Escolar Documentos
Profissional Documentos
Cultura Documentos
50
SELECTION GUIDE FOR TRANSFORMER-PRIMARY FUSES IN MEDIUM-VOLTAGE INDUSTRIAL, COMMERCIAL, AND INSTITUTIONAL POWER SYSTEMS
S&C Power Fuses - Types SM, SML, and SMD-PO Indoor and Outdoor Distribution (4.16 kv through 34.5 kv)
Supersedes Data Bulletln 240-1 10 dated 4-12-82
0 1984
DATA BULLETIN
S&C ELECTRIC COMPANY. C h i c a g o S&C ELECTRIC CANADA LTD . R e x d a l e
2404 10
Page 1 of 78 August 6,1984
Types SM, SML, and SMD-20 Indoor and Outdoor Distribution (4.16 kv through 34.5 kv)
I TABLE OF CONTENTS
Section
GENERAL . . . . . . . . . . . . APPLICATION PRINCIPLES Select the Primary Fuse Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Accommodate Expected Loading Levels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Withstand Inrush Currents . . . . . . . . . . . . . . . . . . . . . . . . . Protect Transformer Against Damaging Overcurrents.. . . Coordinate with Other Protective Devices . . . . . . . . . . . . . 16
Page Number
....................
5
6
Protect Downstream Conductors Against Damaging Overcurrents . . . . . . . . 27 THE FUSE SELECTION TABLES Introduction to Fuse Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basis for Listings in the Fuse Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . Examples.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fuse Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . How to Use the Fuse Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . 29
31
37
I GENERAL
This d a t a bulletin is a guide for the selection, application, a n d coordination of S&C Power Fuses-Types SM, SML, a n d SMD-20 when applied on the primary side of medium-voltage transformers in industrial, commercial, a n d institutional power systems. The information a n d recommendations presented i n this publication apply regardless of whether the fuses are connected directly to the transformer primary or are remotely connected through insulated cable or enclosed bus duct. For the purpose of this guide, medium-voltage transformers are those having primary voltage ratings between 4.16 kv a n d 34.5 kv, with either low-voltage (208 v, 240 v, 480 v, or 600 v) or medium-voltage (2.4 kv or 4.16 kv) secondaries. The function of a transformer primary-sideprotective device is, in general, to provide system protection a s
1
well a s transformer protection. With respect to system protection, a primary-side protective device should detect a potentially damaging overcurrent condition a n d operate promptly to isolate only the faulted segment, thereby minimizing the short-circuit stresses on the remainder of the system a n d limiting the extent of the service interruption to only the affected segment. For transformer protection, a primary-side protective device should operate promptly in response to a bus or cable fault located between the transformer a n d the nearest secondary-side overcurrent protective device. I t should further provide backup protection for the transformer in the event the secondary-side overcurrent protective device either fails to operate due to a malfunction, or operates too slowly due to incorrect (higher) ratings or settings. To best achieve these objectives, group protection of transformers is not generally recom-
I
I
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems
GENERAL
protection. Indeed, many users find t h a t the complexity of such protective relaying, with its requirement for periodic t e s t i n g a n d r e c a l i b r a t i o n , i s a d i s t i n c t disadvantage. Circuit breakers are also used in applications requiring a very high-above 720 amperes-continuous current-carrying capability. While this may be a n advantage in some cases, a higher degree of service continuity can be achieved with less expensive power fuses by subdividing the system into a larger number of discrete segments, with the result that a fault on one segment of t h e system affects fewer loads. This highdegree of segmentation also allows the use of smaller transformers located strategically throughout the system, eliminating the need for the unnecessarily long, high-ampacity secondary conductors t h a t are required where fewer, larger, widely separated transformers are used. Where high continuous current-carrying capability is not required and where reclosing or sophisticated relayi n g is not justified-as is the case in the majority of transformer protection applications in medium-voltage i n d u s t r i a l , commercial, a n d i n s t i t u t i o n a l power systems-power fuses offer a number of advantages. Power fuses are simple to install a n d require no maintenance of a n y kind-even after years of inattention, power fuses will operate properly. Recalibration is neither required nor possible. Hence, elaborate testing procedures a r e not needed, eliminating the possibility t h a t a carefully engineered coordination plan will accidentally be disturbed. Power fuses, unlike circuit breakers, provide fault protection for the system without dependence on a source of control power, such as storage batteries a n d their chargers. Such batteries may be found completely discharged and t h u s incapable of tripping the circuit breaker should a fault occur. I n addition, for high-magnitude faults, power fuses have inherently faster response characteristics t h a n circuit breakers, permitting more rapid removal of faults from the system with these advantages:
1. The duration of the voltage dip associated with the fault is reduced significantly, minimizing the potential for disruption of the remaining loads;
mended-each transformer should be individually protected. The ampere rating of a primary-side protective device selected to accommodate the total loading requirements of two or more transformers would typically be so large t h a t only a small degree of secondaryfault protection-and almost no backup protectionwould be provided for each individual transformer. Moreover, for group-protection situations involving transformers of unequal sizes, t h e ampere rating of the primary-side protective device might even be greater t h a n the already large maximum ampere rating permitted by the National Electrical Code for the smallest transformer. In addition, with group protection of transformers, the degree of service continuity is significantly reduced, since a fault associated with a n y one transformer protected by a given device will result in the loss of service to all transformers protected by t h e device. A variety of primary-side protective devices such as circuit breakers, solid-material power fuses, and currentlimiting fuses are available to accomplish the above tasks.
In industrial, commercial, a n d institutional power systems, circuit breakers have been used for applications requiring complex relaying schemes or high continuous currents. However, for most applications a choice of either circuit breakers or power fuses is available. Fuses have achieved widespread use in most such applications because of their simplicity, economy, fast response characteristics, a n d freedom from maintenance.
Circuit breakers a n d their associated relays are commonly used where the reclosing capability of the circuit breaker is a n advantage, such as applications involving overhead lines which have a relatively high incidence of transient or temporary faults. This reclosing feature is neither useful nor desirable i n industrial, commercial, a n d institutional power systems where the conductors a r e arranged i n cable trays or enclosed in conduit or bus duct. The incidence of faults on these systems is low, a n d the rare faults t h a t do occur are not transient and result i n significant damage t h a t would only be exacerbated by a n automatic reclosing operation. The relaying associated with circuit breakers is available i n varying degrees of sophistication and complexity. Systems requiring differential protection, reversepower relaying, or non-current-magnitude tripping of the protective device typically require circuit breakers. However, the sizes of transformers normally associated with industrial, commercial, a n d institutional power systems generally do not warrant such sophisticated
DATA BULLETIN
S&C ELECTRIC COMPANY- Chicago S & C ELECTRIC CANADA LTO Rexdale
2404 10
Page 3 of 78 August 6,1984
Types SM, SML, and SMD-PO Indoor and Outdoor Distribution (4.16 kv through 34.5 kv)
1 GENERAL
4. The upstream protective device can be set to operate
faster-for better protection-while still coordinati n g with the transformer-primary fuse. Thermal damage to three-phase motors due to singlephasing-once thought to be a problem associated with the use of power fuses on the primary side of a transformer-is of no concern, since the National Electrical Code requires t h a t motors be equipped with a n overcurrent protective device in each of the threesupply phases. In addition, devices are now widely available which detect open-phase conditions caused by blown fuses a n d such other events as utility-line burndown, broken conductors, single-phase switching, or equipment malfunctions, a n d which initiate a switching operation to isolate the load or transfer to a n alternate source. Furthermore, power fuses provide selective isolation of only faulted phases of three-phase feeders serving singlephase loads, unlike the undiscriminating operation of circuit breakers which remove all three phases from the system-even on single-phase faults. As mentioned above, there a r e two types of power fuses: solid-material fuses a n d current-limiting fuses, with significantly different performance characteristics which materially affect their suitability for transformer protection. S&C Types SM, SML, a n d SMD Power Fuses are of the solid-material type, a n d have fusible elements t h a t a r e nondamageable and nonaging. T h e time-current characteristics of S&C Power Fuses are permanently accurate-neither age a n d vibration, nor surges t h a t heat t h e element nearly to the severing point will affect the characteristics of these fuses. There is no need for a n y safety zones or setback allowances. As a consequence of these performance characteristics, SM, SML, a n d S M D Power Fuses allow fusing closer to the transformer full-load current, providing the maximum degree of protection against secondary-side faults. I n addition, the ability to
fuse closer to the transformer full-load current facilitates coordination with upstream protective devices by allowing the use of lower ampere ratings or settings for these devices, resulting i n faster response. Current-limiting fuses on t h e other hand, because of their construction, are inherently susceptible to element damage caused by inrush currents t h a t approach the fuses minimum melting time-current characteristic curve. Because of this potential for damage, a n d because of the effects of loading a n d manufacturing tolerances on the time-current characteristic curve, a safety zone or setback allowance is typically required. This safety zone or setback allowance, combined with the shape of the time-current characteristic curve, results in the selection of a current-limiting fuse ampere rating substantially greater t h a n the transformer full-load current. However, the use of such a high ampere rating is undesirable, since the degree of transformer protection will be reduced, a n d coordination with the upstream protective device may be jeopardized. Also, since highampere-rated current-limiting fuses typically require t h e use of two or three lower-ampere-rated fuses connected i n parallel, increased cost and space requirements may be encountered. Selection of the various types of transformer primaryside protective devices a n d their ratings and settings h a s been a matter of considerable complexity. This publication provides complete, simplified procedures for selecting the optimal transformer-primary fuse, taking into consideration all of the following factors associated with the application:
1. System voltage;
3. Anticipated normal transformer loading schedule, including daily or repetitive peak loads, and emergency peak loads;
A -
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems
4. Transformer inrush current, including the combined effects of transformer magnetizing-inrush current a n d the energizing-inrush currents associated with connected loads-particularly following a momentary loss of source voltage; 5 . The degree of protection provided to the transformer against damaging overcurrents;
6. Coordination with secondary-side as well as other primary-side overcurrent protective devices; and
the selection of the optimal transformer-primary fuse for your particular applications. The fuse selection tables list fuse ampere ratings a n d speed characteristics which have been precoordinated with the full spectrum of low-voltage and mediumvoltage overcurrent protective devices, such as circuit breakers, fuses, a n d Class E-2 high-voltage industrial control equipment, thereby eliminating the need to perf o r m graphical coordination studies. The tables feature a specially designed Transformer Protection Index which indicates the degree of transformer protection provided by the primary fuse, as well as listings of the loading capabilities of the fuses when used with each of t h e transformers shown. You need only refer to these tables to obtain the information required to make your selection.
7. Protection of the downstream primary-side conductors against damaging overcurrents. These factors are discussed i n detail i n the next section, entitled Application Principles. This discussion is followed by tables designed specifically to simplify
APPLICATION PRINCIPLES 1
...
A transformer-primary fuse must be selected for the voltage rating, the available fault current, a n d the continuous current-carrying requirement of the circuit on which it is to be applied. Since there are a multitude of voltage, short-circuit interrupting, a n d maximum ampere ratings available, you should choose the most economical primary fuse t h a t will meet both your present a n d your future requirements. In addition, from the wide variety of ampere ratings and speeds available, you should select the primary fuse providing the optimum protection for the transformer against secondaryside faults. V o l t a g e rating. The maximum design voltage rating of t h e transformer-primary fuse should equal or exceed the maximum phase-to-phase operating voltage level of the system. S&C Types SM, SML, a n d S M D Power Fuses a r e not voltage critical, since they do not produce overvoltages, and therefore, they may be applied a t a n y system operating voltage equal to or less t h a n the maximum design voltage rating of the fuse. Currentlimiting fuses, in contrast, inherently develop a n overvoltage during fault-current interruption. This overvoltage typically restricts the application of current-limiting fuses to t h e same system-voltage class as the maximum voltage rating of the current-limiting fuse, in order to avoid exposing system components such as surge arresters a n d dry-type transformers to damage from excessive voltages. S h o r t - c i r c u i t i n t e r r u p t i n g rating. The symmetrical short-circuit interrupting rating of the transformerprimary fuse should equal or exceed the maximum
available fault current at the fuse location. When determining the interrupting rating of the primary fuse, you should consider the X/R ratio of the system a t the fuse location, since power fuses may have higher-thannominal symmetrical interrupting ratings for those applications where the X/R ratio is less t h a n the value of 15 specified by ANSI Standards.* You may as a result be able to use a less expensive primary fuse having a lower nominal symmetrical interrupting rating. Refer to the fuse manufacturers recommendations for these higher symmetrical short-circuit interrupting ratings. The interrupting rating of t h e transformer-primary fuse should be chosen with sufficient margin to accommodate anticipated increases in the interrupting duty due to system growth. Again, since fuses are available with a wide variety of interrupting ratings, you should choose a primary fuse having a n interrupting rating only as large as necessary to meet your present and future requirements. A m p e r e rating and speed characteristic. The ampere rating a n d speed characteristic of the transformerprimary fuse should be selected to (1)accommodate the anticipated normal transformer loading schedule, including daily or repetitive peak loads, a n d emergency peak loads; (2) withstand the magnetizing-inrush current associated with the energizing of a n unloaded transformer, as well as the combined magnetizing- a n d load-inrush currents associated with the re-energization of a loaded transformer following a momentary
ANSI Standard C37.46, Specifications for Power Fuses and Fuse Disconnecting Switches.
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S & C ELECTRIC CANAOA LTD . Rexdale
240.1 10
Page 5 of 78 August 6,1984
Types SM, SML, and SMD-20 Indoor and Outdoor Distribution (4.16 kv through 34.5 kv)
loss of source voltage; (3) protect the transformer against damaging overcurrents; a n d (4) coordinate with secondary-side as well as other primary-side overcurrent protective devices. These principles, which are examined in greater detail in the following sections, provide the basic foundation of transformer-primary fuse selection. are included i n the fuse selection tables presented in this guide. Conditions may occur during which the transformer will be loaded far i n excess of the normal loading schedule. Such emergency peak loading typically occurs when one of two transformers (in a duplex substation, for example) is compelled, under emergency conditions, to carry the load of both transformers for a short period of time. Where emergency peak loads are contemplated, the transformer-primary fuse ultimately selected should have a n emergency peak-load capability a t least equal to the magnitude a n d duration of the emergency peak load. I t is important to remember that a transformerprimary fuse should be selected to accommodate-not to interrupt-emergency peak loads. This requirement may result i n the selection of a primary fuse ampere rating larger t h a n would be required for a similarly rated single transformer installed alone, a n d therefore
1APPLICATION PRINCIPLES
7-
15.0
14.0
13.0
12.0
Figure 1. Curve lor determining magnitude of combined magnetizing- and load-inrush current.
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems APPLICATION PRINCIPLES
the degree of transformer protection provided by the primary fuse may be reduced.
load-inrush current is referred to as hot-load pickup capability. T h e integrated heating effect on the transformerprimary fuse a s a result of the combined magnetizingand load-inrush current is equivalent to a current having a magnitude of between 12 and 15times the primary full-load current of the transformer for a duration of 0.1 second. The specific multiple of primary full-load current is a function of the transformer load immediately preceding the momentary loss of source voltage, a s illustrated in the curve i n Figure 1. The minimum melting time-current characteristic of the primary fuse (adjusted a s described below) should exceed the magnitude and duration of the combined inrush current. The minimum melting time-current characteristic curves for medium-voltage power fuses are determined i n accordance with ANSI Standards,* which specify testing of fuses at a n ambient temperature of 25C, and with no initial load. I n practice, every fuse is carrying a load, which raises the temperature of the fusible element, and hence reduces the melting time for a given value of current. To ensure t h a t the transformer-primary fuse can withstand hot-load pickup current (and to provide precise coordination between the primary fuse and downstream overcurrent protective devices), it is necessary to adjust the published minimum melting timecurrent characteristic curve of the primary fuse to reflect the reduced melting time for each specific level of fuse loading. Figure 2 illustrates a typical curve used for
..
When a n unloaded distribution or power transformer is energized, there occurs a short-duration inrush of magnetizing current which the transformer-primary fuse must be capable of withstanding without operating (or, in the case of current-limiting fuses, without sustaining damage to the fusible element). T h e integrated heating effect on the primary fuse a s a result of this inrush current is generally considered equivalent to a current having a magnitude of 12 times the primary full-load current of the transformer for a duration of 0.1 second. The minimum melting time-current characteristic of the primary fuse should be such that the fuse will not operate (or again, in the case of current-limiting fuses, sustain damage to the fusible element) as a result of this magnetizing-inrush current. The transformer-primary fuse must also be capable of withstanding the inrush current that occurs when a transformer t h a t is carrying load experiences a momentary loss of source voltage, followed by re-energization (such a s occurs when a source-side circuit breaker operates to clear a temporary upstream fault, and then automatically recloses). In this case, the inrush current i s made up of two components: the magnetizing-inrush current of the transformer, and the inrush current associated with the connected loads. The ability of the primary fuse to withstand combined magnetizing- and
20
40
60
80
100
120
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S & C ELECTRIC CANADA LTD Rsxdale
2404 10
Page 7 of 78 August 6,1984
S C L C Power Fuses
1APPLICATION PRINCIPLES
2. One or more, but not all, of the parallel silver wires or ribbons of the fusible element may melt and separate. Adjusted minimurn melting time-current curve of transformer-primaryfuse ( p u b lished fuse minimum melting time-current curve adjusted to reflect the assumed prefault load)
3. The fusible element may break as a result of fatigue brought about by localized buckling of the fusible element from thermal expansion and contraction.
Certain current-limiting fuses utilize a eutectic or M spot consisting of a drop of tin or tin alloy deposited on the silver element. The tin or tin alloy melts and amal-
Current
Figure 3. The total clearing and the minimum melting time-current curves of a 100E-ampere translormer-primary fuse, with the minimum melting curve adjusted to reflect the reduced melting time resulting from an assumed prefault load current of 87.5 amperes.
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems
APPLICATION PRINCIPLES
gamates (combines)with thesilver element at a temperature lower t h a n the melting temperature of the silver element, thereby initiating fuse operation at lower levels of fault current t h a n for t h e silver element alone. Current-limiting fuses t h a t utilize M spots are even more susceptible to element damage t h a n other types of current-limiting fuses, since the M spot may only partially melt a n d amalgamate when exposed to current surges. Damage to fusible elements of current-limiting fuses, as described above, may shift or alter their time-current characteristics, resulting i n a loss of complete coordination between the fuses a n d other downstream overcurrent protective devices. Moreover, a damaged currentlimiting fuse element m a y melt due to a n otherwise harmless inrush current, but the fuse m a y fail to clear the circuit due to insufficient power flow-with the fuse continuing to arc a n d burn internally due to loadcurrent flow. Because of the potential for damage to the fusible element from inrush currents, a n d because of the effects of loading and manufacturing tolerances, current-limiting fuse manufacturers typically require that, when applying such fuses, the minimum melting time-current characteristic curves be adjusted to allow for these variables. These adjustments are referred to as safety zones or setback allowances, a n d range from 25?6 i n terms of time to 25K in terms of current. The latter can result in a n adjustment of 250% or more in terms of time, depending on the slope of the time-current characteristic curve a t the point where the safety zone or setback allowance is measured. The S&C Types SM, SML, a n d SMD-20 Power Fuses covered i n this publication are available in two speed characteristics: Standard Speed, TCC No. 153;a n d Slow Speed, TCC No. 119. The time-current characteristic
curves for these fuses a r e of the inverse-time form with sufficient time delay so t h a t , i n either speed, a fuse having a n ampere rating even somewhat less t h a n the transformer full-load current will withstand t h e inrush currents described above, for typical industrial transformer loading levels. Current-limiting fuses, i n contrast, have inherently steeper (faster) time-current characteristics. As a consequence, manufacturers of current-limiting fuses ordinarily recommend the use of a n ampere rating substantially higher t h a n the transformer full-load current in order to prevent the fuse from operating or sustaining damage due to inrush currents. However, the use of a higher ampere rating is undesirable for three reasons: (1) protection for the transformer may be greatly reduced; (2) coordination with the upstream protective device may be jeopardized; a n d (3) higher-ampere-rated current-limiting fuses (usually above 100 amperes) typically require t h e use of two or three lower-ampere-rated fuses connected in parallel, resulting in significantly increased cost a n d space requirements.
The most important application principle to be considered when selecting a transformer-primary fuse is t h a t it must protect the transformer against damage from mechanical a n d thermal stresses resulting from a secondary-side fault t h a t is not promptly interrupted. A properly selected primary fuse will operate to clear such a fault before t h e magnitude a n d duration of the overcurrent exceed the short-time loading limits recommended by the transformer manufacturer. I n t h e absence of specific information applicable to a n individual transformer, the primary fuse should be selected i n accordance with recognized guidelines for
DATA BULLETIN
S&C ELECTRIC COMPANY - Chicago S & C ELECTRIC CANADA LTD Rexdale
2404 10
Page 9 of 78 August 6,1984
1000
500
200
100
50
20
10
As mentioned before, the most important consideration when selecting a transformer-primary fuse is the degree of protection it provides the transformer against all types of secondary-side faults. The degree of transformer protection provided by t h e primary fuse should be checked for the level of fault current a n d type of fault (Le., three-phase, phase-to-phase, or phase-to-ground) producing the most demanding conditions possible for each particular application, viz., those for which the ratio of the primary-side line currents to the transformer winding currents is the lowest. For these situations, one or more of t h e primary fuses will be exposed to a proportionately lower level of current t h a n the windings, and, as a consequence, the primary fuses must be carefully selected to operate fast enough to avoid damage to the transformer windings. Figure 5 illustrates the relationship between the per-unit primary-side a n d secondaryside line currents a n d the associated per-unit transformer winding currents for three common transformer connections under a variety of secondary-fault conditions. Table I on page 12 lists the ratio of the per-unit primary-side line currents to the per-unit transformer winding currents for these transformer connections and types of secondary faults.
From Table I, it is clear t h a t a phase-to-phase seconda r y fault on a delta delta connected transformer and a phase-to-ground secondary fault on a delta groundedwye connected transformer produce the most demanding conditions possible for those particular transformer connections, since the per-unit primary-side line currents are less t h a n the per-unit transformer winding currents. Accordingly, to ensure proper transformer protection for these two situations, it is necessary to "shift" the basic transformer short-time characteristic curve to the left (in terms of current) by the ratio of the
0
0 0
N
0.5
02
0.1
0.05
0 0 Lo
0 0
7-
0 0
N Lo
0.87
0
Three- Phase Secondary Fault Phase-to-Phase Secondary Fault Phase-to-Ground Secondary Fault
p g q 1.0
1.o
k q 0.50
Phase-to-Phase Secondary Fault Phase-to-Phase Secondary Fault Phase-to-Ground Secondary Fault
Figure 5. Relationship between the per-unit primary-side and secondary-side line currents and the associated per-unit translormer winding currents for (a) grounded-wye grounded-wye, (b) delta delta, and (c) delta grounded-wye connected transformers l o r various types of secondary faults. (Line current and winding current values are expressed in per unit of their respective values l o r a bolted three-phase secondary fault.)
DATA BULLETIN
S&C ELECTRIC COMPANY Chicago S&C ELECTRIC CANADA LTD Rexdale
2404 10
Page 11 of 78 August 6,1984
1 APPLICATION PRINCIPLES
per-unit primary-side line current to t h e per-unit transformer winding current listed i n Table I. The shifted transformer short-time characteristic curve will then be i n terms of t h e primary-side line current a n d , as such, will be directly comparable with the total clearing timecurrent characteristic curve of the transformer-primary fuse. For the grounded-wye grounded-wye connected transformer, the per-unit primary-side line currents and the per-unit transformer winding currents are the same, hence the basic transformer short-time characteristic curve applies.
