SECTION-5 POWER PLANT CONFIGURATION AND SPECIFICATIONS OF MAIN PLANT EQUIPMENT

16 | P a g e

The capacity of the Proposed Solar Power Plant has been fixed at 1 MWp.x 5Nos. The principle factors considered for designing and selection of proposed plant are local solar radiations, ambient conditions and electrical load characteristics of major system namely the array and power conditioning unit. Moreover, the proposed plant is situated at remote village location, so maximum use of local materials available on site for construction and to retain or preserve the original appearance of the sire and the environment are considered SR.NO. ITEM PV arrays 1.0 Modules in a string 2.0 3.0 4.0 5.0 String in a array Inverters Transformer

50 Nos 18 Nos 28Nos 50 X 100 KVA 5Nos

SPECIFICATION OF MAIN PLANT (A) SOLAR PV MODULE

SR.NO. 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0

ITEM Output Power-Pmax (Watt) Voltage at maximum power-Vmp (Volts) Current at maximum power-Imp (Amps) Open circuit voltage Voc (Volts) Short circuit current-Ise (Amps) Type of solar PV cell Dimensions weight 200 Wp 28.60 V 7.02 36 7.55 Poly Crystalline 1619MM x 1002MM 23.50Kg

17 | P a g e

(B) SR. NO. 1.0

SOLAR INVERTER ITEM Nominal Voltage 230/400 volts three phase, 4 Wire, grid tracking Nominal

voltage can be adjusted by 10% via system stepoints.

2.0

Output Frequency

50Hz 0.5% inverter to follow grid frequency up to 3Hz of the nominal output frequency during normal operation

3.0

Continuous rating

100 kw at unity power factor

4.0

Max DC link Voltage Range

800 volts DC

5.0

MPPT Range

397 to 585 Volts DC

6.0

Control Type

Voltage source, microprocessor assisted output regulation

7.0

Waveform

PWM for low THD, sine wave output

8.0

THD

Less than 3 %

9.0

Efficiency

Up to 94%

10.0

Internal protection system (using electronic detection)

Internal

continuous

overload

protection inverter peak current (short circuit) protection Heatsink over temperature grid protection voltage AC

over/under

18 | P a g e

voltage protection over/under grid frequency protection Anti islanding protection

11.0

Alarm Signals

Via system fault relay (voltage free contact)

12.0

Front panel display (LCD)

LCD

panel

with

membrane

keypad displaying the following inverter per phase voltage,

current, kW, kVA and frequency Grid voltage and frequency

inverter (grid ) on line status PV panel voltage Solar charge current and ambient temperature

individual power stage heat sink and cabinet temperature solar radiation (optional ) Inverter Import & export kWh summation solar kWh summation system stepoints and event logs

13.0

Front Panel Controls (via keypad)

Auto connect

mode

selectionTest off

Grid Mode Mode

Inverter System

selection

selection Fault Reset

14.0

Front Panel Indicators

Inverter On line control power supply OK system Fault

15.0

Circuit Breakers

ACB / MCCB

16.0

RFI

Design conducted emissions

to and

minimize radiated

both RFI

19 | P a g e

17.0

Earthing Provisions

AC bypassing to earth on inverter and DC inputs

18.0

Operating Temperature Range

5-50 degrees Celsius

19.0

Humidity

0-90% non condensing

20.0

Enclosure

Rate for IP30

21.0

Computer port

Isolated RS232 port. Provision for Mod bus protocol. WiFi, LAN protocol

22.0

Computer Access

The system includes a local access port as well as a

telecommunication dialup facility incorporating either a standard PTSN modem or GSM modem for remote access. SCADA package will be windows based OPSComs.

23.0

System feature

Adjustable logging repetition from 1 sec to 900 seconds Storage capacity of up to 3 year with 10 min logs Time and date stamped log entries Time and Date

annotated fault log, holding the fault description and operating statistics View and change system stapoint configurations remotely Bulk log download for data

importation into a spreadsheet where applicable.

20 | P a g e

24.0

Logging Attributes

A summary of the data logging abilities supply with the control

system for instantaneous viewing and periodic logging are listed below:

System

summations

inverter

import and export kWh Solar (C) 415V PCC x 125 Nos Parameters Inverter volts, amps, kW, kVA, frequency Grid volts and frequency SR. NO. 1.0 1.1 1.1.1 1.1.2 1.1.3 ITEM TECHNICAL PARAMETERS System particulars Rated voltage and phases Frequency System earthing Solar panel temp.

