Escolar Documentos
Profissional Documentos
Cultura Documentos
Overview
Delta-Y Transformer Connection Delta-Y Transformer Analysis Transformer Phase Shifts Y-Delta Transformer Connection Y-Delta Transformer Analysis Practical Considerations
Dr. Louie
-Y Transformer
Secondary has a neutral connection Primary connected topto-bottom Line-line voltages appear on the coils on primary Phase voltages appear on the coils on the secondary Less insulation needed on HV winding
Ia Iab
Vab
+
-Y Transformer Analysis
Ia
Van
+
By Faradays Law:
Vab will be in-phase with Van Phase shift introduced
Ia Iab
Vab
+
Ia
Van
+
Ib Ibc
Vbc
+
By KCL:
Ia = Iab Ica
Ib
Vbn
+
By Amperes Law:
Iab will be in-phase with Ia Phase shift introduced
Ib
Ibc
Vbc
+
Ib
Vbn
+
Ic Ica
Vca
+
Ic
Vcn
+
Ic
Ica
Vca
+
Ic
Vcn
+
Dr. Louie
Dr. Louie
-Y Transformer Analysis
Phasor Diagram for Ideal Delta-Y Connected Transformer
Van
Ia = Iab Ica
Van Vbn
30o
Van Ic
30o phase shift from primary to secondary
Iab
30o 30o
Iab
30o
Ica
Ib Ibc
30o phase shift from primary to secondary
Vbn
Vbn
Dr. Louie
Dr. Louie
10/25/2012
Three-Phase Transformer Analysis: Delta-Y Let k be the transformer voltage gain For -Y transformers:
Va'n' nVab nVan 3e
j 6 j 6
kVan
Important result!
Current relationships
Ia' Ib ' Ic '
7
3n
Ia k Ib k Ic k
primary
secondary
Dr. Louie
Dr. Louie
Question
Consider an ideal Delta-Y transformer, with 20 turns on each primary coil, and 80 turns on each secondary coil. If the primary side values are:
Vab Ia 208 0 V 10 5 A
Question
Consider an ideal Delta-Y transformer, with 20 turns on each primary coil, and 80 turns on each secondary coil. If the primary side values are:
Vab Ia 208 0 V 10 5 A
j j
10 5 6.92 30
Dr. Louie
Dr. Louie
10
Y- Transformer
No neutral point on secondary Van, Vab in phase Ian, Iba in phase
Similar results for b, c phase
Ia
Van
+
Ia
Ib
Vbn
+
Icb
+ V -bc
Ib
kVab
Phase voltage across primary coils Line voltage across secondary coils
therefore k =
Important result
Ic
Vcn
+
Iac
V -ca
+
Ic
Note: phase shift is -300, whereas for Delta-Y transformer connection in previous slides it is +30o
n
11 12
Dr. Louie
Dr. Louie
10/25/2012
Question
Is there any concern in connecting a three phase Y-Delta transformer in parallel with a three phase Delta-Y transformer? Assume the transformers are appropriately rated.
