Protection index
IK 01
0.15 10 P
IK 02
0.2 10 P
IK 03
0.35 10 P
IK 04
0.5 10 P
IK 05
0.7 10 P
IK 06
1 10 P
IK 07
2 25 A
IK 08
5 25 A
IK 09
10 50 A
IK 10
20 50 A
= yes
N.B.: 1 of the hammer head 2 Fe 490-2 according to ISO 1052, hardness 50 HR to 58 HR according to ISO 6508 3 hardness HR 100 according to ISO 2039-2
44
Schneider Electric
Switchgear definition
Introduction
IEC 60 056 and ANSI C37-06 define on one hand the operating conditions, the rated characteristics, the design and the manufacture; and on the other hand the testing, the selection of controls and installation.
c The circuit breaker is a device that ensures the control and protection on a network. It is capable of making, withstanding and interrupting operating currents as well as short-circuit currents. c The main circuit must be able to withstand without damage: v the thermal current = short-circuit current during 1 or 3 s v the electrodynamic current: 2.5 Isc for 50 Hz (IEC) 2.6 Isc for 60 Hz (IEC) 2.7 Isc (ANSI), for a particular time constant (IEC) v the constant load current. c Since a circuit breaker is mostly in the "closed" position, the load current must pass through it without the temperature running away throughout the equipment's life.
Characteristics
Compulsory rated characteristics
c Rated voltage c Rated insulation level c Rated normal current c Rated short-time withstand current c Rated peak withstand current c Rated short-circuit duration c Rated supply voltage for opening and closing devices and auxiliary circuits c Rated frequency c Rated short-circuit breaking current c Rated transient recovery voltage c Rated short-circuit making current c Rated operating sequence c Rated time quantities.
Schneider Electric
45
Switchgear definition
Upeak (%)
100 90 50
1.2 s
10
50 s Standardised wave 1.2/50 s
c The insulation level is characterised by two values: v the impulse wave withstand (1.2/50 s) v the power frequency withstand voltage for 1 minute. Rated voltage
(Ur in kV) 7.2 12 17.5 24 36
Ssc e U
(in MVA) (in kV) (in kA)
This is the standardised rms. value of the maximum permissible short-circuit current on a network for 1 or 3 seconds. c Values of rated breaking current under maximum short-circuit (kA): 6.3 - 8 - 10 - 12.5 - 16 - 20 - 25 - 31.5 - 40 - 50 kA.
Rated peak withstand current (cf. 4.6 IEC 60 694) and making current (cf. 4.103 IEC 60 056)
The making current is the maximum value that a circuit breaker is capable of making and maintaining on an installation in short-circuit. It must be greater than or equal to the rated short-time withstand peak current. Isc is the maximum value of the rated short-circuit current for the circuit breakers' rated voltage. The peak value of the short-time withstand current is equal to: 2.5 Isc for 50 Hz 2.6 Isc for 60 Hz 2.7 Isc for special applications.
46