Power company Station Unit Voltage Document ID Previous ID Application Engineer Approving Engineer Date of Approval Path and filename : : : : : : : : : : International Power Station 4 66 kV line to Station 2 66 kV 2001.999 1999.888 Sten-Ole Nilsen Svein Haugen 01.03.2001 c:\protect\lbn_demo\demo-uk1.wk4
2001.999
Page 1
2001.999
1* 95 FeAl OH-line 1* 300 FeAl OH-line 1* 95 FeAl OH-line 3*1* 150 Al TXSP
6,112 12,608 10,7456 52,13632 0,027816 0,163704 0 0 7,449 15,366 13,0962 63,54114 Line-tap. No currents or impedance values here
Combined data (branches excluded) : Positive sequence impedance Positive sequence impedance Zero sequence impedance Zero sequence impedance Earth-fault comp.factor ((Ro/R+)-1)/3 Earth-fault comp.factor ((Xo/X+)-1)/3 Earth-fault comp.factor ((Zo/Z+)-1)/3 Short circuit power Length of line Z+ Z+ Zo Zo CR CX CZ S l : : : : : : : : : 13,589 +j 28,138 ohms/ph 31,247 ohms 64,2 degrees Valid zero-sequence data are not available 0,000 0,000 139,4 MVA (base = 66 kV) 71,456 km
Combined capacitive data (branches included) : Line to earth capacity Capacitive earth fault current Co Io : 480,1376 nF : 17,243291 A (base = 66 kV)
Page 2
Jacobsen elektro System Data System short circuit estimation (66 kV base)
1 2 3 Fault Location 4
2001.999
Max =
Min =
Relay
400 MVA
Min
300 MVA
400 MVA
Min
300 MVA
Station 6
Station 6
Max =
124 MVA
Min =
98 MVA
Max =
Relay
Min =
Max =
Fault Location
0,910832 kA
Max
400 MVA
Max
400 MVA
400 MVA
Max
400 MVA
Station 6
Station 6
Station 6
Max =
124 MVA
Max =
124 MVA
Min =
98 MVA
Min current for arc-resistance estimation Min current for arc-resistance estimation
: :
0,545 kA 0,434 kA
Phase-distance = Phase-distance =
3 m 3 m
Page 3
Jacobsen elektro Manufacturer - Model Location Functions CT (Ip/Is) VT (Up/Us) Conversion factor Descriptions In = 1 eller 5 A Un = 110 V
Impedance Protection : Jacobsen elektro RZ 3x2 nr. : Station 4 - Station 6 : Trip line-breaker : 300 / 5 A : 66 / 0,11 kV : Z primary * 0,100 = Z sec (relay setting) Settings 5 A V Comments
2001.999
110
Setting angle Measuring zones All zone-settings indicate the total reach of each zone in forwards and reverse direction at measuring angle 64 degrees. Secondary values : Measuring zones = 0-5 ohm/ph Starting zone = 0-12 ohm/ph
Angle = 64 deg. Z1+ = Z1+ = Z1- = Z1- = Z2+ = Z2+ = Z2- = Z2- = t2 = 20 ohm/ph prim 2 ohm/ph sec. 0 ohm/ph prim ohm/ph sec. 43,5 ohm/ph prim 4,35 ohm/ph sec. 0 ohm/ph prim ohm/ph sec. 0,3 sec ohm/ph prim ohm/ph sec. ohm/ph prim ohm/ph sec. sec sec Zone 1 covers 85 % of line-length : 0.85*Line impedance =0.85*31.53=26.8 ohm No function in reverse direction
Zone 2 covers 50% of transformer : 0.5*ZT = 0.5*23.98 ohm = 12 ohm No trip in reverse direction t2 selective over transformer differential. Zone 3 is not available at this relay.
Timers Zone 2 timer (t2) = 0.2 - 3 sec Zone 3 additional time : (dt3) = 0.2 - 3 sec Starting zone - additional time : (dts) = 0.2-3 sec
Z3+ = ______ Z3+ = Z3- = ______ Z3- = t3 = ______ dt3 = Zs+ = Zs+ = Zs- = Zs- = ts = dts =
85,8 ohm/ph prim 8,58 ohm/ph sec. 0 ohm/ph prim ohm/ph sec. 0,8 sec 0,5 sec
Starting zone must cover transformer at Station 6 with a safe margin. Must not include the load impedance Load impedance = 101 ohm
Jel-R2I0 no. Standard setting in this system. Io = Io = ko = 2,5 A sec 150 A primary 0,9 ______ ko = ((Zo/Z1)-1)/3 Setting 80% of zone 1 reach
Jel-Z2EH no.
Page 4
Jacobsen elektro
Impedance Protection
2001.999
Characteristic no. 1 :
Test_1
Characteristic no. 2 :
Test_2
100 50 40 30 20
Station 6 Transformer Starting zone
50
Transformer
10 0
Station 4
0
Station 4 Zone 1 Zone 2
30
40
50
60
50
100
Page 5
Jacobsen elektro Manufacturer - Model Location Functions CT (Ip/Is) CT (Ip/Is) In primary value (HV-side) In primary value (LV-side)
Differential protection : ABB - D21se : ________________________________________________ : ________________________________________________ : : : : 200 1500 / / 5 A, class : 5 A, class : _____________________ _____________________
2001.999
140 A (rated current at transf., tap changer in middle pos.) 1400 A (rated current at transformer)
Intermediate-transformer at HV-side of the power transformer : Number of windings : 33 system side Number of windings : 40 relay side Intermediate-transformer at LV-side of the power transformer : Number of windings : 32 system side Number of windings : 30 relay side In sec. value (HV-side) In sec. value (LV-side) Adaptation error Descriptions In : 1 or 5 A
: 5,0013 A (between relay and intermediate transformer) : 4,97778 A (between relay and intermediate transformer) : 0,47026 % Settings 5 A Comments Documentation : N-AE 1455N
40 %
40 %
Summary of measuring errors : Tap changer : 12 Measuring transf.: 4 Interstage transf.: 5 Adaptation error : 0,47026 Other measuring faults : 5 Sum measuring faults :
% % % % %
26,4703 %
Page 6
Jacobsen elektro
Utility Station, unit Voltage Relay type Manufacturer - Model Selectivity plan No. Task type Test engineer Date Filename : : : : : : : : :
Test report
_______________________________________________ _______________________________________________ _______________________________________________ Definite overcurrent relay _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________
2001.999
: c:\protect\lbn_demo\demo-uk1.wk4
CT (Ip/Is)
300
5 A
Def.time overcurrent
Planned L1
Comments
Starting current I> Re-setting current Re-setting ratio Delay t> Re-setting time High-current setting I>> High-current timer t>>
Page 7