TrilliumSeries Condenser

TABLE OF CONTENTS
1 TrilliumSeries Condenser 3 BENEFITS 7 MODES OF OPERATION 8 EcoFlex Controls 9 REBATE MAP 10 ENGINEERING DATA

The TrilliumSeries Condenser


The TrilliumSeries Condenser uses a patented Dry-Coil Adiabatic Design that saves energy, reduces refrigerant charge, and lowers operating costs. With the use of proprietary logic and sophisticated controls, the On-Demand Adiabatic Pre-Cooler uses water only on the hottest days to maintain condensing temperatures that typical air cooled technology cant achieve.

High Efficiency, Whisper Quiet


Fan System
motors

`` Latest noise reducing technology `` High efficiency electronically commutated (EC) `` Internal variable fan speed control

Robust Microchannel Technology

`` 40% higher thermal efficiency `` 30% smaller face area `` Unique top feed design with vertical tubes allowing

for gravity drainage of the condensed refrigerant that also eliminates the need for external manifolding

On-Demand Adiabatic Pre-Cooler


`` Drastically lowers air temperature to heat exchanger `` Increases temperature difference, driving additional
heat rejection

`` Increases unit efficiency by up to 40%

EcoFlex Control System


1
Q U E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W. B A LT I M O R E A I R C O I L . C O M

`` Optimizes unit performance and reduces energy use `` Eliminates the need for water treatment `` Ships pre-programmed, ready for use

Environmentally Friendly High Thermal Performance


`` Lower Total Cost of Ownership `` Reduced Compressor Work `` High Efficiency EC Motors `` Variable Fan Speed Control `` Air Pre-cooling to Temperatures
Approaching Wet-bulb Temperature

`` Smaller Refrigeration System `` Up to 18% Peak Energy Reduction `` 60% Less Refrigerant Charge

Water Saving

`` No Water Treatment `` Minimal Water Use `` Intelligent Controls

P R O D U C T M A N U A L : Tr i l l i u m S e r i e s C o n d e n s e r

Benefits
Ownership Benefits

In a variety of climate conditions, the TrilliumSeries Condenser provides the lowest total cost of ownership compared to air cooled units.
60% lower refrigerant charge Compact Single point electrical connection Direct drive EC motors and Whisper Quiet Fans are standard Reduces overall system size

`` INSTALLATION ADVANTAGES

`` ECONOMICAL ADVANTAGES
Attractive payback timeframes Lower total cost of ownership

TrilliumSeries Condenser Payback (See Notes 1,2,3)


1.4 1.2 1.0 Years 0.8 0.6 0.4 0.2 0.0 Boston5 Atlanta5 Chicago5 Phoenix4,5 Los Angeles4,5

Notes for the TrilliumSeries Condenser Payback Chart: 1. California Title 24 pricing equation for air cooled condensers. 2. California Title 24 2013, effective on 1-1-2014, states all condensers must have VFDs to control fan motors. 3. Condensing temperature for air cooled is set at 100-110F depending on the climate; TrilliumSeries Condenser is set at 95F. 4. In Phoenix and Los Angeles, the first cost of a TrilliumSeries Condenser is lower than the first cost of an air cooled condenser. 5. The cities were selected based on climate conditions.

Q U E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W. B A LT I M O R E A I R C O I L . C O M

System Energy Savings


40,000 35,000 30,000

`` Reduces condensing temperatures `` Less compressor work `` Direct drive EC motors match fan speed to load

Annual 19.2% System Energy Reduction for Chicago, Illinois

Total kWh

25,000 20,000 15,000 10,000 5,000 -26.5 -18.5 -10.5

Air Cooled System Total kWh TrilliumSeries Total kWh

-2.5

5.5

13.5

21.5

29.5

37.5

45.5

53.5

61.5

69.5

77.5

85.5

93.5

Peak Energy Savings

Dry-Bulb Temperatures (F)

`` Up to 18% peak energy reduction compared to air cooled units


Peak energy is more expensive than off peak energy Potential for state, local energy rebates