TABLE I-Relationship Between Per-Unit Primary-Side Line Current and Per-Unit Transformer Winding Current for Various Types of Secondary Faults
0 Line current and winding current values are expressed in per unit of
their respective values for a bolted three-phase secondary fault.
Figure 6 illustrates the basic transformer short-time characteristic curve (Curve @), applicable to t h e grounded-wye grounded-wye connected transformer, as well as short-time characteristic curves adjusted to reflect the two situations discussed above. Curve @ represents Curve 0 adjusted to reflect the reduced level of current (0.87 per unit) seen by two primary fuses
ANSI Standard ( 3 7 . 4 6 , Specifications for Power Fuses and Fuse Ilisconnecting Switches.
2404 10
Page 12 of 78 August 6,1984
DATA BULLETIN
S&C ELECTRIC COMPANY C h i c a g o S&C ELECTRIC CANAOA LTD R e x d a l e
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems APPLICATION PRINCIPLES
1000
500
200
100
20
-u c
0 0 W
u l
10
v)
._
f
5
ANSI Point* for a grounded-wye grounded-wye connected transformer with 5 75% impedance.
ANSI Point* for a delta delta connected transformer with 5.75% impedance
2
A N S I Point*for a delta grounded-wye connected transformer with 5.75% impedance.
1
0.5
*Thecurrent value forthe ANSI Point isdetermined using the following formula
((&))
0.2
(A)
0.1
For example, for a delta grounded-wye connected transformer with 5 75% impedance. the current value for the ANSI Point IS
0.05
0 r 0
0 0 N
0 0 v)
0
r
0 0
N v)
0 0
Current, i n Percent of Transformer Self-Cooled Full-Load Current Figure 6. Transformer short-time characteristic curves.
DATA BULLETIN
S&C ELECTRIC COMPANY Chicago S & C ELECTRIC CANADA LTD . Rexdale
2404 10
Page 13 of 78 August 6,1984
I APPLICATION PRINCIPLES
at not less t h a n 200 or 220 percent of the ampere rating. Accordingly, the total clearing time-current characteristic curve of the transformer-primary fuse will cross the transformer short-time characteristic curve at some low level of current. Because t h e primary fuse does not provide overload protection for the transformer, this should not be a concern; however, efforts should be made to keep the current value at which the two curves intersect as low as possible, to maximize protection for the transformer against secondary-side faults.
Curve 0in Figure 7, which corresponds to the transformer short-time characteristic curve for a delta grounded-wye connected transformer, illustrates these principles. T h e total clearing curves for primary fuses with a fusing ratio* of 1.0, 1.5,2.0, or 2.5 all pass below the ANSI Point of t h e delta grounded-wye connected transformers short-time characteristic curve. The total clearing curve for a primary fuse with a fusing ratio of 3.0 passes completely above a n d to the right of the transformer short-time characteristic curve, a n d thus, as a consequence, would not provide protection for this transformer for a phase-to-ground secondary fault.$ Since the object of transformer-primary fusing is to provide protection for the transformer for all types of secondary faults, a primary fuse with a total clearing curve t h a t passes above the ANSI Point (such as the primary fuse with a fusing ratio of 3.0 i n Figure 7) would be considered unacceptable. The transformer-primary fuse having the lowest usi n g ratio of the four fuses t h a t pass beneath the ANSI Point would provide the maximum protection for the transformer against secondary faults located between the transformer and the secondary-side overcurrent protective device-as well as maximum backup protection for the transformer in the event the secondary-side
Fusing ratio i s defined as the ratio of the transformer-primary fuse ampere rating to the transformer self-cooled full-load current. Transformers in industrial, commercial, a n d institutional power systems typically have impedances less t h a n 8711. For such transformers, the total clearing time-current curve of the slope illustrated for il primary fuse with a fusing ratio of 3.0 would typically pass helow a n d to t h e left of t h e ANSI Point. A transformer with 8%1 impedance w a s selected for Figure 7 to illustrate the concept of a primary fuse providing inadequate protection.
<J. K. Ihnki-Jacobs, The Effects of Arcing Ground Faults on 1,ow-Voltage System Ilesign, Article reprinted from the May) J u n e 1972 issue of IEEIS Transactions on Industry a n d General Applications.
J . K. Ihnki-Jacobs, State of the Art of Grounding a n d Ground Fault Protection. Article reprinted from the 1977 Conference Kec(rrdoftheIEEI.:24th Annual Petroleum a n d Chemical Industry Conference, September 1%14, 1977, I)allas, Texas, Catalog A. No. 77(:H 1 m - 4 - 1
I,. E. Fisher, Kesistance of Low-Voltage Alternating Current Arcs, I E E E Transactions on Industry and General Applications. Vol. IGA-6, Novernher/l)ecember 1970, pages 607-616.
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems APPLICATION PRINCIPLES 1
1000
500
v
200
100
50
20
10
0.5
operate to protect the transformer in accordance with the transformer short-time characteristic curve. (Fusing ratio is 1 .O.)
operate to protect the transformer in accordance with the transformer short-time characteristic curve. (Fusing ratio is 2.5.) secondary fault current equals (0.4) (0.58). or 290% (0.08)
0.05
I i
8
r
1
Ln 0
N 0
0 0
0 0 N
10
DATA BULLETIN
S&C ELECTRIC COMPANY Chicago S&C ELECTRIC CANADA LTD Rexdale
2404 10
Page 15 of 78 August 6,1984
provide protection for the transformer against a phaseto-ground fault under arcing conditions. A primary fuse with a fusing ratio only slightly higher t h a n 1.0 will, however, adequately protect the transformer against permanent or metallic phase-to-ground secondary faults as well as other types of secondary faults, including arcing phase-to-ground secondary faults t h a t escalate to multiphase secondary faults.
As a second example, consider Curve @ i n Figure 8, which corresponds to t h e transformer short-time characteristic curve for a delta delta connected transformer. T h e total clearing curve of a transformer-primary fuse with a fusing ratio as high as 3.0 will pass below the ANSI Point of the transformer short-time characteristic curve, and will t h u s provide protection for the transformer as discussed before. However, a primary fuse with such a high fusing ratio will not provide protection for the transformer unless the fault current exceeds 735% of the full-load current of the transformer as reflected on the primary side. A primary fuse with a fusing ratio of 1.0 will clearly provide much better protection for the delta delta connected transformer by operating at as low as 230%of the transformer-primary full-load current.
As mentioned before, a n effort should be made to select a transformer-primary fuse which will protect the transformer against all types of secondary-side faultsincluding arcing phase-to-ground faults. T h e p r i m a r y
TABLE Il-Secondary
6.5% 8% 4%
1
I
700
500
1I
.~
II
A-A
-
5 5% 5 75% 6 5%
8% 4%
Not Applicable
Not Applicable
580 400
290
A--4
5.5%
5.75% 6.5% 8%
2500
1820 1740 1540 1250
2500
1820 1740 1540 1250
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems APPLICATION PRINCIPLES
1000
200
100
50
ANSI Point
20
m U
10
$
.E
I -
ai
75 %
5
time-current
1
0.5
Maximum total clearing time-cu vent curvetypical of Standard Speed fuses rated 1OOE amperes and below. '
0.2
0.1
1 Minimum primary-side line current at which primary fuse will operate to protect the transformer in accordance with the transformer short-time characteristic curve. (Fusing ratio is 1 .O.)
0.05
operate to protect the transformer in accordance with the transformer short-time characteristic curve. (Fusing ratio is 3.0.)
0
N
v) 0
0
0
7
0 0
UJ N
..
Figure 8. The effect o f fusing ratios on the degree of protection provlded a delta delta connected transformer against a phase-to-phase secondary fault.
DATA BULLETIN
S&C ELECTRIC COMPANY Chicago S & C ELECTRIC CANADA LTO - Rexdale
2404 10
Page 17 of 78 August 6,1984
Indoor and Outdoor Distribution (4.16 kv through 34.5 kv) APPLICATION PRINCIPLES
least possible amount of load by the device clearing the fault, while normal service is maintained on the remainder of the circuit. The following sections describe how proper coordination is achieved both between the transformer-primary fuse a n d secondary-side protective devices, a n d between the transformer-primary fuse and upstream protective devices.
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems
APPLICATION PRINCIPLES~
*
Source
t l
v
Feeders
-c
Figure 9. Coordination between an upstream protective device and a feeder protective device. Reler to text.
7
*
Source
Transformerprimary fuse
I
Feeders
,
Figure 10. Coordination between a transformer-primary fuse and a feeder protective device. Refer to text.
1 APPLICATION PRINCIPLES
to failure of a feeder protective device, or (2) there is a secondary bus fault. Either combination of circumstances is so rare t h a t the primary fuse will seldom operate. Even if t h e primary fuse operates, t h e result is no differe n t from t h a t which ensues if only t h e main secondary protective device operates, since in either case the entire output of the transformer will be lost. Rapid operation of the transformer-primary fuse will actually improve the degree of protection provided the transformer for the two situations mentioned above, since the time required for t h e primary fuse to operate will be less t h a n the time required if the primary fuse a n d the main secondary protective device were fully coordinated. The shorter operating time of t h e primary fuse results in a lesser accumulation of mechanical and thermal stresses on the transformer, thereby helping to preserve transformer operating life. Additionally, since secondary-switchboard a n d other nearby faults generally result i n significant damage requiring repair before re-energization, the time a n d cost involved i n replacing the inexpensive primary fuse will be insignificant compared to t h a t involved in locating and repairing the fault. To establish coordination between the transformerprimary fuse and the feeder protective device, it is necessary to examine t h e relationship between the minimum melting time-current characteristic curve of the primary fuse a n d t h e total clearing time-current characteristic curve of the feeder protective device. I n so doing, however, the time-current characteristic curves for both devices must be converted to equivalent currents applicable to a common voltage (either primary-side or secondary-side). For this publication, the primary-side voltage h a s been used. Complete coordination between the two devices is obtained when the total clearing time-current characteristic curve of the feeder protective device lies below
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems APPLICATION PR INC IPLES
Adjusted minimum melting time-current curve of transformer-primary fuse Total clearing time-current
Adjusted minimum melting time-current curve of transformer-primary fuse Total clearing ti me-current curve of transformer-primary Short-time characteristic curve for delta grounded-wye connected
.E
I -
-voltage current-
k
Current
inrush current
Current
Figure 11. Coordination between transformer-primary fuse and: (a) low-voltage current-limiting feeder fuse, or (b) low-voltage feeder circuit breaker.
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S & C ELECTRIC CANADA LTD Rexdale
2404 10
Page 21 of 78 August 6,1984
Indoor and Outdoor Distribution (4.16 kv throuqh 34.5 kv) APPLICATION PRlNCl PLES
\ -
Adjusted minimum melting time-current curve of hfl transformer-primary fuse Total clearing time-current curve of transformer-primary
\
Total clearing time-curr curve of medium-voltag feeder circuit breaker having highest setting
I
/ \\!
E .I-
-4
I
Current
ll
*
Figure 12. Coordination between transformer-primary fuse and: (a) Class E-2 high-voltage industrialcontrol equipment, or (b) mediumvoltage feeder circuit breaker.
2404 10
Page 22 of 78 August 6,1984
DATA BULLETIN
S&C ELECTRIC CANAOA LTO . Rexdale
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial. and Institutional Power Systems APPLICATION PRINCIPLES
per-unit primary-side line current to the per-unit secondary-side line current for the same transformer connections and types of secondary faults as illustrated in Figure 5 on page 11. For a phase-to-phase secondary fault not involving ground on a delta grounded-wye connected transformer, the per-unit primary-side line current in one phase is the same a s t h a t resulting from a three-phase secondary fault, while the secondary-side line current is only 0.87 per unit of the three-phase secondary fault-current value (hence, the ratio, as listed in Table 111,is 1.0 + 0.87, or 1.15). To compensate for the line-current differential inherent to the delta grounded-wye connected transformer, it is generally recommended that a 15%margin in terms of current (or a n equivalent margin in terms of time) be maintained between the total clearing timecurrent characteristic curve of the feeder protective device a n d the minimum melting time-current characteristic curve of the transformer-primary fuse. Refer to
Figures 13 a n d 14. The only exception to this recommendation is Class E-2 high-voltage industrial control equipment, where the 15% current margin is not required since t h e point of influence of this margin (where the curves for this device a n d the primary fuse are the closest to each other) occurs at approximately 20 seconds (see Figure 12a), before which time a medium-voltage phase-to-phase ungrounded fault would have propagated to ground. This current margin is therefore not required to ensure proper coordination for faults involving ground in this type of equipment. Occasionally, i t may be deemed necessary to coordinate the transformer-primary fuse with the main secondary-side protective device. In this case, the primary fuse will operate to protect the transformer against a fault located between t h e transformer and the main secondary protective device, a n d will further serve as a backup to the main device-operating i n the event the main secondary protective device either fails to operate due to a malfunction, or operates too slowly due to incorrect (higher) ratings or settings. The method for establishing coordination between the primary fuse a n d the main secondary protective device is essentially the same as t h a t described previously for a feeder protective device, except for the handling of the current margin (or equivalent time margin) for the phase-to-phase seconda r y fault not involving ground on a delta grounded-wye connected transformer. For this particular fault, Figure 13 shows t h a t the point of influence of the 15h current margin (or equivalent time margin) typically occurs a t a relatively low current (and long duration) for lowvoltage circuit breakers a n d low-voltage current-limiti n g fuses. The probability of occurrence of a lowmagnitude long-duration phase-to-phase secondary fault not involving ground located between the feeder protective devices a n d the main secondary protective device is extremely remote. Such low-magnitude longduration faults typically occur on a feeder some distance from the transformer, a n d t h u s are cleared by the
TABLE Ill-Relationship Between Per-Unit Primary-Side Line Current and Per-Unit Secondary-Side Line Current for Various Ty !s of Secondary Faults
Ttansfonnsr
Fault _ _ I ) .
14-4
10
10
10
I A-A
10
10
Not Applicable
10
115
0 58
DATA BULLETIN
S&C ELECTRIC COMPANY- C h i c a g o S&C ELECTRIC CANADA LTO Rexdale
2404 10
Page 23 of 78 August 6,1984
Total cleari ng ti me-cu rrent curve of low-voltage feeder circuit breaker having highest Adjusted minimum melting time-current curve of t ransf ormer-p ri rnary fuse
Short-time characteristic curve for delta groundedwye connected transformer Short-time characteristic curve for delta grounded-wye connected transformer
rn 15% current
rn 15% current
inrush current
Current
Current
>
Figure 13. Application of minimum 15% current margin between time-current curves of transformer-primary fuse and: (a) low-voltage current-limiting feeder fuse, or (b) low-voltage feeder circuit breaker, for delta grounded-wye connected transformers.
^-
__
"
-"----
I_"
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems APPLICATION PRINCIPLES 1
feeder protective device. Accordingly, it is not necessary to maintain the 15%current margin (or equivalent time margin) when coordinating low-voltage main seconda r y circuit breakers a n d low-voltage main secondary current-limiting fuses with the primary fuse. Figure 14 shows that, for medium-voltage circuit breakers, the point of influence of the 15%current margin (or equivalent time margin) occurs a t a very high current-on the order of the maximum three-phase secondary faultcurrent level. Accordingly, this margin must be retained when coordinating medium-voltage main secondary circuit breakers with the primary fuse. Since main secondary-side protective devices typically have high ampere ratings or settings, difficulties are sometimes experienced in simultaneously obtaining protection for the transformer against secondary-side faults in accordance with the transformer short-time characteristic curve, and complete coordination between the transformer-primary fuse and the main secondary protective device. If this situation is encountered, it is recommended t h a t the ampere rating or settings of the main secondary protective device be investigated to see if a reduction is possible, rather than accepting a larger t h a n necessary primary-fuse ampere rating, resulting in reduced transformer protection. This point is illustrated i n Figure 15, wherein a transformer-primary fuse, selected to protect the transformer in accordance with the discussion in the previous section, does not coordinate with a low-voltage main secondary circuit breaker over the full range of applicable currents. Coordination between the two devices h a s not been obtained with t h e short-time pickup current of the main secondary circuit breaker set at 12,000 amperes (4X), a n d with the short-time delay setting on maximum. Clearly, by reducing the short-time pickup setting from 4X to 3X or 2.5X a n d by reducing the shorttime delay setting from maximum to intermediate or to minimum, coordination between the main secondary circuit breaker a n d t h e primary fuse will be
Current
I, Maximum three-phase secondary fault current. I, 87% of maximum three-phase secondary fault current. T, Minimum melting time of transformer-primary fuse at I,.
T , Total operating time of medium-voltage circuit breaker at
Note: For coordination, T, must be greater than T P . Figure 14. Application of minimum time margin (equivalent to 15% current margin) between time-current curves of transformer-primary fuse and medium-voltage circuit breaker (feeder or main), for delta grounded-wye connected transformers.
I,.
DATA BULLETIN
S&C ELECTRIC COMPANY * Chicago S & C ELECTRIC CANAOA LTO . Rexdale
2404 10
Page 25 of 78 August 6, 1984
I APPLICATION PRINCIPLES
1000
500
d -
100
20
10
g
0
a , v)
0
4
44
8 O 800
175E Ampere, Slow Speed 2500 Kva z = 5.75% IF L = 104.6 Amperes at 13.8 Kv r IFL = 3000 Amperes at 480 V Short-time pickup current:12.000 amperes (4x1 Clearing time for Maximum short-time delay setting: 0.50 second
Magnetizinginrush current
0.5
+
? )
A
0.2
0.1
0.05
Instantaneous pickup current: 4800 amperes (6X) Clearing time for lnstantaneous setting: 0.05 second
0.02
0.01
N
I n
I n
v) 0
0 0
r
0 0 N 0
0 0 0 I n
0 0 0
r
Figure 15. Coordination between a transformer-primary fuse and a low-voltage main secondary circuit breaker can often be obtained by lowering the short-time pickup current and/or the short-time delay setting.
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems
APPLICATION PRINCIPLES~
obtained. (The time-current characteristic curve for the main secondary circuit breaker adjusted to reflect lower short-time pickup a n d short-time delay settings is illustrated by dotted lines.) Lack of complete coordination of t h e type illustrated in Figure 15 can frequently be corrected by making such adjustments. If it is not practicable to reduce the ampere rating or settings of the main secondary-sideprotective device, as discussed in the example above, incomplete coordination between the transformer-primary fuse and the main secondary-side device should be accepted in order to obtain better transformer protection. Even if these rare circumstances are encountered, coordination will typically be given up over only one or two very small ranges of current. protective devices. Specifically, the minimum melting time-current characteristic curve of upstream power fuses must be adjusted to reflect the assumed prefault load, and the time-current characteristic curve for upstream relays must be adjusted for a n y overtravel and tolerance, as recommended by the manufacturer of the device. Refer to Figure 16. Earlier in this guide, it was recommended t h a t you select the smallest practicable ampere rating of transformer-primary fuse in order to maximize transformer protection. Such a fuse selection will also greatly facilitate coordination with the upstream protective device since the lower total clearing time-current curve associated with this fuse will more easily fit below the timecurrent curve of the upstream protective device. Often the upstream protective device will be on the system of the serving utility, in which case the utility should be consulted to verify t h a t the primary fuse selected for your application coordinates with the utilitys device. Occasionally, the utilitys coordination parameters may preclude the use of the primary fuse ampere rating selected. If difficulties in coordination with upstream protective devices (whether on your system or on the utilitys) are encountered, the primary fuse application should be restudied to verify t h a t the smallest practicable ampere rating h a s indeed been selected. This may involve a reconsideration of the ratings a n d settings of the secondary-side protective devices with which coordination was obtained.
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S&C ELECTRIC CANADA LTD . Rexdale
2404 10
Page 27 of 78 August 6,1984
S I C Power Fuses
-curve
Minimum operating timecurrent curve of upstream circuit-breaker overcurrent relav (adjusted and
Current
____)
Current-
Figure 16. Coordination between transformer-primary fuse and: (a) upstream power fuse, or (b) upstream circuit breaker.
"
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems
transformer against damage from overheating due to excessive overcurrents. I n general, the size of conductor to be used is determined by considering the conductors ampacity, as well as its behavior under short-circuit current conditions. Selection of the conductor size from t h e standpoint of continuous current-carrying capability is easily done by reference to t h e ampacity tables i n the National Electrical Code. Similarly, conductor sizes capable of withstanding available short-circuit currents c a n easily be selected from industry-accepted graphs, such as those contained i n T h e IEEE Buff Book,* or those distributed by the conductor manufacturers. If the
size of conductor to be used is selected i n this manner, the primary fuses selected i n accordance with the recommendations presented i n this publication will easily protect the conductors against damage from overheating due to excessive overcurrents. Verification t h a t this is indeed the case for cables can be obtained by referring to S&C Data Bulletin 240-150,Guide for Power Fuse Protection of Medium-Voltage Cables.
I
Introduction to Fuse Selection Tables
As described in the foregoing text, the selection of a transformer-primary fuse ampere rating and speed characteristic involves consideration of all of the following factors: 1. Anticipated normal transformer loading schedule, including daily or repetitive peak loads, a n d emergency peak loads; 2. Transformer inrush current, including the combined effects of transformer magnetizing-inrush current and the energizing-inrush currents associated with connected loads-particularly following a momentary loss of source voltage; 3 . The degree of protection provided to the transformer against damaging overcurrents; and 4. Coordination with secondary-side as well as other primary-side overcurrent protective devices.
In the past, the task of selecting a transformerprimary fuse ampere rating and speed involved complex graphical solutions using time-current characteristic curves published for the various overcurrent protective devices, taking into consideration the many adjustment factors required by the manufacturers of the various protective devices a n d the particular transformer connection. The fuse selection tables presented in this publication are based on the consideration of all of the aforementioned factors, and permit the direct selection of the
transformer-primary fuse, thereby eliminating the need to perform graphical coordination studies. The tables list, for each transformer, primary-fuse ampere ratings and speeds t h a t will accommodate the full range of loading levels normally encountered, and t h a t will withstand the energizing-inrush currents associated with each transformer shown. I n addition, for each such fuse, the degree of transformer protection provided by the primary fuse is quantified using S&Cs unique Transformer Protection Index, which indicates the level of secondary-fault current down to which the primary fuse will operate to protect the transformer in accordance with the transformer short-time characteristic curve. Furthermore, each fuse ampere rating and speed listed in the tables h a s been precoordinated with the full spectrum of low-voltage and mediumvoltage secondary-side overcurrent protective devices, such as circuit breakers, fuses, and Class E-2 highvoltage industrial control equipment. You need only refer to these tables to select t h e optimal fuse ampere rating and speed to protect your transformer and coordinate with the appropriate secondary-side overcurrent protective device.
S&C Power Fuses-Types SM, SML, a n d SMD possess the performance characteristics and quality t h a t make them especially suited for the simultaneous satisfaction of all of the selection criteria. These time-tested fuses are available in a wide variety of ampere ratings and speeds, permitting close fusing for maximum protection a n d optimum coordination. And their timecurrent characteristics are precise, with only 10% total
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S & C ELECTRIC CANADA LTD - Rexdale
2404 10
Page 29 of 78 August 6,1984
As a consequence of these performance characteristics, S&C Power Fuses allow you to fuse closer to the transformer full-load current t h a n is possible with other fuses, providing the maximum degree of protection against secondary faults. They are thus better able to protect the transformer against damage due to faults between the transformer a n d the secondary-side protective device, a n d furthermore, to supply backup protec-
2404 i 0
Page 30 of 78 August 6,1984
I _
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S&C ELECTRIC CANADA LTD Rexdale
-- ------
-----^
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems
TABLES^
l a r g e r or smaller secondary-side protective device ratings or settings, Transformer Protection Indexes, a n d loading capability values could apply. The advantages represented by these small differences are so slight t h a t they can be ignored.
