Temperature-> F Level /len General 1 Tag Number PSV-503 2 Inlet Line Number 2"-RP-10-2504-B1A Outlet Line Number 3"-RP-10-1108-B1A 3 Vessel Protected 4 Safety / Relief Relief Valve 5 Type : Spring Loaded 6 Full Nozzle Full Lift Mod. Nozzle Full Nozzle Full Lift 7 Bonnet Type Closed 8 Conv. / Bellows / Pilot Operated Bellow 9 Inlet Connection: Size & Rating 2" x 300# 10 : Facing & Finish RF 125-250 AARH 11 Outlet Connection: Size &Rating 3" x 150# 12 : Facing & Finish RF 125-250 AARH 13 Cap Over Adjusting Bolt: Required 14 Screwed Bolted Bolted 15 Lifting Gear- Type Yes 16 Test Gag Yes 17 Material 18 Body and Bonnet A216 Gr. WCB 19 Nozzle and Disc SS 316 20 Spring CS-Zinc Plated 21 Bellows SS 316L 22 Guide & Ring SS 316 23 24 Resilient Seat Seal Options 25 Radiography Yes, 26 Special Requiment PMI for Wetted parts, Helium Basis 27 Code API-520/526 28 Basis of Selection Blocked Discharge Servic 30 Fluid and State Propane / Gas 31 Corrosive Costituent e 13170.9 kg/hr Condit 32 Required Flow Capacity 33 Mol. Wt.Sp.Gr. at Relieving Temp. 44.07 | ions 34 Operating Pressure (Inlet / Outlet) 14.95 Kg/Cm2 g 35 Operating Temp.Relieving Temp. 49.24 0C | 177 0C 36 Valve discharges to Flare 37 Back Press. Constant / Variable 1.70 Kg/Cm2 g | Variable 38 Set Pressure 17.0 Kg/Cm2 g 39 Cold Bench Test Pressure 17.3 Kg/Cm2 g 40 % Over Pressure % Blowdown 10% | 5-7% 41 Cp/Cv Compressibility Factor 1.1763 | 0.7266 42 Viscosity at Rel. Temp. mPas(cP) N.A

43 Vessel:Wall tempCSurf.Area-m2 N.A 44 Orifice 45 Calculated Area - cm2 7.475 Cm2 46 Sel. Area - cm2 Orifice Design 8.303 Cm2 | J 47 No. of valve required for capacity 1 48 Total area - cm2 8.303 Cm2 49 Actual Flow Capacity 14629.98 Kg/hr 50 Nos. 51 Model No. 6636-2-C-2".J.3"-A-P-F-V 52 MAKE : MEKASTER ENGG. LTD 53 IBR Certification N.A N.A N.A DEVIATION NO DEVIATION VENDOR DRAWING NO-6972-010-50-45B-1-1017 ORDER NO:SEL/ONGC/LO/10-11/146 DTD 14-11-2010 FILEREQUISITION NP : 23/2/2011 YASH _ CLIENT : SAVAIR DATEENERGY BY LIMITED ENGINEERS INDIA LIMITED fgngl PLANT : KOCHI REF. NEWDATA PROPANE SHEET GAS NO. COMP. VENDOR : DRESSER RAND INDIA 6972-010-50-45B-1-1017 PVT LTD NEW DELHI

This drawing and the design it covers are the properties of ENGINEERS INDIA LIMITED. They are merel not be reproduced, copied, loaned, exhibited, nor used except in the limited way and private use permitte

erature-> F Level /length -> mm

N.A VENDORS' SIGNATURES WITH SEAL BNS APPD REV 0

YASH CHKD SHEET NO. -50-45B-1-1017

ITED. They are merely loaned and on the borrower's express agreement that they will d private use permitted by any written consent given by lender to the borrower

Você também pode gostar