0.84

PVC ( rated 70 C ) cable

1.13

1.07

1.00

0.93

0.85

0.76

Table 16
Derating factors for variation in depth of burial ( to centre of the trefoil group of cables )
Depth of
laying ( Meter )

600/1000 volt cable


_________________________________________________________
up to
70 mm2 to
Above
50 mm2

300 mm2

300 mm2

0.60

0.99

0.98

0.97

0.80

0.97

0.96

0.94

1.00

0.95

0.93

0.92

1.25

0.94

0.92

0.89

1.50

0.93

0.9

0.87

1.75

0.92

0.89

0.86

2.00

0.91

0.88

0.85

Table 17
Derating factors for variation in thermal resistivity of soil
Thermal resistivity of
soil ( k.m/w )

0.80

0.90

1.00

1.20

1.50

2.00

Rating factor

1.17

1.12

1.07

1.00

0.89

0.84

25

30

35

40

45

50

XLPE Insul.cable

1.14

1.10

1.05

1.00

0.95

0.89

PVC ( rated 85 C ) cable

1.15

1.11

1.05

1.00

0.94

0.88

PVC ( rated 70 C ) cable

1.22

1.15

1.08

1.00

0.91

0.82

Table 18
Derating factors for variation in air temprature
Ground temperature ( C )

Table 19
Group derating factors for multicore cables in flat formation
Spacing
_______________________________________________________

No of cables in group

Touching

0.15 m

0.30 m

0.81

0.87

0.91

0.70

0.78

0.84

0.63

0.74

0.81

0.59

0.70

0.78

0.55

0.68

0.77

Table 20
Group derating factors for three single core cables in trefoil formation
Spacing
_______________________________________________________
No of cables in group

Touching

0.15 m

0.30 m

0.78

0.83

0.88

0.66

0.73

0.79

0.61

0.68

0.73

0.56

0.64

0.73

0.53

0.61

0.71

Current Carrying Capacity

Table 7
Current Carrying Capacity
Single core cables with copper conductor XLPE insulated and PVC sheathed
Cross
Section

mm2

In ground
In air
_____________________________________________________________________
Direct laid
In duct
Free
In Pipe

______________________________________________________________________________________________
Amps.
Amps.
Amps.
Amps.

1.5

30

22

22

19

2.5

39

29

29

24

50

38

38

32

63

47

49

40

10

83

63

66

54

16

107

82

88

70

25

137

105

116

92

35

165

127

143

112

50

195

151

175

134

70

238

187

222

168

95

286

225

274

205

120

327

258

326

237

150

363

290

367

269

185

410

330

425

308

240

474

382

505

361

300

532

431

583

411

400

600

489

676

469

500

673

550

779

533

630

752

615

900

603

Table 7
Current Carrying Capacity
Three and four core cables with copper conductor XLPE insulated and PVC sheathed
Cross

In ground

In air

Section

_____________________________________________________________________________
Unarmoured

Armoured

Unarmoured

________________________________________________________________________________
Direct laid
In duct
Direct laid
Free
mm2

Amps.

Amps.

Amps.

Amps.

1.5

27

22

22

2.5

35

29

29

45

37

46

38

56

46

57

48

10

76

62

76

67

16

98

80

98

88

16

98

80

98

88

25

128

104

128

118

35

157

125

158

142

50

187

149

188

175

70

229

183

229

220

95

276

220

274

272

120

313

251

310

316

150

350

283

346

363

185

395

321

387

418

240

458

372

444

496

300

516

420

494

571

400

584

478

549

665

500

655

538

597

760

EXAMPLE ACTUAL ( MADINA PROJECT )


1000 AMP. FOR A/C PANEL , FEEDER 3 X ( 3X300+150 ) MM2 ,UNARMOURED ON CABLE TRAY TEMP 50 C
CHECK THE AMPACITY AFTER DERATING

AMPACITY FROM TABLE 7 FOR THE MENTION CABLE , ( 571 ) AMP.