Transformer self-cooled ratings. Table XX on page 77 serves as a n index to the fuse selection tables applicable to transformers having primary voltage ratings between 4.16 kv a n d 34.5 kv, with either low-voltage (208 v, 240 v, 480 v, or 600 v) or medium-voltage (2.4 kv or 4.16 kv) secondaries. The transformer ratings i n Table XX are listed on a self-cooled basis. T h e fuse selection tables are applicable to all transformers with the listed ratings even if they are equipped with cooling fans, if they have increased temperature capability (e.g., 65C temperature rise instead of 55C temperature rise), or if they have both cooling f a n s and increased temperature capability. The standard transformer impedances listed i n Table XX were used i n preparing t h e fuse selection tables. Transformers with special impedances are not within the scope of this publication, a n d t h u s have not been considered. I n t h e secondary-side protective-device ratings or settings columns, t h e transformer protection index columns, and the loading capability columns, actual values may differ slightly from t h e listed values for different voltages where multiple voltages are involved. I n each situation, the worst-case values are shown in t h e fuse selection tables. T h a t is, slightly
Prefault load. As mentioned previously, the timecurrent characteristic curves for medium-voltage power fuses are determined at 25C a n d with no initial load. In practice, every fuse is carrying some load which, in addition to ambient temperatures i n excess of 25C, raises t h e temperature of the fusible element, a n d hence reduces the melting time for a given value of current. This is of importance in determining coordination between the transformer-primary fuse and secondaryside protective devices as well as in calculating the hotload pickup capability of the primary fuse.
For the purpose of the fuse selection tables, a prefault load was assumed based solely on the fusing ratio (the ratio of the fuse ampere rating to the transformer fullload current). Specifically, for a fusing ratio less t h a n 1.0,the transformer is assumed to be loaded to 80R)of its full-load current. For a fusing ratio between 1.0 a n d 2.0 inclusive, the transformer is assumed to be loaded to 100% of its full-load current. Finally, for a fusing ratio greater t h a n 2.0, the transformer is assumed to be loaded to 133R) of its full-load current.
Coordination with secondary-side overcurrent protective devices. In general, this section of the fuse selection tables was developed by examining the relationships which exist between the minimum melting time-current characteristic curve of the transformerprimary fuse and the total clearing time-current characteristic curves for the full spectrum of low-voltage and medium-voltage secondary-side overcurrent protective
DATA BULLETIN
S&C ELECTRIC COMPANY Chicago S&C ELECTRIC CANADA LTO . Rexdale
2404 10
Page 31 of 78 August 6,1984
devices. As explained previously, proper coordination between the primary fuse a n d the secondary-side overcurrent protective device requires the consideration of a number of factors. The assumptions made in considering these factors are outlined below for various types of secondary-side overcurrent protective devices.
1. Low-voltage molded-case or power circuit
breakers equipped with electronic tripping devices (Tables IV through VIII, pages 40 through 49).Coordination between the transformerprimary fuse a n d a low-voltage molded-case or power circuit breaker involves comparing the minimum melting time-current characteristic curve of the primary fuse (adjusted to reflect the assumed prefault load a s described on page 31) with the total clearing time-current characteristic curve of the low-voltage circuit breaker. For the purpose of the fuse selection tables, it is assumed t h a t the upper limit of the circuit breakers long-time delay band is a line having a constant It, passing through the point corresponding to a current of 6 times the minimum long-time pickup current of the circuit breaker, and a time of 20 seconds. Refer to Figure 17. This represents a longtime delay band located between the average of the intermediate long-time delay bands for a number of makes of low-voltage circuit breakers and the average of the maximum long-time delay bands for the same circuit breakers.
The short-time or instantaneous pickup current of the low-voltage circuit breaker is listed in the fuse selection tables as a percentage of the transformer secondary full-load current. I n arriving a t these values, the total clearing current of the circuit breaker is assumed to be 10% higher t h a n the short-time or instantaneous pickup current. Refer to Figure 17. The maximum three-phase secondary fault-current level used i n determining coordination between t h e transformer-primary fuse a n d the low-voltage circuit breaker is based on consideration of the source impedance, as well as the more dominant transformer impedance. For t h e purpose of the fuse selection
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems THE FUSE SELECTION TABLES
1000
200
100
Assumed calibration point (6 times minimum long-time pickup current of circuit breaker at 20 seconds)
50
10
2. Low-voltage current-limiting fuses (Tables IX through XIII, pages 50 through 65). Coordination between the transformer-primary fuse a n d a lowvoltage current-limiting fuse involves comparing the minimum melting time-current characteristic curve of the primary fuse (adjusted to reflect the assumed prefault load as described on page 31) with the total clearing time-current characteristic curve of the current-limiting fuse. For low-voltage current-limiting fuses rated 601 amperes or larger, UL (Underwriters Laboratories) Class L fuses have been used in preparing the fuse selection tables. For low-voltage current-limiting fuses rated 600 amperes or less, where applicable, the time-current characteristics of fuses having the most time delay (and having a suitable interrupting rating) for each manufacturer have been used. Specifically, Russmann LOW-PEAK R , UL Class K5 and RK5; General Electric C L F R ,UL Class J; Federal Pacific Econ-Limiter", UL Class K 5 and RK5; and Gould Amp-Trap R , UL Class K5 a n d RK5 have been used. All other classes of low-voltage current-limiting fuses made by each manufacturer (rated 600 amperes or less) will also coordinate with the transformerprimary fuse with even greater margin, because they have less time delay t h a n the current-limiting fuses used. The values listed in the fuse selection tables for low-voltage current-limiting fuses are based on the coordination requirements of the delta grounded-wye connected transformer. For this transformer, a 15% current margin was maintained between the minimum melting time-current characteristic curve of the transformer-primary fuse (adjusted to reflect the assumed prefault load as described on page 31) and the total clearing time-current characteristic curve of
10
Figure 17. The circuit breaker lime-current characteristics shown were used in developing the fuse selection tables.
DATA BULLETIN
r _ A
240-110
Page 33 of 78 August 6,1984
3. Medium-voltage circuit breakers with associated inverse-time overcurrent relays (Tables XIV through XVII, pages 66 through 73). Coordination between t h e transformer-primary fuse a n d a medium-voltage circuit breaker involves compari n g the minimum melting time-current characteristic curve of t h e primary fuse (adjusted to reflect the assumed prefault load as described on page 31) with t h e total clearing time-current characteristic curve of t h e medium-voltage circuit breaker. A time margin of 0.15 second was added to t h e time-current characteristic curve of the relay used with the medium-voltage circuit breaker. This margin consists of a relay time tolerance of 0.07 second (based on the assumption that the relay operating time is carefully calibrated at maximum three-phase secondary fault current), plus a 5-cyclecircuit breaker interrupting time of 0.08 second. Adjustments to accommodate relay time tolerance values other t h a n 0.07 second can be made by adding or subtracting (as applicable) t h e difference
----
-.
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems THE FUSE SELECTION TABLES
margin discussed on pages 20 through 25 was added to t h e total clearing time-current characteristic curve of the circuit breaker/relay combination, to compensate for the line-current differential resulting from a phase-to-phasesecondary fault not involving ground. characteristic curve, and second, the point a t which the two curves intersect should be a t as low a multiple of the transformer primary full-load current as possible. The Transformer Protection Index indicates how well these two objectives are achieved. The presence of a n index indicates t h a t the first objective was achieved, whereas the absence of a n index signifies t h a t the primary fuse does not provide protection for the transformer, since t h e total clearing time-current curve of the primary fuse passes above a n d to the right of the ANSI Point. Accordingly, a smaller primary-fuse ampere rating should be selected. The indexes indicate the percentage of the transformer primary full-load current down to which the primary fuse will operate to protect the transformer in accordance with the transformer short-time characteristic curve. The indexes are listed in the fuse selection tables for commonly used transformer connections. For delta grounded-wye connected transformers, the indexes are based on a phase-to-ground secondary fault, which is the most demanding type of fault for this transformer connection from a protection standpoint. For delta delta connected transformers, the indexes are based on a phase-to-phase secondary fault, which is t h e most demanding type of fault for this transformer connection from a protection standpoint. Similarly, for groundedwye grounded-wye connected transformers, and for delta wye connected transformers with the neutral grounded through a n impedance, the indexes should
4. Class E-2 high-voltage industrial control equipment (Tables XIV through XVII, pages 66 through 73). Coordination between t h e transformerprimary fuse a n d the high-voltage industrial control equipment involves comparing t h e minimum melti n g time-current characteristic curve of t h e primary fuse (adjusted to reflect the assumed prefault load as described on page 31) with t h e total clearing timecurrent characteristic curve of t h e control equipment. A 15%current margin was not maintained between their respective time-current characteristic curves, for the reason outlined on page 23.
The Transformer Protection Index. The Transformer Protection Index is provided in the fuse selection tables to allow you to evaluate t h e degree of transformer protection provided by the transformer-primary fuse ampere rating selected. As explained i n the section entitled, Protect Transformer Against Damaging Overcurrents . . . beginning on page 9, there are two objectives that must be achieved in order to obtain a comprehensive level of protection for the transformer. First, the total clearing time-current characteristic curve of the primary fuse should pass below a n d to the left of the ANSI Point of the appropriate transformer short-time
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S&C ELECTRIC CANADA LTU Hexdale
240-110
Page 35 of 78 August 6,1984
Loading capability. In general, loading capability refers to t h e amount of load t h e transformer-primary fuse c a n pick u p (even after a momentary loss of source voltage) without operating, a n d carry on a continuous basis. The values listed in t h e fuse selection tables were determined to be the minimum of continuous peak-load, hot-load, a n d cold-load pickup capabilities for each fuse ampere rating. These three capabilities are discussed below:
Continuous peak-load c a p a b i l i t y . . . ability of t h e transformer-primary fuse to carry on a continuous basis, daily or repetitive peak loads regardless of duration. Continuous peak-load values for S&C Type SM, SML, a n d SMD-20 Power Fuses c a n be determined by referring to S&C D a t a Bulletin 240-190.
Hot-load p i c k u p c a p a b i l i t y . . . ability of the transformer-primary fuse t h a t is carrying load, to withs t a n d the combined magnetizing- and load-inrush currents associated with the re-energizing of the transformer following a momentary loss of source voltage. Specifically, hot-load pickup capability is the maximum transformer load current which, when used as the pre-outage load current in adjusting the minimum melting time-current characteristic curve of the primary fuse, results in a fuse curve t h a t passes above a n d to the right of the point representing the magnitude and duration of the combined magnetizing- and load-inrush currents. C o l d - l o a d p i c k u p c a p a b i l i t y . . . ability of the transformer-primary fuse to withstand the combined magnetizing- and load-inrush currents associated with the re-energizing of the transformer following a n extended outage (30 minutes or more). Cold-load pickup capability is typically associated with utility distribution transformer loading practices, where
A -
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems
Examples
T h e following examples are provided to illustrate the use of t h e fuse selection tables for various applications involving the full spectrum of low-voltage a n d mediumvoltage secondary-side overcurrent protective devices.
The steps listed i n these examples correspond to those contained in t h e instructions on How to Use t h e Fuse Selection Tables o n page 76 (foldout). For your convenience, the instructions should be left folded out for ready reference while studying these examples.
Example 1
13.8 K v
Transformer-primary fuse installed in metal-enclosed switchgear M a x i m u m ampere rating permitted by serving utility 80E Maximum available fault current at fuse location 10,000 amperes rrns symmetrical lnnn _ _ _ Kva .
I
I
I
I
I
I
I I
I I
I
STEP 5. The primary fuse has a loading capability of 205% of the transformer full-load current, which is adequate for the application in this example. STEP 6. A primary fuse rated 65E amperes, Slow Speed, TCC No. 119, is recommended. STEP 7. The recommended primary-fuse ampere rating (65E) complies with the serving utilitys requirement that the fuse rating not exceed 80E amperes. STEP 8. From Table XVIII on page 74, S&C Power FusesTypes SM-4Z.SML-4Z.SM-20,and SML-20are available in the voltage rating (14.4 kv nominal), maximum ampere rating (200E),and interrupting rating (12,500 amperes rms symmetrical or above), sufficient for the application in this example.
STEP 1. The index on page 77 lists Table XI as applying to transformers rated 13.8 kv three-phase, 1000 kva, 5.75%impedance, with low-voltage secondary current-limiting fuses. STEP 2. The ratio of the Bussmann current-limitingfuse having the highest ampere rating to the transformer secondary full-load current(at 480 volts) is 600 amperes + 1200amperes, or
50k
The appropriate entry in the Bussmann column forthe feeder fuse is 7281. STEP 4. The Transformer Protection Index (TPI) for the transformer in this example is 360%.A comparison of this value with the values listed in Table XIX indicates that the primary fuse associated with this TPI will protect the transformer in accordance with the transformer short-time characteristic curve against all types of secondary faults-even phase-toground arcing faults.
STEP 3.
DATA BULLETIN
S&C ELECTRIC COMPANY- Chicago S & C ELECTRIC CANADA LTD * Rexdale
2404 10
Page 37 of 78 August 6,1984
Example 2
b1
13.8 Kv/\ 480 V
Transformer-primary fuse installed on outdoor station structure or pole top Maximum ampere rating permitted by serving utility: l O O E Maximum available fault current at fuse location: 8000 amperes r m s symmetrical 1000 Kva
2 = 8%
IF.L = 41.8 Amperes at 13.8 Kv IF.L = 1200 Amperes at 480 V
Maximum loading requirement: 100% Short-time pickup current: 6400 amperes (4X) Clearing time for short-time delay setting: 0.50 second Low-voltage power circuit breaker Instantaneous pickup current: 2000 amperes (5X) Clearing time for instantaneous setting: 0.05 second
I
load current (at 480 volts) is 6400 amperes + 1200 amperes, or 533%. STEP 3. The appropriate entry in the column corresponding to the clearing time for short-time delay or instantaneous setting of the main secondary circuit breaker is 570Lfi. STEP 4. The absence of a Transformer Protection Index (TPI) signifiesthat the primary fuse does not provide suitable protection for the transformer, and therefore, a smaller primary fuse ampere rating should be selected. This may be accomplished in this example by reducing the short-time pickup current of the main secondary circuit breaker from 6400 amperes (4X)to 4800 amperes (3X). The ratio of the new short-time pickup current to the transformer secondary full-load current is 4800 amperes + 1200amperes, or 400%.and the appropriate entry in the column corresponding to the clearing time for short-time delay or instantaneous setting is 415%.The TPI for the transformer in A comparison of this value with the this example is 610%1. values listed in Table XIX indicates that the primary fuse associated with this TPI will protect the transformer in accordance with the transformer short-time characteristic curve against all types of bolted or metallic secondary faults.
STEP 5. The primary fuse has a loading capability of 270R of the transformer full-load current, which is adequate for the application in this example. STEP 6. A primary fuse rated lOOE amperes, Standard Speed, TCC No. 153, is recommended. STEP 7. The recommended primary-fuse ampere rating (100E) complies with the serving utilitys requirement that the fuse rating not exceed lO0E amperes. STEP 8. From Table XVIII on page 74, S&C Power FusesTypes SM-4 and SMD-20 are available in the voltage rating (14.4 kv nominal), maximum ampere rating (200E), and interrupting rating (12,500 amperes rms symmetrical or above), sufficient for the application in this example.
STEP 1. The index on page 77 lists Table VI as applying to transformers rated 13.8 kv three-phase, 1000 kva, 8%impedance, with low-voltage secondary circuit breakers. STEP 2. The ratio of the short-time pickup current of the feeder circuit breaker having the highest setting to the transformer secondary full-load current (at 480 volts) is 2400 amperes + 1200 amperes, or 200%. STEP 3. The appropriateentry in the column corresponding to clearing time for short-time delay setting of the feeder circuit breaker is 205%1. STEP 4. The Transformer Protection Index (TPI)for the transformer in this exampleis270fi. A comparison ofthis value with the values listed in Table XIX indicates that the primary fuse associated with this TPI will protect the transformer in accordance with the transformer shorbtime characteristic curve against all types of secondary faults-even phase-toground arcing faults. STEP 5. The primary fuse has a loading capability of 160[% of the transformer full-load current, which is adequate for the application in this example. STEP 6. A primary fuse rated 50E amperes, Slow Speed, TCC No. 119, is recommended. STEP 7. The recommended primary-fuse ampere rating (50E) complies with the serving utilitys requirement that the fuse rating not exceed IOOE amperes. STEP 8. From Table XVIII on page 74, S&C Power FusesTypes SM-4 and SMD-20 are available in the voltage rating (14.4 kv nominal), maximum ampere rating (200E),and interrupting rating (12,500 amperes rms symmetrical or above), sufficient for the application in this example.
If it is deemed necessary for the transformer-primary fuse to coordinate with the main secondary circuit breaker instead of the largest feeder circuit breaker in this example, Steps 2 through 8 would be repeated with these results: STEP 2. The ratio of the short-time pickup current of the main secondary circuit breaker to the transformer secondary full-
.. ...
..
. .-
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems THE FUSE SELECTION TABLES1
Example 3
13.8 Kv
2.4 Kv
A A
3 -
Transformer-primary fuse installed in metal-enclosed switchgear Maximum ampere rating that coordinates with upstream circuit breaker: 300E Maximum available fault current at fuse location: 32,000 amperes rms symmetrical
2500 Kva = 5.5% IF L = 104.6 Amperes at 13.8 Kv IFL = 600 Amperes at 2.4 Kv Maximum loading requirement: 120%
Medium-voltage circuit breaker IAC 77 relay (extremely inverse) Pickup current: 720 amperes Nominal relay operating time at maximum three-phase secondary fault current: 0.20 second
+
T
M 200Hp
@ 400HP
If it is deemed necessary for the transformer-primary fuse to coordinate with the main secondary circuit breaker instead of the largest Class E-2 high-voltage industrial control equipment in this example, Steps 2 through 8 would be repeated with these results: STEP 2. The ratio of the overcurrent relay pickup current to the transformer secondary full-load current (at 2.4 kv) is 720 amperes + 600 amperes, or 120'%.
STEP 3. The appropriate entry in the column containing the
STEP 1. The index on page 77 lists Table XV as applying to transformers rated 13.8 kv three-phase, 2500 kva, 5.5%imped-
ance, with medium-voltage secondary circuit breakers or Class E-2 industrial control equipment. STEP 2. Proceed to Step 3. STEP 3. The appropriate entry i n the column corresponding to the secondary voltage of 2.4 kv i s the first line containing 6R. STEP 4. The Transformer Protection Index (TPI)forthe transformer in this example i s 210%.A comparison of this value with the values listed in Table XIX indicates t h a t the primary fuse associated with this TPI will protect the transformer in accordance with the transformer short-time characteristic curve against all types of secondary faults. STEP 5. The primary fuse h a s a loading capability of 105%of the transformer full-load current. Since this is less t h a n the required loading capability of 12096, the next higher value listed in this column, or 125%, should be selected. STEP 6. A primary fuse rated 125E amperes, Standard Speed, TCC No. 153, is recommended. STEP 7. The recommended primary-fuse ampere rating (125E) coordinates with the upstream circuit breaker, which can accommodate a primary-fuse ampere rating up through 300E. STEP 8. From Table XVIII on page 74, a n S&C Power FuseType SM-5SS is available in the voltage rating (14.4 kv nominal), maximum ampere rating (400E), a n d interrupting rating (34,000 amperes rms symmetrical), sufficient for the application in this example.
range of pickup currents encompassing the value calculated above, for a n extremely inverse relay, i s 0.25. STEP 4. The Transformer Protection Index (TPI) for the transformer in this example is480%. A comparison of this value with the values listed in Table XIX indicates that the primary fuse associated with this TPI will protect the transformer in accordance with the transformer short-time characteristic curve against all types of secondary faults. STEP 5. The primary fuse h a s a loading capability of 180%of the transformer full-load current, which is adequate for the application in this example. STEP 6. A primary fuse rated 200E amperes, Slow Speed, TCC No. 119, is recommended. STEP 7. The recommended primary-fuse ampere rating (200E) coordinates with the upstream circuit breaker, which can accommodate a primary-fuse ampere rating up through 300E. STEP 8. From Table XVIII on page 74, a n S&C Power FuseType SM-5SS is available in the voltage rating (14.4 kv nominal), maximum ampere rating (400E), and interrupting rating (34,000 amperes rms symmetrical), sufficient for the application in this example.
DATA BULLETIN
S&C ELECTRIC COMPANY * Chicago S&C ELECTRIC CANAOA LTD Rexdale
Indoor and Outdoor Distribution (4.16 kv through 34.5 kv) THE FUSE SELECTION TABLES
T A B L E IV-Transformers
1
%ma mer 8
E
_c
-n r ndn.
Of i l r
U*nt
LHdng
:4lWllW.
%fml%toi n#(olauI
m"
m"
_ I I
hHRO,
L
. O C
sc?s) m u r
mpan
_ I
FUll-LoLd
YOH.gM
Maill
P
830 at 208v, 720 at 240v. 360 at 18Ov, or 290 at 600v 1390 at 208v. 1200 at 240~. 600 at 480~. or 480 at 600v
21 5 270 270 335 335 415 415 250 250 335 360 400 430 465 500 535 575
260 260 360 360 430 430 500 500 575 575 360 400 430 465 500 535 280 280 350 350 435 435 350 435 435 -
iahl
1 7 (
260 350 350 440 460 550 560 310 320 450 460 570 580 650 670 760 840 290 290 350 360 410 420 580 590 610 640 730 960
Current
0
270 360 370 500 510 620 330 350 490 530 610 700 800 900 200
780
165 215 215 260 260 280 280 170 170 195 195 225 225 255 255 285 285
-- no.
Slow Std Slow Std. 80e 310w IWE Std. 1 OOE Slow 1 OOE 1O O E 125E 125E
TCC
_ .
Std.
30w
Std.
500
4%
69.4
-208, 240, 480, or 600 2080 at 208v, 1800 at 240v. 900 at 480v, 720 at 600v 220 240 265 285 310 335 355 380 445 480 535 575 285 285 335 335 380 380 480 480 575 575
575
Slow
Std. Slow Std. Slow Std. Std. Slow Std. Slow Std.
150e
150E 175E 175E 200E
430
-
430
500
500
j75
4%
104.1
335
335
750
5.75%
104.1
-- - 215
4% 208, 240, 480, or 600 138.8 2780 at 208v, 241 0 at 240v, 1200 at 480v. or 960 at 600v 235 250 265 285 335 360 400 430 535 575 250 250 285 285 360 360 430 430 575 575
220 240 265 285 310 335 355 380 445 480 535 575
285 285 335 335 380 380 480 480 575 575
575
240
-
-575 335
575 290 290 350 360 410 420 580 590 610 640 730 960
300 31 0 380 390 440 450 600 660 670 880 050
-E
130 130 150 150 170 170 190 190 240 240 285 285 130 130 150 150 170 I 70 190 190 240 240 285 285 125E 125E 150E 150E 175E 175E 200E EOOE 250E 250E 300E 125E 125E 150E 150E 175E 175E 200E 2M)E 250E 250E 3M)E
153 119 153 119 153 119 153 119 153 119 153 119
153 119 153 119 153 119 153 119 153 119
Slow
Std. Slow Std. Slow Std.
