Getting a head start on the 2013 edition of NFPA -72

Presented by: Jon Kapis

Changes Proposed for 2013 Edition


Originally Presented at: The 2013 National Fire Alarm and Signaling Code Panel Discussion of Changes Presentation at the 2012 NFPA Conference & Expo Sessions M12, M25 and M45, Monday, 11 June 2012

Changes Proposed for 2013 Edition

Documentation
Written narrative Riser diagram Floor plan Sequence of operation (matrix or narrative) Equipment technical data sheets Manufacturers published instructions

Documentation
Battery calculations Voltage drop calculations for NACs Completed record of inspection and testing Completed record of completion A copy of site specific software Record (as-built) drawings

Documentation
Identification of the person responsible for the design or layout USE of NFPA 170 symbols or others acceptable to the AHJ

Documentation
Ambient noise & audible design sound pressure levels Designation of spaces to have visible notification Extensive ECS design document requirements

Documentation

Fire Risk Analysis


Fire Risk Analysis added to the Code. A.6.1 See NFPA 551, Guide for the Evaluation of Fire Risk Assessments

Control Unit Protection


Protection of the Control Unit moved to Section 10.4, Installation and Design. 10.4.4 In areas that are not continuously occupied, automatic smoke detection shall be provided at the location of each fire alarm control unit(s), notification appliance circuit power extenders, and supervising station transmitting equipment to provide notification of fire at that location.

Qualifications of Personnel
All qualification requirements moved to Chapter 10 System Designer System Installer Inspection Personnel Testing Personnel Service Personnel Programming Supervising Station Operators

Signal Priority
Signal Priority
Carbon monoxide signals shall be permitted to take precedence over supervisory and trouble signals. Pre-alarm signals shall take precedence over supervisory and trouble signals.

Impairment System Procedures


New paragraphs added to the Impairments section of the Code. 10.21.3 The supervising station shall report to the authority having jurisdiction any fire alarm system for which monitoring has been terminated. 10.21.4 The service provider shall report to the authority having jurisdiction any fire alarm system that is out of service for more than 8 hours.

Unwanted Alarms
10.22 Unwanted Alarms. For the purpose of reporting, alarm signals that are not the result of hazardous conditions shall be classified as Unwanted and sub-classified as one of the following: (1) Malicious Alarm (2) Nuisance Alarm (3) Unintentional Alarm (4) Unknown Alarm

Inspection/Testing/Maintenance
14.2.3.6 Service Personnel Qualifications and Experience Requires compliance with 10.5.3 10.5.3 lists requirements for, inspection, testing, maintenance, and programming personnel

Inspection/Testing/Maintenance
14.2.10 Test Plan 14.2.10.1 A test plan shall be written to clearly establish the scope of testing 14.2.10.2 The test plan and results shall be documented with the testing records Annex material to explain test plan

Software Changes
14.4.2.5 Reacceptance Testing After Executive Software Changes Changes to the system executive software shall require a 10 percent functional test of the system, including a test of at least one device on each input and output circuit to verify critical system functions such as notification appliances, control functions, and off premises reporting.

Intelligibility Testing
14.4.11 Voice Intelligibility Voice communications shall be verified as intelligible. Quantitative testing permitted, but NOT required

Inspection\Testing\Maintenance
Table 14.3.1 Visual Inspection Details inspection frequencies Now details inspection methods What to look for Damage Obstructions Location Condition

Testing\Inspection\Maintenance
Table 14.4.3.2 Testing Combines previous Table 14.4.2.2, Test Methods, and Table 14.4.5, Test Frequencies Item identification numbers coordinated with Table 14.3.1, Visual Inspections Improved user friendliness by including all information in one table

Alarm Monitoring
Supervising Station Alarm Systems 26.6 Communications Methods for Supervising Station Alarm Systems 26.6.3.2 Digital Alarm Communicator Transmitter (DACT) Testing interval has been reduced from 24 hours to 6 hours (for each transmission means) A successful signal transmission sequence of any type within the same 6 hour period satisfies the testing interval requirement

Protected Premises
Protected Premises Fire Alarm Systems New Section 23.6.1 added to require a loss of no more than 50 addressable devices for a signaling line circuit. Section A.23.6.2 clarifies intent that this does not apply to data/backbone circuits.

Protected Premises
Protected Premises Fire Alarm Systems Section 23.8.3.2 revised to permit dwelling unit smoke alarms to be connected to a protected premises control unit but to only initiate a supervisory signal.

Protected Premises
Protected Premises Fire Alarm Systems Section 23.8.4.8 was revised to require signals from CO detectors or CO detection systems to initiate a CO alarm signal (Temporal 4). A new exception to 23.8.4.8 permits supervisory signals where permitted by the building response plan.

Emergency Control Function Interfaces


Emergency Control Function Interfaces Section 21.2.4 revised to clarify terms. ROP 72-270 and ROC 72-247

Emergency Control Function Interface


Emergency Control Function Interfaces New exception to 21.3.3 added: Exception: A waterflow switch shall be permitted to initiate elevator recall upon actuation of a sprinkler installed in the pit, provided the waterflow switch and pit sprinkler are installed on a separately valved sprinkler line dedicated solely for protecting the pit, and the waterflow switch is provided without time delay capability.