DERATING FACTOR ACC TO 3 CABLE IN GROUP AND TEMP, 50 C , TABLES 20,18
DERATING FACTORS = ( 0,78 X 0.89 ) = 0.69
DERATING AMPACITY = 571 X ( 0,78 X 0.89 ) X 3 = 1189 AMP.
DERATING AMPACITY = 571 X ( 0,78 X 0.89 ) X 3 = 1189 AMP.

EXAMPLE ACTUAL ( MADINA PROJECT )


2500 AMP. FOR MDP PANEL , FEEDER 6 X ( 3X300+150 ) MM2 , DIRECT LAID UNARMOURED CABLE
CHECK THE AMPACITY AFTER DERATING
AMPACITY FROM TABLE 7 FOR THE MENTION CABLE , ( 516 ) AMP.
DERATING FACTOR ACC TO 6 CABLE IN GROUP AND GROUND TEMP, 50 C , TABLES 20,15
DERATING FACTORS = ( 0,71 X 0.85 ) = 0.60
DERATING AMPACITY = 516 X ( 0,71 X 0.85 ) X 6 = 1868 AMP.
DERATING AMPACITY = 516 X ( 0,71 X 0.85 ) X 6 = 1868 AMP.

EXAMPLE ACTUAL ( MADINA PROJECT )


2500 AMP. FOR MDP PANEL , FEEDER 14 X ( 1X630 ) MM2 , DIRECT LAID UNARMOURED 1 PH CABLE
CHECK THE AMPACITY AFTER DERATING
AMPACITY FROM TABLE 6 FOR THE MENTION CABLE , ( 752 ) AMP.
DERATING FACTOR ACC TO 4 CABLE IN GROUP AND GROUND TEMP, 50 C , TABLES 20,15
DERATING FACTORS = ( 0,73 X 0.85 ) = 0.62
DERATING AMPACITY = 752 X ( 0,73 X 0.85 ) X 4 = 1866 AMP.
DERATING AMPACITY = 752 X ( 0,73 X 0.85 ) X 4 = 1866 AMP.

AMPACITY FOR MULTICORE CABLES


1- UNBUIRED CABLES

DATA OF CABLES SHOULD BE KNOWN


rated

CABLE SIZE

AMPACITY

INSTALLATION FACTOR

TEMP. FACTOR

GROUP FACTOR

(A)

K1

K2

K3

88

0.7

LOAD KW
voltage

mm2

380

16

25

380

16

25

88

0.7

RESULT
MAX.CIRCUIT CURRENT Iz (A)
RATED CURRENT Ib (A)

CIRCUIT BREAKER In (A)

COMMENTS
DERATED AMPACITY
FOR CIRCUIT BRAKER

47.48

62

62

Ib In Iz

50

55

0.85

0.80

0.84

0.77

0.76

0.65

2.00

2.00

0.84

0.77

50

55

0.89

0.84

0.88

0.82

0.82

0.71

____________
In Pipe

____________
Amps.
19
24
32
40
54
70
92
112
134
168
205
237
269
308
361
411

469
533
603

In air

___________________________________________________
Unarmoured

Armoured

________________________________________________
Free
In Pipe
Free
Amps.

Amps.

Amps.

22

18

29

24

38

31

39

48

39

50

67

52

67

88

68

89

50 C

88

68

89

118

90

120

142

107

149

175

129

182

220

161

229

272

196

280

316

226

322

363

258

368

418

295

420

496

346

491

571

394

557

665

454

636

760

515

705

GROUP FACTOR
COMMENT
K3

K1 Type of installation for cable tray = 1


Data from table H1-13 Page 235 schnieder
0.7

Data for K2 from above table no 18


Data for K3 from above table no 19

0.7
Data for K3 from above table no 19

COMMENTS

R CIRCUIT BRAKER

Ib In Iz

Approximate voltage drop at 60 hz for single core stranded plain copper / aluminium conductors
XLPE insulation , PVC sheath 600/1000 volts
Nominal area of
conductor