335
---
380
-
380
480 575
575
-260 310 310 350 360 450 450 530 590 750 980 280 320 320 370 380 470 520 580 840 930
300 310 380 390 440 450 600 660 670 880 050
Slow
Std. Slow Std. Slow
1000
--
5.75%
138.8
200 215 235 2780 at 250 208v. 265 241 0 at 285 240v, 1200 at 335 480v. or 360 960 at 400 600v 430 535 575 transformers wit imn apply.
--
430
430
575 -
-575 575
575
260 260 310 310 350 360 450 450 530 590 750 980 -
110 130 130 140 140 180 180 215 215 285
285
110 110 130 130 140 140 180 180 215 215 285 285
250 250 250 250 285 285 285 285 360 335 360 360 360 360 400 430 430 430 430 430 575 535 575 575 575 575 he ne al grounded
- -
360
360
-
270 280 320 320 370 380 470 520 580 840 930
150E 150E 175E 175E 200E 200E 250E 250E 300E 300E 400E 400E -
150E 175E 175E 200E 200E 250E 250E 300E 300E 400E 400E
Sloa Std. Slow Std. Sloa Std. Slou Std. Slow Std.
*Std.
119 153 119 153 119 153 119 153 119 153 119 Std. 153 119 SlOV 153 Std 119 SlOV Std. 153 119 SlOV Std. 153 119 SlOV 153 Std SIOV 119 153 Std 119 SlOV -
153 119 153 119 153 119 153 119 153 119 153 119
TABLE CONTINUED
Note: Refer to "How to Use the Fuse Selection Tables" on page 76 (foldout).
A -
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems
TABLES^
Laaclf
1 0 .
--w
~~
E** tbm.
P(0lc
E2
1000
-208, 240, 480, or 600 138 8 2780 at 208v, 241 0 at 240v. 1200 at 480v, or 960 at 600v
-- - -4% 208, 240, 480, or 600 208.2 4160 at 2 OBV, 3610 at 240v, 1800 at 480v, or 1440 at 600v 285 285 285
1500
--208. 240, 480. or 600 41 60 at 208v, 3610 at 240v, 1800 at 480v. or 1440 at 600v
-- - -- - ---515 515 515 515 220 240 265 285 355 380 400 430 480 515 200 215 265 285 300 320 360 385 480 515 215 230 240 255 290 310 385 415 285 285 385 380 430 430 515 515 285 285 320 320 385 385 515 515 240 265 285 355 380 400 430 480 515 285 285 385 380 430 430 515 515 285
-
200 215 235 250 265 285 335 360 400 430 535 575 220 240 265 285 355 380 400 430 480 515
250 250 285 285 360 360 430 430 575 575 200 21 5 235 250 265 285 335 360 400 430 535 575 250 250 285 285 360 360 430 430 575 575
- -- - - --I )
e . IhW
16
Imt" 1)
mcl&um* wsrry
C -
AmP-
e
tee
Fufl.Lo*d
Mal*
' n d a
esln
No.
150E 150E 175E 175E 200E 200E 250E 250E 300E 300E 400E 400E 250E 250E 300E 300E 400E 400E 2-250E 2-250E 2-300E 2-300E Std Slow Std Slow Std 153 119 153 119 153 119 153 119 153 119 153
250
250
285
-
285
-
---
380
380 430 430 515 515
285
380
400 430 480 515
430
-
430
260 260 310 310 350 360 450 450 530 590 750 980 290 290 350 350 480 540 620 640 750 970
110 110 130 130 140 140 180 180 215 215 285 285
Slow
Std Slow Std Slow Std
120 120 140 140 190 190 215 215 255 255 120 120 140 140 190 190 215 215 255 255 105 105 140 140 160 160 195 195 255 255 115 115 130 130 155 155 205 205
Slow
Std
Slow
Std Slow Std
119
153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 153 119 153 119 153 119 153 119
285
-
5.75%
208.2
_ .
380
380
290 290 350 350 480 540 620 640 750 970
250E Std 250E Slow 300E Std 300E Slow 400E Std 400E Slow 2-250E Std 2-250E Slow 2-300E Std 2-300E Slow 300E 300E 400E 400E 2-250E 2-250E 2-300E 2-300E 2-400E 2-400E 400E 400E 2-250E 2-250E 2-300E 2-300E 2-400E 2-400E Std Slow Std
2000
5.75%
480 or 600
277.6
285
-
285
-
385
480 515
260 260 350 370 440 450 540 580 730 940
260 260 360 420 470 500 570 860 820 290 310 370 370 450 520 610
Slow
Std Slow Std Slow Std Std Slow Std Slow Std Slow Std
- slow 2
2500
5.75%
480 or 600
347.0
-- - 3750 5.75% 480 or 600 520.4 451 0 at 480v or 361 0 at 600v 190 205 255 275
~
- slow 2-300E 2-300E 2-400E 2-400E Std Std Slow 153 153 119
275
~
275
275
275
Slow 119
- --For
Ita grou
al grounded t h n i u y h a
the "d
.il
dell
column ;ipply.
Note: Refer to "How to Use the Fuse Selection Tables" on page 76 (foldout).
DATA BULLETIN
S&C ELECTRIC COMPANY Chicago S&C ELECTRIC CANADA LTD Rexdale
2404 10
~-
Indoor and Outdoor Distribution (4.16 kv through 34.5 kv) THE FUSE SELECTION TABLES
T A B L E V-Transformers Rated 12.0 Kv or 12.47 Kv Three-Phase-with
fmke An
-w
f
Tnhr
rrrn
830 at 14.4 at 208v, 12.0 kv 720at or 240~. 13.9at 360at 12.47 480v. or kv 290at 600v 1390 at 208v. 24.1 at 12.0 kv 1200 at or 240v, 23.1 at 600 at 12.47 480v. or kv 480at 600v 2080 at 36.1 at 208v, 12.0 kv 1800 at 240v Or 34.7 at 900at 12.47 480v, or kv 720at
- -
p
760 395
395
20E 20E 25E 25E 30E 30E 40E 40E 30E 30E 40E 40E 50E 50E 65E 65E
Slow
Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow
Std.
153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119
500
-310
470
490
-250 310 320 420 420 540 550 700 710 250 250 310 320 420 420 540 550 700 710 240 310 310 380
4%
750
5.75%
4ip6r
600
208,
t I
2080 at 36.1 at 208v, 12.0 kv 1800 at or 240v. 34.7 at 900at 12.47 480v. or
325
- 250 310 310 385 385 480 480 250 325 325 400 400 500
480
505
480 -
505 -
325 135 155 190 190 245 245 305 305 325 325 145 165 185 225 225 245 245 285
40E 50E 50E 65E 65E 80E 80E l00E lOOE 40E 40E 50E 50E 65E 65E 80E 80E l00E 100E 50E 65E 65E 80E 80E l00E l00E 125E 125E 50E 50E 65E 65E 80E 80E lOOE lOOE 125E 125E 50E 5OE 65E
450
470 620 760
I 2780 at
4% 48.1 at 208v, 208, 12.0 kv 2410 at 240, or 240v, 480, or 46.3 at 1200 at 600 12.47 480v, or kv 960at 600v 235 235
500 --
500 --
400 500
800
400
360 480 520 375 520 520 490 500 700 790 240 240 310 310 380 400 490 500 700 790 240 240 310 310 380 400 490 500 700 790
+
2780 at 48.1 at 208v, 12.0 kv 2410 at or 240v, 46.3 at 1200 at 12.47 480v, of kv 960at 600v
520 180
520
520
520
520 -
520 -
165
300 300 375 375 520 520 235 285 285 360 360 480 520 300 300 375 375 520 520
235 235 285 5.75% 4iio;r 1000 285 600 360 360 480 520 180 185 2780 at 235 46.1 at 208v, 12.0 kv 2410 at 235 208. 240, or 240v, 285 480, or 46.3 1200at 285 12.47 480v, or 600 360 kv 960at 360 600v 480 520 I 1 For ,Ita grounded-wye connected transformers with the values in the delta delta ctilumn apply. 208,
- 185 235 235 285 300 300 285 360 375 360 375 480 520 520 520 ,a1 grounded I
:z
480 520
235 360
- -
i;i I ;;:1
11 i 11
520
--
119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153
% 375
285 360
-TABLE CONTINUED
285
ough an impedance.
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout).
Selection Guide for Transformer-Primary Fuses in Mediurn-Voltage Industrial, Commercial, and Institutional Power Systems THE FUSE SELECTION TABLES 1
T A B L E V-Transformers
208. 240, 480, or 600 72 2 at 120kk or 39 4 at 12 47 kv 41 60 at 208v, 3610 at 24Ov. 1800 at 480v, 0 1 1440 at 600v
w tee -#d
mnt I n .
550
1500 4160 at 208v. 3610 at 240v. 1800 at 480v, 01 1440 at 600v 155 190 190 240 240 320 345 385 415 450 485 515 550 145 180 180 240 260 290 310 335 360 385 415 480 520 ~
--250 250 345 345 41 5 41 5 485 485 550 550 240 320 345 385 41 5 450 485 515 550 250 345 345 415 415 485 485 550 550
250 250 345 345 415 415 485 485 550 550
slow
Std 150E Slow 175E Std 175E Slow 200E Std
550 550 -
slow 125 135 150 160 160 190 190 215 215 245 245 275 275 105 115 120 140 140 160 160 185 185 205 205 260 260 95 110 110 130 130 150 150 165 165 205 205 245 65E 8OE 80E 1O O E 1O O E 125E 125E 150E 150E 175E 175E 200E 200E
119 153 119 153 119 153 119 153 119 153 119
5.75%
Slow
Std Slow Std Slow Std Slow Std Slow
41 5
415
-
-260 290 310 335 360 385 415 480 520 260 310 310 360 360 415 415 520 520
-- 80E Slow 1O O E Std 1OOE Slow 125E Std 125E Slow 150E Std 150E Slow 175E Std 175E Slow 200E Std 200E Slow 250E Std 250E Slow -1OOE Slow 125E Std. 125E Slow 150E Std. 150E Slow 175E Std 175E Slow 200E Std. 200E Slow 250E Std. 250E slow 300E Std Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std.
2000
5.75%
480 or 600
- -
2500
5.75%
480 or 600
180 190 205 180.4 220 at 255 12.0 kr 4510 at 275 or 180v or 480 or 5.75% 305 173.6 3610 at 600 330 at 600v 410 12.47 440 kv 460 495 555 ta grou k d - w y e mnected transformers wi
145 190 205 230 245 270 290 305 330 385 415 460 495
--
119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153
119 153 119 153 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119 153 119 153 119
245 245 290 290 330 330 415 415 495 495 -
310 245
-
330
245
-
3750
- For
- -
275 275 305 330 330 330 330 440 440 410 440 440 440 495 495 460 495 495 495 595 595 555 h e n< .ral grounded 1
ough an impe
440
360 380 370 390 420 430 440 470 540 590 580 640 640 740 760 240 240 250 250 270 280 280 290 340 360 350 370 400 420 440 520 560 610 690 850 750 960 850 910 - , the "delta del
'
ctilumn apply.
Note: Refer to "How to Use the Fuse Selection Tables" on page 76 (foldout).
DATA BULLETIN
S&C ELECTRIC COMPANY. C h i c a g o S&C ELECTRIC CANADA LTD Rexdale
2404 10
Page 43 of 78 August 6,1984
830 at 208v, 720 at 240~. 360 at 480v, or 290 at 600v 1390 at 208v. 1200 at 240v, 600 at 480v. 01 480 at 600v 2080 at 208v. 1800 at 24Ov. 900 at 480v, or 720 at 600v 2080 at 208v. 1800 at 240v, 900 at 480v, or 720 at 600v
---- WMiDTIlW
M n u y FulEUed annnl
kmwm
-1%
TCC
wo.
4%
330
345 395 415 205 235 245 315
41 5 -245 245 330 330 415 415 540 540 275 275 360 360 440 440
395
415 415 -
15E Slow 20E Std 20E Slow 25E Std. 25E Slow 30E Std. 30E Slow 25E 30E 30E 40E 40E 50E 50E 65E 65E
119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119
500
4%
330
395 415 515 515
330
-
330
540 -------515 540 515 220 265 275 345 345 420 420 155 165 210 220 265 275 340 340 420 420
41 5 515 515
41 5
-
415
-
160 2 05 205 260 260 320 320 410 410 170 210 210 270 270 335 335 95 125 165 170 210 210 270 270 335 335 130 160 205 205 250 250 270 270 310 310 130 140 160 205 205 250 250 270 270 310 310 130 140 160 205 205 250 250 270 270 310 310
4%
360 440
-- 30E 30E 40E 40E 50E 50E 65E 65E 80E 80E
Slow Std.
Slow Std. Slow Std. Slow Std. Slow Std. Slow Std.
119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 119 119 153 119 153 119 153 119 153 119
5.75%
43.7 at 208, 13.2 ku 240, or 480. or 41.8 at 600 13.8 ku 2780 at 208v, 2410 at 240v. 1200 at 48Ov, or 960 at 600v
420
440 -
4%
315
395
395 530 570 -
-43.7 at 208, 13.2 kv 240, or 480. or 41.8 at 600 13.8 kv 2780 at 208v, 2410 at 240v, 1200 at 480v, or 960 at 600v 165 195 205 255 255 315 315 395 395 530 570 165 195 205 255 255 315 315 395 395 530 570 270 270 330 330 415 415 570 570
Slow Std. Slow Std. Slow Slow Slow Std. Slow Std. Slow Std. Slow Std.
570 570 -
Slow --
000
5.75%
- -208, 240, 480, or 600 43.7 at 13.2 ku or 41.8 at 13.8 ku 2780 at 208v, 2410 at 240v, 1200 at 480v. 960 at 600v
___.
---
--
8%
-------76 ( f o l d o u t ) .
255
270
40E Slow 50E Std. 50E Slow Std. 65E 65E slow 80E Std. 80E Slow 1O O E Std. 1O O E Slow 125E Std. 125E Slow 40E Slow Std. 50E 50E Slow 65E Std. 65E Slow Std. 8OE 80E Slow Std 1O O E 1O O E Slow 125E Std. 125E Slow
--
For delta grounded-wye connect, transformers with the neutral grounded through a n impedance, the values in the delta delta column apply. N o t e : R e f e r to How to Use the F u s e S e l e c t i o n T a b l e s on p a g e
TABLE CONTINUED
I . A
119 153 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119 153 119 -
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems
or
13.8 Kv Three-Phase-with
Low-Voltage Seconds
Circuit Breakers-Continued
TCC
I 4160 at
208, 240, 480 or 600 55.6 at 13.2 kv
Or
Na
230 280 350 360 490 520 620 650 720 780 230 290 360 380 520 620 670 800 1060 135 165 180 180 205 205 240 240 270 270 135 65E 80E lOOE lOOE 125E 125E 150E 150E 175E 175E 50E 65E 65E 80E 80E lOOE l00E 125E 125E 150E 150E 175E 175E Slow Slow Std. 119 119 153 119 153 119 153 119 153 119
208v3
I
1500 4160 at 208v, 3610at 240v, 1800 at 480v, or 1440 at 600v
-135 170 170 210 21 0 265 265 355 380 425 455 495 530 155 195 195 265 285 315 340 370 400 425 455 530 570 155 210 225 255 270 2 95 320 340 365 425 455 510 545 275 275 380 380 455 455 530 530
Slow
Std. Slow Std. Slow Std. Slow Slow Std. Slow Std Slow Std.
455
-
455
I
530 530 -
530
530 -
210 220 230 270 280 350 360 490 520 620 650 720 780
119 153 119 153 119 153 119 153 119 153 119 153 119
5.75%
55.6 at 13.2 kv
360
380 520 620 670 800
or
52.8 at 13.8 kv
l480 or 600
I3frkv 2410 at 480v or
-285 285 340 340 400 400 455 455 570 570
530 -
380
-
380
-
210 260 260 360 370 450 450 510 520 590 620 770 910 21 0 290 290 350 350 410 41 0 470 480 600 630 720 930
%-e-260 270 370 400 470 530 550 640 650 900 920
Slow
Std. Slow Std. Slow Std. Slow
87'5
2000
5.75%
83.7 at 13.8 kv
lg30 at 'OoV
340
-
455 570
-109.3 at 1 3 2 kv 1006.6
at
400
-
400
-
135 135 155 155 180 180 205 205 225 225 285 285
2500
5.75%
480 or 600
t:b :2 :
I
3010at 480v or
1 3 8 .
3750
140 150 170 180 195 164.0 210 480 or 225 5.75% 600 240 280 305 450 485 510 545 Ita grounded-wve connected transfnrrners with
I
-
kv
270 270 320 320 365 365 455 455 545 545 -
270
I I
270 320
-
510
510
210 290 300 370 390 430 440 500 560 660 880 960
-
105 125 125 140 140 165 165 180 180 225 225 270 270
80E lOOE lOOE 125E 125E 150E 150E 175E 175E 200E 200E 250E 250E lOOE 125E 125E 150E 150E 175E 175E 200E 200E 250E 250E 300E 300E
Slow 119
153 119 153 119 153 119 153 119 153 119 153 119
Slow
Slow
Std.
Slow
Slow Std. Slow Std.
119 153 119 153 119 153 119 153 119 153 119 153 119
Slow
Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std.
230 230 95 150E 230 240 95 150E 270 270 110 175E 270 280 110 175E 310 320 120 200E 310 320 120 21 0 200E 380 400 150 240 250E 390 420 150 240 250E 240 240 240 240 460 280 305 480 180 305 300E 500 305 305 620 180 305 300E 305 305 305 305 640 485 485 700 240 450 485 450 400E 780 485 485 240 485 485 400E 485 I 485 I 485 850 545 545 510 545 270 !-250E 1020 545 545 545 545 270 !-250E the neutral grounded through a n impedance, the valurs in the "delta delta" column apply
153 119 153 119 153 119 153 119 153 Slow 119 Std. 153 Slow 119 Std. 153 Slow 119
Note: Refer to "How to Use the Fuse Selection Tables" on page 76 (foldout).
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S & C ELECTRIC CANADA LTD . Rexdale
2404 10
Page 45 of 78 August 6,1984
Indoor and Outdoor Distribution (4.16 kv through 34.5 kv) THE FUSE SELECTION TABLES
TABLE VII-Transformers
Rated 22.9 Kv o r 24.9
-t-nr plolul
Y I
nnn
lo(
went
RJMa
iwtr Ilr
w
ha
pH
nnn
%JmM
7.6 at 208, 22 9 kv 240, or 480, or 7.0 at 600 24 9 kv 830 at 208v, 720 at 240v, 360 at 480v, 290 at 600v 1390 at 208v, 1200 at 240v, 600 at 480v. or 480 at 600v 230 295 345 360 460 480 310 360 360 480 480 360 460 480 360
-rcc
Ila
480
480
640
690 290 370 380 480 490 590 620 310 310 370 380 510 540 670 760 250 250 310 310 370 380 510 540 670 760 280 290 370 390 480 500 660 700
320 410 510 590 710 I300 300 390 400 520
185 255 295 295 395 395 175 235 235 295 295 355 355 185 195 235 235
1O E 13E 15E 15E 20E 20E 15E 20E 20E 25E 25E 30E 30E 25E 25E N E 30E 40E 40E 50E 50E 20E 20E 25E 25E 30E 30E 40E 40E 50E 50E 30E 30E 40E 40E 50E 50E 65E 65E 25E 25E 30E 30E 40E 40E 50E 50E 65E 65E
Slow
Std. Slow
153 153 153 119 153 119 119 153 119 153 119 153 119
215 275 2 85 345 360 410 430 230 240 275 285 365 385 460 480
- -
- -
-- 285 285 385 385 480 480 275 285 365 385 460 480 265 285 385 385 480 480
360 41 0 430
540
Slow
Std.
660 850
*Std. 153 Slow 119 Std. 153 Slow 119 Std. 153 Slow 119 Std. 153 119 Std. 153 Slow 119 Std. 153 Slow 119 Std. 153 Slow 119 Std. 153 Slow 119 Std. 153 119 Std. 153 Slow 119 Std. 153 Slow 119 Std. 153 Slow 119 Std. 153 119 Std. 153 Slow 119 Std. 153 Slow 119 Std. 153 Slow 119 Std. 153 Slow 119 Std. 153 119 Std. 153 Slow 119 Std. 153 Slow 119 Std. 153 Slow 119 Std. 153 Slow 119 Std. 153 119
4%
- -750
18.9 at 2080 at 208v, 22.9 kv 208. 1800 at or 240, 240v, 17.4 at 480, or 24.9 kv 900 at 600 480v, or 720 at 600v 2080 at 208v, 18.9 at 208, 1800 at 22.9 kv 240, 240v, or 480. or 900 at 17.4 at 600 480v, or 24.9 kv 720 at 600v
300
300 370 370 110 145 185 195 235 235 300 300 370 370 170 175 225 225 275 275 355 355 95 120 170 175 225 225 275 275 355 355
-180 185 230 240 275 285 365 385 460 480 205 21 5 275 285 345 360 445 445 285 285 385 385 480 480
480 ----
385
*-
5.75%
540
740 780
480 -
385
4%
2780 at 208v. 241 0 at 240~. 1200 at 4 8 0 ~ or . 960 at 600v 2780 at 208v. 241 0 at 240v. 1200 at 480v. or 960 at 600v
430
520 670 780
170 180 205 215 275 285 345 360 445 445
-285 285 360 360 465 465 275 285 345 360 445 445
445
465
- 1300
230 240 280 290 370 390 480 500 660 700 240 240 280 290 390 430 520 670 780
IO00
5.75%
285
285
465
465 --- 170 180 2780 at 205 208v, 25.2 at 208, 215 22.9 kv 241 0 at 240, 240~. 275 8% or 480. or 23.2 1200 at 285 at 600 480v, or 345 24.9 kv 960 at 360 600v 445 445 0 For delta grounded-wye connected tr;insfnrmcrs with 205 215 275 285 275 285 285 2 85 345 345 360 360 360 360 445 465 445 445 445 465 ral grounded through an
~
--285 285 285 285 345 360 360 360 360 360 465 465 445 465 445 465 impedance, the values
360
445 445
--
-----
25E 230 95 240 25E 240 120 240 280 280 30E 170 290 290 30E 175 370 40E 225 390 40E 390 225 430 50E 480 275 520 500 275 670 50E 65E 660 355 65E 700 355 in t h r delta delta cnlumn apply
*-
TABLE CONTINUED
Selection Guide for Transformer-Primary Fuses in Medium-Voltage industrial, Commercial, and Institutional Power Systems THE FUSE SELECTION TABLES
4BLE Ill-Tr
Low-Vo
qe S e c o n d a r y C i r c u i t Breakers-
Continued
_ I
I
310 310 385 385 480 480
310
1500 37.8 a t 22.9 kv or 34.8 at !4.9 kv 4160at 190 208v. 230 3610at 240 2 4 0 ~ ~ 295 1800 at 295 MOv, or 365 1440at 365 600v 460 460 140 170 180 220 220 275 275 345 345 460 495 550
5.75% 208, 240, 480. or 600 310 310 385 385 480 480
550 460 480 700 250 250 310 310 420 420
185 185 235 235 290 290 310 310 120 150 185 185 235 235 290 290 310 310 95 95 135 175 175 215 215 230 230 270 270 310 310 105 120 140 175 175 185 185 215 215 250 250 285 285
530
365 460 385 480 550 690
600
710 800
-
230
2000
5.75%
180 or 600
360
495 495 595 595 -
- - -175 i 75 220 220 275 275 365 395 440 475 515 555
275
-
285
345
460
495 550 595
310 380 400 470 500 710 760 900 1120 190 250 250 300 310 370 400 550 580 700 720 800 880 210 250 260 360 360 430
1
5OE 50E 65E 65E 80E 80E lOOE 100E Std. Slow Std.
