Você está na página 1de 4

ECE 6950 POWER SYSTEM PROTECTION SUMMER II 2013 PROJECT DUE 08/06/2013

#2

The one-line diagram of a 7-bus three-phase power system is shown in Fig. l. The machine, line, and transformer data are given in Table 1.
1 T1 2 L1 Branch Fuse 3 L2
4

5 L3 L4

6 L5

l1kvAr
Tap;{USe 190 kVAr 400kW 400kW 400 kW Circuit Breaker

(!::R:t~190 :V.A, (
o
400 kW -400 kW Fuse

800kW 190 kVAr L....----+400kW

Fig.1 Single-line Diagram of Three-phase Power System Table l(a) Generator Ratings Generator Power (MVA) G 1 (Infmite bus) 50

Voltage (kV) 345

X" (pu) 0.12

X2(Pu) 0.14

Xo(Pu) 0.05

The generator neutral is solidly grounded Table l(b) Transformer Ratings Transformer Power (MVA) I T1 5 I The transformer neutral is solidly grounded Table l(c) Transmission Line Ratings Line Maximum Power (MVA) L1 5 L2 5 L3 5 L4 5 L5 5 For All Lines: Zl
=

Voltage (kV) 345 kV Al13.8 kV Y

X(pu) 0.1

Lenzth (km) 2 3 2 2 2

Voltaze (kV) 13.8 kV 13.8 kV 13.8kV 13.8 kV 13.8 kV

0.19 + jO.38 nlkm; Zo = 0.6 + j1.0 n/km; Y 1 = j4.0 E-6 S/km;

Table led) Power Flow Data Bus Bus 1 Bus Bus Bus Bus Bus Bus 2 3 4 5 6 7

Type of Bus Swing Bus, VI


=

345 kV, 0

00

Load Load Load Load Load Load

System Base Quantities: = 10 MV A (three-phase) Vbase =13.8 kV (line-to-line) in the zone of the lines. Convert all the zero-, positive-, negative-sequence, load, and voltage data into per unit using the given system base quantities. Determine the per-unit zero-, positive-, negative-sequence bus impedance matrices. Determine the per-unit zero-, positive-, negative-sequence bus admittance matrices. Using the PowerWorld Simulator, create four input data files: generator data, bus input data, line input data, and transformer input data. Bus 1 is the slack bus (swing bus) Using the PowerWorld Simulator, run the power flow program and obtain the generator, bus, line, and transformer input/output data; at least 12 data files, 3 input and 3 output data files. Using the PowerWorld Simulator, compute the subtransients fault currents for the following: (i) Single-line-to-ground faults at each bus. (ii) Line-to-line faults at each bus. (iii) Double-line-to-ground faults at each bus Neglect prefault load currents and all losses, and assume 1.0 per-unit prefault voltage. Select a suitable circuit breaker from Table 1 for each location shown on the single-line diagram. Each breaker should (i) have a rated voltage larger than the maximum system operating voltage, (ii) have a rated continuous current at least 30% larger than normal load current, and (iii) have a rated short short-circuit current larger than the maximum fault current for any type of fault at the bus where the breaker is located. Assume that the (XlR) ratio at each bus is less tha 15, such that the breakers are capable of interrupting the de-offset in addition to the subtransient fault current. Circuit breaker cost should also be a factor in your selection. Do not select a breaker that interrupts 63 kA if a 40-kA or 31.50kA breaker will do the job.
Sbase

(a) (b) (c) (d)

(e)

(f)

(g)

TABLE

1
\'aIIIp
IdllltJftc:atlon
~

RauldVtluInsUa1Ian Le.1 Rated WkIIIl1Ind

outIIooJ' dmuit brederJ (~wmnt 'oM Qfmtms) [lO] (Appication GahJc ftK' AC wp.Voltqe amm Bndm Rltai ODISy1iiiidrlcaJ. Cmmt~ANSI C37.DlO(Nmr Yak A.m.imn NatioDal
tbndsrds~

PnHmd radoai for

Ornm
Ratad
CGnllllloua CUmllEIit

Vahap

..

Narmnai HVA

CUI (W, mil) Cd I

3-"-'
Cilia

Lad MIX \tI


~

rtat.I
~

lllt'W_
lGw

RatwdS~ C\rn.w;
(Id.Ramd
f'b: kY) Oralie

RIrp (K)
CDI

n.
'-r'lCJ
~ma)

Fatwr

1-...
er...t
Cal ,
(I(g

6OH!
~r'C!:II. n'I'II}

rms)
~3

(leA. nns)
CoI8

Coil 250

cas

CoI7
I!ilD

ltl2).