Ambient temperature PV panel voltage Solar charge current Heat sink & cabinet temperatures solar 415 V, 3 Phase, 4 wire radiation (with external 50 Hz pyranometer optional). Effectively earthed

21 | P a g e

1.1.4 1.1.5

Maximum system voltage One minute power frequency withstand voltage (a) Power circuit (b) Control circuit

457 V

2.5 kV 1.5 kV

1.1.6

Continuous current rating of busbars (a) PCC 2000A

1.1.7

Short circuit withstand (a) PCC 50 kA/1 sec. 500C max. 900C

1.1.8 1.1.9 2.0 2.1 2.1.1 2.1.2 2.1.3 2.2 2.3

Reference ambient Max temp of busbars at rated current CONSTRUCTIONAL REQUIREMENTS Sheet steel thickness Frames Doors Covers Degree of protection Colour finish shade as per IS: 5

2.5 mm cold rolled 2.5 mm cold rolled 2.0 mm cold rolled IP 52 Seven tank process painting with epoxy based

2.3.1 2.3.2

Interior Exterior

Glossy white Shade 631

2.4

Busbar material

All alloy of E 91 E grade. For main bus bars - copper for Auxiliary bus bars fully insulated

2.4.1 2.5

Bus bra installation Earthin bus.

Fully insulated

22 | P a g e

2.5.1 2.5.2

Material Size (a) for PCC

GS

By bidder 5-50 degrees Celsuis 25.4 mm 19.4 mm All panels Rate for IP30 Draw out type Fixed / plug in type Through cables Minimum 250 mm Bottom

2.6 2.6.1 2.6.2 2.7 2.8 2.8.1 2.8.2 2.9 2.10 2.11 3.0 3.1

Clearances in air of live parts Phase to Phase Phase to earth Single front design Draw out / Fixed type design PCC-ACB MCCB Incoming supply to PCCs Vertical cable alley Cable entry INCOMER CIRCUIT BREAKER FOR PCC Circuit breaker type

Fully draw out type Air circuit breaker

3.2 3.3 3.4 3.5 3.6

No. of Phases Rated breaking capacity Short circuit withstand current Rated current Type of operating mechanism

4 pole 50 kA 50 kA for 1 Second Refer enclosed SLD Motorized spring charged Motor voltage, 220 V Ac, 1Ph.

3.7 3.8

Shunt trip require Yes/No Relays / releases / control

Yes Overload / Earth fault / short circuit / static with settable settings (Microprocessor based)

3.9

Remote communication

Through serial link, Port Rs. 485 with formation of bus wires and communication modem

3.10

Breaker Test-Service selector switch

Required

3.11 3.12 4.0 4.1

Local- Remote selector switch Minimum no. of auxiliary contacts OUTGOING CIRCUIT BREAKER FOR PCC Circuit breaker type

Required 4 No, 4 NC spare for purchasers use

MCCB

23 | P a g e

4.2 4.3 4.4 4.5 4.6

No. of phases Rated breaking capacity Type of operating mechanism Shunt trip required Relays / series releases

TP with N 50 kA for 1 sec. Manual Yes Overload / short circuit

(D) SR. NO. 1.0 1.1 1.2 1.3 1.4 1.5 1.6 2.0 2.1 2.2 2.3 2.4

TRANSFORMER ITEM

GENERAL Application Quantity Installation (Indoor / Outdoor ) Type (Auto / 2 Winding / 3 Winding) Rating Cooling TEMRATURE RISE Ambient temp. maximum Temp. Rise of oil by thermometer Temp. Rise of winding by resistance method Impedance at rated current frequency at 75 C 45 C 50 C 55 C 6.25% Power Transformer 1 No. Outdoor 2 Winding 1.6 MVA ONAN

24 | P a g e

3.0 3.1 3.2 3.3 4.0 4.1

TAPPING: Off Load Tap Changer Tapping on winding (HV) Total tapping range Step RATING No load voltages (a) HV Winding (b) LV Winding 11 kV 433 V 433 V +5 to -5% +10 2.5% ( 5 taps)

4.2 5.0 5.1

Frequency TERMINAL CONNECTION HV Winding Line end

50 Hz

XLPE cable (with heat shrink terminations)

5.2 5.3

HV Winding neutral end LV Winding Line / N end

---------XLPE cable (with heat shrink terminations)

5.4

LV Winding neutral bushing

5.5 6.0 6.1

Earthing conductor for Transformer body SYSTEM DATA System voltages

Separate Neutral bushing for earth connection (suitable for 1.1kV grade) (a) Material -- G.I. strip (b) Size -- 60 x 12 mm (a) HV Nominal / Highest 11/12 kV (b) LV Nominal / Highest 0.433/0.457 kV (a) HV (6.6kV) system 40 kA (b) LV (415V) system 50 kA (a) HV (11kV) Earth through Resistor (b) LV (415V) Solidly Earth System