Peak Energy Reduction in %


6.8% Boston

12.3% Atlanta

13.4%

Chicago

18.5% Phoenix

1.5% Los Angeles

10

15

20
4

P R O D U C T M A N U A L : Tr i l l i u m S e r i e s C o n d e n s e r

101.5

Benefits
On-Demand Adiabatic Pre-Cooler
`` Water is used ONLY when load and ambient temperatures require it `` `` Free draining prevents stagnant water `` Up to 4 LEED Points for water efficient landscaping (WE credit 1) based on 2009 LEED for Retail and
Commercial Interior rating system Water from the drain and overflow can be used for irrigation or other non-potable uses Water spray saturates and cleans the pads of any dust and debris No water treatment is required

Annual Water Use

10

90

80

Le Noi ve se l (d B)

TrilliumSeries Condenser

70

60

50

100 150 Water Use (Gallons/Year)

200

250
Sound Levels

Water Use Compared to Evaporative Condensers

Low Sound

`` Whisper Quiet Fans are standard NormalConversation starts and stops `` Direct drive EC fan motors vary the fan speed eliminating sudden AquaVentaOperatingatFullSpeed `` Quiet sides can be positioned toward neighbors Trafficonabusyroad
AirCooledCondenser JackHammer

60

70

Q U E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W. B A LT I M O R E A I R C O I L . C O M

No

ise

60 70 80 84 100

Le

ve

l (d

80

B)

90

10

Typical Evaporative Condenser

Easy Maintenance
``

`` Water treatment is not required


Water is turned on only when load and outside temperatures require it Water spray saturates and cleans the pads of any dust and debris Adiabatic pads act as a filter to prevent debris on the microchannel Can be removed without tools for easy coil inspection Clean-out ports on both ends for easy cleaning
Easy Access to Pump and Valves

`` `` The EcoFlex Controls maintain a clean sump `` Pump and valves are easily accessible from the access hatch

`` 60% less charge than comparable air cooled condensers `` Reduced charge could help meet EPAs Greenchill
commitments

Refrigerant Charge (lbs.)

Charge Reduction
refrigeration system

Unit Refrigerant Charge


250 200 150 100 50 0

`` Lowers global warming potential of the supermarket

Air Cooled Condenser

TrilliumSeries Condenser

Charge Reduction

Peace of Mind

`` All units are equipped with state of the art controls for fan
speed, pre-cooling, and daily automatic sump clean out with a 24-hour delivery

`` All critical components are stocked and can be ordered online `` Manual discrete spray system standard `` Durable materials of construction extend the life of the unit `` Sump and drain pans drain freely `` Ability to switch fans from automatic to manual fan override
for loss of a control signal standard

Discrete Spray System

`` Manual control reset and interlocked hatch sensor are

P R O D U C T M A N U A L : Tr i l l i u m S e r i e s C o n d e n s e r

Modes of Operation
Dry Mode
Warm Air Out

The ambient air at the dry bulb temperature passes through the pads and then over the microchannels. The ambient air condenses the refrigerant in the microchannel coils which is then returned to the evaporators.

Vapor In Microchannel Coils

Vapor In

Adiabatic Pads

Adiabatic Pads

On-Demand Adiabatic
Pre-Cooler Mode
On days when the load is high and the ambient air temperature is high the unit will run in On-Demand Adiabatic Pre-Cooler Mode. Water is evenly sprayed over highly efficient cooling pads. As the air passes through the pads, water is evaporated in to the air, and the air is humidified, cooling temperatures down to 2-3 F above wet-bulb temperature. Such substantial depression of the dry bulb temperature results in a major increase in dry cooling capacity. The cooler air passes over the microchannel and condenses the refrigerant in the microchannel which is then returned to the compressor. In the sump there is an industrial duty pump that recirculates the water. The EcoFlex Controls determine when the water is purged from the sump. Part of the distributed water is evaporated, while the excess water assists in rinsing the pad to keep it free from debris and minerals that would otherwise stay behind on the pad after evaporation.

