Você está na página 1de 3

Parallel Operation of Synchronous Generators Requirements for parallel operation of synchronous generators: Before any two generators can

be connected together, the oncoming unit terminal voltages must: 1. have the same magnitude as the running generator, 2. be in phase with the corresponding phases of the running unit, 3. have the same phase sequence as the running generator, 4. have slightly higher frequency than that of the running generator. If the requirements 1 through 3 are not met, there will be circulating current between the generators sufficiently large that might damage the machines. The following discussion explains a method to check the above requirements: One dark two bright lamps method In this method, one lamp is connected across the a-phase of the two generators, the second lamp between the b-phase of the running generator to the c-phase of the oncoming generator, and the third lamp between the c-phase of the running machine and the b-phase of the oncoming machine as shown in the following figure. With this arrangement, the generators are paralleled when one lamp is dark and the other two are bright.

Dark

A Bright Oncoming B Generator Bright

Running Generator

Running Generator F2 DC Motor Shunt Field A1 Field Winding If A2 A2 Synch. Gen. A RL RL

RL

F1 F2

DC Motor Shunt Field A1

Synch. Gen.

F1

Field Winding If Oncoming Generator

Synchronizing Switch

Three-pahse Wattmeter

Procedure: 1. Couple one of the generators to the dc motor. Adjust its speed to 1800 rpm and its terminal voltage to rated value. Connect a 0.2 A resistive load. This generator will be the running generator. 2. Start the second generator and adjust its voltage and speed to rated values. This generator will be the oncoming generator. 3. Using the combined Dark and Bright Lamp method, parallel the oncoming generator with the running generator. Measure the line voltage, line current, and three-phase power. Also measure the field current of the generator. 4. If the two generators are properly synchronized, the oncoming generator will be floating neither supplying nor receiving power. 5. Increase the speed of the oncoming generator until it supplies half of the load power. Adjust the field current of the oncoming unit for unity power factor. For both generators measure the speed, armature current, terminal voltage, field current, and dc motor field current.

6. Keep the field excitation of the oncoming generator constant and vary its input power (speed of the dc motor) such that its armature current varies from 10% to 150% of the generator rated current. Plot generator output power vs. dc motor field current. What is the significance of this curve? 7. Readjust the input of the generator for 25% of its rated current. Holding this input constant, vary the excitation of the generator and obtain data to draw curves of generator armature current as a function of its field current. What is the significance of this curve? 8. Reduce the speed of the running generator until it is floating on the other machine and open its line circuit breakers. Reduce the load to zero and shutoff the two machines.

Você também pode gostar