MiCOM M840

Reliability, Safety, Economy. Modularity (up to 32 analogue or 144 digital channels) and external compatibility. 12/16 bits resolution and 1,2 to 10 kHz/0.1 to 50/60 Hz sampling rates. Integrated fault location function The purpose of the electrical generation, transmission and distribution systems is to provide the electrical power end users with safe, reliable and dependable electricity. This in turn requires that the companies and industries install high performance monitoring and diagnostic systems. This instrument is the result of considerable experience combined with the most advanced micro-processor-based technologies, in order to meet the users' needs and requirements. Indeed, the consequences of disturbances on the electrical network can occasionally result in considerable financial losses both for the power generation companies as well as the end users. "Managing", i.e. working to prevent and eliminate disturbances by evaluating them via the use of MiCOM M840 disturbance recorders, has become one of the key elements to improve the reliability of electricity companies and industries alike. However, further to the diagnosis systems evolution, the volume of data to be processed increases, as well as the amount of analysis work required. This is where the MiCOM M840 can best be applied. Its capabilities considerably reduce analysis time without sacrificing any other of its functions.

Feature enhancements designed to improve performance


Accelerated fault diagnosis and source finding by analysis of triggering on calculated channels, negative, positive and zero sequence voltages and currents, etc), representative of the real phenomena encountered on the networks and in the industries. Ability to register very short duration transient disturbances Sample frequency: from 1.2 kHz to 10 kHz (50Hz) from 1.44 kHz to 9.6 kHz (60Hz) Capacity to register slow disturbances, set sample frequency: 6.4 kHz Recording period: from 10 s to 15 days, 12 hours, 49 min. and 37s (50 Hz) corresponding to: from 0.012 Hz to 50 Hz from 10 s to 12 days, 22 hours, 41 min. and 21s (60Hz) corresponding to: from 0.014 Hz to 60 Hz

16-bits resolution on the AC analogue channels, thereby guaranteeing extremely accurate measurements. Fault location function incorporated into the recorder, thus instantly available. Modular and expandable system, able to satisfy future needs. Records stored on a protected, internal mass memory so as to avoid any spurious loss of information. Reduction in communication time by means of high performance data compression and transmission protocols. Compatibility of the system with other devices such as recording and fault simulation instruments (IEEE COMTRADE). Access protection using passwords.

The configuration can be fully made by software, on the front panel (option), locally or remotely via a PC, in order to minimize the on site operations.

M840

M840

M840

M840

External synchronization (Time pulse, GPS, IRIGB, etc)

Designed to integrate a system


The architecture of the MiCOM M840 is based on the use of standardized components (VME bus, etc.) which enables integration into existing electrical installation automation and protection systems and allows it to interface with the following components: Battery power supply, Switched or private communication networks (optic fibers, hertzian network, etc.), Synchronization and time resetting (compatible with external time pulse, IRIGB, GPS, etc.).

Modem

Modem

Adaptor

O.F. Modem Optic fibers

Private line, Telephone line, Hertzien beam

Private line, Telephone line, Hertzien beam

Local network

Modem

Other ALSTOM recorders

Other fault analysis and simulation devices

IEEE COMTRADE

Win DR Manager analysis and operating station

Modem

Private line, telephone line Modem Additional Win DR Manager station

Colour printer

Colour printer

Adaptable capacity
The MiCOM M840 is fully modular and can therefore be configured to accomodate the number of analogue and digital channels to be monitored. With a maximum unit capacity of 32 analogue channels and 64 digital channels, or alternately only 144 digital channels, Win DR Manager recorders can be linked and synchronized together to provide monitoring of large electrical networks.

Operating and analysis unit


Installed on a standard PC, the Win DR Manager software enables local or remote configuration of the recorders, as well as the analysis and viewing of the data acquired by any recorders of the ALSTOM range (TPE 2000, EP-EPC, MiCOM M840): Retrieval of records, either in manual or automatic mode, Multi-windows graphic analysis,

Integrated computation functions (harmonics, RMS values, table of power values, etc.), Vectorial representations, Optimized fault location, Black and white or colour printout, Import export ability with other fault processing devices in compliance with IEEE COMTRADE standard format.