= 1m IEEE)

:z.;

14.4 1U

is.s
15.5 2.5.8 l!

1.61
1.29:

1.9
11

34.S

46 8

us
us
l38
l3IJ

US 115 US 115

2.
Not

500 JOO 1500 l"..

115
1.&! 1.2l,
1.2.l

4R.l 72.5
III lZI l~l IZl 121 12]

1200 12m 1200


12llO

llOO
l200

11 17 19
20

I.G 1.n 1.D 1.0


1.0

1~ 2000

40
~

:mm
DIJ 3000 1:DJ
1600

].0
1.0 l.D

lllll l~R

14j
]4.5

a
20
40

61 40

n.
138

145 ]4S
1"'" ApptiGabIe
~

1.0 1.0
1.0

2000

toO
1.0
1.0

138
138
161

145

l.4~
1(6
IW

toO

2000
J)OO l2DO

40 6l 80 40
ISl 80 lti

D.lI)

16) hU 161
230

to
1.0 l.o 1.0 1.0 1.0 1.0

110
lCIOO
2000

31.$
~

1.

1.
~

l600
2!XIO !CIOO

11..5

sa

HI

2A2

U.5
ll..s

m
230

m
142

2m
230 MS
~

242
242

l..o

1.0

362

l.D

3Ci2

1.0
1.0 1.0

DWI

5CIO

:!Ioo
'00
700

0
150 76S

3GOO

2000

40

.to .eo
)
<ID

ti3

3m 2000 2000
~

.mo

1.0
1.0

40 ,I) 40

1fi5

'tABLE (o::~mti :'l1lc.c1:

R..clated Requ~re4 CJpi:l.b-:litie-s Cu rrent Value!!

-Clcr.1oing l'I nd Lat-ching Capilbil~ty '.6K Times Rated Shor~ Circuit Current

Malt

Symrn~
P..at.e.d VJt III es rical II'I[:-erruptir~ Cil~ilicy

l-S~t::ond She rt- Time


CUI'rent Carryin,g OipaDIlk'y

Rated
Rated Int~rrlJ p'tl ng Time (Cy.;I~)

Ft.:ared M:.Jx
'klta,ge DI"'ided

Perm. ssiblc
Tripping D~I~

K Timf!!'i R<"l1:ed ShortCircuit (kA. rrns) Col 12 Current

{S~Cond5J
Col

by J( (leV. r'm:s)
Col II

(k.A.. rrns)
Col I:)
:2.!1

(kA.. rrns)
Co! t4 ";c J_ 31

COl9 5
~ 5 ~ .
<:

ro

':
...,
L

~.b !2
L2 :!::!40

1..1... ~
~J

... ~
L.-.

21

~4

t~
5~

~ ::;:

36

..

n
D
:::0
44,1

."" ;i L
::'12fJ 40
.::Ie}
C'J3

:,~
~7

;i

'"L
1
I
]

eo
121
l:::!l
., I t21 121 L.:!l

.n
!)4 (... 1

3 .~
~
.l,

40
():t

lC'l
f.4 JU] .. . .,~

4(

4U
(J.l,

.3 .l

l I
I I

61
~U

1,1~ 14~
l-l"!

.,

4n
40
fi~

..:K:I
4()

64
IYI

3
~~

3
)

1 1
I 1

1":.:5 .

.,. -,.,

(,.:I
~O
4U

101
I:!J: (-4

so
40
0:>3

~-l:5
145

1 J

63
80
If;

145
I r)"9

gO
]6

101 1":-':
2(. Sf, 64

::
J
,.

1~:)

,~I,S
411

:n..5
..l(:. SIJ ~ I.:') 315 :'1.5

1
I

.-'
}

1
I
I
]

1 (:'l11i~ 242
:,:'42
:!t2

::--.J -" 31.5

so

3
~ ':!
J

31 .. ~
31,5 "'11
'LI
(d

sc .. sc
:511
t)4

14224::!

40
4{J

L
1 1
I

~4~
362 ~fi:::!

J 3 1 2:
~
...

4U

~J. .::10

64 H'L

.5:5U
5:')0
7()':7()~

.to
40
.::10

40

-1()

~o
~U

M f4
-:':4

1 J
f

64
(14

,141
4Q

. 0

6-t-

Você também pode gostar