119 153 119 153 Slow 119 Std. 153 Slow 119 Std. 153 Slow 119
153 119 153 119 153 119 153 119 153 119
eo0
40E Std. 40E Slow 50E Std. 50E Slow 65E Std. 65E Slow 80E Std. 80E Slow lOOE Std. 1O O E Slow 40E .~ Slow 50E Std. 50E Slow 65E Std. 65E Slow 80E Std. 80E stow 1O O E Std. 1W E Slow 125E Std. 125E Slow 150E Std. 150E Slow 50E 65E 65E 80E 80E 1O O E 1O O E 125E 125E 150E 150E 175E 175E
--119 153 119 153 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119 153 119 153 119
2500
5.75%
180 or 600
145
260 260 315 315 370 370 420 420 525 525 the n
190 250 250 310 330 400 420 600 730 760
Slow
Std. Slow Std. Slow Std.
950
-
180
94 5 at 22.9 kv or 87 0 at 24 9 kv 180 245 260 295 260 295 315 340 370 390 420 490 525 260 315 31 5 370 370 420 420 525 525
3750
5.75%
180 or 600
315 340
370
315
315
4 4 0 500
510 580 420 420 610 490 525 750 525 525 840 nce. the values In the
-
540
620 630 860 870
For
!Ita groi
-led-wye mnecti
1
transfnrmers 525 wi
370
370
Ita del
110 80E 120 1O O E 125 1O O E 145 125E 145 125E 150E 165 165 150E 175E 190 190 175E 210 200E 210 200E 260 250E 260 250E column PPlY.
-Slow 119
153 119 153 119 153 119 153 Slow 119 Std. 153 Slow 119 Std. 153 119 Slow -
Slow
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout)
DATA BULLETIN
S&C ELECTRIC COMPANY * Chicago S & C ELECTRIC CANADA LTD Rexdale
2404 10
Page 47 of 78 August 6,1984
IllM-Rmunl
ch.nrcrblk
9md
TCC No.
52a t 33 0 kv or 5 0 at 34 5 kv
520
520
Std. 153
4%
1390 at 208v. 1200 at 240v, t 600 a 480v. or 480 at 600v at 13.1 a t 2080 208v. 33.0 kv 1800 a t or 240v, 12.6 a t 900 at 34.5 kv 480v. or 720 at 600v
255 295 310 395 415 495 520 205 265 275 330 345 395 415
270 310 310 415 415 520 520 275 275 345 345 415 415 41 5 495 520 415 520 520
530 700 495 520 520 700 710 270 350 360 440 450 550 340 340 425 425 170 225 285 340
850
520 - ----
415 415 - -170 195 205 265 275 330 345 395 415
395
415
- Slow
15E 20E 20E 25E 25E 30E 30E 13E 15E 15E 20E 20E 25E 25E 30E 30E 20E 25E 25E 30E 30E 40E 40E 50E 50E Slow
Std.
Slow
Std. Std.
Slow
Std.
Slow
- Slow
260 270 350 360 440 450 550 560 260 330 330 400 400 540 570 710 850 260 260 330 330 400 400 540 570 710 850 260 280 360 370 480 490 600 720 260 340 340 420 440 590 830 870 140 170 225 225 285 285 340 340 165 210 210 255 255 325 325 400 400 135 165 210 210 255 255 325 325 400 400
5.75%
Slow
4%
1000
275
345 345 41 5 41 5 345 395 41 5 345 415 415
Std.
Slow Slow
415
415 -
- Slow
153 153 119 153 119 153 119 119 153 119 153 119 153 119 153 153 119 153 119 153 119 153 119 119 119 119 119 119 153 119 153 119 153 119 153 119 153 119
415
-
415
520
520
520 -
5.75%
- -
--
495 520
520 520 -
- Std.
20E 20E 25E 25E 30E 30E 40E 40E 50E 5OE
Std.
slow
Std.
Slow
Std.
Slow
Std.
- Slow
h e neutral grounded through an impedance, the values in the delta delta column apply.
TABLE CONTINUED
Note: Refer to How to Use the Fuse Selection Tables o n page 76 (foldout).
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems THE FUSE SELECTION TABLES I
4BLE VIII-Transformers
Low-Volta
mpra
8%
2780 at 208v, 17.5 at 208. 33.0 kv 2410 at 240v. 240, or 480, or 16.7 at 1200 at 600 34.5 kv 480v. or 960 at 600v 4160 at 208v, 26.2 at 208, 33.0 kv 3610 at 240v. 240, or 480, or 25.1 at 1800 at 600 480v, or 34.5 kv 1440 at 600v 4160 at 208v, 26.2 at 3610 at 33.0 kv 240v, or 25.1 at 1800 at 480v. or 34.5 kv 1440 at 600v 195 205 245 260 295 310 395 415 495 520 205 265 275 330 345 430 430 260 260 310 310 41 5 41 5 520 520
205 245 260 295 310 395 415 495 520 260 260 310 310 415 415 520 520 260 295 310 395 415 495 520 2Ml 310 310 415 415 520 520
- --260 260 330 330 400 400 540 570 710 850 260 260 340 340 420 440 590
-
Std Slow Std Slow Std Slow Std Slow Std Slow Slow Std Slow Std Slow Std Slow Std Slow Std
n m chlctuw
I
7 2
153 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119 153 153 119 153 119 153 119 153 119
135 165 210 210 255 255 325 325 400 400
49/a
--170 195 205 265 275 330 345 430 430 155 195 205 245 260 320 320 395 395 495 495 275 275 345 345 450 450 275 330 345 430 430
430
450
- - - Slow --220
345
-
30E 40E 40E 5OE 50E 65 E 65 E 25E 30E 30E 40E 40E 50E 50E 65 E 65E
20E 20E 25E 25E 30E 30E 40E 40E 5OE 50E
345
450 - 430 200 260 260 330 330 440 440 560 580 740 750 200 260 270 340 340 470 500 650 820
110 160 170 215 215 265 265 340 340 110 145 160 200 200 255 255 310 310 335 335
- Slow
30E 40E 40E 50E 50E 65E 65E 80E 8OE IO O E Std. Std. Slow Std Slow Std
-165 195 205 255 43.7 at 301 0 at 255 33.0 kv 480v or 315 or 241 0 at 41.8 at 315 600v 34.5 kv 395 395 530 570 170 170 21 0 210 65.6 at 4510 at 265 33.0 kv 480v or 265 or 3610 at 355 62.8 at 600v 380 34.5 kv 425 455 495 530 ,Ita grounded-wye connect transformers wit 270 270 330 330 415 415 570 570
520
Slow
Std.
860
-
E Slow
Slow Std
2500
--2t0 265 265 355 380 425 455 495 530 ral grounded through a n impr
950 --230 230 280 280 350 360 500 510 640 455 455 530 495 530 530 nre. the value 230 230 280 300 360 380 540 630 690
800
210 260 270 350 360 470 490 610 770 920
130 140 160 205 205 250 250 270 270 310 310
I OOE
125E
119 153 Slow 119 Std 153 Slow 119 Std 153 Slow 119 Std 153 Slow 119 Std 153 Slow 119 Std Slow Std Slow Std Slow Std Slow Std 153 119 153 119 153 119 153 119 153 119 153 119
3750
' For
---
660
720 780 n the
830
105 65E 135 65E 165 8OE 165 80 E 180 1O O E 180 lOOE 205 125E 205 125E 240 150E 240 150E 270 175E 270 '' rolumn apply.
Slow
Std. Slow
Note: Refer t o "How to Use the Fuse Selection Tables" on page 76 (foldout).
DATA BULLETIN
S&C ELECTRIC COMPANY- C h i c a g o S & C ELECTRIC C A N A D A LTD - R e x d a l e
2404 10
Page 49 of 78 August 6,1984
- - 16 K v T - jforrne Rated
mdary Current
i m i t i n g Fuses
mnq. TrslmIomU
Prohatloa In*ll,
I p
nmr-cm
cwwc#tlUi#
tMdOra*r
4-4
210 210 260 260 350 350 440 460 550 560 210 210 260 260 350 350 440 460 550 560 210 210 250 260 310 320 450 460 570 580 650 670 760 840
A-A A--4
0
210 210 270 270 360 370 500 510 620 780 210 210 270 270 360 370 500 510 620 780 210 210 250 260 330 350 490 530 610 700 800 900 1200
36
41 49 52 97 100 114 27 33 33 39 41 47 49 59 60 73 24 26 30 57 59 68 83 91 96 106 108 117 119 131 24 27 29 34 36 43 48 62 59 123 70 137 89 94 108 118 129
25 34 33 43 47 54 89 100 107
300
UP thru 4%
120
26 34 33 42 44 52 55 66 67 83
30 38 38 47 51 77 91 95 110 117
-90 135 155 165 215 215 260 260 280 280 90 135 155 165 215 215 260 260 280 280 90 130 145 155 170 170 195 195 225 225 255 255 285 285 40E 40E 50E 50E 65E 65E 8OE 8OE 1O O E 100E
spnd
1 2
153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119
15 -
08
1 0 4 . 1 0 9 . 124 132
Std Slow Std Slow Std Slow Std Slow Std slow
480 or 600
41.6
68 71 86
27 31 52 58 64 71 81
29
38 38 48 52
Sld
Slow Std Slow Std slow Std. Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow
60
64 76 78 93 30 39
60 69 73 86 89 107
65E 65E 80E 80E 1O O E 1O O E 125E 125E 150E 150E 175E 175E 200E 200E
64
70 76 92 101 109 119 121 130 131 146
208 or 240
69.4
96
97 114 113 128 123 143
500
UP thru 4%
480 or 600
69.4
For Ita grounded-wye connecte Applicable at 208 v only. Applicable at 480 v only.
26 66 30 72 32 78 38 88 40 97 49 600 at 121 55 480v or 480 at 164 68 72 600v 174 67 70 188 139 125 190 79 82 206 153 142 206 80 142 133 235 154 172 160 181 207 _ . .ansformers with the neutral grounded through a n
54 62 5 6 6 5 66 77 69 81 89 102 99 115 110 127 123 141 126 145 138 161 142 165 162 186
152
210 210 31 210 210 35 250 250 37 260 260 44 310 330 46 320 350 63 55 450 490 61 70 460 530 75 101 74 125 570 610 120 137 125 144 134 155 141 161 156 180 impedance, the values in the delta delk
-90 65E 130 65 E 145 80E 155 80E 170 1O O E 170 l00E 195 125E 195 125E 150E 225 225 150E 255 175E 175E 255 285 200E 200E 285 column apply.
TABLE CONTINUED
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout).
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems THE FUSE SELECTION TABLES
TABLE IX-Transforme
Low-Volta
Second
Current-Limiting Fuses-Continued
_ I
104 1
43 46 58
65
73 81 84 92 94 107 119 135 144 172 30
66 76
84
94 97 107 110 123 136 157 168
431 45 66 57 75 66 79 70 80 90 90 80 88 IO1 99 88 to1 I16 109 I28 I30 I52 I38 I58
210 210 290 290 350 360 41 0 420 580 590 610 730 960
90 110 130 130 150 150 170 170 190 190 240 240 285 285
660
670
840
880
050
-
100E lOOE 125E 125E 150E 150E 175E 175E 200E 200E 250E 250E 300E 300E
lOOE 1W E 125E 125E 150E 150E 175E 175E 200E 200E 250E 250E 300E 3WE
6436
78 108 115 125 126 137 137 156 166 192 198 231 69 72 78 78 85 40 48 49 80 83 89 94 104 83 91 96 103 107 120 133 153 162 198
104.1
104a
to3a 121 130 153 163
88
106 108 131 130 161
580
590 610 640 730
iia
132 142 169 48 54 60 62 68 70 80 89 101 107 12P 141 174
- 170 192 62 69 71 79 82 91 102 118 125 146 163 202 49 51 59 59 66 65 75 82 97 103 122 125
210 210 300 310 380 390 440 450 600 660 670 880 050
190
190 240 240 285 285
95 110 110 130 130 140 140 180 180 215 215 285 285
- -220 270 280 320 320 370 360 470 520 580 840* 930* 220 270 280 320 320 380 470 520 580 125E 150E 150E 175E 175E 200E 200E 250E 250E 300E 300E 400E 400E
138.8
w
96 104 123 127 155 160 212
66 66 74 73
86
96 114 117 136 138
IO00
138.8
Ita gniunded-wye connecte Applicable at ZOH v only. Applicahle at 4 x 0 v only. Applicable to transformers through 5.75%,impedance.
80 3 E 33 85 3 E 33 92 5 : 41 94 42 39 101 6 E 70 1200 at 7c 102 65 480v or 116 Ti 79 960 at 124 8 E 81 600v 144 95 98 147 1 M 97 172 122 120 177 132 122 209 1 7 : 155 ransformers with the neutral rnunded through an iml
- 156
67 71 76 684 80 89 78( 100 84 115 99 121 104 147 127 160 132 201 ance, the \
I
175
684 674 7?(1 76a 90 98 115 121 143 148
260 310 310 350 360 450 450 530 590 750
370
360
- E 192
840*
930*
....-
a delt;
95 125E 110 150E 110 150E 130 175E 130 175E 140 200E 140 200E 180 250E 180 250E 215 300E 215 300E 285 400E 400E 285 column apply
TABLE CONTINUED
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout).
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S & C ELECTRIC C A N A D A LTD - Rexdale
240-110
Page 51 of 78 August 6,1984
c3_
tmn Praeu! Pn
-m e r
d0 1
Irrd.N
Loadby)
rtaMlwmo1 hp.RI P Y FulbLcwd
-M.ln
56 59 69 74 90 93 122 107 129 131 165 67 73 83 87 103 107 127 118 131 135 167 62 64 76 80 95 89 63 68 81 84 103 106 141 123 148 151 190 77 82 94 98 114 118 139 129 148 154 190 70 72 85 88 103 97 111 116 142 147 53 58 66 71 85
60 67 77
T R n
Full-&,
m.1
*
C I l m
2 E 2 i
Cunux:
llnw4unonl
c(unchr-
RHlnp,
[ * I C
208 or 240
208 2
55 64
69 85 78
-61 67 75
82 73 78 95 88 99 104 121
60 68 73 84
83
97 108 134 127 141 147 180
66 75 80 97 106 134 123 141 150 181
94
116 108 124 131 156 51 58 65 70
49 54 63 68 81 83 104 91 108 112 135 51a 56a 65 69 84 86 109 98 116 124 149 48 51 62 65 81 73 67 93 111 117 152 51 64 58 69 74 88 92 121
- -4-4
230 290 290 350 350 480 540 620 640 750 970
(5,
&-A
A-Ti
spud
95 120 120 140 140 190 190 215 215 255 255 95 120 120 140 140 190 190 215 215 255 255 200E 250E 250E 300E 300E 400E 400E 2-250E 2-250E 2-300E 2-300E 200E 250E 250E 300E 300E 400E 400E 2-250E 2-250E 2-300E 2-300E 250E 300E 300E 400E 400E 2-250E 2-250E 2-300E 2-300E 2-400E 2-400E
Slow Std. Slow Std.
\ y
119 153 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119 153 119
- -64 75 80 95 99 128 110 133 141 175 230 290 290 350 350 480 540 620 640 750 970 230 300 300 350 400 500 650 680 900 1000
-
230 300 300 350 400 500 650 680 900 1000
480 or 600
208 2
8o
96
90
107 99 111 116 135
- -2410 at 480v or 1930at 600v 59 71 75 78 90 95 62 67 79 75 48 47 58 60 76 69 81 83 103 103 136 48 66 69 86 77 92 95 117 118 156
Slow Std.
Slow Std.
83
92 115 106 122 130 157 48 51 61 68 85
-70 73 95 82 100 106 131 135 169 210 260 260 350 370 440 450 540 580 730 940 280 290 350 350 430 440 580 690
3750
c
5.75% thru 5.75%
5.75%
480 or 600
277.6
80
92 97 118 126
83
87 101 108 139 -
98
101 125 128
~
-480 or 600
-60 55
64 66 81 82 66 61 73 75 93 93 123 77
- --
220 260 260 360 420 470 500 570 860 820 290 310 370 370 450 520 610
90
105 105 140 140 160 160 195 195 255 255 115 115 130 130 155 155 205 205
63
347 0 59 66 69 80 86
75 65 79 84 I04 IO8
119 153 119 153 119 153 119 153 119 153 Slow 119
134 - 280 280 370 410 ies i n t h e d 67 71 89 280 290 380 460 a deli
he I
1 through a n imp
47 70 57 78 61 99 80 ance, the v
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout).
Selection Guide for Transformer-Primary Fuses in Medium-Voltage In d ust rial , Co mmerci al , and Inst it ut ional Power Systems THE FUSE SELECTION TABLES
T A B L E X-Transformers
F U P
E !!
k
p1
*dnr
be
6
* b
C I
-55 60 69 84 114 119 131 136 156 187 60 63 69 82 93 106 114 123 144 173 67 69 7% 81 93 111 117 132 149 155 62 69 89 111 126 130 143 151 175 210 33 38 42
M
L 3
w*
ic
*_*
R.U&
Tllncksnnt
m##ewIeik
208 or 240 14.4 at 12.0 kv or 13.9 at 12.47 kv 830 at 208v or 720 at 240v 25 29 34 41 46 84 88 100 115 136 29 33 36 41 45 49 52 59 67 90
--50 80
82 95 103 125 145 71 91 94 109 118 142 166
W a
- 230 240 320 330 390 400 490 490 880 760
- -240 240 330 330 420 420 530 570 760 240 240 330 330 420 420 530 570 760 110 140 195 205 260 260 310 310 395 395 110 140 195 205 260 260 310 310 395 395 110 135 185 185 235 235 290 290 370 370 15E 15E 20E 20E 25 E 25E 30E 30E 40E 40E 15E 15E 20E 20E 25E 25 E 30E 30E 40E 40E
SPrrCl
$?
153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119
88
98 107 118 132 164
UP thru 4%
---
- 40 E
33
-230 240 320 330 390 400 490 490 680 760 230 230 280 280 380 380 480 490 660 680
~
480 or 600
60 6%
78
64 67 78 89 118
- - 90
104 126 133 147 162 169 32 48 56 61 75 86 96 108 130 137 65 70 85 99 112 125 150 159
37 43 51 58 64 68 77 87 113
66 73 78 88 100 129
208 or 240
500
UP thru
4%
- - -
4 7 - - - - 1
601 71 84 98 I07 27 30
1300
230 230 280 290 390 430 520 660 770
Slow
Std Std Slow Std
- Slow
Slow
Std Slow Std
Slow Std
26 28 31 24.1 at 35 600 at 480 or 12.0 kv 480v or 40 or 600 480 at 53 23.1 at 600v 53 12.47 kv 70 74 134 0 For delta grounded-wye connected transfnrmers wil Applicable at 208 v only. Applicable at 480 v only.
63 33 53 62 69 37 67 76 40 73 61 46 98 52 85 70 103 128 62 60 66 60 62 70 115 159 66 77 128 152 172 124 88 83 145 177 194 126 133 150 138 157 163 132 the ncutr;rl grounded thmugh a n i r n ~
202 - -
1464
1 5 1 (
Ueb
680
1300
I
h c d
110 25 E 135 25E 185 30E 185 30E 235 40E 235 40E 290 50E 290 50E 370 65E 370 65E dclta column apply
- Slow
TABLE CONTINUED-
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout).
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S & C ELECTRIC CANADA LTD . Rexdale
2404 10
Page 53 of 78 August 6,1984
se-
vith
Iw-\
;eci
dary Curr
it-Limiting Fuses-Continued
II
68
77 86 93 102 114 125 $41
__I
208 or 240
750
UP thru 5 75%
68 82
ea
98
108 112 126 136 155 170
-64 81 106 114 129 134 152 164 179 197 61 65 72 80 84 94 102 115 126 151 177 75 3c 33 43 44 55 84 88 104 110 129 137 42 47 52 64 67 81
65 75
83
100 106 125 131 153 160 _ .
190 250 250 310 320 420 420 540 550 700 710
190 250 250 310 320 420 420 540 550 700 710
340
450 470 620 760 800
190
250 260 320 340 450 470 620 760 800
100 135 155 190 150 245 245 305 305 325 325 100 135 155 190 190 245 245 305 305 325 325
--30E 40E 40E 50E 50E 65E 65E 80E 80E lOOE 1DOE 40E 50E 50E 65E 65E 80E 80E 1M)E lOOE 125E 125E
30E 40E 40E 50E 50E 65E 65E 80E 80E 1O O E lOOE
nu. -119 stc 153 Slow 119 153 Std Slow 119 Std 153 Slow 119 Std 153 Slow 119 Std 153 Slow 119
Slow
*roe
Slow Std
Slow Std
480 or 600
_e
208 or 240
1000
UP thru 8%
29 29 37 40 68 76
42 43 50 58 62 68 75 81 91 107 124
-- - 64 69 77
80 97
102
122 128 150 158
Slow
Std
-- - Slow 190 240 240 310 310 380 400 490 500 700 790 190 240 240 310 310 380 400 490 190 240 240 320 320 420 420 540 600 7904 110 110 145 185 185 225 225 245 245 285 285 110 110 145 185 185 225 225 245 245 285 285 Std Slow Std Slow Std Slow Std Slow Std 119 153 119 153 119 153 119 153 119 153 119
119 153 119 153 119 153 119 153 119 153 119
86
Q3 105 121 142
a6
99
104 132 145 32 32 40 63 65 78
100
109 132 154
50E 50E 65E 65E 80E 80E lOOE lOOE 125E 125E Std Slow Std
Slow Std
153 119 153 119 153 119 153 119 153 119
60
84
480 or 600
89 101 101 114 117 134 151 134 0 For ta grounded-wye connected transformers with the neutral prounc d through an Applicable a t 208 v only. Applicable at 480 v only. 4 Applicable to transformers through 5.75'R impedance
84
96
- - -
72 76 91
96 96 112 540 500 6M3 102 117 700 7904 128 151 790 146 167 impedance, the values in the "delta delti
_ .
82
:olumn apply.
TABLE CONTINUED
Note: Refer to "How to Use the Fuse Selection Tables" on page 76 (foldout).
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems THE FUSE SELECTION TABLES
-Trar 1 --- 47 I
4BLE
ormer Rated OKvorl
Three-Phase-with
N-V
tage Secc
_ I
--
es-Continued
-i y
208 or 240
72 2 at 120kv or 69 4 at 12 47 kv
38 43 44 51 53 65 73 77 86
51 55 58
-61 67 76 84 100 118 122 144 139 162 157 187 66 74 80 210 210 250 260 260 270 320 330 330 340 450 470 470 530 560 610 580 700 650 800 680 860 750 11904 870 210 250 260 320 330 450 470 560 580
66
72
88
102 106 125 121 141 136 163 60 66 70 78 87 102 114 118 $29 128 139 138 164
86
P ru 5 5%
96
108
125 119 136
1500
95 95 107
a8
97 114 124 128 142 141 163 160 187 60 65 72 85 92 96 107 106 123 119 139 150 177 gh
I
125 135 150 160 160 190 190 215 215 245 245 275 275 125 135 150 160 160 190 190 215 215 245 245 275 275
--ne.
