Você está na página 1de 7

10/25/2012

Overview
Delta-Y Transformer Connection Delta-Y Transformer Analysis Transformer Phase Shifts Y-Delta Transformer Connection Y-Delta Transformer Analysis Practical Considerations

17-Three Phase Transformers Part 2

ECEGR 450 Electromechanical Energy Conversion

Dr. Louie

-Y Transformer
Secondary has a neutral connection Primary connected topto-bottom Line-line voltages appear on the coils on primary Phase voltages appear on the coils on the secondary Less insulation needed on HV winding
Ia Iab
Vab
+

-Y Transformer Analysis
Ia
Van
+

By Faradays Law:
Vab will be in-phase with Van Phase shift introduced

Ia Iab
Vab
+

Ia
Van
+

Ib Ibc
Vbc
+

By KCL:
Ia = Iab Ica

Ib
Vbn
+

By Amperes Law:
Iab will be in-phase with Ia Phase shift introduced

Ib

Ibc
Vbc
+

Ib
Vbn
+

Ic Ica
Vca
+

Ic
Vcn
+

Similar results for b, c phases

Ic

Ica
Vca
+

Ic
Vcn
+

Dr. Louie

Dr. Louie

-Y Transformer Analysis
Phasor Diagram for Ideal Delta-Y Connected Transformer

Delta-Y Transformer Analysis


Phasor Diagram for Ideal Delta-Y Connected Transformer

Vcn Vcn Vcn Vca Vbc Vab


30o

Van

Ia = Iab Ica

Ib = Ibc Iab Ic = Ica Ibc


Ia Ia Ica Ibc Ib Ic

Van Vbn

30o

Van Ic
30o phase shift from primary to secondary

Iab
30o 30o

Iab
30o

Ica

Ib Ibc
30o phase shift from primary to secondary

Vbn

Magnitudes shown assuming N1 < N2

Vbn

Dr. Louie

Dr. Louie

10/25/2012

Three-Phase Transformer Analysis: Delta-Y Let k be the transformer voltage gain For -Y transformers:
Va'n' nVab nVan 3e
j 6 j 6

Delta-Y Transformer Analysis


Voltage relationships
Va'n' Vb 'n' Vc 'n' kVan , Va'b ' kVbn , Vb 'c ' kVcn , Vc 'a' kVab kVbc kVca
c b c n b a a

kVan
Important result!

therefore k = n 3e Ia' Iab n Ia k Iae


j 6

Current relationships
Ia' Ib ' Ic '
7

3n

same phase shift as voltage

Ia k Ib k Ic k

primary

secondary

Dr. Louie

Dr. Louie

Question
Consider an ideal Delta-Y transformer, with 20 turns on each primary coil, and 80 turns on each secondary coil. If the primary side values are:
Vab Ia 208 0 V 10 5 A

Question
Consider an ideal Delta-Y transformer, with 20 turns on each primary coil, and 80 turns on each secondary coil. If the primary side values are:
Vab Ia 208 0 V 10 5 A
j j

Compute: Vab, Van and Ia

Compute: Vab, Van and Ia


k = n 3e 6 Va'b ' Va'n' Ia' k Vabk Vank Ia 4 3e 6 (120 6.92 30 30 )(6.92 30 ) 1.45 35 A 830.4 0 V 1436 30 V

10 5 6.92 30

Dr. Louie

Dr. Louie

10

Y- Transformer
No neutral point on secondary Van, Vab in phase Ian, Iba in phase
Similar results for b, c phase
Ia
Van
+

Three-Phase Transformer Analysis: YIba


Vab
+

Ia

Let k be the transformer voltage gain For Y- transformers: j


Va'b ' nVan nVab e 3 ne
j 6 6

Ib
Vbn
+

Icb
+ V -bc

Ib

kVab

Phase voltage across primary coils Line voltage across secondary coils

therefore k =

Important result

Ic
Vcn
+

Iac
V -ca
+

Ic

Note: phase shift is -300, whereas for Delta-Y transformer connection in previous slides it is +30o

n
11 12

Dr. Louie

Dr. Louie

10/25/2012

Question
Is there any concern in connecting a three phase Y-Delta transformer in parallel with a three phase Delta-Y transformer? Assume the transformers are appropriately rated.

