JSWEL Title: TEST REPORT FOR RET 670 RELAY Doc. No: Date: Page: EM/F/58/00 24.02.

2011
PAGE 1 OF 4

TEST REPORT OF TRANSFORMER PROTECTION RELAY RET670


TESTING DATE : 19/01/13 SERVICE : Transformer-7 CURRENT/ VOLTAGE INJECTION UNIT NAME/ MODEL: DOBLE KIT/ F-6150 INJECTION UNIT SL No : 061003858

GENERAL INFORMATION & DATA TRANSFORMER DATA


Voltage Ratio HV LV1 LV2 Make Auxiliary supply Type 220 / 34.5 / 11.5 MVA FL Current (A) 130MVA 80MVA 50MVA ABB 220V DC RET670 341A 1339A 2510A Vector Group Protection CT Ratio (Diff-600/1), (REF-500/1), (StandbyEF-200/1) 1500/1 (Diff-2500/1), (REF3000/1), (standby400/1) Software version Serial Number Rating YNd11yn0 Metering CT Ratio 600/1

RELAY DETAILS
1.1Rev01 I0733014 Ir=1A, Ur=110V, 50Hz

A. Differential Protection (87T) :1) Pick Up


PHASE HV SIDE R Y B R Y B R Y B Setting in % of Primary current 20%=0.2XIbase 20%=0.2XIbase 20%=0.2XIbase 20%=0.2XIbase 20%=0.2XIbase 20%=0.2XIbase 20%=0.2XIbase 20%=0.2XIbase 20%=0.2XIbase Set Value in Amps 0.1136 0.1136 0.1136 0.29 0.29 0.29 0.5221 0.5221 0.5221 Operated Value 0.115 0.115 0.115 0.291 0.291 0.291 0.523 0.523 0.523 Master Trip operated or Not operated operated operated operated operated operated operated operated operated Remarks

LV2 SIDE 19/01/13 DATE

LV1 SIDE

2) Stability
Indra/Nilesh/Murgan PERFORMED BY M.DEVARAJULU CHECKED BY

JSWEL Title: TEST REPORT FOR RET 670 RELAY Doc. No: Date: Page: HV
0.217L0 0.217L0 0.217L240 0.217L240 0.217L120 0.217L120

EM/F/58/00 24.02.2011
PAGE 2 OF 4

PHASE
R-phase R-phase Y-phase Y-phase B-phase B-phase

HV
0.568L0 0.568L0 0.568L240 0.568L240 0.568L120 0.568L120

LV-1
1.449L210 1.449L195 1.449L90 1.449L75 1.449L330 1.449L315

LV-2
1L180 1L150 1L60 1L30 1L300 1L270

REMARKS
STABLE TRIP STABLE TRIP STABLE TRIP

3)Test Slope ( checked for (a) ES1=1.25,S2=30% & (b) ES1=1.0,S2=30%,ES2=1.5,S3=50%) a)S2=30%
Current @ 1.3% R-phase Y-phase B-phase Current @ 1.5% R-phase Y-phase B-phase HENCE S2=33% FOUND HV 0.738L0 0.738L240 0.738L120 HV 0.852L0 0.852L240 0.852L120 LV-1 1.884L210 1.884L90 1.884L330 LV-1 2.174L210 2.174L90 2.174L330 I1=443.3A I2=547A Id1=104A Ib1=495 I11=511A I22=642A Id2=131A Ib2=576A

b) S3=50%
Current @ 1.6% R-phase Y-phase B-phase Current @ 1.8% R-phase Y-phase B-phase HENCE S3=51% FOUND HV 0.909L0 0.909L240 0.909L120 HV 1.021L0 1.021L240 1.021L120 LV-1 2.319L210 2.319L90 2.319L330 LV-1 2.609L210 2.609L90 2.609L330 I1=545 I2=810 Id1=265 Ib1=677 I11=613 I22=925 Id2=313 Ib2=769

4) Harmonic blocking a) I2/I1 Phase Setting


R-phase Y-phase B-phase

Operated 15
0.149/1,100/50Hz 0.149/1,100/50Hz 0.149/1,100/50Hz

Remark

b) I5/I1
19/01/13 DATE Indra/Nilesh/Murgan PERFORMED BY M.DEVARAJULU CHECKED BY

JSWEL Title: TEST REPORT FOR RET 670 RELAY Doc. No: Date: Page: EM/F/58/00 24.02.2011
PAGE 3 OF 4

Phase
R-phase Y-phase B-phase

Setting 25 %

Operated
0.255/1,250/50Hz 0.255/1,250/50Hz 0.255/1,250/50Hz

Remark

B. HV Restricted Earth Fault Protection:PHASE Setting in % of Primary current 40% X I base Set Value in Amps 200A Operated Value 200.5 A ( 0.401A) Master Trip operated or Not Operated Remarks

C. LV Restricted Earth Fault Protection:PHASE Setting in % of Primary current 40% X Ibase Set Value in Amps 1200A Operated Value 0.397A Master Trip operated or Not Operated Remarks

D. HV Timed Over Current (TOC) Protection:1) TOC1


PHASE R Y B Setting in % of Primary current 110%X Ibase 110% X Ibase 110% X Ibase Set Value in Amps 375A 375A 375A Operated Value I(A) 2XIset 2XIset 2XIset T(sec) 2.54 2.54 2.54 Master Trip operated or Not operated operated operated Remarks Current Injected in all the Phases. Operating as per NI Curve

2) TOC2
PHASE R Y B Setting in % of Primary current 550%X Ibase 550%X Ibase 550%X Ibase Set Value in Amps 1875.5 1875.5 1875.5 Operated Value I(A) 3.2L0 3.2L240 3.2L120 T(sec) 0.03 0.03 0.03 Master Trip operated or Not operated operated operated Remarks

E. HV Residual Earth Fault Protection based on residual current (TEF-1):19/01/13 DATE Indra/Nilesh/Murgan PERFORMED BY M.DEVARAJULU CHECKED BY

JSWEL Title: TEST REPORT FOR RET 670 RELAY Doc. No: Date: Page:
Operated Value 0.04 0.04 0.04 operated

EM/F/58/00 24.02.2011
PAGE 4 OF 4 Master Trip operated or Not

PHASE R Y B

Setting in % of Primary current 20% x Ibase 20% x Ibase 20% x Ibase

Set Value in Amps 68.2A 68.2A 68.2A

Remarks

F. HV Standby Earth Fault Protection:- CT Ratio:200/1


PHASE Setting in % of Primary current 20% X Ibase Set Value in Amps 40A Operated Value 0.22 Master Trip operated or Not operated Remarks

G. OVER EXCITATION: PHASE Setting in % of V/Hz R Y B 120% 120% 120%

Operated Value V/Hz 79.26/48 79.26/48 79.26/48

Master Trip operated or Not

Remarks

Operated Operated Operated

19/01/13 DATE

Indra/Nilesh/Murgan PERFORMED BY

M.DEVARAJULU CHECKED BY