65E 80E 80E 1O O E lOOE 125E 125E 150E 150E 175E 175E 200E 200E Slow Std Slow Std Slow Sld Slow Std Slow Sld 119 153 119 153 119 153 119 153 119 153 Slow 119 Std 153 119 119 153 119 153 119 153 119 153 119 153 119 153 119
TDC
- slow
65E 80E 80E lOOE lOOE 125E 125E 150E 150E 175E 175E 200E 200E Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std
480 or 600
- -
650
680 750 870 190 230 240 32 0 330 400 41 0
210 260 270 330 340 470 530 610 700 800 860 11904
- slow 119 153 119 153 119 153 119 153 119 153 119 153 119 -
41 39 44 42 46 49 57 63 56 62 66 69 96.2 at 241 0 at 74 67 69 12.0 kv UP or 480 480v or thru 2000 or 80 81 73 600 1930 at 5.75% 92.6 at 74 77 82 600v 12.47 kv 80 90 89 80 a 9 83 89 99 100 97 110 106 110 126 125 Fnr i tn groui rd-wyu connected transformers wit he neutral Applicable at 4R0 v only A Applicable to transformers through 4%1 impedance
- -
53 58 64 66 75 74 85 77 88 90 96 8 6 9 6 102 104 95 103 114 122 121 131 143 155 ounded thr
460
190 240 240 340 350 430 450 500 530 580 700 780
105 80E 115 100E 120 O E 1O 140 125E 140 125E 160 150E 160 150E 185 175E 185 175E 205 200E 205 200E 260 250E 260 250E :olumn apply
- slow
TABLE CONTINUED
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout)
DATA BULLETIN
S&C ELECTRIC COMPANY - C h i c a g o S&C ELECTRIC C A N A O A LTO Rexdale
2404 10
Page 55 of 78 August 6,1984
Indoor and Outdoor Distribution (4.16 k v through 34.5 kv) THE FUSE SELECTION TABLES
4BLE X-Transforme
Rated 12.0 Kvor 12.47 Kv Three-Phase-with
mn,
.L
IO
m
- - - -' +
bc Pd-q
Inn
RMI
PwEd
t UIMUr.
10Q
PMi
Tmn PvSlsi
(HCW
nor
CordlnO
nnsr
c l u ; u r m l :
*wrbnns.
eRde
_ I
- -5
&-A
mnramt.i
lw4'ohd C U M
~~t
a (
+
120'3at 1 2 : r k v
Main
_ .
3010at 480v or
115.7at 12.47 kv
24,b t:
37 44 49 53 58 59 64 64 71 77 87 94 110 39 42 42 47 51 58 62 73 76 93 87 98 103
40 45 52 61 55 71 64 63 65 68 61 71 81 71 71 76 67 80 92 80 88 96 84 100 99 113 1 0 6 103 117 143 123 126 40 47 44 52 56 66 68 84 a4 108 95 114 115 -
84 84
97 96 111 119 141 146 180 64 62 72 79 93 97 119 122 161 143 172 175
65 72 81 83 92 95 106 119 132 145 169 61 62 69 79 88 96 112 124 153 142 163 171
- -0
62 65 77 77 86 85 103 110 124 127 151 190 260 260 310 320 360 370 420 440 540 580 640 760 240 250 270 280 340 350 400 440 190 270 270 330 340 380 390 430 470 590 640 740
-
4-4
&-?i-?(
Splxl
rcc
119 153 119 153 119 153 119 153 119 153 119 153 153 119 153 119 153 119 153 119 153 119 153 119 153
95 110 110 130 130 150 150 165 165 205 205 245 245 100 100 110 110 135 135 165 165 220 220 245 245 295
lOOE 125E 125E 150E 150E 175E 175E 200E 200E 250E 250E 300E 300E 175E 175E 200E 200E 250E 250E 300E 300E 400E 400E !-250E '-250E 1-300E
Slow Std Slow Std. Slow Std. Slow Std Slow Std. Slow Std. Slow Std Slow Std. Slow Std. Slow Std Slow Std. Slow Std. Slow Std
NR
1 1 9
64
180'4 at
480 or 600
64
75 78 95 95 119 107 125 126 -
173.6 at 12.47 kv
66 71 82
86
105 98 110 116 -
560 690
750 850 910 -
240 250 280 290 360 370 420 520 610 850 960
-
0 F(ir delta grounded-wye connected transformers with the ncwtral grounded through a n impedance. the values I n the "delta delta" rolumn a p p l y .
Note: Refer to "How to Use the Fuse Selection Tables" on page 76 (foldout).
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems THE FUSE SELECTION TABLES
4BLE XI-Transformers
Low-Volta!
c
Secondary CL w a r AmImanRaUag,
Cut?bBl
w r
?nl-L
TRR Fmtai2l
I#iL
BUS
-mK(
Pm
to(
bdrr,
Loading
c * -
I _
50 59 67 81 107 123 127 139 146 57 62 69 79 91 105 114 125 133 63 73 75 83 87 101 121 128 144 158 165 53 61 67 74 79 95 119 145 168 189 195
ndr
i
M 1 .n
-t
13.' at 13frkv 480 or 600 12.6 at 13.8 kv 28 32 36 360 at 39 480v or 45 49t 2 ~ ~ o ~ 53 57 66
23 28 33 38 46 52 92 99 109
26 32 38 43 51 84 95 104 113 26 32 37 41 49 54 61 65 75
68 81 111 120 135 139 155 165 61 68 80 88 107 120 127 140 155 71 80 82 92 98 113 136 145 156 173 180 30 36 42 47 55 87 90 105 113 30 36 42 48 57 63 70 75 85
ndr
I65 72 80 86 97
_ I
tnn
mlw
roIaii
FuW.Larl
m = i Y & m n c
spnd
13E 15E 15E 20E 20E 25E 25E 30E 30E 13E 15E 15E 20E 20E 25E 25E 30E 30E 20E 25E 25E 30E 30E 40E 40E 50E 50E 65E 65E 20E 25E 25E 30E 30E 40E 40E 50E 50E 65E 65E Std Std Slow Std Slow Std Slow Std Slow Std Std Slow Std Slow Std Slow Std Slow
Slow Std Slow Std Slow Std Slow Std Slow Std Slow
TCC
86 1001 100 1031 104 123 1051 119 132 112 128
_ .
No. -
62
66
76
I-208 or 240
62 70 75 87
__.
210 260 260 310 310 420 440 540 580 750 820
90 140 170 225 225 285 285 340 340 105 140 160 205 205 260 260 320 320 410 410 105 140 160 205 205 260 260 320 320 41 0 410
119 153 119 153 119 153 119 153 119 153 119
at
209at 13 8 kv
500
UP thru 4%
__
-I''"
r: 3
27 30 61 54 58 69 1390 at 65 72 208v or 76 88 lzooat 88 99 240v 95 108 104 116 120 133 124 138
26 28 31 34 39 44 60 59 78 127 145
162
-210 260 260 310 310 420 440 540 580 750 820 210 260 260 320 330 440 510
600
950 960
119 153 119 153 119 153 119 153 119 153 119
at
480 or 600
kv
209at 13.8 kv
Std
Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow
166
210 210 280 280 350 360 460 480 610 620 he "d
950 960
750
go":,"
,":
l8O0 at 240v
38* 43 49 58 63 69
80
83 93 98 For ta grounded-wye connected transformers wit Applicable at 208 v only. Applicable at 480 v only. A Applicable to transformers through 4 % impedance
41 55 61 44 57 65 54 66 74 62 80 89 71 85 96 79 95 104 95 105 115 110 120 101 120 138 120 126 131 151 i through an imp
41I 441 61 62 52 74 72 63 81 83 71 87 91 78 105 111 92 1Of 116 94 125 137 112 135 145 118 ance, the \ ues
E
a delt.
95 30E 125 30E 165 40E 170 40E 50E 210 210 50E 65E 270 270 65E 335 80E 335 80E column apply.
1 1 9
TABLE CONTINUED-
Note: Refer to "How to Use the Fuse Selection Tables" on page 76 (foldout).
DATA BULLETIN
S&C ELECTRIC COMPANY- Chicago S & C ELECTRIC CANADA LTD Rexdale
2404 10
Page 57 of 78 August 6,1984
S C L C Power Fuses
opr
mm
tmd.X. IEf
W -
- --* - -F *
Winnfur
&
acl
nn
I _
h l
w
22 25 28 38 39 51 84 97 106 116 43 47 51 59 61 70 73 84 86 107 120 29 29 37 40 72 79 87 98 103 124 136 39 41 46 48 55 57 71 80 84 93 94 103
l i
_ i
_ 1
- - -iqPd.1
_ I I I _
* & L e
Ira#
mm
:wm gr 'ss)
_ 1 _
L C.p.bUlb,
Pllmnl d
full.ia.d CUmnt
(rur M
Innformu Rkn8W
unprn
R.m.
rcc
No.
vetam
p -
Yun
*r(u
_ L _ I
Farc).
__I
IULln Rmlr
1 1 1
I _ .
210 210 280 280 350 360 460 480 610 620 130 260
260
-4--d
&-&e ! 2 4
UP thru 5 75%
480 or 600
32 8 at 1 3 2 kv or 31 4 at 138kv
- ---43.7 at 13.2 kv or 41.8 at 13.8 kv 2780 at 208v or 2410at 240v 66 68 79 82 95 99 120 134 46 48 55 63 67 73 82 89 101 117 137 62 69 75 e4 94 103 114 133 155 59 63 70 78 82 90 98 109 122 145 170
- - -- 67 71 77 86 89 104 113 126 139 166 195 47 52 59 71 75 90 95 109 115 145 160 61 67 82 86 103 109 125 131 167 187 47 52 58 69 70 84 88 102 111 129 146 60 64 78 80 97 104 116 123 142
29 33 37 48 49 77 93 98 116 122
Q
210 210 280 290 360 390 500 550 690
E
210 260 260 350 360 480 490 610 760* 920*
~
95 125 165 170 210 210 270 270 335 335 130 140 160 205 205 250 250 270 270 310 310 130 140 160 205 205 250 250 270 270 310 31 0 105 135 165 165 180 180 205 205 240 240 270 270
1 9 -- 1
40E 50E 50E 65E 65E 80E 80E 1O O E 1O O E 125E 125E
Slow Std Slow Std Slow Std Slow Std Slow Std Slow -
30E Std 30E Slow 40E Std 40E Slow 50E Std 50E Slow 65E Std 65E Slow 80E Std 80E Slow
208 or 240
UP thru 8%
- - - - - - 78 32 57 85 32 67 68 90 41 82 66 78 73 68 94 103 85 80 75 97 109 93 110 123 92 83 98 92 104 118 135 110 97 111 128 145 115 110 124 142 160 138 128 144 166 181 165 198 151 182 146 52 41 44 54 68 59 48 74 62 64 54 84 63 68 73 59 92 66 76 81 67 80 88 96 110 78 91 103 113 130 89 92 104 117 135 94 104 109 123 138 158 105 105 118 134 154 122 133 179 155 115 36 36 57 69 73 87 92 107 113 143 161 47 50 59 62 72 76 97 107 120 132 135 147 65 79 83 99 107 121 131 163 185 -
340 340 420 450 550 560 800 920 210 260 260 340 340 420 450 550 560 800 920 -
119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 153 119 153 119 153 119 153 119 153 119 153 153 119 I53 I19 153 119 153 119 153 119 I53
1 1 9
480 or 600
43 7 at 132kv or 41 8 a t 13 8 kv
--
7 6 - 1
45 46 55 58 68 74 86 97 98 115 112 127 63
210 260 260 350 360 480 490 610 760* 920*
40E Slow 50E Std 50E Slow 65E Std 65E Slow 80E Std 80E Slow lOOE Std lOOE Slow 125E Std 125E Slow 65E Std 65E Slow 80E Std 80E Slow lOOE Std 1DOE Slow 125E Std 125E Slow l5OE Std 150E Slow 175E Std 175E -
1 1 9
208 or 240
65 6 at 13 2 kv or 62 8 at 13 8 kv
UP thru 5 75%
60 64
_ .
68
77 82 95 109 111 130 128 145 -
230 230 230 230 280 270 290 280 360 350 380 360 520 490 620 520 670 620 800 650 l060A 720 780 -
slow 1 1 9
Std Slow Std Slow Std
Slow Std Slow Std Slow Std
480 or 600
65.6 at 13.2 kv or 62 8 at 13 8 kv
4ta grounded-wye connecte Applicable a t 480 v only A Applicable to transformers through 4'Xt impedance. Applicable tatransfnrmers through 5.75'31 impedance
61 68 74 73 65 83 77 73 96 92 85 100 97 109 99 110 106 117 116 132 118 111 127 131 149 128 the neutra roui
45 49 54
60
68 46 64 72 48 72 81 57 77 88 60 71 85 96 75 94 106 111 121 95 121 132 107 125 137 116 137 159 131 136 157 134 177 148 156 4 through an imp 62
464 474 65 55 59 70 68 81 74 86 109 91 123 102 135 107 151 125 155 125 138 170 ance. the 7
230 105 230 65E 230 230 135 65E 280 270 165 80E 290 280 165 80E 360 180 350 1O O E 380 360 180 1O O E 520 490 125E 205 620 205 520 125E 670 620 240 150E 800 240 650 150E I060A 270 720 175E 780 175E 270 the "delta delta" column apply
1 9 - slow 1
TABLE CONTINUED
Note: Refer to "How to Use the Fuse Selection Tables" on page 76 (foldout)
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial. Commercial. and Institutional Power Svstems THE FUSE SELECTION TABLES
T A B L E XI-Transformers
Evtr
gm
mw@w
UP thru 5 75%
c u m , L 'WUl
8Kw r y P
_ I
R $1
@I
P
__c
-lbol
-Masr
_ I
_ i
8 3 P : a t 13.8 kv
43 45 47 48 54 51 69 61 63 75 67 72 74 79 72 87 88 79 87 78 82 95 86 97 97 86 92 96 1 0 9 110 106 122 116 138 122 138 40 43 48 50 53 57 63 57 59 70 62 69 66 70 63 78 77 69 73 77 69 88 88 77 97 84 92 97 110 109 103 115 113 138 133 119 38 41 41 45 45 51 56 64 39 45 43 50 48 57 61 72 75 92 91 116 103 121
-61 71 81 63 70 82
K*n
90
94 103 102 116 114 132 144 170
56 65 72 75 82 81 93 91 106 115 135 140 172 49 54 53
83
99 94 11c 105 125 133
157
71 78 90 98 103 120 117 131 130 154 164 195 63 71 78 a2 95 94 105 104 123 131 155 160 198 62 61 69 69 81 87 103 107 132 135 178 157 190
- - 151
44 56 63 69 78 80 88 91 102 114 127 138 162 45 51 52 57 60 67 76 85 92 108 120 147 136 156 64 72 80 90 93 101 104 117 131 148 159 189 43 54
-44 60 50 64 54 68 81 91 76 101 80 113 94 116 92 126 103 129 102 146 122 165 134 186
Tat Ikl.
--
210 260 260 360 370 450 450 510 520 590 620 770 910 210 290 290 350 350 410 410 470 480 600 630 720 930
21 0 260 270 370 400 470 530 550 640 650 900 920
125 135 135 155 155 180 180 205 205 225 225 285 285
80E Slow 1O O E Std 1O O E Slow 125E Std. 125E Slow 150E Std 150E Slow 175E Std 175E Slow 200E Std. 200E Slow 250E Std. Slow 250E 1O O E 125E 125E 150E 150E 175E 175E 200E 200E 250E 250E 300E 300E
Slow Std Slow Std Slow Std Slow Std Slow Std. Slow Std Slow
119 153 119 153 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119
2500
UP thru 5.75%
480 or 'O0
60
63 74 74 83 82 98 107 120 123 146
156
560
660 880 960
230 240 270 280 320 320 400 420 480 620 700
-
105 125 125 140 140 165 165 180 180 225 225 270 270 95 95 110 110 120 120 150 150 180 180 240 240 270 270
-150e 150E 175E 175E 200E 200E 250E 250E 300E 300E 400E 400E !-250t
60
65 7c 83 85 104 1O? 127 114 133 60 69 76 90 93 115 117 155 137 165
3750
UP thru 5.75%
480 or
600
68
79 83 101 94 106
I _
Ita Xrou
- - - -
- -
--
230 230 270 270 310 310 380 390 460 500 640 780 850 1020
For
,ansl'orrners with the neutral griiunded through a n impedance, the values in the "delta delta'' column apply
Note: Refer to "How to Use the Fuse Selection Tables'' on page 76 (foldout)
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S&C ELECTRIC CANADA LTO . Rexdale
2404 10
Page 59 of 78 August 6,1984
Indoor and Outdoor Distribution (4.16 kv through 34.5 kv) THE FUSE SELECTION TABLES
T A B L E XII-Transformers Rated 22.9 Kv or 24.9 K v Three-Phase-with
vynunphouac
p a J l
IXl
IIC
Tmn
Pmwl
PM Ton
FtIlC&
me#
, I*.
It d
TlneCumnt
ch.r.derlrtk
14eellbn
rwI
-vol(le.r
Primary
AI -
Fu(lLS
- Main
L
I I
Irc+lox w. 9)
CWMl
. . g
L
208 or 240
7 6 at 22 9 kv or 7 0 at 24 9 kv
85 121 138 152 168 189 81 101 125 137 158 175 71 82 89 100 112 126 135 148 155 73 81 94 104 140 158 176 182
66 73 83 89 98 103 114 136 149 169
Muin
&-A &- d
4-4
310 400 1041 480 500 118 640 131 690 151 310 400 480 500 640 690
3 -320 410 510 590 710 1300 320 410 510 590 710 1300
~
185 255 295 295 395 395 185 255 295 295 395 395 105 150 175 235 235 295 295 355 355 105 150 175 235 235 295 295 355 355 110 145 185 195 235 235 300 300 370 370
Std Std Std Slow Std Slow Std Std Std Slow Std Slow Std Std Slow Std Slow Std Slow Std Slow Std Std Slow Std
Slow
153 153 153 119 153 119 153 153 153 119 153 119 153 153 119 153 119 153 119 153 119 153 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119
64
77 25 31 59 67 73 89 87 97 103 25 30 34 38 46 51 58 63 73 42 47 58 57
67 73 91
61 71 6 1 . 78 68 91 76 106 91 111 97 129 111 140 118 611 69 78 90 106 110 126 132
240 280 290 370 380 480 490 590 620 240 280 290 370 380 480 490 590 620
13E 15E 15E 20E 20E 25E 25E 30E 30E 13E 15E 15E 20E 20E 25E 25E 30E 30E 20E 20E 25E 25E 30E 30E 40E 40E 50E 50E
208 or 240
500
UP thru 4%
66 78 82 93 98 109 115
240 290 300 390 400 520 540 660 850 240 290 300 390 400 520 540 660 850 250 250 320 320 390 410 540 740 780
-
480 or 600
60
- --
68 74 134
60 68 76 83 138
66 74 82 126 135 44
135a 50 59 63 74 79 91 105
120
-250 250 310 310 370 380 510 540 670 760
208 or 240
64
68 79 90 99 106
750
UP thru 5.75%
--
- -
133
480 or 600
- -)
For ,Ita grounded-wye connectel Applicable at 208 v only. Applicable at 480 v only.
91 90 103 97 120 112 127 135 117 132 1421 136 153 the neutra roun
89
61 32 60 68 37 87 42 69 47 76 104 51 105 117 77 110 121 94 124 137 144 163 107 154 174 124 175 196 137 d through an imp
250 250 310 310 370 84 9oa 380 90 2 . 1044 510 107 9 540 0 6 . 123 125 1 670 143 122 138 760 158 133 158 ancl he values I .he d
Slow
Std
a drlt
110 20E 145 20E 25 E 185 25 E 195 235 30E 30E 235 40E 300 40E 300 50E 370 50E 370 column apply
slow
Std Slow Std
Slow
Sid Slow Std
Slow
TABLE CONTINUED-
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout).
__
I -
I _
_-
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems THE FUSE SELECTION TABLES
I)n
-Low.
-ona.
md
CI
,ent-l
nitin(
-uses-Continued
n
psn
vk h
-42 46 50 54 62 75 79 92 105 113 28 32 35 39 68 84 87 102 114 123 41 48 52 60 69 75 83 91 98 110 44 54 58 67 55 59 65 70 78 89 97 109 129 137 51 57 75 82 93 108 116 131 147 157 51 58 64 71 85 91 104 113 126 140 62 66 73 76 85 102 112 127 147 157 65 77 87 90 103 123 130 147 167 174 66 73 83 97 104 119 130 145 161
I I
66 75 84 89 108 113
W l
klgr
I I
I _
Y.i*
45 47 55
50
60 68
74 80 94 98 25 28 31
60
72 84 95 105 125
122 131 - -31 35 38 49 70 81 93 103 121 129 47 55 63 69 83 87 103 108 128 132 230 240 280 290 370 390 480 500 660 700
44 47 54 58 68 78 90
100
-62 65 78 91 03 15 30 36 230 240 280 290 370 390 480 500 660 700
118
240 240 280 290 390 430 520 670 7804 240 240 280 290 390 430 520 670 7804 13004 250 260 320 330 440 460 600 710 800
95 120 170 175 225 225 275 275 355 355 95 120 170 175 225 225 275 275 355 355 120 150 185 185 235 235 290 290 310 310
w
25E 25E 30E 30E 40E 40E 50E 50E 65E 65E 25E 25E 30E 30E 40E 40E 50E 50E 65E 65E 40E 40E 50E 50E 65E 65E 80E 80E lOOE lOOE Std Slow Std Slow Std Slow Std Slow Std Slow
153 119 153 119 153 119 153 119 153 119
TEC No.
153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119
Std
Slow Std
Slow Std
480 or 600
35 41 80 88 95 109 114 39 44 49 52 62 65 76
- -68 76 86 90 101 108 121 131 250 250 310 310 420 420 530 550 690 700
78a 92 03 19 40 44
208 or 240
80
91 UP thru 5.75%
--
95
26 52 57
71 75 85 89 102 106
---
44 51 59 66 78 81 90 96 106 114
--
Std Slow Std. Slow Std Slow Std Slow Std. Slow Std Slow Std Slow
153 119 153 119 153 119 153 119 153 119
~
250 250 120 40E 45 46 61 67 60 61 250 260 150 40E 52 53 62 70 80 60 68 50E 70 310 320 185 61 76 86 66 65 37.8 at 78 68 65 310 50E 78 330 185 86 97 70 75 1800at 63 22.9 kv 75 87 81 93 420 65E 82 95 82 440 235 98 111 480 or 480v or 72 or 600 1440at 76 96 420 65E 460 235 92 105 ?16 86 100 85 81 85 34.8 at 600v 112 530 98 600 290 87 91 101 115 126 103 117 80E 96 24.9 kv 98 110 121 132 108 125 102 117 80E 550 710 290 90 100 102 114 105 118 130 146 126 146 118 136 690 800 310 lOOE 700 310 lOOE 106 119 118 135 139 163 133 153 126 142 0 For delta grounded-wye connected transformers with the neutral grounded through an impedance, the values in the d, a delta column apply. Applicable at 480 v only. Applicahle to transformers through 5.75%impedance. TABLE CONTINUEDA Applicable to transformers through 4%impedance.
- - - -
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout).