Y-Delta Transformer
To achieve at +30o phase shift connect as shown Note the phasing on the secondary Van, Vac in phase Ian, Ica in phase
Ia
Van
+
Ica
Vac
+
Ia
Ib
Vbn
+
Ibc
V -cb
+
Ic
Ic
Vcn
+
Iab
V -ba
+
Ib
n
13 14
Dr. Louie
Dr. Louie
Y-Delta Transformer
A side note: Vbn
1 3 Vab e
j 6
kVab
+ Vab
n
Vcn
-Vbn
30o 30o
therefore k
Vab
Va'n'
j 6
Van
Va'b ' e 3
nVan e 3
kVan
Vbn +
primary
secondary
Vbn
Dr. Louie
16
kVan
Ia k
VanIa
n b
For ideal three-phase xfmrs, power is conserved, as in the single phase case
primary
secondary
Dr. Louie
17
Dr. Louie
18
10/25/2012
1 k
2
ZL
Dr. Louie
19
Dr. Louie
20
n b
n b
low
a
high
30
bottom
Va 'n ' n Van 3 30
low
a
high
n b c b c
n b c b c
low
Dr. Louie
high
21
Dr. Louie
low
high
22
n c b
b c
n b
b c
n b b c
low
Van
high
Vac Van Vba
low
Van
high
Vac Van Vba
high
Van Vca
low
Vab Van
Vcn
Vbn
Vcb
Vcn
Vbn
Vbc
Dr. Louie
23
Dr. Louie
24
10/25/2012
Example
Draw the connections, polarity markers and label the primary and secondary phases for a Delta-Wye step down transformer (assume left side is the high side)
Example
Need secondary (right) side to be regressed in phase by 30 degrees (per convention)
Vca Vcn
Vcn
Vab
30o
Van
Vbn
30o
Van
Vbn Vbc
Dr. Louie
25
Dr. Louie
26
Example
-Vca must be connected to Van winding -Vab must be connected to Vbn winding -Vbc must be connected to Vcn winding
Ia
Vab
+
Ib
Vbc
+
+30o
Ic
Vcn
+ -
Ic
Vca
+
Ia
Van
+ -
Van -
Rc/3
jXm/3 +
e1
-
Dr. Louie
27
Dr. Louie
28
Example
Consider three, single-phase transformers. The transformers have the following specifications:
720VA, 360/120V, RH = 18.9 , XH = 21.6 , RL = 2.1 , XL = 2.4 , RcH = 8.64k , XmH = 6.84k
+30o shift when primary is lower voltage and secondary is higher voltage
Zha + Van Rc jXm
+
Ia
N1
N2 Z /3 la I
Draw the per-phase equivalent circuit if the transformers are connected as Delta-Y What are the nominal line voltages on each side of the transformer?
e1
-
+ Van -
Dr. Louie
29
Dr. Louie
30
10/25/2012
Example
Nominal per-phase voltage on primary is 360V and 208V on secondary
Nominal primary line voltage: 360V Nominal secondary line voltage: 208V
6.3 + j7.2
Example
Consider three, single-phase transformers. The transformers have the following specifications:
720VA, 360/120V, RH = 18.9 , XH = 21.6 , RL = 2.1 , XL = 2.4 , RcH = 8.64k , XmH = 6.84k
I a
2.1+ j2.4
+ Van 2.88k
j2.28k
e1
-
e2
-
+ Van -
Draw the per-phase equivalent circuit if the transformers are connected as Y-Delta What are the nominal line voltages on each side of the transformer?
30
Dr. Louie
31
Dr. Louie
32
Example
Nominal per-phase voltage on primary is 360V and 69V on secondary
Nominal primary line voltage: 624V Nominal secondary line voltage: 120V
18.9 + j21.6
Practical Considerations
Medium-voltage industrial facilities often use -Y incoming transformers Y-side is grounded through a resistor
Reduces ground current during fault Reduces voltage dip during fault
I a
a a
0.7+ j0.8
+ Van 8.64k
j6.84k
e2
-
+ Van c b c
n b
5.196
30
primary
Dr. Louie
secondary
Dr. Louie
33
34
Practical Considerations
Practical Considerations
Source: Mozina, C.J.; , "Protection and Commissioning of Digital Transformer Relays: Improvements in Medium-Voltage Industrial Transformer Protection," Industry Applications Magazine, IEEE , vol.18, no.6, pp.63-73, Nov.-Dec. 2012
Source: Wang, M.; Vandermaar, A.J.; Srivastava, K.D.; , "Review of condition assessment of power transformers in service," Electrical Insulation Magazine, IEEE , vol.18, no.6, pp.12-25, Nov.-Dec. 2002
Dr. Louie
35
Dr. Louie
36
10/25/2012
Practical Considerations
Condition assessment of transformers:
Wang, M.; Vandermaar, A.J.; Srivastava, K.D.; , "Review of condition assessment of power transformers in service," Electrical Insulation Magazine, IEEE , vol.18, no.6, pp.12-25, Nov.-Dec. 2002 [available online in IEEE Xplore through SU library]
Summary
There is a complex gain associated with Y-Delta and Delta-Y transformers Connection of transformer coils allows for different phase shifts to be achieved Convention: phase-neutral voltages advance by 30 degrees from lower voltage to higher voltage side Power in ideal three phase transformers is conserved Impedances are transferred from secondary to 1 ZL primary by: 2
k
Dr. Louie
37
Dr. Louie
38