Y-Delta Transformer
To achieve at +30o phase shift connect as shown Note the phasing on the secondary Van, Vac in phase Ian, Ica in phase
Ia
Van
+

Ica
Vac
+

Ia

Ib
Vbn
+

Ibc
V -cb
+

Ic

Ic
Vcn
+

Iab
V -ba
+

Ib

n
13 14

Dr. Louie

Dr. Louie

Y-Delta Transformer
A side note: Vbn
1 3 Vab e
j 6

Three-Phase Transformer Analysis: Y Voltage relationship


Va'b ' nVbn n Vabe 6 3 n 6 e 3
j 6 j j

kVab

+ Vab
n

Vcn

-Vbn
30o 30o

therefore k

Vab
Va'n'

j 6

Van

Va'b ' e 3

nVan e 3

kVan

Vbn +

For the other phases


Va 'n ' kVan kVbn kVcn
Dr. Louie

primary

secondary

Vbn

Vb 'n ' Vc 'n '


15

Phase shift is now +30o

Dr. Louie

16

Three-Phase Transformer Analysis


It can be shown:
Ia ' Ib ' Ic ' Ia k Ib k Ic k
a a

Three-Phase Transformer Analysis


What about power?
S
' Va 'n ' Ia

kVan

Ia k

VanIa

for all configurations

same phase-shift as voltages


c

n b

For ideal three-phase xfmrs, power is conserved, as in the single phase case

primary

secondary

Dr. Louie

17

Dr. Louie

18

10/25/2012

Three-Phase Transformer Analysis


What about impedances? For all transformer connections:
secondary impedance referred to the primary

Transformer Phase Shifts


Various winding connections of -Y, and Y- xfmrs lead to different phase shifts Standard is to have phase-neutral voltages advance by 30 degrees when going from low voltage to high voltage Previous slides have followed this convention Note: convention is most critical in interconnected power systems. Some homework problems do not follow this convention

1 k
2

ZL

Dr. Louie

19

Dr. Louie

20

Transformer Phase Shifts


a a

Transformer Phase Shifts


a a

Which Y- is correct? Check Van for each


c

n b

Which Y- is correct? Check Van for each case:


top
Va'n ' n Van 3
c

n b

low
a

high

30

bottom
Va 'n ' n Van 3 30

low
a

high

n b c b c

n b c b c

low
Dr. Louie

high
21
Dr. Louie

low

high
22

Transformer Phase Shifts


a a a

Transformer Phase Shifts


a a a

n c b

b c

n b

b c

n b b c

low
Van

high
Vac Van Vba

low
Van

high
Vac Van Vba

high
Van Vca

low
Vab Van

Vcb Vcn Vbn

Vcn

Vbn

Vcb

Vcn

Vbn

Vbc

Dr. Louie

23

Dr. Louie

24

10/25/2012

Example
Draw the connections, polarity markers and label the primary and secondary phases for a Delta-Wye step down transformer (assume left side is the high side)

Example
Need secondary (right) side to be regressed in phase by 30 degrees (per convention)
Vca Vcn
Vcn

Vab

30o

Van
Vbn

30o

Van

Vbn Vbc

Which line-line voltages are in phase with Van or -Van ?