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S&C ELECTRIC CANADA LTD . Rexdale
2404 10
Page 61 of 78 August 6,1984
ABLE XII-Transformers
Low-Voltac
w -anp,
_L_
tns
wh
hA
m
w
U
Ralhil p.r
-XUU-LO u .tal
tm
50 4 at 22.9 kv or 46 4 at 24.9 kv
5.75%
,;ru
480or O0
,A: ,:
lg30 at
6oov
42 44 51 54 61 63 76 83 91 1 02 103 113
- 64 72 82
46 51
60
--ndrl
UHI(
&-a
d-4
230 230 300 310 380 400 470 500 710 760 900
86
94 99 110 122 145 169 176
208
65 68 75 79 87 97 116 135 140 165 160
45 49 61 63 74 77 89 94
153 119 153 119 153 119 153 119 153 119 153 119
69 71 84
88
102 107 135 150 154 177
I16
I35 I40
158 - 1120
48 50 59 61 70 75 93 108 111 126 123 138
66 69 81 85 108 120 122 141 137 155
153 119 153 119 153 119 153 119 153 119 153 119
60
68 71 85 97 103 115 115 126
60 65 71
80
94 110 112 133 128 149
35 40 41 I 50 55 94.5 at 60 22 9 kv 3750 or 68 87.0 at 68 24 9 kv 75 75 84 91 102 ; i ) For delta grounded-wye innected transformers wit
I
:,A
3E tA :
-
64
75 BO 100 112 124 135 142 153
186
- -
250 250 300 310 370 400 550 560 700 720 800 880
~
Slow
Std
Slow
Std
Slow
Slow
119 153 119 153 119 153 119 153 119 153 119 153 119
38 41 46 61 54 6 4 6 3 72 69 65 74 76 77 88 76 75 85 84 88 99 84 82 93 94 98 111 102 102 113 115 118 129 the neutral groun
210 80E 42 40 48 250 46 61 100E 49 51 60 260 100E 52 49 63 54 71 360 61 125E 67 66 76 77 71 360 125E 79 74 84 77 89 74 l5OE 430 81 82 95 82 93 440 93 150E 90 104 83 95 110 500 91 82 175E 95 108 93 106 510 92 103 175E 108 124 102 117 88 200E 580 99 103 119 105 121 610 200E 123 142 117 135 103 116 750 250E 132 151 131 149 109 125 250E 840 157 181 149 171 128 147 d through an impedance. the values in the delta delta column apply
Slow
Std Slow Std Slow Std
Slow
Std Slow
- - -
Note: Refer to How to Use the Fuse Selection Tables o n page 76 (foldout).
~ -_-
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems THE FUSE SELECTION TABLES
Low-Volta! Secondary Current-Limiting Fuses
c
@for
E !
d
I .
Ydh
1 1 1
m .
mwm
-TCC
99 126 152 177 310 440 580 720 780 310 480
--- Na
208 or 240
UP thru 4%
5 2 at 33 0 kv or 5 0 at 34 5 kv
640
870
5.2 at 33.0 kv or 5.0 at 34.5 kv 360 at 480v or 290 at 600v 35 48 59 72 87 30 61 76 81 91 99 113 118
I__
72 88 107 125 80 94 111 125 138 150 165 172 70 84 105 128 165 176 197 206 62 73 82 92 1W 110 114 128 137 51 310 440 580 720 780 260 340 390 400 530 540 700 71 0 260 340 390 400 530 540 700 710 230
260
480 or
600
68 85 102
195 285 370 425 425 140 220 255 255 340 340 425 425 140 220 255 255 340 340 425 425 90 140 170 225 225 285 285 340 340 90 140 170 225 225 285 285 340 340
7E 1O E 13E 15E 15E 1O E 13E 15E 15E 20E 20E 25E 25E
Std. Std. Std. Std. Slow Std Std. Std. Slow Std. slow Std Std. Std. Std. Slow Std Slow Sld. Slow
153 153 153 153 119 153 153 153 119 153 119 153 119 153 153 153 119 153 119 153 119
8 7 at 3 3 0 kv or 8 4 at 3 4 5 kv 1390 at 208v or 1200 at 24Ov 71 88 91 102 110 126 130 70 84 97 107 119 132 143 73 a4 99 111 122 136 151 157
64
79 91 97 115 134 140 37 46 56 65 71 86 131 136 42 52 60 65 76 89 93 109 117 30 36 42 47 55 87
208 or 240
500
UP thru 4%
-480 or 600 8 7 at 33 0 kv or
600 at 480v or 480 at 600v
84at
34 5 kv
40 48 53 60 65 75 78 86 91
28 35 43 52 57 70 78 137
61 67 128 141 t 53
_ I
260 340 420 450 570 700 850 260 340 420 450 570 700 850 230 260 280 360 370 480 490 600 720
60 69 76
1494 1544
--13E 15E 15E 20E 20E 25E 25E 30E 30E Std. Std. Slow Std. Slow 153 153 119 153 119 153 119 153 119
208 or 240
or
126at 34 5 kv
7 50
UP thru 5.75%
60 68 73 84 87 96 101
64
71 79 88 95 103 115
56 65 73 81
90
101 105 113 119 49 61 67 81
88
103 108 126 135
69 77 84 98
101
480 or 600
13 1 at 3 3 0 kv
or
12.6 at 34 5 k v
23 28 33 38 46 52 91 99 107
106
118 128
270 350 360 440 450 550 560 230 260 270 350 360 440 450 550 560
Sld.
Slow Std Slow Std.
153 153 119 153 119 153 119 153 119
68
81 110 117 131 137 153 164
0 For *Itagrounded-wye connecte ransformers wit Applicable at 208 v only. Applicable at 480 v only.
90
105 113
slow
Std.
- -
column apply.
TABLE C O N T I N U E D
DATA BULLETIN
S&C ELECTRIC COMPANY C h i c a g o
S&C ELECTRIC C A N A D A LTD Rexdale
2404 10
Page 63 of 78 August 6,1984
n6r
'*I
fknCrXeml
le
__.
mmw.
Me
208 or 240 17 5 at 33 0 kv or
167at
62
58
65 68 79 91 103 114
28 34 38 68 74 80 94 108 118 128 38 43 45 53 60 69 75
64
72 76 90 104 117 126 63 69 76 87 90 105 121 134 143
34 5 kv
1000
65 70 78
86 98 120 127 145
wd*
Dprm
2 :
153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119
81 87 98 102 115 123 140 167 176 190 62 67 81 98 106 121 141 151
136
50 56 64 66 77 82 98 115 I25
260 260 330 330 400 400 540 570 710 850 260 260 330 330 400 400 540 570 710 850 220 260 270 350 350 450 460
135 165 210 210 255 255 325 325 400 400 135 165 210 210 255 255 325 325 400 400 110 160 170 215 215 265 265 340 340
20E 20E 25E 25E 30E 30E 40E 40E 50E 50E 20E 20E 25E 25E 30E 30E 40E 40E 50E 50E 25E 30E 30E 40E 40E 50E 50E 65E 65 E
Slow Std
Slow Std
slow
Std
480 or
600
84
94 116 124 139 41 45 49 57 71 75 85 95 103
7 4 . 6 . 671 7 784 90 96 84 98 116 119 135 I34 151 '44 162 43 50 54 65 77 83 90 I03
stow Std
Slow Std
208 or 240
26 2 at 33 0 kv or 25 1 at 34.5 kv
1500
UP thru 5.75%
-26.2 at 33 0 kv or 25.1 at 34 5 kv
86 90
60 69 78 84 97 100
480 or 600
25E 110 67 45 61 46 30E 514 160 75 47 67 50 30E 554 170 80 52 63 71 55 1800 at 40E 65 215 71 83 93 62 62 69 480v or 380 40E 79 215 77 72 80 87 99 111 1440 at 450 100 50E 89 265 82 79 89 93 106 117 600v 460 50E 550 108 96 265 92 103 116 126 65 95 114 132 65E 690 340 98 108 102 115 128 141 135 820 65E 118 340 151 101 113 111 126 133 ransformers with the neutral grounded thrvugh a n impedance. the values 1n the "delta delta" column apply
65 80 85 96 110 117
62 75 85 92 101
o 9 l
Note: Refer to "How to Use the Fuse Selection Tables" on page 76 (foldout).
__ - -----
_ _
p _ I I _ _
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems
THE FUSE SELECTION
TABLES^
4BLE XIII-Transformers
*
: u n a
1 6
_c
u n l l Fwe
-Low-Voltat P WL Wc
Wl
Second;
Current-Limitinq Fuses-Continued
BC wwr Lordin#
pndrr EEE!E
r k
Awn m w .
wi
laC
@ I
---Wde
I _ _ I
udn
-- -zfzz
u
milt
tar
hdes
mM
%cuIIHI
u(* a6
whn&wnn
35 0 at 33 0 kv
or
33 5 at 34 5 kv
---UP thru 5.75% 43 7 at 33 0 kv or 41 8 a t 34 5 k v 3010 at 480v or 2410 at 600v 42 46 50 58 60 69 72 83 86 106 39 40 45 47 55 57 70 78 83 92 92 65 67 78 46 48 54 61 66 74 82 89 100 116 136 61 68 75 84 94 103 113 132
39 45 53 59 63 73 76 86 90 104 108
M(tn
'ar6
L
- 136
61 67 82 86 103 108 125 131 167 187 47 52 57 68 70 84 88 102 108 126 144
41' 48 68 58 77 66 85 72 104 86 109 88 129 105 135 110 157 128 164
-- -200 260 260 330 330 440 440 560 580 740 750 200 260 270 340 340 470 500 650 820 860 110 145 160 200 200 255 255 310 310 335 335 30E 40E 40E 50E 50E 65E 65E 80E 80E 1DOE
Slow Std Slow Std
n d $ 7
Nl-LWd Gunrnt
w=w
!mpm
R*sng,
la&
TM:
no.
119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119
Slow
Std Slow Sld Slow Std
- -63 78 83 97 104 113 120 141 210 260 260 340 340 420 440 540 570 800 950 210 260 270 350 360 470 490 610 770 920
E Slow
40E 50E 50E 65E 65E 80E 8M lOOE lOOE 125E 125E Std Slow Std Slow Std Slow Std
Slow
66
69 74 84 90 104 113 126 139 166 195
2500
480 or 600
80
95 99 119 t32
- - 154
63 66 79 87 93 103 104 114 40 44 48 54 59 67 77 90 91 108 103 118 61 68 75
- 68 74 83 92 110 130 135 158 154 179 47 50 59 62 72 76 97 107 120 131 133
- 162
45 46 55 58 68 72 84 96 98 113 111 127
230 230 280 280 350 360 500 51 0 640 660 720 780
130 140 160 205 205 250 250 270 270 310 310 105 135 165 165 180 180 205 205 240 240 270 270
Slow 119
- Slow
65E 65E 80E 80E 1O O E 1O O E 125E 125E 150E 150E 175E 175E
~
3750
UP thru 5.75%
480 or
600
65 6at 33 0 kv or 62 8 at 34 5 kv
a6
102 103 119 115
101
129
For I ta grou led-wye connected transformers with the neutral grounded through a n impedance. the values in the "di Applicable a t 4H0 v only.
- - 147 - -
Std Slow
Std
145 - I
830
delt
column apply.
Note: Refer to "How to Use the Fuse Selection Tables" on page 76 (foldout).
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S&C ELECTRIC CANAOA LTO . Rexdale
2404 10
Page 65 of 78 August 6,1984
_ I _
Tnnl
p n u d
PHC
B1Qo.
we.
V u n
&t-
T m
*Ulldnr
; m
rulwovl h t m
WMrl
bans
hlniomm n*hp,
urgnn
-Sp.M
I I
5R 3R 2 10
M e n nd.n
*o* tlm
&-A
TCC
4 4 4
6R 6R 72 2
at
1 2 0 kv 2400 of 4160
or
69 5
at
1247
kv
-96 2
at
0 07 0 07 0 24 0 17 0 44 0 23 0 59 0 31 0 84 -
0 07 006 0 08 0 07
0 26 0 17 0 46 0 24 0.63 0 33 0 89 -
6R 6R
9R 9R 12R 12R 12R 12R 12R 18R 6R
6R
0 23 0 16 0 42 0 22 0 57 0 29 0 80 -
3R 3R 5R 5R 6R 6R 6R 6R
6R 6R
9R 9R 3R 5R 5R
-6R
9R
006 0 07 0 06
0 04 0 18 0 08 0 26
lnst lnst
6R
2400 of 4160
1 2 0 kv
or
92 6
at
12 47
kv
011 0 37 0 27
0 74 lnst lnsi
0 19 0 08 0 27 0 12 0 40 0 29 0 78 -
0 17 0 07 0 25 0 10 0 36 0 26 0 70 lnst lnst
6R 6R 6R 6R
6R 9R
9R 12R 12R 5R 6R 6R 6R 6R 6R 6R
18R
18R 18R 6R 9R 9R 12R 12R 12R 12R 12R 18R 1 8R 18R 24R 30R 12R 12R 12R 18R 18R 18R 24R 30R 3oR 36R 36R
36R 36R
_ I
--
120.3
at
12.0kr
2500
5.5%
2400 01 4160
or
0 06
lnst lnst
115.7
at
0 12 0 12 0 1 1
9R
9R 12R 12R 12R 12R 6R 6R 9R 9R 12R 12R 12R 12R 18R 18R
18R
12.47
kv
-- 180.4
at
lnst
0.19 0 12 0 40 0 30 0 87
0 . 2 0 0 13 0 42 0 32 0 92 Ins1
0 18
lnst
0.12 0 38 0 29 0 83
Ins1 Ins1
0 10
0.06
173.6
at
12.47
kv
ference t ween For relays not carefully calibrated at maximum three-phase secor time-tolerance value and the assumed tolerance value (0.07 second) tr 0 For delta grounded-wye connected transformers with the neutral grounded through an Impedance, the values in the delta delta column apply
Q
---
0 07 0 29 0 16 0 52 0 26 0 79 0 54
0 07 0 31 0 17 0 55 0 28 0 83 0.57
0 28 0.16 0 49 0 25 0 75 0.52
---
24R 24R
680 750 870 190 230 240 320 330 400 4 10 460 470 540 550 690 740 190 260 260 310 320 360 370 420 440 540 580 640 760 240 250 270 280 340 350 400 440 560 690 750 850 910
190 240 240 340 350 430 450 500 530 580 700 780
210 260 270 330 340 470 530 610 700 800 860
590
640 740 240 250 280 290 360 370 420 520 610 850 960
-
125 135 150 160 160 190 190 2 15 215 245 245 275 275 105 115 120 140 140 160 160 185 185 205 205 260 260 95 110 110 130 130 150 150 165 165 205 205 245 245 100 100 110 110 135 135 165 165 220 220 245 245 295
-65E 119
Slow
no.
80E Std 80E Slow 1 ODE Std 1 OOE Slow 125E Std 125E Slow 150E Std 150E Slow 175E Std 175E Slow 200E Std 200E Slow 80e Slow 1 ODE Std 1 OOE Slow 125E Std 125E Slow 150E Std 150E Slow 175E Std 175E Slow 200E Std 200E Slow 250E Std 250E Slow 1 OOE Slow 125E Std 125E Slow 150E Std 150E Slow 175E Std 175E Slow 200E Std 200E Slow 250E Std 250E Slow 300E Std 300E Slow 175E Std 175E Slow 200E Std 200E Slow 250E Std 250E Slow 300E Std 300E Slow 400E Std 400E Slow -250E Std !-250E Slow
153 119 153 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119 153 119 153 119 119 153
119
153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 -
!-3M)E
Std -
relav
T A B L E CONTINUED
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout).
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems THE FUSE SELECTION TABLES
f
I +
240 6 at 12 0 ki 2400 or or 4160 231 5 at 1247 kv lnst lnst 0 10 1200 at lnst !400v or 0 26 690 at 0 12 4160v 0 42 0 27 0.77 0.52 1.51 lnst 0 08 1800 at lnst 2400~ or 0 18 1040 at 0.12 4160v 0 42 0 29 0 84 Inst. Inst. 0.09 Inst. 0.22 0.11 0.36 0.23 0.66 0.45 1.30 Inst. 0.07 Inst. 0.16 0.10 0.37 0.25 0.72 lnst Inst 0 09 Inst lnst 0 25 0 22 0 12 0 10 0 39 0 35 0 25 0 22 0 73 0.65 0 49 0.44 1 4 3 1.28 lnst lnst lnst 0 07 lnst lnst 0 1 7 0 16 0 11 0 10 0 40 0 36 0 27 0 24 0 79 0 71 Inst lnst 0.10
540
-- -
-- -
100 100 125 125 165 165 185 185 220 220 295 295 110 110 125 125 150 150 200 200
300E
400E 400E 2-250E 2-250E 2-300E 2-300E 2-400E 2-WE 400E 400E 2-250E 2-250E 2-300E 2-300E 2-400E 2-400E
Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std.
Slow
Std. Slow Std.
Slow
Std. Slow Std. Slow
153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119
481.1 at Inst. Inst. Inst. Inst. 270 12.0 kb 2410 at Inst. 320 Inst. Inst. Inst. 2400 or or !400v or 0000 6 5% 0.15 0.13 0 16 0 13 340 4160 463.0 1390 at 0.09 Inst. 0 08 440 at 41 60v 0 10 0.33 0.36 0 32 540 0 38 12.47 kv o l i o r i e ~ a y sno carefully calihra d at ma mum three-Dhase secondarv fault current, add or subtract (as amlical ) the Terence between the actual relav time-tolerancevalue and the assumed tolerance value (0.67 second) to the-nominal relay operating timehefor,rrc&paring with entriesin the table. See text, page:l4 0 For delta grounded-wye connected transformers with the neutral grounded thruugh an impedance. the values in the delta delta cnlumn apply.
--
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout)
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S&C ELECTRIC CANADA LTO . Rexdale
240-110
Page 67 of 78 August 6,1984
LOuUng
CWMb
IW.
-- - - mi,
hY.
Trwrdormw
-w
rranrranur
PIiaCW
FUlUOld
Psnarrt al
ar
L I
or
VIrl
IW.
~orl
Inst. Inst. Inst. Inst. 0.11 0.12 0.11 0.12 0.31 0.34 0.22 0.24 0.55 0.60 0.30 0.33 0.73 0.79
Inst. Inst. 0 11 011 0 30 0.21 0 53 0.29 0 71
1Iw.
--M I
b c , I*%
2100 voll
yon
Sa-
SW.
Milan
n d h A+ d--4 @
r
&%I50E 65E 65E 80E 80E l00E lOOE 125E 125E 150E 150E 175E 175E 80E lOOE lOOE 125E 125E 150E 150E 175E 175E 200E 200E 250E 250E lOOE 125E 125E 150E 150E 175E 175E 200E 200E 250E 250E 300E 300E
Slow Std Slow Std
Dutrou4
;:5
t
87.5 at 13frkv 2000 5.5% 2400 or 4160 at 13.8 kv 480at 2400v o
-- - - 6R 6R
6R
- -lnst lnst 011 lnst 0 18 0 07 0 29 0 20 0 58 0 43 120 lnst Inst. 011 lnst 0 17 0.07 0 27 0 18 0 53 0 40 112 lnst lnst 0 11 lnst 0 18 lnst 0 28 0 20 0 56 0 42 118
-- - Inst. lnst 0 10 lnst 0 16 0.06 0.25 0.17 0 50 0 37 103 lnst lnst 0 11 lnst 0 17 lnst 0 27 0 19 0 54 0 41 114 lnst lnst 0 10 tnst 0 15 lnst 0 24 0 17 0 49 0 36 101 6R 12R 12R 12R 12R 12R 12R 18R 18R 24R 24R 30R 30R
_ I
lnst 0 07 0 25 0 22 0 11 0 10 0 33 0 29 0 16 0 14 0 48 0 43 0 37 0 33 0 95 0 84
12R 12R 12R 12R 12R 12R 18R 18R 24R 24R
210 220 230 270 280 350 360 490 520 620 650 720 780 210 260 260 360 370 450 450 510 520 590 620 770 910 210 290 290 350 350 410 410 470 480 600 630 720 930
210 230 230 280 290 360 380 520 620 670 800
95 105 135 165 165 180 180 205 205 240 240 270 270 125 135 135 155 155 180 180 205 205 225 225 285 285 105 125 125 140 140 165 165 180 180 225 225 270 270
650
900 920
-
600 at 2400v o
i : : : ;
230 230 6R 150E Std 95 153 230 240 95 150E Slow lnst lnst lnst Inst. Inst. lnst lnst lnst 6R 119 - - 270 270 9R 110 175E Std 153 270 280 9R 175E Slow 119 110 lnst lnst lnst Inst. Inst. lnst Inst lnst 164.0 120 310 320 9R 200E Std 153 310 320 9R 120 200E Slow 119 at 900 at Inst 0 03 lnst Inst. Inst. lnst lnst lnst 380 400 12R 150 250E Std 153 2400 or 'fr kv 2400v o lnst lnst lnst lnst. Inst. lnst lnst lnst 3750 5.5% 150 390 420 12R 250E Slow 119 41 60 0 17 0 15 0 16 0.15 0.16 0.14 0 16 0 14 156.9 460 480 12R 180 300E 0 12 0 11 0 11 0.10 0.11 0 10 0 11 0 11 Std 153 at 180 500 620 18R 300E Slow 119 0 41 0 38 0 41 0.37 0.40 0 36 0 39 0 35 13.8 kv 240 640 700 18R 400E Std 153 0 25 0 23 0 24 0.22 0 24 0 21 0 23 0 21 240 780 24R 119 400E Slow 0 72 0 67 0 70 0.63 0.69 0 62 0 68 0 60 270 24R 850 -250E Std 153 0 39 0 37 0 39 0.35 0.38 0 34 0 37 0 33 270 24R 1020 -250E Slow 119 1 0 7 0 99 1 05 0.95 1.03 0 92 1 0 1 0 90 I 4 veen the actual relav For a v s na :arefullv calibrated at ma mun hree-Dhase secondarv fault current. d or subtr; (as applicable) the ( Ference b time-tolerance value anb the assumed tolerance v l e (0.67 second) to thenominal relay operating time forecomparing with entriesin the table. See text, page34. 0 For delta grounded-wye connected transformers with the neutral grounded through an impedance, the values in the "delta delta" column apply
- --
Inst. Inst. 0.10 Inst. 0.16 0.06 0.25 0.18 0.51 0.38 1.06
Slow Std Slow Std Slow Std Slow Std Slow Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Slow Std
119 153 119 153 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119 153 119 153 119
Slow
Std Slow Std Slow Std Slow Std Slow Std Slow
560
660 880 960
-
-- ~
;:;4 :"
- -
- --
--
12R 12R 12R 12R 18R 18R 24R 24R 30R 30R 36R 36R 36R
TABLE
coNriNum
Note: Refer to "How to Use the Fuse Selection Tables" on page 76 (foldout).
-~-.-"
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems
TABLES^
Inc.
or VerY tw.
I I
--Inst.
lnst
Inst. lnst
230 280 290 350 350 470 520 610 620 750 930 230 230 310 320 380 390 470 500 640 790 240 290 290 350 350 460 540
230 290 300 350 390 500 630 680 900 940
110 135 135 180 180 205 2 05 245 245 90 90 120 120 135 135 165 165 215 215 90 100 100 120 120 165 165
0 03
7500
6.5%
3p18
437.4
-0000
lnst
0 13 Inst. 0.25 0.17 0 53 0 33 0 99
lnst
0.24 0.16 0 51 0 32 0 95
lnst
lnst
0 06 lnst 0 07 0 07 lnst lnst 0 03 lnst 0 21 0 23 0 20 0 22 0 13 0 14 0 14 0 15 13.8 k v 0.44 0 48 0.51 0 47 0 50 0 For relays not carefully calibrated at maximum three-phase secondary fault current, add or subtract (as applicable) the difference between the actual relay time-tolerance value and the assumed tolerance value (0.07 second) to the nominal relay operating time before comparing with entries in the table. See text, page 34. 0 For delta grounded-wye connected transformers with the neutral grounded through an impedance, the values in the delta delta column apply.
6.5% 2400 or 1 3 : r k v 2400v or 418.4
l j : : o : t
y:,
--IflSt lnst - - -
300E
Slow Std. Slow Std. Slow Std Slow Std. Slow Std.
I 153
0.23
--
---
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout).