Air in at Dry-Bulb Temp

Air in at Dry-Bulb Temp

Liquid Out

Liquid Out

Dry Mode Operation

Warm Air Out

Water Distribution System Adiabatic Pads

Vapor In Microchannel Coils

Vapor In

Water Distribution System Adiabatic Pads

Air in at Dry-Bulb Temp

Air in at Dry-Bulb Temp

Air Cooled to 2F of WetBulb Temp

Air Cooled to 2F of WetBulb Temp

Liquid Out

Pump

Liquid Out

On-Demand Adiabatic Pre-Cooler Mode

Q U E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W. B A LT I M O R E A I R C O I L . C O M

EcoFlex Controls
The TrilliumSeries Condenser is furnished standard with state of the art controls that provide efficient year round performance. Each unit is shipped with custom controls logic that reduces energy consumption and optimizes water usage. With preset controls, the system is programmed and ready to operate upon arrival from the factory.

YES
Pre-Cool Mode ON

Ambient Temperature = Set Point

NO
Pre-Cool Mode OFF

Vary Fan Speed based on 0-10V signal Start Pump Sequence with Water Hardness Controls

Vary Fan Speed based on 0-10V signal

Continue Sensing Ambient Dry-bulb Temperature

P R O D U C T M A N U A L : Tr i l l i u m S e r i e s C o n d e n s e r

Rebate Map

Potential rebates are available for decreased energy use. These opportunities are highlighted in blue on the map above. As illustrated, a majority of states offer utility incentives and rebates which further decrease the initial investment of the TrilliumSeries Condenser.
There are various types of rebates available for energy savings and are dependent on utility regulations.
Type of Rebate Utility Details

Custom Refrigeration VFDs on Fan Motors or Other Controls

Arizona APS California Pacific Gas and Electric (PG&E) California SCE-Non-Residential Energy Efficiency Programs

Custom Measures and Retro-commissioning: $0.11/ kWh saved up to 75% of incremental cost Refrigeration Equipment: $35-$1000/unit Air Conditioning and Refrigeration: $0.09 - $0.15/kWh saved Variable Frequency Drives: $80/HP Refrigeration Controls: $75-$100/Controller

The above are examples based on information from dsireusa.org. Dsireusa.org is a website with information on state, local, utility, and federal incentives and policies that promote renewable energy and energy efficiency. Established in 1995 and funded by the U.S. Department of Energy, DSIRE is an ongoing project of the N.C. Solar Center and the Interstate Renewable Energy Council. For custom rebates, an analysis of the overall system energy savings from air-cooled to the TrilliumSeries Condenser maybe necessary. This analysis is available from Baltimore Aircoil Company along with any application support.

Q U E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W. B A LT I M O R E A I R C O I L . C O M

Engineering Data
NOTE: Do not use for construction. Refer to factory certified dimensions. This catalog includes data current at the time of publication,
which should be reconfirmed at the time of purchase. Up-to-date engineering data, and more can be found at www.BaltimoreAircoil.com.

2'-11 1/4"

1 1/8" Refrigerant In

3'-10 1/2" 2'-2 3/4" 4'-2"

3/4" GHT Discrete Spray (Garden Hose Thread) 5'-2 1/2"

5'-3 1/4" 1 1/8" Refrigerant Out

8" L

Model
TSDC-033-3 TSDC-058-6.2 TSDC-085-9.6

Fan Qty
1 2 3

Base Heat Rejection (MBH)


386 692 1011

Base Tons
33 58 85

Motor HP
3 6.2 9.6

Pump HP
0.25 0.25 0.25

Airflow (CFM)
14,890 28,000 41,400

Unit Length Total (in) (L)


5'-10 7/8" 8'-6 7/8" 11'-8 3/4"

Shipping Weight (lbs)


1,280 1,740 2,300

6- 0 5/8"

Operating Weight (lbs)


1,450 1,940 2,530

Note: Base Heat Rejection (MBH) is based on R-134a 95F Dry-Bulb/76F Wet-Bulb and 105F Condensing Temperature
P R O D U C T M A N U A L : Tr i l l i u m S e r i e s C o n d e n s e r

6'-11 7/8"

10

COOLING TOWERS CLOSED CIRCUIT COOLING TOWERS ICE THERMAL STORAGE EVAPORATIVE CONDENSERS

HYBRID PRODUCTS