Dr. Louie

25

Dr. Louie

26

Example
-Vca must be connected to Van winding -Vab must be connected to Vbn winding -Vbc must be connected to Vcn winding
Ia
Vab
+

Per-Phase Analysis ( -Y)


Ib
Vbn
+ -

Per-phase equivalent of a non-ideal -Y transformer Complex ideal transformer with gain k or k*


k 3ne
j 6

Ib
Vbc
+

+30o

Ic
Vcn
+ -

shift when primary is lower voltage and secondary is higher voltage


Zha/3 + Ia N1 N2 Z La I a + Van -

Ic
Vca
+

Ia
Van
+ -

Van -

Rc/3

jXm/3 +

e1
-

complex ideal + e2 xfmr


-

Dr. Louie

27

Dr. Louie

28

Per-Phase Analysis (Y- )


Per-phase equivalent of a Y- transformer Complex ideal transformer with gain k or k*
k ne
j 6

Example
Consider three, single-phase transformers. The transformers have the following specifications:
720VA, 360/120V, RH = 18.9 , XH = 21.6 , RL = 2.1 , XL = 2.4 , RcH = 8.64k , XmH = 6.84k

+30o shift when primary is lower voltage and secondary is higher voltage
Zha + Van Rc jXm
+

Ia

N1

N2 Z /3 la I

Draw the per-phase equivalent circuit if the transformers are connected as Delta-Y What are the nominal line voltages on each side of the transformer?

e1
-

complex ideal + e2 xfmr


-

+ Van -

Dr. Louie

29

Dr. Louie

30

10/25/2012

Example
Nominal per-phase voltage on primary is 360V and 208V on secondary
Nominal primary line voltage: 360V Nominal secondary line voltage: 208V
6.3 + j7.2

Example
Consider three, single-phase transformers. The transformers have the following specifications:
720VA, 360/120V, RH = 18.9 , XH = 21.6 , RL = 2.1 , XL = 2.4 , RcH = 8.64k , XmH = 6.84k
I a

Ia complex ideal xfmr


1.732

2.1+ j2.4

+ Van 2.88k

j2.28k

e1
-

e2
-

+ Van -

Draw the per-phase equivalent circuit if the transformers are connected as Y-Delta What are the nominal line voltages on each side of the transformer?

30

Dr. Louie

31

Dr. Louie

32

Example
Nominal per-phase voltage on primary is 360V and 69V on secondary
Nominal primary line voltage: 624V Nominal secondary line voltage: 120V
18.9 + j21.6

Practical Considerations
Medium-voltage industrial facilities often use -Y incoming transformers Y-side is grounded through a resistor
Reduces ground current during fault Reduces voltage dip during fault
I a
a a

Ia complex ideal xfmr e1


+ -

0.7+ j0.8

+ Van 8.64k

j6.84k

e2
-

+ Van c b c

n b

5.196

30

primary
Dr. Louie

secondary
Dr. Louie

33

34

Practical Considerations

Practical Considerations

Source: Mozina, C.J.; , "Protection and Commissioning of Digital Transformer Relays: Improvements in Medium-Voltage Industrial Transformer Protection," Industry Applications Magazine, IEEE , vol.18, no.6, pp.63-73, Nov.-Dec. 2012

Source: Wang, M.; Vandermaar, A.J.; Srivastava, K.D.; , "Review of condition assessment of power transformers in service," Electrical Insulation Magazine, IEEE , vol.18, no.6, pp.12-25, Nov.-Dec. 2002

Dr. Louie

35

Dr. Louie

36

10/25/2012

Practical Considerations
Condition assessment of transformers:
Wang, M.; Vandermaar, A.J.; Srivastava, K.D.; , "Review of condition assessment of power transformers in service," Electrical Insulation Magazine, IEEE , vol.18, no.6, pp.12-25, Nov.-Dec. 2002 [available online in IEEE Xplore through SU library]

Summary
There is a complex gain associated with Y-Delta and Delta-Y transformers Connection of transformer coils allows for different phase shifts to be achieved Convention: phase-neutral voltages advance by 30 degrees from lower voltage to higher voltage side Power in ideal three phase transformers is conserved Impedances are transferred from secondary to 1 ZL primary by: 2
k

Dr. Louie

37

Dr. Louie

38

Você também pode gostar