DATA BULLETIN
S&C ELECTRIC COMPANY * Chicago S&C ELECTRIC C A N A D A LTD Rexdale
2404 10
Page 69 of 78 August 6,1984
ABLE XVI-Transformers
o n t r o l Equipr m t
TIM
p*n
'tamel
Tml
-*Lo
! E % !
PlOB
-mM
0Rert-J
! v i 2
A-lc
TCC
*rusrV
I I
2400 01 41 60
0.07
lnst
lnst
0 15 0 11 0 33 0.27 0.66
0.69
Inst. Inst. 0.14 0.1 1 0.33 0.30 0.71 0.53 1.24 _ . Inst. Inst. 0.12 0.10 0.30 0.26 0.63 0.47 1.11 Inst. Inst. 0.13 0.11 0.32 0.29 0.69 0.51 1.22
lnst Inst. 0 12 0 10 0 29 0 26 0 62 0 46 1 08
5R 5R 6R 6R 6R 9R 9R 12R 12R 12R 12R 6R 6R 9R 9R 12R 12R 12R 12R 18R 18R 24R 24R
200 250 250 310 310 420 420 530 550 690 700
No.
Slow
230 230 300 310 380 400 470 500 710 760 900 120
2400 01 4160
190 6R 5R 250 9R 5R 250 120 65E 250 9R 5R 250 140 65E 12R 6R 310 175 80E 300 63.0 6R 330 175 80E 310 Inst. 12R 0.03 Inst. lnst at 370 6R 185 lOOE 400 lnst 12R 0.03 Inst. Inst. 2400 01 22.9 k\ 400 6R 420 185 1OOE or 0 14 12R 0.16 0.t7 0 15 4160 58.0 550 600 215 125E 0 14 18R 12R 0.16 0.17 0 15 at 730 215 125E 0 37 18R 12R 560 0.41 0.43 0 39 24.9 k\ 250 150E 700 0 26 24R 12R 760 0.29 0.31 0 28 250 150E 720 0 63 24R 12R 0.70 0.74 0.67 800 285 175E 950 0.36 30R 12R 0.39 0.41 0.37 285 175E 880 0.85 30R 12R 0.94 0.99 0.89 210 12R 6R 210 110 80E 250 12R 6R 250 120 lOOE 6R 260 125 lOOE lnst 12R 260 Inst. Inst. lnst 370 145 125E Inst. 18R 12R 360 Inst. Inst. Inst. 94.5 380 145 125E 0 08 18R 12R 360 0.09 0.09 0.08 at 460 165 150E 430 Inst. 24R 12R 0.07 0.07 0.06 2400 01 22.9 k\ 440 165 150E 500 0 21 24R 12R or 0.23 0.25 0 22 41 60 87.0 510 190 175E 540 0 10 30R 12R 0.11 0.11 0 10 at 510 190 175E 620 0 30 30R 12R 0.33 0 34 0 31 24.9 k\ 210 200E 0 13 580 630 30R 18R 0.15 0.16 0.14 210 200E 61 0 860 0 40 30R 18R 0.44 0.47 0.42 870 260 250E 0 32 36R 24R 750 0.35 0.37 0 33 840 260 250E 0.78 36R 24R 0.86 0.91 0 82 d or subtract (as applical ) the difference between For relays not carefully calibra 1 at maximum .hreenhase seconi v v fault current. I time-tolerance value and the ass1 led tolerance v ue(0.67 second) to thenominal relay operating time before comparing with entries in the table. $ 0 For delta grounded-wye connected transformers with the neutral grounded through an impedance, the values in the "delta delta" column apply
--
---
95 135 175 175 215 215 230 230 270 270 310
50E 50E 65E 65E 80E 80E lOOE lOOE 125E 125E 150E
Slow
Std. Slow Std. Slow Std.
Slow -
119 153 119 153 Slow 119 153 Std. Slow 119 153 Std. Slow 119 153 Std. Slow 119 153 Std. 119 Slow 119 Std. 153 Slow 119 153 Std. Slow 119 153 Std. Slow 119 153 Std Slow 119 153 Std. Slow 119 153 Sld. 119 Slow actual relay text, page34. Std. Slow Std.
Slow
119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119
slow -
TABLE CONTINUED
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems THE FUSE SELECTION TABLES
rcc:
5000
5 0 0 ,
126.1 at 22.9 kv 1200 at 2400 or 2400~ of 4160 9 .;1 ; 690 at 4160v at 24.9 kv
lnst lnst
lnst
0.06
lnst 0 12 Inst 0 21 0.15 0.46 0.34 0 92 lnst
-
inst. 0 06
Inst. 0 11 lnst 0 18 0.13 0.41 0.30 0 82 L lnst
-
Inst.
0.12 Inst. 0.20 0.14 0.44 0.32 0.87
-
6R 12R 12R 12R 12R 12R 12R 18R 18R 24R 24R
540
560 660 800
240 280 280
590
740 750
-
I
7500
1189.1 at 1800 at 2400or 22.9 2400v 0 1 4160 1 f i . 9 1040 at 4160v at 24.9 kb 252.1 lnst lnst 0.22 0 17 0 51
Inst.
30R
12R 18R 18R 24R 24R 30R
90 105 105 125 125 140 140 155 155 195 195 235 235 95 105 105 130 130 155 155
1O O E 125E 125E 150E 150E 175E 175E 200E 200E 250E 250E WOE 300E
-Slow Std Slow Std. Slow Std. Slow Std Slow Std. Slow Std. Slow Slow Std Slow Std. Slow Std Slow
119 153 119 153 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119 153 119
n o .
6,5c
0 05 Ins:. 0 19 0 15 0 45
350
350 420 440 260 260 310 310
30R
24R 24R
250 280 280 370 370 450 520 260 270 320 340
0000
95 95
115 115
3oR
30R
For relays not carefully calibra d at ma imum three-phase secondary fault current. Id or subtri (as aDD1iCable) the difference b ween t e actu; relav time-tolerance value and the assumed tolerance value (0.07 second) to the nominal relay operating time fore comparing with entriesin the table. See text, page 3 i . 0 For delta grounded-wye connected transformers with the neutral grounded through an impedance, the values in the delta delta column apply
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout)
DATA BULLETIN
S&C ELECTRIC COMPANY C h i c a g o S & C ELECTRIC C A N A D A LTD R e x d a l e
2404 10
Page 71 of 78 August 6,1984
R a t e d 33 0 K v or 34.5 K v Three-Phase-with
F
ol
or Class E-2
Industrial
-lllwt
ti
lrm.
Qf
* lFIRl
.st,
0
SI68
Mclar, tol m r
%#Et&
-W%
-mY
wndiw
wrrss)
I k u m n l Of
tllthwnrr
FU&Ldad
rcc
25E 25E 30E 30E 40E 40E 50E 50E 65E 65E 30E 40E 40E 50E 50E 65E 65E 80E 80E lOOE lOOE 40E 5OE 50E 65E 65E 80E 80E lOOE lOOE 125E 125E 50E 65E 65E 8OE 80E lOOE lOOE 125E 125E 150E 150E 175E 175E Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow
2
1 1 1
*
sew 5R 5R 6R 6R 6R 6R 9R 12R 12R 12R 3R 3R 3R 3R 5R 5R 6R 6R 6R 6R 220 220 260 270
wn
4 1 1
0
220 220 260 270 360 380 480 550 690 820 200 260 270 340 340 470 500 650 820 860
-
cum
105 125 160 170 215 215 265 265 340 340 110 145 160 200 200 255 255 310 310 335 335 130 140 160 205 205 250 250 270 270 310 310 95 105 135 165 165 180 180 205 205 240 240 270 270
153 119 153 119 153 119 153 119 153 119
tlo.
5.5%
2400 Of 4160
26 2 at 3 3 0 kb or 25 1 at 34 5 kb
-lnst
-
0.55
Inst
-
tnst 0 34 0 07 0 34 0 27
- - 049 lnst
-
Inst. 0 12 0 07 0 31 0 24 050
Inst 0 12 0 06 0 30 0 23
350
350 450 460 600 620 200 260 260 330 330 440 440 560 580 740 750 210 260 260 340 340 420 440 540 570 800 950
6R 6R
Inst.
-
--
119 153 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119 153 119 119 153 119 153 119 153 119 153 119 153 119 153 119 -
lnst
-
lnst
-
lnst
-
lnst
-
or
33 5 at 345 kr
0 09
008 0 21 0 17 0 43 0 35
43.7 at 33.0 k i
or
41.8 at 34.5 k i
- -65.6 at 33.0 kb
_ .
Inst.
lnst 0 09 0.08 0.25 0.21 0 49 0 48 106
--- --
9R
12R 12R 18R 18R 18R 18R 30R 30R 9R 12R 12R 18R 18R 18R 18R 30R 30R 36R 36R 36R 36R
210 260 270 350 360 470 490 810 770 920 180 230 230 280 300 360 380 540 630 890
-
- --
or
62.8 at 34.5 k b
--
lnst lnst 0 14 0 13 0 36 0 26 0 63 0 35 0 86
lnst lnst lnst lnst lnst lnst 0 14 0 13 0 14 0 14 0.13 0.14 0 38 0.34 0.38 0 28 0 25 0.27 0 66 0 60 0 65 0 37 0 33 0 36 E 0 82 0 90
- - 080 -
lnst lnst 0 13 0 12 0 33 0 24 0 58 0 32
640
830
-
Slow Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow Std. Slow
For relays not carefully calibrated at maximum three-phase secondary fault current, add or subtract (as applicable) the difference between the actual relay time-tolerancevalue and the assumed tolerance value (0.07second) to the nominal relay operating time before comparing with entries in the table. See text, page 34. 0 For delta grounded-wye connected transformers with the neutral grounded through an impedance, the values in the delta delta column apply.
T A B L E CONTlNUED
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout).
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems
In0
TCC
18R 18R lnst Inst. Inst. lnst lnst lnst lnst Inst. 18R Inst. Inst. Inst. lnst lnst. Inst. lnst Inst. 30R 87 5 0 15 0.14 0.15 0 14 0 15 0 13 0 15 0.13 30R at 33 0 kv 1200 at 0.11 0.10 0.11 0 t o 0 11 0 09 0.10 0.09 36R 400v or 0 34 0.31 0.33 0 30 0 33 0 29 0 32 0.28 36R or 5000 5.5% 83 7 690 at 0 16 0.15 0.16 0 15 0 16 0 14 0 16 0.14 36R at 4160v 0 46 0.43 0.46 0 41 0 45 0 40 0 44 0 3 9 36R 34 5 kv 0 22 0.21 0.22 0 20 0.22 0 19 0.21 0.19 36R 0 62 0.58 0.61 0 55 0.60 0.54 0.59 0.53 36R 0.47 0.44 0.46 0 42 0.45 0 40 0.44 0.40 36R 1 2 1 1.12 1.19 1 0 7 1 1 7 1 04 1 1 4 1.02 36R 30R lnst 0.03 Inst. lnst lnst lnst lnst Inst. 30R Inst. Inst. lnst. lnst lnst lnst lnst Inst. 36R 131.2 0 11 0.11 0.11 0 10 0 11 0 10 0.1 1 0.10 36R at Inst. 0.04 Inst. Inst. lnst lnst lnst Inst. 36R 33.0 kv 1800 at 0 19 0.18 0.19 0 17 0 19 0 17 0 18 0 1 6 36R 2400 or or 400v or 0 08 0.08 0.08 0 07 0 08 0 08 lnst 0 0 7 36R 7500 6.5% 4160 125.5 1040 at 0 30 0.28 0.29 0 27 0 29 0 26 0 28 0.25 36R at 4160v 0.26 0.25 0.26 0.23 0 26 0 23 0.25 0.22 36R 34.5 kv 0.64 0.59 0.63 0.56 0 62 0.55 0 60 0.54 36R 0.47 0.43 0.46 0 41 0 45 0.40 0 44 0.39 36R 1 2 5 1.16 1.22 1 1 1 1 2 1 1.07 1 1 8 1.05 36R 36R 175.0 lnst 0.03 lnst lnst lnst lnst lnst Inst. 36R at 2410 at Inst Inst. Inst. Inst. Inst. Inst. lnst inst. 36R 2400 or 33.0 k\i 400v 0 1 0.1 0 0.09 0.10 0.09 0 10 0.09 0 09 0.08 36R 0000 6.5% or lnst Inst. 36R 4160 167.3 1390 at 0.07 0.07 0.07 0.08 lnst 0.06 41 60v 0 28 0.26 0 28 0 25 0 28 0 25 0 27 0.24 36R at 0 22 0.21 0.22 0 20 0 22 0 19 0 21 0.19 36R 34.5 kr 0 67 0.62 0.66 0 59 0 65 0 57 0 63 0.56 36R 0 For relays not carefully calibrated at maximum three-phase secon Iry fault current, add or suhtr; time-tolerance value and the assumed tolerance value (0.07 second) to l e nominal relay operating time 0 For delta grounded-wye connected transformers with the neutral grounded through an impedance, the
9R 12R 12R 18R 18R 18R 18R 24R 24R 24R 30R 30R
21 0 260 260 360 370 450 460 520 530 61 0 630 800 900
--
36R - 240 240 290 300 340 350 390 390 500 500 610 680 240 250 300 310 350 360 41 0 420 530 610 680
-
220 260 280 390 390 500 530 570 680 680 980 970
125 135 135 155 155 180 180 205 205 225 225 285 285
125E 125E 150E 150E 175E 175E 200E 200E 250E 250E 300E 300E
80E 1O O E 1O O E 125E 125E 150E 150E 175E 175E 2cQE 200E 250E 250E
-Slow Std Slow Std Slow Std Slow Std Slow Std. Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow Std Slow 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 153 119 -
No.
-- --
----
18R 18R 18R 18R 24R 24R 24R 30R 30R 36R 36R 36R
- -
100 100 120 120 135 135 150 150 190 190 225 225
----
175E 100 250 Std 153 260 24R 175E Slow 119 100 260 260 24R .110 200E 290 Std 153 300 24R 200E Slow 119 110 290 300 30R 250E 140 153 380 30R Std 360 370 250E 140 390 36R Slow 119 300E 170 153 440 460 36R Std 300E Slow 170 119 460 550 36R (as amlica ference ween e actu relay .) the ,fowcdmparing with entriesin the table. : B text, page 34. values in the delta delta column apply
- - -
Note: Refer to How to Use the Fuse Selection Tables on page 76 (foldout).
DATA BULLETIN
S&C ELECTRIC COMPANY. Chicago S & C ELECTRIC CANADA LTO Rexdale
2404 10
Page 73 of 78 August 6,1984
Types SM, SML, and SMD-20 Indoor and Outdoor Distribution (4.16 kv through 34.5 kv)
ABLE XVIII-Primary
4.16*
7.2A
I I
2.4/4.16\1
2.4
2.4
I
17 200 27 500 200E 17 200 27 500
2.4/4.16\1
25000 40000 400E 34 600 55 OO( 25000 40000 400E 34 600 55 OO( 25000 40000 400E 34 000 54 OO( 25000 40000 400E 34 000 54 OO(
20 000 32 000 20 000 32 000 20000 32 000 20 000 32 000
20000 32 000
14.4@
25
200E
I
34.5t
20/34.5\1
34.5
200E
I
~
9 400 15 OOC 200E 12 500 9 400 15 OOC 200E 12 500 12 500 20 OOC
20000 32000
200E
200E 200E
8 450 8 450
8 450 8 450
200E
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems
Power h e Type
SM-4 SM-5 SMD-20 SM-4Z and SML4Z SM-5S a n d SM-5SS SM-20 and SMLBO
Deecriptivo BolletinNo.
242-30 242-32 252-30
A SML-47, Power Fuses are not available at 7.2 kv. Interrupting ratings shown for SM-4Z and SM-5SPower Fuses are applicable to 7.2-kv refill units installed in 7.2-kv holders for use in 4.8-kv mounings for system voltages through 4.16 kv. f l 3 Interrupting ratings shown for SM-4Z, SML-4Z,SM-5S, and SM5SS Power Fuses are applicable to 14.4-kv refill units installed in 14.4-kv holders for usein 13.8-kvmountings. Interrupting ratings shown for SM-20 and SML-20 Power Fuses are applicable to 14.4kv fuse units installed in 13.8-kvmountings.
SML4Z and SML-20 Power Fuses are not available at 94.5 kv. Applicable to solidly-grounded-neutral system only with fuses connected by a single concentric-neutral cable (or directly coupled) to a transformer or transformers, each with a wyegrounded-neutral primary connection. Applicable to 25-kvOverhead-Pole-TopStyle only, for protection of single-phase-to-neutralcircuits (lines or transformers) only. Parallel-fuse arrangements.
DATA BULLETIN
S&C ELECTRIC COMPANY Chicago S & C ELECTRIC C A N A D A LTD . Rexdale
2404 10
Page 75 of 78 August 6,1984
transformer protection is provided in accordance with the transformer short-timecharacteristic curve. If protection is not provided for one or more of the fault types listed, you may wish to select a smaller primary fuse ampere rating to obtain a smaller TPI, as follows:
STEP 1. Locate the appropriate table based on the secondary-side overcurrent protective device. See page 77 for index to selection tables. STEP 2. When using low-voltage circuit breakers: Calculate, in percent, the ratio of the highest feeder circuit breaker short-time or instantaneous pickup current* to the transformer secondary full-load current.
When using low-voltage circuit breakers: Lower the shorttime or instantaneous pickup current by using a lower short-time or instantaneous setting (e.g., 2X instead of 4X). Return to Step 2.And/or-Use a lower short-time delay setting (i.e., intermediate setting instead o f maximum setting), or use a high-level instantaneous setting, if available, in addition to a short-time delay setting (allowing use of the Instantaneous columns in the fuse selection tables). Return to Step 2. When using low-voltage current-limiting fuses: Use a lowvoltage fuse with a lower ampere rating or from a different manufacturer. Return to Step 2. When using R rated fuses in Class E-2 high-voltage industrial control equipment: Use a fuse with a lower R rating. Return to Step 3. When using medium-voltage circuit breakers: Lower the relay time-dial setting. Return to Step 3.-Or--Lower the relay pickup current. Return to Step Z.-Or-Use a different relay time-current characteristic. Return to Step 3.
When using low-voltage current-limiting fuses: Calculate, in percent, the ratio of the highest feeder fuse ampere rating* to the transformer secondary full-load current. When using R rated fuses in Class E-2 high-voltage industrial control equipment: Proceed to Step 3. When using medium-voltage circuit breakers: Calculate, in percent, the ratio of the highest feeder circuit breaker overcurrent relay pickup current* to the transformer secondary full-loadcurrent.
STEP 3. When using low-voltage circuit breakers: Enter the table in the Low-Voltage Secondary Circuit Breaker . . . column containing the clearing time corresponding to the short-time delay o r instantaneous setting, and circuit breaker application (Le., feeder or main). Select the first line containing an entry equal to or larger than the value calculated in Step 2.t.
If the above procedures d o not produce complete coordination between the primary fuse and the main secondary-side protective device, it is suggested that you reconsider your coordination requirements as described on pages 25 through 27.
STEP 5. In the line selected in Step 4, and in the column headed Loading Capability . . ., verify that the listed value is sufficient for your application. If not, read down the table in this column, stopping in the first line containing an adequate loading capability value. Verify that the entries in the secondary-side protective device ratings or settings columns and the Transformer Protection Index . . . columns are still acceptable. If not, try the next line down in this column, or you may wish to consider reducing your loading requirement. STEP 6. The primary fuse ampere rating and time-current characteristic shown in the line selected above are those recommended for your application. STEP 7. Verify that the primary fuse selected in Step 6 coordinates with the upstream protective device. See text, page 27. STEP 8. To select the type of primary fuse (Le., SM-4, SM-4Z, SM-5, SM-SS,SMD-20,SM-20, etc.),refer to Table XVIII on page 74. Based on the fuse location (i.e., indoor o r outdoor), system voltage, interrupting duty, and maximum continuous current, note the power fuse types that can be used. Your local S&C Sales Office will help you make the most economical selection.
When using low-voltage current-limiting fuses: Enter the table in the Low-Voltage Secondary Current-Limiting Fuse column corresponding to the fuse manufacturer and fuse application (i.e., feeder or main). Select the first line containing an entry equal to or larger than the value calculated in Step 2.t When using R rated fuses in Class E-2 high-voltage industrial control equipment: Enter the table in the HighVoltage Industrial Control Equipment , , . column corresponding to the secondary voltage of the transformer. Select the first line containing an entry equal to or larger than the largest control equipment fuse rating.
When using medium-voltage circuit breakers: Enter the table in the Medium-Voltage Secondary Circuit Breaker . . . column pertaining to the range of relay pickup currents encompassing the value calculated in Step 2, and in the specific column corresponding to the relay characteristic. Select the first line containing an entry equal to o r larger than the nominal relay operating time at maximum three-phase secondary fault current. STEP 4. In the line selected in Step 3, and in the Transformer Protection Index . , _ column corresponding to the transformer connection, determine the Transformer Protection Index (TPI).If there is no TPI in this line, choose a smaller primary fuse ampere rating as described below. Compare the TPI to the entries listed in Table XIX, below, corresponding to the transformer connection and impedance. Entries greater than or equal to the TPI indicate the fault types for which
Alternately, the main secondary side protective device can be used in this step 1 1 It is deemed necessary f o r the transformer primary fuse t o coordinate wlth the main f the largest feeder device. secondary-side device instead o The entries listed in the columns for feeder applications are based on the coordination requirements f o r delta grounded wye connected transformers. For grounded-wye grounded wye or delta deltaconnected transformers, the tables may be used a s described above by hrst dividing the walue calculated in Step 2 by 1 15. For this purpose, treat low voltage fused circuit breakers a s circuit breakers with instan taneous settings.
T h e entries listed are based on the coordination requirements for delta grounded-wye connected transformers. Forgrounded-wye grounded-wye or delta delta connected trans formers. the tables may be used a s described above by hrst dividing the nominal relay operating time at maximum three phase secondary lault current by 1.05 lor Inverse and Very Inverse relays. or by 1.13 lor Extremely Inverse relays.
DATA BULLETIN
S&C ELECTRIC COMPANY- Chicago S&C ELECTRIC CANAOA LTD Rexdale
2404 10
Page 76 of 78 August 6,1984
I
I
Selection Guide for Transformer-Primary Fuses in Medium-Voltage Industrial, Commercial, and Institutional Power Systems THE FUSE SELECTION TABLES
to Selection Tables
Iry-side O V e r C r n l Proiectlve
I
TABLE XX-Index
I
Kv
300 thru 750 4 16 1000 1000 1500 1500 thru 3750 300 thru 750 750 1000 1000 1000 1500 1500 thru 3750 1500 thru 5000 7500and10000 300 thru 750 750 1000 1000 1000 1500 1500 thru 3750
~~
Low-Voitage Cuwont-Llmlthrg
40 and 41
IX
50thru52
42 and 43
12 0-12 47
XIV
66 and 67
5.75%
13.2-13.8
avo
VI
44 and 45
XI
57 thru 59
1500 thru 5000 7500and10000 300 thru 750 750 1000 1000 1000 1500 1500 thru 3750 1500 thru 5000 300 thru 750
xv
68 and 69
22.9-24.9
a%
VI I
46 and 47
XI1
60 thru 62
4% 5.75%
XVI
70 and 71
33.0-34.5
Vlll
48 and 49
5.75% 5.5%
XVll
72 and 73
Note: See over for How to Use the Fuse Selection Tables on page 76. For your convenience, these instructions should be left folded out for ready reference while using the fuse selection tables.
DATA BULLETIN
S&C ELECTRIC COMPANY Chicago S&C ELECTRIC CANADA LTD Rexdale
2404 10
Page 77 of 78 August 6,1984
I
1
I
8
c V
I
i