6.2

Fault levels

6.3

System Neutral Earthing

7.0 7.1 7.2 7.3

WINDING Material of Winding Winding connection & vector group Transformer neutral Type of Earthing (a) HV Not applicable (b) LV Solidly Earthed (a) Plain / Flanged : Flanged (b) Unidirectional / Bidirectional : Bidirectional Copper HV (11kV) Delta LV (433V) Star Dyn 11

8.0 8.1

MISCELLANEOUS Wheels

25 | P a g e

8.2 8.3 9.0

Winding temp. indicator required Any special final paint required (Epoxy etc.) Additional connection features for terminal

Yes Epoxy painting

9.1

HV cable box:

With disconnecting chamber, phase segregated type, provided with space heater thermostat Required for earth connection to earth pit 2000/1 A, class PS for 64R, 2000/1 A, CL 5P10, 15 VA for 51NS shall be provided

9.2 9.3 9.4

LT cable box Separate LV Neutral bushing: Neutral CT after bifurcation

NOTES: (1) Transformers shall be provided with necessary accessories

(E) SR. NO. 1.0 2.0 3.0 4.0 5.0 6.0 7.0

HT CABLES ITEM Voltage Grade Conductor Conductor Screen Insulation Inner sheath Outer sheath Armoring 11 kV (UE) grade cables, heavy duty Stranded Aluminium Semi conducting compound XLPE Extruded PVC (Type ST-2) Extruded PVC (Type ST-2) Galvanized steel strips for multi-core cables and non-magnetic Aluminium wires for single core cables 90 C current 40kA for 1 sec. 250 C

8.0 9.0

Cable Operating Temperature Short capacity circuit withstand

10.0

Short circuit withstand temperature

(F) SR. NO. 1.0 1.1

LT CABLES ITEM POWER CABLE Voltage Grade V/V 1100V for 415V system UNIT

26 | P a g e

1.2 1.3 1.4 1.4.1 1.4.2

Frequency Earthing system Conductor Material Max withstand Temp (a) Normal condition (b) Short circuit condition

Hz C C -

50 Solidly earthed system for 415V system

Annealed Cu

90 250 Stranded H4

1.4.3 1.4.4 1.5 1.5.1 1.5.2 1.6 1.6.1 1.6.2 1.7 1.7.1 1.7.2

Conductor type Grade Insulation Material Reference standard Inner Sheath Material Type Outer Sheath Material Type

XLPE IS 7098, Part I and Part II

FRLS PVC ST2

FRLS PVC ST2

(G)

EARTHING & LIGHITNG PROTECTION CODES & STANDARDS The earthing of all outdoor equipment and provision of associated earthing systems, electrodes and connections shall be in accordance with the recommendations in the latest IEEE 80/IS 3043. DESIGN CRITERIA GROUNDING SYSTEM The grounding design calculation shall conform to ANSI / IEEE Standard 802000. Earth electrodes shall be provided throughout the plant areas along with the main earth grid. The number of earth electrodes shall be according to achieve the total earth grid resistance less than one (1) ohm. Earth electrodes shall be provided in earth pits. The earth pits shall be of two types namely treated with

27 | P a g e

test links and untreated. Earth electrodes shall be of heavy duty GI pipes, 40 mm dia and 3 meter long. The main buried grid conductors shall be connected to all the earth electrodes to form a total earth grid.

28 | P a g e

GROUNDING MATERIAL Galvanised steel flats of required size shall be used as per approved design. In any case the minimum size shall be 75 x 10 mm. GS strip for earthing conductor. Treated earth pits shall conform to relevant INDIAN Standards. The earth grid shall be installed specified / approved depth of minimum 600mm. EQUIPMENT EARTHING The frames of all electrical equipment and structural steel work shall be earthed by connection to earth grid by branches of same cross sectional area of the earth grid. LIGHTINING PROTECTION SYSTEM Power plant needs protection against Lighting. The system will be designed as per IS: 2309 and Indian Electricity Rules. Vertical air termination of 40mm diameter, 3 M long shall be provided above highest point of array to provide radius of protection full array. (H) SR. NO. 1.0 2.0 3.0 4.0 STRUCTURAL MOUNTING EQUIPMENT ITEM

Type Material Overall dimension Coating

Ground Mounting MS Galvanized As per design Hot dip (Galvanized) Minimum of 130 Micron size 150 km / hr 30 PCC SS 304 Fastners

5.0 6.0 7.0 8.0

Wind rating Tilt angle Foundation Fixing type