Outline
Commissioning Product Physical Layout Information Needed Start up Procedure Testing and Adjusting CAT PC Software Gain Settings
CAUTION
Information Needed
Generator Set Rating Voltage Current Frequency Power Power Factor Generator Time Constants (Td0 & Te) Protection Settings Generator Over / Under Voltage Trip Value and Time Delay Over Excitation Type, Trip Value and Time Setting Reverse kvar Trip Value and Time Delay Exciter Diode Monitor Ripple Current Trip Value Loss of Sensing Time Delay
Startup Connections
Startup Connections
Startup Connections
PMG Power, 1-Phase Sensing
Startup Connections
Startup Connections
Startup Connections
Startup Connections
Startup Connections
AREP Power, 3-Phase Sensing
Establish Communications
Establish Communications
Password = CAT
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Establish Communications
Communications Established
Load Compensation
106 105 104 103 102 101 100 99 98 97 96 -100 -50 0 50 100 150 % Reactive Load
% Rated Voltage
Soft Start
generator voltage Vref
SS bias
SS time
Tdo from Generator Data Sheet Te ranges from 0.06s to 0.26s see Table 9
Cannot be saved in EEPROM Cycling power causes function to become disabled on power up Generator Overvoltage (105 135%, 2 30s, 135%, 2s default) Generator Undervoltage (60 95%, 10 120s, 60%, 30s default)