Initiating Devices - Definitions Accessible Spaces Spaces or concealed areas of construction Space that can be entered via panel, door hatches, ceiling tiles Applies only for the purpose of determining extent of detector coverage, relevant when Total Coverage used Gas Detector Device that detects presence of a specified gas concentration Spot type, line-of-sight, open path type

Initiating Devices

Initiating Devices New Annex Material Effects of HVAC Systems Guidance on factors to consider when using smoke detectors near HVAC registers Ceiling jet verses HVAC flow velocities

Initiating Devices

Audibility Documentation/Application Information


A.18.4.1.4.1 Audibility of a fire or emergency signal might not be required in all rooms and spaces. For example, a system that is used for general occupant notification should not require audibility of the signal in closets and other spaces that are not considered as occupiable spaces. However, a space of the same size used as a file room would be considered occupiable and should have coverage by notification appliances. Also, signaling intended only for staff or emergency forces might only have to be effective in very specific locations.

Occupant Notification

Occupant Notification
Audibility Documentation 18.4.1.4.4 The design sound pressure levels to be produced by the notification appliances for the various coverage areas shall be documented for use during acceptance testing of the system.

Occupant Notification
Audibility Documentation 18.4.2.1* To meet the requirements of Section 10.9, the alarm audible signal pattern used to notify building occupants of the need to evacuate (leave the building) or relocate (from one area to another) shall be the standard alarm evacuation signal consisting of a three-pulse temporal pattern.

Occupant Notification
Intelligibility Relocated existing 24.4.1.2.2.4 to chapter 18 as 18.4.10.2.1 18.4.10.2.1* Unless specifically required by other governing laws, codes or standards, or by other parts of this Code, intelligibility shall not be required in all ADSs.

Occupant Notification
Intelligibility
A.18.4.10.2.1 For example, based on the system design the following locations might not require intelligibility. See also Annex D. (1) Private bathrooms, shower rooms, saunas and similar rooms/areas (2) Mechanical/electrical/elevator equipment rooms (3) Elevator cars (4) Individual offices (5) Kitchens (6) Storage rooms (7) Closets (8) Rooms/areas where intelligibility cannot reasonably be predicted

Occupant Notification
Intelligibility 18.4.10.4 Intelligibility shall not be required to be determined through quantitative measurements. 18.4.10.5 Quantitative measurements as described in Annex D.2.4 shall be permitted, but are not required.

Documentation of Visible Appliances A.18.5.3 Occupant notification by visible signaling is not required by NFPA 72 except in high noise areas (see 18.4.1.1). Just as with audible occupant notification, the requirement to have such signaling originates from other governing laws, codes, or standards. Those other governing laws, codes, or standards specify the areas or spaces that require either audible, visible or both types of occupant notification. NFPA 72 then provides the standards for those systems.

Occupant Notification

Emergency Communications System


Level 1, Level 2, or Level 3 Survivability is required for a two-way radio communications enhancement system Exception: Where leaky feeder cable is utilized as the antenna, it shall not be required to be installed in metal raceway. Extensive searches and discussions with cable manufacturers have not been able to identify a source of listed 2 hour rated coaxial or fiber cables.

Emergency Communications Systems


Layer 1 = In-Building MNS, controlled only by authorized users Layer 2 = Wide-Area MNS, controlled only by authorized users Layer 3 = Distributed Recipient MNS, notification of personnel through individual measures Layer 4 = Public media notification, Broadcast Radio, TV, etc.

Emergency Communications Systems


24.3.11* Risk Analysis for Mass Notification Systems. This section and its Annex material has been relocated and expanded to provide additional guidance for performing a Risk Analysis. Additional references for risk analysis as well as an RA Checklist has been added to the Annex

Emergency Communications Systems


24.4.2.2 Voice Evacuation Messages. In occupancies where sleeping accommodations are provided and the voice message is intended to communicate information to those who could be asleep, a low-frequency tone that complies with 18.4.5 shall be used for the 2 cycles before and after the message.

Emergency Communications Systems


24.4.2.6 Loudspeakers. Loudspeakers in each enclosed stairway, each exit passageway, and each group of elevator cars within a common hoist way must be connected to separate notification zones for manual paging only. The evacuation signal shall not operate in elevator cars, exit stair enclosures and exit passageways.

Emergency Communications Systems


24.4.3.18* Textual and Graphical Visible Appliances. Textual and graphical visible notification appliances are now permitted to be used for primary or supplemental notification Textual and graphical visible appliances are also permitted to be used for nonemergency purposes

Emergency Communications Systems


24.5.1* Two-Way, In-Building Wired Emergency Services Communications Systems. Installation requirements are now more specific: 1. Wall mount telephones or jacks mounted not less than 36 inches no more than 66 inches AFF 2. If accessible to the public one telephone or jack must be 48 inches AFF 3. Clear access must be provided minimum 30 inches wide