Recording of faulty characteristics


The response time required for the faults to be recorded by the MiCOM M840 can be either fixed, or automatically adjusted to suit the choice of application, so as to take into account the full scope of the fault. Adjustable hysteresis, rebound filtering and repetitive fault devices are also provided to guard against recording spurious phenomena.

Win DR Manager 3

Functional characteristics
M840

Computed channels Zero sequence voltages and/or currents, Positive sequence voltages and/or currents,

Sampling Sampling rate: to be programmed:

Negative sequence voltages and/or currents, Phase to phase voltages. Triggering Up to 3 programmable triggering criteria for each direct or computed analogue input:

slow sampling rate in RMS values from: 0.1 Hz to 50/60 Hz (option) from 1,200 to 10,000 Hz, (50 Hz) or from 1,440 to, 9,600 Hz (60 Hz).

Duration of recording and storage capacity Pre-fault time to be programmed from 0.1 s. to 2 s., Post-fault time to be programmed from 0.3 s. to 20 s. with choice of automatic extension (retriggerable), Storage on > 2 Gb mass memory, for example 1000 x 1 second records sampled at 10 KHz, on 16 analogue channels and 32 digital channels. Printout Locally or remotely, on most black and white printers, All records can be printed out either fully or partially, automatically or on request, by the following ways:

v v

8 9

min and/or max thresholds, variation (derived), frequency variation (option),

3 4

v
10

2 programmable triggering criteria per digital channel


General Basic configuration expandable by modules, Front panel with optional keyboard and screen (VT 100 emulation), Database generation/modification on front panel or by PC in local or remote mode, Autotest with visual or external alarm (relay), External time pulse, GPS, IRIGB compatible synchronization, Settings and software information stored in mass memory, Alarm relays and external controls. Direct channels Modules with 8 AC voltages and direct current analogue channels, 16 bits resolution and galvanic insulation, Modules with 4 AC/DC voltages and current analogue channels, 12 bits resolution and galvanic insulation, Modules with 16 digital channels fitted with anti-rebound filters and isolated by photocouplers, Frequency modules (optional).

rising edge status change, and/or falling edge,

By external contact (dry contact or application of a voltage from 24 to 250V DC) triggering can be initiated on request or by another recorder in the case of high capacity systems.

Fault location
The M840 incorporates a fault location function on the monitored line, whether the fault is initiated in single phase, two phase, three phase, in isolated or earthed configuration. The distance to the fault location is documented on printout or during graphic analysis. Mostly, location accuracy is within 2%.

when starting a recording and when a fault is located, selection of particular channels only, selection of a portion of a record,

U Analogue inputs I Hz

BUS SCSI

ANALOGUE ACQUISITION BOARDS (1 to 32 channels) Galvanic insulation DIGITAL ACQUISITION BOARDS (1 to 64 channels or 144 channels). Insulation by photocouplers

> 2 Gb HARD DISK (extension optional) Alarms, external commands B&W/printer Modem, Win DR Manager master station Local link, Win DR Manager master station or VT100 emulation

Synchronization clock and time pulse External triggering 48-120 VDC 220 VDC 110 VAC 220 VAC

SERVICING BOARD

BUS VME

Analogue inputs

CPU BOARD WITH COPROCESSOR WITH 16 MB RAM

FRONT PANEL (SCREEN/KEYBOARD) (optional) FILTERED POWER SUPPLY

MiCOM M840 INTERNAL BLOCK DIAGRAM

Sub-sample restoration (at a lower sampling speed than for the acquisition sampling), restoration of curve ranges, full restoration. Communication/Interfaces The MiCOM M840, designed to communicate, contains interfaces that enable the following functions: On input: Synchronization by external time pulse, GPS and IRIG B clock, and time resetting function,

Triggering on an external pulse either from another EPMF or from any other device, by applying a DC voltage or closing a free contact, Configuration of settings locally or remotely via a PC, the Win DR Manager or the MiCOM M840 front panel. On output: Control of triggering and external synchronization,

Transmission of records and data automatically or on request, by:

standardized local network (optional), private line, hertzian network, etc., telephone line, STN, optic fiber, etc.

Direct connection to a standard printer, or to a PC for data transmission by RS 232 serial link.