Copper conductor

Aluminium conductor

mv / amp / m

mv / amp / m

1.5

22.9

2.5

14.1

8.8

5.9

10

3.6

16

2.3

3.7

25

1.5

2.4

35

1.1

1.8

50

0.84

1.3

70

0.61

0.95

95

0.47

0.71

120

0.39

0.58

150

0.34

0.5

185

0.29

0.42

240

0.25

0.34

300

0.22

0.29

400

0.19

0.25

500

0.17

0.22

630

0.16

0.19

data for single phase cable must be known


length of cable

rated current

rated voltage

in meter

in amp

in volt

14

11.4

220

% voltage drop
in percentage

0.64

single phase cable


the percentage voltage drop =

nium conductors

ble must be known


Parallel Case

mv/amp/m

Number of Cable

from above table

8.80

hase cable

0.64

Approximate voltage drop at 60 hz for three and four core stranded plain copper / aluminium
XLPE insulation , PVC sheath 600/1000 volts
Nominal area of
conductor

Copper conductor

Aluminium conductor

mv / amp / m

mv / amp / m

1.5

22.8

2.5

14

8.7

5.9

10

3.5

16

2.2

25

1.5

35

1.1

50

0.81

70

0.58

95

0.44

120

0.37

150

0.31

185

0.27

240

0.23

300

0.20

400

0.18

500

0.15

data for three phase cable must be


length of cable

rated current

rated voltage

in meter

in amp

in volt

100

100

380

% voltage drop
in percentage

2.13

three phase cable


the percentage voltage drop =

re stranded plain copper / aluminium conductors

Aluminium conductor
mv / amp / m

3.7
2.4
1.7
1.3
0.92
0.68
0.56
0.47
0.39
0.32
0.27
0.23
0.20

three phase cable must be known


rated voltage

(Parralel Case)

mv/amp/m

in volt

Number of cable

from above table

380

0.81

three phase cable

ntage voltage drop =

2.13

Single Core THHN Wires ( 600 V )


Copper Conductor PVC Insulated NAYLON Jacketed THHN / THWN Wires UL 83,1581
Equiv.

Overall
Diameter

AWG
mm

Comment

mm

18

0.82 ~ 1

2.3

16

1.31 ~ 1.5

2.5

14

2.08 ~ 2

2.9

12

3.31 ~ 4

3.4

10

5.26 ~ 6

4.3

8.37

5.6

Single Core
Unarmoured Cable - Copper Conductors XLPE insulation , PVC sheath 600/1000 volts
Nominal

Overall

Area

Diameter

mm

mm

1x1.5

1x2.5

1x4

1x6

1x10

1x16

10

1x25

11

1x35

13

1x50

14

1x70

16

1x95

18

1x120

20

1x150

22

1x185

24

1x240

27

1x300

30

1x400

34

1x500

37

1x630

42

Comment

Two Core
Unarmoured Cable - Copper Conductors XLPE insulation , PVC sheath 600/1000 volts
Nominal

Overall
Comment

Nominal

Overall

Area

Diameter

mm

mm

2x1.5

13

2x2.5

13

2x4

14

2x6

16

2x10

17

2x16

19

2x25

23

2x35

25

Comment

Three Core
Unarmoured Cable - Copper Conductors XLPE insulation , PVC sheath 600/1000 volts
Nominal

Overall

Area

Diameter

mm

mm

3x1.5

11

3x2.5

12.5

3x4

13.5

3x6

15.5

3x10

19

3x16

21.5

Comment

four Core
Unarmoured Cable - Copper Conductors XLPE insulation , PVC sheath 600/1000 volts
Nominal

Overall

Area

Diameter

mm

mm

4x1.5

13

4x2.5

15

4x4

16

4x6

17

4x10

20

4x16

22

4x25

26

4x35

26

4x50

30

Comment

4x50

30

4x70

34

4x95

38

4x120

43

4x150

47

4x185

52

4x240

58

4x300

64

4x400

73

4x500

80

DATA OF CABLES SHOULD BE KNOWN


PIPES

PIPES

CABLE

CONDUCTOR

EARTHING

SIZE INCH

SIZE INCH

SIZE mm2

DIAMETER mm

DIAMETER mm

1.5

38.1

15.5

RESULT

INSIDE PIPE AREA mm2

CABLE AREA mm2

FILLING FACTOR

823.3

188.6

0.23

No.Of Cables
No.Of Wire

FILLING FACTOR

0.23