M840

1 - Simplified record header: A detailed header can be printed out on request. It contains the description of each channel and its nominal values, and other data. 6 2 - Pre-fault recording 3 - Triggering (Instant 0) 4 - Fault recording 7 5 - Post-fault recording 6 - Fault cause and location (type, distance) with further information described in detailed header. 7 - Header for each channel 8 - Amplitude markers: Values for each channel 8 indicated in the detailed header. 9 9 - Graduation at 10 ms intervals. Value indicated at 100 ms intervals, negative before 10 triggering, positive after. 10 - Triggering of a protection

3 4

v
5

(digital channel, no.1).

Technical specifications
Power supply 48-120 VDC , 220 VDC, 110 VAC, 220 VAC, 15% 100 VA typical Analogue inputs AC channels: 8 channels/board 16 bits resolution Voltage channels: 140 VAC or 260 VAC Current channels: through external shunts or CTs. Burden < 0.1 VA Bandwidth 2-2,500 Hz Accuracy 0.5% AC/DC channels: 4 channels/board 12 bits resolution Voltage channels: 0 to 600 VDC Current channels: through shunts Burden < 0.1 VA Bandwidth: DC - 2,500 Hz Accuracy 3% Fast Sampling rate 50 Hz: 1,200 to 10,000 Hz step 400 Hz 60 Hz: 1,440 to 9,600 Hz step 480 Hz Slow Sampling rate 50 Hz: 0.012 Hz to 50 Hz record duration: 15 Days 12 Hours 49 Min. 60 Hz: 0.014 Hz to 60 Hz record duration: 12 Days 22 Hours 41 Min. Digital inputs 16 channels/board Voltages: 24-250 VDC Burden < 0.5 mA Time resolution:1 ms Symmetrical components Zero sequence, Positive sequence, Negative sequence, voltage and current Frequency inputs 4 channels/board Voltage: 18 - 180 Vrms 37.5 Hz - 75 Hz Resolution: +/- 0.01 Hz Accuracy: +/- 0.1 Hz Internal clock Absolute date, hour, minute, second Time synchronisation GPS / IRIG-B Voltage pulse Master/slave RS 485 pulse Recording parameters in fast sampling rate Pre-fault time: 0.1 s. to 2 s. step 0.1 s. Post-fault time: 0.3 s. to 20 s. step 0.3 s. automatically expandable Internal memory 16 Mb Mass memory 1 Gb, 2 Gb (option) Storage of 2,000 s. of faults sampled at 5 kHz for 2 feeders Setpoints selection for triggerings Analogue channels, Symmetrical components, Frequency channels: minimum and/or maximum threshold, minimum and/or maximum of rate of change Digital channels: rising and/or falling edge. Communication Protocol: standard modem protocol, compatible with WINDOWS 95/98/NT environment Speed: 300 to 19,200 Bauds Interfaces: optical fibre (option), leased lines, STN Direct transfer to PC Corporate LAN link between more than one Master Station
6

Alarms Record in progress Memory full (20 - 80%) an internal fault (selfcheck result) Loss of synchronization CPU memory overflow, etc. Type 50 VA resisitive Environment Dielectric withstand (CM): 2.5 kV - 50 Hz , IEC 600255-5 Insulation resistor: > 100 M (500 VDC CM) , IEC 600255-5 Electrical shock: 1.2/50 S, 5 kV , CM and DM , IEC 600255-5 Damped 1 Mhz sinus wave: CM 2.5 kV, DM 1 kV, IEC 600255-22-1, IEC 61000-4-12 Fast transient: 2 kV, IEC 61000-4-4 Electrostatic discharge: contact 4 kV, air 8 kV, IEC 61000-4-2 Electromagnetic compatibility: IEC 61000-4-3 10 V/m Radiated and conducted emission: EN 55011 (CISPR 11) Susceptibility: ENV 50141 (IEC 61000-4-6) , ENV 50140 (IEC 61000-4-3), ENV 50204 Sismic test: IEEE C37 98 Temperature: operating -10C + 55C, storage -20C + 70C Relative humidity: 85% at 40C (not condensing) Other applicable standards: ANSI/IEEE C 37.90 Dimensions and weight 19 inch rack, 7U Weight: 32 kg maximum Dim.: 310 x 419 x 440 casing dim.: 310 x 458 x 440 (fan) overall dim.: 310 x 490 x 440 (H x D x W).